Transformer Protection IED

Size: px
Start display at page:

Download "Transformer Protection IED"

Transcription

1 Transformer Protection IED

2 GR-00 series - The GR-00 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive hardware and modular software combinations facilitating an application oriented solution. Meeting your needs - Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements. Future upgrade paths and minor modifications are readily achievable on demand. Powerful and wide application - In addition to protection & control, GR-00 has been designed to meet the challenges and take advantage of developments in information & communications technology. Process bus capability and teleprotection based upon packet-based communications are just two of the features of GR-00. APPLICATION GRT00 transformer protection is implemented on Toshiba s next generation GR-00 series IED platform and has been designed to provide comprehensive protection and control applications for transformers in all types of network. This powerful and user-friendly IED will provide you with the flexibility to meet your application and engineering requirements in addition to offering outstanding performance, high quality and operational peace of mind. - Current differential protection is applied for fast and selective main protection for two-winding or three-winding power transformers, auto-transformers and generatortransformer units. This protection requires no interposing CTs and provides stability against magnetizing inrush, overexcitation and CT saturation. - Restricted earth fault protection incorporating enhanced stability against CT saturation detects internal earth faults where the transformer star point is directly or low impedance earthed. - Comprehensive back up protections - Communications Within a substation automation system or to a remote control centre, IEC [Station bus],

3 FEATURES Application - Application for two-winding or three-winding power transformers, auto-transformers and generator-transformer units. - Current differential protection is applied for fast and selective main protection. This protection requires no interposing CTs and provides stability against magnetizing inrush, overexcitation and CT saturation. - Restricted earth fault protection detects internal earth faults where the transformer star point is directly or low impedance earthed and can be applied on high-voltage and low-voltage sides respectively. - Time-overcurrent protection is mainly used as backup protection and can be applied on high- and low-voltage sides respectively. - Thermal overload protection protects the transformer against thermal stress and provides two independently set levels for alarm and tripping. GRT00 can be applied to the various kinds of transformer configuration as per the transformer configuration and applicable model: V Configuration Analog inputs Model I I x three-phase CT + x one-phase VT GRT00--* Functionality - Eight settings groups - Automatic supervision - Metering and recording functions - Time synchronization by external clock such as IRIG-B and system network Communication - System interface RS45, Fiber optic, 00BASE-TX,-FX - Protocol IEC 650 Security - Password protection Flexibility - Various models and hardware options for flexible application depending on system requirement and controlled object - Mixed A / 5A phase and neutral current inputs - Phase and neutral CT polarity settings - Multi range DC power supply: 4 to 4V / 4 to 0 V / 0 to 40V - Multi-language options - Configurable binary inputs and outputs - Programmable control, trip and alarm logic with PLC tool software Human Machine Interface - Graphical LCD and 4 LEDs - configurable function keys - USB port for local PC connection - Direct control buttons for open/close (O/I) and control authority (43R/L) - Help key for supporting operation - Monitoring terminals for testing V In I In In3 3 x three-phase CT + 3 x zero-phase CT + x one-phase VT / GRT00--* I I3 V In I I In In3 I3 3 x three-phase CT + 3 x zero-phase CT + x three-phase VT GRT00-3-*

4 FUNCTIONS Protection - Current differential protection for two or three winding transformers (DIF) incorporating stability against inrush, over-excitation and CT saturation - No interposing CTs required - Mixed A/5A inputs for phase and neutral currents - CT ratio, vector and zero-sequence compensation - Restricted earth fault protection (REF) incorporating enhanced stability against CT saturation - Breaker failure protection (CBF) - Overcurrent protection for phase faults (OC) - Non-directional overcurrent protection for earth faults using neutral current (EFIn) - Directional / nondirectional overcurrent protection for earth faults using phase currents (EF) - Negative phase sequence overcurrent protection (OCN) - Thermal overload protection (THM) - Broken conductor protection (BCD) - Inrush current detector (ICD) - Overexcitation protection (VPH) - Residual overvoltage protection (OVG) - Under/over frequency and rate of change of frequency protection (FRQ) - Trip and/or Indication of external devices (MECH. TRIP) Monitoring - Plausibility check - Measurement s of I, V, f - Current and voltage circuit supervision - Trip circuit supervision (TCS) - HMI function - Selection of HMI: Standard LCD / large LCD / Separate large LCD - Large LCD supports single line diagram indication and touch-type operation or multi-language option - 4 configurable tri-state LEDs selectable red/green/yellow - Programmable function keys for user configurable operation - Recording - Fault record - Event record - Disturbance record - Communication - System interface RS45, Fiber optic, 00BASE-TX,-FX - Protocol IEC General functions - Eight settings groups - Automatic supervision - Time synchronization by external clock using IRIG-B or system network - Password protection for settings and selection of local / remote control - Checking internal circuit by forcible signal - Checking internal circuit using monitoring jacks APPLICATIONS PROTECTION Current Differential Protection (DIF) GRT00 provides fast, selective protection for two and three winding transformers. It has three phasesegregated differential elements (DIF-Stage ), each with a dual-slope, percentage differential characteristic as shown in Figure. GRT00 also provides high-set unrestrained differential elements (DIF-Stage ). 3

5 I d DIF- S-I I B I A I C I d = I res Operating zone Small current characteristic (DIF-S-Slope= 5-50%) 0 DIF-S-I I d: Differential REF_DIF current ( I A + I B + I C ) I res: Restraining current ( I A + I B + I C ) DIF-S-I: Minimum operating value DIF-S-I: Knee point Large current characteristic (DIF-S-Slope = 5-00%) I res Figure : DIF-Stage characteristic The small current characteristic provides sensitivity to low level faults. For higher level faults, the large current characteristic with increased bias compensates for the effects of CT saturation. Furthermore, GRT00 provides a CT saturation countermeasure function against a very large through-fault current. GRT00 incorporates internal CT ratio and vector compensation, so that the relay requires no interposing CTs. Mixed A/5A inputs for phase currents are available. CT polarities for each three-phase CT can be set flexibly within GRT00 in accordance with external physical connections to each three-phase CT. During periods of transformer energization, the use of a second harmonic restraint method blocks the relay operation. neutral point current, restricted earth fault protection (REF) provides a highly sensitive differential protection for earth faults in a transformer which has a star point directly earthed or low impedance earthed. The REF-DIF element has a dual slope, percentage characteristic as shown in Figure and the independent elements can be applied for each transformer winding. I 0d REF- -I 3I 0 I N Operating zone REF- -Slope = 0% I 0d = I res REF- -Slope = 50 00% REF- -I I od: Residual differential current ( 3I 0 + I N ) I res: Restraining current (Max( I A, I B, I C, I N )) REF- -I: Minimum operating value REF- -I: Knee point ( : P, S, T) Figure : REF-DIF characteristic The REF provides a directional check element REF-DEF to discriminate between internal and external faults to enhance stability against CT saturation as shown in Figure 3. The REF_DEF characteristic consists of both of the characteristics as shown in Figure 4 (a) and (b). REF_DIF REF_DEF internal fault detection Ires.0 Max_kct & & I res REF When the transformer is overexcited due to a transient power system disturbance, the use of a fifth harmonic restraint method blocks the relay operation. [REF_DEF] ON OFF Figure 3: REF block diagram GRT00 also provides high-set unrestrained differential elements (DIF-Stage) and ensures rapid clearance of heavy internal faults. GRT00 provides differential current supervision functions for T elements to monitor erroneous differential current under normal conditions. Restricted Earth Fault Protection (REF) Employing residual current of each winding and I 0 I N Operating zone ik (Fixed) (a) Directional characteristic 0 Figure 4: REF-DEF characteristic ik (Fixed) (b) Non directional characteristic 3I 0 4

6 Mixed A/5A inputs for phase and neutral currents are available. CT polarities for each neutral CT can be set flexibly within GRT00 in accordance with external physical connections to each neutral CT. Breaker Failure Protection (CBF) When an overcurrent element remains in operation longer than a pre-determined length of time following the output of a trip signal the associated circuit breaker is judged to have failed and adjacent circuit breakers can be tripped as a back-up measure. can be blocked by a binary input signal. GRT00 provides up to 4 non-directional overcurrent protections (EFIn) with inverse time and definite time for earth faults which can be applied flexibly for each transformer winding, utilizing neutral current values observed. GRT00 also provides up to directional or non-directional overcurrent protections (EF) with inverse time and definite time for earth faults which can be applied flexibly for each transformer winding, utilizing residual current values calculated by phase currents observed. Two independent timers are available, one of which can be used to control the RETRIP of the original circuit breaker(s). The second timer is used to control the back-tripping of adjacent circuit breakers. For high-speed protection, an overcurrent element with high-speed reset time is used to prevent a spurious re-trip or back-trip following a successful trip or re-trip action. Overcurrent Protection (OC / EFIn / EF) GRT00 provides up to directional or non-directional overcurrent protections (OC) with inverse time and definite time for phase faults which can be applied flexibly for each transformer winding. Inverse time overcurrent protection consists of an IDMT (inverse definite minimum time) element. IDMT is available in conformity with the IEC standard which encompasses both the IEC and IEEE/ANSI standard characteristics as shown in Figure 3. Alternatively, a user-configurable curve may be created. The IDMT element has a programmable reset feature, selectable for instantaneous, definite time or dependent time operation. This feature can be used to protect against flashing/intermittent fault conditions, or to grade correctly with electromechanical overcurrent relays. Definite time overcurrent protection is enabled by the instantaneous overcurrent element and pickup-delay timer. Tripping by each element can be disabled by the scheme switches, and overcurrent backup protection Figure 5: Characteristics of inverse time delayed overcurrent element Negative Phase Sequence Overcurrent Protection (OCN) Up to 4 negative phase sequence overcurrent protections (OCN) can be applied flexibly for each 5

7 transformer winding. OCN can be used in applications where certain fault conditions may not be detected by the normal phase and earth overcurrent protections, for example, in the case of a relay applied on the delta side of a delta-star transformer, to detect an earth fault on the star side. Thermal Overload Protection (THM) The thermal overload feature provides protection for cables and other plant against the effects of prolonged operation under excess load conditions. A thermal replica algorithm is applied to create a model for the thermal characteristics of the protected plant. Tripping times depend not only on the level of overload current, but also on the level of prior load current, the thermal replica providing memory of previous conditions. The thermal characteristics of the system are defined by entering settings for full load current and thermal time constant. The GRT00 issues a trip in accordance with the cold and hot curves specified in IEC to prevent the protected system from exceeding its thermal capacity. The cold curve tripping times are applicable when the system is first energized, while the hot curves are relevant when the system has already been carrying some prior load for a period of time. An alarm output is also available to give early warning of high load current, set as a percentage of thermal capacity. Broken Conductor Detection (BCD) GRT00 provides up to 3 broken conductor detections (BCD). Detects unbalance conditions in each transformer winding caused by an open circuited conductor. An unbalance threshold with programmable definite time delay is provided. Inrush Current Detector (ICD) The inrush current detector (ICD) is used to prevent an incorrect operation of the aforementioned OC, EF, OCN and BCD against a magnetizing inrush current during transformer energization. ICD detects second harmonic inrush currents during transformer energization. Overexcitation Protection (VPH) provided. The alarm is definite time delayed whilst the characteristic may be selected as either having a definite time or an inverse time delay as shown in Figure 6. V/Hz VPH-H VPH-L VPH-A 0 TVPHA Figure 6: VPH characteristic Zero Phase Sequence Overvoltage Protection (OVG) Up to 4 zero phase sequence overvoltage protections (OVG) are provided for detection of earth faults in high impedance earthed or isolated systems. OVG can be programmed with definite time delays, and one stage is also available with an inverse delay. The zero sequence voltage may be derived from the phase voltages, or directly measured. Suppression of superimposed 3rd harmonic components of the supply voltage is included. Under/Over Frequency and Rate of Change of Frequency Protection (FRQ) GRT00 provides up to 6 stage frequency protections where over/under frequency protections or rate-of-change-of-frequency protections can be selected flexibly. VPH-HT TVPHH VPH-L: VPH-H: VPH-LT: VPH-HT: TVPHH: VPH-A: TVPHA: VPH-LT These protections provide independent frequency protection stages. The over/under frequency protection is programmable for either under- or over-frequency operation, and each has an associated delay timer. The rate-of-change-of-frequency protection calculates the gradient of frequency change (df/dt). Low level i.e. Pick up level High level i.e. Definite time tripping level Operate time at low level Operate time at high level Definite time delay at high level Alarm level Definite time delay for alarm sec (log T) Alarms and tripping for overexcitation, based on a measurement of the voltage/frequency ratio are 6

8 Trip and/or Indication of External Devices (MECH. TRIP) through binary input circuits. Logic can be arranged for alarms, event recording and tripping. Up to 6 external signals such as overpressure devices and Buchholz relay operations can be applied HMI FUNCTION Front Panel GRT00 provides the following front panel options. - Standard LCD - Large LCD (optional separate LCD type is also available) The standard LCD panel incorporates the user interfaces listed below. Setting the relay and viewing stored data are possible using the Liquid Crystal Display (LCD) and operation keys. - characters, lines LCD with back light - Support of English language The large LCD panel incorporates a touch type screen for control and navigation purposes character, 40 line LCD with back light - Support of multi-languages (0 characters and 6 lines LCD for multi-languages) The local human machine interface includes an LCD which can display the single line diagram for the bay. The local human machine interface is simple and easy to understand with the following facilities and indications. - Status indication LEDs (IN SERVICE, ERROR and 4 configurable LEDs) - Function keys for control, monitoring, setting group change and screen jump functions of which operation is configurable by the user - Test terminals which can monitor three different signals from the front panel without connection to the rear terminals. - USB port Local PC Connection The user can communicate with GRT00 from a local PC via the USB port on the front panel. Using GR-00 series engineering tool software (called GR-TIEMS), the user can view, change settings and monitor real-time measurements. Figure : HMI Panel (large LCD type) MONITORING Metering The following power system data is measured continuously and can be displayed on the LCD on the relay fascia, and on a local or remotely connected PC. - Measured analog voltages, currents, frequency. The accuracy of analog measurement is ±0.5% for I, V, at rated input and ±0.03Hz for frequency measurement. Status Monitoring The open or closed status of each switchgear device and failure information concerning power apparatus and control equipment are monitored by GRT00. Both normally open and normally closed contacts are used to monitor the switchgear status. If an unusual status is detected, a switchgear abnormality alarm is generated.

9 RECORDING Event Record Continuous event-logging is useful for monitoring of the system from an overview perspective and is a complement to specific disturbance recorder functions. Up to,04 time-tagged events are stored with ms resolution. Fault Record Information about the pre-fault and fault values for currents and voltages are recorded and displayed for trip event confirmation. The most recent time-tagged faults with ms resolution are stored. Fault record items are as follows. - Date and time - Faulted phase - Phases tripped - Tripping mode - Pre-fault and post-fault current and voltage data (phase, phase to phase, symmetrical components) Disturbance Record The Disturbance Recorder function supplies fast, complete and reliable information for disturbances in the power system. It facilitates understanding of system behavior and performance of related primary and secondary equipment during and after a disturbance. The Disturbance Recorder acquires sampled data from all selected analogue inputs and binary signals. The data can be stored in COMTRADE format. COMMUNICATION Station Bus Ethernet port(s) for the substation communication standards IEC 650 is provided for the station bus. GENERAL FUNCTION Self Supervision Automatic self-supervision of internal circuits and software is provided. In the event of a failure being detected, the ALARM LED on the front panel is illuminated, the UNIT FAILURE binary output operates, and the date and time of the failure is recorded in the event record. Time Synchronization Current time can be provided with time synchronization via the station bus by SNTP (Simple Network Time Protocol) with the IEC 650 protocol. IRIG-B port is also available as an option. Setting Groups settings groups are provided, allowing the user to set one group for normal conditions, while the other groups may be set to cover alternative operating conditions. Password Protection Password protection is available for the execution of setting changes, executing control, clearing records and switching between local/remote control. Simulation and Test GRT00 provides simulation and test functions to check control functions without modification to wiring provided by a dummy circuit breaker (virtual equipment), and the capability to test communication signals by forced signal status change. The simulation and test can work on in the test mode only.

10 TOOLS & ACCESSORY The PC interface GR-TIEMS allows users to access GRT00 and other Toshiba GR-00 series IEDs from a local personal computer (PC) to view on-line or stored data, to change settings, to edit the LCD screen, to configure sequential logics and for other purposes. LCD configuration The user can configure and customize the MIMIC data displayed on the LCD of GRT00 using GR-TIEMS software. Remote Setting and Monitoring The engineering tool supports functions to change settings and to view and analyze fault and disturbance records stored in GRT00. Waveform data in the disturbance records can be displayed, edited, measured and analyzed in detail. An advanced version of the engineering tool can provide additional and powerful analysis tools and setting calculation support functions. Figure : PC Display of MIMIC configuration Programmable Logic Editor The programmable logic capability allows the user to configure flexible logic for customized application and operation. Configurable binary inputs, binary outputs and LEDs are also programmed by the programmable logic editor. This complies with IEC63-3 standard. Figure : PC Display of GR-TIEMS Figure 0: PC display of PLC editor

11 TECHNICAL DATA HARDWARE Analog Inputs Rated current In Rated voltage Vn Rated Frequency Overload Rating Burden Power Supply Current inputs Voltage inputs Phase current inputs Earth current inputs Sensitive earth fault inputs Voltage inputs Rated auxiliary voltage Superimposed AC ripple on DC supply 5% Supply interruption Restart time Power consumption Binary Inputs Input circuit DC voltage Capacitive discharge immunity Maximum permitted voltage Power consumption Binary Outputs Fast operating contacts: Make and carry Break Operating time A / 5A (selectable by user) 00V to 0V 50Hz / 60Hz (selectable by user) 4 times rated current continuous 5 times rated current for 3 mins 6 times rated current for mins times rated current for 0 sec 00 times rated current for second 50 times rated current for one power cycle (0 or 6.6ms) times rated voltage continuous.5 times rated voltage for second 0.VA at In = A, 0.VA at In = 5A 0.3VA at In = A, 0.4VA at In = 5A 0.3VA at In = A, 0.4VA at In = 5A 0.VA at Vn 4/4/60Vdc (Operative range:. Vdc), 4/0Vdc (Operative range: 3.4 3Vdc), 0/50Vdc or 5/0Vac (Operative range: 0Vdc or 0 Vdc) 0ms at 0Vdc < minutes 5W (quiescent) 5W (maximum) 4/4/60Vdc (Operating range:. Vdc), 4/0Vdc (Operating range: 3.4 3Vdc), 0/5/0/50Vdc (Operating range: 0Vdc) Note: Variable threshold settings are available for BI from 4V to 54V in various steps. 0μF charged to maximum supply voltage and discharged into the input terminals, according to ENA TS 4-4 with an external resistor Vdc for 4/4/60Vdc rating, 0Vdc for 0/50Vdc rating 0.5W per input at 0Vdc 5A continuously A, 0Vdc for 0.s (L/R=5ms) 0.5A, 0Vdc (L/R=40ms) Typically 3 ms 0

12 Semi-fast operating contacts: Make and carry Break Operating time Auxiliary contacts: Make and carry Break Operating time Hybrid contacts (0 A breaking): Make and carry Break Operating time Durability Measuring input capability Full scale Standard current input Sensitive current input Voltage input Sampling rate Frequency response Mechanical Design Installation Weight Case colour A continuously A, 40Vdc for s (L/R=5ms) 0.A, at 50Vdc (L/R=40ms) 0.A, at 0Vdc (L/R=40ms) Typically 6 ms A continuously A, 40Vdc for s (L/R=5ms) 0.A, at 50Vdc (L/R=40ms) 0.A, at 0Vdc (L/R=40ms) Typically ms A continuously 0A, 0Vdc for 0.5s (L/R=5ms) 0A, 0Vdc (L/R=0ms) 0A, 0Vdc (L/R=40ms) ms 0,000 operations (loaded contact) 00,000 operations (unloaded contact) 60A (A rating) or 0A (5A rating) 3A (A rating) or 5 A (5A rating) 00V 4 samples / cycle < 5% deviation over range 6.Hz to 600Hz Flush mounting Approx. kg (/ size), 5kg (3/4 size), 5kg (/ size).5y.5/ (approximation to Munsell value) LED Number Color Function keys Number Local Interface USB Maximum cable length System Interface (rear port) 00BASE-TX Physical medium 00BASE-FX Physical medium Protocol Serial communication (rear port) RS45 6 (Fixed for In service and ERROR ) Red / Yellow / Green (configurable) except In service (green) and Error (red) Type B m (max.) Fast Ethernet Twisted pair cable, RJ-45 connector Fast Ethernet 50/5 or 6.5/5 m fibre, SC connector IEC 650 or Modbus RTU IEC or Modbus RTU Fiber optical IEC

13 Terminal Block CT/VT input Binary input, Binary output M3.5 Ring terminal (ring lug type terminal only) Compression plug type terminal with 5mm stripping length M3.5 Ring terminal (ring lug type terminal) Compression type terminal Ring lug type terminal

14 FUNCTIONAL DATA Current differential protection (T) Stage : Biased current differential element Minimum operating value (DIF-S-I) Small current region slope (DIF-S-Slope) Large current region slope (DIF-S-Slope) Knee point (DIF-S-I) nd harmonic sensitivity for Inrush currents (DIF-f) 5th harmonic sensitivity for Overexcitation (DIF-5f) Operate time 0.0 to.00pu in 0.0pu steps 0 to 00% in % steps 0 to 00% in % steps.00 to 0.00pu in 0.0pu steps 0 to 50% in % steps 0 to 00% in % steps Typical 5ms Stage : High-set unrestrained differential element Overcurrent (DIF-S-I) Operate time Restricted earth fault element (N) [Low-impedance scheme] Minimum operating value (REF- -I) Small current region slope (REF- -Slope) Large current region slope (REF- -Slope) Knee Point (REF- -I) : P, S, T Phase Overcurrent Protection (50P, 5P) st, nd, 3 rd, 4 th Definite time overcurrent threshold st, nd, 3 rd, 4 th Inverse time overcurrent threshold.00 to 0.00pu in 0.0pu steps Typical 0ms 0.05 to 0.50pu in 0.0pu steps 0 % 50 to 00% in % steps 0.50 to.00pu in 0.0pu steps 0.0 to 50.00A in 0.0A steps (A rating) 0.0 to 50.00A in 0.0A steps (5A rating) 0.0 to 5.00A in 0.0A steps (A rating) 0.0 to 5.00A in 0.0A steps (5A rating) Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-EI / US-CO / US-CO / Original Drop-out/pick-up ratio DTL delay IDMTL Time Multiplier Setting TMS Reset type Reset definite delay Reset Time Multiplier Setting RTMS 0 to 00% in % steps 0.00 to 0.00s in 0.0s steps 0.00 to in 0.00 steps Definite Time or Dependent Time 0.00 to 0.00s in 0.0s steps 0.00 to in 0.00 steps 3

15 Non-directional and Directional Earth Fault Protection (50N, 5N, 50G, 5G, 6N) st, nd, 3 rd, 4 th Definite time earth fault threshold 0.0 to 50.00A in 0.0A steps (A rating) 0.0 to 50.00A in 0.0A steps (5A rating) st, nd, 3 rd, 4 th Inverse time earth fault threshold 0.0 to 5.00A in 0.0A steps (A rating) 0.0 to 5.00A in 0.0A steps (5A rating) Direction characteristic Characteristic angle Polarising voltage (3V0) Non Directional / Forward / Backward 0 to 0 in steps (3I0 lags for 3V0) 0.5 to 00.0V in 0.V steps Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-EI / US-CO / US-CO / Original Drop-out/pick-up ratio DTL delay IDMTL Time Multiplier Setting TMS Reset type Reset definite delay Reset Time Multiplier Setting RTMS 0 to 00% in % steps Negative Phase sequence overcurrent Protection (46) 0.00 to 0.00s in 0.0s steps 0.00 to in 0.00 steps Definite Time or Dependent Time 0.00 to 0.00s in 0.0s steps 0.00 to in 0.00 steps st, nd, 3 rd, 4 th Definite time NOC threshold 0.0 to 50.00A in 0.0A steps (A rating) 0.0 to 50.00A in 0.0A steps (5A rating) st, nd, 3 rd, 4 th Inverse time NOC threshold 0.0 to 5.00A in 0.0A steps (A rating) 0.0 to 5.00A in 0.0A steps (5A rating) Direction characteristic Characteristic angle Polarising voltage Non Directional / Forward / Backward 0 to 0 in steps (3I0 lags for 3V0) 0.5 to 5.0V in 0.V steps Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-EI / US-CO / US-CO / Original Drop-out/pick-up ratio DTL delay IDMTL Time Multiplier Setting TMS Reset type Reset definite delay Reset Time Multiplier Setting RTMS Thermal Overload Protection (4) Thermal setting (THM = k.iflc) Time constant (τ) Thermal alarm Pre-load current setting Broken conductor protection (46BC) Broken conductor threshold DTL delay Inrush Current Detection Second harmonic detection Inrush current thresholds CBF Protection (50BF) Overcurrent element BF timer for retry-trip of failed breaker BF timer for related breaker trip 0 to 00% in % steps 0.00 to 0.00s in 0.0s steps 0.00 to in 0.00 steps Definite Time or Dependent Time 0.00 to 0.00s in 0.0s steps 0.00 to in 0.00 steps A in 0.0A steps (A rating).0 0.0A in 0.A steps (5A rating) mins in 0.min steps OFF, 50% to 00% in % steps A in 0.0A steps (A rating) A in 0.A steps (5A rating) 0.0 to.00 in 0.0 steps 0.00 to 0.00s in 0.0s steps 0 to 50% in % steps 0.0 to 5.00A in 0.0A steps (A rating) 0.5 to 5.0A in 0.A steps (5A rating) 0. to.0a in 0.A steps (A rating) 0.5 to 0.0A in 0.A steps (5A rating) 50 to 500ms in ms steps 50 to 500ms in ms steps 4

16 Zero Phase Sequence Overvoltage (5N) Delay type Drop-out/pick-up ratio DTL delay IDMTL Time Multiplier Setting TMS Reset delay Overexcitation Protection (4) Pickup voltage Alarm level (A) High level (H) Low level (L) LT (Definite time) HT (Definite time) TVFH (Definite time) TVFA (Definite time) Start time RT (Definite time) Frequency Protection (U/O).0 0.0V in 0.V steps DTL, IDMT, Original 0 to 00% in % steps 0.00 to 0.00s in 0.0s steps 0.00 to in 0.00 steps 0.0 to 0.0s in 0.s steps 00.0 to 0.0V in 0.V steps.03 to.pu in 0.0pu steps.0 to.40pu in 0.0pu steps.05 to.pu in 0.0pu steps to 600s in s steps to 600s in s steps to 600s in s steps to 600s in s steps less than ms 60 to 3600s in s steps st - 6 th under/overfrequency threshold (F nom 0.00Hz) (F nom 0.00Hz) in 0.0Hz steps F nom: nominal frequency DTL delay: Frequency UV Block s in 0.0s steps V in 0.V steps st - 6 th rate-of-change frequency threshold Hz/s in 0.Hz/s steps Metering Function Current Voltage Frequency Time Synchronisation Protocol Accuracy 0.5% (at rating) Accuracy 0.5% (at rating) Accuracy 0.03Hz SNTP 5

17 ENVIRONMENTAL PERFORMANCE Atmospheric Environment Temperature IEC / IEC Humidity IEC IEC Operating range: -0 C to +55 C. Storage / Transit: -5 C to +0 C. Cyclic temperature test as per IEC days at 40 C and 3% relative humidity. Cyclic temperature with humidity test as per IEC Enclosure Protection IEC 605 IP5 - Dust and Dripping Water Proof IP0 for rear panel Mechanical Environment Vibration IEC Response - Class Endurance - Class Shock and Bump IEC Shock Response Class Shock Withstand Class Bump Class Seismic IEC Class Electrical Environment Dielectric Withstand IEC kvrms for minute between all terminals and earth. kvrms for minute between independent circuits. kvrms for minute across normally open contacts. High Voltage Impulse IEC IEEE C3.0 Voltage Dips, Interruptions, Variations and Ripple on DC supply IEC 6055-, IEC , IEC IEC Ed 3 Three positive and three negative impulses of 5kV(peak),./50 s, 0.5J between all terminals and between all terminals and earth.. Voltage dips: 0 % residual voltage for 0 ms 40 % residual voltage for 00 ms 0 % residual voltage for 500 ms. Voltage interruptions: 0 % residual voltage for 5 s 3. Ripple: 5 % of rated d.c. value, 00 / 0 Hz 4. Gradual shut-down / start-up: 60 s shut-down ramp, 5 min power off, 60s start-up ramp 5. Reversal of d.c. power supply polarity: min Capacitive Discharge ENA TS 4-4 0μF charged to maximum supply voltage and discharged into the input terminals with an external resistance 6

18 Electromagnetic Environment High Frequency Disturbance / Damped Oscillatory Wave IEC Class 3, IEC IEC Ed 3 Electrostatic Discharge IEC Class 4, IEC IEEE C IEC Ed 3 Radiated RF Electromagnetic Disturbance Radiated RF Electromagnetic Disturbance Fast Transient Disturbance IEC , IEC Level 3 IEC Ed 3 IEEE C IEC IEC IEC Ed 3 Surge Immunity IEC IEC IEC Ed 3 MHz burst in common / differential modes Auxiliary supply and I/O ports:.5 kv / kv Communications ports: kv / 0 kv Contact:, 4, 6, kv Air:, 4,, 5kV Sweep test ranges: 0 MHz to GHz and.4 GHz to. GHz. Spot tests at 0, 60,, 450, 00, 50 and 50 MHz. Field strength: 0 V/m Field strength 35V/m for frequency sweep of 5MHz to GHz. 5 khz, 5/50ns disturbance Auxiliary supply and input / output ports: 4 kv Communications ports: kv./50µms surge in common/differential modes: Auxiliary supply and input / output ports: 4,,, 0.5 kv /, 0.5 kv Communications ports: up to, 0.5 kv / 0 kv Surge Withstand IEEE C kV, MHz damped oscillatory wave Conducted RF Electromagnetic Disturbance Power Frequency Disturbance Power Frequency Magnetic Field Conducted Radiated Emissions and IEC IEC IEC Ed 3 IEC IEC IEC Ed 3 IEC Class 4 IEC Ed 3 IEC EN 550 Class A, EN IEC Ed 3 4kV, 5/50ns fast transient Sweep test range: 50 khz to 0MHz Spot tests at and 6 MHz. Voltage level: 0 V r.m.s 50/60 Hz disturbance for 0 s in common / differential modes Binary input ports: 0 V / 50 V Field applied at 50/60Hz with strengths of: A/m continuously, 0A/m for second. Conducted emissions: 0.5 to 0.50MHz: <db (peak) or <66dB (mean) 0.50 to MHz: <3dB (peak) or <60dB (mean) Radiated emissions to MHz: < 40 db(uv/m) to 000 MHz: < 4 db(uv/m) Measured at a distance of 0 m

19 Performance and Functional Standards Category Standards General Common requirements IEC Data Exchange IEC / IEEE C3. (COMTRADE) IEEE C3-3 (COMFEDE) Product Safety IEC Functional Synchronizing IEC Under/Over Voltage Protection IEC Under/Over Power Protection IEC Thermal Protection IEC Over/Under Current Protection IEC Directional Current Protection IEC Reclosing IEC Frequency Protection IEC Teleprotection IEC European Commission Directives 004/0/EC Compliance with the European Commission Electromagnetic Compatibility Directive is demonstrated according to generic EMC standards EN and EN , and product standard IEC /5/EC Compliance with the European Commission Low Voltage Directive for electrical safety is demonstrated according EN

20 ORDERING INFORMATION A B C D E F G H J K L Configurations G R T Analog inputs x three-phase CT + x one-phase VT (Module No. 35) Outline Standard LCD /3 x rack Flush mounting Large LCD /3 x rack Flush mounting 5 Standard LCD /3 x rack Rack mounting (*) E Large LCD /3 x rack Rack mounting (*) H Rated Phase Currents (Default settings) (*) A 5A Rated Neutral Currents (Default settings) None 0 See page (*) For rack panel mounting, accessories of joint kits are available. (See Figure 5, page-3) (*) Please refer to page 6 and select the appropriate CT configuration when you require another rated current configuration.

21 A B C D E F G H J K L Configurations G R T Analog inputs 3 x three-phase CT + 3 x zero-phase CT + x one-phase VT (Module No. 44) Outline Standard LCD / x rack Flush mounting Standard LCD 3/4 x rack Flush mounting 3 Standard LCD / x rack Flush/rack mounting 4 Large LCD / x rack Flush mounting 6 Large LCD 3/4 x rack Flush mounting Large LCD / x rack Flush/rack mounting Standard LCD / x rack Rack mounting (*) F Standard LCD 3/4 x rack Rack mounting (*) G Large LCD / x rack Rack mounting (*) J Large LCD 3/4 x rack Rack mounting (*) K Rated Phase Currents (Default settings) (*) A 5A Rated Neutral Currents (Default settings) (*) A 5A See page (*) For rack panel mounting, accessories of joint kits are available. (See Figure 5, page-3) (*) Please refer to page 6 and select the appropriate CT configuration when you require another rated current configuration. 0

22 A B C D E F G H J K L Configurations G R T DC rating 0-40 Vdc/Vac 4-0 Vdc 4-4 Vdc 3 BI/BO Module Refer to Number of BI/BO Table Number of Serial and/or Ethernet Communication and/or Time Sync Port(s) port port + GPS port + IRIG-B 3 ports 4 ports + GPS 5 ports + IRIG-B 6 3 ports 3 ports + GPS 3 ports + IRIG-B Selection of Serial and/or Ethernet Communication Port(s) 00Base-TX x port (When position E = - 3 ) 3 00Base-FX x port (When position E = - 3 ) 4 00Base-TX x ports (When position E = 4-6 ) 5 00Base-FX x ports (When position E = 4-6 ) 6 RS45 x port + 00Base-TX x port (When position E = 4-6 ) RS45 x port + 00Base-TX x ports (When position E = - ) RS45 x port + 00Base-FX x port (When position E = 4-6 ) RS45 x port + 00Base-FX x ports (When position E = - ) Fiber optic (for serial) + 00Base-TX x port (When position E = 4-6 ) Fiber optic (for serial) + 00Base-TX x ports (When position E = - ) Fiber optic (for serial) + 00Base-FX x port (When position E = 4-6 ) Fiber optic (for serial) + 00Base-FX x ports (When position E = - ) A B C D E F G H Function Block (linked with software selection) See function table of software selection BI/BO Terminal Type Compression plug type terminal 0 Ring lug type terminal Rated Frequency (Default setting) 50Hz 60Hz

23 CT configuration Rated phase currents x three-phase CT (When position = ) CT group (Ia, Ib, Ic) CT group (Ia, Ib, Ic) Ordering No. (Position K ) A A 5A 5A A 5A A 5A A J 3 x three-phase CT (When position = ) CT group (Ia, Ib, Ic) CT group (Ia, Ib, Ic) 3CT group (3Ia, 3Ib, 3Ic) Ordering No. (Position K ) A A A 5A 5A 5A A A 5A 6 A 5A A A A 5A 5A E 5A A A J 5A A 5A N 5A 5A A S Rated neutral currents (When position = ) Ordering No. (Position L ) NCT NCT 3NCT A A A 5A 5A 5A A A 5A 6 A 5A A A A 5A 5A E 5A A A J 5A A 5A N 5A 5A A S

24 Independent BI Independent BI (variable) Common BI DC-AI Fast-BO Semi-fast BO BO Hybrid BO DC-AO Independent BI Independent BI (variable) Common BI DC-AI Fast-BO Semi-fast BO BO Hybrid BO DC-AO Number of BI/BO Note: module names for compression plug type to be added letter A at the end. Ex. BIOA, BIOA, BIA, BOA, etc. x I/O module Number of BI/BO Ordering No. (Position A to B ) Configuration xbio xbio xbio xbio xbi xbi xbi3 Other Configuration ZZ To be specified at ordering x I/O module (Set code position to other than ) Number of BI/BO Ordering No. (Position A to B ) Configuration xbi3+xbo xbi3+xbio xbi3+xbio xbi+xbo xbi+xbio xbi+xbio xbo+xbio xbio+xbio xbo+xbio 6 4 A xbio3 Other Configuration ZZ To be specified at ordering 3

25 Independent BI Independent BI (variable) Common BI DC-AI Fast-BO Semi-fast BO BO Hybrid BO DC-AO Independent BI Independent BI (variable) Common BI DC-AI Fast-BO Semi-fast BO BO Hybrid BO DC-AO 3 x I/O module (Set code position to other than.) Number of BI/BO Ordering No. (Position A to B ) Configuration xbo+xbio+xbio xbo+xbio+xbio xbio+xbio xbi+xbo+xbio xbi3+xbo+xbio xBIO xbi+xbo+xbio xbi+xbo A xbi+xbo B xbi+xbo+xbio C xbi3+xbio+xbo D xbi3+xbo+xbio E xbi3+xbo+xbo G xbo+xbio H xbi3+xbo+xbio J xbo+xbio3+xbi K xbi3+xbo Other Configuration ZZ To be specified at ordering 4 x I/O modules (Set code position to 3, 4,,, G or K.) Number of BI/BO Ordering No. (Position A to B ) Configuration xbi+xbo+xbio xBIO xbi3+xbo+xbio xbi3+xbo xBI+xBO xbi3+xbo+xbio +xbio xbo+xbi+xbo +xbio xbo+xbio+xbio B xbi+xbo+xbio3 Other Configuration ZZ To be specified at ordering 4

26 Independent BI Independent BI (variable) Common BI DC-AI Fast-BO Semi-fast BO BO Hybrid BO DC-AO Independent BI Independent BI (variable) Common BI DC-AI Fast-BO Semi-fast BO BO Hybrid BO DC-AO 5 x I/O modules (Set code position to 3, 4,,, G or K.) Number of BI/BO Ordering No. (Position A to B ) Configuration xbi+xbio+xbio3 +xbo xbi+xbo+xbio xbi+3xbi3+xbio xBI3+xBO+xBIO xBI+xBO+xBIO xBI+xBO+xBIO B 3xBI3+xBO Other Configuration ZZ To be specified at ordering 6 x I/O modules (Set code position to 3, 4,,, G or K.) Number of BI/BO Ordering No. (Position A to B ) Configuration xbi+xbo+xbio +xbio xBI3+xBO+xBIO xBI3+xBO xBI3+xBO+xBIO xbi+xbio3+xbo A xbi+xbo+xbio B xbi+4xbo C xbi+xbi3+xbo Other Configuration ZZ To be specified at ordering 5

27 Independent BI Independent BI (variable) Common BI DC-AI Fast-BO Semi-fast BO BO Hybrid BO DC-AO Independent BI Independent BI (variable) Common BI DC-AI Fast-BO Semi-fast BO BO Hybrid BO DC-AO x I/O modules (Set code position to 4 or.) Number of BI/BO Ordering No. (Position A to B ) Configuration xBI+xBO+xBIO xBI+xBO+xBIO xBI3+3xBO+xBIO xBI3+3xBO+xBIO xBI+xBO+xBO xBI3+xBO B 3xBI + xbi3 + xbo D 4xBI3+3xBO Other Configuration ZZ To be specified at ordering x I/O modules (Set code position to 4 or.) Number of BI/BO Ordering No. (Position A to B ) Configuration xBI3+3xBO xBI+xBO+xBO xBI3+3xBO+xBIO C xbi3 Other Configuration ZZ To be specified at ordering Please contact with our sales staffs when you require other configuration (number: ZZ) that is not indicated in the ordering sheet above. 6

28 [Software Ordering] S G T E F U V Configurations G R T Analog inputs Assignment on position Function Block Refer to Function Table Number of Serial and/or Ethernet Communication and/or Time Sync Port(s) Assignment on position E Selection of Serial and/or Ethernet Communication Port(s) Protocol Assignment on position F IEC 650 Outline Assignment on position Language English E

29 x three-phase CT + x one-phase VT 3 x three-phase CT + 3 x zero-phase CT + x one-phase VT FUNCTION TABLE Function Block DIF () REF (N) OC (50/5/6) EF (50G/5G/ 6G) EFIn (50N/5N) OCN (46) BCD (46BC) THM (4) Description Current differential protection Low-impedance restricted earth fault protection Non-directional definite / inverse time overcurrent protection Directional definite / inverse time overcurrent protection Non-directional definite / inverse time earth fault protection (using phase currents) Directional definite / inverse time overcurrent protection (using phase currents) Non-directional definite / inverse time earth fault protection (using neutral current) Non-directional negativesequence overcurrent protection Directional negative- sequence overcurrent protection Broken conductor protection Thermal overload protection stages stages 4 stages 4 stages THM trip THM alarm Ordering No. (Position 'G & T') A B ICD Inrush current detector function CBF (50BF) Circuit breaker failure protection CBF re-trip CBF trip - OVG (5G) Residual overvoltage protection 4 stages (#) - (#) FRQ/DFRQ (U/O) VPH (4) MECH. TRIP Under-frequency / Over-frequency / Rate of change of frequency protection Over-excitation protection Trip and/or Indication of external devices 6 stages V/f trip V/f alarm 3 stages (*) - (*) (*) - (*) (*) (*) Available for phase-to-phase or phase-to-ground voltage inputs (#) Available for zero-sequence voltage input Basic Standard

30 DIMENSION AND PANEL CUT-OUT (/3 size) (Panel cut-out) Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit. Figure Dimension and Panel Cut-out /3 x case size (when compression plug type terminals are applied) - -

31 DIMENSION AND PANEL CUT-OUT (/3 size) (Panel cut-out) Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit. Figure Dimension and Panel Cut-out /3 x case size (when ring lug type terminals are applied) - -

32 DIMENSION AND PANEL CUT-OUT (/ size) (Panel cut-out) Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit. Figure Dimension and Panel Cut-out / x case size (when compression plug type terminals are applied) - 3 -

33 DIMENSION AND PANEL CUT-OUT (/ size) (Panel cut-out) Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit. Figure Dimension and Panel Cut-out / x case size (when ring lug type terminals are applied) - 3 -

34 DIMENSION AND PANEL CUT-OUT (3/4 size) (Panel cut-out) Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit. Figure 3 Dimension and Panel Cut-out 3/4 x case size for flush mounting type (when compression plug type terminals are applied)

35 DIMENSION AND PANEL CUT-OUT (3/4 size) (Panel cut-out) Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit. Figure 3 Dimension and Panel Cut-out 3/4 x case size for rack mounting type (when ring lug type terminals are applied)

36 DIMENSION AND PANEL CUT-OUT (/ size) (Panel cut-out) Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit. Figure 4 Dimension and Panel Cut-out / x case size for flush mounting type (when compression plug type terminals are applied)

37 DIMENSION AND PANEL CUT-OUT (/ size) (Panel cut-out) Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit. Figure 4 Dimension and Panel Cut-out / x case size for rack mounting type (when ring lug type terminals are applied)

38 RACK MOUNTING JOINT KITS ATTACHMENT <Panel mounting kits only for compressed terminal type racks> Name Code Joint kits for single /3 x size rack EP-0 Joint kits for two /3 x size racks EP-0 Joint kits for three /3 x size racks EP-03 Joint kits for single / x size rack EP-04 Joint kits for two / x size racks EP-05 Joint kits for single 3/4 x size rack EP-06 EP-04 (single / x size rack) EP-05 (two / x size racks) Figure 5 Joint kits example for rack panel mounting - 3 -

39 - 3 - CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE) BI A BI 3 4 BI 5 6 BI3 BI4 0 BI5 3 4 BI BI6 5 6 BI BI BI0 3 4 BI 5 6 BI BI3 BI4 3 3 BI BI BI6 3 3 BI BI A BI 5 6 BI BI3 BI4 3 4 BI5 BI BI6 5 6 BI BI 3 3 BI BI 3 3 BI BI3 A BI BI 3 BI3 4 BI4 5 BI5 6 BI6 BI BI BI 0 BI0 BI BI 3 BI3 4 BI4 5 BI5 6 BI6 BI BI BI BI0 3 BI 4 BI 5 BI3 6 BI4 BI5 BI6 BI BI 3 BI 3 BI 33 BI3 34 BI3 BO A BO0 BO(*) BO(*) 3 4 BO3(*) 5 6 BO4(*) BO5(*) 0 BO6(*) BO 3 4 BO 5 6 BO BO 3 4 BO 5 6 BO3 BO4 BO5 3 3 BO BO BO 3 3 BO A BO(*3) BO(*3) 3 4 BO3(*3) 5 6 BO4(*3) BO5(*3) 0 BO6(*3) BO(*3) 3 4 BO(*3) 5 6 BO(*3) BO0(*3) BO(*3) 3 4 BO(*3) 5 6 BO3(*3) BO4(*3) BO5(*3) 3 3 BO6(*3) (*) Semi-fast BO (*3) Hybrid BO Figure 6 Binary input board and binary output module (for compression plug type terminal)

40 - 3 - CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE) BIO A BO(*) 5 6 BO(*) BO3(*) BO4(*) 3 4 BO5(*) 5 6 BO6(*) BO BO 3 3 BO BI 3 4 BI 5 6 BI3 BI4 0 BI5 3 4 BI BI BO0 BIOA BO(* BO(* BO3(* 3 3 BO BO5 BI 3 4 BI 5 6 BI3 BI4 0 BI5 3 4 BI BI6 5 6 BI BI BI0 3 4 BI 5 6 BI BIO3A BO(*) BO(*) 3 4 BO3(*) 5 6 BO4(*) BO5(*) BO6(*) 3 3 BO BO BI 3 4 BI 5 6 BI3 BI4 0 BI5 3 4 BI BI6 5 6 BI BIO4A BO BO BI 3 4 BI 5 6 BI3 BI4 0 BI5 BI6 BO(*3) BO(*3) BO3(*3) 3 4 BO4(*3) 5 6 BO5(*3) BO6(*3) (*) Fast BO (*) Semi-fast BO (*3) Hybrid BO Figure Combined binary input and output module (for compression plug type terminal)

41 CONNECTIONS DIAGRAM (COMPRESSION PLUG TYPE) PWS A 4 FAIL 3 0 FAIL DC/DC Protective Earth Figure DC/DC module (for compression plug type terminal)

42 - 4 - CONNECTIONS DIAGRAM (RING TYPE) BI A B BI A B BI A3 B3 BI3 A4 B4 BI4 A5 B5 BI5 A B BI A6 B6 BI6 A B BI A B BI A0 B0 BI0 A B BI A B BI A3 B3 BI3 A4 B4 BI4 A5 B5 BI5 A B BI A6 B6 BI6 A B BI BI A B BI A3 B3 BI A4 B4 BI3 A6 B6 BI4 A B BI5 A0 B0 BI A B BI6 A B BI A3 B3 BI A5 B5 BI0 A6 B6 BI A B BI BI3 A B A B A BI B BI A BI3 B BI4 A3 BI5 B3 BI6 A4 BI B4 BI A5 BI B5 BI0 A6 BI B6 BI A BI3 B BI4 A BI5 B BI6 A BI B BI A0 BI B0 BI0 A BI B BI A BI3 B BI4 A3 BI5 B3 BI6 A4 BI B4 BI A5 BI B5 BI A6 BI3 B6 BI3 BO BO(*) A B BO(*) A B BO3(*) A3 B3 BO4(*) A4 B4 BO5(*) A5 B5 BO6(*) A6 B6 BO A B BO A B BO A B BO0 A0 B0 BO A B BO A B BO3 A3 B3 BO4 A4 B4 BO5 A5 B5 BO6 A6 B6 BO A B BO A B BO BO(*3) A B BO(*3) A B BO3(*3) A3 B3 BO4(*3) A4 B4 BO5(*3) A5 B5 BO6(*3) A6 B6 BO(*3) A B BO(*3) A B BO(*3) A B BO0(*3) A0 B0 BO(*3) A B BO(*3) A B BO3(*3) A3 B3 BO4(*3) A4 B4 BO5(*3) A5 B5 BO6(*3) A6 B6 (*) Semi-fast BO (*3) Hybrid BO Figure Binary input board and binary output module (for ring type terminal)

43 CONNECTIONS DIAGRAM (RING TYPE) BIO BIO BIO3 BIO4 A B BI A B BI A B BI A B BI A B BI A B BI A B BI A B BI A3 B3 BI3 A3 B3 BI3 A3 B3 BI3 A3 B3 BI3 A4 B4 BI4 A4 B4 BI4 A4 B4 BI4 A4 B4 BI4 A5 B5 BI5 A5 B5 BI5 A5 B5 BI5 A5 B5 BI5 A6 B6 BI6 A6 B6 BI6 A6 B6 BI6 A6 B6 BI6 A B BO(*) BO(*) BI A B A B A B A B A B BI BI BI A B A B BI BI (*3) BO (*3) BO A B A0 B0 BO3(*) BO4(*) BO5(*) A0 B0 A B A B A0 B0 A B A B BI0 BI BI BO(*) BO(*) BO3(*) A0 B0 A B A B (*3) BO3 (*3) BO4 (*3) BO5 A B A B A3 B3 BO6(*) A3 B3 BO(*) A3 B3 BO4(*) A3 B3 (*3) BO6 A4 B4 BO BO BO A4 B4 A5 B5 A6 B6 A A BO(*) BO3(*) BO4 A4 B4 A5 B5 A6 B6 A A BO5(*) BO6(*) BO A4 B4 A5 B5 A6 B6 A A BO BO A6 B6 A A B B BO0 B B BO5 B B BO B B (*) Fast BO (*) Semi-fast BO (*3) Hybrid BO Figure 0 Combined binary input and output module (for ring type terminal) - 4 -

Multi Function Protection IED

Multi Function Protection IED Multi Function Protection IED GR-200 series - The GR-200 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing a platform for

More information

- Control and monitoring of switchgear, transformers and other equipment or devices in EHV, HV, MV and LV substations

- Control and monitoring of switchgear, transformers and other equipment or devices in EHV, HV, MV and LV substations Bay Control IED GR-200 series - The GR-200 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing a platform for distributed

More information

General catalog. Copyright 2017 Toshiba Energy Systems & Solutions Corporation. All rights reserved.

General catalog. Copyright 2017 Toshiba Energy Systems & Solutions Corporation. All rights reserved. General catalog 72-34, Horikawa-cho, Saiwai-ku, Kawasaki 212-8585, Japan Tel +81-44-331-1462 Fax +81-44-548-9540 http://www.toshiba-relays.com - The information provided in this catalog is subject to change

More information

GRT100 FEATURES APPLICATION

GRT100 FEATURES APPLICATION FEATURES Fully numerical transformer protection Current differential protection for two-winding or three-winding transformers High-set differential overcurrent protection No interposing CTs required CT

More information

General catalog. Energy Systems & Solutions Company A2. Copyright 2017 Toshiba. All rights reserved.

General catalog. Energy Systems & Solutions Company A2. Copyright 2017 Toshiba. All rights reserved. General catalog Energy Systems & Solutions Company 72-34, Horikawa-cho, Saiwai-ku, Kawasaki 212-8585, Japan Tel +81-44-331-1462 Fax +81-44-548-9540 http://www.toshiba-relays.com - The information provided

More information

GRD110 FEATURES APPLICATION

GRD110 FEATURES APPLICATION FEATURES Overcurrent protection for phase and earth faults with IDMTL or DTL. Three instantaneous elements with DTL. Programmable reset characteristics. Sensitive earth fault protection (SEF). Restricted

More information

- Control and monitoring of switchgear, transformers and other equipment or devices in EHV, HV, MV and LV substations

- Control and monitoring of switchgear, transformers and other equipment or devices in EHV, HV, MV and LV substations Bay Control IED GR-200 series - The GR-200 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing a platform for distributed

More information

GRE120. Motor Protection and Control for MV Systems

GRE120. Motor Protection and Control for MV Systems Motor Protection and Control for MV Systems FEATURES Overcurrent protection for phase and earth faults (50/51P, 50/51N). Dependent and independent time characteristics (IDMTL and DTL). Restricted earth

More information

General catalog AP. Copyright 2014 Toshiba. All rights reserved.

General catalog AP. Copyright 2014 Toshiba. All rights reserved. General catalog 72-34, Horikawa-cho, Saiwai-ku Kawasaki-shi, Kanagawa 212-8585, Japan Tel +81-44-331-1462 Fax +81-44-548-9540 http://www.toshiba-relays.com - The information provided in this catalog is

More information

GRD130 - FEATURES APPLICATION

GRD130 - FEATURES APPLICATION FEATURES Phase undervoltage protection with IDMTL or DTL. Phase overvoltage protection with IDMTL or DTL. Zero phase sequence overvoltage (neutral voltage displacement) protection with IDMTL/DTL. Negative

More information

Multi Function Protection IED

Multi Function Protection IED Multi Function Protection IED GR-200 series - The GR-200 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing a platform for

More information

Busbar Protection IED

Busbar Protection IED Busbar Protection IED GR-00 series - The GR-00 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing a platform for distributed

More information

GRE130. Protection and Control for MV Systems

GRE130. Protection and Control for MV Systems Protection and Control for MV Systems FEATURES Phase undervoltage protection with IDMTL or DTL(27). Phase overvoltage protection with IDMTL or DTL(59). Zero phase sequence overvoltage (neutral voltage

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 TOSHIBA Corporation 2004 All Rights Reserved. ( Ver. 1.6 ) Safety Precautions Before using this product, please read this chapter carefully. This

More information

GRE160. Transformer Protection

GRE160. Transformer Protection Transformer Protection FEATURES Fully numerical transformer protection Current differential protection for two-winding transformers with inrush restraint (87T) High-set differential overcurrent protection

More information

Table 1 Relay Model and Function

Table 1 Relay Model and Function FEATURES Numerical autoreclosing function Single-shot, single-phase and/or three-phase autoreclose scheme for one or two circuit breakers Multi-shot (selectable between 2 and 4) threephase autoreclose

More information

Transformer Protection Relay

Transformer Protection Relay Transformer Protection Relay T-PRO Product Overview The IEC 61850 station bus embedded T-PRO relay provides complete three-phase multi-winding transformer protection and overload protection, DFR-quality

More information

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Relion 605 series. Self-powered feeder protection REJ603 Product Guide Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1. Description... 3 2. Relay functions... 3 3. Protection functions... 4

More information

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Type MVTT 14 and MVTT 15: Static Digital Time delay relays Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction

More information

GRE110. Protection and Control for MV Systems

GRE110. Protection and Control for MV Systems Protection and Control for MV Systems FEATURES Overcurrent protection for phase and earth faults (50/5P, 50/5N). Dependent and independent time characteristics (IDMTL and DTL). Four independent current

More information

GRE140. Protection and Control for MV Systems

GRE140. Protection and Control for MV Systems Protection and Control for MV Systems FEATURES Four stage non-directional and directional overcurrent protection for phase and earth faults with IDMTL or DTL. Polarizing voltage memory. Directional earth

More information

Relion 611 series. 611 series Type Test Certificate

Relion 611 series. 611 series Type Test Certificate Relion 611 series 611 series Document ID: 1MRS757466 Issued: 2016-02-22 Revision: B Product version: 2.0 Copyright 2016 ABB. All rights reserved Table of contents Table of contents Section 1 Section

More information

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement

More information

GRD150. FEATURES Protection functions. Control functions. Monitoring and Metering. Recording. User Interface APPLICATION

GRD150. FEATURES Protection functions. Control functions. Monitoring and Metering. Recording. User Interface APPLICATION FEATURES Protection functions Non-directional and directional overcurrent and earth-fault protection and sensitive earth fault protection (option) Overvoltage and undervoltage protection Thermal overload

More information

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs SIPROTEC easy 7SJ4 Numerical Overcurrent Protection Relay Powered by CTs Function overview Fig. /1 Description The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

Protection Relays PHASE & RESIDUAL OVERCURRENT

Protection Relays PHASE & RESIDUAL OVERCURRENT Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms modules

More information

Busbar Protection IED

Busbar Protection IED Busbar Protection IED GR-200 seriess - The GR-200 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing a platform for distributed

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

Scout-S Station Controller

Scout-S Station Controller Scout-S Station Controller Substation Automation Scout-S Station Controller The Scout-S Station Controller is a SCADA enabled remote terminal unit (RTU) with a data concentrator, event reporter, and built-in

More information

Distance Protection IED

Distance Protection IED Distance Protection IED GR-200 series - The GR-200 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing a platform for distributed

More information

7SR18 Solkor Line Differential Protection Energy Management

7SR18 Solkor Line Differential Protection Energy Management Reyrolle Protection Devices 7SR18 Solkor Line Differential Protection Energy Management 7SR18 Solkor five or eight user-programmable binary output contacts and three or six user programmable status inputs

More information

Reyrolle Protection Devices. 7SG13 Delta Protection and Control Relays. Answers for energy

Reyrolle Protection Devices. 7SG13 Delta Protection and Control Relays. Answers for energy Reyrolle Protection Devices 7SG13 Delta Protection and Control Relays Answers for energy 7SG13 Delta Protection and Control Relays User Interface 20 character x 2 line backlit LCD Menu navigation keys

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

Busbar Protection IED - Centralized model

Busbar Protection IED - Centralized model Busbar Protection IED - Centralized model GR-200 seriess - The GR-200 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing

More information

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy Reyrolle Protection Devices 7SG118 Argus 8 Voltage & Frequency Relay Answers for energy 7SG118 Argus 8 Voltage and Frequency Relay Data Storage and Communication Serial communications conform to IEC60870-5-103

More information

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive

More information

MINER-S Station Controller

MINER-S Station Controller MINER-S Station Controller Substation Automation MINER-S Station Controller The MINER-S Station Controller is a SCADA enabled fixed point remote terminal unit (RTU) with a data concentrator, event reporter,

More information

RT4F-110V/25A RECTIFIER

RT4F-110V/25A RECTIFIER The RT4F-110V/25A is a hot-pluggable switched mode rectifier (SMR) module designed to provide up to 25A of output current into a 110V nominal system. Examples of such systems are 60 cells lead acid (136V

More information

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A) IRI1-ES Sensitive Earth Fault Current Relay Manual IRI1-ES (Revision A) Woodward Manual IRI1-ES GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Protection relays.

Protection relays. Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation

More information

FL MC 2000E (SM40) LC

FL MC 2000E (SM40) LC IEC 61850 fiber optic converter with LC fiber optic connection (1310 nm) to convert 100Base-Tx to single- or multi-mode fiber glass Data sheet 3205_en_C 1 Description PHOENIX CONTACT 2014-04-04 2 Features

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

RT4B-110V/12A RECTIFIER

RT4B-110V/12A RECTIFIER The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box INTRODUCTION The PL-50 MO units are available in the next mechanical version: The PL-50 MO and PM-250 families represent the different solutions that Team Arteche offers for motor protection. Both families

More information

Line Differential Protection IED

Line Differential Protection IED Line Differential Protection IED GR-200 series - The GR-200 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing a platform

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay Protective Relays Electrical Apparatus ixp-420 Transformer Protection Relay 165-420 Figure 1: Edison Idea Relay The ixp-420 is a member of Cooper Power Systems Edison Idea line of protective relays. The

More information

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide Directional or Non-Directional Earth-Fault Product Guide Issued: 17.06.19994 Status: Updated Version: C/16.10.2002 Data subject to change without notice Features Directional or non-directional low-set

More information

Reyrolle Protection Devices. 7SR242 Duobias Transformer Protection Relay. Energy Management. Unrestricted

Reyrolle Protection Devices. 7SR242 Duobias Transformer Protection Relay. Energy Management. Unrestricted Reyrolle Protection Devices 7SR4 Duobias Transformer Protection Relay Energy Management Unrestricted Unrestricted Siemens Protection Devices Limited 7SR4 Duobias Transformer Protection Relay User Interface

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

RT4F-48V/50A-WAC RECTIFIER

RT4F-48V/50A-WAC RECTIFIER The RT4F-48V/50A-WAC is a switched mode rectifier (SMR) module designed to provide up to 58A of output current into a 48V nominal system, over a wide range of AC input voltage. This rectifier has been

More information

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D WPM 770 Data Sheet 679.D.141.02 Digital Multifunctional Power Meter with LCD Display and Application The digital Weigel Power Meters WPM 770 have been designed to display the electrical parameters in low

More information

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy Reyrolle Protection Devices 7SG117 Argus 7 Synchronising Relay Answers for energy 7SG117 Argus 7 Synchronising Relay Fig 1. Independent check & system synchronising settings Adjustable slip frequency,

More information

ACOS 300. Reliable protection for network and constructions in medium- and high voltage

ACOS 300. Reliable protection for network and constructions in medium- and high voltage ACOS 300 Reliable protection for network and constructions in medium- and high voltage IDS GmbH: Your competent partner for protection technology Network protection for medium- and high voltage Already

More information

Arc protection relay. Features Three-phase overcurrent function. Application

Arc protection relay. Features Three-phase overcurrent function. Application Arc protection relay REA 10_ Page 1 Issued: May 1999 Status: New Data subject to change without notice Features Three-phase overcurrent function Loop-type or radial sensor fibre for arc detection Two high-speed

More information

7SR23 DAD High Impedance Protection Relay Energy Management

7SR23 DAD High Impedance Protection Relay Energy Management Reyrolle Protection Devices 7SR23 DAD High Impedance Protection Relay Energy Management 2 Siemens Protection Devices Limited 7SR23 DAD High Impedance Relay User Interface 20 character x 4 line backlit

More information

RT4F-120V/20A-WAC RECTIFIER

RT4F-120V/20A-WAC RECTIFIER The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with

More information

7SR11 and 7SR12 Argus Overcurrent Relays Answers for infrastructure & cities.

7SR11 and 7SR12 Argus Overcurrent Relays Answers for infrastructure & cities. Reyrolle Protection Devices 7SR11 and 7SR12 Argus Overcurrent Relays Answers for infrastructure & cities. 7SR11 and 7SR12 Argus Overcurrent Relays Supervision 60CTS CT Supervision 74T/CCS Trip & Close

More information

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy Reyrolle Protection Devices 7SR11 and 7SR12 Argus Overcurrent Relays Answers for energy 7SR11 and 7SR12 Argus Overcurrent Relays 74T/CCS Trip & Close Circuit Supervision 60VTS VT Supervision Control 79

More information

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay SPAA 341 C. Product Guide Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay

More information

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

Feeder protection relay

Feeder protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay modules and a flexible

More information

Feeder/ Motor Protection Relay VAMP 40

Feeder/ Motor Protection Relay VAMP 40 Feeder/ Motor Protection Relay Feeder/motor protection relay Main characteristics Complete protection Comprehensive selection of protection functions for distribution network overhead line feeders, cable

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay 7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional

More information

InteliPro. Protection Relay for Parallel Applications. Technical Specification

InteliPro. Protection Relay for Parallel Applications. Technical Specification InteliPro Protection Relay for Parallel Applications Product description InteliPro is a highly flexible interconnection/mains decoupling protective relay with extensive protective functions. It meets the

More information

Reyrolle Protection Devices. 7SR210 & 7SR220 Argus Overcurrent Protection Relay. Answers for energy

Reyrolle Protection Devices. 7SR210 & 7SR220 Argus Overcurrent Protection Relay. Answers for energy Reyrolle Protection Devices 7SR10 & 7SR0 Argus Overcurrent Protection Relay Answers for energy 7SR10 7SR0 Argus Overcurrent Protection Relay Additional Functionality 7SR0n Directional Relay 7/59 Under/Over

More information

Reyrolle Catalogue Answers for Energy

Reyrolle Catalogue Answers for Energy Reyrolle Protection Devices Reyrolle Catalogue Answers for Energy Index Compact Overcurrent Argus C 7SR11 & 7SR12 1 Multifunction Overcurrent Argus M 7SR21 & 7SR22 2 Multifunction Reclose Controller Recloser

More information

TM221CE40R controller M IO relay Ethernet

TM221CE40R controller M IO relay Ethernet Characteristics controller M221 40 IO relay Ethernet Main Range of product Product or component type [Us] rated supply voltage Jan 6, 2019 Modicon M221 Logic controller 100...240 V AC Discrete input number

More information

Feeder Protection Relay REF 610. Product Guide

Feeder Protection Relay REF 610. Product Guide Product Guide Contents 1 Description.............................. 3 2 Protection functions....................... 3 3 Measurement............................ 4 4 Disturbance recorder......................

More information

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy Reyrolle Protection Devices 7SR11 and 7SR12 Argus Overcurrent Relays Answers for energy 7SR11 and 7SR12 Argus Overcurrent Relays Control 79 Auto Reclose 86 Lockout CB Control Features Cold Load Settings

More information

TM221ME32TK controller M IO transistor PNP Ethernet

TM221ME32TK controller M IO transistor PNP Ethernet Product data sheet Characteristics TM221ME32TK controller M221 32 IO transistor PNP Ethernet Complementary Main Discrete I/O number 32 Number of I/O expansion module Supply voltage limits Inrush current

More information

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay IE ON RESET.5 X1 t IE X1.6%.2.4.8 1.6 X1.1s.2.4.8 1.6 X2 OFF ON S1 S2 IRI1-ES IRI1-ES C&S Electric Limited (Protection & Control Division) Contents

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

7SG14 Duobias-M Transformer Protection

7SG14 Duobias-M Transformer Protection 7SG4 Duobias-M Transformer Protection Document Release History This document is issue 200/02. The list of revisions up to and including this issue is: Pre release 200/02 Document reformat due to rebrand

More information

7SR242 Duobias Transformer Protection Relay Answers for energy.

7SR242 Duobias Transformer Protection Relay Answers for energy. Reyrolle Protection Devices 7SR242 Duobias Transformer Protection Relay Answers for energy. 2 Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration & Instruments 3.

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types Millenium 3 General Characteristics Millenium 3 Compact Range Millenium 3 Expandable Range Millenium 3 Communication Options Millenium 3 Range General environment characteristics for CB, CD, XD, XR and

More information

Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Numerical motor protection in medium voltage networks Motor Protection and Control REM620 Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,

More information

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation

More information

TM221M16TG controller M IO transistor PNP spring

TM221M16TG controller M IO transistor PNP spring Characteristics controller M221 16 IO transistor PNP spring Main Range of product Product or component type [Us] rated supply voltage Discrete input number Analogue input number Discrete output type Discrete

More information

TM221CE40T controller M IO transistor PNP Ethernet

TM221CE40T controller M IO transistor PNP Ethernet Product data sheet Characteristics TM221CE40T controller M221 40 IO transistor PNP Ethernet Complementary Main Discrete I/O number 40 Number of I/O expansion module Supply voltage limits Inrush current

More information

Published by and copyright 2015 Siemens AG Energy Management Freyeslebenstr Erlangen, Germany

Published by and copyright 2015 Siemens AG Energy Management Freyeslebenstr Erlangen, Germany Published by and copyright 2015 Siemens AG Energy Management Freyeslebenstr. 1 91058 Erlangen, Germany For more information, please contact our Customer Support Center Phone: +49 180/524 84 37 Fax: +49

More information

TWO-WINDING TRANSFORMER DIFFERENTIAL

TWO-WINDING TRANSFORMER DIFFERENTIAL E3-TR PROTECTION WITH AUTOMATIC VOLTAGE Because of the control, measuring and monitoring functions implemented, the IED can also be used as a bay control unit. The EuroCAP configuration tool, which is

More information

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - on base plate Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific

More information

ATV12P075M3 variable speed drive ATV kW - 1hp V - 3ph - on base plate

ATV12P075M3 variable speed drive ATV kW - 1hp V - 3ph - on base plate Characteristics variable speed drive ATV12-0.75kW - 1hp - 200..240V - 3ph - on base plate Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

RT12-240V/2.4kW Rectifier Specification

RT12-240V/2.4kW Rectifier Specification The RT12-240V/2.4kW is a switched mode rectifier (SMR) module that delivers up to 2.4kW of output power (and up to 11A output current) into a 240V nominal DC system. The RT12 suits AC supply voltages between

More information

For Transmission, Distribution and Machinery protection.

For Transmission, Distribution and Machinery protection. Founded in 1953, Microelettrica Scientifica has developed a wide range of products, divided into three main lines: For Transmission, Distribution and Machinery protection. A-Line Electronic analogic. M-Line

More information

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications Power Circuit Control Circuit (External Source) Control Circuit (Internal Source) Short Circuit Current Rating (SCCR) Application Electrical Ratings Three-phase Number of Poles 3 Input Power Terminals

More information