REFERENCE GUIDE. Copyright 2013 ComAp a.s.

Size: px
Start display at page:

Download "REFERENCE GUIDE. Copyright 2013 ComAp a.s."

Transcription

1 Compact Controller for Stand-by and Parallel Operating Gen-sets Inteli New Technology Modular Generator Controller Multiple Internal engines application SW configuration MINT - GeCon IG-NT, IG-NTC, IS-NT Software version IGS-NT-GeCon-MARINE, November 2013 REFERENCE GUIDE Copyright 2013 ComAp a.s. ComAp a.s.. Kundratka 2359/17, Praha 8, Czech Republic Tel: , Fax: Technical support hotline: info@comap.cz,

2 Table of Contents Table of Contents... 2 General guidelines... 3 What is described in this manual?... 3 General description... 5 Description of the controller system (with all options)... 5 Comparing of IGS-NT-GeCon-1.7 to the standard IGS-NT-MINT Available documentation... 5 Functions... 6 Modified setpoints... 6 Controller modes in MINT application... 6 Power management PLC functions Multi language support Protections and Alarm management Gen-set operation states Inputs and Outputs Virtual and physical modules Maximum number of configured I/O modules Binary Inputs - Control Binary inputs Status information Binary outputs Breaker control Binary outputs Control loops Binary outputs Status information Binary outputs Fixed protection outputs Binary outputs Power management Binary outputs Configurable Prg. States Analog inputs Analog outputs Analog values Setpoints ProcessControl Basic settings Delays/Timers Analog protect Gener protect Pwr management Sync/Load ctrl Sync/load control adjustment Volt/PF ctrl Volt/PF control adjustment Force value Load shedding Timer settings Act. calls/sms Date/Time Controller configuration and monitoring Direct connection to the PC GenConfig functions InteliMonitor Modbus protocol Value and setpoint codes Technical data

3 General guidelines What is described in this manual? This manual describes IGS-NT-GeCon - MINT software configuration. The Generator controller software configuration is designed for multiple sets applications with internal load sharer and synchronizer. What is the purpose of this manual? This manual provides general information on how to configure and operate the controller. This manual is intended for use by: Operators of gen-sets Gen-set control panel builders For everybody who is concerned with installation, operation and maintenance of the gen-set!! Warnings!! Remote control The IG-NT controller can be remotely controlled. In case that maintenance needs to be done to the gen-set, check the following to ensure that the engine cannot be started. To be sure: Disconnect remote control via RS232 line Disconnect input REMOTE START/STOP or Disconnect output STARTER and output GCB CLOSE/OPEN The controller contains a large number of configurable setpoints, because of this it is impossible to describe all of its functions. These are subject to change from SW version to SW version. This manual only describes the product and is not guaranteed to be set for your application on arrival. Text PAGE Break Return Generator protections REMOTE START/STOP Cyan background (Capital letters in the frame) buttons on the front panel (Italic) set points (Bold) Set point group (Capital letters) binary inputs and outputs Valid for IS-NT only Conformity declaration Following described machine complies with the appropriate basic safety and health requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type, as brought into circulation by us. Note: ComAp believes that all information provided herein is correct and reliable and reserves the right to update at any time. ComAp does not assume any responsibility for its use unless otherwise expressly undertaken. 3

4 WARNING VERY IMPORTANT!!! Be aware that the binary outputs can change state during and after software reprogramming (before the controller is used again ensure that the proper configuration and setpoint settings are set in the controller)!!! Be aware that gen-set can automatically or remotely start!!! Switch the controller to SEM mode and disconnect the Binary outputs Starter and Fuel to avoid unexpected automatic start of gen-set and GCB closing. Dangerous voltage!!! CAUTION!!! The terminals for voltage and current measurement should never be touched. Properly connect the grounding terminals. Do not disconnect the CT terminals for any reason. Adjust set points All setpoints are preadjusted to their typical values. But the set points in the Basic settings settings group!!must!! be adjusted before the first startup of the gen-set.!!! WRONG ADJUSTMENT OF BASIC PARAMETERS CAN DESTROY THE GEN-SET!!! The following instructions are for qualified personnel only. To avoid personal injury do not perform any action not specified in this User guide!!! 4

5 General description Description of the controller system (with all options) NT Family controllers are comprehensive AMF-controllers for single and multiple generating sets operating in stand-by or parallel modes. A modular construction allows upgrades to different levels of complexity in order to provide the best solution for various customer applications. NT Family controllers are equipped with a powerful graphic display showing icons, symbols and bar-graphs for intuitive operation, which sets, together with high functionality, new standards in Gen-set controls. The controller automatically starts the gen-set, closes the Gen-set C.B. when all conditions are met, then stops the engine* (* sw GeCon opens GCB only, not stops the engine) on external signal or by pressing push buttons. Parallel to the Mains operation is a standard feature. Isolated parallel and Power Management System support are optional. Forward and reverse synchronizing, Generator protections, Mains protection including vector shift, load and power factor control are the major functions provided. Interfacing to foreign synchronizers and load sharers is supported. The key feature of the controller is its easy-to-use operation and installation. Predefined configurations for typical applications are available as well as user-defined configurations for special applications. Comparing of IGS-NT-GeCon-MARINE 3.0 with standard IGS-NT GeCon does not take care of Engine control GeCon accepts in SEM mode external control of GCB and Engine GeCon can control the engine via Binary start/stop output signals only see below. The independent Engine controller (e.g. ID-DCU) is expected. Synchronizing and unloading timeouts can be disabled by setpoint setting (or Force value function) All regulations (load, VAr sharing, frequency, voltage) can be disabled by setpoint change or by Force value Interface GeCon to engine controller is provided by I/O wires no by communication line. Active protections does not send stop request to engine (except for SlowStop protection) Available documentation PDF FILE InteliMonitor-2.7-Reference Guide GenConfig-2.6-Reference Guide IGS-NT Communication Guide IGS-NT-2.6 Installation Guide IGS-NT-2.6 Application Guide IGS-NT-2.6-Operator guide.pdf DESCRIPTION Reference Guide for monitoring tool Reference Guide for configuration tool Communication guide for IG/IS-NT controllers. It contains information how to connect control unit and all communication features descriptions Installation guide for IG/IS-NT controllers. It contains technical information about controler and extension modules Application guide for IG/IS-NT controllers. It refers to application and typical installation settings and sites structures Operator guide for IG/IS-NT 5

6 Functions For the IGS-NT-GeCon-MARINE is possible to use IGS-NT-LSM+PMS or IGS-NT-GeCon-LSM+PMS dongle which enables the Load sharing and Power management functions. (both types of dongles have the same function) Modified setpoints Below mentioned are GeCon specific setpoints only. Group Setpoint Option Function Process control StartStopBtn ENABLED DISABLED Standard panel Start/Stop buttons function. Panel Start/Stop buttons are disabled. ProtectionMode ACTIVE NOT ACTIVE 2-nd level protections are blocked. GCB is not controlled. Sync/Load ctrl Sync timeout s NO TIMEOUT Standard MINT function. Unlimited synchronizing time. GCB open level 1-100% NO LEVEL Standard MINT function. No generator power open level detection. GCB open del s NO TIMEOUT Standard MINT function. Unlimited unloading procedure. All above mentioned setpoints can be Forced by Binary input(s) to another value (or switched between ENABLED and DISABLED). Based on setpoint settings there are three possible operational modes HAND SEM - AUT: HAND SEM AUT Basic setting ControllerMode SEM SEM AUT Process control StartStopBtn DISABLED ENABLED ENABLED ProtectionMode NOT ACTIVE ACTIVE ACTIVE Sync/Load ctrl Sync timeout NO TIMEOUT s s GCB open level NO LEVEL 1-100% 1-100% GCB open del NO TIMEOUT s s It is possible to configure (Force value) HAND SEM switching via Binary input. Controller modes in MINT application OFF mode Use OFF mode to block controller functions (even if is switched on). OFF mode is used for controller firmware or configuration change. Binary outputs (e.g. GCB CLOSE/OPEN) are not energized, all closed Binary outputs are opened when controller is switched to OFF mode. Gen-set cannot be started and operated from IGS-NT-GeCon controller no response for panel buttons and Binary input commands. Switching to OFF mode is blocked on running engine to avoid accidental engine stop by mode change or by firmware or configuration programming. 6

7 SEM mode Engine start can be activated from o Engine controller (e.g. ID-DCU, ID-MCU) o GeCon panel Start button o GeCon BI: StartButton o Remotely e.g. from InteliMonitor GeCon BI: ReadyToLoad initiates GeCon Running state - activates Gener protect: Min stab time a Max stab time within the generator electric protections are activated. Gen-set is loaded/unloaded from o GeCon panel GCB button o GeCon BI: GCBButton o Direct GCB hand control o Remotely e.g. from InteliMonitor GCB closing from controller can be blocked by BI: GCB disable (does not block synchronization process) Controller flow chart in SEM mode: 7

8 AUT mode Engine start or Power management is activated from GeCon BI: Sys start/stop GeCon BI: ReadyToLoad initiates GeCon Running state - activates Gener protect: Min stab time a Max stab time within the generator electric protections are activated. Gen-set starts synchronizing and is loaded/unloaded automatically based on o Power management setting o GeCon BI: Sys start/stop GeCon will stop engine started from engine controller when BI Sys start/stop or due to Power management function. 8

9 MAN mode In MANual mode, the controller evaluates configured protections only. All the regulation loops are disabled, not active. Controller s state changes based on sensed signals ReadyToLoad and GCB feedback. In case there is some active protection, this is signalized by appropriate binary outputs. Engine cannot be started from GeCon, GeCon cannot close the GCB, etc..,only opens GCB in cause SD alarm and Setpoint:Protection mode:active. BI:ReadyToLoad Running BI:GCB feedback active Stopped BI:ReadyTo Load - deact BI:GCB feedback not active BI:ReadyTo Load - deact Loaded HAND mode Hand mode is a special type of SEM mode. In Hand mode, the panel Start, Stop buttons are not working, GCB is supposed to be controlled externally. The Hand mode is achieved by setpoints adjustment - see the following picture. IG-EE GeCon MINT generator measuring Vg, Ig, Vb GCB feedback External GCB Close / Open GCB close/open (ReadyToLoad) MCU G G GCB START STOP Speed control (Sync/Load ctrl) RS232 - PC MCU Process control: StartStopBtn = DISABLED ProtectionMode = NOT ACTIVE Sync/Load ctrl: Sync timeout = NO TIMEOUT GCB open level = NO LEVEL GCB open del = NO TIMEOUT External Engine Start / Stop 9

10 Power management Automatic gen-set start / stop function based on load changes and/or Running hours or Engine size. Following functions are available: Power management in kw Guarantees adjustable load reserve (load step) in kw. Suitable for load demand-based optimization. Activation: #Pwr mgmt mode = ABS (kw) Power management in kva Guarantees adjustable load reserve (load step) in kva. Suitable for generator- or busbar dimensioningbased optimization. Activation: #Pwr mgmt mode = ABS (kva) Relative power management in % Guarantees that the engines will be not continuously loaded more than to a certain level, leaving less than selected relative load reserve. Suitable for engine life-based optimization. Activation: #Pwr mgmt mode = REL (%) 10

11 Start/Stop conditions in Power management Reserve Actual Reserve Start condition Stop condition Absolute ARstrt = ΣPg Nom ΣPg Act ARstrt < #LdResStrt ARstp > #LdResStp kw / kva ARstp = ΣPg* Nom ΣPg Act Relative % RRstrt = (ΣPg Nom ΣPg Act ) / ΣPg Nom RRstp = (ΣPg* Nom ΣPg Act ) / ΣPg* Nom RRstrt < #%LdResStrt RRstp > #%LdResStp Where ARstrt ARstp RRstrt RRstp ΣPg Nom ΣPg* Nom ΣPg Act Actual Absolute reserve in kw or kva - for engine start calculation. Actual Absolute reserves in kw or kva - for engine stop calculation. Actual Relative reserve in % - for engine start calculation. Actual Relative reserves in % - for engine stop calculation. Sum of Nominal power of all gen-sets on the bus. Sum of Nominal power of all gen-sets on the bus apart of the one, which is going to be stopped. Sum of Actual power of all gen-sets on the bus = system load. Optional functions in absolute or relative Power management are: - Running hours balancing (equalization), - Load demand (different size) engines swap and - Power management of two or more gen-set groups (bus tie support). 11

12 Running hours balancing The gen-sets priorities are automatically swapped to balance engine running hours. Up to 32 controllers are supported. Activation: #PriorAutoSwap = RUN HOURS EQU Important setpoints: RunHoursBase, #RunHrsMaxDiff LOAD G1 G2 G3 1.controller 2.controller 3.controller Basic settings: Contr.addr = 1 Pwr management: #Pwr mgmt mode = RUN HOURS EQU Priority ctrl = MASTER RunHoursBase = 100 h #RunHrsMaxDiff = 10 h Control group = COMMON Basic settings: Contr.addr = 2 Pwr management: #Pwr mgmt mode = RUN HOURS EQU Priority ctrl = SLAVE RunHoursBase = 200 h #RunHrsMaxDiff = 10 h Control group = COMMON Basic settings: Contr.addr = 3 Pwr management: #Pwr mgmt mode = RUN HOURS EQU Priority ctrl = SLAVE RunHoursBase = 300 h #RunHrsMaxDiff = 10 h Control group = COMMON Different sized engines (Load demand) swap Three running engines (priorities) are swapped based on load demand (one small engine runs on small load and swaps to another one big engine that runs when load increases). Activation: #PriorAutoSwap = LD DEMAND SWAP Important setpoints: #PwrBandContr1, #PwrBandContr2, #PwrBandContr3, #PwrBandContr4, #PwrBandChngDe. LOAD G1 G2 G3 1.controller 2.controller 3.controller Basic settings: Contr.addr = 1 Pwr management: #Pwr mgmt mode = LD DEMAND SWAP Priority ctrl = MASTER #PwrBandContr1 = 1 #PwrBandContr2 = 2 #PwrBandContr3 = 2+3 #PwrBandChngDe = 10 s Control group = COMMON Basic settings: Contr.addr = 2 Pwr management: #Pwr mgmt mode = LD DEMAND SWAP Priority ctrl = SLAVE #PwrBandContr1 = 1 #PwrBandContr2 = 2 #PwrBandContr3 = 2+3 #PwrBandChngDe = 10 s Control group = COMMON Basic settings: Contr.addr = 3 Pwr management: #Pwr mgmt mode = LD DEMAND SWAP Priority ctrl = SLAVE #PwrBandContr1 = 1 #PwrBandContr2 = 2 #PwrBandContr3 = 2+3 #PwrBandChngDe = 10 s Control group = COMMON 12

13 Pwr management of splitted group Important setpoints: Control group, GroupLinkLeft, GroupLinkRight When a Bus-tie disconnects the gen-set group the Power management and Load and Var share can operate separately on each of them. To enable the independent Pwr management, Load and Var sharing between the gensets, group of gensets splitted by bus tie breaker, configure the setpoints as depicted on this picture. LOAD1 LOAD 2 BTB G1 G2 G3 G4 G5 1.controller 2.controller 3.controller 4.controller 5.controller Basic settings: Contr.addr = 1 Pwr management: Control group = 1 GroupLinkLeft = 1 GroupLinkRight = 2 Basic settings: Contr.addr = 2 Pwr management: Control group = 1 GroupLinkLeft = C GroupLinkRight = C Basic settings: Contr.addr = 3 Pwr management: Control group = 2 GroupLinkLeft = C GroupLinkRight = C Basic settings: Contr.addr = 4 Pwr management: Control group = 2 GroupLinkLeft = C GroupLinkRight = C Basic settings: Contr.addr = 5 Pwr management: Control group = 2 GroupLinkLeft = C GroupLinkRight = C BI Group link Control group 1. BTB feedback Control group 2. Load shedding Load shedding fiction is dedicated for tripping of non-essential load in case of high generator current, or drop of generator frequency above/below preadjusted limits, for preadjusted time. All LOAD SHED outputs are activated (closed) to trip the unessential load when gen-set goes to island: a) When GCB is closed after mains fail and gen-set starts in AUT mode. b) When MCB opens from parallel to mains operation in AUT mode. c) Before MCB is opened in SEM mode by button. The load shedding function is active in all controller modes except OFF and MAN. Load shedding has ten steps and each step is linked with its own Load shed x binary output. The non essential load shedding is based on generator current and generator frequency. There is only one level for current load shedding and one level for frequency load shedding for all 10 steps, as well for reconnection level and delay. Load shed can only move from one step to the next, e.g. No LoadShed to LdShed S1 to LdShed S2 to LdShed S10 and vice versa. If manual reconnection of the load is desired, the AutoLd recon setpoint needs to be disabled (AutoLd recon = DISABLED) and the MAN load recon binary input needs to be configured. Rising edge on this input resets the controller to a lower stage, but only if the load is under the Ld recon level at that moment. The current load shedding can be activated in case any of phase current exceeds the adjusted limit. The reconnection is able only in case all of the current values are below reconnection level. 13

14 ManualLdRecon CurShedLev CurRecLev FreqShedLvl FreqRecLvl Load shedding: Ld Shed delay Ld recon delay LdShed stage 1 LdShed stage 2 LdShed stage 10 If no Load Shedding outputs are configured, there is no record to history and no screen timer indication of the activity of this function. On the following pictures, the generator current load shedding is depicted. The current is evaluated from all 3 phases, each phase can activate the load shedding. On the picture, due to transparency, only 3 load shed outputs are depicted, not all 10. The generator frequency based load shedding is in fact the same, but fall below preadjusted limit is watched, instead of exceeding of the limit as in case of current load shedding. Gen-set current Curr shed level BO Load shed 1 BO Load shed 2 BO Load shed 3 closed closed closed Ld shed del Ld shed del Ld shed del Load reconnection automatic -> AutoLd recon = ENABLED Curr recon level Gen-set current BO Load shed 3 opened BO Load shed 2 opened BO Load shed 1 opened Ld recon del Ld recon del Ld recon del Load reconnection manual -> AutoLd recon = DISABLED 14

15 Curr recon level Gen-set current BO Load shed 3 opened BO Load shed 2 opened BO Load shed 1 opened BI Man load recon no action PLC functions Following functions are available in IGS-NT-GeCon-MARINE firmware. Group PLC Block IS-NT-GeCon MARINE 3.0 IG-NT-GeCon MARINE 3.0 Logical function OR/AND XOR/RS Comparators Comp Hyst 16 4 Comp Time 16 4 Comp Win 16 4 Math operations Math Fc 16 2 Ext math Fc 8 2 Interpol Fc 4 1 Regulators PID Ana B 4 2 PID Bin 4 2 Ramp functions Ramp 4 2 Up/Down 4 2 Inc/Dec 2 2 Mov Avg 2 1 Time functions Timer 4 1 Delay 24 8 Others Ana Switch 16 2 Force Hist 4 4 Force Prot 4 4 Jump 4 4 Mux Const. 4 4 Counter 4 1 Decomp 4 4 Convert Multi language support NT Family controllers support up to three Languages that is possible to switch during controller duty. Every terminal (i.e. Remote display or PC-InteliMonitor) can be switched to different language. Use PC-GenConfig - Translator tool to translate texts to another language. Default application archives contain all texts in English only. 15

16 ECU interface customizing The list of available ECU interfaces can be found in GenConfig / Modules / ECU list. In sw GeCon is possible to configure the any ECU, but controller can read information only. Writing any information is not possible. ECUs comunicate via modbus are not supported. 16

17 Protections and Alarm management Protection groups There are two groups of protections in the controller: fix and customer configurable. Setpoint group Analog protections Configurable Analog protect Generator protections Configurable Gener protect Mains protections should not be used in MINT application Fix protections Configurable Fix Mains protect Engine params, Gener protect part of them, Analog protect part of them Protection types Because of limited (adjustable) GeCon influence to the Engine and GCB (depends on configuration and wiring) the GeCon protection system is more focused to fail indication. All Protection types are available because of IGS-NT system compatibility even if some Protection types have the same result in GeCon (e.g. BO, Stp, Sd). Level Protection Abbre GeCon action Record types viation 1 History record Hst None History only 1 Alarm only Al None Alarmlist only 1 Warning Wrn None Alarmlist and History 2 Off load OfL Controller opens GCB without soft Alarmlist and History unloading, gen-set runs 1 minute at Nominal RPM in AUT mode, in SEM mode it runs till operator intervene 2 Breaker Open BO Controller opens GCB without soft Alarmlist and History unloading, gen-set state changes to Running. 2 Slow stop Stp Soft unloading then the GCB opens, BO: Alarmlist and History Stop pulse activation, or deactivation of Remote S/S signal; the gen-set state changes to Stopping. 2 Shutdown Sd Controller opens GCB without soft Alarmlist and History unloading. X Sensor fail Fls Can be indicated when Analog input value is ±6% out of sensor characteristic range. Fls can optionally activate corresponding (e.g. Sd) Analog input protection as well. Alarmlist and History 17

18 Default protections in MINT Fix firmware based Generator: Corresponding setpoints IDMT overcurrent BO Basic settings: Nomin current; Gener protect: 2Inom del It is possible to switch off this protection. IDMT Active power BO Gener protect: OverldStrtEval; 2POvrldStrtEvDel Shortcurrent BO Gener protect: Ishort; Ishort del Default configurable Batt <V, Batt >V Wrn Analog protect: Batt >V; Batt <V; Batt V del EarthFaultCurr BO Gener protect: EarthFaultCurr; EthCurr del Generator frequency: fg<, fg> BO Gener protect: Gen >f; Gen <f; Generator voltage: <V, >V BO Gener protect: Gen >V; Gen <V; Gen V del Reverse power protection is not configured as default protection. This protection can be added using the GenConfig PC sw, in card Protections. Bus voltage and frequency protections it s up to the operator to configure protection in card protections (in GenConfig). Generator voltage and frequency protections - it s up to the operator to configure protection on Generator voltage values. Both protections can be deactivated by value 0 in setpoint. Shutdown override If the Binary input Sd override is closed, all 2 nd level protections are disabled to allow engine run in an emergency situation, e.g. sprinkler devices power supply. All protections are shown in Alarmlist and recorded into History, but the controller doesn t stop the engine because of them. If the input is deactivated and some protections are still active or not yet reset, the controller starts to take these protections into account and consequently stops the engine. Take in account, that the binary outputs, signalizing activation of the particular protection are active independently on the state of BI: SdOverride. All 2 nd level protections are locked out, except of these: - Emergency stop 18

19 Circuit breakers operation sequence, GCB/MCB fail detection Note: In the following text, CB abbreviation is used for MCB or GCB respectively. Related binary inputs: - CB fdb CB feedback binary input - CB fdb neg negative CB feedback binary input. Used for increasing the reliability of CB status evaluated by the controller. In case that it is not configured, negative value of CB fdb is calculated internally within the controller. Related binary outputs: - CB close/open output for circuit breaker. Equals to 1 during the time when CB is requested o be closed. - CB ON coil output for closing coil of the CB. 2s pulse (5s if synchronising is not provided by the particular CB) is used for closing the CB. - CB OFF coil output for opening coil of the CB. 2s pulse (5s if synchronising is not provided by the particular CB) is used for opening the CB. - CB UV coil output for undervoltage coil of the CB. Permanently active, 2s negative pulse (5s if synchronising is not provided by the particular CB) is used for CB opening request - CB status output indicating CB status as evaluated by the controller. This signal is used for lighting LEDs on the panel, switching the regulations, CB fail evaluation, etc. Possible CB sequences: CB close command: BO: CB close/open BO: CB UV coil BO: CB ON coil 1s minimum 1s from UV switching on, together with MinStab time elapsing is necessary before the CB is allowed to close BI: CB fdb BI: CB fdb neg BO: CB status When closing the CB, the CB status LBO switches over only when both feedbacks are in correct position 19

20 Repeated CB close command: BO: CB close/open BO: CB UV coil 1s 2s 2s 1s 2s BO: CB ON coil BO: CB OFF coil BI: CB fdb BI: CB fdb neg If the CB is not closed after the first attempt, it is only reset by OFF pulse and no CB fail is issued. This would be issued after the second unsuccessfull attempt. BO: CB status BI: CB fdb = 0 BI: CB fdb neg = 1 BO: CB status = 0 ON pulse has finished and CB status is not =1. CB fail is issued immediatelly BO: CB fail CB fail fdb mismatch: BO: CB close/open 2s BO: CB UV coil BO: CB ON coil 1s <2s ON pulse is shortened/interrupted and replaced by UV and OFF pulse BO: CB OFF coil 500 ms OFF pulse is activated until both feedbacks return to the correct position +2 seconds. BI: CB fdb BI: CB fdb neg = 1 CB fail If any inconsistence between the two feedback signals is detected, CB fail is issued. BO: CB status = 0 BO: CB fail 20

21 CB open command: BO: CB close/open BO: CB UV coil BO: CB OFF coil BI: CB fdb BI: CB fdb neg 2s Further behavior of UV output depends on the system status. In case of transition to cooling stays off, if the Cb was opened manually and the engine keeps running, it activates again after timeout elapses. During CB opening the CB status LBO is deactivated with change of the first feddback status BO: CB status Transition closing -> opening (opening command is issued during closing pulse): BO: CB close/open BO: CB ON coil <2s Closing pulse is shortened, opening sequence is started immediatelly BO: CB UV coil BO: CB OFF coil 2s CB opening by protection or manual command (button pressed) BI: CB fdb BI: CB fdb neg BO: CB status 21

22 Transition opening -> closing (closing command is issued during opening pulse) BO: CB close/open BO: CB ON coil 2s 2s In this moment, the reason for closing the CB is activated again (e.g. Remote Start/Stop is activated) BO: CB UV coil BO: CB OFF coil Here starts the standard closing sequence see CB close command. BI: CB fdb BI: CB fdb neg OFF a UV pulse is always activated for the full time. manual control (= CB button) is deactivated during opening pulse. BO: CB status Other CB fail reasons: When the BO CB close/open is in steady state and CB feedback is changed, the CB fail is detected immediately (no delay). BO GCB close/open BI GCB feedback Alarm: GCB fail opened closed active Alarm detection: immediatelly BO GCB close/open BI GCB feedback Alarm: GCB fail closed opened active Alarm detection: immediatelly When the BO CB close/open opens, there is 5 resp. 2 sec delay for the breaker to respond before a CB fail is detected. In such case, if CB OFF coil is used for opening the CB and CB fail occurs during opening the CB, the signal CB OFF coil is automatically extended until the breaker opening is detected (evaluated as CB status). 2 sec when the CB is used for synchronizing 5 sec in other cases BO GCB close/open opened BI GCB feedback Alarm: GCB fail Time delay 5 sec active opened 22

23 In case that CB fail is detected after switching the controller on (CB is closed), the CB OFF coil output is activated immediately. 23

24 Gen-set operation states Gen-set can operate in following states Not ready Gen-set is not ready to start Init After controller power supply switch on Stopped No Running indication Starting Waiting for ReadyToLoad signal Running Waiting for GCB connection or start synchronizing Soft load Gen-set power is ramping up Loaded Gen-set is loaded Soft unld Gen-set power is ramping down Stopping Stopping procedure before the BI ReadyToLoad is opened. Stopped Stopped - initial state waiting for engine start Breakers conditions Brks Off Synchro MultIslOp MultParOp GCB opened Gen-set is synchronizing (bus voltage OK, GCB is open) Multiple Island - gen-set is running loaded in island parallel mode (MCB is open, GCB is closed) Multiple Parallel gen-set is running loaded in mains parallel mode (MCB is closed, GCB is closed) 24

25 BIN BOUT AIN AOUT Inputs and Outputs Virtual and physical modules Number of I/O can be extended and project wiring can be reduced using the following extension and virtual modules. Module name Note IGS-NT controller x x x x Number of I/O depends on type. IGS-PTM Standard I/O extension module. IS-AIN Standard I/O extension module. IS-BIN16/ Standard I/O extension module. I-CB x x x x Configurable communication bridge. IGL-RA Green, Red, Yellow LED panel. I-AOUT Analog outputs VPIO Virtual periphery I/O module. SHBIN SHared (virtual) Binary INput module SHBOUT SHared (virtual) Binary OUTput module SHAIN Shared (virtual) Analog Input module SHAOUT Shared (virtual) Analog OUTput module PLC x x x x Programmable (internal) logic module. Maximum number of configured I/O modules Module name Maximum number IGS-PTM 4 IS-AIN8 10 IS- BIN16/8 6 Note Address of the module can be only 1-4. Configuration of this module decrease the maximum number of IS-AIN8 and IS-BIN16/8 and I-AOUT8 which can be additionally configured to IGS-NT controller In case there is connected any IGS-PTM (address 1-4) the maximum number of IS-AIN8 is reduced by this number In case there is connected any IGS-PTM (address 1-4) the maximum number of IS-BIN16/8 is reduced by this number. In case, there is connected any IGL-RA15 module, then one IGL-RA15 means loose of possibility to configure 2 IS-BIN16/8 I-CB 1 Address of any I-CB module must be 1 IGL-RA15 4 Configuration of this module decrease the maximum number of IS-BIN16/8 which can be additionally configured to IGS-NT controller I-AOUT8 4 Configuration of this module decrease the maximum number of IGS-PTM which can be additionally configured to IGS-NT controller VPIO 4 SHBIN 6 SHBOUT 6 SHAIN 2 SHAOUT 2 Take in account that each controller which has configured SHBOUT module should have configured this module with different address, otherwise there will be mismatch of SHBOUT modules on CAN line and Shared outputs will not work correctly Take in account that each controller which has configured SHAOUT module should have configured this module with different address, otherwise there will be mismatch of SHAOUT modules on CAN line and Shared outputs will not work correctly 25

26 Binary Inputs - Control AccessLock int If the input is closed, no setpoints can be adjusted and no commands can be issued from the controller front panel. The setpoints can be changed only externally from another panel, via remote connection (PC direct, internet, modem). As the controller mode (OFF-SEM-AUT-MAN) is one of the setpoints, not even that can be changed. The START, STOP, FAULT RESET and other control buttons are disabled as well. AccessLock D#2 If the input is closed, no setpoints can be adjusted and no commands can be issued from IG/IS-Display #2. AccessLock D#3 If the input is closed, no setpoints can be adjusted and no commands can be issued from IS-Display #3. AccessLock ext If the input is closed, no setpoints can be adjusted and no commands can be issued from any external terminal = via direct/modem/internet connection to the controller. Use these inputs to lock out the selected terminals for setpoint changes and commands. Such a terminal can only be used for monitoring. Alt brightness Active binary input switches controller display backlight to the alternative setting. Alternative intensity of the backlight can be set independently using the controller panel buttons. Input available in IG-NT/NTC and modifications only. For IG-Display and IS-Display modules, this binary input is located in the Power connector and its function is fixed (not configurable). FaultResButton Binary input has the same function as Fault reset button on the controller front panel. Take in account the setpoint Basic settings: Local buttons must be set to EXTBUTTONS or BOTH option, otherwise this input has no influence. HornResButton Binary input has the same function as Horn reset button on the controller front panel. Take in account the setpoint Basic settings: Local buttons must be set to EXTBUTTONS or BOTH option, otherwise this input has no influence. StopButton Binary input has the same function as Stop button on the controller front panel. It is active in SEM mode only. Take in account the setpoint Basic settings: Local buttons must be set to EXTBUTTONS or BOTH option, otherwise this input has no influence. StartButton Binary input has the same function as Start button on the controller front panel. It is active in SEM mode only. Take in account the setpoint Basic settings: Local buttons must be set to EXTBUTTONS or BOTH option, otherwise this input has no influence. GCBButton Binary input has the same function as GCB button on the controller front panel. It is active in SEM mode only. Take in account the setpoint Basic settings: Local buttons must be set to EXTBUTTONS or BOTH option, otherwise this input has no influence. 26

27 All Binary inputs, which simulate controller front panel buttons, are edge (no level) sensitive, and they react on the rising edge only. Minimal input pulse duration is 0,2 seconds. Remote OFF If closed, the controller mode is forced to OFF mode. When opened, controller is switched to previous - original mode. Use this input to block the engine start during service. Remote SEM Active binary input forces the controller mode to SEM mode. When opened, controller is switched to original mode. Remote AUT Active binary input forces the controller mode to AUT mode. When opened, controller is switched to original mode. Use this input to switch the controller to automatic operation, e.g. using the external key switch. Remote MAN Active binary input forces the controller mode to MAN mode. When opened, controller is switched to original mode. Force block 1 6 Three binary inputs for user-specific blocking of programmable protections. If the particular input is active, all the protections with the corresponding Force block X block type are blocked. BINARY INPUT closed Prot. block type = Force block BINARY INPUT FORCE BLOCK closed ForceBlock del Protection active inactive active BinInpDelayX Force value 1 16 If any of the particular 16 input s is active, the Force value function on that corresponding channel gets active, forcing an alternative value to the selected setpoint. Force value function enables to change the setting of some setpoints by activation of binary input or PLC function. It is also possible that the forced setpoint value is based on Analogue input value (generally any analogue value in the controller). IssueActCallC1 3 Rising edge on these binary inputs initiates an active call to be issued via the corresponding channel see setpoints Act. calls/sms Sys start/stop If the input is active, the controller activates BO: Start pulse (in AUT mode only) for 1 second, binary output Remote S/S is also activated. Request to start depends on state of setpoint Pwr management: Pwr management state and, if ENABLED, on the actual need of load reserve. I.e. all controllers in the system should have their Sys start/stop inputs active, but it doesn t mean that all engines are running. If Pwr management: Pwr management is DISABLED, the closed input requests the engine to start regardless of the load reserves. 27

28 If the input opens, based on the state of automat (running, soft load, loaded) the generator is softly unloaded via Load ramp (if there is another gen-set which can take the load) and BO:Stop pulse is activated, as well as the binary output Remote S/S (level signal). In case there is no other gen-set which can take the load, the GCB is opened immediately. Reaction on binary input change is delayed by setpoints Pwr management:#sysamfstrtdel [ s ], Pwr management: #SysAMFstopDel [ s ] in island mode, by 1 sec in mains parallel mode (= input MCB feedback active). Emergency stop If the input is activated, controller immediately trips the GCB. The BO: Stop pulse is not activated, binary output Remote S/S stays active (if engine was running). GeCon is considered as Generator controller, so is not supposed to stop in these cases engine. If this is required, the PLC inside the controller can be used, or copy of this input can be configured to physical binary output to signalize the active input into the engine controller. Sd override If the input is closed, all 2 nd level protections are disabled to allow engine run in an emergency situation, e.g. sprinkler devices power supply. All protections are shown in Alarmlist and recorded into History, but the controller itself doesn t stop the engine due to their occurrence. If the input is deactivated and some protections are still active or not yet reset, the controller starts to take these protections into account and consequently trips the GCB. The binary outputs, which signalize activation of particular protection are active independently on the BI: Sd override activation. In case even these outputs are not requested to be active, the internal PLC can be used (AND function of (particular output and NOT Sd override)) All 2 nd level protections are locked out, except of: Emergency stop HotStndBy The controller behaves like when switched to OFF mode if input is closed. Opens all binary outputs but the output terminals that are configured with inversion are closed. Detection of "running engine" condition and subsequent alarm message "Sd Stop fail" is blocked. The controller shows "Emerg Man" state and the engine can not be started from GeCon panel. Generator current and power (energy) measurement is active in this mode, regardless of the actual state of the engine. After the binary input HotStndBy is open again, the controller recovers to previous mode and behaves according to the actual situation. Should the engine run and any of the conditions to start the engine was active, it will keep the engine running. Function is active in any controller mode and activation of this input is written to history. Load res 2 4 If the input LOAD RES x (2, 3 or 4) is closed, the setpoint set Pwr management: #LoadResStrt X + #LoadResStop X (#%LdResStrt X + #%LdResStop X) will be selected. Higher index has higher priority when more these binary inputs are closed together. When not configured or not active, setpoint set #LoadResStrt 1 + #LoadResStop 1 (#%LdResStrt 1 + #%LdResStop 1) is used. All controllers operating in Power management must have the same Load reserves selected. It is possible to use Virtual periphery to share the signals between more controllers on the CAN bus. In such case one controller is a server which physically has the signals connected and other controllers get these signals via CAN bus. Setpoint set selection depends on the #Pwr mgmt mode if set to ABS (kw or kva), #LoadResStrt X type setpoints are active, if set to REL (%), #%LdResStrt X type setpoints are active. 28

29 BI:Load res 2 SHBOUT(1) CAN2 LBI:Load res 2 SHBIN(1) SHBIN(1) GeCon 1 LBI:Load res 2 LBI:Load res 2 GeCon 2 GeCon 3 The blue colour depicts the connection is done automatically, the yellow colour depicts the connection must be done by operator, using GenConfig PC sw. MinRun power 1 3 When binary input MinRun power 1 or 2 or 3 is closed, the corresponding setpoint Pwr management: #MinRun power 1 or 2 or 3 is selected. Higher index has higher priority when more these binary inputs are closed together. When not configured or not active, minimal running power is 0, i.e. the system works only based on Load reserves. When this input is activated, genset, or group of gensets will never be loaded below the corresponding setpoint: Pwr management: MinRunPower in case of parallel operation with mains. All controllers operating in Power management must have selected the same MinRun power input. It is possible to use Virtual periphery to share the signals between more controllers on the CAN bus. In this case one controller is a server which physically has the signals connected and other controllers get these signals via CAN bus. Priority sw A (Priority switch A) B C D Binary inputs for controller priority selection. Using these inputs, the controller s priority can be changed externally. Priority value Priority Priority sw A 0 or nc Priority sw B 0 or nc Priority sw C 0 or nc Priority sw D 0 or nc Priority value is defined by setpoint PwrManagement:Priority when all Priority switches are opened or not configured. The priority value defined by a combination of binary inputs Priority sw X is accepted with 1s delay. So if a change is made to more inputs simultaneously, it is accepted 1s after the last change sensed. GroupLink If the input is configured, the group linking function is active, i.e. this controller becomes the status server for two groups of gen-sets and informs them about the IM-NT-BTB controller status. If this input is closed, the controller reports BTB status as closed, if open, the controller reports open BTB status. This input can be used for splitting/joining the gensets from/into different groups. In case the gensets are in different groups - PwrManagement: Control group setpoint is adjusted different in both controllers (groups) and the BI: GroupLink is not active, the Load sharing, VAr sharing and power management is not done between the gensets (groups of genstes). As soon as the BI: GroupLink is closed, the Load sharing, VAr sharing and power management became active between the gensets (groups of gensets) with different adjusted Control group setpoint see setpoint: Pwr management:control group [ ]. ManualLdRecon The rising edge on this input switches the controller to the lower Load Shedding stage when Load shedding: AutoLd recon = DISABLED and the load is under Load shedding: Ld recon level. 29

30 GCB disable The input blocks the GCB closing, even if all other conditions for its closing are fulfilled. Valid in all modes. However GCB is blocked to be closed, the synchronization process starts and runs independently on this input state. If you want to lock out the GCB closing during synchronizing loop test, set Sync/Load ctrl: Phase window = 0. This allows the control loop to be tested while actual GCB closing is blocked. Conditions for closing: 1) voltage only on generator side of GCB 2) voltage on both sides of GCB and all synchronizing conditions fulfilled. Startblocking If this input is activated, start signal is not activated (Start pulse or Remote S/S signal) Cyldifevalblk If the signal is active, the protection based on the difference amongst cylinder temperatures is blocked. After signal deactivation, the protection is unblocked immediately. ReadyToLoad This signal is the essential for right functionality of GeCon. As soon as this signal is active, GeCon starts to count down the MinStabTime, and when finished, starts to evaluate configured generator protection if configured by operator. Without activation of this input the GeCon will be sitting in the Starting state and will not proceed into Running state. As soon as this signal is deactivated, GeCon proceed into state Stopping, until still condition is sensed (zero freq measured). In case this signal is lost in Loaded state, the GCB is immediately open. ECU Stopped Eng Engine stop was activated in ECU, not from controller. The controller reflects this situation and also goes to Stop to avoid an Underspeed alarm (and record in the Alarm list). CtrlHB Sense BI "CtrlHBeat sens" should be assigned to the output "CtrlHeartBeat" from the other controller. If input signal does not correspond to right form (log 1 / log ms / 500 ms; +/- 100 ms), BO: "CtrlHBeat FD" (Fail Detect) is activated. This BO can be used for primary controller blocking (switching to Emerg. manual, disconnecting BO,...) and mainly for disconnecting of BI "HotStndBy" of this controller. What means that the backup controller assumes engine control. 500 ms 500 ms >500ms Ctrl HHB Sense CtrlHB FailureDetect GenStandby Controller is automatically forced into the AUT mode as soon as this BI is activated. Controller does not send the start signal to engine controller, engine is supposed to be started externally. GeCon waits till the BI:ReadyToLoad is activated, then starts with MinStabTime count down, synchronization, etc. As soon as the ReadyToLoad signal is activated the behaviour is the same as in AUT mode with activated BI: Sys start/stop, BUT set with activated BI: GenStandby is excluded from power management. As soon as the BI: GenStandby is deactivated, controller is forced into the mode, where was originally and behaves based on the sensing signals. 30

31 GCB close GeCon initiates the synchronization process, if the sync conditions are fulfilled send signal to close GCB. If the dead bus is measured, GCB close command is issued immediately. In case both the BI: GCB close and BI: GCB open are activated, the BI: GCB open wins (generator is unloaded and GCB opened, or sync procedure is terminated). Working only in SEM mode GCB open Active input initiates the soft unload procedure, if the generator load is below: Sync/Load ctrl: GCB open level [ % ] (FV) or GCB open del [ s ] (FV) elapsed, the GCB open command is issued. In case there is no other gen-set on the bus, which can take the load, the GCB is opened immediately. Working in SEM mode only. Gen sync Active input initiates the synchronization process, but the GCB close command is not send automatically. It is up to operator to close GCB by GCB I/O button on GeCon front panel, or use BI: GCB Button, or close GCB externally. The In Sync condition is signalized by BO: InSynchronism. As soon as the BI: Gen sync is deactivated, the synchronization process is terminated. This input is taken in account in SEM and MAN modes only. Function is activated by level (1= sync run, 0= No sync / stop synch). Condition: setpoint: Synchro Enable. Gen unload Active input initiates the soft unload of the generator. The load is ramped towards the Sync/Load ctrl: GCB open level [ % ] (FV), GCB open command is not initiated it is up to operator. In case there is no other genset available to take the load, there is no influence of this input activation. Working in SEM mode only. Function is activated by level (1= Unload, 0= No unload / stop unload.) Sync disable Active input disables synchronization process. Working in both SEM and AUT mode. ExtValue1up Extvalue4up Active input initiates increase of the value ExtValue x (x = 1-4), slope (ratio) of increase is defined by setpoint: Volt/PF control adjustment IG-AVRi output connection Every time refer to corresponding AVR manual before interface connecting. Use no droop AVR. IG-AVRi-TRANS (AC power supply for AVRi) has to be supplied from gen-set voltage. AVRi outputs can be connected as symmetrical: OUT1-OUT2 or unsymmetrical OUT1-GND or OUT2-GND. Potentiometer on the AVRi defines maximal OUT1, OUT2 voltage range. Use symmetrical (OUT1,OUT2) AVRi output to connect the AVRi to AVR auxiliary voltage input. Use unsymmetrical output if an external AVR potentiometer has to be replaced with AVRi. AVRi output voltage should change generator voltage typically in range 10 % of Nominal voltage. For more details please refer to Installation guide chapter AVR interface examples. Out1 - GND [V] Out2 - GND [V] 10 V 2 V AVRi pot set to maximum AVRi pot set to minimum 10 V 2 V AVRi pot set to maximum AVRi pot set to minimum 0 V 0 % AVR DCout bias % 0 V 0 % AVR DCout bias AVRi Out1 or Out 2 to GND output voltage depends on AVRi trim setting % 31

32 [V] 10 V Out1 to Out2 0 % 0 V 50 % AVRi pot = minimum AVRi pot = maximum AVR DCout bias % AVRi output voltage Out1 - GND Out2 - GND Out1 Out2 Bias \ Pot Min Max Min Max Min Max 0 % V -10 V 50 % V 0 V 100 % V 10 V -10 V AVRi Out1 to Out 2 output voltage Voltage control adjustment 1) Set Voltage gain, Voltage int to zero and AVR DCout bias to 50%. 2) Start always with AVRi pot min adjustment (fully counter clockwise). 3) Start the gen-set in SEM Mode to nominal speed, without load. 4) Adjust generator voltage to nominal value by the potentiometer present on the AVR. If there is no potentiometer on the AVR, use AVR DCout bias to adjust the nominal voltage. 5) Change AVR DCout bias to 0% and 100% to check generator voltage control range (typically 10 % of nominal voltage). Adjust voltage control range by AVRi trim. 6) Set AVR DCout bias to be Nominal voltage on generator (50%). 7) When gen-set is running unloaded increase carefully Voltage gain to unstable point and then decrease value by 30 % to insure stable performance. 8) Adjust Voltage int (usually setting to 100% gives optimal performance). To judge optimal adjusting induce generator voltage jumps by AVR DCout bias change or by Nominal voltage change. PF control adjustment The genset should be cca 30 % loaded in parallel to mains and baseload mode. 1) Set the same values PF gain, PF int as in voltage control loop. 2) Set Process control: #SysLdCtrl PtM = BASELOAD, #SysBaseLoad = 30 % of Nominal load, #SysPFCtrl PtM = BASEPF, #SysPwrFactor = ) Start and synchronize the gen-set in SEM Mode by pressing GCB ON/OFF 4) When running in parallel 30% loaded increase slowly PF gain to unstable point and then decrease value by 30 % to insure stable performance. 5) Adjust PF int (usually setting to 100% gives optimal performance). To judge optimal adjusting induce generator power jumps by SysBaseLoad change or by soft changes of AVR DCout bias. Force value:extvalue1 rate [ X/s ] (FV) (2,3,4) ExtValue1down ExtValue4down Active input initiates decrease of the value ExtValue x (x = 1-4), slope (ratio) of decrease is defined by setpoint: Volt/PF control adjustment IG-AVRi output connection Every time refer to corresponding AVR manual before interface connecting. Use no droop AVR. IG-AVRi-TRANS (AC power supply for AVRi) has to be supplied from gen-set voltage. AVRi outputs can be connected as symmetrical: OUT1-OUT2 or unsymmetrical OUT1-GND or OUT2-GND. Potentiometer on the AVRi defines maximal OUT1, OUT2 voltage range. 32

OPERATOR GUIDE. InteliGen NT, InteliSys NT Modular Gen-set Controller. Operator guide for SPI, SPtM, MINT, COX

OPERATOR GUIDE. InteliGen NT, InteliSys NT Modular Gen-set Controller. Operator guide for SPI, SPtM, MINT, COX Compact Controller for Stand-by and Parallel Operating Gen-sets InteliGen NT, InteliSys NT Modular Gen-set Controller Operator guide for SPI, SPtM, MINT, COX IG-NT, IG-NTC, IG-EE, IG-EEC, IS-NT Software

More information

REFERENCE GUIDE IS NT BF. Inteli New Technology. Modular Gen-set Bi-fuel Controller. Conversion Kit Software Configuration.

REFERENCE GUIDE IS NT BF. Inteli New Technology. Modular Gen-set Bi-fuel Controller. Conversion Kit Software Configuration. InteliSys-NT IS NT BF Inteli New Technology Modular Gen-set Bi-fuel Controller Conversion Kit Software Configuration SW version 1.0.3, December 2008 REFERENCE GUIDE Copyright 2008 ComAp s.r.o. ComAp, spol.

More information

REFERENCE GUIDE. MainsCompact NT P Mains controller for the InteliCompact gen-set controllers. SW version 1.0, March Copyright 2008 ComAp s.r.o.

REFERENCE GUIDE. MainsCompact NT P Mains controller for the InteliCompact gen-set controllers. SW version 1.0, March Copyright 2008 ComAp s.r.o. MainsCompact NT P Mains controller for the InteliCompact gen-set controllers SW version 1.0, March 2009 REFERENCE GUIDE Copyright 2008 ComAp s.r.o. ComAp, spol. s r.o. Kundratka 17, 180 00 Praha 8, Czech

More information

TROUBLESHOOTING GUIDE

TROUBLESHOOTING GUIDE DEKRACertification Compact Controller for Stand-by and Parallel Operating Gen-sets InteliGen NT, InteliSys NT, InteliMains NT Modular Controller Troubleshooting guide IG-NT, IG-NTC, IG-NT-BB, IG-NTC-BB,

More information

c InteliGen NTC general purpose HIGH-END gen set controller

c InteliGen NTC general purpose HIGH-END gen set controller G E N - S E T C O N T R O L L E R S / H I G H - E N D InteliGen nt is a comprehensive controller f both single and multiple gen-sets operating in standby parallel modes. Compact construction is optimized

More information

New features of IC-NT sw V1.2.1

New features of IC-NT sw V1.2.1 Page 1 of 13 1. Available firmware, archives and documentation Firmware Mhx file IC-NT-MINT-1.2.1.mhx IC-NT-SPtM-1.2.1.mhx Archives Archives IC-NT-MINT-1.2.aic IC-NT-MINT-MultiKit-1.2.aic IC-NT-SPtM-1.2.aic

More information

OPERATOR'S MANUAL Generator Paralleling Controller, GPC-3 - Generator Protection Unit, GPU-3/GPU-3 Hydro - Paralleling and Protection Unit, PPU-3

OPERATOR'S MANUAL Generator Paralleling Controller, GPC-3 - Generator Protection Unit, GPU-3/GPU-3 Hydro - Paralleling and Protection Unit, PPU-3 OPERATOR'S MANUAL Generator Paralleling Controller, GPC-3 - Generator Protection Unit, GPU-3/GPU-3 Hydro - Paralleling and Protection Unit, PPU-3 Display and push-button functions Alarm handling Log list

More information

InteliDrive Nano. Reference Guide. Engine Controller. InteliDrive Nano. Compact Controller for Industrial Engines. SW version 1.

InteliDrive Nano. Reference Guide. Engine Controller. InteliDrive Nano. Compact Controller for Industrial Engines. SW version 1. InteliDrive Nano InteliDrive Nano Engine Controller Compact Controller for Industrial Engines SW version 1.3, October 2012 Reference Guide Copyright 2012 ComAp s.r.o. ComAp, spol. s r.o. Kundratka 17,

More information

Genset control and protection with safety system

Genset control and protection with safety system APPLICATION NOTES Generator Protection Unit, GPU-3 APPLICATION NOTES Genset control and protection with safety system Application description Functional description Wiring I/O lists Basic setup Flowcharts

More information

REFERENCE GUIDE. Copyright 2008 ComAp a.s.

REFERENCE GUIDE. Copyright 2008 ComAp a.s. GenConfig Configuration Tool for Gen-set controllers To be used with ComAp controllers from following product lines: InteliGen-NT, InteliSys-NT, InteliMains-NT SW version 3.0, June 2013 REFERENCE GUIDE

More information

InteliNano NT Plus Modular Gen-set Controller with Current Measurement

InteliNano NT Plus Modular Gen-set Controller with Current Measurement InteliNano NT InteliNano NT Plus Modular Gen-set Controller with Current Measurement Compact Controller for Stand-by Operating Gen-sets SW version 1.4, March 2013 Reference Guide TABLE OF CONTENTS 1 Document

More information

Operator Guide. InteliGen 200. Controller for parallel gen-set applications

Operator Guide. InteliGen 200. Controller for parallel gen-set applications InteliGen 200 Controller for parallel gen-set applications SW version 1.1.0 1 Front panel elements 2 2 Display screens and pages structure 5 3 Browsing alarms 21 4 Password 22 5 Information screen 29 6

More information

Comprehensive Modular Genset Controller

Comprehensive Modular Genset Controller Inteligen Learn More Comprehensive Modular Genset Controller Brief Description The Inteligen is a comprehensive controller for single and multiple generating sets operating in standby or parallel to the

More information

Compact Genset Controller, CGC 400 What's in the delivery? The first steps Push-buttons and LEDs

Compact Genset Controller, CGC 400 What's in the delivery? The first steps Push-buttons and LEDs QUICK START GUIDE Compact Genset Controller, CGC 400 What's in the delivery? The first steps Push-buttons and LEDs DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com

More information

ALL-IN-ONE Generator & CHP Control System ALL-IN-ONE MOTORTECH GENERATOR & CHP CONTROL SYSTEM

ALL-IN-ONE Generator & CHP Control System ALL-IN-ONE MOTORTECH GENERATOR & CHP CONTROL SYSTEM ALL-IN-ONE Generator & CHP Control System ALL-IN-ONE MOTORTECH GENERATOR & CHP CONTROL SYSTEM General Information ALL-IN-ONE MOTORTECH GENERATOR & CHP CONTROL SYSTEM ALL-IN-ONE For monitoring, controlling,

More information

Comprehensive Modular Genset Controller

Comprehensive Modular Genset Controller InteliGen Comprehensive Modular Genset Controller Brief Description InteliGen is a comprehensive AMF-controller for single and multiple generating sets operating in standby or parallel modes. A modular

More information

InteliPro. Installation and Operation Guide Application Guide Communication Brochure Reference Guide. Protection Relay for Parallel Applications

InteliPro. Installation and Operation Guide Application Guide Communication Brochure Reference Guide. Protection Relay for Parallel Applications InteliPro Protection Relay for Parallel Applications Comprehensive Guide SW version 1.6, November 2014 Installation and Operation Guide Application Guide Communication Brochure Reference Guide Copyright

More information

MULTI-LINE 2 APPLICATION NOTES. Converting PPU-2 to PPU-3 Parameter conversion Wiring Options I/O list. Document no.: A SW version:

MULTI-LINE 2 APPLICATION NOTES. Converting PPU-2 to PPU-3 Parameter conversion Wiring Options I/O list. Document no.: A SW version: MULTI-LINE 2 APPLICATION NOTES Converting PPU-2 to PPU-3 Parameter conversion Wiring Options I/O list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com

More information

Application Note (Revision NEW) Original Instructions. EGCP-2 Differences

Application Note (Revision NEW) Original Instructions. EGCP-2 Differences Application Note 51199 (Revision NEW) Original Instructions General Precautions Read this entire manual and all other publications pertaining to the work to be performed before installing, operating, or

More information

LiteEdit 2.0. User guide. Configuration and Monitoring Tool. PC Software for InteliLite Controllers. SW version 2.0, August 2004

LiteEdit 2.0. User guide. Configuration and Monitoring Tool. PC Software for InteliLite Controllers. SW version 2.0, August 2004 PC Software for InteliLite Controllers LiteEdit 2.0 Configuration and Monitoring Tool SW version 2.0, August 2004 User guide Copyright 2004 ComAp s.r.o. Written by Ladislav Kadaník Prague, Czech Republic

More information

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC QUICK START GUIDE Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615

More information

ÓÉ Foxit PDF Editor ±à¼ æè ËùÓÐ (c) by Foxit Software Company, 2004 ½öÓÃÓÚÆÀ¹À. Reference Guide

ÓÉ Foxit PDF Editor ±à¼ æè ËùÓÐ (c) by Foxit Software Company, 2004 ½öÓÃÓÚÆÀ¹À. Reference Guide ÓÉ Foxit PDF Editor ±à¼ æè ËùÓÐ (c) by Foxit Software Company, 2004 ½öÓÃÓÚÆÀ¹À Reference Guide Table of Contents Table of Contents... 2 General Guidelines... 4 What describes this manual?... 4!! Warnings!!...

More information

InteliNano NT. Operator Guide. Copyright 2011 ComAp s.r.o.

InteliNano NT. Operator Guide. Copyright 2011 ComAp s.r.o. InteliNano NT Operator Guide Copyright 2011 ComAp s.r.o. ComAp, spol. s r.o. Kundratka 17, 180 00 Praha 8, Czech Republic Tel: +420 246 012 111, Fax: +420 266 316 647 E-mail: info@comap.cz, www.comap.cz

More information

InteliLite NT MRS Modular Gen-set Controller User guide ComAp, spol. s r.o.

InteliLite NT MRS Modular Gen-set Controller User guide ComAp, spol. s r.o. InteliLite NT InteliLite NT MRS Modular Gen-set Controller Compact Controller for Single Operating Gen-sets (IL-NT MRS10/11/15/16 unit) SW version 1.0, August 2007 User guide Copyright 2007 ComAp s.r.o.

More information

InteliLite AMF. User guide. Modular Gen-set Controller. InteliLite. Compact Controller for Stand-by Operating Gen-sets. (IL-CU AMF20/25 unit)

InteliLite AMF. User guide. Modular Gen-set Controller. InteliLite. Compact Controller for Stand-by Operating Gen-sets. (IL-CU AMF20/25 unit) InteliLite InteliLite AMF Modular Gen-set Controller Compact Controller for Stand-by Operating Gen-sets (IL-CU AMF20/25 unit) SW version 2.2, November 2004 User guide Copyright 2004 ComAp s.r.o. Written

More information

Option M2 Configurable engine control cards Multi-line 2 version B SW version 2.4X.X

Option M2 Configurable engine control cards Multi-line 2 version B SW version 2.4X.X Description of options Option M2 Configurable engine control cards Multi-line 2 version 2 4189340482B SW version 2.4X.X Description of options Functional description DEIF A/S Display units Additional functions

More information

REFERENCE GUIDE. Copyright 2008 ComAp s.r.o.

REFERENCE GUIDE. Copyright 2008 ComAp s.r.o. PC Software for Gen-set Controllers LiteEdit Monitoring Tool for ComAp Controllers To be used with ComAp controllers: IL MRSXX, IL AMFXX, IL-NT MRSXX, IL-NT AMFXX, IC-NT SPtM, IC-NT MINT, MC-NT and derived

More information

Automatic Genset Controller, AGC-3 What's in the delivery Getting started The first steps Using the AGC

Automatic Genset Controller, AGC-3 What's in the delivery Getting started The first steps Using the AGC QUICK START GUIDE Automatic Genset Controller, AGC-3 What's in the delivery Getting started The first steps Using the AGC DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615

More information

InteliNano NT. MRS Lite GEN-SET CONTROLLER. Description. Benefits

InteliNano NT. MRS Lite GEN-SET CONTROLLER. Description. Benefits GEN-SET CONTROLLER Description is a cost effective generator set controller which offers outstanding protection, monitoring and control for small and middle size generator sets. There are three different

More information

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC QUICK START GUIDE Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615

More information

Option H3 Serial communication Profibus DP

Option H3 Serial communication Profibus DP MULTI-LINE 2 DESCRIPTION OF OPTIONS Option H3 Serial communication Profibus DP Description of option Functional description Parameters Data tables Document no.: 4189340443H Multi-line 2 Option H3, Serial

More information

What is new in the easygen3000xt

What is new in the easygen3000xt PRELIMINARY What is new in the easygen3000xt Content Hardware... 3 Housing... 3 New Layout / Operation... 3 Base Models... 3 Terminals... 4 I/O Features... 4 Communication Interfaces... 4 Functionality...

More information

EMS-GC10 Genset Controller. Modbus Communication Mapping Manual Section 75

EMS-GC10 Genset Controller. Modbus Communication Mapping Manual Section 75 EMS-GC10 Genset Controller Modbus Communication Mapping Manual 1311311 2013-10-10 Section 75 In order to consistently bring you the highest quality, full featured products, we reserve the right to change

More information

InteliLite NT AMF. User guide. Modular Gen-set Controller. InteliLite NT. Compact Controller for Stand-by Operating Gen-sets. (IL-NT AMF20/25 unit)

InteliLite NT AMF. User guide. Modular Gen-set Controller. InteliLite NT. Compact Controller for Stand-by Operating Gen-sets. (IL-NT AMF20/25 unit) InteliLite NT InteliLite NT AMF Modular Gen-set Controller Compact Controller for Stand-by Operating Gen-sets (IL-NT AMF20/25 unit) SW version 1.0, August 2007 User guide Copyright 2004 ComAp s.r.o. Written

More information

MULTI-LINE 2 APPLICATION NOTES

MULTI-LINE 2 APPLICATION NOTES MULTI-LINE 2 APPLICATION NOTES Converting PPM-2 to PPM 300 Parameter conversion Wiring Options I/O list Modbus DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com

More information

Remote announciator igl-ra15

Remote announciator igl-ra15 Extension module for il/ig/is genset controllers Remote announciator igl-ra15 Version 1.1, August 2003 Prague, Czech Republic Copyright 2003 ComAp s.r.o. Written by: Jan Tomandl ComAp s.r.o. Svetova 7,

More information

Accessory Modules. Reference Guide. Extension modules for IL-NT, IC-NT, ID-Lite genset or engine controllers, IA-NT. April ComAp, spol. s r.o.

Accessory Modules. Reference Guide. Extension modules for IL-NT, IC-NT, ID-Lite genset or engine controllers, IA-NT. April ComAp, spol. s r.o. Extension modules for IL-NT, IC-NT, ID-Lite genset or engine controllers, IA-NT Accessory Modules April 2011 Reference Guide ComAp, spol. s r.o. Kundratka 2359/17, 180 00 Praha 8, Czech Republic Tel: +420

More information

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits SINGLE SET GEN-SET CONTROLLER Description The range offers a wide choice of integrated control solutions for gen-sets operating in single standby mode. Based on the field proven InteliLite architecture,

More information

M2500 Engine Controller Configuration Manual

M2500 Engine Controller Configuration Manual M2500 Engine Controller Configuration Manual Revision: 08-04-2011 Page 1 Contents 1 Preface... 4 2 Configuration from front panel... 5 2.1 Engine Controller Configuration... 6 2.1.1 RPM settings... 6 2.1.2

More information

InteliNano NT GEN-SET CONTROLLER. Description. Benefits MEMBER

InteliNano NT GEN-SET CONTROLLER. Description. Benefits MEMBER GEN-SET CONTROLLER Description is a cost effective diesel and gasoline generator set controller which offers outstanding protection, monitoring and control for small and middle size generator sets. There

More information

Control Systems Product Overview

Control Systems Product Overview Control Systems Product Overview Gen-set controllers InteliLite NT MRS InteliLite NT MRS models are integrated controllers for single engine control in Manual and Remote Start applications, featuring full

More information

COMMUNICATION GUIDE. Communication Guide for ComAp Controllers. IGS-NT SW version 3.0

COMMUNICATION GUIDE. Communication Guide for ComAp Controllers. IGS-NT SW version 3.0 Communication Guide for ComAp Controllers InteliGen NT InteliGen NTC InteliGen NT BaseBox InteliGen NTC BaseBox InteliSys NT InteliSys NTC BaseBox Inteli Mains NT Inteli Mains NT BaseBox Inteli Mains NTC

More information

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits SINGLE SET GEN-SET CONTROLLER Description The range offers a wide choice of integrated control solutions for gen-sets operating in single standby mode. Based on the field proven InteliLite architecture,

More information

DEIF A/S. Description of options. Option A and B, Loss of mains protection package Automatic Gen-set controller. Description of options

DEIF A/S. Description of options. Option A and B, Loss of mains protection package Automatic Gen-set controller. Description of options Description of options Option A and B, Loss of mains protection package Automatic Gen-set controller 4189340394B SW 2.3X.X Description of options Functional descriptions DEIF A/S Parameter list DEIF A/S,

More information

Genset Controller Unit Model EMS - GC10. Installation Manual Section

Genset Controller Unit Model EMS - GC10. Installation Manual Section Genset Controller Unit Model EMS - GC10 Installation Manual 00-02-0794 Section 75 2013-01-28 In order to consistently bring you the highest quality, full featured products, we reserve the right to change

More information

TT /12b INSTALLATION INSTRUCTIONS. Introduction

TT /12b INSTALLATION INSTRUCTIONS. Introduction TT-1545 11/12b INSTALLATION INSTRUCTIONS Original Issue Date: 6/10 Model: 20-300 kw Generator Sets Market: Industrial Subject: Decision-Maker 3000 Controller Service Replacement Kit GM75376 Introduction

More information

SIGMA. Advanced Generator Protection and Control. Short Form Catalogue

SIGMA. Advanced Generator Protection and Control. Short Form Catalogue Short Form Catalogue SIGMA Advanced Generator Protection and Control Generator protection, synchronizing and load sharing Power management system Easy to install and commission Control most governors/avrs

More information

DEIF A/S. Description of options. Option C1 Generator add-on protection package Multi-line 2 version 2. Description of options. Functional description

DEIF A/S. Description of options. Option C1 Generator add-on protection package Multi-line 2 version 2. Description of options. Functional description Description of options Option C1 Generator add-on protection package Multi-line 2 version 2 4189340267E SW version 2.42.X Description of options DEIF A/S Functional description Parameter list DEIF A/S,

More information

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology HGM9580 Bus Tie Bus Parallel Unit USER MANUAL Smartgen Technology This manual is suitable for HGM9580 bus tie bus parallel unit only. Clarification of notation used within this publication. SIGN INSTRUCTION

More information

Table of Contents. Section 10 - Grid Tie

Table of Contents. Section 10 - Grid Tie Table of Contents Warnings/Hazards Reference Materials Use Cases Use Cases and Available Features Connection to a Utility for Mains Paralleling Part of a Microgrid Stand-Alone Operation Commissioning Procedure

More information

QUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3

QUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3 QUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3 What's in the delivery? Getting started The first steps PC

More information

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

Safety Instructions 1-1 Avoid unintended Start General Description 2-2 Contents Contents 1 Safety and precautions 1-1 Safety Instructions 1-1 Avoid unintended Start. 1-1 2 Introduction 2-1 General Description 2-2 3 Supported Configuration 3-1 Introduction 3-1 Fixed-speed

More information

AGC 200 Advanced Gen-set Controller What s in the delivery? Getting started The first steps Using the AGC 200

AGC 200 Advanced Gen-set Controller What s in the delivery? Getting started The first steps Using the AGC 200 QUICK START GUIDE AGC 200 Advanced Gen-set Controller What s in the delivery? Getting started The first steps Using the AGC 200 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614

More information

Operating Instructions Extended Cascade Controller MCO 101

Operating Instructions Extended Cascade Controller MCO 101 Operating Instructions Extended Cascade Controller MCO 101 VLT AQUA Drive FC 200 Extended Cascade Controller Option Contents Contents 1. Safety and precautions 3 Safety Instructions 3 Avoid unintended

More information

InteliCompact NT. Reference Guide. Paralelling gen-set controller. SW version 1.3.1, November Copyright 2011 ComAp s.r.o.

InteliCompact NT. Reference Guide. Paralelling gen-set controller. SW version 1.3.1, November Copyright 2011 ComAp s.r.o. InteliCompact NT Paralelling gen-set controller SW version 1.3.1, November 2011 Reference Guide Copyright 2011 ComAp s.r.o. ComAp, spol. s r.o. Kundratka 17, 180 00 Praha 8, Czech Republic Tel: +420 246

More information

Appendix C: HVAC PRO Modules

Appendix C: HVAC PRO Modules FANs 637.5, 1637.5 Appendix Section Issue Date 0400 APPLICATION NOTE Appendix C: HVAC PRO Modules HVAC PRO Modules...3 Introduction...*3 Key Concepts...*4 ABS VALUE... 6 ADD... 6 ANALOG OUTPUT... 6 AND...

More information

DEIF A/S. Description of options. Option C2, Generator add-on protection package Automatic Gen-set Controller. Description of option

DEIF A/S. Description of options. Option C2, Generator add-on protection package Automatic Gen-set Controller. Description of option Description of options Option C2, Generator add-on protection package Automatic Gen-set Controller 4189340345C SW version 2.1X.X Description of option Functional description DEIF A/S Parameter list DEIF

More information

ALL-IN-ONE.NT GENERATOR & CHP CONTROL SYSTEM FIRMWARE IS-NT-AFR / 2.2 OPERATING MANUAL

ALL-IN-ONE.NT GENERATOR & CHP CONTROL SYSTEM FIRMWARE IS-NT-AFR / 2.2 OPERATING MANUAL ALL-IN-ONE.NT GENERATOR & CHP CONTROL SYSTEM FIRMWARE IS-NT-AFR 2.3.1 / 2.2 OPERATING MANUAL MOTORTECH Gas Engine Control Systems P/N 01.30.008-EN Rev. 09/2016 Copyright Copyright 2016 MOTORTECH GmbH.

More information

InteliATS NT. Reference Guide. Automatic Transfer Switch Controller. IA-NT STD unit. SW version 2.0, June 2010

InteliATS NT. Reference Guide. Automatic Transfer Switch Controller. IA-NT STD unit. SW version 2.0, June 2010 InteliATS NT Automatic Transfer Switch Controller IA-NT STD unit SW version 2.0, June 2010 Reference Guide June 2010 Copyright 2010 ComAp s.r.o. Written by Vlastimil Vostřák Prague, Czech Republic ComAp,

More information

InteliATS NT. Reference Guide. Automatic Transfer Switch Controller. IA-NT PWR unit. SW version 2.0, June 2010

InteliATS NT. Reference Guide. Automatic Transfer Switch Controller. IA-NT PWR unit. SW version 2.0, June 2010 InteliATS NT Automatic Transfer Switch Controller IA-NT PWR unit SW version 2.0, June 2010 Reference Guide June 2010 Copyright 2010 ComAp s.r.o. Written by Vlastimil Vostřák Prague, Czech Republic ComAp,

More information

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC COMPLEX SOLUTIONS MADE SIMPLE. DEEP SEA ELECTRONICS PLC DSE5520 AUTOMATIC MAINS FAILURE CONTROL MODULE OPERATING MANUAL Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND

More information

HAT600 Series HAT600/HAT600I/HAT600B/HAT600BI ATS CONTROLLER USER MANUAL

HAT600 Series HAT600/HAT600I/HAT600B/HAT600BI ATS CONTROLLER USER MANUAL HAT600 Series HAT600/HAT600I/HAT600B/HAT600BI ATS CONTROLLER USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO.,LTD CONTENT 1 OVERVIEW... 5 2 PERFORMANCE AND CHARACTERISTICS... 6 3 SPECIFICATION... 8 4 OPERATING...

More information

Option Fail-Safe-Accu NRGS1-24VDC incl. positioner

Option Fail-Safe-Accu NRGS1-24VDC incl. positioner Option Fail-Safe-Accu -24VDC incl. positioner General The electronic AGS-positioner -24VDC is used to control the electric actuator with a continuous current or voltage signal. In case of missing power

More information

QUICK START GUIDE Paralleling and Protection Unit PPU 300

QUICK START GUIDE Paralleling and Protection Unit PPU 300 QUICK START GUIDE Paralleling and Protection Unit PPU 300 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4189341107C 1. Introduction

More information

Fail-Safe-Function with Positioner NR-C1

Fail-Safe-Function with Positioner NR-C1 Fail-Safe-Function with Positioner Fail-Safe-Function via Capacitor: The Fail-Safe-Function with Positioner is used to drive a DC- Actuator in case of missing power supply into a choosable final position.

More information

InteliLite MRS17 Click Here to Learn More

InteliLite MRS17 Click Here to Learn More InteliLite MRS17 Click Here to Learn More Comprehensive Genset Controller Brief Description The InteliLite is a cost effective controller for generator sets in stand-by and prime power applications. The

More information

GC2000 Generator Controller Power Management and Protection

GC2000 Generator Controller Power Management and Protection GC2000 Generator Controller Power Management and Protection Control. Monitor. Protect. A powerful generator controller and power management system for marine and offshore applications SELCO s GC2000 provides

More information

Welcome to the safety functions configuration training module for ACS880 Cabinet-built industrial drives.

Welcome to the safety functions configuration training module for ACS880 Cabinet-built industrial drives. Welcome to the safety functions configuration training module for ACS880 Cabinet-built industrial drives. 1 After viewing this presentation you will be able to describe: The functionality of cabinet-built

More information

InteliGen InteliSys InteliMains

InteliGen InteliSys InteliMains InteliGen InteliSys InteliMains Communication Guide for ComAp Controllers Copyright 2017 ComAp a.s. Prague, Czech Republic ComAp a.s., U Uranie 1612/14a, 170 00 Praha 7, Czech Republic Tel: +420 246 012

More information

GRUNDFOS INSTRUCTIONS. Control MPC. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Control MPC. Installation and operating instructions GRUNDFOS INSTRUCTIONS Control MPC Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions CONTENTS Page

More information

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety Drive Technology \ Drive Automation \ System Integration \ Services Manual Control Cabinet Inverter MOVITRAC B Functional Safety Edition 05/2009 16811216 / EN SEW-EURODRIVE Driving the world Content Content

More information

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits SINGLE SET CONTROLLER Description The range offers a wide choice of integrated control solutions for gen-sets operating in single standby mode. Based on the field proven InteliLite architecture, the family

More information

Communicative controller for VAV systems

Communicative controller for VAV systems FCR015 Communicative controller for VAV systems Summary FCR015 is a communicative controller for heating and cooling panels and a VAV (variable air volume) damper. It measures temperature and CO 2 concentration

More information

QUICK START GUIDE Paralleling and Protection Unit PPU 300

QUICK START GUIDE Paralleling and Protection Unit PPU 300 QUICK START GUIDE Paralleling and Protection Unit PPU 300 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4189341107B 1. Introduction

More information

HAT560NC SERIES (HAT560NC /HAT560NBC) ATS CONTROLLER USER MANUAL

HAT560NC SERIES (HAT560NC /HAT560NBC) ATS CONTROLLER USER MANUAL HAT560NC SERIES (HAT560NC /HAT560NBC) ATS CONTROLLER USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD. Chinese trademark English trademark SmartGen make your generator smart SmartGen Technology Co.,

More information

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits MEMBER

InteliLite NT SINGLE SET GEN-SET CONTROLLER. Description. Benefits MEMBER SINGLE SET CONTROLLER Description The range offers a wide choice of integrated control solutions for gen-sets operating in single standby mode. Based on the field proven InteliLite architecture, the family

More information

Status line The top line of the LCD display shows the basic status information of the drive.

Status line The top line of the LCD display shows the basic status information of the drive. Control panels 91 Status line The top line of the LCD display shows the basic status information of the drive. LOC 49.1Hz LOC MAIN MENU 1 No. Field Alternatives Significance 1 Control location LOC Drive

More information

MULTI-LINE 2 APPLICATION NOTES. Converting PPM-2 to PPM-3 Parameter conversion Wiring Options I/O list Modbus. Document no.: A SW version:

MULTI-LINE 2 APPLICATION NOTES. Converting PPM-2 to PPM-3 Parameter conversion Wiring Options I/O list Modbus. Document no.: A SW version: MULTI-LINE 2 APPLICATION NOTES Converting to Parameter conversion Wiring Options I/O list Modbus DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com

More information

YOUR EXPERT IN GENERATOR SOLUTIONS. NEW GENSYS/MASTER 2.0 Range V5.03 Firmware. NEW CRE Config V2.80 SOFTWARE

YOUR EXPERT IN GENERATOR SOLUTIONS. NEW GENSYS/MASTER 2.0 Range V5.03 Firmware. NEW CRE Config V2.80 SOFTWARE YOUR EXPERT IN GENERATOR SOLUTIONS NEW GENSYS/MASTER 2.0 Range V5.03 Firmware NEW CRE Config V2.80 SOFTWARE V_092017 Improvements & CORRECTIONS CRE config software (V2.80) GENSYS2.0 range (V5.03a1) MASTER2.0

More information

InteliLite NT MRS. Reference Guide. Modular Gen-set Controller. InteliLite NT. Compact Controller for Single Operating Gen-sets

InteliLite NT MRS. Reference Guide. Modular Gen-set Controller. InteliLite NT. Compact Controller for Single Operating Gen-sets InteliLite NT InteliLite NT MRS Modular Gen-set Controller Compact Controller for Single Operating Gen-sets (IL-NT MRS10/11/15/16 unit) SW version 2.2, September 2014 Reference Guide Copyright 2014 ComAp

More information

PRoDUCt GUIDe. gen-set controllers engine controllers product comparison table. control systems. electronic edition section i.

PRoDUCt GUIDe. gen-set controllers engine controllers product comparison table. control systems. electronic edition section i. PRoDUCt GUIDe leader in gen set communication solutions control systems electronic edition section i. gen-set controllers engine controllers product comparison table leader in gen set communication solutions

More information

APPLICATION NOTES H-coupling

APPLICATION NOTES H-coupling APPLICATION NOTES H-coupling Application description Functional description Wiring Basic setup Flowcharts Document no.: 4189340548A SW version 3.3X.X or later Table of contents 1. WARNINGS AND LEGAL INFORMATION...

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

Firmware Manual - EC Series Drives

Firmware Manual - EC Series Drives 1 Firmware Manual - EC Series Drives Doc Ver 1.01 Firmware ver: EC series drives For installation details refer to Hardware Manual Safety: Read safety instruction in hardware manual before installation

More information

InteliLite SINGLE SET GEN-SET CONTROLLER. Description. Benefits

InteliLite SINGLE SET GEN-SET CONTROLLER. Description. Benefits SINGLE SET GEN-SET CONTROLLER Description AirGate Modern communications made simple. ComAp s powerful AirGate technology is provided in a range of our controllers and makes remote Internet connection to

More information

InteliLite NT AMF. Reference Guide. Modular Gen-set Controller. InteliLite NT. Compact Controller for Stand-by Operating Gen-sets

InteliLite NT AMF. Reference Guide. Modular Gen-set Controller. InteliLite NT. Compact Controller for Stand-by Operating Gen-sets InteliLite NT InteliLite NT AMF Modular Gen-set Controller Compact Controller for Stand-by Operating Gen-sets (IL-NT AMF20/25 unit) SW version 2.1, November 2012 Reference Guide Copyright 2012 ComAp s.r.o.

More information

Control D. Controller Module for Proportional Valve Control. Installation Manual

Control D. Controller Module for Proportional Valve Control. Installation Manual Control D Controller Module Table of Contents Control D 1 1.1 1.2 1.3 1.3.1 1.3.2 1.4 2 3 4 5 5.1 5.2 5.3 6 7 8 Description 3 How To Order 3 Operating Elements 3 Adjustment 4 Operation 4 Auto-adapt 4 Operating

More information

InteliCompact NT EASY TO USE PARALLELING CONTROLLER. Description. Benefits

InteliCompact NT EASY TO USE PARALLELING CONTROLLER. Description. Benefits EASY TO USE PARALLELING CONTROLLER Benefits Simple paralleling (easy wiring, installation and configuration) Remote moniting helps reduce call-out costs of service engineers Optional Internet with control

More information

FREQUENCY CONVERTER FC102 (QUICK GUIDE)

FREQUENCY CONVERTER FC102 (QUICK GUIDE) FREQUENCY CONVERTER FC102 (QUICK GUIDE) INSTALLATION AND MAINTENANCE Content Page Safety instructions 2 IT system 3x230VAC 2 Connections 3 Control unit (LCP) 4 Manual operation 4 Reverse the direction

More information

VAMP 221. Table of Contents

VAMP 221. Table of Contents 2 V221/EN M/E019 VAMP 221 Table of Contents Table of Contents 1. General... 7 1.1. VAMP 221 arc protection system components... 7 1.1.1. Central unit VAMP 221... 9 1.1.2. I/O units VAM 12L / VAM 12 LD,

More information

Quick Installation Guide

Quick Installation Guide Manual# 1100274 Quick Installation Guide SDU 410 Safety Unit Quick Installation Guide for SDU 410 Safety Unit ~~~ Revision 1.1 Revised November 10, 2016 Revision history: Rev. Date Description 1.0 04.2012

More information

SK TU4-IOE-M12-C Part Number

SK TU4-IOE-M12-C Part Number SK TU4-IOE-M2-C Part Number 275 28 256 IO Extension Only qualified electricians are allowed to install and commission the module described below. An electrician is a person who, because of their technical

More information

Configuration Manual KH EN. TROVIS Electric Actuator with Process Controller. for heating and cooling applications

Configuration Manual KH EN. TROVIS Electric Actuator with Process Controller. for heating and cooling applications TROVIS 5757-7 Electric Actuator with Process Controller for heating and cooling applications Translation of original instructions Configuration Manual Firmware version 2.20 Edition September 2016 Notes

More information

1 Extended and Advanced Cascade Controller Option 3

1 Extended and Advanced Cascade Controller Option 3 VLT Operating Instructions Contents Contents Extended and Advanced Cascade Controller 3 How to read these Operating Instructions 3 High Voltage Warning 3 Safety Instructions 3 Avoid unintended Start 3

More information

HAT162 ATS CONTROLLER USER MANUAL

HAT162 ATS CONTROLLER USER MANUAL HAT162 ATS CONTROLLER USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO.,LTD. Chinese trademark English trademark SmartGen make your generator smart SmartGen Technology Co., Ltd. No. 28 Jinsuo Road Zhengzhou

More information

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors Ron Boe 5/15/2014 This user guide details the servo drives capabilities and physical interfaces. Users will be able to

More information

Application program: description and examples

Application program: description and examples F a n C o i l U n i t C o n t r o l l e r F a n C o i l 4 9 5 5 1 Application program: description and examples Woertz AG Electrotechnical accessories, installation systems Hofackerstrasse 47, P.O. Box

More information

ac wave 2 supply ( analog device )

ac wave 2 supply ( analog device ) ac wave 2 supply ( analog device ) «SPECIFIC PRODUCT SECTION» Instruction and user s manual Release 2.1 00/05 REEL S.r.l. Electronic Power Drives Via Riviera Berica, 42 36024 Ponte di Nanto - Vicenza -

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL Circuit Breaker Failure Relay Operating Principle Revision: 2 from 2005-02-25 Edition: 2005-02-25 _CBF-description_eng.doc Page 1 /14 Table of Contents: 1 GENERAL DESCRIPTION 4 2 FUNCTIONAL DESCRIPTION

More information