1 Switchgear LIFe ExtenSIon: Replacement of electromechanical Overcurrent Relaying By Todd Martin, Basler Electric Company Chemical Facility U p d at i n g S w i t c h g e a r R e l ay s Electromechanical overcurrent relays such as the IAC and CO are the historical backbone of power system protection. These relays use delicate mechanisms and precision components to develop their operating characteristics and are subject to misoperation and failure resulting from contamination, corrosion, and simple aging. As a result, frequent testing and recalibration are required to ensure proper operation. As the relays continue to age, failing internal insulation and increasing cost associated with maintenance and repair of the relays makes it increasingly difficult to ensure reliable operation. Reliable operation is essential for personal safety and the prevention of unnecessary outages and/or extensive damage due to overloads and faults. One solution to this problem is to upgrade the relays which will easily extend the life of the switchgear 10 to 20 years with minimal financial investment and very little labor. Upgrading reduces the need for maintenance and increases protection reliability which is very valuable during times of limited maintenance budgets. At the same time, upgrades often improve accuracy which is increasingly important because many systems are operating with less margin than planned for in their original design. The technology available in modern relay systems allows one device to replace what once took many separate devices to accomplish. Phase and ground protection are available in one box, along with ancillary features such as metering, data capture, advanced communications, and post fault analysis. What is sometimes overlooked is the value that newer technology can add by simply providing the same functionality as existing relays with less maintenance, less system burden, better precision, and greater reliability. There are several options for extending the life of switchgear by upgrading to newer technology, retrofit relays. NETAWORLD 43

2 One option is to replace existing relays with plug and play relays that require no wiring changes. The second option is to upgrade in place which means that a retrofit relay will fit the existing panel cutout. Some rewiring for the upgrade relay is required, but the existing panel does not have to be replaced. The first option benefits from being easier. It requires no down time and often can be done as part of routine maintenance and testing. The second option requires slightly more work and down time, but provides an avenue to add immediate benefits such as metering, event reporting, remote communications, and future automation. Plug and Play Relay Upgrade When facing electromechanical overcurrent relay obsolescence, a chemical facility in the Midwest chose to upgrade with plug and play relays. Their facility had 72 General Electric IAC relays that were to be replaced. For the upgrade, they selected the Basler BE1-50/51B-214 time overcurrent relays. The relay, a direct plug and play replacement for the IAC relay, is installed with no wiring or case change. The BE1-50/51B-214 has selectable time curves that emulate the majority of IAC variations, and it has less CT burden than the IAC model. This makes for a simple, economical way to upgrade from aging relays without the expense of completely redesigning and rewiring the systems to accept currently available functional replacements. The retrofit kit consists of a relay cradle, an adapter plate, and a cover. The kit allows plugin installation in an existing lac case. In order to prepare for the retrofit process, the facility s test and maintenance personnel received a day of on-site training. Fifteen employees spent most of the day learning about the relay. The training covered the relay basics, specifics of the 214 retrofit version, the retrofit process, and relay setup and testing. The identified process contained six steps: STEp 1: Set the relay to the desired pickup and timing settings. An available spreadsheet provided the necessary information to convert the electromechanical time curves to the correct equivalent curve on the replacement relay. STEp 2: Remove the existing relay. STEp 3: Attach the cover adapter with four provided screws. STEp 4: Install the new relay. STEp 5: Reinstall the existing connection plug. STEp 6: Install the new relay cover. The newly trained personnel were able to test and install the relays at a rate of three relays per hour. At this pace, replacement of all 72 relays was completed in only a few days. The retrofit was accomplished with minimal down time, minimal work, and most importantly, minimal expense. Because the new relays are solid state, they have no critical moving parts that can affect their performance and they require minimal maintenance. They also meet all ANSI/IEEE standards for operation in harsh power system environments. The benefits continued well after the installation. During periodic maintenance or troubleshooting, an electromechanical relay s timing characteristics must be checked and calibrated. Correct pickup and timing need to be determined by test in an iterative process. Settings in the relays are made by front panel switch settings. There is no calibration. These relays are not subject to drift or change in performance, so recalibration is never necessary. This can save valuable time in an outage emergency and save money in periodic maintenance costs on an ongoing basis. The savings in maintenance costs alone easily justify the cost of the new relays. 44 SUMMER 2011

3 Numeric Retrofit Upgrade Plug and play relays are not the only easy solution for accomplishing life extension of switchgear. The chemical facility could have chosen an alternate solution: a numeric retrofit installation. The IAC relays being replaced were simple devices with only instantaneous (50) and time (51) overcurrent elements. Any numeric relay far exceeds the protection available from the IAC relay. Just because the numeric relays provide multiple 50s, 51s, and a variety of other protective and control elements, does not mean the installer must use them. Remember, the goal was not to reengineer the switchgear, but to remove the existing relays that provided 50 and 51 protection and install one or more devices to provide the same protection to improve precision, increase reliability, and reduce maintenance. The solution of installing numeric retrofit required some wiring changes. Figure 1 shows the CT connections for a typical installation with three phase and neutral IAC relays. Figure 2 shows the DC circuit for the same typical system. The two diagrams show four relays with one each for phase A, phase B, phase C, and ground. Each relay has time and instantaneous outputs. All outputs are paralleled together to provide voltage to the 52 trip coil in the case of a fault. Figure 1 The process is a little different from the process of installing the plug and play but is still an easy install. Steps one (setting the relay) and two (wiring the relay) are the key differences. The list of steps is as follows. STEp 1: Set the relay to the desired pickup, timing settings, and logic. An available spreadsheet provided the information needed to convert the electromechanical time curves to the correct equivalent curve on the replacement relay. STEp 2: Remove the existing relay and case, taking care to label the wires before detaching. STEp 3: Install the new relay case in the panel. STEp 4: Wire up the new case. STEp 5: Install the new connection (paddle) plug. STEp 6: Install the relay cover that came with the new relay. Figure 2 NETAWORLD 45

4

5

Common Departures Interconnecting Facilities Requirements

Common Departures Interconnecting Facilities Requirements Welcome to our e-rew Express. In our last issue, we discussed the common departures on metering installation requirements. This time, we would like to discuss the common departures on the customer low

More information

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY The BE1-51 Series of Time Overcurrent Relays is microprocessor-based to provide versatile overload and fault protection on 50Hz or 60Hz systems. ADVANTAGES

More information

Outline. 1. Introduction 2. Why Upgrading? 3. Who Is Affected? 4. How to Upgrade? 5. Benefits of the New Upgraded UR

Outline. 1. Introduction 2. Why Upgrading? 3. Who Is Affected? 4. How to Upgrade? 5. Benefits of the New Upgraded UR UR Upgrade Program Outline 1. Introduction 2. Why Upgrading? 3. Who Is Affected? 4. How to Upgrade? 5. Benefits of the New Upgraded UR 2 UR Upgrade Program 9/9/2015 1. Introduction UR Protection and Control

More information

Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades

Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades May 2012 / 1910DB1202 by Hal Theobald, Product Manager, Schneider Electric Services and Reza Tajali, P.E.,

More information

ISGS. Intelligent SwitchGear System The Flexible Solution

ISGS. Intelligent SwitchGear System The Flexible Solution TM ISGS Intelligent SwitchGear System The Flexible Solution Multi-Function Flexibility At The Touch Of A Key Siemens introduces the ISGS Intelligent SwitchGear System a remarkable new development in switchgear

More information

No actual trip output occurs if the upper paddle is removed first.

No actual trip output occurs if the upper paddle is removed first. BE1-27/59 SCOPE This test procedure covers the testing of the Basler BE1-27/59 under/overvoltage relay. Refer to IM 9170600990 Rev. L (12/12) for testing support information and component level identification.

More information

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES BE1-50/51M TIME OVERCURRENT RELAY The BE1-50/51M Time Overcurrent Relay provides economical overload and fault protection for generators, transformers, lines and motors. ADVANTAGES Self powered from 50/60Hz

More information

MPSC Microprocessor-based protection and metering devices for low voltage power circuit breakers. ABB Power Distribution

MPSC Microprocessor-based protection and metering devices for low voltage power circuit breakers. ABB Power Distribution MPSC-2000 Microprocessor-based protection and metering devices for low voltage power circuit breakers ABB Power Distribution Introduction For circuit breaker protection, metering and communications, the

More information

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Figure.1 Altech s three new series deliver multiple capabilities. In all three series, ground fault sensitivity levels range

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements Introduction to Bus Protection By Matt Horvath, P.E. November 6, 2018 Electrical Buses Physical and Electrical Junction A bus is a critical element of a power system, as it is the point of convergence

More information

MODERNIZE YOUR DC CRANES. Convert Your DC Controls to State-of-the-Art Energy Efficient OmniPulse DDC Series 2 Drives

MODERNIZE YOUR DC CRANES. Convert Your DC Controls to State-of-the-Art Energy Efficient OmniPulse DDC Series 2 Drives TM MODERNIZE YOUR DC CRANES Convert Your DC Controls to State-of-the-Art Energy Efficient OmniPulse DDC Series 2 Drives Magnetek, the leader in digital power and motion control systems, brings you the

More information

S Contents. Figure 1. Kyle Form 4C Analog Current Metering Accessory KME

S Contents. Figure 1. Kyle Form 4C Analog Current Metering Accessory KME Reclosers Form 4C Microprocessor-Based Recloser Control Analog Current Metering Accessory KME4-82-1, KME4-82-2 Installation and Operation Instructions Service Information S280-77-8 Figure 1. Kyle Form

More information

DIAC/DIFC/DSFC. Single Phase Digital O/C. Single phase or ground overcurrent protection for industrial and utility power systems.

DIAC/DIFC/DSFC. Single Phase Digital O/C. Single phase or ground overcurrent protection for industrial and utility power systems. DIAC/DIFC/DSFC Single Phase Digital O/C DIAC DIFC DSFC Single phase or ground overcurrent protection for industrial and utility power systems. Features and Benefits models: DIAC, DIFC, DSFC Direct/functional

More information

INSTRUCTION MANUAL FOR OVERCURRENT RELAYS BE1-50/51B-219 AND BE1-50/51B-226

INSTRUCTION MANUAL FOR OVERCURRENT RELAYS BE1-50/51B-219 AND BE1-50/51B-226 INSTRUCTION MANUAL FOR OVERCURRENT RELAYS BE1-50/51B-219 AND BE1-50/51B-226 Publication: 9 2520 00 981 Revision: D 12/2000 INTRODUCTION This manual provides information concerning the operation and installation

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

INSTRUCTION MANUAL FOR

INSTRUCTION MANUAL FOR INSTRUCTION MANUAL FOR OVERCURRENT RELAY BE1-50/51B Publication: 9 2520 00 991 Revision: M 11/2000 BE1-50/51B - Introduction INTRODUCTION This manual provides information concerning the operation and installation

More information

Cost Effective Upgrade of Obsolete Electronics

Cost Effective Upgrade of Obsolete Electronics of Obsolete Electronics Barry W. Wiles Industry Manager Crane Systems Avtron Manufacturing Inc. 7900 E. Pleasant Valley Rd. Independence, OH 44131 Phone: (216) 642-1230 FAX: (216) 642-6037 bwiles@avtron.com

More information

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI)

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) GROUND FAULT CIRCUIT INTERRUPTERS Wiring design and protection. - 1926.404 Our company uses ground fault circuit

More information

Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability

Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability 1910DB1207 By Hal Theobald, Product Marketing Manager, Schneider Electric Services Summary 1.0 Abstract...3 2.0 Introduction...3

More information

MP-4000 motor protection. Protection, control and diagnostics

MP-4000 motor protection. Protection, control and diagnostics MP-4000 motor protection Protection, control and diagnostics Multi-function motor protection Introducing Eaton s MP-4000 motor protection relay Eaton s MP-4000 motor protective relay combines all the features

More information

FT Flexitest Family. Switches, Covers and Test Plugs

FT Flexitest Family. Switches, Covers and Test Plugs FT Flexitest Family Switches, Covers and Test Plugs FT Flexitest Switches Description The flexibility provided by the FT case design evolved into a separate family of molded base test switches for testing

More information

SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT

SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT ESTABLISHED SINCE 1985 Circuit Breaker Solid State Controls with RMS-2007AF LOGIC (All logics come with ARC FLASH as a standard) The SURE TRIP SOLID STATE

More information

RELT Reduced Energy Let Thru 2018

RELT Reduced Energy Let Thru 2018 RELT Reduced Energy Let Thru 2018 RELT Reduced Energy Let Thru Rick Schlobohm, P.E Senior Specification Engineer, There is an increasing concern in the electrical industry about arc flash energy levels

More information

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc Redundant Bus Protection Using High-Impedance Differential Relays Josh LaBlanc Purpose Discuss the configuration of the bus under study, and touch on the needs for redundant protection on the bus. Briefly

More information

Elastimold Molded Vacuum Recloser - MVR

Elastimold Molded Vacuum Recloser - MVR Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical

More information

When to use multi-function safety relays

When to use multi-function safety relays When to use multi-function safety relays In applications where single-function relays aren t capable enough and a safety-rated PLC is overkill, multi-function safety relays can be the best technology choice.

More information

KILOVAC WD Series, DIN Rail or Screw Mounted Protective Relays

KILOVAC WD Series, DIN Rail or Screw Mounted Protective Relays KILOVAC WD Series, DIN Rail or Screw Mounted Protective Relays n WD25 Paralleling (Synch Check) Relays n WD2759 Over/undervoltage Relays n WD32 Reverse Power Relays n WD47 Phase Sequence Relays n WD5051

More information

International Journal of Engineering Trends and Technology (IJETT) Volume 26 Number 2- August 2015

International Journal of Engineering Trends and Technology (IJETT) Volume 26 Number 2- August 2015 Microprocessor-Based Protective Applications in Nigeria Power System Protections J.O. Aibangbee #1, S.O. Onohaebi *2. # Department of Electrical &Computer Engineering, Bells University of Technology, Ota,

More information

An Innovative Approach to Implementing SCADA into the Industrial Environment

An Innovative Approach to Implementing SCADA into the Industrial Environment Feature An Innovative Approach to Implementing SCADA into the Industrial Environment by Lynn Hamrick and David Charles ESCO Energy Services ESCO Energy Services Company recently implemented a Supervisory,

More information

4. CIRCUIT BREAKERS. Functional Emergency Switching

4. CIRCUIT BREAKERS. Functional Emergency Switching 4. CIRCUIT BREAKERS The circuit breaker/disconnector fulfils all of the basic switchgear functions, while, by means of accessories, numerous other possibilities exist. As shown in table H2-19 the circuit

More information

Increasing Distribution Demands: 5 Benefits of Modular Substations

Increasing Distribution Demands: 5 Benefits of Modular Substations Increasing Distribution Demands: 5 Benefits of Modular Substations ACHILA JAYASURIYA, SUBSTATION ENGINEER Substations play a critical role in the power industry. They support the transmission grid in moving

More information

Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins

Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins Today's Moderator Ed Sulivan Editor Today's Presenter Steve Maling Director, US Field Services Marketing, Schneider

More information

2. Site Planning lists the prerequisites and physical requirements for installing the 289H M LSS monitor.

2. Site Planning lists the prerequisites and physical requirements for installing the 289H M LSS monitor. 289H M LSS Installation & Operations Manual Overview Section 1 INTRODUCTION This manual provides procedures for installing and operating the 289H M Loop Surveillance System (LSS) monitor. It addresses

More information

Instructions for Testing Magnum DS Trip Units Using PACB Test Kit Styles 87C0270G01-G03

Instructions for Testing Magnum DS Trip Units Using PACB Test Kit Styles 87C0270G01-G03 Instructions for ing Magnum DS Trip Units Contents Description Page 1: Introduction............................ 2 2: Kit / Breaker Information.............. 2 3: Kit Setup.......................... 3 4:

More information

INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS

INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS Konstantine Kolevatov, AS Tavrida Electric Export It has become a major task to provide uninterrupted electricity supply to customers and minimize the outage

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.

More information

BREAKER FAILURE PROTECTION

BREAKER FAILURE PROTECTION 0 th Annual HANDS-ON RELAY SCHOOL March 11-15, 201 REAKER FAILURE PROTECTION brent.c@relayapplication.com OUTLINE Protection System Failures and reaker Failures Protection versus Relaying Relay Schemes

More information

PRC Coordination of Protection Systems for Performance During Faults

PRC Coordination of Protection Systems for Performance During Faults PRC-027-1 Coordination of Protection Systems for Performance During Faults A. Introduction 1. Title: Coordination of Protection Systems for Performance During Faults 2. Number: PRC-027-1 3. Purpose: To

More information

SSV-T and SSC-T High Drop-out Relay. Range amps amps amps amps. Operating Frequency: Temperature Error:

SSV-T and SSC-T High Drop-out Relay. Range amps amps amps amps. Operating Frequency: Temperature Error: 41-766.7 SSV-T and SSC-T High Drop-out Relay device. A magnetic armature, to which leaf-spring mounted contacts are attached, is attracted to the magnetic core upon energization of the switch. When the

More information

GE Multilin 350 Feeder Protection Relay Specifications

GE Multilin 350 Feeder Protection Relay Specifications GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following

More information

Spectra RMS Circuit Breakers with microentelliguard Trip Units

Spectra RMS Circuit Breakers with microentelliguard Trip Units GE Energy Industrial Solutions Spectra RMS Circuit Breakers with microentelliguard Trip Units Greater system coordination, arc flash protection and reliability for new equipment and retrofit applications

More information

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold Tru-Break switchgear module Tru-Break switchgear module agenda Design platform and value Product specifications Operation Configuration examples

More information

Testing for the Unexpected Using PXI

Testing for the Unexpected Using PXI Testing for the Unexpected Using PXI An Automated Method of Injecting Faults for Engine Management Development By Shaun Fuller Pickering Interfaces Ltd. What will happen if a fault occurs in an automotive

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

MicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Westinghouse Power Circuit Breakers

MicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Westinghouse Power Circuit Breakers MicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Westinghouse Power Circuit Breakers Easily replace electro-mechanical trip units with the latest electronic, digital trip unit technology Ensure

More information

289H LSS Installation & Operations Manual Overview

289H LSS Installation & Operations Manual Overview 289H LSS Installation & Operations Manual Overview Chapter 1 INTRODUCTION This manual explains the procedures for installing and operating the 289H Loop Surveillance System (LSS). It addresses both new

More information

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators. SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering

More information

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

To: Honorable Public Utilities Board Submitted by: From: Diosdado Hernandez, P. E. Approved by:

To: Honorable Public Utilities Board Submitted by: From: Diosdado Hernandez, P. E. Approved by: AGENDA ITEM NO.: 4.F.1 ADMINISTRATIVE REPORT NO.: 2018-50 To: Honorable Public Utilities Board Submitted by: /S/ Andre Basler AGM Engineering and Operations From: Diosdado Hernandez, P. E. Approved by:

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II Reclosers Form 4C Microprocessor-Based Recloser Control KME4-88-1 (120V) and KME4-88-2 (240V) Analog Current Metering Accessory Design II Service Information S280-77-6 961015, 961016 Figure 1. Kyle KME4-88

More information

Lesson Learned Initiatives to Address and Reduce Misoperations

Lesson Learned Initiatives to Address and Reduce Misoperations Lesson Learned Initiatives to Address and Reduce Misoperations Primary Interest Groups Transmission Owners (TOs) Generator Owners (GOs) Problem Statement A registered entity experienced a high rate of

More information

PC-250B Solid State Vital Biased Code Following Track Relay

PC-250B Solid State Vital Biased Code Following Track Relay Union Switch & Signal Inc., an Ansaldo Signal company 1000 Technology Drive, Pittsburgh, PA 15219 645 Russell Street, Batesburg, SC 29006 SM 9268 PC-250B Solid State Vital Biased Code Following Track Relay

More information

Why is my AFCI tripping?

Why is my AFCI tripping? www.garyklinka.com Page 1 of 21 Instructions: Fee $25 1. Print these pages. 2. Use the included information located on pages 12-20 to answer the 61 questions below. 3. Circle the correct answers and transfer

More information

ABB Data Center Forum 2017

ABB Data Center Forum 2017 ABB DATA CENTER FORUM 2017, 11 TH JULY 2017 ABB Data Center Forum 2017 Perfecting Data Center availability with Ultra-Fast Protection Devices Barbara Schlegel ABB DATA CENTER FORUM 2017, 11 TH JULY 2017

More information

Voltage Dip-Proofing Inverter

Voltage Dip-Proofing Inverter Voltage Dip-Proofing Inverter DPI54S / 54L Series Models 120V & 208/230 50/60Hz Contents: Introduction...3 Theory of operation...3 Specifications...5 Up-time considerations...6 Installation Guide...7 Test

More information

Lessons Learned Implementing an IEC based Microgrid Power- Management System. K.A. GRAY, J.J. MRAZ* POWER Engineers, Inc.

Lessons Learned Implementing an IEC based Microgrid Power- Management System. K.A. GRAY, J.J. MRAZ* POWER Engineers, Inc. 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Lessons Learned Implementing an IEC 61850-based Microgrid Power- Management System K.A.

More information

It is the job of the protection system equipment to recognize and remove the fault.

It is the job of the protection system equipment to recognize and remove the fault. Protection 1 (read section 13.0 of text) 1.0 Introduction Faults do not occur that frequently 1/year/100 miles of transmission is typical. Distribution systems may see more than this. However, when they

More information

Energy Storage Systems Utilizing the SunDial Plus 30PV+S Inverter

Energy Storage Systems Utilizing the SunDial Plus 30PV+S Inverter APPLICATION NOTE 601 Energy Storage Systems Utilizing the SunDial Plus 30PV+S Inverter CONTENTS 1.0 Purpose and Scope.... 1 2.0 Disclaimer.... 1 3.0 Overall Energy Storage System... 1 4.0 Electrical Interfaces...

More information

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching 7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Switch rated 1000 Amperes in Type 1 enclosure. Closed Transition Switching Closed Transition Switches feature main contacts that

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

Installation Instructions

Installation Instructions Installation Instructions Cat. No. 1771 P3, P4, P5 and P5E Use this document as a guide when installing the catalog number 1771-P3, -P4, -P5 or -P5E power supplies. Because of the variety of uses for the

More information

MicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Allis Chalmers Power Circuit Breakers

MicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Allis Chalmers Power Circuit Breakers MicroVersaTrip Plus & MicroVersaTrip PM Conversion Kits for Allis Chalmers Power Circuit Breakers Easily replace electro-mechanical trip units with the latest electronic, digital trip unit technology Ensure

More information

MOUNTING BASE AQB-A402 PLAN VIEW OF MOUNTING BLOCK & CIRCUIT BREAKER AQB-A802 CIRCUIT BREAKER MOUNTING BLOCK 2.50 MOTOR OPERATOR 25.

MOUNTING BASE AQB-A402 PLAN VIEW OF MOUNTING BLOCK & CIRCUIT BREAKER AQB-A802 CIRCUIT BREAKER MOUNTING BLOCK 2.50 MOTOR OPERATOR 25. Weights & Dimensions 4 1/8 4 5/16 4 1/8 4 5/16 Weights & Dimensions 5 1/16 6 1/2 15 1/2 17 15/16 A C A C 6 3/16 MOUNTING ASE MOUNTING ASE 5 1/16 6 3/16 MOUNTING ASE DIMENSIONS DESCRIPTION A C SINGLE ASE,

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA SURGE PROTECTION DESIGN. Parallel Versus Series Protection. Surge protectors within the scope of this UFC should normally be of the parallel

More information

GE Power Management. Frequently Asked Questions:

GE Power Management. Frequently Asked Questions: ACR Are we still able to repair ACR relays in Anasco? The ACR reclosing relays have been obsolete for 2 years. We still can repair ACR relays subject to having all parts needed. PVD What are the Drop Out

More information

Source-Transfer Application Guide

Source-Transfer Application Guide S&C Model 6802 Automatic Switch Control Source-Transfer Application Guide Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this

More information

Substation SCADA Monitoring

Substation SCADA Monitoring Substation SCADA Monitoring Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Substations are a critical component

More information

NGRM700. Neutral Grounding Resistor Monitor

NGRM700. Neutral Grounding Resistor Monitor NGRM700 Neutral Grounding Resistor Monitor The better tool to monitor grounding resistors Are you concerned with the reliability of your system grounding? The NGRM700 is a sophisticated device that allows

More information

URC Utility Relay Company

URC Utility Relay Company communications i-comm modbus / rs-485 AC-PRO Communicating Trip Units instruction manual ZERO-Hertz Communicating Trip Units URC Utility Relay Company Chagrin Falls, OH 44023 Phone: 888.289.2864 www.utilityrelay.com

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

HydroGuard 4 to 20 ma Output Module. For use with HydroGuard Water Quality Monitor and Controller

HydroGuard 4 to 20 ma Output Module. For use with HydroGuard Water Quality Monitor and Controller HydroGuard 4 to 20 ma Output Module For use with HydroGuard Water Quality Monitor and Controller Technician's Manual Installation, Operation, and Maintenance Guide Chapter 1: Preface... 3 1.1 Intended

More information

Power System Protection with Relay Co-Ordination

Power System Protection with Relay Co-Ordination Power System Protection with Relay Co-Ordination Mehulkumar D. Devdhariya 1, Vibhuti R. Adroja 2, Kajal M. Rafaliya 3, Prof. Manan M. Desai 4 1,2,3 Students, B.E. in Electrical Engineering, 4 Assistant

More information

www. ElectricalPartManuals. com .Basler Electric BE1-878 HIGH IMPEDANCE BUS DIFFERENTIAL RELAY ADVANTAGES ADDITIONAL INFORMATION APPLICATION Page2

www. ElectricalPartManuals. com .Basler Electric BE1-878 HIGH IMPEDANCE BUS DIFFERENTIAL RELAY ADVANTAGES ADDITIONAL INFORMATION APPLICATION Page2 The Bus Differential Relay provides economical high speed protection in a conventional package for all high impedance differential applications. ADVANTAGES Proven performance of High Impedance Differential

More information

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD United States MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD Product Information Features and Specifications For Use With: OEM Panels Approvals: UL

More information

2012 Grid of the Future Symposium. Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation Program

2012 Grid of the Future Symposium. Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation Program 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

PUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System

PUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System PUBLIC SERVICE OF NEW HAMPSHIRE Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System September 2013 1.0 Purpose of this document Public Service of New Hampshire

More information

Switchgear Design Impacts the Reliability of Backup Power Systems

Switchgear Design Impacts the Reliability of Backup Power Systems Switchgear Design Impacts the Reliability of Backup Power Systems December 2010/AT307 by Reza Tajali, P.E. Square D Power Systems Engineering Make the most of your energy SM Revision #1 12/10 When a cascaded

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft

More information

DEH-433. Warnings, Cautions, and Notes as used in this publication

DEH-433. Warnings, Cautions, and Notes as used in this publication DEH-433 Warnings, Cautions, and Notes as used in this publication Warnings WARNING! Warning notices are used in this publication to emphasize that hazardous voltages, currents, or other conditions that

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

GE Entellisys Low Voltage Switchgear. System Test Kit. User Manual

GE Entellisys Low Voltage Switchgear. System Test Kit. User Manual GE Entellisys Low Voltage Switchgear System Test Kit User Manual DEH-233 Warnings, Cautions, and Notes as used in this publication Warnings WARNING! Warning notices are used in this publication to emphasize

More information

WHAT NEW TECHNOLOGIES AND DATA CAN DO FOR THE WATER INDUSTRY

WHAT NEW TECHNOLOGIES AND DATA CAN DO FOR THE WATER INDUSTRY WHAT NEW TECHNOLOGIES AND DATA CAN DO FOR THE WATER INDUSTRY Increase Quality and Safety of Products, and Improve Performance with New Technologies and Continuous Availability simplify and modernize automation

More information

ESD Monitoring, Ionization & Test. SmartLog V5. ESD Data Acquisition System. Rev Made in United States of America.

ESD Monitoring, Ionization & Test. SmartLog V5. ESD Data Acquisition System. Rev Made in United States of America. EMIT ESD Monitoring, Ionization & Test SmartLog V5 ESD Data Acquisition System Rev. 2013-05 Features and Benefits The patented* EMIT SmartLog V5 is designed for fast, frequent, and accurate testing of

More information

The Space-Time (and Cost) Continuum of Programmable Switches A Back to the Future Look at ROI By NKK Switches

The Space-Time (and Cost) Continuum of Programmable Switches A Back to the Future Look at ROI By NKK Switches The Space-Time (and Cost) Continuum of Programmable Switches A Back to the Future Look at ROI By NKK Switches When Marty McFly jumped into the DeLorean, Dr. Emmett Brown had already programmed the car

More information

Request publication Request publication DNP 3.0 INSTRUCTION MANUAL. Request publication

Request publication Request publication DNP 3.0 INSTRUCTION MANUAL. Request publication BE1-851 OVERCURRENT PROTECTION SYSTEM The BE1-851 is a multifunction, numeric relay that provides three phase, ground, and negative sequence overcurrent protection with four shot recloser, breaker failure,

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

Connecting a Cisco Output Module

Connecting a Cisco Output Module CHAPTER 5 Overview The optional Cisco Output Module (Figure 5-1) is attached to a Cisco Physical Access Gateway or Cisco Reader Module to provide additional connections for up to 8 outputs, each of which

More information

30-Cycle Rated Switchboards - Selectivity Tradeoffs

30-Cycle Rated Switchboards - Selectivity Tradeoffs 30-Cycle Rated Switchboards - Selectivity Tradeoffs By Rick Schlobohm, P.E. Senior Specification Engineer, Franklin Bohac, P.E. Specification Engineer, Increased focus on selective coordination has resulted

More information

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs SIPROTEC easy 7SJ4 Numerical Overcurrent Protection Relay Powered by CTs Function overview Fig. /1 Description The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended

More information

Power systems 5: Protection

Power systems 5: Protection Power systems 5: Protection Introduction In this series of articles, we will be looking at each of the main stages of the electrical power system in turn. As you will recall from our Introduction to Electrical

More information

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D.

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D. Electrical Integration of PV Systems Ridha Hamidi, Ph.D. 1 Many articles in the NEC are applicable to the electrical integration of a PV system, particularly Article 690. 2 The NEC defines the various

More information

Catalog. Arc Guard System TM TVOC-2

Catalog. Arc Guard System TM TVOC-2 Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already

More information