11 kv Indoor Switchgear - SCADA Controlled

Size: px
Start display at page:

Download "11 kv Indoor Switchgear - SCADA Controlled"

Transcription

1 Specification 11 kv Indoor Switchgear - SCADA Controlled Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the NSW Government and its agencies. It is not suitable for any other purpose. You must not use or adapt it or rely upon it in any way unless you are authorised in writing to do so by a relevant NSW Government agency. If this document forms part of a contract with, or is a condition of approval by, a NSW Government agency, use of the document is subject to the terms of the contract or approval. This document may not be current. Current standards are available for download from the Asset Standards Authority website at State of NSW through Transport for NSW

2 Standard governance Owner: Authoriser: Approver: Lead Electrical Engineer, Asset Standards Authority Chief Engineer Rail, Asset Standards Authority Director, Asset Standards Authority on behalf of ASA Configuration Control Board Document history Version Summary of change 1.0 First issue For queries regarding this document, please the ASA at or visit State of NSW through Transport for NSW

3 Preface The Asset Standards Authority (ASA) is an independent unit within Transport for NSW (TfNSW) and is the network design and standards authority for defined NSW transport assets. The ASA is responsible for developing engineering governance frameworks to support industry delivery in the assurance of design, safety, integrity, construction, and commissioning of transport assets for the whole asset life cycle. In order to achieve this, the ASA effectively discharges obligations as the authority for various technical, process, and planning matters across the asset life cycle. The ASA collaborates with industry using stakeholder engagement activities to assist in achieving its mission. These activities help align the ASA to broader government expectations of making it clearer, simpler, and more attractive to do business within the NSW transport industry, allowing the supply chain to deliver safe, efficient, and competent transport services. The ASA develops, maintains, controls, and publishes a suite of standards and other documentation for transport assets of TfNSW. Further, the ASA ensures that these standards are performance based to create opportunities for innovation and improve access to a broader competitive supply chain. This standard has been updated from RailCorp document EP SP 11kV AC Indoor SCADA Controlled Switchgear Fitted with Stationary (Non-Withdrawable) Switching Devices. This RailCorp document is withdrawn with the publication of this specification. This document is a first issue. State of NSW through Transport for NSW Page 3 of 59

4 Table of contents 1. Introduction Purpose Scope Application Reference documents Terms and definitions Functional requirements of 11 kv indoor switchgear Switchboard requirements Circuit breaker specific ratings Busbar inter-panel partition Busbar earthing facility Switchboard extension Earthing bar Transient earth clamp Current transformers for circuit breaker Current transformer rating plate Voltage transformers for switchboards Low voltage cabinet for secondary equipment Circuit breakers Circuit breaker interrupters Circuit breaker operating mechanisms Circuit breaker indications Switchgear auxiliary equipment Interlocks Mechanical interlocks Circuit breaker and switch panel HV cable compartment Fully insulated cable terminations Non-fully insulated cable terminations Cable compartment size Surge arresters for 11 kv switchboards Circuit earthing facilities Voltage detecting system Circuit test facilities Padlocking Floor fixing and penetration details Segregation of LV wiring in HV compartment Instruments, transducers and metering Current transducers Voltage transducers Ammeters Voltmeters Watthour meter State of NSW through Transport for NSW Page 4 of 59

5 23. Busbar and circuit protection High impedance bus zone protection Internal arc fault detection scheme Feeder protection System transformer protection Distribution transformer protection SCADA indications and controls Binary indication and ACCB control Analogue indication Controls Appendix A - Switchboard configurations...29 A.1 Switchboard configurations...29 A.1.1 Switchboard panel configuration codes A.1.2 Bus coupling circuit breaker A.1.3 Capacitor/harmonic filter circuit breaker A.1.4 Feeder circuit breaker (non Auto) A.1.5 Feeder network switch (supervisory indication only) Appendix B - Typical switchboard configurations...34 B.1 Supply point switchboard configurations...34 B.2 Switching station switchboard configurations...34 B.3 System substation switchboard configurations...34 B.4 Mid point switching switchboard configuration...35 B.5 Bus coupled circuit breaker switchboard...35 B.6 Example switchboard configurations...35 Appendix C - Integrated system support requirements...46 C.1 Integrated support objectives...46 C.2 Equipment supplier deliverable...46 Appendix D - Tests...47 D.1 Routine tests...47 D.2 Type tests...47 Appendix E - Data set associated with the equipment...48 E.1 Information...48 E.2 Technical schedule...48 E.3 Life cycle costing...48 Appendix F - Technical schedule...49 Appendix G - Guide to information requirements for Request for Tender...58 State of NSW through Transport for NSW Page 5 of 59

6 1. Introduction This document details the requirements for indoor 11 kv non-withdrawable SCADA controlled switchgear for use in the RailCorp distribution system. All information required to ensure that the switchgear is electrically suitable for the RailCorp network is contained in this document or referenced by this document. 2. Purpose 2.1. Scope The purpose of this document is to specify the requirements for 11 kv non-withdrawable SCADA controlled switchgear to enable suitable equipment to be procured for use in the RailCorp network. This document provides the specifications of factory assembled, type tested, metal enclosed, single busbar, fixed (stationary) switching devices designed for indoor installation on railway distribution systems operating at nominal 11 kv ac, three-phase, 50 Hz. The switchgear panels include equipment that comprises of a fixed functional unit with an associated off-load disconnector and interlocked earthing facility, in combination with the associated SCADA control, measuring, indicating, alarm and protective equipment, including interconnections, accessories, enclosures and supporting structure Application The requirements of this document apply to purchase or installation of a new 11 kv indoor switchboard in a RailCorp substation. These requirements are applicable from the date of issue of this specification. The requirements of this document are not applicable to existing 11 kv indoor switchboards currently in service in the RailCorp network. 3. Reference documents International standards IEC Voltage detection systems Australian standards AS :1985 International electrotechnical vocabulary - Switchgear, controlgear and fuses AS :1996 High-voltage test techniques - General definitions and test requirements State of NSW through Transport for NSW Page 6 of 59

7 AS 2067:2008 Substations and high voltage installations exceeding 1 kv ac AS 2629:2008 Separable insulated connectors for power distribution systems above 1 kv AS 2700:2011 Colour standards for general purposes AS 3760:2010 In-service safety inspection and testing of electrical equipment AS :2007 Instrument transformers - Current transformers AS :2007 Instrument transformers Inductive voltage transformers AS 60137:2008 Insulated bushings for alternating voltages above 1000 V AS :2001 High-voltage switches - Switches for rated voltages above 1 kv and less than 52 kv AS 60270:2001 High-voltage test techniques Partial discharge measurements AS 60417(all parts) Graphical symbols for use on equipment (identical to IEC 60417) AS 60529:2004 Degrees of protection provided by enclosures (IP Code) AS :2012 High-Voltage switchgear and controlgear - Common specifications AS :2008 High-voltage switchgear and controlgear - High voltage alternating-current circuit breakers AS :2005 High-voltage switchgear and controlgear - Alternating current disconnectors (isolators) and earthing switches AS :2005 High-voltage switchgear and control gear A.C. metal enclosed switchgear and controlgear for rated voltages above 1 kv and up to and including 52 kv AS :2005 High voltage switchgear and control gear - Dimensional standardardization of terminals Transport for NSW standards Several significant sets of requirements applicable to 11 kv ac indoor, supervisory controlled switchgear are common to other classes of equipment and are set out in the following TfNSW standards. The equipment shall comply with the relevant requirements set out therein. T HR EL PR Electrical Power Equipment - Integrated Support Requirements T HR EL SP Common Requirements for Electric Power Equipment EP SP Electrical Power Equipment - Design Ranges of Ambient Conditions EP SP Protection System Requirements for the High Voltage Network State of NSW through Transport for NSW Page 7 of 59

8 EP SP Insulation Coordination and Surge Arrester Selection EP SP Standard Voltage Tolerances 4. Terms and definitions The following terms and definitions apply in this document: ACCB alternating current circuit breaker ASA Asset Standards Authority CT current transformer MTM protection relay for the multi-tripping of ACCBs This is a manually reset relay with a hand reset flag. NER neutral earthing resistor RTU remote terminal unit SCADA supervisory controlled and data acquisition system TfNSW Transport for New South Wales UGOH underground to overhead (aerial line) VDS voltage detection system VPIS voltage presence indicating system VT voltage transformer For the purpose of this specification, the terms and definitions in AS and the following apply: circuit breaker a mechanical switching device that is capable of making, carrying and breaking currents under normal circuit conditions, and also of making, carrying for a specified time and breaking currents under specified abnormal conditions, such as those of a short-circuit circuit breaker panel a switchgear panel complete with a fixed circuit breaker, switch-disconnector, earthing switch and protection and control equipment earthing switch as defined in AS 1852(441) fixed circuit breaker a circuit breaker which is not a withdrawable part of the panel assembly in which it is mounted metal enclosed switchgear and controlgear switchgear and controlgear assemblies with an external metal enclosure intended to be earthed and completely assembled, except for external connections State of NSW through Transport for NSW Page 8 of 59

9 non-withdrawable switchgear switchgear such as circuit breaker and switches, which are not a withdrawable part of the panel assembly in which they are mounted rated insulation level the combinations of the rated lightning impulse withstand voltage and the rated short duration power frequency withstand voltage specified in AS 2650 rated normal current for main circuits and switching devices, the rms value of the current that they are designed to carry continuously under the specified conditions of use and behaviour rated peak withstand current for main and earthing circuits, the peak current associated with the first major loop of the short-time withstand current that a mechanical switching device is designed to carry in the closed position under prescribed conditions of use and behaviour rated short-time withstand current for main and earthing circuits, the rms value of current that the switching device is designed to carry in the closed position during a specified short time under prescribed conditions of use and behaviour rated voltage the highest rms phase-to-phase voltage of the supply on which the switchgear is designed to operate switch a mechanical switching device that is capable of making, carrying and breaking currents under normal circuit conditions, which can include specified operating overload conditions, and also capable of carrying for a specified time, currents under specified abnormal circuit conditions such as those of a short-circuit switchboard two or more switchgear panels coupled together in various combinations switch-disconnector as defined in AS 1852(441) switchgear a general term that covers switching devices and their combination with associated control, measuring, indicating, alarm, protective and regulating equipment, also assemblies of such devices and equipment with associated interconnections, accessories, enclosures and supporting structures, intended, in principle, for use in connection with the generation, transmission, distribution and conversion of electric energy 5. Functional requirements of 11 kv indoor switchgear The 11 kv indoor switchgear shall consist of 11 kv busbar, fixed type circuit breakers, disconnectors and associated control and protection equipment. The 11 kv indoor switchgear shall provide for the following: connection of 11 kv feeders, bus tie cables, system transformer and distribution transformer circuits to the 11 kv busbar isolation and earthing of feeders, bus tie cables, system transformer and distribution transformer circuits State of NSW through Transport for NSW Page 9 of 59

10 protection and SCADA control for 11 kv feeders, system transformer and distribution transformer circuits and sections on the 11 kv busbar connection, protection and SCADA control of 11 kv harmonic filter or capacitor banks means to perform a dc test on the HV cables, without disturbing existing HV cable connections 6. Switchboard requirements Table 1 provides details of general requirements of a switchboard for 11 kv indoor switchgear. Table 1 - Switchboard general requirements Parameter Switchboard type Class Method of neutral earthing of the system Main device type Busbar insulation medium IP rating Possible extension to switchboard Designation Metal enclosed Indoor Effectively earthed and non-effectively earthed Non-withdrawable (stationary) Cast resin or air IP3X Both sides The switchboard shall be designed and manufactured in accordance with the standards stated in Table 2 and Table 3 along with the specific class and classification. Equipment Switchgear (common specifications) Metal enclosed switchgear Table 2 - Switchboard standards Standard AS AS Current transformer AS Voltage transformer AS Degrees of protection provided by enclosure (IP code) AS General AS 2067 Switchgear status indicators (definite indication of position) AS Appendix A State of NSW through Transport for NSW Page 10 of 59

11 Table 3 - Switchboard standards with class Designation Standard Class Service conditions AS Normal (except for temperature which shall comply with EP SP) Refer to note 1. Partition class AS PI Internal arc classification (IAC) AS AFLR Earthing switch AS E2 Disconnector AS M2 Switch AS M1, E3 Circuit breaker (except capacitor) Capacitor switching AS AS M2, E2, C1 M2, E2, C1 Note 1: Where the switchgear does not meet the temperature requirements of EP SP, then the applicable derating factors shall be provided. Table 4 details switchboard and specific equipment rating requirements. Parameter Table 4 Switchboard common ratings Number of phases 3 Rating Rated system voltage (Ur) Rated frequency (fr) Busbar Rated normal current Rated lightning impulse withstand voltage (Up) Common value Across the isolating distance Rated short-duration power-frequency withstand voltage (Ud) Common value Across the isolating distance Rated short time withstand current (Ik) (for main and earthing circuits) Rated peak withstand current (Ip) (for main and earthing circuits) Rated duration of short circuit (tk) (for main and earthing circuits) Internal arc classification (IAC) Arc test current Arc test current duration 12 kv (minimum) 50 Hz Single 630 A or 1250 A Refer note kv (peak) Refer note kv (peak) 28 kv (rms) 32 kv (rms) 16 ka (rms) 40 ka (peak) 1 sec AFLR 16 ka 1 sec State of NSW through Transport for NSW Page 11 of 59

12 Parameter Rated supply voltage of closing and opening devices and of auxiliary and control circuits (Ua) Refer to note 3. Partial discharge level of complete switchboard including all components Rating Option V dc Option 2 50 V dc < 50 pc Note 1: The required busbar rating for a particular location is specified on the approved proposed operating diagram provided at the time of order. Note 2: The rated lightning impulse withstand voltages mentioned are specific to Australian conditions and compatibility with the existing RailCorp network. These values are not from the current version of AS Note 3: Auxiliary voltage will be nominated at time of order of switchboard. These requirements are specified in T HR EL ST, Common Requirements for Electric Power Equipment Circuit breaker specific ratings Table 5 and Table 6 provide details of specific ratings for the circuit breakers. Table 5 ACCB Common Ratings -1 Parameter (common to all ACCBs) Rating Rated supply voltage of closing and opening devices and of auxiliary and control circuits (Ua) Refer to note 1. Rated normal current (Ir)2 - Bus Tie Refer to note 2. Feeder System transformer Distribution transformer Capacitor/harmonic filter Rated short circuit breaking current (Isc) Rated duration of short circuit (tk) Interrupter type Number of trip coils Number of close coils 1 Breaking time Command response time both ON and OFF Option V dc Option 2 50 V dc Option A Option A 400 A 630 A 200 A 400 A 16 ka 1 sec Vacuum 2 independently operated coils < 60 msec (max) < 25 msec (max) State of NSW through Transport for NSW Page 12 of 59

13 Parameter (common to all ACCBs) Rated operating sequence Cables connected Rating O - 0.3s-CO-3min-CO Bottom front or rear and optional top Table 6 - ACCB Common Ratings -2 Parameter (applicable to capacitor ACCB) Rated short-duration withstand voltage (across the isolating distance) (Ud) Rating 12 kv ac rms with 13.5 kv dc offset Note 1: Auxiliary voltage will be nominated at time of order of switchboard. These requirements are specified in T HR EL ST Common Requirements for Electric Power Equipment. Note 2: The current ratings for the switchboard are mentioned in the proposed electrical operating diagram, provided at the time of order. The requirements specified in this document ensure that the switchboards will fully integrate into the RailCorp network in terms of operability, maintainability and technical compatibility Busbar inter-panel partition The switchboard shall be designed to have a partition between panels in the busbar compartment. This is required to contain an electrical fault associated with the busbar to the panel where the fault originated Busbar earthing facility If any part of the busbar requires routine maintenance then busbar earthing facilities shall be provided Switchboard extension The switchboard and associated functional units shall be designed so that an extension to an existing switchboard is possible at both ends with minimal dismantling to the existing switchboard. State of NSW through Transport for NSW Page 13 of 59

14 7. Earthing bar Each switchgear panel shall include two copper earthing bars, rated for maximum fault levels and not less than 120 mm² cross section area to facilitate earthing. To assist with stray current mitigation measures from the dc traction system, it may be necessary to connect 11 kv cable screens to a separate cable screen earth bar on feeder panels only. This arrangement is to facilitate future installation of a transient earth clamp. The cable screen earth bar shall be connected to the switchboard earth bar via removable links and shall be isolated from similar bars in adjacent panels. The cable screen earth bar shall be insulated from the frame of the switchboard by insulated mounts that have been rated for maximum earth potential rise and tested for at least 11/ 3 kv for 1 minute. The cable screen earth bar shall provide for connection of the removable link, three HV cable screens and two cable connections holes for a transient earth clamp. The switchboard earth bar shall interconnect adjacent switchgear panels and provide the following: switchgear bonding two cable connections to the main substation earth grid a removable link per feeder panel for connection to the insulated earth screen earthing bar three cable screens for panels other than feeders requirements for circuit test facility Earth termination requirements are provided in T HR EL ST Transient earth clamp The transient clamp acts as a dc decoupler to provide dc isolation between earthing points that are still ac connected. Under an ac earth fault the clamp impedance momentarily changes state to a virtual short circuit, acting to provide a direct connection of HV cable screens to the switchboard earth bar. The transient earth clamp blocks the path to dc stray current that may otherwise flow via the cable screen. Transient earth clamps (if required) are installed on feeder panels only. State of NSW through Transport for NSW Page 14 of 59

15 8. Current transformers for circuit breaker The circuit breaker panels shall be provided with protection and metering current transformers in compliance with EP SP Protection System Requirements for the High Voltage Network. The typical quantity of CTs required is as follows: feeder panel: 4 (BZ, PW, OC, metering) transformer panel: 4 (BZ, Tx diff, OC, metering) bus-tie panel: 2 (BZ, bus-tie cable protection) Where an alternative busbar scheme (such as arc detection) is installed then a CT for BZ will not be required. Refer to Appendix B for further detail on typical CT ratio and class. Specific CT requirements for individual switchboards will be provided in the protection concept report for individual switchboards which is issued at the time of order Current transformer rating plate A rating plate shall be fitted to each current transformer. A second identical plate shall be fixed within the LV compartment in a position that facilitates ease of access to read the information. 9. Voltage transformers for switchboards A three-phase voltage transformer or three single phase voltage transformers in compliance with EP SP shall be provided for each switchboard. A voltage transformer (VT) is required for each busbar and incoming supply transformer ACCB. Specific VT requirements for individual switchboards will be provided in the approved protection concept report which is issued at the time of order. For the maintenance and commissioning of protection relays, voltage conditions that would occur during earth faults shall be simulated and the supplier shall explain how this is achieved. The VT alarm, protection relay VT supply alarm and phase failure relay shall be in accordance with EP SP. State of NSW through Transport for NSW Page 15 of 59

16 10. Low voltage cabinet for secondary equipment The secondary equipment including protective relays, controls, transducers, metering and other systems shall be housed in a low voltage cabinet located on the relevant circuit breaker panel. The location of the panel shall be suitable to enable the installation of all secondary wiring and accessibility for terminating wiring, programming of protection relays and general testing and commissioning activities. The low voltage panel shall be a lockable, closed, fully shrouded and arc resistant cabinet of IP3X standard suitable for accommodating digital protection relays, test blocks, panel meters and other secondary equipment for control and measurement. Where it is appropriate, equipment may be mounted on a torsion resistant panel door. The cabinet shall be fitted with a removable gland plate, cable ducting and terminals. The layout within the cabinet shall ensure for the following: adequate room is provided for the termination of multi-core control cables, dc auxiliary supply cables and other miscellaneous cables that are required for interfacing with equipment within the substation cable terminals shall be readily accessible to enable connection of test equipment associated with protection relay testing and commissioning cable ducting within the cabinet shall be located to allow for the installation of multi-core control cables In particular, adequate room between duct and cable entry points to allow for the bending radius of cables internal cabinet colour shall be white Refer to T HR EL ST for details on low voltage wiring, terminals and labelling requirements. Mechanical drive elements shall not be installed in the low voltage cabinet. 11. Circuit breakers Circuit breaker panels shall comprise of a fixed circuit breaker, switch-disconnector and earthing switch and shall have specific ratings as specified in Table 5 and Table Circuit breaker interrupters Interrupters shall be capable of at least 10,000 operations at rated current and at least 50 operations at rated short circuit breaking current. State of NSW through Transport for NSW Page 16 of 59

17 The contacts of the interrupter shall be held open by a positive fail-safe device independent of interrupter vacuum. The closing arrangement shall be designed to give a positive closing action while overcoming the contact hold open device Circuit breaker operating mechanisms The circuit breaker operating mechanism shall be an integral part of the circuit breaker. The circuit breaker busbar isolator and associated earth switch shall be actuated mechanically. Auxiliary switches shall provide indication of each switch position. Any part of the circuit breaker mechanism that requires routine inspection and maintenance shall not be enclosed in any gas tight compartment. All circuit breaker operating mechanisms shall be the stored energy type by means of energy stored in a motor-charged spring with manual and electrical release. Solenoid based mechanisms shall not be used. Magnetic actuator type operating mechanisms will be considered, provided that full technical details of the proposed arrangement are supplied. Typical details shall include principle of operation, auxiliary power supply requirements, details on manual operation and how the requirement for duplicate trip coils is addressed. The suitability of existing dc battery and associated dc circuit wiring shall require assessment in existing locations Circuit breaker closing mechanism The circuit breaker closing mechanism shall be electrically operated, trip-free. The circuit breaker mechanism shall provide lockout that prevents closing, as specified in Section of AS 1852 (441): All circuit breakers in the closed position shall be able to trip-close-trip before the spring needs to be charged again Circuit breaker operation and control The circuit breakers shall be arranged for operation by local control and by remote supervisory control. Refer to Section 24.3 for further details. The circuit breaker shall close without delay when the close command signal is applied. While this command signal is applied, the circuit breaker shall not make a second attempt to close if it fails to close on the first attempt. The circuit breaker shall open without delay when the open command signal is applied independently to any of the trip coils or to all trip coils simultaneously. A mechanical push-button or similar device for tripping the circuit breaker shall be provided. State of NSW through Transport for NSW Page 17 of 59

18 Continuously rated control equipment shall be provided to make the successful closing of the circuit breaker independent of the length of time that the control switch is held in the CLOSE position. This shall ensure that only one closing attempt can be made if the control switch is held in the CLOSE position Circuit breaker auxiliary contacts A minimum of two normally open and two normally closed auxiliary switches rated at 5 amperes in a 125 V dc inductive circuit or a 415 V ac circuit shall be provided. These auxiliary switches shall be provided in addition to those essential to the circuit breaker operation Circuit breaker indications The circuit breaker and switch panel shall have indications clearly visible from the front of the panel (that is, either on the circuit breaker or on the circuit breaker panel). The circuit breaker / switchgear panel shall have the following definite indications: circuit breaker open/close This shall be implemented by a mechanically operated indicator, indelibly marked, to show whether the circuit breaker is open or closed. The word OPEN shall be visible only if the circuit breaker is open and the word CLOSED shall be visible only if the circuit breaker is closed. If colours are used in addition, then the colour green shall indicate the open condition and the colour red shall indicate the closed condition. switch disconnector open/close (if applicable) This shall be implemented by a mechanically operated indicator. earth switch position This shall be implemented by a mechanically operated indicator. stored energy device charged/discharged non-resettable operation counter (nominally mechanical) However, alternatives shall be accepted after if approved by ASA. 12. Switchgear auxiliary equipment Each switchgear panel shall be fitted with a control panel with the following: a local CLOSE and OPEN switch or push-buttons coloured red and green respectively LOCAL REMOTE (SUPERVISORY) changeover switch electrically operated indicating lights of the LED type State of NSW through Transport for NSW Page 18 of 59

19 a set of terminals for the termination of auxiliary wiring All auxiliary wiring for remote closing and tripping circuits, incoming dc control supplies and all spare auxiliary switches shall be connected to these terminals This control panel shall have the capability for installing instruments to measure voltage, current and energy. The requirement for which instruments are to be installed will be specified at the time of order. The requirements of any instrumentation to be fitted are set out in Section 22. Each switchboard shall be fitted with a voltmeter and associated phase selection switch to indicate the bus voltage. Anti-condensation heaters where required shall be provided. 13. Interlocks Interlocking requirements regarding operating lever actuation shall be designed to interrogation interlock principles. Operating levers can only be inserted or actuating forces may only act on the components if this is permitted by the appropriate operating condition of the associated functional unit. Digital switchgear interlock units are not accepted. Actuating levers shall remove or insert in clearly defined positions 'Close' or 'Open'. The interlocking shall comply with the following conditions: interlock between busbar isolator and outgoing earthing switch interlock between busbar isolator and circuit breaker interlock between the switch disconnector and the outgoing earthing switch interlock between the cable compartment cover and the outgoing earthing switch For cable testing, specific equipment shall be provided to eliminate the outgoing earth. Interlocks shall ensure that the disconnector cannot be moved or operated unless the circuit breaker is open. Interlocks shall ensure that the circuit breaker cannot be closed unless the disconnector is fully in the 'closed', 'isolated' or 'earth' position. State of NSW through Transport for NSW Page 19 of 59

20 13.1. Mechanical interlocks Facilities provided for operational access to parts of the switchgear panel that contain live components shall be mechanically interlocked. Access to such parts is not possible unless all live parts have been rendered safe, either by a visibly applied earth connection or by positively disconnected and screened from the remaining live parts. Mechanical interlocks shall be provided to ensure positive and substantial protection against malfunction. Mechanical interlocks shall be designed and constructed to ensure dependable fail-safe operation. Positive mechanical interlocking shall be provided to prevent inadvertent switching from the ON position to the EARTH position without a definite stop in the OFF position, or from the EARTH position to the ON position without a definite stop in the OFF position. Access to the test terminals shall only be possible when the associated earth switch is in the EARTH position. When the circuit test facility is in use, the disconnection shall not be able to close. The operator shall directly observe the making of the contacts in the circuit EARTH position. If the earthing of a circuit is not visible, the corresponding indication shall be directly coupled to the earthing mechanism to ensure fail-safe indication. If the switchgear panel is designed in a way that the circuit to be earthed is earthed through the main contacts of the circuit breaker, then the circuit breaker shall be interlocked. This is done so that it cannot be tripped by the protection relays or SCADA control while the circuit is earthed. An analysis shall be provided detailing the integrity of the interlocking system. The analysis shall include all possible failure modes and the controls employed to prevent an unsafe operation. A table shall be provided of all possible and inhibited states the switchgear may occupy. 14. Circuit breaker and switch panel HV cable compartment Each circuit breaker and switch panel shall be equipped with an 11 kv cable compartment interlocked with the ACCB for connection of the 11 kv cables. Due to the variety in physical configurations of existing substations in the RailCorp network there is the requirement for two separate options for access to the high voltage cable terminations. State of NSW through Transport for NSW Page 20 of 59

21 The two options are as follows: access to the high voltage cables from the front access to the high voltage cables from the rear The cable bushings shall be arranged side by side facing the front of the switchboard. Bushings shall be positioned to suit connection of three core cables with tails of equal length to facilitate phase transposition without re-terminating the cable. All cable compartments shall be adequately sealed to prevent entry of vermin and dust in compliance with IP3X. Each circuit breaker and switch panel shall provide the means to perform a dc cable test on the HV cables, without disturbing existing HV cable connections Fully insulated cable terminations All cable termination compartments shall be suitable for dead-break, separable, fully insulated and shielded system for connection of HV cables. The separable, insulated, shielded connection system shall comply with AS 2629 (or equivalent IEC, EN) and relevant ratings specified in Section Non-fully insulated cable terminations All cable termination compartments shall be suitable for air insulated termination. compartment shall have at a minimum the clearances specified in AS The To provide protection against flashover due to rodents or high humidity, removable and re-installable elastomeric insulating boots (or approved alternative) shall be fitted Cable compartment size The cable compartment shall accept single, three-conductor belted or three core dry type cables including separately lead sheathed paper or XLPE insulated cables of up to 240 mm² in size. Where three phase cables are to be terminated the dimension of the cable compartment shall enable adequate clearances for crossing of cable cores. All cable compartments shall be of dimensions such that full standard cable withstand power frequency tests as specified in AS can be conducted after cable termination is complete. The minimum of one cable shall be achieved without sacrificing space for surge arrester equipment if required. State of NSW through Transport for NSW Page 21 of 59

22 Where the cable compartment design results in a length of unsupported cable greater than the length recommended by cable manufacturers, then a method of cable support is required within the compartment. The standard cable compartment requirement is for bottom entry of cables. A limited requirement for top entry of cables applies. Details of the cable connections options shall be nominated in the technical schedule provided in Appendix F. 15. Surge arresters for 11 kv switchboards Surge arresters are not normally required in 11 kv switchboards installed on the RailCorp network. This is valid for the standard connection arrangement where the feeder consists of cable to a pole and the 11 kv surge arrester is located on that pole as part of the standard UGOH (underground to overhead - aerial) arrangement. 16. Circuit earthing facilities All panels shall be equipped with circuit earthing switches manufactured and tested in accordance with the relevant standard specified in Section 6. Earth switches shall be the integral type. The earthing of the circuit cables shall be effected via a separately designed make-proof earthing switch. The earthing shall be located directly on the circuit cable and designed without interposing further switching devices. The earthing system shall be designed and tested for making a live circuit with a prospective peak fault current in accordance with the switchboard requirements specified in Table 1 in Section 6. Each circuit-earthing switch shall be mechanically interlocked with the corresponding circuit breaker or switch. Refer to Section 13 for interlocking requirements. The earthing switch shall be fully rated for fault making to the requirements specified in Section 6. Each switch shall be provided with a fail safe indicating device to positively indicate whether it is in the OPEN OR EARTH position and the words 'OPEN' and 'EARTH' shall be used for the respective indication of these positions. The equipment shall be configured to allow the position of the earth switch contacts in the EARTH position to observe directly. Appropriate long life, maintenance free illumination shall be provided. The light source shall be replaced without the need for isolating HV equipment or significant disassembly of the switchgear. State of NSW through Transport for NSW Page 22 of 59

23 17. Voltage detecting system A voltage detection system (VDS) in accordance with IEC with integrated display to detect the following shall be provided for all HV circuits: dead state operating voltage phase balance A voltage presence indicating system (VPIS) in accordance with IEC is acceptable if a VDS system is not available. Suitable capacitive voltage dividers fitted in the cable connection area is acceptable. Appropriate connections shall be provided to enable phase comparison in normal operating conditions. An optional feature is for remote indication of 11 kv cable voltage status and interlocking with the earth switch. Interlocking shall inhibit the earthing of live circuit conductors. 18. Circuit test facilities Each circuit breaker panel shall incorporate an integral type circuit test facility. All test facilities shall be suitable for the application of dc test voltages associated with the after-installation testing of power cables. They shall be rated for the same system voltage as the switchgear. The test facility shall facilitate the connection of test equipment with the circuit earthed and then allow the earths to be removed with the test equipment still connected. A hand applied earthing set shall be connected to the circuit side of each circuit breaker panel for use in conjunction with test equipment. The earth connection shall be applied or removed independent of the application or removal of the test equipment connection. External removable accessories shall be used to achieve this function. 19. Padlocking Facilities shall be provided to padlock the following: disconnector in the closed, open and earth positions circuit breaker in the open positions and the closed position while the disconnector is in the earthed position circuit test facility, if applicable (see Section 12) State of NSW through Transport for NSW Page 23 of 59

24 All padlocking facilities shall be suitable for padlocks with a 6 mm shank diameter. 20. Floor fixing and penetration details All equipment required for the fixing of the switchgear to the floor shall be provided, inclusive of the switchboard. Drawings detailing the required floor levels, penetrations and any other civil requirements for the installation of the switchboard shall be provided. 21. Segregation of LV wiring in HV compartment Any low voltage wiring within HV compartments shall be segregated, mechanically protected and installed to provide adequate protection from a HV fault damaging the LV circuits. Compliance with this requirement is detailed in the technical schedule provided in Appendix F. 22. Instruments, transducers and metering All instruments, transducers and metering equipment that are required to be fitted shall comply with this section and the relevant requirements in T HR EL ST. All indicating instruments shall be flush-mounted industrial type instruments that comply with the requirements of the following IEC standards: IEC , IEC , IEC , IEC , IEC and IEC The instruments shall be clearly visible and easily readable from a standing position in front of the panel. Analogue instruments shall have a scale length of at least 90 mm. All instruments on a switchboard shall be scaled with the same type of characters of the same size. The instruments shall be 96 mm x 96 mm in size, with black scales on a white background. All current-operated instruments shall be protected against continuous over current up to 120% of nominal value and high current surges up to the fault rating of the circuit breaker Current transducers Each feeder or transformer panel shall have one current transducer connected to B of a metering CT. The output of the current transducer shall be used to drive the ammeter and then be connected to the SCADA RTU for remote indication. The approved current transducers are specified in EP SP. State of NSW through Transport for NSW Page 24 of 59

25 22.2. Voltage transducers A voltage transducer shall be connected to each VT and connected to the SCADA RTU for remote indication. The approved voltage transducers are specified in EP SP Ammeters Ammeters shall have two scales that are essentially linear. The main scale shall allow for 120% of the primary current rating of the current transformer and the second scale shall be equivalent to the main scale divided by 5, to allow reading of lower currents. A pushbutton fitted to the front of the ammeter shall activate the minor scale. The current transformer ratio shall be clearly marked on the face of the ammeter. The accuracy of ammeters shall be 3% or better and shall be stated in the technical schedule provided in Appendix F Voltmeters Voltmeter shall have analogue indication with scales that have an indicating range of 80% to 120% of the nominal system voltages. Where voltmeters that have a nominal range from 0% to 120% are required, this will be specified at the time of order. The nominal voltage shall be marked in red on the scale Watthour meter kwh meters shall be three phase, with pulse output. The pulse output rate shall be 10 per kwh. Where required for revenue metering the kwh meter shall be connected to a metering CT of suitable rating and accuracy class. 23. Busbar and circuit protection Protection schemes shall be in accordance with EP SP. The specific protection schemes for a switchboard are specified in the protection concept which is issued at time of switchboard procurement. State of NSW through Transport for NSW Page 25 of 59

26 23.1. High impedance bus zone protection When a high impedance unit protection scheme is used, the associated components such as protection relay, MTM, test block are to be located within one of the end panels that will be nominated at time of order Internal arc fault detection scheme An alternative to the traditional high impedance scheme is subject to an approval by the ASA. If approved, this system is the preferred scheme. If offered as an alternative to the high impedance scheme the complete system description shall be provided during tender for assessment Feeder protection The protection for feeders consists of overcurrent and earth fault protection and line differential protection at strategic locations shall be required. The protection scheme shall be specified in the protection concept which is required at time of switchboard procurement System transformer protection The relays and associated equipment for the protection of system transformers are normally located with the protection and control equipment for the higher voltage winding. The 11 kv circuit breaker panel for a system transformer shall be configured for connection to the required protection equipment located elsewhere. The neutral leakage relay is normally located on the 11 kv panel Distribution transformer protection The protection functions required for distribution transformers shall be implemented within the 11 kv panel. Inputs from gas relays or gas over pressure voltage free contacts, low voltage equipment voltage free contacts and high temperature RTDs inputs shall form part of the tripping circuit of the circuit breaker. EP SP defines two schemes for distribution transformers. Primary protection is a transformer differential scheme, with overcurrent and earth fault protection as backup. Primary protection is overcurrent and earth fault protection with no backup. State of NSW through Transport for NSW Page 26 of 59

27 Where a differential scheme is required, terminals shall be provided for the connection of current transformers on the secondary side of the transformer and the protection equipment shall provide a trip output to trip the low voltage circuit breaker. 24. SCADA indications and controls The SCADA alarms from equipment are implemented by a combination of hard wiring and using the serial link on the electronic protection relays. The serial communication port on all electronic protection relays within a switchboard shall be connected together and wired to a terminal strip for connection to the SCADA RTU. Refer to EP SP for further SCADA alarm requirements Binary indication and ACCB control Certain information is critical for system operation and shall be independent on the protection relay or communication link to the RTU. Table 7 details the SCADA alarms and control that are required to be hard wired to the RTU. Table 7 - SCADA alarms and control Hard wired I/O Point Description. Circuit breaker (Open, Closed) Isolator position (Open, Closed) Earthing switch position (Open, Closed) Circuit breaker alarms (example: spring charge motor) Trip circuit supervision alarms Gas/vacuum monitoring alarms Protection relay watchdog alarms Bus zone trip ACCB Open Control ACCB Close Control Hard Wired Analogue indication The following analogue indications shall be provided to SCADA: circuit current (B phase) for each circuit breaker bus voltage (at least 1 phase ) for each switchboard State of NSW through Transport for NSW Page 27 of 59

28 Current transducers shall be provided to allow monitoring of primary circuit currents by SCADA. Transducers shall be connected to a dedicated metering CT on B phase. Refer to Section 22.1 and Section Controls The SCADA RTU provides voltage free contacts which close for a maximum of 2 seconds for the following control functions: circuit breaker Open (trip) circuit breaker Close The SCADA RTU voltage free contacts have a maximum current rating of 1 A. Interposing relays are to be provided for the SCADA initiated ACCB close and ACCB trip. Refer to Section for additional details. The disconnector and earthing switch are manually operated and do not require SCADA control. State of NSW through Transport for NSW Page 28 of 59

29 Appendix A - Switchboard configurations Appendix A specifies the configuration requirements for the switchboards and switchgear. A.1 Switchboard configurations Most of the switchboard configurations applicable to the RailCorp network are detailed in Appendix B. Each switchboard shall be designed and manufactured specifically for each site within the following constraints: the switchgear functional units shall be assembled into switchboard panels each switchboard shall include a bus bar voltage transformer (VT) standard circuit breaker functions are feeder, system transformer, distribution transformer, tie (bus) and bus coupler switchboards with single bus tie panels shall have the bus tie at one end of the switchboard Switchboards with two bus tie panels shall have the bus tie panels at opposite ends of the switchboard. The position of each functional unit will be specified at time of order in accordance with the approved for purchase operating diagram. Where required for 11 kv network reasons, more than one switchboard may be required in a substation. Such switchboards would normally be physically separated to reduce the risk of one event damaging both. Switchboards are interconnected by a tie cable through a bus tie circuit breaker at each end of the tie cable. This is the preferred bus sectioning arrangement at a substation location. The cable tie requires a high impedance unit protection scheme. Where space or building constraints (example, cable ducts) exists, a bus coupling circuit breaker arrangement may be required for the busbar sectionalising function. However, this is not a preferred configuration. A.1.1 Switchboard panel configuration codes Table 8 provides the switchboard panel configuration and their codes. Table 8 - Switchboard panel configuration codes Switchboard panel configuration Bus tie cable circuit breaker: switchgear code Feeder circuit breaker: switchgear code System transformer (incomer) circuit breaker: switchgear code Codes T F ST State of NSW through Transport for NSW Page 29 of 59

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR 22 kv Version: 2 Issued: 19 th December 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical

More information

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

Specification Voltage Limiting Device

Specification Voltage Limiting Device Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering,

More information

TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY

TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY Engineering Specification Electrical TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY Version: 2 Issued: October 2017 Owner: Chief Engineer Approved By: Phil Ellingworth Chief Engineer PRINTOUT

More information

Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly

Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly Specification Electrical Networks L1-CHE-SPE-128 Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly Version: 1 Issued: February 2016 Owner: Head of Engineering - Electrical Approved

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A AUTOMATION MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A GRID Note: The technical manual for this device gives instructions for its installation, commissioning,

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

GHA. Gas-Insulated Circuit-Breaker Switchgear Unit up to 40.5 kv. Gas-Insulated Switchgear. Customer Benefits

GHA. Gas-Insulated Circuit-Breaker Switchgear Unit up to 40.5 kv. Gas-Insulated Switchgear. Customer Benefits 01 Gas-Insulated Circuit-Breaker Switchgear Unit up to 40.5 kv PM103255 Energy supply security is our permanent challenge. At Schneider Electric, we are constantly developing and improving our products

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety MEDIUM VOLTAGE PRODUCTS UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety 2 UNISEC AIR-INSULATED MEDIUM VOLTAGE SECONDARY DISTRIBUTION SWITCHGEAR Operator

More information

Air-insulated medium-voltage secondary distribution switchgear

Air-insulated medium-voltage secondary distribution switchgear DISTRIBUTION SOLUTIONS Air-insulated medium-voltage secondary distribution switchgear Compact size Complete solution Factory tested Air-insulated medium-voltage secondary distribution switchgear The ABB

More information

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation Location(s) where activities are performed under accreditation Head Office Utrechtseweg 310, Building no. R11 6812 AR Arnhem The Netherlands Location Abbreviation/ location code Utrechtseweg 310, Building

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

Medium Voltage Metal-Enclosed Harmonic Filter Systems

Medium Voltage Metal-Enclosed Harmonic Filter Systems 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Harmonic Filter Systems General NEPSI s armorvar, medium voltage metal-enclosed

More information

power pazifik MV Switchgear Secondary Distribution Networks Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kv

power pazifik MV Switchgear Secondary Distribution Networks Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kv Manufactured by: MV Switchgear Secondary Distribution Networks Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kv BO-CGM.3/3 SMART RMU Switchgear in Metro Manila Protection and safety for

More information

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP)

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP) Discipline Engineering Standard - NSW Category Signalling Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units Reference Number SPS 30 - (RIC Standard: SC 09 10 07 00 SP)

More information

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

Medium Voltage Distribution Catalogue GenieEvo range. Air Insulated MV Switchgear kv

Medium Voltage Distribution Catalogue GenieEvo range. Air Insulated MV Switchgear kv Medium Voltage Distribution Catalogue 2015 GenieEvo range Air Insulated MV Switchgear 3.3-13.8 kv Medium Voltage Distribution GenieEvo Your requirements Peace of mind Energy availability Safety GenieEvo

More information

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with

More information

Innovation on Medium Voltage Switchgear

Innovation on Medium Voltage Switchgear Bruno Rivas, Guarulhos - Brazil, April 2015 Jornadas Técnicas de ABB en Chile Innovation on Medium Voltage Switchgear May 13, 2015 Slide 1 Application 13. Mai 2015 Slide 2 PPMV Brazil Factory Unigear Insourcing

More information

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 BY H S W Karunaratne Assistant Director - Engineering Sri Lanka Standards Institution. 1 DEFINITIONS Ac module:

More information

Medium Voltage Metal-Enclosed Power Capacitor Banks

Medium Voltage Metal-Enclosed Power Capacitor Banks 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Power Capacitor Banks General Northeast Power System s (NEPSI's) medium

More information

SECTION SWITCHGEAR

SECTION SWITCHGEAR SECTION 26 23 13 SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title s Reference Number PCP 07 - (RIC Standard: EP 99 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 TOSHIBA Corporation 2004 All Rights Reserved. ( Ver. 1.6 ) Safety Precautions Before using this product, please read this chapter carefully. This

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards)

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards) ////// SUBSTATIONS DC Switchgear Range Type MBS (IEEE/ANSI standards) GENERAL INFORMATION With a complete range of equipment and a leading expertise in DC traction power substations, Sécheron SA is a world

More information

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS Engineering Specification Electrical Networks MESP 081000-01 TECHNICAL SPECIFICATION FOR SCADA CABLING IN Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

Switch Disconnectors, Main and EMERGENCY-STOP Switches

Switch Disconnectors, Main and EMERGENCY-STOP Switches General data Overview Siemens G 2010 1 2 3 NSE0_01931b 4 5 6 7 1 uxiliary switch (3SB for 3K; 3KX for 3KE) 2 IP20 terminal cover (Operator side) 3 3K switch disconnector 4 rcing contacts (only for 3KE)

More information

IMP/ 001 / 014 Policy for the Protection of Distribution Networks

IMP/ 001 / 014 Policy for the Protection of Distribution Networks Version:- 1.1 Date of Issue:- July 2016 Page 1 of 39 IMP/ 001 / 014 Policy for the Protection of Distribution Networks 1. Purpose The purpose of this document is to detail the network protection philosophy

More information

Central Power Research Institute, Medipally PO, Uppal, Hyderabad, Telangana. Discipline Electrical Testing Issue Date

Central Power Research Institute, Medipally PO, Uppal, Hyderabad, Telangana. Discipline Electrical Testing Issue Date Last Amended on 31.07.2015 Page 1 of 11 I. SWITCHGEAR EQUIPMENT 1. High Voltage switchgear & control gear and AB switches Ratings upto 1200 kv system Switching Impulse Voltage (Dry & Wet) Power Frequency

More information

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment NTSA has developed the ultimate solution for protecting

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-0150 LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES LPN This standard provides guidelines for the development of the 33kV distribution

More information

KMP A3. Air Insulated Medium Voltage Switchgear Powerful. Safe. Highly Available

KMP A3. Air Insulated Medium Voltage Switchgear Powerful. Safe. Highly Available KMP A3 Air Insulated Medium Voltage Switchgear Powerful. Safe. Highly Available High power switchgear systems For primary applications The name MediPower represents powerful medium voltage energy distribution

More information

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9 PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

REYROLLE 2RMLG. Operating Recommendations

REYROLLE 2RMLG. Operating Recommendations 2RMLG Operating Recommendations SAFETY The commissioning and maintenance of protection equipment should only be carried out by skilled personnel trained in protective relay operation and capable of observing

More information

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power 1. Abstract Dinesh Mithanthaya Design Manager, Horizon Power Higher capacity substation power transformers ( 5MVA),are

More information

MV Network Switchgear, Protection and Control

MV Network Switchgear, Protection and Control MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control

More information

2 Principle of lightning protection

2 Principle of lightning protection 2 Principle of lightning protection The system for protecting a building against the effects of lightning must include: bprotection of structures against direct lightning strokes; bprotection of electrical

More information

Elastimold Molded Vacuum Recloser - MVR

Elastimold Molded Vacuum Recloser - MVR Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical

More information

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Type MVTT 14 and MVTT 15: Static Digital Time delay relays Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction

More information

SPM Series. Plug-in Surge Protection

SPM Series. Plug-in Surge Protection SPM Series Plug-in Surge Protection The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects

More information

Power Transmission Division Link between power generation and distribution

Power Transmission Division Link between power generation and distribution Power Transmission Division Link between power generation and distribution Seite 4 High Voltage Substations Schemes, Devices and Types of AIS Installation Content Link between power generation and distribution

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

MIC-2 MKII, Multi-instrument DATA SHEET

MIC-2 MKII, Multi-instrument DATA SHEET MIC-2 MKII, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)

More information

MESP MODULAR SUBSTATION USER REQUIREMENTS

MESP MODULAR SUBSTATION USER REQUIREMENTS Engineering Specification Electrical Networks MODULAR SUBSTATION USER Version: 2 Issued: November 2015 Owner: Head of Engineering/Electrical Approved By: Head of Engineering/Electrical PRINTOUT MAY NOT

More information

PRODUCT. Battery Charger

PRODUCT. Battery Charger PRODUCT Battery Charger Model : BC 9080 Battery Charger The ICD Battery Charger is designed to supply required DC Voltage and Current to the connected load and recharge the Battery on boost charging over

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Ancillary Electrical Equipment for Use in Conjunction with Switchgear and Protection/Control Panels NOTE: The current version of this document is

More information

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS GB Contents Page 1 Introduction 4 2 Safety 5 3 Use 6 4 Checking on Delivered Equipment 6 5 General Specification and Dimensions 7 6 Positioning 10 7 Operating

More information

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects of transient over voltages caused by

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV) 1.1 DESCRIPTIONS OF WORK A. The Bidder shall furnish and install the equipment as specified herein and as shown on the contract drawings. B. The switchgear and circuit breakers shall be manufactured by

More information

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Revision 0-C-041918 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document

More information

ABB Digital medium-voltage switchgear

ABB Digital medium-voltage switchgear NAMIBIA AMEU/AEDU MARCH 2018 ABB Digital medium-voltage switchgear Barry Addinall UniGear Digital Contents 1. Digital switchgear 2. Complexity of Distribution networks 3. New technologies using digital

More information

SPM Series Plug-in Surge Protection

SPM Series Plug-in Surge Protection SPM Series Plug-in Surge Protection The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany Lightning and Surge Protection of Photovoltaic Installations 1 Lightning and Surge Protection for PV Installations 2 Safeguard from Risks Ups, that was the insurance policy of my house!! 3 Why Lightning

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5 Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System

More information

UEMC 41 Motor Operating Device

UEMC 41 Motor Operating Device Installation and operating instructions UEMC Motor Operating Device Your safety first always! All legally recognized standards, the connection conditions of the local electrical utility and the applicable

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus Non-conventional instrument transformers Advanced GIS substations with IEC 61850-9-2LE process bus Content Towards the digital GIS substations Optimized substation design NCIT for gas-insulated switchgears

More information

Merlin Gerin GenieEvo metalclad MV switchgear kV Selection guide

Merlin Gerin GenieEvo metalclad MV switchgear kV Selection guide Merlin Gerin GenieEvo metalclad MV switchgear 3.3-13.8kV Selection guide GenieEvo selection guide Contents Section one Product overview 5 Section two Introduction 15 Section three Network functions Summary

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

Sivacon S4. Low-Voltage Switchboards. siemens.co.uk/tip

Sivacon S4. Low-Voltage Switchboards. siemens.co.uk/tip Product Managers and dedicated Business Development Managers are available to assist with all your enquiries. Technical presentations (Forms of Separation, Discrimination etc) available Site response capability

More information

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays... .1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....

More information

Network Configuration Document Selection for New Substations Framework

Network Configuration Document Selection for New Substations Framework Network Configuration Document Selection for New Substations Current version: 20/06/2018 EXTERNAL USE Page 1 of 14 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References...

More information

Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

Type 8DA and 8DB up to 40.5 kv, Gas-Insulated Catalog H 35.11 Edition September 2017 Fixed-Mounted d Circuit-Breaker it Switchgear Type 8D and 8DB up to 40.5 kv, Gas-Insulated Medium-Voltage Switchgear siemens.com/medium-voltage-switchgear pplication

More information

MMLG 01, 02, 03, 04 MMLB01

MMLG 01, 02, 03, 04 MMLB01 MMLG 01, 02, 03, 04 MMLB01 Technical Data Test Blocks and Test Plugs Publication Reference: MMLG_MMLB/EN/TD/B - ALSTOM 2015. All rights reserved. Information contained in this document is indicative only.

More information

Overvoltage Protection Devices

Overvoltage Protection Devices Siemens AG 2010 Overvoltage Protection Devices /2 Introduction /3 Lightning Arresters, Type 1 /5 Combination Surge Arresters, Type 1 and Type 2 /7 Surge Arresters, Type 2 /11 Surge Arresters, Type 3 /12

More information

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

AIR COOLED MODULAR RECTIFIER

AIR COOLED MODULAR RECTIFIER CONTROLLED POWER COMPANY SPECIFICATIONS AIR COOLED MODULAR RECTIFIER Spc1800a1 5JAN1999 SPECIFICATION S-1800-A MODULAR (REMOVABLE AND NON-REMOVABLE MODULES) AIR COOLED RECTIFIER Standard output power range:

More information

Application Techniques CENTERLINE 2100 Motor Control Centers

Application Techniques CENTERLINE 2100 Motor Control Centers POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product

More information

ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS

ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS Presentation by: RANA NASIR ALI General Manager, Power Plants Projects, at PITCO November 02, 2017 ELECTRICAL PLANT CONCEPT The electrical equipment, depending

More information

NU-LEC. Loop Automation. Reclosers & Sectionalizers

NU-LEC. Loop Automation. Reclosers & Sectionalizers NU-LEC Loop Automation Reclosers & Sectionalizers 1 NU-LEC LLC NU-LEC LLC is a wholly unit of NU-LEC Industries, Pty, Ltd. Sales and service center for United States, Canada, and the Caribbean. Warehouse

More information

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-300

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-300 INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-300 COPYRIGHT 1988 American Mine Research, Inc Manual Part Number 160-0094 Original: 07-19-88 Revised: 03-28-90 NOT TO BE CHANGED WITHOUT MSHA

More information

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

ENhanced TEChnology.  Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver. ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Ver. 081226 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser

More information

Description. Installation. Power supply

Description. Installation. Power supply Air circuit breakers Special versions Series MEGT07 0V/500V/DC 50 up to 5000 A The air circuit breakers MEGT07 are suitable for use as disconnecting switch in DC distributions up to a rated voltage of

More information

SIEBREAK-VCB 5-15 kv metal-enclosed interrupter switchgear usa.siemens.com/siebreak

SIEBREAK-VCB 5-15 kv metal-enclosed interrupter switchgear usa.siemens.com/siebreak Reducing arc-flash energy SBRK-VCB 5-15 kv metal-enclosed interrupter switchgear usa.siemens.com/siebreak SBRK-VCB with ORS Brochure Reducing the arc-flash incident energy in low-voltage substation applications

More information

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum) Section 16306 50/60-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER Index PART 1 GENERAL PART 2 PRODUCTS 1.1 References 2.1 Frequency Converters 1.2 Factory Tests 2.2 Conduit and Fittings 1.3 Submittals 2.3

More information

White Paper. UL Standards for Power Control System Equipment

White Paper. UL Standards for Power Control System Equipment White Paper UL Standards for Power Control System Equipment UL Standards for Power Control System Equipment An Introduction to UL 891 and UL 1558 Commercially available Power Controls Systems (PCS) can

More information

4. CIRCUIT BREAKERS. Functional Emergency Switching

4. CIRCUIT BREAKERS. Functional Emergency Switching 4. CIRCUIT BREAKERS The circuit breaker/disconnector fulfils all of the basic switchgear functions, while, by means of accessories, numerous other possibilities exist. As shown in table H2-19 the circuit

More information

7XG225-3RMLG Test Block System Answers for infrastructure & cities.

7XG225-3RMLG Test Block System Answers for infrastructure & cities. Reyrolle Protection Devices 7XG5-3RMLG Test Block System Answers for infrastructure & cities. Siemens Protection Devices Limited 7XG5-3RMLG Test Block System Application Test blocks enable test technicians

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

Arc protection relay. Features Three-phase overcurrent function. Application

Arc protection relay. Features Three-phase overcurrent function. Application Arc protection relay REA 10_ Page 1 Issued: May 1999 Status: New Data subject to change without notice Features Three-phase overcurrent function Loop-type or radial sensor fibre for arc detection Two high-speed

More information

MEDIUM VOLTAGE RING MAIN UNIT

MEDIUM VOLTAGE RING MAIN UNIT MEDIUM VOLTAGE RING MAIN UNIT SFA-RM up to www.alfanar.com Contents 1 - Introduction 4 Introduction to SFA-RM 4 a - SFA - RM Solution 4 b - Quality Management 4 c - Quality Checks and Tests 4 d - Environmental

More information

LC35SE-CC LOOP

LC35SE-CC LOOP 35 W SELV Constant current LED driver Product code: 5748 35 W 220 240 V 0/ 50 60 Hz SELV output protection for safety and flexibility in luminaires Very low current ripple, complying with IEEE 1789 standard

More information

LC51SE-CC LOOP

LC51SE-CC LOOP 51 W SELV Constant current LED driver Product code: 5740 51 W 220 240 V 0/ 50 60 Hz SELV output protection for safety and flexibility in luminaires Very low current ripple, complying with IEEE 1789 standard

More information

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B GE Energy Connections Grid Solutions MMLZ Technical Data Sheet Auxiliary Modules Publication reference: MMLZ/EN TDS/B MMLZ Technical Data Sheet FEATURES Wide choice of application specific models Fully

More information

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation: DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated

More information

PDI Modular Compact Remote Power Panel

PDI Modular Compact Remote Power Panel Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications

More information