Protecting the electronic world from surges OEM. Industrial Product Catalog SURGE PROTECTIVE DEVICES

Size: px
Start display at page:

Download "Protecting the electronic world from surges OEM. Industrial Product Catalog SURGE PROTECTIVE DEVICES"

Transcription

1 Protecting the electronic world from surges OEM Industrial Product Catalog SURGE PROTECTIE DEICES

2 WHY APT?, Inc. (APT) has been a worldwide leader in the surge suppression industry since Headquartered in central Florida, heart of lightning activity, APT s surge protection products have long set the standard for protection of commercial and industrial facilities. In addition to superior products, APT has received numerous awards for customer service including the coveted Frost and Sullivan Market Engineering Award. Our commitment to service and exceeding expectations comes from our people and sophisticated system integration. We value the client relationship and support it with integrity, responsiveness and technical excellence. We are... Professionals Serving Professionals

3 SPD Sizing Chart...4 Type 1 SPDs OEM / INDUSTRIAL PRODUCT CATALOG Table of Contents SPDEE Series...5 SPDEE DC Series...7 S-Kit Series...9 iarrest Series...11 TEXCS Series...13 TEXDS Series...15 TEXAS Series...17 TEXAL Series...19 TEXBS Series...21 TEXBL Series...23 Type 2 MODULAR SPDs TE/HP Series...25 TE/HPS Series...27 TE/XGA Series...29 Type 4 INERGRAL SPDs TE/XRS Series...31 TE/XRL Series...33 TE/XWS Series...35 TE/XWL Series...37 Specialy SPDs TWL Series...39 BNCB5kA...41 BNCA10kA...42 BNC Guide...43 DIN Rail - Low oltage...44 Medium oltage SPDs STFB Series...45 M Series...47 What Electrical System is It?...49 Why do I need Surge Protection?...50 Frequently Asked Questions...51 Protecting the electronic world from surges Since 1985

4 SPD Sizing Chart XAS XDS XCS SPDEE Service Entrance Greater than 2000A Exposure Level High Exposure Medium Exposure Low Exposure Lowest Exposure ka per phase 300 ka 200 ka 150 ka 100 ka Model XAS30 XAS20 XAS15 XDS10 Service Entrance 1200A A Exposure Level High Exposure Medium Exposure Low Exposure Lowest Exposure ka per phase 250 ka 200 ka 150 ka 100 ka Model XAS25 XAS20 XDS15 XCS10 Service Entrance 800A A Exposure Level High Exposure Medium Exposure Low Exposure Lowest Exposure ka per phase 200 ka 150 ka 100 ka 50 ka Model XDS20 XDS15 XCS10 SPDEE Distribution/Branch Panel 800A A Exposure Level High Exposure Medium Exposure Low Exposure Lowest Exposure ka per phase 200 ka 150 ka 100 ka 50 ka Model XDS20 XDS15 XCS10 SPDEE Distribution/Branch Panel Less than 800A Exposure Level High Exposure Medium Exposure Low Exposure Lowest Exposure ka per phase 150 ka 100 ka 100 ka 50 ka Model XDS15 XDS10 XCS10 SPDEE PRICING & PRODUCT INFORMATION Call and ask for the OEM Department or visit 4

5 SPDee Series SURGE PROTECTIE DEICE The Next Generation SPD designed for UL 1449 Third Edition Features: UL 1449 Third Edition (Sept 2009) Listed 50kA 8x20μs Type 1 SPD - 20kA l n & 10kA (cul Type 2 optional) 20kA ln Meets UL 96A Lightning Protection Master Label Can be installed upstream or downstream of main disconnect 200kA SCCR (most models) All UL-required OCP & Safety Coordination Included Inside oltage Specific Design: Performs better than one-size fits all Tri-Mount Installation for more mounting flexibility: Same unit mounts on Pipe Nipple, Bracket or Din-Rail Green=Go isual Diagnostics: Easy to See; Easy to Understand Performance Specifications 50kA 8x20μs Per Mode UL 1449 tested Inominal: 20kA (highest available) + 10kA UL 1449 tested SCCR: 200kA (most models) Large-Block, 34mm square, 50kA MOs Individually Fused & Thermally Protected MOs UL 1449 oltage Protection Ratings (PRs): for 120, 120/240, 208Y/ for 277, 480Y/277 Repetitive Impulse: kA-8x20μs; kA-8x20μs Data table located on backpage Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Peak Operating Temperature: +85 o C (185 o F) Typical Operating Temperature: -40 o C (-40 o F) to +60 o C (140 o F) Response Time: < 1nanosecond Solid State Bi-directional Operation NEMA 4X Polycarbonate Enclosure UL746C(f1), UL 94-5A Pre-wired with 3 (1m) of #10 AWG conductor Typical Type 2 Connection: #10 AWG to 30A breaker Dimensions Weight: 1.60 lbs (0.73 kg) Sized for std 35mm DIN-rail /4-14 Green=Go isual Diagnostic Monitoring Green LED = A-OK, Out = replace LED isible from Multiple Sides & Angles - Better iewing Every MO is Monitored as opposed to power is present Tri-Mount Installation - L-bracket mounting kit is no cost accessory Std. 3/4-14 Nipple DIN-rail Mount (rail not incl.) Bracket Mount for flat surfaces Options N-G protection Dry Contact & Audible Alarm Dry contact connection leads exit through nipple via #18 AWG Other configurations available for OEM - Call L-bracket mounting kit for DIN-rail is no cost accessory Quality, Standards & alidation 2 year warranty (longer optional) UL 1449 Third Edition file: ZCA.E at cul ANSI/IEEE C , C , and C NEMA LS-1 IEC 61643, CE Burn-In tested Prior to Shipment ISO 9001:2008 Certified Quality Management System ISO 17025:2005 Certified Test Lab RoHS-compliant Special Thank You to NASA/SATOP for design assistance & validation 5

6 th St. N. Clearwater, FL X th St. N. Clearwater, FL X th St. N. Clearwater, FL X th St. N. Clearwater, FL X th St. N. Clearwater, FL X th St. N. Clearwater, FL X th St. N. Clearwater, FL X th St. N. Clearwater, FL X th St. N. Clearwater, FL X SPDEE Model Numbers SPDEE Application Guide S 50 A oltage System Options SPDEE ka/phase Default 120 1P N 50kA 127 2P D 220 3Y 2 1P=One Pole, Single Phase 240 3D 2P=Two Pole, Split Phase 277 3H 3Y=Three Pole Wye N = N-G 347 3D=Three Pole Delta Protection 480 3H=Three Pole Hi-Leg Delta D = Dry Contact 600 & Audible Alarm No cost accessories: 9876 L-bracket mounting kit 2 = Type 2 SPD Bearing cul Mark 8483 Supplementary label 1 Pole - Single SYSTEM CONFIGURATION v INSTALLED AT OR NEAR SERICE ENTRANCE OR TRANSFORMER N-G Bonded - Does not require N-G protection BLK INSTALLED >10 (3M) FROM SERICE ENTRANCE OR TRANSFORMER Downstream of N-G Bond - N-G protection suggested WHT WHT GRN oltage Model Number Model Number BLK Examples: S50A1203Y = 50kA, 120, 3 pole (208Y/120) S50A2773YN = 50kA, 277, 3 pole (480Y/277), with N-G SPDEE MODEL Performance Data System oltage & Config UL 1449 THIRD Edition (Sept 2009) oltage Protection Rating PR 3000A I n SCCR MCO L-N L-L N-G * L-G * S50A1201P * 1000* 20kA 200kA 150 S50A1202P 120/ * 1000* 20kA 200kA 150 S50A1203Y 208Y/ * 1000* 20kA 200kA 150 S50A1271P * 1200* 20kA 100kA 180 S50A1272P 127/ * 1200* 20kA 100kA 180 S50A1273Y 220Y/ * 1200* 20kA 100kA 180 S50A2201P pole * 1800* 20kA 200kA 320 S50A2203Y 380Y/ * 1800* 20kA 200kA 320 S50A2403H 120/240 - Hi-Leg Delta 600 / / * 1000* /1500* 20kA 200kA 150 /320 S50A2401P pole kA 200kA 320 S50A2403D 240 Delta - 3 pole kA 200kA 320 S50A2771P * 1800* 20kA 200kA 320 S50A2772P 240/ * 1800* 20kA 200kA 320 S50A2773Y 480Y/ * 1800* 20kA 200kA 320 S50A3473Y 600Y/347Y * 2500* 20kA 200kA 420 S50A4801P pole kA 200kA 550 S50A4803D 480 Delta - 3 pole kA 200kA 550 S50A4803H 240/480 - Hi-Leg Delta 1200/ kA 200kA 320/ 550 S50A6003D 600 Delta - 3 pole kA 200kA 690 S100A1202P 120/ kA 100kA 150 S100A2772P 240/ kA 100kA 320 * with optional N-G protection Optional Form C Dry Contact & Audible Alarm 2 Pole - Split Phase Wye Hi-Leg v v Phase B (ORNG) BLK WHT BLK BLK WHT BLK GRN oltage Model Number Model Number BLK A B Phase B (BLK) BLK N WHT C v v BLK oltage Model Number Model Number BLK ORNG (L-G, not L-N) BLK WHT BLK WHT GRN oltage Model Number Model Number S50A2403H N/A BLK BLK WHT BLK GRN BLK ORNG Form C Dry Contact: Three (3) #18 wires exit the pipe nipple Gray is Common, Blue is Normally Open, Red is Normally Closed Normally Open: Use Gray & Blue Normally Closed: Use Gray & Red Power Leads Dry Contact Leads Delta v Phase B (BLK) oltage BLK BLK BLK GRN Model Number S50A2403D Corner Grounded Delta? Use same models & connect one SPD black & green to ground (diagnostics will function correctly) 6 Audible Alarm: Alarm sounds when any protection is lost (If diagnostic LED extinguishes (i.e. problem), alarm will sound) lh # 8179 Blue Gray Red

7 Go Green with APT DC SPDee Series DC SPDEE DC oltage Surge Protective Device UL Listed to UL Photovoltaic Standard (ZCA.E & ZCA7.E321351) UL Listed as opposed to Recognized - avoids scrutiny over Technical Considerations of Recognized products Avoids Certification Surprises No Unexpected Installation Requirements Listed to UL 1449 as DC SPD for use in P applications Options & Configurations for OEMs (see back) Does not require additional upstream fusing for SPD safety protection 100kA DC Short Circuit Current Rating (SCCR) Fail-Safe operation arc breaking, slide-gate thermal disconnectors built-in Avoids safety challenges & fusing shortcomings of overseas-standard SPDs Performance Specifications 50kA 8x20μs Per Mode 300dc, 600dc, 1000dc & OEM models All modes of protection: DC+ G, DC- G, DC+ DC- UL 1449 tested I n : 20kA (highest available) UL 1449 tested SCCR: 100kA DC UL Listed as Type 1 SPD UL 1449 Type 2 optional for cul Mark Large-Block arrestor-grade 34mm square MOs Individually Fused & Thermally Protected MOs Repetitive Impulse: kA-8x20μs; kA-8x20μs Response Time: < 1nanosecond Monitoring Configurations Standard - Low consumption LED; monitors every MO Illuminates when power is produced Options: R Removes LED and its circuitry M MO Microswitch access option (requires R above) Dimensions Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: DC Operating Temperature: -40 C (-40 F) to +65 C (149 F) Solid State Bi-directional Operation NEMA 4X Polycarbonate Enclosure UL746C(f1), UL 94-5A Pre-wired with 3 (1m) of #8 AWG & #6 AWG ground conductor Tri-Mount Installation - Mounting Kit Included Std. 3/4-14 Nipple DIN-rail Mount (rail not incl.) Bracket Mount for flat surfaces Quality, Standards & alidation 2 year warranty (longer optional) ANSI/IEEE C , C & C Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025: Certified Test Lab IEC 61643, CE UL 96A Lightning Protection Master Label Eligible 7

8 Applications & Models: DC SPDEE DC oltage Surge Protective Device UL Model Number S50A300DC S50A600DC S50A1000DC DC oltage 0-300dc 0-600dc dc Maximum Continuous Operating oltage 424dc 905dc 1188dc oltage Protection Level 6k/3kA <1000p <2000p <2500p SPDEE DC Model Number Configurator & Options UL 1449: S50A oltage Options 50kA default 300DC 600DC 1000DC Examples: - S50A300DCRM = 50kA, 300dc, Remove LED, Microswitch Monitoring 2 = Type 2 SPD bearing culus Mark (for Canada) R M = Removes LED and its circuitry isual Monitoring via pop-up indicator tabs on each MO. = Microswitch option requires R option above. Allows remote access to logic connected MO diagnostics. Includes 20 AWG wires out of nipple. Power must be limited to 50mA at 12DC - S50A1000DC2 = 50kA, 1000dc, Type 2 marking for Canada G = For Grounding DC + terminal of system Schematic: All Modes of Protection DC+ red wire 8 AWG DC black wire 8 AWG Available Z Mounting Bracket Accessory AC oltage SPDEE s Also Available GROUND green/yellow wire 6 AWG #8383 OEM & Brand Label Opportunities Please call

9 In-Line, Series-Connection S-KIT Accessory SPD connects via feed-thru connection on Std 35mm DIN Rail Power feeds through Load conductors Arrestor SPD Robustness for In-Line, Series-Connected DIN Rail Applications Features & Where This Makes Sense: 50kA Service Entrance rated SPD Suitable for UL 96A Lightning Protection System High Surge Environments: Outdoor, Pole-Mount, Traffic, ITS Robust Arrestor Grade Components No dwarf suppression elements UL rd Edition Listed SPD UL Mark Avoids regulatory or compliance issues Type 1 SPD - does not require separate overcurrent protection at additional cost & space Includes On-Board LED diagnostics No More Costly Than Traditional In-Line SPD (Maybe Less When Extra Fusing is Required) Disadvantages of Traditional Series-Connected SPDs: Not robust (take one apart: small dwarf/electronic grade MOs) Usually need extra cost & extra space for overcurrent protection Not UL Listed (Series SPDs are historically Recognized, not Listed) Not UL Recognized (dangerous? - mfg knew it would not pass recent UL 1449 changes?) UL Recognized with substantial shortcomings?( Surprises buried in File s Conditions of Acceptability?) Series SPDs can completely deenergize their loads if their fuse/breaker clears. Unacceptable to critical loads such as traffic control cabinets, fire alarm panels, etc. Installation Instructions & Photos on Back For Indoor Use Only - Up to 600, 35A, UL Recognized Connectors APT Technical Support at (800) Ordering Information (SPDee is Ordered Separately): SKIT 1 for 120 (true single phase): 1 Hot, 1 Neutral, 1 Ground Includes two Altech CMC1-2 term blocks, two Altech CGT6N term blocks, one EPCMC-1-2 end plate, label SKIT 2 for 120/240 (split phase): 2 Hots, 1 Neutral, 1 Ground Includes three Altech CMC1-2 term blocks, two Altech CGT6N term blocks, one EPCMC-1-2 end plate, label SKIT 3 for 208Y/120 (three phase, rare for series application): 3 Hots, 1 Neutral, 1 Ground D suffix option Adds 6 35mm DIN rail and two mounting screws (example: SKIT1D) Component Specifics (Or To Build Your Own): Energized and Neutral Feed-Through Terminal Blocks: Altech CMC1-2, Gray, tri-connect, 600, 35A, AWG, Altech EPCMC1-2 end plate, cяuus, file E Ground Feed-Through Terminal Blocks: Altech CGT6N, Green/Yellow, 600, 35A, AWG, cяuus, file E (two required one connects feed-through ground leads to DIN rail ground, other connects SPD to DIN rail ground) Identification Label for affixing to SPDEE SPD th Street North Clearwater, Florida

10 S-KIT In-Line, Series-Connection Accessory Installation: Qualified Personnel Only - Follow all applicable codes - Ensure all loads are de-energized - Do not install during lightning storm. Select appropriate SPDEE from SPDEE datasheet. SPDEE mounts to DIN rail as standard feature. (Alternate mounting possible - SPD does not have to be mounted on DIN rail) Select appropriate S-KIT, or build your own from Feed-Through Terminal Blocks (Altech, Wago, etc.). Ensure DIN rail is solidly electrically grounded. Connect SPDEE and Feed-Through Terminal Blocks to DIN rail, covering exposed side(s) with end plate. Wire SPD hot and neutral leads to terminal blocks. Cut leads as short as possible. (May fit better in top terminals) Torque: 7 lb-in Wire load connections into and out-of terminal blocks. Torque: 7 lb-in Wire SPD ground to one of two grounding blocks. (One grounds SPD to DIN rail, other grounds feed-through ground leads). Ensure leads are tight. Energize. Ensure LED illuminates. Load Out (or In, can go either way) Standard SPDee LED visible here Supplemental label affixes to SPDEE Mounts and Grounds thru std 35mm DIN rail Make sure rail is electrically grounded Two ground terminals: One provides feed-thru connection to existing ground conductor and simultaneously grounds to DIN rail One connects SPD ground to DIN rail ground, bonding grounds together Three Position Feed-Thru Terminal Blocks: One for each Energized Black conductor One for Neutral Nut tightens aluminum L-bracket to DIN rail Strip & Install SPD lead to upper lug (all three terminals are connected together) Strip & Install feed-through load conductors on bottom Make leads short as possible inches matter! Gentle radius no sharp bends Leads from Load Load Out (or In, can go either way) SPD Hot SPD Ground KEY = Power = Neutral (white) = Ground 10 SPD Connection to Terminal Block Upper & Lower Terminals inside Terminal Block are connected to each other lh # 8678 SPD Netural th Street North Clearwater, Florida 33760

11 iarrest LA Series Arrester/Surge Protective Device/SPD Features: Budget Surge Protection Intended for outdoor loads, light poles, DOT, etc. 20kA and 40kA Per Mode Surge Current Ratings Hi-Energy MO based design Low Clamping oltages better protection than air-gap, spark-gap, GDT or silica oxide varistor technologies Encapsulated in Ceramgard elastomeric potting compound for below grade application oltage Specific Design Highly configurable Pre-attached 12 AWG 24 Leads Parallel Connection - Solid State Bidirectional Operation Optional EMI/RFI Noise Filter (1 & 2 pole models) Optional series type connection (aka two-port, Kelvinconnected or feed-thru connection) Model Number Configurator on Back Performance Specifications: Available Surge Current Capacities: 20kA in each of all specified modes 40kA in each of all specified modes Nominal DIscharge Current Rating (I n ): 20kA Operating Frequency: DC-500Hz Operating Temperature: -40 C (-40 F) to +85 C (185 F) Weight: 1.65 lbs (0.75 kg) Polycarbonate enclosure UL 746C(f1) & UL 94-5A 3/4 male threaded hub 10A upstream overcurrent protection recommended Maximum Continuous Operating oltage (MCO): Nominal System oltage: SPD MCO: Lead Configurations: (graphic on back) Standard configuration: 12 AWG leads exit the mouth of the SPD enclosure, not the nipple. This ensures maximum potting coverage around the leads for environmental & moisture protection. N suffix option: Moves 12 AWG leads to exit thru the nipple area (unit is still potted). S suffix option: Provides Series connection leads thru the mouth (not available with N option). This is also known as two-port, Kelvin or feed-thru connection. Some DOT light pole configurations require this. Steady state current rating for S option is 12A. Not intended for continuous loads above 12A. Mounting Configurations: (graphic on back) Intended for mounting via nipple hub (1.05 OD) B suffix option mounting bracket permits mounting on flat surface or standard 35mm DIN rail Weight: 1.65 lbs (0.75 kg) Sized for std 35mm DIN-rail /4-14 Quality, Standards & alidation: Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C High Energy Parallel Design for Category C3 & C-High applications UL Recognized MOs & EMI/RFI Filter RoHS-compliant 2 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 11

12 LA MODEL NUMBER CONFIGURATOR & OPTIONS LA llll ll ll ll l... oltage (see Figures) Power System (see Figures) 1P 2P = One Pole, Single Phase (powered L-N, see Figure 5) = Two Pole, Split Phase (powered L-L, see Figure 1) 3Y = Three Pole Wye (Figure 2) 3C = B Phase Corner Grounded Delta (Figure 6) 3D = Three Pole Delta (Figure 4) 3H = Three Pole Hi-Leg Delta (Figure 3) Modes of Protection Configuration A B C D E F G H = L-G and N-G protection (suggested for tall poles, or when far from service entrance) = L-G protection only = L-N protection only (B or C suggested when at service entrance) = L-N and N-G protection (suggested when close to service entrance) = L-G and L-N protection = L-L and L-G protection (for Delta systems) = L-L protection (for Delta Systems) = L-N, L-G & N-G protection (Available up to 20kA per mode and 40kA N-G, Not available with F or S options) ka Rating Per Mode 20 = 20kA 40 = 40kA Please call APT at for questions and application assistance Options B F N S Q = Aluminum Mounting Bracket = EMI/RFI Noise Filter (1 and 2 pole only) = Thru-nipple conductors (not available with S option) = Series connected, aka Kelvin connection An energized lead into the SPD and another energized lead out of the SPD. Power to the load goes through the SPD. Limited to 12A maximum current. (1 and 2 pole only) = Call for Custom or Special Builds Figure 1 Figure 2 A B Phase B (BLK) N C Figure 3 Phase B (ORNG) Figure 4 Phase B (BLK) Figure 5 Neutral (WHT) Figure 6 SPLIT 2 Hots, 1 Neu, 1 Grnd WYE 3 Hots, 1 Neu, 1 Grnd HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd DELTA & HRG WYE 3 Hots, 1 Grnd SINGLE POLE 1 Hot, 1 Neu, 1 Grnd Examples: LA4801PA40S = L-G and N-G protection of 40kA for 480 true single phase (Meets FDOT Light Pole specs) LA2402PA40S = L-G and N-G protection of 40kA for 240/480 split phase (Meets FDOT Light Pole specs) LA1202PD20BFN = L-N and N-G protection of 20kA for 120/240 split phase with bracket, filter and thru-nipple wires LA1201PB40BFS = L-G protection of 40 ka for 120 true single phase with bracket, filter and series connection wires CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd Lead Configurations: Standard configuration (blank) 12 AWG leads exit the mouth of the SPD enclosure, not the nipple. This ensures maximum potting coverage around the leads for environmental & moisture protection Mounting Configurations: Intended for mounting via nipple hub (1.05 OD, needs appropriately sized hole) B suffix option mounting bracket permits mounting on flat surface or standard 35mm DIN rail N suffix option moves 12 AWG leads to exit thru the nipple area (unit is still potted) S suffix option provides Series connection leads thru the mouth (not available with N option). This is also known as two-port, Kelvin or feed-thru connection. Some DOT light pole configurations require this. Steady state current rating for S option is 12A. Not intended Leads out of SPD Leads into Ground Std. 3/4-14 Nipple DIN-rail Mount (rail not incl.) Bracket Mount for flat surfaces lh #8691

13 TEXCS Series Type 1 Surge Protective Device/SPD Features: UL 1449 Third Edition Listed (Sept 2009) 100kA per phase rating Type 1 SPD All UL required OCP & Safety Coordination included inside Can be installed line-side or load-side of main disconnect 20kA Inominal (I n ) (most models) 200kA SCCRs (most models) UL 96A Lightning Protection Master Label compliant (@20kA I n ) oltage Specific Design Highly configurable All MO suppression elements monitored Performance Specifications Surge Capacities L-N L-G N-G 100kA/phase 50kA 50kA 50kA UL 1449 Third Edition Listed UL Type 1 SPD (cul Type 2 optional) UL tested Inominal (I n ): 20kA & 10kA UL tested SCCR: 200kA & 100kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1000 (data table on back) Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz (also 400Hz on <480) Peak Operating Temperature: +85 o C (185 o F) Operating Temperature: -40 C (-40 F) to +60 C (140 F) Weight: 3 lbs (1.4 kg) NEMA 4X Polycarbonate enclosure UL 746C(f1) & UL 94-5A Dimensions: 8 x 3 x 3 (203mm x 76mm x 76mm) 3/4 threaded hub - weather resistant 4X Pre-wired with 3 (1m) of #10 AWG conductor Typical connection: #10 AWG and 30A breaker Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC 61643, CE High Energy Parallel Design for Category C3 & C-High applications For External Mounting next to Switchgear, Motor Controls Centers or Panelboards Individually Fused & Thermally Protected MOs Large-Block, 34mm square, 50kA MOs Solid State Bidirectional Operation Diagnostic Monitoring 100% monitoring Every MO is monitored, incl. N-G Green LED Status indicator per phase Phase Loss monitoring (toggles LED & dry contacts) Electrically isolated circuitry ensures surges do not damage diagnostics Optional: Audible Alarm & Form C Dry Contact, (Contact rated 240, 5A; leads are pre-wired through nipple with #18 AWG) Quality, Standards & alidation UL 1449 Third Edition, (cul Type 2 optional) UL file: ZCA.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 13

14 TEXCS MODEL NUMBER CONFIGURATOR & OPTIONS TE ll XCS ll 4X l... oltage Code for Electrical System Surge Current Rating Options Common North American Systems: 01 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 02 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 03 = 240/120 High Leg Delta (B High) (Fig 3) 04 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) 05 = 480 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye 08 = 600Y/347 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 15 = 254/127 Split Phase - 1Ø 3W+Grnd (Fig 1) 18 = 480/277 2-Pole, (480/240 Split Phase) (Fig 1) 21 = 220Y/127 Wye - 3Ø 4W+Grnd (Fig 2) 41 = 520Y/300 Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240 Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230 Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250 Wye - 3Ø 4W+Grnd (Fig 2) 51 = 480 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 06 = 240 Delta - 3Ø 3W+Grnd (Fig 4) 61 = 240 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 07 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 09 = 600 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye 91 = 600 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 11 = 120 Single Phase (Fig 5) 12 = 240 Single Phase (Fig 5) - Not split phase 13 = 127 Single Phase (Fig 5) 14 = 300 Single Phase (Fig 5) 16 = 277 Single Phase (Fig 5) 17 = 480 Single Phase (1 Hot, 1 Neu, 1 Grnd) (Fig 5) 10 = 100kA/Phase Enclosure Rating 4X = NEMA 4X Non-Metallic (size 8 x 3 x 3 ) A = Audible Alarm & Dry Contacts Form C, 240, 5A (pre-wired) E = Remote Indicator LED on 6 Cable (pre-wired through nipple) 2 = Type 2 SPD bearing cul Mark Delete Options - Consult Factory for Order Code Delete L-N Protection (reduces ka rating) Delete L-G Protection (reduces ka rating) Delete N-G Protection (reduces ka rating) Available Accessory (order separately) FMKITC = Flush Mount Kit RM = Remote Monitor Figure 1 Figure 2 A B Phase B (BLK) N C Figure 3 Phase B (ORNG) Figure 4 Phase B (BLK) Figure 5 Neutral (WHT) Figure 6 SPLIT 2 Hots, 1 Neu, 1 Grnd WYE 3 Hots, 1 Neu, 1 Grnd HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd DELTA & HRG WYE 3 Hots, 1 Grnd SINGLE POLE 1 Hot, 1 Neu, 1 Grnd CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd Performance Data Common North American Systems UL 1449 THIRD Edition (Sept 2009) Test Data oltage Protection Ratings (PR - 3kA) L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 1 20kA 100kA = 208Y/120 3Ø Wye Type 1 20kA 200kA = 240Y/120 B High Leg Delta 600/ / Type 1 20kA 200kA 150 / = 480Y/277 3Ø Wye Type 1 20kA 200kA = 480 3Ø Delta Type 1 10kA 200kA = 600Y/347 3Ø Wye Type 1 10kA 200kA 420 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA Optional disconnect switch may increase PRs lh #8389

15 TEXDS Series Type 1 Surge Protective Device/SPD Features: UL 1449 Third Edition Listed (Sept 2009) 100kA 200kA per phase ratings Type 1 SPD All UL required OCP & Safety Coordination included inside Can be installed line-side or load-side of main disconnect 20kA Inominal (I n ) (most models) 200kA SCCRs (most models) UL 96A Lightning Protection Master Label compliant (@20kA I n ) oltage Specific Design Highly configurable All MO suppression elements monitored Performance Specifications Surge Capacities L-N L-G N-G 100kA/phase 50kA 50kA 50kA 150kA/phase 100kA 50kA 50kA 200kA/phase 100kA 100kA 100kA UL 1449 Third Edition Listed, UL 1283 R/C and cul UL Type 1 SPD (cul Type 2 optional) UL tested Inominal (I n ): 20kA & 10kA UL tested SCCR: 200kA & 100kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1000 (data table on back) Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 5 lbs (2.3 kg) NEMA 4X Polycarbonate enclosure UL 746C(f1) & UL 94-5A Dimensions: 6 x 6 x 4 (152mm x 152mm x 102mm) (excluding removable mounting feet) Lug size: #8 - #10 AWG Typical connection: #8 AWG and 40A breaker Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC 61643, CE High Energy Parallel Design for Category C3 & C-High applications For External Mounting next to Switchgear, Motor Controls Centers or Panelboards Individually Fused & Thermally Protected MOs Large-Block, 34mm square, 50kA MOs Solid State Bidirectional Operation Diagnostic Monitoring 100% monitoring Every MO is monitored, incl. N-G Green LED Status indicator per phase Red LED service indicator Phase Loss monitoring (toggles LED & dry contact) Electrically isolated circuitry ensures surges do not damage diagnostics Optional: Audible Alarm & Form C Dry Contact (Contact rated 240, 5A) Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 R/C UL file: ZCA.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 15

16 TEXDS MODEL NUMBER CONFIGURATOR & OPTIONS TE ll XDS ll 4X l... oltage Code for Electrical System Surge Current Rating Options Common North American Systems: 01 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 02 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 03 = 240/120 High Leg Delta (B High) (Fig 3) 04 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) 05 = 480 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye 08 = 600Y/347 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 15 = 254/127 Split Phase - 1Ø 3W+Grnd (Fig 1) 18 = 480/277 2-Pole, (480/240 Split Phase) (Fig 1) 21 = 220Y/127 Wye - 3Ø 4W+Grnd (Fig 2) 41 = 520Y/300 Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240 Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230 Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250 Wye - 3Ø 4W+Grnd (Fig 2) 51 = 480 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 06 = 240 Delta - 3Ø 3W+Grnd (Fig 4) 61 = 240 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 07 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 09 = 600 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye (Available: 100kA) 91 = 600 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (Available: 100kA) 11 = 120 Single Phase (Fig 5) 12 = 240 Single Phase (Fig 5) - Not split phase 13 = 127 Single Phase (Fig 5) 14 = 300 Single Phase (Fig 5) 16 = 277 Single Phase (Fig 5) 17 = 480 Single Phase (1 Hot, 1 Neu, 1 Grnd) (Fig 5) Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 A B Phase B (BLK) N C Phase B (ORNG) Phase B (BLK) 10 = 100kA/Phase 15 = 150kA/Phase 20 = 200kA/Phase Enclosure Rating A = Audible Alarm & Dry Contacts, Form C, 240, 5A 2 = Type 2 SPD Bearing cul Mark Delete Options - Consult Factory for Order Code Delete L-N Protection (reduces ka rating) Delete L-G Protection (reduces ka rating) Delete N-G Protection (reduces ka rating) Delete Noise Filtering Available Accessory (order separately) KITFMXF = Flush Mount Kit RM = Remote Monitor 4X = NEMA 4X Non-Metallic (size 6 x 6 x 4 ) A (BLK) Phase SPLIT 2 Hots, 1 Neu, 1 Grnd Performance Data WYE 3 Hots, 1 Neu, 1 Grnd HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd DELTA & HRG Wye 3 Hots, 1 Grnd SINGLE POLE 1 Hot, 1 Neu, 1 Grnd CORNER GROUND DELTA (B grounded) 3 Hots, 1 Grnd UL 1449 THIRD Edition (Sept 2009) Test Data Common North American Systems oltage Protection Ratings (PR - 3kA) L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 1 20kA 100kA = 208Y/120 3Ø Wye Type 1 20kA 200kA = 240Y/120 B High Leg Delta 700/ / /2000 Type 1 20kA 200kA 150 / = 480Y/277 3Ø Wye Type 1 20kA 200kA = 480 3Ø Delta Type 1 10kA 200kA = 600Y/347 3Ø Wye Type 1 10kA 200kA 420 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA Optional disconnect switch may increase PRs lh #8390

17 TEXAS Series Type 1 Surge Protective Device/SPD Features: UL 1449 Third Edition Listed (Sept 2009) 100kA 500kA per phase ratings Type 1 SPD All UL required OCP & Safety Coordination included inside Can be installed line-side or load-side of main disconnect 20kA Inominal (most models) 200kA SCCRs (most models) UL 96A Lightning Protection Master Label compliant (@20kA I n ) oltage Specific Design Highly configurable All MO suppression elements monitored Optional Rotary Disconnect Switch Performance Specifications Surge Capacities L-N L-G N-G 100kA/phase 50kA 50kA 50kA 150kA/phase 100kA 50kA 50kA 200kA/phase 100kA 100kA 100kA 250kA/phase 150kA 100kA 100kA 300kA/phase 150kA 150kA 150kA 400kA/phase 200kA 200kA 200kA 500kA/phase 250kA 250kA 250kA UL 1449 Third Edition Listed, cul, UL 1283 R/C UL Type 1 SPD (cul Type 2 optional) UL tested Inominal: 20kA & 10kA UL tested SCCR: 200kA & 100kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1000 Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring 100% monitoring Every MO is monitored, incl. N-G Green LED Status indicator per phase Red LED service indicator Audible Alarm with Silence Switch Test Function: toggles red service LED, audible alarm & dry contact (if equipped) N-G overvoltage detection Phase Loss monitoring (toggles LED & dry contacts) Electrically isolated circuitry ensures surges do not damage diagnostics Form C Dry Contacts, 240, 5A (two sets) Optional Surge Counter, six-digit LCD, with test function, reset & no-maintenance Eprom memory Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC High Energy Parallel Design for Category C3 & C-High applications For External Mounting next to Switchgear, Motor Controls Centers or Panelboards Individually Fused & Thermally Protected MOs Large-Block, 34mm square, 50kA MOs Replaceable Module Construction Solid State Bidirectional Operation Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 24 lbs (11 kg) Standard NEMA 1/12/3R/4 enclosure Standard size: 12 x 12 x 6.5 (305mm x 305mm x 165mm) Lug size: #2 - #14 AWG (w/opt. disconnect: #6 - #1/0) Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 R/C UL file: ZCA.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 17

18 TEXAS MODEL NUMBER CONFIGURATOR & OPTIONS TE ll XAS ll ll l... oltage Code for Electrical System Surge Current Rating Options Common North American Systems: 01 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 02 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 03 = 240/120 High Leg Delta (B High) (Fig 3) 04 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) 05 = 480 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye (450kA replaces 400kA or 500kA) 08 = 600Y/347 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 15 = 254/127 Split Phase - 1Ø 3W+Grnd (Fig 1) 18 = 480/277 2-Pole, (480/240 Split Phase) (Fig 1) 21 = 220Y/127 Wye - 3Ø 4W+Grnd (Fig 2) 41 = 520Y/300 Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240 Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230 Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250 Wye - 3Ø 4W+Grnd (Fig 2) 51 = 480 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (450kA replaces 400kA or 500kA) 06 = 240 Delta - 3Ø 3W+Grnd (Fig 4) (450kA replaces 400kA or 500kA) 61 = 240 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (450kA replaces 400kA or 500kA) 07 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 09 = 600 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye (Available: 100kA, 150kA, 200kA, 250kA) 91 = 600 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (Available: 100kA, 150kA, 200kA, 250kA) 11 = 120 Single Phase (Fig 5) 12 = 240 Single Phase (Fig 5) - Not split phase 13 = 127 Single Phase (Fig 5) 14 = 300 Single Phase (Fig 5) 16 = 277 Single Phase (Fig 5) 17 = 480 Single Phase (1 Hot, 1 Neu, 1 Grnd) (Fig 5) 10 = 100kA/Phase 15 = 150kA/Phase 20 = 200kA/Phase 25 = 250kA/Phase 30 = 300kA/Phase 40 = 400kA/Phase 45 = 450kA/Phase (oltage Codes 05, 51, 06 & 61) 50 = 500kA/Phase Enclosure Rating X = Surge Counter, six-digit LCD counter includes maintenance-free Eprom memory backup E = Remote Locatable Display on 4 ft Cable custom cable lengths available F = Noise Filtering - Extended Range & Attenuation (available on 400kA & 500kA models) D = Rotary Disconnect Switch, Bussmann, UL98 T = Thru-Door Rotary Disconnect Switch, Bussmann, UL98, E1 enclosure only (Consult factory for other disconnect switch options) 2 = Type 2 SPD Bearing cul Mark Delete Options - Consult Factory for Order Code Delete L-N Protection (reduces ka rating) Delete L-G Protection (reduces ka rating) Delete N-G Protection (reduces ka rating) Delete Noise Filtering Available Accessory (order separately) RM = Remote Monitor E1 = NEMA 1/12/3R/4 (size: 12 x 12 x 7.5 ) 4X = NEMA 4X Non-Metallic (size: 14 x 12 x 6 ) (polycarbonate, display inside clear front door) 4S = NEMA 4X Stainless Steel (size: 12" x 12"x 6") (display inside door) FM = NEMA 1 Flush Mount (wall cavity size: 12 x 12 x 6 deep) P1 = NEMA 1 pullbox indoor (size: 12 x 12 x 6 ) includes E option (Optional rotary disconnect increases enclosure sizes to 16 x 14 x 6 on models > 300kA) Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 A B Phase B (BLK) N C Phase B (ORNG) Phase B (BLK) A (BLK) Phase SPLIT 2 Hots, 1 Neu, 1 Grnd Performance Data WYE 3 Hots, 1 Neu, 1 Grnd Common North American Systems HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd UL 1449 THIRD Edition (Sept 2009) Test Data oltage Protection Ratings (PR - 3kA) L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase (<300kA) Type 1 20kA 100kA = 240/120 Split Phase (=>300kA) Type 1 20kA 100kA = 208Y/120 3Ø Wye (<300kA) Type 1 20kA 200kA = 208Y/120 3Ø Wye (=>300kA) Type 1 20kA 200kA = 240Y/120 B High Leg Delta 700/ / Type 1 20kA 200kA 150 / = 480Y/277 3Ø Wye (<300kA) Type 1 20kA 200kA = 480Y/277 3Ø Wye (=>300kA) Type 1 20kA 200kA = 480 3Ø Delta (<300kA) Type 1 10kA 200kA = 480 3Ø Delta (=>450kA) Type 1 20kA 200kA = 380Y/220 3Ø Wye (<300kA) Type 1 20kA 200kA = 600Y/347 3Ø Wye (<300kA) Type 1 10kA 200kA = 600Y/347 3Ø Wye (=>300kA) Type 1 20kA 200kA 420 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA Optional disconnect switch may increase PRs DELTA & HRG WYE 3 Hots, 1 Grnd SINGLE POLE 1 Hot, 1 Neu, 1 Grnd CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd lh #8386

19 TEXAL Series Type 1 Surge Protective Device/SPD Performance Specifications Directly Connected, Discrete Protection Elements Between All Possible Modes with True 10-Mode Protection Surge Capacities L-N L-G L-L N-G 150kA/phase 50kA 50kA 50kA 50kA 300kA/phase 100kA 100kA 100kA 100kA 450kA/phase 150kA 150kA 150kA 150kA UL 1449 Third Edition Listed, cul, UL 1283 R/C UL Type 1 SPD (cul Type 2 optional) UL tested Inominal (I n ): 20kA UL tested SCCR: 200kA & 100kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1000 Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave True Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring 100% monitoring Every MO is monitored, incl. N-G Green LED Status indicator per phase Red LED service indicator Audible Alarm with Silence Switch Test Function: toggles red service LED, audible alarm & dry contact (if equipped) N-G overvoltage detection Phase Loss monitoring Electrically isolated diagnostic circuitry Form C Dry Contacts, 240, 5A (two sets) Optional Surge Counter, six-digit LCD, with test function, reset & no-maintenance Eprom memory Features: Directly Connected, Discrete Protection Elements Between All Possible Modes UL 1449 Third Edition Listed (Sept 2009) 150kA 450kA per phase ratings Type 1 SPD All UL required OCP & Safety Coordination included inside Can be installed line-side or load-side of main disconnect 20kA Inominal (I n ) 200kA SCCRs (most models) UL 96A Lightning Protection Master Label compliant (@20kA I n ) All MO suppression elements monitored Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC 61643, CE High Energy Parallel Design for Category C3 & C-High applications For External Mounting next to Switchgear, Motor Controls Centers or Panelboards Individually Fused & Thermally Protected MOs Large-Block, 34mm square, 50kA MOs Replaceable Module Construction Solid State Bidirectional Operation Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 24 lbs (11 kg) Standard NEMA 1/12/3R/4 enclosure Standard size: 12 x 12 x 6.5 (30.5cm x 30.5cm x 16.5cm) Lug size: #2 - #14 AWG (w/opt. disconnect: #6 - #1/0) Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 UL file: ZCA.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 19

20 TEXAL 10-MODE MODEL NUMBER CONFIGURATOR & OPTIONS TE ll XAL ll ll l... oltage Code for Electrical System Surge Current Rating Options Common North American Systems: 01 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 02 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 03 = 240/120 High Leg Delta (B High) (Fig 3) 04 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 15 = 254/127 Split Phase - 1Ø 3W+Grnd (Fig 1) 18 = 480/277 2-Pole, (480/240 Split Phase) (Fig 1) 21 = 220Y/127 Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240 Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230 Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250 Wye - 3Ø 4W+Grnd (Fig 2) 07 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) Figure 1 15 = 150kA/Phase 30 = 300kA/Phase 45 = 450kA/Phase X = Surge Counter, six-digit LCD counter includes maintenance-free Eprom memory backup E = Remote Locatable Display on 4 ft Cable custom cable lengths available F = Noise Filtering - Extended Range & Attenuation (available on 400kA & 500kA models) D = Rotary Disconnect, Bussmann, UL98 T = Thru-door Rotary Disconnect Switch, Katko, UL 508, E1 enclosure only (Consult factory for other disconnect switch options) 2 = Type 2 SPD beaing cul mark Delete Options - Consult Factory for Order Code Delete L-N Protection (reduces ka rating) Delete L-G Protection (reduces ka rating) Delete N-G Protection (reduces ka rating) Delete Noise Filtering Figure 3 Available Accessory (order separately) RM = Remote Monitor SPLIT 2 Hots, 1 Neu, 1 Grnd Figure 2 A B Phase B (BLK) N C WYE 3 Hots, 1 Neu, 1 Grnd Phase B (ORNG) HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd Enclosure Rating E1 = NEMA 1/12/3R/4 (size: 12 x 12 x 7.5 ) 4X = NEMA 4X Non-Metallic (size: 14 x 12 x 6 ) (polycarbonate, display inside clear front door) 4S = NEMA 4X Stainless Steel (size: 12" x 12"x 6") (display inside door) FM = NEMA 1 Flush Mount (wall cavity size: 12 x 12 x 6 deep) P1 = NEMA 1 pullbox indoor (size: 12 x 12 x 6 ) - includes E option (Optional rotary disconnect increases enclosure sizes to 16 x 14 x 6 on 450kA only) Performance Data Common North American Systems UL 1449 THIRD Edition (Sept 2009) Test Data oltage Protection Ratings (PR - 3kA) L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 1 20kA 100kA = 208Y/120 3Ø Wye Type 1 20kA 200kA = 240Y/120 B High Leg Delta 800/ / Type 1 20kA 200kA 150 / = 480Y/277 3Ø Wye Type 1 20kA 200kA 320 Other Available Systems - Confirmation encouraged: 15 = 254/127 Split Phase Type 1 20kA 200kA = 220Y/127 3Ø Wye Type 1 20kA 200kA = 415Y/240 3Ø Wye Type 1 20kA 200kA = 400Y/230 3Ø Wye Type 1 20kA 200kA = 440Y/250 3Ø Wye Type 1 20kA 200kA = 380Y/220 3Ø Wye Type 1 20kA 200kA 320 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA Optional disconnect switch may increase PRs lh #8385

21 TEXBS Series Type 1 Surge Protective Device/SPD Features: UL 1449 Third Edition Listed (Sept 2009) 400kA 1,000kA per phase ratings Type 1 SPD All UL required OCP & Safety Coordination included inside Can be installed line-side or load-side of main disconnect 20kA Inominal (I n ) 200kA SCCRs (most models) UL 96A Lightning Protection Master Label compliant Rotary Disconnect Switch included as Standard Equipment Dual Redundant Replaceable Modules oltage Specific Design Highly configurable All MO suppression elements monitored Performance Specifications Surge Capacities L-N L-G N-G 400kA/phase 200kA 200kA 200kA 600kA/phase 300kA 300kA 300kA 800kA/phase 400kA 400kA 400kA 1000kA/phase 500kA 500kA 500kA UL 1449 Third Edition Listed, UL 1283 and cul UL Type 1 SPD UL tested Inominal (In): 20kA UL tested SCCR: 200kA & 100kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1200 Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring 100% monitoring Every MO is monitored, incl. N-G Green LED Status indicator per phase Red LED service indicator Audible Alarm with Silence Switch Test Function: toggles red service LED, audible alarm & dry contact (if equipped) N-G overvoltage detection Phase Loss monitoring (toggles LED & dry contacts) Electrically isolated circuitry ensures surges do not damage diagnostics Form C Dry Contacts, 240, 5A (two sets) Optional Surge Counter, six-digit LCD, with test function, reset & no-maintenance Eprom memory Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC 61643, CE High Energy Parallel Design for Category C3 & C-High applications For External Mounting next to Switchgear, Motor Controls Centers or Panelboards Individually Fused & Thermally Protected MOs Large-Block, 34mm square, 50kA MOs Dual Replaceable Module Construction Solid State Bidirectional Operation Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 52 lbs (23.6 kg) Standard NEMA 1/12/3R/4 enclosure Standard size: 20 x 20 x 7.5 (50.8cm x 50.8cm x 19cm) Lug size: #6 - #1/0 AWG Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 UL file: ZCA.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 21

22 TEXBS MODEL NUMBER CONFIGURATOR & OPTIONS TE ll XBS ll ll l... oltage Code for Electrical System Surge Current Rating Options Common North American Systems: 01 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 02 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 03 = 240/120 High Leg Delta (B High) (Fig 3) 04 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) 05 = 480 Delta - 3Ø 3W+Grnd (Fig4) & HRG Wye (Available: 400kA, 600kA, 900kA) 08 = 600Y/347 Wye - 3Ø 4W+Grnd (Fig2) Other Available Systems - Confirmation encouraged: 15 = 254/127 Split Phase - 1Ø 3W+Grnd (Fig 1) 18 = 480/277 2-Pole, (480/240 Split Phase) (Fig 1) 21 = 220Y/127 Wye - 3Ø 4W+Grnd (Fig 2) 41 = 520Y/300 Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240 Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230 Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250 Wye - 3Ø 4W+Grnd (Fig 2) 51 = 480 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (Available: 600kA & 900kA) 06 = 240 Delta - 3Ø 3W+Grnd (Fig 4) (Available: 600kA & 900kA) 61 = 240 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (Available: 600kA & 900kA) 07 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 09 = 600 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye (Available: 400kA & 500kA) 91 = 600 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (Available: 400kA & 500kA) 11 = 120 Single Phase (Fig 5) 12 = 240 Single Phase (Fig 5) - Not split phase 13 = 127 Single Phase (Fig 5) 14 = 300 Single Phase (Fig 5) 16 = 277 Single Phase (Fig 5) 17 = 480 Single Phase (1 Hot, 1 Neu, 1 Grnd) (Fig 5) Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 A B Phase B (BLK) N C Phase B (ORNG) 40 = 400kA/Phase (oltage Codes 09 & 91 only) 50 = 500kA/Phase (oltage Codes 09 & 91 only) 60 = 600kA/Phase 80 = 800kA/Phase 90 = 900kA/Phase (oltage codes 05, 51, 06, 61 only) 1K = 1000kA/Phase Phase B (BLK) Enclosure Rating X = Surge Counter, six-digit LCD counter includes maintenance-free Eprom memory backup E = Remote Locatable Display on 4 ft Cable custom cable lengths available F = Noise Filtering - Extended Range & Attenuation (available on 400kA & 500kA models) T = Thru-Door Rotary Disconnect Switch, Bussmann, UL98, E1 enclosure only K = Rotary Disconnect Switch, Katko, UL508 S = Thru-Door Rotary Disconnect Switch, Katko, UL 508, E1 enclosure only Delete Options - Consult Factory for Order Code Delete L-N Protection (reduces ka rating) Delete L-G Protection (reduces ka rating) Delete N-G Protection (reduces ka rating) Delete Noise Filtering Available Accessory (order separately) RM = Remote Monitor. E1 = NEMA 1/12/3R/4 (size: 20 x 20 x 7.5 ) 4X = NEMA 4X Non-Metallic (size: 24 x 24 x 8 ) (fiberglass, display inside door) 4S = NEMA 4X Stainless Steel (size: 20" x 20"x 7") (display inside door) P1 = NEMA 1 pullbox indoor (size: 20 x 20 x 6 ) - includes E option FM = NEMA 1 Flush Mount (wall cavity size: 20 x 20 x 6 deep) (Dimensions include standard rotary disconnect switch. Optional Thru-Door handle does not increase enclosure sizes.) A (BLK) Phase SPLIT 2 Hots, 1 Neu, 1 Grnd Performance Data WYE 3 Hots, 1 Neu, 1 Grnd HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd DELTA & HRG Wye 3 Hots, 1 Grnd SINGLE POLE 1 Hot, 1 Neu, 1 Grnd CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd UL 1449 THIRD Edition (Sept 2009) Test Data: Common North American Systems oltage Protection Ratings (PR - 3kA) L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 1 20kA 100kA = 208Y/120 3Ø Wye Type 1 20kA 200kA = 240/120 B High Leg Delta 700/ / / /1800 Type 1 20kA 200kA 150 / = 480Y/277 3Ø Wye Type 1 20kA 200kA = 480 3Ø Delta Type 1 20kA 200kA = 600Y/347 3Ø Wye Type 1 20kA 200kA 420 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA Optional disconnect switch may increase PRs lh #8388

23 TEXBL Series Type 1 Surge Protective Device/SPD Features: Directly Connected, Discrete Protection Elements Between All Possible Modes UL 1449 Third Edition Listed (Sept 2009) 600 & 900kA per phase ratings Type 1 SPD All UL required OCP & Safety Coordination included inside Can be installed line-side or load-side of main disconnect 20kA Inominal (I n ) 200kA SCCRs (most models) UL 96A Lightning Protection Master Label compliant Rotary Disconnect Switch included as Standard Equipment Dual Redundant Replaceable Module Construction All MO suppression elements monitored Performance Specifications Directly Connected, Discrete Protection Elements Between All Possible Modes with True 10-Mode Protection Surge Capacities L-N L-G L-L N-G 600kA/phase 200kA 200kA 200kA 200kA 900kA/phase 300kA 300kA 300kA 300kA UL 1449 Third Edition Listed, UL 1283 and cul UL Type 1 SPD UL tested Inominal (I n ): 20kA UL tested SCCR: 200kA & 100kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1200 Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave True Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring 100% monitoring Every MO is monitored, incl. N-G Green LED Status indicator per phase Red LED service indicator Audible Alarm with Silence Switch Test Function: toggles red service LED, audible alarm & dry contact (if equipped) N-G overvoltage detection Phase Loss monitoring Electrically isolated diagnostic circuitry Form C Dry Contacts, 240, 5A (two sets) Optional Surge Counter, six-digit LCD, with test function, reset & no-maintenance Eprom memory Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC 61643, CE High Energy Parallel Design for Category C3 & C-High applications For External Mounting next to Switchgear, Motor Controls Centers or Panelboards Individually Fused & Thermally Protected MOs Large-Block, 34mm square, 50kA MOs Dual Redundant Replaceable Module Construction Solid State Bidirectional Operation Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 52 lbs (23.6 kg) Standard NEMA 1/12/3R/4 enclosure Standard size: 20 x 20 x 7.5 (50.8cm x 50.8cm x 19cm) Lug size: #6 - #1/0 AWG Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 UL file: ZCA.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 23

24 TEXBL 10-MODE MODEL NUMBER CONFIGURATOR & OPTIONS TE ll XBL ll ll l... oltage Code for Electrical System Surge Current Rating Options Common North American Systems: 01 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 02 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 03 = 240/120 High Leg Delta (B High) (Fig 3) 04 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 41 = 520Y/300 Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240 Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230 Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250 Wye - 3Ø 4W+Grnd (Fig 2) 07 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 60 = 600kA/Phase 90 = 900kA/Phase X = Surge Counter, six-digit LCD counter includes maintenance-free Eprom memory backup E = Remote Locatable Display on 4 ft Cable custom cable lengths available F = Noise Filtering - Extended Range & Attenuation (available on 400kA & 500kA models) T = Thru-Door Rotary Disconnect Switch, Bussmann, UL98, E1 enclosure only K = Rotary Disconnect Switch, Katko, UL 508 S = Thru-Door Rotary Disconnect Switch, Katko, UL 508, E1 enclosure only Figure 1 SPLIT 2 Hots, 1 Neu, 1 Grnd Figure 2 A B Phase B (BLK) N C Figure 3 Phase B (ORNG) Enclosure Rating Delete Options - Consult Factory for Order Code Delete L-N Protection (reduces ka rating) Delete L-G Protection (reduces ka rating) Delete N-G Protection (reduces ka rating) Delete Noise Filtering Available Accessory (order separately) RM = Remote Monitor E1 = NEMA 1/12/3R/4 (size: 20 x 20 x 7.5 ) 4X = NEMA 4X Non-Metallic (size: 24 x 24 x 8 ) (fiberglass, display inside door) 4S = NEMA 4X Stainless Steel (size: 20" x 20"x 7.5") (display inside door) HI-LEG DELTA (B High) P1 = NEMA 1 pullbox indoor (size: 20 x 20 x 6 ) - includes E option 3 Hots, (B HIGH), FM = NEMA 1 Flush Mount (wall cavity size: 20 x 20 x 6 deep) 1 Neu, 1 Grnd Figure 3 (Dimensions include Figure standard 4 rotary disconnect Figure switch. 5Optional Thru-DoorFigure 6 handle does not increase enclosure sizes.) WYE 3 Hots, 1 Neu, 1 Grnd Performance Data Common North American Systems UL 1449 THIRD Edition (Sept 2009) Test Data oltage Protection Ratings (PR - 3kA) L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Wye Type 1 20kA 100kA = 208Y/120 3Ø Wye Type 1 20kA 200kA = 240Y/120 B High Leg Delta 700/ / /1800 Type 1 20kA 200kA 150 / = 480Y/277 3Ø Wye Type 1 20kA 200kA 320 Less Common & Specialty 42 = 415/240 3Ø Wye Type 1 20kA 200kA = 400/230 3Ø Wye Type 1 20kA 200kA = 440/250 3Ø Wye Type 1 20kA 200kA = 380/220 3Ø Wye Type 1 20kA 200kA 320 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA lh #8387

25 TE/HP Series Type 2 Surge Protective Device/SPD Features: UL 1449 Third Edition Listed (Sept 2009) 120kA & 160kA per phase ratings Type 2 SPD All UL required OCP & Safety Coordination included inside Can be installed load-side of main disconnect Replaceable module construction 200kA SCCRs oltage Specific Design Highly configurable MO suppression elements monitored Performance Specifications Surge Capacities L-N N-G 120kA/phase 120kA 120kA Standard 160kA/phase 160kA 160kA Optional UL 1449 Third Edition Listed, UL 1283 and cul UL Type 2 SPD UL tested SCCR: 200kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1000 Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring Green LED Status indicator per phase Red LED service indicator Audible Alarm with Silence Switch Test Function: toggles red service LED, audible alarm Redundant monitoring LEDs on modules Phase Loss monitoring (toggles LED & dry contacts) Electrically isolated circuitry ensures surges do not damage diagnostics Optional Form C Dry Contacts, 240, 5A (two sets) Optional Surge Counter, six-digit LCD, with test function, reset & no-maintenance SuperCap energy storage device Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC High Energy Parallel Design for Category C3 & C-High applications For External Mounting next to Switchgear, Motor Controls Centers or Panelboards Individually Fused Suppression Modules Large-Block 34mm square MOs Replaceable Phase Module Construction Thermal Cutout in Each Mode Busbar Construction Solid State Bidirectional Operation Enclosure-less version for OEM available Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 25 lbs (11.4 kg) Standard NEMA 1/12/3R/4 enclosure Standard size: 12 x 12 x 7.5 (30.5cm x 30.5cm x 19cm) Lug size: #1/0 - #14 AWG Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 UL file: ZCA.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 25

26 TE/HP MODEL NUMBER CONFIGURATOR & OPTIONS TE = Transient Eliminator, Listed Type 2 SPD in NEMA 1/3R/04/12 enclosure XTE = Transient Eliminator, Recognized Type 4 SPD on backplane for installation within gear in Type 2 installation (display on 6 cable) ll / l... / HP / ll / l... Model Family Option Suffixes (Seperated by slashes -/) HP = HP Family 120kA rating standard CL = 160kA Option DC = Dry Contacts Two sets Form C on terminal strip FM = Flush Mount enclosure, NEMA 1 only (wall cavity size: 12 x12 x6 deep) SC = Surge Counter oltage Code for Electrical System Common North American Systems: 1 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 2 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 3 = 240/120 High Leg Delta (B High) (Fig 3) 4 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) 5 = 480 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye 8 = 600Y/347 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 11 = 120 Single Phase - 1Ø 2W + Grnd (Fig 5) 12 = 240 Single Phase - 1Ø 2W + Grnd (Fig 5) 51 = 480 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 6 = 240 Delta - 3Ø 3W+Grnd (Fig 4) 61 = 240 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 7 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 9 = 600 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye 91 = 600 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) Enclosure Rating Available Accessory (order separately): RM = Remote Monitor 04 = Standard: NEMA 1/3R/04/12 (size: 12 x 12 x 7.5 ) FM = Flush Mount Enclosure, NEMA 1 only (wall cavity size: 12 x 12 x 6 ) 4X = NEMA 4X Non-Metallic (size: 14 x 12 x 6 ) (polycarbonate, display inside clear front door) 4S = NEMA 4X Stainless Steel (size: 12" x 12"x 6") (display inside door) (Note: Enclosure-less version for OEM uses XTE prefix) Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Phase B (ORNG) Phase B (BLK) A B Phase B (BLK) N C A (BLK) Phase SPLIT 2 Hots, 1 Neu, 1 Grnd WYE 3 Hots, 1 Neu, 1 Grnd HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd DELTA & HRG WYE 3 Hots, 1 Grnd SINGLE POLE 1 Hot, 1 Neu, 1 Grnd CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd Performance Data Common North American Systems UL 1449 THIRD Edition (Sept 2009) Test Data oltage Protection Ratings (PR - 3kA) L-N N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 2 5kA 200kA = 208Y/120 3Ø Wye Type 2 5kA 200kA = 240Y/120 B High Leg Delta 800/ Type 2 5kA 200kA 150 / = 480Y/277 3Ø Wye Type 2 5kA 200kA = 480 3Ø Delta 1800 Type 2 5kA 200kA = 600Y/347 3Ø Wye Type 2 5kA 200kA 420 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA lh #8397

27 TE/HPS Series Type 2 Surge Protective Device/SPD Features: UL 1449 Third Edition Listed (Sept 2009) 80kA, 120kA & 160kA per phase ratings Type 2 SPD All UL required OCP & Safety Coordination included inside Can be installed load-side of main disconnect Replaceable module construction 200kA SCCRs oltage Specific Design Highly configurable MO suppression elements monitored Performance Specifications Surge Capacities L-N N-G 80kA/phase 80kA 80kA Standard 120kA/phase 120kA 120kA Optional 160kA/phase 160kA 160kA Optional UL 1449 Third Edition Listed, UL 1283 and cul UL Type 2 SPD UL tested SCCR: 200kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1000 Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring Green LED Status indicator per phase Redundant monitoring LEDs on modules Phase Loss monitoring (toggles LED & dry contacts) Electrically isolated circuitry ensures surges do not damage diagnostics Optional Form C Dry Contacts, 240, 5A (two sets) Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC High Energy Parallel Design for Category C3 & C-High applications For External Mounting next to Switchgear, Motor Controls Centers or Panelboards Individually Fused Suppression Modules Large-Block 34mm square MOs Replaceable Phase Module Construction Thermal Cutout in Each Mode Busbar Construction Solid State Bidirectional Operation Enclosure-less version for OEM available Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 25 lbs (11.4 kg) Standard NEMA 1/12/3R/4 enclosure Standard size: 12 x 12 x 7.5 (30.5cm x 30.5cm x 19cm) Lug size: #1/0 - #14 AWG Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 UL file: ZCA.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 27

28 TE/HPS MODEL NUMBER CONFIGURATOR & OPTIONS ll / ll / HPS / ll / l... Model Family Option Suffixes (Seperated by slashes -/) TE = Transient Eliminator, Listed Type 2 SPD in NEMA 1/3R/04/12 enclosure XTE = Transient Eliminator, Recognized Type 4 SPD on backplane for installation within gear in Type 2 installation (display on 6 cable) HPS = HPS Family 80kA rating standard CX = 120kA Option CL = 160kA Option DC = Dry Contacts Two sets Form C on terminal strip FM = Flush Mount enclosure, NEMA 1 only (wall cavity size: 12 x12 x6 deep) oltage Code for Electrical System Common North American Systems: 1 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 2 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 3 = 240/120 High Leg Delta (B High) (Fig 3) 4 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) 5 = 480 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye 8 = 600Y/347 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 11 = 120 Single Phase - 1Ø 2W + Grnd (Fig 5) 12 = 240 Single Phase - 1Ø 2W + Grnd (Fig 5) 51 = 480 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 6 = 240 Delta - 3Ø 3W+Grnd (Fig 4) 61 = 240 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 7 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 9 = 600 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye 91 = 600 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) Enclosure Rating Available Accessory (order separately): RM = Remote Monitor 04 = Standard: NEMA 1/3R/04/12 (size: 12 x 12 x 7.5 ) FM = Flush Mount Enclosure, NEMA 1 only (wall cavity size: 12 x 12 x 6 ) 4X = NEMA 4X Non-Metallic (size: 14 x 12 x 6 ) (polycarbonate, display inside clear front door) 4S = NEMA 4X Stainless Steel (size: 12" x 12"x 6") (display inside door) (Note: Enclosure-less version for OEM uses XTE prefix) Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Phase B (ORNG) Phase B (BLK) A B Phase B (BLK) N C A (BLK) Phase SPLIT 2 Hots, 1 Neu, 1 Grnd WYE 3 Hots, 1 Neu, 1 Grnd HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd DELTA & HRG WYE 3 Hots, 1 Grnd SINGLE POLE 1 Hot, 1 Neu, 1 Grnd CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd Performance Data Common North American Systems UL 1449 THIRD Edition (Sept 2009) Test Data oltage Protection Ratings (PR - 3kA) L-N N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 2 5kA 200kA = 208Y/120 3Ø Wye Type 2 5kA 200kA = 240Y/120 B High Leg Delta 800/ Type 2 5kA 200kA 150 / = 480Y/277 3Ø Wye Type 2 5kA 200kA = 480 3Ø Delta 1800 Type 2 5kA 200kA = 600Y/347 3Ø Wye Type 2 5kA 200kA 420 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA lh #8396

29 Performance Specifications Surge Capacities L-N L-G N-G 160kA/phase 80kA 80kA 120kA Standard 240kA/phase 120kA 120kA 120kA Optional Silicon Avalanche Diode (SAD) Hybrid (120/240 & 208Y/120) 90kA/phase 50kA 40kA 120kA Optional 130kA/phase 50kA 80kA 120kA Optional 170kA/phase 90kA 80kA 120kA Optional UL 1449 Third Edition Listed, cul, UL 1283 R/C UL Type 2 SPD UL tested SCCR: 200kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as kAIR rated fusing Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring Tri-color Green, Amber, Red LED Status indicator per phase Red LED service indicator Audible Alarm with Silence Switch Test Function: toggles red service LED, audible alarm Redundant monitoring LEDs on modules Phase Loss monitoring (toggles LED & dry contacts) Electrically isolated circuitry ensures surges do not damage diagnostics Optional Form C Dry Contacts, 24, 1A (two sets) Optional Surge Counter, six-digit LCD, with test function, reset & no-maintenance SuperCap energy storage device TE/XGA Series Type 2 Surge Protective Device/SPD Features: UL 1449 Third Edition Listed (Sept 2009) 160kA & 240kA per phase ratings Type 2 SPD All UL required OCP & Safety Coordination included inside Can be installed load-side of main disconnect Replaceable module construction 200kA SCCRs oltage Specific Highly configurable All MO suppression elements monitored Optional Silicon Avalanche Diode (SAD) Hybrid System Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC High Energy Parallel Design for Category C3 & C-High applications For External Mounting next to Switchgear, Motor Controls Centers or Panelboards Individually Fused Suppression Modes Large-Block utility grade 34mm square MOs Replaceable Phase Module Construction Thermal Sensitivity in Each Mode Busbar Construction Solid State Bidirectional Operation Busbar connection Enclosure-less version for OEM available (XTE Series) Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 25 lbs (11.5 kg) Standard NEMA 1 (Other Enclosures Optional) Standard size: 12 x 12 x 6 (30.5cm x 30.5cm x 15cm) Lug size: #2 - #14 AWG Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 R/C UL file: ZCA.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 29

30 TE/XGA MODEL NUMBER CONFIGURATOR & OPTIONS ll / ll / XGA / ll / l... Model Family Option Suffixes (Seperated by slashes -/) TE = Transient Eliminator, Listed Type 2 SPD in NEMA 1 enclosure XTE = Transient Eliminator, Recognized Type 4 SPD on backplane for installation within gear in Type 2 installation (display on 6 cable) oltage Code for Electrical System Common North American Systems: 1 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 2 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 3 = 240/120 High Leg Delta (B High) (Fig 3) 4 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) 5 = 480 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye 8 = 600Y/347 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 11 = 120 Single Phase - 1Ø 2W + Grnd (Fig 5) 12 = 240 Single Phase - 1Ø 2W + Grnd (Fig 5) 51 = 480 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 6 = 240 Delta - 3Ø 3W+Grnd (Fig 4) 61 = 240 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 7 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 9 = 600 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye 91 = 600 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) XGA = XGA Family 160kA rating standard Enclosure Rating /240 = 240kA Option /090 = 090kA SAD option (120/240 & 208Y/120) /130 = 130kA SAD option (120/240 & 208Y/120) /170 = 170kA SAD option (120/240 & 208Y/120) /DC = Dry Contacts Two sets Form C (24, 1A) /SC = Surge Counter, six digit LCD /2S = Dual Surge Counter (12 x12 x6 - display inside door) Available Accessory (order separately): RM = Remote Monitor 04 = Standard: NEMA 1/3R/04/12 (size: 12 x 12 x 7.5 ) FM = Flush Mount Enclosure, NEMA 1 only (wall cavity size: 12 x 12 x 6 ) 4X = NEMA 4X Non-Metallic (size: 14 x 12 x 6 ) (polycarbonate, display inside clear front door) 4S = NEMA 4X Stainless Steel (size: 12" x 12"x 6") (display inside door) (Note: Enclosure-less version for OEM uses XTE prefix) Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 A B Phase B (BLK) N C Phase B (ORNG) Phase B (BLK) A (BLK) Phase SPLIT 2 Hots, 1 Neu, 1 Grnd WYE 3 Hots, 1 Neu, 1 Grnd HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd DELTA & HRG WYE 3 Hots, 1 Grnd SINGLE POLE 1 Hot, 1 Neu, 1 Grnd CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd Performance Data Common North American Systems UL 1449 THIRD Edition (Sept 2009) Test Data oltage Protection Ratings (PR - 3kA) L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 2 5kA 200kA = 208Y/120 3Ø Wye Type 2 5kA 200kA = 240Y/120 B High Leg Delta 600/ / /1500 Type 2 5kA 200kA 150 / = 480Y/277 3Ø Wye Type 2 5kA 200kA = 480 3Ø Delta Type 2 5kA 200kA = 600Y/347 3Ø Wye Type 2 5kA 200kA 420 SAD Models 01 = 240/120 Split Phase Type 2 5kA 200kA = 208Y/120 3Ø Wye Type 2 5kA 200kA 138 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA lh #8391

31 TEXRS Series Type 4 Surge Protective Device/SPD For Use in Type 1 Applications Features: UL 1449 Third Edition Listed (Sept 2009) 100kA 300kA per phase ratings UL tested and evaluated to Type 1 SPD All UL required OCP & Safety Coordination included inside Can be installed line-side or load-side of main disconnect 20kA Inominal (I n ) (most models) 200kA SCCRs (most models) UL 96A Lightning Protection Master Label 20kA I n oltage Specific Design Highly configurable All MO suppression elements monitored Display on 4 cable Performance Specifications Surge Capacities L-N L-G N-G 100kA/phase 50kA 50kA 50kA 150kA/phase 100kA 50kA 50kA 200kA/phase 100kA 100kA 100kA 250kA/phase 150kA 100kA 150kA 300kA/phase 150kA 150kA 150kA UL 1449 Third Edition Recognized, UL 1283 R/C and cul UL Type 4 for use in Type 1 Applications UL tested Inominal (I n ): 20kA & 10kA UL tested SCCR: 200kA & 100kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1000 Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring 100% monitoring Every MO is monitored, incl. N-G Green LED Status indicator per phase Red LED service indicator Audible Alarm with Silence Switch Test Function: toggles red service LED, audible alarm & dry contact (if equipped) N-G overvoltage detection Phase Loss monitoring (toggles LED & dry contacts) Electrically isolated circuitry ensures surges do not damage diagnostics Form C Dry Contacts, 240, 5A (two sets) Optional Surge Counter, six-digit LCD, with test function, reset & no-maintenance Eprom memory Installer-locatable display on 4 cable Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC High Energy Parallel Design for Category C3 & C-High applications For Mounting Internal to Switchgear, Motor Controls Centers, Panelboards or Control Panels Individually Fused & Thermally Protected MOs Large-Block 34mm square MOs Replaceable Module Construction Solid State Bidirectional Operation Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 5 lbs (2.3 kg) Standard size: 6.5 x 11 x 4.5 (16.5cm x 29.9cm x 11.4cm) Lug size: #2 - #14 AWG (w/opt. disconnect: #6 - #1/0) Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 UL file: ZCA2.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 31

32 TEXRS MODEL NUMBER CONFIGURATOR & OPTIONS TE ll XRS ll l... oltage Code for Electrical System Surge Current Rating Options Common North American Systems: 01 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 02 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 03 = 240/120 High Leg Delta (B High) (Fig 3) 04 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) 05 = 480 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye 08 = 600Y/347 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 15 = 254/127 Split Phase - 1Ø 3W+Grnd, (Fig 1) 18 = 480/277 2-Pole, (480/240 Split Phase) (Fig 1) 21 = 220Y/127 Wye - 3Ø 4W+Grnd (Fig 2) 41 = 520Y/300 Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240 Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230 Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250 Wye - 3Ø 4W+Grnd (Fig 2) 51 = 480 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 06 = 240 Delta - 3Ø 3W+Grnd (Fig 4) 61 = 240 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) 07 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 09 = 600 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye (Available: 100kA, 150kA) 91 = 600 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (Available: 100kA, 150kA) 11 = 120 Single Phase (Fig 5) 12 = 240 Single Phase (Fig 5) - Not split phase 13 = 127 Single Phase (Fig 5) 14 = 300 Single Phase (Fig 5) 16 = 277 Single Phase (Fig 5) 17 = 480 Single Phase (1 Hot, 1 Neu, 1 Grnd) (Fig 5) 10 = 100kA/Phase 15 = 150kA/Phase 20 = 200kA/Phase 25 = 250kA/Phase 30 = 300kA/Phase X = Surge Counter, six-digit LCD counter includes maintenance-free Eprom memory backup M = Mount Display on SPD instead of Cable D = Rotary Disconnect Switch, Bussman UL98, SPD & Disconnect mounted on alum. backplane (10.75 x x 4.5 ) K = Rotary Disconnect Switch, Katko UL 508, SPD & Disconnect mounted on alum backplane (10.75 x x 4.5 ) Extended Disc. Sw. handle hardware available consult factory Display on 4 Cable - other lengths available consult factory Delete Options - Consult Factory for Order Code Delete L-N Protection (reduces ka rating) Delete L-G Protection (reduces ka rating) Delete N-G Protection (reduces ka rating) Delete Noise Filtering Available Accessory (order separately) RM = Remote Monitor Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 A B Phase B (BLK) N C Phase B (ORNG) Phase B (BLK) A (BLK) Phase SPLIT 2 Hots, 1 Neu, 1 Grnd WYE 3 Hots, 1 Neu, 1 Grnd HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd DELTA & HRG Wye 3 Hots, 1 Grnd SINGLE POLE 1 Hot, 1 Neu, 1 Grnd CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd Performance Data Common North American Systems UL 1449 THIRD Edition (Sept 2009) Test Data oltage Protection Ratings (PR - 3kA) L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 1 20kA 100kA = 208Y/120 3Ø Wye Type 1 20kA 200kA = 240Y/120 B High Leg Delta 700/ / Type 1 20kA 200kA 150 / = 480Y/277 3Ø Wye Type 1 20kA 200kA = 480 3Ø Delta Type 1 10kA 200kA = 600Y/347 3Ø Wye Type 1 10kA 200kA 420 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA Optional disconnect switch may increase PRs lh #8393

33 Performance Specifications Directly Connected, Discrete Protection Elements Between All Possible Modes with True 10-Mode Protection Surge Capacities L-N L-G L-L N-G 150kA/phase 50kA 50kA 50kA 50kA 300kA/phase 100kA 100kA 100kA 100kA UL 1449 Third Edition Recognized, UL 1283 and cul UL Type 4 for use in Type 1 Applications UL tested Inominal (I n ): 20kA & 10kA UL tested SCCR: 200kA & 100kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1000 Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring 100% monitoring Every MO is monitored, incl. N-G Green LED Status indicator per phase Red LED service indicator Audible Alarm with Silence Switch Test Function: toggles red service LED, audible alarm & dry contact (if equipped) N-G overvoltage detection Phase Loss monitoring (toggles LED & dry contacts) Electrically isolated circuitry ensures surges do not damage diagnostics Form C Dry Contacts, 240, 5A (two sets) Optional Surge Counter, six-digit LCD, with test function, reset & no-maintenance Eprom memory Installer-locatable display on 4 cable TEXRL Series Type 4 Surge Protective Device/SPD For Use in Type 1 Applications Features: Directly Connected, Discrete Protection Elements Between All Possible Modes UL 1449 Third Edition Listed (Sept 2009) 150kA - 300kA per phase ratings UL tested and evaluated to Type 1 SPD All UL required OCP & Safety Coordination included inside Can be installed line-side or load-side of main disconnect 20kA Inominal (I n ) (most models) 200kA SCCRs (most models) UL 96A Lightning Protection Master Label compliant oltage Specific Design Highly configurable All MO suppression elements monitored Display on 4 cable Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC High Energy Parallel Design for Category C3 & C-High applications For Mounting Internal to Switchgear, Motor Controls Centers, Panelboards or Control Panels Individually Fused & Thermally Protected MOs Large-Block 34mm square MOs Replaceable Module Construction Solid State Bidirectional Operation Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 5 lbs (2.3 kg) Standard size: 6.5 x 11 x 4.5 (16.5cm x 29.9cm x 11.4cm) Lug size: #2 - #14 AWG (w/opt. disconnect: #6 - #1/0) Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 UL file: ZCA2.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 33

34 TEXRL 10-MODE MODEL NUMBER CONFIGURATOR & OPTIONS TE ll XRL ll l... oltage Code for Electrical System Surge Current Rating Options Common North American Systems: 01 = 240/120 Split Phase - 1Ø 3W+Grnd, (Fig 1) 02 = 208Y/120 Wye - 3Ø 4W+Grnd, (Fig 2) 03 = 240/120 High Leg Delta (B High), (Fig 3) 04 = 480Y/277 Wye - 3Ø 4W+Grnd, (Fig 2) Other Available Systems - Confirmation encouraged: 15 = 254/127 Split Phase - 1Ø 3W+Grnd, (Fig 1) 18 = 480/277 2-Pole, (480/240 Split Phase) (Fig 1) 21 = 220Y/127 Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240 Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230 Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250 Wye - 3Ø 4W+Grnd (Fig 2) 07 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) Figure 1 Figure 2 Figure 3 15 = 150kA/Phase 30 = 300kA/Phase X = Surge Counter, six-digit LCD counter includes maintenance-free Eprom memory backup M = Mount Display on SPD instead of cable D = Rotary Disconnect Switch, Bussmann UL98, SPD & Disconnect mounted on alum. backplane (10.75 x x 4.5 ) K = Rotary Disconnect Switch, Katko UL 508, SPD & Disconnect mounted on alum. backplane (10.75 x x 4.5 ) Extended Disc. Sw. handle hardware available consult factory Display on 4 Cable - other lengths available consult factory Delete Options - Consult Factory for Order Code Delete L-N Protection (reduces ka rating) Delete L-G Protection (reduces ka rating) Delete N-G Protection (reduces ka rating) Delete Noise Filtering Available Accessory (order separately) RM = Remote Monitor A B Phase B (BLK) N C Phase B (ORNG) SPLIT 2 Hots, 1 Neu, 1 Grnd WYE 3 Hots, 1 Neu, 1 Grnd HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd Performance Data Common North American Systems UL 1449 THIRD Edition (Sept 2009) Test Data oltage Protection Ratings (PR - 3kA) L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 1 20kA 100kA = 208Y/120 3Ø Wye Type 1 20kA 200kA = 240Y/120 B High Leg Delta 800/ / Type 1 20kA 200kA 150 / = 480Y/277 3Ø Wye Type 1 20kA 200kA 320 Other Available Systems - Confirmation Encouraged: 15 = 254/127 Split Phase Type 1 20kA 100kA = 220Y/127 3Ø Wye Type 1 20kA 100kA = 415Y/240 3Ø Wye Type 1 20kA 200kA = 400Y/230 3Ø Wye Type 1 20kA 200kA = 440Y/250 3Ø Wye Type 1 20kA 200kA = 380Y/220 3Ø Wye Type 1 20kA 200kA 320 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA Optional disconnect may increase PRs lh #8392

35 TEXWS Series Type 4 Surge Protective Device/SPD For Use in Type 1 Applications Features: UL 1449 Third Edition Listed (Sept 2009) 300kA 500kA per phase ratings UL tested and evaluated to Type 1 SPD All UL required OCP & Safety Coordination included inside Can be installed line-side or load-side of main disconnect 20kA Inominal (I n ) 200kA SCCRs (most models) UL 96A Lightning Protection Master Label compliant oltage Specific Design Highly configurable All MO suppression elements monitored Display on 4 cable Performance Specifications Surge Capacities L-N L-G N-G 300kA/phase 150kA 150kA 150kA 400kA/phase 200kA 200kA 200kA 500kA/phase 250kA 250kA 250kA UL 1449 Third Edition Recognized, UL 1283 and cul UL Type 4 for use in Type 1 Applications UL tested Inominal (I n ): 20kA UL tested SCCR: 200kA & 100kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1000 Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring 100% monitoring Every MO is monitored, incl. N-G Green LED Status indicator per phase Red LED Service indicator Audible Alarm with Silence Switch Test Function: toggles red service LED, audible alarm & dry contact (if equipped) N-G overvoltage detection Phase Loss monitoring (toggles LED & dry contacts) Electrically isolated circuitry ensures surges do not damage diagnostics Form C Dry Contacts, 240, 5A (two sets) Optional Surge Counter, six-digit LCD, with test function, reset & no-maintenance Eprom memory Installer-locatable display on 4 cable Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC High Energy Parallel Design for Category C3 & C-High applications For Mounting Internal to Switchgear, Motor Control Centers, Panelboards or Control Panels Individually Fused & Thermally Protected MOs Large-Block 34mm square MOs Replaceable Module Construction Solid State Bidirectional Operation Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 7 lbs (3.2 kg) Standard size: 9 x 11 x 5.3 (22.9cm x 28.0cm x 13.5cm) Lug size: #2 - #14 AWG (w/opt. disconnect: #6 - #1/0) Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 UL file: ZCA2.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 35

36 TEXWS MODEL NUMBER CONFIGURATOR & OPTIONS TE ll XWS ll l... oltage Code for Electrical System Surge Current Rating Options Common North American Systems: 01 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 02 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 03 = 240/120 High Leg Delta (B High) (Fig 3) 04 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) 05 = 480 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye (Available: 300kA, 450kA) 08 = 600Y/347 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 15 = 254/127 Split Phase - 1Ø 3W+Grnd, (Fig 1) 18 = 480/277 2-Pole, (480/240 Split Phase) (Fig 1) 21 = 220Y/127 Wye - 3Ø 4W+Grnd (Fig 2) 41 = 520Y/300 Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240 Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230 Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250 Wye - 3Ø 4W+Grnd (Fig 2) 51 = 480 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (Available: 300kA, 450kA) 06 = 240 Delta - 3Ø 3W+Grnd (Fig 4) (Available: 300kA, 450kA) 61 = 240 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (Available: 300kA, 450kA) 07 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 09 = 600 Delta - 3Ø 3W+Grnd (Fig 4) & HRG Wye (Available: 200kA, 250kA) 91 = 600 B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (Available: 200kA, 250kA) 11 = 120 Single Phase (Fig 5) 12 = 240 Single Phase (Fig 5) - Not split phase 13 = 127 Single Phase (Fig 5) 14 = 300 Single Phase (Fig 5) 16 = 277 Single Phase (Fig 5) 17 = 480 Single Phase (1 Hot, 1 Neu, 1 Grnd) (Fig 5) A B Phase B (BLK) N C 20 = 200kA/Phase (oltage Codes 09 & 91 only) 25 = 250kA/Phase (oltage Codes 09 & 91 only) 31 = 300kA/Phase 40 = 400kA/Phase 45 = 450kA/Phase (oltage Codes 05, 51, 06, 61 only) 50 = 500kA/Phase X = Surge Counter, six-digit LCD counter includes maintenance-free Eprom memory backup F = Noise Filtering - Extended Range & Attenuation M = Mount Display on SPD instead of Cable D = Rotary Disconnect Switch, Bussman UL98, SPD & Disconnect mounted on alum. backplane (14.75 x x 5.25 ) K = Rotary Disconnect Switch, Katko UL 508, SPD & Disconnect mounted on alum backplane (14.75 x x 5.25 ) Extended Disc. Sw. handle hardware available consult factory Display on 4 Cable - other lengths available consult factory Delete Options - Consult Factory for Order Code Delete L-N Protection (reduces ka rating) Delete L-G Protection (reduces ka rating) Delete N-G Protection (reduces ka rating) Delete Noise Filtering Available Accessory (order separately) RM = Remote Monitor Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Phase B (ORNG) Phase B (BLK) A (BLK) Phase SPLIT 2 Hots, 1 Neu, 1 Grnd Performance Data WYE 3 Hots, 1 Neu, 1 Grnd Common North American Systems HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd DELTA & HRG Wye 3 Hots, 1 Grnd SINGLE POLE 1 Hot, 1 Neu, 1 Grnd UL 1449 THIRD Edition (Sept 2009) Test Data oltage Protection Ratings (PR - 3kA) CORNER GROUND DELTA (B grounded) 2 Hots, 1 Grnd L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 1 20kA 100kA = 208Y/120 3Ø Wye Type 1 20kA 200kA = 240Y/120 B High Leg Delta 700/ / Type 1 20kA 200kA 150 / = 480Y/277 3Ø Wye Type 1 20kA 200kA = 480 3Ø Delta Type 1 20kA 200kA = 600Y/347 3Ø Wye Type 1 20kA 200kA 420 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA Optional disconnect may increase PRs lh #8395

37 TEXWL Series Type 4 Surge Protective Device/SPD For Use in Type 1 Applications Features: Directly Connected, Discrete Protection Elements Between All Possible Modes UL 1449 Third Edition Listed (Sept 2009) 300kA - 450kA per phase ratings UL tested and evaluated to Type 1 SPD All UL required OCP & Safety Coordination included inside Can be installed line-side or load-side of main disconnect 20kA Inominal (I n ) 200kA SCCRs (most models) UL 96A Lightning Protection Master Label compliant oltage Specific Design Highly configurable All MO suppression elements monitored Display on 4 cable Performance Specifications Directly Connected, Discrete Protection Elements Between All Possible Modes with True 10-Mode Protection Surge Capacities L-N L-G L-L N-G 300kA/phase 100kA 100kA 100kA 100kA 450kA/phase 150kA 150kA 150kA 150kA UL 1449 Third Edition Recognized, UL 1283 and cul UL Type 4 for use in Type 1 Applications UL tested Inominal (I n ): 20kA UL tested SCCR: 200kA & 100kA UL oltage Protection Ratings (PRs): 208Y/120: as low as Y/277: as low as 1000 Less than 1 nanosecond response time Repetitive Impulse: 5,000 hits AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz Diagnostic Monitoring 100% monitoring Every MO is monitored, incl. N-G Green LED Status indicator per phase Red LED service indicator Audible Alarm with Silence Switch Test Function: toggles red service LED, audible alarm & dry contact (if equipped) N-G overvoltage detection Phase Loss monitoring (toggles LED & dry contacts) Electrically isolated circuitry ensures surges do not damage diagnostics Form C Dry Contacts, 240, 5A (two sets) Optional Surge Counter, six-digit LCD, with test function, reset & no-maintenance Eprom memory Installer-locatable display on 4 cable Design Features Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C NEMA LS-1 NEC Article 285 IEC High Energy Parallel Design for Category C3 & C-High applications For Mounting Internal to Switchgear, Motor Controls Centers, Panelboards and Control Panels Individually Fused & Thermally Protected MOs Large-Block 34mm square MOs Replaceable Module Construction Solid State Bidirectional Operation Physical Specifications Relative Humidity Range: 0-95% non-condensing Operating Frequency: 47-63Hz Operating Temperature: -25 C (-15 F) to +60 C (140 F) Weight: 7 lbs (3.2 kg) Standard size: 9 x 11 x 5.3 (22.9cm x 28.0cm x 13.5cm) Lug size: #2 - #14 AWG (w/opt. disconnect: #6 - #1/0) Typical connection: #6 AWG and 60A breaker Quality, Standards & alidation UL 1449 Third Edition, cul, UL 1283 UL file: ZCA2.E at RoHS-compliant IEC 61643, CE 10 year warranty (longer optional) Burn-In tested Prior to Shipment ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification Made in USA 37

38 TEXWL 10-MODE MODEL NUMBER CONFIGURATOR & OPTIONS TE ll XWL ll l... oltage Code for Electrical System Surge Current Rating Options Common North American Systems: 01 = 240/120 Split Phase - 1Ø 3W+Grnd (Fig 1) 02 = 208Y/120 Wye - 3Ø 4W+Grnd (Fig 2) 03 = 240/120 High Leg Delta (B High) (Fig 3) 04 = 480Y/277 Wye - 3Ø 4W+Grnd (Fig 2) Other Available Systems - Confirmation encouraged: 15 = 254Y/127 Split Phase - 1Ø 3W+Grnd, (Fig 1) 18 = 480/277 2-Pole, (480/240 Split Phase) (Fig 1) 21 = 220Y/127 Wye - 3Ø 4W+Grnd (Fig 2) 42 = 415Y/240 Wye - 3Ø 4W+Grnd (Fig 2) 43 = 400Y/230 Wye - 3Ø 4W+Grnd (Fig 2) 44 = 440Y/250 Wye - 3Ø 4W+Grnd (Fig 2) 07 = 380Y/220 Wye - 3Ø 4W+Grnd (Fig 2) 31 = 300kA/Phase 45 = 450kA/Phase X F = Surge Counter, six-digit LCD counter includes maintenance-free Eprom memory backup = Noise Filtering - Extended Range & Attenuation M = Mount Display on SPD instead of cable D = Rotary Disconnect Switch, Bussmann UL98, SPD & Disconnect mounted on alum. backplane (14.75 x x 5.25 ) K = Rotary Disconnect Switch, Katko UL 508, SPD & Disconnect mounted on alum. backplane (14.75 x x 5.25 ) Extended Disc. Sw. handle hardware available consult factory Display on 4 Cable - other lengths available consult factory Delete Options - Consult Factory for Order Code Delete L-N Protection (reduces ka rating) Delete L-G Protection (reduces ka rating) Delete N-G Protection (reduces ka rating) Delete Noise Filtering Figure 1 Figure 2 Figure 3 A B Phase B (BLK) N C Phase B (ORNG) Available Accessory (order separately) RM = Remote Monitor SPLIT 2 Hots, 1 Neu, 1 Grnd WYE 3 Hots, 1 Neu, 1 Grnd HI-LEG DELTA (B High) 3 Hots, (B HIGH), 1 Neu, 1 Grnd Performance Data UL 1449 THIRD Edition (Sept 2009) Test Data Common North American Systems oltage Protection Ratings (PR - 3kA) L-N L-G N-G L-L Type I n SCCR MCO 01 = 240/120 Split Phase Type 1 20kA 100kA = 208Y/120 3Ø Wye Type 1 20kA 200kA = 240Y/120 B High Leg Delta 700/ / Type 1 20kA 200kA 150 / = 480Y/277 3Ø Wye Type 1 20kA 200kA 320 Other Available Systems - Confirmation Encouraged: 15 = 254/127 Split Phase Type 1 20kA 100kA = 220Y/127 3Ø Wye Type 1 20kA 100kA = 415Y/240 3Ø Wye Type 1 20kA 200kA = 400Y/230 3Ø Wye Type 1 20kA 200kA = 440Y/250 3Ø Wye Type 1 20kA 200kA = 380Y/220 3Ø Wye Type 1 20kA 200kA 320 Other Available Systems: Please see supplementary data sheet, contact us at info@aptsurge.com, or confirm at using CCN of ZCA Optional disconnect may increase PRs lh #8394

39 TWL Series Datasheet Tower Light Controller Protectors Also See TWL Configuration Sheet Features: TWL is a Central Bonding/Grounding Hub intended to reference individual-load SPDs to the same ground. Referencing all load SPDs to the same ground is a significant challenge to tower surge suppression. TWL solves that. Cover in place Side view Cover removed Note: For demonstration purposes, the standard TWL pictured above is displayed with SPDEE and XCS SPDs and representative copper strap ground busing. TWL is predrilled on all four sides for 4 copper ground strap connection to the tower s earth/ground system. Strap conductors minimize inductive voltage drops associated with traditional round wire conductors, thus ensuring superior performance. MODULAR: TWL is intended for use with APT XCS, SPDEE, and DIN-Rail SPDs. These are standard offthe-shelf SPDs for ease of service, UL Compliance, flexibility, cost-control and obsolescence-avoidance, ordered separately based on individual project needs. TWL is infinitely configurable to virtually any tower configuration. TWL is also expandable should needs change. TWL includes no SPDs. SPDs must be ordered separately. TWL includes two rows of 35mm DIN Rail with UL Recognized Feed-Through and Grounding terminal blocks. An AC Power XCS-series SPD is intended for installation in the center of the TWL to protect the Tower Light Controller. Individual SPDEE SPDs are intended to mount on the sides of TWL. DIN Rail SPDs for photocell(s) are also mounted on DIN rail. These connect and ground via the internal TWL terminal blocks onto a tin-plated aluminum backplane. Individual tower lights & loads feed-through the terminal blocks.spds are connected to those terminal blocks. The SPDs are parallel-connected, thus eliminating problems of series-connected SPDs (small surge current capacity, dwarf -size components, disconnecting load if SPD fails, etc.) Physical Specifications: Wire Range: 10 AWG 22 AWG Relative Humidity Range: 0-95% non-condensing Operating Frequency: DC - 400Hz ( selected SPDs may be frequency - specific) Operating Temperature: -40 C (-40 F) to +100 C (212 F) (excludes SPDs) Weight: 13 lbs (5.9 kg) (excluding SPDs) NEMA 1 Metallic Enclosure Overall Dimensions: 14 x 12 x (excluding SPDs) Enclosure Dimensions: 12 x 12 x 6 Indoor use (outdoor use within a larger weather-resistant enclosure) Design Features: Designed, Manufactured & Tested consistent with: ANSI/IEEE C , C , and C UL 96A, NFPA 780 Lightning Protection Stds High Energy Parallel Design Tin-plated Aluminum backplane Quality & alidation: UL Recognized Terminal Blocks 10 year warranty ISO 9001:2008 Quality Management System ISO 17025:2005 Laboratory Qualification RoHS-compliant Made in USA 39

40 TWL Installation Overview: TWL is a grounding hub. The objective is to provide SPDs for each protected circuit and give those SPDs a common reference point to ground. (If SPDs are grounded to different locations, those different locations can/will provide voltages differentials, which cause problems.) Existing tower wiring bundle enters the TWL, is connected to Terminal Blocks which connect to SPDs, then the wiring bundle leaves the TWL. TWL is configured to be easy to install and service. TWL1 Assembly Includes: Tin-plated aluminum backplane pre-attached to NEMA 1 style metallic enclosure with metallic lid & label. Multiple knockouts on four sides. Four pre-drilled 1 holes positioned for APT SPDee SPDs with four blank-hole-covers Stand-off mounting studs pre-positioned for APT XCS SPD Two ½ /13 x 1 stainless steel bolts & washers for ground strap connection Two pre-attached std 35mm DIN Rails Tri-Connect UL Recognized Feed-through connection hardware for up to eight (8) typical SPDs as follows Power Feed-thru Terminal Blocks Neutral Feed-thru Terminal Blocks Ground Terminal Blocks Separator/End Blocks AC Power SPD (assumes split-phase): SPD# SPD# SPD# SPD# SPD# SPD# SPD# SPD# Spares TOTAL TWL-Z1 Spares/Accessory Kit (additional Terminal Blocks): Includes 10 additional Power Feed-thru, 10 Neutral Feed-thru, 20 Ground and 5 Separator End Blocks SPDs Not Included and Ordered Separately: XCS & SPDEE SPDs are Type 1 UL 1449 Listed SPDs with 20kA Nominal Discharge Current Ratings (L-N) as required per UL 96A and NFPA 780 Lightning Protection standards. These are robust SPDs having arrestor-grade surge current performance with low clamping voltages. See separate datasheets for individual SPDs. Also see TWL Configuration Sheet. Call APT for Help at (800) (Knowing voltages and number of circuits is useful.) lh

41 BNCB5kA Coax In-Line Surge Protective Device/SPD Features: Primary Protector Kit for Coaxial Communication Lines Includes SAFFF UL 497C Listed Coaxial SPD Includes two F to BNC connectors for BNC applications Coaxial Gas Discharge Tube (GDT) Technology Protects personnel and equipment from lightning and power induced overvoltage surges Performance Specifications: Breakdown oltage: Maximum Operating oltage: Maximum Signal Current: I max Surge Current Rating (8/20μs): Analog Frequency Range: SPD Insertion Loss: Response Time: Listing: mA 5kA DC-1GHz 0.2 db typical <25ns UL 497C Physical Specifications: Intended for use within a weather-resistant enclosure Relative Humidity Range: 0-95% non-condensing Operating Temp: -40 C (-40 C) to +176 F (+80 C) Weight: 0.2lbs (56g) (excluding BNC conn.) Length: 3.0 (76mm long) Metallic Case Female F Connectors Two (2) F-BNC connectors included Pin-Grounded Shield Mode of Protection Grounding: Requires reliable ground SPD may be grounded via its legs with screw connections, or via screw terminal that accepts up to 8 AWG (wire and attachment screws not included) Intended Application: Primary Protector at Service Entrance for life safety protection from power line crosses and lightning. SAFFF is UL 497C Listed (QKC.E303380) Suitable for use in UL 96A Master Label Lightning Protection System Per regulatory & industry convention, cascaded SPDs provide maximum protection. An additional Secondary SPD is highly recommended for critical electronics applications. Additional standards and regulatory explanation & data available at XYZ Design Features: Designed, Manufactured & Tested consistent with: IEEE C IEEE C IEEE C , C & C62.45 IEC Integral Fail-Short Mechanism Quality, alidation: 5 year warranty (longer optional) UL 497C Listed (QKC.E303380) APT employs an ISO 9001:2008 Quality Management System Installation: SPD is bidirectional; not direction-sensitive. Industry Best Practices recommend SPDs at both ends of cabling and/or cascade protection. SPD must be connected to a reliable ground via screw-down connection or ground wire (or both). Locate SPD such that ground lead is as short and straight as possible. Inches matter! Connect to a reliable ground, which should be the same ground reference for power and Pan-Tilt-Zoom (if equipped). SPD redirects damaging energy to ground. If equipment/spd are atop tall pole, the long path to earth ground adds inductive impedance and may affect performance This SPD intentionally short-circuit the line when failed. Remove SPD, and test system. If system operates normally, replace SPD. If signal quality decreases when SPD is installed, most likely cause is a ground loop. Disconnect ground lead, and test system. If system operates normally, contact APT for BNCA10kA, which has ground isolation circuitry lh #

42 BNCA10kA BNC In-Line Coax Surge Protective Device/SPD Top iew Features: The BNCA10kA is a premium SPD intended for Severe Service at BNC coaxial connections for video equipment such as CCT cameras. Bottom iew Performance Specifications: Nominal Operating oltage: 5 Maximum Operating oltage: 8 Maximum Signal Current: 300mA I max Surge Current Rating (8/20μs): 10kA Clamping oltage (Pin-Shield): 8/20μs, 5kA: /700μs, 1k: 14.7 Digital Transmission Rate: 10Mbps Analog Frequency Range: 0-10Mhz Insertion Loss: 0.5dB@10MHz Response Time: <1ns Connection Type: BNC, 50 / 75 ohm Discrete Modes of Protection: Pin-Shield, Shield-Ground Quality & alidation: RoHS - compliant 5 year warranty (longer optional) Individually Tested Prior to Shipment APT employs an ISO 9001:2008 Quality Management System The BNCA10kA SPD features Three Stage Series Hybrid Surge Protection Primary Course Protection: Gas Discharge Tubes (GDTs) Series Current Limiting Component Secondary Fine Protection: Silicon Avalanche Diodes (SADs) Easy to Install, Din Rail Mounting Bracket Included Design Features: Designed, Manufactured & Tested consistent with: IEEE C IEEE C IEEE C , C & C62.45 IEEE Location Categories C, B and A NFPA 780 Lightning Protection IEC Shield - Ground Isolation: The BNCA10kA includes separate protection modes for Pin to Shield and Shield to Ground. This prevents SPD ground loops and possible signal interference caused if a long run of cable references a different ground than the head-end ground. Physical Specifications: Intended for use within a weather-resistant enclosure Relative Humidity Range: 0-95% non-condensing Operating Temp: -40 C (-40 C) to +176 F (+80 C) Weight: 0.25lbs (100g) Dimensions: 3.35 (85mm long) x 1 square (25mm) Pre-wired with 2 (60cm) of #12 AWG ground conductor (User to cut to shortest length possible) Anodized Extruded Aluminum Case; metallic bracket BNC gender changers are available Installation: This is a directional, in-line series-connected SPD. PROTECTED end of SPD must be at equipment or camera end. UNPROTECTED end must be at cable end. Industry Best Practices recommend SPDs at both ends of cabling. Grounding: Locate SPD such that Ground lead is as short and straight as possible. Connect to a reliable ground, which should be the same ground reference for power and Pan-Tilt-Zoom (if equipped). Trim Ground lead as appropriate. Inches matter! Do not coil excess lead - cut off excess lead. Crimp-attach included wire terminal and connect to reliable ground. Din-rail bracket does not electrically ground this SPD. SPD attachment to Din-rail is not mandatory. All applicable Code(s) and regulation(s) must be followed. If SPD problems are suspected, remove SPD, and test system. If system operates normally, replace SPD lh #8540

43 Protecting Coax Cables from Surges Most surges on coax originate on the shield, not the pin. In a coax application, the pin is protected by the shield. For example, lightning induces onto the shield, as would accidental contact with a power line. Consequently, excessive emphasis on protecting the pin may be misguided. According to IEEE C62.43 research: Surge current injected equally onto the pin and shield will distribute unequally. Due to inductance, the shield will carry about four times more surge current than the pin. Surge propagation speed is faster on the shield than the pin, leading to voltage differentials between pin and shield on long runs of coax cable. Coax surge protection is different than AC power surge protection: Focus is on the grounded shield conductor as opposed to the active conductor. (On AC systems, focus is usually on the energized conductor.) MO suppression components may degrade signal quality due to higher capacitance. Primary & Secondary SPDs are intended for use together in a cascade arrangement Irony: People routinely protect AC circuits with sizeable cascade SPDs, but won t do it with coax, despite smaller SPDs and sometimes a more difficult environment. Cascade SPDs as appropriate. Concept of Cascade Protection Secondary SPD (UL 497B) with better clamping performance to better protect Primary SPD (UL 497C) for life safety purposes to protect against Power line cross or direct stroke UL 497 Listing categories are often misunderstood: UL has two generalized categories for Communication SPDs: Primary and Secondary Protectors Primary Protectors: e.g., UL 497, UL 497C. Primary protectors are intended to suppress abnormal overvoltage conditions that may exist on the circuit due to accidental contact with electric light or power conductors operating at or over 300 to ground. Translation: These are more intended for life safety protection from power line crosses & lightning, and may not clamp low enough to protect sensitive electronics. Secondary Protectors: e.g., UL 497A, UL 497B. Secondary protectors are intended to suppress abnormal voltage and/or current conditions that bypass the primary protector. Translation: Secondary Protectors offer better clamping protection for sensitive electronics. Hiccup?: There are single SPDs having the robust componentry of Primary SPDs and the lower and better clamping performance of Secondary SPDs. However, by quirk, the lower clamping voltage and better performance prevents them from passing UL s testing as a Primary Protector. The resulting confusion factor is one reason why various manufacturers do not UL List coax SPDs. Note that UL 96A Lightning Protection applications mandate a UL 497C unit. Good practice suggests an additional Secondary Protector to protect sensitive electronics. SECONDARY SPD PRIMARY SPD SPD SPD BUILDING SPD SPD COAX CABLE Hiccup: Ground Loops and resulting signal loss Coax cable shields are grounded at their head-end. The shield is not supposed to be grounded further downstream. Reason: If the shield is grounded at multiple locations, and those grounds are at different potentials, then current will loop through the shield as the ground potentials attempt to equalize themselves. This is called a Ground Loop, and can/will cause signal decay. Avoiding Ground Loops Away from the head-end, if the SPD s shield protection is directly connected to ground, it can/will cause a ground loop. Different SPD technology with ground isolation is required to prevent this. The APT XYZ SPD will not cause ground loops. SPD Head-End Coax Shield is Referenced to Ground If remote SPD shield is hard-grounded and there is a voltage between the two grounds, then a Ground Loop is likely. An SPD with ground isolating qualities is required (APT XYZ). COMMUNICATION EQUIPMENT SPD COAX CABLE If these two grounds have a voltage difference, and the coax Shield can complete the circuit, then current will flow through the Shield creating a Ground Loop., Inc th Street North, Clearwater, Florida

44 Popular Traffic / ITS Low oltage DIN Rail SPDs In-Line, Series-Connected Premium SPDs intended for use on a wide range of low voltage applications inside appropriate enclosures, including high speed communication circuits. Terminals are finger-safe. SPDs include three stage high-energy surge suppression in a Pi (π) configuration: 1st Stage: Parallel-connected Gas Discharge Tubes 2nd Stage: Series-connected impedance 3rd Stage: Parallel-connected Transorbs Each SPD Protects Two (2) Pairs of Wire UL 497B Recognized UL File: QGQ.E Circuit schematic printed on side of SPD Dual Grounding: Ground Wire Lug (recommended) Through DIN Rail Connection Two or Four Wire Data Lines such as Camera PTZ or ehicle Detectors Low oltage Power Protection Application RS-232 RS423 RS-422 RS DC 24DC 24AC 30DC 48DC 60DC Model Number RS232/D1 RS423/D1 RS422/D1 RS485/D1 12DC/D1 24DC/D1 24AC/D1 30DC/D1 48DC/D1 60DC/D1 Protocol Operating oltage +/- 25 +/ DC 24DC 24AC 48DC 48DC 60DC SPD Max Cont Op olt (MCO) 28DC 15DC 15DC 15DC 15DC 28DC 36AC 52DC 52DC 64DC Clamping oltage (DC) <46 <27 <27 <27 <27 <46 <60AC <85 <85 <27 Typical Breakdown oltage (DC) AC Maximum Leakage Current (μa) 5μA 5μA 5μA 5μA 5μA 5μA 5μA 5μA 5μA 5μA Other Applications: Other Low oltage: See D60401 Series data sheets BNC: See BNCA10KA or BNCB5KA data sheets 120: See AC DIN Rail data sheets Specifications & Features: Surge Current Rating: 15kA Rated Operating Current I L (ma): 800mA Number Wires Protected: up to 4 wires (2 pair) Wire Size: 14 AWG - 26 AWG Response Time (ns): <1 ns Mounting Type: 35mm DIN rail Temperature Rating: -40 F to 176 F (-40 C to 80 C) Enclosure Material: Thermoplastic UL 94-0 Enclosure: NEMA 1 (IP 20) Dimensions: 3.9 x 2.6 x 0.47 (99mm x 65mm x 12mm) Weight: 4.75oz (135g) Thermal Protection: Yes Color: Gray IEEE C , Cat C, B & A: Yes IEC Compliant: Yes IEC Max. Discharge Current Imax (8x20μs): 15kA IEC Max. Discharge Current In (8x20μs): 10kA IEC Max. Lightning Pulse Iimp (10x350μs): 2.5kA CE Mark: Yes Easy to Install: In-line series connected SPD. Normal signal goes through this unit. Unprotected side Install such that surge hits this side Dimensions: s: 0.47 in. (12 mm) Protected side Camera, MDS, widget, etc. Ground Lug internally connects to tab contacting DIN Rail. We recommend cable connection from Ground Lug to erified Ground. Weight: 4.75oz (135g) 3.9 in. 80 mm 2.56 in. (65 mm) lh #8632

45 STFB Series Three Phase Fuse Kit for Medium oltage Surge Protective Device The STFBB5K15A is a stand-alone, 3 phase fuse kit that is designed to be installed on the line side of, and in-line with, the STM and STMT Medium oltage SPDs. The STFBB5K15A is designed to safely disconnect the SPD from the electrical system in the event of a SPD failure without taking the customer s equipment offline. The STFBB5K15A enclosure is rated NEMA 4X (indoor or outdoor applications) and is intended for surface mounting on a flat vertical surface. The enclosure dimensions (excluding mounting feet) are 18 x 16 x 10 (47.6 cm x 35.6 cm x 27.9 cm) and weighs 35 lbs (15.9 kg). Specifications Enclosure Dimensions: 457.2mm X mm X 254mm (18 x 16 x 10 ) Weight: 15.9 kg (35 lbs) Maximum oltage: 5500AC Maximum Current: 15 Amp Recommended Wire Size: Phase Wires: #8 AWG 1/0 AWG Ground Wires: # 14 AWG 1/0 AWG Torque: 80 Inch-Lbs Design Features Designed to be installed in front of, and in-line with APT s STM and STMT Series Medium oltage SPD NEMA 4X Polycarbonate Enclosure with Stainless Steel Lockable Latches All Connecting Wires Included 2.4m (8 ft) of #6 AWG, 25k Wire each (3 Phase, 1 Ground) Additional 6k sleeving on each wire for added safety 2 1 ¼ threaded hubs included to enter and exit enclosure 45

46 SURGE COUNTER A SURGE COUNTER B SURGE COUNTER C HIGH OLTAGE STFB Series Three Phase Fuse Kit for Medium oltage Surge Protective Device Installation Instructions WARNING IMPORTANT PLEASE READ WARNING Safety First Hazardous oltage & Shock Hazard Only qualified licensed electricians should install or service the STFB Series Hazardous voltages may exist within the STFB Series The STFB Series should never be installed or serviced when energized! Use appropriate safety precautions including Personal Protection Equipment Failure to follow these instructions will result in death, serious injury, and/or equipment damage. The STFBB5K15A Fuse Kit includes the following: QTY DESCRIPTION 1 NEMA 4X Enclosure with 3 fuses installed, Bussman model 5.5CA15E (5.5k, 15A) 3 Phase conductors, 8 ft. (2.4cm) each, #6 AWG 25k rated conductors, with insulated sleeve 1 Ground conductor, 8 ft. (2.4cm) each, #6 AWG THHN PRE-PLAN YOUR INSTALLATION. YOU WILL NEED TO ACCOMPLISH THE FOLLOWING: Meet all National and Local codes. erify that all power circuits are de-energized and locked out. Coordinate the installation and location of the STFBB5K15A with the STM or STMT Medium oltage SPD. Mount the STFBB5K15A as close to the SPD as possible to keep lead lengths to a minimum. The SPD and Fuse Kit should be installed as close as possible to the point of connection with the electrical distribution system. Excessive overall wire length, from the SPD, through the fuse kit, to the point of connection with the electrical distribution system will adversely affect the performance of the SPD. Plan the installation that will result in the shortest possible overall lead length. INSTALLATION 1. Mount the enclosure using the hardware provided along with conduit and other fittings as needed. 2. Thread the 3 Phase and 1 Ground conductors from the SPD through top hub and connect to the Phase and Ground lugs inside the STFBB5K15A. Remember to keep the leads as short as possible. 3. Thread the 3 Phase and 1 Ground conductors provided with the fuse kit through the bottom hub and connect to the Phase and Ground lugs on the opposite end of the fuse. 4. Connect the other end of the 3 Phase and 1 Ground conductors to Phase A, B, C and Ground Note: Each conductor from the SPD will be labeled A, B or C. Be sure A, B & C Phase conductors from the SPD are connected to Phase A, B & C at the point of connection with the electrical system. MAINTENANCE, TROUBLESHOOT AND SERICE The STFBB5K15A requires no regular maintenance or servicing. If the STFBB5K15A is connected to a STM or STMT Series SPD that does not include the monitoring feature we suggest testing the fuses during any scheduled shutdown periods. When connected to STM or STMT Series SPDs with the monitoring option, a failure indication (light out) could mean any of the following: 1. Grounded Phase 2. Phase Loss 3. Failed SPD Only a failed SPD will blow the fuse. Blown fuses should be replaced with the same make, model and amperage. Do not replace with fuses under 15A, due to the possibility of inadvertant nuisance tripping from everyday surges, or fuses rated 200A and higher which may not properly disconnect the SPD from the electrical system in the event of an SPD failure. If you need assistance troubleshooting a failure indication on a STM or STMT Series SPD please refer to the SPD manual or contact APT Support at or info@aptsurge.com FIG 1 - Represents a typical view of an SPD and fuse kit installed on the back of a switchgear or control panel. A B C Switchgear / Control Panel (view from behind switchgear) lh 46

47 M Series Medium oltage Surge Protective Device Medium oltage Parallel Suppressor designed for Oil & Gas, Water, Chemical, Large Industrial & Heavy Duty Applications at Service Entrance, Distribution and Individual Equipment. Specifications Available Surge Current Ratings 120kA per phase Proven large block 40mm MO Technology Protection Modes: All Modes L-L & L-G (Normal mode & Common mode) Directly connected MO suppression elements NEMA 4 (IP66) Heavy Gauge Steel Enclosure Dimensions 31cm (12 ) X 31cm (12 ) X 15.5cm (6 ) Weight: Without monitoring: 29.5kg (65 Lbs) With monitoring: 34.5kg (75 Lbs) Relative Humidity Range: 0 100% Non-Condensing Operating Frequency: 50Hz, 60Hz Operating Temperature: -40 C (-40 F) to +85 C (+185 F) Quality, Standards & alidation Seven (7) Year Warranty on SPD One (1) Year Warranty on Diagnostic Instrumentation Every unit Burn-in Tested Prior to Shipment ANSI/IEEE C62.11 APT s Quality Management System is ISO 9001:2008 Certified Design Features Low clamping voltage for maximum equipment protection Parallel design MO suppression allows installation flexibility Bi-directional operation for positive & negative surges) Solid state, fully automatic action & reset Intended for High Energy applications including all IEEE C Category A, B & C High Applications Pre-wired with 5 feet (1.3 Meters) #6 stranded leads Includes internally threaded conduit hub External Mounting Flanges Inorganic silica particle encapsulation Noncombustible at extreme temperature Superior gaseous expansion tolerance Double insulated against ground fault or arcing with separate polypropylene and polyethylene layers Elastomeric Ceramgard potting protects against environmental contaminants Fusing - coordinate to electrical system High oltage warning labels standard Optional Monitoring Package Allows for on-site or remote monitoring of suppression circuits Indicator lights for each phase Dry Contacts for each phase 47

48 M Series Medium oltage Surge Protective Device MODEL SERICE OLTAGE MCO ST10M 1000AC 1200AC ST15M 1500AC 2000AC ST20M 2000AC 2400AC ST25M 2500AC 3400AC ST30M 3000AC 4000AC ST36M 3600AC 4800AC ST41M 4160AC 5600AC Example Part Number: ST41M1204D = 4160, 120kA per phase, NEMA 4 Enclosure, Monitoring Package Included. ST 4 1 M D 10 = = = = = = = 4160 OLTAGE CODES SERIES DESIGNATION M = Non-Modular, Fixed oltage, Medium oltage SURGE CURRENT RATINGS 12 = 120kA per phase ENCLOSURE RATINGS 04 = NEMA 4 D = AAILABLE OPTIONS Monitoring Package: Indicator lights per phase & dry contacts per phase Note: Monitoring Package available only on 120kA per phase models lh 48

49 What Electrical System Is It? Based on secondary side of upstream transformer, NOT by how load is connected Most SPD/TSS miss-orders are misunderstandings related to grounding or neutrals Grounded system means that the system is referenced to ground, NOT that there is a safety ground By convention, ground wires are not counted as one of the wires (3-wire, 4-wire, etc.) 3-phase 4-wire Grounded Wye Neutral bonded to ground Neutral pulled into facility Common system configuration = 120 (20BY/120) APT 2 = 277 (4BOY/277) APT 4 = 347 (600Y/347) APT B = 127 (220Y/127) APT 21 (non-usa) = 220 (3BOY/220) APT 7 (non-usa) Resistive or Impedance Grounded Wye Neutral bonded to ground via grounding resistor Neutral may, or may not, be pulled into facility Becoming popular system on high-tech = 120 (20BY /120) Rare - Call = 277 (4BOY/277) APT 5 = 347 (600Y/347) APT 9 Single-Phase erify where Neutral and Ground are! Often for one leg or one piece of equip. Neutral bonded to ground Less common than perceived! = 120 APT 11 = 240 APT 12 = 277 APT 16 = 4BO APT 17 Call - almost always different = 127 APT 13 (non-usa) = 220 APT 12 (non-usa) Hi-Leg Grounded Delta Neutral bonded to ground Neutral often pulled into facility Common system configuration = 120/240 APT 3 = 240/4BO Call 3-phase 3-wire Corner Grounded Delta System has reference to ground because B phase is grounded = 240 APT 61 = 4BO APT 51 = 600 APT 91 Note NEC 2B5.3(2) Occasionally seen at industrial facilities, normally not used on new construction 3-phase 4-wire Grounded Wye Neutral bonded to ground. Neutral NOT pulled into facility. Common system configuration at MCC, pumping and water treatment = 120 (20BY/120) APT 2 = 277 (4BOY/277) APT 4 = 347 (600Y/347) APT B = 127 (220Y/127) APT 21 (non-usa) = 220 (3BOY/220) APT 7 (non-usa) 3-phase 4-wire Ungrounded Wye Neutral NOT bonded to ground. Neutral mayor may not be pulled into facility. Rare system configuration; Error/miss-wire?. Note NEC 2B5.3(2), = 120 (20BY/120) Rare - Call = 277 (4BOY/277) APT 5 = 347 (600Y/347) APT 9 = 127 (220Y/127) Call (non-usa) = 220 (3BOY/220) Call (non-usa) Split-Phase Single-Phase Neutral bonded to ground. Neutral usually pulled into facility. ery, very Common = 120 (120/240) APT 1 = 240 (240/4BO) Rare - Call = 127 (127/254) APT 15 (non-usa) 3-phase 3-wire Ungrounded Delta System has no reference to ground L-L voltages fixed by transformer, but LG voltages can vary; Known to become unstable. = 240 APT 6 = 4BO APT 5 = 600 APT 9 Note NEC 2B5.3(2) Common system configuration at older industrial facilities, normally not used on new construction Open Delta 3-phase 3 or 4-wire Could be ungrounded, corner grounded or Hi-leg ery rare, tend to be rural arious solutions, Call for info Protecting the electronic world from surges th Street North, Clearwater, Florida (727) (800) Fax (727) info@aptsurge.com 49

50 Why Do I Need Surge Protection? WHAT IS A SURGE? An extremely brief spike of current and voltage which can damage distribution equipment such as motors and sensitive electronics. WHAT CAUSES SURGES? Externally generated surges can come from utilities, source switching (smart grid, capacitor banks), lightning and other power disturbances from the outdoor environment. Internally generated surges can result from any reactive loads that switch on and off. Examples are compressors, AC handlers, large pumps, motors and more. WHAT KIND OF DAMAGE IS CAUSED BY A SURGE? Disruption: Cost of downtime while equipment is reset, bad data transfer which can disrupt the operation. Degradation: Surges slowly cause damage to electrical components. This is referred to as electronic rust and it causes a shortened lifespan of the equipment. Destruction: Large surges from outside the facility can burn up sensitive microprocessors and motors. In extreme cases, this can cause the equipment to smoke or catch fire. HOW DO I TELL IF MY EQUIPMENT HAS SURGE DAMAGE? Frequent computer lock-ups Equipment shut-downs Flickering lights Blown ballasts Shortened lifespan WHY SHOULD I INEST IN SURGE PROTECTIE DEICES? SPDs are a cost effective solution that are far less expensive than the cost replacement equipment and labor involved in replacing damaged equipment. WHY APT? APT is a privately-owned company based in Clearwater, FL. We ve been manufacturing American-made SPDs for over 27 years. When you call us, you re dealing directly with the factory and SPD experts who will help you find the best application for your installation. If you suspect you re dealing with a surge problem, call APT today at We will help you design a custom SPD package for your facility so that your valuable equipment is protected. 50

51 Frequently Asked Questions WHAT IS SPD? SPD is an abbreviation for Surge Protective Device. A SPD is a device that attenuates (reduces in magnitude) random, high energy, short duration electrical power anomalies caused by utilities, atmospheric phenomena, or inductive loads. Such anomalies occur in the form of voltage and current spikes with a duration of less than half an ac cycle. These high energy power spikes can damage sensitive electronic equipment, such as computers, instrumentation, and process controllers. WHERE ARE SURGE SUPPRESSORS INSTALLED? AC surge suppressors are typically installed in these three areas: 1. at a utility service entrance for protection of an 1. entire facility. 2. in distribution panelboards and switchboards for 2. protection of sensitive downstream loads. 3. connected to a wall outlet for individual protection of 3. a specific piece of equipment, such as a computer or 3. solid-state controller WHAT FEATURES SHOULD BE CONSIDERED WHEN SELECTING A SURGE SUPPRESSOR? Two important areas to consider during the selection of a surge suppressor are performance and safety. The performance of a surge suppressor is measured in surge current capacity and clamping voltage. Safety should also be a priority in this selection process. The individual suppression circuit should be fused to clear an inoperative MO during an extreme transient event, and provide overcurrent protection for the surge suppressor during a fault condition. SPACE IS A CONCERN, DOES APT OFFER SOLUTIONS FOR DIN RAIL APPLICATIONS? Yes. APT offers a wide range of DIN Rail SPD solutions. Our AC products range from 120 to 600. In addition we have a series of DC and low voltage DIN Rail surge suppressors as well. Our SPDee product is also Din Rail mountable. I AM A SYSTEMS INTEGRATOR AND BUILD CUSTOM FABRICATIONS. WHAT DOES APT OFFER THAT WOULD PROTECT MY SOLUTIONS? We have a hard wired SPD solution for every type of panelboard, switchgear, motorcontrol and PLC application. Within our line of products, we offer external, internal, modular and non-modular configurations as well. We also custom design. WHAT SURGE CURRENT CAPACITY IS REQUIRED? Surge current capacity is dependent on the application and the amount of required protection. The selection of the proper surge suppressor is not an exact science and cannot be scientifically calculated from a standard algorithm. Questions to consider when specifying the proper surge current capacity for surge a surge suppressor include: What is the geographic location of the facility and its susceptibility to lightning? (For example, Florida is a high-lightning area; California is a low-lightning area.) Is the facility in a rural or urban setting? Is the facility the tallest building around? Is the facility at the end of the utility grid? If it is an existing facility, what is its power quality history? DOES APT OFFER TSS PRODUCTS FOR RENEWABLE ENERGY APPLICATIONS? Yes. APT offers a variety of solutions that can accommodate both the needs of the Wind and Solar markets. WHAT ARE YOUR STANDARD LEAD-TIMES? Our normal ship date is no more than 10 days from the receipt of the purchase order on custom builds, and same day shipping for the most common modular and nonmodular inventory units ordered before 2:00 pm EST. WHY WOULD I BUY FROM APT? As a leading manufacturer of quality U.S. made products, our highly trained design engineers have designed TSS products that are of high quality, low in cost and contain the highest level of performance and safety features! You are working directly with the manufacturer. Who knows our product better than we do! 51

52 INDUSTRIAL & SPECIALTY SALES USA DANA PAPALARDO APT Industrial & Specialty Sales Manager x 203 MATT SMITH APT Industrial & Specialty Sales x 232 ROBBY GRAHAM APT Industrial & Specialty Sales x 210 RICK SOUSA APT Industrial & Specialty Sales x 241 AMY WELGE APT Industrial & Specialty Sales Admin. x lh

Protecting the electronic world from surges

Protecting the electronic world from surges Protecting the electronic world from surges 2016 SPD PRODUCT CATALOG Surge Protective Devices www.aptsurge.com 1.800.237.4567 info@aptsurge.com Table of Contents SPD Sizing Chart...5 Type 1 and Type 2

More information

Surge Protection Solutions. Industrial Market Automation Market OEM Market

Surge Protection Solutions. Industrial Market Automation Market OEM Market Surge Protection Solutions Industrial Market Automation Market OEM Market ASCO Power Technologies is Combining the Surge Protection solutions of Advanced Protection Technologies, EDCO, Islatrol & Emerson

More information

BSPD Surge Protective Devices

BSPD Surge Protective Devices BUSSMANN Supersedes December 2016 SERIES BSPD Surge Protective Devices High capacity Type 1 and Type 2 SPDs for overvoltage protection on Contents Description Page Introduction 2 Applications 2 Features

More information

White Paper National Electrical Code (NEC) Requirements for Surge Protective Devices

White Paper National Electrical Code (NEC) Requirements for Surge Protective Devices White Paper National Electrical Code (NEC) Requirements for Surge Protective Devices National Electrical Code (NEC) Requirements for Surge Protective Devices In the United States, The National Electrical

More information

Architecture - Engineering - Planning

Architecture - Engineering - Planning Architecture - Engineering - Planning www.mkcinc.com Mansfield, Ohio New Philadelphia, Ohio Powell, Ohio 419-525-1102 - phone 330-364-8871 - phone 740-657-3202 - phone 419-525-1428 - fax 330-343-3075 -

More information

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Part 1 General 1.01 Summary A. These specifications describe

More information

GE TR7000 Series Wall Mounted Surge Protective Device (SPD)

GE TR7000 Series Wall Mounted Surge Protective Device (SPD) Digital Energy Power Quality Product Specification GE TR7000 Series Wall Mounted Surge Protective Device (SPD) Medium Exposure - Rated 65kA to 100kA Per STANDARDS UL 1449 3rd Edition UL 1283 UL 96A CSA

More information

Surge Protection Devices (SPD)

Surge Protection Devices (SPD) TPS3 03 TPS3 03 is a UL 1449 3rd Edition, cul 50 ka Type 1 (Type cul) compact Surge Protective Device. For cul applications, the TPS3 03 can be used as a secondary surge or lighting arrestor alternative

More information

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC. [Refer to Engineering Notes at End of Spec] Section [16XXX] [264XXX] - SURGE PROTECTIVE DEVICES (SPDs) PART 1 - GENERAL 1.1 SCOPE A. This section includes Surge Protective Devices (SPDs) for low-voltage

More information

Surgelogic Surge Protective Device I-Line Plug-On Unit Series

Surgelogic Surge Protective Device I-Line Plug-On Unit Series Surgelogic Surge Protective Device I-Line Plug-On Unit Series Catalog 1310CT0201R5/07 2007 Class 1310 CONTENTS Description Page Product Description.................................................. 2 Application

More information

Total Home Surge Protection for Point-of-Entry. FirstSurge TM. User Manual - Canada (English)

Total Home Surge Protection for Point-of-Entry. FirstSurge TM. User Manual - Canada (English) Total Home Surge Protection for Point-of-Entry FirstSurge TM User Manual - Canada (English) www.siemens.ca/surge Introduction Thank you for choosing the Siemens FirstSurge Residential Surge Protective

More information

Introducing. From Advanced Protection Technologies, Inc.

Introducing. From Advanced Protection Technologies, Inc. Introducing From, Inc. 2008 NEC Adoption and UL 1449 Reision hae changed the surge suppression industry. Arrestors and TVSS are now ealuated and listed under the Surge Protectie Deice (SPD) umbrella. Most

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

Surge Protective Devices (SPD)

Surge Protective Devices (SPD) Surge Protective Devices (SPD) SPEEDFAX TM 2017 Section c o n t e n t s Scan to connect online to the most up-todate version of this Section of SPEEDFAX. Siemens TPS3 family of hardwired Surge Protective

More information

White Paper Avoiding SPD Procurement Errors

White Paper Avoiding SPD Procurement Errors White Paper Avoiding SPD Procurement Errors Avoiding SPD Procurement Errors Application Information and Manufacturer Support are Keys to Receiving Correct SPDs BACKGROUND INFORMATION Surge protection devices

More information

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC. [Refer to Engineering Notes at End of Spec] Section [16XXX] [264XXX] - SURGE PROTECTIVE DEVICES (SPDs) PART 1 - GENERAL 1.1 SCOPE A. This section includes Surge Protective Devices (SPDs) for low-voltage

More information

Specifications, Installation, and Operating Instructions

Specifications, Installation, and Operating Instructions Specifications, Installation, and Operating Instructions Model: Power Vantage AC Panel Protector CAUTION: The installation of a surge protection device () must be done by qualified electrical personnel.

More information

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual Surge Protective Devices STV100K Series Instruction Manual Contents 1.0 Installation... 4 1.1 Environment... 4 1.2 Mounting... 4 1.3 Proper Connection of SPDs... 4 1.4 Mechanical Dimensions... 5 1.5 Voltage

More information

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual Surge Protective Devices STV100K Series Instruction Manual Contents 1.0 Installation... 4 1.1 Environment... 4 1.2 Mounting... 4 1.3 Proper Connection of SPDs... 4 1.4 Mechanical Dimensions... 5 1.5 Voltage

More information

Eaton s SPD Series for integration into electrical distribution equipment

Eaton s SPD Series for integration into electrical distribution equipment Technical Data TD01006E Supersedes August 2009 Eaton s SPD Series for integration into electrical distribution equipment Contents Description Page Introduction....2 Applications....2 Features....2 Standards

More information

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death. Installation/Operation Manual TABLE OF CONTENTS Page UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection...2, 3 Model Number...9 LOCATION CONSIDERATIONS Environment, Equipment Performance,

More information

Surge Protective Devices. Installation & Operation Manual. NEMA 12 (Steel) NEMA 1 (Non-Metallic) Model 350

Surge Protective Devices. Installation & Operation Manual. NEMA 12 (Steel) NEMA 1 (Non-Metallic) Model 350 Surge Protective Devices Installation & Operation Manual NEMA 12 (Steel) NEMA 1 (Non-Metallic) Model 50 ASCO SURGE PROTECTIVE DEVICE INSTALLATION, OPERATION AND MAINTENANCE MANUAL TABLE OF CONTENTS INSTALLATION

More information

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH)

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH) Surge-Trap STZ-R series Surge Protective Device (SPD) Danger Hazard of Electrical Shock, Explosion or Arc Flash Only qualified licensed electricians should install or service SPDs Verify that all power

More information

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285. SECTION 26 04 75 - SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Applicable provisions of the General Conditions, Supplementary General Conditions and Special Conditions shall govern work performed

More information

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) Instruction Bulletin 8222-0513B Retain for future use. SPIKESHIELD Wired-In Branch Panels 8222-0513B 05/2012 Table of Contents Precautions...

More information

Installation and Operation Manual

Installation and Operation Manual Installation and Operation Manual APC 2X Series Hardwire Products PMP2X-A PMF2X-A PMG2X-A PMH2X-A APC hardwired products are designed to provide specification-grade performance at the service entrance,

More information

SINETAMER. ESPECIFIACIONES EQUIPOS COMERCIALIZADOS POR EDC SUPPLY y RESPALDADOS POR EDCEECA EN VENEZUELA

SINETAMER. ESPECIFIACIONES EQUIPOS COMERCIALIZADOS POR EDC SUPPLY y RESPALDADOS POR EDCEECA EN VENEZUELA SINETAMER. ESPECIFIACIONES EQUIPOS COMERCIALIZADOS POR EDC SUPPLY y RESPALDADOS POR EDCEECA EN VENEZUELA SUPRESOR PRINCIPAL DE 300 KA. ST-SMLA 3N4 TRANSIENT VOLTAGE SURGE SUPPRESSORS. PROTECTION AGAINST

More information

User Manual - Canada. TPS3 03 DC For DC Photovoltaic Applications. Surge Protective Device

User Manual - Canada. TPS3 03 DC For DC Photovoltaic Applications. Surge Protective Device TPS3 03 DC For DC Photovoltaic Applications Surge Protective Device DC Voltage Photovoltaic System Instructions Do Not Use for AC Voltage Installation Save These Instructions - This manual contains important

More information

Surgelogic Surge Protective Devices LC, XR, and XW Series

Surgelogic Surge Protective Devices LC, XR, and XW Series Surgelogic Surge Protective Devices LC, XR, and XW Series Catalog 1311CT0101R6/07 2007 Class 1311 CONTENTS Description..............................................Page Product Description...........................................

More information

TPS3 09. Surge Protective Device. User Manual - USA

TPS3 09. Surge Protective Device. User Manual - USA TPS3 09 Surge Protective Device User Manual - USA V WARNING - Hazardous Voltage & Shock Hazard Failure to Follow These Instructions Could Result in Death or Serious Injury Only qualified licensed electricians

More information

SECTION SURGE PROTECTIVE DEVICES

SECTION SURGE PROTECTIVE DEVICES SECTION 16289 PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Internal Modular SPDs

Internal Modular SPDs Internal Modular SPDs Square D Internally Mounted Protective Devices Square D TM brand logic TM internal modular Protective Devices (SPDs) deliver specification grade performance for service entrance or

More information

Always "On" UPS Systems Inc. USER MANUAL

Always On UPS Systems Inc. USER MANUAL Always "On" UPS Systems Inc. SMART HOME PROTECTOR USER MANUAL Bldg 1-150 Campion Road, Kelowna, BC, Canada, V1X 7S8 Phone: (250) 491-9777 Ext. 451, Fax: (250) 491-9775, Email: sales@alwaysonups.com Web

More information

Section 6. Surge Protective Devices (SPDs) Table of Contents. Externally Mounted Surge Protective Devices

Section 6. Surge Protective Devices (SPDs) Table of Contents. Externally Mounted Surge Protective Devices Table of Contents Section (SPDs) Commercial Applications EMA/EBA SPDs, pages -2, -3, & -4 Externally Mounted External Modular SPDs EMA SPDs -2 External Modular L-L Enhanced SPDs -3 External Brick Assembly

More information

ZoneMaster Series Surge Protection Devices

ZoneMaster Series Surge Protection Devices ZoneMaster Series Surge Protection Devices New Improved ZoneMaster Series Configurable Hard-Wired Surge Protection Devices Wiremold ZoneMaster Series Surge Protection Devices are fully configurable panel

More information

Surgelogic. Surge Protective Devices (SPDs) Residential. Catalog 6671CT9701R08/

Surgelogic. Surge Protective Devices (SPDs) Residential. Catalog 6671CT9701R08/ Surgelogic Surge Protective Devices (SPDs) Residential Catalog 6671CT9701R08/12 2012 CONTENTS Whole House Surge Protective Devices (SPDs).................... 3 SDSB1175C / SDSB1175CB Whole House SPDs..................4

More information

Instruction Manual IM E Table of Contents

Instruction Manual IM E Table of Contents Instruction Manual IM01005031E Effective For Mounting External To Table of Contents 1.0 Introduction 2.0 Installation 3.0 Operating Features 4.0 Troubleshooting 5.0 Specifications 6.0 Ordering Guidelines

More information

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

Panelmount (Facility-Wide) Surge Protection

Panelmount (Facility-Wide) Surge Protection Power Switching & Controls For Business-Critical Continuity Panelmount (Facility-Wide) Surge Protection AC Power Protection Table of Contents Introduction to Surge Protection Why Should I Install Facility-Wide

More information

GE Digital Energy. Power Quality

GE Digital Energy. Power Quality GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Wall Mounted Medium and High Exposure Surge Protective Devices (SPDs)

More information

R-LB R-LX Series Installation, Operation & Maintenance Manual

R-LB R-LX Series Installation, Operation & Maintenance Manual Installation, Operation & Maintenance Manual WARNINGS Safety First Hazardous Voltage & Shock Hazard Only qualified licensed electricians should install or service SPDs Hazardous voltages exist within SPDs

More information

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

DIVISION 16 SECTION Surge Protective Device Submittal (SPD) DIVISION 16 SECTION 16289 Surge Protective Device Submittal (SPD) PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Protect your facility from the destructive effects of power surges with a fully

Protect your facility from the destructive effects of power surges with a fully Protect your facility from the destructive effects of power surges with a fully configurable panel protection solution from The Wiremold Company. The all new ZoneMaster Series is fully configurable with

More information

I-Line SPDs Square D TM Internally Mounted Surge Protective Devices

I-Line SPDs Square D TM Internally Mounted Surge Protective Devices Square D TM Internally Mounted Protective Devices Square D TM brand logic TM I-Line Protective Devices (SPDs) deliver specification grade performance for service entrance or critical branch panel applications.

More information

Liebert TVSS: The First Line of Defense - Product Overview. Jim Tiesi

Liebert TVSS: The First Line of Defense - Product Overview. Jim Tiesi Liebert TVSS: The First Line of Defense - Product Overview Jim Tiesi INTERCEPTOR SURGE SUPPRESSION Overall Design True modular design Low impedance copper conduction plates Best in class performance Real-time

More information

BUSSMANN. North American UL Type 1, 2 and 4, and data signal surge protective devices SERIES. Application note 3193

BUSSMANN. North American UL Type 1, 2 and 4, and data signal surge protective devices SERIES. Application note 3193 Application note 3193 Supersedes January 2015 BUSSMANN North American UL Type 1, 2 and 4, and data signal surge protective devices SERIES Application Note 3193 Application note for North American Contents

More information

Clipper Power System Visor Series

Clipper Power System Visor Series Clipper Power System Visor Series Technical Data Supersedes TD.37B.21.T.E pages 1-8 dated October 2001 Description Page Applications.................................................. 2 General Description............................................

More information

The protection you rely on

The protection you rely on Surge protective devices 13 Contents The protection you rely on Section page Description Type 1 SPDs Selecting Type 1 SPDs 2-3 SurgePOD PRO Type 1, NEMA 4 4-5 BSPA, Type 1 and 2, NEMA 4 6-9 BSPD high capacity

More information

TPS3 11. Surge Protective Device. User Manual - USA

TPS3 11. Surge Protective Device. User Manual - USA TPS3 11 Surge Protective Device User Manual - USA V WARNING - Hazardous Voltage & Shock Hazard Failure to Follow These Instructions Could Result in Death or Serious Injury Only qualified licensed electricians

More information

TWL Series Installation Guide

TWL Series Installation Guide TWL Series Installation Guide Tower Light Controller Protectors Also See TWL Datasheet and Configuration Sheet The TWL Surge Suppressor is probably different than anything you have seen before. You will

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements Change History Date Description of Change Pages / Sections Modified 6/15/16 Updated division section from 16289 to 26 35 00, removed references to other section numbers 10/14/14 Amend text in section B

More information

SURGELOGIC TM. Surge Protective Device Transient Voltage Surge Suppressor (TVSS) XGA, XT, XF, XP Series. Class Schneider Electric Brands

SURGELOGIC TM. Surge Protective Device Transient Voltage Surge Suppressor (TVSS) XGA, XT, XF, XP Series. Class Schneider Electric Brands SURGELOGI TM Surge Protective Device Transient Voltage Surge Suppressor () XG, XT, XF, XP Series lass 1310 OTETS Description Page Product Descriptions..................................................

More information

Hubbell Surge Protective DeviceS

Hubbell Surge Protective DeviceS Hubbell Surge Protective DeviceS Hubbell Modular Panel Products Surge Protective Devices (SPD) The Hubbell Modular Panel Product Surge Protective Devices (SPD) are designed to provide protection at the

More information

TransGuard. Electrical Transient Suppression Filter Systems. Installation, Operation and Maintenance Manual PN ,

TransGuard. Electrical Transient Suppression Filter Systems. Installation, Operation and Maintenance Manual PN , Installation, Operation and Maintenance Manual PN 750-0068-003, TransGuard TransGuard Electrical Transient Suppression Filter Systems A member of the MasterPlan family of products 2002, Danaher Power Solutions

More information

Surge Protection. Fail-safe overvoltage protection in a full range of options. N Surge Protection

Surge Protection. Fail-safe overvoltage protection in a full range of options. N Surge Protection Surge Protection Fail-safe overvoltage protection in a full range of options Your problem: Power-related problems cost U.S. companies more than $80 billion dollars a year. Most transients originate from

More information

SURGE PROTECTION SOLUTIONS

SURGE PROTECTION SOLUTIONS SURGE PROTECTION SOLUTIONS SOLUTIONS GUIDE Comprehensive overvoltage protection Surge. Transient Spike. Over Voltage. POWER RELATED FLUCTUATIONS COST U.S. COMPANIES MORE THAN $80 BILLION A YEAR You have

More information

OVRH catalog Surge protective devices

OVRH catalog Surge protective devices OVRH catalog Surge protective devices 2 Product catalog OVRH series surge protective devices Table of contents SPDs IEC and UL SPD Test Standards Terminology...4 Fill in contents when all page content

More information

TPS3 Internal Manual. Surge Protective Device. User Manual - Canada

TPS3 Internal Manual. Surge Protective Device. User Manual - Canada TPS3 Internal Manual Surge Protective Device User Manual - Canada V WARNING - Hazardous Voltage & Shock Hazard Failure to Follow These Instructions Could Result in Death or Serious Injury Only qualified

More information

Surg Sur e P ot r ection

Surg Sur e P ot r ection Surge Protection Power Disturbances Lightning and fluctuations in utility power (caused by grid switching, for example) are often assumed to be the main sources of power disturbances. However, the overwhelming

More information

Model 450 Model 451 Model 452 Model 453 Model 460 Model 465 Model 480 Model 485. Surge Protective Devices. Installation & Operation Manual

Model 450 Model 451 Model 452 Model 453 Model 460 Model 465 Model 480 Model 485. Surge Protective Devices. Installation & Operation Manual Surge Protective Devices Installation & Operation Manual Model 460/465 Model 450/451 Model 480/485 Model 452/453 Model 450 Model 451 Model 452 Model 453 Model 460 Model 465 Model 480 Model 485 WARNING

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs)

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs) ga GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs) 2020005003 (12/09) Page 1 of 18

More information

THE SURGE PROTECTION SOLUTION

THE SURGE PROTECTION SOLUTION THE SOLUTION Unique product features and benefits never before offered in the surge protection industry POWER QUALITY INTERNATIONAL, LLC 2404 Merchant Ave., Odessa, Florida, USA 33556 (888) 539-7712 PowerQuality.net

More information

2.1. SPD, Power Conditioning, PF Capacitors and Harmonic Filters. Contents Description. Introduction. Surge Protection and Power Conditioning

2.1. SPD, Power Conditioning, PF Capacitors and Harmonic Filters. Contents Description. Introduction. Surge Protection and Power Conditioning .1 Industrial and Commercial Surge Protection Introduction Industrial and Commercial Surge Protection SPD Series for Integration into Electrical Distribution Equipment SPD Series for Mounting External

More information

PDI Modular Compact Remote Power Panel

PDI Modular Compact Remote Power Panel Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications

More information

Surge Protective Devices Installation, Operation and Maintenance Manual. ServiceTrack ST Series: 080, 120, 160, 200, 240, 300 and 400

Surge Protective Devices Installation, Operation and Maintenance Manual. ServiceTrack ST Series: 080, 120, 160, 200, 240, 300 and 400 ServiceTrack ST Series: 080, 120, 160, 200, 240, 300 and 400 Surge Protective Devices Installation, Operation and Maintenance Manual TEL: 800-853-8265 www.innosyspower.com SERVICETRACK ST INSTALLATION,

More information

TDX Series. Transient Discriminating TM TVSS

TDX Series. Transient Discriminating TM TVSS TDX Series Transient Discriminating TM TVSS TDX Series TDX150 is ideal for service entrance protection. Best Value Engineered Protection With emphasis on efficiency and value, ERICO developed the TDX Series.

More information

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches Series 300 Power Transfer Switches Maximum Reliability & Excellent Value With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289 PART 1 - GENERAL DIVISION 16 SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) 1.1 RELATED DOCUMENTS General: Drawings and general provisions of the Contract, including General and Supplementary

More information

Surge Protective Devices. Installation & Operation Manual. Model 457

Surge Protective Devices. Installation & Operation Manual. Model 457 Surge Protective Devices Installation & Operation Manual Model 457 WARNING IMPORTANT PLEASE READ WARNING Safety First Hazardous Voltage & Shock Hazard Only qualified licensed electricians should install

More information

Total Protection Solutions Surge Protective Devices SurgeTrack Series: 080, 120, 160, 240, 300 and 400

Total Protection Solutions Surge Protective Devices SurgeTrack Series: 080, 120, 160, 240, 300 and 400 Total Protection Solutions SurgeTrack Series: 080, 120, 160, 240, 300 and 400 Surge Protective Devices Installation, Operation and Maintenance Manual SURGETRACK INSTALLATION, OPERATION AND MAINTENANCE

More information

Surge Protection. Fail-safe overvoltage protection in a full range of options. N Surge Protection

Surge Protection. Fail-safe overvoltage protection in a full range of options. N Surge Protection Surge Protection Fail-safe overvoltage protection in a full range of options Your problem: Power-related problems cost U.S. companies more than $80 billion dollars a year. Most transients originate from

More information

Surge Protective Devices. Installation & Operation Manual. Model 420

Surge Protective Devices. Installation & Operation Manual. Model 420 Surge Protective Devices Installation & Operation Manual Model 420 CALIFORNIA CUSTOMERS - PROP 65 WARNING WARNING: This product can expose you to chemicals including DINP, which is known to the State of

More information

Qipof!)815*: !+!Gby!)815*61:.5594!+!Q/P/!Cpy!2969!+!Ivoufstwjmmf-!OD!!39181!+!!! xxx/tjofxbwfufdiopmphjft/cj{!

Qipof!)815*: !+!Gby!)815*61:.5594!+!Q/P/!Cpy!2969!+!Ivoufstwjmmf-!OD!!39181!+!!! xxx/tjofxbwfufdiopmphjft/cj{! Qipof!)815*:32.3413!+!Gby!)815*61:.5594!+!Q/P/!Cpy!2969!+!Ivoufstwjmmf-!OD!!39181!+!!! xxx/tjofxbwfufdiopmphjft/cj{! What Is Transient Voltage? An electrical transient is a temporary excess of voltage/current

More information

Powerware TVSS (Transient Voltage Surge Suppression) ZoneMaster, ZoneSentinel, ZoneDefender

Powerware TVSS (Transient Voltage Surge Suppression) ZoneMaster, ZoneSentinel, ZoneDefender Features ZoneMaster Replaceable modules Full protection redundancy Module diagnostics Remote indication capabilities NO/NC dry contacts NEMA rated enclosures Ultra low impedance construction Thermal fusing

More information

Models 120LS, 200LS, 300LS, 400LS, 560LS Installation Instructions

Models 120LS, 200LS, 300LS, 400LS, 560LS Installation Instructions 299-600-96 Rev. F MCG Surge Protection Models 120LS, 200LS, 300LS, 400LS, 560LS Installation Instructions Important Warranty Information: MCG surge protectors are designed to work at specific voltages

More information

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications TCMOV Varistors for Type 1 and Type What is UL 1449? Underwriters Laboratories standard UL 1449 has become the primary safety standard for surge protective devices (SPDs). It describes the materials and

More information

920 Remote Control (RC) Switches

920 Remote Control (RC) Switches 920 Remote Control (RC) Switches ASCO is the global leader in power switching and controls ASCO 920 PRODUCT SPECIFICATIONS SWITCH ONLY (PANELBOARD MOUNTING) 1,2,3 () DIMENSIONS, IN.(MM) WIDTH HEIGHT DEPTH

More information

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL LoadTrack LTL Surge Protective Devices Installation, Operation and Maintenance Manual P.O. Box 3760 Winter Park, FL 32790 USA TEL: 800-647-1911 www.tpssurge.com LOADTRACK LTL INSTALLATION, OPERATION AND

More information

Installation and Operation Manual

Installation and Operation Manual Installation and Operation Manual APC Panel Mount Modular SPDs PMP3S-A PMP3DS-A PMP4S-A PMP4DS-A PMF3S-A PMF3DS-A PMF4S-A PMF4DS-A PMG3S-A PMG3DS-A PMG4S-A PMG4DS-A PML3S-A PML3DS-A PML4S-A PML4DS-A The

More information

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B SURGE PROTECTION PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) USER MANUAL Surge Protection Device B 01 156 9000 This Surge Protection Device is intended for professional use only Read this

More information

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE IMPORTANT! Please read all the information on this sheet. SAVE THESE INSTRUCTIONS! NOTICE BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL

More information

PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY

PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY REVISION 3-B-041318 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document

More information

400 Series 460 Surge Protective Device Installation, Operation and Maintenance Manual

400 Series 460 Surge Protective Device Installation, Operation and Maintenance Manual 400 Series 460 Surge Protective Device Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual IO-70104 Rev 1, 1/2014 EMERSON NETWORK POWER SURGE PROTECTIVE DEVICE

More information

AC and DC Protector Applications

AC and DC Protector Applications * AC and DC Protector Applications Grid-Tie Inverter (GTI): An inverter performs the function of converting DC power into AC power. However, what separates a grid-tie inverter from a common inverter is

More information

MIL STD 220a (50 Ohm) Model Ordering: 400LS - 277Y - DS - UFP - MX

MIL STD 220a (50 Ohm) Model Ordering: 400LS - 277Y - DS - UFP - MX 299-401-20A MCG Surge AC MODEL: 400LS Executive Main Service Panel AC Power Line Protection with Enhanced Power/Energy Metering The 400LS Executive Series provides 400,000A of rugged surge protection at

More information

SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014

SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014 SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014 1.0 SCOPE This secondary Type 1 surge protective device specification covers

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA SURGE PROTECTION DESIGN. Parallel Versus Series Protection. Surge protectors within the scope of this UFC should normally be of the parallel

More information

Surge Protective Devices. STV25K Series. Instruction Manual

Surge Protective Devices. STV25K Series. Instruction Manual Surge Protective Devices STV25K Series Instruction Manual Contents 1.0 Installation & Operation... 4 1.1 Environment... 4 1.2 Mechanical Dimensions... 4 1.3 DIN Rail Mounting... 5 1.4 Supplemental Enclosures...

More information

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET Technical Publications SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET for ARTIS Q / Q.ZEN / ONE ARTIS ZEEGO / ZEEGO.ZEN ARTIS ZEE MULTIPURPOSE SINGLE PLANE IECAX480V125A Main Disconnect Panel Bevco Engineering

More information

ASCO 920 Remote Control (RC) Switches

ASCO 920 Remote Control (RC) Switches Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder disconnect switch for load capacities

More information

Installation Instructions & User Manual

Installation Instructions & User Manual Installation Instructions & User Manual ZONEMASTER PRO AC Panel Transient Voltage Surge Suppressors The Wiremold Company In US: 60 Woodlawn Street, West Hartford, CT 06110 800-621-0049 FAX 860-232-2062

More information

Quick Start Guide TS A

Quick Start Guide TS A Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

UL th Edition SPD. TPS3 Internal SPDs. User Manual - USA. usa.siemens.com/spd

UL th Edition SPD. TPS3 Internal SPDs. User Manual - USA. usa.siemens.com/spd UL 1449 4 th Edition SPD TPS3 Internal SPDs User Manual - USA usa.siemens.com/spd NOTICE CONDUCTING DIELECTRIC AND/OR HI-POTENTIAL TESTING WILL CAUSE INTERNAL DAMAGE TO TPS3 UNIT. Do not perform dielectric

More information

Liebert LM Series Surge Protective Device Continuous Protection For Your Business. Surge Protection For Business-Critical Continuity

Liebert LM Series Surge Protective Device Continuous Protection For Your Business. Surge Protection For Business-Critical Continuity Liebert LM Series Surge Protective Device Continuous Protection For Your Business Surge Protection For Business-Critical Continuity The Liebert LM Series: The Most Advanced, Cost-Effective Product Line

More information

TransEnd Surge Suppression Filter Systems

TransEnd Surge Suppression Filter Systems Installation, Operation and Maintenance Manual P 750-0064-REV. 44 TransEnd TransEnd Surge Suppression Filter Systems TransEnd 100 TransEnd 80 TransEnd 50 TransEnd 25 JOSLY ISTALLATIO, OPERATIO AD MAITEACE

More information

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated

More information

TST SERIES. Din Rail Surge Protective Device for SCADA Systems. Meter-Treater, Inc. Dimensions. Product Specifications. Notes

TST SERIES. Din Rail Surge Protective Device for SCADA Systems. Meter-Treater, Inc. Dimensions. Product Specifications. Notes Utility Equipment Din Rail Surge Protective Device for SCADA Systems The TST Series of SPDs (surge protection devices) are designed to protect sensitive electronic equipment from the harmful effects of

More information

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service. PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA

More information

Instruction Manual: IM E

Instruction Manual: IM E Innovative Technology TVSS Products The I.T. Equalizer Installation Instruction Manual: IM01005011E Rev. 2 May 2009 Contents Page 1 Introduction... 1 1.1 Scope... 1 1.2 I.T. Equalizer Catalog Numbering

More information