KNX SYSTEM INSTALLATION AND CONFIGURATION GUIDE

Size: px
Start display at page:

Download "KNX SYSTEM INSTALLATION AND CONFIGURATION GUIDE"

Transcription

1 KNX SYSTEM INSTALLATION AND CONFIGURATION GUIDE

2 Contents 4 INTRODUCTION TO THE KNX OFFER 4 Composition 6 KNX standard architecture 7 Wiring rules 8 IP structure 9 ETS software 10 DEVICE PRESENTATION AND INSTALLATION 10 Simple controls 12 Scenario control Cat. Nos and IR remote control Cat. No IR/RF remote control Cat. No Light level cell Cat. No Detectors 16 Mobile configuration tool Cat. No KNX false ceiling controllers 19 KNX DALI modular controller Cat. No KNX roller blind modular controller Cat. No Multi-channel modular controller Cat. No SCS modular controllers 22 Touch control Cat. No IP communication module Cat. No USB interface Cat. No Line coupler Cat. No KNX power supply Cat. No KNX cable Cat. No Building manager viewer Cat. Nos /04 25 Building manager controller Cat. No

3 26 ARCHITECTURE 26 Architecture with false ceiling controller 27 Architecture with modular controller 28 Wiring 29 DESIGN 29 Introduction 30 Product layout (CAD) 32 Installation wiring and powering-up 33 ETS configuration

4 PRI PRI: V mA 50/60Hz SCS : 27Vdc 600mA SCS V Hz LEARN Introduction to the KNX offer COMPOSITION The Legrand KNX offer is used to create flexible, open installations. The KNX lighting management system consists of the following assemblies: - Controls: these can be manual (wiring accessories) or automatic (detectors). They send commands to the various components in the system. - Controllers (also called actuators): these receive commands from the controls or automation devices in the system. They have various outputs and control the lighting, blind or shutter loads. - Automation devices: these can send commands to the various controllers in the system and/or receive commands. - Accessories: these supply power to, connect and interface the lighting management system. 4

5 Controls: : lighting control /22/21: false ceiling detector Controllers: /66/62/61: false ceiling controller PRI SCS LEARN PRI: V mA 50/60Hz SCS : 27Vdc 600mA V Hz : KNX multi-channel modular controller : KNX modular controller for roller blinds Accessories: : touch screen /04: building manager viewer : building manager controller Automation devices: : KNX power supply : IP communication module 5

6 Introduction to the KNX offer (continued) KNX STANDARD ARCHITECTURE The KNX specification is published by the KONNEX association. The KNX protocol was recognised by ISO/IEC x as an international standard in November Diagram of an installation An installation can be divided into lines and zones. A line contains a maximum of 64 participants (products). A zone comprises a maximum of 15 lines linked to the main line by line couplers. A backbone links a maximum of 15 zones via zone couplers. Zone 1 Main line Zone Power supply controller + Maximum 15 lines Line15 + Line coupler + power supply Linecou coupler r+p power supply 15 zones maximum Backbone 64 modules maximum m Modular controller False ceiling controller Zone 15 6

7 WIRING RULES The BUS must be supplied with 29 V= ± The data forming the KNX "message" is transmitted in differential serial mode at a rate of 9600 bps. A single pair (2 x 0.8 mm) cable must be used. Maximum lengths - Maximum distance between 2 products: 700 m - Maximum distance between a product and the KNX power supply: 350 m - Maximum BUS length: 1000 m - Termination resistors are not necessary Modular controller 700 m 350 m False ceiling controller Power supply 7

8 Introduction to the KNX offer (continued) IP STRUCTURE KNX IP BUS/KNX IP/KNX gateway Cat. No Peripheral BUS controller Peripheral BUS controller Touch screen Detector Control Detector Control Detector Control Detector Control Wiring topologies There are several wiring topologies. It is not necessary to have an impedance at the end of the line. Line Star Tree structure Mixed topology Ring 8

9 ETS SOFTWARE Used to configure and set the parameters of KNX products. The products must be configured using the Konnex certified software: ETS3 and ETS4. The products are programmed using the Legrand database. ETS configuration (see p. 33) 9

10 Device presentation and installation SIMPLE CONTROLS The control can operate in two different modes whose parameters can be set on ETS: - The first for controlling the lighting - The second for controlling blinds or shutters Flush-mounted wall installation in flush-mounting box Technical characteristics Power supply: 27 V=, wiring on the peripheral BUS Consumption: 5 ma Operating temperature: -5 to + 45 C Protection index: IP 20 Dimensions: 45 x 45 x 347 mm Installation (supplied with BUS connector Cat. No ): - Flush-mounted in 2-module box - Surface mounted with 2-module frame Cat. No To be equipped with Mosaic plate Cat. No (white) or (aluminium) and Batibox support Cat. No mm min. CLICK CLICK Wall mounted installation with support frame CLICK CLICK 40 mm min. 10

11 Lighting controls For wiring on the peripheral BUS and controlling one controller. For ON/OFF/dimming control of the configured loads. Pushbutton control. The Plug and Go configuration in this case is: CH1 controls channel 1 and CH2 controls the other channels. 1 way lighting controls: Cat. Nos way lighting controls: Cat. Nos Communication object The operation of the controls is dependent on the links created on ETS Number of communication objects: 8 Type Inputs Outputs Objects 1 On/Off status bit 1 level status byte 1 ON/OFF bit 4 Dimming bits (1 down, 9 up, 0 stop) Lighting and roller blind controls For wiring on the communication BUS and controlling several controllers. Used for ON/OFF/dimming control of lighting loads and raise/lower and slat orientation control of roller blinds. Switch control. The Plug and Go configuration in this case is: CH1 controls channel 1 and CH2 controls the other channels. 1 way controls: Cat. Nos way controls: Cat. Nos Communication object The operation of the controls is dependent on the links created on ETS Number of communication objects: 8 for lighting 6 for blinds Lighting Type Inputs Outputs Objects 1 On/Off status bit 1 level status byte 1 ON/OFF bit 4 Dimming bits (1 down, 9 up, 0 stop) Blinds Type Objects Inputs 1 position byte (1%= 1, 2-100%=0) Outputs 1 Up/Down bit 1 Open/Close bit 11

12 Device presentation and installation (continued) 4 buttons (or units) for controlling 4 scenes SCENARIO CONTROL CAT. NOS AND The scenario numbers assigned to the buttons are configured with the ETS tool. Can initiate 4 scenarios. The Plug and Go configuration in this case is: - Pushbutton 1 = all actuator channels 40% - Pushbutton 2 = all actuator channels 60% - Pushbutton 3 = all actuator channels 100% - Pushbutton 4 = all actuator channels 0% The control is reset by a short press followed by a long press (10 seconds) on the Learn button. The pink LED then flashes quickly. Communication object Type Output Object 1 Scenario number byte This object is common to all the products connected to the controller Technical characteristics Power supply: 27 V=, wiring on the peripheral BUS Consumption: 5 ma Operating temperature: - 5 to + 45 C Protection index: IP 20 Dimensions (H x W x D): 45 x 45 x 32.7 mm Installation (supplied with BUS connector Cat. No ): - Flush-mounted in 2-module box - Surface mounted with 2-module frame Cat. No To be equipped with Mosaic plate Cat. No (white) or (aluminium) and Batibox support Cat. No Installation (see p. 10) 12

13 CH1 controls CH2 controls 1 scenario per button Scenario control IR REMOTE CONTROL CAT. NO IR/RF REMOTE CONTROL CAT. NO The remote controls communicate with the actuators (false ceiling or modular controllers). As the controllers do not have IR technology, a detector acts as an IR gateway between the remote control and the actuator. The scenario remote control is used for remote control of switching on/off and dimming 2 local lighting zones. The buttons can be configured on the ETS tool. The infrared (IR) control has a 10 m range. This remote control is used to control the outputs of a single controller. Technical characteristics Power supply: 2 x LR V alkaline batteries (supplied) The remote controls communicate with the actuators (false ceiling or modular controllers). As the controllers do not have IR technology, a detector acts as an IR gateway between the remote control and the actuator. The scenario remote control is used for remote control of a scenario using the buttons. These numbers can be configured on the ETS tool. The infrared (IR) control has a 10 m range. The remote control has 5 action buttons, each dedicated to one scenario. A short press on one of the 5 buttons activates a scenario that has been defined on ETS. Loop control is disabled when using the remote control. Technical characteristics Power supply: 2 x LR V alkaline batteries (supplied) Communication object Type Output Object 1 Scenario number byte 13

14 Device presentation and installation (continued) LIGHT LEVEL CELL CAT. NO DETECTORS Used to measure the amount of light coming in from outside the installation. Internal cell for "open loop" lighting management. It is also used to show the light level on a screen or supervision system display. The parameters of detectors associated with the loop must be set for open loop. It is essential to calibrate the detectors to ensure the control loop operates correctly. Technical characteristics Power supply: 27 V=, wiring on the peripheral BUS Operating temperature: - 5 to + 45 C Protection index: IP 20 Consumption: 15 ma Installation: - Directly in false ceiling with claws (supplied) - In Batibox box, depth 50 mm Cat. No Communication object Number of communication objects: 1 Type Output Object 2 light level bytes (lux) The detector controls the actuators. It has various operating modes (Manual ON/Auto OFF, etc.) There are two possible control methods: - Closed loop control: the detector operates independently - Open loop: the detector is combined with a light level cell The parameters are set with the ETS tool (time delay, light level threshold, sensitivity, operating mode: AUTO/MANUAL, type of control) Communication object Number of communication objects: 8 Type Inputs Outputs Objects 1 On/Off value bit 1 level value byte 1 presence/end of presence (end of time delay) status bit 2 in lux bytes 1 synchronisation bit 1 On/Off bit 1 Value byte 1 presence/end of presence bit To obtain the correct operation of the light control loops it is essential to comply with the recommended links. For further information, please refer to the technical data sheet in the e-catalogue, For further information, please refer to the technical data sheets in the e-catalogue, 14

15 Flush mounting detectors For wiring on the communication BUS Recommended fixing height: 1 m Integrated pushbutton 180 detection Optimum distance between 2 detectors: 6 m Infrared detection: Cat. No Infrared and ultrasonic detection: Cat. No The Plug and Go configuration is used to control all the channels. The parameters of the detectors can be set using the ETS software and the mobile configuration tool Cat. No Technical characteristics Power supply: 27 V=, wiring on the peripheral BUS Operating temperature: - 5 to + 45 C Protection index: IP 20 Consumption on standby: 12 ma for Cat. No ma for Cat. No Installation (supplied with BUS connector Cat. No ): - Flush-mounted in 2-module box - Surface mounted with 2-module frame Cat. No To be equipped with Mosaic plate Cat. No and Batibox support Cat. No Installation (see p. 10) Connection False ceiling detectors For wiring on the communication BUS Recommended fixing height 2.50 m 360 detection Infrared detection: Cat. No Infrared and ultrasonic detection: Cat. No Ultrasonic detection: Cat. No The Plug and Go configuration is used to control all the channels. The parameters of the detectors can be set using the ETS software and the mobile configuration tool Cat. No Technical characteristics Power supply: 27 V=, wiring on the peripheral BUS Operating temperature: - 5 to + 45 C Protection index: IP 20 Consumption: 0.2 W on standby for Cat. No W on standby for Cat. Nos /21 Installation: - Directly in false ceiling with claws (supplied) - In Batibox box, depth 50 mm Cat. No Surface mounting on ceiling with support frame Cat. No For Cat. Nos /21 Cat. No for Cat. No Connection Cat. No To be ordered separately 15

16 Device presentation and installation (continued) DETECTORS (CONTINUED) Surface mounting detectors For wiring on the communication BUS. Recommended fixing height: 2.50 m 180 infrared detection: Cat. No infrared detection - IP 55: Cat. No infrared detection - special version for corridors/ very high areas: Cat. No infrared and ultrasonic detection: Cat. No The parameters of the detectors can be set using the ETS software and the mobile configuration tool Cat. No Technical characteristics Power supply: 27 V=, wiring on the peripheral BUS Operating temperature: - 5 to + 45 C Protection index: IP 42 (except for IP 55) Consumption on standby: 12 ma for Cat. No /25 17 ma for Cat. No /23 Installation: flush-mounted on walls (supplied with fixing plate) MOBILE CONFIGURATION TOOL CAT. NO Used to specify certain settings for detectors: Time delay Light level threshold Sensitivity Calibration Digital programming to the nearest decimal place on digital screen Instant programming control Option of saving a setting in the memory and applying it to other detectors (standard preset configurations for each room (office, corridor, bedroom, bathroom, etc.) in accordance with EN Technical characteristics Infrared communication technology (4 m max.) Operating temperature: - 5 to + 45 C Impact resistance: IK 04 Recharging: with USB - mini USB cable (not supplied) IR transmission and reception LED Display screen On/Off and validation Control and navigation keys Function access keys Mini-USB connector 16

17 KNX input SCS output (RJ 45) KNX FALSE CEILING CONTROLLERS A false ceiling controller is a power unit or an actuator which is used to control and manage the lighting in one or more rooms. False ceiling controllers use the same variables, the only difference is the DALI fault for DALI controllers (Cat. Nos /66). DALI false ceiling controller with 4 outputs: Cat. No DALI false ceiling controller with 8 outputs: Cat. No False ceiling controller for 1-10 V ballast with 4 outputs: Cat. No Halogen false ceiling controller with 2 outputs: Cat. No To reset the controllers: a short press followed by a long press on the Prog & Reset button. When a controller has been reset, all the configurations created on ETS are deleted and a Plug and Go procedure is started on all the peripherals connected to the controller. Technical characteristics Power supply: 29 V=, wiring on BUS/KNX Con sumption: - Off-load: 2.4 W (for Cat. Nos /66) 4 W (for Cat. No ) 1.8 W (for Cat. No ) - Max. depending on the load Operating temperature: - 5 to + 45 C Protection index: IP 20 Install ation: - In false ceiling - On a suitable cable tray DALI false ceiling controllers Cat. Nos /66 This device is a power unit for managing lighting loads (DALI or DSI). Communication object Number of communication objects: 68 for Cat. No for Cat. No Type Inputs Outputs Object 1 On/Off bit 4 Dimming bits 1 level byte 1 enable/disable bit 2 force/unforce bits 1 clock (for stopping all automatic control devices) 1 scenario byte 1 On/Off status bit 1 Value status byte 1 control BUS fault bit 1 DALI fault bit 1 scenario byte For further information, please refer to the technical data sheet in the e-catalogue, 17

18 Device presentation and installation (continued) KNX FALSE CEILING CONTROLLERS (CONTINUED) False ceiling controller for 1-10 V ballast Cat. No This device is a power unit for controlling lighting loads in switch mode (fluorescent tubes, halogen bulbs, compact fluorescent bulbs) and in dimming mode (1-10 V ballast). Communication object Number of communication objects: 32 Type Inputs Outputs Object 1 On/Off bit 4 Dimming bits 1 level byte 1 enable/disable bit 2 force/unforce bits 1 clock (for stopping all automatic control devices) 1 scenario byte 1 On/Off status bit 1 Value status byte 1 control BUS fault bit 1 scenario byte False ceiling controller for LV and ELV halogen Cat. No This device is a power unit for controlling lighting loads (incandescent bulbs, halogen bulbs, halogen bulbs with ferromagnetic transformer, halogen bulbs with separate electronic transformer). Communication object Number of communication objects: 17 Type Inputs Outputs Object 1 On/Off bit 4 Dimming bits 1 level byte 1 enable/disable bit 2 force/unforce bits 1 clock (for stopping all automatic control devices) 1 scenario byte 1 On/Off status bit 1 Value status byte 1 control BUS fault bit 1 scenario byte 18

19 KNX DALI MODULAR CONTROLLER CAT. NO The DALI modular controller combines the crossfunctional KNX installation BUS and the DALI BUS specifically designed for lighting control. It is thus possible to integrate luminaires with low-cost digital DALI ballasts in a global KNX architecture and control them from existing KNX devices. DALI groups/scenes can be created locally via an LCD menu or a WEB interface. The DALI modular controller can be used for lighting management in large areas (open spaces, ballrooms, etc.). All the controls (switch, detector, etc.) will be connected to the inputs of the nearest controllers in the rest of the installation. The controller can indicate 3 faults in the installation: general, group and luminaire. Each fault is specified: Ballast, BUS, Lamp. Technical characteristics Power supply: 29 V=, wiring on BUS/KNX 16 control groups 16 scenes 64 ballasts per group Fault management Communication object Type Inputs Outputs Object 1 On/Off bit 4 Dimming bits 1 level byte 1 enable/disable control bit 1 clock 1 scenario byte 1 On/Off status bit 1 Value status byte 1 lamp fault bit 1 ballast fault bit 1 DALI BUS fault bit For further information, please refer to the technical data sheet in the e-catalogue, 19

20 V Hz Device presentation and installation (continued) PRI PRI: V mA 50/60Hz SCS : 27Vdc 600mA LEARN SCS KNX ROLLER BLIND MODULAR CONTROLLER CAT. NO MULTI-CHANNEL MODULAR CONTROLLER CAT. NO This module can control up to four blinds or shutters. The blind controls are available on the front panel, enabling wiring and operating tests to be carried out. This module can be configured via the ETS tool and provides a number of communication objects. To obtain a status, it is essential to have entered the blind lowering time parameters and to have initialised the controller (raised and lowered the blinds). Technical characteristics Power supply: V - 29 V= Operating temperature: - 5 to + 45 C Dimensions: 4 modules Communication object Type Inputs Outputs Object 1 Up/Down bit 1 Open/Close bit 1 Up/Down blocking bit 1 Save/Restore bit 1 Alarm bit 8 Open/Close status bits 8 Up/Down status bits The controller is used with other products (SCS controllers, controls). The modular controller Cat. No is used with a power supply (supplied) to power all the connected BUS peripherals. Technical characteristics Power supply: 27 V=, 600 ma (supplied) Communication object Number of communication objects: 2 The number of communication objects changes according to the number of associated products Type Inputs Outputs Object 1 scenario byte 1 scenario byte Architecture with modular controller (see p. 27) 20

21 SCS MODULAR CONTROLLERS To be used in conjunction with the multi-channel modular controller. For connection to the peripheral BUS with accessory Cat. No For dimming: DALI modular controller with 8 outputs: Cat. No Modular controller with 1-10 V ballast: Cat. No Halogen modular controller with 1 output: Cat. No Halogen modular controller with 2 outputs: Cat. No Technical characteristics Power supply: VA Consumption: - Off-load: 0.8 W for Cat. Nos / W for Cat. No W for Cat. No Max. depending on the load Operating temperature: - 5 to + 45 C Dimensions: 10 modules for Cat. Nos /12 6 modules for Cat. Nos /22 Communication object Number of communication objects: 48 for Cat. No for Cat. No for Cat. No for Cat. No Type Inputs Outputs Object 1 On/Off bit 4 Dimming bits 1 level byte 1 enable/disable bit 1 scenario byte 1 On/Off status bit 1 Value status byte For on/off lighting: 16 A modular controller with 1 output: Cat. No A modular controller with 2 outputs: Cat. No A modular controller with 4 outputs: Cat. No A modular controller with 8 outputs: Cat. No Technical characteristics Power supply: VA Consumption: - Off-load: 0.8 W for Cat. Nos /01/ W for Cat. No Max. depending on the load Operating temperature: - 5 to + 45 C Dimensions: 4 modules for Cat. Nos /01 6 modules for Cat. No modules for Cat. No Communication object Number of communication objects: 3 for Cat. No for Cat. No for Cat. No for Cat. No Type Inputs Outputs Object 1 On/Off bit 1 enable/disable bit 1 scenario byte 1 On/Off status bit 21

22 Device presentation and installation (continued) TOUCH CONTROL CAT. NO IP COMMUNICATION MODULE CAT. NO The touch control is used for two operations: - To create a local supervision system - To create automatic control devices Configuration is carried out via the ETS tool. Automatic control device: time programming, scene, logic function, presence simulation, display of curves. Technical characteristics Power supply: 230 V and 29 V= Consumption: 4.4 W Operating temperature: - 5 to + 45 C Fixing: in flush-mounting box supplied Supplied complete with aluminium finishing plate and support Communication object Type Inputs Outputs Object 1 On/Off bit 1 Up/Down bit 1 Open/Close bit 4 Dimming bits 1 level byte 2 override bits 1 scenario byte 8 Open/Close status bits 8 Up/Down status bits 1 On/Off bit 1 Up/Down bit 1 Open/Close bit 4 Dimming bits 1 level byte 2 override bits 1 scenario byte Enables KNX communication on the IP network, and display and control of the installation via a web page. There can only be one client connected to the gateway at once. Technical characteristics Power supply: V= Operating temperature: - 5 to + 45 C Dimensions: 4 modules Communication object Type Inputs Outputs Object 1 On/Off bit 1 presence bit 1 Up/Down bit 1 Open/Close bit 4 Dimming bits 1 level byte 2 override bits 1 scenario byte 8 Open/Close status bits 1 On/Off bit 4 Dimming bits Relative value (0 to 100%) 1 value byte (0 255) Real number 2 bytes Real number 4 bytes 1 level byte 2 override bits 1 scenario byte For further information, please refer to the technical data sheet in the e-catalogue, 22

23 USB INTERFACE CAT. NO LINE COUPLER CAT. NO Used to connect a PC to the BUS/KNX system via the USB port. Can be configured on ETS. Technical characteristics Power supply: Via USB connected to PC Operating temperature: - 5 to + 45 C Dimensions: 1 module Operating principle KNX OFFER Provides galvanic isolation between lines. Required for installations with more than 64 KNX products. For use in conjunction with power supply Cat. No Technical characteristics Power supply: 29 V= Consumption: 6 ma on primary line 8 ma on secondary line Operating temperature: - 5 to + 45 C Dimensions: 2 modules Operating principle x 64 ETS software Zone line KNX power supply KNX/DALI controller Zone Main line + KNX/1-10 V controller Controls and detectors Line coupler R 1 R 2 R 3 R = Repeater Controls and detectors Bus/KNX KNX/SCS interface SCS power supply *SCS power supply Cat. No supplied with Cat. No (KNX/SCS interface) * Line Part 0 Line Part Line Part Line Part 3 Communication configuration (see p. 34) KNX architecture (see p. 6) 23

24 Device presentation and installation (continued) KNX POWER SUPPLY CAT. NO KNX CABLE CAT. NO Can supply 1 BUS/KNX line. Integrated filter to avoid BUS message short-circuits. Voltage: 230 VA; 29 V=; 320 ma Connection by automatic terminals. Technical characteristics Supply voltage: VA 50/60 Hz BUS output voltage: 29 V= Operating temperature: -5 to + 45 C Size: 4 DIN modules Cable supplied in 500 m lengths. For indoor use. Colour RAL 6018 green. Technical characteristics Copper cable - Bare 0.5 mm² - Ø 0.80 mm. Maximum DC resistance loop: 73.2 ohms/km Maximum capacitance at 800 Hz: 100 nf/km Inductance: 0.65 mh/km Maximum DC operating voltage: 800 V Maximum AC operating voltage (5 mins): 2500 V Maximum AC operating voltage (1 min): 4000 V Insulation: PE - Ø 1.6 mm. Insulation resistance (at 500 V, 1 min): 10 Gohm km Number of pairs: 1 pair (2 conductors/pair) Identification of the conductor: RED/BLACK Packaging: 1 x PET sheet Within the shielding: wire aluminium foil-film mm² copper drain wire Cable and identification rip wire: YES Outer diameter: 5.5 mm² Smoke density: IEC Corrosive fire gas emissions: IEC /2 Outer sheath: LSFROH - Green RAL 6018 Cable marking: LEGRAND EIB BUS LSFROH 1x2/0.8, week, year, batch number and marking counter. Operating temperature: -25 to + 70 C 24

25 BUILDING MANAGER VIEWER CAT. NOS /04 BUILDING MANAGER CONTROLLER CAT. NO Software providing display, analysis and alarms for small commercial projects: - Display of the status of the connected systems - Simple scenario control of the systems - Display of alarms - Time programming For permanent installation on a dedicated PC. Integrated configuration wizard for easy creation of the project and the display screens: Legrand solutions pre-programmed (lighting management, emergency lighting, power measurement, fire alarms). When used with the building manager controller, Cat. No , provides total building management. Cat. No : Up to 100 points Cat. No : Up to 2000 points Automatic control device dedicated to automated control in commercial buildings requiring interoperability between the various connected systems: - Legrand solutions: lighting management, emergency lighting, power measurement, fire alarms - Other solutions: HVAC, etc. Performs the following: - Collection of data from the various systems: KNX IP, MODBUS IP, BACNET IP, SCS IP - Programming of scripts (with algorithm), alarms and data logging - Exchanges of collected data between systems (for example: display of the measured power circuit consumption values on digital screen) - Inclusion of HVAC systems (air conditioning, heating) - Sending s for alarms For installation in the VDI cabinet with dedicated patching of the various application systems Can be used with the building manager viewer Cat. No or to display the installation Operates with: - The measurement offer: with the RS 485/IP converter, or with communication modules used with the measurement control unit - The BUS/KNX lighting offer, with the KNX/IP converter - The BUS/SCS lighting offer with the zone controller - The BUS/SCS actimetry offer with the zone controller - The emergency lighting offer with the management interface for addressable self-contained emergency lighting units - The fire alarm offer with the RS 485/IP converter 25

26 Architecture ARCHITECTURE WITH FALSE CEILING CONTROLLER Role and operating principle Several types of peripheral can be connected to the false ceiling controller. The false ceiling controller performs the following functions: - Supplies power to each of its peripherals - Associates one or more load(s) with each peripheral during the Plug and Go procedure - Acts as the interface between its peripherals and the rest of the KNX system (ETS3/ETS4) - Controls all the loads KNX Input Output to controls L max = 150 m RESTRICTIONS Maximum 32 products/255 objects 8 control loops Max. line length Distance between 1 component and the false ceiling controller = 150 m 6 scenarios (10 max. per output) 26

27 PRI: V ma 50/60 Hz SCS: 27 VDC 600 ma SCS ARCHITECTURE WITH MODULAR CONTROLLER Role and operating principle Several types of peripheral can be connected to the modular controller. The modular controller acts as the interface between its peripherals and the rest of the KNX system. The purpose of this architecture is to implement an installation on DIN rail. The peripherals can be connected to the controller, however it is preferable to connect the controls to the nearest false ceiling controllers. Modular controller Modular controller Touch control KNX Modular controller Detector Control RESTRICTIONS - Maximum 32 products/ 255 objects/200 ma - Maximum 4 actuators - 8 control loops - Total line length 500 m - Distance between 1 component and a power supply 250 m -16 scenarios (10 max. per output) 27

28 Architecture (continued) WIRING Cat. No or Peripheral BUS Cat. No Do not use the BUS/KNX to wire the control BUS. 28

29 Design INTRODUCTION When creating a KNX project, it is essential to follow a sequence in the work process and in the actions to be carried out. The diagram below shows these actions, and the procedure to be adopted for each of the actions is described on the following pages. Design AUTOCAD layout Wire and power up Design the KNX project Configure the installation on ETS Check the operation of the installation 29

30 Design (continued) PRODUCT LAYOUT DESIGN (CAD) Layout diagram In order to be able to set all the parameters of the products, it is essential to indicate the following on the layout diagram for each control point (detector, control, etc.) and each actuator: - The identifier (ID) - The catalogue number Each of the lighting zones must be identified (zone number, name, etc.) so that the actuators concerned can be assigned to it on the wiring diagram. NOTES: In order to use less cable, it is logical to connect the controls (detector, switch, etc.) to the nearest actuator. It is important to connect the controls to the controller which controls the loads associated with it. Each product has a self-adhesive label on which all the necessary information is marked. These labels must be stuck onto the diagram when the products are physically installed. 30

31 Wiring diagram The diagram shows all the connections of the controllers and controls on the BUS INFORMATION TO BE PLACED ON THE WIRING DIAGRAM: 1 - Product catalogue number 2 - Identifier (ID) 3 - Physical address for KNX products 4 - Zone allocated to the outputs (controllers) 5 - Zone controlled by the controls 4 Take care not to exceed the maximum number of peripherals connected to the controllers see table below. 3 Before starting the configuration of all the products on ETS, check that the IDs on the diagram are correct with the Table for calculating the limits Product False ceiling controller Detectors Controls Total Max. Communication object 32 4 x 8 3 x 8 88 < 255 OK Consumption 4 x 17 3 x 5 83 < 200 OK No. of products < 32 OK No. of channels 4 4 x 1 3 x 2 14 < 64 OK No. of control loops 4 < 8 OK As in the above example 31

32 Design (continued) INSTALLATION WIRING AND POWERING-UP Wiring During wiring, the installer must comply with all the information in the documents (layout diagram, wiring diagram, description, etc.). If the IDs of the products are not on the diagram, it is essential to stick the label of each product, carrying its ID and catalogue number, onto the diagram. If the products are not identified on the diagram, it will not be possible to configure the products on ETS. Powering-up The KNX false ceiling controller has a Plug and Go (PnG) system which enables the peripherals connected to it to be configured independently. This step enables the physical connections and correct operation of the products to be checked. The false ceiling controller can be reset with a short press followed by a long press on the Prog & Reset button. This operation resets all the parameters of the peripherals and the false ceiling controller. The reset initiates a new Plug and Go procedure. The peripheral is reset by a short press followed by a long press (10 seconds) on the Learn button. The pink LED then flashes quickly. Plug and Go mode is automatically disabled once loading on ETS is complete. Following loading on ETS, the Plug and Go configuration is disabled. The controllers are used to control the loads via the pushbuttons on the front panel. This step is used to check the wiring of the loads. DALI learning: To address the ballasts: a short press followed by a long press on the DALI button. Plug and Go operation for each product, see product specification (p.11 to 17) 32

33 ETS CONFIGURATION The software used for KNX configuration is ETS3 or ETS4. It is used to create, design and test a KNX project. There are two options: the installer can create a project in the design office and then load the project on-site (OFFLINE) or create the project directly on-site while connected to the bus (ONLINE). The procedure is as follows: ONLINE configuration Load the Legrand Product database Add products and build the architecture OFFLINE configuration Configure the KNX physical addresses Find the peripherals on the network Open the plug-in Add all the products and enter the IDs Plug-in Add the peripherals to the configuration If necessary, select and modify the parameters of the products Create the group addresses Create the KNX links Configure the KNX physical addresses Open the plug-in + Find the peripherals Replace the products by the products found Plug-in Load the products 33

34 Design (continued) ETS CONFIGURATION Configuring the communication The communication media available are IP and USB. The gateways are connected to the KNX network and the configuration PC is connected to the gateway. The communication mode is selected on ETS. The IP/KNX gateway can be configured with a fixed IP address. In this case, an address must have been previously reserved on the network by the IT department. > For further information, please refer to the technical data sheet on Building the product architecture See the architecture section Configuring the physical addresses Once you are connected to the BUS you can configure the physical addresses of the products. Each product has a unique address. To do this, select the product then start loading on ETS. The products on the control BUS are not part of the BUS/KNX but are seen on ETS for configuration. Loading the product database Download the database from then import all the products into ETS. 34

35 Create the group addresses (Legrand template) Legrand requires the installer to follow the syntax rules for creating KNX groups so that a supervision system can be created quickly and assistance to engineers is optimised. If this architecture is not adhered to, Legrand cannot guarantee the automatic creation of the supervision system. To make this simpler, a Legrand template is available on Proposed architecture (Main and Middle Group Addresses). Syntax of Group Addresses: Zone Product ID, Product type, "installer character string" Office 05693F, SENSOR, Window Office 00437A92, CMD, CH1 Corridor Office 1.7.2, NRC, OUT1 Zone: location of the control or the load being controlled ID: ID or KNX physical address of the product Type: CMD SENSOR NRC etc. Character string: free field for the installer to assist with location. 35

36 Design (continued) ETS CONFIGURATION Communication parameters and objects DETECTORS Inputs SENSOR_IN_OCC/UNOCC (SIOU) SENSOR_IN_ON/OFF_STATUS (SIOOS) SENSOR_IN_LEVEL_STATUS (SILS) SENSOR_IN_SYNCHRO (SISC) SENSOR_IN_LUX (SIL) Additional I/O External Motion Detection Daylight Level Measure Output SENSOR_OUT_OCC_UNOCC (SOOU) SENSOR_OUT_ON/OFF (SOOO) SENSOR_OUT_LEVEL (SOL) Accessible Parameters Mandatory Parameters TimeDelayHours (TDH) TimeDelayMinutes (TDM) TimeDelaySeconds (TDS) Functional Mode (FM) Daylight SetPoint (DS) Optional Parameters TypeLoop (TP) Lighting Regulation (LR) Initial Occupancy (IO) Maintain Occupancy (MO) Retrigger (RT) Acoustic Alert (AA) MANUAL CONTROLS Inputs IN_ON/OFF_STATUS (IOOS) IN_LEVEL_STATUS (ILS) Additional I/O Status LED Output OUT_ON/OFF (OOO) OUT_DIM (ODIM) Accessible Parameters Functional Mode (FM) 36

37 SCENARIO CONTROL Inputs NONE Additional I/O None Output NONE Accessible Parameters Num Scene (NS) ACTUATOR OUTPUTS Inputs IN_ON/OFF (IOO) IN_LEVEL (ILV) IN_DIM (IDIM) IN_ENABLE/DISABLE (ILO) IN_OVERRIDE ON/OFF-2bits (IOVR) IN_RECALL_SCENARIO (IRS) (1) IN_ENABLE_AUTOMATION (ILA) (1) (1) Only on false ceiling controllers. Additional I/O None Output OUT_ON/OFF (OOO) OUT_LEVEL_STATUS (SLV) Accessible Parameters Minimum Level (V_MINI_LEVEL) Levels for Scenarios (LVS) LIGHT LEVEL CELL Inputs NONE Additional I/O None Output OUT_LUX (SOL) reflects Lux measurement Accessible Parameters Send_Condition "send on change + cyclical" / "send on change" / "cyclical" Limit number of messages/minute 1-60 Dead Band Percentage (1% - 100%) TimeBase (minutes) 1-59 minutes (+/- 5%) 37

38 Design (continued) ETS CONFIGURATION Simple on/off control IOOS DPT_Switch Manual control OOO IOO DPT_Switch Actuator output SOO Simple on/off control + dimming DPT_Scaling Manuel control ODIM DPT_ IDIM Control_Dimming OOO DPT_Switch IOO Actuator output SLV Scenario control Scenario control DPT_SceneNumber IRS Actuator output 38

39 Control by detector (closed loop on/off control) DPT_Switch SIOOS Detector SOOO DPT_Switch IOO Actuator output SOO "Closed loop" mode is activated when the "Type loop" (TP) parameter is set to "closed loop" value. The "functional mode" (FM) parameter cannot be set to "manual on/auto off". Control by detector (open loop on/off control including light level cell) DPT_Switch SIOOS Light level cell SOL SIL DPT_Value_Lux Detector SOOO DPT_Switch IOO Actuator output SOO "Open loop" mode is activated when the "Type loop" (TP) parameter is set to "open loop" value. The "functional mode" (FM) parameter cannot be set to "manual on/auto off". 39

40 Design (continued) ETS CONFIGURATION (CONTINUED) Manual control combined with one detector (closed loop on/off control) DPT_Switch SIOOS CIOO COOO SISC SOOO IOO Manual control Detector DPT_Switch DPT_Switch IOO Actuator output SOO DPT_Switch Important: "COOO/IOO/SISC" and "SOOO/IOO" must be in two different groups. Control by detector (control with closed loop dimming) DPT_Scaling SILS Detector SOOO SOL DPT_Switch DPT_Scaling IOO ILV Actuator output SLV "Closed loop" mode is activated when the "Type loop" (TP) parameter is set to "closed loop" value. The "functional mode" (FM) parameter cannot be set to "manual on/auto off". 40

41 Control by detector (control with open loop dimming) DPT_Scaling SILS SOOO IOO Light level cell SOL SIL DPT_Value_Lux Detector DPT_Switch SOL ILV Actuator output SLV DPT_Scaling DPT_Switch "Open loop" mode is activated when the "Type loop" (TP) parameter is set to "open loop" value. The "functional mode" (FM) parameter cannot be set to "manual on/auto off". Manual control combined with one detector (control with closed loop dimming) DPT_Scaling SILS SOL DPT_Scaling ILV CILV Manual control COOO SISC DPT_Switch Detector SOOO DPT_Switch IOO Actuator output SLV IOO DPT_Switch Important: "COOO/IOO/SISC" and "SOOO/IOO" must be in two different groups. 41

42 Design (continued) ETS CONFIGURATION (CONTINUED) Manual control combined with several detectors (control with closed loop dimming) DPT_Scaling SILS SOL ILV DPT_Scaling ILV Manual control OOO SISC DPT_Switch Detector MASTER SOOO IOO DPT_Switch Actuator output SLV SIOU IOO DPT_Switch DPT_Occupancy Detector SLAVE Detector SLAVE SOOU Important: "COOO/IOO/SISC" and "SOOO/IOO" must be in two different groups. The slave detectors must have the "lighting regulation" (LR) parameter set to "Disabled". 42

43 Setting the parameters of products via the plug-in The Legrand plug-in is used to set the parameters of all the products. It can also be used to find all the peripherals connected to the product. The plug-in can also be used to copy a configuration from one controller to another. For further information, go to the help section in ETS. Loading the products Loading can be carried out via all available gateways (IP, USB). 43

44 LE05504AA Head office 128, av. du Maréchal-de-Lattre-de-Tassigny Limoges Cedex - France Tel: +33 (0) Fax: +33 (0)

Lighting control for commercial buildings

Lighting control for commercial buildings [ INTELLIGENT SOLUTIONS ] Products and systems Lighting control for commercial buildings For management of different functions in a simultaneous and integrated way, via a BUS line Cost saving thanks to

More information

Niloé. Getting it just right

Niloé. Getting it just right Niloé Getting it just right Just right... for the environment and for you Eco design laser marking reduction packaging optimization packaging and dust protection recycled materials the Niloé range is manufactured

More information

OT EASY 60 II. LED control unit Operating instructions

OT EASY 60 II. LED control unit Operating instructions II LED control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Intended use 4 Description... 5 Function and application 5 Function 5 Important definitions

More information

Plexo IP 55/IP 66. Makes your day, rain or shine PLEXO / WEATHERPROOF PRODUCT GUIDE. For reference only.

Plexo IP 55/IP 66. Makes your day, rain or shine PLEXO / WEATHERPROOF PRODUCT GUIDE. For reference only. Plexo IP 55/IP 66 Makes your day, rain or shine PLEXO / WEATHERPROOF PRODUCT GUIDE www.legrand.com.sg Plexo IP 55 Ingenious features for easy installation >> Time saving guaranteed: no cut-out Uncut pierceable

More information

Small and Medium Building New and Renovation Prescription Assistance Complete Solution

Small and Medium Building New and Renovation Prescription Assistance Complete Solution Small and Medium Building New and Renovation Prescription Assistance Complete Solution 1 1) Introduction... 3 2) Control/Automation of the building... 4 2.1) Control interfaces... 4 2.1.1) Commands by

More information

Electrical devices may only be mounted and connected by electrically skilled persons.

Electrical devices may only be mounted and connected by electrically skilled persons. DALI gateway TW Art. No. : 2099REGHE Operating instructions 1 Safety instructions Electrical devices may only be mounted and connected by electrically skilled persons. Serious injuries, fire or property

More information

1 Safety instructions. 2 Device components. 3 Function. IC00P01DAL - DALI gateway. DALI gateway. Operating instructions

1 Safety instructions. 2 Device components. 3 Function. IC00P01DAL - DALI gateway. DALI gateway. Operating instructions DALI gateway Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Serious injuries, fire or property damage possible. Please

More information

All two-way switches with indicator have a terminal for neutral connection and have to be equipped with an indicator

All two-way switches with indicator have a terminal for neutral connection and have to be equipped with an indicator Programme switches, pull-cord switches and ventilation control 0 792 01 0 792 11 0 770 02 0 792 12 0 770 14 0 770 27 All two-way switches with indicator have a terminal for neutral connection and have

More information

Product documentation

Product documentation Product documentation Universal push-button module with integrated BCU, 1-gang Universal push-button module with integrated BCU, 2-gang Universal push-button module with integrated BCU, 3-gang Universal

More information

L4561N Stereo Control. Installation manual.

L4561N Stereo Control. Installation manual. L4561N Stereo Control www.legrand.com Stereo Control Contents Stereo Control 1 Introduction 4 1.1 Warnings and tips 4 1.2 General description 4 2 Installation 5 2.1 Wiring diagram 5 3 Configuration 7 3.1

More information

Operating and mounting instructions

Operating and mounting instructions General Usage IPAS DALI Gateways bring together the crossfunctional KNX installation bus and the lighting control specific DALI-Bus (IEC 60929). Lights with cost-effective, digital DALI ECGs can therefore

More information

General catalogue Export SMOUTS ARCHITECTEN

General catalogue Export SMOUTS ARCHITECTEN General catalogue 2011-2012 Export SMOUTS ARCHITECTEN 01 NIKO HOME CONTROL INTERIEUR DEWAIDE Project management Configuratie Installatie Help Niko Home Control (available from 1 August 2011) Live it, love

More information

Installation and User Guide

Installation and User Guide D5 Installation and User Guide 8-Channel DALI Controller (478) Introduction The 478 is for controlling DALI ballasts, drivers and load interface units (except for the 490 Blinds Controller). Do not connect

More information

M-bus web server. Meters and Energy Cost Allocation WTV676-HB6035

M-bus web server. Meters and Energy Cost Allocation WTV676-HB6035 Meters and Energy Cost Allocation M-bus web server WTV676-HB6035 The web server reads out wireless or wired M-bus devices over Ethernet or the Internet using a browser. Power and connection for up to 20

More information

Chorus Home Automation KNX - Easy BUS

Chorus Home Automation KNX - Easy BUS Chorus KNX - Easy BUS KNX Easy protocol BUS system, according to EN50090 European Standard for Home Automation. Simplified programming that does not require a PC. Portable solution, thanks to the wireless

More information

Plexo IP 55/IP 66 Makes your day, rain or shine

Plexo IP 55/IP 66 Makes your day, rain or shine Plexo IP 55/IP 66 Makes your day, rain or shine PLEXO / WEATHERPROOF WIRING DEVICES www.legrand.com.sg Plexo IP 55 Ingenious features for easy installation >> Time saving guaranteed: no cut-out Uncut pierceable

More information

1-channel shutter actuator 6A UP Installation Instructions

1-channel shutter actuator 6A UP Installation Instructions 2-channel switching actuator 6A UP 1-chan. universal dimming actuator 210 W 1-channel switching actuator 16A UP Order no.: 1047 00 Order no.: 1057 00 Order no.: 1058 00 Order no.: 1059 00 System rmation

More information

System Installation guide

System Installation guide System Installation guide Ligo System installation guide V3 newestpage 1 of 14 Contents 1 INTRODUCTION... 3 2 SYSTEM TOPOLOGY... 3 3 CONTROL ELEMENTS... 4 3.1 LIGO CONTROLLERS... 4 3.2 IP DOMAIN... 5 3.3

More information

DALI Professional Controller-4. Control unit Operating instructions

DALI Professional Controller-4. Control unit Operating instructions LI Professional Controller-4 Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Configuration 5 Design 5 Connections

More information

Building Control GAMMA instabus

Building Control GAMMA instabus The worldwide standard for home and building control Building Control GAMMA instabus siemens.com/gamma The comprehensive GAMMA instabus product portfolio comprises intelligent devices and is your key to

More information

Operating voltage Maximum

Operating voltage Maximum , 2CDG 110 0x R0011 2CDC 071 023 F000 The ABB i-bus Light Controllers, (x = 2 or 4) are KNX modular installation devices in ProM Design for installation in the distribution board on 35 mm mounting rails.

More information

4 CHANNEL UNIVERSAL DIMMING ACTUATOR

4 CHANNEL UNIVERSAL DIMMING ACTUATOR 4 CHANNEL UNIVERSAL DIMMING ACTUATOR USER MANUAL Tel.: 943627988 E-mail: knx@dinuy.com Web: www.dinuy.com General Description - 4 Channel universal modular dimming actuator for leading and trailing edge

More information

Universal dim actuator 1gang RMD Universal dim actuator 2gang RMD Universal dim actuator 4gang RMD

Universal dim actuator 1gang RMD Universal dim actuator 2gang RMD Universal dim actuator 4gang RMD KNX Product documentation Universal dim actuator 1gang RMD Universal dim actuator 2gang RMD Universal dim actuator 4gang RMD Issue: 19.12.2012 Page 1 of 153 KNX Product documentation Contents 1 Product

More information

Colour Touch Panel 3.5

Colour Touch Panel 3.5 Guangzhou Video-star Electronics Industrial Co., Ltd K-BUS R Colour Touch Panel 3.5 User manual-ver. 1.2 CHTF-35/01.1 CHTF-35/01.2.21 CHTF-35/01.2.22 CHTF-35/01.2.24 KNX/EIB Intelligent Installation Systems

More information

Single Channel Lighting Control Module

Single Channel Lighting Control Module Product Guide LMS-MIN-LCM, LMS-MIN-LCM-DIM, LMS-MIN-LCM-EM Single Channel Lighting Control Module The LMS-MIN-LCM series of lighting control modules (LCMs) are used as part of the LMS Lighting Management

More information

Modular Lighting Controls

Modular Lighting Controls Lighting Controls CONTROLS IP20 Simple to install and set up, Modular Lighting Controls offer the opportunity to create individually tailored systems to meet the requirements of many types of applications.

More information

idim Standalone idim idim Sense (316) (Master ) idim Ballast s idim Sol o Multisensor (312), (PIR extension) idim Sense (316) (PIR extension)

idim Standalone idim idim Sense (316) (Master ) idim Ballast s idim Sol o Multisensor (312), (PIR extension) idim Sense (316) (PIR extension) ) ( idim Standalone idim Multisensor (), (PIR extension) (PIR extension) (Master ) RJ Style PC Cable 0 V LI 6 ma idim Ballast s L N www.helvar.com idim Sol o SW Interface Modul e com 00-0 V 50-60Hz SW

More information

Control unit for lux control, MDRC Type: SL/S 50.1, GH Q R0001

Control unit for lux control, MDRC Type: SL/S 50.1, GH Q R0001 SK 0012 B 98 The control unit is a DIN rail mounted device for insertion in the distribution board. It is used to control digitally dimmable electronic ballast devices or transformers via the EIB. In a

More information

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005 Product and Applications Description Application Programs The application programs of the dimmer UP 525/01 consist of two elements: the actuating and the sensor program element. The tasks actuating program

More information

NiloéTM. Another timeless classic from Legrand now even easier to install. THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

NiloéTM. Another timeless classic from Legrand now even easier to install. THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES NiloéTM Another timeless classic from Legrand now even easier to install. THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES THE NILOÉ RANGE IS CHANGING And it s even easier to install!

More information

AIAS. Technical description

AIAS. Technical description Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains AIAS - and Efficient Heating Demand Products Controlled Tunnel Ventilation Fans 1 / 4 AIAS Technical description 2 / 9 AIAS -

More information

SWISS GARDE 360 HOKUSPOKUS KNX/KLR APPLICATION DESCRIPTION

SWISS GARDE 360 HOKUSPOKUS KNX/KLR APPLICATION DESCRIPTION SWISS GARDE 360 HOKUSPOKUS KNX/KLR APPLICATION DESCRIPTION MODEL TYPE NO. SG HOKUSPOKUS KNX/KLR 25010 Program version 2.7 2012 M. Züblin AG Neue Winterthurerstrasse 30, 8304 Wallisellen, Switzerland The

More information

KNX DALI Gateway Plus - User Manual

KNX DALI Gateway Plus - User Manual KNX DALI Gateway Plus - User Manual Item No.: LC-013-064 1. Product Description The KNX DALI gateway Plus is the interface between the KNX installation and the DALI lighting system. It allows up to 64

More information

Product and function description

Product and function description GAMMA instabus The following display and operating functions can be configured: switching, switching with forced control, dimming, sun protection control, recall and save scenes, sending and displaying

More information

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication 3 870 DESIO RXB Room controller for chilled ceilings and radiators with EIB bus communication RXB10.1 The RXB10.1 controller is used for temperature control in individual rooms: For chilled ceilings and

More information

Arteor TM Radio/ZigBee

Arteor TM Radio/ZigBee Arteor TM Radio/ZigBee n Switches and dimmers maximum loads at 230 V For values at 0 V, please halve values Leading edge Trailing edge Cat.Nos. Incandescent lamp Halogen lamp ELV halogen with ferromagnetic

More information

Valena Life TM - Valena TM Cat. 6A RJ45 sockets

Valena Life TM - Valena TM Cat. 6A RJ45 sockets 128, av. du Maréchal-de-Lattre-de-Tassigny - 87045 LIMOGES Cedex Tel: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 www.legrand.com Valena Life TM - Valena TM 7 554 /21/22 1. USE Category 6A RJ45 socket.

More information

EY-EM : Remote I/O module, ecolink

EY-EM : Remote I/O module, ecolink EY-EM 510...512: Remote I/O module, ecolink510...512 How energy efficiency is improved Optimum adjustment to applications by means of module technology. Reduction in wiring Features Part of the SAUTER

More information

Data sheet. Function description. Benefits

Data sheet. Function description. Benefits Function description To permit direct communication with the Philips SR interface, we offer two of our best and most innovative sensors: the ED PIR sensor with its patented multi-segment sensor lens and

More information

DALI Professional Frequently asked questions Light is OSRAM

DALI Professional Frequently asked questions Light is OSRAM www.osram.com DALI Professional Frequently asked questions Light is OSRAM DALI PROFESSIONAL Frequently Asked Questions What is the max. cable length in OSRAM DALI PROFESSIONAL system? Is it 300 m in total

More information

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications 3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for

More information

DESIGN SOLUTIONS FOR HOME AUTOMATION

DESIGN SOLUTIONS FOR HOME AUTOMATION DESIGN SOLUTIONS FOR HOME AUTOMATION Arteor TM, design options for Home Automation The system works through 2 different media formats: - Radio using ZigBee protocol - BUS using SCS protocol Products have

More information

Nemo SX - Multifunction control module

Nemo SX - Multifunction control module Via Travaglia 7, 20094 Corsico (MI) - Italia Tel. +39 0244878.1 - Fax +39 024503448 Contents Pages 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection... 1 5.

More information

Suno TM switches, push-buttons, dimmers, roller blind controls

Suno TM switches, push-buttons, dimmers, roller blind controls switches, push-buttons, dimmers, roller blind controls 7746 01 + 7746 41 7740 02 + 7740 41 7740 96 + 7740 41 7740 13 + 7740 41 7740 62 + 7740 41 Mechanisms supplied with Ivory or White cover plates, to

More information

Lighting Controls and Connectivity scenecom. scenecom L, XL, XL EM and XL EM Bac scenecom Controller

Lighting Controls and Connectivity scenecom. scenecom L, XL, XL EM and XL EM Bac scenecom Controller L, XL, XL EM and XL EM Bac Controller Product description Independent lighting control for up to 192 DALI control gears on 3 DALI lines Simple setup via WEB interface Cross DALI line control Freel programmable

More information

KNX/EIB Flush-mounted universal dimming actuator 210 W. 1 Safety instructions. 2 Device components. Order-No. : Operating instructions

KNX/EIB Flush-mounted universal dimming actuator 210 W. 1 Safety instructions. 2 Device components. Order-No. : Operating instructions Order-No. : 1058 00 Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe the instructions may cause damage

More information

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02 s 3 878 RXL Room controller RXL24.1 Communicating controller for chilled ceiling and radiator applications CC-02 The RXL24.1 room controller is used for temperature control in individual rooms. For chilled

More information

Data sheet MK 20 GR. Customized solution or off-the-shelf: The choice is yours!

Data sheet MK 20 GR. Customized solution or off-the-shelf: The choice is yours! Data sheet MK 20 GR Customized solution or off-the-shelf: The choice is yours! MK20-GR data sheet Looking for a quick and reliable solution? Then rely on our standard products: Our universal controls provide

More information

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs Product and Applications Description Example of Operation dimmer UP 525/11 load circuit AC 230 V L1 N The dimmer UP 525/11 is a dimming actuator for mounting in box mounts (a.o. 60 mm Ø, 60 mm depth).

More information

ATS Automatic transfer switches Advanced version

ATS Automatic transfer switches Advanced version 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 ATS CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. ELECTRICAL AND MECHANICAL CHARACTERISTICS 2 5. CONFORMITY 4 6. EQUIPMENTS

More information

SECTION DIGITAL LIGHTING CONTROLS

SECTION DIGITAL LIGHTING CONTROLS SECTION 26 09 25 PART 1 - GENERAL 1.1 SUMMARY A. Work included: 1. General Performance 2. Digital Wall or Ceiling Mounted Occupancy Sensor System 3. Digital Wall Switches 4. Handheld Remote Controls 5.

More information

Emergency. Lighting. CATALOGUE Vol. 01. Decentralised and centralised supply

Emergency. Lighting. CATALOGUE Vol. 01. Decentralised and centralised supply Emergency CATALOGUE Vol. 01 Lighting Decentralised and centralised supply Light is safety Light must be safe! Interior luminaire, exterior luminaire and emergency luminaire are all important to ensure

More information

LDALI ME204-U, LDALI ME201 U

LDALI ME204-U, LDALI ME201 U Functions BACnet/ Controller L ME204-U, L ME201 U BACnet CEA 709 Modbus OPC Datasheet #89021219 L WEB, L STUDIO L Controllers are multifunctional devices combining constant light con trol, sunblind control

More information

HDL KNX/EIB Koduautomaatika Hinnakiri 2015

HDL KNX/EIB Koduautomaatika Hinnakiri 2015 HDL KNX/EIB Koduautomaatika Hinnakiri 0 (A) Lighting & Dimming Control Modules Jan 0 S/N Picture Brief Description Model Number BUS Power Dimension (mm) CH 6A High Power Switch Actuator,DIN-Rail Mount,0VAC

More information

Office Roombox 4 in 1 Energy Optimiser

Office Roombox 4 in 1 Energy Optimiser Electrical Distriution and Roller linds Office Roomox DB797 DB79 Roomox is a new innovative device for electrical distriution, protection, electrical energy metering and control for lighting, shutter and

More information

KNX. Preliminary edition 17 Jan Siemens Building Technologies HVAC Products. Synco Konnex bus. For devices of the Synco 700, Synco RXB series

KNX. Preliminary edition 17 Jan Siemens Building Technologies HVAC Products. Synco Konnex bus. For devices of the Synco 700, Synco RXB series Preliminary edition 17 Jan 2003 3 127 3127Z01 Synco Konnex bus For devices of the Synco 700, Synco RXB series KNX The Konnex bus (short KNX) unites the three existing bus technologies EIB (European Installation

More information

Push-buttons 18. Light scenes push-buttons 21. Push-buttons with thermostat 22. Labelling ields 24

Push-buttons 18. Light scenes push-buttons 21. Push-buttons with thermostat 22. Labelling ields 24 A wide array of alternative materials and colours have been added to the convenient variety of KNX functionality of the. Frameless KNX push-button with full-material rockers (glass, stainless steel and

More information

RVL470. Heating controller. G2522en. Installation Instructions. 1 Installation. 2 Commissioning Wall mounting DIN rail mounting

RVL470. Heating controller. G2522en. Installation Instructions. 1 Installation. 2 Commissioning Wall mounting DIN rail mounting G2522en Heating controller Installation Instructions RVL470 1 Installation 1.1 Place of installation In a dry room, e.g. the boiler room Mounting choices: In a control panel (on the inner wall or on a

More information

Product and functional description

Product and functional description Product and functional description The RS 520/23 shutter / blind actuator is a KNX device with one relay output. The device is installed in an AP 118 Control Module Box or an AP 641 Room Control Box. The

More information

Application description

Application description Manufacturer Berker Motion detector Application description KNX motion detector module comfort 1.10m KNX motion detector module comfort 2.20m ETS KNX motion detector module comfort 1.10m ETS KNX motion

More information

Specification Sheet For electronically commutated motors

Specification Sheet For electronically commutated motors SC-VAV-N Specification Sheet For electronically commutated motors Used in constant pressure applications The SC-EFC is designed to control exhaust air in various building applications. The system includes

More information

- NLS NAVIGATION LIGHT CONTROL

- NLS NAVIGATION LIGHT CONTROL Technical documentation - NLS 3000 - NAVIGATION LIGHT CONTROL For use on seagoing vessels Change status Version Date Author Checked Remark 0.1 07.08.2008 STO HN 1. Edition 0.2 29.09.2010 STO TK Changes

More information

WAGO Lighting Management The Lighting Control Solution Stay in Control of Your System

WAGO Lighting Management The Lighting Control Solution Stay in Control of Your System WAGO Lighting Management The Lighting Control Solution Stay in Control of Your System OUR CONCEPT The Solution for Efficient Lighting Management in Production Facilities and Warehouses Using a combination

More information

INDEX PRESENCE DETECTOR AND BRIGHTNESS SENSOR INFRARED TRANSMITTER/RECEIVER & DECODER. PLC LOGO! and COMMUNICATION MODULE

INDEX PRESENCE DETECTOR AND BRIGHTNESS SENSOR INFRARED TRANSMITTER/RECEIVER & DECODER. PLC LOGO! and COMMUNICATION MODULE INDEX INTRODUCTION SINGLE PHASE POWER UNIT DL 20T70 POWER SUPPLY DL 20T7 PUSH BUTTON INTERFACE DL 20T72 DOUBLE PUSH BUTTON DL 20T74 SMOKE DETECTOR DL 20T75 TEMPERATURE CONTROLLER DL 20T76 PRESENCE DETECTOR

More information

WIRING ACCESSORIES NEW PRODUCTS. Mallia TM complete white. Mallia TM customisable colours. Belanko TM. Plexo, Industrial sockets

WIRING ACCESSORIES NEW PRODUCTS. Mallia TM complete white. Mallia TM customisable colours. Belanko TM. Plexo, Industrial sockets Mallia TM complete white P. 7 Switches and push-buttons Mallia TM customisable colours P. 7 Switches and push-buttons and other lighting functions P. 69 Switches and push-buttons WIRING ACCESSORIES Belanko

More information

Belimo Gateway MP to Modbus RTU - UK24MOD

Belimo Gateway MP to Modbus RTU - UK24MOD Product information UK24MOD MODBUS RTU Belimo Gateway MP to Modbus RTU - UK24MOD Contents Complete overview 2 Technical data 3 Safety notes 4 Product features 4 Installation and commissioning 4 Electrical

More information

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station s 3 836 3836P01 Desigo TRA PL-Link IO Block Use with PXC3 series room automation station RXM39.1 The PL-Link IO Block contains the inputs and outputs controlled by a room automation station via PL-Link.

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

Power supply 142. Couplers 143. Data interfaces 144. Accessories 145

Power supply 142. Couplers 143. Data interfaces 144. Accessories 145 KNX system units The system components are KNX devices, which assume higher-level functions, independent of the application. They guarantee the necessary infrastructure in the building, ensuring a flawless

More information

EMS CX 3 - Signalling Auxiliary Contact (CA + SD)

EMS CX 3 - Signalling Auxiliary Contact (CA + SD) 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 EMS CX 3 - Signalling Auxiliary Contact Contents Pages 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

IP gateway, MDRC IG/S 1.1, GH Q R0001

IP gateway, MDRC IG/S 1.1, GH Q R0001 , GH Q631 0067 R0001 The IP gateway IG/S is the interface The IP address of the IG/S can be between EIB / KNX installations and IP fixed or received from a DHCP server. CDC 071 130 F0003 networks. Data

More information

K-BUS R. Dimming Actuators. User manual-ver. 4 KA/D KA/D KA/D KA/D 04.T1.1 ADTV-04/16.1 KA/D 04.L1.1 ADLD-04/

K-BUS R. Dimming Actuators. User manual-ver. 4 KA/D KA/D KA/D KA/D 04.T1.1 ADTV-04/16.1 KA/D 04.L1.1 ADLD-04/ Guangzhou Video-star Electronics Industrial Co., Ltd K-BUS R Dimming Actuators User manual-ver. 4 KA/D 0103.1 KA/D 0203.1 KA/D 0403.1 KA/D 04.T1.1 ADTV-04/16.1 KA/D 04.L1.1 ADLD-04/03.1...... KNX/EIB Intelligent

More information

alena switc es Switches 10 AX VA - IP 44 Mechanisms supplied with cover plates, to be equipped with plates (p ) Screw or claw mounting

alena switc es Switches 10 AX VA - IP 44 Mechanisms supplied with cover plates, to be equipped with plates (p ) Screw or claw mounting alena switc es 7 701 01 + 7 701 51 7 744 10 + 7 744 51 (p. 498-499) Screw or claw mounting Pack Cat.Nos Switches 10 AX - 250 VA One-way switch 10 7 743 01 Ivory 10 7 744 01 White 10 7 701 01 Brilliant

More information

EY-RU : Room operating unit, ecounit

EY-RU : Room operating unit, ecounit Product data sheet 94.040 EY-RU 341...346: Room operating unit, ecounit341...346 How energy efficiency is improved Individual setting of occupancy and absence as well as a room setpoint correction and

More information

Mosaic TM LCS2 Cat. 6 RJ 45 socket

Mosaic TM LCS2 Cat. 6 RJ 45 socket 870 LIMOGES Cedex Telephone : + 33 0 5 55 06 87 87 - Fax: + 33 0 5 55 06 88 88 Mosaic TM LCS2 Cat. 6 Page 765 61 765 44 765 94 1. General characteristics...1 2. Presentation...2 3. Installation....2 4.

More information

11 Series - Light Dependent Relay A. Features pole 17.5 mm wide. 1 pole zero hysteresis 4 position selector

11 Series - Light Dependent Relay A. Features pole 17.5 mm wide. 1 pole zero hysteresis 4 position selector Features 11.31 11.41 Relays for automatic control of lighting according to ambient light level - with separate light sensor 11.31-1 NO 16 A output contact Sensitivity adjustment from 1 to 100 lux One module,

More information

Switching Actuators N530, 6AX Switching Actuators N532, 10AX Switching Actuators N534, 16/20AX

Switching Actuators N530, 6AX Switching Actuators N532, 10AX Switching Actuators N534, 16/20AX Gamma instabus Technical Product nformation Switching Actuators N53, 6AX Switching Actuators N532, 1AX Switching Actuators N534, 16/2AX 4x AC 23V 5WG1 53-1DB31 5WG1 532-1DB31 5WG1 534-1DB31 8x AC 23V 5WG1

More information

TM221CE24R controller M IO relay Ethernet

TM221CE24R controller M IO relay Ethernet Product data sheet Characteristics TM221CE24R controller M221 24 IO relay Ethernet Complementary Main Discrete I/O number 24 Number of I/O expansion module Supply voltage limits Network frequency Inrush

More information

Mosaic TM LCS2 Cat. 6 RJ 45 socket

Mosaic TM LCS2 Cat. 6 RJ 45 socket 870 LIMOGES Cedex Telephone : + 33 0 5 55 06 87 87 - Fax: + 33 0 5 55 06 88 88 Mosaic TM LCS2 Cat. 6 Page 765 61 765 44 765 94 1. General characteristics....1 2. Presentation...2 3. Installation...2 4.

More information

High-performance switching actuators

High-performance switching actuators High-performance switching actuators Wide-ranging applications efficient installation and set-up operation for many years The worldwide standard for home and building control siemens.com/gamma Switching

More information

PRESENCE DETECTOR, CONSTANT LIGHT CONTROLLER PD00D01KNX. Product Handbook

PRESENCE DETECTOR, CONSTANT LIGHT CONTROLLER PD00D01KNX. Product Handbook PRESENCE DETECTOR, CONSTANT LIGHT CONTROLLER PD00D01KNX Product Handbook Product: PD00D01KNX Description: PRESENCE DETECTOR, CONSTANT CONTROLLER Document Version: 1.3 Date: 03/10/2017 Tribunale di Mila

More information

Product data sheet accessories control and regulation Accessories AIRWIN

Product data sheet accessories control and regulation Accessories AIRWIN Product data sheet accessories control and regulation BO-CT1 Continuous controller Item no. 6100101 Control of humidification performance BO-CT1 Option board 2 binary inputs Item no. 002212 Setpoint switching,

More information

How to choose the correct Mount Kelvin central unit

How to choose the correct Mount Kelvin central unit Installation guide Outside world Property Wirepas mesh Mount Kelvin app Internet connection Ethernet DALI 3rd party integrations Mount Kelvin cloud Mount Kelvin central unit Voice control EnOcean wireless

More information

EMS CX 3 - Modbus/EMS Interface

EMS CX 3 - Modbus/EMS Interface 87045 LIMOGES Cedex Telephone : 05 55 06 87 87 Fax: 05 55 06 88 88 EMS CX 3 - Modbus/EMS Interface Contents Pages 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Product and functional description

Product and functional description Product and functional description The UP 525/13 Universal Dimmer is a KNX device with one dimmer output. The device is installed in a flushmount wall box (60 mm Ø, depth 60 mm) or an installation box.

More information

IntesisBox KNX - AIRZONE

IntesisBox KNX - AIRZONE IntesisBox KNX - AIRZONE Gateway for the integration of Airzone InnoBUS into KNX systems. Full integration of Airzone InnoBUS air conditioning with KNX control systems. CS CS KNX EIB Bus IntesisBox RS485

More information

Chorus Building Automation KNX BUS

Chorus Building Automation KNX BUS Chorus Building Automation A KNX protocol BUS system, according to European standard EN50090, for Home and Building Automation. Economic benefits thanks to advanced functions which allow smart automation

More information

DELTA style 6/1. 6/6 Introduction. 6/7 Frames. 6/8 Switches and pushbuttons. 6/14 Socket outlets. 6/16 International plug-and-socket devices

DELTA style 6/1. 6/6 Introduction. 6/7 Frames. 6/8 Switches and pushbuttons. 6/14 Socket outlets. 6/16 International plug-and-socket devices / Introduction /7 Frames /8 Switches and pushbuttons /14 Socket outlets /1 International plug-and-socket devices /17 Shutter/blind controls /21 Lighting controls /24 Motion detectors /2 Room temperature

More information

Tebis application software

Tebis application software 5 Tebis application software SXB322AU V 1.x 2 inputs / 2-output module LED SXB344AU V 1.x 4 inputs / 4-output module LED Product reference Product designation TXB322AU TXB344AU Embedded module: 2 inputs

More information

Room automation station

Room automation station s 9 203 9203mmP01 Desigo TRA Room automation station PXC3.E7... Modular, programmable room automation stations for HVAC, lighting, and shading. BACnet / IP communications; BACnet profile ASC (BTL label).

More information

pole 17.5 mm wide. electronic ballast W

pole 17.5 mm wide. electronic ballast W SERES SERES Relays for automatic control of lighting according to ambient light level - with separate light sensor.31-1 NO 16 A output contact Sensitivity adjustment from 1 to 100 lux One module, 17.5

More information

application software

application software application software application software RF input product Electrical / Mechanical characteristics: see product user manual Product reference Product designation TP device RF devices 8565 52 xx 8565 62

More information

LUXORliving System manual Version 1

LUXORliving System manual Version 1 LUXORliving System manual Version 1 2018-04-18 Contents 1 General 3 2 System 4 3 Installation 5 4 Start-up 7 4.1 Establish a connection 7 4.2 Configuration with LUXORplug 10 4.3 Programming with LUXORplug

More information

The output variables can be force-controlled from a coordinating control system.

The output variables can be force-controlled from a coordinating control system. Produktname: 4-channel analog actuator Bauform: rail-mounted device Artikel-Nr.: 1022 00 ETS-Suchpfad: Gira Giersiepen / Output / Analog output 4fach / Analog actuator 4fach Scope of application: The analog

More information

Product documentation

Product documentation Product documentation Rotary sensor ALBRECHT JUNG GMBH & CO. KG Volmestraße 1 58579 Schalksmühle Telefon: +49.23 55.8 06-0 Telefax: +49.23 55.8 06-2 04 kundencenter@jung.de www.jung.de Service Center Kupferstr.

More information

LLR-MOD Modbus Light Level and Occupancy Sensor

LLR-MOD Modbus Light Level and Occupancy Sensor Product sheet SN1.418 Type LLR-MOD LLR-MOD Modbus Light Level and Occupancy Sensor The LLR-MOD sensors are designed to measure Light Level (LUX) in the room spaces and have built-in RS485 Modbus communication

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

Swiss Garde 360 PresenceDALI Master A-Comfort 24 m

Swiss Garde 360 PresenceDALI Master A-Comfort 24 m Installation instructions - Swiss Garde 360 Presence DALI Master A-Comfort m Art.-Nr. 750, 75, 76 - Edition 8-07 Swiss Garde 360 PresenceDALI Master A-Comfort m Edition UP Art.-Nr. 750, 75 360 H ca. 50%

More information

M-Bus Central Unit. Use

M-Bus Central Unit. Use 6 M-Bus Central Unit OZW The M-bus central unit is used for the remote readout, remote operation and supervision of an M-bus plant with a maximum of consumption meters and controllers featuring an M-bus

More information

LCC1653/01, LRI1653/01 ActiLume DALI System

LCC1653/01, LRI1653/01 ActiLume DALI System 1/8 Product description The Philips ActiLume lighting control system consists of a small, lightweight sensor and controller, designed for easy integration into luminaires. ActiLume is a true Plug and Play

More information