Capacitor/Filter-Protection Relay CPR 04
|
|
- Silvia Morgan
- 6 years ago
- Views:
Transcription
1 Capacitor/Filter-Protection Relay CPR 04
2 Capacitor/Filterprotection Relay CPR 04 Introduction The Trench CPR 04 is a comprehensive, numeric protection relay, featuring: Compact draw-out design Panel or 19 inch rack mounting Four software configurable measuring elements Five configurable output relays One self-supervision output relay Operating mode software selectable (NORMAL / H-BRIDGE) RS232 serial data port at the front Software selectable RS232 or RS485 serial data port at the rear Time stamping function for trip history and setting menu Application The CPR 04 provides comprehensive protection for the capacitive, inductive and resistive elements of three phase medium and high voltage shunt capacitor banks and harmonic filter circuits. The capacitor banks may have a single star, double star, delta or H configuration, with internally fused, externally fused or unfused capacitor units. User configurable, to cater for a wide range of relay settings A high performance protection relay for capacitor banks and harmonic filter circuits 2
3 NORMAL MODE - Protective functions Peak repetitive overvoltage protection For each phase, CPR 04 determines the peak repetitive capacitor voltage using advanced Digital Signal Processor (DSP) techniques, by integrating the measured line current waveform, to give a signal representing the voltage waveform applied to the capacitor bank. The peak repetitive voltage of this signal is then extracted, and compared to adjustable thresholds. For calculated peak repetitive voltages above the thresholds, a starter signal is output, and the inverse time ANSI capacitor temporary overvoltage withstand curve respectively adjustable definite timers define the time before trip signals are output. Thermal overcurrent protection For each phase, CPR 04 protects a capacitor bank / harmonic filter circuit from excess thermal current stressing, by modelling the thermal response of the circuit to the rms heating current, Irms. A second order thermal model and associated adjustable heating / cooling time constant is then used to continuously calculate the thermal current response lth, to the rms heating current. Ith is compared to adjustable thresholds, which are linked to adjustable definite timers. Trip signals are output, if the associated threshold is exceeded for the definite time set. Star point unbalance protection CPR 04 measures the star point unbalance current, and calculates the fundamental frequency component, Iub. This can then be compensated, in magnitude and phase angle to zero, to enable detection of further changes, in both magnitude and phase angle, ( Iub). The magnitude is a measure of the change in capacitance in any leg of a double star capacitor bank arrangement, whereas the phase angle indicates the leg in which the change in capacitance has occurred. The magnitude of ( )Iub is continuously compared with adjustable thresholds, each with an adjustable definite timer. Trip signals are output, if the associated thresholds are exceeded for the definite times set. Line current unbalance protection The monitoring of line current unbalance provides a means of detecting changes in impedance resulting from failures and faults within the capacitor bank / harmonic filter circuit. These faults or failures invariably result in an unbalance in the fundamental frequency component of the line currents. CPR 04 calculates the fundamental frequency line current unbalance, Ilub, from the three phase line currents. Ilub is continuously compared with adjustable thresholds each with an adjustable definite timer. Trip signals are output if the associated thresholds are exceeded for the definite times set. The sensitivity of line current unbalance protection is limited by the effect of supply voltage unbalance on the line currents. Nevertheless, line current unbalance protection is useful as back-up protection to star point unbalance protection. 3
4 NORMAL MODE - Protective functions 4 Earth fault protection CPR 04 calculates the fundamental frequency earth fault current, Io, as the magnitude of the vector sum of the three phase line currents. Io is compared with adjustable thresholds each with an adjustable definite timer. Trip signals are output, if the associated thresholds are exceeded for the definite times set. Fundamental frequency overcurrent protection For each phase, CPR 04 calculates the fundamental frequency component, I1, of the line current. I1 is continuously compared with adjustable thresholds each with an adjustable definite timer. Trip signals are output, if the associated thresholds are exceeded for the definite times set. RMS - overcurrent protection For each phase, CPR 04 calculates the rms current, Irms, (fundamental + harmonics up to the 50th). Irms is continuously compared with adjustable thresholds each with an adjustable definite timer. Trip signals are output if the associated thresholds are exceeded for the definite times set. Undercurrent protection For each phase, CPR 04 calculates I1, the fundamental frequency component of the line current. I1 is continuously compared with an adjustable undercurrent threshold, I1<, with an associated adjustable definite timer. With the capacitorbank / harmonic filter circuit breaker on, if the mains power supply fails, as indicated by a drop in I1 below I1< for longer than the definite time set, then the undercurrent trip signal is output. Breaker fail protection If I1 remains above the undercurrent threshold for longer than the adjustable definite time after the breaker switches off, or after a trip output signal has been given by CPR 04, then this indicates a failure of the breaker, and the breaker fail signal is output. This signal can be used trip to an up-stream breaker. Capacitor bank discharge timer CPR 04 provides the necessary logic, and a breaker inhibit output signal, Bena, to inhibit the re-energization of the capacitor bank / harmonic filter circuit breaker, for an adjustable definite time since de-energization Event Trip CPR 04 provides the necessary logic, to trip any of the output relays via a change in the status of the digital input.
5 H-BRIDGE MODE - Protective function H configuration capacitor bank unbalance protection In an alternative user-configurable operating mode, CPR 04 provides fundamental frequency H configuration capacitor bank unbalance protection only. This provides sensitive unbalance protection independently for each phase of a capacitor bank. For each phase the CPR04 calculates the fundamental component of the measured unbalance current. The natural unbalance of each phase can then be compensated in amplitude and phase angle, to detect subsequent changes. ( a/b/c lub) The unbalance current ( )a/b/c lub is then compared to adjustable thresholds, each with an adjustable timer. Trip signals are output, if the thresholds are exceeded for the definite times set. 5
6 Relay design 6 Measuring elements Four current measuring elements are provided within CPR 04. The nominal current (1A/5A) can be set in the menu. Relay outputs CPR 04 has six output relays. The functionality of output relays 1 to 5 is user configurable. The user may program the relays to be manual or selfresetting, and to be normally energized or de-energized during the power-up healthy condition. In addition, the user may direct any of the binary output signals of the protective functions to output relays 1 to 5. Output relay 6 is the self-supervision relay for CPR 04, and is energized in the power-up, normal condition, and de-energizes on loss of auxiliary power supply, or on failure of CPR 04 internal power supply, microprocessor hardware, software or memory. Contact forms Output relays 1 to 6 each have one change-over contact. As default, all output relays are supplied with the normally open (relay de-energized) contacts wired to the terminal block. However, the user can easily change the contacts of the output relays to be as required by the application. Auxiliary power supply A high efficiency, low loss, wide range AC/DC auxiliary power supply is provided within CPR 04. Special care has been taken to minimize the overall standing load of CPR 04 on the DC station batteries or AC busbar voltage supply. The CPR 04 nominal auxiliary power supply voltage is V ac/dc. For the operative range see technical specifications, page 10. Time stamping CPR04 features a built in real time clock which allows to time and date stamp trip events as well as modifications to settings and status registers. The clock is backed up by a maintenance free supercap. Serial data port CPR 04 is provided with a RS232 frontport and a softwareselectable RS232 or RS485 serial data port at the rear for data communications between an intelligent host device and the protection relay. The RS232 port at the front also allows for future firmware upgrades as additional functions and features might be added. The serial data port can be used for the following purposes: Downloading of a set-up file to a CPR 04. Uploading from a CPR 04 of the set-up file currently active within the relay. Uploading from a CPR 04 of any error codes, or alarm and trip annunciation messages. The uploading from a CPR 04 of various instantaneous parameters, measured and calculated by the relay during normal operation. Interconnection into a SCADA system using MODBUS RTU protocol
7 Relay design LED indicators Three LED indicators are provided on the front panel of CPR 04, as follows: Green LED: This indicates that the auxiliary power supply is on, and the self-supervision output relay is energized, indicating that the protection relay is healthy. Yellow LED: This indicates that one (or more) of the starter binary outputs signals of a protection function is (are) at logic 1 (high), and that the protection relay may trip if the condition persists. Red LED: This indicates that a trip condition has occurred that has not yet been reset and / or acknowledged. LCD display A two line, 16 character, full alpha-numeric, back-lit, Liquid Crystal Display (LCD) is provided on the front panel of CPR 04 for the following purposes: During normal operation: The display of various measured and calculated parameters, together with the low-set thresholds associated with these parameters. After a relay trip condition: Annunciation of all the fault conditions after a trip, including the value of the fault currents and voltages at the instant of trip, and the relay trip time after occurance of the fault condition. During relay configuration and normal operation: Display of the current and voltage thresholds and timer settings for each element, and display of each output relay configuration and check-sum. During relay configuration: Interactive configuration of the protection relay During testing: Interactive self testing of the protection relay After failure: Annunciation of any protection relay hardware, software or memory failures detected during self-testing of the protection, by display of the relevant error codes. Test facilities While CPR 04 is in service, it continuously performs various self-testing functions, and if any errors or failures are detected, the corresponding error code(s) will be displayed, and the self-supervision output relay will de-energize, to signal the malfunction. These selftests include tests of the microprocessor, RAM, ROM and EEPROM. In addition, a further set of hardware diagnostic tests may be performed on the protection relay by the user, to test and check the functionality of the measurement offsets for elements 1 to 4, the digital input, relay outputs, keypad, LCD display and LEDs. 7
8 Relay design Housing and terminals CPR 04 is housed in a draw-out chassis within a fixed case. This housing is particularly suitable for both flush mounting and 19 inch rack mounting. The case is designed for indoor use in tropical climate and is designed to withstand shock, vibration and the ingress of dust and moisture. A terminal block, with 28 recessed terminals, is provided on the fixed case. Standard screw terminals, or fast-on connectors, can be used on the terminal block, for the external connections to the protection relay. PC based software package A Windows based software package is available for CPR 04 to exploit its communication facilities. This software package enables the user to create, edit, save, open and print any number of CPR 04 set-up files on a PC, and to download or upload a set-up file to or from a CPR 04, either directly or via MODEM. In addition, all the other facilities and functions of the serial data port, as detailed above, can be exploited using this software package. Digital input CPR 04 is provided with an optically isolated, binary (on / off), voltage input channel. Any voltage from V AC/DC applied to this input channel will signal that the input is active. The functionality of the digital input is depending on the setting in the relevant menu. Withdrawing the protection relay module automatically short circuits the current transformer terminals. Keypad A five button key-pad is provided on the front panel of CPR 04 for the following purposes: Interactive configuration of the protection relay Acknowledgment and resetting of trip conditions 8 Hardware diagnostic testing
9 General characteristics Applicable standard IEC and EN Operating temperature range -10 to +55 C to IEC Storage temperature range -20 to +70 C to IEC Humidity 4 days, 95% RH, with temperature cycled between +25 O C and + 45 O C, to IEC Enclosure degree of protection IP50 to IEC Shock and bump Shock: 15g, 3 pulses per direction, per axis. (total 18 times). Bump : 10g, 1000 pulses per direction, per axis (total 6000 times). To IEC Vibration 9,8ms -2 (1g) constant frequency from 10 to 150 Hz per axis. To IEC Power frequency voltage withstand 2 kv rms 50 Hz for 1 minute, from all terminals to case (earth), and between terminals of independent circuits. 1,5 kv rms across open contacts of output relays. To IEC Impulse voltage withstand 5 kv peak, 1,2/50 µs waveshape, 0,5 J energy content, 10 shots in each polarity, between all terminals and case (earth), and between terminals of independent circuits. To IEC Insulation resistance 50 MΩ minimum at 500 VDC, to IEC Immunity to high frequency 2,5 kv peak between independent circuits, and to case (earth). disturbances 1 kv peak across terminals of the same circuit. (1MHz burst disturbance test) To IEC Immunity to electrostatic 8 kv discharge in air discharges 6 kv point contact discharge (Electrostatic discharge test) To IEC and EN Immunity to fast transient bursts 4kV supply lines / 2kV input & output lines / (Fast transient burst test) 1kV communication lines To IEC and EN Immunity to high frequency 10 V / m, 100% PM, at 900 MHz electromagnetic fields 10 V, 80% AM, from 150 khz to 80 MHz as well as 10 V / m, 80% AM, from 80 MHz to 1000 MHz, to EN Immunity to surge voltages 2kV peak common / 1kV peak differential To EN and EN Immunity to voltage interruptions 230 VAC 100% interruption 200ms 110 VDC 100% interruption 50ms To EN Harmonics and flicker of main current To EN Conducted emissions To EN 50263, from 150 khz to 30 MHz. Radiated emissions To EN 50263, from 30 MHz to 1000 MHz. Nett Mass 3 kg Overall dimensions 103(w) x 177(h) x 248(d) 9
10 Technical specifications Measuring Quantity 4 elements Nominal rated current, In 1A or 5A selectable in the software Continuous current 15A Short time current 300A for 1s Burden <40mΩ Accuracy of measurement +/- 2% of nominal rated current Auxiliary power Nominal rated voltage, Vx V AC / DC supply Operative range AC / DC V AC / V DC Burden with DC supply <14W with all relays and back-light ON Burden with AC supply <24VA with all relays and back-light ON Output relays Quantity Alarm / trip relays: 5 Self-supervision relay: 1 Contact form (per relay) 1 changeover contact (form C), user configurable as N/O or N/C Load Resistive load: Inductive load: (cos = 1) (cos = 0,4 L/R = 7 ms) K1 Rated load 5A at 250 VAC 3,5A at 250 VAC 1A at 220 VDC 0,8A at 220 VDC 3A at 110 VDC 2A at 110 VDC 5A at 48 VDC 4A at 48 VDC Max. operating voltage 380VAC, 250 VDC K2, K3, K4, K5, K6 Rated load 5A at 250 VAC 3,5A at 250 VAC 5A at 30 VDC 2,5A at 30 VDC Rated carry current 5A Max. operating voltage 380VAC, 125 VDC Min. permissible load 100mA at 5 VDC Digital input Quantity 1 channel Function Breaker on; Remote reset; Event trip Isolation Optically isolated Type V AC / DC voltage input Pushbuttons Function >, <, ^,, and ACCEPT (red) Type Miniature spring loaded manual pushbuttons Display Type Back-lit Liquid Crystal Display (LCD), with full alpha-numeric character set Screen Size 16 character x 2 line Character height 4mm Indicators Type Light Emitting Diodes (LEDs) Function Green : POWER ON / HEALTHY Yellow : START (ALARM) Red : TRIP Serial data port Quantity 2 Isolation Optically isolated Frontport type RS232 via DB9 socket Rearport type RS232 or RS485 selectable in the software Baudrate (kbd) 2.4 up to for each port seperatly selectable Real Time Clock Functionality Date; Weekday; HH:MM:SS Accuracy +/- 30 s per month Backup Supercap (>14 days without power) ^ 10
11 Block diagram 11
12 Trench Austria GmbH Paschinger Straße 49 AT-4060 Linz-Leonding/Austria Phone Fax Trench Brasil LTDA Via Expressa de Contagem, 2685 CEP Contagem, Minas Gerais/Brasil Phone Fax Trench China Limited 3658 Jiang Cheng Road Minhang, Shanghai P.R. China Phone Fax Trench France S.A. 16, rue du Général Cassagnou B.P. 70 FR St-Louis/France Phone Fax Trench Germany GmbH Nürnberger Straße 199 DE Bamberg/Germany Phone Fax Trench Italia S.r.l. Strada Curagnata 37 IT Cairo-Montenotte/Italy Phone Fax Trench Limited Coil Product Division 71 Maybrook Drive, Scarborough Ontario, Canada M1V 4B6 Phone Fax Trench Limited Instrument Transformer Division 390 Midwest Road, Scarborough Ontario, Canada M1P 3B5 Phone Fax Trench Switzerland AG Lehenmattstraße 353 CH-4052 Basel/Switzerland Phone Fax ema il Änderungen vorbehalten E 647 Trench (UK) Limited South Drive Hebburn Tyne & Wear NE31 1UW, Great Britain Phone Fax sales.uk@trench-group.com
Residual overvoltage relay
Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one
More informationProtection Relays PHASE & RESIDUAL OVERCURRENT
Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent
More informationSensitive Earth-fault Relay SPAJ 111 C. Product Guide
Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent
More informationFor Transmission, Distribution and Machinery protection.
Founded in 1953, Microelettrica Scientifica has developed a wide range of products, divided into three main lines: For Transmission, Distribution and Machinery protection. A-Line Electronic analogic. M-Line
More informationRT4F-110V/25A RECTIFIER
The RT4F-110V/25A is a hot-pluggable switched mode rectifier (SMR) module designed to provide up to 25A of output current into a 110V nominal system. Examples of such systems are 60 cells lead acid (136V
More informationType MVTT 14 and MVTT 15: Static Digital Time delay relays
Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction
More informationPROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL
MICROPROCESSOR PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL MICROELETTRICA SCIENTIFICA MANUFACTURES A COMPLETE RANGE OF
More informationSM100. On-Line Switchgear Condition Monitoring
On-Line Switchgear Condition Monitoring On-Line Switchgear Condition Monitoring Introduction Weis is a specialist company with over 40 years of experience in the commissioning, testing & maintenance of
More informationCombined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide
Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with
More informationFeeder protection relay SPAA 121 C. Product Guide
Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase
More informationRT4F-48V/50A-WAC RECTIFIER
The RT4F-48V/50A-WAC is a switched mode rectifier (SMR) module designed to provide up to 58A of output current into a 48V nominal system, over a wide range of AC input voltage. This rectifier has been
More informationRT4B-110V/12A RECTIFIER
The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs
More informationReyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy
Reyrolle Protection Devices 7SG118 Argus 8 Voltage & Frequency Relay Answers for energy 7SG118 Argus 8 Voltage and Frequency Relay Data Storage and Communication Serial communications conform to IEC60870-5-103
More informationReyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy
Reyrolle Protection Devices 7SG117 Argus 7 Synchronising Relay Answers for energy 7SG117 Argus 7 Synchronising Relay Fig 1. Independent check & system synchronising settings Adjustable slip frequency,
More informationRT4F-120V/20A-WAC RECTIFIER
The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with
More informationReyrolle Protection Devices. 7SG21 DDB20 Multi Range Digital Setting Time Delay Relay. Energy Management
Reyrolle Protection Devices 7SG21 DDB20 Multi Range Digital Setting Time Delay Relay Energy Management 7SG21 DDB20 Digital Time Delay Induction disc reset emulation Replacement of induction disc timing
More informationEarth-fault Relay SPAJ 110 C. Product Guide
Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral
More informationSIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs
SIPROTEC easy 7SJ4 Numerical Overcurrent Protection Relay Powered by CTs Function overview Fig. /1 Description The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended
More informationCombined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide
Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with
More informationDATASHEET. Ultra Capacitor Charger, UCC-4
DATASHEET Ultra Capacitor Charger, UCC-4 Easy installation Monitoring and surveillance of operation Balancing to save energy 90-450 V DC 3.5A Output Modular Ultra Capacitor system Document no.: 4921260003
More informationDGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field
DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description
More informationArc protection relay. Features Three-phase overcurrent function. Application
Arc protection relay REA 10_ Page 1 Issued: May 1999 Status: New Data subject to change without notice Features Three-phase overcurrent function Loop-type or radial sensor fibre for arc detection Two high-speed
More information1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection
Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output
More informationVoltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice
Issued: July 1998 Status: Revised Version: C/08.10.2003 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
More informationRelion 611 series. 611 series Type Test Certificate
Relion 611 series 611 series Document ID: 1MRS757466 Issued: 2016-02-22 Revision: B Product version: 2.0 Copyright 2016 ABB. All rights reserved Table of contents Table of contents Section 1 Section
More informationRT7-48V/6kW Specification
The RT7-48V/6kW is a 3 phase, active power factor corrected, switched mode rectifier (SMR) module designed to provide up to 6kW of output power (100A nominal) into a 48V nominal system. This rectifier
More informationContact protection relay
Contact protection relay Ordering details SVR 450 08 F0000 The protects sensitive control contacts from excessive load. It can be used with latching function or without. Bounce time of control contacts
More informationSolid-state Timer. Ordering Information. Miniature Timer with Multiple Time Ranges and Multiple Operating Modes H3YN- - Accessories (Order Separately)
Solid-state Timer Miniature Timer with Multiple Time Ranges and Multiple Operating Modes Minimizes stock. Pin configuration compatible with MY Power Relay. Standard multiple operating modes and multiple
More informationRelion 605 series. Self-powered feeder protection REJ603 Product Guide
Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1. Description... 3 2. Relay functions... 3 3. Protection functions... 4
More informationBus Bar Protection Relay B-PRO 4000
Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation
More informationIRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)
IRI1-ES Sensitive Earth Fault Current Relay Manual IRI1-ES (Revision A) Woodward Manual IRI1-ES GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
More informationSolid-state Timer H3YN
Solid-state Timer H3YN Miniature Timer with Multiple Time Ranges and Multiple Operating Modes Minimizes stock. Pin configuration compatible with MY Power Relay. Standard multiple operating modes and multiple
More informationRT12-240V/2.4kW Rectifier Specification
The RT12-240V/2.4kW is a switched mode rectifier (SMR) module that delivers up to 2.4kW of output power (and up to 11A output current) into a 240V nominal DC system. The RT12 suits AC supply voltages between
More informationE P S Y. Earthfault Protection System Electronic-Components
E P S Y Earthfault Protection System Electronic-Components Introduction Basic Units EPSY (Earthfault Protection System) is a new and comprehensive earthfault protection system designed for compensated
More informationSensitive definite time or inverse time earth-fault stage for back-up residual earthfault
Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive
More informationINTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box
INTRODUCTION The PL-50 MO units are available in the next mechanical version: The PL-50 MO and PM-250 families represent the different solutions that Team Arteche offers for motor protection. Both families
More informationINSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1
INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 TOSHIBA Corporation 2004 All Rights Reserved. ( Ver. 1.6 ) Safety Precautions Before using this product, please read this chapter carefully. This
More informationMIN II. Complete numerical ground directional protection. Digital Energy Multilin. Protection and Control. Monitoring and Metering.
MIN II Key Benefits Reduce troubleshooting and maintenance cost - event recording, and analogy/digital oscillography Design flexibility - Easy to use programming logic Access to information - Modbus RTU
More informationwww. ElectricalPartManuals. com l Basler Electric MPS100 MOTOR PROTECTION SYSTEM ADVANTAGES WINDOWS SOFTWARE ADDITIONAL INFORMATION
The Motor Protection System is a microprocessor based digital relay which provides comprehensive motor protection including metering, communications, data recording and diagnostics. ADVANTAGES Extensive
More informationFeeder protection relay SPAA 341 C. Product Guide
Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay
More informationModel Number Structure
Solid State Relays with Failure Detection Function G3PC Detects failures in SSR used for heater temperature control and simultaneously outputs alarm signal. This SSR supports the safe design of heater
More informationFeeder protection relay
Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay modules and a flexible
More informationSynchro-check relay. Application
Issued: April 1999 Status: Updated Version: B/08.11.2001 Data subject to change without notice Features Two identical operation stages allowing the closing conditions of two separate circuit breakers to
More informationG3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend
Solid State Relays with Failure Detection Function G3PC Refer to Warranty and Application Considerations (page 1), Safety Precautions (page 4), and Technical and Safety Information (page 6). Detects failures
More informationNewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators
NewCode Comprehensive Motor Protection and Control Relay Relay Field Input and Output LEDs LED Fault Indicators Configurable Memory Module on a T-Bus IrDA and USB Connectors Profibus Address Indicator
More informationRTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.
Binary Output 23BO62 Characteristics The binary output is made via relay contacts. The 8 outputs are potential isolated against the electronic by optocoupler. All 8 outputs have a separate return. Application
More informationArc protection relay. Features Three-phase overcurrent function. Application
Arc protection relay REA 10_ Issued: May 1999 Status: Updated Version: B/12.11.2001 Data subject to change without notice Features Three-phase overcurrent function Loop-type or radial sensor fibre for
More informationElectronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts
Data sheet Electronic timer CT-SDD. Star-delta change-over with n/o contacts The CT-SDD. is an electronic time relay with star-delta change-over. It is from the CT-D range. With their MDRC profile and
More informationRT9-48V/1.4kW Rectifier Specification
The RT9-48V/1.4kW is a switched mode rectifier (SMR) module that delivers up to 1.4kW of output power (and up to 30A output current) into a 48V nominal DC system. The RT9 suits AC supply voltages between
More informationRM35JA32MR Current control relay 0.15A 15A, 2 C/O
Characteristics Current control relay 0.15A 15A, 2 C/O Main Range of product Product or component type Relay type Relay name Relay monitored parameters Time delay type Switching capacity in VA Measurement
More informationMRA1 Trip circuit supervision. Manual MRA1 (Revision A)
MRA1 Trip circuit supervision Manual MRA1 (Revision A) Woodward Manual MRA1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by
More informationPM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features
PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER The PM174 is a compact, multi-function, three-phase AC powermeter and power quality analyzer specially designed to meet the requirements of users ranging
More informationDirectional or Non-Directional Earth-Fault Relay REJ 527. Product Guide
Directional or Non-Directional Earth-Fault Product Guide Issued: 17.06.19994 Status: Updated Version: C/16.10.2002 Data subject to change without notice Features Directional or non-directional low-set
More informationHigh-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay
High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay IE ON RESET.5 X1 t IE X1.6%.2.4.8 1.6 X1.1s.2.4.8 1.6 X2 OFF ON S1 S2 IRI1-ES IRI1-ES C&S Electric Limited (Protection & Control Division) Contents
More information2C138. Sensitive Earth Fault Relay. Features. Application. Operation
Technical Bulletin 2C138 Sensitive Earth Fault Relay Features High sensitivity (0.1% of I n ) 2 nd & 3rd harmonic & HF noise suppression - tuned to 50 Hz Optional reset functions Instantaneous (Fast),
More informationPowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006
PowerLogic power-monitoring units Technical data sheet 2006 Functions and characteristics E90463 The PowerLogic PM500 Power Meter provides all measurement capabilities required to monitor an electrical
More informationEM132 EM132. Main Features. Multi-functional 3-Phase Transducer. Energy Meter
EM132 MULTI-FUNCTION TRANSDUCER SATEC EM132 is a Smart DIN Rail Multi-Function Transducer with a local display. It is based on SATEC s best seller PM130 PLUS with an off-the-shelf LCD display (similar
More informationElectronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact The CT-EBD.12 is an electronic time relay with the function flasher starting with ON. It is from the CT-D range.
More information2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation
2T15 Multi Range Digital Setting Time Delay Relay Technical Bulletin Features Four time ranges -.99s, -9.9s, -99s, -99s High accuracy & repeatability timing compensated for output relay delay Time settings
More informationSEL-734B Data Sheet. Advanced Monitoring and Control System. Major Features and Benefits
Advanced Monitoring and Control System Compact Enclosure Full-Size Enclosure Major Features and Benefits The SEL-734B combines volt/var based capacitor bank control with power quality monitoring and advanced
More informationFP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay
FP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay The power of fusion. 1874 1886 1893 1899 1906 1908 1911 1934 1962 1963 1976 1983 1990 1999 There s a certain energy at Eaton.
More informationRE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O
Characteristics Star-Delta Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts
More informationData Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D
WPM 770 Data Sheet 679.D.141.02 Digital Multifunctional Power Meter with LCD Display and Application The digital Weigel Power Meters WPM 770 have been designed to display the electrical parameters in low
More informationXU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)
XU1-E Earth fault voltage relay (August 1996) Manual XU1-E (Revision New) Woodward Manual XU1-E GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
More informationRE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O
Characteristics star-delta timing relay - 230VAC/440VAC - 1 C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts type
More informationElectronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts
Data sheet Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts The CT-APS.21 is an electronic timer from the CT-S range with OFF-delay. It provides 10 time ranges and a continuous rated control
More informationMRC1800H SERIES. Output. Features
DS11. MRC18H SERIES 18W TELECOM RECTIFIERS Output 33A, 48V/54V 56A, 24V/27V Features 91% efficiency including series output diode High power density 242mW/cm 3, 4.W/in 3 Power Factor Corrected to EN61-3-2
More information02/11/2015
DIN Rail Mount 22.5 mm TU2R1 Part number 88865305 Product with 1 relays (88 865 100/103/105/115/125/135/145/155/185/503) : Replaced by the 17,5 mm range For instance : previous part number 88 865 XXX /
More informationPMC 530 Series Advanced Multifunction Meter
IEC 62053 22 Class 0.5S WF Capture @ 128 samples/cycle WF and Data Recording Harmonics & Transient Monitoring I residual Monitoring Setpoint Alarms, SOE Log RS 485 and I/O Capabilities Large, Bright, Backlit
More informationRE22R2QTMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O
Characteristics StarDelta Timing Relay 0.05s 300h 24 240V AC/DC 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Zelio Time Modular timing
More informationMiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays
01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety
More informationMiCOM P124 T&D. Self and Dual Powered Overcurrent Relays
PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can
More informationwww. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES
Protective Relays Electrical Apparatus Capacitor Bank Protection Relay 165-440-900 Figure 1: Edison Idea Relay The capacitor bank protection relay is a member of Cooper Power Systems Edison Idea TM line
More information7SR45 Argus 7SR45 Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault Relay
7SR5 Argus 7SR5 Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault Relay Energy Management 7SR5 Argus 7SR5 Argus Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault
More informationElectronic timer CT-ARS.11
2CDC 251 088 F0t07 Features Rated control supply voltage 24 240 V AC/DC Single function OFF delay timer without auxiliary voltage One device includes 7 time ranges (0.05 s 10 min) 1 c/o (SPDT) contact
More informationTU531, TU532 Terminal Unit
Ordering Data DATA SHEET TU531, TU532 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 217 200 R0001 1SAP 217 000 R0001 1SAP 417 000 R0001 TU531, terminal unit, 230 VAC,
More informationSolid-state Timer. Ordering Information. Specifications. Miniature Timer Compatible with the MY Relay. Accessories. Time Ranges
Solid-state Timer Miniature Timer Compatible with the MY Relay Large transparent time-setting knob facilitates time setting. Flat-blade and Phillips screwdrivers can also be used for time setting. Approved
More informationSyr-line TMR48D Digital Timer
yr-line MR48D Digital imer Front Panel 48x48 (1/16 DIN) Large LED or LCD creen (13.2 mm) Multi-function and single-function Basic & Advance configuration modes Multi-range (0.05 s 9999 h) Multi-voltage
More informationRelays for Various Protection Applications / 7SV600
Relays for Various Protection Applications / SV00 SIPROTEC SV00 numerical circuit-breaker failure protection relay Fig. 0/ Description SIPROTEC SV00 numerical circuit-breaker failure protection relay The
More informationTransformer Protection Relay
Transformer Protection Relay T-PRO Product Overview The IEC 61850 station bus embedded T-PRO relay provides complete three-phase multi-winding transformer protection and overload protection, DFR-quality
More informationRE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O
Characteristics Off-delay Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts
More information7SR18 Solkor Line Differential Protection Energy Management
Reyrolle Protection Devices 7SR18 Solkor Line Differential Protection Energy Management 7SR18 Solkor five or eight user-programmable binary output contacts and three or six user programmable status inputs
More informationSwitching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers
Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers Switching Control Sentinel (SCS) for circuit breakers Voltage and current transients generated during switching
More informationElectronic timer CT-ERS.21
2CDC 251 057 F0t07 Features Rated control supply voltage 24 240 V AC/DC Single function ON delay timer One device includes 10 time ranges (0.05 s 300 h) 2 c/o contacts 2 LEDs for status indication Width
More informationThermistor motor protection relays CM-MSS.12 and CM-MSS.13
Data sheet Thermistor motor protection relays CM-MSS.12 and CM-MSS.13 The thermistor motor protection relays CM-MSS.12 and CM-MSS.13 monitor the winding temperature of motors and protect them from overheating,
More informationFP-5000 Feeder Protection
Effective: April 2001 Page 1 New Information FP-00 Feeder Protection Contents Description Page FP-00 Description......... 2 Application Description...... 2 Features, Functions and Benefits..............
More informationTM221M16R controller M IO relay
Product data sheet Characteristics TM221M16R controller M221 16 IO relay Complementary Main Discrete I/O number 16 Number of I/O expansion module Supply voltage limits Inrush current Power consumption
More informationRE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O
Characteristics On-delay Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts
More informationMillenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types
Millenium 3 General Characteristics Millenium 3 Compact Range Millenium 3 Expandable Range Millenium 3 Communication Options Millenium 3 Range General environment characteristics for CB, CD, XD, XR and
More informationFeeder Protection Relay REF 610. Product Guide
Product Guide Contents 1 Description.............................. 3 2 Protection functions....................... 3 3 Measurement............................ 4 4 Disturbance recorder......................
More informationElectronic timer CT-AHD.22
2CDC 251 093 F0t06 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied
More informationIndustrial Power Supplies
50-600 Watt Features Switch mode power supplies for DIN-rail mounting 6 power ranges with 2, 3, 6, 12, 20 and 24 A output current (24 VDC models) Selectable 115/ 230 VAC input Very low ripple and noise
More informationTable 1 Relay Model and Function
FEATURES Numerical autoreclosing function Single-shot, single-phase and/or three-phase autoreclose scheme for one or two circuit breakers Multi-shot (selectable between 2 and 4) threephase autoreclose
More informationTF501, TF521 Terminal Bases
Ordering Data DATA SHEET TF501, TF521 Terminal Bases 1 Ordering Data Part No. Scope of delivery Product life cycle status 1SAP 117 000 R0271 1SAP 317 000 R0271 1SAP 117 200 R0271 1SAP 317 200 R0271 TF501-CMS,
More informationVoltage Transducer UMT516 / MT516
Voltage Transducer UMT516 / MT516 True RMS AC voltage measurements Voltage auto range measurements up to 600V # Wide frequency measurement range 16 400 Hz High accuracy class 0.2 (IEC-688), 0.1 on communication
More informationElectronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts
Data sheet Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts The CT-ARS.21 is an electronic timer from the CT-S range with true OFF-delay. It provides 7 time ranges
More informationElectronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact The CT-ARS.11 is an electronic timer from the CT-S range with true OFF-delay. It provides 7 time ranges
More informationPart No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version
Ordering Data DATA SHEET TU520 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 214 400 R0001 1SAP 414 400 R0001 TU520-ETH, PROFINET I/O terminal unit, 24 VDC, spring
More informationThermistor motor protection relays CM-MSS.12 and CM-MSS.13
Data sheet Thermistor motor protection relays CM-MSS.12 and CM-MSS.13 The thermistor motor protection relays CM-MSS.12 and CM-MSS.13 monitor the winding temperature of motors and protect them from overheating,
More informationBinary output and supervision 520CSD01 Data sheet
RTU520 product line Binary output and supervision 520CSD01 Data sheet R01 C01 O01 R02 O02 RTU I/O bus ERR Microcontroller RAM Flash IOC Output register DC DC (1 out of n) check Output state monitoring
More information