N2 Analog Input/ BACnet Analog Input

Size: px
Start display at page:

Download "N2 Analog Input/ BACnet Analog Input"

Transcription

1 Object Dictionary 1 N2 Analog Input/ BACnet Analog Input Introduction Note: The Johnson Controls N2 Analog Input object is considered a BACnet Analog Input object because it supports BACnet functionality. In addition, this object has Johnson Controls proprietary attributes. The N2 Analog Input object s attributes represent the external, visible characteristics of an analog input. This object integrates N2 controllers into supervisory controllers, resulting in: a consistent interface to N2 point objects for all controller types, so they appear as a homogenous set to the user interface flexibility in point mapping support for all Metasys and Facilitator controllers. Refer to Table 1 in the Controller chapter (LIT ) of the Object Dictionary. For example, this object allows you to map a temperature or humidity sensor point into a supervisory controller. See the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE) Standard for information on this object and the BACnet communication standard. May 1, 2002 Johnson Controls, Inc. Code No. LIT Software Release 5.1

2 2 N2 Analog Input/BACnet Analog Input Attributes Specific Attributes Table 1: Attribute Properties Table 1 lists the attributes specific to the N2 Analog Input object. The N2 Analog Input object also has the attributes of the Metasys Common object. Refer to Table 1 in the Metasys Common Object chapter (LIT ) for details. Attribute Name Data Type N30 M-Series N30 Default Value Options/Range Metasys Common Attributes See Table 1 in the Metasys Common Object chapter (LIT ). BACnet Required Attributes Event State Enumeration Normal Normal, Fault, Offnormal, High-Limit, Low-Limit Object Identifier BACnet Object ID C Out of Service Boolean False False True Present Value Float DNRW DNRW Status Flags Bit String False, False, False, False In Alarm, Fault, Overridden, Out of Service See BAC Status Flags Units Enumeration CW W Deg F See Units Enumeration Set in BACnet Optional Attributes Acked Bit String True, True, Transitions 1 True To-Offnormal, To-Fault, To-Normal See BAC Event Bits COV Float CW W 0.1 Deg F Any value > 0 Increment 2 Deadband 1 Float CW W 0.0 Device Type String CW W Null Limit: 20 characters * C - Configurable, D - Default Attribute, N - Value Not Required, R - Association to Reliability, W - Writable 1 These attributes are required if the object supports intrinsic reporting. 2 This attribute is required if the object supports Change-of-Value (COV) reporting.

3 Object Dictionary 3 Attribute Name (Cont.) Data Type N30 M-Series N30 Default Value Options/Range BACnet Optional Attributes (Cont.) Event Enable 1 Bit String CW W True, True, True To-Offnormal, To-Fault, To-Normal See BAC Event Bits Event Time Stamps 1 Array NONE_FFFF BACnetArray[3] of BACnet Time Stamp High Limit 1 Float CW W 70.0 Limit Enable 1 Bit String CW W False, False Low Limit Enable, High Limit Enable See BAC Limit Enable Low Limit 1 Float CW W 65.0 Max Pres Value Float CW W Min Pres Value Float CW W Notification Class 1 Unsigned Long CW W The BACnet Object Identifier of the Notification Class object used for routing Notify Type 1 Enumeration CW W Alarm Alarm, Event See BAC Notify Type Profile Name This BACnet optional attribute is not supported. Reliability Enumeration W W Reliable No Fault Detected (Reliable), No Sensor, Over Range, Under Range, Open Loop, Shorted Loop, Unreliable Other See Reliability Enumeration Set in Resolution Float W 0.1 Time Delay 1 Unsigned Short Update Interval Unsigned Short * C - Configurable, W - Writable CW W 0 Units = seconds 1 These attributes are required if the object supports intrinsic reporting. W 100 Units = hundredths of a second

4 4 N2 Analog Input/BACnet Analog Input Attribute Name (Cont.) Data Type N30 M-Series N30 Default Value Options/Range Display Precision Intrinsic Alarming Net N2 Address Net Point Address Johnson Controls Proprietary Attributes Enumeration CW W 10ths See Display Precision Boolean C False True, False Byte C 0 Range: Unsigned Short C 0 Range: Net Point Type Enumeration C 0 See Network Point Type Offline Boolean False False True Overridden Boolean R R False False True * C - Configurable, R - Association to Reliability, W - Writable

5 Object Dictionary 5 Attribute Definitions Table 2: Attribute Definitions Attribute Name Metasys Common Attributes Event State Object Identifier Out of Service Present Value Status Flags Units Acked Transitions Table 2 lists the definitions of the attributes specific to the N2 Analog Input object. Definition See Table 2 in the Metasys Common Object chapter (LIT ). BACnet Required Attributes Indicates if an active event state is associated with the object. If the object supports intrinsic reporting, this attribute indicates the event state of the object. If not, the attribute is Normal. Identifies the object with a unique numeric code. Indicates the offline/online state of the connected hardware. The attribute exists for compatibility with BACnet protocol and indicates whether the physical input that the object represents is in service. When out of service, the Present Value is not taken from the hardware input. Indicates the current value of the analog input. When Out of Service is True, this attribute is writable. Represents four Boolean flags that indicate the general health of an analog input. Three flags are associated with the values of other attributes of the object. The four flags are: In Alarm - In Alarm flag is False (0) if the Event State property value is Normal; otherwise, the In Alarm flag is True (1). Fault - Fault flag is True (1) if the Reliability attribute is not reliable; otherwise, the Fault flag is False (0). Overridden - Overridden flag is Logical 1 if the Present Value is decoupled from the hardware output, because operator intervention provided a different value. Out of Service - Out of Service flag is True if the Out of Service attribute value is True; otherwise, the Out of Service flag is False. Indicates the increments of measure used by the object. BACnet Optional Attributes Conveys three flags that separately indicate the receipt of acknowledgements for To-Offnormal, To-Fault, and To-Normal events. In Analog Input objects, transitions to High Limit and Low Limit Event States are considered Offnormal events. These flags clear with the occurrence of the corresponding event and set under any of the following conditions: upon receipt of the corresponding acknowledgement upon the occurrence of the event if the corresponding flag is not set in the Event Enable attribute (Event notifications are not generated for this condition. No acknowledgement is expected.) upon the occurrence of the event if the corresponding flag is set in the Event Enable attribute and the corresponding flag in the Ack Required attribute of the Notification Class object implicitly referenced by the Notification Class attribute of this object is not set (No acknowledgement is expected.) This attribute is required if the object supports intrinsic reporting.

6 6 N2 Analog Input/BACnet Analog Input Attribute Name (Cont.) COV Increment Deadband Device Type Event Enable Event Time Stamps High Limit Definition BACnet Optional Attributes (Cont.) Specifies the minimum change in Present Value that sends a COV Notification to subscriber COV clients. This attribute is required if the object supports COV reporting. Specifies a range between the High and Low Limits in which the Present Value must remain for a To-Normal event to generate under these conditions: The Present Value falls below the High Limit minus Deadband. The Present Value exceeds the Low Limit plus the Deadband. The Present Value remains within this range for a minimum period of time (specified in the Time Delay attribute). Either the High Limit Enable or Low Limit Enable flag is set in the Limit Enable attribute. The To-Normal flag is set in the Event Enable attribute. This attribute is required when the object supports intrinsic reporting. Contains the text description of the physical device connected to the Analog Input, usually describing the type of sensor. Conveys three flags for enabling and disabling To-Offnormal, To-Fault, and To-Normal events. In Analog Input objects, transitions to High Limit and Low Limit Event States are considered Offnormal events. An unreliable condition generates a Fault event. This attribute is required if the object supports intrinsic reporting. Conveys the times of the last To-Offnormal, To-Fault, and To-Normal event notifications, respectively. Time or Date time stamps have FF in each octet. Sequence time stamps are 0 if no event notification of that type has been generated. If intrinsic reporting is supported by the object, this attribute is required. Specifies a limit that the Present Value attribute must exceed before an event is generated. This attribute is required if the object supports intrinsic reporting. A To-Offnormal event generates under these conditions: The Present Value exceeds the High Limit for a minimum period of time, specified in the Time Delay attribute. The High Limit Enable flag is set in the Limit Enable attribute. The To-Offnormal flag is set in the Event Enable attribute. Once the Present Value exceeds the High Limit, the Present Value must fall below the High Limit minus the Deadband before a To-Normal event generates under these conditions: The Present Value falls below the High Limit minus the Deadband for a minimum period of time, specified in the Time Delay attribute. The High Limit Enable flag is set in the Limit Enable attribute. The To-Normal flag is set in the Event Enable attribute. Limit Enable Conveys two flags that separately enable and disable reporting of High Limit and Low Limit Offnormal events and their return to Normal. This attribute is required if the object supports intrinsic reporting.

7 Object Dictionary 7 Attribute Name (Cont.) Low Limit Max Pres Value Min Pres Value Notification Class Notify Type Reliability Resolution Time Delay Definition BACnet Optional Attributes (Cont.) Specifies a limit below which the Present Value attribute must fall before an event generates. This attribute is required if the object supports intrinsic reporting. A To-Offnormal event generates under these conditions: The Present Value falls below the Low Limit for a minimum period of time, specified in the Time Delay attribute. The Low Limit Enable flag is set in the Limit Enable attribute. The To-Offnormal flag is set in the Event Enable attribute. Once the Present Value falls below the Low Limit, the Present Value must exceed the Low Limit plus the Deadband before generating a To-Normal event under these conditions: The Present Value exceeds the Low Limit plus the Deadband for a minimum period of time, specified in the Time Delay attribute. The Low Limit Enable flag is set in the Limit Enable attribute. The To-Normal flag is set in the Event Enable attribute. Indicates the highest number (in engineering units) that is reliably obtained for Present Value. Indicates the lowest number (in engineering units) that is reliably obtained for Present Value. Specifies the notification class used when handling and generating event notifications for the object. This attribute implicitly refers to the BACnet Notification Class object that has a Notification Class attribute of the same value. This attribute is required if the object supports intrinsic reporting. Conveys whether the notifications generated by the object are Events or Alarms. This attribute is required if the object supports intrinsic reporting. Indicates whether the Present Value is unreliable and why. Sets the Reliability attribute to one of the following values when the Present Value attribute is written: Reliable - Last value written to Present Value was between the Min Value and Max Value limits. Unreliable High - Last value written to Present Value was greater than the Max Value limit. Unreliable Low - Last value written to Present Value was less than the Min Value limit. In addition to the three values to which the object can set the Reliability attribute, any value defined in the Metasys Common Object (LIT ) can be written directly to this attribute. Any value written to the Reliability attribute remains until the next time the Present Value is written. Indicates the smallest possible measurable change in Present Value (in engineering units). Specifies the minimum number of seconds that the Present Value must remain: outside the range defined by the High Limit and Low Limit attributes before a To-Offnormal event generates within the range defined by the High Limit and Low Limit attributes, including the Deadband attribute, before a To-Normal event generates This attribute is required for intrinsic alarming. Update Interval Indicates the time span (in hundredths of a second) between updates to Present Value when the input is not overridden or out of service.

8 8 N2 Analog Input/BACnet Analog Input Attribute Name (Cont.) Display Precision Intrinsic Alarming Definition Johnson Controls Proprietary Attributes Indicates the rounded position and decimal places to display for this object. Enables the definition of the intrinsic alarm related attributes. Net N2 Address Indicates the controller N2 Address (1-254) as defined by switch settings on the controller. Net Point Address Indicates the network point address of the specified type (1-256). Net Point Type Offline Overridden Indicates the point type in the controller. Indicates whether the object is online or offline as determined by the controller s offline condition. Shows the override state of the hardware (if supported by the hardware). Commands The N2 Analog Input object supports the commands listed in Table 3. The order of the commands in the table reflects how the commands appear on the user interface. Table 3: Supported Commands Command Name Parameters Access Level Description Override The value to be written to the Supervise Updates the Present Value at Command Priority equal to Operator Override. Present Value attribute. Override Release Supervise Releases Command Priority Operator Override from Present Value. Enable Modify Allows distribution of Changes-of-Value and commanding. Disable Modify Prevents distribution of Changes-of-Value and commanding. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI Printed in U.S.A.

N2 Binary Input/ BACnet Binary Input

N2 Binary Input/ BACnet Binary Input Object Dictionary 1 N2 Binary Input/ BACnet Binary Input Introduction Note: The Johnson Controls Binary Input object is considered a BACnet Binary Input object, because it supports BACnet functionality.

More information

N2 Multistate Output/ BACnet Multistate Output

N2 Multistate Output/ BACnet Multistate Output Object Dictionary 1 N2 Multistate Output/ BACnet Multistate Output Introduction Note: The Johnson Controls N2 Multistate Output object is considered a BACnet Multistate Output object because it supports

More information

N2 Binary Output/ BACnet Binary Output

N2 Binary Output/ BACnet Binary Output Object Dictionary 1 N2 Binary Output/ BACnet Binary Output Introduction Note: The Johnson Controls Binary Output object is considered a BACnet Binary Output object because it supports BACnet functionality.

More information

Multistate Value/ BACnet Multistate Value

Multistate Value/ BACnet Multistate Value Object Dictionary 1 Multistate Value/ BACnet Multistate Value Introduction Note: The Johnson Controls Multistate Value object is considered a BACnet Multistate Value object because it supports BACnet functionality.

More information

Trend Log/BACnet Trend Log

Trend Log/BACnet Trend Log Object Dictionary 1 Trend Log/BACnet Trend Log Introduction Notes: The Johnson Controls Trend Log object is considered a BACnet Trend Log object because it supports BACnet functionality. In addition, this

More information

Runtime Totalization. Introduction

Runtime Totalization. Introduction Object Dictionary 1 Runtime Totalization Introduction The Runtime Totalization object tracks the time that elapses while a designated input, such as a binary or multistate value, matches a specified state.

More information

Display. Introduction

Display. Introduction Object Dictionary 1 Display Introduction The Display object configures the display of a Local Display Terminal (LDT) in an N30 supervisory controller. Use Project Builder to create a Display object for

More information

Object Dictionary 1. Pager. Introduction

Object Dictionary 1. Pager. Introduction Object Dictionary 1 Pager Introduction The Pager object provides alarm notifications via pager to personnel at a remote location who would otherwise not be aware of the alarm coming into a workstation

More information

Schedule/BACnet Schedule

Schedule/BACnet Schedule Object Dictionary 1 Schedule/BACnet Schedule Introduction Note: The Johnson Controls Schedule object is considered a BACnet Schedule object because it supports BACnet functionality. In addition, this object

More information

Working with BACnet Group Objects

Working with BACnet Group Objects N30 Supervisory Controller User s Manual 33-1 Chapter 33 Working with BACnet Group Objects Introduction Note: Do not confuse the BACnet Group object with the Johnson Controls Group object. For information

More information

Device Diagnostic. Introduction

Device Diagnostic. Introduction Object Dictionary 1 Device Diagnostic Introduction The Device Diagnostic object supports various diagnostic functions of the device and monitors the device for an overload condition. This object allows

More information

Ethernet IP Datalink. Introduction

Ethernet IP Datalink. Introduction Object Dictionary 1 Ethernet IP Datalink Introduction The Ethernet Internet Protocol (IP) Datalink object manages the Ethernet communications bus and the messages transmitted on it. This object allows

More information

Working with Runtime Totalization Objects

Working with Runtime Totalization Objects N30 Supervisory Controller User s Manual 25-1 Chapter 25 Working with Runtime Totalization Objects Introduction The Runtime Totalization object tracks the number of one minute time intervals that elapse

More information

Wonderware Operations Integration Supervisory BACnet/IP BACLITE Server (G-1.2 Series)

Wonderware Operations Integration Supervisory BACnet/IP BACLITE Server (G-1.2 Series) Wonderware Operations Integration Supervisory BACnet/IP BACLITE Server (G-1.2 Series) Contents Contents WONDERWARE OPERATIONS INTEGRATION - SUPERVISORY BACNET/IP BACLITE SERVER (G-1.2 SERIES)... 3 Legal

More information

Metasys System Extended Architecture Glossary

Metasys System Extended Architecture Glossary Technical Bulletin Issue Date March 31, 2003 Metasys System Extended Architecture Glossary Key Concepts... 2 Metasys System Extended Architecture Component Acronyms... 2 Metasys System Extended Architecture

More information

Proposed Addendum bd to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks

Proposed Addendum bd to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks BSR/ASHRAE Addendum bd to ANSI/ASHRAE Standard 135-2012 Public Review Draft Proposed Addendum bd to Standard 135-2012, BACnet - A Data Communication Protocol for Building Automation and Control (February

More information

Working with Demand Limiting/Load Rolling (DLLR) Objects

Working with Demand Limiting/Load Rolling (DLLR) Objects N30 Supervisory Controller User s Manual 19-1 Chapter 19 Working with Demand Limiting/Load Rolling (DLLR) Objects Introduction The Demand Limiting/Load Rolling (DLLR) object selectively sheds loads to

More information

Appendix C: HVAC PRO Modules

Appendix C: HVAC PRO Modules FANs 637.5, 1637.5 Appendix Section Issue Date 0400 APPLICATION NOTE Appendix C: HVAC PRO Modules HVAC PRO Modules...3 Introduction...*3 Key Concepts...*4 ABS VALUE... 6 ADD... 6 ANALOG OUTPUT... 6 AND...

More information

NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement

NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement NS-BCN7004-0, NS-BCN7004-2 Code No. LIT-12011581 Issued November 9, 2011 Supersedes April 12, 2011 Refer to the QuickLIT

More information

What a BACnet system looks like and how it can be used generally depends. By Roland Laird

What a BACnet system looks like and how it can be used generally depends. By Roland Laird This article was published in ASHRAE Journal, November 2009. Copyright 2009 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information

Downloading Metasys Integrator 300 Series Code

Downloading Metasys Integrator 300 Series Code M-Tool Manual 693 System Tools Applications Section Issue Date 0101 APPLICATION NOTE Downloading Metasys Integrator 300 Series Code Downloading Metasys Integrator 300 Series Code...3 Introduction...3 Key

More information

ASHRAE STANDARD. BACnet - A Data Communication Protocol for Building Automation and Control Networks

ASHRAE STANDARD. BACnet - A Data Communication Protocol for Building Automation and Control Networks BSR/ASHRAE Addendum c to ANSI/ASHRAE Standard 135-2001 This supplement will be submitted to the American National Standards Institute Board of Standards Review (BSR) for approval. ASHRAE STANDARD BACnet

More information

APPLICATION NOTE JC/85

APPLICATION NOTE JC/85 Metasys Network Technical Manual 636 App. Notes: Network Communications Section Application Note Issue Date 0401 APPLICATION NOTE JC/85 Gateway Introduction Page 3 Application Details *3 Hardware and Software

More information

FOREWORD. In addition, changes to BTL Specified Tests might also contain a yellow highlight to indicate the changes made by this addendum.

FOREWORD. In addition, changes to BTL Specified Tests might also contain a yellow highlight to indicate the changes made by this addendum. [This foreword and the Overview on the following pages are not part of this Test Package. They are merely informative and do not contain requirements necessary for conformance to the Test Package.] FOREWORD

More information

NS Series Temperature and Humidity Network Zone and Discharge Air Sensors Protocol Implementation Conformance Statement

NS Series Temperature and Humidity Network Zone and Discharge Air Sensors Protocol Implementation Conformance Statement NS Series Temperature and Humidity Network Zone and Discharge Air Sensors Protocol Implementation Conformance Statement Technical Bulletin NS-AHx7x0x-x, NS-APx7x0x-0, NS-ATx700x-x, NS-BHx7x0x-0, NS-BPx700x-0,

More information

Introduction to the N30 Supervisory Controller

Introduction to the N30 Supervisory Controller N30 Supervisory Controller User s Manual 2-1 Chapter 2 Introduction to the N30 Supervisory Controller Introduction This chapter describes the basic functions and operation of an N30 Supervisory Controller

More information

WT-BAC-IP Gateway Protocol Implementation Conformance Statement

WT-BAC-IP Gateway Protocol Implementation Conformance Statement WT-BAC-IP Gateway Protocol Implementation Conformance Statement Technical Bulletin WT-BAC-IP Code No. LIT-12011936 Issued June 2017 Refer to the QuickLIT Web site for the most up-to-date version of this

More information

BACnet MS/TP Protocol for LabVIEW. User Manual

BACnet MS/TP Protocol for LabVIEW. User Manual BACnet MS/TP Protocol for LabVIEW User Manual Ovak Technologies 2015 Contents 1 Introduction... 3 1.1 Definitions and Acronyms... 3 1.2 Purpose... 3 1.3 Overview... 3 2 BACnet Background... 4 3 BACnet

More information

Defining Points. Introduction

Defining Points. Introduction M-Series Workstation with Companion/Facilitator Manual 9-1 Chapter 9 Defining Points Introduction This chapter explains how to define software points. Points are software representations of input and output

More information

Site Book User s Guide

Site Book User s Guide Issue Date 11/01/01 USER S GUIDE...3 Introduction... 3 Key Concepts... 5 Related Documentation...5 Communications Options...5 N30 Supervisory Controller...5 Project Builder...6 N30 Upgrade Utility...6

More information

Zoning System TEC2647Z-2 and TEC2647Z-2+PIR Zone Controllers Protocol Implementation Conformance Statement

Zoning System TEC2647Z-2 and TEC2647Z-2+PIR Zone Controllers Protocol Implementation Conformance Statement Zoning System TEC2647Z-2 and TEC2647Z-2+PIR Zone Controllers Protocol Implementation Conformance Statement Technical Bulletin TEC2647Z-2 and TEC2647Z-2+PIR Code No. LIT-12011399 Issued March 9, 2009 Supersedes

More information

Alarms & Events Plug-In Kepware Technologies

Alarms & Events Plug-In Kepware Technologies 2011 Kepware Technologies 2 Table of Contents Table of Contents 2 3 Overview 3 AE Plug-In Terminology 3 AE Plug-In Conditions 3 The AE Plug-In from the AE Clients' Perspective 4 Real World Examples 5 User

More information

OWNER S MANUAL. Building Gateways MD-CCM08/E (K01-BACNET)

OWNER S MANUAL. Building Gateways MD-CCM08/E (K01-BACNET) OWNER S MANUAL Building Gateways MD-CCM08/E (K01-BACNET) Thank you very much for purchasing our air conditioner, please read this owner's manual carefully before using your air conditioner. CATALOGUE 1.

More information

FX Server BACNET AWS Protocol Implementation Conformance Statement

FX Server BACNET AWS Protocol Implementation Conformance Statement FX Server BACNET AWS Protocol Implementation Conformance Statement Document Introduction. 2 Annex A- Protocol Implementation Conformance Statement (Normative) 3 Product Description. 3 BACnet Standardized

More information

BrightCore BACnet Lookout V2.2 Product Family

BrightCore BACnet Lookout V2.2 Product Family Page 1 BrightCore BACnet Lookout User Guide Essential, Standard and Extended v.2.2 Page 2 Copyright 2013 by ELMA Kurtalj ltd. All rights reserved. The contents of this documentation are taken in part from

More information

BACstac/Win v6.8. User s Guide. Document Version: 1.0. Cimetrics, Inc.

BACstac/Win v6.8. User s Guide. Document Version: 1.0. Cimetrics, Inc. BACstac/Win v6.8 User s Guide Document Version: 1.0 Cimetrics, Inc. 141 Tremont Street, Floor 11 BOSTON, MASSACHUSETTS 02111 USA TELEPHONE: +1 (617) 350-7550 FAX: +1 (617) 350-7552 E-MAIL: products@cimetrics.com

More information

Metasys System Configuration Tool (SCT)

Metasys System Configuration Tool (SCT) Product Bulletin Issue Date March 31, 2003 Metasys System Configuration Tool (SCT) As an integral part of the Metasys system extended architecture, the System Configuration Tool (SCT) supports the engineering,

More information

SAUTER BACnet PICS EY-modulo 5 ecos504/505 BACnet Protocol Implementation Conformance Statement

SAUTER BACnet PICS EY-modulo 5 ecos504/505 BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement D100275255-05 Content Note: This statement corresponds to the ANSI/ASHRAE 135-2012 release. Changes are taking place constantly, without prior notification.

More information

CENTRALINE NX BACNET UTILITIES DRIVER

CENTRALINE NX BACNET UTILITIES DRIVER CENTRALINE NX BACNET UTILITIES DRIVER User Guide Copyright 2017 Honeywell GmbH! All Rights Reserved EN2Z-1020GE51 R0217 CENTRALINE NX - BACNET UTILITIES DRIVER USER GUIDE EN2Z-1020GE51 R0217 USER GUIDE

More information

Metasys BACnet System Integrator (BSI) Monitoring

Metasys BACnet System Integrator (BSI) Monitoring Metasys Connectivity Technical Manual 629.5 Metasys BACnet System Integrator Section Issue Date 73 TECHNICAL BULLETIN Metasys BACnet System Integrator (BSI) Monitoring Monitoring the BSI Communicator...2

More information

Proposed Addendum bd to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks

Proposed Addendum bd to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks BSR/ASHRAE Addendum bd to ANSI/ASHRAE Standard 135-2016 Public Review Draft Proposed Addendum bd to Standard 135-2016, BACnet - A Data Communication Protocol for Building Automation and Control Networks

More information

N30 Device. Introduction

N30 Device. Introduction Object Dictionary 1 Introduction Note: The Johnson Controls object functions differently than the BACnet Device object. For information on the BACnet Device object, refer to the BACnet Device chapter (LIT-694150)

More information

Working with Objects and the M-View Screen

Working with Objects and the M-View Screen Project Builder User s Guide 6-1 Chapter 6 Working with Objects and the M-View Screen Introduction The Project Builder uses a variety of objects to configure controllers and perform tasks. This chapter

More information

INTERIM TEST SPECIFICATION

INTERIM TEST SPECIFICATION BACnet TESTING LABORATORIES INTERIM TEST SPECIFICATION To Be Used with Test Package 15.1 Version 10 July 19, 2018 Approved by the BTL Working Group on July 12, 2018 Approved by the BTL Working Group Voting

More information

BACnet Protocol Implementation Conformance Statement Unitary Protocol Converter (UPC)

BACnet Protocol Implementation Conformance Statement Unitary Protocol Converter (UPC) Date: 10/05/2016 Vendor Name: OEMCtrl Product Name: Unitary Protocol Converter Product Model Number: UPC Applications Software Version: Firmware Revision: 6.00a BACnet Protocol

More information

P2000 Commend Intercom Interface Option

P2000 Commend Intercom Interface Option P2000 Commend Interface Option Product Bulletin Code No. LIT-12012142 Software Release 3.14 Issued November 30, 2015 Johnson Controls offers a purchase option that enables the P2000 Security Management

More information

Direct Connect and Dial-Up Connection on Windows 2000 Operating Systems

Direct Connect and Dial-Up Connection on Windows 2000 Operating Systems Application Note Issue Date March 6, 2003 Direct Connect and Dial-Up Connection on Windows 2000 Operating Systems Direct Connect and Dial-Up Connection on Windows 2000 Operating Systems...2 Introduction...

More information

Metasys Integrator GE Lighting Application

Metasys Integrator GE Lighting Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator GE Lighting Application lntroduction Page 3 Application Details

More information

Alarms & Events Plug-In PTC Inc. All Rights Reserved.

Alarms & Events Plug-In PTC Inc. All Rights Reserved. 2017 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 4 Overview 4 OPC AE Plug-In Terminology 4 OPC AE Plug-In Conditions 5 The OPC AE Plug-In from the OPC AE Clients' Perspective

More information

Facility Explorer for Validated Environments

Facility Explorer for Validated Environments Facility Explorer for Validated Environments User s Guide 1 Facility Explorer for Validated Environments Introduction Facility Explorer for Validated Environments is an information-based software application

More information

Metasys Integrator Caterpillar Application

Metasys Integrator Caterpillar Application Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Caterpillar Application Introduction Application Details Component Requirements Vendor Contact Information Design Considerations

More information

for M-Bus, Modbus and 1-Wire devices

for M-Bus, Modbus and 1-Wire devices Kara Systems Kara BACnet Gateway V2.2 for M-Bus, Modbus and 1-Wire devices The Kara BACnet Gateway integrates M-Bus(EN-1434-3) Modbus and 1-Wire devices to a BACnet Infrastructure Network. It is a three

More information

Guidelines and Recommendations for Better Graphics Performance with Integrated N1 Networks

Guidelines and Recommendations for Better Graphics Performance with Integrated N1 Networks M-Graphics User s Manual G-1 Appendix G Guidelines and Recommendations for Better Graphics Performance with Integrated N1 Networks Introduction This chapter discusses guidelines and recommendations for

More information

ICC. BACnet MS/TP Server Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc.

ICC. BACnet MS/TP Server Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc. INDUSTRIAL CONTROL COMMUNICATIONS, INC. BACnet MS/TP Server Driver Manual August 17, 2017 2017 Industrial Control Communications, Inc. TABLE OF CONTENTS 1 BACnet MS/TP Server... 2 1.1 Overview... 2 1.2

More information

Proposed Addendum bd to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks

Proposed Addendum bd to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks BSR/ASHRAE Addendum bd to ANSI/ASHRAE Standard 135-2016 Public Review Draft Proposed Addendum bd to Standard 135-2016, BACnet - A Data Communication Protocol for Building Automation and Control Networks

More information

Metasys Integrator Powerware Application (previously the Exide Application)

Metasys Integrator Powerware Application (previously the Exide Application) Application Note Issue Date 11/01/01 APPLICATION NOTE Metasys Integrator Powerware Application (previously the Exide Application) lntroduction Page Application Details Component Requirements 4 Vendor Contact

More information

BACnet: A Data Communication Protocol for Building Automation and Control Networks

BACnet: A Data Communication Protocol for Building Automation and Control Networks . BACnet: A Data Communication Protocol for Building Automation and Control Networks.......... CS495 Computer Networking Research Project Submitted By: Eric Durant Submitted To: Dr. Henry Welch Date: Wednesday

More information

MatrixBBC. Protocol Implementation Conformance Statement (PICS) Product Description: BACnet Standardized Device Profile:

MatrixBBC. Protocol Implementation Conformance Statement (PICS) Product Description: BACnet Standardized Device Profile: Vendor Name: American Auto Matrix Product Name: BACnet Building Controller Product Model Number: x BBC y (x indicating target model; y feature) Firmware Revision: Target using BBC module v1.1.56 or later

More information

M-Tool. Features and Benefits System Configuration and Project Management. Allows fast adjustment and commissioning of systems

M-Tool. Features and Benefits System Configuration and Project Management. Allows fast adjustment and commissioning of systems Product Bulletin Issue Date July 6, 2006 Supersedes June 30, 2004 M-Tool M-Tool transforms the way you create control strategies by providing a suite of tools with an intuitive and efficient work environment.

More information

BACnet Protocol Implementation Conformance Statement OEMPrtl Pro

BACnet Protocol Implementation Conformance Statement OEMPrtl Pro Date: 12/13/2011 Vendor Name: OEMCtrl Product Name: Product Model Number: Applications Software Version: Firmware Revision: 4.02 BACnet Protocol Revision: 9 Product Description: The is

More information

CENTRALINE NX BACNET UTILITIES DRIVER

CENTRALINE NX BACNET UTILITIES DRIVER CENTRALINE NX BACNET UTILITIES DRIVER User Guide Copyright 2017 Honeywell GmbH All Rights Reserved EN2Z-1020GE51 R0917 CENTRALINE NX - BACNET UTILITIES DRIVER USER GUIDE EN2Z-1020GE51 R0917 2 USER GUIDE

More information

Metasys Integrator Allen-Bradley Custom Application

Metasys Integrator Allen-Bradley Custom Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Allen-Bradley Custom Application Introduction Page 3 Application

More information

BACnet Controller Integration with NAE/NCE/ODS Technical Bulletin

BACnet Controller Integration with NAE/NCE/ODS Technical Bulletin BACnet Controller Integration with NAE/NCE/ODS Technical Bulletin Code No. LIT-1201531 Software Release 9.0 Issued August 2017 Refer to the QuickLIT website for the most up-to-date version of this document.

More information

N30 Supervisory Controller Quick Start

N30 Supervisory Controller Quick Start Issue Date June 30, 2004 TECHNICAL BULLETIN N30 Supervisory Controller Quick Start N30 Supervisory Controller Quick Start...2 Introduction... 2 Key Concepts... 3 Using This Document... 3 Related Information...

More information

Polling the N2 Network or Zone Bus for Devices

Polling the N2 Network or Zone Bus for Devices Metasys Checkout Tool User s Guide 3-1 Chapter 3 Polling the N2 Network or Zone Bus for Devices Introduction The first step in the checkout process is using the Metasys Checkout Tool to find and display

More information

Building Product CCM08 Series BACnet Central Control Module User Manual

Building Product CCM08 Series BACnet Central Control Module User Manual Building Product CCM08 Series BACnet Central Control Module User Manual 2007.10 1 1. connect diagrammatic sketch (1)CCM08 interfaces diagrammatic sketch An Ethernet interface connected to BACnet/IP network.

More information

Metasys Integrator Multistack Application

Metasys Integrator Multistack Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Multistack Application lntroduction Page *3 Application Details

More information

M-Password Application Actions

M-Password Application Actions Issue Date 11/01/01 TECHNICAL BULLETIN M-Password s M-Password s...3 Introduction... 3 Key Concepts... 4 M-Password s...4 Analog Profile s...5 AWX Container (M-Alarm View) s...5 AWXInd32 (M-Alarm Indicator)

More information

BACnet Protocol Implementation Conformance Statement Automated Logic Corporation LGR25, LGR250, LGR1000

BACnet Protocol Implementation Conformance Statement Automated Logic Corporation LGR25, LGR250, LGR1000 Date: 9/18/2008 Vendor Name: Automated Logic Corporation Product Name: LGR Product Model Number: LGR25, LGR250, LGR1000 Applications Software Version: ExecB ME-LGR-melgr Firmware Revision: 2.18 BACnet

More information

Metasys Integrator United Power Application

Metasys Integrator United Power Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator United Power Application lntroduction Page 3 Application Details

More information

GLAS Smart Thermostat

GLAS Smart Thermostat GLAS Smart Thermostat Product Bulletin SIO-00000, SIO-0000 Code No. LIT-098 Issued August 08 Refer to the QuickLIT website for the most up-to-date version of this document. The GLAS Smart Thermostat is

More information

Direct Connect and Dial-Up on Windows 98

Direct Connect and Dial-Up on Windows 98 N30 Supervisory Controller System Communications Manual 689.3 Application Notes Section Issue Date 0101 APPLICATION NOTE Direct Connect and Dial-Up on Windows 98 Direct Connect and Dial-Up on Windows 98...3

More information

FX Input/Output (I/O) Modules XM07 and XM14

FX Input/Output (I/O) Modules XM07 and XM14 Product Bulletin FX I/O Modules Issue Date July 6, 2009 FX Input/Output (I/O) Modules XM07 and XM14 The FX Input/Output (I/O) Modules provide additional physical input and output points for FX field controllers

More information

Metasys Web Access System Overview

Metasys Web Access System Overview Technical Bulletin Issue Date February 18, 2003 Metasys Web Access System Overview Metasys Web Access System Overview...2 Introduction... 2 Key Concepts... 3 Related Information... 3 Hardware and Software

More information

ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS)

ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS) ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS) Date: February 7, 2018 Vendor Name: Lutron Electronics Co., Inc. Product Name: myroom BACnet Integration Applications Version: 2.0 Firmware

More information

FX Tools Express Software Package

FX Tools Express Software Package Product Bulletin FX Tools Express Issue Date October 31, 2005 FX Tools Express Software Package FX Tools Express is a Windows based software package for configuring, downloading and commissioning of predefined

More information

APPLICATION NOTE. N2 Dial Application. Using N2 Dial...3. Introduction...3. Key Concepts...4

APPLICATION NOTE. N2 Dial Application. Using N2 Dial...3. Introduction...3. Key Concepts...4 FANs 637.5, 1637.5 N2 Dial Section Issue Date 0400 APPLICATION NOTE N2 Dial Application Using N2 Dial...3 Introduction...3 Key Concepts...4 N2 Dial Configuration... 4 Downloading with N2 Dial...*6 Dial-in

More information

Using M-Collector. Using M-Collector...2. Introduction Key Concepts... 3

Using M-Collector. Using M-Collector...2. Introduction Key Concepts... 3 Technical Bulletin Issue Date October 3, 2003 Using M-Collector Using M-Collector...2 Introduction... 2 Key Concepts... 3 M-Collector... 3 Configuration... 3 Runtime Display...4 Maximum Capacity... 6 Collection

More information

CCS Handheld VAV Balancing Tool Technical Bulletin

CCS Handheld VAV Balancing Tool Technical Bulletin CCS Handheld VAV Balancing Tool Technical Bulletin NS-ATV7003-0 Code No. LIT-12011470 Software Release 1.2 Issued July 15, 2011 Supersedes January 14, 2009 Refer to the QuickLIT Web site for the most up-to-date

More information

Metasys Integrator Northern Application

Metasys Integrator Northern Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Northern Application lntroduction Page *3 Application Details

More information

COMPASS1.5 WORKSTATION DEALER GUIDE

COMPASS1.5 WORKSTATION DEALER GUIDE COMPASS1.5 WORKSTATION DEALER GUIDE Before you begin COMPASS 1.5 DEALER GUIDE ABOUT COMPASS About Compass Compass is an operator workstation software package for BACnet-compliant systems. Compass, which

More information

Analog Data (AD) Object

Analog Data (AD) Object Issue Date 11/01/01 TECHICAL BULLETI Analog Data (AD) Object Introduction Page 2 Applications 2 Quick Start 3 Engineering 9 Overview of Operation 9 Input Processing 12 Alarm Limit Analysis 25 Triggers

More information

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS)

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) July 2017 Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) Topic: BACnet Protocol Implementation Conformance Statement (PICS) Date: 13 st September 2017

More information

Metasys System Extended Architecture Overview

Metasys System Extended Architecture Overview Technical Bulletin Issue Date March 31, 2003 Metasys System Extended Architecture Overview Metasys System Extended Architecture Overview...2 Introduction... 2 Key Concepts... 4 Metasys System Extended

More information

BACnet Controller for General-purpose Building Applications

BACnet Controller for General-purpose Building Applications Specifications BACnet Controller for General-purpose Building Applications General Model WJ-1101 is the BACnet controller to be used for a wide range of building applications such as air-conditioning and

More information

Metasys Integrator Graham Application

Metasys Integrator Graham Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Graham Application Introduction Page 3 Application Details 3

More information

Spreadsheet Applications

Spreadsheet Applications Metasys Network Technical Manual 3 App. Notes: Network Communications Technical Bulletin Issue Date 9 Spreadsheet Applications lntroduction Page 3 Metasys and Spreadsheet Applications 5 Locating and Opening.DBF

More information

BACnet Protocol Guide for 2X Series Control Panels

BACnet Protocol Guide for 2X Series Control Panels BACnet Protocol Guide for 2X Series Control Panels P/N 00-3243-505-0503-01 ISS 02DEC15 Copyright Trademarks and patents Manufacturer Version REV 01 Certification 2015 UTC Fire & Security. All rights reserved.

More information

FOREWORD. In addition, changes to BTL Specified Tests might also contain a yellow highlight to indicate the changes made by this addendum.

FOREWORD. In addition, changes to BTL Specified Tests might also contain a yellow highlight to indicate the changes made by this addendum. [This foreword and the Overview on the following pages are not part of this Test Package. They are merely informative and do not contain requirements necessary for conformance to the Test Package.] FOREWORD

More information

Defining Color Spectrum

Defining Color Spectrum Color Spectrum User s Guide 2-1 Chapter 2 Defining Color Spectrum Introduction The Color Spectrum display provides a compact view of history data of an analog point in a color spectrum format. It reads

More information

Supervisory Controllers

Supervisory Controllers FACILITY EXPLORER SUPERVISORY CONTROLLERS Supervisory Controllers FX20, FX60 The FX20, FX60 and FX70 are building automation supervisory class controllers in the Facility Explorer product family. They

More information

Proposed Addendum aq to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks

Proposed Addendum aq to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks BSR/ASHRAE Addendum aq to ANSI/ASHRAE Standard 135-2012 Public Review Draft Proposed Addendum aq to Standard 135-2012, BACnet - A Data Communication Protocol for Building Automation Fourth Public Review

More information

Lab and Central Plant Controller

Lab and Central Plant Controller Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0290 Lab and Central Plant Controller The Metasys Lab and Central Plant (LCP) Controller is

More information

P216 Series Condenser Fan Speed Controller

P216 Series Condenser Fan Speed Controller P216 Series Condenser Fan Speed Controller Installation Instructions P216xxx-x Part No. 24-85895-18, Rev. D Issued 27 August 2015 Applications Refer to the QuickLIT website for the most up-to-date version

More information

FX-DIS Local Controller Display Technical Bulletin

FX-DIS Local Controller Display Technical Bulletin FX-DIS Local Controller Display Technical Bulletin FX-DIS1710-0 Code No. LIT-12011666 Issued February 28, 2014 Supersedes April 12, 2011 Refer to the QuickLIT website for the most up-to-date version of

More information

DNP3 V3.00 DEVICE PROFILE DOCUMENT

DNP3 V3.00 DEVICE PROFILE DOCUMENT DNP3 V3.00 DEVICE PROFILE DOCUMENT Vendor Name: DAQ Electronics. Device Name: DNP3 Master Station Server in the Callisto Computer. Date: June 8, 2000 Highest DNP Level Supported: For Requests: DNP-L3.

More information

BCPro System Product Bulletin

BCPro System Product Bulletin CH-BCM100-0, CH-BCM200-0 Introduction The BCPro system from Johnson Controls is ideally suited to automating the environmental control and energy usage functions of conventional buildings. Not only does

More information

BACnet Integration User s Manual

BACnet Integration User s Manual BACnet Integration User s Manual Target Audience for this Document This document is aimed at system operators and provides a description of how to install and configure the Milestone BACnet Integration.

More information

NB-GPC Family Protocol Implementation Conformance Statement (PICS)

NB-GPC Family Protocol Implementation Conformance Statement (PICS) Vendor Name: American Auto-Matrix Product Name: NB-GPC Family Product Model Number: NB-GPC1, NB-GPC2, NB-GPC3, NB-GPC4 Firmware Revision: 2.00 BACnet Protocol Revision: 4 Product Description: NB-GPC controllers

More information

Wireless Metasys System

Wireless Metasys System Metasys Product Bulletin Code No. LIT-12011244 Software Release 5.0 Issued January 4, 2010 Supersedes February 25, 2009 The Metasys provides a wireless platform for multiple levels of the Johnson Controls

More information