New FOUNDATION Fieldbus Interface Techniques Increased Availability and Reduced Costs. Andreas Agostin Pepperl+Fuchs
|
|
- Sabina Parks
- 6 years ago
- Views:
Transcription
1 New FOUNDATION Fieldbus Interface Techniques Increased Availability and Reduced Costs Andreas Agostin Pepperl+Fuchs Abstract InfraServ Hoechst and Aventis Pharma of Germany performed a comparison study between an installation using conventional technology and a comparable planned installation using fieldbus. Conclusion: fieldbus reduces overall costs if used with the herein described FieldBarrier. Existing fieldbus topologies for intrinsic safety (I.S.) applications in explosive atmospheres consist of a host controller, a Fieldbus power supply and the field instruments. The new topology replaces the traditional fieldbus power supply with two redundant power supplies and a failure-free fieldbus power conditioner. The spur connections of the field instruments are replaced by the FieldBarrier or the Segment Protector. The FieldBarrier is a field-mounted junction box that includes four integrated IS barriers, while the Segment Protector is a junction box that includes short circuit protection for the spur outputs. This topology has the following advantages: - Redundancy for the power supply - Standard power supplies with higher output current can be used - Increased number of instruments can be connected - Independent I.S. barriers for each spur means increased availability of instruments - In case of a failure at one spur (e.g. short circuit) the other spurs or the trunk are not affected The new concept is also beneficial in non-ex applications. The rationale will be covered in this document. Page 1 of 11
2 1. Introduction In recent years, fieldbus began to replace the conventional 4-20 ma signal interface technology. Several requirements need to be fulfilled by a fieldbus to be accepted by end users, especially in process industries: - Low power consumption - No separate power supplies for the instruments - Allow intrinsic safety (I.S.) installations The instrument manufacturers can fulfill the first two requirements while interface manufacturers like Pepperl+Fuchs can solve the intrinsic safety requirements. However, end users ask for two additional requirements in a fieldbus installation: - Increased reliability of the fieldbus power supply (implementing redundancy) - Increased availability of the field instruments and protection against failures 2. Fieldbus topology Figure 1 illustrates a typical fieldbus topology for a safe area application that shows a control system with a fieldbus communication controller, the fieldbus cable, a FF power supply and several field instruments. The device at the end of the bus cable is a fieldbus terminator that is needed to ensure proper communication. Most of the instruments are bus -powered and the communication signal is superimposed on the DC power on the same pair of wires (shielded twisted pair fieldbus cable). The communication controller in the DCS usually does not supply power for these buspowered devices. Hence, it is necessary to use a separate fieldbus-dedicated power supply. Andreas Agostin Page 2 of 11
3 FF interface H1 segment Terminator FF Power Supply Bus-powered instruments 24 VDC Fig 1. Typical fieldbus topology in non -hazardous areas A fieldbus power supply consists of a power converter with voltage regulator and a filter (conditioner). The power converter transforms the variable input voltage (not necessarily 24 Vdc) into the desired fixed output voltage. The filter decouples the communication signal from the voltage regulation unit. Without filtering, the power regulation would destroy the communication signal since the regulator tries to maintain a fixed output voltage. The fieldbus power supply and the field instruments are connected in parallel to the fieldbus cable. This results in the following problem - If there is a failure of the power supply or if there is a short circuit at any of the connected field instruments, signals from every device will be lost. The new topology provides two solutions. One solution covers the loss of the power supply while the other covers the availability of the field instruments. Andreas Agostin Page 3 of 11
4 3. Power Supply Redundancy (Non-Hazardous Area) 3.1 Introduction To create a reliable fieldbus installation, the above-mentioned topology requires redundancy for active power supplies. Active is stressed since passive devices are considered and proven to be more reliable and failure-free when compared to an active device. A typical passive device is, for example, a backplane motherboard equipped with screw terminals, module sockets, connectors, diodes and resistors. Examples of active devices include galvanically isolated power supplies, barriers or complex electronic components. Until recently, fieldbus power supplies have always been active. 3.2 Fieldbus Power Conditioner (FPC) Most fieldbus power supplies consists of a power converter and a filter (conditioner). The new approach is to divide the traditional fieldbus power supply into two components. Using this concept, there is no need to have a dedicated fieldbus power supply but only a standard power supply and a separate filter. The Fieldbus Power Conditioner (FPC) contains this filter. The filter is a passive device and contains only a few discrete, fixed-value components (inductors, capacitors and resistors). As such, the filter can be considered failure-free and does not need to be redundant. The standard power supply unit still must be redundant. Standard power supplies can be used but it is not possible to simply connect two independent power supplies in parallel. Since these supplies would not be compatible, each power supply attempts to regulate the output voltage concurrently. The connection can only be done through decoupling diodes. For this purpose, redundant power feed modules can be used (see Figure 2). Two, passive power feed modules are energized by two independent power supplies Andreas Agostin Page 4 of 11
5 and provide the voltage to the Power Rail. The FPC picks the voltage from the Power Rail and supplies it through the filter to the fieldbus cable. To fieldbus cable + - DIN rail with P+F PowerRail Power Feed Module FPC + - To power supply #1 + - To power supply #1 Fig 2. Redundant Power feed modules and FPC Whenever one power supply or one power feed module fails, the FPC will still be supplied by the other power feed module and power supply. Even triple redundancy is possible in the same manner. By using the FPC, not only is reliability increased but also the amount of hardware is reduced. As many as four FPCs can be energized by the two Power Feed Modules (see Figure 3). Fig 3. Redundant power feed modules and four FPC s Andreas Agostin Page 5 of 11
6 4. Intrinsic Safety (I.S.) Applications 4.1 Introduction With the fieldbus topology described in Section 2, the availability of all instruments depends on a single failure. The same problem applies to applications in hazardous areas (see Figure 4). FF interface H1 segment Terminator FF Power Repeater 24VDC Bus - powered instruments Fig 4. Typical fieldbus topology in hazardous areas The I.S. barrier (Power Repeater) not only isolates the safe area from the hazardous area (Ex and non-ex), it functions as a power supply for the bus-powered instruments. As such, the entire segment is lost if the I.S. barrier fails. Unlike the fieldbus power supply, the power repeater cannot be split into a power supply barrier and filter. From a safety perspective, it is not possible to connect multiple I.S. barriers for fieldbus (Johannsmeyer, 1994). Hence, it would be reasonable to connect only one instrument to one I.S. barrier. However this would make a fieldbus installation very expensive since additional wiring would be required and barriers would be under-utilized. One possible solution for this problem is the FieldBarrier. Andreas Agostin Page 6 of 11
7 4.2 FieldBarrier The FieldBarrier combines four I.S. barriers (channels) in a common IP66/Type 4 field housing. In the previous section, we described why it is necessary to connect only one instrument per barrier to ensure instrument availability. Figure 5 shows an alternate approach. Fig 5. FPC and FieldBarrier FF interface (host) 24 VDC Safe area FF Power Supply H1 segment FieldBarrier 2 Zone 1 or 2 Division 2 Zone 0 or 1 Division 1 Fig 5. FPC and FieldBarrier Each of the four channels provides enough current for up to four instruments, typically one or two devices would normally be connected in either FISCO (Johannsmeyer, 1994) or entity configurations. If one instrument is connected per channel, the maximum availability is achieved. If there is a failure along any of the four channels, the other FieldBarrier channels remain unaffected. Andreas Agostin Page 7 of 11
8 In addition, the outputs of the FieldBarrier are galvanically isolated from the host segment; therefore, potential equalization is unnecessary. Those who are familiar with this topic appreciate the tremendous cost savings of this feature. FieldBarrier itself consumes a limited amount of current from the bus to operate; hence, the connected field instruments can use almost all of the available current from the fieldbus power source. To increase the total number of instruments on the host, several FieldBarriers can be connected to the fieldbus trunk. Most of the available hosts support 16 devices on one communication controller segment. This number can only be achieved with the new FPC since this device produces as much as 3 times the amount of current than existing supplies. To allow this high current to be delivered into the hazardous area, the protection method Exe (increased safety) is used for the incoming bus connection. Alternatively, this same fieldbus segment can be installed within an acceptable wiring method for Division 2 applications. Mounting of the FieldBarrier is generally very close to the instruments. Since the FieldBarrier creates isolated spurs, the maximum distance between the instruments and the outputs is limited to 120 m. This distance is independent of whether the application involves a safe area or a hazardous area (Zone 1 or Division 2 mounting). This feature also allows operation without additional fieldbus terminators at each output and saves costs. Since all of the field instruments are directly connected to the FieldBarrier, it functions as a T junction box and there is no need to have additional junction boxes at the instruments. This is another cost saving factor. According to Fig 5 above, if the power supply fails, every signal from the system is again lost. As such, redundancy for the power supply is mandatory. Andreas Agostin Page 8 of 11
9 5. Power redundancy and increased instrument availability The FieldBarrier in conjunction with the FPC combines power redundancy and instrument availability, as shown in Figure VDC 24 VDC Safe area EExe or Div. EEx 2 e wiring FF H1 segment Long distance between the host and the field n Division 1 Division 2 Zone 0/1 Zone 1/2 Fig 6. FPC and FieldBarrier Several FieldBarriers can be connected to the trunk in order to use all of the available current provided by the power source. The 24 Vdc power source must be highly reliable (redundant). The FPC and redundant power feed modules described in section 3.2 must also be implemented. The redundancy of the power supply ensures the availability of power in the fieldbus segment while the current limitation and short circuit protection of the FieldBarrier ensures availability of the instruments in case of failure. Andreas Agostin Page 9 of 11
10 6. Power Redundancy and Increased Instrument Availability in Non-Ex Applications The Segment Protector for non-hazardous applications provides a topology similar to the FieldBarrier. Figure 7 shows this set-up. 24 VDC 24 VDC FF H1 segment Long distance between the host and the field n Segment Protector Safe area Fig 7. FPC and Segment Protector Andreas Agostin Page 10 of 11
11 7. Conclusion Although many fieldbus capable products have been available for years, the potential of fieldbus is just now being realized, mainly because end users and manufacturers needed to obtain knowledge and experience on the new technology. New generation fieldbus products like the FieldBarrier overcome the limitations of previous topologies and make it possible to incorporate the lower cost of this new technology. The unique features of the FPC, the Segment Protector and the FieldBarrier result in a new installation topology that can be used in hazardous and non-haz ardous applications. In addition to the improved reliability of the entire structure, and especially the availability of field instruments, a significant cost saving can be achieved. Reference Berge, J.: Fieldbus for Process Control: Engineering, Operation and Maintenance, ISA Press, 2002 Pepperl+Fuchs datasheets, brochures and catalogs: Andreas Agostin Page 11 of 11
Benefits derived from the FF specification FF-831
Foundation Fieldbus End Users Council Australia Inc. 9 Corcoran St Duncraig, WA 6023 P.O. Box Z5546 Perth, WA 6831 Benefits derived from the FF specification FF-831 Why we need it, and why it improves
More informationDistributed Intrinsically Safe Fieldbus Applications
Application Note FB01-1 - Distributed Intrinsically Safe Fieldbus Applications Emerson Process Management DeltaV DCS System Pepperl+Fuchs June 2003 Application Note FB01-2 - c Pepperl+Fuchs Inc. All rights
More informationDC Power Considerations for Intrinsically Safe Applications
Chapter 3 Intrinsically Safe Fieldbus Applications This chapter provides information about fieldbus applications that provide Intrinsically Safe (IS) power to fieldbus devices located in hazardous areas.
More informationPROCESS AUTOMATION YOUR PARTNER FOR INDUSTRY-SPECIFIC INSTALLATION SOLUTIONS FIELD JUNCTION BOX
PROCESS AUTOMATION YOUR PARTNER FOR INDUSTRY-SPECIFIC INSTALLATION SOLUTIONS FIELD JUNCTION BOX OUR COMPONENTS... CONFIGURABLE TO YOUR NEEDS No application is like the others; every application always
More information10 Mb/s Single Twisted Pair Ethernet Process Industry Requirements Steffen Graber Pepperl+Fuchs
10 Mb/s Single Twisted Pair Ethernet Process Industry Requirements Steffen Graber Pepperl+Fuchs IEEE802.3 10 Mb/s Single Twisted Pair Ethernet Study Group 9/8/2016 1 Overview Introduction Current bus Infrastructure
More informationTrusted Strategic Partners in Process Automation. Alliance Member
Trusted Strategic Partners in Process Automation Alliance Member Together with Pepperl+Fuchs, the Emerson Alliance Program provides a total automation solution Emerson and Pepperl+Fuchs have worked together
More informationDesign Benefits. Teo Puay Yong Pepperl+Fuchs. On Behalf of FF Marketing Society. The Future is Digital. 1 The Future is Digital
Design Benefits The Future is Digital Teo Puay Yong Pepperl+Fuchs On Behalf of FF Marketing Society 1 The Future is Digital Design Benefits from Applying Foundation Fieldbus Bus structure and Wiring Loop
More informationThe High Power Trunk Alternative to FISCO and FNICO
The High Power Trunk Alternative to FISCO and FNICO Bernd Schuessler, Business Development Manager Pepperl+Fuchs Twinsburg, OH 330-486-0002 www.fieldconnex.info End users throughout the Fieldbus world
More information5 Fieldbus Technology
5 Fieldbus Technology Ex e / Ex i 10922E00 The s Ex e/ex i connect intrinsically safe Foundation Fieldbus H1 or Profibus PA field devices to a non-intrinsically safe / Ex e trunk. Up to four intrinsically
More informationMARINE CERTIFIED PRODUCTS BY PEPPERL+FUCHS
FIELDBUS Power Hub with Power Supply Modules KLD2-FBPS-1.25.360 HD2-FBPS-1.25.360 HD2-FBPS-1.500 HD2-FBPS-1.23.500 HD2-FBPS-1.17.500 Fieldbus Power Supply, 25 V/360 ma, stand-alone, DIN-rail mountable
More informationHigh Availability Fieldbus Networks New Physical Layer Technologies. : Nagesha Nayak : Manager Project Pursuit
High Availability Fieldbus Networks New Physical Layer Technologies Name Job Title Company : Nagesha Nayak : Manager Project Pursuit : Cooper -MTL What could possibly go wrong? Host H1 Card Control Room
More informationFF Physical Layer Components
FF Physical Layer Components Best Practices Binoy Kamath AGM Project Pursuit Pepperl+Fuchs India Pvt. LTd.,Bangalore Agenda Introduction to FF and FF Physical Layer FF Physical Layer Components FF Wiring
More informationPROCESS AUTOMATION. Installation Technology for FOUNDATION Fieldbus
PROCESS AUTOMATION Installation Technology for FOUNDATION Fieldbus HOST Plant Communication with Fieldbus page 4 Benefit from the future proof, enabling technology page 10 Power Supply Power your field
More informationSegment Protector for Cabinet Installation R2-SP-IC* Features. Assembly. Function. Connection. Trunk, Ex na non-arcing. Spur.
egment Protector for Cabinet nstallation Features Assembly 4... 12 outputs Ex ic (FCO or Entity) or non-incendive (Div 2) Advanced fault isolation at the spur egment Protector in Zone 2/Div. 2 nstruments
More informationIntroduction to Fieldbus Foundation Physical Layer
Introduction to Fieldbus Foundation Physical Layer Fazi Hashim MTL Muhammad Syafiq bin Hamid KLAESB Product Sales /Application Engineer Email: muhammad.syafiq@klaesb.com Fieldbus What is fieldbus Benefits
More informationTermination Board. HiCTB08-SCT-44C-SC-RA. Features. Assembly. Function. Connection. 24 V DC (I), 24 V DC (II), Fault. Zone 0, 1, 2 Div.
Termination Board HiCTB08-SCT-C-SC-RA Features Assembly For 8 modules V DC supply Supported signal types: DI/DO/AI/TI/AO Hazardous area: screw terminals, blue Safe area: screw terminals, black Function
More informationTermination Board FC-GPCS-RIO16-PF. Features. Assembly. Function. Connection USIO/UPIO 24 V DC (I), 24 V DC (II) Fault. Zone 0, 1, 2 Div.
Features Assembly System board for Honeywell Universal Safety IO System board for Honeywell Universal Process IO For 6-channel cards USIO and UPIO For 6 modules Recommended modules: HiC8R (DI), HiC85R
More informationNon-Incendive Fieldbus for Simplified Maintenance
Non-Incendive Fieldbus for Simplified Maintenance 1 INTRODUCTION Many plants using FOUNDATION Fieldbus are installed in Class I Division 2 (Zone 2) hazardous area. Designers must choose a protection method
More informationTermination Board FC-GPCS-SAI16-PF. Features. Assembly. Function. Connection. SAI-1620m HART 24 V DC (I), 24 V DC (II) Fault. Zone 0, 1, 2 Div.
Features Assembly System board for Honeywell Safety Manager For 6-channel AI card SAI-60m For 6 modules Recommended module: HiC05 (AI) 4 V DC supply Hazardous area: pluggable screw terminals, blue Non-hazardous
More information7/2005. Reprint. Oldenbourg. Automation Technology in Practice. Breakthrough in Fieldbus technology High Power Trunk concepts.
7/2005 July Automation Technology in Practice Breakthrough in Fieldbus technology High Power Trunk concepts Reprint Oldenbourg 3 Breakthrough in Fieldbus technology High Power Trunk concepts Do we see
More informationMANUAL SEGMENT CHECKER
PROCESS AUTOMATION MANUAL SEGMENT CHECKER A UNIVERSAL AND EASY-TO- USE SEGMENT DESIGN TOOL FOR FIELDBUS NETWORKS With regard to the supply of products, the current issue of the following document is applicable:
More informationSegment Protector for Cabinet Installation R2-SP-IC* Features. Assembly. Function. Connection. Trunk, Ex na non-arcing. Spur.
egment Protector for Cabinet nstallation Features Assembly 4... 12 outputs Ex ic (FCO or Entity) or non-incendive (Div 2) Advanced fault isolation at the spur egment Protector in Zone 2/Div. 2 nstruments
More informationPROCESS AUTOMATION. MANUAL Compact Fieldbus Power Hub, Common Interface
PROCESS AUTOMATION MANUAL Compact Fieldbus Power Hub, Common Interface With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for
More informationPROCESS AUTOMATION. MANUAL Z-System. Zener Barriers ISO9001
PROCESS AUTOMATION MANUAL Z-System Zener Barriers ISO9001 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and
More informationFieldLink process networking
FieldLink process networking Enclosures Junction module (JM) StoneL s Junction Module (JM) enclosure is an environmetally hardened platform which is suitable for use in the most extreme corrosive and hazardous
More informationHigh Availability Fieldbus Networks in Hazardous Areas
High Availability Fieldbus Networks in Hazardous Areas Phil Saward MTL Instruments Automation 2011, Mumbai 21 st September 2011 In this presentation Foundation Fieldbus physical layer failure modes Keys
More informationFieldbus Foundation TM Physical Design. Joseph Khoo AP Regional Sales Director R.Stahl
Fieldbus Foundation M Physical Design Joseph Khoo AP Regional Sales Director R.Stahl 1 Fieldbus How is fieldbus different to 4-20mA? Wiring and Interconnection Components opologies Design tools Installation
More informationAssembly. Front view. LED yellow: Relay output. LED red: LB/SC Power Rail
Switch Amplifier Features Assembly -channel isolated barrier 4 V DC supply (Power Rail) Dry contact or NAMUR inputs Relay contact output Line fault detection (LFD) Reversible mode of operation Up to SIL
More informationPROCESS AUTOMATION MANUAL FIELDBUS POWER HUB INVENSYS
PROCESS AUTOMATION MANUAL FIELDBUS POWER HUB INVENSYS Advanced high performance power supplies and conditioner With regard to the supply of products, the current issue of the following document is applicable:
More informationTutorial: Characteristics & Requirements of Physical Networks in the Process Industry
Tutorial: Characteristics & Requirements of Physical Networks in the Process Industry IEEE802.3cg 10 Mb/s Single Twisted Pair Ethernet Task Force Brian Franchuk Martin Zielinski Introduction 2 Pertinent
More informationPROFIBUS and Integrated Safety architectures in Ex areas
PROFIBUS and Integrated Safety architectures in Ex areas Since 1989, PROFIBUS has developed into a worldwide leading fieldbus system used in machine and process plant automation. The main reason why PROFIBUS
More informationFieldIT Multi Barrier NMB204/NMB204-EX (MB 204/MB 204-Ex)
Data Sheet FieldIT Multi Barrier NMB204/NMB204-EX (MB 204/MB 204-Ex) Intrinsically safe power supply of up to 31 stations on the bus cascadable multi barrier Intrinsically safe connection of up to 4 field
More informationAssembly. Front view. LED yellow/red: Status output Ι/ Fault signal Function. Switch Power Rail
Switch Amplifier KCD-SR-Ex.LB Features Assembly -channel isolated barrier V DC supply (Power Rail) Dry contact or NAMUR inputs Usable as signal splitter ( input and outputs) Relay contact output Fault
More information10 Mb/s Single Twisted Pair Ethernet Power Distribution
10 Mb/s Single Twisted Pair Ethernet Power Distribution Supporters: Matthias Wendt, Philips Lennart Yseboodt, Philips Steffen Graber Pepperl+Fuchs IEEE802.3 10 Mb/s Single Twisted Pair Ethernet Study Group
More informationAbout the FLEX Ex I/O Systems
Section 2.1 About the FLEX Ex I/O Systems 1797 FLEX Ex I/O Overview FLEX Ex I/O offer: Adapter Terminal base I/O module Bus connectors Keyswitch FlexBus connectors 24V DC field power Terminal strips FLEX
More informationThe PROFIBUS and PROFINET Company. COMbricks Modules. Copyright 2013 PROCENTEC. All rights reserved.
Modules SCOPE Repeater Module Name 1 Channel RS 485 SCOPE Repeater Type 1 Order code 101 201210 Description 1 Channel RS 485 PROFIBUS SCOPE repeater module with integrated quality oscilloscope for 12 Mbps
More informationMANUAL Surge Protectors
PROCESS AUTOMATION MANUAL Surge Protectors DP-LBF-I1.36.DE and DP-LBF- I1.36.IE With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery
More informationDual Module VCT. 5. Lexan Enclosure is Water & Corrosion Proof Contaminants will not affect the module as long as terminal strip is not immersed.
2 The integrates position sensing, communication electronics, power outputs, auxiliary inputs and wire termination into a fully sealed compact package. The module also integrates a terminal strip directly
More informationABB Fieldbus Infrastructure and Network Devices An overview
ABB Fieldbus Infrastructure and Network Devices An overview ABB ABB fieldbus devices Industrial automation with the fieldbus Fieldbus technology is becoming increasingly important throughout industry.
More informationSeparating and protective. Separating and protective instruments. VEGATRENN 149AEx Separator type KFDO Barrier type Product Information
Separating and protective instruments Separating and protective instruments VEGATRENN 149AEx Separator type KFDO Barrier type 9001 Product Information Content Content 1 Product description..........................................................................
More informationMTL8000-2/x Series Modular I/O
-2/x Series Modular Overview Modules Modules - Overview - 2/2 components Use this option for general purpose or nonhazardous applications, or where the equipment and/or field wiring has to be mounted in
More informationINSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F
PSD1000 - PSD1000F INSTRUCTION MANUAL Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD1000 - Universal AC Input Switching Power Supply 24 Vdc Output ISM0089-4
More informationProudly present. Ethernet to the Field (APL)
Proudly present Ethernet to the Field (APL) 2018 page 1 Supporters l A large collaboration effort in automation supported by: ABB Endress+Hauser Krohne Pepperl+Fuchs Phoenix Contact Rockwell Automation
More informationOperating Instructions. Intrinsically Safe Isolation Relay for Switches Model: REL manual_rel-6_0505
Operating Instructions Intrinsically Safe Isolation Relay for Switches Model: REL-6003 manual_rel-6_0505 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...3 5. Operating
More informationF101, F102, F104. Relcom Installation Instructions. Fieldbus Power Supply F101-PS
F101, F102, F104 Fieldbus Power Supply F101-PS Installation Instructions Relcom www.mtl-fieldbus.com CONTENTS PAGE 1 OVERVIEW 2 2 DESCRIPTION 2 3 COMPONENTS AND ACCESSORIES 2 4 MECHANICAL 3 4.1 Mounting
More informationTURCK Process Automation IS Interface Technology. Interface Modules. IM Series Cabinet
Process Automation IS Interface Technology Interface Modules TURCK's IM series of Isolating Intrinsically Safe Barriers is designed to be a simple and safe way to solve the problems associated with the
More informationCerabar S PMC71, PMP71, PMP ma HART, PROFIBUS PA, FOUNDATION Fieldbus
Safety Instructions PMC71, PMP71, PMP75 4-20 ma HART, PROFIBUS PA, FOUNDATION Fieldbus Ex ia IIC T6 Ga/Gb IECEx KEM06.0011 0 XA00696P-D Safety instructions for electrical apparatus for explosion-hazardous
More informationIEEE Mb/s single twisted pair Ethernet for Process Industry
IEEE 802.3 10 Mb/s single twisted pair Ethernet for Process Industry Harald Mueller, Markus Wucher, Dr. Joerg Haehniche Endress+Hauser Page 1 Purpose Scope Initiate discussion/understanding on typical
More informationPepperl+Fuchs Fieldbus Power Hub for Redundant Fieldbus Power
Pepperl+Fuchs Fieldbus Power Hub for Redundant Fieldbus Power The Fieldbus Power Hub connects to one or two +24 VDC input power supplies and provides redundant fieldbus power to up to four fieldbus segments.
More informationAssembly MAU. MUX 4 Channels 8 Channels Zone 1
Multi-Input/Output Device for Cabinet Installation Features Assembly For discrete inputs and outputs Installation in Zone 1/Div. 1, intrinsically safe Sensors in Zone 0/Div. 1 Connection to fieldbus acc.
More informationAPPLICATION GUIDE. Interface Modules IM Series.
Interface Modules IM Series APPLICATION GUIDE www.turck.com Interface Technology Interface Modules TURCK's IM series of Isolating Intrinsically Safe Barriers is designed to be a simple and safe way to
More informationMANUAL HART Multiplexer System
PROCESS AUTOMATION MANUAL HART Multiplexer System KFD*-HM*-16 ISO9001 3 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for
More informationIntrinsically Safe Barriers
Intrinsically Safe Barriers Description Page No. Safety Barriers 464-472 Din Rail Isolated Barriers 473-488 477 Intrinsically Safe Barriers Product Overview We have simplified intrinsic safety! Cooper
More informationSafety instructions Overvoltage protection B81-35
Safety instructions Overvoltage protection B81-35 IECEx BVS 15.0084X Intrinsic safety Document ID: 51001 Contents 1 Area of applicability... 3 2 General information... 3 3 Technical data... 5 4 Application
More informationPROCESS AUTOMATION INSTALLATION TECHNOLOGY FOR PROFIBUS PA
PROCESS AUTOMATION INSTALLATION TECHNOLOGY FOR PROFIBUS PA SYSTEM OVERVIEW AND CONTENT HOST Plant Communication page 4 with Fieldbus Benefit from the future proof, enabling technology page 12 Segment coupler
More informationInstalling Fieldbus: Some practical advice, Part 1
Installing Fieldbus: Some practical advice, Part 1 By: Mike O Neill, Director, International Sales MooreHawke, a Division of Moore Industries Many automation engineers are coming face to face with real
More informationwww.pepperl-fuchs.com From Industry 4-20 ma to Industrie 4.0 for Process Industries New Ideas for an Ethernet Physical Layer www.pepperl-fuchs.com 2 Field Instrumentation Today Operator Engineering Industrial
More informationFOUNDATION. Product Overview. Foundation Fieldbus
FOUNDATION Product Overview Foundation Fieldbus PROFIBUS PA Process Fieldbus wired infrastructure Control cabinet The Fieldbus (FB ) line of modular fieldbus components offers connectivity from the process
More informationFOUNDATION Fieldbus Fieldbus Basics & its Benefits
FOUNDATION Fieldbus Fieldbus Basics & its Benefits James Loh Yokogawa Engineering Asia On behalf of Fieldbus Foundation TM Vietnam FF Seminar Fieldbus Basics - Agenda 1. H1 Basic Review. 2. H1 Benefits.
More informationAssembly MAU. MUX 4 Channels 8 Channels Zone 1
Multi-Input/Output Device for Cabinet Installation Features Assembly For discrete inputs and outputs Installation in Zone 1/Div. 1, intrinsically safe Sensors in Zone 0/Div. 1 Connection to fieldbus acc.
More informationIECEx Certificate of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Status: Current Page 1 of 5 issue No.:1 Certificate
More informationOperating Instructions
Introduction To protect the signal lines of field devices and systems in the cabinet against lightning. Pepperl+Fuchs covers the complete range of Surge Protection Barriers. Housing types Depending on
More informationMANUAL Functional Safety
PROCESS AUTOMATION MANUAL Functional Safety Switch Amplifier HiC283* ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery
More informationMANUAL Functional Safety
PROCESS AUTOMATION MANUAL Functional Safety Switch Amplifier KFD2-SOT3-Ex*(.LB)(.IO)(-Y1), KFD2-ST3-Ex*(.LB) ISO9001 2 With regard to the supply of products, the current issue of the following document
More informationAppendix B MTL Power Supplies for Intrinsically Safe Fieldbus Applications
Appendix B ML Power Supplies for Intrinsically Safe Fieldbus Applications he ML9121 and the ML9122 Power Supplies can be used to power field devices in hazardous areas for FCO (Fieldbus Intrinsically Safe
More informationAssembly. Front view. LED yellow: Relay output I. LED yellow: Relay output II
Switch Amplifier, Timer Relay Features 1-channel signal conditioner Universal usage at different power supplies 3-wire PNP/NPN sensor or push-pull input 2 relay contact outputs Adjustable energized/de-energized
More informationPHOENIX CONTACT - 05/2007
Ex Universal Module Carrier (Motherboard) for Accommodating 3-Wire Measuring Transducers, Intrinsically Safe, for a Maximum of 8 PI Ex Modules INTERFACE Data Sheet 103030_00_en PHOENIX CONTACT - 05/2007
More informationADAMCZEWSKI. Ordering data AD-STVEX 710 GVD Option: Factory-software configuration as per customer specifications.
EN ADAMCZEWSKI Elektronische Messtechnik GmbH Felix-Wankel-Str. 13 / 74374 Zaberfeld Tel. +49 (0)7046-875 Fax +49 (0)7046-7678 vertrieb@ad-messtechnik.de Operating Instructions Supply Isolation Amplifier
More informationPROCESS AUTOMATION MANUAL. Temperature Trip Amplifier. KFD2-GU-(Ex)1 ISO9001
PROCESS AUTOMATION MANUAL Temperature Trip Amplifier KFD2-GU-(Ex)1 ISO9001 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery
More informationSafety Instructions Cerabar M PMC51, PMP51, PMP55
XA00470P-B/00/EN/14.13 71224652 Products Solutions Services Safety Instructions PMC51, PMP51, PMP55 4-20 ma HART, PROFIBUS PA, FOUNDATION Fieldbus Ex ia IIC T6...T4 Ga/Gb Ex ia IIC T6...T3 Ga/Gb IECEx
More informationMINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description
Repeater power supply, active Data sheet 09_en_0 PHOENIX CONTACT 0--0 Description The. mm wide... repeater power supply supplies transmitters in the field and electrically isolates the input signal from
More informationFLEX Ex Spring Clamp Terminal Base
Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification
More informationHow to calculate an Intrinsically Safe loop approval.
MIE TALK - October 2016 How to calculate an Intrinsically Safe loop approval. EXPLOSIVE ATMOSPHERES Compile by: Gary Friend BSc PrEng, CEng MIET, Sales DirectorExtech Safety Systems (MTL, Beka Associates,
More informationSAFETY MANUAL SIL Switch Amplifier
PROCESS AUTOMATION SAFETY MANUAL SIL Switch Amplifier KCD2-SOT-(Ex)*(.LB)(.SP), KCD2-ST-(Ex)*(.LB)(.SP) ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable:
More informationFB-6SP and FB-12SP. Block device couplers. Data sheet 3177_en_A. 2 Features. 1 Description
Block device couplers Data sheet 3177_en_A 1 Description PHOENX CONTACT 2015-01-20 2 Features The and block couplers provide an interface between the fieldbus trunk cable and field devices on Foundation
More informationInstallation & Operation Manual
Via Enrico Fermi, 2 I-25015 Desenzano del Garda (BS) - Italy Phone: +39 030 7870787 Fax: +39 030 7870777 www.solexy.net BAF Intrinsically Safe Ethernet Coupler for signals operating in Hazardous Areas
More informationSignal processor MS96 for flow sensors MS96-11EX0-R/230VAC
MS96-11EX0-R/230VAC ATEX category II (1) G, Ex Zone 0 ATEX category II (1) D, Ex Zone 20 single-channel signal processor MS96 for connection of an intrinsically safe flow control sensor in zone 0 adjustment
More informationM-series Intrinsically Safe I/O
DeltaV Distributed Control System Product Data Sheet M-series Intrinsically Safe I/O Features full system modularity Reduces system footprint Decreases installation time and expense Plug-and-play installation
More informationSYSTEM DESCRIPTION H-System
PROCESS AUTOMATION SYSTEM DESCRIPTION H-System Isolated Barriers and Termination Boards for Triconex ISO9001 With regard to the supply of products, the current issue of the following document is applicable:
More informationTHE BARRIER and the Universal Barrier Cabinets from Pepperl+Fuchs
THE BARRIER and the Universal Barrier Cabinets from Pepperl+Fuchs Overview This document provides information relating to the use of THE BARRIER HiC2, the SMART universal barrier from Pepperl+Fuchs, a
More informationTemperature Converters
TURCK Interface Technology Temperature measurement is a very common application, even in hazardous areas. The IM34 temperature converting device provides advanced diagnostics, versatility and convenience
More informationMANUAL Functional Safety
PROCESS AUTOMATION MANUAL Functional Safety Frequency Converter with Trip Values KF**-UFC-(Ex)1.D ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable:
More informationSMARTLINE RM76 Supplementary instructions
SMARTLINE RM76 Supplementary instructions 2-wire / Guided Radar (TDR) Level Meter Supplementary Instructions for ATEX applications CONTENTS SMARTLINE RM76 1 General safety information 5 1.1 Scope of the
More informationTerminal Block Catalog Numbers 1719-TB6, 1719-TB6S, 1719-TB8, 1719-TB8S, 1719-TB8Sx2, 1719-TB8x2
Technical Data Communication Adapter Catalog Number 1719-AENTR I/O Module Catalog Numbers 1719-IJ, 1719-IBN8B, 1719-IF4HB, 1719-IR4B, 1719-IT4B, 1719-OB2, 1719-OB2L, 1719-CF4H Power Supply Catalog Number
More informationPROCESS AUTOMATION. MANUAL H-System. Isolated Barriers and Termination Boards ISO9001
PROCESS AUTOMATION MANUAL H-System Isolated Barriers and Termination Boards ISO9001 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of
More informationMANUAL Functional Safety
PROCESS AUTOMATION MANUAL Functional Safety Repeater KFD0-CS-(Ex)*.54*, KFD0-CS-(Ex)*.56* ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable: The
More informationEngineering Guideline. pac-carriers Type for Honeywell system Experion Series C I/O
Engineering Guideline pac-carriers Type 995 for Honeywell system Experion Series C I/O pac-carrier Type 995 Engineering Guideline/Honeywell 04..009 pac-carrier Type 995 Integration of conventional process
More informationFOUNDATION Fieldbus Fieldbus Basics
FOUNDATION Fieldbus Fieldbus Basics Nik Suzaimi Berkat Honeywell Sdn Bhd, MALAYSIA On behalf of Fieldbus Foundation TM End User Seminar 25 Oct 2010 Kuala Lumpur, MALAYSIA Agenda H1 Basic Review. What is
More informationPROCESS AUTOMATION MANUAL. Universal Temperature Converter KCD2-UT2-(Ex)1 ISO9001
PROCESS AUTOMATION MANUAL Universal Temperature Converter KCD2-UT2-(Ex)1 ISO9001 With regard to the supply of products, the current issue of the following document is applicable: The general terms of delivery
More informationSignal conditioning instruments for level switches. Conductive VEGATOR 256C VEGATOR 532 VEGATOR 631. Product Information
Signal conditioning instruments for level switches Conductive VEGATOR C VEGATOR VEGATOR Product Information Content Content Product description..........................................................................
More informationTrendmaster* Galvanic Isolator
162459-01 Trendmaster* Galvanic Isolator Product Datasheet Bently Nevada* Asset Condition Monitoring Description The Trendmaster Galvanic Isolator enables the Trendmaster system to connect to intrinsically
More informationPACSystems* RX3i and Series IC693MDL940 / IC694MDL940
May 2015 PACSystems* RX3i and Series 90-30 IC693MDL940 / IC694MDL940 Output Module, Relay, NO, 2 Amp, 16 Point The Series 90*-30 and PACSystems * MDL940 2 Amp Relay Output module provides 16 normally-open
More informationSafety instructions VEGATOR 121, 122
Safety instructions Intrinsic safety IECEx TUN 14.0005X Document ID: 47471 Contents 1 Area of applicability... 3 2 General information... 3 3 Technical data... 3 4 Installation... 4 Supplementary documentation:
More informationABB Drives. User s Manual Modbus Adapter Module FMBA-01
ABB Drives User s Manual Modbus Adapter Module FMBA-01 Modbus Adapter Module FMBA-01 User s Manual 3AFE68586704 REV A EN EFFECTIVE: 27.06.2005 2005 ABB Oy. All Rights Reserved. 5 Safety instructions
More informationFIELDBUS ENGINEER S GUIDE
PROCESS AUTOMATION FIELDBUS ENGINEER S GUIDE About Pepperl+Fuchs Pepperl+Fuchs is a leading developer and manufacturer of electronic sensors and components for the global automation market. Since more
More informationRSTI-EP Slice I/O. PROFINET Scanner EPXPNS001. GFK-2965C November 2017
November 2017 Ethernet Ports PWR, SF, BF, MT, LINK 1, ACT 1, LINK 2, and ACT 2 LEDs Door for Micro USB Port PROFINET Scanner Power Supply LED RSTI-EP Slice I/O PROFINET Scanner The PROFINET Scanner is
More informationZener Barriers Bulletin 937Z
Technical Data Zener Barriers Bulletin 937Z Topic Page Introduction 2 Mounting 2 Housing 3 Operating Principle 3 Specifications 6 Introduction Allen-Bradley Zener barriers are a cost-effective solution
More informationPROCESS AUTOMATION INSTRUCTION MANUAL FIELDBUS SURGE PROTECTOR F*-LBF-I1.32 F*-LBF-D1.32
PROCESS AUTOMATION INSTRUCTION MANUAL FIELDBUS SURGE PROTECTOR F*-LBF-I1.32 F*-LBF-D1.32 With regard to the supply of products, the current issue of the following document is applicable: The General Terms
More informationMINI MCR-SL-CVS NC
Constant voltage source Data sheet 105264_en_01 PHOENIX CONTACT 2013-04-03 1 Description Configurable constant voltage source for generating highprecision constant voltages. The voltage supply is also
More informationEnclosures for Remote I/O System I.S. 1
STAINLESS STEEL (V2A) STAINLESS STEEL (V4A) POLYESTER RESIN IP66 For Installation in II 2 G EEx e II Increased safety protection Certified according to 94/9EG (ATEX) For Installation in Zone 2 Declaration
More information