US Catalog March Surge protective devices (SPDs) UL range

Size: px
Start display at page:

Download "US Catalog March Surge protective devices (SPDs) UL range"

Transcription

1 US Catalog March 017 Surge protective devices (SPDs) UL range

2 Surge protective devices (SPDs) UL range Introduction 1 1 OVR surge protective devices Joslyn surge protective devices Marketing tools 4 US Catalog Surge protective devices (SPDs) 1/1

3 Introduction General points on lightning and its risks 1 1 The lightning protection device diverts the high strike to ground, considerably raising the potential of the ground close to the building on which it is installed. This causes overs on the electrical equipment directly via the ground terminals and induced via the underground supply cables. Switching effects on power distribution The switching of transformers, motors or inductances in general, variation of load, disconnection of circuit breakers or cut outs lead to overs that penetrate a building. The closer the building is to a generating station, substation or upstream switching point, the higher the overs may be. Facilities and operations left unprotected are highly susceptible to the damaging effects of transients. such as: Catastrophic equipment failure Immediate operation shutdown Long term disruption of business Expensive equipment repair and replacement Data losses, system resets and network down time In order to ensure protection from transient surges, installation of surge protective devices (SPD) is a must. ABB has a long history of engineering and manufacturing quality surge protective devices. This brochure will provide information needed to select the proper products to begin protecting any facility or operation. ABB s family of surge protective devices include the following: OVR NE1 enclosed SPD for service entrance locations OVR DIN rail AC SPD for equipment protection OVR PV DIN rail DC SPD for photovoltaic installations OVR DIN rail data line SPD for sensitive communications networks Overs due to direct lightning strikes These can take two forms: When lightning strikes a lightning conductor or the roof of a building which is grounded, the lightning is dissipated into the ground. The impedance of the ground and the flowing through it create large difference of potential. This is the over. This over then propagates throughout the building via the cables, damaging equipment along the way. When lightning strikes an overhead low line, the strike produces high s which penetrate into the building creating large overs. The damage caused by this type of over is usually catastrophic (e.g. fire in the electrical switchboard causing the destruction of buildings and industrial equipment) and results in explosions. Overs due to the indirect effects of lightning strikes Overs are also produced when lightning strikes in the vicinity of a building, due to the increase in potential of the ground at the point of impact. The electromagnetic fields created by the lightning generate inductive and capacitive coupling, leading to other overs. Within a radius up to several kilometers, the electromagnetic field caused by lightning in clouds can also create sudden increases in. Although less spectacular than in the previous case, irreparable damage is also caused to sensitive equipment such as fax machines, computer power supplies and safety and communication systems. What is a transient surge? A transient surge is a sudden (shorter than a millisecond) rise in the flow of power. Voltage can peak at 1x the nominal system. Transient surges result from a number of sources, the most common of which are internal, such as load switching and even normal equipment operations. In fact, approximately 80% of transients are generated internally. External transients are the result of lightning and load switching by utilities and upstream facilities. Internal load switching Switching on/off any elements that create a sudden variation of load will also cause a sudden change in flow and generate transient surges. Direct lightning strike on a lightning conductor or the roof of a building Direct lightning strike on an overhead line Lightning strikes A lightning strike (direct or indirect) can have a destructive or disturbing effect on installations located up to several miles from the actual point of the strike. During a storm, underground cables can transmit energy from a lightning strike to equipment installed inside buildings. A lightning protection device (such as a lightning rod or Faraday cage) installed on a building to protect against the risk of a direct strike can increase the risk of damage to electrical equipment connected to the main power supply near or inside the building. Increase in ground potential Magnetic field Electrostatic field 1/ Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) 1/

4 UL The Underwriters Laboratories (UL) standard for surge protective devices (SPDs) has been the primary safety standard for surge protection since the first edition was published in 1985, and updated to the second edition in The objective of UL 1449 has always been to increase safety in terms of surge protection. Change in the standard's name: From TVSS to SPDs Prior to UL 1449 rd Edition taking effect, the devices this standard covers were known as Transient Voltage Surge Suppressors (TVSS), operating on power circuits not exceeding 600 V. With the inception of the rd Edition, these devices are now known as Surge Protective Devices (SPDs), and may operate on power circuits not exceeding 1500 V DC. This new designation moves the UL standard closer to the international designation and to IEC standards. The new edition is now renamed UL Standard for Safety for Surge Protective Devices, UL The different type designations of surge protective devices The new UL 1449 rd Edition places SPDs into five different Type categories based on installation location within an electrical system. While Type 1, Type and Type categories refer to different types of SPDs that can be installed at specific locations, Type 4 and Type 5 categories refer to components used in an SPDs configuration. Type 1 "Permanently connected SPDs intended for installation between the secondary of the service transformer and the line side of the service equipment over device." Type "Permanently connected SPDs intended for installation on the load side of the service equipment over device." Type "Point of utilization SPDs, installed at a minimum conductor length of 10 meters (0 feet) from the electrical service panel." Type 4 - Component assemblies "Component assembly consisting of one or more Type 5 components together with a disconnect (integral or external) or a means of complying with the limited tests." Type 1,, - Component assemblies "Consists of a Type 4 component assembly with internal or external short circuit protection." Type 5 "Discrete component surge suppressors, such as MOVs that may be mounted on a PWB, connected by its leads or provided within an enclosure with mounting means and wiring terminations." These new categories are major changes applied to UL 1449 rd Edition. SPDs installation location is now taken into account. The closer an SPD is installed to the equipment, the better the protection is. This is a push in the direction of providing stepped protection including external and internal surge protection. The measured protection level One of the last changes found in the new UL 1449 rd Edition is the modification in the measured protection level. The Measured Limiting Voltage (MLV) is the maximum magnitude of measured at the application of a specific impulse wave shape. When applying a certain surge on the SPD, the measured at the device terminals is the so called "let-through." In UL 1449 nd Edition, the let-through was referred to as Suppressed Voltage Rating (SVR) and was calculated with a 0.5 ka surge wave form at 6 kv. The new designation is Voltage Protection Rating (VPR) and is calculated with a ka surge wave form at 6 kv. All products in this chapter have been certified according to the UL 1449 rd Edition. The MLV will allow comparison of different types of SPDs with regards to the let-through. However, it is important to note that the surge used to measure the let-through is six times higher in the rd Edition than in the nd Edition. This means that, comparing the obsolete SVR designation with the new VPR ratings will not be valid. VPR ratings will be higher than SVR ratings. 1/4 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) 1/5

5 Terminology of SPD electrical characteristics 1 1 SPD terminology 8/0 wave Current waveform which passes through equipment when subjected to an over (low energy). V Shaved Peak Residual Voltage UL wiring diagrams Single phase 10/40/77 V Split phase 40/10 V, 480/40 V Type surge protective device (SPD) Permanently connected SPDs intended for installation on the load side of the service equipment over device including SPDs located at a branch panel. It has successfully passed testing to the standard with the 8/0 wave (class II test). Metal oxide varistor (MOV) A varistor is an electronic component with a diode like nonlinear - characteristic, used to protect circuits against excessive transient s. Most commonly composed of metal oxides. Maximum continuous operating (MCOV, Uc) The maximum designated root mean square (rms) value of power frequency that may be applied continuously between the terminals of the SPD. (In) Peak value of an 8/0 waveform which the SPD is rated for based on the test program. Maximum (Imax) Peak value of an 8/0 waveform which can be safely d by the SPD, with an amplitude complying with the class II operating test sequence. Imax > In Short circuit rating (SCCR) Maximum symmetrical fault, at rated, that the SPD can withstand without sustaining damage that exceeds acceptable criteria or creates a hazardous operating condition. A * Graph depicts an 8/0 µs wave Time (µs) Time (µs) Notes: Test wave 8/0 µs according to IEEE # C6.6-00/UL 1449 The first number corresponds to the time from 10 % to 90 % of its peak value (8 µs). The second number corresponds to the time taken for the wave to descend to 50 % of its peak value (0 µs). Common mode and / or differential mode protection Common mode Common mode overs appear between the live conductors and ground, e.g. phase/ground or neutral/ground. A live conductor not only refers to the phase conductors but also to the neutral conductor. This over mode destroys equipment connected to ground (class I equipment) and also equipment not connected to ground (class II equipment) which is located near a grounded mass and which does not have sufficient electrical isolation (a few kilovolts). Class II equipment not located near a grounded mass is theoretically protected from this type of attack. Delta 40/480/600 V High-Leg Delta 40/100 V HLD L1 N G L1 L L G L1 L N L G Grounded Wye 08 Y/10 V, 480 Y/77 V, 600 Y/47 V L1 N L G L1 L N L G Voltage protection rating (VPR) The value of the VPR is determined as the nearest highest value, taken from table 6.1 of ANSI/UL 1449 rd edition, to the measured limiting determined during the transient surge suppression test using the combination wave generator at a setting of 6 kv, ka. Voltage protection level (Up or Ures) The let through by the SPD while diverting surge to ground must not exceed the withstand value of the equipment connected downstream. Differential mode Differential mode overs circulate between live conductors: phase/phase or phase/neutral. These overs have a potentially high damaging effect for all equipment connected to the electrical network, especially sensitive equipment. Ph N Imc Note: Common mode overs affect all grounding systems. I md 1/6 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) 1/7

6 Selection tables OVR Type surge protective devices Single pole /7 Delta networks /10 Single phase networks /1 Split phase networks /17 Grounded Wye networks /1 OVR for applications OVR PV surge protective devices - Photovoltaic applications /5 OVR TC surge protective devices - Dataline protection /8 US Catalog Surge protective devices (SPDs) /1

7 UL 1449 OVR surge protective devices UL version Selection tables List of OVR T UL products according to their certification Type acc. To UL 1449 Ed Range Type Order code Type 4 CA Type 1 CA T U OVR T P U CTB8041R0000 OVR T 15-0 P U CTB8041R0400 OVR T P U CTB8041R000 OVR T P TS U CTB8041R100 OVR T 40-0 P U CTB8041R400 OVR T 40-0 P TS U CTB8041R500 OVR T P TS U CTB8041R900 OVR T P TS U CTB8041R00 OVR T P TS U CTB8041R700 OVR T 70 N P U CTB8041R8000 OVR T 1N P U CTB804R0000 OVR T 1N 15-0 P U CTB804R0400 OVR T 1N P U CTB804R000 OVR T 1N P TS U CTB804R100 OVR T 1N 40-0 P TS U CTB804R500 OVR T 1N P TS U CTB804R900 OVR T 1N P TS U CTB804R00 OVR T 1N P TS U CTB804R700 OVR T L P U CTB804R0000 OVR T L 15-0 P U CTB804R0400 OVR T L P TS U CTB804R100 OVR T L 40-0 P TS U CTB804R500 OVR T N P U CTB8044R0000 OVR T N 15-0 P U CTB8044R0400 OVR T N P TS U CTB8044R100 OVR T N 40-0 P TS U CTB8044R500 OVR T N P TS U CTB8044R900 OVR T N P TS U CTB8044R00 OVR T N P TS U CTB8044R700 OVR T L P U CTB8045R0000 OVR T L 15-0 P U CTB8045R0400 OVR T L P TS U CTB8045R100 OVR T L 40-0 P TS U CTB8045R500 OVR T L P TS U CTB8045R900 OVR T L P TS U CTB8045R00 OVR T N P U CTB8046R0000 OVR T N 15-0 P U CTB8046R0400 OVR T N P TS U CTB8046R100 OVR T N 40-0 P TS U CTB8046R500 OVR T N P TS U CTB8046R900 OVR T N P TS U CTB8046R00 OVR T N P TS U CTB8046R700 OVR T C U CTB8048R500 OVR T 15-0 C U CTB8048R700 OVR T C U CTB8048R500 OVR T 40-0 C U CTB8048R700 OVR T C U CTB8048R900 OVR T C U CTB8048R4100 OVR T C U CTB8048R400 OVR T 70 N C U CTB8048R6500 Type acc. To UL 1449 Ed Range Type Order code Type 4 CA Type 1 CA PV U OVR PV P U CTB8040R0800 OVR PV P TS U CTB8040R0900 OVR PV P U CTB8040R000 OVR PV P TS U CTB8040R100 OVR PV P U CTB8040R00 OVR PV P TS U CTB8040R00 OVR PV P U CTB8040R5600 OVR PV P TS U CTB8040R5700 OVR PV P U CTB8040R6800 OVR PV P TS U CTB8040R6900 OVR PV P U CTB8040R8000 OVR PV P TS U CTB8040R8100 OVR PV C U CTB8049R0400 OVR PV C U CTB8049R1000 OVR PV C U CTB8049R1600 OVR PV C U CTB8049R900 OVR PV C U CTB8049R500 OVR PV C U CTB8049R4100 Choosing the correct model 1) Determine the service Consult qualified personnel if the facility or operation service is unknown. ) Select the SPD maximum continuous operating (MCOV, Uc) The MCOV should correspond to the service. Example: If the service is 480 V Delta, an SPD with 550 V or 660 V MCOV will be required. Surge protection devices must also provide a level of protection compatible with the withstand of the equipment. This withstand depends on the type of equipment and its sensitivity. The incoming surge protector may not provide adequate protection by itself, as certain electrical phenomena may greatly increase its residual if cable lengths exceed 10 m. A second SPD may be necessary. ) Select the SPD surge capacity (Imax) Surge capacity is the amount of energy the SPD can withstand from a single surge event. The higher the surge capacity, the longer the device will protect the system. A second surge protector may be required if the surge capacity of the first is not capable of diverting all surge to ground. See coordination below. 4) Remote monitoring (optional) Integrated auxiliary contact for remote monitoring available on models with "TS" designation. Refer to the "selection tables" on next page for assistance selecting SPDs. OVR DIN rail SPD - catalog number explanation ABB SPD Phases Without = 1P L = P L = P 1N = 1P+N N = P+N N = P+N Max (Uc) 150 (175 V) 0 V 440 V 550 V 660 V UL 1449 rd edition OVR T N 40 0 P TS U Complete facility protection Installing surge protection at the main distribution panel is only the beginning of protecting the entire operation. As most transient surges are created internally, it is necessary to install surge protection at sub-distribution panels (equipment protection) to be fully protected. Stepping down the Imax level from the service entrance panel toward equipment to be protected is recommended. For example, if a 40 ka Imax SPD is installed in the main distribution panel, then 15 ka Imax SPDs should be installed in sub-distribution panels for equipment protection. Coordination It may be necessary to add a second surge protector, wired to the incoming unit, to achieve the required protection and/or surge capacity. For Type or 4 SPDs, installing this second unit a minimum of 1 m from the first unit will allow the two to work together, achieving the required protection. Wiring rules The impedance of the cables increases the across the connected equipment. Therefore, the length of the cable between the surge protector and the equipment should be minimized. The surge protective device should be installed as close to the equipment to be protected as possible. If this is not possible (the equipment is over 0 m from the panel), then a second surge protector must be installed. Designation Type apps Surge capacity (Imax) 15 ka 40 ka Pluggable Auxiliary contact (optional) / Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /

8 OVR surge protective devices UL version Selection tables OVR surge protective devices UL version Selection tables General wiring diagrams - DIN rail devices Delta Single phase Split phase L1 L1 Delta N 1 Protected lines Impulse OVR SPD OVR SPD L N L G L1 L L G OVR SPD OVR SPD N G L1 L N L G OVR SPD 40 / 10 V HLD 10 V, 40 V, 77 V 40 / 10 V, 480 / 40 V Max. In Wye 40 V, 480 V, 600 V 08 / 10 V, 480 / 77 V, 600 / 47 V NOTE: Multiple pole SPDs shown. Wiring diagrams for reference only. Follow interrupting rating Ifi Voltage protection rating VPR Max. cont. operating MCOV Iimp 10/50 Imax 8/0 Un ka ka ka ka kv V V Type - Pluggable - Single pole networks OVR T P U ±15% 0 OVR T 15-0 P U OVR T P U OVR T P TS U ±15% 0 OVR T 40-0 P U ±15% 0 OVR T 40-0 P TS U ±15% 440 OVR T P TS U ±15% 550 OVR T P TS U ±15% 660 OVR T P TS U Neutral OVR T 70 N P U Cartridges 1 10 ±15% 175 OVR T C U 1 77 ±15% 0 OVR T 15-0 C U 1 10 ±15% 175 OVR T C U 1 77 ±15% 0 OVR T 40-0 C U 1 47 ±15% 440 OVR T C U ±15% 550 OVR T C U ±15% 660 OVR T C U OVR T 70 N C U L1 N L G Protected lines Impulse Max. In Follow interrupting rating Ifi Voltage protection rating VPR Max. cont. operating MCOV Iimp 10/50 Imax 8/0 Un ka ka ka ka kv V V Type - Pluggable - delta networks % 0 OVR T L 15-0 P U ±15% 0 OVR T L 40-0 P TS U ±15% 550 OVR T L P TS U Cartridges 1 77 ±15% 0 OVR T 15-0 C U 1 77 ±15% 0 OVR T 40-0 C U ±15% 550 OVR T C U Type - Pluggable - Single phase networks OVR T 1N P U OVR T 1N 15-0 P U OVR T 1N P U OVR T 1N P U (x10) OVR T 1N P TS U OVR T 1N 40-0 P TS U OVR T 1N P TS U OVR T 1N P TS U OVR T 1N P TS U Cartridges 1 10 ±15% 175 OVR T C U 1 77 ±15% 0 OVR T 15-0 C U 1 10 ±15% 175 OVR T C U 1 77 ±15% 0 OVR T 40-0 C U 1 47 ±15% 440 OVR T C U ±15% 550 OVR T C U ±15% 660 OVR T C U Type - Pluggable - Split phase networks ±15% 175 OVR T L P U ±15% 0 OVR T L 15-0 P U ±15% 175 OVR T N P U ±15% 0 OVR T N 15-0 P U ±15% 175 OVR T L P TS U ±15% 0 OVR T L 40-0 P TS U ±15% 175 OVR T N P TS U ±15% 0 OVR T N 40-0 P TS U ±15% 440 OVR T N P TS U ±15% 550 OVR T N P TS U ±15% 660 OVR T N P TS U Cartridges 1 10 ±15% 175 OVR T C U 1 77 ±15% 0 OVR T 15-0 C U 1 10 ±15% 175 OVR T C U 1 77 ±15% 0 OVR T 40-0 C U 1 47 ±15% 440 OVR T C U ±15% 550 OVR T C U Type - Pluggable - Grounded Wye networks ±15% 175 OVR T L P U ±15% 175 OVR T N P U ±15% 0 OVR T N 15-0 P U ±15% 175 OVR T L P TS U ±15% 440 OVR T L P TS U ±15% 175 OVR T N P TS U ±15% 0 OVR T N 40-0 P TS U ±15% 440 OVR T N P TS U ±15% 550 OVR T N P TS U ±15% 660 OVR T N P TS U Cartridges 1 10 ±15% 175 OVR T C U 1 10 ±15% 175 OVR T C U 1 47 ±15% 440 OVR T C U 1 77 ±15% 0 OVR T 15-0 C U 1 77 ±15% 0 OVR T 40-0 C U ±15% 550 OVR T C U ±15% 660 OVR T C U /4 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /5

9 OVR surge protective devices UL version Selection tables OVR type surge protective devices - single pole Protected lines Impulse Iimp 10/50 Max. Imax 8/0 In Short circuit withstand Isccr/Iscpv Voltage protection rating VPR Un Max. cont. operating Uc ka ka ka ka kv V V DC Type - pluggable - photovoltaic applications OVR PV P U OVR PV P TS U OVR PV P U OVR PV P TS U OVR PV P U OVR PV P TS U OVR PV P U OVR PV P TS U OVR PV P U OVR PV P TS U OVR PV P U OVR PV P TS U OVR PV H P U OVR PV H P TS U Cartridges OVR PV C U OVR PV C U OVR PV C U OVR PV C U OVR PV C U OVR PV C U OVR PV H C U Dataline protection - pluggable OVR TC 00FR US OVR TC 06V US OVR TC 1V US OVR TC 4V US OVR TC 48V US CTC4116F1701 OVR T P U CTC410F1701 OVR T P TS U CTC415F1701 Descripiton Single pole devices provide great flexibility for any kind of network configuration. OVR T devices provide the best protection as they are designed to protect electric installations and sensitive equipment against indirect surges with ensuring a low protection level (VPR). They are characterized by their capacity to safely with 8/0 μs wave form. Protected lines Max Imax 8/0 Voltage protection rating Max. cont. operating Bbn In VPR Un MCOV ka ka kv V V EAN Pluggable OVR T P U ±15% OVR T 15-0 P U OVR T P U OVR T P TS U ±15% OVR T 40-0 P U ±15% OVR T 40-0 P TS U ±15% OVR T P TS U ±15% OVR T P TS U ±15% OVR T P TS U Neutral - Pluggable OVR T 70 N P U OVR T 70 N P U Main dimensions mm Width mm OVR T P U 17.8 OVR T 15-0 P U 17.8 OVR T P U 17.8 OVR T P TS U 17.8 OVR T 40-0 P U 17.8 OVR T 40-0 P TS U 17.8 OVR T P TS U 17.8 OVR T P TS U 17.8 OVR T P TS U 17.8 OVR T 70 N P U OVR T P U OVR T 15-0 P U OVR T P U OVR T 40-0 P U OVR T 70 N P U OVR T P TS U OVR T 40-0 P TS U OVR T P TS U OVR T P TS U OVR T P TS U 96 /6 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /7

10 OVR type surge protective devices - single pole General technical specifications Type OVR T P U OVR T 15-0 P U OVR T P U OVR T 40-0 P U OVR T 70 N P U with auxiliary contact (TS) OVR T P TS U OVR T 40-0 P TS U OVR T P TS U OVR T P TS U OVR T P TS U Technology Varistor Varistor Varistor Varistor Varistor Varistor Varistor Spark gap Electrical features Standard UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 Type / test class (UL 1449) Protected lines System network Type of / frequency AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz Voltage regulation of the system network ±15% ±15% ±15% ±15% ±15% ±15% ±15% +15% system Un 10 V 77 V 10 V 77 V 47 V 480 V 600 V 0 V Maximum continuous operating MCOV 150 V 0 V 150 V 0 V 440 V 550 V 660 V 75 V Maximal (8/0) Imax 15 ka 15 ka 40 ka 40 ka 40 ka 40 ka 40 ka 70 ka (8/0) In 5 ka 5 ka 0 ka 0 ka 10 ka 10 ka 10 ka 0 ka Voltage protection rating (L-N / N-G / L-G) VPR 0.6 kv 1 kv 0.6 kv 1 kv 1. kv 1.7 kv 1.9 kv 1. kv Response time < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns Short circuit withstand SCCR 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka Back up protection fuse (gg - gl) 100 A 100 A 100 A 100 A 100 A 100 A 100 A 100 A maximum rating circuit breaker (B or C Curve) 15 A 15 A 15 A 15 A 15 A 15 A 15 A 15 A Pluggable cartridges Yes Yes Yes Yes Yes Yes Yes Yes Integrated QuickSafe technology Yes Yes Yes Yes Yes Yes Yes No State indicator Yes Yes Yes Yes Yes Yes Yes Yes Safety reserve Auxiliary contact (TS) No No Yes (TS option) Yes (TS option) Yes Yes Yes No Installation Wire range (L,N,PE) solid wire.5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm² stranded wire.5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm² Stripping length (L,N,PE) 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm Tightening torque (L,N,PE).8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm Auxiliary contact (TS) Contact information 1 NO 1 NC 1 NO 1 NC 1 NO 1 NC 1 NO 1 NC 1 NO 1 NC Min. load 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma Max. load 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A Connection cross section 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² Miscellaneous characteristics Stocking temperature C C C C C C C C Operating temperature C C C C C C C C Degree of protection NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 Fire resistance according to UL 94 V0 V0 V0 V0 V0 V0 V0 V0 Dimensions mm h x w x d 88 x 17.8 x 64.8 mm 88 x 17.8 x 64.8 mm 88 x 17.8 x 64.8 mm 88 x 17.8 x 64.8 mm 88 x 17.8 x 64.8 mm inches h x w x d.46 x 0.7 x.55 in.46 x 0.7 x.55 in.46 x 0.7 x.55 in.46 x 0.7 x.55 in.46 x 0.7 x.55 in Dimensions with mm h x w x d 96 x 17.8 x 64.8 mm 96 x 17.8 x 64.8 mm 96 x 17.8 x 64.8 mm 96 x 17.8 x 64.8 mm 96 x 17.8 x 64.8 mm auxiliary contact (TS) inches h x w x d.78 x 0.7 x.55 in.78 x 0.7 x.55 in.78 x 0.7 x.55 in.78 x 0.7 x.55 in.78 x 0.7 x.55 in Replacement cartridges Phase product ID Type OVR T C U OVR T 15-0 C U OVR T C U OVR T 40-0 C U OVR T C U OVR T C U OVR T C U Order code CTB8048R500 CTB8048R700 CTB8048R500 CTB8048R700 CTB8048R900 CTB8048R4100 CTB8048R400 Neutral product ID Type OVR T 70 N C U Order code CTB8048R6500 /8 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /9

11 OVR type surge protective devices Delta networks OVR type surge protective devices Delta networks OVR T L 15-0 P U CTC411F1701 CTC41F1701 OVR T L 40-0 P TS U Description Delta devices provide the protection required by the three phases of a Delta network system. OVR T devices provide the best protection as they are designed to protect electric installations and sensitive equipment against indirect surges with ensuring a low protection level (VPR). They are characterized by their capacity to safely with 8/0 μs wave form. Protected lines Max Imax 8/0 Voltage protection rating Max. cont. operating Bbn In VPR Un MCOV, Uc ka ka kv V V EAN Pluggable ±15% OVR T L 15-0 P U ±15% OVR T L 40-0 P TS U ±15% OVR T L P TS U Main dimensions mm General technical specifications Type OVR T L 15-0 P U with auxiliary contact (TS) OVR T L 40-0 P TS U OVR T L P TS U Electrical features Standards UL 1449 UL 1449 UL 1449 Type / test class (UL 1449) Protected lines Type of / frequency AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz Voltage regulation of the system network ±15% ±15% ±15% system Un 77 V 77 V 480 V Maximum continuous operating MCOV 0 V 0 V 550 V Maximal (8/0) Imax 15 ka 40 ka 40 ka (8/0) In 5 ka 0 ka 10 ka Voltage protection rating (L-N / N-G / L-G) VPR 1 kv 1 kv 1.7 kv Response time < 5 ns < 5 ns < 5 ns Short circuit withstand SCCR 00 ka 00 ka 00 ka Back up protection fuse (gg - gl) 100 A 100 A 100 A maximum rating circuit breaker (B or C curve) 15 A 15 A 15 A Pluggable cartridges Yes Yes Yes Integrated QuickSafe technology Yes Yes Yes State indicator Yes Yes Yes Safety reserve Auxiliary contact (TS) No Yes Yes Installation Wire range (L,N,PE) solid wire.5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm² stranded wire.5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm² Stripping length (L,N,PE) 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm Tightening torque (L,N,PE).8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm Auxiliary contact (TS) Contact information NO NC NO NC Min. load 1 V DC 10 ma 1 V DC 10 ma Max. load 50 V AC 1 A 50 V AC 1 A Connection cross section 1.5 / 16 mm² 1.5 / 16 mm² Miscellaneous characteristics Stocking temperature C C C Operating temperature C C C Degree of protection NEMA 1 NEMA 1 NEMA 1 Fire resistance according to UL 94 V0 V0 V0 Dimensions mm h x w x d 90.5 x 5.4 x 64.8 mm inches h x w x d.56 x.1 x.55 in Dimensions with mm h x w x d 98.5 x 5.4 x 64.8 mm 98.5 x 5.4 x 64.8 mm auxiliary contact (TS) inches h x w x d.88 x.1 x.55 in.88 x.1 x.55 in Replacement cartridges Phase product ID Type OVR T 15-0 C U OVR T 40-0 C U OVR T C U Order code CTB8048R700 CTB8048R700 CTB8048R4100 Neutral product ID Type Order code Width mm OVR T L 15-0 P U 5.4 OVR T L 40-0 P TS U 5.4 OVR T L P TS U OVR T L 15-0 P U OVR T L 40-0 P TS U OVR T L P TS U /10 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /11

12 OVR type surge protective devices Single phase networks Description Single phase devices are composed by a MOV pole plus a spark gap one. The spark gap pole guarantees the lowest protection rating and has to be connected to the Neutral. CTC480F1701 OVR T devices provide the best protection as they are designed to protect electric installations and sensitive equipment against indirect surges with ensuring a low protection level (VPR). They are characterized by their capacity to safely with 8/0 μs wave form. OVR T 1N P U CTC4177F1701 OVR T 1N P TS U Protected lines Max Imax 8/0 Voltage protection rating Max. cont. operating Bbn In VPR Un MCOV, Uc ka ka kv V V EAN Pluggable OVR T 1N P U OVR T 1N 15-0 P U OVR T 1N P U OVR T 1N P U (x10) OVR T 1N P TS U OVR T 1N 40-0 P TS U OVR T 1N P TS U OVR T 1N P TS U OVR T 1N P TS U (x10) packaging of 10 pieces Main dimensions mm Width mm OVR T 1N P U 5.6 OVR T 1N 15-0 P U 5.6 OVR T 1N P U 5.6 OVR T 1N P TS U 5.6 OVR T 1N 40-0 P TS U 5.6 OVR T 1N P TS U 5.6 OVR T 1N P TS U 5.6 OVR T 1N P TS U OVR T 1N P U OVR T 1N 15-0 P U OVR T 1N P U OVR T 1N P TS U OVR T 1N 40-0 P TS U OVR T 1N P TS U OVR T 1N P TS U OVR T 1N P TS U /1 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /1

13 OVR type surge protective devices Single phase networks General technical specifications Type OVR T 1N P U OVR T 1N 15-0 P U OVR T 1N P U with auxiliary contact (TS) OVR T 1N P TS U OVR T 1N 40-0 P TS U OVR T 1N P TS U OVR T 1N P TS U OVR T 1N P TS U Electrical features Standards UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 Type / test class (UL 1449) Protected lines Type of / frequency AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz Voltage regulation of the system network ±15% ±15% ±15% ±15% ±15% ±15% ±15% system Un 10 V 77 V 10 V 77 V 47 V 480 V 600 V Maximum continuous operating MCOV 150 V 0 V 150 V 0 V 440 V 550 V 660 V Maximal (8/0) Imax 15 ka 15 ka 40 ka 40 ka 40 ka 40 ka 40 ka (8/0) In 5 ka 5 ka 0 ka 0 ka 10 ka 10 ka 10 ka Voltage protection rating (L-N / N-G / L-G) VPR 1. kv 1. kv 1. kv 1. kv 1. kv 1. kv 1. kv Response time < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns Short circuit withstand SCCR 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka Back up protection fuse (gg - gl) 100 A 100 A 100 A 100 A 100 A 100 A 100 A maximum rating circuit breaker (B or C 15 A 15 A 15 A 15 A 15 A 15 A 15 A curve) Pluggable cartridges Yes Yes Yes Yes Yes Yes Yes Integrated QuickSafe technology Yes Yes Yes Yes Yes Yes Yes State indicator Yes Yes Yes Yes Yes Yes Yes Safety reserve Auxiliary contact (TS) No No Yes (TS option) Yes Yes Yes Yes Installation Wire range (L,N,PE) solid wire.5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm² stranded wire.5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm² Stripping length (L,N,PE) 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm Tightening torque (L,N,PE).8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm Auxiliary contact (TS) Contact information NO NC NO NC NO NC NO NC NO NC Min. load 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma Max. load 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A Connection cross section 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² Miscellaneous characteristics Stocking temperature C C C C C C C Operating temperature C C C C C C C Degree of protection NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 Fire resistance according to UL 94 V0 V0 V0 V0 V0 V0 V0 Dimensions mm h x w x d 90.5 x 5.6 x 64.8 mm 90.5 x 5.6 x 64.8 mm 90.5 x 5.6 x 64.8 mm inches h x w x d.56 x 1.4 x.55 in.56 x 1.4 x.55 in.56 x 1.4 x.55 in Dimensions with mm h x w x d 98.5 x 5.6 x 64.8 mm 98.5 x 5.6 x 64.8 mm 98.5 x 5.6 x 64.8 mm 98.5 x 5.6 x 64.8 mm 98.5 x 5.6 x 64.8 mm auxiliary contact (TS) inches h x w x d.88 x 1.4 x.55 in.88 x 1.4 x.55 in.88 x 1.4 x.55 in.88 x 1.4 x.55 in.88 x 1.4 x.55 in Replacement cartridges Phase product ID Type OVR T C U OVR T 15-0 C U OVR T C U OVR T 40-0 C U OVR T C U OVR T C U OVR T C U Order code CTB8048R500 CTB8048R700 CTB8048R500 CTB8048R700 CTB8048R900 CTB8048R4100 CTB8048R400 Neutral product ID Type OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U Order code CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 /14 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /15

14 OVR type surge protective devices Split phase networks CTC416F1701 OVR T L 15-0 P U Description Split phase devices are composed by two MOV poles or two MOV poles plus a spark gap one, depending on the number of lines the customer wants to pretect. The spark gap pole guarantees the lowest protection rating and has to be connected to the neutral. OVR T devices provide the best protection as they are designed to protect electric installations and sensitive equipment against indirect surges with ensuring a low protection level (VPR). They are characterized by their capacity to safely with 8/0 μs wave form. CTC419F1701 OVR T L 40-0 P TS U CTC4179F1701 Protected lines Max Imax 8/0 Voltage protection rating Max. cont. operating Bbn In VPR Un MCOV, Uc ka ka kv V V EAN Pluggable ±15% OVR T L P U ±15% OVR T L 15-0 P U ±15% OVR T L P TS U ±15% OVR T L 40-0 P TS U ±15% OVR T N P U ±15% OVR T N 15-0 P U ±15% OVR T N P TS U ±15% OVR T N 40-0 P TS U ±15% OVR T N P TS U ±15% OVR T N P TS U ±15% OVR T N P TS U OVR T N 15-0 P U CTC418F1701 OVR T N P TS U Width mm OVR T L P U 5.6 OVR T L 15-0 P U 5.6 OVR T L P TS U 5.6 OVR T L 40-0 P TS U 5.6 OVR T N P U 5.4 OVR T N 15-0 P U 5.4 OVR T N P TS U 5.4 OVR T N 40-0 P TS U 5.4 OVR T N P TS U 5.4 OVR T N P TS U 5.4 OVR T N P TS U 5.4 Main dimensions mm OVR T L P U OVR T L 15-0 P U OVR T N P U OVR T N 15-0 P U OVR T L P TS U OVR T L 40-0 P TS U OVR T N P TS U OVR T N 40-0 P TS U OVR T N P TS U OVR T N P TS U OVR T N P TS U /16 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /17

15 OVR type surge protective devices Split phase networks General technical specifications Type OVR T L OVR T L OVR T N OVR T N P U 15-0 P U P U 15-0 P U with auxiliary contact (TS) OVR T L P TS U OVR T L 40-0 P TS U OVR T N P TS U OVR T N 40-0 P TS U OVR T N P TS U OVR T N P TS U OVR T N P TS U Electrical features Standards UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 Type / test class (UL 1449) Protected lines Type of / frequency AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz Voltage regulation of the system network ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15% system Un 10 V 77 V 10 V 77 V 10 V 77 V 10 V 77 V 47 V 480 V 600 V Maximum continuous operating MCOV 175 V 0 V 175 V 0 V 175 V 0 V 175 V 0 V 440 V 550 V 660 V Maximal (8/0) Imax 15 ka 15 ka 40 ka 40 ka 15 ka 15 ka 40 ka 40 ka 40 ka 40 ka 40 ka (8/0) In 5 ka 5 ka 0 ka 0 ka 5 ka 5 ka 0 ka 0 ka 10 ka 10 ka 10 ka Voltage protection rating (L-N / N-G / L-G) VPR 0.6 kv 1 kv 0.6 kv 1 kv 0.7 kv 1.1 kv 0.7 kv 1.1 kv 1.4 kv 1.8 kv kv Response time < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns Short circuit withstand SCCR 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka Back up protection fuse (gg - gl) 100 A 100 A 100 A 100 A 100 A 100 A 100 A 100 A 100 A 100 A 100 A maximum rating circuit breaker 15 A 15 A 15 A 15 A 15 A 15 A 15 A 15 A 15 A 15 A 15 A (B or C curve) Pluggable cartridges Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Integrated QuickSafe technology Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes State indicator Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Safety reserve Auxiliary contact (TS) No No Yes Yes No No Yes Yes Yes Yes Yes Installation Wire range (L,N,PE) solid wire.5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm² stranded wire.5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm² Stripping length (L,N,PE) 1.5 / / / / / / / / / / / 0.5 Tightening torque (L,N,PE).8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm Auxiliary contact (TS) Contact information NO NC NO NC NO NC NO NC NO NC NO NC NO NC Min. load 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma Max. load 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A Connection cross section 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² Miscellaneous characteristics Stocking temperature C C C C C C C C C C C Operating temperature C C C C C C C C C C C Degree of protection NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 Fire resistance according to UL 94 V0 V0 V0 V0 V0 V0 V0 V0 V0 V0 V0 Dimensions mm h x w x d 90.5 x 5.6 x 64.8 mm 90.5 x 5.6 x 64.8 mm 90.5 x 5.4 x 64.8 mm 90.5 x 5.4 x 64.8 mm inches h x w x d.56 x 1.4 x.55 in.56 x 1.4 x.55 in.56 x.1 x.55 in.56 x.1 x.55 in Dimensions with mm h x w x d 98.5 x 5.6 x 64.8 mm 98.5 x 5.6 x 64.8 mm 98.5 x 5.4 x 64.8 mm 98.5 x 5.4 x 64.8 mm 98.5 x 5.4 x 64.8 mm 98.5 x 5.4 x 64.8 mm 98.5 x 5.4 x 64.8 mm auxiliary contact (TS) inches h x w x d.88 x 1.4 x.55 in.88 x 1.4 x.55 in.88 x.1 x.55 in.88 x.1 x.55 in.88 x.1 x.55 in.88 x.1 x.55 in.88 x.1 x.55 in Replacement cartridges 1 NO 1 NC 1 NO 1 NC 1 NO 1 NC 1 NO 1 NC 1 NO 1 NC Phase product ID Type OVR T C U OVR T 15-0 C U OVR T C U OVR T 40-0 C U OVR T C U OVR T 15-0 C U OVR T C U OVR T 40-0 C U OVR T C U OVR T C U OVR T C U Order code CTB8048R500 CTB8048R700 CTB8048R500 CTB8048R700 CTB8048R500 CTB8048R700 CTB8048R500 CTB8048R700 CTB8048R900 CTB8048R4100 CTB8048R400 Neutral product ID Type OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U Order code CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 /18 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /19

16 OVR type surge protective devices Grounded Wye networks CTC41F1701 OVR T L P TS U Description Wye devices are composed by three MOV poles or three MOV poles plus a spark gap one, depending on the number of lines the customer wants to protect. The spark gap pole guarantees the lowest protection rating and has to be connected to the neutral. OVR T devices provide the best protection as they are designed to protect electric installations and sensitive equipment against indirect surges with ensuring a low protection level (VPR). They are characterized by their capacity to safely with 8/0 μs wave form. Protected lines Max Imax 8/0 Voltage protection rating Max. cont. operating Bbn In VPR Un MCOV, Uc ka ka kv V V EAN Pluggable ±15% OVR T L P U ±15% OVR T L P TS U ±15% OVR T L P TS U ±15% OVR T N P U ±15% OVR T N 15-0 P U ±15% OVR T N P TS U ±15% OVR T N 40-0 P TS U ±15% OVR T N P TS U ±15% OVR T N P TS U ±15% OVR T N P TS U Width mm OVR T L P U 5.4 OVR T L P TS U 5.4 OVR T L P TS U 5.4 OVR T N P U 71. OVR T N 15-0 P U 71. OVR T N P TS U 71. OVR T N 40-0 P TS U 71. OVR T N P TS U 71. OVR T N P TS U 71. OVR T N P TS U 71. Main dimensions mm OVR T L P U OVR T N P U OVR T N 15-0 P U OVR T L P TS U OVR T L P TS U OVR T N P TS U OVR T N 40-0 P TS U OVR T N P TS U OVR T N P TS U OVR T N P TS U /0 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /1

17 OVR type surge protective devices Grounded Wye networks General technical specifications Type OVR T L OVR T N OVR T N P U P U 15-0 P U with auxiliary contact (TS) OVR T L P TS U OVR T L P TS U OVR T N P TS U OVR T N 40-0 P TS U OVR T N P TS U OVR T N P TS U OVR T N P TS U Electrical features Standards UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 Type / test class (UL 1449) Protected lines Type of / frequency AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz AC 47-6 Hz Voltage regulation of the system network ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15% ±15% system Un 10 V 10 V 47 V 10 V 77 V 10 V 77 V 47 V 480 V 600 V Maximum continuous operating MCOV 175 V 175 V 440 V 175 V 0 V 175 V 0 V 440 V 550 V 660 V Maximal (8/0) Imax 15 ka 40 ka 40 ka 15 ka 15 ka 40 ka 40 ka 40 ka 40 ka 40 ka (8/0) In 5 ka 10 ka 10 ka 5 ka 5 ka 0 ka 0 ka 10 ka 10 ka 10 ka Voltage protection rating (L-N / N-G / L-G VPR) 0.6 kv 0.6 kv 1. kv 0.6 kv 1 kv 1. kv 1. kv 1. kv 1. kv 1. kv Response time < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns Short circuit withstand SCCR 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka 00 ka Back up protection fuse (gg - gl) 100 A 100 A 100 A 100 A 100 A 100 A 100 A 100 A 100 A 100 A maximum rating circuit breaker (B or C curve) 15 A 15 A 15 A 15 A 15 A 15 A 15 A 15 A 15 A 15 A Pluggable cartridges Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Integrated QuickSafe technology Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes State indicator Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Safety reserve Auxiliary contact (TS) No Yes Yes No No Yes Yes Yes Yes Yes Installation Wire range (L,N,PE) solid wire.5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm² stranded wire.5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm² Stripping length (L,N,PE) 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm Tightening torque (L,N,PE).8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm Auxiliary contact (TS) Contact information 4 NO 4 NC 4 NO 4 NC 4 NO 4 NC 4 NO 4 NC 4 NO 4 NC 4 NO 4 NC 4 NO 4 NC Min. load 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma Max. load 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A Connection cross section 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² 1.5 / 16 mm² Miscellaneous characteristics Stocking temperature C C C C C C C C C C Operating temperature C C C C C C C C C C Degree of protection NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 Fire resistance according to UL 94 V0 V0 V0 V0 V0 V0 V0 V0 V0 V0 Dimensions mm h x w x d 90.5 x 5.4 x 64.8 mm 90.5 x 71. x 64.8 mm 90.5 x 71. x 64.8 mm inches h x w x d.56 x.1 x.55 in.56 x.8 x.55 in.56 x.8 x.55 in Dimensions with mm h x w x d 98.5 x 5.4 x 64.8 mm 98.5 x 5.4 x 64.8 mm 98.5 x 71. x 64.8 mm 98.5 x 71. x 64.8 mm 98.5 x 71. x 64.8 mm 98.5 x 71. x 64.8 mm 98.5 x 71. x 64.8 mm auxiliary contact (TS) inches h x w x d.88 x.1 x.55 in.88 x.1 x.55 in.88 x.8 x.55 in.88 x.8 x.55 in.88 x.8 x.55 in.88 x.8 x.55 in.88 x.8 x.55 in Replacement cartridges Phase product ID Type OVR T C U OVR T C U OVR T C U OVR T C U OVR T 15-0 C U OVR T C U OVR T 40-0 C U OVR T C U OVR T C U OVR T C U Order code CTB8048R500 CTB8048R500 CTB8048R900 CTB8048R500 CTB8048R700 CTB8048R500 CTB8048R700 CTB8048R900 CTB8048R4100 CTB8048R400 Neutral product ID Type OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U OVR T 70 N C U Order code CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 CTB8048R6500 / Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /

18 OVR PV surge protection devices Photovoltaic applications Description Specifically designed for photovoltaic DC installations, the OVR PV family provides a safe and reliable surge and lightning protection of solar panels and converters. CTC494F1701 OVR PV P TS U The OVR PV surge protective devices comply with UL Protected lines Max Imax 8/0 In Voltage protection rating VPR Max. cont. operating MCOV, Uc Bbn Un ka ka kv V V EAN Pluggable OVR PV P U OVR PV P TS U OVR PV P U OVR PV P TS U OVR PV P U OVR PV P TS U OVR PV P U OVR PV P TS U OVR PV P U OVR PV P TS U OVR PV P U OVR PV P TS U OVR PV H P U OVR PV H P TS U Width mm OVR PV P U 5.4 OVR PV P TS U 5.4 OVR PV P U 5.4 OVR PV P TS U 5.4 OVR PV P U 5.4 OVR PV P TS U 5.4 OVR PV P U 5.4 OVR PV P TS U 5.4 OVR PV P U 5.4 OVR PV P TS U 5.4 OVR PV P U 5.4 OVR PV P TS U 5.4 OVR PV H P U 5.4 OVR PV H P TS U 5.4 Main dimensions mm OVR PV P U OVR PV P U OVR PV P U OVR PV P U OVR PV P U OVR PV P U OVR PV H P U OVR PV P TS U OVR PV P TS U OVR PV P TS U OVR PV P TS U OVR PV P TS U OVR PV P TS U OVR PV H P TS U /4 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /5

19 OVR PV surge protection devices Photovoltaic applications General technical specifications Type OVR PV P U OVR PV P U OVR PV P U OVR PV P U OVR PV P U OVR PV P U OVR PV H P U with auxiliary contacts (TS) OVR PV P TS U OVR PV P TS U OVR PV P TS U OVR PV P TS U OVR PV P TS U OVR PV P TS U OVR PV H P TS U Technology Varistor Varistor Varistor Varistor Varistor Varistor Varistor Electrical features Standards UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 Type / test class (UL 1449) Protected lines Type of / frequency Photovoltaic systems - DC side Photovoltaic systems - DC side Photovoltaic systems - DC side Photovoltaic systems - DC side Photovoltaic systems - DC side Photovoltaic systems - DC side Photovoltaic systems - DC side Voltage regulation of the system network DC DC DC DC DC DC DC system Un 600 V 600 V 800 V 800 V 1000 V 1000 V 1500 V Maximum continuous operating MCOV 670 V 670 V 1000 V 1000 V 150 V 150 V 1500 V Maximal (8/0) Imax 15 ka 40 ka 15 ka 40 ka 15 ka 40 ka 40 ka (8/0) In 5 ka 10 ka 5 ka 10 ka 5 ka 10 ka 15 ka Voltage protection rating (L-N / N-G / L-G) VPR kv kv 4 kv 4 kv 4 kv 4 kv 4.5 kv Response time < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns < 5 ns Residual IPE < 5 µa < 5 µa < 5 µa < 5 µa < 5 µa < 5 µa < 5 µa Short circuit withstand SCCR 1 ka 1 ka 1 ka 1 ka 1 ka 1 ka 1 ka Disconnector fuse (gg - gl) circuit breaker (B or C curve) Pluggable cartridges Yes Yes Yes Yes Yes Yes Yes Integrated QuickSafe technology Yes Yes Yes Yes Yes Yes Yes State indicator Yes Yes Yes Yes Yes Yes Yes Safety reserve No No No No No No No Auxiliary contact (TS) Yes (TS option) Yes (TS option) Yes (TS option) Yes (TS option) Yes (TS option) Yes (TS option) Yes (TS option) Installation Wire range (L,N,PE) solid wire.5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm².5 5 / 4 14 mm² stranded wire.5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm².5 16 / 6 14 mm² Stripping length (L,N,PE) 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm 1.5 / 0.5 mm Tightening torque (L,N,PE).8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm.8 / 4.5 Nm Auxiliary contact (TS) Contact information NO NC NO NC NO NC NO NC NO NC NO NC NO NC Min. load 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma 1 V DC 10 ma Max. load 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A 50 V AC 1 A Connection cross section mm² mm² mm² mm² mm² mm² mm² Miscellaneous characteristics Stocking and operating temperature C C C C C C C Degree of protection NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 Fire resistance according to UL 94 V0 V0 V0 V0 V0 V0 V0 Dimensions mm h x w x d 91.5 x 5.4 x 64.8 mm 91.5 x 5.4 x 64.8 mm 91.5 x 5.4 x 64.8 mm 91.5 x 5.4 x 64.8 mm 91.5 x 5.4 x 64.8 mm 91.5 x 5.4 x 64.8 mm 91.5 x 5.4 x 64.8 mm inches h x w x d.6 x.1 x.55 in.6 x.1 x.55 in.6 x.1 x.55 in.6 x.1 x.55 in.6 x.1 x.55 in.6 x.1 x.55 in.6 x.1 x.55 in Dimensions with mm h x w x d 96 x 5.4 x 64.8 mm 96 x 5.4 x 64.8 mm 96 x 5.4 x 64.8 mm 96 x 5.4 x 64.8 mm 96 x 5.4 x 64.8 mm 96 x 5.4 x 64.8 mm 96 x 5.4 x 64.8 mm auxiliary contact (TS) inches h x w x d.78 x.1 x.55 in.78 x.1 x.55 in.78 x.1 x.55 in.78 x.1 x.55 in.78 x.1 x.55 in.78 x.1 x.55 in.78 x.1 x.55 in Replacement cartridges Phase product ID Type OVR PV C U OVR PV C U OVR PV C U OVR PV C U OVR PV C U OVR PV C U OVR PV H C U Order code CTB8049R900 CTB8049R0400 CTB8049R500 CTB8049R1000 CTB8049R4100 CTB8049R1600 CTB8049R1700 /6 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /7

20 OVR TC surge protective devices Dataline protection OVR TC surge protection devices Dataline protection CSC400006F001 OVR TC 00FR US Description The OVR TC family offers a reliable surge protection to dataline networks for datacenters, water treatment installations or wind turbine installations. With the RJ11 and RJ45 bases, they allow a flexible and easy installation. Protected lines Max Imax 8/0 In Voltage protection rating VPR Max. cont. operating MCOV, Uc Bbn Un ka ka V V V EAN Pluggable OVR TC 00FR US OVR TC 06V US OVR TC 1V US OVR TC 4V US OVR TC 48V US OVR TC 00 V US General technical specifications Type OVR TC 00FR US OVR TC 06V US OVR TC 1V US OVR TC 4V US OVR TC 48V US with auxiliary contact (TS) Connection configuration Serie Serie Serie Serie Serie Electrical features Standards UL 1449 UL 1449 UL 1449 UL 1449 UL 1449 Test class II II II II II Number of protected wires Types of network RTC analog / ADSL MIC/T - RS4/485 RS LS - 4/0mA RNIS - To Type of DC DC DC DC DC Un 00 V 6 V 1 V 4 V 48 V Maximal continuous operating Mcov 0 V 7 V 14 V 7 V 5 V Maximal (8/0) Imax 10 ka 10 ka 10 ka 10 ka 10 ka (8/0) In 5 ka 5 ka 5 ka 5 ka 5 ka Voltage protection level at In / VPR 00 V 15 V 0 V 5 V 70 V Short circuit withstand 10 ka 10 ka 10 ka 10 ka 10 ka Response time <1 ns <1 ns <1 ns <1 ns <1 ns Operating Ic 140 ma 140 ma 140 ma 140 ma 140 ma Series resistance 10 Ohm 10 Ohm 10 Ohm 10 Ohm 10 Ohm Cut frequency MHz 10 MHz MHz 4 MHz 6 MHz Pluggable unit No No No No No State Indicator Yes Yes Yes Yes Yes Safety reserve No No No No No Auxiliary contact (TS) No No No No No Installation Wire range (L,N, PE) solid wire mm mm mm mm mm stranded wire Stripping length (L, N, PE) 6 mm 6 mm 6 mm 6 mm 6 mm Tightening torque (L, N, PE) 0. Nm 0. Nm 0. Nm 0. Nm 0. Nm Auxiliary contact (TS) Contact complement Min. load Max. load Connection cross section Miscellaneous characteristics Operating temperature C C C C C Degree of protection IP0 IP0 IP0 IP0 IP0 Fire resistance according to UL 94 V0 V0 V0 V0 V0 Dimensions mm h x w x d 85 x 1 x 64 mm 85 x 1 x 64 mm 85 x 1 x 64 mm 85 x 1 x 64 mm 85 x 1 x 64 mm inches h x w x d.5 x 0.47 x.5 in.5 x 0.47 x.5 in.5 x 0.47 x.5 in.5 x 0.47 x.5 in.5 x 0.47 x.5 in Main dimensions mm Width mm OVR TC 00FR US 1 OVR TC 06V US 1 OVR TC 1V US 1 OVR TC 4V US 1 OVR TC 48V US 1 OVR TC 00FR US OVR TC 06V US OVR TC 1V US OVR TC 4V US OVR TC 48V US /8 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /9

21 Joslyn surge protective devices JSP / Surgitron I /4 TransEnd /5 Surgitron III -1 series /6 Surgitron III -49 series /7 Surgitron III - series /8 LDP / series /10 US Catalog Surge protective devices (SPDs) /1

22 JSP Heavy duty for service entrance applications Description Listed to UL th Edition for a Type 1 and Type SPD application. Fail-safe design with individually fused Metal Oxide Varistors (MOVs) eliminating single point failure, protecting against both over and over events. 00kAIC short circuit rating permits direct bus connection to most electrical services. Low let through ensured by the lowest possible impedance path to ground and equal sharing during surge events. All weather sealed, powder-coated NEMA 4/IP65 housing is designed for any orientation and indoor/outdoor applications. 10-year standard warranty with optional 15-year extended warranty. JSP /4" MYERS HUB (D1) (D) (W1) (W) ø0.1 (7.87) (H1) (H) (H) JSP " (4.5 mm) (D).0" (8.8 mm) (W1) (W) ø0.1 (7.87) (H1) (H) (H) JSP " (4.5 mm) (D).0" (8.8 mm) (W1) (W) ø0.1 (7.87) (H1) (H) (H) Allowable Area For Conduit Entry Allowable Area For Conduit Entry Voltage Configuration JSPxxx-1P10 10V 1-Phase, -Wire + Ground JSPxxx-1P40 40V 1-Phase, -Wire + Ground JSPxxx-1S40 10/40V -Phase, -Wire + Ground JSPxxx-Y08 10/08V -Phase Wye, 4-Wire + Ground JSPxxx-Y80 0/80V -Phase Wye, 4-Wire + Ground JSPxxx-Y415 40/415V -Phase Wye, 4-Wire + Ground JSPxxx-Y480 77/480V -Phase Wye, 4-Wire + Ground JSPxxx-H40 10/40V -Phase High-Leg, 4-Wire + Ground JSPxxx-D40 40V -Phase Delta, -Wire + Ground JSPxxx-D80* 80V -Phase Delta, -Wire + Ground JSPxxx-D480* 480V -Phase Delta, -Wire + Ground JSPxxx-Y600* 600V -Phase Wye, 4-Wire + Ground JSPxxx-D600* 600V -Phase Delta, 4-Wire + Ground *Not available in all ka Where xxx = 60, 80, 100, 10, 160, 00, 40, 00, 400kA per phase Above are the most popular configurations. Warranty 10-years (optional 15-years) Available options Advanced monitoring Add suffix -M (available in 60, 80, 100kA only) Surge counter Add suffix -B (available in 10kA or higher only) Transient filter Add suffix -F Stainless steel enclosure Add suffix -S Recessed option (to be ordered as a separate Item) JSPR Compact design to allow the SPD to be recessed into the wall. (available in 10, 160kA only in all configurations. Optional surge counter not available.) Flush-mount options (to be ordered as a separate Item) JSP-FMP Flush-mount plate kit (available in 60, 80, 100kA only) JSPR-FMP-10/160 Flush-mount plate kit (available in 10, 160kA JSPR only) / Surge protective devices (SPDs) US Catalog Technical specifications Electrical Discharge Current Rating (I-n) (I-n) 60, 80, 100kA 10kA 10kA or higher 0kA Operating Frequency 47 6Hz Connection Method Parallel to electrical distribution system Pre-wired with 6 inches of #10 AWG conductor (JSPR only) Response Time Less than 1 nanosecond Standard Monitoring kA and JSPR only LED status indicator lights (one per phase) 10kA or higher LED status indicator lights (one per phase) Standard Dry (From C) Relay Contacts Audible Alarm with Silence Button Mechanical Weight lbs. (4.5 kg) lbs. (9 kg) lbs. (18. kg) Enclosure Type Powder-coated, impactresistance steel, weather-proof NEMA 4 Installation Location Indoor/Outdoor Operating Environment -40 to +185 F (-40 to +70 C) Altitude Up to 1,000 ft. (4000 m) Product Design Parallel design with individually fused MOVs Regulatory UL th Edition Type Type 1 UL 18 Yes IEEE C6.41.1,., C6.45 Yes Listed By ETL kA models only UL kA models only CE kA models only Technical specifications Dim JSP 60, 80, 100 JSP 10, 160 JSP 00, 40, 00, 400 H (15.4) (54.0) (55.6) H 6.75 (171.5) (7.1) (74.7) H 7.50 (190.5) (9.1) (9.7) W (15.4) 8.00 (0.) 1.00 (04.8) W 4.00 (101.6) 6.00 (15.4) (54.0) D 6.0 (157.5) 6.0 (157.5) D (105.7) D.00 (50.8) All measurements in inches (mm) JSPR Made in U.S.A. Stud Drywall Flush-Mount Plate JSPR unit (D1) (D) (W1) (W) /4" Myers Hub Ø 0.1 (7.87) (H1) (H) (H) Approximate dimensions Dim JSPR H (54.0) H (7.1) H (9.1) W (0.) W 6.00 (15.4) D1 4.0 (106.9) D.00 (50.8) All measurements in inches (mm) US Catalog Surge protective devices (SPDs) /

23 PMS 19 Old Glory Red PMS 81 Old Glory Blue PMS 19 Old Glory Red PMS 81 Old Glory Blue Surgitron I Heavy duty service entrance application modular design TransEnd Medium duty for distribution applications Description Listed by ETL to UL th Edition for a Type 1 SPD application. Matrix of individually fused Metal Oxide Varistors (MOVs) housed in replaceable modules. Cover lights indicate status of modules. ka Per Phase Voltage Configuration /85 10kA 10V 1-Phase, -Wire + Ground /85 10kA 0V 1-Phase, -Wire + Ground /85 10kA 10/40V 1-Phase, -Wire + Ground M*/MN* 40kA 10/40V 1-Phase, -Wire + Ground /80/85 10kA 10/08V -Phase Wye, 4-Wire + Ground M*/MN* 40kA 10/08V -Phase Wye, 4-Wire + Ground /80/85 10kA 0/400V -Phase Wye, 4-Wire + Ground /80/85 10kA 77/480V -Phase Wye, 4-Wire + Ground M*/MN* 40kA 77/480V -Phase Wye, 4-Wire + Ground L 40kA 77/480V -Phase, 4-Wire + Ground kA 0-40V -Phase, -Wire Ungrounded Delta kA 40V -Phase Delta, -Wire + Corner Grounded /85 10kA 10/40V -Phase High-Leg Delta, 4-Wire + Ground kA 440/480V -Phase, -Wire Ungrounded *M = L-N only *MN = L-N, N-G only Warranty 5-years Available options Surge counter Add suffix -S Stainless Steel NEMA 4X Add suffix -4X enclosure Dry Relay Contacts available on select models. Stand alone option Remote Monitor (available on select models) Technical specifications Electrical Discharge Current Rating (I-n) Operating Frequency Connection Methods 0kA 50 60Hz Parallel to Load (shunt) Lugs #14 # Directly connect or through 60A (min) breaker Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED status indicator lights (one per phase) Mechanical Weight Model dependent Enclosure Type Model dependent Installation Location Indoor/Outdoor Operating Environment -40 to +185 F (-40 to +85 C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs Over Fusing Regulatory UL th Edition Type Type 1 UL 18 No IEEE C6.41.1,., C6.45 Yes Listed By ETL Description Listed to UL th Edition for a Type SPD application. Protects facilities and equipment against the harmful effects of lightning strikes and internally generated electrical transients. Includes pre-wired pigtail conductors to streamline installation. Features internal copper bus conduction path to minimize system impedances, lowering clamping and increasing protection. Voltage Configuration XNxx-10/40-G 10/40V 1-Phase, -Wire + Ground XNxx-10/08-GY 10/08V -Phase Wye, 4-Wire + Ground XNxx-0/80-GY 0/80V -Phase Wye, 4-Wire + Ground XNxx-10/40-GHD 10/40V -Phase High-Leg Delta, 4-Wire + Ground XNxx-77/480-GY 77/480V -Phase Wye, 4-Wire + Ground XNxxx-40-DG 40V -Phase, -Wire + Ground XNxxx-80-DG 80V -Phase, -Wire + Ground XNxxx-480-DG 480V -Phase, -Wire + Ground Where XX = 5, 50, 80, 100kA Per Mode Warranty 5-years Available options Dry Form C Relay Contacts Stand alone option Option A XN Metallic Conduit Kit Option B XN Plastic Conduit Kit Add suffix -FC (to be ordered as a separate Item) (available on select models) Metallic conduit installation kit has a /4" (.019 m) x " (.076 m) metallic nipple and all associated hardware required to complete the TransEnd installation Flexible plastic conduit installation kit, including 18" (.457 m) flexible conduit and all associated hardware required to complete the TransEnd installation Technical specifications Electrical Discharge Current Rating (I-n) Operating Frequency Connection Methods 0kA 47 6Hz Parallel to Load (shunt) 4" #10 AWG wires Through 0A (max) breaker Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED status indicator lights Mechanical Weight 1.7 lbs. (5.8 kg) Enclosure Type NEMA 4X fiberglass-reinforced polyester (FRP) surface-mount, non-removable cover Installation Location Indoor/Outdoor Operating Environment -40 to +140 F (-40 to +60 C) Altitude Up to 16,400 ft. (5000 m) Product Design No internal fusing Regulatory UL th Edition Type Type UL 18 Yes IEEE C6.41.1,., C6.45 Yes Listed By UL Made in U.S.A. D H W W1 H1 Approximate dimensions Dim /85, M/MN, , , /85, /80/85, /85, M/MN, / /80/85, L, M/MN, /80/85 H (.9) (74.7) (7.1) H 1.50 (4.9) (9.7) (9.1) W (76.9) 1.90 (7.7) (6.1) W (0.) (54.0) (15.4) D 05.0 (1.1) 06.0 (157.5) 04.0 (106.7) All measurements in inches (mm) Made in U.S.A. Approximate dimensions Dim TransEnd H (156.7) H 6.75 (171.5) H 7.50 (190.4) W (101.9) W 6.1 (155.4) D 5.01 (17.5) All measurements in inches (mm) /4 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /5

24 PMS 19 Old Glory Red PMS 81 Old Glory Blue Surgitron III -1 series Medium duty for residential or industrial applications Surgitron III -49 series Medium duty for residential or industrial applications Description Listed to UL th Edition for a Type 1 or Type SPD application. Individual fusing for each Metal Oxide Varistors (MOVs). LED indicates proper functioning of L-N and N-G MOVs. Description Listed to UL th Edition for a Type 1 or Type SPD application. Individual fusing for each Metal Oxide Varistors (MOVs). LED indicates proper function of individual MOVs. Type 1 ka Per Phase Voltage Configuration kA 10V 1-Phase, -Wire +Ground kA 10/40V -Phase, -Wire + Ground G 40kA 10/40V -Phase, -Wire + Ground kA 10/08V -Phase, 4-Wire + Ground A 40kA 10/08V -Phase, 4-Wire + Ground D 40kA 0/40V -Phase Delta, -Wire + Ground Type ka Per Phase Voltage Configuration xx 40kA 0V 1-Phase, -Wire + Ground kA 77V 1-Phase, -Wire + Ground kA 480V 1-Phase, -Wire kA 10/40V -Phase High-Leg Delta, 4-Wire + Ground kA 77/480V -Phase, 4-Wire + Ground D 40kA 480V -Phase, -Wire + Ground kA 0/400V -Phase, 4-Wire + Ground xx = -TNG, -TMS, -TT, -IT, -IT-L Bracket comes standard with all models Warranty -years Approximate dimensions.9" (75mm) Technical specifications Electrical Discharge Current Rating (I-n) 0kA Operating Frequency 47 6Hz Connection Methods Parallel to Load (shunt) #14 AWG wires Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED status indicator lights Mechanical Weight lbs. (.9 kg) Enclosure Type NEMA 1, Non-metallic Installation Location Indoor 1/ 14 NPT Thread Operating Environment -40 to +176 F (-40 to +80 C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs Regulatory UL th Edition Type Model #14 dependent AWG (mm ) STRANDED WIRE UL 18 No 600V PVC INSULATION IEEE C6.41.1,., C6.45 Yes UL 18" (450mm) LONG ALUMINUM BRACKET Listed By.56" (90mm) Bracket detail.9" (75mm) Type 1 ka Per Phase Voltage Configuration kA 10V 1-Phase, -Wire + Ground C 40kA 10V 1-Phase, -Wire + Ground C 40kA 40V 1-Phase, -Wire + Ground kA 10/40V -Phase, -Wire + Ground C 40kA 10/40V -Phase, -Wire + Ground kA 40V -Phase Delta, 4-Wire + Ground kA 10/08V -Phase Delta, 4-Wire + Ground Type ka Per Phase Voltage Configuration kA 40V 1-Phase, -Wire + Ground kA 480V -Phase Delta, -Wire + Ground kA 10/40V -Phase High-Leg Delta, 4-Wire + Ground kA 77/480V -Phase, 4-Wire + Ground kA 0-400V -Phase, 4-Wire + Ground -CF Model (Contains UL 18 listed filter) ka Per Phase Voltage Configuration CF* 80kA 10/40V -Phase, Wire + Ground *Dry Relay Contacts not available. Warranty -years Options 1 Set of Dry Relay Contacts (All Models) 1 Set of Dry Relay Contacts + Mounting Bracket xx-rb Option only Available on 161 and 1457 models (to be ordered as a separate Item) Add suffix -R Add suffix -RB Technical specifications Electrical Discharge Current Rating (I-n) 0kA Operating Frequency 47 6Hz Connection Methods Parallel to Load (shunt) #14 AWG wires Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED status indicator lights Mechanical Weight lbs. (.9 kg) Enclosure Type NEMA 1, Non-metallic Installation Location Indoor Operating Environment -40 to +176 F (-40 to +80 C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs Regulatory UL th Edition Type Model dependent UL 18 No (Except for CF model) IEEE C6.41.1,., C6.45 Yes Listed By UL 1/ 14 NPT Thread ø.1" (5.5mm) HOLES 1.7" (5mm) Approximate dimensions.9" (75mm).56" (90mm) ø.1" (5.5mm) HOLES 1.6" (mm) 1.7" (5mm).9" (75mm).75" (19mm) #14 AWG (mm ) STRANDED WIRE 600V PVC INSULATION 18" (450mm) LONG ALUMINUM BRACKET 1.6" (mm).5" (64mm) BRACKET DETAIL.75" (19mm) LED.90" (7mm) 1.60" (41mm) 5.6" (14 mm).0" (58mm) REMOTE MONITORING TERMINALS, -R or -RB only.75" (19mm).16 DIA. BLIND HOLES,.40 DEEP FOR #8 SELF-TAPPING SCREWS () 0.5" (6mm) #14 AWG (mm ) STRANDED WIRE 600V PVC INSULATION 18" (450mm) LONG Alarm Relay Contacts (-R and -RB Models) Shown with Power On 1 1 RE M OT E AL AR M -RB MODEL ONLY 8.5" (10mm) 1.94" (49mm) M4 THREADED HOLE 4 PLCS " (195mm) CF model SAme DImensions as -R With no Dry Relay Contacts Made in U.S.A..5" (64mm).00" (51mm) BRACKET DETAIL 1/ 14 NPT Thread.47" (1mm) 1.000" (5mm).8" (7mm) Mounting Bracket /6 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /7

25 PMS 19 Old Glory Red PMS 81 Old Glory Blue PMS 19 Old Glory Red PMS 81 Old Glory Blue Surgitron III - series Medium duty for residential or industrial applications LDP Light duty for AC applications Description Listed to UL th Edition for Type SPD application. Multiple Metal Oxide Varistors (MOVs) with individual and over protection. LED indicates proper function of individual MOVs. ka Per Phase Voltage Configuration Description Listed by ETL to UL th Edition for a Type 1 SPD application. Multiple Metal Oxide Varistors (MOVs), with individual fusing and thermal disconnects for each MOV. LED indicates proper functioning of L-N MOVs. Intended for use on U.S., TN-C, TN-C-S and TNS grounded systems F1 80kA 10/40V 1-Phase, -Wire F1 60kA 10/40V 1-Phase, -Wire F1 40kA 10/40V 1-Phase, -Wire Warranty -years Stand alone option Flush-Mount Plate Kit Approximate dimensions D1 D D W (to be ordered as a separate Item) -FMP-KIT 1/ 14 NPT Thread Schematic shown in horizontal position. (Photo shown in vertical position) Approximate dimensions Dim TransEnd H1.75 (19.1) H.5 (6.4) H.9 (74.4) W.56 (90.4) D1. (8.1) D.78 (70.6) D.10 (78.7) All measurements in inches (mm) H H H1 Technical specifications Electrical Discharge Current Rating (I-n) Model dependent Operating Frequency 50 60Hz Connection Methods #14 AWG wires 0A Max Breaker Response Time Less than 1 nanosecond (one per phase) Standard Monitoring LED status indicator lights Mechanical Weight lbs. (.9 kg) Enclosure Type NEMA 1, Non-metallic Installation Location Indoor Operating Environment -40 to +185 F (-40 to +85 C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs Regulatory UL th Edition Type Type UL 18 No IEEE C6.41.1,., C6.45 Yes Listed By UL scheme ka Voltage Rating." (56 mm) LDP XX YYY Z L1-N, N-G (1 LED) 5 17 L1-N, L-N ( LEDs) 0 0 L1-G, L-G ( LEDs) 77 4 L1-G, N-G (1 LED) 5 L1-N, L1-G ( LEDs) 6 L1-N (1 LED) 7 L1-G (1 LED) 8 N-G (0 LEDs) 9 L1-L (1 LED) Example: LDP kA device suitable for 10V systems, designed to protect L1-N and N-G mode A dedicated breaker should be 0A at main panel or 10A at subpanel.." (56 mm) Modes Protected Warranty -years Available options Mounting Bracket Add suffix -B Approximate dimensions.7" (69 mm).1" (54 mm) #14 AWG (mm ) STRANDED WIRE 600V PVC INSULATION 1/ 14 NPS THD. Technical specifications Electrical Discharge Current Rating (I-n) 10kA Operating Frequency 47 6Hz Connection Methods Parallel to Load (shunt) 18" #14 AWG wires Direct connect or Breaker Response Time Less than 1 nanosecond Standard Monitoring LED status indicator lights (one per phase) Mechanical Weight 1 lb. (.5kg) Enclosure Type NEMA 1, Non-metallic Installation Location Indoor Operating Environment -40 to +176 F (-40 to +80 C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs Over Fusing Thermal Fusing Regulatory UL th Edition Type Type 1 UL 18 No IEEE C6.41.1,., C6.45 Yes Listed By ETL LOCKNUT Made in U.S.A. Made in U.S.A. /8 Surge protective devices (SPDs) US Catalog US Catalog Surge protective devices (SPDs) /9

26 1000 Series Light Duty for DC Applications Marketing tools Description Full weather permanently connected. Individually fused Metal Oxide Varistors (MOVs). May be used on grounded (+ or -) or floating power systems, for DC or low AC (up to 400Hz). LED indicates proper functioning of L-L and L-G MOVs. OVR Practical guide for the protection against surges Lightning and over protection for lighting systems Autoprotected surge arresters New OVR PLUS range 4 ka Per Phase Voltage Configuration kA 0Vdc 5Vac kA 60Vdc 45Vac kA 90Vdc 65Vac * 50kA 150Vdc 110Vac 1TXH00009C001_OVR practical guide.indd 1 1/0/014 1:0:08 Brochure OVR Practical guide for the protection against surges with QuickSafe technology 1TXH000416C001 1TXH B00 - Autoprotected Surge Arresters.indd 7 0/01/01 10:40:08 1TXH0001B00_Lightning and over protection.indd 1 1/10/014 15:5:6 Brochure Lightning and over protection for lighting systems 1TXH0001B00 Brochure Autoprotected surge arresters New OVR PLUS range 1TXH000045B00 * is not intended for use on 110/10 Vac power system. Mounting bracket standard on all units Warranty -years Approximate dimensions.91" (7.9 mm) Technical specifications ø.18" Hole, Pl..80" (96.5 mm).10" (78.7 mm) 1.7" 1.5".75".5".50".54" (89.9 mm) #14 AWG ( mm ) STRANDED WIRE 600V PVC INSULATION 18" (450 mm) LONG 1/ 14 NPS THD. LOCKNUT ALUMINUM BRACKET Schematic shown in vertical position. (Photo shown in horizontal position) Electrical Discharge Current Rating (I-n) None Operating Frequency AC/DC Hz Connection Methods Mounts through 1/" knockout or by its bracket Connects in parallel with load Modes of Protection L-L, L-G Response Time Less than 1 nanosecond Standard Monitoring LED status indicator lights Mechanical Weight 1.5 lbs. (.7kg) Enclosure Type NEMA 1 Installation Location Indoor Operating Environment -40 to +176 F (-40 to +80 C) Altitude Up to 16,400 ft. (5000 m) Product Design Individually fused MOVs Over Fusing Thermal Fusing Regulatory Requirements are discretionary and respective to the product application Earthing, lightning and over protection Wind turbines Brochure Solar energy Lightning and surge protective devices 1TXH00015B001_Wind turbines.indd 1 Main catalog OPR lightning protection systems External lightning protection 8/01/01 15::10 Brochure Earthing, lightning and over protection Wind turbines 1TXH00015B001 Brochure Solar energy Lightning and surge protective devices 1TXH000118B00 1TXH00047C00_OPR_lightning_protection_systems.indb 1 19/09/014 09:5:0 Main catalog OPR lightning protection systems External lightning protection 1TXH00047C00 New Surge Protective Devices QS technology Application note Surge protective devices OVR PV range. The toughest SPD PV range on the market. New EN for photovoltaic products Part 11: Requirements and tests for SPDs in photovoltaic applications. A new standard on a developing market A new document taking account of varied aspects of photovoltaic generators and technologies is available, designed EN , to define specific surge protection to photovoltaic installations. According to the very specific characteristics of PV generators and PV installations with high s and low DC, the EN introduces the idea of testing the behavior of photovoltaic surge protective devices on end of life for the safety of the equipments. UL 1449 rd edition The UL 1449 standard for SPDs has been the primary safety standard for surge protection since Prior to UL 1449 rd edition, the devices covered by the standard were known as Transient Voltage Surge Suppressors (TVSS), operating on circuits not exceeding 600 V. With the rd edition these devices are now known as SPDs and may operate on power circuits not exceeding 1500 V. Fine vita Sistema di riserva di sicurezza Surge arrester Maximum operating Short circuit (EN ) Over protection (UL 1449 rd edition) OVR PV Ucpv: 670 V Iscpv: 00 A OVR PV Ucpv: 1100 V Iscpv: 10 ka 9 These Surge Protective Devices are equipped with two varistors per pole. If one varistor is damaged, the SPD gives advanced warning that it is approaching the end of its life while the other varistor continues to protect the equipment, allowing to perform Preventive Maintenance. According to the new IEC :01 standard, the patented technology QuickSafe allows the product perfect performances even in extreme conditions (up to +80 C as rated temperature) and guarantees a quick disconnection in case of interruption of the neutral and short-circuit conditions in case of failure. A safer installation with QuickSafe technology. Indicatore di fine vita Normale PV characteristics The following information shall be given by the manufacturer: PV symbol on the product Ucpv maximum continuous operating In nominal Iimp or Imax depending on if it is a Type 1 or Type surge protection Up protection level at In Iscpv short circuit DC withstand. Only SPDs with the above declared characteristics and with their conformity declaration are suitable for photovoltaic installations. Using a surge protection not conform to such specific application on DC photovoltaic installations shall result in fire and equipment damages. 5 A safety reserve system for an extended protection. T1-Ts and Ts. Iscpv = 10 ka The highest value on the market OVR PV Ucpv: 1500 V Iscpv: 10 ka UL approved with SCCR 1000A. If continuity of service is preferred, an additional 10AgPV fuse is recommended. Back-up protection for applications with Iscpv up to 10 ka (for 1500 V DC and 1100 V DC), no back-up needed. OVR PV range from ABB has been specifically developed for photovoltaic applications. To avoid the disconnecting problem at the end of life of the product on specific high DC PV network and therefore offer a safe and efficient protection to photovoltaic installations, ask for a photovoltaic dedicated surge protective device! Normale Normal In riserva In reserve Fine vita End-of-life Nota Uno scaricatore di sovratensioni a fine vita non pregiudica la continuità del servizio se cablato in modo da dare priorità alla stessa; semplicemente, si scollega. Tuttavia l apparecchiatura a valle non è più protetta. 6 8 The front mechanical end of life indicator provides the information of the status of the SPD (changing color from green to red), when the device reaches the end of its life. This is available for all cartridges with MOV technology. There is the possibility to use the signaling contact "TS" to transmit this end of life information to a remote control system. In case of products with Safety Reserve system, the TS will change status as soon as one MOV is damaged, allowing to perform Preventive Maintenance activities. In the case where the SPD ends its life in short circuit condition, we therefore need a back-up protection (fuse or circuit breaker) in order to open the circuit. With the QS series, the rated of this back up protection has been increased up to: 15 A MCB (B or C) or 160 A (gg or gl) for T1-Ts and Ts series 15 A (B or C/gG or GL) for T and T-T series. Easier inspection of equipment with state indicator and signaling contact No dedicated back up protection needed for the SPD. 7 New ABB photovoltaic OVR surge protection ratings Complying with the new EN or UL 1449 rd edition, the new ratings of our OVR PV range have been defined for an easier selection and to fulfil requirements of photovoltaic specific networks. TS contact Compact design to save space in enclosure OVR QS series are DIN rail mounting and sizes are ideal to be installed in all reduced size plants. Starting with the single-pole versions for maximum flexibility, it will allow you to save space in your installation or choose a smaller enclosure and at the same time protecting the equipment against transient over. Made in U.S.A. 1TXH0001L00_OVR PV.indd 1 PMS 19 Old Glory Red PMS 81 Old Glory Blue /10 Surge protective devices (SPDs) US Catalog 14/11/014 07:44:59 Application note Surge protective devices - OVR PV range. The toughest SPD PV range on the market. 1TXH0001L00 Leaflet New Surge Protective Devices QS technology 1TXH00051E001 US Catalog Surge protective devices (SPDs) 4/1

Technical features OVR Surge Protective Devices Type 1 & Type 1+2

Technical features OVR Surge Protective Devices Type 1 & Type 1+2 Type 1 & Type 1+2 TECHNICAL FEATURES Technology Type 1 OVR T1 2 TS Triggered spark-gap Electrical features Standard IEC 61643-1 / EN 61643-11 Type / test class 1 / I Poles 1P - 1P -, 2P 2L 3P 3L 4P 4L

More information

Overvoltage Protection

Overvoltage Protection Overvoltage Protection OVR Range FRSOX 0100 03 GB ABB Lightning Protection Group 1 Main causes of transient overvoltages The solution: ABB OVR Surge Protective Device Range Lightning strike A lightning

More information

2 Principle of lightning protection

2 Principle of lightning protection 2 Principle of lightning protection The system for protecting a building against the effects of lightning must include: bprotection of structures against direct lightning strokes; bprotection of electrical

More information

CPS block & CPS nano UL rd Ed. Surge protective devices (SPD)

CPS block & CPS nano UL rd Ed. Surge protective devices (SPD) V4 Cirprotec CPS block & CPS nano UL 1449 3rd Ed. Surge protective devices (SPD) Transient voltage surge suppressors (TVSS) Cirprotec, more than just protection Cirprotec, specialists in lightning and

More information

Surge Protective Devices OVR Series - Enclosed SPD Mining and Aggregates

Surge Protective Devices OVR Series - Enclosed SPD Mining and Aggregates Application note Surge Protective Devices OVR Series - Enclosed SPD Mining and Aggregates ABB OVR Series Electrical surges can be a real downer. Sherwood Construction's stone quarry in Tulsa, Oklahoma,

More information

CONTA-ELECTRONICS. CONTA-PROTECT overvoltage protection

CONTA-ELECTRONICS. CONTA-PROTECT overvoltage protection CONTA-ELECTRONICS CONTA-PROTECT overvoltage protection When choosing the correct device for overvoltage protection, it is important to consider the regulations VDE 110-1, IEC 61643-1, EN 61643-11 and VDE

More information

Surge Protection Devices Type 1+2

Surge Protection Devices Type 1+2 Surge Protection Devices Type 1+2 Description The combined surge protection devices offer as an all-in-one solution lightning and surge-voltage in one device. They are in accordance with the requirement

More information

glossary GE Digital Energy Power Quality Surge Protective Devices (SPDs)

glossary GE Digital Energy Power Quality Surge Protective Devices (SPDs) GE Digital Energy Power Quality Surge Protective Devices (SPDs) glossary Active Tracking A term used to describe the ability of a filter to reduce frequency disturbances at a constant level with respect

More information

ENGR. MARITES R. PANGILINAN, P.E.E.

ENGR. MARITES R. PANGILINAN, P.E.E. ENGR. MARITES R. PANGILINAN, P.E.E. WHAT IS LOW VOLTAGE INSULATION COORDINATION AND WHY IT IS IMPORTANT WHERE DO SURGES COME FROM HOW DO SPDs WORK/TYPE OF SPDs SPD SPECIFICATIONS SPD COORDINATION /CASCADING

More information

Surge Protection Devices Ex9UE2

Surge Protection Devices Ex9UE2 Surge Protection Devices Ex9UE2 Surge Protection Devices Type 2 (Class II, T2, C) Tested according to EN 61643-11 Maximum continuous operational voltage U c from 275 V up to 440 V AC Versions with 1+0,

More information

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC. [Refer to Engineering Notes at End of Spec] Section [16XXX] [264XXX] - SURGE PROTECTIVE DEVICES (SPDs) PART 1 - GENERAL 1.1 SCOPE A. This section includes Surge Protective Devices (SPDs) for low-voltage

More information

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC. [Refer to Engineering Notes at End of Spec] Section [16XXX] [264XXX] - SURGE PROTECTIVE DEVICES (SPDs) PART 1 - GENERAL 1.1 SCOPE A. This section includes Surge Protective Devices (SPDs) for low-voltage

More information

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications TCMOV Varistors for Type 1 and Type What is UL 1449? Underwriters Laboratories standard UL 1449 has become the primary safety standard for surge protective devices (SPDs). It describes the materials and

More information

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Part 1 General 1.01 Summary A. These specifications describe

More information

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany Lightning and Surge Protection of Photovoltaic Installations 1 Lightning and Surge Protection for PV Installations 2 Safeguard from Risks Ups, that was the insurance policy of my house!! 3 Why Lightning

More information

wietap wietap Overvoltage Protection Tensions running high

wietap wietap Overvoltage Protection Tensions running high wietap wietap Overvoltage Protection Tensions running high 2 wietap wietap Overvoltage protection Important information on overvoltage The necessity of overvoltage protection on machines and systems as

More information

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing MULTI-POLE Lightning Current and Surge Arresters for PHOTOVOLTAIC SYSTEMS Class I / (B+C) and Class II / (C) COMPACT and MODULAR Housing 44 PV ISPRO BS(R) 12,5 The PV ISPRO BS(R) 12,5 series of over voltage

More information

Surge Protection Devices OVR series

Surge Protection Devices OVR series PRODUCT CATALOGUE CANADA Surge Protection Devices OVR series UL / CSA range of SPDs Type 1 and Type 2 for main electrical distribution equipment and control panel applications Hardwired and DIN rail versions

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA SURGE PROTECTION DESIGN. Parallel Versus Series Protection. Surge protectors within the scope of this UFC should normally be of the parallel

More information

TDX Series. Transient Discriminating TM TVSS

TDX Series. Transient Discriminating TM TVSS TDX Series Transient Discriminating TM TVSS TDX Series TDX150 is ideal for service entrance protection. Best Value Engineered Protection With emphasis on efficiency and value, ERICO developed the TDX Series.

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 2010 Overvoltage Protection Devices /2 Introduction /3 Lightning Arresters, Type 1 /5 Combination Surge Arresters, Type 1 and Type 2 /7 Surge Arresters, Type 2 /11 Surge Arresters, Type 3 /12

More information

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual Surge Protective Devices STV100K Series Instruction Manual Contents 1.0 Installation... 4 1.1 Environment... 4 1.2 Mounting... 4 1.3 Proper Connection of SPDs... 4 1.4 Mechanical Dimensions... 5 1.5 Voltage

More information

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment NTSA has developed the ultimate solution for protecting

More information

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual Surge Protective Devices STV100K Series Instruction Manual Contents 1.0 Installation... 4 1.1 Environment... 4 1.2 Mounting... 4 1.3 Proper Connection of SPDs... 4 1.4 Mechanical Dimensions... 5 1.5 Voltage

More information

INTRODUCTION TO SPECIFYING SURGE PROTECTION SURGE PROTECTION NOTE 1 INTRODUCTION TERMS PROBABILITY OF SURGES APPEARING:

INTRODUCTION TO SPECIFYING SURGE PROTECTION SURGE PROTECTION NOTE 1 INTRODUCTION TERMS PROBABILITY OF SURGES APPEARING: INTRODUCTION TO SPECIFYING SURGE PROTECTION SURGE PROTECTION NOTE 1 BY PETER WALSH, PE INDUSTRIAL SOLUTIONS ENGINEER INTRODUCTION Surge Protective Devices (SPDs) can protect electrical equipment from harmful

More information

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

DIVISION 16 SECTION Surge Protective Device Submittal (SPD) DIVISION 16 SECTION 16289 Surge Protective Device Submittal (SPD) PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Surge & Filter Protection Addressing your industrial power quality needs.

Surge & Filter Protection Addressing your industrial power quality needs. Surge & Filter Protection Addressing your industrial power quality needs. BULLETIN 983 INTRODUCING SURGE & FILTER PROTECTION SURGE & FILTER PROTECTION Rockwell Automation is pleased to introduce the Bulletin

More information

File E Project 05NK Issued: Revised: REPORT CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD)

File E Project 05NK Issued: Revised: REPORT CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD) File E248748 Project 05NK27956 Issued: 2007-11-01 Revised: 2009-12-04 REPORT on SURGE PROTECTIVE DEVICES/PANELBOARD EXTENSION MODULES, CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD) GE ZENITH CONTROLS

More information

Equipment protection

Equipment protection Equipment protection Serie K Risk of electrical surges Equipment protection 5.000.000 ightning strikes per day 61% Electrical damages caused by surges 30k verage current of a lightning strike ightning

More information

GE Digital Energy. Power Quality

GE Digital Energy. Power Quality GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Wall Mounted Medium and High Exposure Surge Protective Devices (SPDs)

More information

Surge Protection Devices and Surge Protection Kit

Surge Protection Devices and Surge Protection Kit Surge and Surge Kit SPD s protect electrical and electronic equipment against transients, originating from lightning, switching of transformers, lighting and motors 3. Main protection - class 3 To cut-down

More information

LPI SG + SST Spark Gap Surge Filter

LPI SG + SST Spark Gap Surge Filter LPI SG + SST Spark Gap Surge Filter Features High performance surge protector for an operating voltage of 220-240Vac Encapsulated spark gap and SST capable of sustaining fault and over-voltage conditions

More information

Technical Data Sheet Medium Current Power Surge Filters

Technical Data Sheet Medium Current Power Surge Filters Technologies Technical Data Sheet Medium Current Power Surge Filters Features High performance surge protector for an operating voltage of 0-220Vac Designed to withstand fault and over-voltage conditions

More information

LPI SG + SS480 Spark Gap Surge Filters

LPI SG + SS480 Spark Gap Surge Filters LPI SG + Spark Gap Surge Filters Features High performance surge protector for an operating voltage of 220-277Vac Encapsulated spark gap and technology capable of operation under fault /overvoltage conditions

More information

Surgelogic Surge Protective Device I-Line Plug-On Unit Series

Surgelogic Surge Protective Device I-Line Plug-On Unit Series Surgelogic Surge Protective Device I-Line Plug-On Unit Series Catalog 1310CT0201R5/07 2007 Class 1310 CONTENTS Description Page Product Description.................................................. 2 Application

More information

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS FOR SURGE PROTECTION DEVICES This Tech Note provides an overview of the key standards associated with surge suppressors and AC powerline filters.

More information

White Paper Surge Protective Devices in Automatic Transfer Switches

White Paper Surge Protective Devices in Automatic Transfer Switches White Paper Surge Protective Devices in Automatic Transfer Switches Standby power systems provide emergency power, legally required power, or optional standby AC power during utility outages. Standby AC

More information

Reliability in Surge Protection. Photovoltaic Systems.

Reliability in Surge Protection. Photovoltaic Systems. Reliability in Surge Protection Photovoltaic Systems www.citelcp.com Roof top installations For low power PV applications, i.e. residences and small offices, it is necessary to consider surge protecting

More information

Eaton s SPD Series for integration into electrical distribution equipment

Eaton s SPD Series for integration into electrical distribution equipment Technical Data TD01006E Supersedes August 2009 Eaton s SPD Series for integration into electrical distribution equipment Contents Description Page Introduction....2 Applications....2 Features....2 Standards

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

LPI SST Surge Filters

LPI SST Surge Filters LPI SST Surge Filters Features High performance surge protector for an operating voltage of 200-240Vac Designed to withstand fault and over-voltage conditions of up to 85Vac, as per IEC664 Impulse discharge

More information

Surge Protection for Surveillance Systems

Surge Protection for Surveillance Systems Surge Protection for Surveillance Systems 1-in-1 Protection for Network Cameras 2-in-1 Protection for Power and Audio/Video Signals 3-in-1 Protection for Power, Audio/Video and PTZ Control Signals Application:

More information

MDSP-Series 90kA, 150kA, 300kA Modular Distribution Surge Protector Type 2 Class II Surge Arrester

MDSP-Series 90kA, 150kA, 300kA Modular Distribution Surge Protector Type 2 Class II Surge Arrester These modular distribution panel protectors for three phase power systems are designed to prevent damage to electrical distribution systems from mainsborne transient voltages which can occur as the result

More information

File E Project 08NK November 24,2009 REPORT TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7)

File E Project 08NK November 24,2009 REPORT TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7) File E3456 Project 08NK10151 November 24,09 REPORT ON TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7) *********************************************************** Complementary Product Category ELECTROMAGNETIC

More information

Lightning and Surge Protection for PV Systems

Lightning and Surge Protection for PV Systems Lightning and Surge Protection for PV Systems Application Note (AU) Phillip Tompson Introduction Like all electrical equipment photovoltaic systems can be damaged by both direct and indirect lightning

More information

NEW surge protective devices

NEW surge protective devices NEW surge protective devices For use in low-voltage systems For overhead power lines and buildings Made in EU ABOUT COMPANY INTRODUCTION Company ELEKTROMEHANIKA & BB d.o.o. was established from recent

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES SUITABLE SOLUTIONS FOR ALL TYPES OF INSTALLATIONS AND ALL RISK LEVELS 1 CONTENT: Introduction Theory and principles Installation rules Legrand offer 2 2 INTRODUCTION Lightning

More information

The following standards are the basis of design, manufacture, and test of SPD equipment: Guide for Surge Voltages in Low-Voltage AC Power Circuits

The following standards are the basis of design, manufacture, and test of SPD equipment: Guide for Surge Voltages in Low-Voltage AC Power Circuits ENGINEERING BULLETIN Manufacturing & Test Standards for SPDs APT SPD/TVSS are manufactured and tested in accordance with applicable industry standards. UL Marks are found on APT equipment. These are the

More information

Low voltage. Acti 9. the efficiency you deserve. Catalogue 03/2016

Low voltage. Acti 9. the efficiency you deserve. Catalogue 03/2016 Low voltage Acti 9 the efficiency you deserve Catalogue 03/2016 schneider-electric.com 1 and 2 LV surge s 1 and 2 LV surge s (cont.) The 1 range of surge s meets the normative withstand capability of wave

More information

BSPD Surge Protective Devices

BSPD Surge Protective Devices BUSSMANN Supersedes December 2016 SERIES BSPD Surge Protective Devices High capacity Type 1 and Type 2 SPDs for overvoltage protection on Contents Description Page Introduction 2 Applications 2 Features

More information

CC COMPACT DIP SWITCH

CC COMPACT DIP SWITCH CC COMPACT DIP SWITCH COMFORTLINE DIP SWITCH C-R5 186841, 186842, 186843 Typical Applications Built-in in compact luminaires for Shop lighting Downlights Panels ComfortLine DIP switch C-R5 SELECTABLE OUTPUT

More information

Type of surge arrester

Type of surge arrester ipf surge arresters Type 2 or 3 LV surge arresters The ipf multi-pole single-piece surge arrester range is adapted for earthing systems: TT, TN-S,. Type 2 surge arresters are tested with a 8/20 µs current

More information

Surge Protection for Low Voltage Power Systems

Surge Protection for Low Voltage Power Systems Surge Protection for Low Voltage Power Systems 2017 CATALOG Table of Contents About Raycap 3 Introduction 5 Regulatory Standards 6 Surge Protective Device Components & Terminology 8 Low Voltage Power Distribution

More information

3 Design of the electrical installation protection system

3 Design of the electrical installation protection system J - Protection against voltage surges in LV 3 Design of the electrical To protect an electrical installation in a building, simple rules apply for the choice of b (s); b its protection system. 3.1 Design

More information

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.: Extract from the online catalog QUINT-PS/1AC/24DC/10 Order No.: 2866763 DIN rail power supply unit 24 V DC/10 A, primary-switched mode, 1- phase. The SFB technology (Selective Fusebreaking Technology)

More information

GUIDE TO VERIFYING SURGE PROTECTIVE DEVICES INSTALLED IN LIGHTNING PROTECTION SYSTEM INSTALLATIONS ARE COMPLIANT WITH UL 96A.

GUIDE TO VERIFYING SURGE PROTECTIVE DEVICES INSTALLED IN LIGHTNING PROTECTION SYSTEM INSTALLATIONS ARE COMPLIANT WITH UL 96A. JULY 29, 2014 GUIDE TO VERIFYING SURGE PROTECTIVE DEVICES INSTALLED IN LIGHTNING PROTECTION SYSTEM INSTALLATIONS ARE COMPLIANT WITH UL 96A. HOW TO VERIFY SURGE PROTECTIVE DEVICES SUITABLE FOR USE ON ELECTRIC

More information

COMPACT LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , , , , , ,

COMPACT LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , , , , , , COMPACT LED DRIVERS EasyLine SIMPLE FIX 186719, 186720, 186721, 186722, 186723, 186724, 186725, 186726, 186727, 186728 Typical Applications Built-in in compact luminaires Shop lighting Downlights EasyLine

More information

Modular surge protective devices

Modular surge protective devices S D 870 LIMOGES Cedex Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88 Modular surge protective devices Cat. o(s): 039 10-030 00/0//3/7 age /L 1. General characteristics... 1. Overall dimensions....1-3.

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1.1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Section 4 Ground-Fault Protection Devices

Section 4 Ground-Fault Protection Devices Multi 9 System Catalog Section 4Ground-Fault Protection Devices Section 4Ground-Fault Protection Devices Selection Table The Multi 9 System includes one UL Listed and three IEC rated product families that

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects of transient over voltages caused by

More information

Surge Protective Devices. STV25K Series. Instruction Manual

Surge Protective Devices. STV25K Series. Instruction Manual Surge Protective Devices STV25K Series Instruction Manual Contents 1.0 Installation & Operation... 4 1.1 Environment... 4 1.2 Mechanical Dimensions... 4 1.3 DIN Rail Mounting... 5 1.4 Supplemental Enclosures...

More information

Extract from the online catalog SFP 1-5/120AC Commercial data Product description Technical data Standards

Extract from the online catalog SFP 1-5/120AC Commercial data Product description Technical data Standards Extract from the online catalog SFP 1-5/120AC Order No.: 2920667 Device surge protection filter to limit powerful surge voltages, mounting on NS 35. Commercial data EAN 4046356158558 Pack 1 pcs. Customs

More information

COMPACT LED CONVERTERS 48 V

COMPACT LED CONVERTERS 48 V COMPACT LED CONVERTERS 48 V EasyLine 48 V 186691, 186692 Typical Applications Shop lighting for 48 V systems Furniture lighting EasyLine 48 V VERY COMPACT SHAPE VERY LOW RIPPLE CURRENT LONG SERVICE LIFETIME:

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs)

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs) ga GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs) 2020005003 (12/09) Page 1 of 18

More information

PRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION

PRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION INTERNAL PROTECTION systems PRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION INDUSTRIAL INSTALLATIONS 2 1 2 5 5 7 2 2 2 2 4 6 6 7 3 OBJECT: Industrial premises, Industrial complexes, Hospitals, Public buildings

More information

Lightning and Surge Arresters

Lightning and Surge Arresters Lightning and Surge Arresters 5/4 Product overview 5/5 Lightning arresters, requirement category I (B) 5/6 Combined arresters, requirement category I (B) and II (C) 5/7 Single-pole surge arrester, requirement

More information

Tel: Web: Lightning and surge protection help pages

Tel: Web:    Lightning and surge protection help pages Lightning and surge protection help pages Effects of lightning on your home or office Modern Technology has progressed to the point where detecting and preventing surges, has become an exact science -

More information

TDS Transient Discriminating Surge Diverters

TDS Transient Discriminating Surge Diverters TDS Transient Discriminating Surge Diverters Surge Protection And Surge Ratings The stress, which an SPD will experience under surge conditions, is a function of many complex and interrelated parameters.

More information

QUINT-PS/ 1AC/24DC/ 5

QUINT-PS/ 1AC/24DC/ 5 Extract from the online catalog QUINT-PS/ 1AC/24DC/ 5 Order No.: 2866750 DIN rail power supply unit 24 V DC/5 A, primary switched-mode, 1- phase. The SFB technology (Selective Fuse Breaking Technology)

More information

In the simplest terms, surge protective devices (SPDs) prevent damaging transient voltage surge levels from reaching the devices they protect.

In the simplest terms, surge protective devices (SPDs) prevent damaging transient voltage surge levels from reaching the devices they protect. How SPDs Work In the simplest terms, surge protective devices (SPDs) prevent damaging transient voltage surge levels from reaching the devices they protect. A useful analogy makes this clearer. Consider

More information

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units. Model KEP Automatic Transfer Switches Service Entrance Rated Controller D Decision-Makerr MPAC 1500 Ratings Power Switching Device Current Voltage, Frequency Molded case (MCCB) Insulated Case (ICCB) 200

More information

Page 14-4 Page Page 14-4 SURGE PROTECTION DEVICES TYPE 2 VERSIONS WITH PLUG-IN CARTRIDGE 1P, 1P+N, 2P, 3P, 3P+N, 4P

Page 14-4 Page Page 14-4 SURGE PROTECTION DEVICES TYPE 2 VERSIONS WITH PLUG-IN CARTRIDGE 1P, 1P+N, 2P, 3P, 3P+N, 4P Page -4 Page -4 SURGE PROTECTIO DEVICES TY 1 AD 2 MOOBOCK VERSIOS 1P, 1P+, 2P, 3P, 3P+, 4P IEC impulse current Iimp (10/350μs): 25kA IEC maximum discharge current Imax (8/20μs): 100kA SPD status indicator

More information

SPD Catalogue. SPD Catalogue. for AC applications

SPD Catalogue. SPD Catalogue. for AC applications SPD Catalogue SPD Catalogue for AC applications Eaton and Cooper united. Energizing a world that demands more. We deliver: Electrical solutions that use less energy, improve power reliability and make

More information

ETITEC - Lightning and Surge Arresters

ETITEC - Lightning and Surge Arresters ETITEC Lightning and Surge Arresters Overvoltage protection selection ETITEC selection Define system data: U max Uc > 1,2 x U max External lightning protection exist? NO Apply ETITEC C on string and on

More information

SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014

SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014 SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014 1.0 SCOPE This secondary Type 1 surge protective device specification covers

More information

COMPACT LED DRIVERS. PrimeLine DALI dimmable & Selectable Current (Dip Switch) PrimeLine DALI DIMMABLE & SELECTABLE CURRENT (DIP SWITCH)

COMPACT LED DRIVERS. PrimeLine DALI dimmable & Selectable Current (Dip Switch) PrimeLine DALI DIMMABLE & SELECTABLE CURRENT (DIP SWITCH) COMPACT LED DRIVERS PrimeLine DALI DIMMABLE & SELECTABLE CURRENT (DIP SWITCH) 186762, 186763 Typical Applications Built-in in compact luminaires Shop lighting Downlights PrimeLine DALI dimmable & Selectable

More information

LINEAR LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , ,

LINEAR LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , , LINEAR LED DRIVERS EasyLine SIMPLE FIX 186712, 186713, 186714, 186715, 186716, 186760 Typical Applications Built-in in linear luminaires for Office lighting Weatherproof Luminaires EasyLine Simple Fix

More information

LINEAR LED DRIVERS. ComfortLine Industry Selectable Current (LEDset) ComfortLine INDUSTRY SELECTABLE CURRENT (LEDset) ,

LINEAR LED DRIVERS. ComfortLine Industry Selectable Current (LEDset) ComfortLine INDUSTRY SELECTABLE CURRENT (LEDset) , LINEAR LED DRIVERS ComfortLine INDUSTRY SELECTABLE CURRENT (LEDset) 186695, 186696 Typical Applications Built-in in linear luminaires for Industrial lighting ComfortLine with selectable current HIGH POWER

More information

Reliability in Surge Protection. Surge Protection. AC & DC Power Photovoltaic Coaxial Telecom Gas Discharge Tubes.

Reliability in Surge Protection. Surge Protection. AC & DC Power Photovoltaic Coaxial Telecom Gas Discharge Tubes. Reliability in Surge Protection Surge Protection AC & DC Power Photovoltaic Coaxial Telecom Gas Discharge Tubes www.citel.us CITEL Established in 1937, CITEL is the global leader in the development and

More information

CONNECT AND PROTECT. nvent ERICO Critec SRF N-Series. Surge Reduction Filters

CONNECT AND PROTECT. nvent ERICO Critec SRF N-Series. Surge Reduction Filters CONNECT AND PROTECT nvent ERICO Critec SRF N-Series Surge Reduction Filters TABLE OF CONTENTS PROVEN FOR CRITICAL APPLICATIONS... 3 SRF N-SERIES COMBINED TECHNOLOGY PROTECTION... 4 SPARK GAP TECHNOLOGY...

More information

VAL-CP-1S-175. Extract from the online catalog. Order No.:

VAL-CP-1S-175. Extract from the online catalog. Order No.: Extract from the online catalog VAL-CP-1S-175 Order No.: 2859479 Pluggable type 2 arrester (surge arrester) for 1-phase current supply networks with separate N and PE (3-conductor system: L1, N, PE), with

More information

Always "On" UPS Systems Inc. USER MANUAL

Always On UPS Systems Inc. USER MANUAL Always "On" UPS Systems Inc. SMART HOME PROTECTOR USER MANUAL Bldg 1-150 Campion Road, Kelowna, BC, Canada, V1X 7S8 Phone: (250) 491-9777 Ext. 451, Fax: (250) 491-9775, Email: sales@alwaysonups.com Web

More information

Chapter J. Protection against voltage surges in LV. Contents. General. Overvoltage protection devices. Choosing a protection device

Chapter J. Protection against voltage surges in LV. Contents. General. Overvoltage protection devices. Choosing a protection device Chapter J Protection against voltage surges in LV 1 2 3 4 Contents General J2 1.1 What is a voltage surge? J2 1.2 The four voltage surge types J2 1.3 Main characteristics of voltage surges J4 1.4 Different

More information

White Paper. AC Surge Protection. Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems

White Paper. AC Surge Protection. Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems White Paper AC Surge Protection Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems Richard Odenberg, Research & Advanced Applications, Founder of Transtector

More information

Maximize Your Uptime: Reducing Risk of Power Supply Failure

Maximize Your Uptime: Reducing Risk of Power Supply Failure Maximize Your Uptime: Reducing Risk of Power Supply Failure White Paper presented by: Phoenix Contact P.O. Box 4100 Harrisburg, PA 17111-0100 Phone: 717-944-1300 Fax: 717-944-1625 Website: www.phoenixcontact.com

More information

COMPACT LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , ,

COMPACT LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , , COMPACT LED DRIVERS EasyLine SIMPLE FIX 186591, 186592, 186593, 186594, 186595, 186669 Typical Applications Built-in in or independent version for Shop lighting Downlights EasyLine with fixed output current

More information

SECTION TRANSIENT VOLTAGE SURGE SUPPRESSION

SECTION TRANSIENT VOLTAGE SURGE SUPPRESSION SECTION 16709 TRANSIENT VOLTAGE SURGE SUPPRESSION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Transient Voltage Surge Suppression (TVSS) devices, also known as Surge Protective Devices (SPDs), for

More information

File E Project 08NK October 2, 2009 REPORT SURGE PROTECTIVE DEVICES (VZCA) GE Zenith Controls Bonham, TX

File E Project 08NK October 2, 2009 REPORT SURGE PROTECTIVE DEVICES (VZCA) GE Zenith Controls Bonham, TX File E3456 Project 08NK10151 October 2, 9 REPORT ON SURGE PROTECTIVE DEVICES (VZCA) GE Zenith Controls Bonham, TX Copyright 9 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the

More information

COMPACT LED DRIVERS. ComfortLine Residential. ComfortLine RESIDENTIAL , , ,

COMPACT LED DRIVERS. ComfortLine Residential. ComfortLine RESIDENTIAL , , , COMPACT LED DRIVERS ComfortLine RESIDENTIAL 186679, 186680, 186681, 186682 Typical Applications Built-in in compact luminaires for Residential lighting Downlights ComfortLine Residential VERY COMPACT SHAPE

More information

Surgelogic Surge Protective Devices LC, XR, and XW Series

Surgelogic Surge Protective Devices LC, XR, and XW Series Surgelogic Surge Protective Devices LC, XR, and XW Series Catalog 1311CT0101R6/07 2007 Class 1311 CONTENTS Description..............................................Page Product Description...........................................

More information

SPM Series Plug-in Surge Protection

SPM Series Plug-in Surge Protection SPM Series Plug-in Surge Protection The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects

More information

LINEAR LED DRIVERS. PrimeLine DALI dimmable. PrimeLine DALI DIMMABLE , , , , ,

LINEAR LED DRIVERS. PrimeLine DALI dimmable. PrimeLine DALI DIMMABLE , , , , , LINEAR LED DRIVERS PrimeLine DALI DIMMABLE 186445, 186446, 186575, 186576, 186577, 186578 Linear LED drivers with preset operating window or individual programming Typical Applications Built-in in linear

More information

Surge Protective Device

Surge Protective Device Surge Protective Device LED Light / Machine protection SPD Class 2 LT-C34G801W General Information LT-C and LT-HC series Surge Protective Devices are for protection of indirect lightning. They are designed

More information

QUINT-PS AC/24DC/10

QUINT-PS AC/24DC/10 Extract from the online catalog QUINT-PS-100-240AC/24DC/10 Order No.: 2938604 DIN rail power supply unit 24 V DC/10 A, primary switched-mode, 1- phase Commercial data EAN 4017918890537 Pack 1 Pcs. Customs

More information

Fundamentals of Thyristor Overvoltage Circuit Protection

Fundamentals of Thyristor Overvoltage Circuit Protection Fundamentals of Thyristor Overvoltage Circuit Protection Thyristor Surge Protection Technology The Problem of Overvoltages Electronic components have been designed to function properly when used within

More information

GLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc.

GLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc. GLOSSARY OF TERMS Surge and Lightning Protection ERICO Inc. Air Termination - shall mean that part of a lightning protection system designed to capture the lightning strike. Normally is mounted on the

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

Surge Protector. Esma Khatun

Surge Protector. Esma Khatun Surge Protector Esma Khatun 1.04.17 Overall Size Electronic Usage Use of electronic equipment has increased Overall size of the equipment has decreased TIME Smaller more compact electronic devices have

More information