1 Analog User s Guide TG Series Senva Sensors 9290 SW Nimbus Ave Beaverton, OR A Rev. Release Date Description of Change ECR 0A 4/14/2016 Initial Release --- Copyright All rights reserved. This document contains Senva Sensors proprietary information, and may not be reproduced or distributed without written permission.

2 Contents General Overview... 3 User Menu / Setup Menu Testing Menu References: TG Series Analog Installation Instructions Analog User s Guide, TG Series Page 2 of A

3 General Overview The TG product contains 3 menus: User Menu, Setup Menu, and Testing Menu. The User Menu gives access to system functional setpoints, the Setup Menu allows the user to view device sensor information and add or remove sensors, and the Testing Menu allows the user to turn on certain interfaces for a limited time in order to test functionality. Each menu is comprised of a variation of 4 primitive elements: Categories, Sub- Categories, Items, and Values/Options. Categories can contain items and sub-categories, while Sub-Categories contain only items. Items contain only values/options. Values are either integer or decimal based numbers, which can be incremented and decremented. Options are multiple choice based values, which can be scrolled through and selected. An example of each is shown below in Figure 1. Menu Category Sub-Category Item Options User Menu Quickstart A Default 0-10V 0-5V 4-20mA 1-5V Outputs Out1 Setpoints V.HI. Fan Relay. Min On Time Value 0-10 (volts) (minutes) Figure 1: Example of how the primitive elements are used to comprise the menus. Here the Quickstart category contains an item A, which has a set of multiple choice options. The Outputs category contains a sub-category Out1 Setpoints, which in turn contains an item V.HI that can be set to any value between 0-10 (in volts).the Fan Relay category has an item Min On Time which can be set to any value between 0 and 120 (in minutes). Buttons Select button. Up button. Down button. Navigation and Selection Pressing or while viewing a Category/Sub-Category/Item advances to the next or previous Category/Sub-Category/Item. Pressing or while viewing a Value increments or decrements the Value. Pressing or while viewing an Option scrolls through the available Options. Pressing while viewing a Category allows you to view the items and sub-categories it contains. Pressing while viewing an Item allows you to view and modify the values/options for that Item. Pressing while viewing a Value/Option applies your selection and returns you to the Item view. Each Menu contains an Item, which will exit the current menu. Each Category/Sub-Category contains an Item, which will return you to the previous Menu/Category. Note: Some Values/Options do not require the button to be pressed before your change is applied. Assume all changes to Values/Options occur at the time or is pressed Analog User s Guide, TG Series Page 3 of A

4 User Menu Access this menu by pressing the button for one second. Categories Quickstart (): Allows the user to select from a list of pre-defined user setpoint configurations for quick and easy startup. Analog Outputs ( ): Allows the user to select the output mode (voltage or current) for their analog outputs. Also contains 2 sub-categories for Analog output channels 1 and 2. This category is only available on the Analog version. o o Analog Output Channel 1 ( ): Contains all of the settings which control the output signal on channel 1. Analog Output Channel 2 ( ): Contains all of the settings which control the output signal on channel 2. CO Setpoints ( ): Contains all of the user configurable setpoints, which control the system response to the CO Gas Sensor. This category is only available on TG products which contain a CO sensor. NO2 Setpoints (): Contains all of the user configurable setpoints, which control the system response to the NO2 Gas Sensor. This category is only available on TG products which contain an NO2 sensor. Temperature Setpoints (): Contains all of the user configurable setpoints, as well as unit selection, which control the system response to the thermistor. Fan Relay ( ): Allows the user to customize the performance of the fan relay (warning relay). Alarm Relay ( ): Allows the user to customize the performance of the alarm relay. This category is only available on the Analog version. Buzzer (): Allows the user to customize the performance of the alarm buzzer. Display ( ): Allows the user to customize the performance of the display. Analog User s Guide, TG Series Page 4 of A

5 Applies the following setpoints to their respective sensors: CO Warning = 25, CO Alarm = 100, NO2 Warning = 1, NO2 Alarm = 3 (in PPM), Buzzer Delay = 30 (minutes). 0-10V Output Range (Default) 1-5V Output Range (Analog Version Only) 4-20mA Output Range (Analog Version Only) 0-5V Output Range (Analog Version Only) Applies the following setpoints to their respective sensors: CO Warning = 15, CO Alarm = 50, NO2 Warning = 0.7, NO2 Alarm = 2 (in PPM), Buzzer Delay = 30 (minutes). 0-10V Output Range 1-5V Output Range (Analog Version Only) 4-20mA Output Range (Analog Version Only) 0-5V Output Range (Analog Version Only) Applies the following setpoints to their respective sensors: CO Warning = 35, CO Alarm = 100, NO2 Warning = 1, NO2 Alarm = 5 (in PPM), Buzzer Delay = 30 (minutes). 0-10V Output Range 1-5V Output Range (Analog Version Only) 4-20mA Output Range (Analog Version Only) 0-5V Output Range (Analog Version Only) Applies the following setpoints to their respective sensors: CO Warning = 5, CO Alarm = 10, NO2 Warning = 0.5, NO2 Alarm = 1 (in PPM), Buzzer Delay = 2 (minutes). 0-10V Output Range 1-5V Output Range (Analog Version Only) 4-20mA Output Range (Analog Version Only) 0-5V Output Range (Analog Version Only) Analog User s Guide, TG Series Page 5 of A

6 Selects the units for the analog output signals. Voltage Out (Default) Current Out Selects the Output 1 sub-category. Selects the Output 2 sub-category. / Selects the sensor to be output on Output channel 1. No sensor selected. (Default) CO Gas. NO2 Gas. Temperature. Sets the max voltage for the output signal. Increments by whole volts. Default: Volts Sets the min voltage for the output signal. Increments by whole volts. Default: Volts Sets the max current for the output signal. Increments by whole milliamps. Default: Milliamps Sets the max voltage for the output signal. Increments by whole milliamps. Default: Milliamps Exits back to the Outputs category. Analog User s Guide, TG Series Page 6 of A

7 Sets the value in PPM which corresponds to the maximum analog output signal. Accepts any value between PPM. Increments/Decrements in integers. (Analog Version Only) Default: PPM Sets the value in PPM which corresponds to the minimum analog output signal. Accepts any value between PPM. Increments/Decrements in integers. (Analog Version Only) Default: PPM Sets the alarm setpoint level in PPM. Accepts any value between PPM. Increments/Decrements in integers. Default: PPM Sets the warning setpoint level in PPM. Accepts any value between PPM. Increments/Decrements in integers. Default: PPM Sets the hysteresis, in PPM, which is how far below the Warning/Alarm setpoint the sensor value must drop before changing state from Alarm to Warning or Warning to Normal. Default: PPM Sets the value in PPM which corresponds to the maximum analog output signal. Accepts any value between 0-10 PPM. Increments/Decrements in integers. (Analog Version Only) Default: PPM Sets the value in PPM which corresponds to the minimum analog output signal. Accepts any value between 0-10 PPM. Increments/Decrements in integers. (Analog Version Only) Default: PPM Sets the alarm setpoint level in PPM. Accepts any value between 0-10 PPM. Increments/Decrements in integers. Default: PPM Analog User s Guide, TG Series Page 7 of A

8 Sets the warning setpoint level in PPM. Accepts any value between 0-10 PPM. Increments/Decrements in integers. Default: PPM Sets the hysteresis, in PPM, which is how far below the Warning/Alarm setpoint the sensor value must drop before changing state from Alarm to Warning or Warning to Normal. Default: PPM Selects the units for temperature to be displayed and output in. Degrees Celsius Degrees Fahrenheit (Default) Sets the value, in Degrees Celsius, which corresponds to the maximum analog output signal. Accepts any value between -20 C (-4 F) and 85 C (185 F). Increments/Decrements in integers. (Analog Version Only) Default: F Sets the value, in Degrees Celsius, which corresponds to the minimum analog output signal. Accepts any value between -20 C (-4 F) and 85 C (185 F). Increments/Decrements in integers. (Analog Version Only) Default: F Sets the minimum time, in minutes, which the relay must be active before it can turn off. Accepts any value between minutes. Default: Minute Analog User s Guide, TG Series Page 8 of A

9 Sets the minimum time, in minutes, which the relay must be inactive before it can turn on. Accepts any value between minutes. Default: Minute Sets the maximum time, in minutes, which the relay can be inactive. Accepts any value between minutes. If set to 0 the maximum off time will be infinite. Default: Minutes Sets the minimum time, in minutes, which the relay must be active before it can turn off. Accepts any value between minutes. Default: Minute Sets the minimum time, in minutes, which the relay must be inactive before it can turn on. Accepts any value between minutes. Default: Minute Sets the maximum time, in minutes, which the relay can be inactive. Accepts any value between minutes. If set to 0 the maximum off time will be infinite. Default: Minutes Sets the time delay, in minutes, before the buzzer activates once its activation setpoint has been reached. Accepts any value between 0-60 minutes. Default: Minutes Sets the minimum time, in minutes, which the buzzer must be active before it can turn off. Accepts any value between minutes. Default: Minutes Analog User s Guide, TG Series Page 9 of A

10 Sets the minimum time, in minutes, which the buzzer must be inactive before it can turn on. Accepts any value between minutes. Default: Minutes Sets the sensor values to be displayed in the Idle menu. CO, NO2, and Temperature. (CO, NO2, and Temp sensor must be installed) CO. (CO sensor must be installed) NO2. (NO2 sensor must be installed) Temperature. (Temp sensor must be installed) CO, NO2. (CO and NO2 sensors must be installed) CO, Temperature. (CO and Temp sensor must be installed) NO2, Temperature. (NO2 and Temp sensor must be installed) No values selected. Sets the contrast of the display. The higher the value of the contrast, the darker the lettering on the screen will be. Accepts any integer value from Default: Sets the amount of time, in seconds, that a value in the Idle menu is displayed before automatically moving to the next value. Accepts any integer value from 1-10 seconds. Default: Seconds Analog User s Guide, TG Series Page 10 of A

11 Setup Menu Access this menu by pressing the and buttons simultaneously for one second. Categories CO ( ): Allows the user to view information about the CO sensor (na/ppm, and sensor lifetime left in days), as well as add/remove the sensor and set a 0 PPM point. NO2 (): Allows the user to view information about the NO2 sensor (na/ppm, and sensor lifetime left in days), as well as add/remove the sensor and set a 0 PPM point. Displays the device firmware version string. The version string contains the major, minor, and patch levels of the device firmware. Shows the nanoamp per PPM setting for the CO sensor. If the value is more than 4 digits long it will be rounded to only 3 digits. Example: will become Shows the number of days remaining in the CO sensor s lifespan. This value is used to see if a sensor needs to be replaced in the near future. Allows the user to set the 0 PPM present value into the device. This should only be used in an environment where the user is sure there is zero CO gas present. Allows the user to clear the current CO zero setting of the device. Allows the user to add a CO sensor to their device. If a CO sensor is already installed it will be overwritten at the end of the Add process. Allows the user to remove a CO sensor from their device. This item is only visible if a CO sensor is currently installed. Exits back to the main Setup Menu screen. Analog User s Guide, TG Series Page 11 of A

12 Allows the user to set the Integer value for the nanoamp per PPM setting of the CO sensor. Allows the user to set the Decimal value for the nanoamp per PPM setting of the CO sensor, in hundredths of PPM. Applies the nanoamp per PPM setting for the CO sensor, as provided by the user in the and Items. The and values will not be permanently set until they are applied through this Item. Exits back to the CO Category screen in the Setup Menu. Shows the nanoamp per PPM setting for the NO2 sensor. You can use this to verify that an added sensor value is correct. If the value is more than 4 digits long it will be rounded to only 1 decimal point. Example: will become Shows the number of days remaining in the NO2 sensor s lifespan. This value is used to see if a sensor needs to be replaced in the near future. Allows the user to set the 0 PPM present value into the device. This should only be used in an environment where the user is sure there is zero NO2 gas present. Allows the user to clear the current NO2 zero setting of the device. Allows the user to add an NO2 sensor to their device. If an NO2 sensor is already installed it will be overwritten at the end of the Add process. Allows the user to remove an NO2 sensor from their device. Exits back to the main Setup Menu screen. Analog User s Guide, TG Series Page 12 of A

13 Allows the user to set the Integer value for the nanoamp per PPM setting of the NO2 sensor. Allows the user to set the Decimal value for the nanoamp per PPM setting of the NO2 sensor, in hundredths of PPM. Applies the nanoamp per PPM setting for the NO2 sensor, as provided by the user in the and Items. The and values will not be permanently set until they are applied through this Item. Exits back to the NO2 Category screen in the Setup Menu. Analog User s Guide, TG Series Page 13 of A

14 Testing Menu Access this menu by pressing the and buttons simultaneously for one second. Categories NA Allows the user to set the testing interval. This interval will be acknowledged by all tests activated by the user. Accepts any value between seconds. Default: Seconds Allows the user to force the output signal to its highest value (ie. 20mA in Current mode, or 10 Volts in voltage mode). Begin output testing Turn off output testing Allows the user to turn on the Fan relay for the length of the testing interval. Begin Fan relay testing. Turn off Fan relay testing. Allows the user to turn on the Alarm relay for the length of the testing interval. Begin Alarm relay testing. Turn off Alarm relay testing. Allows the user to turn on the Piezo Buzzer for the length of the testing interval. Begin Buzzer testing. Turn off Buzzer testing. Analog User s Guide, TG Series Page 14 of A

User s Guide TG Series C. Senva Sensors 9290 SW Nimbus Ave Beaverton, OR 97008

User s Guide TG Series C. Senva Sensors 9290 SW Nimbus Ave Beaverton, OR 97008 User s Guide TG Series Senva Sensors 9290 SW Nimbus Ave Beaverton, OR 97008 154-0031-0C Rev. Release Date By Description of Change ECR 0A 4/14/2016 CKB Initial Release --- 0B 3/7/2017 CKB Updated for RS485

More information

B. Rev. Release Date Description of Change ECR 0A 10/10/2014 Initial Release --- 0B 10/30/2014 Added firmware version to setup menu ---

B. Rev. Release Date Description of Change ECR 0A 10/10/2014 Initial Release --- 0B 10/30/2014 Added firmware version to setup menu --- User s Guide AQ Series Senva Sensors 9290 SW Nimbus Ave Beaverton, OR 97008 154-0011-0B Rev. Release Date Description of Change ECR 0A 10/10/2014 Initial Release --- 0B 10/30/2014 Added firmware version

More information

Model 305e OEM CO 2 concentration sensor

Model 305e OEM CO 2 concentration sensor Model 305e OEM CO 2 concentration sensor preliminary Reference manual DIGITAL CONTROL SYSTEMS 7401 SW Capitol Hwy. Portland, OR 97219 USA 503/246-8110 503/246-6747 (fax) www.dcs-inc.net Scope...3 Introduction...3

More information

ERC 21X Modbus parameter

ERC 21X Modbus parameter Programming Guide ERC 21X Modbus parameter Copyright Danfoss Produced by ZA 2015.02 Programming guide ERC21X Modbus parameter DKRCC.EZ.RL0.A1.02 / 520H9702 1 ERC 211-1 relay Software version: 4.13 Configuration

More information

ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet DataSheet ev 1.12.307/4.0 Jun 20, 2018 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

EnCell Battery Cell Monitor

EnCell Battery Cell Monitor EnCell Battery Cell Monitor Instruction Manual Model RCM15S12 NERC Compliant YO R U H T PA TO Z O R E W O D N M I T E enchargepowersystems.com sales@enchargepowersystems.com (888) 407.5040 Contents 1 Warnings,

More information

Model No Universal Input Indicator Start-up Guide

Model No Universal Input Indicator Start-up Guide Model No. 1480 Universal Input Indicator Start-up Guide Contents 1. Setting up a unit straight out of the box... 3 1.1. Entry into Configuration mode... 3 1.2. Scrolling through Parameters and s... 3 1.3.

More information

R7X CONFIGURATOR. (model: R7CON) Users Manual , Minamitsumori, Nishinari-ku, Osaka JAPAN Tel: Fax:

R7X CONFIGURATOR. (model: R7CON) Users Manual , Minamitsumori, Nishinari-ku, Osaka JAPAN Tel: Fax: R7X CONFIGURATOR (model: R7CON) Users Manual 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Tel: +81-6-6659-8201 Fax: +81-6-6659-8510 http://www.m-system.co.jp/ E-mail: info@m-system.co.jp R7CON

More information

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet DataSheet ev 1.12.302/4.3 October 27, 2014 Operating Sequence Standard Occupied During normal occupied operation the display will

More information

Contents 1 Warnings, Cautions, and Notes Description Features... 1

Contents 1 Warnings, Cautions, and Notes Description Features... 1 EnCell Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 1 3 Features... 1 3.1 STANDARD FEATURES... 1 3.2 FRONT PANEL FEATURES... 2 3.2.1 Display... 2 3.2.2 OK LED... 2 3.2.3 FAULT LED...

More information

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION Revised Last Revised by Alex Messner This page was intentionally left blank. Table of Contents 1 Overview... 2 2 User Interface... 3 2.1 LEDs... 3 2.2 Buttons...

More information

CDD Carbon Dioxide Transmitter

CDD Carbon Dioxide Transmitter Introduction The OSA CO2 transmitter uses Infrared Technology to monitor CO2 levels within a range of 0 2000 ppm and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. The enclosure is designed to operate

More information

ExactLogic BACnet Communicating Thermostat EXL01716 Sequence Datasheet Duel Deck VAV

ExactLogic BACnet Communicating Thermostat EXL01716 Sequence Datasheet Duel Deck VAV ExactLogic BACnet Communicating Thermostat EXL01716 Sequence Datasheet Duel Deck VAV DataSheet ev 1.12.302/4.1 June 26, 2018 Operating Sequence Standard Occupied Thermostat occupancy can be set from a

More information

Series SD-3PB Digital THERMOSTAT + TIMER

Series SD-3PB Digital THERMOSTAT + TIMER SD-3PB Thermostat and Interval Timer in one Unit. This microcomputer based controller consists of two sections: The Digital Timer and Digital Thermostat, working together to control the power switched

More information

CDD4 Series Room CO2 Transmitter Installation Instructions

CDD4 Series Room CO2 Transmitter Installation Instructions CDD4 Series Room CO2 Transmitter Installation Instructions Introduction The CO2 transmitter uses Infrared Technology to monitor CO2 levels and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. Options include

More information

Installation and Operation Guide

Installation and Operation Guide Installation and Operation Guide KMD 1162 NetSensor Contents Specifications... 2 Network Cable Preparation... 4 Rough-in preparation... 5 Installing the NetSensor... 5 Operation... 6 Maintenance... 7 Programming

More information

CDD4 Duct Carbon Dioxide Transmitter

CDD4 Duct Carbon Dioxide Transmitter Drill or punch a 1-1/8 or 1-1/4 hole in the duct at the preferred location and insert the probe into the hole to mark the enclosure mounting holes. Remove the unit and drill the four mounting holes. Clean

More information

LD-RTD / LD-TC Temperature Controller

LD-RTD / LD-TC Temperature Controller 1 LD-RTD / LD-TC Temperature Controller Available in either an RTD model or a thermocouple model, these units accept all common temperature probe types, and offer a technically advanced, but cost effective

More information

ORP Arc Sensors. Modbus RTU Programmer s Manual. Firmware version: ERXUM031. ORP Arc Sensors Modbus RTU Programmer s Manual (ERXUM031)

ORP Arc Sensors. Modbus RTU Programmer s Manual. Firmware version: ERXUM031. ORP Arc Sensors Modbus RTU Programmer s Manual (ERXUM031) ORP Arc Sensors RTU Programmer s Manual Firmware version: ERXUM031 624465/01 page 1 / 70 Important Notice All rights reserved. No part of this document may be reproduced, stored in a retrieval system,

More information

DEKKER KNOWLEDGE DATABASE KNOWLEDGE IS POWER

DEKKER KNOWLEDGE DATABASE KNOWLEDGE IS POWER DEKKER KNOWLEDGE DATABASE For Use with DEKKER Vacuum Systems Equipped with the DEKKER Controller Each Vmax system is tested and checked at the factory prior to shipment to ensure trouble-free operation.

More information

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet DataSheet ev 1.12.307/4.0 June 14, 2018 Operating Sequence Standard Occupied During normal occupied

More information

(Assembly instructions and latest firmware you can find on my website) ALENA Assembled my own hands

(Assembly instructions and latest firmware you can find on my website) ALENA Assembled my own hands wwwkama-labscom (Assembly instructions and latest firmware you can find on my website) ALENA Assembled my own hands Thanks for purchase!!! Features: * 6 IN4 Russian NIXIE tubes (made in 1970-80) * 2 IN-3

More information

Model Ultima OPIR-5. Infrared Open Path Gas Detector HART Field Device Specification. Instruction Manual

Model Ultima OPIR-5. Infrared Open Path Gas Detector HART Field Device Specification. Instruction Manual Model Ultima OPIR-5 Infrared Open Path Gas Detector HART Field Device Specification The information and technical data disclosed in this document may be used and disseminated only for the purposes and

More information

MAXDTC-BT Family User Manual

MAXDTC-BT Family User Manual MAXDTC-BT Family User Manual Description The MAXDTC-BT is a fully programmable industrial temperature controller. The controller is configurable and monitorable thru a Bluetooth connection from your Android

More information

Series SD6 Limit with DeviceNet

Series SD6 Limit with DeviceNet Series SD6 Limit with DeviceNet DeviceNet Communications This appendix describes the DeviceNet protocol as it is implemented in the Series SD6 controller. It primarily describes the objects and attributes

More information

HART USER GUIDE FOR GASSONIC OBSERVER-H ULTRASONIC GAS LEAK DETECTOR

HART USER GUIDE FOR GASSONIC OBSERVER-H ULTRASONIC GAS LEAK DETECTOR HART USER GUIDE FOR GASSONIC OBSERVER-H ULTRASONIC GAS LEAK DETECTOR This page intentionally left blank. HART USER GUIDE FOR GASSONIC OBSERVER-H ULTRASONIC GAS LEAK DETECTOR HART User Guide for Gassonic

More information

Factory Packaged Controls. MODGAS-X Controller Field Technical Guide

Factory Packaged Controls. MODGAS-X Controller Field Technical Guide Factory Packaged Controls MODGAS-X Controller Field Technical Guide TABLE OF CONTENTS GENERAL INFORMATION... 3 Overview... 3 Features... 3 INSTALLATION & WIRING... 4 Important Wiring Considerations...

More information

TEC Controller Extended I/O Application 2497 with Slave Mode Application Application Note Building Technologies

TEC Controller Extended I/O Application 2497 with Slave Mode Application Application Note Building Technologies TEC Controller Extended I/O Application 2497 with Slave Mode Application 2489 Application Note 140-1074 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 4 Hardware Outputs... 4

More information

MODEL IR5500 Infrared Open Path Gas Detector HART Field Device Specification

MODEL IR5500 Infrared Open Path Gas Detector HART Field Device Specification MODEL IR5500 Infrared Open Path Gas Detector HART Field Device Specification The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the

More information

Integral Electronics with Local Menu System

Integral Electronics with Local Menu System Integral Electronics with Local Menu System THERMAL INSTRUMENT COMPANY Trevose, PA 215-355-8400 New Menu Features & Benefits Available with either Hart Communication or Modbus output Visibility to current

More information

Oxygen Pen Copyright 2015 by Sper Scientific ALL RIGHTS RESERVED. Printed in the USA

Oxygen Pen Copyright 2015 by Sper Scientific ALL RIGHTS RESERVED. Printed in the USA Oxygen Pen 800047 Oxygen Pen - 800047 Copyright 2015 by Sper Scientific ALL RIGHTS RESERVED. Printed in the USA The contents of this manual may not be reproduced or transmitted in any form or by any means

More information

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities MiG2 CONTROLLERS 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities The MiG2 controllers incorporate: 2 Inputs (Configurable as Resistive, 0 10V, 0 20mA or 4 20mA) 2 or 4 Relay Outputs

More information

OPERATION INSTRUCTIONS

OPERATION INSTRUCTIONS 2018 Lennox Industries Inc. Dallas, Texas, USA OPERATION INSTRUCTIONS V0STAT52 Wireless Indoor Unit Controller CONTROLS 507459-04 05/2018 This manual must be left with the owner for future reference. IMPORTANT

More information

Instruction Manual CTC-1

Instruction Manual CTC-1 Troubleshooting & Specs CTC-1 Amps / Volts requirements Min / Max operating temperature Min / Max operating Humidity Temperature Measurement range Temperature Accuracy CO2 sensor type CO2 Measurement range

More information

Status line The top line of the LCD display shows the basic status information of the drive.

Status line The top line of the LCD display shows the basic status information of the drive. Control panels 91 Status line The top line of the LCD display shows the basic status information of the drive. LOC 49.1Hz LOC MAIN MENU 1 No. Field Alternatives Significance 1 Control location LOC Drive

More information

HT Series Wall Mount with Relay Setpoints, LCD, and Humidistat and Thermostat Control

HT Series Wall Mount with Relay Setpoints, LCD, and Humidistat and Thermostat Control Wall Mount with Relay Setpoints, LCD, and Humidistat and Thermostat Control NOTICE This product is not intended for life or safety applications. Do not install this product in hazardous or classified locations.

More information

NFC110. Flow Computer For Low Pulses FEATURES

NFC110. Flow Computer For Low Pulses FEATURES Flow Computer For Low Pulses FEATURES l STABLE READING WITH PULSES DOWN TO ONE PULSE EVERY 5 MINUTES l PULSE FLOW INPUT UP TO 100 Hz, CAN POWER THE SENSOR l WORKS WITH OPTO-COUPLER FLOW METERS l SEVEN

More information

P2 Configuration Guide

P2 Configuration Guide P2 Configuration Guide March 2018 Rev. 4.00 #220, 550 71 st Avenue SE Calgary, Alberta, Canada T2H 0S6 Phone: (403) 255-9544 Fax: (403) 259-2343 www.barnettprotalk.com E-mail: sales@barnettprotalk.com

More information

LogBox-BLE. INSTRUCTION MANUAL V1.0x NOVUS AUTOMATION 1/51

LogBox-BLE. INSTRUCTION MANUAL V1.0x NOVUS AUTOMATION 1/51 LogBox-BLE INSTRUCTION MANUAL V1.0x NOVUS AUTOMATION 1/51 1. SAFETY ALERTS...3 2. INTRODUCTION...4 3. DISPLAY AND NAVIGATION...5 3.1 DISPLAY INFORMATION...5 3.2 OPERATION KEYS...6 3.3 NAVIGATION KEYS...6

More information

IPM500 Series QuickStart Manual

IPM500 Series QuickStart Manual IPM500 Series QuickStart Manual The Force of Innovation 10 Thomas Irvine, CA 92618 USA (949) 465-0900 FAX: (949) 465-0905 E-Mail: HTUfutek@futek.comUTH www.futek.com Manufacturer of Load Cells, Pressure

More information

M1000 INTELLIGENT ZONE CONTROL SYSTEM

M1000 INTELLIGENT ZONE CONTROL SYSTEM HARDWARE GUIDE DIMENSIONS & SPECIFICATIONS REV. 5.2 M1000 INTELLIGENT ZONE CONTROL SYSTEM ROOFTOP CONTROLLER 2 Table of Contents GENERAL INFORMATION... 3 PL-M1000 Rooftop Controller...3 Description...3

More information

32MP Gateway. Overview and Configuration Manual

32MP Gateway. Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual This document is the property of Carrier Corporation and is delivered on the express condition that it is not

More information

MICROPROCESSOR BATCH CONTROLLER MOD.DOSAX

MICROPROCESSOR BATCH CONTROLLER MOD.DOSAX MICROPROCESSOR BATCH CONTROLLER MOD.DOSAX 2020-2030-2040 THE APPLIANCE DESCRIBED HEREIN CONFORMS TO STANDARDS EN55011, EN61000-3-2, IEC 1000-4-2, IEC1000-4-4 24/01/2006 VERSION 3.0 1 OPERATING MODE SELECTION:

More information

Introduction. To use Carrier wireless sensors, you must have: A i-vu v6.5 or later system v6-00 or later drivers

Introduction. To use Carrier wireless sensors, you must have: A i-vu v6.5 or later system v6-00 or later drivers Wireless Sensor CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-583-01 6/2/2017 Verify that you have the most current version of this

More information

Innovative Electronics for a Changing World INDEX

Innovative Electronics for a Changing World INDEX Innovative Electronics for a Changing World INDEX 1. SYSTEM DESCRIPTION 2. BOARD CONNECTIONS terminals and indicators 3. CONNECTION DIAGRAM 4. START UP GUIDE and passwords 5. HOME PAGE 6. STATUS PAGE 7.

More information

Basic control panel. Features. Control panels 75

Basic control panel. Features. Control panels 75 Control panels 75 Basic control panel Features The basic control panel features: numeric control panel with an LCD display copy function parameters can be copied to the control panel memory for later transfer

More information

Dryer. M720 Programming and Operation Manual. July 15, 2015 Revision 1.51

Dryer. M720 Programming and Operation Manual. July 15, 2015 Revision 1.51 Dryer M720 Programming and Operation Manual July 15, 2015 Revision 1.51 Contents 1 Important Safety Information 1 1.1 FOR YOUR SAFETY - CAUTION!............................. 1 2 Control Overview 2 2.1

More information

Page 1 MRK-D-0011, V1.1 Aeroqual SM50 User Guide

Page 1 MRK-D-0011, V1.1 Aeroqual SM50 User Guide Page 1 Table of Contents 1. Description... 3 2. Operating Instructions... 3 2.1. Power... 3 2.2. Warm Up... 3 2.3. Input and Output signals... 3 2.3.1. ZERO CAL... 4 2.3.2. RESET... 4 2.3.3. SPAN... 4

More information

User Manual Digi-Sense 12-Channel Benchtop Data Logging Thermocouple Thermometer

User Manual Digi-Sense 12-Channel Benchtop Data Logging Thermocouple Thermometer User Manual Digi-Sense 12-Channel Benchtop Data Logging Thermocouple Thermometer Model: 92000-01 THE STANDARD IN PRECISION MEASUREMENT Table of Contents Introduction... 3 Unpacking... 3 Initial Setup...3

More information

Range. Body Material. Max. Press ms K=0, C 4 bar Glass Graphite 13.5 PG Full integrated 5-meter cable

Range. Body Material. Max. Press ms K=0, C 4 bar Glass Graphite 13.5 PG Full integrated 5-meter cable Conductivity Range Conductivity 0 20 μs; 0 200 μs; 0 2.000 μs; 0 20.000 μs; 0 200.000 μs Resolution 0,01 μs; 0,1 μs; 1 μs; μs Avaiable versions with double parameter 4238-22 [ph/orp - Conductivity] 4293-22

More information

Contents. Temperature & Process Measurement Indicators Setup Guide

Contents. Temperature & Process Measurement Indicators Setup Guide Contents Introduction... 2 Installation... 3 Connections... 5 Connecting the Sensor... 6 Powering the Instrument... 7 Operator Functions... 8 The Setup Menus... 9 Configuration Menu Map... 12 Menu Options...

More information

ACE-SDC-V3 Stepper Driver +Controller with USB 2.0 Communication

ACE-SDC-V3 Stepper Driver +Controller with USB 2.0 Communication ACE-SDC-V3 Stepper Driver +Controller with USB 2.0 Communication ACE-SDC-V3 Manual page 1 rev 1.00 COPYRIGHT 2008 ARCUS, ALL RIGHTS RESERVED First edition, April 2008 ARCUS TECHNOLOGY copyrights this document.

More information

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER SERIES CMT CARBON MONOXIDE GAS TRANSMITTER INSTALLATION OPERATION AND MAINTENANCE MANUAL DWYER INTRUMENTS, INC. PO BOX 373, MICHIGAN CITY, IN. 46360 USA PHONE: 800-872-9141 FAX: 219-872-9057 Web: www.dwyer-inst.com

More information

PF MODBUS REGISTER MAP. v1.4 Revised Nov 29, 2016

PF MODBUS REGISTER MAP. v1.4 Revised Nov 29, 2016 PF3107-00 MODBUS REGISTER MAP v1.4 Revised TRADEMARKS AND COPYRIGHT All content is subject to copyright and may not be reproduced in any form without the express written consent of the author. 2016 Profire

More information

Model IR4000M. HART Field Device Specification Multi-Point Monitor. Instruction Manual 07-08

Model IR4000M. HART Field Device Specification Multi-Point Monitor. Instruction Manual 07-08 Model IR4000M HART Field Device Specification Multi-Point Monitor The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR QLC MANUAL 013114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING

More information

Master-Touch INSTRUCTION MANUAL. Series 9000MP Multipoint System Series 9600MP System Control Panel Thermal Gas Mass Flowmeters. version 7.

Master-Touch INSTRUCTION MANUAL. Series 9000MP Multipoint System Series 9600MP System Control Panel Thermal Gas Mass Flowmeters. version 7. Master-Touch version 7.x firmware Series 9000MP Multipoint System Series 9600MP System Control Panel Thermal Gas Mass Flowmeters INSTRUCTION MANUAL 80201501 Addendum Rev. C www.epiflow.com Eldridge Products,

More information

ControlMaster CM10, CM30 and CM50 Universal process controllers, 1 /8, 1 /4 and 1 /2 DIN

ControlMaster CM10, CM30 and CM50 Universal process controllers, 1 /8, 1 /4 and 1 /2 DIN User Guide Basic Functionality IM/CM/B EN Rev. Q ControlMaster CM10, CM30 and CM50 The Company We are an established world force in the design and manufacture of instrumentation for industrial process

More information

ThermoPad Reference Manual

ThermoPad Reference Manual ThermoPad Reference Manual Revision 0.6 www.coolautomation.com 2/18/2015 2 Table of Contents 1 Revision History 3 2 Specification 4 3 Thermopad Models 5 4 Terminals 6 5 MODBUS Map 7 6 Special Features

More information

Omni. User Manual. Economic Self-Tune PID Temperature Controller. Omni 96. Omni 72 72X72. Omni ~ 265 V AC SUPPLY

Omni. User Manual. Economic Self-Tune PID Temperature Controller. Omni 96. Omni 72 72X72. Omni ~ 265 V AC SUPPLY Omni Economic Self-Tune PID Temperature Controller Omni 7 Omni 4 6 5 4 3 1 7X7 7 1 11 5 ~ 65 V AC SUPPLY Omni 6 CONTENTS 1. PANEL MOUNTING & ELECTRICAL CONNECTIONS 1. FRONT PANEL : LAYOUT AND OPERATION

More information

RAMSES D GB F NL. Installation and operating instructions Room thermostat. RAMSES 832 top2

RAMSES D GB F NL. Installation and operating instructions Room thermostat. RAMSES 832 top2 309 358 04 RAMSES RAMSES 811 top2 RAMSES 831 top2 811 9 132 831 9 132 RAMSES 812 top2 RAMSES 832 top2 812 0 132 832 0 132 GB Installation and operating instructions Room thermostat D GB F E I NL RAMSES

More information

Modbus on tsense. Table of contents:

Modbus on tsense. Table of contents: Modbus on tsense Table of contents: 1. Revision information.... General... 3. Byte transmission... 3 4. Modbus registers on sensor... 3 5. Serial line frame and addressing... 4 6. Bus timing... 4 7. Function

More information

CDR-RH Room CO 2, Temperature and Humidity Sensors (Controllers)

CDR-RH Room CO 2, Temperature and Humidity Sensors (Controllers) Product sheet SN1.401 Type CDR-RH CDR-RH Room CO 2, Temperature and Humidity Sensors (Controllers) CDR-RH sensors are designed to detect carbon dioxide concentration, relative humidity and temperature

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Network Communication The device parameters must be set before connection to the network and will ensure each device will have a unique MAC address and Device Instance for startup. On startup, the MAC

More information

Measure & Control Temperature & CO2 levels with analog & digital I/O

Measure & Control Temperature & CO2 levels with analog & digital I/O MADE IN OZ HTC-DIGITAL-LCD PROGRAMMABLE TEMPERATURE CONTROLLER c/w YEARLY PROGRAMMABLE TIME SWITCH COMPATIBLE WITH A WIDE RANGE OF SENSORS ROOM O/A WALL DUCT PIPE Use Features Measure & Control Temperature

More information

INSTRUCTIONS FOR USING THE CONTROL PANEL

INSTRUCTIONS FOR USING THE CONTROL PANEL DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY 1.09.370E 10.01.2007 VALLOX These instructions replace and complement the instructions for use and maintenance of the following VALLOX units: VALLOX DIGIT

More information

MOD-RI Room Interface Modules with Modbus

MOD-RI Room Interface Modules with Modbus Product sheet MOD3.00 Type MOD-RI MOD-RI Room Interface Modules with Modbus The MOD-RI are room interface modules designed to provide room control interface for the building management systems. The MOD-RI

More information

BACnet PTEC Controller Constant Volume - Cooling Only, Application Application Note Building Technologies

BACnet PTEC Controller Constant Volume - Cooling Only, Application Application Note Building Technologies BACnet PTEC Controller Constant Volume - Cooling Only, Application 6660 Application Note 140-1107 Building Technologies Table of Contents Overview... 4 BACnet... 5 Hardware Inputs... 5 Room Unit Identification...

More information

FRICK QUANTUM ACUair CONTROL PANEL Version 2.1x

FRICK QUANTUM ACUair CONTROL PANEL Version 2.1x S90-500 O/JUL 2002 File: SERVICE MANUAL - SECTION 90 Replaces: S90-500 O/APR-2001 Dist: 3, 3a, 3b, 3c OPERATION FRICK QUANTUM ACUair CONTROL PANEL Version 2.1x S90-500 O FRICK QUANTUM ACUair CONTROL PANEL

More information

CommandCenter Operator Panel

CommandCenter Operator Panel CommandCenter Operator Panel Introduction This document describes the different features of the Operator Panel (local or remote) that is used with the Seresco units. Startup Screens When the unit start

More information

FX 2 Instruction Manual

FX 2 Instruction Manual FX 2 Instruction Manual Climma Compact Version Annapolis MD USA 301 352 6962 info@veco-na.com Introduction: The FX2-DX digital controller operates onboard air conditioning equipment to provide room temperature

More information

QEL - DEDESCO 5935 Ottawa Street Richmond, Ontario, Canada, K0A 2Z0.

QEL - DEDESCO 5935 Ottawa Street Richmond, Ontario, Canada, K0A 2Z0. QEL - DEDESCO 5935 Ottawa Street Richmond, Ontario, Canada, K0A 2Z0. Q5 TRANSMITTER Software Specification Document ModBus Protocol 85940-001-000 Name Signature Date Prepared: Xiangyang 2008/08 Reviewed:

More information

Loadcell. Table Of Contents. Loadcell Help Rev: 17/06/04

Loadcell. Table Of Contents. Loadcell Help Rev: 17/06/04 Loadcell Help Rev: 17/06/04 Table Of Contents Loadcell... 1 Loadcell Quickstart... 1 FB Operations... 1 Loadcell Help Rev: 17/06/04... 2 Loadcell Quickstart... 2 FB Operations... 2 Loadcell Hardware Configuration...

More information

Zio Lite TOOL CONFIGURATION, NETWORK ACCESS, SYLK CAPACITY, AND OPERATION TR40/TR42

Zio Lite TOOL CONFIGURATION, NETWORK ACCESS, SYLK CAPACITY, AND OPERATION TR40/TR42 Zio Lite TOOL CONFIGURATION, NETWORK ACCESS, SYLK CAPACITY, AND OPERATION TR40/TR42 Contents Tool Configuration... 1 General Settings Tab (Fig. 1).... 2 Categories and Parameters Tab (Fig. 4).... 5 Home

More information

Operating instructions for RAMSES 811 top2_812 top2 and RAMSES 831 top2_832 top2

Operating instructions for RAMSES 811 top2_812 top2 and RAMSES 831 top2_832 top2 Operating instructions for RAMSES 811 top2_812 top2 and RAMSES 831 top2_832 top2 Dear client, if you have the newer device, please use page 1 to 33 RAMSES RAMSES 811 top2 RAMSES 831 top2 8119132 8319132

More information

Model (DRS-54V) Ver. 2.0 August. Dongah Rectifier System Operating Manual

Model (DRS-54V) Ver. 2.0 August. Dongah Rectifier System Operating Manual 2011 Model (DRS-54V) Ver. 2.0 August DRS-54V Dongah Rectifier System AC 240V 1Phase 3WIRE Input -54VDC Output 55A per Shelf 18.5Amps per Module DONGAHELECOMM.LTD _ Proprietary This document contains proprietary

More information

N2 Analog Input/ BACnet Analog Input

N2 Analog Input/ BACnet Analog Input Object Dictionary 1 N2 Analog Input/ BACnet Analog Input Introduction Note: The Johnson Controls N2 Analog Input object is considered a BACnet Analog Input object because it supports BACnet functionality.

More information

USER MANUAL V1.1. Setpoint unit 2022Setp

USER MANUAL V1.1. Setpoint unit 2022Setp USER MANUAL 0.4.005 V. Setpoint unit 0Setp INTRODUCTION 0Setp is a special edition of Nokeval 0 multi-input indicator. It is available in wall-mounted 800 enclosure or in a /8 DIN panel enclosure. Normally

More information

Arc Module SU ph. Modbus RTU Programmer s Manual. Firmware version: EPHUM070. Arc Module SU ph Modbus RTU Programmer s Manual (EPHUM070)

Arc Module SU ph. Modbus RTU Programmer s Manual. Firmware version: EPHUM070. Arc Module SU ph Modbus RTU Programmer s Manual (EPHUM070) Arc Module SU ph RTU Programmer s Manual Firmware version: EPHUM070 627143/00 page 1 / 56 Important Notice All rights reserved. No part of this document may be reproduced, stored in a retrieval system,

More information

INSTRUCTION MANUAL FOR GUARDIAN INFINITY SIM PROGRAM

INSTRUCTION MANUAL FOR GUARDIAN INFINITY SIM PROGRAM INSTRUCTION MANUAL FOR GUARDIAN INFINITY SIM PROGRAM Model: INF Firmware 60.xxx Date: July 16, 2008 Page 0 of 29 INDEX 1- INFSIM OVERVIEW:...3 1.1- STARTING THE SOFTWARE:...3 1.2- ESTABLISHING COMMUNICATIONS:...3

More information

SlimLine. Compliant to DO-160D. Document # Rev G. www. rosenaviation.com. www. rosenaviation.com

SlimLine. Compliant to DO-160D. Document # Rev G. www. rosenaviation.com. www. rosenaviation.com 6.5 Model DISPLAY SlimLine Number 6500 www. rosenaviation.com CORPORATE OFFICE 1020 Owen Loop South Eugene, OR 97402 1-888-668-4955 Fax (541) 342-4912 6500 www. rosenaviation.com Document # 9002751 Rev

More information

ECI1. COMPASS display. ECI1-REV For latest update: Electronic Compass Indicator ECS1

ECI1. COMPASS display. ECI1-REV For latest update:   Electronic Compass Indicator ECS1 ECI1 COMPASS display Electronic Compass Indicator ECS1 ECI1-REV. 1.3 20-12-2004 For latest update: www.elproma.com/compass Contents 1 Introduction... 1 1.1 Package contents... 1 2 Working... 2 2.1 The

More information

Track-It User s Guide. 1. Table of Contents. Track-It User Guide

Track-It User s Guide. 1. Table of Contents. Track-It User Guide Track-It User s Guide Track-It is a PC based (Windows XP / Vista/ Windows 7) program to enable a user to program and view data from the Track-It series of micro data loggers. The program allows the loggers

More information

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA UM Channel Monitor.

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA UM Channel Monitor. 5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL 33309 3211 Fruitland Ave Los Angeles, CA 90058 UM-600 6-Channel Monitor Version 2 Installation and Operation Manual Rev. G P/N145F-12990 PCO 00007462 (c)

More information

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL. Total System Manager

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL. Total System Manager ISO 9001 CERTIFIED Phone: (352) 629-5020 or 800-533-3569 Fax: (352)-629-2902 Total System Manager PAGE 1 of 17 1. REVISION LOG... 2 2. SYSTEM OVERVIEW... 3 2.1. SCOPE... 3 2.2. FEATURES... 3 3. OPERATIONAL

More information

Display Unit User Manual

Display Unit User Manual Display Unit User Manual Contents 3 Specifications 3 Display Specifications 3 Absolute Maximum Ratings 3 Characteristics 4 Get started 4 Wiring 5 Application interface 5 Firmware upgrade 8 Settings 9 Display

More information

Control instruments GUARDIAN 2 - GUARDIAN 3

Control instruments GUARDIAN 2 - GUARDIAN 3 Control instruments GUARDIAN 2 - GUARDIAN 3 Table of contents 1. General informations... 3 2. Technical data... 3 3. GUARDIAN 2 connection diagram...4 3.1. TTL connection diagram for GUARDIAN 2 instrument...5

More information

INSTALLATION INSTRUCTIONS MBPEFY Series Mixing Box for Mitsubishi PEFY Series Units. Before Starting Installation Warning. Installation Instructions

INSTALLATION INSTRUCTIONS MBPEFY Series Mixing Box for Mitsubishi PEFY Series Units. Before Starting Installation Warning. Installation Instructions Before Starting Installation Warning Shut power to unit prior to any work being done. Personal injury or death could result. Only qualified HVAC service personnel should install, troubleshoot, repair or

More information

Home Manager System Model TS40B Wall Display Operating Instructions

Home Manager System Model TS40B Wall Display Operating Instructions 4700 Lang Avenue McClellan, CA 95652 1.800.BEUTLER www.beutler.com Home Manager System Provides control for Heating and Air Conditioning Zoning Option SmartVent Option Security System Interface Option

More information

HT Series Wall Mount with Analog Setpoints, LCD, and Humidistat and Thermostat Control

HT Series Wall Mount with Analog Setpoints, LCD, and Humidistat and Thermostat Control Wall Mount with Analog Setpoints, LCD, and Humidistat and Thermostat Control NOTICE This product is not intended for life or safety applications. Do not install this product in hazardous or classified

More information

Standard-Signal-Panelmeter S 9648 Industry standard signals - integrated transmitter-supply - potentiometer

Standard-Signal-Panelmeter S 9648 Industry standard signals - integrated transmitter-supply - potentiometer Martens Elektronik GmbH Kiebitzhörn 18 D22885 Barsbüttel/Germany www.martenselektronik.de F+49(0)40670 730 Fax +49(0)40670 73288 J info@martenselektronik.de StandardSignalPanelmeter S 9648 Industry standard

More information

SDL User s Manual. Contents. Introduction... 1 Overview Installation Sport Dash Manager Software... 23

SDL User s Manual. Contents. Introduction... 1 Overview Installation Sport Dash Manager Software... 23 MoTeC SDL User s Manual Contents Introduction... 1 Overview... 2 Display...2 Alarms...5 Data Logging...5 Other Functions...7 Measurement Inputs...8 Auxiliary Outputs...12 Communications Overview...13 ECU

More information

CONTROLLER INSTALLATION OPERATION & QUICK START

CONTROLLER INSTALLATION OPERATION & QUICK START CONTROLLER INSTALLATION OPERATION & QUICK START Controller: 8403-066 ECU Series Controller Manual: 2100-559 Supersedes: NEW File: Tab 19 Date: 05-02-11 Page 1 of 6 TABLE OF CONTENTS Installation Note...

More information

Carbon Dioxide Monitor/Controller With The USB Data Logger

Carbon Dioxide Monitor/Controller With The USB Data Logger Carbon Dioxide Monitor/Controller With The USB Data Logger F000IAQ-CO -1XXU series The monitor/controller is special design to monitor and alarm CO level, also provides one on/off relay output to control

More information

PowerShield 8. Configuration Manual

PowerShield 8. Configuration Manual PowerShield 8 Configuration Manual Introduction Part Number 6300-103 23 August 2017 The information contained in this manual is copyright and may not be reproduced without the written authority of PowerShield

More information

SP6R Level Controller Operation Manual

SP6R Level Controller Operation Manual SP6R Level Controller Operation Manual www.sjerhombus.com SP6R LEVEL CONTROLLER INTRODUCTION SJE-Rhombus, an industry leader in water and wastewater pump controls, introduces the SP6R Level Controller.

More information

INDEX. Network Power Monitor R10 SNMP

INDEX. Network Power Monitor R10 SNMP Innovative Electronics for a Changing World NPM-R10 Remote Network Power Monitor With optional relay board and GSM module INDEX Amended 21 March 2017: Add user defined Password see page 13 Add wire Connection

More information

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

Safety Instructions 1-1 Avoid unintended Start General Description 2-2 Contents Contents 1 Safety and precautions 1-1 Safety Instructions 1-1 Avoid unintended Start. 1-1 2 Introduction 2-1 General Description 2-2 3 Supported Configuration 3-1 Introduction 3-1 Fixed-speed

More information

TagTemp-NFC 3 TECHNICAL DATA 1 INTRODUCTION 2 MECHANICAL INSTALATION. TEMPERATURE LOGGER INSTRUCTIONS MANUAL V 1.0x D

TagTemp-NFC 3 TECHNICAL DATA 1 INTRODUCTION 2 MECHANICAL INSTALATION. TEMPERATURE LOGGER INSTRUCTIONS MANUAL V 1.0x D TagTemp-NFC TEMPERATURE LOGGER INSTRUCTIONS MANUAL V 1.0x D 1 INTRODUCTION The TagTemp-NFC is an electronic temperature logger. The sensor measures this physical quantity and the values are stored in memory.

More information

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins Service Bulletin SB685 Date: 8/18/2017 Subject: TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins Units: All TriPac EVOLUTION Summary: This bulletin updates and

More information