Installers Course. Training Guide Advanced lighting controls made easy. Version 1.0

Size: px
Start display at page:

Download "Installers Course. Training Guide Advanced lighting controls made easy. Version 1.0"

Transcription

1 Installers Course Training Guide Advanced lighting controls made easy Version 1.0

2 Background Philips Dynalite is a highly specialized company whose principal occupation is to provide cutting edge solutions for lighting control. Our achievements have been recognized worldwide and Philips Dynalite is generally the system of choice for projects involving integration with thirdparty vendor s equipment and for large-scale applications. Philips Dynalite s philosophy is to provide the best solution possible for each and every project. This is the key to our success. Our considerable investment in Research & Development ensures that we remain at the forefront of our industry. Our position as a world leader in lighting management systems for the future is sustained through our total commitment to innovation. We are represented around the world by distributors and dealers who are handpicked for their ability to provide the highest possible level of service. From a stock exchange in Shanghai, to a luxury resort in Dubai, a smart home in Sao Paulo to limestone caves in New Zealand, Philips Dynalite s innovative solutions deliver intelligent light. Ongoing research and development has enabled Philips Dynalite to create secure automated systems that control tens of thousands of individual light fittings in high-rise office buildings from any location anywhere in the world. Our networks are engineered to deliver instant notification of power or system failure, and report via a LAN, internet, or through an SMS gateway to a mobile phone. This provides the assurance necessary in applications where continuous operation is vital, such as road tunnels, computer servers or cold storage units. Philips Dynalite s modular product design philosophy also improves system flexibility. Through this approach, specific application requirements can be accommodated with greatly reduced lead times. As an industry leader Philips Dynalite is committed to creating superior lighting control and energy management systems, setting new benchmarks in performance and efficiency. In receiving the International Association of Lighting Designers award for Most Innovative Product, the Philips Dynalite control system has been independently recognized as A user friendly and sensible modular approach, which takes it from sophisticated domestic settings to large architectural spaces. 2 Installers Course User Guide

3 Contents Topic 1: Infrastructure... 9 Overview... 9 Learning outcomes... 9 Cabling... 9 Networking requirements... 9 CAT 5 cable limits CAT 5 wiring diagram Recommended DyNet color coding for CAT5 cable Recommended DyNet CAT 5 data cable types Belden wiring diagram Recommended DyNet color coding for Belden cable S-Flat 6 cable limits Recommended DyNet color coding for S-Flat 6 cable Pin out conversion for RJ45 cable testers RJ12 socket connections DDPB22RJ12 Network Junction Box Termination CAT5 Instructions Flat cable instructions DyNet voltages Network architecture The DyNet Network The Physical Layer Trunk & spur network Implementing trunk & spur topology Trunk & spur network DLight III trunk &spur network Ethernet networks Multi trunk networks Network cable current limits and voltage drop DyNet 1 & 2 networks Operational differences HF Ballast installation Installation instructions Network addressing DALI network wiring Device compatibility Normal DALI DALI Multi Master Enumeration Emergency lighting Self contained luminaries Testing emergency lighting Essential supply load shedding Installers Course User Guide 3

4 Maintaining circuits by bypassing load controllers DMX End of line resistors Topic 2: Installing load controllers Overview Learning outcomes Hardware controls Service LED and switch AUX input Top set Wall mounted devices Select a suitable location Fixing the device Allow for cable entry Supply & load cable Powering up the dimmers prior to commissioning Operating environments DIN rail mounted devices Instructions Circuit breakers Multi controllers Structured wiring boxes Select a suitable location Fixing the device Wiring terminations Supply and output connections Dry contact switch input connections Network connections Topic 3: Installing panels Overview Learning outcomes Instructions Connecting data cables Factory presets Changing button configurations DLP & DL2P DR2P DPN 57 Panel network connections Dingus LSP-PRO FFC-LSP Topic 4: Installing motion sensors Overview Learning outcomes Installation instructions Installers Course User Guide

5 Mounting PIR motion sensors Mounting Ultra sonic motion sensors DUS704C motion coverage DUS804C and DUS804C-SM motion coverage DUS804C-UP ultra sonic motion coverage Motion detection lens pattern Optional motion detector lens for DUS704W Selecting sensor installation locations Sensor mounting for PE (photo electric) Infrared receiver mounting location Installing DUS704W-MB mounting brackets Topic 5: Installing touch screens Overview Learning outcomes General installation points for touch screens Installing the DTP Fixing the device Installing the DTP Fixing the Device Power supply Topic 6: Installing integration devices Overview Learning outcomes Installing the DDMIDC Features Installation notes Electrical diagram Analogue fader Installation steps Installing DDNG DPMI Using the DPMI Installation steps Electrical diagram Mounting details Connecting to a motion detector Connecting volt free inputs Install DDFCUC024 / DDFCUC Topic 7: Testing and troubleshooting Overview Learning outcomes Walk through test procedure LED tracking Luminaires Sensors Touch screens Installers Course User Guide 5

6 Troubleshooting Network Fault finding Power Supply faultfinding Panel Fault finding End of line resistors Common problems DDMIDC8 Troubleshooting Do s and don ts of dimming low voltage transformers Do s and don ts of dimming fluorescent lighting Installers Course User Guide

7

8 About this guide Guide Overview Disclaimer Copyright This guide is designed to assist in the configuration of Dynalite control devices. A working knowledge of EnvisionProject and Dynalite commissioning processes is required to effectively use this document. For more information on commissioning processes, consult the Dynalite Programmers Guide. Parameters in the software may require information that must be sourced from third party manufacturer s device details and specifications. These instructions have been prepared by Philips Dynalite and provide information on Philips Dynalite products for use by registered owners. Some information may become superseded through changes to the law and as a result of evolving technology and industry practices. Any reference to non- Philips Dynalite products or web links does not constitute an endorsement of those products or services 2011 Dynalite manufactured by WMGD Pty Ltd (ABN ). All rights reserved. Not to be reproduced without permission. Dynalite, Dimtek, DLight, DyNet and associated logos are the registered trademarks of WMGD Pty Ltd. Philips Dynalite 6/691 Gardeners Road Mascot NSW 2020 Australia P: +61 (0) F: +61 (0) E: dynalite.info@philips.com W: 8 Installers Course User Guide

9 Topic 1: Infrastructure Overview In this topic we investigate network architecture of Philips Dynalite networks, cabling requirements and terminations of different cabling types. Learning outcomes The approach to programming a Philips Dynalite system can be broadly categorized as follows: Cabling requirements of a Dynalite network Termination of data cables Topology of small networks Topology of trunk & spur networks Topology of Ethernet networks. Termination of different cabling types. Cabling Networking requirements Here are some important points to understand about cabling requirements: The system communicates over screened, stranded RS485 data cable (such as Cat5) and requires a minimum of three twisted pairs. It is recommended that the data cable is connected between devices in a daisy chain arrangement. Start at the first device then loop in then out of devices, with a single cable terminating at the last device. If it is necessary to wire the system in a star configuration the system will still operate normally but diagnosing installation network faults should this be necessary may be more difficult. Topic 1: Infrastructure Installers Course User Guide 9

10 Figure 1 Cabling A 5-way pressure pad terminal strip is provided on devices for each data cable termination. Some devices also have an RJ12 connector for temporary connection of portable programming devices. DR2P/E panels are available with 2x RJ12 connectors instead of a pressure pad terminal strip for data connection. These panels use Philips Dynalite flat network cable. Using RJ connectors speeds up the instillation time and helps to eliminate cabling errors. The flat cable supports up to 10 panels on one cable run and its maximum cable run for a single cable is limited to 100m before a network bridge is required. Note: That any data cable that is connected to an energized device is live. Data cable should not be cut or terminated while live! CAT 5 cable limits Philips Dynalite Cat5 data cable is specifically designed for high reliability RS485 network wiring. In addition to a twisted pair for RS485 data, conductors are provided to supply DC power to network powered peripherals. Conductors are shielded for maximum data integrity. The data cable is flexible, as all conductors are stranded, which also allows for robust termination into pressure plate style terminals used on most Philips Dynalite equipment. The extra thick outer jacket is mains rated for use in switchboards, and enhances the robustness of the cable. The cable is supplied in 305 meter lengths. Cable limits: Maximum Philips Dynalite devices per CAT5 cable: 100. Maximum Cat5 cable length: 1000m. 10 Installers Course User Guide

11 Figure 2 CAT5 CAT 5 wiring diagram Figure 3 CAT5 Wiring Recommended DyNet color coding for CAT5 cable COLOR Blue Mate Blue Orange Mate } Orange Green Mate } Green Brown Mate } Brown SIGNAL Data- Data+ Paralleled for +12Volts. Paralleled for Ground. Spare pair if required to repair damaged cable or can be used as a drain for static if unshielded cable used in the installation. Topic 1: Infrastructure Installers Course User Guide 11

12 Recommended DyNet CAT 5 data cable types MANUFACTURER PART NUMBER Philips Dynalite DyNet STP-Cable Belden 9503 Garland MCP3S Garland STPL5e Hartland HCK603 M & M Cable B2003CS M & M Cable B9503CS Multicables AWM E RS Components Belden wiring diagram Figure 4 Belden Wiring 12 Installers Course User Guide

13 Recommended DyNet color coding for Belden cable COLOR Black Blue White Red SIGNAL Ground Data+ Data- +12Volts/+24 Volts The recommended cable types for Belden are: #1502R #1502P S-Flat 6 cable limits Flat data cable is specifically designed for high reliability localized network wiring as found in hotel rooms and residential applications. In addition to a conductor pair for data, conductors are provided to supply DC power to network powered peripherals. Conductors have an overall shield for maximum data integrity. The data cable is flexible, as all conductors are stranded. It is designed for rapid crimp termination into RJ12 plugs for use with Philips Dynalite products with supporting RJ12 sockets. The cable is supplied in 200 meter rolls, or in pre-terminated leads of 3, 5 and 10 meter lengths. Cable limits: Maximum Philips Dynalite devices per special flat cable: 10. Maximum special flat cable length: 100m. Figure 5 Flat cable Silver White Red Yellow Green Brown Topic 1: Infrastructure Installers Course User Guide 13

14 Recommended DyNet color coding for S-Flat 6 cable COLOR SIGNAL Silver Not connected White Ground Red Data + Green Data - Yellow +12 Volts Brown Not connected Pin out conversion for RJ45 cable testers RJ12 PINS RJ45 CABLE COLOR Silver drain 2 3 White 3 4 Red 4 5 Green 5 6 Yellow 6 7 Orange RJ12 socket connections The diagram below details RJ12 socket connections: Figure 6 - RJ12 Socket Connection 14 Installers Course User Guide

15 DDPB22RJ12 Network Junction Box The DDPB22RJ12 allows for 22 DyNet flat cables of the Philips Dynalite system, to be terminated together in one location. Acting as a junction box, the DDPB22RJ12 takes advantage of the RJ12 connection system allowing for a quick install and easy implementation of a network star topology. Figure 7 Termination CAT5 Instructions Follow instructions below for CAT5 cable termination on a Philips Dynalite network. 1. Using side-cutters cut a slit at the end of the cable. Use care to ensure only the out plastic sheath is cut, avoiding the inner cores and shielding sheath. Figure 8 Topic 1: Infrastructure Installers Course User Guide 15

16 2. Locate the draw string between the outer sheath and the foil shield wrapper and using pliers pull downwards to cut a 90mm slit in the outer sheath shown in figure 8. Figure 9 Figure Using side-cutters carefully trim away the outer plastic sheath, again ensuring not to cut the inner cores. 16 Installers Course User Guide

17 Figure Locate the shield drain wire and separate from the shield s foil sheath. Once separated carefully trim away the foil shield and plastic wrap. Figure 12 Topic 1: Infrastructure Installers Course User Guide 17

18 5. Bend the Brown/Brown-White pairs back towards the outer sheath to be kept as spares. Figure Using a cable-tie secure the two cables together. Figure Installers Course User Guide

19 7. Trim away the excess from the cable tie. 8. Twist both of the shield wires together. Figure On both cables untwist the Blue/Blue-White pairs. Figure 16 Topic 1: Infrastructure Installers Course User Guide 19

20 10. Twist together the Blue wire from each pair. 11. Twist together the Blue/White wire from each pair. 12. Twist together the Green-Green/White wire from each pair. 13. Twist together the Orange-Orange/White wire from each pair. Figure Strip 10mm of sheath from each of the wires and twist together. Figure Installers Course User Guide

21 15. Fold this back on itself to improve contact with the screw terminal, this should then be 5mm in length. 16. Over the shield wire slide a piece of sheathing. This is to help prevent the shield being inadvertently shorted. Figure 19 Terminate each cable as shown. Shield - Shield Ground - Green/Green-White Data + - Blue Data - - Blue-White +12V Orange/Orange-White. Topic 1: Infrastructure Installers Course User Guide 21

22 Figure Ensure the conductors are fully inserted into the terminals with no loose strands escaping. 18. The process in complete. Figure Installers Course User Guide

23 Flat cable instructions Correctly stripped cable Incorrectly stripped cable shield still present Figure 22 Figure 23 Figure 24 DyNet voltages Below are voltage values for proper operation of a DyNet network: Max Min voltages: EU/AUS 10-18V, NA Max ripple: Max voltage range for Data+ and Data : -6.5V V (Data+ must be greater) Min voltage difference between Data + and Data-: 500mV recommended, 200mV is absolute minimum Max voltage range for power connections: +9V- +16V Topic 1: Infrastructure Installers Course User Guide 23

24 Network architecture The concept of a centralized controller and the complicated task of binding individual slave devices to the central controller in a DyNet network is completely eliminated. Each individual device will inherently know what they are and simply listen to and broadcast onto the network. This means that in most cases, particular devices on the network do not know or care about other devices. They simply respond to network messages, to which they are inherently sensitive, and broadcast their own class of messages with no particular destination in mind. A key principle of the DyNet network is that all of the functions associated with a particular device are located within that device. For example, all scene preset information is stored within the actual controllers. This means that if any device should fail, only the functions associated with that device are lost, other devices on the network are not affected. From a maintenance point of view, this concept of distributed control (self-contained) units both speeds up fault-finding, and allows a high level of fault tolerance in large systems. This Broadcast Network operating principle provides the necessary flexibility to ensure that the system can be easily (and at low cost) altered or added to after installation. It is possible to add extra equipment at any time without the need to re-configure or rewire the entire system. The DyNet Network The DyNet network is the communications layer that links the various Dynalite products together and enables them to interact with each other. For the purpose of discussion it can be divided into two sections, the Physical Layer and the network protocol. The Physical Layer Dynalite products utilize RS485 which is an industry standard method of data transmission as detailed in the TIA/EIA-485-A specification, with some variations. The TIA/EIA-485-A specification defines a UL (Unit Load), which declares that an RS-485 driver must be able to drive 32 ULs. This means that an RS-485 network supports 32 nodes, when each node bears a unit load on the line. Dynalite products use 1/8 UL drivers, which allow up to 256 devices on a network segment. Another important variation from the TIA/EIA-485-A specification is the addition of an extra conductor that carries a DC supply, which is generated by an integral power supply contained within all mains powered devices and is used to energize those devices that do not connect to mains power, such as motion detectors and wall switches. 24 Installers Course User Guide

25 Trunk & spur network Implementing trunk & spur topology This style of topology is used in large installations, where there are one or more data trunk cables that may interconnect network bridges located at different floors or distribution boards. The second port on the network bridge is then connected to a spur that feeds the dimmers and control panels in that locale. The recommended method of connection is to connect the Spur to the Port 1, and the trunk to the Port 2. Some reasons for implementing Trunk/Spur topology include: Optical isolation A fault on a Spur will be localized to that Spur only, the rest of the system will be unaffected. Quantity of network devices A finite number of devices can be connected to a single RS485 data cable. The recommended maximum number of devices is 100. The use of network bridge gives a maximum of 100 devices per spur, with 128 spurs per trunk gives a total of devices per trunk. Adding network isolators on spurs and running multiple trunks removes any realistic limitation from a single Philips Dynalite network. Topic 1: Infrastructure Installers Course User Guide 25

26 Trunk & spur network Figure Installers Course User Guide

27 DLight III trunk &spur network Figure 26 Topic 1: Infrastructure Installers Course User Guide 27

28 Ethernet networks It is possible to use an Ethernet network to work as a trunk with DyNet spurs. The figure below shows an Ethernet trunk connected to DyNet spurs with the DNG100BT Ethernet interface. Figure Installers Course User Guide

29 Multi trunk networks Multi trunk networks are used in large multi story projects, the purpose of a multi trunk network is to increase the speed of communication. Figure 28 Topic 1: Infrastructure Installers Course User Guide 29

30 Network cable current limits and voltage drop Because a number of devices are powered over the network the quantity of consuming devices such as panels and sensors needs to be considered. Typically most panels and sensors will run between 10-15V 25mA. To overcome voltage drop or large numbers of consuming devices a secondary power supply (DDNP1501) may be added to boost the overall network voltage. The DDNP1501 will deliver 15V at 1.5A. Generally most Philips Dynalite load controllers generate around 100mA to the DyNet network and will drive 4 or 5 consuming devices without the need for a secondary power supply. It is important to note that all Cat5 cable has a maximum current capacity of 2A. It is important that the network is designed not to exceed this rating. Devices such as touch screens draw as much as mA from the DC supply. In this case it is recommended that the touch screen be feed directly from a DDNP1501. Furthermore we would recommend that the connections at this device be limited to only GND, D+ and D- to avoid exceeding the 2A cable limit. See below figure. Figure 29 Data only Connection Figure 30 Power only connection 30 Installers Course User Guide

31 Power Supply Leading edge Trailing edge 0-10V Power only connection Touch screen DyNet network Standard connection Data only connection DyNet 1 & 2 networks Figure 31 Operational differences The maximum number of available Areas in a Dynet 1 network is 255. DyNet 1 is an open protocol. The maximum number of available Areas in a Dynet 2 network is DyNet 2 is a closed protocol. Topic 1: Infrastructure Installers Course User Guide 31

32 HF Ballast installation Installation instructions 1. Calculate loads to ensure any channels are not overloaded, then connect loads to the output channels. The maximum loading of this device is as follows: 2. *DALI broadcast mode: 80 ballasts per channel, do not exceed 500 ballasts in total 3. *1-10V mode: 100mA, 50mA source 4. *DSI Mode: 100 ballasts per channel, do not exceed 1200 ballasts 5. Remember that most 1-10V cabling scenarios are polarity conscious. DALI and DSI cables are not polarity conscious. 6. Connect a single phase 0.5A feed to the supply terminals. This device must be earthed. 7. Connect data cables to the device as per diagram in instruction manual for the controller. 8. If the Auxiliary input is to be used, connect a dry contact device in between the AUX and GND terminals. Keep cable runs between the controller and the dry contacts under 2 meters. The function of the Auxiliary input will need to be programmed at the time of commissioning. Note: The correct operation of DALI broadcast mode relies on the ballasts being set to their factory defaults. If problems are encountered, press the service switch 3 times, this will reset all ballasts connected and energized to their default settings. Note: It is recommended that you refer to individual product instruction manuals as max limits may differ. Network addressing A DyNet network has two different addressing modes: Physical addressing is used primarily during the testing and commissioning stage to configure DyNet Devices. It is also used for physical, location specific parameters such as circuit breaker trip signaling. A Device Type, Box Number and Physical channel number are used to identify each individual lighting circuit. Logical addressing is used in the day-to-day operation of the lighting system. Lighting circuits and control panels are configured to Areas; independent of the physical device they are connected to. An Area Number and Logical channel number are used to identify single or groups of Physical Channels. 32 Installers Course User Guide

33 Areas are used to group related lighting points by the area/room they are in. Consider the example of a load controller that supplies lighting circuits to 2 rooms, with a control panel in each room. The controllers lighting circuits and the control panel in Room 1 could be configured as Area 2, and the controllers lighting circuits and the control panel in Room 2 could be configured as Area 3. The end result would be that the control panel configured to Area 2 would only control circuits designated Area 2. The control panel configured to Area 3 would only control circuits designated Area 3. This allows the two rooms to operate independently of one another. Logical 1 Logical 2 Logical 1 Logical 2 Office 1 Office 2 Area 2 Area 3 CP 1 CP 2 Figure 32 DALI network wiring Device compatibility Philips Dynalite DALI compatible load controller range is listed below, : DMBC110 - HF Ballast Fixture Coupler 1 x output selectable to: DALI Broadcast, 1-10V, DSI DALI Ballasts and transformers: 5, 0-10V: 10mA source or 20mA sink DSI Ballasts and transformers: 15. DDBC100 - DALI- DALI HF Ballast Controller 1 x DALI control output, supporting a full DALI universe of 64 channels, including backward channel Diagnostics include; Lamp failure reporting, Ballast failure reporting, Ballast run time tracking for each ballast, Device Online/Offline status. DDBC300 - DALI- DALI HF Ballast Controller 3 DALI control outputs, each supporting a full DALI universe of 64 channels (192 total), including backward channel. Topic 1: Infrastructure Installers Course User Guide 33

34 DDBC320 - DALI- DALI HF Ballast Controller 3 DALI control outputs, each supporting a full DALI universe of 64 channels (192 total), including backward channel 3 x 20A feed through switched circuits for DALI ballast mains supply. DDMC802 - Multipurpose Controller DDBM100 1 channel ballast module, suitable for controlling DALI (Broadcast mode only), DSI & 1-10V ballasts and transformers (a relay module must be paired with a HF ballast module when controlling 1-10V ballasts). DDBC HF Ballast Controller 12 control outputs, selectable to DALI (Broadcast mode only), 0-10V or DSI Output capacity - DALI mode: 80 DALI ballasts per channel, 500 total, 0-10V mode: 100mA sink, 50mA source per channel, DSI: 100 DSI ballasts per channel, 1200 total. DBC V & DSI HF Ballast Controller 9 x HF ballast control outputs, each selectable to 1-10V, DSI or DALI. DBC1220GL - DALI, DSI & 1-10V & HF Ballast Controller 12 x HF ballast control outputs, each selectable to 1-10V, DALI (Broadcast mode) or DSI Output capacity - DALI mode: 64 DALI ballasts per channel, up to a maximum of 400. DBC DALI, DSI & 1-10V HF Ballast Controller. 12 x HF ballast control outputs, each selectable to 1-10V, DALI (Broadcast mode) or DSI. Output capacity - DALI mode: 64 DALI ballasts per channel, up to a maximum of 400, DSI mode: 100 ballasts per channel, up to a maximum of 1,200, 1-10V mode: 50mA sink/source per channel. 34 Installers Course User Guide

35 Normal DALI Figure 33 DALI Multi Master Topic 1: Infrastructure Installers Course User Guide 35

36 Figure 34 Enumeration DALI ballast enumeration can cause some trouble shooting confusion, below is a list of points to keep in mind when addressing DALI issues: Hit the service switch 4 times to start the test sequence. (wait for the time out or reset device) Check that the number of ballasts does not exceed 64 per universe Check voltage on circuits, it should be 15v Split the universe and then enumerate.- this will narrow down the search area for the defective ballast. Check for miss wired ballasts miss wired ballasts will cause a variety of dimming issues Check that all ballasts have been earthed correctly Check ballasts are wired correctly make sure that the long and short wires are connected correctly, to check remove the lamp and short the 2 wires together, this should cause the universe to alternate between 0% and 100%. Figure 35 Cable length to long or too skinny We recommend the Tridonic config tool v1.5 Cross wired universes. Emergency lighting There is a common requirement for emergency lighting to be used alongside general lighting connected to a control system. There are a few ways of achieving this, the most appropriate method is dependent on the type of emergency lighting fixture and control equipment used. Following is a description of several different techniques and their respective deployment methods. Sometimes it will be necessary to combine two or more techniques to achieve the desired outcome. 36 Installers Course User Guide

37 Self contained luminaries There are three common types of Self Contained Luminaires (also known as Single Point Luminaires): Maintained luminaires - This is an exit or emergency luminaire, where the lamps used for emergency lighting also operate under normal supply. The lamps used in these luminaires are often fluorescent, with a dimmable ballast and can be controlled in exactly the same manner as a normal dimmable fluorescent luminaire. Maintained Luminaires have two line inputs. One is connected to the Normal lighting output of the load controller. The Maintained input is connected to the load side of the load controller s circuit breaker, which supplies power to charge the internal battery and to use as a signal to turn the lamp on in the event of a power failure. In this example the Maintained Luminaire is also used for Normal Lighting, it s ballast is dimmable so ballast control lines are shown. Commonly used control protocols are DALI, DSI and 1-10V. Figure 36 Non-maintained luminaires - This is an exit or emergency luminaire, where the lamps used for emergency lighting only operate when the normal supply fails. The lamps used in these luminaires are often incandescent such as the small Spitfire halogen lamp and the larger, sealed beam flood lamp units. Non-Maintained Luminaires are connected to the load side of the load controller s circuit breaker, which supplies power to charge the internal battery and to use as a signal to turn the lamp on in the event of a power failure. This connection method allows full control of the normal lighting while providing for emergency lighting in the event of a circuit breaker trip or power supply failure. Topic 1: Infrastructure Installers Course User Guide 37

38 Figure 37 Sustained luminaires - This is an exit or emergency luminaire with two or more lamps where at least one lamp operates in non-maintained mode and is only illuminated when normal supply fails. The other lamp operates on the normal supply only. This is identical in functionality to having a Non-Maintained Luminaire and a Normal Luminaire both in the same housing. charge the internal battery and to use as a signal to turn the lamp on in the event of a power failure. In this example the normal half of the Sustained Luminaire is used for Normal Lighting, it s ballast is dimmable so two ballast control lines are shown, common protocols are DALI, DSI and 1-10V. Sustained Luminaires have two line inputs. One is connected to the Normal lighting output of the load controller. The Sustained input is connected to the load side of the load controller s circuit breaker, which supplies power to charge the internal battery and to use as a signal to turn the lamp on in the event of a power failure. In this example the normal half of the Sustained Luminaire is used for Normal Lighting, it s ballast is dimmable so two ballast control lines are shown, common protocols are DALI, DSI and 1-10V. Figure Installers Course User Guide

39 Testing emergency lighting Most local lighting codes require the testing of emergency lighting systems at defined intervals. Common problems include failed lamps and aged batteries that no longer meet the luminaire s rated duration. To assist in the testing process, some models of Dynalite load controllers are optionally available with Emergency Lighting Outputs (ELx). This controlled output is fed via an NC relay and provides power to the maintained input of Emergency Luminaires. The ELx outputs from multiple load controllers can be remotely disconnected for a defined period of time, for example a test button would switch off all ELx outputs for a particular office floor, maintenance staff would then perform a walk through to identify failed components. This process can be automated with the addition of extra hardware in the luminaire. Figure 39 Essential supply load shedding Some sites are equipped with a standby generator, which will automatically start upon failure of normal supply and, after operating parameters are reached, will switch part or all of the site from the normal supply circuit to the generator s output, resulting in the site being re-energised some 10 to 20 seconds after normal supply failure. Quite often the standby generator is coupled with a UPS (Uninterruptible Power Supply), which ensures there is no power dropout during the changeover period. In theory, the lighting system should operate as it would on normal supply, but in practice it is often desirable to modify its behavior. Two common reasons for doing this are: The Standby Generator does not have the power capacity required to operate the site normally. In this case it is desirable to place the lighting system into a load shedding mode. Topic 1: Infrastructure Installers Course User Guide 39

40 The site should not be occupied while normal power is not available. In this case it is desirable to place the lighting system into an egress mode. To change the operating mode, the lighting system must be made aware that the generator is online. This is typically carried out via a relay that actuates when the generator is online, (or sometimes via a relay that actuates when the normal supply fails) providing a dry contact signal to an input unit on the lighting control network, such as a DDMIDC8 Multifunction Input Interface. 1 Phase 40 AMP Figure 40 In egress mode The DDMIDC8 locks out all control devices such as wall mounted Control panels, touch screens, motion detectors etc, and selects a global egress preset, which is pre-defined to illuminate egress paths and reduce lighting in workspaces to assist in alerting occupants that something is amiss. When normal power is restored the DDMIDC8 restores normal control functionality. Load shed mode The DDMIDC8 instructs all load controllers to use a different set of presets than the normal ones. Consider the example of a room with two channels of lighting and a control panel that recalls four presets: During normal operation, presets 1-4 are recalled from the control panel. In load shed mode the DDMIDC8 uses a part of the DyNet feature set called Preset Offset, which instructs the load controllers to recall presets 5-8. This function can target a single or group of rooms, or more commonly, the whole site. If it is desirable that no lighting is on at all in particular rooms in load shed mode, then all load shed presets are set to 0%. This method has the advantage of minimal impact on the site, as lighting levels in particular rooms are not disturbed if they are already off or at low levels. 40 Installers Course User Guide

41 Maintaining circuits by bypassing load controllers When there are only a small number of circuits to be maintained when a site changes over to a standby generator or UPS, a simple solution is to bypass the lighting control system with contactors that connect the circuits to be maintained directly to the essential supply. DMX Figure 41 In this scenario the non-essential supply is used to hold a contactor closed, connecting the lamp to the load controller. When the non-essential supply fails the load controller will be deenergized as will the contactor, which will connect the lamp to the essential supply. End of line resistors At 9600 Baud the distortion of the original signal is usually within limits and so EOL resistors are not recommended on a standard DyNet system. Baud rates greater than 9600 Baud must be terminated using a 120Ω resistor across D+ and D-. Usually fitted into network connector strip for 1st and last devices. For DMX integration network must be daisy chained with end of line resistors. 120R D+ D-- D+ D-- 120R Figure 42 Topic 1: Infrastructure Installers Course User Guide 41

42 Topic 2: Installing load controllers Overview This document is a guide to installing Philips Dynalite components to a state where it is really to be commissioned. Every Dynalite product is delivered with a comprehensive instruction manual. It is important that you read the installation instructions for each product before using this guide. Learning outcomes By the end of this topic you ll be able to detail the installation steps for the following devices: Wall mounted devices DIN rail mounted devices Mounting structured wiring boxes Mounting panels Mounting sensors Mounting touch screens End of line resistors. Hardware controls Service LED and switch The Service LED has 3 signaling modes, which are useful for troubleshooting: Blinking slowly (1Hz) = Normal Operation Blinking fast (0.25Hz) = Network Activity Detected On = Fault. 42 Installers Course User Guide Topic 2: Installing load controllers

43 The Service Switch, when pressed, causes a sign-on message to be transmitted onto the network. If the transmission is successful, the Service LED will indicate network activity detected. The Sign-on message contains information about the device, such as: box number, device type and embedded software version. This information is captured by DLight configuration software to speed up commissioning of large systems. The Service Switch three states are: 1 push = Transmit Network ID 3 pushes = All Channels 100% Push & hold for 4 sec = Reboot. AUX input This is a dry contact interface that is active low. The dry contact is connected between the AUX and GND terminals on the DyNet connector strip. The function of the AUX input is programmable. Ensure that the cable length between the dry contact and terminal strip is no longer than 2 meters. Top set This adjusts the maximum output that all other control sources can select, i.e. if the Top Set is fully clockwise, 100% selected by a control source will give 100% output. If it is fully anticlockwise, 100% selected by a control source will give 50% output. This control is useful for extending lamp life and can be operated without any form of network control, effectively turning the device into a stand-alone power conditioner and lamp protector. Wall mounted devices Select a suitable location Some of Philips Dynalite products are available in the wall mounted form factor, these include: Load controllers Network Bridges. Wall mounted devices are designed for indoor use only. If installing in an external location, the device must be housed in a suitable well-ventilated enclosure. Choose a dry location that will be accessible after the installation is complete. To ensure the cooling system functions correctly, the load controller should only be mounted vertically, the right way up. Topic 2: Installing load controllers Installers Course User Guide 43

44 The load controller will generate heat when operating, approximately 2 Watts per Amp of load, and requires an air gap of 200mm on each side and at the top and bottom of the device. This air gap is also required to ensure serviceability of the load controller without complete removal from the mounting surface. This device may emit some mechanical noise. Take this into account when deciding the mounting location. Figure 43 Figure 44 Figure Installers Course User Guide Topic 2: Installing load controllers

45 Fixing the device The load controller has integral mounting brackets attached to the enclosure. The brackets are designed to accommodate 4 fixing screws up to 8mm diameter. The load controller can be fixed to the wall without opening the cabinet or removing covers. Make sure no dust or other debris enters the device during installation. Do not leave the front cover off for any length of time. Excessive dust and dirt can degrade the cooling of internal components. Allow for cable entry Supply and load cables enter the enclosure at the top. If these cables are fed from below the mounting position, they should be routed around the enclosure to enter at the top. An alternative method is to stand the enclosure off from the mounting surface by mounting it on a cable tray or a Unistrut style product. The cables can then be routed between the enclosure and the mounting surface, and enter the enclosure via the cut out provided on the mounting face. The control cables enter at the bottom of the enclosure. Control cables should never be run in the mains voltage sections of the enclosure. Supply & load cable Supply Cables -The supply input terminals are located toward the top of the enclosure and consist of Earth, Neutral, and Phase. The supply cables should have enough capacity to allow the device to be loaded to its maximum capacity. Load Cables - Load cables can be terminated on the 4 x 3 way load terminal strips (one for each channel), a Neutral link and an Earth link located at the centre of the enclosure. It is important that an individual output circuit is not overloaded. Calculate the intended load, and ensure that it is below the maximum capacity of an individual channel. To ensure compliance with interference standards, the load neutral cables must be individually connected to the neutral link terminals inside the cabinet. Never use a common neutral at a remote location. Emergency Lighting Connections - Connect the emergency lighting circuit active to the load side on the circuit breaker for the relevant channel, as indicated by the labels next to the circuit breakers. Do not remove any cables that may already be terminated at this location. Energizing the Device - If it is necessary to energies load circuits before any control cables are connected, it is acceptable to replace the cover and energies the device immediately, as the default factory programming is to have all channels set to 100% output. This device should be deenergized before terminating the control and data cables. Topic 2: Installing load controllers Installers Course User Guide 45

46 Powering up the dimmers prior to commissioning All devices are pre-programmed with a default configuration before leaving the factory. When all the devices are installed and networked together, every button panel will control all the dimmers. The Dynalite engineer requires the system to be installed to this level to commission the project successfully. All Dynalite load controllers are set to provide full output to the load as the default, irrespective of having the network connected. When the network is connected, every button panel will operate every circuit of every device. Operating environments This device is designed for indoor use only. If installing in an external location, the DLE1205 must be housed in a suitable well ventilated enclosure. Choose a dry location that will be accessible after the installation is complete. In addition the load controller must not be in a location that exceed the following limits for temperature and humidity: 0º to 40ºC ambient temperature 0% to 95% RH non condensing. DIN rail mounted devices Instructions A number of devices are available in the DIN rail form factor, these include: Load controllers Time clocks Power supplies Network gateways Dry contact interface devices. 46 Installers Course User Guide Topic 2: Installing load controllers

47 Follow the points below to ensure correct installation of DIN rail mounted devices: Mount the device on a DIN rail inside an approved enclosure. Calculate loads to ensure any channels are not overloaded, then connect loads to the output channels. This device must be earthed Connect data cables to the device as per diagrams in the previous topic. If the Auxiliary input is to be used, connect a dry contact device in between the AUX and GND terminals. Keep cable runs between the device and the dry contacts under two meters. The function of the Auxiliary input will need to be programmed at the time of commissioning. Every Dynalite product is delivered with a comprehensive instruction manual. It is important that you read the installation instructions for each product before installation. Figure 46 Topic 2: Installing load controllers Installers Course User Guide 47

48 Figure 47 Circuit breakers Required by each device, consult the product data sheet or instruction manual for details. Multi controllers When installing Multi Controllers there are some additional considerations to take into account regarding the controller modules. Verify that the Output Cards supplied are suitable for your intended loads. Pay attention to any Output Card specific documentation that may be packed with Output Cards. When dimming electronic transformers, ensure that the intended transformer is included in Dynalite s Compatible Electronic Transformer List, the latest revision is available at dynalite-online.com 1. Snap the cover off the base unit. Plug each Output Card into the slots provided on the main circuit board. Replace the base unit s cover. If using different types of Output Cards, remember which type is associated with each set of output terminals. 2. Mount the device on a DIN rail inside an approved enclosure. 3. Calculate loads to ensure any channels are not overloaded, then connect loads to the output terminals. The maximum loading of this device is 16A. A de-rating factor may need to be applied if installed in a smaller sealed switchboard when using Leading or Trailing edge dimmers, contact your dealer for details. 48 Installers Course User Guide Topic 2: Installing load controllers

49 The output card ratings are: DDBM100 Ballast Controller Digital mode : 5 x Ballasts DDBM100 Ballast Controller DSI mode : 15 x DSI Ballasts DDBM100 Ballast Controller 1-10V mode : 10mA source, 20mA sink DDCM102 Curtain Controller : 2 Amps DDFM102 Fan Controller : 1 x Fan, max 400VA DDLM102 Leading Edge Dimmer : 2 Amps DDLM104 : Leading Edge Dimmer : 4 Amps DDRM104 Relay Controller : 4 Amps DDTM102 Trailing Edge Dimmer : 2 Amps WARNING : Ballast controller output is referenced to mains neutral and is live. Only mains rated cables and control ports should be connected. Ensure that lamp holders are marked with the maximum permissible lamp size that will not overload a channel. This is to protect the end user from inadvertently overloading a channel by replacing lamps with higher wattage types. 1. Every time the front cover is removed, ensure that all modules are correctly seated and locked into sockets before the cover is replaced. 2. Ensure that lamp holders are marked with the maximum permissible lamp size that will not overload a channel. This is to protect the end user from inadvertently overloading a channel by replacing lamps with higher wattage types. 3. Connect a single phase 16A feed to the supply terminals, via a 16A circuit breaker or HRC fuse. This device must be earthed. 4. Connect data cables to the device as per diagrams below. 5. The Auxiliary input is connected via a dry contact device in between the AUX and GND terminals. Keep cable runs between the device and the dry contacts under two metres. The function of the Auxiliary input will need to be programmed at the time of commissioning. Topic 2: Installing load controllers Installers Course User Guide 49

50 Structured wiring boxes Select a suitable location This device is designed for indoor use only. If installing in an external location, the DBC905 must be housed in a suitable enclosure. Choose a dry location that will be accessible after the installation is complete. To prevent dust or particle penetration the controller should be mounted so that connector apertures do not face directly upwards. Recommended mounting methods include surface wall, slab, cable tray or drop rod suspension. Fixing the device The controller has two keyhole slots located at each end of the housing, which can accommodate fixing screws up to 6mm diameter. The preferred method of mounting is shown below using drop rods with appropriate fastening clips. Figure Installers Course User Guide Topic 2: Installing load controllers

51 Wiring terminations Removable connectors are utilized for all wiring terminations to simplify maintenance, installation and replacement. Note that controllers are supplied without connectors. Please order connectors separately as required. Figure 49 Supply and output connections The DBC905 is available in two configurations supporting popular structured wiring brands; CMS Electracom / Modular Wiring tag series and Wieland GST18 series. Units are designated by item code as DBC905C (CMS) OR DBC905W (Wieland). Both cable vendors offer a range of wiring solutions and accessories for both the upstream supply and downstream load wiring. The upstream wiring solutions combine both the mains supply and floor network circuits into one wiring assembly, which can dramatically reduce installation time. Please refer to respective vendor for guidelines on connector and cable assembly selection. DBC905W Output Connector Pole Assignments Figure 50 DBC905W pole mains input socket Figure 51 DBC905C Output Connector Pole Assignments Figure 52 Topic 2: Installing load controllers Installers Course User Guide 51

52 DBC905C pole mains input socket Figure 53 Dry contact switch input connections The DBC905 incorporates 4 x voltage free single pole double throw (SPDT) switch inputs, momentary or latch action with four x 3 pole removable terminal sockets for connection of two way on and off retroactive switches. Network connections Figure 54 Serial ports are used to interconnect other dimmers, smart control panels, sensors and AV controllers. The DBC905 circuit design incorporates multiple layers of isolation to deliver robust fault tolerance and uncompromising safety. It should be noted that most structured wiring solutions for upstream supply circuitry which include both network and power (i.e. 5 pole systems) only provide functional isolation between the data and mains circuits. Where such wiring systems are used, the floor network must be considered at mains potential not SELV and all floor network wiring should include the appropriate provision for prevention of access to live parts. The main floor network port on the DBC905 is isolated for this reason. The isolation will tolerate a fault which raises the floor network to mains potential. Note that this does not include mains potential applied across D+ and D- which would of course result in destruction of circuit components. Isolation is also separately provided to the local DyNet ports and switch inputs. This ensures that all switch inputs and local network circuits are SELV and prevents propagation of faults from these circuits across the floor network. Where an upstream structured wiring solution is used, care should be made when terminating network spur wiring at floor bridges (area controllers), to again prevent access to parts and wiring considered potentially live. In this case only DBC905 controllers should be connected to the floor network as they incorporate the isolated port. Under no circumstances should a 52 Installers Course User Guide Topic 2: Installing load controllers

53 standard user interface be connected directly to the floor network as this may permit user access to potentially live parts. All user interfaces such as sensors and panels should be connected to the local network ports on the DBC905 which provide SELV isolation from mains and the floor network. Where it is necessary to connect user interfaces to a floor network of this type, a bridge should be always used to provide effective isolation. Topic 2: Installing load controllers Installers Course User Guide 53

54 Topic 3: Installing panels Overview This topic covers the requirements and step for installing the Philips Dynalite range of panels. Instructions for DLP, DPN and DR2P are covered. Learning outcomes By the end of this topic you ll be able to: Install DR2P series user interface panels Install DLP user interface panels Install DPN user interface panels. Instructions Follow the points below to ensure correct installation: Use the mounting screws provided To comply with local electrical standards, some products may be required to be installed into a metal wall box (not supplied). Connecting data cables Follow the points below when connecting data cables to ensure correct installation: Use screened, stranded RS485 data cable with three twisted pairs. Connect data cable to devices in a daisy chain whenever possible. Start at the first device, then loop in then out of devices, with a single cable terminating at the last device. Devices may be wired in any order. Physical constraints may dictate that data cable spurs are necessary. In these cases, Network Bridges may be needed. The Data Cable should be segregated from any Mains Cables by a minimum of 300mm. If the Data Cable has to cross over any Mains Cables, it should do so at a 90 angle. A data cable that is connected to an energized dimmer is live. Do not cut or terminate live data cables. Panels can be mounted vertically or horizontally if desired. 54 Installers Course User Guide Topic 3: Installing panels

55 Factory presets Default preset levels are factory preprogrammed into give basic level of functionality. These can be customized to specifically suit each room or area. Figure 55 Figure 56 The default preset levels are listed below: PRESET LIGHT LEVEL P1 100% P2 70% P3 40% P4 0% P5 80% P6 60% P7 50% P8 20% Note: Hold down a button for 5 seconds to sign on a panel to a network. Topic 3: Installing panels Installers Course User Guide 55

56 Changing button configurations DLP & DL2P Buttons, bezels and covers snap-on, remove the fascia to access buttons without the need for any tools or extra wiring. DR2P Figure 57 Figure 58 DR2P panel buttons are changed individually, see figure 47 below: Figure Installers Course User Guide Topic 3: Installing panels

57 DPN Buttons for DPN panels can be replaced without the need for any tools or extra wiring. By pinching the button cap on the sides and pulling gently the cap can be removed. The fascia of the DPN panel doesn t need to be removed for button maintenance. Figure 60 Panel network connections Dingus You can connect to the back of a panel using a Dingus supplied with the DTK622 PC node. Figure 61 In addition to the dingus, the LSP-PRO and FFC-LSP can be used to connect to the DyNet network via DL2P and DR2P panels. Topic 3: Installing panels Installers Course User Guide 57

58 LSP-PRO Remove the panel s fascia to access the connector shown in figure 56 below: Figure 62 Figure 63 FFC-LSP A third type of connector can be used to connect to the DyNet network via a DR2P panel Remove the panel s fascia to access the connector shown in figure 48 below: Figure 64 Figure Installers Course User Guide Topic 3: Installing panels

59 Topic 4: Installing motion sensors Overview This topic covers the requirements and step for installing the Philips Dynalite range of sensors. Instructions for DUS704C, DUS704W and DUS804C are covered. Learning outcomes By the end of this topic you ll be able to: Install motion sensors using PIR motion control Install motion sensors using ultra sonic motion control Install motion sensors for light control Install sensors for IR control. Installation instructions Follow the points below to ensure correct installation: WARNING * Do not touch the Pyro Sensor with your fingers. For indoor use only. Select an appropriate indoor mounting location, as detailed in the location guidelines on the following pages. Note that this product has three functions, and the optimum mounting location for each individual function may conflict with each other, and may require the use of multiple sensors. Remove the cover from the base unit by turning the cover in an anti clockwise direction. Screw the base unit to the ceiling, passing the data cable through the cable entry hole. Terminate the data cable as shown previously. Use silicon sealant to seal any cable entry and screw holes to prevent air draughts, dust and insects from entering the enclosure. Replace the cover onto the base unit by turning the cover in a clockwise direction. Topic 4: Installing motion sensors Installers Course User Guide 59

60 Mounting PIR motion sensors Follow the points below to ensure correct installation for motion detection: Fix the sensor to a firm section of ceiling Position the sensor so it is between 2.1 and 4.0 meters from the floor. Optimum height for the sensor is 2.4 meters Position the sensor so it is at least 1 meter away from electrical lighting such as neon and fluorescent lights Position the sensor as to avoid exposing it to direct sunlight and heating/cooling sources Keep data cables away from electrical wiring Position the sensor where pedestrian traffic is more likely to walk across the detection fingers rather than parallel with them (see Lens pattern diagram). Note: That the coverage area for our sensors differ from model to model (see Motion Detector Coverage diagram on the following pages). Mounting Ultra sonic motion sensors Sensor must be mounted in a dry location on a rigid, vibration free surface. Ideal location for PIR should have a clear view of all workspaces in coverage area. The ultrasonic sensor s field of view is less directional. Avoid placing sensor where it may face doorways etc which could cause false triggering. Sensor should be located at a distance of at least 7ft from horizontal or vertical air ducts. Adjacent sensors with ultrasonic detector enabled should be installed with a minimum of 60ft spacing between. Sensor should be placed such that the PE cell s field of view is unobstructed, and does not have an artificial light source or natural light directly incident on it. For flush mount drill a 2.5 inch hole in ceiling, noting the ceiling void should be at least 2 inches deep. If surface mounting option is used, use provided mud ring mounting adaptor. For this option removal of the spring clips from the sensor s rear housing is required. Wire the sensor following the recommendations. See data cable permanent connections. Insert the sensor into the ceiling using spring clips or attach it to the mud ring mounting adaptor provided, and rotate to secure. Rotate the sensor in the direction of desired Ultrasonic coverage. If required pull-down the PIR masking bezel to stop the PIR sensing in unwanted areas (e.g. movement past doorways). Refer to separate installation guideline document for detailed install information. 60 Installers Course User Guide Topic 4: Installing motion sensors

61 DUS704C motion coverage PIR motion detection coverage area: 9m x 6m At a height of 2.5m Figure 66 DUS804C and DUS804C-SM motion coverage DUS804C PIR motion coverage area: 5.6m x 7.4m At a height of 2.5m DUS804C-SM PIR motion coverage area: 5.0 m circular At a height of 2.5m Figure 67 Figure 68 Topic 4: Installing motion sensors Installers Course User Guide 61

62 DUS804C-UP ultra sonic motion coverage Ultrasonic Motion Detection coverage area: Major motion detection area: up to 1500 sq. ft * (50 ft x 30 ft) Minor motion detection area: up to 1000 sq. ft * (36 ft x 30 ft) Figure 69 Motion detection lens pattern Figure Installers Course User Guide Topic 4: Installing motion sensors

63 Figure 71 Optional motion detector lens for DUS704W In addition to the supplied Wide Angle lens, two other types are available for specific applications: DUS704W Curtain Creates a solid, thin barrier which is useful for monitoring a perimeter in an open space. DUS704W Long Range Useful for monitoring a long thin space such as a corridor. Contact your local supplier for more details. Optional Lens DUS704W Curtain Figure 72 Figure 73 Topic 4: Installing motion sensors Installers Course User Guide 63

64 Optional Lens DUS704W Long Range Figure 74 Figure 75 Selecting sensor installation locations Selecting the correct location for a motion sensor is of critical concern, incorrect placement can result in sensors not detecting occupants or false triggers (lights turning on incorrectly). False triggers from passersby Lights trigger only upon entry Figure 76 Figure 77 It is possible to reduce the field of view of the DUS804C and DUS804C-SM from their normal 3600 by use of the in-built rotating pull out shield. The shield blocks 1200 of the field of view, reducing the motion detection field area to The shield can also be rotated to block any 1200 area once the sensor has been installed. 64 Installers Course User Guide Topic 4: Installing motion sensors

65 Figure 78 DUS804C shield By suing the mask installation errors like in figure 55 can be corrected without the need to remount the sensor. Sensor mounting for PE (photo electric) Follow the points below to ensure sensors operate properly for light sensing: Position the sensor so it sees a combination of artificial light and natural light. Position the sensor so it not directly exposed to artificial light or sunlight. Keep data cables away from electrical wiring. Figure 79 Topic 4: Installing motion sensors Installers Course User Guide 65

66 Infrared receiver mounting location Follow the points below to ensure the sensor operates properly for IR detection: Position the sensor so it is within 6 meters of the intended operating position of the infrared transmitter Position the sensor so it is not directly exposed to light, especially incandescent and sunlight, both of which can substantially reduce IR range Keep data cables away from electrical wiring. Figure 80 Installing DUS704W-MB mounting brackets Follow the steps below to mount a wall mount sensor: Fix the sensor to a firm section of wall. Position the sensor so it is between 1.1 and 3.1 meters from the floor. Optimum height for the sensor is 2.1meters. Slide the circuit board up or down so the marker on the housing matches up with the installed height on the scale provided on the right hand side of the circuit board. Position the sensor so it is at least 2 meters away from electrical lighting such as neon and fluorescent lights. Position the sensor as to avoid exposing it to direct sunlight and heating / cooling sources. Keep data cables away from electrical wiring. Select a location where persons are more likely to walk across the detection fingers rather than into them (see Figure 63). For programming instructions refer to Dynalite Tech Note Setting up Motion Detection functions. 66 Installers Course User Guide Topic 4: Installing motion sensors

67 Figure 81 Topic 4: Installing motion sensors Installers Course User Guide 67

68 Topic 5: Installing touch screens Overview Philips Dynalite currently has two models of color touch screen available, the DTP100 and DTP170. These feature a rich color LCD touch screen that uses vivid graphics and sophisticated on screen controls. Control of various equipment such as lighting, AV, security and HVAC can be easily integrated and controlled from the one location. Learning outcomes By the end of this topic you ll be able to: Install DTP100 touch screen Install DTP170 touch screen. General installation points for touch screens Remember the display height should be equal to, or slightly below, the eye level of all users. Avoid a location in which bright light is present, either directly in front of, or behind, users. Figure 82 The DTP160 Touch Panel must be flush-mounted. 68 Installers Course User Guide Topic 5: Installing touch screens

69 Installing the DTP170 Dimensions: 140mm high x 218mm wide x 71mm deep. Figure 83 Fixing the device The DTP170 Touch Screen is designed to be flush-mounted, with or without a wall box. If using a wall box, separate the wall box from the Touch Screen and make sure no dust or debris enters the Touch Screen during installation. The wall box can then be fixed in place using an appropriate method. Topic 5: Installing touch screens Installers Course User Guide 69

70 Installing the DTP100 Dimensions: Hidden Wall box: Height 69mm x Width 129mm x Depth 27mm. Exposed Face: Height 86mm x Width 146mm x Depth 5mm. Keyboard/Mouse port Type B USB socket Programming port Type B USB socket DyNet port 3.5mm stereo jack Ethernet RJ45 network socket Figure Installers Course User Guide Topic 5: Installing touch screens

71 Fixing the Device The DTP100 Touch screen Panel must be flush-mounted. Separate the wall box from the panel and make sure no dust or debris enters the device during installation. Recommended back box for dry lining / plasterboard applications, use the following part numbers: Wallbox recess metal Wallbox recess drywall Wallbox surface mount. Power supply Figure 85 - MK electric 2 gang wall box The DTP100 Touchscreen Panel is powered from the DyNet network and does not require mains voltage supply. Topic 5: Installing touch screens Installers Course User Guide 71

72 Topic 6: Installing integration devices Overview In this topic we cover the installation requirements for a number of Philips Dynalite integration devices: DDMIDC8 multi function input interface DDNG485 gateway DPMI940 dry contact interface. Learning outcomes By the end of this topic you ll be able to Install a DDMIDC8 Install a DDNG485 gateway Install a DPMI940 dry contact interface Install a DDFCUC024 / DDFCUC010. Installing the DDMIDC8 Features 8 x Opto Isolated inputs - each configurable to dry contact or 0-24V input. 4 x Analogue Inputs Configurable to 0-5V or 0-10V. LED Status Indicators for each opto isolated input. Power Supplied from Network - No mains connection. Powerful Internal PLC - Custom scripts can be written to provide process control based on conditional logic. Simple Installation - DIN Rail mount facilitates installation. Fixing points are provided for installation without the use of DIN rail. 72 Installers Course User Guide Topic 6: Installing integration devices

73 Figure 86 Installation notes Read Instructions We recommend that you read this Instruction Manual prior to commencement of installation. Special Programming This device will only operate in basic modes unless programmed via a computer. If programming is required, contact your local agent for details. Once the data cable is connected to the devices, the factory default settings will allow any control panel or input to operate all channels in all controllers. Mounting Location Install in a dry, well-ventilated location. Controllers may emit some mechanical noise. Take this into account when deciding the mounting location. Data Cable Use screened, stranded RS485 data cable with three twisted pairs. Segregate from mains cables by 300mm minimum. Connect devices in a daisy chain. A data cable that is connected to an energized device is live. Do not cut or terminate live data cables. Electrical diagram SHIELD GND D + D - +15V µp A/D A/D A/D A/D Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8 AN1 DyNet RS485 0V AN2 0V AN3 0V AN4 0V +5V Opto Isolated Dry Contact/0-24V AC/DC Digital Inputs 0-5V/0-10V Analogue Inputs Figure 87 Topic 6: Installing integration devices Installers Course User Guide 73

74 Analogue fader Dynalite DDMIDC8 Input Interface 0-5V / 0-10V Analogue Inputs AN1 0V AN2 0V AN3 0V AN4 0V +5V Figure 88 Installation steps 1. Mount the device on a DIN rail inside an approved enclosure. The device can also be installed without the use of DIN rail by removing the cover to access two mounting screw holes. 2. Connect RS485 data cable to the serial port as per the connection diagram overleaf. 3. If used, connect volt free contacts or 0-24V AC/DC inputs to any of the 8 opto-isolated inputs. Remove the lid and ensure that the jumpers for each input are set to the appropriate 0-24V or volt free setting, depending on the input type. 4. If any opto-isolated inputs are of the Dry Contact type, ensure that the power supply jumper is fitted in the volt free position. Note that this will increase the current consumption of the device from 15mA to 40mA, which may require consideration of voltage drop on long runs of DyNet data cable. 5. If used, connect 0-5V or 0-10V inputs to the analogue ports. Ensure the input voltage is DC and a maximum of 10 Volts. Note that bare faders can also be connected to the analogue inputs by using the adjacent +5V terminal as a supply. Suggested fader value is 10K ohm. Do not attempt to draw more than 25mA from the +5V terminal. 74 Installers Course User Guide Topic 6: Installing integration devices

75 Installing DDNG Mount the device on a DIN rail inside an appropriate enclosure. Alternatively there are 2 holes provided to fix the device to a surface without the use of DIN rail. Remove the front cover to access these holes. 2. Connect data cables to the device as per diagrams. Note that the device is powered from the DyNet network segment that is connected to Port 1. When implementing Repeaters, connect the link to Port 2 of both Gateways. Shielded cable must be used for long runs. When implementing Trunk / Spur topology, connect the Trunk to Port 2 and the Spur to Port 1. Note that up to 150mA of power from the DyNet network on Port 1 is fed to Port 2, so providing there is surplus power available on the Spurs it is normally not necessary to provide a network power supply for the Trunk. 3. If using the device as a DMX receiver, ensure DMX termination rules are obeyed, use a 120 Ohm terminating resistor across D+ and D- at the end of line. Note that Port 2 should be used for DMX Reception. Figure 89 Figure 90 Topic 6: Installing integration devices Installers Course User Guide 75

76 DPMI940 Using the DPMI940 To install 3 rd party panels in a Dynalite project you will require the use of a DPMI940 dry contact interface. Figure 91 Figure 92- DPMI940 installed in wall box and connected to switches Installation steps 1. Mount the device on a DIN rail inside an approved enclosure. The device can also be installed without the use of DIN rail by removing the cover to access two mounting screw holes. 2. Connect RS485 data cable to the serial port as per the connection diagram overleaf. 3. If used, connect volt free contacts or 0-24V AC/DC inputs to any of the 8 opto -isolated inputs. Remove the lid and ensure that the jumpers for each input are set to the appropriate 0-24V or volt free setting, depending on the input type. 4. If any opto-isolated inputs are of the Dry Contact type, ensure that the power supply jumper is fitted in the volt free position. Note that this will increase the current consumption of the device from 37mA to 68mA, which may require consideration of voltage drop on long runs of DyNet data cable. 5. If used, connect 0-5V or 0-10V inputs to the analogue ports. Ensure the input voltage is DC and a maximum of 10 Volts. Note that bare faders can also be connected to the 76 Installers Course User Guide Topic 6: Installing integration devices

77 analogue inputs by using the adjacent +5V terminal as a supply. Suggested fader value is 10K ohm. Do not attempt to draw more than 25mA from the +5V terminal. Electrical diagram Mounting details Figure mm Ribbon Cable side view 19 mm 19 mm top view Figure 94 Topic 6: Installing integration devices Installers Course User Guide 77

78 Connecting to a motion detector Connect Ground and +12V leads to the motion detector s 0V & +12V terminals. Connect Ground and Switch 1 leads to the motion detector s Alarm terminals. Connect Ground and Switch 4 leads to the motion detector s Tamper terminals. Connecting volt free inputs Inputs: 7 core Flat Ribbon Cable Flying Lead inputs PIN FUNCTION COLOR Volts Gray with Red Trace 2 Ground Gray 3 Ground Gray 4 Switch 1 Gray 5 Switch 2 Gray 6 Switch 3 Gray 7 Switch 4 Gray To trigger a preset place a short between SW 1, 2, 3 or 4 to the Ground. The +12V terminal is provided to power 3rd party devices such as motion detectors, ensure that it does not touch any other terminal of the device. Figure Installers Course User Guide Topic 6: Installing integration devices

DBC1220GL. 12 x 20A HF Ballast Controller Installation Manual. contents

DBC1220GL. 12 x 20A HF Ballast Controller Installation Manual. contents DBC1220GL 12 x 20A HF Ballast Controller Installation Manual contents Warning.. 2 Hardware Controls... 7 Features.. 2 Troubleshooting. 8 Important Safeguards.. 2 Specification.. 8 Internal View.. 3 Mounting.

More information

DBC x 10A HF Ballast Controller Installation Manual

DBC x 10A HF Ballast Controller Installation Manual DBC1210 12 x 10A HF Ballast Controller Installation Manual contents Warning.. 2 Hardware Controls... 7 Features.. 2 Troubleshooting. 8 Important Safeguards.. 2 Specification.. 8 Internal View.. 3 Mounting.

More information

DTE x 10A Trailing Edge Dimmer Installation Manual. contents

DTE x 10A Trailing Edge Dimmer Installation Manual. contents DTE310 3 x 10A Trailing Edge Dimmer Installation Manual contents Warning.. 2 Features.. 2 Important Safeguards.. 2 Internal View.. 3 Mounting. 4 Supply & Load Cable Connections. 5 Connecting Serial Control

More information

Ecolinx 9 x 5A Structured Wiring HF Ballast Controller Installation Manual. contents

Ecolinx 9 x 5A Structured Wiring HF Ballast Controller Installation Manual. contents DBC905 Ecolinx 9 x 5A Structured Wiring HF Ballast Controller Installation Manual contents Warning. 2 Typical system / Equiptment Layout... 9 Features. 2 Trouble shooting.. 10 Important Safeguards.. 2

More information

DMC810GL. contents. Leading Edge Dimmer/HF Ballast Controller Installation Manual

DMC810GL. contents. Leading Edge Dimmer/HF Ballast Controller Installation Manual DMC810GL Leading Edge Dimmer/HF Ballast Controller Installation Manual contents Warning.. 2 Dimmable Lamps Chart... 7 Features.. 2 Troubleshooting. 8 Important Safeguards.. 2 Specification. 8 Internal

More information

DLE x 10A Leading Edge Dimmer Installation Manual

DLE x 10A Leading Edge Dimmer Installation Manual DLE1210 12 x 10A Leading Edge Dimmer Installation Manual contents Warning.. 2 Dimmable Lamps Chart... 7 Features.. 2 Troubleshooting. 8 Important Safeguards.. 2 Specification.. 8 Internal View.. 3 Mounting.

More information

Instruction Manual. Contents

Instruction Manual. Contents SceneSelect II Scene-setting and Dimming System SBD410 HF BALLAST CONTROLLER Instruction Manual Warning... 2 Features... 2 Important Safeguards... 2 Internal View......3 Mounting... 4 Supply & Load Cable

More information

DLE1220GL-S. 12 x 20A Leading Edge Dimmer Installation Manual. contents

DLE1220GL-S. 12 x 20A Leading Edge Dimmer Installation Manual. contents DLE1220GL-S 12 x 20A Leading Edge Dimmer Installation Manual contents Features.. 2 Dimmable Lamps Chart... 7 Important Safeguards.. 2 Troubleshooting. 8 Internal View.. 3 Specifications. 8 Mounting. 4

More information

DLE405 4 x 5A Leading Edge Dimmer Installation Manual

DLE405 4 x 5A Leading Edge Dimmer Installation Manual DLE405 4 x 5A Leading Edge Dimmer Installation Manual contents Features.. 2 Important Safeguards.. 2 Internal View.. 3 Mounting. 4 Supply & Load Cable Connections. 5 Connecting Serial Control Cables..

More information

PLPC905GL-3-KNX / PLPC905GL-3-HD-KNX / PLPC905GL-4-KNX / PLPC905GL-4-HD-KNX LightMaster Dimmer Actuator

PLPC905GL-3-KNX / PLPC905GL-3-HD-KNX / PLPC905GL-4-KNX / PLPC905GL-4-HD-KNX LightMaster Dimmer Actuator Features Supply 100-240V 50/60Hz single phase at 16A. Switched Outputs 9 x Maintained NC switched output 9 x Switched outputs, total box load 16A Standard & Heavy Duty (HD) models Mains switched outputs,

More information

DTP170. Colour Touch Screen Installation Manual. contents

DTP170. Colour Touch Screen Installation Manual. contents DTP170 Colour Touch Screen Installation Manual contents Warning.. 2 Internal View.. 3 Features.. 2 Mounting. 4 Important Safeguards.. 2 Connecting Serial Control Cables.. 5 Specifications. 3 WMGD Pty Limited

More information

DMC2. Installation Guide Version 1.0. Area for main photograph. Area for insert photo. W: 46.1mm up to 79 mm H: 46.1mm

DMC2. Installation Guide Version 1.0. Area for main photograph. Area for insert photo. W: 46.1mm up to 79 mm H: 46.1mm Area for main photograph Area for insert photo W: 46.1mm up to 79 mm H: 46.1mm X: 12.6mm absolute on page Y: 132.6mm abs on page This insert has a shadow DMC2 Installation Guide Version 1.0 Contents DMC2

More information

Dimmer Controllers. Load Controllers. 38 Philips Dynalite

Dimmer Controllers. Load Controllers. 38 Philips Dynalite Dimmer Controllers Philips Dynalite support a wide selection of dimmer units that are compatible to most lamp types. By selecting the right dimmer for the different lamp types, an unlimited number of combinations

More information

DLE1210 LEADING EDGE DIMMER INSTRUCTION MANUAL. Contents

DLE1210 LEADING EDGE DIMMER INSTRUCTION MANUAL. Contents DLE1210 LEADING EDGE DIMMER INSTRUCTION MANUAL Contents Features.. 2 Preset Programming Using The Program Key. 8 Important Safeguards.. 2 Hold Down Programming Of Presets. 9 Internal View.. 3 Dimmable

More information

Network Devices & Commissioning Tools

Network Devices & Commissioning Tools 74 Philips Dynalite Network Devices & To bring all the different devices together, Philips Dynalite supports a range of network devices that are useful in creating a problem free installation. Network

More information

Sophisticated yet simple energy-efficient lighting solutions

Sophisticated yet simple energy-efficient lighting solutions Lighting Sophisticated yet simple energy-efficient lighting solutions Dynalite System Integration Within any modern project, many third-party systems can be found performing different roles. Each separate

More information

Load Controllers. 30 Philips Dynalite

Load Controllers. 30 Philips Dynalite Acting as the heart of the automation system, the Philips Dynalite range of load controllers can directly drive the different lighting groups within projects. By supporting a variety of different style

More information

Compact controller for single room solutions

Compact controller for single room solutions Multipurpose Controllers DDMC-GRMS Multipurpose Modular Room Controller Compact controller for single room solutions The Philips Dynalite DDMC-GRMS is a general room automation and energy management system.

More information

Sophisticated yet simple energy-efficient lighting solutions

Sophisticated yet simple energy-efficient lighting solutions Lighting Sophisticated yet simple energy-efficient lighting solutions Dynalite System Integration Within any modern project, many third-party systems can be found performing different roles. Each separate

More information

Integration Devices. 60 Philips Dynalite

Integration Devices. 60 Philips Dynalite Within any modern project, many third-party systems can be found performing different roles. Each separate system may use a different protocol for communication. To unite the efforts of these different

More information

Sophisticated yet simple energy-efficient lighting solutions

Sophisticated yet simple energy-efficient lighting solutions Lighting Sophisticated yet simple energy-efficient lighting solutions Dynalite System Integration Within any modern project, many third-party systems can be found performing different roles. Each separate

More information

Control different load types with one device

Control different load types with one device Multipurpose Controllers DDMC802 Multipurpose Modular Controller Control different load types with one device The Philips Dynalite DDMC802 provides up to eight configurable output channels, controlled

More information

EnvisionTouch Intuitive mobile app with predesigned controls for your Philips Dynalite System

EnvisionTouch Intuitive mobile app with predesigned controls for your Philips Dynalite System EnvisionTouch Intuitive mobile app with predesigned controls for your Philips Dynalite System User Guide Version 1.2 November 11, 2013 Background Philips Dynalite is a highly specialized company whose

More information

Product and functional description

Product and functional description Product and functional description Connection example The universal dimmer main module N 528/31 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,

More information

Model HM-535 Power Supply Installation and Service Instructions

Model HM-535 Power Supply Installation and Service Instructions Model HM-535 Power Supply Installation and Service Instructions 430-535 0104 2004 Heritage MedCall, Inc SENTRY INSTALLATION & SERVICE INSTRUCTIONS POWER SUPPLY UNIT Model HM-535 IMPORTANT SAFETY INSTRUCTIONS

More information

Control different load types with one device

Control different load types with one device Multipurpose Controllers DDMC802 Multipurpose Modular Controller Control different load types with one device The Philips Dynalite DDMC802 provides up to eight configurable output channels, controlled

More information

Installation Instructions

Installation Instructions Please read all instructions before installing RS-350 PIR Dual Relay Universal Application Wall Switch Vacancy Sensor with Manual ON/OFF Lens Lighted Switch ON/OFF button for Relay 1 ON/OFF button for

More information

LCC1653/01, LRI1653/01 ActiLume DALI System

LCC1653/01, LRI1653/01 ActiLume DALI System 1/8 Product description The Philips ActiLume lighting control system consists of a small, lightweight sensor and controller, designed for easy integration into luminaires. ActiLume is a true Plug and Play

More information

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005 Product and Applications Description Application Programs The application programs of the dimmer UP 525/01 consist of two elements: the actuating and the sensor program element. The tasks actuating program

More information

Sophisticated yet. solutions. Dynalite Integration Devices. Benefits. Features. Application

Sophisticated yet. solutions. Dynalite Integration Devices. Benefits. Features. Application Lighting Sophisticated yet simple energyefficient lighting solutions Within any modern project, many third-party systems can be found performing different roles. Each separate system may use a different

More information

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis.

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis. A21 DIMMER CABINET SPECIFICATION. GENERAL. A.) Overview. 1.) The dimmer cabinets shall be fully digital, designed specifically for architectural and entertainment lighting applications, and shall consist

More information

Product and functional description

Product and functional description Product and functional description The RS 525/23 Universal Dimmer is a KNX device with one dimmer output. The device is installed in an AP 118 Control Module Box or an AP 641 Room Control Box. The bus

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

10W LED PIN SPOT. User Manual LED-PS10D W. Innovation, Quality, Performance. Professional Entertainment Technology 11-

10W LED PIN SPOT. User Manual LED-PS10D W. Innovation, Quality, Performance. Professional Entertainment Technology 11- Innovation, Quality, Performance 11-10W LED PIN SPOT LED-PS10D W User Manual Professional Entertainment Technology TABLE OF CONTENTS 1. Safety Instruction 2. Technical Specification 3. Installation 4.

More information

Product and functional description

Product and functional description Product and functional description Connection example The universal dimmer submodule N 528/41 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,

More information

Extension module for lighting control

Extension module for lighting control s 3 842 DESIGO RXC Extension module for lighting control Extension to the RXC30 / RXC31 / RXC38 room controller RXC40.1 RXC40.5 The RXC40 extension module is used in conjunction with an RXC30, RXC31 or

More information

WINSTA. Full Line Catalog 2008/2009

WINSTA. Full Line Catalog 2008/2009 WINSTA Full Line Catalog 2008/2009 5 Contents FULL LINE CATALOG W4, Volume 1 Rail-Mounted Terminal Block Systems FULL LINE CATALOG W4 Rail-Mounted Terminal Blocks Volume 1 X-COM -SYSTEM Terminal Strips

More information

Switched Relay Controller - Relay Panel with Breakers

Switched Relay Controller - Relay Panel with Breakers Installation Instructions Model # SC-RPB INS # Contents Contents Description Page Safety....................................................................... 3 Please Read This First... 3 Introduction...

More information

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs Product and Applications Description Example of Operation dimmer UP 525/11 load circuit AC 230 V L1 N The dimmer UP 525/11 is a dimming actuator for mounting in box mounts (a.o. 60 mm Ø, 60 mm depth).

More information

Single Channel Lighting Control Module

Single Channel Lighting Control Module Product Guide LMS-MIN-LCM, LMS-MIN-LCM-DIM, LMS-MIN-LCM-EM Single Channel Lighting Control Module The LMS-MIN-LCM series of lighting control modules (LCMs) are used as part of the LMS Lighting Management

More information

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011 Technical data 2CDC507101D0202 ABB i-bus KNX Product description The ABB i-bus KNX DALI Light Controller DLR/S 8.16.1M is a KNX modular installation device (MDRC) in ProM design for installation in the

More information

DTC602. Timeclock Installation Manual. contents. Operating the DTC Installing the DTC602 7

DTC602. Timeclock Installation Manual. contents. Operating the DTC Installing the DTC602 7 DTC602 Timeclock Installation Manual contents Operating the DTC602. 2 Installing the DTC602 7 WMGD Pty Limited trading as Dynalite Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia t +61 8338 9899 f

More information

CP 64 BD15 CP 64 PD15

CP 64 BD15 CP 64 PD15 COLOR PAR 64 CP 64 BD15 CP 64 PD15 User Manual Please read the instruction carefully before use Contents 1. Safety Instruction...2 2. Technical Specification...3 3. Installation...4 4. DMX Address Setting...4

More information

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet General Information ControlKeeper 4 Installation Sheet Model# CK4-120NO- Model# CK4-277NO The ControlKeeper-4 model is shipped in one package and is configured with either a 120V or a 277V transformer.

More information

BW-108. Building Wash BW-108. User Guide. Advanced LED Technology

BW-108. Building Wash BW-108. User Guide. Advanced LED Technology Building Wash User Guide Advanced LED Technology TABLE OF CONTENTS 1. Safety Instruction 2. Technical Specification 3. Change Beam Angle 4. Main Function 5. How To Control The Unit 6. Troubleshooting 7.

More information

H704-42(H)(E), H704-42/1(H)(E)

H704-42(H)(E), H704-42/1(H)(E) POWER MONITORING INSTALLATION GUIDE H704-42(H)(E), H704-42/1(H)(E) Branch Current Monitor DANGER NOTICE Installer's Specifications General: Operating Temp. Range 0 to 60 C (32 to 140 F) (

More information

SCD96 DMX Output Interface. Installation guide

SCD96 DMX Output Interface. Installation guide SCD96 DMX Output Interface Installation guide Contents Introduction 2 Welcome 2 Dimensions 2 Specification 2 Safety 3 Please read this first 3 Mounting 4 Location and spacing 4 Ambient atmosphere requirements

More information

Product and functional description

Product and functional description Product and functional description The UP 525/13 Universal Dimmer is a KNX device with one dimmer output. The device is installed in a flushmount wall box (60 mm Ø, depth 60 mm) or an installation box.

More information

1 IF-812 or IF-815 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-812/IF-815

1 IF-812 or IF-815 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-812/IF-815 95-10324_V2016-11-23 IF-812/IF-815 1 IF-812 or IF-815 Terminal (Slave) Thank you for choosing an Interflex system. With an IF-812 or IF-815 terminal (slave), you have purchased a reliable device for capturing

More information

C-Bus Network Bridge 5500NB. Series. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

C-Bus Network Bridge 5500NB. Series. Installation Instructions REGISTERED DESIGN REGISTERED PATENT C-Bus Network Bridge 5500NB Series Installation Instructions REGISTERED DESIGN REGISTERED PATENT Contents 1.0 Description...3 1.1 Capabilities...3 1.2 Status Indicators...4 2.0 C-Bus Network Connections...5

More information

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies ADC7520 SERIES 1600W Battery Chargers and Power Supplies Wide output adjustment range 0 72VDC Analog control by external 0-5VDC voltage Temp.comp charging, sense as on option Power fail relay alarm Master-Slave

More information

LED BEAM 300 LED-MB50. User. Guide. Professional Entertainment Technology

LED BEAM 300 LED-MB50. User. Guide. Professional Entertainment Technology LED BEAM 300 LED-MB50 Guide User Professional Entertainment Technology TABLE OF CONTENTS 1. Safety Instruction 2. Technical Specification 3. How To Set The Unit 4. How To Control The Unit 5. Troubleshooting

More information

Professional Entertainment Technology LED BEAM 300 LED-MB50. Innovation, Quality, Performance 23-

Professional Entertainment Technology LED BEAM 300 LED-MB50. Innovation, Quality, Performance 23- Innovation, Quality, Performance 23- LED BEAM 300 LED-MB50 User Guide Professional Entertainment Technology EC Declaration of Conformity We declare that our products (lighting equipments) comply with the

More information

dynamic white par manual

dynamic white par manual dynamic white par manual V2.0 AUGUST 2017 table of CONTENTS Dimensions 1 Safety information 2 Fixture overview 4 Introduction 5 AC power 5 Power voltage 5 Power cables 6 Relaying power to other devices

More information

Professional Entertainment Technology LED BEAM 300 LED-MB50. User. Guide

Professional Entertainment Technology LED BEAM 300 LED-MB50. User. Guide Professional Entertainment Technology LED BEAM 300 LED-MB50 Guide User 1- 1. Safety Instruction WARNING Please read carefully the instruction, which includes important information about the installation,

More information

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Rhino Buffer Module PSM24-BFM600S. Operating Instructions Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts

More information

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications 3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for

More information

TABLE OF CONTENTS 1. Safety Instructions 2. Technical Specifications 3. Installation 4. How to Connect the Fixture 5. DMX512 Connections 6.

TABLE OF CONTENTS 1. Safety Instructions 2. Technical Specifications 3. Installation 4. How to Connect the Fixture 5. DMX512 Connections 6. TABLE OF CONTENTS 1. Safety Instructions 2. Technical Specifications 3. Installation 4. How to Connect the Fixture 5. DMX512 Connections 6. How to Set the Unit 7. DMX Configuration 8. IR Remote Control

More information

CLS LDV-45. CLS Atmosphere LED-panel CLS LDV-45

CLS LDV-45. CLS Atmosphere LED-panel CLS LDV-45 INTRODUCTION The is a DMX controllable LED dimmer, which has a maximum of 4 regulated voltage DC outputs. Up to a maximum of 5A per channel at 2-24 Volts, with a total maximum current of 0A. Equipped with

More information

1 Safety instructions. 2 Device components. 3 Function. IC00P01DAL - DALI gateway. DALI gateway. Operating instructions

1 Safety instructions. 2 Device components. 3 Function. IC00P01DAL - DALI gateway. DALI gateway. Operating instructions DALI gateway Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Serious injuries, fire or property damage possible. Please

More information

Measurement Systems Datascan Installation and User Guide

Measurement Systems Datascan Installation and User Guide Measurement Systems Datascan Installation and User Guide Supplied By Contents Contents 1. INTRODUCTION... 1 1.1 GENERAL... 1 1.2 DATASCAN MODULE RANGE... 1 1.2.1 Measurement Processors... 1 1.2.2 Analog

More information

LED SPIDER MOVING HEAD LIGHT

LED SPIDER MOVING HEAD LIGHT LED SPIDER MOVING HEAD LIGHT MJ-1031C (4IN1) INSTRUCTION MANUAL Thank you for choosing our LED spider moving head light. For the sake of your safety, Please read and follow these instructions carefully

More information

Professional Entertainment Technology. imove 50SR. Innovation, Quality, Performance 21-

Professional Entertainment Technology. imove 50SR. Innovation, Quality, Performance 21- Innovation, Quality, Performance 21- imove 50SR User Guide Professional Entertainment Technology EC Declaration of Conformity We declare that our products (lighting equipments) comply with the following

More information

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Clipsal Bus Couplers Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Instruction Bulletin Retain for future use. Clipsal Bus Couplers 63249-420-236A2 Instruction

More information

VBAR 270. User Manual. Version 1.2

VBAR 270. User Manual. Version 1.2 VBAR 270 User Manual Version 1.2 VBAR 270 User Manual Page 1of 19 Introduction Thank you for purchasing VBAR 270. VBAR 270 is a LED light fixture for professional use. Using the RGB color mixing technology

More information

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities MiG2 CONTROLLERS 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities The MiG2 controllers incorporate: 2 Inputs (Configurable as Resistive, 0 10V, 0 20mA or 4 20mA) 2 or 4 Relay Outputs

More information

AirTest Model CN9000 Series Sensor Controller

AirTest Model CN9000 Series Sensor Controller AirTest Model CN9000 Series Sensor Controller AirTest Model CN9000 Series Sensor Controller THEORY OF OPERATION A basic CN9000 configuration consists of Input/Process/Display combination modules, a 3 relay

More information

AB0602D ARCHITECTURAL BALLAST DRIVER. Version Date 06/25/2012

AB0602D ARCHITECTURAL BALLAST DRIVER. Version Date 06/25/2012 AB0602D ARCHITECTURAL BALLAST DRIVER Version 0.10 Date 06/25/2012 Page 2 of 10 DESCRIPTION AND FEATURES The AB-0602D is a 6 circuit, 2400 Watts per circuit ballast driver intended for dimmable fluorescent

More information

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING Product and Applications Description Note If the application program is not loaded completely by the ETS, you had better interrupt the 24 V voltage supply of the I/O-module during the loading interval.

More information

Lighting Energy Management Building Controls. LibRE Installation Guide

Lighting Energy Management Building Controls. LibRE Installation Guide Lighting Energy Management Building Controls LibRE Installation Guide V 0.1 March 2015 1 Safety Information Save These Instructions The following symbols are used throughout this manual to indicate potentially

More information

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016 Operating instructions AS-i SmartLine module AC3200 AC3201 80237876/00 06/2016 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Warnings used...3 2 Safety instructions...3 2.1 General...3 2.2 Target

More information

Sophisticated yet simple energy-efficient lighting solutions

Sophisticated yet simple energy-efficient lighting solutions Lighting Sophisticated yet simple energy-efficient lighting solutions Dynalite System Integration Within any modern project, many third-party systems can be found performing different roles. Each separate

More information

X-618 Public Address and Voice

X-618 Public Address and Voice X-618 Public Address and Voice Alarm System Installation Manual M_XXXXXX_EN_1.0 Copyright 2012 Honeywell International Inc. All rights reserved. No part of this document may be reproduced in any form

More information

Control different load types with one device

Control different load types with one device Multipurpose Controllers DMC2 Multipurpose Modular Controller Control different load types with one device The Philips Dynalite DMC2 provides multichannel control via two interchangeable output modules.

More information

1 IF-810 or IF-811 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-810/IF-811

1 IF-810 or IF-811 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-810/IF-811 95-10326_V2016-10-20 IF-810/IF-811 1 IF-810 or IF-811 Terminal (Slave) Thank you for choosing an Interflex system. With an IF-810 or IF-811 terminal (slave), you have purchased a reliable device for capturing

More information

ICLS Installation Guidelines

ICLS Installation Guidelines ICLS Installation Guidelines 6 1 1 2 Control Pack / Row Pack 1 2 / Install these components in a easily accessible place near the main input power for the room. The default location is near the main room

More information

SAMURAI SCAN 50 LED-SC50D. User Guide. Innovation, Quality, Performance. Professional Entertainment Technology 19-

SAMURAI SCAN 50 LED-SC50D. User Guide. Innovation, Quality, Performance. Professional Entertainment Technology 19- SAMURAI SCAN 50 LED-SC50D Innovation, Quality, Performance User Guide Professional Entertainment Technology 19- EC Declaration of Conformity We declare that our products (lighting equipments) comply with

More information

QSNE-2DAL-D Energi Savr Node QSTM 20 V. DALI Loop 2. seetouch QS Wallstation Energi Savr Node QS. QS Control Link

QSNE-2DAL-D Energi Savr Node QSTM 20 V. DALI Loop 2. seetouch QS Wallstation Energi Savr Node QS. QS Control Link LUTRON R Node TM NE-2DAL-D Fixture Controller NE-2DAL-D 09.0.09 Node TM The Node is a DIN-rail mounted controller for -compliant Digital Addressable loads. It provides bus power and control for two independent

More information

Eternal Lighting. Premier150 Spot. User Manual

Eternal Lighting. Premier150 Spot. User Manual Eternal Lighting Premier150 Spot User Manual Introduction: Thank you for your purchase of the Premier150 Spot. When unpacking and before disposing of the carton, check there is no transportation damage

More information

LED PANEL. User Manual Please read the instructions carefully before use LED-7TC. Innovation, Quality, Performance 15-

LED PANEL. User Manual Please read the instructions carefully before use LED-7TC. Innovation, Quality, Performance 15- LED PANEL LED-7TC Innovation, Quality, Performance User Manual Please read the instructions carefully before use 15- 9. Fixture Cleaning TABLE OF CONTENTS 1. Safety Instructions 2. Technical Specifications

More information

DynamicTouch. User Guide Advanced lighting controls made easy. Version 1.3

DynamicTouch. User Guide Advanced lighting controls made easy. Version 1.3 DynamicTouch User Guide Advanced lighting controls made easy Version 1.3 Background Philips Dynalite is a highly specialized company whose principal occupation is to provide cutting edge solutions for

More information

Non-communicating room controllers

Non-communicating room controllers 3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,

More information

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0 BS 287 DUAL CHANNEL POWER SUPPLY User Manual January 2017 V1.0 Table of contents 1.0 SAFETY INSTRUCTIONS... 3 2.0 GENERAL DESCRIPTION PS 289... 4 3.0 MECHANICAL INSTALLATION... 5 4.0 MAINS POWER & SAFETY

More information

Mini Recessed PIR. Model: PDFM360MINI. Installation & Operating Instructions

Mini Recessed PIR. Model: PDFM360MINI. Installation & Operating Instructions Mini Recessed PIR Model: PDFM360MINI Installation & Operating Instructions 1 1. General Information These instructions should be read carefully and retained for further reference and maintenance. 2. Safety

More information

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318 ATS-16 HV Automatic Transfer Switch 16A / 230Vac USER MANUAL V090318 SAFETY Intended use The ATS-16 HV device serves as a power source selector to provide improved power supply for connected loads. ATS-16

More information

User Guide Attracta Magnetic Lighting

User Guide Attracta Magnetic Lighting User Guide Attracta Magnetic Lighting Magnetic Lighting System Models and accessories covered by this manual: UFO ATR-CM Corner Mount Extrusion UFO ATR-SM Surface Mount Extrusion UFO ATR-LG L Shaped Gantry

More information

Component identification

Component identification IO-ATC8 I/O Expansion Module 8 Analog/Thermocouple Inputs The IO-ATC8 is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 8 inputs that

More information

Installation manual for for Schleifenbauer DPM3

Installation manual for for Schleifenbauer DPM3 Installation manual for for Schleifenbauer DPM3 Installatie handleiding voor Schleifenbauer DPM3 Installationsanleitung für Schleifenbauer DPM3 Guide d installation du Schleifenbauer DPM3 Installation

More information

Fibre Modem - Single-mode

Fibre Modem - Single-mode Revision 1.0 November. 2006 1 - Single-mode P/N: : 995087 Model 3000 / Access 4000 Optically Isolated Interface INSTALLATION GUIDE OVERVIEW: The Inner Range Single-mode provides 2 separate, optically isolated

More information

Distributed Power Series

Distributed Power Series GENERAL INFORMATION The Room Controller offers a full power and control solution for standalone and integrated room controls. With up to eight zones of relay switching with 0-10V control fully rated at

More information

4. How to Connect the Fixture 3-Pin and 5-Pin XLR DMX Connectors:

4. How to Connect the Fixture 3-Pin and 5-Pin XLR DMX Connectors: TABLE OF CONTENTS 1. Safety Instructions 2. Technical Specifications 3. Installation 4. How to Connect the Fixture 5. DMX512 Configuration 6. DMX512 Connections 7. How to Set the Unit 8. Troubleshooting

More information

STAGE TRI-PAR 18TC CP-18TC. User Manual. Please read the instructions carefully before use

STAGE TRI-PAR 18TC CP-18TC. User Manual. Please read the instructions carefully before use STAGE TRI-PAR 18TC CP-18TC User Manual Please read the instructions carefully before use TABLE OF CONTENTS 1. Safety Instructions 2. Technical Specifications 3. How to Set the Fixture 4. How to Control

More information

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits.

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits. Peripheral Relay The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits. Up to 16 Cards can be connected to a multi-loop panel

More information

NMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02

NMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02 1/8 NRK16/A, NRK16-B/A, (NRK16-T /A, NRK14-T /A, NRK16-WEB/A) Control and interlock devices with pre-programmed system-specific application modules The controllers may be used as stand-alone control and

More information

LED W RGBA User Manual

LED W RGBA User Manual LED- 245-1W RGBA User Manual Please read the instructions carefully before use CONTENTS 1. Safety Instructions...2 2. Technical Specifications...3 3. How To Set The Unit...4 3.1 Control Panel...4 3.2 Main

More information

Installation & Operation Guide

Installation & Operation Guide Installation & Operation Guide (Shown with optional Override Board Cover) KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller 902-019-04B 1 Introduction This section provides a brief

More information

E600 VX01 Installation guide

E600 VX01 Installation guide E600 VX01 Installation guide illuminfx Dimensions 2007 Viso Systems ApS, Denmark All rights reserved. No part of this manual may be reproduced, in any form or by any means, without permission in writing

More information

MATRIX LED LED User Manual Please read the instructions carefully before use

MATRIX LED LED User Manual Please read the instructions carefully before use MATRIX LED LED-7871 User Manual Please read the instructions carefully before use 1- 1. Safety Introductions TABLE OF CONTENTS WARNING Please read the instructions carefully which includes important information

More information

Fan Coil Unit Controller

Fan Coil Unit Controller Fan Coil Unit Controller Networked heating, ventilation and air conditioning control User Guide Version 1.0 Philips Dynalite 6/691 Gardeners Road Mascot NSW 2020 Australia P: +61 (0)2 8338 9000 F: +61

More information

COMPACT LED DRIVERS. PrimeLine DALI dimmable & Selectable Current (Dip Switch) PrimeLine DALI DIMMABLE & SELECTABLE CURRENT (DIP SWITCH)

COMPACT LED DRIVERS. PrimeLine DALI dimmable & Selectable Current (Dip Switch) PrimeLine DALI DIMMABLE & SELECTABLE CURRENT (DIP SWITCH) COMPACT LED DRIVERS PrimeLine DALI DIMMABLE & SELECTABLE CURRENT (DIP SWITCH) 186762, 186763 Typical Applications Built-in in compact luminaires Shop lighting Downlights PrimeLine DALI dimmable & Selectable

More information