Electronic Overcurrent Protector REF16-S

Size: px
Start display at page:

Download "Electronic Overcurrent Protector REF16-S"

Transcription

1 Electronic Overcurrent Protector REF6-S Description Type REF6-S is an extension of the product group»electronic Overcurrent Protection«for DC 2 V applications. It provides selective protection for all DC 2 V load circuits at a width of only 2.5 mm. This is achieved by a combination of active electronic current limitation in the event of a short circuit and overload disconnection at typically.25 times rated current. Plugged into an E-T-A socket, which is available with screw terminals or screwless terminals, the REF6-S provides ease of installation. The sockets allow power distribution and signalling via plug-in type jumpers. In addition the REF6-S latches on when plugged into the socket and by means of coding pins a clear assignment to current ratings or slots is possible. Dimensions are in compliance with the standard DIN 3880 for the installation of built-in units. DC 2 V switch-mode power supplies are widely used in automation. In the event of an overload, however, they turn down the output voltage which is meant to supply all connected loads. Therefore a failure occurring in an individual load of the system causes a voltage dip in all other load circuits. This does not only lead to an undefined fault status, but may even cause a stoppage of the machinery or plant. The REF6-S responds much faster to overload conditions than the switch-mode power supply. It limits the max. possible overcurrent to typically.25 times rated current (see table ). This allows connection of capacitive loads up to 20,000 μf with disconnection only in the event of overload or short circuit. For optimal adjustment to the load conditions the REF6-S can be selected in fixed values of 0.5 A 0 A. Status and failure indication is provided by a multi-coloured LED, a potential-free signal contact or by means of an integral short-circuitproof status output. Remote actuation is possible by a remote reset signal or a remote control signal ON/OFF. The manual ON/OFF button on the device allows intentional start-up of individual load circuits. As soon as the REF6-S identifies an overload or short circuit condition in a load circuit, it will block the load output transistor and interrupt the current flow in the faulty circuit. Upon remedy of the failure, the load output of the REF6-S will be re-activated by an electronic reset signal or by manual operation of the ON/OFF button. Features and benefits l Selective load protection, electronic trip characteristics l Active current limitation when connecting capacitive loads up to 20,000 µf and in the event of overload/short circuit l Fixed current ratings 0.5 A...0 A l Reliable overload disconnection at typically.25 x IN, even with long load lines or small cable cross sections l Low voltage monitoring l Manual ON/OFF button (S) l Control input IN+ for remote ON/OFF signal l Clear status indication through LED, signal contact F or status output SF/SF l Electronic reset input RE l Integral fail-safe element, adjusted to current rating l Width per channel only 2.5 mm l Plug-in type for sockets to be mounted side-by-side, with screwless or screw terminals l Protector plus socket comply with the dimensional requirements of DIN 3880 Approvals Authority Standard Rated voltage Current ratings UL UL 2367 DC 2 V 0.5 A...0 A UL *) UL 508 C22.2 No. DC 2 V 0.5 A...0 A CSA*) CSA C22.2 No.23 DC 2 V 0,5 A...0 A GL Rules VI, part 7, GL 202, category C, EMC DC 2 V 0.5 A...0 A *) culus (listed) and CSA using with socket 80plus or socket 8plus with socket 80plus Technical data Operating data Operating voltage U S DC 2 V ( V) Terminals LINE+ () GND (2(b)) Current rating I N fixed current ratings: 0.5 A, A, 2 A, 3 A, A, 6 A, 8 A, 0 A Closed current I 0 ON condition: typically 8 ma with status output SF: typically ma with signal output F: typically 7 ma Status indication by means of Load circuit Load output Terminal LOAD+ (2) Overload and short circuit disconnection Trip times Temperature disconnection Low voltage monitoring of operating voltage Starting delay t Start l multicolour LED: Green: - unit is ON, load circuit is activated Orange: - in the event of overload or short circuit until electronic disconnection Red: - after disconnection on grounds of overload or short circuit - short circuit until disconnection - low voltage in ON condition - device switched OFF via control input IN+ OFF: - manually switched off via ON/OFF button no operating voltage - status output SF l potential-free signal contacts F l status output SF/SF l ON/OFF/ condition of switch S Power-MOSFET switching output (high side switch) typically.25 x I N with active current limitation see time / current characteristic typically ms depending on rated current (see table ) internal temperature monitoring an delectronic disconnection OFF: at typically < V ON: at typically > 7 V with automatic ON/OFF REF6-S with socket 8plus typically 2 ms after every switch-on after reset and after applying U S 6

2 Electronic Overcurrent Protector REF6-S Technical data Disconnection of load circuit Leakage current in load circuit in OFF condition Capacitive loads Free-wheeling circuit electronic disconnection without physical isolation typically ma up to 20,000 μf external free-wheeling diode recommended with inductive load Several load outputs must not be connected in parallel Signal output SF / REF6-S0/02 Electrical data potential-free signal contact max. DC 30 V / 0.5 A, min. 0 V / 0 ma REF6-S0 terminal: Si ((a))/si ((c)) REF6-S02 terminal: Si ((a))/si ((c)) auxiliary contact, make contact open in OFF or fault condition auxiliary contact, break contact closed in OFF or fault condition Status output SF / REF6-S/2 Status output SF/ REF6-S7/27 Electrical data Plus-switching signal output, connects U S to terminal SF ((c)) Data: DC 2 V / max. 0.2 A (short-circuitproof). The status output is internally blocked against GND with a 0 kohm resistor. Status output SF Status output SF Signal delay of signal output (F) or status output (SF) OK condition typically 20 ms Fault condition typically 200 ms Display of fault condition REF6-S/2, at U S = + 2 V Connection: SF ((c)) + 2 V level at status output anytime when: l device is in operating condition l load output is connected/green LED is lighted 0 V level at status output anytime when: l device is OFF or in error mode REF6-S7/27, at U S = + 2 V Connection: SF ((c)) 0 V level at status output anytime when: l device is in operating condition l load output is connected / green LED is lighted + 2 V level at status output anytime when: l device is OFF or in error mode signal output or status output is in fault condition when l the unit is in the OFF condition - due to an overcurrent disconnection - due to power failure - due to low voltage - due to ON/OFF button operation - due to external control input Control input IN+ / REF6-S/7 Electrical data voltage: max. + DC 30 V high > DC 8 V DC 30 V low DC 3 V > 0 V power consumption typically 2.6 ma (+ DC 2 V) signal delay typically 5 ms Technical data Control signal IN + terminal: IN+ ((a)) Switch S ON/OFF + 2 V level (HIGH): device will be switched on by a remote ON/OFF signal. 0 V level (LOW): device will be switched off by a remote ON/OFF signal Unit can only be switched on with S if a HIGH level is applied to IN+ Reset input RE / REF6-S2/27 Electrical data voltage: max. + DC 30 V high > DC 8 V DC 30 V low DC 3 V > 0 V power consumption typically 2.6 ma (+ DC 2 V) min. pulse duration 20 ms Reset signal RE terminal: RE ((a)) General data Fail-safe element The electronically blocked REF6- S2/27 may remotely be reset via an external momentary switch due to the falling edge of a + DC 2 V pulse. This reset signal can be applied to all devices connected in parallel. Such a wiring is made possible by means of the socket accessory. Its effect will be that all blocked devices will be reset. Switched on devices remain unaffected. integral fail-safe element adjusted to current rating (back-up fuse) see table Blade terminals 6.3 mm to EN Housing material Mounting moulded plug-in type with sockets including coding pins and retaining clips Ambient temperature C (without condensation, see EN 6020-) Storage temperature C Humidity Vibration 96 hrs/95 % RH/0 C to IEC , test Cab. climate class 3K3 to EN g, test to IEC test Fc Degree of protection IEC 60529, DIN VDE 070 operating area: IP30 terminal area: IP00 EMC requirements (EMC directive, CE logo) Insulation co-ordination (IEC 6093) Dielectric strength Insulation resistance (OFF condition) Approvals Dimensions (W x H x D) Mass emission: EN susceptibility: EN kv/2 pollution degree 2 re-inforced insulation in operating area max. DC 32 V (load circuit) n/a, only electronic disconnection CE logo UL 2367 # E30670 UL 508 # E32259 CSA C22.2 No.23 # 6597 (0.5 A 0 A) GL # 669-3HH (0.5 A 0 A) 2. x 52 x 5 mm approx. 20 g 2 6

3 Electronic Overcurrent Protector REF6-S Table : voltage drop, current limitation, trip time, fail-safe element, max. load current Rated current I N typical voltage drop U ON at I N typical active current limitation trip time fail-safe element max. load current at 00 % ON duty T U = 0 C T U = 50 C 0.5 A 85 mv.25 x I N 800 ms 2 A 0.5 A 0.5 A A 0 mv.25 x I N 800 ms 2 A A A 2 A 00 mv.25 x I N 00 ms A 2 A 2 A 3 A 20 mv.25 x I N 300 ms 6.3 A 3 A 3 A A 00 mv.25 x I N 200 ms 6.3 A A A 6 A 30 mv.25 x I N 30 ms 0 A 6 A 5 A 8 A 00 mv.25 x I N 00 ms 5 A 8 A 7.2 A 0 A 20 mv.25 x I N 80 ms 5 A 0 A 9 A Caution: When mounted side-by-side without convection, the REF6-S should not carry more than 80 % of its rated load continuously (00 % ON duty) due to thermal effects. Ordering information Type No. REF6 Electronic circuit breaker with current limit Mounting and design S plug-in type Version without physical isolation Signal input 0 without signal input with control input IN+ (only REF6-S, REF6-S7) 2 with reset input RE (only REF6-S2, REF6-S27) Signal output 0 without signal output (only REF6-S00) signal output F signal contact, make contact (only REF6-S0) 2 signal output F signal contact, break contact (only REF6-S02) status output SF (only REF6-S, REF6-2) 7 status output SF inverted (only REF6-S7, REF6-S27) Operating voltage DC 2 V rated voltage DC 2 V Rated current 0.5 A A 2 A 3 A A 6 A 8 A (without REF6-S02) 0 A (without REF6-S02) REF6 - S 0 - DC 2 V A ordering example Class 2 Meets requirement for Class 2 current limitation (REF6-S A/ A/2 A/3 A) Terminals Example of REF6-S0-DC2V-A multi-colour LED for status indication label version ON/OFF button S on off A -S0 r e s e t LINE+ 2(b) GND (a) Si (c) Si 2 LOAD+ Pin assignment Pin no. 2(b) (a) (c) 2 REF6-S0/02 LINE+ GND Si Si LOAD+ REF6-S LINE+ GND IN+ SF + 2 V LOAD+ REF6-S2 LINE+ GND RE SF + 2 V LOAD+ REF6-S7 LINE+ GND IN+ SF LOAD + REF6-S27 LINE+ GND RE SF LOAD + Dimensions Made in Germany xxxx Electronic Overcurrent Protector REF6-S0-DC2V-A G E R M A N Y Caution l l The user has to ensure that the cable cross sections of the relevant load circuit are suitable for the current rating of the REF6-S used. Automatic start-up of the machinery after a shut-down must be prevented (Machinery Directive 2006/2/EG and EN 6020-), e.g. by means of a safety PLC. In the event of a short circuit or overload the load circuit will be disconnected electronically by the REF6-S blade terminals EN

4 Electronic Overcurrent Protector REF6-S Information on UL-approvals / CSA-approvals UL2367 Non-hazardous use UL File # E30670 UL508 Non-hazardous use UL File # E32259 Industrial Control Equipment, Listed only when used with Socket 80plus or Socket 8plus CSA C22.2 No.23 CSA File # 6597 Hazardous locations: Class Ⅰ, Division 2, Group A, B, C, D, 0 C to 50 C, TA WARNING EXPLOSION HAZARD AVERTISSEMENT RISQUE D EXPLOSION DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS. NE PAS DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION, A MOINS QU ll NE S AGISSE D UN EMPLACEMENT NON DANGEREUX. SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITYFOR CLASS Ⅰ, DIVISION 2. LA SUBSTITUTIOND DE COMPOSANTS PEUT RENDRE CE MATERIEL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE Ⅰ, DIVISION 2; This device is open type equipment that must be used within a suitable end-use system enclosure. The suitability of the enclosure is subject to investigation by the local Authority Having Jurisdiction at the time of installation. Wiring to or from this device, which enters or leaves the system enclosure, must utilize wiring methods suitable for Class Ⅰ, Division 2 Hazardous Locations, as appropriate for the installation. Instruction leaflet E-T-A Elektrotechnische Apparate GmbH Industriestraße ALTDORF DEUTSCHLAND Tel Fax info@e-t-a.de. UL2367 Non-hazardous use UL File # E30670 Electronic Overcurrent Protector REF6- DC2V-0.5-0A UL508 CSA C22.2 No. Non-hazardous use UL File # E32259 Hazardous locations: Class I, Division 2, Group A, B, C, D, 0 C to 50 C, TA Warning Explosion hazard Do not disconnect while circuit is live unless area is know to be non-hazardous. Substitution of components may impair suitability for CLASS I, DIVISION 2. C22.2 No. 23 CSA File # 6597 Avertissment Risque d explosion Ne pas debrancher tant que le circuit est sous tension, a moins qu il ne s agisse d un emplacement non dangereux. La substitution de composants peut rendre ce materiel inacceptable pour les emplacements de CLASSE I, DIVISION 2; Example Example of of REF6-S0-DC2V-A Terminals: REF6 multi-colour multi-colour LED for status LED for status indication indication label version ON/OFF button S Pin assignment Pin no. 2(b) (a) (c) 2 REF6-S0/02 LINE+ GND Si Si LOAD+ REF6-S LINE+ GND IN+ SF + 2 V LOAD+ REF6-S2 LINE+ GND RE SF + 2 V LOAD+ REF6-S7 LINE+ GND IN+ SF LOAD + REF6-S27 LINE+ GND RE SF LOAD + Socket 80plus 2 (b) label version ON/OFF button S on off A -S0 r e s e t A on off -S0 r e s e t LINE+ 2(b) GND (a) Si (c) Si 2 LOAD+ LINE+ Made in Germany xxxx 2(b) GND (a) Si (c) Si 2 LOAD+ Electronic Overcurrent Protector REF6-S0-DC2V-A Made in Germany xxxx G E R M A N Y Socket 8plus 2 (b) Electronic Overcurrent Protector REF6-S0-DC2V-A G E R M A N Y Wiring: REF6 with socket wire type wire range term., 2; (line, load) 80PLUS-.. Cu AWG20-0 sol/str 8PLUS-.. Cu AWG-0 sol/str torque Nm strip length wire range term., 2, (signal) mm AWG26- sol/str mm AWG26-6 sol/str torque Nm strip length mm mm This device is open type equipment that must be used within a suitable end-use system enclosure. The suitability of the enclosure is subject to investigation by the local Authority Having Jurisdiction at the time of installation. Wiring to or from this device, which enters or leaves the system enclosure, must utilize wiring methods suitable for Class I, Division 2 Hazardous Locations, as appropriate for the installation. (a) (c) LINE + 2. / 2.2 LOAD + (a) Si or IN+ or RE (c) Si or SF 2 (b) GND Detailed data sheet is available at the E-T-A homepage for download. Please make sure to always use the most recent document. 2 (c) (a) LINE + 2 LOAD + (a) Si or IN+ or RE (c) Si or SF 2 (b) GND Y39800 Index: - All rights reserved 6

5 REF6-S... - Accessories / Socket 80plus Description Single pole, with PT connection technology, to accommodate -pole circuit protector type REF6-S. Part number: 80PLUS-PT0 l Push-in design: push the stripped wire (cross section 0.25 mm 2, rigid or with wire end ferrule) into the round hole of the terminal without using a tool l For smaller cable cross sections or flexible wires without wire end ferrule you have to push in the orange push button to open the spring. l For release push in the orange push button with a screw driver. Time/current characteristic (T U = 25 C) Line connection 2 (b) (a) (c) trip time in seconds , min..05 / max..5 x I N LINE + 2. / 2.2 LOAD + (a) Si or IN+ or RE (c) Si or SF 0, IK trip time depending on I N (see table ) Trip time and current limitation typically,25 x I N times rated current 2 (b) GND Dimensions l The trip is typically in a range of 80 ms to 800 ms depending on the rated current (I N ) l Electronic disconnection and/or current limitation typically occur at.25 x I N. This means that under all overload conditions the max. overload before disconnection will not exceed.25 times rated current. l Without this current limitation a considerably higher overload current would flow in the event of an overload or short circuit Cable cross section Cross section when opening the push-in terminal Cable cross section directly pluggable stripped wire length terminal (line) (with plastic sleeve) - flexible with TWIN-wire end ferrule (0 mm 2 ) 0.5 mm 2 - rigid (with plastic sleeve) 6 mm 2 (0 mm 2 ) 2 mm terminals 2. and 2.2 (load) (with plastic sleeve) - flexible with TWIN-wire end ferrule: mm mm mm mm mm 2 (with plastic sleeve) 0.75 mm mm 2 2 mm terminals, 2 and (signalling) (with plastic housing) 0..5 mm mm mm 2 0. mm 2 (with plastic housing) mm mm mm 2 8 mm 6 5

6 REF6-S... - Accessories / Socket 80plus Insertion of busbars/jumpers Application examples Common line entry 2 (b) cross bridging terminals (line) bridging contacts (c) and (a) Coding of REF6-S and socket 80plus following the lock-key-principle Common line entry GND cross bridging terminals 2 (b) Remove black coding pin of the circuit protector by means of a screwdriver Insert red coding star (accessory part number Y ) into the receptacle of the socket Note: see coding table on page Accessories socket 80/8plus Series connection of aux. contacts (REF6-S0) Replacing a REF6-S Loosen device by slightly pressing on the retaining clip 2 Pull circuit breaker out of socket 6 individual bridging of terminals (a) and (c) 6

7 REF6-S... - Accessories / Socket 8plus Description Line connection Single pole, with screw terminals, to accommodate -pole circuit protector type REF6-S. 2 (b) Part number: 8PLUS-UT0 Dimensions (c) (a) 2 LINE + 2 LOAD + (a) Si or IN+ or RE (c) Si or SF 2 (b) GND Cable cross section terminals (line) and 2 (load) thread size max. cable cross section stripped wire length M Wire - rigid (single-wire or multistrand) (with and without plastic sleeve) - flexible with TWIN-wire end ferrule: Multi-lead connection (two wires with identical cross section) - rigid (single-wire or multistrand) - flexible with TWIN-wire end ferrule mm mm mm mm mm 2 0 mm.2 Nm tightening torque terminals, 2 and (signalling) M3 Wire (with and without plastic sleeve) 0. mm 2 0. mm mm 2 Multi-lead connection (two wires with identical cross section) - flexible with TWIN AEH: (with plastic sleeve) - flexible with AEH: 0..5 mm mm mm mm 2 9 mm 0.5 Nm This is a metric design and millimeter dimensions take precedence ( mm ) inch All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.product markings may not be exactly as the ordering codes. Errors and omissions excepted

8 REF6-S... - Accessories / Socket 8plus Insertion of busbars/jumpers Application examples Common line entry 2 (b) cross bridging terminals (line) bridging contacts (c) and (a) Coding of REF6-S and socket 8plus following the lock-key-principle Common line entry GND cross bridging terminals 2 (b) Remove black coding pin of the circuit protector by means of a screwdriver Insert red coding star (accessory part number Y ) into the receptacle of the socket Series connection of aux. contacts (REF6-S0) Note: see coding table on page Accessories socket 80/8plus Replacing a REF6-S Loosen device by slightly pressing on the retaining clip individual bridging of terminals (a) and (c) 2 Pull circuit breaker out of socket 8 6

9 REF6-S... Accessories - Socket 80/8plus Accessories Accessories for Socket 80plus and Socket 8plus part number packing qty busbar, for cross-bridging in the bridge shaft, red, 2 poles * Y busbar, for cross-bridging in the bridge shaft, red, poles * Y busbar, for cross-bridging in the bridge shaft, red, 0 poles * Y busbar, for cross-bridging in the bridge shaft, blue, 2 poles * Y busbar, for cross-bridging in the bridge shaft, blue, poles * Y busbar, for cross-bridging in the bridge shaft, blue, 0 poles * Y busbar, for cross-bridging in the bridge shaft, grey, 2 poles * Y busbar, for cross-bridging in the bridge shaft, grey, 0 poles * Y coding star, red, with coding pins each Y label X busbar/jumper, 0 poles coding star label * Max. bridge current: 32 A When using two busbars/jumpers (in both bridge shafts of terminal ), the max. current capacity is A. Caution: When using busbars/jumpers for bridging the aux. contacts ((a), 2(b) and (c)), the max. bridge current is A. Coding table Coding example: Avoid hazardous oversize current ratings Your benefit: Coded electronic overcurrent protector can no longer be inserted into slots with a lower current rating coding. Coding of electrionic overcurrent protector and sockets Sockets: Insert coding pins in accordance with coding table into receptacles of the sockets. Electronic Overcurrent Protector: Remove coding pins in accordance with coding table by means of screw driver. Protector-socketcoding for the circuit protector with the highest current rating decreasing current rating Coding table Protector Socket Protector 0 Socket 0 0 Protector 0 Socket 0 0 Protector 0 0 Socket 0 Example 0 A 8 A 6 A A 0 Protector 0 Socket A Protector-socketcoding for the circuit protector with the lowest current rating Protector 0 0 Socket 0 Protector 0 0 Socket 0 Protector Socket 2 A A 0.5 A 0 0 : With PIN / 0: No PIN 6 9

10 Electronic Overcurrent Protector REF6-S 0 6

Thermal-Magnetic Circuit Breaker 2216-S

Thermal-Magnetic Circuit Breaker 2216-S Thermal-Magnetic Circuit Breaker 226-S Description One and two pole thermal-magnetic circuit breaker in compact design with slide actuator, trip-free mechanism, various trip characteristics and optional

More information

Operating Instructions Electronic Circuit Protector ESX10-TC-DC 12 V

Operating Instructions Electronic Circuit Protector ESX10-TC-DC 12 V Y 310 410 01 Version: 03/2012 Operating Instructions Electronic Circuit Protector ESX10-TC-DC 12 V Specifications: Warning This device is only suitable for operation at 24 VDC (safety extra-low voltage).

More information

Module 18plus. Description. 18plus

Module 18plus. Description. 18plus Module 8plus Description Wiring of load and signal lines in a space-saving manner will become ever more important for designers of electrical plants and systems, because all control cabinets and control

More information

Thermal-Magnetic Circuit Breaker 4220-T...

Thermal-Magnetic Circuit Breaker 4220-T... Thermal-Magnetic Circuit Breaker 40-T... Description Single, double and three pole thermal-magnetic circuit breakers with high rupture capacity to UL 489 (5 ka), EN/IEC 60934 (6kA) and UL 077 (5 ka). With

More information

REX12D Electronic Circuit Protector

REX12D Electronic Circuit Protector Description The compact and flexible all-in-one solution REX consists of several perfectly matched components. It comprises the EM12D-T / EM12-T supply module for the plus and minus potential via a single

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker

Magnetic and Hydraulic-Magnetic Circuit Breaker Description Single or multipole hydraulic-magnetic circuit breakers with trip-free - mechanism and toggle actuation. A choice of switching characteristics ensures suitability for a wide range of applications.

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-T... Description ngle, two and three pole magnetic and hydraulic-magnetic circuit breakers with trip-free mechanism and toggle actuation. A choice of fast magnetic only hydraulically delayed switching characteristics

More information

Introduction Electronic Circuit Protection ESX10-T

Introduction Electronic Circuit Protection ESX10-T Introduction Electronic Circuit Protection ESX0-T Electronic circuit protection type ESX0-T is designed to ensure selective disconnection of 24VDC load systems. 24VDC power supplies, which are widely used

More information

Solid State Remote Power Controller E /627

Solid State Remote Power Controller E /627 Solid State Remote Power Controller E--623/62 Description The E-T-A Solid State Remote Power Controllers E--623/62 are electronic control modules suitable for inductive loads such as electromagnetic valves

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-F...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-F... Magnetic and Hydraulic-Magnetic Circuit Breaker 830-F... Description Single and multipole magnetic circuit breakers with trip-free mechanism and toggle actuation. A choice of fast magnetic only or hydraulically

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-F...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-F... Description Single and multipole magnetic circuit breakers with trip-free mechanism and toggle actuation. A choice of fast magnetic only or hydraulically delayed switching characteristics (S-type MO or

More information

Solid State Remote Power Controller E

Solid State Remote Power Controller E Description The E-T-A is a transistorised switching device providing both protection and signalisation. It is suitable for all applications where the capabilities of the existing PLC s are not sufficient

More information

QUINT-BUFFER/24DC/24DC/40

QUINT-BUFFER/24DC/24DC/40 Buffer module Data sheet 105496_en_01 PHOENIX CONTACT 2013-11-01 1 Description The QUINT BUFFER buffer module combines the electronic switchover unit and power storage in the same housing. The buffer module

More information

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA Continous voltage monitoring Mains fluctuation detection Detects voltage drop / short interruptions of at least 10ms Prevents undefined states in switching and control systems Generates reset pulse after

More information

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary switched power supply, 3-phase, output current: 40 A INTERFACE Data Sheet 102782_01_en PHOENIX CONTACT - 06/2007 Description TRIO POWER is the rail mountable 24 V power supply unit with basic functions.

More information

Power supply CP-C 24/5.0

Power supply CP-C 24/5.0 2CDC 271 064 F0004 Features Supply voltage ranges: 85-264 V AC, 100-350 V DC Output voltage adjustable from 22-28 V DC, default setting 24 V DC 0,5 % 5 A output current Open-circuit, overload and continous

More information

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary-switched power supply for building automation INTERFACE Data sheet 103505_en_02 1 Description PHOENIX CONTACT - 08/2009 Features STEP POWER power supply units for building automation The new STEP

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 Operating Instructions Seite 1 Dimensions drawings: TSP-REM360 Weight: 0.882lb Gewicht: 0.40kg Seite 2 Dimensions drawings: TSP-REM600 Bottom view Top view Side

More information

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Rhino Buffer Module PSM24-BFM600S. Operating Instructions Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts

More information

STEP-PS/1AC/24DC/1.75

STEP-PS/1AC/24DC/1.75 Primary-switched power supply, 1 AC, output current 1.75 A INTERFACE Data Sheet 103506_en_00 1 Description PHOENIX CONTACT - 05/2008 Features STEP POWER power supply units for building automation The new

More information

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog Issued February 2011 DATA SHEET 5SX2 MCB Based on Siemens Industrial Control Catalog General Data Trip characteristics Tripping characteristics acc. to EN 60 898 Tripping characteristic A, -5 Type A characteristic

More information

PHOENIX CONTACT - 12/2007

PHOENIX CONTACT - 12/2007 Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Active Transistor Output, Two-Channel INTERFACE Data Sheet 0943_00_en PHOENIX CONTACT - /007 Description The PI-EX-ME-NAM/TO-A is a two-channel

More information

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

Rhino Redundancy Module PSM24-REM360S. Operating Instructions Rhino Redundancy Module PSM4-REM360S Operating Instructions RHINO REDUNDANCY MODULE PSM4-REM360S Description With this module and two power supplies of the PSM series (78, 90, 56, 80 and 360 watt models),

More information

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA Monitoring of phase sequence and phase loss Monitoring of asymmetry Supply voltage 208-480 V AC Supply circuit = measuring circuit 1 change-over contact Width 22,5 mm Control elements Asymmetry Status

More information

Contact protection relay

Contact protection relay Contact protection relay Ordering details SVR 450 08 F0000 The protects sensitive control contacts from excessive load. It can be used with latching function or without. Bounce time of control contacts

More information

PI-EX-ME-2NAM/COC-24VDC

PI-EX-ME-2NAM/COC-24VDC Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Relay Output, PDT, Two-Channel, 4 V DC Supply INTERFACE Data Sheet 0033_0_en PHOENIX CONTACT - /007 Description The PI-EX-ME-NAM/COC-4VDC

More information

RTU500 series Data Sheet Power Supply CP-E 24/2.5

RTU500 series Data Sheet Power Supply CP-E 24/2.5 Data Sheet Power Supply CP-E 24/2.5 Power Supply CP-E 24/2.5 Application The primary switch mode power supply offers two voltage input ranges. This enables the supply with AC or DC. Furthermore it is equipped

More information

454 PHOENIX CONTACT Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA

454 PHOENIX CONTACT Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 454 PHOENIX CONTACT and feed-through terminal blocks The more varied the tasks in electrical engineering, the more varied the components for the solution have to be. The industrial connection technology

More information

Model Number Structure

Model Number Structure Solid State Relays with Failure Detection Function G3PC CSM_G3PC_DS_E_1_1 Refer to Safety Precautions for All Solid State Relays. Detects failures in SSR used for heater temperature control and simultaneously

More information

PI-EX-ME-2NAM/COC-120VAC

PI-EX-ME-2NAM/COC-120VAC PI-EX-ME-NAM/COC-0VAC Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Relay Output, PDT, Two-Channel, 0 V AC Supply INTERFACE Data Sheet 0944_00_en PHOENIX CONTACT - 0/008 Description

More information

PHOENIX CONTACT - 07/2006

PHOENIX CONTACT - 07/2006 Buffer module with maintenance-free capacitor-based power storage device INTERFACE Data sheet 102035_03_en PHOENIX CONTACT - 07/2006 Description Short-term mains interruptions are bridged by QUINT BUFFER,

More information

Power distribution system SVS16-PB

Power distribution system SVS16-PB Power distribution system SVS1PB Description The new power distribution and remote output system type SVS1 PBxx offers selective overcurrent protection, power distribution of load circuits and switching,

More information

Page Housing Plastic Metal Mounting DIN Rail or surface mount Panel or bracket mount Wattage Range 10W to 240W 7.5W to 240W 10W to 300W

Page Housing Plastic Metal Mounting DIN Rail or surface mount Panel or bracket mount Wattage Range 10W to 240W 7.5W to 240W 10W to 300W Selection Guide Selection Guide PS5R Slim Line PS5R PS3L Operator Interfaces Communication & Networking PLCs NEW Models Appearance Automation Software Page 107 113 118 Housing Plastic Metal Mounting DIN

More information

TSP-BCM48, TSP-BCM48A. Operating Instruction Manual. Page 1 of 13

TSP-BCM48, TSP-BCM48A. Operating Instruction Manual.  Page 1 of 13 Battery Controller Module TSP-BCM24, TSP-BCM24A TSP-BCM48, TSP-BCM48A Operating Instruction Manual http://www.tracopower.com Page 1 of 13 Dimensions drawings: TSP-BCM24 & TSP-BCM48 Weight: 0.816lb Gewicht:

More information

1492-SP Supplementary Protectors

1492-SP Supplementary Protectors Dual terminals provide wiring/bus bar flexibility and clamp from both sides to improve connection reliability Approval marks are easily visible on dome Terminal design helps prevent wiring misses Scratch-

More information

TO 161 S-DIAS Digital Output Module

TO 161 S-DIAS Digital Output Module TO 161 S-DIAS Digital Output Module Date of creation: 30.07.2013 Version date: 20.09.2018 Article number: 20-007-161-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax:

More information

TXM1.8RB. TX-I/O Blinds module

TXM1.8RB. TX-I/O Blinds module s 8 178 8178p01 TX-I/O Blinds module TXM1.8RB 8 non-floating relay outputs for... 4 blinds motors with 2 end switches, or 2 blinds motors with 3 end switches, or 2 blinds motors with 2 end switches + 1

More information

Power distribution systems - accessories

Power distribution systems - accessories Power distribution systems - accessories Connections and terminals Line terminal X 50 0 suitable for Power-D-Box with sockets pre-wired Line terminal (max. 6 A) X 50 0.55 max. tightening torque.0 Nm 5.59

More information

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064 Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window

More information

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/ DC - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type Time

More information

Rack Installation Instruction

Rack Installation Instruction Rack Installation Instruction Date of issue: Date of publication: May 2017 This document replaces the following documents: ControlPlex Rack I_19BGTCP_d_200916 Editor: Elektrotechnische Apparate GmbH Industriestraße

More information

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages The CM-ESS.1 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact The CT-ERS.12 is an electronic timer from the CT-S range with ON-delay and 10 time ranges. All electronic timers from the CT-S

More information

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h. On-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status

More information

Rhino PSM Power Supplies. Operating Instructions

Rhino PSM Power Supplies. Operating Instructions Rhino PSM Power Supplies Operating Instructions RHINO Power Supplies PSM Series Description The PSM power supplies are built-in units. The mounting position for PSM power supplies must fulfill the requirements

More information

02/11/2015

02/11/2015 DIN Rail Mount 35 mm HSV Part number 84874320 Control of overspeed, underspeed, operating rate, stopping Measurement via discrete sensors - 3-wire PNP or NPN, Namur, voltage 0-30V or volt-free contact

More information

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/DC - solid state output Complementary Control type Voltage range Main Range of product Product or component type Discrete output type Width

More information

Communication & Networking

Communication & Networking MicroSmart Master Module Capable of Connecting 62 Slaves Compliance with Ver. 2.1 specifi cations Digital and analog slaves can be connected. Configuration and slave monitoring can be done using LED indicators

More information

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA 4 time ranges 4 transition times Supply voltage 12-240V AC/DC 2 normally open contacts Width 22,5 mm Control elements Fine adjustment star contactor Setting of time range star contactor Transit time Status

More information

Model Number Structure

Model Number Structure Solid State Relays with Failure Detection Function G3PC Detects failures in SSR used for heater temperature control and simultaneously outputs alarm signal. This SSR supports the safe design of heater

More information

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA Off-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5 mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status

More information

Redundancy unit CP-A RU

Redundancy unit CP-A RU 2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power

More information

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary switched power supply, 1-phase, output current: 5 A ITERFACE Data Sheet 103349_en_00 1 Description PHOEIX COTACT - 05/2008 Features TRIO POWER is the DI-rail-mountable power supply unit with basic

More information

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend Solid State Relays with Failure Detection Function G3PC Refer to Warranty and Application Considerations (page 1), Safety Precautions (page 4), and Technical and Safety Information (page 6). Detects failures

More information

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts Data sheet Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts The CT-ARS.21 is an electronic timer from the CT-S range with true OFF-delay. It provides 7 time ranges

More information

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet 2CDC 251 113 F0004 CT-AHS 1 7 2 6 5 4 8 3 1 10 selectable time ranges, from 0.05 s to 300 h 2 Potentiometer with direct reading scale for the fine adjustment of the time delay 3 Sliding switch to set the

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

Approved Standards. Motor Protection Circuit Breaker (MPCB) J7MN. MPCB system (motor protection CLASS 10) Auxiliary contact modules.

Approved Standards. Motor Protection Circuit Breaker (MPCB) J7MN. MPCB system (motor protection CLASS 10) Auxiliary contact modules. Motor Protection Circuit Breaker (MPCB) J7MN MPCB system (motor protection CLSS 0) Rotary and switch types Rated operational current = 2, 25, 50 and 00 Switching capacity up to 2.5 = 00 k/400 V Fixed short-circuit

More information

Introduction Circuit Protection

Introduction Circuit Protection Introduction Circuit Protection Weidmuller s DIN-rail mounted circuit breakers are available for use in applications where circuit protection must be able to distinguish between circuit overloads and short

More information

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5 Power Supply, Primary Switch Mode for Universal Use -PS-100-240AC/48/5 POWER provides: Preventive function monitoring through professional signaling Global use due to a wide range input A high level of

More information

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING Product and Applications Description Note If the application program is not loaded completely by the ETS, you had better interrupt the 24 V voltage supply of the I/O-module during the loading interval.

More information

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts Data sheet Electronic timer CT-SDS. Star-delta change-over with n/o contacts The CT-SDS. is an electronic timer from the CT-S range with Star-delta change-over and 7 time ranges. All electronic timers

More information

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts Data sheet Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts The CT-APS.21 is an electronic timer from the CT-S range with OFF-delay. It provides 10 time ranges and a continuous rated control

More information

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input Safety + standard I/O in one module Safety relay output with galvanically isolated contact sets, approved up to 230 V IEC 61508 SIL 3, EN ISO 13849-1/PLe Kat 4, EN 62061 SIL 3 Protection category IP20

More information

ISOMETER isoev425/isoev425hc with coupling device AGH420

ISOMETER isoev425/isoev425hc with coupling device AGH420 with coupling device AGH420 Insulation monitoring device for unearthed DC circuits (IT systems) for charging electric vehicles isoev425_d00126_04_d_xxen/06.2018 with coupling device AGH420 Insulation monitoring

More information

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output Characteristics off-delay timing relay - control - 1 s..100 h - 24..240 V - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type

More information

Miniature Circuit Breakers for Railway Applications

Miniature Circuit Breakers for Railway Applications Siemens AG 00 for Railway Applications BETA Low-Voltage Circuit Protection The miniature circuit breakers are used in fixed railway systems and rolling stock for protecting system components against overcurrent

More information

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet 2CDC 251 056 F0t07 Features Rated control supply voltage 24-48 V DC, 24-240 V AC Single-function ON-delay timer One device includes 10 time ranges (0.05 s - 300 h) 1 c/o contact 2 LEDs for status indication

More information

Solid-state Timer H3YN

Solid-state Timer H3YN Solid-state Timer H3YN Miniature Timer with Multiple Time Ranges and Multiple Operating Modes Minimizes stock. Pin configuration compatible with MY Power Relay. Standard multiple operating modes and multiple

More information

Messaging module CP-C MM

Messaging module CP-C MM 2CDC 271 087 F0t04 Features Pluggable onto CP C range primary switch mode power supplies REMOTE OFF input to switch off the power supply unit remotely Monitoring of the input voltage of the power supply

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

Electronic timer CT-ERD.12

Electronic timer CT-ERD.12 2CDC 251 092 F0t06 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied

More information

PHOENIX CONTACT - 05/2007

PHOENIX CONTACT - 05/2007 Ex Universal Module Carrier (Motherboard) for Accommodating 3-Wire Measuring Transducers, Intrinsically Safe, for a Maximum of 8 PI Ex Modules INTERFACE Data Sheet 103030_00_en PHOENIX CONTACT - 05/2007

More information

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact Data sheet Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact The CT-ARS.11 is an electronic timer from the CT-S range with true OFF-delay. It provides 7 time ranges

More information

Electronic timer CT-ERS.21

Electronic timer CT-ERS.21 2CDC 251 057 F0t07 Features Rated control supply voltage 24 240 V AC/DC Single function ON delay timer One device includes 10 time ranges (0.05 s 300 h) 2 c/o contacts 2 LEDs for status indication Width

More information

Power supply CP-E 48/1.25 Primary switch mode power supply

Power supply CP-E 48/1.25 Primary switch mode power supply Data sheet Power supply CP-E 48/1.25 Primary switch mode power supply The CP-E range offers enhanced functionality while the number of different types has been considerably reduced. Now all power supply

More information

ETD-BL-1T-OFF-CC- 10S

ETD-BL-1T-OFF-CC- 10S Timer relay with off delay (with control contact) and adjustable time Data sheet 103617_en_03 1 Description PHOENIX CONTACT - 2013-09-16 Features Compact timer relay in 6.2 mm housing for controlling time

More information

ISOMETER isoev425 with coupling device AGH420

ISOMETER isoev425 with coupling device AGH420 with coupling device AGH420 Insulation monitoring device for unearthed DC circuits (IT systems) for charging electric vehicles Preliminary datasheet isoev425_d00126_02_d_xxde/09.2015 with coupling device

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

ST 200 M data sheet System pro M compact miniature circuit breakers for supplementary protection acc. to UL 1077

ST 200 M data sheet System pro M compact miniature circuit breakers for supplementary protection acc. to UL 1077 MINIATURE CIRCUIT BREAKERS ST 200 M data sheet System pro M compact miniature circuit breakers for supplementary protection acc. to UL 1077 The ST 200 M miniature circuit breaker provides supplementary

More information

TRIO-DIODE/12-24DC/2X10/1X20

TRIO-DIODE/12-24DC/2X10/1X20 Redundancy module INTERFACE Data sheet 104278_en_00 1 Description PHOENIX CONTACT 20100423 Features TRIO DIODE is the DINrail mountable redundancy module from the TRIO POWER product range. Using the redundancy

More information

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Uninterruptible power supply with integrated power supply unit INTERFACE Data sheet 104211_en_00 1 Description PHOENIX CONTACT - 01/2010 Features The MINI-DC-UPS provide an uninterruptible DC voltage both

More information

Electronic timer CT-AHD.22

Electronic timer CT-AHD.22 2CDC 251 093 F0t06 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied

More information

UNO-PS/1AC/12DC/30W. Primary-switched power supply unit. Data sheet. 1 Description

UNO-PS/1AC/12DC/30W. Primary-switched power supply unit. Data sheet. 1 Description Primaryswitched power supply unit Data sheet 105549_en_00 PHOENIX CONTACT 20130405 1 Description The UNO POWER power supply unit impresses in worldwide use thanks to maximum energy efficiency. Low noload

More information

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet 2CDC 251 116 F0004 1 5 2 4 3 6 Characteristics Single-function ON-delay and OFF-delay timer One device includes 10 time ranges, from 0.05 s to 300 h, for the adjustment of the time delay Remote potentiometer

More information

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F Approvals a culus f CCC CT-BS Circuit diagram Marker label Marks g c CE C-Tick Order data

More information

DM 161 S-DIAS Digital Mixed Module

DM 161 S-DIAS Digital Mixed Module DM 161 S-DIAS Digital Mixed Module Date of creation: 27.02.2014 Version date: 18.10.2017 Article number: 20-008-161-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax: +43/6274/4321-18

More information

Power supply CP-E 24/0.75 Primary switch mode power supply

Power supply CP-E 24/0.75 Primary switch mode power supply Data sheet Power supply CP-E 24/0.75 Primary switch mode power supply The CP-E range offers enhanced functionality while the number of different types has been considerably reduced. Now all power supply

More information

Functional configuration Rated input voltage Power ratings Output voltage Output current Part number Non-PFC

Functional configuration Rated input voltage Power ratings Output voltage Output current Part number Non-PFC Switching Power Supply DIN-Rail Mount Power Supply With Capacity Up to 240 W for General or Industrial Applications Wide power range: 15 to 240 W 15 W and PFC Models with Universal voltage of 100 to 230

More information

Power Supply HARTING pcon

Power Supply HARTING pcon HARTING pcon 2060 Advantages Compact design and high power density Easy installation and tool-less connection Wide input range for world-wide use Wide operating temperature range (up to 70 C without derating)

More information

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary switched power supply, 1-phase, output current: 5 A ITERFACE Data Sheet 102777_en_03 1 Description PHOEIX COTACT - 05/2008 Features TRIO POWER is the DI-rail-mountable power supply unit with basic

More information

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview Supplementary Protectors / Miniature Circuit Breakers Page System overview 10/003 10/001 Supplementary protectors

More information

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A)

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A) Product and functional description also functions if the bus cable is not connected or if the bus communication fails. After a long push button action (> 2 s), the other valve group is selected. The yellow

More information

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300 Monitoring Technique VARIMETER PRO Multifunction Measuring Relay MK 93N, MH 93 268581 Product Description MK 93N MH 93 The universal measuring relays MK 93N / MH 93 of the VARIMETER PRO series monitor

More information

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1 Power Supply, Primary Switch Mode, arrow Design -PS-100-240AC/24/1 POWER provides: Extra narrow widths of 22.5, 45, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide range input A high

More information

RO 051 S-DIAS Relay Output Module

RO 051 S-DIAS Relay Output Module RO 051 S-DIAS Relay Output Module Date of creation: 10.08.2015 Version date: 18.10.2017 Article number: 20-064-051-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax: +43/6274/4321-18

More information

AO 081 S-DIAS Analog Output Module

AO 081 S-DIAS Analog Output Module AO 081 S-DIAS Analog Output Module Date of creation: 05.08.2013 Version date: 18.10.2017 Article number: 20-010-081-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: +43/6274/4321 Fax: +43/6274/4321-18

More information

Description. Green. Red. Orange

Description. Green. Red. Orange GP3000 Series DIO Interface Installation Guide Caution Be sure to read the Warning/Caution Information on the attached sheet before using the product. CAUTION This manual describes the part names and general

More information

- 1 - Product catalogue PCB connection systems PCB terminals Clamping yoke connection LM 5.00 / 5.08 LM 5.00/135

- 1 - Product catalogue PCB connection systems PCB terminals Clamping yoke connection LM 5.00 / 5.08 LM 5.00/135 General ordering data Order No. 1715360000 Part designation LM5.00/3/135 OR Version EAN 4008190365240 Qty. 500 pc(s). PCB terminal, Clamping yoke connection, Soldered connection, Clamping range, max.:

More information