MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR

Size: px
Start display at page:

Download "MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR"

Transcription

1 Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR 22 kv Version: 2 Issued: 19 th December 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION

2 Approval Amendment Record Approval Date Version Description 17/12/ Initial issue under MTM. 19/12/ Additional VT requirements. Appendix B Minor additions. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 2 of 24

3 Table of Contents 1. Purpose Scope Abbreviations Definitions References & Legislation Background Configuration Operating Conditions Service Conditions Electrical Conditions Ratings General Requirements Modules Enclosure Control Voltage Labelling Anti-condensation Heaters SCADA Interface Prohibited Materials Busbar Requirements Busbar Voltage Transformer and Bus Alive Indication Busbar Earthing Switch Power Cable Termination Requirements Terminal Requirements Line Earth Switch Requirements Line Alive and Bus Alive Detection System Requirements Circuit Breaker Module Requirements Circuit Breaker Requirements Circuit Breaker Operation Disconnector Requirements (Fixed Circuit Breaker only) Circuit Breaker Test Position (Withdrawable Circuit Breaker only) Power Terminal Compartment Additional Requirements Control Compartment Requirements Feeder Circuit Breaker Control System Requirements Rectifier Unit Circuit Breaker Control System Requirements Protection Scheme Requirements PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 3 of 24

4 13.10 Control Wiring Requirements Testing Type Test Routine Tests Documentation and Support Documentation Requirements Design Drawings Drawing Format Technical Maintenance Plan Maintenance Manual Installation Instructions Manual Operating Instructions Manual Tools & Equipment Information to be Supplied in Scope Document Appendix A Design Management Requirements Appendix B Information to be Supplied by Tenderers PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 4 of 24

5 1. Purpose This document is the MTM technical specification for Modular, Single and Multi Busbar, Metal Enclosed, Partitioned, 22kV Switchgear and Controlgear with fixed or withdrawable Switching Devices. 2. Scope This document applies to the supply of the Switchgear and Controlgear for use in a new Traction Substation, and for upgrades and renewals of existing Traction Substations, on the MTM Traction Power Supply System, where the installation requires only a single busbar. 3. Abbreviations MTM - Metro Trains Melbourne SCADA - Supervisory Control and Data Acquisition 4. Definitions For all technical terms refer to AS Shall Should Is used as the descriptive word to express a requirement that is mandatory to achieve conformance to the standard. Is used as the descriptive word to express a requirement that is recommended in order to achieve compliance to the standard. Should can also be used if a requirement is a design goal but not a mandatory requirement. 5. References & Legislation The Switchgear and Controlgear shall comply with the following Australian Standards and Acts. Standard/Act Title AS 2650 AS 2791 AS AS AS/NZS IEC IEC High Voltage A.C. Switchgear and Controlgear Common Requirements High-Voltage Switchgear And Controlgear - Use And Handling Of Sulphur Hexafluoride (SF6) In High Voltage Switchgear And Controlgear Instrument transformers - Current transformers Instrument transformers- Inductive voltage transformers Insulated bushings for alternating voltage above 1000V Measuring relays and protection equipment Specification of technical grade sulphur hexafluoride (SF6) for use in electrical equipment PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 5 of 24

6 Standard/Act IEC AS AS AS AS AS AS AS Title Basic and safety principles for man-machine interface, marking and identification Identification of equipment terminals, conductor terminations and conductors Degrees of protection provided by enclosures (IP Code) High-voltage Switchgear and Controlgear - Common specifications High-voltage Switchgear and Controlgear High-voltage alternating-current circuit breakers High-voltage Switchgear and Controlgear AC Metal enclosed switchgear and controlgear for rated voltages above 1kV and up to 52kV High-voltage Switchgear and Controlgear AC Insulation-enclosed switchgear and controlgear for rated voltages above 1kV and up to 52kV High-voltage Switchgear and Controlgear Dimensional standardization of terminals High-voltage Switchgear and Controlgear Guide for asymmetrical short-circuit breaker test duty Rail Safety Act 2006 (Victoria) Occupational Health and Safety Act 2004 (Victoria) Victorian Occupational Health and Safety Regulation 2007 (Victoria) Electricity Safety Act 1998 (Victoria) Electricity Safety (Installations) Regulations 2009 (Victoria) If the equipment offered does not comply with Australian Standards, but complies with similar International Standards (e.g. IEC), then detailed descriptions shall be given of the differences between the apparatus offered and the requirements of the specified Australian Standard. 6. Background The Melbourne Traction Substations primarily convert electricity from High Voltage AC to 1500 Volt DC power for the operation of the Electric Train System in Melbourne. There are two types of 22 kv Switchgear and Controlgear specifications applicable to new MTM Substations. The choice is dependent on the Substation application. The two Switchgear applications are: 1. A Single Busbar 22 kv Switchgear with fixed Circuit Breaker protected Supply Feeders and Rectifier Unit, and Fuse protected secondary Transformers. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 6 of 24

7 2. A multiple Busbar 22 kv Switchgear with withdrawable Circuit Breakers. This is for a Substation that requires greater operational flexibility and a more sophisticated protection system. This is a common Specification for the 22kV Switchgear and Controlgear with fixed or withdrawable Circuit Breakers. It is intended that the Switchgear of this Specification be able to be installed indoors. 7. Configuration The Switchgear shall be modular with each module typically consisting of a Circuit Breaker and an earth switch. Modules with fixed type Circuit Breaker shall also have a line isolator. A typical configuration could contain 4 or 5 Circuit Breaker modules on each bus. Some locations require multiple bus arrangement with bus tie facility. The specific requirements for each Substation will be defined in a separate Scope Document. 8. Operating Conditions 8.1 Service Conditions The Switchgear will be installed indoors; on a solid concrete type or inside a portable building on steel framed floor. The normal indoor service conditions as detailed in AS shall apply, with the exception that the maximum ambient air temperature shall be taken to be 45 C, and the air may be slightly polluted by dust. 8.2 Electrical Conditions The Switchgear will be connected to a 22kV, 50 Hz Distribution System. The System shall be considered as non-effectively earthed. The design fault level of the 22kV system is 500MVA unless otherwise specified. 9. Ratings The Switchgear shall comply with the following minimum Ratings unless otherwise stated in the Scope Document: Description Value Unit Rated Voltage 24 kv rms Rated Frequency 50 Hz Number of Phases 3 Phase Lightning Impulse Withstand Voltage 150 (preferred) 125 (acceptable) kv peak 1 minute Power Frequency Withstand Voltage 50 kv rms Rated Normal Current of Busbar 630 A rms Rated Short Time Withstand Current (3s) 16 ka for 3s Busbar Insulation Medium Air* Degree of Protection for the Enclosure IP 31 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 7 of 24

8 Description Value Unit Loss of Service Criticality class LSC 2B Class of Partitions PM Internal Arc Classification Type AFLR Internal Arc 16 ka for 1s Circuit Breaker Interrupter type Vacuum* Rated Normal Current of Circuit Breaker 630 A rms Rated Short Circuit Breaking Current of Circuit Breaker 16 ka rms Rated Operating Sequence of Circuit Breaker 0 0.3s CO 15s CO Maximum Opening Time of Circuit Breaker 100 ms No-Load Mechanical Endurance of Circuit Breaker M2 class Rated Electrical Endurance of Circuit Breaker E2 class Number of switching operations at rated shortcircuit breaking current 100 operations Number of Trip Coils 2 Rated Short Circuit Making Current of Earth Switch 40 ka peak Rated Mechanical Life of Earthing Switch 1,000 cycles Rated Electrical Endurance of Earth Switch E2 class *SF6 type may be considered subject to further consultation with MTM regarding environmental concerns. 10. General Requirements 10.1 Modules The Switchgear shall consist of a number of individual Modules as specified. Each Module shall contain one Switching Device and one Earthing Device, along with its associated equipment as detailed below. Additional Modules shall be able to be added as required. The specific requirements for each of these Modules are given below Enclosure The Switchgear and Controlgear shall be Metal-Enclosed. Each Module shall be partitioned. The Circuit Breaker, the Busbar, the Power Cable Termination and the Control and Protection System of each Module shall be metallically partitioned into separate Compartments. Each Module shall be as compact as possible. All metalwork shall be suitably prepared and painted to protect it against corrosion for the expected life of the equipment. All external surfaces shall be coloured beige (colour X43 in accordance with AS 2700S). A lifting facility shall be provided. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 8 of 24

9 10.3 Control Voltage The control supplies for the 22kV Switchgear Assembly is generally provided from the Substation Battery supply that could be 50Vdc, 110Vdc or 125Vdc. The Control Voltage will be specified in the Scope Document. The control supply shall be looped between panels and brought to terminals in the incomer feeder panel. Three separate supplies shall be provided to the 22kV switchgear assembly: A supply for the Bus Protection, Primary Protection and the first trip coils of all the circuit breakers (supply to be looped between circuit breaker panels) A supply for the Backup Protection and the second trip coils of all the circuit breakers (supply to be looped between circuit breaker panels) A supply for panel indications which will be fed from the Substation battery supply. Refer Scope document for battery supply voltage. AC auxiliary supply shall also be looped between panels and brought to terminals in the incomer feeder. The auxiliary supply shall be 230Vac and will be provided from the substation 415Vac switchboard. This shall be used only for the anti-condensation heaters Labelling All Modules, Switching Devices, control switches, components and indicators shall be labelled and have appropriate warning signs on the front and back of the panel. The external labels shall be of the Traffolyte type and shall be fastened by screws. Bus shutters shall be colour coded Yellow and line shutters shall be colour coded Red. Each Module will be assigned a standard Operating Designation label. This will be supplied by MTM at Final Approval Stage. The Module shall be fitted with this label. The Single Line Diagram for each module shall be permanently and indelibly shown on the front of the module. The manufacturer shall obtain the device numbers from MTM prior to manufacture Anti-condensation Heaters An anti-condensation Heater shall be fitted in each Compartment of each Module. If the manufacturer can demonstrate that this is not required, a submission shall be provided for consideration by MTM. The Heaters shall be powered from the 230Vac supply of the Substation. A switch shall be provided in the Control Compartment to switch off the Heaters. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 9 of 24

10 10.6 SCADA Interface Each bus section of the switchgear shall be fitted with a SEL fibre optic transceiver type EIA 485 (SEL 2824) complete with required power supply. All required cabling for SCADA connections shall be made to the transceiver. 3xOC3 ST/ST fibre optic cabling shall be provided between the transceiver and the RTU. Each media converter should then be wired onto a RS485 copper bus connected to each Protection relay which is installed. A single phase 230V 10A captive Socket outlet needs to be installed to the top left of each RTU Minimum clearance of 600mm required to both sides of each RTU for access Prohibited Materials There shall be no asbestos or materials containing asbestos in the Switchgear and Controlgear. A statement certifying that the product is free of asbestos containing materials must be completed and signed, and delivered to MTM prior to despatch. 11. Busbar Requirements Each Module shall contain a single 22 kv Busbar System located in its designated Busbar Compartment which can be connected to the adjacent Modules. One Busbar Voltage Transformer and one Busbar Earthing Switch shall be provided for each combination of Modules. The Voltage Transformer and Earthing Switch shall be provided on the same Module Busbar Voltage Transformer and Bus Alive Indication A three phase Voltage Transformer shall be provided and connected to the Busbar for the purpose of providing an indication of the status of the Busbar, and for any protection schemes that require it. It can be a plug in type. The Voltage Transformer shall comply with AS : Instrument transformers - Inductive voltage transformers. It shall be rated at 50 VA, 22kV/110 V, Class 0.5 M, Voltage Factor 1.9 / 8h. The Voltage Transformer shall have a rating plate fitted to the Transformer with an identical plate be affixed within the Control compartment so that it is readily able to be read. Suitable instrument transformer fuse protection shall be provided for each phase on the primary side to protect the switchgear and the Voltage Transformer against possible faults. A low voltage circuit breaker shall be provided on the secondary side of the Voltage Transformer. This shall be installed in the same compartment as the Transformer. The secondary wiring from the Voltage Transformers shall be run separately from all other wiring, and shall be terminated on a separate terminal strip in the Control Compartment. The Voltage Transformer secondary neutral shall be connected as per the requirement of the protection relays. It shall have a minimum cross-sectional area of 2.5mm2. Where 2.5mm2 is used, it shall have a stranding of 50/0.25mm, and the lugs shall be of the double grip ring pre-insulated crimp type. The cable insulation shall be coloured according to the phase (red/white/blue/black). PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 10 of 24

11 11.2 Busbar Earthing Switch A fixed, fault-make Earthing Switch shall be provided for earthing of the Busbar. The Earthing Switch shall be mechanically or key interlocked with all the Modules. An interlocking diagram shall be provided in the Scope document. The Castell and Fortress type key interlocking systems are an acceptable system. Requirements of section General Earthing Switch Requirements shall apply to the Busbar Earth. 12. Power Cable Termination Requirements Each Module shall have a Power Cable Termination Compartment with interlock-controlled access. The Compartment shall contain the Terminals for the connection of the external power cable, the Line Earthing Switch, and a Line Alive Detection System. The terminals shall only be accessible when the Line Earthing Switch is closed. The Compartment shall be suitable for the power cable to entering from below and shall allow power cable termination via the front of the assembly Terminal Requirements The Terminals shall be suitable for the connection of a terminated insulated cable. The cross-section area of the cable cores will be typically be in the range mm2. Appropriate brackets, clamps and gland plates shall be provided to adequately support the cables in the Compartment so that the weight of the conductor is not taken by the Terminals. The gland plates shall be 3.0mm Aluminium plate unless otherwise agreed in writing. The height of the Terminal shall allow space for the 22kV cable termination within the Compartment and is typically 400mm. A means shall be provided for insulation and phase testing of the Cable Line Earth Switch Requirements General Earthing Switch Requirements The Earthing Switch shall be rated to close onto the fault rating of the Assembly and the closing action shall be operator independent. Each Earthing Switch shall be provided with a mechanical indicating device to positively indicate whether it is in the OPEN OR EARTH position and the words "OPEN" and "EARTH" shall be used for the respective indication of these positions. A padlock shall be provided to lock the Earth Switch into position and prevent the position from being changed. A window shall be provided for observing the position of the Earthing Switch contacts. Retro-reflective tape shall be installed on the Earth Switch blades to highlight the position of the blades. White light emitting diodes (LEDs) shall be fitted to provide appropriate internal illumination of the earthing switch. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 11 of 24

12 The light shall not form part of the high voltage zone containing the Earthing Switch and shall have ready and safe access for maintenance (lamp changing) from outside of the Assembly, without having to de-energise the Assembly. The lights shall be supplied by the substation battery and each light shall be fitted with a timed push button switch, ensuring that the light shall only be illuminated for a limited time period (range 1 to 5 mins) Circuit Earthing Switch Each of the Circuit Breakers shall be provided with an Earthing Switch to earth the cable (power terminal) side of the switchgear. The Earthing Switch shall be mechanically interlocked with the Circuit Breaker to prevent closing the Earth Switch on to live circuit. In the case of the Auxiliary Transformer supplies and Signal Transformer supplies the Circuit Breakers shall be also mechanically and/or electrically and/or key interlocked with the corresponding 415 v switch and 2200 v circuit breaker to prevent closure of earth switch on to back feed Line Alive and Bus Alive Detection System Requirements The Line Alive and Bus Alive Detection System shall detect the energised state of the Terminals. It shall be in accordance with IEC Live working - Voltage detectors - Part 5: Voltage detecting systems and be provided on each phase. The use of a complying capacitive voltage detector is acceptable. The System shall provide an indication on the front of the Control Compartment of the Module. 13. Circuit Breaker Module Requirements The Circuit Breaker will be used to connect to the Supply Feeders, Rectifier Units, Auxiliary Transformer and Signal Transformer at the Substation. The Circuit Breaker Module shall be compartmented as specified in the General Requirements. The Circuit Breaker can be fixed mounted, with an interlocked Disconnector to isolate the Power Cable Terminals from the Circuit Breaker or withdrawable type. Refer to the Scope document for the site specific requirement Circuit Breaker Requirements The Circuit Breaker shall be a three pole vacuum interrupter with the Ratings specified in Clause 9. SF6 type may be considered subject to further consultation with MTM regarding environmental concerns. A mechanical indication of the status of the Circuit Breaker, and the state of the closing spring shall be provided on the front of the Module. The Circuit Breaker shall be fitted with a non-resettable mechanical operations counter. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 12 of 24

13 There shall be a minimum of 6 normally open and 6 normally closed auxiliary contacts provided for control & indication purposes in addition to those required for the operation and local indication of the Circuit Breaker. These contacts shall be of a reliable and robust design and have a current rating of 20A carrying and 5A break at the control voltage without arc quenching devices. They shall be easily adaptable to be either make or break contacts Circuit Breaker Operation The Circuit Breaker shall be able to be manually and electrically closed and opened. The manual closing and opening shall be able to be performed from the front of the Module. The electrical closing and opening shall be performed locally or by a remote control. The details are given in the Control Compartment Requirements The control power supply shall be used for the electrical operations. The current required to operate shall not exceed 5A Disconnector Requirements (Fixed Circuit Breaker only) The Disconnector shall disconnect the Circuit Breaker from the Power Cable Terminals. It shall be interlocked with the Circuit Breaker so that it cannot be opened when the Circuit Breaker is closed, and the Circuit Breaker cannot be closed with the Disconnector is open. It shall also be interlocked with the Line Earthing Switch as specified in the Line Earthing Switch requirements Circuit Breaker Test Position (Withdrawable Circuit Breaker only) The Circuit Breaker shall have a test position which isolates the power circuit while keeping all control circuits connected. A mechanical indication of the position (Inserted/Test /Withdrawn) of the Circuit Breaker shall be provided on the front of the Module. A padlock shall be provided to lock the Circuit Breaker into position and prevent the position from being changed. Two spare auxiliary contacts shall be provided for each position Power Terminal Compartment Additional Requirements The Power Terminal Compartment shall be capable to house 2 sets of Protection Current Transformers on each Phase for the Protection System. The Current Transformers shall comply with AS : Instrument transformers - Current transformers. The details of the Current Transformers will be supplied separately in the Scope Document. The Current Transformers shall have rating plates fitted to the Transformer with an identical plate affixed within the Control Compartment so that it is easily read. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 13 of 24

14 13.6 Control Compartment Requirements The Control Compartment shall contain all of the low voltage control and protection components not mounted on the Circuit Breaker. It shall be accessed by a non-lockable hinged, dustproof, sealed door. A stay shall be provided to enable the door to be held in the open position. The Protection Relays, Indication Meters, Control Switches and Indicating Lights may be mounted on the door. When it is not mounted on the door, they shall be visible and accessible for control/interrogation without opening the door. All other equipment including the Master trip Relay shall be mounted inside the Compartment. The control and auxiliary wiring terminations for connection to external circuits shall be located in a suitable position inside the compartment. A separate terminal strip shall be provided for the protection CT secondary winding terminals. Indicating Lights shall be provided for the Open and Closed indications of the Circuit Breaker. These shall be energized by dedicated and electrically isolated auxiliary contacts of the Circuit Breaker. Indicating lights shall be provided for the Line Alive Detection System and the Bus Alive Detection System. All Indicating Lights shall be long life, high reliability type LED lights. A single Switch shall be provided for the set of Modules to switch on and off the Indicating Lights. A Test Switch for the testing of all lights shall be provided. The control and auxiliary terminals for connection to external circuits shall be provided at a convenient and accessible position inside the Control Compartment. The terminals for the external SCADA cables shall be disconnect test terminals with test sockets. This is to facilitate the isolation of the SCADA cables for testing and faulty finding purposes of the input and output signals. Push in terminals shall not be used and all terminals shall be screw in type Feeder Circuit Breaker Control System Requirements The Circuit Breaker, except for the Rectifier Unit Circuit Breaker, shall be locally electrically operated by a Control Switch on the Control Compartment door. It shall be a spring return to neutral type with a distinctive handle. It shall also be operated by the SCADA System. Interposing relays for closing and for opening shall be provided in the Compartment. The voltage of the coil of the relay shall be rated as specified in the Scope Document. For fixed mounted Circuit Breakers; it shall have a two position C & I Isolating Switch on the Control Compartment door to isolate the control and indication function of the Circuit Breaker from the SCADA RTU. The Switch positions shall be labelled Isolated and Normal. The escutcheon on the Switch shall be coloured yellow. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 14 of 24

15 13.8 Rectifier Unit Circuit Breaker Control System Requirements For fixed mounted Circuit Breakers; the Rectifier Circuit Breaker shall have a two position Rectifier Control Isolating Switch on the Control Compartment door to isolate the control and indication function of the Circuit Breaker from the Rectifier Unit Control & Protection System. The Switch positions shall be labelled Isolated and Normal. The escutcheon on the Switch shall be coloured yellow. The Rectifier Circuit Breaker shall have a local Test Switch on the Control Compartment door. It shall be interlocked with the Circuit Breaker s Disconnector and Rectifier Control Isolating Switch. It shall be a spring return to neutral type with a distinctive handle Protection Scheme Requirements The details of the Protection Scheme and Protection Relays for each Circuit Breaker Module will be specified in the Scope Document. The Protection Relay associated with a Circuit Breaker may be mounted on the Control Compartment door. The optical arc protection shall be RMS 1S20 or equivalent. The Test Links shall be connected to each of the Current Transformer connections to the Relay, and to the main Tripping Contacts of the Relay. The preferred Test Terminals are Weidmuller tyle WTL6/1/STB part no or equivalent. The protection and metering CTs shall be tested by a NATA accredited laboratory unless agreed to in writing with MTM Control Wiring Requirements Control and Auxiliary Wiring All control and auxiliary wiring shall be arranged as simply as possible so that the course of every conductor may be readily traced. All wiring shall not be less than 1.5 mm2 stranded copper conductors unless otherwise agreed in writing. For control wiring supplied from the substation battery, no single insulated conductor shall be in direct contact with earthed metal work Current Transformer and Voltage Transformer Wiring The secondary wiring from the Current Transformers shall be run separately from all other secondary wiring to the terminal strip in the control compartment. Current Transformer (CT) and Voltage Transformer (VT) secondary wiring shall be a minimum size of 2.5mm2 and coloured according to the colour of the respective phase (red/white/blue/black). Where 2.5mm2 wiring is used it shall have a stranding of 50/0.25mm. All wiring connections to CTs, VTs and to protection relays shall be made using double grip ring type pre-insulated crimp lugs. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 15 of 24

16 Auxiliary Terminals Terminals for the connection of the control and auxiliary wiring to external circuits shall be provided at a suitably accessible position in the Assembly. The arrangement of the wiring at the terminals shall be reviewed by the Client before the Assembly is wired. Terminals for the connection of the control and auxiliary wiring to external circuits shall not be located in the HV compartment. Provision shall be made for running the external cable to the terminals that is separated from other internal cabling and connections Current Transformer and Voltage Transformer Test Terminals Disconnect Test terminals shall be provided to facilitate: - testing of the current transformers and voltage transformers - secondary injection testing of the protection relays or measuring instruments (it shall be possible to test each device independently) - isolation of the protection relay input and output signals The preferred terminals are Weidmuller type: WTL6/1/STB- part No The Disconnect Test terminals for the current transformer circuits shall be fitted with the appropriate cross connection sliders (for this terminal type) for shorting out the current transformer secondary windings Protection Relays Disconnect Test links shall be provided on all trip contacts of Protection Relays SCADA Disconnect Test Terminals Suitable Disconnect Test terminals shall be provided for the connection of the SCADA cables, to facilitate isolation of the SCADA supply to the equipment, and shall have suitable test sockets for testing of the equipment input and output signals for SCADA control and monitoring. 14. Testing 14.1 Type Test The Switchgear shall have Type Test Certificates complying with Standard AS The Certificates shall include oscillograms and drawings of the test circuit. Copies of these Certificates shall be supplied with the tender documentation. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 16 of 24

17 14.2 Routine Tests The Switchgear and Controlgear shall be subjected to Routine Tests at the Manufacturer s Workshop complying with AS MTM reserves the right to appoint a representative to witness these Tests. Seven working days notification shall be given to MTM of intention to carry out factory testing. The results of all Routine Tests shall be recorded on test certificates. The test certificates shall clearly show the performance of the equipment and shall be accompanied by tables showing the actually measured values and all calculations. The test certificates shall be forwarded to MTM and the results approved by MTM prior to delivery. 15. Documentation and Support The Supplier must supply all materials, special tools and documents for the Switchgear and Controlgear. The documents shall contain all necessary information and instructions required for operation and maintenance of items Documentation Requirements All documentation shall be provided in English. One electronic and eight paper copies of the each final document shall be provided and the content shall be identical in each copy. Every page of the documentation shall be clearly identified in relation to the document to which it belongs and the version of that document. All pages of multi-page documents shall be uniquely numbered. It shall be possible to readily determine if all pages of a document are present. Manuals shall be A4 size and shall be bound in durable covers or in 4-D ring binders Design Drawings The following drawings must be supplied: i. Construction details of the Switchgear and Controlgear including dimensions. ii. iii. iv. Physical layout and arrangement of the components of the Switchgear and Controlgear. Physical layout and arrangement of the Circuit Breaker and Switch Fuse Modules. Physical layout and arrangement of the Earthing Switches. v. The interlocking arrangement of the Switching Devices, Disconnectors and Earthing Switches. vi. vii. viii. ix. Mounting requirements for the Switchgear. Control circuit diagrams of the Circuit Breaker. Physical layout and arrangement of the Power Cable Connections. Details of control, protection and auxiliary wiring terminations. x. Details of the Protection System. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 17 of 24

18 xi. xii. Details of manual operation of the equipment and any tools to be provided. All other drawings required for Installation, Testing, Commissioning, Operation and Maintenance The drawings shall be submitted for MTM approval prior to manufacturing Drawing Format All drawings must comply with VRIOGS Infrastructure Drafting Standard. Files shall be provided in Microstation format on a compact disk (CD) Technical Maintenance Plan A Technical Maintenance Plan which establishes the maintenance policy for the Switchgear as recommended by the Supplier shall be provided. This shall detail the preventative servicing schedules and maintenance intervals for all components. The servicing schedules shall reference appropriate detailed instructions in the maintenance manual. The Technical Maintenance Plan shall contain a list of any recommended spare parts, detailing price, supplier and procurement lead-times. The Technical Maintenance Plan shall detail safe disposal procedures applicable for when the Assembly is no longer serviceable (recycling, hazardous waste etc.) Maintenance Manual The Maintenance Manual shall detail: a) The theory of operation of the equipment. b) All servicing activities. c) Overhaul instructions. d) Adjustment procedures. e) The changing of components for repairs. f) Fault-finding procedures. g) The spares support schedule. The Maintenance Manual shall also include a complete set of as-built drawings and a comprehensive parts list for the Assembly Installation Instructions Manual Installation Instructions Manual shall enable the Switchgear to be properly installed, tested and commissioned. This shall include all necessary drawings, and information regarding the storage, handling, loading and off-loading instructions Operating Instructions Manual The Operating Instructions Manual shall clearly describe the required procedures for physically operating all of the components of the Switchgear. The operating procedures shall be consistent with the PTC Train Infrastructure Electrical Safety Rules (High Voltage Rules) (IPGOR-01). PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 18 of 24

19 15.8 Tools & Equipment A complete set of operating tools and any other equipment necessary to operate and maintain the Switchgear and Controlgear shall be provided. This shall include any special devices required to test the Switchgear and Controlgear. Storage facilities for the tools and equipment shall also be provided. The software and a PC interface for loading and downloading of Protection Relay settings and the latest fault current data to a laptop PC shall be provided. This shall include all peripheral interfacing equipment and connection cables necessary to connect and communicate with the system. Any special lifting and installation equipment shall be supplied with the Switchgear. 16. Information to be Supplied in Scope Document The following is a summary of the information to be supplied in the Scope Document to make the Supply of the Switchgear and Controlgear to this Specification complete. Number Item 1 Configuration of the Switchgear and Controlgear 2 Supporting Single Line Diagram 3 Control Voltage 4 Protection Current Transformers details 5 Protection Scheme and Protection Relays 6 Interlocking Diagram PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 19 of 24

20 Appendix A Design Management Requirements This Appendix describes the documentation which should be provided as a minimum at each stage of the procurement process. The documentation shall comply with the specifications above. Tender Submission The following documents shall be provided as part of the tender submission: Pamphlets detailing the operating and interlocking principles of the Switchgear and Controlgear. A General Arrangement drawing of the Switchgear which clearly shows: o o Type Test Certificates The overall dimensions of the Switchgear and each Module. Details of the proposed cable terminals and cable entry requirements The Technical Data Schedule in Appendix B filled in. A list of recommended spare parts. Contract Documentation One set of PDF copies of the drawings and documentation detailed in Clause 16, including any other information considered necessary for completeness shall be provided for review and approval by MTM four weeks after the Contact Award Date. No manufacture shall commence until the drawings have been approved. An allowance of seven working days should be made by the Supplier for the review and approval of submitted documents. A draft Installation Instructions Manual shall also be included. Pre-Delivery Documentation Prior to delivery, the Supplier shall provide the paper and electronic copies of the Manuals, Drawings and Routine Test Certificates. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 20 of 24

21 Appendix B Information to be Supplied by Tenderers The Tenders shall supply all of the information requested in Appendix A.1, and fill in the Information and Guaranteed Performance Schedule below of the Switchgear and Controlgear. Manufacturer 1 Manufacturer s Name 2 Manufacturer s Address 3 Country of Manufacture General 4 Manufacturer s Switchgear Type 5 Model Type 6 Part Number 7 Busbar Insulation System 8 Enclosure Type and Material 9 Partitioning between Switching Elements Type 10 IP rating 11 Overall dimensions (l x h x d mm) 12 Weight, Circuit Breaker Module kg 13 Weight, Switch-Fuse Module kg 14 Lifting Facilities Switchgear Rating 15 Rated System Voltage kv 16 Nominal Voltage kv 17 Rated Busbar Normal Current A 18 Rated Short-circuit Level MVA PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 21 of 24

22 19 Rated Frequency Hz 20 Phases 21 Rated Lightning Impulse Withstand Voltage kv 22 Rated short-duration Power-frequency Withstand Voltage kv Circuit Breaker 22 Manufacturer 23 Model Type 24 Interrupter Type 25 Rated Normal current A 26 Rated short circuit Breaking Current ka 27 Rated short circuit Making Current ka 28 Operating Sequence 29 Rated supply voltage of closing and opening devices V Switch - Fuse 30 Manufacturer 31 Model Type 32 Interrupter Type 33 Rated Normal current A 34 Rated short circuit Breaking Current ka 35 Rated short circuit Making Current ka 36 Fuse Type 37 Rated supply voltage of closing and opening devices V PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 22 of 24

23 38 Type Line Disconnecting System 39 Model Type 40 Rated Normal current A 41 Rated Breaking Current A 42 Rated Making Current A 43 Interlocking Mechanism with Circuit Breaker 44 Interlocking Mechanism with Line Status Line Short-circuit Switch 45 Model Type 46 Rated Normal current A 47 Rated Short circuit Making Current A 48 Interlocking Mechanism with Line Disconnector 49 Interlocking Mechanism with Line Status 50 Is Switch able to be viewed in both Open and Closed positions? Yes / No Busbar Short-circuit Switch 51 Short-circuiting System 52 Rated Normal current A 53 Rated Short Circuit Making Current ka 54 Interlocking System with Circuit Breakers and Disconnectors 55 Is Switch able to be viewed in both Open and Closed positions? Yes / No PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 23 of 24

24 Indication and Protection Systems 56 Line Protection Relay Manufacturer 57 Relay Model 58 Current Transformer Manufacturer & Type 59 Current Transformer Ratios 60 Voltage Transformer Manufacture & Type 61 Voltage Transformer Ratings 62 Bus Protection Scheme 63 Bus Protection Device Manufacturer 64 Device Type and Model PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 24 of 24

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

Specification Voltage Limiting Device

Specification Voltage Limiting Device Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering,

More information

Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly

Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly Specification Electrical Networks L1-CHE-SPE-128 Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly Version: 1 Issued: February 2016 Owner: Head of Engineering - Electrical Approved

More information

TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY

TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY Engineering Specification Electrical TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY Version: 2 Issued: October 2017 Owner: Chief Engineer Approved By: Phil Ellingworth Chief Engineer PRINTOUT

More information

11 kv Indoor Switchgear - SCADA Controlled

11 kv Indoor Switchgear - SCADA Controlled Specification 11 kv Indoor Switchgear - SCADA Controlled Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the

More information

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS Engineering Specification Electrical Networks MESP 081000-01 TECHNICAL SPECIFICATION FOR SCADA CABLING IN Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

MESP MODULAR SUBSTATION USER REQUIREMENTS

MESP MODULAR SUBSTATION USER REQUIREMENTS Engineering Specification Electrical Networks MODULAR SUBSTATION USER Version: 2 Issued: November 2015 Owner: Head of Engineering/Electrical Approved By: Head of Engineering/Electrical PRINTOUT MAY NOT

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Switchboards 2. Commercial Metering Switchboards 3. Non-Utility Power Meters (Microprocessor-Based Metering Equipment) PART 2 - PRODUCTS

More information

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A AUTOMATION MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A GRID Note: The technical manual for this device gives instructions for its installation, commissioning,

More information

MTM DESIGN PRACTICE NOTE 110V AC SURGE PROTECTION IN SIGNAL EQUIPMENT ROOMS AND TRACKSIDE ZONE BOXES

MTM DESIGN PRACTICE NOTE 110V AC SURGE PROTECTION IN SIGNAL EQUIPMENT ROOMS AND TRACKSIDE ZONE BOXES SURGE PROTECTION IN SIGNAL Approval Amendment Record Approval Date Version Description 11/05/2016 1 Initial Issue under MTM PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION

More information

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Air-insulated medium-voltage secondary distribution switchgear

Air-insulated medium-voltage secondary distribution switchgear DISTRIBUTION SOLUTIONS Air-insulated medium-voltage secondary distribution switchgear Compact size Complete solution Factory tested Air-insulated medium-voltage secondary distribution switchgear The ABB

More information

CENTERLINE 2500 Motor Control Centers

CENTERLINE 2500 Motor Control Centers CENTERLINE 2500 Motor Control Centers High Performance Motor Control Centers and Switch Gear Meeting IEC 61439-2 Product Description Allen-Bradley CENTERLINE 2500 motor control centers (MCCs) are designed

More information

Elastimold Molded Vacuum Recloser - MVR

Elastimold Molded Vacuum Recloser - MVR Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical

More information

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety MEDIUM VOLTAGE PRODUCTS UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety 2 UNISEC AIR-INSULATED MEDIUM VOLTAGE SECONDARY DISTRIBUTION SWITCHGEAR Operator

More information

SECTION SWITCHGEAR

SECTION SWITCHGEAR SECTION 26 23 13 SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

VAMP 221. Table of Contents

VAMP 221. Table of Contents 2 V221/EN M/E019 VAMP 221 Table of Contents Table of Contents 1. General... 7 1.1. VAMP 221 arc protection system components... 7 1.1.1. Central unit VAMP 221... 9 1.1.2. I/O units VAM 12L / VAM 12 LD,

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards)

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards) ////// SUBSTATIONS DC Switchgear Range Type MBS (IEEE/ANSI standards) GENERAL INFORMATION With a complete range of equipment and a leading expertise in DC traction power substations, Sécheron SA is a world

More information

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV) 1.1 DESCRIPTIONS OF WORK A. The Bidder shall furnish and install the equipment as specified herein and as shown on the contract drawings. B. The switchgear and circuit breakers shall be manufactured by

More information

MMLG 01, 02, 03, 04 MMLB01

MMLG 01, 02, 03, 04 MMLB01 MMLG 01, 02, 03, 04 MMLB01 Technical Data Test Blocks and Test Plugs Publication Reference: MMLG_MMLB/EN/TD/B - ALSTOM 2015. All rights reserved. Information contained in this document is indicative only.

More information

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

Sivacon S4. Low-Voltage Switchboards. siemens.co.uk/tip

Sivacon S4. Low-Voltage Switchboards. siemens.co.uk/tip Product Managers and dedicated Business Development Managers are available to assist with all your enquiries. Technical presentations (Forms of Separation, Discrimination etc) available Site response capability

More information

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. SECTION 26 43 00 SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment. 1.2 DEFINITIONS A. ATS:

More information

SECTION DISCONNECT SWITCHES

SECTION DISCONNECT SWITCHES SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

60103 Circuit Breaker

60103 Circuit Breaker 6003 Circuit Breaker United States MINIATURE CIRCUIT BREAKER, 20/240VAC, 2A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Circuit Breaker Type: Standard

More information

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title s Reference Number PCP 07 - (RIC Standard: EP 99 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

Switch Disconnectors, Main and EMERGENCY-STOP Switches

Switch Disconnectors, Main and EMERGENCY-STOP Switches General data Overview Siemens G 2010 1 2 3 NSE0_01931b 4 5 6 7 1 uxiliary switch (3SB for 3K; 3KX for 3KE) 2 IP20 terminal cover (Operator side) 3 3K switch disconnector 4 rcing contacts (only for 3KE)

More information

63 to 125 A. Functions. Conformity standards. General characteristics. Changeover switches SIRCO VM1 changeover switches.

63 to 125 A. Functions. Conformity standards. General characteristics. Changeover switches SIRCO VM1 changeover switches. comut_004_a_1_cat Changeover switches switches 63 to 125 A switches are manually operated three or four pole switches. They provide, source inversion or switching under load between two low voltage power

More information

REYROLLE 2RMLG. Operating Recommendations

REYROLLE 2RMLG. Operating Recommendations 2RMLG Operating Recommendations SAFETY The commissioning and maintenance of protection equipment should only be carried out by skilled personnel trained in protective relay operation and capable of observing

More information

CONTROL PANEL WIRING SPECIFICATIONS

CONTROL PANEL WIRING SPECIFICATIONS CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,

More information

Medium Voltage Metal-Enclosed Power Capacitor Banks

Medium Voltage Metal-Enclosed Power Capacitor Banks 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Power Capacitor Banks General Northeast Power System s (NEPSI's) medium

More information

SIRCO Load break switches for power distribution from 125 to 5000 A

SIRCO Load break switches for power distribution from 125 to 5000 A The solution for Load break switches sirco_456_a_1_cat > Main switchboard > Distribution panel > Emergency breaking > Network coupling > Local safety breaking sirco-ac_001_a_1_cat SIRCO 3 x 250 A direct

More information

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated

More information

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2

More information

power pazifik MV Switchgear Secondary Distribution Networks Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kv

power pazifik MV Switchgear Secondary Distribution Networks Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kv Manufactured by: MV Switchgear Secondary Distribution Networks Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kv BO-CGM.3/3 SMART RMU Switchgear in Metro Manila Protection and safety for

More information

AThink future. Switch to green. Mini Panel Board. Cost-effective, space-saving board up to 400A.

AThink future. Switch to green. Mini Panel Board. Cost-effective, space-saving board up to 400A. www.moeller.co.uk Mini Panel Board Cost-effective, space-saving board up to 400A Product Catalogue and Selection Guide Mini Panel Board Miniature Circuit Breakers Moulded Case Circuit Breakers XBoard Consumer

More information

Document C0. Use for:

Document C0. Use for: Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized

More information

PDI Modular Compact Remote Power Panel

PDI Modular Compact Remote Power Panel Guide Specifications (Revision 000, 6/17/2016) 1 GENERAL 1.1 Summary These specifications describe requirements for a remote power panel (RPP) distributing power to sensitive loads. These specifications

More information

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1993 Specifications CSJ s 0924-06-221,etc. & 0924-06-223 SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet 1. Description. This specification describes the minimum acceptable requirements for a weatherproof

More information

CONTROL MICROSYSTEMS and 5402 Digital I/O Module. Hardware Manual

CONTROL MICROSYSTEMS and 5402 Digital I/O Module. Hardware Manual 50 and 50 Digital I/O Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676

More information

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Ancillary Electrical Equipment for Use in Conjunction with Switchgear and Protection/Control Panels NOTE: The current version of this document is

More information

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series POWER & ACTUATION OVERLOAD RELAYS series Need reliable, accurate overload and phase-loss protection for your motors? c3controls Series Bimetallic Overload Relays provide unmatched protection and can be

More information

60W Power over Ethernet Waterproof Adapter PoE IEEE BT Single Port Injector for Outdoor Application

60W Power over Ethernet Waterproof Adapter PoE IEEE BT Single Port Injector for Outdoor Application WWW.PHIHONG.COM 60W Power over Ethernet Waterproof Adapter PoE IEEE BT Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3bt Standard Non-Vented Case with Mounting Bracket

More information

Innovation on Medium Voltage Switchgear

Innovation on Medium Voltage Switchgear Bruno Rivas, Guarulhos - Brazil, April 2015 Jornadas Técnicas de ABB en Chile Innovation on Medium Voltage Switchgear May 13, 2015 Slide 1 Application 13. Mai 2015 Slide 2 PPMV Brazil Factory Unigear Insourcing

More information

SECTION ELECTRIC METERING

SECTION ELECTRIC METERING SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

The right solution for every home

The right solution for every home Domae Household switchboards The right solution for every home Household guide 2002 Building a New Electric World. Household switchboards Domae The right solution for every home Household guide 2002 Building

More information

SENTRON ATC Automatic Transfer Control Device

SENTRON ATC Automatic Transfer Control Device Siemens A 2010 SENTRON - SENTRON switching, protection and measuring devices The SENTRON, when equipped with two motor-driven circuit breakers, serves as a transfer system that automatically or manually

More information

CP30F Series Circuit Protector for Improving Safety and Wiring Workability

CP30F Series Circuit Protector for Improving Safety and Wiring Workability CP30F Series Circuit Protector for Improving Safety and Wiring Workability EMURA, Takeshi * A B S T R A C T A circuit protector is a circuit-breaker that possesses both overcurrent protection and switch

More information

SERIES SD3800 / SD3810 SPECIFICATION

SERIES SD3800 / SD3810 SPECIFICATION SERIES SD3800 / SD3810 SPECIFICATION SOLID DIELECTRIC SINGLE SIDED 15 KV & 25 KV PADMOUNTED VACUUM LOAD INTERRUPTERS AND VACUUM FAULT INTERRUPTERS WITH VISIBLE DISCONNECTS MANUALLY OPERATED / REMOTELY

More information

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Individually Mounted Switches and Circuit Breakers Used for the following: a. Service

More information

References. References. Rating (A) Référence

References. References. Rating (A) Référence DIRECT OPERATION T O O R D E R EXTERNAL OPERATION picto_080_c_1_gb Switch body Direct Switch body + handle + Shaft + + OTHER ACCESSORIES External handle acces_128_a_1_cat acces_129_a_1_cat Direct handle

More information

IEC & 2 standard. The reference for safe and reliable LV switchboards

IEC & 2 standard. The reference for safe and reliable LV switchboards IEC 61439-1 & 2 standard The reference for safe and reliable LV switchboards IEC61439-1 & 2 The power of a standard adapted to your needs IEC standards are today legal or market references. The new IEC

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

Medium Voltage Distribution Catalogue GenieEvo range. Air Insulated MV Switchgear kv

Medium Voltage Distribution Catalogue GenieEvo range. Air Insulated MV Switchgear kv Medium Voltage Distribution Catalogue 2015 GenieEvo range Air Insulated MV Switchgear 3.3-13.8 kv Medium Voltage Distribution GenieEvo Your requirements Peace of mind Energy availability Safety GenieEvo

More information

GHA. Gas-Insulated Circuit-Breaker Switchgear Unit up to 40.5 kv. Gas-Insulated Switchgear. Customer Benefits

GHA. Gas-Insulated Circuit-Breaker Switchgear Unit up to 40.5 kv. Gas-Insulated Switchgear. Customer Benefits 01 Gas-Insulated Circuit-Breaker Switchgear Unit up to 40.5 kv PM103255 Energy supply security is our permanent challenge. At Schneider Electric, we are constantly developing and improving our products

More information

Test Report S

Test Report S Sunkom Pty Ltd FDX card s A101, A102, A104 and A108 Laboratory Details All tests were performed at : Comtest Laboratories Pty. Ltd. Unit 1 / 570 City Road South Melbourne Victoria 3205 Australia Telephone

More information

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP)

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP) Discipline Engineering Standard - NSW Category Signalling Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units Reference Number SPS 30 - (RIC Standard: SC 09 10 07 00 SP)

More information

ABB AG - EPDS. Gas-insulated switchgear Type ZX2

ABB AG - EPDS. Gas-insulated switchgear Type ZX2 ABB AG - EPDS Gas-insulated switchgear Medium voltage switchgear Single or double busbar systems 12 kv, 2500 A, 40 ka 24 kv, 2500 A, 40 ka 36 kv, 2500 A, 40 ka Slide 2 Medium voltage switchgear With IAC

More information

Power supply unit NG3-16ib

Power supply unit NG3-16ib Ordering Data Designation Type Item no. Power supply unit NG3-16ib (42 V AC / ) 371 008 31 AX Power supply unit NG3-16ib (230 V AC / ) 371 008 32 AX Power supply unit NG3-16ib (100 V AC / ) 371 008 34

More information

Adaptors Busplug Low Voltage Switchboard Equipment

Adaptors Busplug Low Voltage Switchboard Equipment Busplug Adaptors Low Voltage Switchboard Equipment Publication BA 2012 CONTENTS Descriptive Advantages of Busplugs 2 General Description 3 Use of Busplugs Adaptors 3 Construction 4 Technical Standards

More information

Ground Breaking MV Switchgear

Ground Breaking MV Switchgear ISO 9001:2008 and ISO 14001:2004 certification ETALON Ground Breaking MV Switchgear Etalon is vacuum switchgear that fits most of the switchgear applications available and meets the most strict safety

More information

ABB AG Calor Emag Medium Voltage Products Gas-insulated switchgear Type ZX2. ABB Gas-insulated switchgear type ZX2 1

ABB AG Calor Emag Medium Voltage Products Gas-insulated switchgear Type ZX2. ABB Gas-insulated switchgear type ZX2 1 ABB AG Calor Emag Medium Voltage Products Gas-insulated switchgear 17.02.2015 Gas-insulated switchgear type ZX2 1 Medium voltage switchgear type ZX2 Single or double busbar systems 12 kv, 2500 A, 40 ka

More information

Miniature Circuit Breakers for Railway Applications

Miniature Circuit Breakers for Railway Applications Siemens AG 00 for Railway Applications BETA Low-Voltage Circuit Protection The miniature circuit breakers are used in fixed railway systems and rolling stock for protecting system components against overcurrent

More information

PCT2000. User Manual. Precision current transducer 2000 A

PCT2000. User Manual. Precision current transducer 2000 A PCT2000 User Manual PCT2000 Precision current transducer 2000 A User Manual Status: November 6, 2018 Copyright 2018 ZES ZIMMER Electronic Systems GmbH Pfeiffstraße 12 61440 Oberursel (Taunus), Germany

More information

SIEBREAK-VCB 5-15 kv metal-enclosed interrupter switchgear usa.siemens.com/siebreak

SIEBREAK-VCB 5-15 kv metal-enclosed interrupter switchgear usa.siemens.com/siebreak Reducing arc-flash energy SBRK-VCB 5-15 kv metal-enclosed interrupter switchgear usa.siemens.com/siebreak SBRK-VCB with ORS Brochure Reducing the arc-flash incident energy in low-voltage substation applications

More information

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B GE Energy Connections Grid Solutions MMLZ Technical Data Sheet Auxiliary Modules Publication reference: MMLZ/EN TDS/B MMLZ Technical Data Sheet FEATURES Wide choice of application specific models Fully

More information

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD. (INDIA) VT. LTD. 5. INCOMING SULY CONDUCTOR TERMINATIONS AND DEVICES FOR DISCONNECTING AND SWITCHING OFF 5.1 Incoming supply conductor terminations The electrical equipment of the machine shall have only

More information

Package Substation. The efficient solution for your electrical distribution network

Package Substation. The efficient solution for your electrical distribution network Package Substation The efficient solution for your electrical distribution network Why Prefabricated Substations? Biosco, safe and effective substations Safety: A fully tested electrical equipment > Much

More information

MiCOM Agile P99x. Grid Solutions. Testing & Commissioning. Test Block, Multi-finger Test Plug and Single-finger Test Plug. Design Flexibility

MiCOM Agile P99x. Grid Solutions. Testing & Commissioning. Test Block, Multi-finger Test Plug and Single-finger Test Plug. Design Flexibility GE Grid Solutions MiCOM Agile P99x Test Block, Multi-finger Test Plug and Single-finger Test Plug The MiCom Agile P991 test block offers safe and configurable facilities for monitoring and secondary injection

More information

24kV SF6 INSULATED SWITCHGEAR SPECIFICATION

24kV SF6 INSULATED SWITCHGEAR SPECIFICATION 24kV SF6 INSULATED SWITCHGEAR SPECIFICATION 1.0 REQUIRED EQUIPMENTS & QUANTITY ITEM NO MATERIAL 1 24 kv SF6 Compact Ring Main Unit (Extensible/motorised ). Shown in figure 1 2 24 kv SF6 Fuse Switch (Extensible/motorised).

More information

Installation and commissioning guide SmartLink PSD Power Supply Module (DC)

Installation and commissioning guide SmartLink PSD Power Supply Module (DC) Installation and commissioning guide SmartLink PSD Power Supply Module (DC) Rev. 1 September 2012 Part No. 4417551 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15

More information

Bulletin Installation of solar photovoltaic systems Rules , , , , and

Bulletin Installation of solar photovoltaic systems Rules , , , , and Bulletin 64-5-0 Installation of solar photovoltaic systems Rules 64-060, 64-200, 64-214, 84-020, 84-024 and 84-030 Scope (1) Introduction (2) Disconnecting means (a) Disconnecting means for solar photovoltaic

More information

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical

More information

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2 The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results

More information

L1-CHE-SPE-303 ELECTRICAL AND ELECTRONIC COMPONENTS (RATINGS AND CONSTRUCTION REQUIREMENTS)

L1-CHE-SPE-303 ELECTRICAL AND ELECTRONIC COMPONENTS (RATINGS AND CONSTRUCTION REQUIREMENTS) Engineering Specification Signalling L1-CHE-SPE-303 ELECTRICAL AND ELECTRONIC COMPONENTS (RATINGS AND CONSTRUCTION REQUIREMENTS) Version: 1 ENGINEERING SPECIFICATION ELECTRICAL AND ELECTRONIC COMPONENTS

More information

Switches 6/1. 6/4 Introduction. 6/5 5TE8 control switches. 6/7 5TE4 8 pushbuttons. 6/9 5TE8 On/Off switches. 6/11 5TE1 switch disconnectors

Switches 6/1. 6/4 Introduction. 6/5 5TE8 control switches. 6/7 5TE4 8 pushbuttons. 6/9 5TE8 On/Off switches. 6/11 5TE1 switch disconnectors 6/4 Introduction 6/5 5TE8 control switches 6/7 5TE4 8 pushbuttons 6/9 5TE8 On/Off switches 4 6/11 5TE1 switch disconnectors 6 6/1 Switch to manual? Wherever electrical systems need to be switched on or

More information

KMP A3. Air Insulated Medium Voltage Switchgear Powerful. Safe. Highly Available

KMP A3. Air Insulated Medium Voltage Switchgear Powerful. Safe. Highly Available KMP A3 Air Insulated Medium Voltage Switchgear Powerful. Safe. Highly Available High power switchgear systems For primary applications The name MediPower represents powerful medium voltage energy distribution

More information

Safegard V4 Panel. Installation Datasheet. Safegard V4 Panel Installation Instructions and Datasheet release 1.7 August 2016

Safegard V4 Panel. Installation Datasheet. Safegard V4 Panel Installation Instructions and Datasheet release 1.7 August 2016 Safegard V4 Panel Installation Datasheet ELECTROSTATIC SENSITIVE DEVICE This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product will directly

More information

NU-LEC. Loop Automation. Reclosers & Sectionalizers

NU-LEC. Loop Automation. Reclosers & Sectionalizers NU-LEC Loop Automation Reclosers & Sectionalizers 1 NU-LEC LLC NU-LEC LLC is a wholly unit of NU-LEC Industries, Pty, Ltd. Sales and service center for United States, Canada, and the Caribbean. Warehouse

More information

Integration Fully integrated Controls, Power Monitoring, Generator Paralleling, and Switching Schemes as a complete turnkey solution.

Integration Fully integrated Controls, Power Monitoring, Generator Paralleling, and Switching Schemes as a complete turnkey solution. Technical Datasheet Tier Power Systems, Inc. iq Series UL 1558 Switchgear Tier Power Systems iq Series is a leader in switchgear technology. iq Series provides advanced power distribution technology and

More information

UL 489 DIN Rail Miniature Circuit Breakers

UL 489 DIN Rail Miniature Circuit Breakers UL 489 DIN Rail Miniature Circuit Breakers Product Overview................................................ 2 Product Selection................................................ 4 Accessories.....................................................

More information

K1K015NZ4 cam stepping switch - 2-pole A - screw mounting

K1K015NZ4 cam stepping switch - 2-pole A - screw mounting Characteristics cam stepping switch - 2-pole - 60-12 A - screw mounting Complementary Number of steps 5 Main Range of product Product or component type Component name [Ith] conventional free air thermal

More information

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content 1. About this document DE Betriebsanleitung...............Seiten 1 bis 6 Übersetzung der Originalbetriebsanleitung 1.1 Function This operating instructions manual provides all the information you need

More information

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units. Model KEP Automatic Transfer Switches Service Entrance Rated Controller D Decision-Makerr MPAC 1500 Ratings Power Switching Device Current Voltage, Frequency Molded case (MCCB) Insulated Case (ICCB) 200

More information

MV Network Switchgear, Protection and Control

MV Network Switchgear, Protection and Control MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control

More information

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content 8 Appendix 8.1 Wiring examples...3 8.2 Integral System Diagnostics (ISD)....4 9 EU Declaration of conformity Operating instructions.............pages 1 to 6 Original x.000 / 11.2017 / v.a. - 101172890-

More information

J7MN. Ordering Information. Motor Protection Circuit Breaker. Model Number Legend. MPCB system. Options. Motor Protection Circuit Breaker J7MN I-1

J7MN. Ordering Information. Motor Protection Circuit Breaker. Model Number Legend. MPCB system. Options. Motor Protection Circuit Breaker J7MN I-1 Motor Protection Circuit Breaker J7MN ) MPCB system Rotary and switch types Rated operational current 32 A, 63 A and 00 A Switching capacity up to 00 ka/400 V Fixed short-circuit release = 3 x I u Overload

More information

UL 489 DIN Rail Miniature Circuit Breakers

UL 489 DIN Rail Miniature Circuit Breakers UL 9 DIN Rail Miniature Circuit Breakers Product Overview................................................ Product Selection................................................ Accessories.....................................................

More information

Meter Enclosure and Equipment Standards

Meter Enclosure and Equipment Standards Meter Enclosure and Equipment Standards (a) (b) General Requirements: CITY OF OCALA UTILITY SERVICES METER ENCLOSURE AND EQUIPMENT STANDARDS: (1) To avoid the costs associated with having to replace unacceptable

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

K1B004TLH cam switch - 1 pole A - screw mounting

K1B004TLH cam switch - 1 pole A - screw mounting Characteristics cam switch - 1 pole - 30-12 A - screw mounting Main Range of product Product or component type Component name [Ith] conventional free air thermal current Product mounting Fixing mode Cam

More information

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Type MVTT 14 and MVTT 15: Static Digital Time delay relays Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction

More information

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5

More information

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD United States MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD Product Information Features and Specifications For Use With: OEM Panels Approvals: UL

More information