INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS
|
|
- Scot Collins
- 5 years ago
- Views:
Transcription
1 INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS Konstantine Kolevatov, AS Tavrida Electric Export It has become a major task to provide uninterrupted electricity supply to customers and minimize the outage times in the countries of New Europe since adopting the new quality norms of electric services set by the European Union. Thus the success of an electric company and in turn its profitability is directly dependant on the quality of the electricity supplied to the customers. To achieve the highest reliability standards of electrical supply, minimization of outage times and provision for uninterrupted electricity to important customers, many electric companies have begun significantly improving their overhead electricity distribution lines. One of the key products for this improvement is the automatic circuit recloser. In the previous articles we considered the design and distinguishing features of the 27kV reclosers by TAVRIDA ELECTRIC and the most common applications of these devices. Useful operational algorithms of protection and automation functions of the recloser that allow for the resolution of frequent problems occurring on overhead distribution lines were also explained. The aim of this article is to consider possibilities presented by the TAVRIDA ELECTRIC reclosers when used by electric companies in their SCADA systems. TAVRIDA ELECTRIC recloser is outfitted with a fast response drive, i.e. a magnetic actuator that makes it an ideal executive device of a SCADA system. In addition to quick response, the reclosers by TAVRIDA ELECTRIC have built-in systems for remote signaling, control and telemetry that provide for their direct connection into SCADA systems. Implementation of TAVRIDA ELECTRIC reclosers into SCADA systems gives an opportunity to transmit the following information to dispatcher locations in the shortest possible time: 1. Current status of a recloser (on/off). This information is displayed on a dispatcher s monitor in the on-line mode.
2 2. Information about executed trips, pickups as well as operational data on protective equipment and automatic controls. 3. Normal operating parameters of the recloser systems. Monitoring of the systems status will help reduce the possibility of potential failures as well as prevent human injuries caused by electrocution in some cases. It will also reduce the possibility of destruction and theft of electric equipment. For instance, TAVRIDA ELECTRIC recloser is capable of relaying data on battery charge status, unauthorized control cubicle opening or any other troublesome matter. 4. Quality characteristics of supplied electricity in the on-line mode. The recloser by TAVRIDA ELECTRIC can hold up to 3840 such characteristics. For instance, constant monitoring of the supplied electricity frequency, current, voltage and power will prevent the possibility of unacceptable work modes of the interconnected electric equipment, which may cause premature breakdowns.
3 5. Electric Energy Metering and Load Profile. The function of the electric energy metering will allow the personnel of the electric companies to receive information on the modes that the interconnected electric equipment is operating in and provide information on the loads. The recloser by TAVRIDA ELECTRIC records active, reactive and full power in plus and minus directions. Power values are kept in the memory of the recloser and can be relayed to the collection devices at a dispatching location. The function of Load Profile can be used to monitor and optimize the maximum and minimum electric consumption. Electric Energy Metering and Load profile do not require additional expense because these functions come standard with the reclosers by TAVRIDA ELECTRIC.
4 6. Databases of statistics and events with graphic and table views. Accumulated statistics allow evaluating the efficiency of electric company operations, indirectly determine the level of wear and tear of the interconnected electric equipment and expose sections of the electric network needing renovation. Using statistical data various Electric Power Distribution Reliability Indices can be calculated and taken into consideration for developing actions to improve electric company performance. While being able to relay information, the reclosers by TAVRIDA ELECTRIC are also capable of remote control, up/downloading protection and automation settings, en/disabling protection and automation functions as well as selecting one of the four preinstalled independent groups of settings. These features can be beneficial in many cases. For instance, during line maintenance and repairs plenty of time is spent on routine switching required to de-energize the line section where work is being done. It is possible to minimize the outage time by allowing the dispatching personnel to operate switching devices without actually sending a service crew to the installation sites. Another example is seasonal changes of protection and automation settings as this also can be performed remotely via a SCADA system without customers interruption. Besides the above-mentioned features, the experience of creating SCADA systems using the reclosers by TAVRIDA ELECTRIC and their extended functions has exposed the following positive factors arising from their implementation in the electric companies: 1. Reduction of the human factor in occurring faults. Accidental actions of personnel are often the cause of faults and emergency situations. SCADA systems significantly simply the work of the dispatching personnel by reducing the human factor during routine or emergency switching of electrical equipment (the software installed in the recloser doesn t allow a dispatcher to conduct actions contradicting the safety rules), as well as gives a dispatcher the opportunity to see his commands in a mnemonic diagram.
5 2. Display of the entire diagram of the served network zone on a topographic map allows a dispatcher to make more efficient decisions about the actions of the service crew, which reduces the time to eliminate the problem. Dispatching personnel do not always have a clear idea of exactly where electricity distribution lines are located. The topographic map of the terrain displayed on the monitor will allow the dispatchers to have a better idea not only of the installation sites of the switching equipment but also about potentially troublesome and hard to reach sections of the lines. 3. The function of the recloser by TAVRIDA ELECTRIC that records the development of a fault and actions of the protection and automation equipment makes it possible to prevent fault repetition in the future. Every electric supply company has a task to prevent emergency situations. A detailed analysis of fault development and performance of protection and automation equipment can help to achieve this. The reclosers by TAVRIDA ELECTRIC make such data acquisition possible because each recloser comes standard with the function of recording faults and the course of their development. The recloser samples electric parameters 16 times in 20 milliseconds. Average values are calculated by a DSP (digital signal processor) and recorded in the memory. At fault the electric parameters and the protection and automation equipment actions are stored in the memory for the period of the last 1000 milliseconds (of the last 50 cycles of the power frequency) before the trip moment. This will provide the personnel of an electric company with complete and comprehensive information about the fault development and clearance. The recloser by TAVRIDA ELECTRIC can simultaneously hold information on four faults in its memory. The records about fault development and actions of the protection and automation equipment will allow the personnel of an electric company to determine the errors in calculations of the protection settings.
6 4. TAVRIDA ELECTRIC reclosers have wide communication capabilities. In case an electric company already has a SCADA system installed, a question will arise when selecting a supplier to make sure that new equipment can be integrated into the existing SCADA system. Experience in more than 40 counties has shown that the establishment of a new SCADA system using the reclosers by TAVRIDA ELECTRIC or their implementation in the existing SCADA systems is an easy task. Reclosers are programmed with two widely used communications protocols: Modbus and DNP3. Optionally the reclosers can also be equipped with communications protocol converters to support SCADA systems using IEC (103) protocols. In case an electric system uses traditional remote control systems, integration of TAVRIDA ELECTRIC reclosers is also an easy task because the reclosers can have optional modules of discrete programmable inputs/outputs up to 12 inputs and 12 outputs. The same modules can be used in non-standard or limited use SCADA systems. Radio, GSM (GPRS)-modems by various manufacturers, fiber optical communications, direct two-wire or four-wire connection or a trunked communications system can be used to provide connectivity between the reclosers and dispatching locations.
7 The recloser control cubicle has an internal source of 12 V DC. This powers the communications equipment. In spite of its small size, the recloser control cubicle has a section for housing communications equipment that is mounted on the RTU plate. The cubicle has cable glands with variable diameter to connect external cables without breaking the seal. Thus this article explained the possibilities presented by the TAVRIDA ELECTRIC reclosers when used by electric companies in their SCADA systems. You can have more information on the reclosers by TAVRIDA ELECTRIC if you visit TAVRIDA ELECTRIC Export s Internet site at
CABLETROLL 3 CABLETROLL CABLETROLL CABLETROLL CABLETROLL LED-2 5 CABLETROLL CABLETROLL REMOTE INDICATION 7
CABLETROLL 3 CABLETROLL 2310 4 CABLETROLL 2320 4 CABLETROLL 2330 5 CABLETROLL 2350 5 LED-2 5 CABLETROLL 2410 6 CABLETROLL 2440 6 REMOTE INDICATION 7 The CableTroll indicators are fault current detectors
More informationProducts Portfolio. Pole mounted Vacuum Recloser
Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,
More informationElastimold Molded Vacuum Recloser - MVR
Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical
More informationENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.
ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Ver. 081226 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser
More informationS&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application
Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The
More informationAUTOMATION OF POWER DISTRIBUTION USING SCADA
1 2 ABSTRACT In every substation certain measurements, supervision, control, operation and protection functions are necessary. Traditionally these functions were performed manually by system operator from
More informationIntelliTeam II Automatic Restoration System
No system is too complex to automate with... IntelliTeam II Automatic Restoration System Introduced in 1997, the IntelliTeam Automatic Restoration System was the first product of its kind. Using peer-to-peer
More informationReal-Time Automation Controllers (RTACs) Economical, multifunctional, compact real-time automation control
SEL-3505/3505-3 Real-Time Automation Controllers (RTACs) Economical, multifunctional, compact real-time automation control RTAC versatility facilitates easy event collection, protocol conversion, and secure
More informationTait GridLink THE INTELLIGENT CHOICE FOR DISTRIBUTION AUTOMATION. harris.com #harriscorp
Tait GridLink THE INTELLIGENT CHOICE FOR DISTRIBUTION AUTOMATION harris.com #harriscorp GRID VISIBILITY AND CONTROL Improving distribution grid operations with real time remote monitoring and control of
More informationENhanced TEChnology. Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1
ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated
More informationProduct Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet
S&C IntelliNode Interface Module Product Description Table of Contents Section Page Section Page Introduction Qualified Persons.......................... 2 Read this Instruction Sheet..................
More informationNU-LEC. Loop Automation. Reclosers & Sectionalizers
NU-LEC Loop Automation Reclosers & Sectionalizers 1 NU-LEC LLC NU-LEC LLC is a wholly unit of NU-LEC Industries, Pty, Ltd. Sales and service center for United States, Canada, and the Caribbean. Warehouse
More informationMONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES
MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity
More informationSolid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3
www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated with
More informationS&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv)
Outdo Distribution (15.5 kv and 27 kv) Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault interrupting system shall confm to the following specification. 1.02 The
More informationMV Network Managment Fault tracking, monitoring and control. Easergy Range Merlin Gerin
MV Network Managment Fault tracking, monitoring and control Easergy Range Merlin Gerin References Schneider Electric Industries SAS Postal address MV department F-38050 Grenoble Cedex 9 Tél. : +33 (0)4
More informationHigh-Reliability Fault-Clearing System solution. Application Guide. Outdoor Distribution (15.5 kv through 38 kv) S&C ELECTRIC COMPANY
S&C Remote Supervisory V ista Outdoor Distribution (15.5 kv through 38 kv) Electric utility customers are increasingly concerned about the frequency and duration of outages they are experiencing, and are
More informationDistributed Generation Requirements Update
Distributed Generation Requirements Update Toronto Hydro has updated its real time monitoring and control requirements for Distributed Generation facilities. The latest version of the Distributed Generation
More informationType SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage
Overhead solutions Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead switching products Brochure Your outdoor overhead distribution
More informationMV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA)
MV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA) Runjic Darijo Koncar Power Plant and Electric Traction Engineering Inc. - Croatia darijo.runjic@koncar-ket.hr Sporec Marko, Strmecki Goran
More informationMV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA)
MV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA) Runjic Darijo Koncar Power Plant and Electric Traction Engineering Inc. - Croatia darijo.runjic@koncar-ket.hr Sporec Marko, Strmecki Goran
More informationSmart Distribution Technology
Smart Distribution Technology Presentation Agenda Alabama Power Company, A Southern Company Distribution Automation Supervisory Control And Data Acquisition (SCADA) Multiple Address System (MAS) communications
More informationGround Breaking MV Switchgear
ISO 9001:2008 and ISO 14001:2004 certification ETALON Ground Breaking MV Switchgear Etalon is vacuum switchgear that fits most of the switchgear applications available and meets the most strict safety
More informationEM132 EM132. Main Features. Multi-functional 3-Phase Transducer. Energy Meter
EM132 MULTI-FUNCTION TRANSDUCER SATEC EM132 is a Smart DIN Rail Multi-Function Transducer with a local display. It is based on SATEC s best seller PM130 PLUS with an off-the-shelf LCD display (similar
More informationSubstation monitoring and control
Substation monitoring and control Part 3. Substation Automation Author Peter Johansen, www.jomitek.dk In the preceding 2 articles the topics of measurement techniques for voltage and current has been covered.
More informationWiAutoLink Frequently Asked Questions
Rev. 0 December 2014 Page 1 of 8 WiAutoLink Frequently Asked Questions December 2014 1 Rev. 0 December 2014 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the WiAutoLink Single Phase Electronic
More informationIntelligent Grid and Lessons Learned. April 26, 2011 SWEDE Conference
Intelligent Grid and Lessons Learned April 26, 2011 SWEDE Conference Outline 1. Background of the CNP Vision for Intelligent Grid 2. Implementation of the CNP Intelligent Grid 3. Lessons Learned from the
More information1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection
Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output
More informationSacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10,
Sacramento Municipal Utility District SMUD May 10, 2010 1 SMUD Facts and Figures 900 Sq. Miles Service Area 585,500 Customers 1.4 million Area Population 10 Bulk Substations 473 Miles of Transmission Lines
More informationHow smart can the grid really be?
How smart can the grid really be? by Dale Pudney, HVT Power Systems and Luo Wei, NR Electric With the improvement of electronic communications and computing technology, it becomes possible to integrate
More informationSolving the challenge
Solving the challenge How to implement power distribution automation with TETRA 2 How to implement power distribution automation with TETRA Contents Challenge Distributing power more efficiently... 3 Secure
More informationLightweight and flexible recloser control for single-phase applications
SEL-35S Kestrel Single-Phase ecloser Control Lightweight and flexible recloser control for single-phase applications Plug-and-work operation with popular single-phase reclosers simplifies new and retrofit
More informationCONTENTS... 2 COMTROLL SAS. SURVEILLANCE AND AUTOMATION SYSTEM...
GENERAL INFORMATION Contents CONTENTS... 2 COMTROLL SAS. SURVEILLANCE AND AUTOMATION SYSTEM... 3 COMMUNICATION... 4 BUILDING-BLOCKS... 5 NETTROLL AND NETDRAW... 5 NETALERT... 6 NETGRAPH... 7 COMTROLL OUTSTATIONS...
More informationGrid Automation packaged solutions Optimal automation of medium voltage grids
Grid Automation packaged solutions Optimal automation of medium voltage grids Application principles of the Zone concept Grid Automation (GA) packaged solutions The zone concept offers a method to analyze
More information////// SUBSTATIONS. Control command and local Scada
////// SUBSTATIONS Control command and local GENERAL INFORMATION The solution provided by Sécheron for local control and monitoring of traction substations is a significant step in supporting operations
More informationProtection, Monitoring, and Control System for Distribution Substations ALARM HISTORY SYSTEM COMM. On-Line Documentation TRANSFORMER 12 MW
SEL Distribution Substation Protection and Automation System Protection, Monitoring, and Control System for Distribution Substations Data Sheet SYSTEM ONE-LINE RELAY TARGETS ALARM HISTORY SYSTEM COMM.
More informationA low-cost, economical solution for distribution feeder protection
SEL-351A Protection System A low-cost, economical solution for distribution feeder protection Achieve sensitive and secure fault detection using comprehensive protection functions. Track breaker status
More informationSmall Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility
Small Generator Interconnection Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Proposed Interconnection PacifiCorp s 34.5-kV West Cedar Substation December 29, 2010 TABLE OF CONTENTS
More informationTETRA for SCADA Challenges in CLP
TETRA for SCADA Challenges in CLP CCW 2016 Amsterdam Ir. Terrance Lai Digital Systems Manager CLP Power Hong Kong Ltd CLP Group One of the largest investor-owned utility companies in Asia We generate,
More informationOSM PRODUCT GUIDE. OSM AUTOMATIC CIRCUIT RECLOSER 15kV, 27kV & 38kV Models
OSM PRODUCT GUIDE OSM AUTOMATIC CIRCUIT RECLOSER 15kV, 27kV & 38kV Models 1. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction INTRODUCTION The OSM15, OSM27 and OSM38 automatic
More informationTHE RAINBOW SCADA D-700
THE RAINBOW SCADA D-700 INTERNET ENABLED SYNCHRONIZATION SYSTEM REV-03 25.12.2014 EXPANSION CAPACITY MAX 16 LOADS MAX 48 GENSETS MAX 4 BUS COUPLERS MAX 16 MAINS MULTIFUNCTIONAL THE SAME UNIT IS A... MULTI-GENSET
More informationIMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7
IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7 LINETROLL 110Eµ 8 LINETROLL 111K 9 LINETROLL L400D 10
More informationMINER-S Station Controller
MINER-S Station Controller Substation Automation MINER-S Station Controller The MINER-S Station Controller is a SCADA enabled fixed point remote terminal unit (RTU) with a data concentrator, event reporter,
More informationDC Substations / Supply Program
DC Substations / Supply Program Sécheron offers an extensive range of products for DC electrification of public transport This document is intended to give a brief idea of our services, cubicles and systems
More informationEquipment Strategy For High Voltage Circuit Breakers
Current version: 23/05/2018 EXTERNAL USE Page 1 of 7 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References... 3 1.4 Defined terms... 3 1.5 Monitoring and compliance... 3
More information2 ms arc-flash protection and feeder relay in one platform
Feeder Protection Relay 2 ms arc-flash protection and feeder relay in one platform Combine light sensor inputs with high-speed overcurrent protection to achieve secure arc-flash protection in as fast as
More informationAutomation Services and Solutions
Automation Services and Solutions Automate substation data acquisition and control to improve performance Maintain uninterrupted power services with proactive grid monitoring and controlling features.
More informationRevised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer )
Revised Generation Interconnection Impact Study Report For Queue Position 31 ( Interconnection Customer ) September 22, 2004 1 Generation Interconnection System Impact Study Report I. Revision of Original
More informationSource-Transfer Application Guide
S&C Model 6802 Automatic Switch Control Source-Transfer Application Guide Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this
More informationHigh performance monitoring & Control ACE3600 Remote Terminal Unit
High performance monitoring & Control ACE3600 Remote Terminal Unit Empower Your SCADA Network Utilities, now more than ever, are facing newer and greater hurdles. Multiple wired and wireless communication
More informationSwitchgear FEATURE. Basler Electric Company
Switchgear LIFe ExtenSIon: Replacement of electromechanical Overcurrent Relaying By Todd Martin, Basler Electric Company Chemical Facility U p d at i n g S w i t c h g e a r R e l ay s Electromechanical
More informationDKG-210 UNIVERSAL INTERNET GATEWAY UNIT
DKG-210 UNIVERSAL INTERNET GATEWAY UNIT AC & DC SUPPLY VERSIONS DESCRIPTION The DKG-210 is designed for internet monitoring and control of industrial devices using different protocols through the RAINBOW
More informationRecloser Controller for feeder protection and automation siemens.com/distribution-automation
SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast
More informationSPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station
SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal
More informationZC Series Zone Monitoring Controllers
ZC Series Zone Monitoring Controllers Installation Instructions MANUAL Reset Controllers Model Description Part Number ZC-1 1 Zone Controller 0421 ZC-2 2 Zone Controller 0422 ZC-3 3 Zone Controller 0423
More informationOnline data sheet. C4C-EB10530A10000 detec SAFETY LIGHT CURTAINS
Online data sheet C4C-EB10530A10000 detec A B C D E F Ordering information Type Part no. C4C-EB10530A10000 1219563 Included with delivery with every device: 1 system connecting cable with flying leads
More informationtapcon 230 user-friendly, FleXiBle and reliable. transformer control
tapcon 230 user-friendly, FleXiBle and reliable. transformer control Tapcon 230 tapcon 230 the new standard in voltage control. 2 Maschinenfabrik Reinhausen (MR) has been developing and manufacturing voltage
More informationPrimary Injection Test Procedure
S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Primary Injection Test Procedure Table of Contents Section Page Section Page Introduction Qualified Persons....
More informationElectrical Demand Specification (Reference SOP: )
Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3
More informationCircuit Breaker Sentinel (CBS) for SF 6. power circuit breakers
Circuit Breaker Sentinel (CBS) for SF 6 power circuit breakers Circuit Breaker Sentinel (CBS) for SF 6 power circuit breakers It is widely recognized that the concept of periodic equipment maintenance
More informationTRANSMISSION ENGINEERING STANDARDS SUBSTATIONS
This standard was reviewed and approved by key managers on. Officer approval of this revision is not required. 1.0 SCOPE 1.1 This guide applies to the interconnection of a generating plant with the Oncor
More informationFG Wilson Control Systems
www.fgwilson.com FG Wilson Control Systems FG Wilson Control Systems Putting You in Control Whatever your power requirements, FG Wilson can provide a control system to suit your needs. Our generator set
More informationApproved Standards. Motor Protection Circuit Breaker (MPCB) J7MN. MPCB system (motor protection CLASS 10) Auxiliary contact modules.
Motor Protection Circuit Breaker (MPCB) J7MN MPCB system (motor protection CLSS 0) Rotary and switch types Rated operational current = 2, 25, 50 and 00 Switching capacity up to 2.5 = 00 k/400 V Fixed short-circuit
More informationSIPROTEC 5 Application Note
www.siemens.com/protection SIPROTEC 5 Application Note SIP5-APN-001: Properties and Functional Structure Answers for infrastructure and cities SIPROTEC 5 Properties SIPROTEC 5 - Application: SIP5-APN-001
More informationCatalog. Arc Guard System TM TVOC-2
Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already
More informationDiamondback. Solid Dielectric Load Break Switch Catalog. Distributed By;
Solid Dielectric Load Break Switch Catalog Distributed By; p G&W headquarters in Bolingbrook, IL USA Company profile Since 1905, G&W Electric has helped energize the world with innovative power system
More informationSDG&E s EPIC Demonstration Projects on Emerging Communication Standards. IEC Europe 2017 Conference. Frank Goodman, SDG&E EPIC Program Manager
SDG&E s EPIC Demonstration Projects on Emerging Communication Standards Frank Goodman, SDG&E EPIC Program Manager IEC 61850 Europe 2017 Conference September 26-28, 2017 2017 San Diego Gas & Electric Company.
More informationSpending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker
More informationICM Project Station Infrastructure and Equipment
EB 0 00 Schedule B ( pages) ICM Project Station Infrastructure and Equipment (THESL) EB 0 00 Schedule B I EXECUTIVE SUMMARY. Description THESL relies on an extensive Supervisory Control and Data Acquisition
More informationOnline data sheet. i10-m0233 Lock i10 Lock SAFETY LOCKING DEVICES
Online data sheet i10-m0233 Lock i10 Lock i10-m0233 Lock i10 Lock A B C D E F actuator not supplied with delivery Ordering information Type Part no. i10-m0233 Lock 60580 The actuator has to be ordered
More informationOHL Fault Indicators Grid Monitoring Software
OHL Fault Indicators Grid Monitoring Software About Company We independently carry out the development, design, manufacture, installation and commissioning of power- generating equipment and its technical
More informationIntrinsically safe batch controller Batching Master 110i
Intrinsically safe batch controller Batching Master 110i Installation Guide BVS 04 AT E 172 Revision 12.2 IBS BatchControl GmbH Im Sträßchen 2-4 Tel.: ++49 2441 9199 801 53925 Kall Fax.: ++49 2441 9199
More informationFCIs reduce fault-locating times and improve reliability metrics, especially the Customer Average Interruption Duration Index (CAIDI).
1 Intelligent electronic devices (IEDs) are the preferred choice for modernizing the grid. Communication among networks of robust IEDs designed for protection, control, and monitoring (PCM) of the power
More informationSiprotec 7ST61 / 7ST63
Siprotec / Numerical overhead contact line protection for AC traction power supply siemens.de/rail-electrification The numerical overhead contact line protection relay Siprotec / is a selective and quick
More informationSicat CMS. siemens.com/mobility. Catenary monitoring system for overhead contact line systems
The contactless catenary monitoring system Sicat CMS continuously monitors the tensile forces in the contact wire and catenary wire and also acquires and evaluates the information. The filtered information
More informationMiCOM P122C Time-Overcurrent Protection
Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance
More information21 st Century Landfill Technology: Telemetry, Automation, and Alternative Power Sources
21 st Century Landfill Technology: Telemetry, Automation, and Alternative Power Sources Automation Automation provides for the starting and stopping of the operating system without the need of additional
More informationNpefm!681F! !!!681F!Gjcfspqujd!Usbotdfjwfs! Gjcfspqujd!Ofuxpsl!Tpmvujpo!! Model 570E Features. The Fiberoptic Communications Specialists
!!!681F!Gjcfspqujd!Usbotdfjwfs! Gjcfspqujd!Ofuxpsl!Tpmvujpo!! The Fiberoptic Communications Specialists The Model 570E offers high-speed serial communication to meet the challenging needs of distribution
More informationCIGRE U.S. National Committee
CIGRE U.S. National Committee 2014 Grid of the Future Symposium October 20, 2014 Houston, TX New Tools for Managing Smart Switching Devices Chris McCarthy, Jason Lombardo S&C Electric Company CWG/9416P
More informationg Energy Multilin Recloser Controller DGCR Communications Protection Automation & Control Security & EnerVista Software Hardware Metering & Monitoring
Multilin Recloser Controller DGCR Key Benefits 4 shot auto-recloser 3 setting groups enable different setting selections based on switched conditions Advanced logic engine and multiple IOs for creating
More informationOnline data sheet. i15-mm0123 Lock i15 Lock SAFETY LOCKING DEVICES
Online data sheet i15-mm03 Lock i15 Lock i15-mm03 Lock i15 Lock A B C D E F actuator not supplied with delivery Ordering information Type Part no. i15-mm03 Lock 6034024 The actuator has to be ordered separately.
More informationOnline data sheet. i110-e0453 i110 Lock SAFETY LOCKING DEVICES
Online data sheet i0-e0453 i0 Lock i0-e0453 i0 Lock A B C D E F actuator not supplied with delivery Ordering information Type Part no. i0-e0453 6051601 The actuator has to be ordered separately. See "Accessories"
More informationOnline data sheet. i200-m0323 Lock i200 Lock SAFETY LOCKING DEVICES
Online data sheet i200-m0323 Lock i200 Lock A B C D E F actuator not supplied with delivery Ordering information Type Part no. i200-m0323 Lock 6025113 The actuator has to be ordered separately. See "Accessories"
More informationAn Innovative Approach to Implementing SCADA into the Industrial Environment
Feature An Innovative Approach to Implementing SCADA into the Industrial Environment by Lynn Hamrick and David Charles ESCO Energy Services ESCO Energy Services Company recently implemented a Supervisory,
More informationShabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India
SCADA in Transmission Line Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India ABSTRACT: Transmission line equivalent circuit parameters are often 25%
More informationOnline data sheet. i200-m0413 Lock i200 Lock SAFETY LOCKING DEVICES
Online data sheet i200-m03 Lock i200 Lock i200-m03 Lock i200 Lock A B C D E F actuator not supplied with delivery Ordering information Type Part no. i200-m03 Lock 6025115 The actuator has to be ordered
More informationLecture 5 Substation Automation Systems. Course map
Lecture 5 Substation Automation Systems 1 Course map 2 1 Contents of the Lecture Part 1 Substation Automation Components Substation Automation Functions Communication within the Substation (Intro) Part
More informationEvolution of Control for the Power Grid
Evolution of Control for the Power Grid Anjan Bose Washington State University Pullman, Washington, USA University of Seville Seville, Spain June 17, 2016 THE INTERCONNECTED GRID Economics Transfer electric
More informationKEDS DSO Development Plan. George Karagutoff, KEDS CEO Prishtina, Kosovo 20 March, 2018
KEDS DSO Development Plan George Karagutoff, KEDS CEO Prishtina, Kosovo 20 March, 2018 1 INVESTMENTS AT A GLANCE KEDS begun its operations after the successful unbundling of Distribution and Supply business
More informationGE Multilin 350 Feeder Protection Relay Specifications
GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following
More informationWi-Fi and Security Administration
S&C PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Wi-Fi and Security Administration Table of Contents Section Page Section Page Introduction Qualified Persons...2 Read
More informationDRAFT. Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters. 1.0 Introduction DANGER. 1.1 Related Documents
Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters AP-XC-025 Revision B 1.0 Introduction DANGER RISK OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This Application Note is in
More informationOctober 05, ECE 421 Session 12. Utility SCADA and Automation. Presented by: Chris Dyer
ECE 421 Session 12 October 05, 2017 Utility SCADA and Automation Presented by: Chris Dyer Utility SCADA & Automation Chris Dyer, P.E. BSEE University of Idaho, 1997 SCADA & Automation Engineer POWER Engineers,
More informationThis webinar brought to you by the Relion product family
This webinar brought to you by the Relion product family Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter, more flexible and more adaptable. Easy
More informationg Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications
Multilin Voltage Regulator DGCV KEy BENEFITS Increases grid efficiency by optimizing voltage regulation Through deployment of the Volt/VAR system, the Multilin DGCV: - Enables up to a 6% reduction in energy
More information////// SUBSTATIONS. Voltage Limiting Device. VGuard
////// SUBSTTIONS Voltage Limiting Device GENERL INFORMTION During normal operation of railway system, dangerous voltage can occur across accessible points of the return circuit and earth due to the voltage
More informationRapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS
Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS RAPIER GX Gas Enclosed Switch Our new RAPIER GX, pole-mounted
More informationUPLC-100. Universal Power Line Carrier. 5C Communications Inc.
Universal Power Line Carrier Overview UPLC100 uses the high-voltage line between transformer substations as a communication path for multi-service of data, tele-protection, voice and video signals. This
More informationDemonstration of the UPGRID project urban network of the future
Demonstration of the UPGRID project urban network of the future SŁAWOMIR NOSKE, DOMINIK FALKOWSKI ENERGA-OPERATOR SA e-mail: {slawomir.noske/dominik.falkowski}@energa.pl 1. Introduction Sustainable development,
More informationMaxwell Dondo PhD PEng SMIEEE
Maxwell Dondo PhD PEng SMIEEE 1 Evolution of grid automation SCADA introduction SCADA Components Smart Grid SCADA Security 2 Traditionally power delivery was unsophisticated Generation localised around
More information