30-Cycle Rated Switchboards - Selectivity Tradeoffs

Size: px
Start display at page:

Download "30-Cycle Rated Switchboards - Selectivity Tradeoffs"

Transcription

1 30-Cycle Rated Switchboards - Selectivity Tradeoffs By Rick Schlobohm, P.E. Senior Specification Engineer, Franklin Bohac, P.E. Specification Engineer, Increased focus on selective coordination has resulted due to requirements in the 2005 and 2008 editions of the National Electrical Code (NEC). These requirements, which focus on emergency systems (NEC Article 700), legally required standby systems (NEC Article 701), and Critical Operation Power Systems (NEC Article 708), have also led the electrical designer to pursue selective coordination for many other electrical systems. This paper will attempt to define and address the need for 30-cycle withstand ratings for distribution equipment, not only for low voltage switchgear, but also for low voltage switchboards when instantaneous selective coordination is specified. This paper will also address the consequences, such as increased arc flash hazard categories, that occur when a system is designed to achieve complete selective overcurrent protection through the instantaneous range. What is Selective Coordination? The NEC in Article 100 defines selective coordination as the localization of an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished by the choice of overcurrent protective devices and their ratings or settings. A system designed to be selectively coordinated simply implies that the overcurrent device closest to a fault or overload will open the circuit before any upstream overcurrent device. An important aspect, which must be considered when designing and specifying a selectively coordinated distribution system, is the minimum time level for which selective coordination needs to be maintained and the maximum fault level at each piece of equipment in the system. The two most common time levels specified for selectively coordinated systems are 0.01 seconds and 0.1 seconds. The NEC Articles , , or do not provide a definition for selective coordination and do not indicate a preference for one or the other common selectivity levels. This NEC selectivity requirement is generally, but not always, interpreted as meaning that selective coordination must extend throughout the instantaneous region (0.01 seconds) of the device s trip curve. Other standards such as Florida s Agency for Health Care Administration (AHCA) mandates selective coordination for time delays beginning at 0.1 seconds. The 0.1 second standard has been adopted by many other authorities having jurisdiction (AHJ) and is considered a good engineering compromise between the benefits of selective coordination and the associated increase of arc flash hazard levels resulting from the time delays needed to achieve complete selectivity among overcurrent devices. The 0.1 second standard will allow some overlap in the time bands for the devices in the instantaneous time region. These overlaps will occur at the higher fault levels. One item to understand in the selectivity discussion is the fact that even though the main device and feeder device both have an instantaneous trip function and their time bands overlap at high fault levels, they are selective up to the point of minimum instantaneous pickup for the upstream device (Reference Point A in Figure TCC-1). Even though the instantaneous time bands overlap for fault levels above Point A, the system is fully selective for faults and overloads below that level. Traditional switchboards and other distribution equipment can be utilized in designing to 0.1 second selective coordination if care is taken in the selection and adjustment of the overcurrent protective devices.

2 When instantaneous selective coordination for the main distribution equipment is desired for time levels of 0.01 second and greater, selectivity is easily achieved throughout this instantaneous range by using conventional low voltage switchgear. This is accomplished by utilizing main devices without an instantaneous trip function. This feature is also available in some vendor s switchboards, but the switchboards must be provided with internal bus that is braced for the available fault current for 30-cycles and not just the 3-cycles as defined in the UL 891 standard for switchboards. Without an instantaneous trip to isolate severe faults to a 3 cycle total clearing time, the bus withstand needs to be rated for 30-cycles. This is the maximum time delay permitted by the adjustment ranges of short-time and ground fault protection provided on fully adjustable UL 1066/ANSI rated low voltage power circuit breakers (LVPCB). When designing a project for selectivity, more thought and planning may be required to ensure selectivity throughout the distribution system in addition to the protective devices at the main distribution equipment. While perfect selectivity through the instantaneous range may be attained using ANSI rated switchgear for the main equipment, the switchgear feeder breakers may not be as selective with downstream molded case breakers as would be desired, or the large frame size may force the designer to add another level of overcurrent devices which would hamper the overall selective coordination of the system. Switchboards are available to achieve instantaneous selectivity with a low voltage power circuit breakers (LVPCB) main not utilizing an instantaneous trip function. These switchboards offer the designer the ability to have switchboard mounted feeder breakers utilizing molded case breakers. Many of these molded case breakers will provide selective coordination into the instantaneous range to higher fault values than can be obtained with breakers rated to the ANSI standards. The use of molded case breakers in the main distribution equipment as feeders can eliminate a layer of overcurrent devices that could be difficult to selectively coordinate. What is a 30-Cycle Withstand Rating? This term can be simply defined as the ability of the distribution equipment to withstand the mechanical and thermal stresses associated with a rated fault, for a time period of 30-cycles (0.5 seconds). The 30-cycle withstand rating has long been a requirement of low voltage switchgear designed and tested to the ANSI C standard and labeled to the UL 1558 standard. Switchgear short circuit ratings per these standards are based on two 30-cycle withstand tests with a 15-second interval in between tests performed at 15% power factor at 635VAC maximum. Switchboards however are only required to pass a single 3-cycle (0.05 second) short circuit test at 20% power factor and 600VAC maximum. Switchboards standards of UL 891 and NEMA PB-2 do not include requirements or testing procedures for a withstand test greater than 3-cycles since the circuit breakers used in these switchboards are UL 489 listed and all have an instantaneous trip function. With an instantaneous trip function, the breaker is expected to open within 3-cycles to prevent catastrophic damage to the distribution equipment. Figure TCC-2 references the 30-cycle time period (0.5 seconds) by Point B and the 3-cycle time period (0.05 seconds) by Point C. Even though UL 891 does not address a 30-cycle withstand rating, there are UL 891 listed switchboards available with this higher duration withstand rating. These switchboards are tested to the ANSI test standards and are witnessed by UL and thus can be labeled as suitable for applications requiring a 30-cycle withstand rating.

3 When is a 30-Cycle Withstand Rating required? As mentioned previously, the 30-cycle withstand rating is required for some equipment by the standards for which they are designed and tested. The reason the ANSI standards for switchgear require the 30-cycle withstand rating is that this equipment is designed to accept UL 1066/ANSI C37 circuit breakers which are not required to have an instantaneous trip function. This is why any overcurrent device mounted in a traditional UL 891 switchboard with a 3-cycle withstand rating must have an instantaneous trip. Figures TCC-1 and TCC-2 below show typical time current curves for a main and feeder device. Figure TCC-1 shows a 4000A insulated case circuit breaker (ICCB) main and 1200A molded case circuit breaker (MCCB) feeder both with instantaneous trips. Figure TCC-2 shows the same main and feeder devices, however the main is now a low voltage power circuit breaker (LVPCB) without an instantaneous trip. In figure TCC-1 you can see that the main device will detect the faults greater than 33,000A at 0.01 seconds and due to the mechanical function of the breaker, will clear these faults within 3-cycles. In figure TCC-2 the same fault will continue until cleared by the short time function of the main device which will initiate breaker tripping in about 25-cycles (0.416 seconds) after the short-time pickup has been exceeded. Main 2 requires a switchboard with the 30-cycle withstand rating while Main 1 does not. CURRENT IN AMPERES CURRENT IN AMPERES ComponentName MAIN-1 PowerBreak II, EGTU SS Trip A Plug A LTPU/LTD (0.5-1 x In) 0.50X (2000A); Min CB STPU (1.5-9 x LTPU) 1.5X (3000A) STD (ST01 - ST11) ST02-Min (I^2t Out) INST (2-9 x In) 9X (36000A) Override (HSIOC) Fixed (50200A) MAIN MAIN-2 ComponentName MAIN-2 WavePro, EGTU WPS-40 Trip A Plug A LTPU/LTD (0.5-1 x In) 0.50X (2000A); C-1 STPU (1.5-9 x LTPU) 2X (4000A) STD (ST01 - ST11) ST11-Min (I^2t Out) 10 1 ComponentName FDR-1 SK, MVT Plus/PM SKL Trip A Plug A LTPU ( x P) 0.5 (600A) LTD (1-4) 1 STPU (1.5-9 x LTPU) 1.5 (900A) STD (1-4) 1 (I^2t Out) INST ( x P) 1.5 (1800A) FDR-1 TIME IN SECONDS B 10 1 FDR-2 ComponentName FDR-2 SK, MVT Plus/PM SKL Trip A Plug A LTPU ( x P) 0.5 (600A) LTD (1-4) 1 STPU (1.5-9 x LTPU) 1.5 (900A) STD (1-4) 1 (I^2t Out) INST ( x P) 1.5 (1800A) TIME IN SECONDS 0.10 C K 10K 100K SWBD-1.tcc Ref. Voltage: 480V Current in Amps x 1 SWBD-1.drw Figure TCC-1 A K 10K 100K SWBD-2.tcc Ref. Voltage: 480V Current in Amps x 1 SWBD-2.drw Figure TCC-2

4 There are UL 489 listed breakers available on the market that are advertised with switchable instantaneous trip functions. When many of these breakers are investigated, the switchable function does not switch the instantaneous off, but simply increases the instantaneous pickup to a fixed high level setting. The reason these breakers are capable of being provided in a traditional UL 891 switchboard with only a 3-cycle fault withstand rating is that they continue to retain an instantaneous trip function. Breakers available without an instantaneous trip function are not listed to UL 489, but rather are low voltage power circuit breakers listed to UL 1066 and built per the standards of ANSI C37. These true UL 1066/ANSI rated low voltage power circuit breakers are available in Spectra and PowerBreak switchboards as main devices without instantaneous trip functions when these switchboards are provided with a 30-cycle withstand rating to accommodate these breakers. If the designer of an electrical system chooses to achieve the 0.01 second selectivity by eliminating the instantaneous function on the main device, he can choose to use UL 891 switchboards that are tested for a 30-cycle withstand. However, the designer must be aware of consequences of an increased arc flash hazard that is present with this design approach. How does meeting selectivity affect Arc Flash Hazard risk categories? The awareness of arc flash hazards has made tremendous strides in recent years. The standard for electrical safety in the workplace started in the 1970s when OSHA asked the NFPA to create a standard. This standard became NFPA 70E. Awareness in the general industry started increasing when the 2002 edition of the NEC was published requiring arc flash warning labels on equipment that was likely to be worked on or maintained while energized. Around the same time IEEE 1584 was published which provided calculations to quantify arc flash thermal energy release and the aid in the determination of appropriate personal protective equipment (PPE) to protect workers from arc flash. While this paper is not intended to be a tutorial on arc flash, there are a few facts that must be remembered. An arc flash is a violent event which releases thermal and mechanical energy from an arc, which can be as hot as the sun s surface and can vaporize copper to 67,000 times its solid volume propelling from the incident area through a pressure wave with deafening sound. An arc flash energy magnitude is determined by the magnitude of the current in the arc, the time to clear the arc, and the distance of the worker from that arc, in addition to other variables which are not under the control of the designer. The hazard risk categories for personal protective equipment (PPE) are certified for the level of heat energy applied over a given area to allow the worker to survive the incident with no worse than curable (second degree) burns on his torso. Looking back at our examples in Figure TCC-1 and TCC-2 which show how removing the instantaneous trip function on the main can increase selectivity, we will now look at arc flash hazard categories for each of these main versus feeder protection schemes. For the simple system shown in Figure TCC-1 with a 4000A main with an instantaneous trip in a UL 489 switchboard and an available fault current of 65kA the arc flash level is calculated to 14 cal/cm², which would be within the capabilities of Category 3 PPE. Category 3 PPE consists of cotton underwear, flame resistant (FR) shirt and pant and flame resistant (FR) coveralls. This same piece of equipment shown in Figure TCC-2 designed for instantaneous selectivity (0.01 second) with a main device without instantaneous trip protection would have an arc flash level of 73 cal/cm² which exceeds the capabilities of all hazard risk categories. There is no appropriate PPE recommended by NFPA 70E for arc flash energies that exceed 40 cal/cm², because the blast effects of arc flash are a bigger

5 concern than the thermal effects and there is no recognized protection against the blast effects of an arc flash for these high levels. Reference Figures AFL-1 and AFL-2 for respective Arc Flash and Shock Hazard equipment labels for the examples in TCC-1 and TCC-2. The electrical designer now has a tough decision to make with regard to the need for instantaneous selectivity and the corresponding increase in the arc flash hazard category for the equipment. The scenario presented in the example of TCC-2 and AFL-2 utilized a switchboard with a 30 cycle bus withstand rating, an ANSI rated main circuit breaker without instantaneous and a molded case circuit breaker feeder rated at 1200A. Many designers would consider true ANSI rated switchgear construction for this type of application instead of a rated and tested switchboard. Using switchgear does not necessarily solve the selectivity or the arc flash hazard risks. Most circuit breaker manufacturers have published tables and guidelines that list the various combinations of overcurrent protection devices whose instantaneous trips have been found to be selective with each other along with the corresponding maximum fault values for which the combinations achieve instantaneous selectivity. Many of the combinations require the use of molded case feeders because the same level of selectivity is not achieved with the ANSI rated devices. Using switchgear could hinder the ability to selectively coordinate the downstream combination of devices. The arc flash incident energy will be different when switchgear is applied due to the difference in the input data used in the calculations for low voltage switchgear versus switchboards. The gap measurement (conductor phase spacing gaps) used for switchboard construction is 25mm but increases to 32mm for switchgear. The working distance measurement used in the calculations also is different between the equipment types. For switchboards the input data is 18 while for switchgear the data used is 24. While these differences in input data for the different types of equipment do change the calculated incident energy, the low voltage switchgear does not present a lower hazard risk category. The incident energy available when utilizing switchgear in lieu of a switchboard for the scenario presented in TCC-2 is 43 cal/cm². This value is still greater than the thermal energy rating of Category 4 PPE and so no suitable PPE is available. The electrical designer has options, but must weigh the benefits of instantaneous selectivity with corresponding arc flash hazards of each design option. Figure AFL-1 Figure AFL-2

6 What does this all mean? When an electrical designer makes a decision to have a selectively coordinated system, he must first decide what level of selectivity is required. If selectivity is desired beginning at 0.1 seconds, then traditional switchboards can be utilized with careful selection and specification of the overcurrent protective devices. If the design requires selectivity through the instantaneous range beginning at 0.01 seconds, the designer must then be aware of requirements in equipment selection when the instantaneous trip function is eliminated for the main device. If the main device does not have an instantaneous trip function, a 30-cycle withstand rating must be specified for the distribution equipment. With true 30 cycle rated switchboards now available, the designer is not required to specify ANSI rated switchgear to apply main breakers without instantaneous trips. One must also consider the safety aspects of the design and the corresponding differences in arc flash hazard categories for the various types of distribution equipment to be utilized for the project. The designer must work with the owner, architect and AHJ and make them aware of the consequences of the deign criteria. They should work as a team to provide the best compromise between the benefits of selective coordination and arc flash safety hazards that increase with some designs.

RELT Reduced Energy Let Thru 2018

RELT Reduced Energy Let Thru 2018 RELT Reduced Energy Let Thru 2018 RELT Reduced Energy Let Thru Rick Schlobohm, P.E Senior Specification Engineer, There is an increasing concern in the electrical industry about arc flash energy levels

More information

GE Energy Industrial Solutions. GE Overcurrent Device Instantaneous Selectivity Tables

GE Energy Industrial Solutions. GE Overcurrent Device Instantaneous Selectivity Tables GE Energy Industrial Solutions GE Overcurrent Device Instantaneous Selectivity Tables Contents Introduction...3 Selectivity with EntelliGuard TU and microentelliguard EntelliGuard TU Trip Units in ANSI

More information

Dynamic Arc Flash Reduction System

Dynamic Arc Flash Reduction System www.usa.siemens.com/mcc Dynamic Arc Flash Reduction System and its application in motor control centers White Paper Author: Pablo Medina Product Manager, tiastar MCC Executive Summary The risk of Arc Flash

More information

Siemens Dynamic Arc Flash Reduction System and its application in motor control centers

Siemens Dynamic Arc Flash Reduction System and its application in motor control centers Siemens Dynamic Arc Flash Reduction System and its application in motor control centers www.sea.siemens.com www.usa.siemens.com/mcc Prepared by Mike Sachau, Product Engineer The risk of Arc Flash is a

More information

Mitigating Arc Flash Hazards

Mitigating Arc Flash Hazards 1910DB1402 / March, 2015 by Antony Parsons, Ph.D., P.E. and Reza Tajali, P.E. Schneider Electric Engineering Services Make the most of your energy SM Contents 1.0 Introduction... 3 2.0 What is Arc Flash

More information

2008 Code Changes for Power Distribution

2008 Code Changes for Power Distribution 2008 Schaedler Yesco Expo 2008 Code Changes for Power Distribution April 17, 2008 / Version 1.0 For internal use only / Copyright Siemens AG 2007. 2008. All rights reserved. Contact Consulting Account

More information

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL SECTION 26 05 73 1.1 SUMMARY OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL A. This Section includes the following: 1. Requirements for computer-based, fault-current and overcurrent

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE PART 1 - GENERAL 1.1 SUMMARY A. Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices

More information

POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT

POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT 26 05 73 POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT Delete the following current section in its entirety (deletions are shown struck through)..01 General A. Short circuit Studies,

More information

UL 508 A standard-compliant design of industrial control panel

UL 508 A standard-compliant design of industrial control panel UL 508 A standard-compliant design of industrial control panel Axel Jöhnke System Architecture Expert 14-15 SEPTEMBER 2011, MUNICH Agenda www.infoplc.net Origin and Comprehension Organizations Certificates

More information

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1. Coordination of series-rated devices is permitted where indicated on Drawings. SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing Understanding SCCR What is SCCR? When it comes to industrial machinery, it s critical to ensure that electrical panels are designed and built with the proper SCCR to maintain the system, eliminate downtime

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Supersedes June 2017 FAZ-NA-L FAZ-NA FAZ Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers three types of miniature circuit breakers for use in North

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Product Application AP01102005E WMZT WMZS Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers two types of miniature circuit breakers for use in North

More information

Thermal and Arc Flash Analysis of Electric Motor Drives in Distribution Networks

Thermal and Arc Flash Analysis of Electric Motor Drives in Distribution Networks Thermal and Flash Analysis of Electric Motor Drives in Distribution Networks Srete Nikolovski Josip Juraj Strossmayer University of Osijek, Faculty of Electrical Engineering, Computer Science and Information

More information

Spectra RMS Circuit Breakers with microentelliguard Trip Units

Spectra RMS Circuit Breakers with microentelliguard Trip Units GE Energy Industrial Solutions Spectra RMS Circuit Breakers with microentelliguard Trip Units Greater system coordination, arc flash protection and reliability for new equipment and retrofit applications

More information

SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT

SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT ESTABLISHED SINCE 1985 Circuit Breaker Solid State Controls with RMS-2007AF LOGIC (All logics come with ARC FLASH as a standard) The SURE TRIP SOLID STATE

More information

EntelliGuard* G Circuit Breakers Application Guide

EntelliGuard* G Circuit Breakers Application Guide GE Industrial Solutions EntelliGuard* G Circuit Breakers Application Guide Now with the following new features: New optimized dimension at 4000A Envelope 3, 200KAIC, @ 480V rating DET-653E EntelliGuard

More information

GE Energy Industrial Solutions. Entellisys 4.5. Low-Voltage Switchgear Application Guide

GE Energy Industrial Solutions. Entellisys 4.5. Low-Voltage Switchgear Application Guide GE Energy Industrial Solutions Entellisys 4.5 Low-Voltage Switchgear Application Guide Contents Section Page 1 Introduction 1 2 General Description 3 3 System Architecture 5 4 Minimizing Potential Exposure

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

2014 NEC Code Changes. Code changes based on the 2014 NEC

2014 NEC Code Changes. Code changes based on the 2014 NEC 2014 NEC Code Changes Code changes based on the 2014 NEC Table of contents Overview Coordination What you ll find in this handbook... 3 517.30(G) Coordination Article 517 Healthcare facilities Part III

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable options

More information

EntelliGuard* G Circuit Breakers Don t compromise arc flash protection for system reliability.

EntelliGuard* G Circuit Breakers Don t compromise arc flash protection for system reliability. GE Energy Management EntelliGuard* G Circuit Breakers Don t compromise arc flash protection for system reliability. The next chapter in the history of low-voltage circuit breakers EntelliGuard* G circuit

More information

PRODUCT BROCHURE. Deploying effective power protection in data centers

PRODUCT BROCHURE. Deploying effective power protection in data centers PRODUCT BROCHURE Deploying effective power protection in data centers 2 D E P L OY I N G E F F E C T I V E P O W E R P R O T E C T I O N I N D ATA C E N T E R S The following document was written to serve

More information

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality,

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality, integrity, and innovation. Our mission is to offer the safest,

More information

Best practices for making switchgear safer.

Best practices for making switchgear safer. Best practices for making switchgear safer. www.sea.siemens.com www.usa.siemens.com/switchgear Prepared by: Ken Newsome - Consulting Business Developer Kevin Mullins - Consulting Business Developer Joe

More information

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service

More information

Certification Exams. Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician

Certification Exams. Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician Certification Exams How to Use the Detailed Content Outlines These Detailed

More information

Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades

Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades May 2012 / 1910DB1202 by Hal Theobald, Product Manager, Schneider Electric Services and Reza Tajali, P.E.,

More information

White Paper Surge Protective Devices in Automatic Transfer Switches

White Paper Surge Protective Devices in Automatic Transfer Switches White Paper Surge Protective Devices in Automatic Transfer Switches Standby power systems provide emergency power, legally required power, or optional standby AC power during utility outages. Standby AC

More information

Contractor to provide a draft and final power study report to be reviewed by the Engineer.

Contractor to provide a draft and final power study report to be reviewed by the Engineer. ADDENDUM NO. 3 PROJECT: Penticton Advanced Waste Water Treatment PAGE: of 3 Plant MCC- Upgrade DATE: March, -TENDER MCC- UPGRADE PROJECT NO.: 579 CONTRACT NO.: DISTRIBUTION: OWNER: City of Penticton Owner

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

Impact of Proposed IEEE 1584 Empirical Model in Comparison to Existing Arc-Flash Hazard Assessment Calculation Methods

Impact of Proposed IEEE 1584 Empirical Model in Comparison to Existing Arc-Flash Hazard Assessment Calculation Methods Impact of Proposed IEEE 1584 Empirical Model in Comparison to Existing Arc-Flash Hazard Assessment Calculation Methods Justin McCann P.E., MidSouth Utility Consultants Inc. Joseph Johnson, MidSouth Utility

More information

Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability

Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability 1910DB1207 By Hal Theobald, Product Marketing Manager, Schneider Electric Services Summary 1.0 Abstract...3 2.0 Introduction...3

More information

Integrating Monitoring and Diagnostic Equipment on Aging Transformers

Integrating Monitoring and Diagnostic Equipment on Aging Transformers May 13-14, 2008 International Centre, Mississauga, Ontario April 2008 Volume 20, No. 3 Integrating Monitoring and Diagnostic Equipment on Aging Transformers Valuable information on maintaining critical

More information

Equipment Short-Circuit Current Rating and Available Fault Current

Equipment Short-Circuit Current Rating and Available Fault Current Equipment Short-Circuit Current Rating and Available Fault Current Dan Neeser Field Application Engineer Eaton s Bussmann Business Dan.Neeser@CooperIndustries.com Agenda Interrupting Rating & Series Rating

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY The BE1-51 Series of Time Overcurrent Relays is microprocessor-based to provide versatile overload and fault protection on 50Hz or 60Hz systems. ADVANTAGES

More information

Zone-Selective Interlocking Field Testing and Commissioning

Zone-Selective Interlocking Field Testing and Commissioning GE Energy Connections DEH-583 Instruction Guide Zone-Selective Interlocking Field Testing and Commissioning For EntelliGuard* and microentelliguard* Trip Units 2 Table of Contents 1. Overview... 4 2. ZSI

More information

Page 1 of 149 First Revision No. 50-NFPA 79-2012 [ Global Input ] Delete the parenthetical terms used to describe IEC terms that follow terms used in NFPA 79 such as "protective bonding". Add information

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

s July 2006 T e c h n i c a l

s July 2006 T e c h n i c a l s July 2006 T e c h n i c a l J o u r n a l. Selective Trip Coordination with Modern Molded Case Circuit Breakers Electrical System Design. The electrical distribution system designer must consider many

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM> SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Best practices for making switchgear safer

Best practices for making switchgear safer Best practices for making switchgear safer White Paper Introduction What could be more important than protecting the safety of our most valuable assets, our people? Today s workers hold the keys to an

More information

Industries. Switchgear Interlock Applications. Process safety Control. Power Distribution Power Generation Power Transmission.

Industries. Switchgear Interlock Applications. Process safety Control. Power Distribution Power Generation Power Transmission. Switchgear Interlock Applications Data Sheet Industries Power Distribution Power Generation Power Transmission Type DM Access Interlock with Spring Bolt Type PPS Interlock Quick-Trip ARC Flash Reduction

More information

Quick Start Guide TS 870 ATS

Quick Start Guide TS 870 ATS Quick Start Guide TS 870 ATS 100A - 800A (with TSC 900 Controller) DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

NEMA Standards Publication AB Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers

NEMA Standards Publication AB Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers NEMA Standards Publication AB 5-2011 Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers Published by: National Electrical Manufacturers Association 1300 North 17th Street, Suite

More information

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units. Model KEP Automatic Transfer Switches Service Entrance Rated Controller D Decision-Makerr MPAC 1500 Ratings Power Switching Device Molded case (MCCB) Insulated Case (ICCB) Current Voltage, Frequency 200

More information

920 Remote Control (RC) Switches

920 Remote Control (RC) Switches 920 Remote Control (RC) Switches ASCO is the global leader in power switching and controls ASCO 920 PRODUCT SPECIFICATIONS SWITCH ONLY (PANELBOARD MOUNTING) 1,2,3 () DIMENSIONS, IN.(MM) WIDTH HEIGHT DEPTH

More information

Panelboard and switchboards series rating information manual

Panelboard and switchboards series rating information manual Information Manual 1C96944H02 Effective April 2014 Supersedes March 2011 Panelboard and switchboards series rating information manual Play it safe...read this manual! Panelboard and Effective: April 2014

More information

E-Series General Specifications

E-Series General Specifications -Series General Specifications Ideally suited for higher amperage applications. Available with front and back mounting, screw terminals, stud terminals and heavy duty box wire connectors for solid wire

More information

Refurbishment of Switchgear and Switchgear Devices

Refurbishment of Switchgear and Switchgear Devices White Paper Refurbishment of Switchgear and Switchgear Devices Low and Medium Voltage Products Introduction There are many suppliers who suggest to users that switchgear assemblies, circuit breakers, and

More information

Product Brochure. Series 70 erpp-fs. Web-Enabled Remote Power Panel

Product Brochure. Series 70 erpp-fs. Web-Enabled Remote Power Panel Product Brochure Series 70 erpp-fs Web-Enabled Remote Power Panel erpps Remote Power Panel Purpose Increase Reliability and Safety In Two Ways With erpp Remote Power Panels Reliability Increase #1: Finger

More information

White Paper. UL Standards for Power Control System Equipment

White Paper. UL Standards for Power Control System Equipment White Paper UL Standards for Power Control System Equipment UL Standards for Power Control System Equipment An Introduction to UL 891 and UL 1558 Commercially available Power Controls Systems (PCS) can

More information

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Figure.1 Altech s three new series deliver multiple capabilities. In all three series, ground fault sensitivity levels range

More information

Section 4 Ground-Fault Protection Devices

Section 4 Ground-Fault Protection Devices Multi 9 System Catalog Section 4Ground-Fault Protection Devices Section 4Ground-Fault Protection Devices Selection Table The Multi 9 System includes one UL Listed and three IEC rated product families that

More information

2 ms arc-flash protection and feeder relay in one platform

2 ms arc-flash protection and feeder relay in one platform Feeder Protection Relay 2 ms arc-flash protection and feeder relay in one platform Combine light sensor inputs with high-speed overcurrent protection to achieve secure arc-flash protection in as fast as

More information

ASCO 920 Remote Control (RC) Switches

ASCO 920 Remote Control (RC) Switches Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder disconnect switch for load capacities

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

AIR COOLED MODULAR RECTIFIER

AIR COOLED MODULAR RECTIFIER CONTROLLED POWER COMPANY SPECIFICATIONS AIR COOLED MODULAR RECTIFIER Spc1800a1 5JAN1999 SPECIFICATION S-1800-A MODULAR (REMOVABLE AND NON-REMOVABLE MODULES) AIR COOLED RECTIFIER Standard output power range:

More information

PRODUCT BROCHURE. Cyberex Remote Power Panel (RPP) Power distribution system

PRODUCT BROCHURE. Cyberex Remote Power Panel (RPP) Power distribution system PRODUCT BROCHURE Cyberex Remote Power Panel (RPP) Power distribution system 2 CYBEREX RPP POWER DISTRIBUTION REMOTE POWER PANEL Cyberex power distribution Remote Power Panel (RPP) With constantly evolving

More information

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017 APPLICATION CONTROL GUIDELINES IntelliROL Power Supply PN 1176718 Revision Date: March 15, 2017 Table of Contents List of Tables...3 TGW Safety Recommendation...4 Warnings and Safety Instructions...5 Introduction...6

More information

BSPD Surge Protective Devices

BSPD Surge Protective Devices BUSSMANN Supersedes December 2016 SERIES BSPD Surge Protective Devices High capacity Type 1 and Type 2 SPDs for overvoltage protection on Contents Description Page Introduction 2 Applications 2 Features

More information

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI)

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI) GROUND FAULT CIRCUIT INTERRUPTERS Wiring design and protection. - 1926.404 Our company uses ground fault circuit

More information

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches Series 300 Power Transfer Switches Maximum Reliability & Excellent Value With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually

More information

I-Line Panelboards. Innovative design, smart bus technology, and simple installation

I-Line Panelboards. Innovative design, smart bus technology, and simple installation I-Line Panelboards Innovative design, smart bus technology, and simple installation TM Smart: designed for efficient installation Simple: Efficient Installation Process I-Line Breakers Main Lugs: Fixed-mounted

More information

Power System Protection Training

Power System Protection Training Power System Protection Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Refresh your knowledge of

More information

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements Introduction to Bus Protection By Matt Horvath, P.E. November 6, 2018 Electrical Buses Physical and Electrical Junction A bus is a critical element of a power system, as it is the point of convergence

More information

UL 508A Industrial Control Panels Eaton. All Rights Reserved.

UL 508A Industrial Control Panels Eaton. All Rights Reserved. UL 508A Industrial Control Panels Objectives Who is UL? UL508A Origin Current emphasis on UL508A What is the UL 508A Standard? Implementation of the Standard Component Selection Short Circuit Current Ratings

More information

Electrical Plan Review

Electrical Plan Review Electrical Plan Review Overcurrent Protection and Devices, Short-Circuit Calculations, Component Protection, Selective Coordination, and Other Considerations Table of Contents Part I: Overcurrent Protection

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 26 24 11 This section specifies the furnishing, installation, and connection of the distribution switchboards. 1.2 RELATED WORK: A. Section 13 05 41, SEISMIC RESTRAINT

More information

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview Supplementary Protectors / Miniature Circuit Breakers Page System overview 10/003 10/001 Supplementary protectors

More information

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units. Model KEP Automatic Transfer Switches Service Entrance Rated Controller D Decision-Makerr MPAC 1500 Ratings Power Switching Device Current Voltage, Frequency Molded case (MCCB) Insulated Case (ICCB) 200

More information

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE IMPORTANT! Please read all the information on this sheet. SAVE THESE INSTRUCTIONS! NOTICE BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL

More information

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES BE1-50/51M TIME OVERCURRENT RELAY The BE1-50/51M Time Overcurrent Relay provides economical overload and fault protection for generators, transformers, lines and motors. ADVANTAGES Self powered from 50/60Hz

More information

R-LB R-LX Series Installation, Operation & Maintenance Manual

R-LB R-LX Series Installation, Operation & Maintenance Manual Installation, Operation & Maintenance Manual WARNINGS Safety First Hazardous Voltage & Shock Hazard Only qualified licensed electricians should install or service SPDs Hazardous voltages exist within SPDs

More information

A. Operation and Maintenance Data: For the overcurrent protective devices to include in emergency, operation, and maintenance manuals.

A. Operation and Maintenance Data: For the overcurrent protective devices to include in emergency, operation, and maintenance manuals. 1.5 INFORMATIONAL SUBMITTALS A. Product Certificates: For overcurrent protective device coordination study software, certifying compliance with IEEE 399. 1.6 CLOSEOUT SUBMITTALS A. Operation and Maintenance

More information

SECTION 16496E ATS MOLDED CASE WITH ATC 900 CONTROLLER

SECTION 16496E ATS MOLDED CASE WITH ATC 900 CONTROLLER ATS MOLDED CASE WITH ATC 900 CONTROLLER PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install the low voltage automatic transfer switches having the ratings, features/accessories and enclosures as specified

More information

In the simplest terms, surge protective devices (SPDs) prevent damaging transient voltage surge levels from reaching the devices they protect.

In the simplest terms, surge protective devices (SPDs) prevent damaging transient voltage surge levels from reaching the devices they protect. How SPDs Work In the simplest terms, surge protective devices (SPDs) prevent damaging transient voltage surge levels from reaching the devices they protect. A useful analogy makes this clearer. Consider

More information

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH)

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH) Surge-Trap STZ-R series Surge Protective Device (SPD) Danger Hazard of Electrical Shock, Explosion or Arc Flash Only qualified licensed electricians should install or service SPDs Verify that all power

More information

ARC-FLASH INCIDENT ENERGY REDUCTION USING ZONE SELECTIVE INTERLOCKING

ARC-FLASH INCIDENT ENERGY REDUCTION USING ZONE SELECTIVE INTERLOCKING ARC-FLASH INCIDENT ENERGY REDUCTION USING ZONE SELECTIVE INTERLOCKING Copyright Material IEEE Paper No. PCIC-2007-XX Donna Lee Hodgson David Shipp Shell Exploration and Production Co. Eaton Electrical

More information

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/ Symmetra PX 160 Maintenance Bypass Enclosure Installation 05/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

Product brochure. Cyberex. Remote Power Panel (RPP) Power distribution system

Product brochure. Cyberex. Remote Power Panel (RPP) Power distribution system Product brochure Cyberex Remote Power Panel (RPP) Power distribution system Cyberex power distribution Remote power panel (RPP) With constantly evolving demands and the increasing need to store critical

More information

Enabling a Solid State Circuit Breaker

Enabling a Solid State Circuit Breaker Enabling a Solid State Circuit Breaker USING SOLID-STATE CIRCUIT BREAKERS TO REVOLUTIONIZE POWER DISTRIBUTION Mike Harris Atom Power, Inc. Copyright 2019 Atom Power, Inc. All rights reserved. Enabling

More information

1 Installation of accessories in molded case switches requires dummy trip; see page. Breaker/Switch Type TQD/TJD

1 Installation of accessories in molded case switches requires dummy trip; see page. Breaker/Switch Type TQD/TJD Molded Case Circuit Section Tri-Break Line Integrally Fused Thermal Magnetic Circuit Integrally Fused Magnetic Circuit Integrally Fused Molded Case Switches These breakers are available in three types.

More information

LV MCC with Arc Flash Mitigation (AFM) Units

LV MCC with Arc Flash Mitigation (AFM) Units LV MCC with Arc Flash Mitigation (AFM) Units Technical Tuesday June 30, 2015 Imagination at work. Markets Oil and Gas Petro-Chemical Mining and metals Pulp and paper Mass-production manufacturing Water

More information

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety MEDIUM VOLTAGE PRODUCTS UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety 2 UNISEC AIR-INSULATED MEDIUM VOLTAGE SECONDARY DISTRIBUTION SWITCHGEAR Operator

More information

Entry Level Assessment Blueprint Electrical Occupations

Entry Level Assessment Blueprint Electrical Occupations Entry Level Assessment Blueprint Electrical Occupations Test Code: 3029 / Version: 01 Specific Competencies and Skills Tested in this Assessment: Safety Apply shop safety rules and ergonomics Explain fire

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

SENTRON. Protective devices Selectivity for 3VA molded case circuit breakers. Introduction. Selectivity - terms and definitions

SENTRON. Protective devices Selectivity for 3VA molded case circuit breakers. Introduction. Selectivity - terms and definitions Introduction 1 Selectivity - terms and definitions 2 SENTRON Methods of implementing selectivity using circuit breakers 3 Protective devices Selectivity for 3VA molded case circuit breakers Configuration

More information

Prime Point on Wave Energy Reducing Switchgear ( SWITCHGEAR ).

Prime Point on Wave Energy Reducing Switchgear ( SWITCHGEAR ). S W I T C H G E A R Prime Point on Wave Energy Reducing Switchgear ( SWITCHGEAR ). Prime Engineering is a full service electrical engineering firm that specializes in medium and high voltage equipment

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA SURGE PROTECTION DESIGN. Parallel Versus Series Protection. Surge protectors within the scope of this UFC should normally be of the parallel

More information

F550e E-learning course Residual current devices basics RCDs Standards. ABB Group April 2, 2009 Slide 1

F550e E-learning course Residual current devices basics RCDs Standards. ABB Group April 2, 2009 Slide 1 F550e E-learning course Residual current devices basics RCDs Standards April 2, 2009 Slide 1 Objectives After completing this module, you will be able to have a clear overview of the residual current device

More information

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5

More information

Products Portfolio. Pole mounted Vacuum Recloser

Products Portfolio. Pole mounted Vacuum Recloser Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,

More information