Using the Bitronics 70 Series to Improve Local Monitoring and Control

Size: px
Start display at page:

Download "Using the Bitronics 70 Series to Improve Local Monitoring and Control"

Transcription

1 Automate a Substation and Preserve the Electromechanical Relay Investment Part Two of Four Using the Bitronics 70 Series to Improve Local Monitoring and Control Paul Grabowski - Bitronics Senior Application Engineer January 20 23, 2009

2 About the Author Paul Grabowski implemented automation in over 100 substations during his 29-year career with Pennsylvania Power and Light. More recently, Paul spent five years as a US protection application engineer for AREVA T&D. He is now a Senior Application Engineer for the Bitronics product lines. Paul is a registered Professional Engineer in the State of Pennsylvania.

3 January 20 23, 2009 Introduction

4 Meeting Automation Requirements Technology Microprocessor based technology provides a solution Two alternatives 1) Install microprocessor based relays - Replace electromechanical relays OR 2) Install microprocessor based recording and monitoring IEDs - Such as the Bitronics 70 Series - Allows retention of electromechanical relay scheme Realize substantial cost savings

5 Some Typical Automation Goals 1) Fault Analysis and Recording 2) Improve Local Monitoring and Control 3) Provide/Improve Remote Monitoring and Control 4) Monitor Power Quality 5) Provide Protective Function Setting Groups and Backup Protective Features

6 Conclusions from Part 1 Comparison of costs Alternative 1 Replace electromechanical relays with microprocessor based relays more costly Alternative 2 - install microprocessors based non-relay IED such as Bitronics 70 Series Relay replacement is 3x to 5x as costly

7 Some Typical Automation Goals 1) Fault Analysis and Recording 2) Improve Local Monitoring and Control 3) Provide/Improve Remote Monitoring and Control 4) Monitor Power Quality 5) Provide Protective Function Setting Groups and Backup Protective Features

8 Goal 2 Improve Local Monitoring and Control examples using non-relay IEDs 1) Metering Improvements 2) Remove paper recorders 3) Add monitoring features 4) Add Local Indication 5) Add SOE logging 6) Provide station battery monitoring 7) Distributed Control

9 Using the Bitronics 70 Series M870D Display Bitronics M871

10 Goal 2 Example 1 Metering Improvements January 20 23, 2009

11 Replace Electromechanical Meters Basic 70 series installation 2 Pieces minimum - base unit plus display Install Mx70 unit behind panel Install display in 4 round meter hole Connect using communications cable

12 Improvement Explicit Meter Readings Existing electromechanical metering CT ratio Reading Pri Sec

13 Improvement Explicit Meter Readings, cont d Compare with 70 series CT ratio Reading Pri Sec

14 Measurements available Measurements available A, B & C Phase Amps, fundamental RMS Instantaneous Maximum Minimum All these Plus January 20 23, 2009

15 Measurements available, cont d - A, B, C Phase Amps - True RMS - Instantaneous, Max and Min - Power Readings (per phase and 3 phase) Up to 64 screens - Bus and/or Line Voltages - Harmonics Digital I/O - Display up to 192 of all the measurements in device - Scroll manually or auto-scroll January 20 23, 2009

16 Using Multiple Displays Multiple displays can be driven from each Mx70 Advantages Simultaneous viewing of data Display data in various locations Four examples follow

17 Simultaneous viewing of measurements RS485 M871 Line Volts Line Amps Line Watts/ VARs

18 Simultaneous viewing of measurements, cont d RS485 M871 Transf Pri kv Transf Sec kv 345kV- 66kV 66kV 3 Bus

19 Viewing measurements from two lines M872 (or M572) Line 1 RS485 M872 Line 2 Line 1 Line 2

20 Viewing measurements at two locations 345kV Yard RS485 M872 66kV Yard Transf Values up to 1500 meters 345kV- 66kV Transf Values 66kV 3 Bus

21 Goal 2 - Example 2 Remove paper recorders January 20 23, 2009

22 70 Series Recorders Non-relay IEDs equipped with various recorders One of the 70 Series recorders is Trend recorder Trend recorder replaces chart recorder

23 70 Series Trend Record Page duration = 20 hours 30 minutes

24 70 Series Trend Record Page duration = 2 days 23 hours

25 70 Series Trend Record 1 2 Avg RMS Watts Total 1 3 Avg RMS Vars Total 1 Page duration = 20 hours 30 minutes

26 Trend Record Retrieval M871 behind panel M870D on front of panel OR, Retrieve trend record Retrieve Trend record

27 Goal 2 - Example 3 Add monitoring features January 20 23, 2009

28 Add Monitoring Features where none existed Non-relay IEDs have digital I/O and Logic 70 Series also has digital I/O and Logic Add Monitoring of critical substation elements using Digital I/O and logic Monitoring of circuit conditions from the CT and PT inputs using logic Three examples Trip coil monitor using digital I/O and logic DC fuse monitor using digital I/O and logic Abnormal voltage swings using logic

29 Elementary diagram - substation line 1 bay 1 +VDC Fuse Protective Relays 50 52a Trip Circuit TC Link -VDC 2 51 Auto Close 3 52b Close Circuit Fuse CC Link Fuse Other items Aux Circuit

30 Trip Circuit Issues Blown Fuse Link not installed Corrosion / poor contact Open Trip coil circuit Consequenses fail to trip during a fault +VDC Fuse Protective Relays 50 52a TC Link -VDC 51

31 Mx70 Trip Circuit Monitor Use Bitronics 70 Series Digital Inputs Example below +VDC -VDC Fuse 50 52a TC Link 51 Input Mx70 Digital Input

32 Operation Trip Circuit Normal Digital Input on +VDC -VDC Fuse 50 52a TC Link 51 Input Mx70 Digital Input External LED on

33 Operation Trip circuit failed Digital Input off VDC -VDC Fuse 50 52a TC Link 51 Input Mx70 Digital Input External LED off

34 Operation Undesirable trip circuit failed Indication Digital Input off with CB open 1 +VDC -VDC Fuse 50 52a TC Link 51 Input Mx70 Digital Input External LED off

35 Fix Undesirable Indication using logic Monitor CB 52a auxiliary switch status Build logic using both inputs +VDC -VDC Fuse 50 52a TC Link 51 52a Input Normal - DI energized Input CB closed - DI energized

36 Trip circuit monitor Logic Final logic to eliminate nuisance outputs DC Trip Circuit Status Indication CB 52a aux switch closed Line 1 Trip Circuit Failed Digital Output #1 Program as unlatched or latched

37 DC Fuses Issues Blown Fuse Corrosion / poor contact Consequences associated control element fails to operate +VDC Fuse Protective Relays 50 52a Trip Circuit TC Link -VDC 2 51 Auto Close 52b Close Circuit Fuse CC Link Fuse Other items Aux Circuit

38 DC Fuse Monitor +VDC Fuse Protective Relays 50 52a Trip Circuit TC Link -VDC 51 Mx70 Digital Input Auto Close 52b Close Circuit Fuse CC Link Mx70 Digital Input Fuse Other items Mx70 Digital Input Aux Circuit

39 DC Fuse Monitor, cont d +VDC Fuse Protective Relays 50 52a Trip Circuit TC Link -VDC 51 Normal - DI energized Auto Close 52b Close Circuit Fuse CC Link Normal - DI energized Fuse Other items Aux Circuit Normal - DI energized

40 Line Bay DC Fuse Monitor Logic Combine fuse fail indication into one alarm point If one or more fuses fail, the output is on. Trip Circuit Fuse Indication Close Circuit Fuse Indication Aux Circuit Fuse Indication t = 10s Line 1 Bay Fuse Failed Digital Output #2 Program as unlatched or latched

41 Monitor abnormal voltage swings using logic Voltage and current input conditions can be monitored using logic Example: 138kV nominal system Alarm when any phase exceeds 5% overvoltage A phase voltage 1 > kv B phase voltage 1 > kv C phase voltage 1 > kv Line 1 Overvoltage Condition Digital Output #3 Program as unlatched or latched

42 Goal 2 - Example 4 Add Local Indication January 20 23, 2009

43 Provide Local Indication Developed logic to monitor various conditions How do I provide local indication?

44 Provide Local Indication from the 70 Series View Digital I/O LEDs on 70 Series View DIO LEDs

45 Provide Local Indication on the 70 Series Display 70 Series Display on front panel Display the status of selected digital I/O points View DIO Values Digital Output # 1 (Trip Circuit Status) Digital Output # 2 (DC Fuse Status) Digital Output # 3 (Overvoltage Condition) Custom Label

46 Provide Local Indication via Indicating lights or annunciator panel Install indicating lights on panel Connect digital outputs to lights Drive an annunciator panel from the digital outputs Line 1 Trip Circuit Failed Line 1 Bay DC Fuse Failed Line 1 Overvoltage Condition

47 Goal 2 - Example 5 Add SOE Logging January 20 23, 2009

48 SOE Recorder Each Mx70 has its own SOE recorder Digital I/O and other events can be added to SOE recorder Multiple 70 series provide distributed SOE recording

49 SOE Recorder, cont d Can a substation wide SOE recorder be created? Yes Use Bitronics BiView test & commissioning software Comes on CD with 70 series configurator Primarily designed for use on a local IP or RS485 network BiView Merges all SOE logs sent to a folder into one SOE log Creates substation recorder functionality

50 SOE Recorder, cont d SOE Record Bay 1 SOE Record Bay 2 Upload with BiView to the same folder One record for Sub SOE Record Bay 3

51 SOE Record Retrieval M871 behind panel M870D on front of panel Retrieve SOE Log OR, Retrieve SOE Log

52 Time Synchronization Merged SOE records meaningless without time sync between units Time Sync available in 70 series IRIG-B SNTP UCA DNP3.0 RS485 network

53 Goal 2 - Example 6 Station Battery Monitoring January 20 23, 2009

54 Substation DC systems Function Operate the trip and control circuits during a loss of ac station service DC system design Battery charger Substation battery (lead acid) Not grounded

55 Substation DC systems, cont d Normal operation Battery charger supplied from ac station service Battery charger on Battery charger provides tripping and operating current Emergency operation Loss of ac station service Battery alone provides trip and operating currents

56 Substation DC systems, cont d Problems Battery charger failed or faulty Ground on dc system Bad cells in battery DC system monitor very useful

57 Monitor Station DC Non-relay IEDs may have dc battery monitoring M871 has required inputs Monitor signals from 0 Hz (dc) to 70 Hz VT inputs terminal block Location of Auxiliary voltage inputs

58 Monitor Station Battery, cont d Aux voltage inputs (station battery) can be placed in records Waveform record Disturbance record Trend record SOE Log Use logic To give external output for desired Aux input conditions

59 Monitor Station Battery, grounding considerations Substation batteries are not connected to ground 70 series aux inputs Designed with this in mind Aux inputs filitering No surge arrestors such a Metallic Oxide Varistors ( MOVs) are used MOVs fail in shorted mode MOVs could place the first short on the station battery Use Capacitors for filtering Therefore, Aux inputs inherently safe in this application

60 Goal 2 Example 7 Distributed Control January 20 23, 2009

61 Distributed control - definition Non-relay IED (Bitronics M871) LAN Values Commands PLC / DCS Monitor system Voltages Currents Digital Inputs Operate Digital Outputs when requested Provide logic and control functions

62 Distributed Control Functions currently in use Generator control Transformer tap changer Capacitor bank control Voltage check Sync check Many others Sync check example next

63 Why Sync Check? Power System CB open Gen Vbus Vline

64 Distributed control Sync Check system Bitronics M871 LAN Health Reg Heartbeat Reg PLC / DCS 52b Va1 f Va1 Angle Va1-Va2 Va2 f Va2

65 Distributed control Sync Check in PLC/DCS Registers from M871 Health Reg Heartbeat Reg Va1 Va2 f Va1 f Va2 Angle Va1-Va2 PLC / DCS Logic Contact outputs from Logic M871 OK Va1 live Va2 live Delta f <.05 Angle < 40 52b

66 Distributed control Sync Check in PLC/DCS cont d Permissive string developed from M871 data M871 OK 52b Va1 live Va2 live Delta f <.05 Hz Angle < 40 Other Reclose logic in the PLC/DCS

67 Non-relay IED Requirements Accurate data measurements Frequent updating of measurements Good communications Must have health information

68 Mx70 Capabilities Power system inputs Two sets of 3 phase voltages One or two sets of three phase currents Accuracy Exceeds accuracy requirements of ANSI C12.20 and IEC Measurement update rate Voltage and currents every _ cycle Watts, VARs, frequency and phase angle every cycle

69 Mx70 Capabilities, cont d Communications DNP or MODBUS over RS485 DNP or MODBUS over 10/100 Ethernet MODBUS PLUS UCA and IEC61850 (Ethernet) Health information Health register Heartbeat Register

70 Conclusions Electromechanical relay schemes Provide adequate protection Lacks local monitoring and control features required and desired Improving local monitoring and control can be provided by Bitronics 70 Series monitoring and recording IED Allows retention of the Electromechanical relays Provides improvements in monitoring and control And allows new features to be developed

71 Future Webinars Part Three Improve remote monitoring and control April 2009 Part Four Improve power quality monitoring June 2009

72 Questions? Thank you. January 20 23, 2009

73 Part Two of Four Using the Bitronics 70 Series to Improve Local Monitoring and Control The End January 20 23, 2009

Automate and Preserve Electromechanical Relay Investment Part 3 of 3 Using the Bitronics 70 Series to Improve Remote Monitoring and Control

Automate and Preserve Electromechanical Relay Investment Part 3 of 3 Using the Bitronics 70 Series to Improve Remote Monitoring and Control Welcome to NovaTech Automate and Preserve Electromechanical Relay Investment Part 3 of 3 Using the Bitronics 70 Series to Improve Remote Monitoring and Control Paul Grabowski About the Author Paul Grabowski

More information

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100% Operating range: 0.10 to 30 xin (step 0.01) 50P(2) Activation level 100% Deactivation level 95% Timer accuracy: 30 ms Operating range: 0.10 to 30 xin (step 0.01) 50N/G(2) Activation level 100% Deactivation

More information

NovaTech Orion I/O Overview

NovaTech Orion I/O Overview NovaTech Orion I/O 2 NOVATECH ORION I/O 3 NovaTech Orion I/O Overview NovaTech Orion I/O is an extension of the family of OrionLX Automation Platforms for substation automation and incorporates the same

More information

NPW800R RETROFITTING. Power and Volatge Protection Relay

NPW800R RETROFITTING. Power and Volatge Protection Relay RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)

More information

2 NOVATECH. This page is intentionally left blank.

2 NOVATECH. This page is intentionally left blank. NovaTech Orion I/O 2 NOVATECH This page is intentionally left blank. ORION I/O 3 NovaTech Orion I/O Overview NovaTech Orion I/O is an extension of the family of OrionLX Automation Platforms for substation

More information

Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording

Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording Two independent, simultaneously operating recorders in one package Triggering on input quantities and calculated values, such as

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK SDR recloser A PH Fault B PH Fault C PH Fault Ground Fault SGF Lockout Aux Power OK Recloser OK Open Close Reclose ON Hot Line Tag ON All Protn OFF Inst Protn OFF Ground Fault Protn OFF SGF Protn OFF Trip

More information

Transformer Protection Relay

Transformer Protection Relay Transformer Protection Relay T-PRO Product Overview The IEC 61850 station bus embedded T-PRO relay provides complete three-phase multi-winding transformer protection and overload protection, DFR-quality

More information

Bitronics. An Overview of the Bitronics Product Line

Bitronics. An Overview of the Bitronics Product Line Bitronics An Overview of the Bitronics Product Line Precision Crafted Quality Backed by a Hassle-Free 10-Year Guarantee Bitronics tradition of quality craftsmanship stretches from the first hand-jeweled,

More information

Bitronics Electric Power Measurement and Recording Products

Bitronics Electric Power Measurement and Recording Products Bitronics Electric Power Measurement and Recording Products Bitronics D/3 Orion The Engineer s Choice Utility-Grade Design Bitronics Electric Power Measurement and Recording Products are found in more

More information

Lecture 6 Substation Automation Systems

Lecture 6 Substation Automation Systems Lecture 6 Substation Automation Systems 1 Course map 2 Contents of the Lecture Part 1 Substation Automation Components & Architectures Substation Automation Functions Communication within the Substation

More information

Metering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs

Metering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs .3 Features and Benefits Saves installation time and cost One part number to order; no need to worry that any part has been left out Pick the meter or meters you need as it is designed to fit various Eaton

More information

www. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES

www. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES Protective Relays Electrical Apparatus Capacitor Bank Protection Relay 165-440-900 Figure 1: Edison Idea Relay The capacitor bank protection relay is a member of Cooper Power Systems Edison Idea TM line

More information

FP-5000 Feeder Protection

FP-5000 Feeder Protection Effective: April 2001 Page 1 New Information FP-00 Feeder Protection Contents Description Page FP-00 Description......... 2 Application Description...... 2 Features, Functions and Benefits..............

More information

Lecture 5 Substation Automation Systems. Course map

Lecture 5 Substation Automation Systems. Course map Lecture 5 Substation Automation Systems 1 Course map 2 1 Contents of the Lecture Part 1 Substation Automation Components Substation Automation Functions Communication within the Substation (Intro) Part

More information

Product Overview 2Pro AC Devices Provide Overcurrent/Overvoltage/ Overtemperature Protection for AC Industrial and Appliance Applications

Product Overview 2Pro AC Devices Provide Overcurrent/Overvoltage/ Overtemperature Protection for AC Industrial and Appliance Applications Product Overview 2Pro AC Devices Provide Overcurrent/Overvoltage/ Overtemperature Protection for AC Industrial and Appliance Applications The 2Pro AC family of devices provide integrated overcurrent/ overvoltage/overtemperature

More information

GE Power Management. MMII Intelligent MCC Controller

GE Power Management. MMII Intelligent MCC Controller A concept that will offer reduced overall installed cost and production efficiency through information availability to operators and maintenance. Presentation Overview 6 Applications 6 Protection and Control

More information

Power System Monitoring Recorder TESLA 3000

Power System Monitoring Recorder TESLA 3000 Power System Monitoring Recorder TESLA 3000 Product Overview TESLA 3000 is an easy-to-use and cost-effective, stateof-the-art, multi-time frame (simultaneous) power system recording monitor. The optional

More information

Quantum Chargers Enhanced AC Line Transient Immunity

Quantum Chargers Enhanced AC Line Transient Immunity Introduction Quantum Chargers Enhanced AC Line Transient Immunity By: Nasser Kutkut, PhD, DBA Advanced Charging Technologies Inc. This white paper outlines the most common AC power quality disturbances

More information

PM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features

PM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER The PM174 is a compact, multi-function, three-phase AC powermeter and power quality analyzer specially designed to meet the requirements of users ranging

More information

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation: DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated

More information

BF 79 81

BF 79 81 BE1-11f FEEDER PROTECTION SYSTEM The BE1-11f is a multifunction numeric relay that provides three phase, ground, and negative sequence directional or non-directional overcurrent protection with four shot

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

BITRONICS 878 DIOD Product Description BITRONICS 878 DIOD DISTRIBUTED INPUT/OUTPUT DEVICE

BITRONICS 878 DIOD Product Description BITRONICS 878 DIOD DISTRIBUTED INPUT/OUTPUT DEVICE BITRONICS 878 DIOD Product Description BITRONICS 878 DIOD DISTRIBUTED INPUT/OUTPUT DEVICE This page intentionally left blank 2 l BITRONICS 878 DIOD APPLICATION NOTE 878 Distributed Input/Output Device

More information

AC Power Quality and Protection

AC Power Quality and Protection Lab 5-2 Video System Troubleshooting Copyright 2006 Heathkit Company, Inc. All Rights Reserved AC Power Quality and Protection 2 Today we will look at... AC Line Surge Suppressors Phone Line Surge Suppressors

More information

Siprotec 7ST61 / 7ST63

Siprotec 7ST61 / 7ST63 Siprotec / Numerical overhead contact line protection for AC traction power supply siemens.de/rail-electrification The numerical overhead contact line protection relay Siprotec / is a selective and quick

More information

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators. SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering

More information

Power System Monitoring Recorder

Power System Monitoring Recorder Power System Monitoring Recorder TESLA 4000 Model 4000 Model 4003 Product Overview TESLA 4000 is an easy-to-use and cost effective, state of the art, multi-time frame (simultaneous) power system monitoring

More information

Power System Monitoring Recorder. Product Overview. 10 Year WARRANTY

Power System Monitoring Recorder. Product Overview. 10 Year WARRANTY Power System Monitoring TESLA 4000 Product Overview TESLA 4000 is an easy-to-use, state of the art, multi-time frame (simultaneous) power system monitoring recorder. Its integrated Phasor Measurement Unit

More information

Protection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system

Protection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system SEL-451 Protection, Automation, and Bay Control System Advanced feeder protection and complete substation bay control in one economical system Customize distribution protection using multiple instantaneous,

More information

BE1-951 OVERCURRENT PROTECTION SYSTEM ADVANTAGES

BE1-951 OVERCURRENT PROTECTION SYSTEM ADVANTAGES BE1-951 OVERCURRENT PROTECTION SYSTEM The BE1-951 is a multifunction numerical relay that provides three phase, ground, and negative sequence directional or non-directional overcurrent protection with

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3

Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3 www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated with

More information

Bitronics. Electric Power Measurement and Recording Products

Bitronics. Electric Power Measurement and Recording Products Bitronics Electric Power Measurement and Recording Products Bitronics D/3 Orion The Engineer s Choice Utility-Grade Design Bitronics Electric Power Measurement and Recording Products are found in more

More information

POWER METER HC Features

POWER METER HC Features Introduction The power quality meter HC 6030 is an ideal device to power monitoring in power quality when continuous monitoring to a power system is required. The HC 6030 provides metering for current,

More information

SM100. On-Line Switchgear Condition Monitoring

SM100. On-Line Switchgear Condition Monitoring On-Line Switchgear Condition Monitoring On-Line Switchgear Condition Monitoring Introduction Weis is a specialist company with over 40 years of experience in the commissioning, testing & maintenance of

More information

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 PC83 and PC830 series devices are designed to perform the relay protection functions and 6-154 kv networks automation, have different functionality

More information

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc Redundant Bus Protection Using High-Impedance Differential Relays Josh LaBlanc Purpose Discuss the configuration of the bus under study, and touch on the needs for redundant protection on the bus. Briefly

More information

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication GE Grid Solutions DS Agile C264 Dual-bay Modular Substation Controller The DS Agile C264 substation controller is a sophisticated solution supporting multiple applications and functions for substation

More information

THE INTEGRATED TESTING SOLUTION

THE INTEGRATED TESTING SOLUTION Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters THE INTEGRATED TESTING SOLUTION

More information

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology HGM9580 Bus Tie Bus Parallel Unit USER MANUAL Smartgen Technology This manual is suitable for HGM9580 bus tie bus parallel unit only. Clarification of notation used within this publication. SIGN INSTRUCTION

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

Installation Instructions

Installation Instructions Installation Instructions (Catalog Number 1771-OD) This document provides information on: Because of the variety of uses for the products described in this publication, those responsible for the application

More information

Request publication Request publication DNP 3.0 INSTRUCTION MANUAL. Request publication

Request publication Request publication DNP 3.0 INSTRUCTION MANUAL. Request publication BE1-851 OVERCURRENT PROTECTION SYSTEM The BE1-851 is a multifunction, numeric relay that provides three phase, ground, and negative sequence overcurrent protection with four shot recloser, breaker failure,

More information

ADDITIONAL INFORMATION MODBUS INSTRUCTION MANUAL Request publication Request publication

ADDITIONAL INFORMATION MODBUS INSTRUCTION MANUAL Request publication Request publication BE1-GPS100 GENERATOR PROTECTION SYSTEM The BE1-GPS100 is a multifunction, programmable numerical protection, meter, and control relay. Functions provided include three phase voltage controlled, voltage

More information

M-6200A DIGITAL VOLTAGE REGULATOR CONTROL SUGGESTED SPECIFICATIONS

M-6200A DIGITAL VOLTAGE REGULATOR CONTROL SUGGESTED SPECIFICATIONS M-6200A DIGITAL VOLTAGE REGULATOR CONTROL SUGGESTED SPECIFICATIONS Pole-Top/Pad Mount Digital Voltage Regulator Control, for metering, monitoring, and operational control for step-voltage Regulators shall

More information

2008 Many Changes in IEEE C37.2. IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations

2008 Many Changes in IEEE C37.2. IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations 2008 Many Changes in IEEE C37.2 IEEE Standard Electrical Power System Device Function Numbers, Acronyms and Contact Designations Major revisions first since 1995 Substantial additions 1 - New ten more

More information

Commission Testing Methods for Protection Systems

Commission Testing Methods for Protection Systems Commission Testing Methods for Protection Systems Tom Ernst GE Grid Solutions Ken Sletten Minnesota Power Abstract Commission testing should be designed to assure that the protection system is set and

More information

RMS Product Presentation

RMS Product Presentation RMS Product Presentation THE RELAY SPECIALISTS relay monitoring systems pty ltd www.rmpl.com.au Relay Monitoring Systems Pty Ltd 6 Anzed Court - Melbourne - Australia Manufacturing in Australia Company

More information

Feeder/ Motor Protection Relay VAMP 40

Feeder/ Motor Protection Relay VAMP 40 Feeder/ Motor Protection Relay Feeder/motor protection relay Main characteristics Complete protection Comprehensive selection of protection functions for distribution network overhead line feeders, cable

More information

Power Systems Communications Implementation of IEC61850 in a Substation Environment

Power Systems Communications Implementation of IEC61850 in a Substation Environment Power Systems Communications Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Document Control Document ID: DOCUMENT1 Rev No Date Revision Details

More information

PUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System

PUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System PUBLIC SERVICE OF NEW HAMPSHIRE Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System September 2013 1.0 Purpose of this document Public Service of New Hampshire

More information

FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control

FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control Key Benefits FM2 FEEDER Protection System Economical and compact feeder protection for low voltage feeders Comprehensive low voltage feeder management system - Integrated feeder protection and process

More information

MONITORING ABSTRACT KEYWORDS. TRANSFORMERS MAGAZINE Special Edition: Bushings, 2017

MONITORING ABSTRACT KEYWORDS. TRANSFORMERS MAGAZINE Special Edition: Bushings, 2017 MONITORING The difference between safe and reliable on-line bushing monitoring and false alarms often lays in the quality of the sensor design and the installation procedure ABSTRACT On-line monitoring

More information

EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters

EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters Power and Energy Meters Code No. LIT-1900845 Issued December 4, 2013 EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters EM-1000 Series Meter Description The EM-1000 Series monitor is

More information

EDR-3000 Eaton Distribution Relay

EDR-3000 Eaton Distribution Relay EDR-3000 Eaton Distribution Relay Technical Data New Information Description Page 1. General Description.......................... 2 2. Applications............................... 2 3. Drilling Pattern.............................

More information

PQube 3. Power Quality, Energy & Environment Monitoring. New Low-Cost, High-Precision

PQube 3. Power Quality, Energy & Environment Monitoring. New Low-Cost, High-Precision New Low-Cost, High-Precision Power Quality, Energy & Environment Monitoring PQube 3 Power Quality Class A Energy Revenue Grade class 0.2s Accuracy Additional AC, DC, and Environment Sensor Channels World

More information

M-2001D DIGITAL TAPCHANGER CONTROL SUGGESTED SPECIFICATIONS

M-2001D DIGITAL TAPCHANGER CONTROL SUGGESTED SPECIFICATIONS M-2001D DIGITAL TAPCHANGER CONTROL SUGGESTED SPECIFICATIONS Pole-Top/Pad Mount Digital Tapchanger Control, for metering, monitoring, and operational control of step-voltage load tapchangers shall be provided

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

U lity network. system Q sys. Interconnected P sys. P load Q load. P gen Q gen. Generator network

U lity network. system Q sys. Interconnected P sys. P load Q load. P gen Q gen. Generator network SIL-G Feeder & Generator Protection Relay RC FLSH Main characteristics The SIL-G is a relay for primary distribution which can protect a feeder by means of current and voltage functions. It is also provided

More information

PM130 PLUS PM130 PLUS POWER METER. Features. Models. Multifunctional 3-phase Power Meter

PM130 PLUS PM130 PLUS POWER METER. Features. Models. Multifunctional 3-phase Power Meter PM130 PLUS POWER METER The PM130 PLUS is a compact, multi-function, three-phase AC powermeter specially designed to meet the requirements of users ranging from electrical panel builders to substation operators.

More information

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay Protective Relays Electrical Apparatus ixp-420 Transformer Protection Relay 165-420 Figure 1: Edison Idea Relay The ixp-420 is a member of Cooper Power Systems Edison Idea line of protective relays. The

More information

A low-cost, economical solution for distribution feeder protection

A low-cost, economical solution for distribution feeder protection SEL-351A Protection System A low-cost, economical solution for distribution feeder protection Achieve sensitive and secure fault detection using comprehensive protection functions. Track breaker status

More information

Protection, Automation, and Control System. Combine subcycle line protection with complete substation bay control

Protection, Automation, and Control System. Combine subcycle line protection with complete substation bay control Protection, Automation, and Control System Combine subcycle line protection with complete substation bay control Subcycle distance protection minimizes damage and expensive repairs on transmission lines.

More information

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II Reclosers Form 4C Microprocessor-Based Recloser Control KME4-88-1 (120V) and KME4-88-2 (240V) Analog Current Metering Accessory Design II Service Information S280-77-6 961015, 961016 Figure 1. Kyle KME4-88

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

ENhanced TEChnology. Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1

ENhanced TEChnology.   Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1 ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated

More information

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential

More information

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay 7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional

More information

Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers

Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers Switching Control Sentinel (SCS) for circuit breakers Voltage and current transients generated during switching

More information

Protection relay for secondary distribution

Protection relay for secondary distribution Protection relay for secondary distribution Dual and Self powered Signalling with flag indicators High electromagnetic compatibility Events recorder and specific test menu Protection relay for secondary

More information

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

ENhanced TEChnology.  Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver. ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Ver. 081226 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser

More information

EM133 EM133 TOU SMART ENERGY METER. Main Features. Multifunctional 3-Phase Smart Meter. Billing/TOU Energy Meter

EM133 EM133 TOU SMART ENERGY METER. Main Features. Multifunctional 3-Phase Smart Meter. Billing/TOU Energy Meter TOU SMART ENERGY METER SATEC is a Smart DIN Rail TOU Energy Meter. It is based on SATEC s best seller PM130 PLUS with an off-theshelf LCD display (similar to the BFM136 display). The provides the full

More information

FP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay

FP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay FP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay The power of fusion. 1874 1886 1893 1899 1906 1908 1911 1934 1962 1963 1976 1983 1990 1999 There s a certain energy at Eaton.

More information

Testing Instruments Manufactured by

Testing Instruments Manufactured by Circuit Breaker Dynamic Contact Resistance Meter HISAC Ultima Circuit Breaker Dynamic Test Set with up to Six Channel Dynamic Contact Resistance Meter 24 Binary Channels (4 Main + 4 PIR per Pole, 3 Poles

More information

RT4F-120V/20A-WAC RECTIFIER

RT4F-120V/20A-WAC RECTIFIER The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with

More information

Multilin EPM Energy and Demand Submeter with Wi-Fi. Monitoring & Metering. Communications. Key Benefits. Applications

Multilin EPM Energy and Demand Submeter with Wi-Fi. Monitoring & Metering. Communications. Key Benefits. Applications Multilin EPM 6100 Energy and Demand Submeter with Wi-Fi The EPM 6100 is a powerful tool that allows customers to monitor and manage their energy usage within factories, businesses and across campuses.

More information

RTU560. CT/VT Interface 560CVT10. Meter Operation. Application. Characteristics. Data Sheet CT/VT Interface 560CVT10. Instantaneous Meter Values

RTU560. CT/VT Interface 560CVT10. Meter Operation. Application. Characteristics. Data Sheet CT/VT Interface 560CVT10. Instantaneous Meter Values CT/VT Interface 560CVT10 The fault current is measured up to 20 times nominal current. Therefore the current inputs withstand 50 times nominal current for 1 s. The CT/VT interface is equipped with one

More information

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The

More information

ADDITIONAL INFORMATION MODBUS INSTRUCTION MANUAL. Request publication Request publication DNP 3.0 INSTRUCTION MANUAL

ADDITIONAL INFORMATION MODBUS INSTRUCTION MANUAL. Request publication Request publication DNP 3.0 INSTRUCTION MANUAL BE1-851E ENHANCED OVERCURRENT PROTECTION SYSTEM DEVICE FUNCTIONS 43 50 51 62 The BE1-851E is an enhanced overcurrent protection system based on the design of the BE1-851, a multifunction, numeric relay

More information

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES Introduction The supply of electrical energy occupies an important position in the life of modern society. Operation of commerce, industry, transport,

More information

BF

BF BE1-11i INTERTIE PROTECTION SYSTEM DEVICE FUNCTIONS The BE1-11i Intertie Protection System is a multifunction numeric relay providing the protection and control requirements outlined in IEEE 1547-2003

More information

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5 Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System

More information

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS Armando Guzmán Schweitzer Engineering Laboratories, Inc. Pullman, WA 99163 A reliable power system maintains frequency and voltage

More information

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection 1 Process PG&E Order No. 754 Analysis Receive Bus List from Planning that Meet the Criteria in Table A Protection Computes Actual Clearing

More information

EDR-3000 Eaton Distribution Relay

EDR-3000 Eaton Distribution Relay Supersedes November 2014 Contents Description Page General Description.... 2 Applications.... 3 Dimensions.... 5 Wiring Diagram.... 6 Specifications... 7 Ordering Information....11 Applications Provides

More information

SIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics

SIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics SIA-C Overcurrent and Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered Main characteristics The SIA-C is a overcurrent protection relay with self powered and dual powered (self

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating Advanced Line Differential Protection, Automation, and Control System Combine subcycle line protection with traveling-wave fault locating Subcycle differential and distance protection minimizes damage

More information

I/A Series HARDWARE Product Specifications

I/A Series HARDWARE Product Specifications I/A Series HARDWARE Product Specifications I/A Series Remote Terminal Unit (RTU) C50 3 Phase Digital Transducer Module FEATURES Simultaneous sampling eliminates skew error Replaces MW, MVAR, MVA, Volts,

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

BE1-951 MULTIFUNCTION PROTECTION SYSTEM ADVANTAGES

BE1-951 MULTIFUNCTION PROTECTION SYSTEM ADVANTAGES BE1-951 MULTIFUNCTION PROTECTION SYSTEM DEVICE FUNCTIONS The BE1-951 is a multifunction numeric relay that provides three phase, ground, and negative sequence directional or non-directional overcurrent

More information

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES BE1-50/51M TIME OVERCURRENT RELAY The BE1-50/51M Time Overcurrent Relay provides economical overload and fault protection for generators, transformers, lines and motors. ADVANTAGES Self powered from 50/60Hz

More information