STA STA TPRG. Programmable RTD, T/C, Ohms, mv. and Potentiometer Safety Trip Alarm. April A1

Size: px
Start display at page:

Download "STA STA TPRG. Programmable RTD, T/C, Ohms, mv. and Potentiometer Safety Trip Alarm. April A1"

Transcription

1 April A1 STA Programmable RT, T/C, Ohms, mv TPRG STA Programmable RT, T/C, Ohms, mv All product names are registered trademarks of their respective companies.

2 (TPRG) Quick Start Guide se the front pushbuttons to quickly and easily set-up the STA for your application. After programming your alarm using the diagram below, install the unit into your application using the connection diagrams and terminal designation table located in this manual. WARNING: This menu is intended to aid in the configuration of your instrument. However, proper use of the STA at its intended safety level cannot be acheived without thorough review of the STA in Safety Instrumented Systems Section of this manual. Front Panel Pushbuttons se the P and OWN pushbuttons to scroll through menus and sub-menus. se the ECT pushbutton to access menus and/or make a choice. P OWN ECT SYS LOCK Security Jumper installed in No Acess position. Configure Input: Choose input type. INPT SCALE INPT Security Jumper installed in Full Acess position. ENTER PASS Security Jumper installed in Password Required position. Scale Input: Set the values to be displayed at zero and full scale without calibration equipment. Enter the password code to enable settings changes. (efault = 1) (If the incorrect password is entered, access to the configuration menus is denied.) Trim Input: Match the actual reading of your STA to a calibrated or known value. Configure Analog Output: Select volt or current output. Choose damping value and fail mode. (Requires -AO Option) Trim Analog Output: Connect the STA into a calibration set-up as shown in the manual and trim the analog output. (Requires -AO Option) Password: View or change password. Exit Configuration Menu: Return to process display. TRIM INPT ALARM AOT SCALE AOT TRIM AOT OPTNS PASS RESET FALT EXIT Configure Alarm: Set trip point, dead band, high/low trip and latching/non-latching. Scale Analog Output: Set the values for output at zero and full input (Requires -AO Option) Configure Options: isplay mode, decimal places, 50/60Hz filter, display test and factory reset. Reset Fault: Reset fault option, select Yes or No.

3 Table of Contents Introduction... 6 About This Manual... 6 Model and Serial Numbers... 6 STA escription... 6 Inputs... 6 Alarms... 6 Options... 6 Configuration... 6 STA Application Examples... 7 Alarm Terminology... 8 STA iagnostics & Fault Alarms... 9 Specifications imensions Security Settings Password Setting STA Configuration View Menu Main Configuration Menu Configuring the Input Scaling the Input Input Trimming Configuring the Alarm(s) Configuring the Analog Output (-AO Option)... 25

4 Scaling the Analog Output (-AO Option) Trimming the Analog Output (-AO Option) Configuring the Options Password Configuration Reset Fault Configuration Exit STA iagnostic Messages STA Transfer tility Software Installing the Transfer tility Software Connecting the STA to the PC Transfer tility Software Summary Menu and Tool Bar Legend File Management Save a File Load a File Installation Mounting Making the Electrical Connections Recommended Ground Wiring Practices CE Conformity Operation Maintenance... 35

5 Customer Support STA in Safety Instrumented Systems Functional Safety escription Failure Rate ata Product Life Installation Configuration Process Safety Time Analog Output - Non-Safety Sensor Types Broken Wire etection Sensor Trimming Enable/isable Latching Mode Enable/isable Remote Manual Reset Operation and Maintenance Proof Test Steps eclaration of Conformity Return Procedures and Warranty Information... 40

6 Programmable RT, T/C, Ohms, mv Introduction This is the user s manual for Moore Industries STA (TPRG): Programmable RT, T/C, Ohms, mv, and Potentiometer Safety Trip Alarm. The Moore Industries Safety Trip Alarm (STA) is designed and manufactured to provide a high level of availability for safety critical applications and for use as a component part of a safety instrumented system. This manual contains all of the information needed to confi gure, install, operate and maintain this product. When the STA is used in a SIL rated safety application (as defi ned by IEC 61508), the Safety Instrumented Systems section of this manual must be read and followed in order for the STA to meet it s IEC certifi cation requirements. About this Manual Wherever you see a Note, Caution or WARNING pay particular attention. WARNING - Hazardous procedure or condition that could injure the operator. Caution - Hazardous procedure or condition that could damage or destroy the unit. Note - Information that is helpful for a procedure, condition, or operation of the unit. Model and Serial Numbers Moore Industries uses a system of model and serial numbers to keep track of all of the information on every unit it sells and services. If a problem occurs with your STA, check for a tag affi xed to the unit listing these numbers. Supply the Customer Support representative with this information when calling. STA escription Moore Industries STA (TPRG) is a programmable RT, T/C, Ohms, mv and Potentiometer safety trip alarm. The STA monitors a process variable and provides two fully user-confi gurable contact closure outputs that can be individually programmed to trip whenever the input falls outside a user-set, high or low trip point. It also has one fault alarm output which is triggered by a self-diagnosed failure of the input or the STA itself. The STA is typically used to activate a warning light, bell or buzzer; or to initiate a system shutdown. Thus, the instrument acts as a simple, but highly reliable and effective means of monitoring and safe-guarding a process. The STA is confi gured using front panel push buttons and a confi guration can also be saved and downloaded using the PC transfer utility. A large 5-digit display shows menu prompts during push button confi guration and process variable and status messages during normal operation. Inputs The STA (TPRG) supports RT, T/C, mv, Potentiometer and Ohms as confi gurable inputs. These inputs can be trimmed and scaled, refer to the Confi guring Inputs section of this manual for additional information. Alarms The STA has three (-3PRG) contact closure alarms. One relay is factory confi gured as a Fault alarm and the remaining two relays are user-confi gurable Trip alarms. A dual color LE (Red/Green) is provided with each alarm to indicate its condition. The fault alarm trips on a self-diagnosed failure within the STA or on any of its inputs. This alarm is latching and has to be reset by the user. Only user confi guration faults will clear automatically once the confi guration is valid. Input faults can be cleared by the RESET FALT menu, and unit faults can only be cleared by power cycling the unit. For more information refer to the iagnostics and Fault Alarm section. The Trip alarms are confi gurable for high or low trip with an adjustable dead band. These alarms can be latching or non-latching. Latched alarms are reset through the Manual Reset (MR) terminals. The relay outputs have a 3A@250Vac or 3A@30Vdc, 50/60Hz non-inductive contact rating. The contact arrangement is SPT. All outputs are fail safe and will de-energize to trip (ET) with NO & NC relay contacts. Refer to the Alarm Terminology and Confi guring the Alarms sections of this manual for additional information. 6 The Interface Solution Experts

7 Programmable RT, T/C, Ohms, mv Options Analog Output (-AO) The Analog Output can be confi gured to provide a voltage (0-10V) or current (0-20mA) output. The current output can be sink or source. Refer to the Confi guring the Analog Output section of this manual for additional information. Note: The Analog Output is not part of the safety path in the STA. Figure 2. High Availability example REAY INPT TRIP 1 TRIP 2 FALT COM EG C TAG STA SAFETY TRIP ALARM P OWN ECT Process Trip 1 Process Trip 2 Fault Alarm NC1 CM1 NO1 NC2 CM2 NO2 NC3 CM3 NO3 Final Element Logic Solver/ SIF Alarm Configuration The STA can be confi gured from either the front panel keyboard or by downloading a proven confi guration using the PC Transfer tility. STA Application Examples The following are examples of typical STA confi gurations. Figure 1. High Integrity example This confi guration (Figure 2) offers higher system availability. The Fault alarm is wired separately to inform the safety system that there is a fault alarm and that this component s ability to carry out its portion of Safety Instrumented Function cannot be performed. This confi guration can be used in applications where it is safe to keep the process running for a short time while a defective instrument is repaired. The output process trip relays are connected 1oo2 to trip providing security against a single relay failure, however this confi guration will NOT trip if an STA fault is diagnosed. REAY INPT TRIP 1 TRIP 2 FALT COM EG C P OWN ECT Process Trip 1 Process Trip 2 NC1 CM1 NO1 NC2 CM2 NO2 Final Element This type of confi guration must be used with care in a safety system. The end user must determine how long the process is allowed to continue after a STA fault is detected and ensure that the unit can be repaired or replaced within this time. TAG STA SAFETY TRIP ALARM Fault Alarm NC3 CM3 NO3 This confi guration (Figure 1) offers the highest trip integrity. Since all three relays are wired in series, any trip alarm or STA fault will trip the fi nal element or logic solver. This provides security against one process relay failure and any unit failures. However this confi guration is vulnerable to spurious trips as STA safe failures will also trip the fi nal element. The Interface Solution Experts 7

8 Programmable RT, T/C, Ohms, mv Alarm Terminology Before setting up the STA, or incorporating the unit in your application, Moore Industries suggests that all users take a few moments to become familiar with some of the terms associated with the use of process instrumentation alarms. Figure 3 illustrates the way the STA alarms operate. The Trip Point is the process input level at which the user wants an alarm relay to change state, typically going into an alarm condition, or tripping. In the STA, the user sets the trip point for each installed relay. High/Low Alarms; High Alarms trip when the process input goes above the trip point. Low Alarms trip when the process input drops below the trip point. Each of the STA relay outputs can be set by the user to function independently as either high or low alarms. Latching and Non-latching Alarms; once tripped, a latching alarm remains in an alarm state until the input returns to a non-alarm level AN is manually reset. Non-latching alarms return to a non-alarm state whenever the process input returns to the Reset Point. The STA relays can be set by the user to function as either latching or non-latching. Figure 3. How Alarms Work with the Process Input HIGH ALARM TRIP POINT RESET RESET LOW ALARM TRIP POINT TIME EABAN IN ALARM IN NON-ALARM EABAN The Reset Point is the process input level at which the user wants an alarm relay to change state, typically going from alarm to non-alarm. The reset point is not necessarily the same as the trip point, because most applications call for a buffer zone or dead band around the trip point to allow for minute fl uctuations in the process input. In the STA, the reset point is determined by the dead band setting. Latching STA alarms will not clear unless the reset point has been reached or passed AN the manual reset contacts have been shorted. The ead band is the range in which an alarm remains tripped even after the process input has returned to or passed the trip point. ead band is not required. When it is not incorporated into a non-alarm application, the trip point and reset point are the same. The dead band of the STA is set by the user. Failsafe Alarms are de-energized when tripped, energized when the process input is at a non-alarm level. Non-failsafe alarms are energized whenever tripped, de-energized when the process input is at a non-alarm level. The relays in the STA are failsafe only. Normal is the term used to describe the shelf-state of relay contacts. The contacts of a Normally Open relay are open (infi nite resistance) when the relay is not energized. The contacts of a Normally Closed relay are open when the relay is energized (closed when not energized). NOTE: Sometimes a non-alarm input level is referred to as being in a normal condition. This practice is intentionally avoided in this manual. o not confuse the term normal, as in Normally Open or Normally Closed, with a non-alarm input condition. In this manual, normal is an exclusive reference to the shelf state or quiescent state of an alarm s relay contacts, whether open or closed. 8 The Interface Solution Experts

9 iagnostics & Fault Alarms The STA has a high level of diagnostic capability to continually monitor itself and its input. This section outlines these diagnostics and functionality of the alarms. For a full list of diagnostic messages and corrective actions please refer to Table 7. Internal diagnostics On power up the unit runs through a thorough diagnostic test (RAM and ROM TEST messages are displayed) and an initialization process (SYS INIT is displayed) before the fault alarm is cleared. If any failure is found during power up, the fault alarm will not be cleared and an error message will be displayed. Once in operation, the unit continues diagnostic tests in the background and will set the fault alarm on any failure. All internal diagnostic faults are latched on the fault alarm relay. The fault alarm must be cleared by power cycling the unit. If a fault is still present on power up then please contact Customer Service for further assistance. Note: The trip alarms are independent from the fault alarms and will be unaffected by the fault alarms (however they may be affected by the specifi c failure in the unit). STA Programmable RT, T/C, Ohms, mv Input diagnostics The STA has extensive hardware diagnostics of the input to detect broken wire and saturation. It also detects out of range and linearization errors. Broken wire is automatically set on the STA and enables the system to distinguish between a low trip condition (which sets the trip alarm) and a failed transmitter or open input (which sets the fault alarm). All input faults are latched on the fault alarm relay. The fault alarm can be cleared by fi rst clearing the input failure and then using the confi guration menus to reset faults. If the input error is not cleared when resetting the fault alarm, the error condition will immediately be re-applied and will not cause the relay to glitch. Note: The trip alarms are independent from the fault alarm and will be unaffected by the fault alarm. Therefore if the trip alarm has already been activated it will remain so but will NOT be activated by a broken wire or input saturation error. For broken wire detection, this only applies if the input is immediately broken. If there is degradation of sensor wires, false readings could occur before the wire breaks and the trip alarm could be activated before the fault alarm. (Slow degradation is characterized by events that occur over a span of a second or so) Configuration diagnostics On power up the stored confi guration is validated. If it is invalid then the fault alarm will be set. To clear the alarm, use the menu system, to reset to the factory confi guration (FCTRY selection in the options menu), then confi gure as appropriate for the application. Before saving a new confi guration to the unit, it will be checked for validity. If it is invalid, the fault alarm will be set. Once the confi guration is corrected, the fault alarm will be cleared. The Interface Solution Experts 9

10 Programmable RT, T/C, Ohms, mv Specifications Performance Input Accuracy and Alarm Trip Repeatability: Refer to Table 4 Overall Accuracy: The overall accuracy of the unit is the combined input and output accuracies. It includes the combined effects of linearity, hysteresis, repeatability and adjustment resolution. It does not include ambient temperature effect. For T/C input, add the RJC error. Reference Junction Compensation Accuracy (T/C inputs only): ±0.45 C Stability: Refer to Table 1 ead Band: ser-set within selected input range; fully scalable and set in user-selected engineering units Input to Output Trip Response Time: 256msec maximum from step change on input to alarm state change when alarm is set to trip at mid-point of step Alarm Trip elay: Programmable from seconds Isolation: 500Vrms between case, input, output, and power ielectric Strength: 1966Vdc for 2 seconds, between case, input, output, and power Power Supply: 24C range, 18-30Vdc; AC range, Vac Power Consumption: 3.5W maximum for C supply; 4W maximum for AC supply Power Supply Effect: ±0.002% of span per 1% line voltage change Input Over-Range Protection: ±5Vdc, maximum Input Resistance: T/C and mv inputs, 40Mohms, nominal Excitation Current: RT and Ohms, 250 microamps, ±10% Performance (continued) Performance of Analog Output (-AO Option) Ambient Conditions Output Relays ual Process Relays and One Fault Relay (Relays are single-pole/double-throw SPT, 1 form C, rated 3A@250Vac or 3A@30Vdc, 50/60Hz, non-inductive) Non-Safety-Critical Analog Output Option Output Accuracy: Current, ±0.01% of maximum span (±2 microamps); Voltage, ±0.01% of maximum span (±1mV) Input to Output Response Time: 256msec for the output to change 10% to 90% of its scale for an input step change of 0 to 100% Output Step Response Time: 100msec maximum Output Ripple (up to 120Hz): 50mV peak-topeak maximum on voltage output; 10mV peak-to-peak measured across a 250 ohm load resistor for current output (frequencies up to 120Hz) Output Current Limiting: Current outputs, Output Failure Limits 0-20mA 0, 23.6mA 4-20mA 3.6, 23.6mA X-20mA (90% of X), 23.6mA (0<X<4) Voltage output, V Load Capability: Source mode (internal power supply), 0-1 kohms for current output; 2 kohms for voltage output; Sink Mode (External power Supply), 42Vdc Max Load Effect (current outputs): ±0.01% of span from 0 to maximum load resistance on current output Operating Range: -40 C to +85 C (-40 F to +185 F) Relay Range: -40 C to +85 C (-40 F to +185 F) Storage Range: -40 C to +85 C (-40 F to +185 F) Ambient Conditions (continued) Adjustments Indicators Weight Ambient Temperature Effect: Refer to Table 3 Effect of Ambient Temperature on Reference Junction Compensation (T/C inputs only): ±0.005 C per C change of ambient temperature; With Non-Safety-Critical Analog Output: ±0.009% of maximum span/ C Relative Humidity: 0-95%, non-condensing RFI/EMI Protection: 20V/m@ MHz, 1kHz AM, when tested to IEC61326 with 0.5% of span or less error Noise Rejection: Common Mode, 100dB@50/60Hz Normal Mode, refer to Table 2 Front panel push-buttons for parameter confi gurations; Internal jumper and menu password protect parameter settings LC: 2x5 14-segment characters, backlit, alphanumeric readout accurate to the nearest digit. Range: to 99999; ecimal point can be userset LE Type: INPT LE: ual color LE indicates input failure REAY LE: Green LE indicates unit is operating properly ALARM 1 and 2 LE: ual color LE per relay indicates alarm status FALT LE: Green LE indicates unit is operating properly; Red LE indicates unit has fault or is latched. isplay Accuracy: ±1 digit; when scaling the display (or in custom mode), high input-to-display span ratios decrease display accuracy 527 g to 581 g (18.6 oz to 20.5 oz) Specifi cations and information subject to change without notice. 10 The Interface Solution Experts

11 Programmable RT, T/C, Ohms, mv Table 1. Long-Term Stability Stability (% of maximum span) Input to Non-Safety Critical Analog Output (Years) Input to Relay (Years) Table 2. Normal Mode Rejection Ratio Sensor Type T/C: J, K, N, C, E T/C: T, R, S, B Pt RT: 100, 200, 300 ohms Pt RT: 400, 500, 1000 ohms Ni: 120 ohms Cu: 9.03 ohms Resistance 1-4k ohms k ohms k ohms mv Max. p-p Voltage Injection for 100dB at 50/60Hz 150mV 80mV 250mV 1V 500mV 100mV 1V 250mV 100mV Table 3. Ambient Temperature Effect Accuracy per 1 C (1.8 F) change in Ambient *RT C Millivolt 0.5 microvolts % of reading Ohm 0.002ohms % of reading Thermocouple Accuracy per 1 C (1.8 F) change in Ambient J C % of reading K C % of reading E C % of reading T C % of reading R, S C % of reading B C % of reading N C % of reading C C % of reading mv 0.5microvolts % of reading *Accuracy of Ni672 is C The Interface Solution Experts 11

12 Programmable RT, T/C, Ohms, mv Table 4. Accuracy with RT, Thermocouple, Ohms, Potentiometer and Millivolt Inputs Input Type Ohms Conformance Range Minimum Span Input Accuracy/ Repeatability Maximum Range RT 2-Wire, 3-Wire, 4-Wire to 850 C (-328 to 1562 F) -240 to 960 C (-400 to 1760 F) Platinum to 650 C (-148 to 1202 F) 10 C (18 F) ±0.1 C (±0.18 F) -150 to 720 C (-238 to 1328 F) to 510 C (-328 to 950 F) -240 to 580 C (-400 to 1076 F) Ohms T/C Nickel Copper irect Resistance Potentiometer J K to 320 C (-112 to 608 F) -50 to 250 C (-58 to 482 F) ohms 0-100% -180 to 760 C (-292 to 1400 F) -150 to 1370 C (-238 to 2498 F) 10 ohms 10% 35 C (63 F) 40 C (72 F) ±0.85 C (±1.53 F) ±0.4 ohms ±0.1% ±0.25 C (±0.45 F) ±0.3 C (±0.54 F) -100 to 360 C (-148 to 680 F) -65 to 280 C (-85 to 536 F) ohms 0-100% -210 to 770 C (-346 to 1418 F) -270 to 1390 C (-454 to 2534 F) E -170 to 1000 C (-274 to 1832 F) 35 C (63 F) ±0.2 C (±0.36 F) -270 to 1013 C (-454 to F) T -170 to 400 C (-274 to 752 F) 35 C (63 F) ±0.25 C (±0.45 F) -270 to 407 C (-454 to F) R 0 to 1760 C (32 to 3200 F) 50 C (90 F) ±0.55 C (±0.99 F) -50 to 1786 C (-58 to F) S 0 to 1760 C (32 to 3200 F) 50 C (90 F) ±0.55 C (±0.99 F) -50 to 1786 C (-58 to F) B 400 to 1820 C (752 to 3308 F) 75 C (135 F) ±0.75 C (±1.35 F) 200 to 1836 C (392 to F) N -130 to 1300 C (-202 to 2372 F) 45 C (81 F) ±0.4 C (±0.72 F) -270 to 1316 C (-454 to F) C 0 to 2300 C (32 to 4172 F) 100 C (180 F) ±0.8 C (±1.44 F) 0 to 2338 C (32 to F) mv C 4mV ±30microvolts -50 to 1000mV 12 The Interface Solution Experts

13 Programmable RT, T/C, Ohms, mv Figure 4. STA (TPRG) imensions 55mm (2.1 in) 118mm (4.6 in) 131mm REF. (5.17 in) 136mm REF. (5.35 in) REAY INPT TRIP 1 TRIP 2 FALT 52mm REF. (2.06 in) COM P OWN ECT 100mm (3.9 in) C L TAG STA SAFETY TRIP ALARM 47mm REF. (1.87 in) 123mm (4.8 in) Table 5. STA (TPRG) Terminal esignations Input Type Top Terminals (Left to Right) T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 RT, Ohm, Potentiometer, T/C & mv Inputs See Figure 4 MR MR +Io Source -Io Source +Io Sink +Vo -Vo -Io Sink Output Type Middle Terminals (Left to Right) Fault Alarm (SPT Relays) NO3 CM3 NC3 Output/Power Type Bottom Terminals (Left to Right) B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 3PRG (SPT Relays) NO CM1 NC1 NO2 CM2 NC2 Not sed AC or C ACC or CC GN NOTES: 1. Terminal blocks can accommodate AWG solid wiring. 2. ±Io/±Vo labeling is present only when the unit is equipped with the Analog Output (-AO) option. 3. Your input power requirement (AC or C / ACC or CC) will depend upon your unit s power need. KEY: AC or C = Power Input ACC or CC = Power Input CM = Relay Common GN = Ground Io = Current Output MR = Manual Reset NO = Normally Open NC = Normally Closed Sink = Current Sink Source = Current Source SPT = Single-Pole/ouble-Throw Vo = Voltage Output The Interface Solution Experts 13

14 Programmable RT, T/C, Ohms, mv Figure 5. Sensor Hook-p Guide Thermocouple and Millivolt Input 2-Wire RT or ecade Resistance Box 3-Wire RT or ecade Resistance Box 4-Wire RT or ecade Resistance Box Potentiometer Input Figure 6. STA (TPRG) Hook-p iagram MILLIVOLT _ SORCE OR T/C + SIMLATOR OHMS OR RT SIMLATOR REAY INPT TRIP 1 TRIP 2 FALT COM P OWN ECT TAG *Power Supply for unit is determined by configuration ordered. STA SAFETY TRIP ALARM POWER SPPLY GN The Interface Solution Experts

15 Security Settings The password security function of the STA is controlled by a single jumper inside the top of the unit housing. You will need to remove the top cover in order to access the jumper. The password jumper setting will default to Password Required (Pins 1 and 2). The default security password is 1. This is valid until the password is changed to another value. Password Setting The STA can operate in one of three password modes. Full Access (Security Jumper set to Pins 2 and 3) Complete access to the STA confi guration menu is permitted with no password required for any read or write operations. STA Programmable RT, T/C, Ohms, mv Password Required (Security Jumper set to Pins 1 and 2) A one to four-digit access code is required to gain access to the STA confi guration menu. If the correct code is entered, full read and write operation is permitted. If an incorrect code is entered, WRONG PASW will appear for 3 seconds, and return user to View menu, with read-only access to the View menu (see Figure 8). No Access (Security Jumper removed) The user is limited to read-only access to the View menu. SYS LOCK will appear if user attempts to enter Main menu by entering. Enter a second time to return to View Menu. Note: These security settings are only applicable to access via the front panel pushbuttons. Security can be bypassed using the Transfer tility Software. See Transfer tility Software section for more information. Figure 7. Setting the Internal Jumper for Password Security ON or OFF STA (TPRG) TOPSIE REMOVE PANEL BY NSCREWING TOP FOR SCREWS SET PASSWOR SECRITY PASSWOR SECRITY IS OFF. NO PASSWOR REQIRE. PASSWOR SECRITY IS ON. PASSWOR REQIRE. FRONT BACK NO ACESS. The Interface Solution Experts 15

16 Programmable RT, T/C, Ohms, mv STA Configuration The STA (TPRG) operating parameters are set using the pushbuttons found on the instrument s front panel. This section describes the steps in order to confi gure your STA. There are three pushbuttons on the unit s front panel; P, OWN and ECT. Together with the prompts displayed on the LC, these are used to access menus, and to view and change the settings. se ECT as your Enter button, to make your selections. se the P and OWN buttons to navigate within the menus. Note: If the Security jumper is removed (see Figure 7.) entering ECT will cause SYS LOCK to appear if user attempts to enter Main menu. nder fault conditions, the STA will display the error message describing the fault (see Table 7 for list of messages) which can be cleared from the Reset Fault menu or by power cycling the unit. Figure 8. View Menu TOP LEVEL MEN (isplay of Variable) MAIN Menu View Menu Figure 8 gives an overview of the View menu. pon power-up, the STA displays a SYS INIT message until the power up self test is complete. In normal operation the View menu will display the variable as confi gured. This can be the process variable, the analog output variable, or both being toggled (Refer to Confi guring the Options Menu for more details). 1. From the display, press OWN. 2. If the -AO option is present, and the unit is NOT confi gured to toggle, the other variable will be displayed. Continue pressing OWN to view the Analog output zero, Analog output full, trip point (AL1), trip point (AL2) and fi nally returning to display measured value. 3. Enter Main Menu at any point by pressing ECT. If no Analog Output If toggling vars isplay of other var XXXXX ZERO XXXXX FLL XXXXX AL1 X* If toggling vars If no Analog Output MAIN Menu MAIN Menu MAIN Menu MAIN Menu XXXXX AL2 X* MAIN Menu 16 The Interface Solution Experts

17 Programmable RT, T/C, Ohms, mv Main Configuration Menu Figure 9 gives an overview of the Main Confi guration menu. pon power-up, the STA displays the variable(s) as confi gured via the Confi gure Options menu. Pressing the button accesses a series of displays that show, in succession, the settings currently stored in unit memory. epending upon whether or not the Security Jumper has been installed (Figure 7), pressing ECT will access either the fi rst screen in the main confi guration menu, INPT, the password code query screen, ENTER PASS or the SYS LOCK screen. 3. If you have entered the correct password, the sensor confi guration menu, INPT, will be accessed. If not, the display will show a WRONG PASS message. 4. From WRONG PASS, wait three seconds to go back to the View menu. se the P and OWN buttons to view the settings in the View menu. Note: The menu to set or change the password stored in STA memory is detailed in the Password Confi guration section of the manual. Once the Main Menu has been accessed, the OWN button is used to move through all of the sub-menus in a loop. Pressing the ECT button accesses the fi rst screen of the sub-menu shown on the LC. Note: STA is programmed to time out from the confi guration menu after 5 minutes of inactivity. When trimming the unit, 30 minutes of inactivity are allowed before the time out. If the unit times out, the previous settings will be reapplied. Password This menu is bypassed if the Password Security is OFF (if the jumper is not installed then no access is allowed). To access the security jumpers, you must remove the top cover (refer to Figure 7). Refer to the Password Confi guration section of this manual for a more detailed description of the password feature. 1. If the Password Security is ON, pressing ECT from the display of the process variable input will bring up the ENTER PASS screen. 2. Press ECT again to enter the PASS screen. se the P and OWN buttons to select correct password (default value is 1 ). When the password is displayed, press ECT. Note: If the correct password is not known, the password can be determined by either setting password security to OFF and entering the menu system, or using the PC Transfer tility to download a confi guration with a known password. The Interface Solution Experts 17

18 Programmable RT, T/C, Ohms, mv Figure 9. Main Menu WRONG PASS (if incorrect PW) ENTER PASS PASS XXXX (PW required) = Inc. count (if correct PW) = ec. count PROCESS VALE ISPLAY (Full access) (No Access) P VIEW menu OWN VIEW menu SYS LOCK LOCK MOE = P Key = OWN Key = ECT Key = No action = No action PW = Password INPT SENSOR TYPE menu SCALE INPT SCALE INPT menu TRIM INPT TRIM INPT menu ALARM ALARM menu AOT AOT menu If no -AO option SCALE AOT TRIM AOT If no -AO option SCALE AOT menu TRIM AOT menu OPTNS OPTNS menu PASW PASW menu RESET FALT RESET FALT EXIT EXIT menu 18 The Interface Solution Experts

19 Programmable RT, T/C, Ohms, mv Configuring the Input Figure 10 gives an overview of the Confi guration Input menu. This allows you to select what type of sensor will be used with the SPA unit. If the Password Security is OFF, the password submenu is bypassed, and the INPT menu is accessed by pressing ECT from the View menu. 1. From the INPT display, press ECT. 2. At SENSR TYPE press ECT. se the P or OWN arrow buttons to scroll through the options in the Sensor Selection List box, for input type. The default display for this menu is always the current confi guration. 3. When the display shows the type of input that you choose to use, press ECT. 4. If you selected an RT or T/C input, use the P and OWN buttons to select RT or Thermocouple that will be used; press ECT. Next, you will be prompted to select the temperature units. se the P and OWN buttons to choose and press ECT to continue to the next menu. 5. Next, the INPT ZERO appears. Press ECT and use the P or OWN buttons to defi ne the input range. Press ECT when correct value has been displayed. 6. Next, the INPT FLL appears. Press ECT and use the P or OWN buttons to defi ne the input range. Press ECT when correct value has been displayed. Note: If the input variable goes 1% out of the range defi ned by INPT ZERO and INPT FLL, the fault relay will latch in an error state, and the ERROR OOR (Out of Range) status message will be displayed. 8. The next display is the SCALE INPT menu. To skip the rest of the confi guration menus and return to the process variable display, press the OWN until you reach EXIT, and press ECT. Refer to EXIT section of this manual for more information. Figure 10. INPT Menu INPT SENSR TYPE INPT ZERO EXIT SENSR INPT FLL SCALE INPT menu se the P and own buttons to cycle through the lists Sensor Selection List RT 2WIRE RT 3WIRE RT 4WIRE MV OHMS 2WIRE OHMS 3WIRE OHMS 4WIRE T/C POT : mv, Ohms and Potentiometer Value Change: XX.XX EG Value Change: XX.XX EG : T/C and RT T/C Selection List: T/C J T/C K RT Selection List: P P P P P P P P P P P P Ni Cu Temp Selection List: EG C EG F KELVIN EG R 7. EXIT SENSR appears. If all values in this parameter have been set, press ECT. If not, return to the menu and set your values. The Interface Solution Experts 19

20 Programmable RT, T/C, Ohms, mv Scaling the Input Figure 11 gives an overview of the Input Scaling menu. Scaling allows you to take your PV (Process Variable) reading and transform it to a custom engineering units range. PV is the unit read after selecting your input type. For example, choosing a Resistance input would then produce a PV displayed in ohms. Also known as Smart Ranging, scaling of the STA (TPRG) allows you to set the zero and full scale values of the input from the intended application, without having to connect the unit to any calibration equipment. 5. SCALE FLL appears. Press ECT to enter the menu. Enter the value you wish as your full scaled range. This value will appear when you are at the full end of your range. Press ECT. 6. EXIT SCALE appears. If all scaling parameters have been set, press ECT. The next menu selection to appear is TRIM INPT. Figure 11. SCALE INPT Menu SCALE INPT 1. At the SCALE INPT display, press ECT. 2. SCALE MOE appears; press ECT. Choose whether or not to enable scaling. This will be confi gured in the next menu. Select SCALE OFF or SCALE ON and press ECT. Scale Mode This allows you to customize your display for your application. For example, if your process is sending a reading to the STA and you wish to view the input as 0-100% then this can be accomplished with the Scale Mode feature. 3. The SCALE EG prompt is brought up. Press ECT and choose the desired fi ve character string to be displayed. While editing the string, the current position being edited will be alternated with a ^ character. se the P and OWN button to select the correct character. Pressing ECT will move to the next position. If you selected SCALE OFF in the SCALE MOE menu, the menu skips to Step 6. If you selected SCALE ON, proceed to Step Next, SCALE ZERO is displayed. se the P and OWN buttons to adjust your scaled zero value. This is the value that will be displayed when you are at the zero end of the input range. Press ECT. SCALE MOE SCALE EG SCALE ZERO SCALE FLL EXIT SCALE Selection: SCALE ON SCALE OFF ON Set Chars: X---- Value Change: XX.XX SCALE EG Value Change: XX.XX SCALE EG TRIM INPT menu OFF 20 The Interface Solution Experts

21 Programmable RT, T/C, Ohms, mv Input Trimming Figure 12 gives an overview of the Input Trimming menu. Sensor trimming increases the measurement accuracy of your instrument by matching the reading of its actual input to its scaling. The STA offers the use of a factory-confi gured trimming feature ( FCTRY TRIM ) or user-set, one-point or two-point ( SER 1 PNT OR SER 2 PNT ) trimming. Note: Trim points are restricted to the sensor s conformance range (refer to Table 4). nit default is FCTRY TRIM. If another trimming selection had been made and you wish to return to the FCTRY TRIM feature follow the instructions below. 1. Press ECT at the TRIM INPT screen. Once TRIM MOE appears, press ECT. 2. se the P and OWN buttons to reach the FCTRY TRIM display, and then press ECT. This takes you to the EXIT TRIM screen. 3. To exit, press ECT. Proceed to the ALARM menu To input user-specifi c trim values, perform the following steps: Refer to Table 6 for necessary equipment. 3. TRIM ZERO appears. To program, press ECT. Your present zero-scale trimming value is shown, use the P and OWN buttons to change value, to APPLY your value; press ECT. Once your value is present and fl ashing, press ECT again. If you selected SER 1 PNT trimming, EXIT TRIM appears. Press ECT to reach the ALARM menu. Proceed to Step 4 for SER 2 PNT trimming. 4. If you selected SER 2 PNT trimming, repeat the instructions in Step 2 for the TRIM FLL setting. Press ECT when EXIT TRIM is displayed to reach the ALARM menu. Note: In the event that captured values for TRIM ZERO and/or TRIM FLL are incorrect, ERROR TRIM will be displayed after values are applied. Press ECT to exit ERROR TRIM, which will prompt EXIT TRIM. se the P and OWN buttons to return to TRIM ZERO and/or TRIM FLL to make changes needed. 1. At the TRIM INPT display, press ECT. When TRIM MOE appears, press ECT again. se the P and OWN buttons to reach the user-set trimming menus. Press ECT once the desired parameter is displayed SER 1 PNT or SER 2 PNT. 2. RESET TRIM appears, press ECT. se the P and OWN buttons to the desired parameter, RESET NO? or RESET YES?. Select RESET YES? to clear previous trimming adjustment values, or RESET NO? to keep them. Resetting will keep trimming enabled, however no adjustment will be made to the input value. If the input is about to be trimmed, then this step is unnecessary The Interface Solution Experts 21

22 Programmable RT, T/C, Ohms, mv Figure 12. TRIM INPT Menu TRIM INPT TRIM MOE Selection: FCTRY TRIM SER 1 PNT SER 2 PNT FCTRY TRIM RESET TRIM Selection: RESET NO RESET YES FCTRY TRIM SER 1PT TRIM ZERO TRIM FLL 1PT Change Value: XX.XX APPLY 2PT Change Value: XX.XX APPLY Capture Value: XX.XX (Flashing) 2PT Capture Value: XX.XX (Flashing) SER 1PT ERROR TRIM 1PT EXIT TRIM FCTRY TRIM ERROR TRIM ALARM menu Table 6. Necessary Equipment to Confi gure Input trimming on the STA (TPRG) evice Variable Input Simulator for Thermocouple, RT, Millivolt, Potentiometer, or ecade Resistance Box Power Supply Multimeter Specifications Variable; Accurate to ±0.05% of unit span 24Vdc, ±10% or 117/230Vac, 110Vdc (depending on model) Accurate to ±0.009% of span; e.g., HP Model 3478A 22 The Interface Solution Experts

23 Programmable RT, T/C, Ohms, mv Configuring the Alarm(s) The STA has one relay which is a Fault alarm and two user-confi gurable Trip alarms. The Fault alarm is not confi gurable by the user. The instructions below will explain the steps to follow in order to set the Trip alarms. For more information about trip points, damping, etc., please reference the Alarm Terminology section of this manual. 1. At the ALARM menu, press ECT. se the P and OWN buttons to toggle between both alarms. When the desired alarm appears, press ECT. 2. At the ALRM1 menu press ECT. At ENTER TRIP, press ECT and enter your alarm trip value. se the P and OWN buttons to select your trip value; press ECT. If you prefer to capture the input trip value instead of entering it, you must use the INPT TRIP menu. To do so, bypass the ENTER TRIP menu by using the OWN button to scroll to the menu; press ECT. Ensure that the value you wish to capture is present then press ECT. 3. Press ECT at ENTER B and enter your dead band value using the P and OWN buttons. Press ECT once your desired setting appears. 4. Pressing ECT at the SET HI/LO menu directs you to confi gure the alarm as an ALARM HI or ALARM LO. se the P and OWN buttons to reach your selection and press ECT. ALARM LO You are notifi ed if your process input drops below your trip point setting. ALARM HI You are notifi ed if your process input exceeds your trip point setting. 5. At the SET LATCH display, press ECT and choose LATCH ON or LATCH OFF using the P and OWN buttons; press ECT. Latching Alarm When a STA is confi gured with latching alarms, an alarm condition will not clear (the relay will not change states) until the input returns to a non-alarm state AN manual reset terminals are shorted. The manual reset terminals, labeled MR are located on the top row of terminals on the STA (see Table 5). 6. At the ENTER ELAY display, press ECT. sing the P and OWN buttons enter the desired value (range is seconds); press ECT. elay When your unit is in an alarm condition, the delay is the amount of time you set (0-120sec) to elapse before a relay trips. 7. If you are to program Alarm 2, use the P and OWN buttons to reach ALRM2 and repeat the steps performed from Alarm 1 using the appropriate values and settings. If you have completed your alarm confi gurations, use the P and OWN buttons to bypass the alarm menu. To exit, press ECT at the EXIT ALRMx display. 8. At the EXIT ALARM display, press ECT, this will exit the ALARM menu. The Interface Solution Experts 23

24 Programmable RT, T/C, Ohms, mv Figure 13. ALARM Menu ALARM ENTER TRIP Value Change: XX.XX EG INPT TRIP Capture PV: XX.XX EG ALRM1 ALRM2 EXIT ALRM1 ENTER B Value Change: XX.XX EG SET HI/LO Selection: ALARM HI ALARM LO SET LATCH Selection: LATCH ON LATCH OFF EXIT ALARM EXIT ALRM2 ENTER ELAY EXIT ALRMx Value Change: X SEC AOT menu 24 The Interface Solution Experts

25 Programmable RT, T/C, Ohms, mv Configuring the Analog Output (-AO Option) Figure 14 gives an overview of the Analog Output Confi guration menu. If your unit is equipped with the -AO option, use this menu for confi guration. 1. Press ECT at the AOT display. This sends you to the AOT section. Press ECT and use the P and OWN buttons to toggle between current and voltage. When the selection you desire is displayed, press ECT. 2. Once you reach the SET AMP fi eld, you may skip the damping parameter, by using the OWN button to reach the next fi eld. To set damping, proceed to Step 3. amping Output damping applies fi ltering to slow the response of the output so that momentary input variations reduce output spikes. The time setting (0-30 seconds) defi nes how long it takes for the output to reach 63% of the target value. 3. To set damping, press ECT at the SET AMP display. se the P and OWN buttons to enter a value between 0 and 30 seconds; press ECT. 4. Press ECT at FAIL MOE to program the setting. Choose from FAIL HIGH, FAIL LOW or HOL LAST then press ECT. This sends you to EXIT AOT. HIGH/LOW Choosing either of these options will send the output to a High or Low (see Specifi cations table), respectively. This can also be translated as 90% of the output s zero value. HOL LAST This will output the last value present before the failure. Figure 14. AOT Menu AOT AOT SET AMP FAIL MOE EXIT AOT Selection: VOLT CRNT Value Change: XX SEC Selection: FAIL HIGH FAIL LOW HOL LAST SCALE AOT menu The Interface Solution Experts 25

26 Programmable RT, T/C, Ohms, mv Scaling the Analog Output (-AO Option) Figure 15 gives an overview of the Analog Output Scaling menu. Follow these instructions to scale the analog output after you have performed the confi guration. Note: When using the front panel pushbuttons to enter your scaling values, you may enter only values to two decimal places (hundredths). 1. At the SCALE AOT display, press ECT. 2. Press ECT at the AOT ZERO parameter and enter the value you want to output when your input is at zero. Press ECT. 3. Press ECT at the AOT FLL screen. Enter the value you want to output when your input is at full scale. Press ECT. 4. EXIT SCALE appears. If all scaling parameters have been set, press ECT. Figure 15. SCALE AOT Menu SCALE AOT AOT ZERO AOT FLL EXIT SCALE Value Change: XX.XX MA/VOLT Value Change: XX.XX MA/VOLT TRIM AOT menu Trimming the Analog Output (-AO Option) Figure 16 gives an overview of the Analog Output Trimming menu. Output trimming increases the measurement accuracy of the STA by calibrating its analog output to the device that is receiving the output. This ensures that the instrument is being correctly interpreted. Connect the unit as shown in Figure 17 and allow fi ve minutes for warm up and stabilization. 1. At the TRIM AOT display, press ECT. 2. TRIM ZERO appears. Press ECT. The value 0.00 (ma or V depending on the set up) is shown. While monitoring your reading on the meter, use the P and OWN buttons to adjust the output to the desired level. se the meter in the set up to monitor the output as it is adjusted. When the output is set as desired, press ECT. Note: The value on the LC is an adjustment to the AOT ZERO or FLL value. This adjustment is limited to 10% of span. 3. Press ECT at TRIM FLL and repeat Step 2. Press ECT. FCTRY TRIM is shown on the display. 4. If you wish to reset the user-confi gured trimming values and use factory trimming, press ECT at the FCTRY TRIM screen. se the P and OWN buttons to choose YES ; press ECT. TEST AOT is brought up on the display. By selecting NO at the FCTRY TRIM screen, the user-confi gured trim values will be used. 5. In order to check output performance and accuracy, you may want to perform an output test. If you choose to enable this test, follow the instructions in Step 6. To bypass this feature, use the OWN button and scroll to EXIT TRIM. 6. To enable the analog output test, press ECT at the TEST AOT display. se the P and OWN buttons to set your output test value and press ECT. EXIT TRIM appears; press ECT. 26 The Interface Solution Experts

27 Programmable RT, T/C, Ohms, mv Figure 16. TRIM AOT Menu Figure 17. STA (TPRG) Trimming Hook-p iagram TRIM AOT MILLIVOLT _ SORCE OR T/C + SIMLATOR OHMS OR RT SIMLATOR TRIM ZERO Value Change: XX.XX MA/VOLT REAY INPT TRIP 1 TRIP 2 FALT TRIM FLL FCTRY TRIM Value Change: XX.XX MA/VOLT Selection: RESET NO RESET YES *Power Supply for unit is determined by configuration ordered. POWER SPPLY* GN - + COM TAG STA SAFETY TRIP ALARM P OWN ECT HOOK-PS FOR OTPT TRIMMING TEST AOT EXIT TRIM Value Change: XX.XX MA/VOLT MLTIMETER OR CS + MLTIMETER OR CS EXTERNAL POWER SPPLY + + MLTIMETER OR CS + CRRENT OTPT SORCE CRRENT OTPT SINK VOLTAGE OTPT OPTNS menu The Interface Solution Experts 27

28 Programmable RT, T/C, Ohms, mv Configuring the Options Figure 18 gives an overview of the Options Confi guration menu. You may confi gure the process variable display, decimal places, 50/60Hz fi lter selection, display mode, and the run a display test from this menu. To confi gure STA options, follow the steps below. 1. At the OPTNS screen, press ECT. 2. SPLY MOE appears. Press ECT to enter the menu. Choose between PV, AOT and PV + AOT by using the P and OWN buttons. Press ECT. 3. Next, the SET PS display appears. Press ECT. Scroll through the available choices by using the P and OWN buttons and press ECT once you have made your selection. 4. SET FILTR appears; press ECT. Here, you must select the proper line frequency of your AC source 50Hz or 60Hz; press ECT. 5. SPLY TEST appears; press ECT. isplay test is executed and iterates through fi ve different character patterns (this ensures all LC segments function properly). 6. FCTRY appears. sing the P and OWN buttons choose between RESET NO? and RESET YES? ; press ECT. When resetting unit to factory default, unit is set with the following confi guration: 4 wire resistance: ohms Scaling: disabled Alarms trip: 2000, at high Current output: EXIT OPTNS appears. Press ECT. Proceed to the PASW menu. Figure 18. OPTNS Menu OPTNS SPLY MOE SET PS SET FILTR Selection: PV AOT PV + AOT Selection: ATO XXXXX XXXX.X XXX.XX XX.XXX Selecton: 50 HZ 60 HZ SPLY TEST isplay test is executed, returns to FCTRY. FCTRY Selecton: RESET NO RESET YES EXIT OPTNS PASW menu 28 The Interface Solution Experts

29 Programmable RT, T/C, Ohms, mv Password Configuration Figure 19 gives an overview of the Password Confi guration menu. The PASW menu, is for setting a new password. 1. At PASW, press ECT. This puts you in the PASS menu. The previously saved password appears. 2. se the P and OWN buttons to set a new password to any number between 0 and Press ECT. 3. The EXIT PASW appears. Press ECT, to exit, RESET FALT menu will appear. Figure 19. PASW Menu Reset Fault Figure 20 gives an overview of the Reset Fault menu. 1. At RESET FALT, press ECT. 2. se the P and OWN buttons between RESET NO? and RESET YES?. Press ECT. 3. The EXIT option appears. Press ECT, to exit Main Confi guration Menu or use the P and OWN buttons cycle through Main Confi guration Menu. RESET FALT will clear all input related faults. All unit faults must be cleared by power cycling the unit. If a fault is still present after these steps, please contact Customer Service for further assistance. Refer to Table 7 for a full list of STA diagnostic messages and corrective actions. PASW Figure 20. RESET FALT RESET FALT PASW Value Change: XXXX PASS EXIT PASW Selection: RESET YES? RESET NO? EXIT RESET FALT menu The Interface Solution Experts 29

30 Programmable RT, T/C, Ohms, mv Configuration Exit Figure 21 gives an overview of the Confg Exit menu. 1. At EXIT, press ECT. 2. If no error is present use the P and OWN buttons between SAVE NO? and SAVE YES?. 3. If SAVE NO? is selected, you will be returned to View menu and no changes will be applied to unit (previous confi guration will remain unchanged). 4. If SAVE YES? is selected, you will be returned to View menu and changes will be applied to unit and stored in non-volatile memory. 5. If error is present two options are available ERROR LIST and ERROR NO. se the P and OWN buttons to cycle these two options. 6. If ERROR LIST is selected, you see the list of confi guration errors, press ECT and this will return you to the Main menu to make changes where needed. 7. If ERROR NO is selected, you will be returned to View menu and no changes will be applied to unit (previous confi guration will remain unchanged). STA iagnostic Messages Every STA is subjected to a complete suite of operational checks and tests prior to its shipment. Occasionally, however, units can sustain damage in transit from the factory to the user. The STA is also equipped with a full set of internal diagnostics that check operation and confi guration upon power-up. If there are problems with the unit, or with confl icting operating parameter settings, the LC will display an error message upon unit start-up, and the fault alarm will remain set. Identical diagnostics are performed in the background during run time. If a fault is detected, the fault alarm will immediately be set, and an error message will be displayed. Table 7 provides a full list of diagnostic messages and corrective actions. Figure 21. EXIT Menu EXIT (no error) Selection: SAVE NO? SAVE YES? VIEW menu (error) Selection: ERROR LIST? ERROR NO? NO LIST Errors List: XXXXX XXXXX XXXXX MAIN menu 30 The Interface Solution Experts

31 Programmable RT, T/C, Ohms, mv Table 7. STA iagnostic messages and corrective actions Error Message SYS INIT ERROR CKSM ERROR CONFIG WIREn BROKE WIRES BROKE ERROR OTOF/ LIMIT ERROR INSAT ERROR OOR ERROR LINE/ RES ERROR CALIB ERROR FCTRY/ INFO ERROR AC ERROR RJC ERROR RLAYF ERROR RLAY1 ERROR RLAY2 ERROR SWARE ERROR HWARE What it Means The system is completing initialization The configuration stored in non-volatile memory is invalid ser has reconfigured the unit with an illegal configuration A specific wire was detected as broken ndetermined wire broken The measured resistance / voltage was outside the RT or Thermocouple table s range Input saturation condition (input reached 110% of calibrated range) Input has gone outside the legal range (as defined by the input LRV and RV by more than 1%) Excessive lead resistance Calibration data is bad Factory information is bad General AC failure Reference Junction Compensation RT burnout Fault alarm failure Trip alarm 1 hardware failure Trip alarm 2 hardware failure General software failure detected by diagnostics General hardware failure detected by diagnostics What to o Wait. Operation should commence in a few seconds. sing the menu system, trigger the unit to use the FCTRY selection in the options menu causing it to reset to factory configuration. Next configure as appropriate for the application. sually caused by changing the input range, or scaled range such that the trip points and/ or deadband settings have become illegal. Reconfigure with legal values. Repair the broken wire(s), and use the menu system to RESET FALTS or cycle power. Check the input and/or the selected input mode/sensor type (specifically a RT s alpha value), and use the menu system to RESET FALTS or cycle power. Check the input signal to ensure that it is within the sensor limits and use the menu system to RESET FALTS or cycle power. Check the input and/or the input pper and Lower Range settings and use the menu system to RESET FALTS or cycle power. Check sensor lead resistance. A resistance over 35 ohms is excessive (5 ohms for the Cu RT). se the menu system to RESET FALTS or cycle power. Cycle power to the unit. If the error occurs again, contact MII Customer Support to arrange for a return. Note: The Manual Reset (MR) contact does not affect the fault relay. The Interface Solution Experts 31

32 Programmable RT, T/C, Ohms, mv STA Transfer tility Software Provided with the STA is a Transfer tility Software program. This allows you to upload/download, view and print your instrument s confi guration. Figure 22. STA (TPRG) PC Hook-p iagram PC Installing the Transfer tility Software Refer to Table 8 for the equipment needed. 1. Insert the Moore Industries Interface Solution PC Confi guration Software C into the C drive of the PC. Access the C and open the STA Transfer tility Software folder. 2. ouble-click the installation program located in the folder. Follow the prompts to correctly install the program. TO SERIAL (COM) PORT OF PC To SB (COM) Port of PC REAY INPT TRIP 1 TRIP 2 FALT COM TAG P STA SAFETY TRIP ALARM OWN ECT *Power Supply for unit is determinded by configuration ordered. POWER SPPLY* GN - + Connecting the STA to the PC To connect the STA unit to your PC use the RS-232 or SB end of the cable to the PC s COM port. See Table 8 for information on the necessary equipment. Table 8. Necessary Equipment for using the STA Transfer tility evice Specifications Power Supply Personal Computer (Optional) Moore Industries Transfer tility Software (Optional) Communication Cable or SB Cable (Optional) 24Vdc, ±10% or 117/230Vac, 110Vdc (depending on model) based (or faster) IBM PC, or 100% compatible; 4Mb free RAM; 8Mb recommended; 20Mb free disk space on hard drive (More RAM & hard disk space is required for Windows NT, 2000, XP, or Vista) Microsoft Windows NT, 2000, XP, or Vista 1 (one) serial port (COM 1, 2, 3, or 4) set to 19.2kbaud, no parity, 8 data bits, and 1 stop bit or one available SB port (with optional SB cable) Version 1.0 or greater, successfully installed to the hard drive Part# Communications Cable A or optional SB cable, Part# A 32 The Interface Solution Experts

33 Transfer tility Software Summary Figure 23. STA (TPRG) Main PC Screen STA Programmable RT, T/C, Ohms, mv The Transfer tility Software is made up of these sections: 1. Program Status isplays the activity of the connected unit. It will display such messages as: Reading STA Info, Idle, Monitoring Variables and Monitor Fail. 2. STA Status Indicates if there are problems or faults with the instrument. 3. Process Variables isplays Process Variable and Reference Junction Compensation readings. 4. STA evice Info Indicates device identifi cation and software revision. 5. Progress isplay indicates instrument communication progress. 6. Communications Notifi es user of current PC connection/communications status. 7. Tool Bar/Status Bar rop down menus and corresponding icons allow you to perform various functions within the Transfer tility. Refer to the Status and Tool Bar Legend for a complete description. 8. evice Configuration isplays current device confi guration. The window lists data source, model number (if device connected), input type, scaling, display settings, alarm settings, and analog output settings. The Interface Solution Experts 33

STA SIL 2 and SIL 3 Capable Programmable Current/Voltage and RTD/Thermocouple Safety Trip Alarms

STA SIL 2 and SIL 3 Capable Programmable Current/Voltage and RTD/Thermocouple Safety Trip Alarms R February 2017 Description Part of the Moore Industries FS FUNCTIONAL SERIES, the exida SIL 2 and SIL 3 certified Safety Trip performs as a logic solver and acts on potentially hazardous process conditions;

More information

TCS. Description. Features. IECEx. Temperature Concentrator System Multi-Channel Transmitter

TCS. Description. Features. IECEx. Temperature Concentrator System Multi-Channel Transmitter INPUT READY FAULT 1 FAULT 2 CONVERTER TCS System September 2010 Description The TCS System substantially reduces the cost of transmitting multiple temperature sensor measurements in general purpose and

More information

THZ 2 & TDZ 2 THZ 2 & TDZ. 2 Programmable Smart HART. TPRG Programmable Smart HART. Temperature Transmitter and Display. November D

THZ 2 & TDZ 2 THZ 2 & TDZ. 2 Programmable Smart HART. TPRG Programmable Smart HART. Temperature Transmitter and Display. November D November 007 35-797-01D THZ & TDZ TPRG THZ & TDZ Table of Contents Introduction...4 About this Manual... 4 The THZ and TDZ...4 Model and Serial Numbers... 4 Specifications...5 Input Type and Accuracy Table...

More information

NCS MIM. with MODBUS Interface. NET Concentrator System. September A. with MODBUS Interface

NCS MIM. with MODBUS Interface. NET Concentrator System. September A. with MODBUS Interface September 2003 288-766-00 A NCS MIM with MODBUS Interface NCS MIM with MODBUS Interface Table of Contents The...3 About this Manual...3 The MODBUS Interface (MIM)... 4 Specifications MIM...5 Connecting

More information

CPT CPT HLPRG. PC-Programmable Signal. Isolater/Converter. PC-Programmable Signal Isolater/Converter. January B

CPT CPT HLPRG. PC-Programmable Signal. Isolater/Converter. PC-Programmable Signal Isolater/Converter. January B January 2004 225-708-00 B CPT HLPRG CPT All product names are registered trademarks of their respective companies. Table of Contents Introduction...4 About this Manual... 4 The CPT...4 Model and Serial

More information

dual-line 6-dIGIt process MeteR

dual-line 6-dIGIt process MeteR dual-line 6-dIGIt process MeteR ProVu Se r i e S provu Model pd6000 0-20 ma, 4-20 ma, 0-5 V, 1-5 V, and ±10 V Inputs NEMA 4X, IP65 Front Universal 85-265 VAC or 12/24 VDC Input Power Large Dual-Line 6-Digit

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate RTD Temperature Panel Meter / Controller Features Factory calibrated for 100Ω platinum, 10Ω copper & 120Ω nickel RTDs 2, 3 or 4-wire connection with lead resistance compensation

More information

SFY Functional Safety Frequency-to-DC Transmitter with Display

SFY Functional Safety Frequency-to-DC Transmitter with Display Functional Safety -to-dc March 2017 Description The SFY Functional Safety SIL 3 capable -to-dc is part of Moore Industries FS Functional Safety Series. It monitors frequency, period, high or low pulse

More information

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 4-20 ma & Relay Output Features 4-20 ma, ± 10 V, TC & RTD Inputs 12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 24 VDC @ 200 ma Transmitter Power Supply Options Type

More information

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications LAUREL ELECTRONICS, INC. Laureate RTD Temperature Panel Meter / Controller Features Factory calibrated for 100Ω platinum, 10Ω copper & 120Ω nickel RTDs 2, 3 or 4-wire connection with lead resistance compensation

More information

SPA TPRG. Thermocouple Limit Alarm Trips. Site-Programmable RTD & April D. Site-Programmable RTD & Thermocouple Limit Alarm Trips

SPA TPRG. Thermocouple Limit Alarm Trips. Site-Programmable RTD & April D. Site-Programmable RTD & Thermocouple Limit Alarm Trips April 2016 224-721-00D SPA TPRG SPA The Interface Solution Experts 1 TPRG Quickstart Guide Use the front push-buttons to quickly and easily setup the SPA for your application. After programming your alarm

More information

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR QLC MANUAL 013114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING

More information

NOW A PRODUCT! 1/4 DIN Auto/Manual Station. The Interface Solution Experts. The Interface Solution Experts. PS532 V6 March 2017

NOW A PRODUCT! 1/4 DIN Auto/Manual Station. The Interface Solution Experts. The Interface Solution Experts. PS532 V6 March 2017 NOW A 5 3 2 The Interface Solution Experts PRODUCT! 5 3 2 1/4 DIN Auto/Manual Station The Interface Solution Experts PS532 V6 March 2017 GENERAL DESCRIPTION The 532 Auto/Manual Station ensures the integrity

More information

HIT/HIX HART Isolator

HIT/HIX HART Isolator / Isolator December 2017 Description Moore Industries Isolators provide highly economical solutions to common and costly problems that plague many of today s smart process loops. Protect and enhance your

More information

DFI 7000 DIGITAL FORCE INDICATOR USER S GUIDE 1.0 INTRODUCTION 2.0 DESCRIPTION. 2.1 Configuration. 2.2 Specifications

DFI 7000 DIGITAL FORCE INDICATOR USER S GUIDE 1.0 INTRODUCTION 2.0 DESCRIPTION. 2.1 Configuration. 2.2 Specifications DFI 7000 DIGITAL FORCE INDICATOR USER S GUIDE 1.0 INTRODUCTION The DFI 7000 Signal Conditioner-Indicator is a complete 4-1/2-digit signal conditioner and indicator housed in a 1/8 DIN case. This unit provides

More information

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA SST7000 SST7100. Speed Switch / Transmitter

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA SST7000 SST7100. Speed Switch / Transmitter 5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL 33309 3211 Fruitland Ave Los Angeles, CA 90058 SST7000 SST7100 Speed Switch / Transmitter Installation and Operation Manual Rev. C P/N145F-13112 PCO 00009270

More information

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 12/99 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC 1000 and UDC 1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers

More information

PD765 TRIDENT. Trident Series Process & Temperature Meters.

PD765 TRIDENT. Trident Series Process & Temperature Meters. PD765 Trident Series Process & Temperature Meters TRIDENT PROCESS & Temp 4-20 ma, ± 10 V, TC & RTD Inputs 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) Type 4X, NEMA 4X, IP65 Front 1/8 DIN Shallow

More information

Trident and Trident X2 Digital Process and Temperature Panel Meter

Trident and Trident X2 Digital Process and Temperature Panel Meter Sign In New User ISO 9001:2008 Certified Quality System Home Products Online Tools Videos Downloads About Us Store Contact Policies Trident and Trident X2 Digital Process and Temperature Panel Meter Products

More information

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature

More information

Tempco Instruction Manual

Tempco Instruction Manual Tempco Instruction Manual 1/16 DIN Solid State Temperature Controller Relay Output Solid State Output For Heating Model Numbers: TEC-901, TEC-902, TEC-905 Temperature controls in this series are designed

More information

PIECAL 322 Automated Thermocouple Calibrator Operating Instructions. Product Description. Practical Instrument Electronics

PIECAL 322 Automated Thermocouple Calibrator Operating Instructions. Product Description. Practical Instrument Electronics PIECAL 322 Automated Thermocouple Calibrator Operating Instructions Product Description Easy to use With the PIECAL 322-1 you can check & calibrate all your thermocouple instruments and measure thermocouple

More information

PD765 TRIDENT. Trident Series Process & Temperature Meters.

PD765 TRIDENT. Trident Series Process & Temperature Meters. PD765 Trident Series Process & Temperature Meters TRIDENT PROCESS & Temp 4-20 ma, ± 10 V, TC & RTD Inputs 4-Digit Display, 0.56" (14.2 mm) or 1.20" (30.5 mm) Linear or Square Root with Low-Flow Cutoff

More information

Intrinsically Safe Temperature Concentrator System

Intrinsically Safe Temperature Concentrator System Intrinsically Safe Temperature Concentrator System Up to 32 Channels per Network HART and PC configurable 2, 3 & 4-wire RTD or Thermocouple Transmitter like Sensor Diagnostics and performance, RTD ±0.1

More information

NCS EIM. with Ethernet Interface. NET Concentrator System. May C. with Ethernet Interface

NCS EIM. with Ethernet Interface. NET Concentrator System. May C. with Ethernet Interface May 2006 288-70-00C NCS EIM with Ethernet Interface NCS EIM with Ethernet Interface Table of Contents The...3 About this Manual...3 The EIM Ethernet Interface...4 Specifications EIM...5 Connecting the

More information

3690 N.W. 53rd Street Fort Lauderdale, FL SC-2124 SC-2124M. 24 Channel Universal Scanner. Installation and Operation Manual P/N 145F-11902

3690 N.W. 53rd Street Fort Lauderdale, FL SC-2124 SC-2124M. 24 Channel Universal Scanner. Installation and Operation Manual P/N 145F-11902 3690 N.W. 53rd Street Fort Lauderdale, FL 33309 SC-2124 SC-2124M 24 Channel Universal Scanner Installation and Operation Manual P/N 145F-11902 Rev. 3.30 (c) Copyright 2000, Dynalco Controls All Rights

More information

TC-9102 Series Surface Mount Temperature Controllers

TC-9102 Series Surface Mount Temperature Controllers TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may

More information

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description LAUREL ELECTRONICS, INC. Laureate Digital Panel Meter for Process and Ratiometric Signals Features Reads process signals from ±200 mv to ±600V or ±2 ma to ±5A full scale Ratiometric mode for bridges and

More information

High Voltage DC Meter

High Voltage DC Meter High Voltage DC Meter Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

The PM1000 series is a universal 4 digit LED plug-on display for transmitters with 4-20mA 2 wire output and fitted with DIN43650 connector.

The PM1000 series is a universal 4 digit LED plug-on display for transmitters with 4-20mA 2 wire output and fitted with DIN43650 connector. PM1000 SERIES PLUG-ON DISPLAY BRIGHT LED DISPLAY INDICATION RANGE -999 TO +9999 FITS TO DIN 43650 CONNECTOR PLUG-ON TO ANY TRANSMITTER WITH 4-20MA OUTPUT EASY TO SCALE ON SITE ROBUST DESIGN SET POINT OPTION

More information

ICS Regent. Guarded Analog Output Modules. 4 to 20 ma (T3480) PD-6026

ICS Regent. Guarded Analog Output Modules. 4 to 20 ma (T3480) PD-6026 ICS Regent PD-6026 Guarded Analog Output Modules 4 to 20 ma (T3480) Issue 1, March, 06 Guarded analog output modules provide 4 to 20 ma current outputs for a maximum of six user loads per module. These

More information

TC Type Range Conformity Error. J -210 C to +760 C (-347 F to F) ±0.09 C (±0.16 F) K -244 C to C (-408 F to F) ±0.1 C (±0.

TC Type Range Conformity Error. J -210 C to +760 C (-347 F to F) ±0.09 C (±0.16 F) K -244 C to C (-408 F to F) ±0.1 C (±0. LAUREL ELECTRONICS, INC. Laureate Thermocouple Panel Meter / Controller Features Factory calibrated for thermocouple types J, K, T, E, N, R, S Entire range of each thermocouple in one scale Highly accurate

More information

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS MAINTENANCE MANUAL EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS SPECIFICATIONS*... 2 INTRODUCTION... 3 DESCRIPTION...

More information

MODCELL 2050R Single Loop Controllers

MODCELL 2050R Single Loop Controllers Isolated universal process and remote set-point input Four internal set-points No jumpers required to define instrument parameters Ratio/bias on process and remote set-point Totalizer Ramp/soak profile

More information

ECT Signal Isolator/Converter

ECT Signal Isolator/Converter August 1997 Now with Dual I/O Channels Data Sheet 2.02 Description The family of signal isolators and converters delivers economical solutions for a wide variety of signal interface applications. Isolator

More information

TPE 1464 Series Pressure Transducer

TPE 1464 Series Pressure Transducer TPE 1464 Series Pressure Transducer Description The KMC TPE 1464 series of pressure transducers incorporate a gauge pressure transmitter featuring low hysteresis, excellent repeatability, and longterm

More information

Temperature Measurement

Temperature Measurement Copyright 1999-2002. All rights reserved. Web design by Sullivan Creative -1000 to +3500 and -10000 to +35000 Count Thermocouple, RTD, and Thermistor Temperature Measurement in C or F without Recalibration

More information

HIGH-VOLTAGE DC METER

HIGH-VOLTAGE DC METER HIGH-VOLTAGE DC METER Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

HTZ. Description. Features. Smart HART Humidity and Temperature Transmitter

HTZ. Description. Features. Smart HART Humidity and Temperature Transmitter March 2018 Description The HTZ Smart HART Transmitter simultaneously measures humidity and temperature in industrial, commercial, manufacturing, and HVAC applications. Based on the humidity and temperature

More information

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 Introduction Honeywell s STT 3000 family of microprocessor based smart temperature

More information

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA UM Channel Monitor.

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA UM Channel Monitor. 5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL 33309 3211 Fruitland Ave Los Angeles, CA 90058 UM-600 6-Channel Monitor Version 2 Installation and Operation Manual Rev. G P/N145F-12990 PCO 00007462 (c)

More information

User s Guide DP20. Economical Multisignal Meter for Process, Temperatures and Electrical signals. Shop online at omega.com

User s Guide DP20. Economical Multisignal Meter for Process, Temperatures and Electrical signals. Shop online at omega.com TM User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: www.omegamanual.info DP20 Economical Multisignal Meter for Process, Temperatures and Electrical signals U.S.A.

More information

Isolated Linearized RTD Input 5B34 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated Linearized RTD Input 5B34 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated Linearized RTD Input 5B34 FEATURES Amplifies, Protects, Filters, and Isolates Analog Input. Linearize a wide variety of 2 & 3 wire RTDs. (True 4-wire RTD measurements are provided by the 5B35).

More information

H3 Series. Nanmac Corporation. Dual-Line 6-Digit Temperature Meter.

H3 Series. Nanmac Corporation. Dual-Line 6-Digit Temperature Meter. H3 Series Dual-Line 6-Digit Temperature Meter Temperature J, K, T, E, R, S, B, N, C Thermocouples 100 or 1000 Ω Platinum, 10 Ω Copper, 120 Ω Nickel RTDs 1 or 0.1 Resolution Averages up to 10 RTD Sensors

More information

POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual IM2493WVP-3

POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual IM2493WVP-3 POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual General Description The POWER SERIES Plus digital switchboard meters incorporate the latest DSP microprocessor technology.

More information

Pump-Down Controller MODEL mA Input Scalable 4-20mA Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters

Pump-Down Controller MODEL mA Input Scalable 4-20mA Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters DESCRIPTION Pump-Down Controller Input Scalable Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters The Model 4052 Pump-Down Controller provides total control for duplex pumping

More information

masibus : UT-94 Page 1 of 6 INTRODUCTION SPECIFICATIONS Dimensions Document Ref No. m98a/om/101 Issue No: 08

masibus : UT-94 Page 1 of 6 INTRODUCTION SPECIFICATIONS Dimensions Document Ref No. m98a/om/101 Issue No: 08 INTRODUCTION This is a micro-controller based Universal Transmitter which retransmits the Universal Inputs given, into the required Voltage or current. This instrument provides isolation at 4 levels: (a)

More information

IPM500 Series QuickStart Manual

IPM500 Series QuickStart Manual IPM500 Series QuickStart Manual The Force of Innovation 10 Thomas Irvine, CA 92618 USA (949) 465-0900 FAX: (949) 465-0905 E-Mail: HTUfutek@futek.comUTH www.futek.com Manufacturer of Load Cells, Pressure

More information

Model No Universal Input Indicator Start-up Guide

Model No Universal Input Indicator Start-up Guide Model No. 1480 Universal Input Indicator Start-up Guide Contents 1. Setting up a unit straight out of the box... 3 1.1. Entry into Configuration mode... 3 1.2. Scrolling through Parameters and s... 3 1.3.

More information

Flomatic Smart Card TM Model FDHC-100 (Digital High-Resolution Controller) Configuration and Operation Manual

Flomatic Smart Card TM Model FDHC-100 (Digital High-Resolution Controller) Configuration and Operation Manual The Flomatic FDHC-100 is a high performance Digital positioner intended to control AC actuators, providing 450 points of resolution with quarter turn actuators ranging from 2 sec to 120 sec and rated for

More information

User's Guide. 1/16 th DIN ph Controller. Model 48PH2. Introduction

User's Guide. 1/16 th DIN ph Controller. Model 48PH2. Introduction User's Guide 1/16 th DIN ph Controller Model 48PH2 Introduction Thank you for selecting the Extech Model 48PH2 controller. This 1/16 th DIN-size controller offers dual display, high resolution measurements,

More information

TRACKER 220 SERIES. Digital Panel Indicators. A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement

TRACKER 220 SERIES. Digital Panel Indicators. A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES Digital Panel Indicators A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES INDICATORS Universal Input Analogue Output

More information

Carbon Monoxide (CO) Gas Detection and Control System

Carbon Monoxide (CO) Gas Detection and Control System Carbon Monoxide (CO) Gas Detection and Control System DESCRIPTION Gas monitor with built-in carbon monoxide (CO) sensor, wall-mounted, accepts inputs from remote devices such as other gas sensors, temperature

More information

PD7000. PROVU Dual-Line 6-Digit Temperature Meter SERIES.

PD7000. PROVU Dual-Line 6-Digit Temperature Meter SERIES. PD7000 PROVU Dual-Line 6-Digit Temperature Meter PR VU SERIES Temperature J, K, T, E, R, S, B, N, C Thermocouples 00 or 000 Ω Platinum, 0 Ω Copper, 0 Ω Nickel RTDs or 0. Resolution Averages up to 0 RTD

More information

SX90 Process Controller

SX90 Process Controller Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description

LAUREL. Laureate Digital Panel Meter for Load Cell & Microvolt Input ELECTRONICS, INC. Features. Description Description LAUREL ELECTRONICS, INC. Features Laureate Digital Panel Meter for Load Cell & Microvolt Input 20, 50, 100, 250 & 500 mv ranges Span adjust from 0 to ±99,999, zero adjust from -99,999 to +99,999

More information

LCI Load Cell Junction Box with Fault Monitor

LCI Load Cell Junction Box with Fault Monitor LCI Load Cell Junction Box with Fault Monitor User Manual www.mantracourt.co.uk The LCI Load Cell Failure Alarm Manual Chapter 1 Introduction to the LCI...2 Chapter 2 Installing the LCI...3 Figure 2.1

More information

Isolated Wideband Voltage Input 3B40 / 3B41 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated Wideband Voltage Input 3B40 / 3B41 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated Wideband Voltage Input 3B40 / 3B41 FEATURES Interfaces, amplifies, protects& filters wide-bandwidth (h0 khz) single-channel analog voltage inputs. Module provides simultaneous precision voltage

More information

OPERATIONAL MANUAL FOR 85XX

OPERATIONAL MANUAL FOR 85XX TECHNICAL DETAILS OPERATIONAL MANUAL FOR 85XX Ref. No. : m83/om/402 This is a versatile microcontroller based Scanner with a very high performance to price ratio. The features offered in this product are

More information

TRANSMITTER CONFIGURATION MANUAL

TRANSMITTER CONFIGURATION MANUAL Model 5030-881 TRANSMITTER CONFIGURATION MANUAL ACROMAG INCORPORATED 30765 South Wixom Road P.O. BOX 437 Wixom, MI 48393-7037 U.S.A. Tel: (248) 295-0880 Fax: (248) 624-9234 Email: sales@acromag.com Web:

More information

CONTENTS. Chapter 1...Description. Chapter 2...Installation. Chapter 3...Operation. Chapter 4...Calibration. Chapter 5...

CONTENTS. Chapter 1...Description. Chapter 2...Installation. Chapter 3...Operation. Chapter 4...Calibration. Chapter 5... CONTENTS Chapter 1...Description Chapter 2...Installation Chapter 3...Operation Chapter 4...Calibration Chapter 5.....Doric Viewer Chapter 6.Specifications Description Chapter 1 The Series 5000 is designed

More information

ICS Regent. Relay Output Modules. Low Power and High Power (T3446L and T3446H) PD-6017

ICS Regent. Relay Output Modules. Low Power and High Power (T3446L and T3446H) PD-6017 ICS Regent PD-6017 Relay Output Modules Low Power and High Power (T3446L and T3446H) Issue 1, March, 06 Relay output modules provide control of eight user output loads. Two types of relay output modules

More information

LCI User Manual mantracourt.com

LCI User Manual mantracourt.com LCI User Manual mantracourt.com LCI Load Cell Junction Box with Fault Monitor Contents Chapter 1 Introduction to the LCI... 2 Chapter 2 Installing the LCI... 3 Chapter 3 Setting up the LCI... 4 Sequence

More information

POWER SERIES Plus. 3 in 1 AC Voltage. Digital Switchboard Meter. User s Manual IM2493VVV-2

POWER SERIES Plus. 3 in 1 AC Voltage. Digital Switchboard Meter. User s Manual IM2493VVV-2 POWER SERIES Plus 3 in 1 AC Voltage Digital Switchboard Meter User s Manual General Description The POWER SERIES Plus digital switchboard meters incorporate the latest DSP microprocessor technology. Careful

More information

The IQ300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

The IQ300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications. IQ300 Wall Mount Load Cell Indicator Data sheet English 1.01 Introduction The IQ300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications. The high

More information

The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement

The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement Acquisition Measurement Control The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement TRACKER 220 SERIES INDICATORS Universal Input

More information

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER SERIES CMT CARBON MONOXIDE GAS TRANSMITTER INSTALLATION OPERATION AND MAINTENANCE MANUAL DWYER INTRUMENTS, INC. PO BOX 373, MICHIGAN CITY, IN. 46360 USA PHONE: 800-872-9141 FAX: 219-872-9057 Web: www.dwyer-inst.com

More information

iothinx 4500 Series (45MR) Modules

iothinx 4500 Series (45MR) Modules iothinx 4500 Series (45MR) Modules Modules for iothinx 4500 Series Feature and Benefits Easy tool-free installation and removal Built-in LED indicators for IO channels Wide operating temperature range:

More information

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES Load Cell and Weighing Indicators A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES INDICATORS Ratiometric Measurement Tare and Auto Transducer Excitation

More information

DIGITAL METERS Universal Analog Input Process Meter With Rate/Totalizer/Batch Control Features Instruction Manual

DIGITAL METERS Universal Analog Input Process Meter With Rate/Totalizer/Batch Control Features Instruction Manual DIGITAL METERS Universal Analog Input Process Meter With Rate/Totalizer/Batch Control Features 4-20 ma, 1-5 V, 0-5 V, or 0-10 V Field Selectable Inputs Full Six Digit Display for Total, 4½ Digit + Extra

More information

Amplifiers, Counters, Timers & Controls

Amplifiers, Counters, Timers & Controls Amplifiers, Counters, Timers & Controls Panel Meter 814 Counter/Timer/Rate Indicator 815-817 Speed Monitor 818-819 Signal Converter 820-822 Power Supplies/Amplifier 823-824 813 Panel Meter Panel Meter

More information

MICRO-P & MIGHTY-1 SERIES B OWNERS MANUAL

MICRO-P & MIGHTY-1 SERIES B OWNERS MANUAL MICRO-P & MIGHTY-1 SERIES B OWNERS MANUAL ELECTRO-NUMERICS, INC. 1. USER NOTES 2 TABLE OF CONTENTS 1. USER NOTES... 2 2. TABLE OF CONTENTS... 3 3. PRODUCT INTRODUCTION... 4 4. RECEIVING & UNPACKING...

More information

MICRO SERIES PROCESS DISPLAYS LARGE DIGIT MODELS

MICRO SERIES PROCESS DISPLAYS LARGE DIGIT MODELS The MICRO SERIES PROCESS DISPLAYS LARGE DIGIT MODELS Mighty-5 DPM MODELS Micro-P & Mighty-1 Mighty-1 Micro-P ELECTRO-NUMERICS, INC. Introduction The Electro-Numerics family of Digital Panel Meters and

More information

ControlMaster CM10, CM30 and CM50 Universal process controllers, 1 /8, 1 /4 and 1 /2 DIN

ControlMaster CM10, CM30 and CM50 Universal process controllers, 1 /8, 1 /4 and 1 /2 DIN User Guide Basic Functionality IM/CM/B EN Rev. Q ControlMaster CM10, CM30 and CM50 The Company We are an established world force in the design and manufacture of instrumentation for industrial process

More information

iologik 4000 Series (M) Modules

iologik 4000 Series (M) Modules iologik 4000 Series (M) s Remote I/O modules Features and Benefits I/O expansion without a backplane Active communication with MX-AOPC UA Server Supports SNMP v1/v2c Easy configuration with Modular ioadmin

More information

LDC. Flexible, Comprehensive Control of Laser Diodes. Modular Laser Diode Controller. Product Features

LDC. Flexible, Comprehensive Control of Laser Diodes. Modular Laser Diode Controller. Product Features Product Features 4 independent channels with 8 isolated outputs Laser current source modules from 200mA to 8A LD controller modules from 200mA to 2A with integrated 12W TEC 32W TEC only modules with voltage

More information

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR LC1 MANUAL 062114 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features Dimensions WIRING

More information

From lab to production, providing a window into the process. Universal Input Indicator Start-up Guide. Operating Manual.

From lab to production, providing a window into the process. Universal Input Indicator Start-up Guide. Operating Manual. Universal Input Indicator Start-up Guide Operating Manual -1- Contents 1. Setting up a unit straight out of the box 1.1. Entry into Configuration mode 1.2. Scrolling through Parameters and Values 1.3.

More information

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3 INSTALLATION MANUAL LC 200 Electronic Overload Guard Software versione PW0501 R 0.3 CONTENTS MAIN FEATURES LC 200 TECHNICAL FEATURES Page 2 SYMBOLS Page 3 WARNINGS Page 3 IDENTIFICATION DATA PLATE Page

More information

DUAL-LINE TEMPERATURE METER

DUAL-LINE TEMPERATURE METER DUAL-LINE TEMPERATURE METER PROPLUS YPP7000 J, K, T, E, R, S, B, N, C Thermocouples 100 or 1000 Ω Platinum, 10 Ω Copper, 120 Ω Nickel RTDs 1 or 0.1 Resolution Averages up to 10 RTD Sensors Automatic Cold

More information

MRC 7000 Proven Recording Reliability that Became the Industry Standard!

MRC 7000 Proven Recording Reliability that Became the Industry Standard! Data Sheet Recorder//Profiler DESCRIPTION The MRC7000 Recorder/ is a microprocessor based circular chart instrument capable of measuring, displaying, recording and controlling up to two process variables

More information

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review... TPR-6 Temperature Protection Relay Instruction Manual Ver. June 1 st 2010 2 Table of Contents 1. TABLE OF CONTENTS 1. Table of Contents... 2 2. Introduction... 3 3. Wiring Diagram... 5 4. Terminals Review...

More information

This Datasheet for the IC670ALG310. Analog Output Voltage, 8 Channel, +/-10V, 0 to 10V.

This Datasheet for the IC670ALG310. Analog Output Voltage, 8 Channel, +/-10V, 0 to 10V. This Datasheet for the IC670ALG310 Analog Output Voltage, 8 Channel, +/-10V, 0 to 10V http://www.qualitrol.com/shop/p-14493-ic670alg310.aspx Provides the wiring diagrams and installation guidelines for

More information

P/N /02 Rev. C ECO # Model 1440 Microprocessor-based Temperature Controller Installation and Operation Manual

P/N /02 Rev. C ECO # Model 1440 Microprocessor-based Temperature Controller Installation and Operation Manual P/N 974073 06/02 Rev. C ECO # 27007 Model 1440 Microprocessor-based Temperature Controller Installation and Operation Manual 2 CONTENTS Quick Start Instructions...3 1. Introduction...6 2. Specifications...

More information

Multi Units Humidity/Temperature Transmitter. HygroViewer Model JW300 User Manual

Multi Units Humidity/Temperature Transmitter. HygroViewer Model JW300 User Manual Multi Units Humidity/Temperature Transmitter HygroViewer Model JW300 User Manual 1. Electrical Wired & Installation The power cord is a one-meter length, 22 AWG, 7 different colors for recognition. Please

More information

Process & Temperature Digital Panel Meter

Process & Temperature Digital Panel Meter Process & Temperature Digital Panel Meter TRIDENT PD765 4-20 ma, ± 10 V, TC & RTD Inputs NEMA 4X, IP65 Front Shallow Depth Case 3.6" Behind Panel Universal Power Supply 85-265 VAC Two Relays Option with

More information

CDD Carbon Dioxide Transmitter

CDD Carbon Dioxide Transmitter Introduction The OSA CO2 transmitter uses Infrared Technology to monitor CO2 levels within a range of 0 2000 ppm and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. The enclosure is designed to operate

More information

Digital Indicator Solutions

Digital Indicator Solutions Digital Indicator Solutions Loop-Powered Attachable Compact Attachable Loop-Powered Smart Compact System Loop-Powered Compact Smart System Intelligent Smart System "Intelligent" Options Dual & Display

More information

Isolated Voltage Input 3B30 / 3B31 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated Voltage Input 3B30 / 3B31 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated Voltage Input 3B30 / 3B31 FEATURES Interfaces, amplifies, & filtersanalog input voltages. Narrow-bandwidth (3Hz) single-channel single conditioning. Module provides simultaneous precision voltage

More information

Intrinsically Safe Barriers

Intrinsically Safe Barriers Intrinsically Safe Barriers Description Page No. Safety Barriers 464-472 Din Rail Isolated Barriers 473-488 477 Intrinsically Safe Barriers Product Overview We have simplified intrinsic safety! Cooper

More information

SED2 Variable Frequency Drives with Electronic (E) Bypass Options

SED2 Variable Frequency Drives with Electronic (E) Bypass Options SED2 Variable Frequency Drives with Electronic (E) Options Description The E- Options are companion packages for the family of SED2 Variable Frequency Drives (s). For information on the family of SED2

More information

SIY. Features. PC-Programmable Signal Isolator/Converter

SIY. Features. PC-Programmable Signal Isolator/Converter September 2017 Description Moore Industries Signal Isolator/Converter combines smart digital technology with advanced analog operation to deliver superior reliability, accuracy, and ease of use. The highly

More information

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Revision 0-C-041918 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document

More information

/23/05 GRT SERIES INSTALLATION & OPERATING INSTRUCTIONS

/23/05 GRT SERIES INSTALLATION & OPERATING INSTRUCTIONS 99880 11/23/05 GRT SERIES INSTALLATION & OPERATING INSTRUCTIONS ! SAFETY INSTRUCTIONS The following instructions must be observed. This instrument was designed and is checked in accordance with regulations

More information

SINGLE-CHANNEL PROCESS INDICATOR series 8001

SINGLE-CHANNEL PROCESS INDICATOR series 8001 SINGLE-CHANNEL PROCESS INDICATOR series 8001 Analog Inputs - all inputs available in one unit - Pt100 RTD type DIN 43 760 or GOST 6651-78 (range from 0 to +600 C) - TC type: J - range from 0 to +600 C

More information

EPWR Series. RoHS. Product Description. Available Products. Installation Instructions 01

EPWR Series. RoHS. Product Description. Available Products. Installation Instructions 01 01 Series RoHS Compliant Product Description The Series remote pressure transducers are designed for differential pressure applications. The sensors are remotely installed on existing plumbing runs. The

More information

MYRIAD RTU REMOTE TELEMETRY UNITS INSTRUCTION MANUAL

MYRIAD RTU REMOTE TELEMETRY UNITS INSTRUCTION MANUAL MYRIAD RTU REMOTE TELEMETRY UNITS INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR RTU MANUAL 061314 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING 8 Dwg

More information

I-7520: RS-232 to RS-485. Input: RS-232 protocol Output:RS-485/RS-422 Speed: Self Tuner 'inside, auto switching baud rate, 300~ BPS

I-7520: RS-232 to RS-485. Input: RS-232 protocol Output:RS-485/RS-422 Speed: Self Tuner 'inside, auto switching baud rate, 300~ BPS I-7520 RS-232 to RS-485 Converter I-7510 RS-485 Repeater RS-232 RS-485 I-7000 SERIES Common Specifications Isolation voltage: 3000VDC Speed: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115000 Dual watchdog

More information

Safety. 2. Configuration - Operation 2.1 RTD Selection 2.2 Driver Test Header. 3. Diagnostics 3.1 ph Input 3.2 Temperature Input

Safety. 2. Configuration - Operation 2.1 RTD Selection 2.2 Driver Test Header. 3. Diagnostics 3.1 ph Input 3.2 Temperature Input Safety 1. Installation 1.1 PT:Services 1.2 erature Compensation of 1.3 Controller Services 1.4 Driver Card Installation 1.5 Sensor Part Numbers 1.6 Sensor Wiring 2. Configuration - Operation 2.1 Selection

More information

Data Sheet T 6493 EN. TROVIS 6400 Automation System TROVIS 6493 Compact Controller. For panel mounting (front frame 48 x 96 mm/1.89 x 3.

Data Sheet T 6493 EN. TROVIS 6400 Automation System TROVIS 6493 Compact Controller. For panel mounting (front frame 48 x 96 mm/1.89 x 3. Data Sheet T 6493 EN TROVIS 6400 Automation System TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and

More information