Rosemount 3300 Series with HART to Modbus Converter

Size: px
Start display at page:

Download "Rosemount 3300 Series with HART to Modbus Converter"

Transcription

1 Manual Supplement Rosemount 3300 Series Rosemount 3300 Series with HART to Modbus Converter Introduction page 1-3 Workflow page 1-3 Mechanical Installation page 1-3 Electrical Installation page 1-4 Transmitter Configuration page 1-7 Protocol description page 1-8 Common Modbus Host Configuration page 1-19 Specific Modbus Host Configuration page 1-24 Troubleshooting page 1-30 HMC Firmware Upgrade in Rosemount Radar Master.. page 1-31 RCT Communication with MA(+), MB(-) page 1-36 Levelmaster Protocol Description page 1-36 Specifications page 1-37 Hazardous Locations Certifications page 1-38 This instruction is a supplement to the Rosemount 3300 Series Reference Manual (Document No ). Explosions could result in death or serious injury: Verify that the operating environment of the transmitter is consistent with the appropriate hazardous locations certifications. Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices. Do not remove the gauge cover in explosive atmospheres when the circuit is alive.

2 Rosemount 3300 Series Manual Supplement Failure to follow safe installation and servicing guidelines could result in death or serious injury: Make sure only qualified personnel perform the installation. Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment. High voltage that may be present on leads could cause electrical shock: Avoid contact with leads and terminals. Make sure the main power to the 3300 transmitter is off and the lines to any other external power source are disconnected or not powered while wiring the gauge. Probes covered with plastic and/or with plastic discs may generate an ignition-capable level of electrostatic charge under certain extreme conditions. Therefore, when the probe is used in a potentially explosive atmosphere, appropriate measures must be taken to prevent electrostatic discharge. 1-2

3 Manual Supplement Rosemount 3300 Series INTRODUCTION The Rosemount 3300 Series transmitter is a Modbus compatible measurement device that supports communication with a Remote Terminal Unit (RTU) using a subset of read, write, and diagnostic commands used by most Modbus compatible host controllers. It also supports communication through Levelmaster ASCII protocol. The HART to Modbus Converter (HMC) module is located inside the Rosemount 3300 transmitter enclosure and provides power to and communicates with the 3300 transmitter through a HART interface. Figure 1-1. System Overview Modbus and Levelmaster communication Remote Terminal Unit 3300 transmitter electronics HART signals HART to Modbus Converter HART signals RCT/ 375 Field Communicator During normal operation, the HMC mirrors the contents of process variables from the 3300 transmitter to the Modbus registers. To configure the 3300 transmitter, it is possible to connect a configuration tool to the HMC. See Transmitter Configuration on page 1-7 for more information. WORKFLOW MECHANICAL INSTALLATION Overview of workflow for commissioning a Rosemount 3300 transmitter with Modbus protocol: 1. Mount the transmitter on the tank. 2. Connect the power and communication wires. 3. Configure the 3300 transmitter through Rosemount Radar Configuration Tools (RCT) or a 375 Field Communicator: Tank geometry, product data Communication settings 4. Configure host. 5. Verify output values as reported by the 3300 transmitter. For instructions on how to mount the Rosemount 3300 transmitter, refer to Rosemount 3300 Series Reference Manual (Document No ). 1-3

4 Rosemount 3300 Series Manual Supplement ELECTRICAL INSTALLATION NOTE For general electrical installation requirements, including grounding requirements, refer to Rosemount 3300 Series Reference Manual (Document No ). Figure 1-2. Field Wiring Connections To connect the Rosemount 3300: 1. Make sure the power supply is disconnected. 2. Remove the cover on the transmitter housing terminal side (see label). Do not remove the cover in an explosive atmosphere with a live circuit. 3. Pull the cable through the cable gland/conduit. For the RS-485 bus, use shielded twisted pair wiring, preferably with an impedance of 120Ω (typically 24 AWG) in order to comply with the EIA-485 standard and EMC regulations. The maximum cable length is 4000 ft/1200 m. 4. Make sure that the transmitter housing is grounded, then connect wires according to Figure 1-2 and Table 1-1. Connect the lead that originates from the A line from the RS-485 bus to the terminal marked MA (+), and the lead that originates from the B line to the terminal marked MB (-). 5. If it is the last transmitter on the bus, connect the 120Ω termination resistor. 6. Connect the leads from the positive side of the power supply to the terminal marked PWR +, and the leads from the negative side of the power supply to the terminal marked PWR -. The power supply cables must be suitable for the supply voltage and approved for use in hazardous areas, where applicable. 7. Attach and tighten the housing cover. Tighten the cable gland, then plug and seal any unused terminals, and connect the power supply. A B 120Ω RS-485 Bus 120Ω Power Supply HART + HART - 120Ω In case it is the last transmitter on the bus, connect the 120Ω termination resistor 1-4

5 Manual Supplement Rosemount 3300 Series Connection Terminals The connection terminals are described in Table 1-1 below: Table 1-1. Connection Terminals Connector label Description Comment HART + HART - Positive HART connector Negative HART connector Connect to PC with RCT software, 375 Field Communicator, or other HART configurators. MA (+) MB (-) PWR + PWR - Modbus RS-485 A connection (RX/TX+) (1) Modbus RS-485 B connection (RX/TX-) (1) Positive Power input terminal Negative Power input terminal Connect to RTU Apply +8 VDC to +30 VDC (1) The designation of the connectors do not follow the EIA-485 convention, which states that RX/TX- should be referred to as 'A' and RX/TX+ as 'B'. Figure 1-3. Connection Terminals for Rosemount 3300 with HART to Modbus Converter HART + HART - 1-5

6 Rosemount 3300 Series Manual Supplement RS-485 Bus The 3300 transmitter does not provide electrical isolation between the RS-485 bus and the transmitter power supply Maintain a bus topology and minimize stub length Figure 1-4 identifies multidrop wiring topology where up to 32 devices may be wired on one RS-485 bus The RS-485 bus needs to be terminated once at both ends, but should not be terminated elsewhere on the bus Figure 1-4. Multidrop Connection of 3300 Transmitters 120Ω RS-485 Bus A B 120Ω Rosemount 3300 Rosemount 3300 Rosemount 3300 Power Supply 1-6

7 Manual Supplement Rosemount 3300 Series TRANSMITTER CONFIGURATION The Rosemount 3300 can be configured using the Rosemount Configuration Tools (RCT) PC software or a 375 Field Communication Unit. Configuration is done by sending HART commands through the HART to Modbus Converter (HMC) to the 3300 transmitter electronics. To configure the 3300 transmitter, connect the communicator or PC to the HART terminals, see Figure 1-3 on page 1-5. Both the configuration tool and the RS-485 bus can be connected simultaneously. Configuration data is sent with HART commands through the HMC to the 3300 transmitter electronics, as illustrated in Figure 1-1 on page 1-3. Note that the power supply must be connected during configuration, see also Electrical Installation on page 1-4. NOTE Measurement data is not updated to the Modbus Master when a configuration tool is connected. NOTE The Rosemount 3300 can also be configured in RCT by using the MA (+), MB(-). For more information, see RCT Communication with MA(+), MB(-) on page Configuration data such as Tank Height, Upper Null Zone, dielectric constants, and other basic parameters are configured in the same way as for a standard Rosemount 3300 transmitter. For more information, see the Guided Wave Radar Level and Interface Transmitter Quick Installation Guide (Document No ). Make sure that the measurement unit of the Primary Variable (PV) matches the configuration of the Modbus Host since the transmitter output value does not include any information on associated measurement units. For further information on basic configuration, see the Rosemount 3300 Series Reference Manual (Document No ). NOTE The 3300 transmitter with Modbus protocol is configured to HART short address 1 at factory. This reduces power comsumption by locking the analog output at 4 ma. 1-7

8 Rosemount 3300 Series Manual Supplement PROTOCOL DESCRIPTION The Rosemount 3300 level transmitter can communicate with RTUs using Modbus RTU (often referred to as just Modbus ), Modbus ASCII, and Levelmaster (also known as Siemens or Tank protocol). Table 1-2. List of RTUs Supported Protocols RTU ABB Totalflow Bristol ControlWave Micro Fisher ROC Kimray DACC 2000/3000 ScadaPack Thermo Electron Autopilot Protocols Modbus RTU, Levelmaster Modbus RTU Modbus RTU Levelmaster Modbus RTU Modbus RTU, Levelmaster Modbus ASCII is not commonly used, since it doubles the amount of bytes for the same message as the Modbus RTU. If you do not have any of these RTUs, check your RTU manual to see which protocols it supports. Proceed to the chapter where setup of the protocol is described. Modbus RTU Communication Setup The Rosemount 3300 is configured with the default Modbus RTU address 246. The 3300 is configured with the following Modbus RTU communication parameter default setting: Table 1-3. Modbus RTU Communication Parameters Parameter Default Value Configurable Values Baud Rate , 2400, 4800, 9600, Start Bits (1) One One Data Bits (1) Eight Eight Parity None None, Odd, Even Stop Bits One One or Two Address range (1) Start Bits and Data Bits cannot be changed. NOTE It takes 30 seconds for a change of Modbus RTU communication parameters to take effect. 1-8

9 Manual Supplement Rosemount 3300 Series Using the RCT Setup to change Modbus RTU communication parameters NOTE To change Modbus RTU communication parameters, the Rosemount 3300 must use HART address 1, the default address. To change the Modbus RTU address and communication parameters (1) in the Rosemount Configuration Tool (RCT): 1. Start the RCT. 2. In the RCT workspace Project Bar, click the Setup icon to open the Setup window: Modbus setup 3. Select the Output tab. 4. Click the Modbus Setup button. 5. In the Modbus Setup window, type the desired Modbus RTU address. 6. Enter the baude rate, parity, and stop bits, then click the OK button. (1) The Modbus Setup function is available in RCT version and later. 1-9

10 Rosemount 3300 Series Manual Supplement Using a Rosemount 375 Field Communicator to change Modbus RTU communication parameters When using the 375 Field Communicator, the Message Area is available with HART command [1,4,1,6]: Figure 1-5. Message Area is Available via HART Command Online Menu 1 DEVICE SETUP 2PV 3AO 4LRV 5URV 1 Process Variables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5Review 1Device Information 2 Display 3 Volume Geometry 4HART 5 Advanced Service 1 Distributor 2 Model 3Dev Id 4Tag 5 Descriptor 6 Message 7Date 8 Write Protect 9 Revision # s - Construction Details For example: You want to use address 44 for the 3300 transmitter, and the following communication parameters are used by the host: Table 1-4. Communication Parameters Used by the Host (example) Parameter Value Baud Rate 4800 Start Bits One Data Bits Eight Parity Odd Stop Bits Two To configure the 3300 transmitter to communicate with the Host in this example, the following text string is written to the HART Slave 1 Message Area: HMC A44 B4800 PO S2. Note: Only values that differ from the current values need to be included in the text string. HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake. A44: A indicates that the following number is the new address (address 44). Leading zeroes are not needed. B4800: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200). PO: P identifies the following letter as parity type (O = odd, E = even, and N = none). 1-10

11 Manual Supplement Rosemount 3300 Series S2: S indicates that the following figure is the number of stop bits (1 = one, 2 = two). Only values that differ from the current values need to be included. For example, if only the address is changed, the following text string is written into the 3300 (HART Slave 1) Message Area: HMC A127, indicates that 127 is the new address. Modbus ASCII Communication Setup Modbus ASCII communication setup can be carried out using the Rosemount Configuration Tool (RCT). The parameter, default, and configurable values are shown in Table 1-5 below. NOTE It takes 30 seconds for a change of Modbus communication parameters to take effect. NOTE To change Modbus ASCII communication parameters, the Rosemount 3300 must use HART address 1, the default address. Table 1-5. Modbus ASCII Communication Parameters Parameter Default value Configurable values Baud Rate , 2400, 4800, 9600, Start Bits One One Data Bits Seven Seven, Eight Parity None None, Odd, even Stop Bits One One or Two Address

12 Rosemount 3300 Series Manual Supplement Using the RCT Setup to change Modbus communication parameters To change the Modbus address and communication parameters in the Rosemount Configuration Tool (RCT): 1. Start the RCT. 2. In the RCT workspace Project Bar, click the Setup icon to open the Setup window: Modbus setup 3. Select the Output tab. 4. Click the Modbus Setup button. Modbus ASCII Parameter Configuration Example on page 1-13 shows how to enter messages in this area. 1-12

13 Manual Supplement Rosemount 3300 Series Modbus ASCII Parameter Configuration Example Example: You want to use address 246 for the 3300 transmitter and the host uses the following parameters: Table 1-6. Parameters Used by the Host (in case of Modbus ASCII, example) Parameter Value Baud Rate 9600 Start Bits One Data Bits Seven Parity None Stop Bits One To configure the 3300 transmitter to communicate with the Host in this example, the following text string is written to the Modbus Message area. HMC M1 A246 B9600 D7 PN S1. NOTE Include all the parameters when writing to the message area. Note that an address must be unique on the bus. HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake. M1: This means that the Modbus ASCII protocol is to be used. A246: A indicates that the following number is the new address (address 246). Leading zeroes are not needed. B9600: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200). D7: D indicates that the following data bits are to be used (7 = seven, 8 = eight). PN: P identifies the following letter as parity type (O = odd, E = even, and N = none). S1: S indicates that the following figure is the number of stop bits (1 = one, 2 = two). Note: Start Bits are not configurable and cannot be set. 1-13

14 Rosemount 3300 Series Manual Supplement Using a Rosemount 375 Field Communicator to change Modbus ASCII communication parameters When using the 375 Field Communicator, the Message Area is available with HART command [1,4,1,6]. In the message area Modbus ASCII parameters can be configured as described in Modbus ASCII Parameter Configuration Example on page Figure 1-6. HART Command [1,4,1,6] Online Menu 1 DEVICE SETUP 2PV 3AO 4LRV 5URV 1 Process Variables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5Review 1Device Information 2 Display 3 Volume Geometry 4HART 5 Advanced Service 1 Distributor 2 Model 3Dev Id 4Tag 5 Descriptor 6 Message 7Date 8 Write Protect 9 Revision # s - Construction Details 1-14

15 Manual Supplement Rosemount 3300 Series Levelmaster Communication Setup Use the Rosemount Configuration Tool (RCT) to setup Levelmaster communication. The default and configurable parameter values can be found in Table 1-7. NOTE It takes 30 seconds for a change of Levelmaster communication parameters to take effect. NOTE To change Levelmaster communication parameters, the Rosemount 3300 must use HART address 1, the default address. Table 1-7. Levelmaster Communication Parameters Parameter Default value Configurable value Baud Rate , 2400, 4800, 9600, Start Bits One One Data Bits Seven Seven, Eight Parity None None, Odd, Even Stop Bits One One or Two Address

16 Rosemount 3300 Series Manual Supplement Using the RCT Setup to change Levelmaster communication parameters To change the Levelmaster address and communication parameters in the Rosemount Configuration Tool (RCT): 1. Start the RCT. 2. In the RCT workspace Project Bar, click the Setup icon to open the Setup window: Modbus setup 3. Select the Output tab. 4. Click the Modbus Setup button. Levelmaster Parameter Configuration Example on page 1-17 shows how to enter messages in this area. 1-16

17 Manual Supplement Rosemount 3300 Series Levelmaster Parameter Configuration Example Example: You want to use address 2 for the 3300 transmitter and the host uses the following parameters: Table 1-8. Parameters Used by the Host (in case of Levelmaster, example) Parameter Value Baud Rate 9600 Start Bits One Data Bits Seven Parity None Stop Bits One To configure the 3300 transmitter to communicate with the Host in this example, the following text string is written to the Modbus Message area. HMC M2 A2 B9600 D7 PN S1. NOTE Include all the parameters when writing to the message area. Note that an address must be unique on the bus. HMC: These three letters are used for safety and will eliminate the risk of changing the configuration data by mistake. M2: This means that the Levelmaster protocol is to be used. A2: A indicates that the following is the new address (address 2). Leading zeroes are not needed. B9600: B indicates that the following number is the new baud rate (1200, 2400, 4800, 9600, 19200). D7: D indicates that the following data bits are to be used (7 = seven, 8 = eight). PN: P identifies the following letter as parity type (O = odd, E = even, and N = none). S1: S indicates that the following figure is the number of stop bits (1 = one, 2 = two). Note: Start Bits are not configurable and cannot be set. 1-17

18 Rosemount 3300 Series Manual Supplement Using a Rosemount 375 Field Communicator to change Levelmaster communication parameters When using the 375 Field Communicator, the Message Area is available with HART command [1,4,1,6]. In the message area Levelmaster parameters can be configured as described in Levelmaster Parameter Configuration Example on page Figure 1-7. HART Command [1,4,1,6] Online Menu 1 DEVICE SETUP 2PV 3AO 4LRV 5URV 1 Process Variables 2 Diag/Service 3 Basic Setup 4 Detailed Setup 5Review 1Device Information 2 Display 3 Volume Geometry 4HART 5 Advanced Service 1 Distributor 2 Model 3Dev Id 4Tag 5 Descriptor 6 Message 7Date 8 Write Protect 9 Revision # s - Construction Details NOTE See Detailed Levelmaster information section for more detailed protocol specifications. 1-18

19 Manual Supplement Rosemount 3300 Series Host specific information Kimray DACC 2000/3000 This table shows input types in Kimray IMI software and the corresponding value. The communication port must be configured to use Tank Levels protocol. Table 1-9. Kimray Input Types and Corresponding Values COMMON MODBUS HOST CONFIGURATION Kimray Inp type 3300 variable Format Tank Level1 PV ddd.dd.alt. -dd.dd Tank Level2 SV ddd.dd.alt -dd.dd When using Modbus RTU or Modbus ASCII, the registers to receive status and variables must be configured in the host system. The transmission of single-precision (4 bytes) IEEE 754 floating point numbers can be rearranged in different byte orders specified by the Floating Point Format Code. The format code information, stated for each Remote Terminal Unit (RTU) respectively, specifies which registers to poll from the 3300 transmitter in order for the RTU to correctly interpret floating point numbers. The byte transmission order for each format code is demonstrated in Table 1-10 below. Table Byte Transmission Order is Specified by the Floating Point Format Code Format Code 0 ABCD 1 CDAB 2 DCBA 3 BADC Byte transmission order NOTE Some Modbus hosts cannot read the information described here using input Registers (Modbus function code 4). The Input Register information can also be read using Holding Register (Function code 3). In this case, Input Register number is used as Holding Register number. Input Registers The register area starting with 1300 can be configured to have any of the four format codes. The configuration is done by setting FloatingPointFormatCode register (holding register 3000) to 0-3, as shown in Table This configuration can be done with the Rosemount Radar Master program. NOTE Depending on the slave number the 3300 transmitter is using, different registers must be used with the default slave number being

20 Rosemount 3300 Series Manual Supplement Table Output Variables for the Configurable Floating Point Format Code Register Name Slave 1 Status Conf Register Number 1300 Slave 1 PV Conf 1302 Slave 1 SV Conf 1304 Slave 1 TV Conf 1306 Slave 1 FV Conf 1308 Note Bit information in bitfield. Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 Non PV. Bit 2: Invalid Measurement Slave 1 Non PV. Bit 3: Invalid Measurement Slave 1 Non PV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV. i.e. all three bits are set simultaneously. Primary variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register. Secondary variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register. Tertiary variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register. Fourth variable from slave 1 represented in IEEE 754 format, using the byte order set in the FloatingPointFormatCode register. Slave 2 data Same data as for Slave 1. Slave 3 data Same data as for Slave 1. Slave 4 data Same data as for Slave 1. Slave 5 data Same data as for Slave 1. The Rosemount 3300 register area starting with register 2000 is used for hosts that require Floating Point Format Code 0 (see Table 1-12). When Floating Point Format Code 1 is required, the register area starting with register 1400 is used (see Table 1-13). Floating Point Format Codes 2 and 3 use register areas 2100 and 2200, respectively (see Table 1-14 and Table 1-15). 1-20

21 Manual Supplement Rosemount 3300 Series Table Output Variables for Floating Point Format Code 0 Register Name Register Number Note Slave 1 Status 2000 Bit information in bitfield: Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 SV. Bit 2: Invalid Measurement Slave 1 TV. Bit 3: Invalid Measurement Slave 1 FV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV, i.e. all three bits are set simultaneously. Slave 1 PV 2002 Primary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0. Slave 1 SV 2004 Secondary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0. Slave 1 TV 2006 Tertiary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0. Slave 1 FV (QV) 2008 Fourth variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 0. Table Output Variables for Floating Point Format Code 1 Register Name Register Number Note Bit information in bitfield: Bit 0: Invalid Measurement Slave 1. Bit 1: Invalid Measurement Slave 2. Bit 2: Invalid Measurement Slave 3. Bit 3: Invalid Measurement Slave 4. Bit 4: Invalid Measurement Slave 5. Bit 8: Slave with short address 0 is used, but not alone on bus. Only one HART slave can be connected on the bus if the slave is in Analog Current mode (this is Slave Status 1400 the case if short address = 0 by HART definition). Bit 9: Slave with short address > 5 detected on bus. Maximum of five HART Slaves can be connected on the HART Bus. Their short address MUST be between 1 and 5. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Slave 1 PV 1402 Primary variable from slave

22 Rosemount 3300 Series Manual Supplement Register Name Register Number Note Slave 1 SV 1414 Secondary variable from slave 1. Slave 1 TV 1426 Tertiary variable from slave 1. Slave 1 FV (QV) 1438 Fourth variable from slave 1. Table Output Variables for Floating Point Format Code 2 Register Name Register Number Note Slave 1 Status 2100 Bit information in bitfield: Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 SV. Bit 2: Invalid Measurement Slave 1 TV. Bit 3: Invalid Measurement Slave 1 FV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV, i.e. all three bits are set simultaneously. Slave 1 PV 2102 Primary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2. Slave 1 SV 2104 Secondary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2. Slave 1 TV 2106 Tertiary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 2. Slave 1 FV (QV) 2108 Fourth variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code

23 Manual Supplement Rosemount 3300 Series Table Output Variables for Floating Point Format Code 3 Register Name Register Number Note Slave 1 Status 2200 Bit information in bitfield: Bit 0: Invalid Measurement Slave 1 PV. Bit 1: Invalid Measurement Slave 1 SV. Bit 2: Invalid Measurement Slave 1 TV. Bit 3: Invalid Measurement Slave 1 FV. Bit 14: HART bus busy (slave in burst or other master present) Bit 15: HTM Task not running (option not available). Note: Bit 1-3 is set when Invalid Measurement of Slave 1 Non PV, i.e. all three bits are set simultaneously. Slave 1 PV 2202 Primary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3. Slave 1 SV 2204 Secondary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3. Slave 1 TV 2206 Tertiary variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3. Slave 1 FV (QV) 2208 Fourth variable from slave 1 represented in IEEE 754 format, using Floating Point Format Code 3. Measurement Units Measurement units for the various HART slaves are stored in input registers as a Unit Code presented in Table Conversion from Unit Code to measurement unit is given in Table 1-17 on page Table Measurement units and corresponding input registers Register Name Register Number Note Slave 1 PV Units 104 Slave 1 SV Units 108 See Table 1-17 for conversion from Unit Slave 1 TV Units 112 Code to Measurement Unit. Slave 1 FV (QV) Units

24 Rosemount 3300 Series Manual Supplement Table Conversion of Unit Code to Measurement Unit Unit Code Measurement Unit Unit Code Measurement Unit Volume Length 40 US Gallon 44 Feet 41 Liters 45 Meters 42 Imperial Gallons 47 Inches 43 Cubic Meters 48 Centimeters 46 Barrels 49 Millimeters 111 Cubic Yards Temperature 112 Cubic Feet 33 Degree Fahrenheit 113 Cubic Inches 32 Degree Celcius SPECIFIC MODBUS HOST CONFIGURATION The Remote Terminal Unit needs to be configured to communicate and correctly interpret data when reading input registers from the Rosemount 3300 transmitter. Baud Rate The specified Baud Rates below are recommendations. If other Baud Rates are used, make sure that the 3300 and the RTU are configured for the same communication speed. Floating Point Format Code See Section Common Modbus Host Configuration on page RTU Data Type The RTU Data Type specifies which configuration to use in the RTU in order for the RTU to correctly interpret a floating point number transmitted from the 3300 transmitter with Modbus. Input Register Base Number Data registers in the 3300 transmitter with Modbus are numbered exactly as they are transmitted in the Modbus communication. Some RTUs use different naming conventions and to configure the RTU to poll the correct registers from the 3300 Modbus, an Input Register Base Number is stated for each RTU respectively. E.g. if the input register base number is 1 for the RTU, the 3300 Modbus input register 1402 has to be entered in the RTU address as input register

25 Manual Supplement Rosemount 3300 Series Fisher ROC 809 Figure 1-8. Wiring Diagram for Connecting 3300 Modbus to Fischer ROC 809 Power Supply Table Parameter Values (in case of Fisher ROC 809) Parameter Value Baud Rate 9600 Floating Point Format Code 0 RTU Data Type Conversion Code 66 Input Register Base Number 0 The Input Register Base Number needs to be added to the Input Register address of the 3300 transmitter. In this case, register 1300 needs to have 1300 entered as the address. 1-25

26 Rosemount 3300 Series Manual Supplement ABB TotalFlow Figure 1-9. Wiring diagram for connecting 3300 Modbus to ABB TotalFlow Table Parameter Values (in case of ABB TotalFlow) Parameter Value Baud Rate 9600 Floating Point Format Code 0 RTU Data Type 16 Bit Modicon Input Register Base Number 1 The Input Register Base Number needs to be added to the Input Register address of the 3300 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc. 1-26

27 Manual Supplement Rosemount 3300 Series Thermo Electron Autopilot Figure Wiring Diagram for Connecting 3300 Modbus to Thermo Electron Autopilot Power Supply Table Parameter Values (in case of Thermo Electron Autopilot) Parameter Value Baud Rate 9600 Floating Point Format Code 1 RTU Data Type IEEE Flt 2R Input Register Base Number 0 The Input Register Base Number needs to be added to the Input Register address of the 3300 transmitter. In this case, register 1302 needs to have 1302 entered as the address etc. 1-27

28 Rosemount 3300 Series Manual Supplement Bristol ControlWave Micro Figure Wiring Diagram for Connecting 3300 Modbus to Bristol ControlWave Micro Power Supply DB9 Male Table Parameter Values (in case of Bristol ControlWave Micro) Parameter Baud Rate 9600 Floating Point Format Code 2 (FC 4) Value RTU Data Type 32-bit registers as 2 16-bit registers Input Register Base Number 1 The Input Register Base Number needs to be added to the Input Register address of the 3300 transmitter. In this case, register 1302 needs to have 1303 entered as the address etc. 1-28

29 Manual Supplement Rosemount 3300 Series ScadaPack Figure Wiring Diagram for Connecting 3300 Modbus to SCADAPack 32 Power Supply Table Parameter Values (in case of SCADAPack 32) Parameter Value Baud Rate 9600 Floating Point Format Code 0 RTU Data Type Floating Point Input Register Base Number The Input Register Base Number needs to be added to the Input Register address of the 3300 transmitter. In this case, register 1302 needs to have entered as the address etc. 1-29

30 Rosemount 3300 Series Manual Supplement TROUBLESHOOTING No communication on RS-485 bus (MA, MB) Check that the cables are connected Check that PWR+ is connected to + and PWR- is connected to - on the power supply Make sure the 3300 transmitter is supplied with 8-30 VDC Try alternating MA/MB if you are unsure of the polarity If an RS-232/RS-485 converter is used, make sure it is properly installed and configured The last 3300 transmitter may need a terminating 120Ω resistor connected between MA and MB No 3300 communication in RCT Using HART+, HART- HART modem is not properly connected Polling address is incorrect in RCT (default 1) Using MA (+), MB (-) See No communication on RS-485 bus Polling address is incorrect in RCT (default 1) Cycle the power and wait 20 seconds before polling No communication with Modbus RTU protocol See No communication on RS-485 bus Make sure the Modbus RTU Communication Setup is done properly Make sure the Modbus RTU address is unique on the bus Cycle the power and try to connect Check the RTU communication settings No communication with Modbus ASCII protocol See No communication on RS-485 bus Make sure the Modbus ASCII Communication Setup is done properly Make sure the Modbus ASCII address is unique on the bus Cycle the power, waiting 40 seconds before communication begins Check the RTU communication settings No communication with Levelmaster protocol See No communication on RS-485 bus Make sure the Levelmaster Communication Setup is done properly Make sure the Levelmaster address is unique on the bus Cycle the power, waiting 40 seconds before communication begins Check the RTU communication settings 1-30

31 Manual Supplement Rosemount 3300 Series HMC FIRMWARE UPGRADE IN ROSEMOUNT RADAR MASTER The HMC s firmware is upgraded with Rosemount Radar Master (RRM). A detailed description on how to carry out the firmware upgrade is shown on the following pages. NOTE During firmware upgrade, the HMC Modbus RTU address must be 246, the default address. Make sure to disconnect other Modbus RTU devices that are connected and have address 246. NOTE Do not interrupt communication between the PC and the 3300 level transmitter during the firmware upload. 1. Connect the HMC to a PC as described in Electrical Installation, Connection Terminals, and RS-485 bus on page Start RRM and open the Search Device window. 3. Click the Settings button in the Search Device window. 1-31

32 Rosemount 3300 Series Manual Supplement 4. Ensure that the above communication settings are used. 5. Open the Search Device window. 6. Search for HMCs by selecting Scan Address Range, and choose a start and end address for Modbus. The default HMC Modbus address is Click the Start Scan button. 8. Click OK to connect when the device is found. 1-32

33 Manual Supplement Rosemount 3300 Series 9. From the Service menu, choose the Enter Service Mode option. 10. Type password, admin. 11. From the Service menu, choose the Upload Firmware option. 12. Click Browse. 13. Select the upgrade.cry file. 14. Click Open. 1-33

34 Rosemount 3300 Series Manual Supplement 15. Click the Upload button to start the firmware upgrade. 16. When upload is finished, click the alert symbol. Checksum 17. Click Device Errors and check for Checksum. 18. If it is on the list, choose the Factory Settings option from the Tools menu. 1-34

35 Manual Supplement Rosemount 3300 Series 19. Select All and click OK. 20. Select Yes. 21. The Checksum error will no longer be on the list. 22. Now you can start using the HMC. 1-35

36 Rosemount 3300 Series Manual Supplement RCT COMMUNICATION WITH MA(+), MB(-) The 3300 level transmitter can be configured with RCT using the MA (+), MB (-) connectors. When the power and communication wires are connected, start configuring the transmitter using the RCT. NOTE The 3300 level transmitter must use HART address 1 to communicate with the NOTE Switch the power off, then switch it on and wait 20 seconds before connecting to the This can be done by clicking the Search for Device button in RCT. The PC communicates with the 3300 by tunnelling the HART protocol over RS-485, using a RS-232/RS-485 Converter. To communicate with the 3300 transmitter, the COM port used for serial communication (RS-232) must be selected in RCT. Check the Device Manager in Windows if you are unsure which COM port to use. See Help, Contents in RCT to see how to use a specific COM port. NOTE Make sure the 3300 transmitter is alone on bus. Disconnect or turn off power from any other devices. LEVELMASTER PROTOCOL DESCRIPTION Implemented functions of the Levelmaster protocol Here is a description of the implemented functions of Levelmaster protocol in the HMC. Table Implemented Functions of Levelmaster Protocol Input format Description Output format UnnN? Return ID number UnnNnnCcccc UnnNmm Set ID number UnnNOKCcccc UnnF? Return number of floats UnnFxCcccc UnnFx? Set number of floats UnnFOKCcccc Unn? Return floats and other data UnnDddd.ddFfffEeeee WwwwCcccc (1) (1) In this case, number of floats is set to 1. If number of floats is set to 2, the Output Format would be: UnnDddd.ddDddd.ddFfffEeeeeWwwwCcccc NOTE If one float is sent, it is Float1. If two floats are sent, it is Float 1 before Float

37 Manual Supplement Rosemount 3300 Series Explanation of letters and expressions used in previous tables: Table Letters and Expressions Used in Previous Tables Letter Description nn is used to identify slave to respond, nn is a number or ** (wildcard). nn The EmulCtrl Address Holding register can be configured to a higher value than 99. In that case, the address will be truncated to 99. mm mm is the new ID number for the slave; mm is a number x cccc x is the number of floats returned when slave receives Unn?, x is a number 0-2. Is the 16 bit CRC checksum, cccc are hexadecimal characters. ddd.dd ddd.dd is the distance value from slave 1. Note that the first d can also be a - (minus). Float 1 Slave 1 PV. Float 0 Slave 1 SV. fff The temperature value. Configured by Holding Register 3208 in HMC. (1) eeee Wwww An error value. Bit 0: Invalid SV value (Float 0). Bit 8: Invalid Temperature value. Bit 12: Invalid PV value (Float 1). A warning value, not used in this implementation. (1) Any of the four available variables from any of the five HART slaves can be selected as the temperature source. The least four significant bits (bit 0-3) select the variable number. Bits 4-7 select the HART slave address. If invalid values are used, the temperature value will be invalid, with no Error bit set. For example, if we want to use FV from HART Slave 3 as temperature source, we have to write the value 34 Hex (52 decimal). SPECIFICATIONS Table Specifications Power consumption Signal wiring Power supply cabling Bus termination < 0.5 W (with HART adress=1) Two-wire half duplex RS-485 Modbus. Use shielded twisted pair wiring, preferably with an impedance of 120Ω (typically 24 AWG), in order to comply with EIA-485 standard and EMC regulations. The power supply cables must be suitable for the supply voltage and approved for use in hazardous areas, where applicable. Standard RS-485 bus termination per EIA-485 See the Rosemount 3300 Series Reference Manual (Document No ) for further specifications. 1-37

38 Rosemount 3300 Series Manual Supplement HAZARDOUS LOCATIONS CERTIFICATIONS The Rosemount 3300 Series Guided Wave Radar Level and Interface Transmitters that have the following labels have been certified to comply with the requirements of the noted approval agencies. Factory Mutual (FM) Approvals Project ID: Figure Approval Labels Factory Mutual (FM) and Name Plate For connection in ambients above 70 C, use wiring rated for 90 C minimum. E5 Explosion-proof for use in Class I, Div. 1, Groups B, C, and D; Dust-ignition-proof for use in Class II/III, Div. 1, Groups E, F, and G; With Intrinsically Safe connections to Class I, II, III, Div. 1, Groups A, B, C, D, E, F, AND G. Temperature class +85 C. Ambient temperature limits: -50 C to + 85 C. Factory Sealed. Approval valid for Modbus and HART option. 1-38

39 Manual Supplement Rosemount 3300 Series ATEX APPROVAL Figure Approval Label ATEX Approval and Name Plate E1 Flameproof: II 1/2 GD T80 C. EEx d [ia] IIC T6 (-40 C<T a <+75 C). KEMA 01ATEX2220X. U m = 250 V. Approval valid for Modbus and HART option. SPECIAL CONDITIONS FOR SAFE USE (X): When used in a potentially explosive atmosphere where the use of equipment-category 1 apparatus is required, appropriate measures must be taken to prevent electrostatic discharge. 1-39

40 Rosemount 3300 Series Manual Supplement CANADIAN STANDARDS ASSOCIATION (CSA) APPROVAL Figure Approval Label Canadian Standards Association (CSA) Approval and Name Plate Cert. no E6 Explosion-proof: Class I, Div. 1, Groups C and D. Dust-ignition-proof: Class II, Div. 1 and 2, Groups G and coal dust. Class III, Div. 1, Haz. Loc. [Ex ia IIC T6]. Ambient temperature limits -50 C to +85 C. Factory sealed. Approval valid for Modbus and HART option. 1-40

41

42 Rosemount 3300 Series Manual Supplement The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. PlantWeb is a registered trademark of one of the Emerson Process Management group of companies. Teflon, VITON, and Kalrez are registered trademarks of DuPont Performance Elastomers. Asset Management Solutions is a trademark of Emerson Process Management. All other marks are the property of their respective owners. Standard Terms and Conditions of Sale can be found at Rosemount Inc. All rights reserved. Emerson Process Management Rosemount Measurement 8200 Market Boulevard Chanhassen MN USA Tel (USA) Tel (International) F Emerson Process Management Shared Services Ltd Heath Place Bognor Regis West Sussex PO22 9SH England Tel +44 (1243) Fax +44 (1243) Emerson Process Management Asia Pacific Pte Ltd 1 Pandan Crescent Singapore Tel Fax Service Support Hotline: Enquiries@AP.EmersonProcess.com Rev BA 09/08

Guided Wave Radar Level and Interface Transmitter

Guided Wave Radar Level and Interface Transmitter Quick Installation Guide Rosemount 3300 Series Guided Wave Radar Level and Interface Transmitter Start Step 1: Mount the Transmitter Head/Probe Step 2: Set Jumpers and Switches Step 3: Connect the Wiring

More information

3420 Fieldbus Interface Module (FIM) Contents

3420 Fieldbus Interface Module (FIM) Contents Obtain all the benefits of FOUNDATION fieldbus technology and products without a fieldbus ready system Interface to existing systems with Modbus, OPC, XML, and HTTP protocols Integrated webserver for access

More information

Smart Wireless THUM Adapter

Smart Wireless THUM Adapter Quick Installation Guide Smart Wireless THUM Adapter Smart Wireless THUM Adapter Start Wireless Considerations Step 1: Physical Installation Step 2: Verify Operation Reference Information Product Certifications

More information

TORRIX-HART. Technical Documentation. The magnetostrictive level sensor with HART Protocol. Edition: Version: 5 Article no.

TORRIX-HART. Technical Documentation. The magnetostrictive level sensor with HART Protocol. Edition: Version: 5 Article no. Technical Documentation TORRIX-HART The magnetostrictive level sensor with HART Protocol Edition: 2016-10 Version: 5 Article no.: 207095 FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel:

More information

Rosemount 248 Wireless Temperature Transmitter

Rosemount 248 Wireless Temperature Transmitter Quick Installation Guide Rosemount 248 Wireless Rosemount 248 Wireless Temperature Transmitter Start Wireless Considerations Step 1: Physical Installation Step 2: Verify Operation Reference Information

More information

Smart Wireless THUM Adapter

Smart Wireless THUM Adapter Reference Manual Smart Wireless THUM Adapter www.rosemount.com Reference Manual Smart Wireless THUM Adapter Smart Wireless THUM Adapter Smart Wireless THUM Adapter Hardware Revision 1 HART Device Revision

More information

LCD Meter for Model 3051 Pressure Transmitters English Rev. AA

LCD Meter for Model 3051 Pressure Transmitters English Rev. AA LCD Meter for Model 3051 Pressure Transmitters 00809-0300-4001 English Rev. AA CONTENTS Before you Install the Meter Kit...................... 3 Overview....................................... 5 Safety

More information

Rosemount 2410 Tank Hub

Rosemount 2410 Tank Hub Upgrade Instruction for Primary Bus and Secondary Bus Manual Supplement 1.1 Safety Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing

More information

Rosemount VeriCase User Guide

Rosemount VeriCase User Guide Quick Start Guide 00825-0500-4530, Rev AC Rosemount VeriCase User Guide Rosemount 3308 and 5300 Series Level Transmitters with HART and Modbus Quick Start Guide Rosemount VeriCase 1.0 Rosemount VeriCase

More information

1420 Wireless Gateway

1420 Wireless Gateway Highest level of wireless security in the industry >99% data reliability No site survey required Seamless and flexible host integration Integrated web server for access to field device and process data

More information

HART Communicator. Emerson Process Management Catalog

HART Communicator. Emerson Process Management Catalog HART Communicator Connect to any HART instrument with the HART Communicator the only communicator you ll need Store over 100 device configurations in just one HART Communicator ready to carry to the field

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Rosemount 2088 and 2090 Appendix B Rosemount 275 HART Communicator Overview....................................... page

More information

FIELDVUE Digital Valve Controllers. Tri-Loop Signal Converter Operation with FIELDVUE Digital Valve Controllers

FIELDVUE Digital Valve Controllers. Tri-Loop Signal Converter Operation with FIELDVUE Digital Valve Controllers Instruction Manual Supplement D103267X012 FIELDVUE Digital Valve Controllers Supplement to HART Communicating Fisher FIELDVUE Digital Valve Controller Instruction Manuals Using the HART Tri-Loop HART-to-Analog

More information

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description I/O extension module, eight digital transistor outputs Data sheet 105364_en_00 PHOENIX CONTACT 2013-03-26 1 Description The I/O extension module can be used in conjunction with Radioline wireless modules

More information

FLEX Ex Spring Clamp Terminal Base

FLEX Ex Spring Clamp Terminal Base Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification

More information

Rosemount 702 Wireless Discrete Transmitter

Rosemount 702 Wireless Discrete Transmitter Reference Manual Rosemount 702 Wireless Discrete Transmitter www.rosemount.com Reference Manual Rosemount 702 Rosemount 702 WirelessHART Discrete Transmitter Rosemount 702 Hardware Revision HART Device

More information

Rosemount 2051G Pressure Transmitter

Rosemount 2051G Pressure Transmitter Quick Start Guide 00825-0700-4101, Rev AA Rosemount 2051G Pressure Transmitter with 4-20 ma HART Protocol (Revision 5 and 7) Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount

More information

ABB Drives. User s Manual Modbus Adapter Module FMBA-01

ABB Drives. User s Manual Modbus Adapter Module FMBA-01 ABB Drives User s Manual Modbus Adapter Module FMBA-01 Modbus Adapter Module FMBA-01 User s Manual 3AFE68586704 REV A EN EFFECTIVE: 27.06.2005 2005 ABB Oy. All Rights Reserved. 5 Safety instructions

More information

FloBoss 107 IEC Interface

FloBoss 107 IEC Interface FB107:62591 Product Data Sheet D301713X012 May 2018 FloBoss 107 IEC 62591 Interface The IEC 62591 Interface allows a FloBoss 107 Flow Manager (FB107) to communicate with any mix of up to 20 WirelessHART

More information

Carbon Monoxide Sensor - ModBus

Carbon Monoxide Sensor - ModBus Introduction The CO Sensor uses an electrochemical sensor to monitor CO level in a range of 0 to 500 ppm and communicates via an RS-485 network configured for ModBus protocol. Before Installation Read

More information

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description I/O extension module with 8 digital inputs or 2 pulse inputs INTERFACE Data sheet 0483_en_00 PHOENIX CONTACT 203-04-05 Description The I/O extension module can be used in conjunction with Radioline wireless

More information

Installation & Operation Manual

Installation & Operation Manual Via Enrico Fermi, 2 I-25015 Desenzano del Garda (BS) - Italy Phone: +39 030 7870787 Fax: +39 030 7870777 www.solexy.net BAF Intrinsically Safe Ethernet Coupler for signals operating in Hazardous Areas

More information

General Specifications. P2-SCM Serial Communications

General Specifications. P2-SCM Serial Communications General Specifications Module Type Intelligent Modules per Base I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to Logic

More information

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description I/O extension module, 4 digital relay outputs INTERFACE Data sheet 104834_en_01 PHOENIX CONTACT 2013-01-21 1 Description The RAD-DOR4-IFS I/O extension module can be used in conjunction with Radioline

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

ControlWave Micro IEC Interface

ControlWave Micro IEC Interface CWMICRO:62591 Product Data Sheet D301714X012 January 2015 ControlWave Micro IEC 62591 Interface The IEC 62591 Interface allows a ControlWave Micro to communicate with any mix of up to 100 WirelessHART

More information

ROC800-Series IEC Interface

ROC800-Series IEC Interface ROC800:62591 Product Data Sheet D301712X012 October 2016 ROC800-Series IEC 62591 Interface The IEC 62591 Interface allows a Series 2 ROC800 Remote Operations Controller (ROC800) to communicate with any

More information

P3-SCM. General Specifications

P3-SCM. General Specifications General Specifications Module Type Modules per Base Modules per Group I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to

More information

Instruction Manual. T3110 T3110L T3110Ex

Instruction Manual. T3110 T3110L T3110Ex www.cometsystem.cz Instruction Manual T3110 T3110L T3110Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with 4-20 ma outputs Copyright: COMET System,

More information

Transducers & Transmitters HART USERS MANUAL. GP:50 New York LTD Long Road Grand Island, NY USA

Transducers & Transmitters HART USERS MANUAL. GP:50 New York LTD Long Road Grand Island, NY USA Transducers & Transmitters Industrial & Aerospace Pressure Measurement WWW.GP50.COM HART USERS MANUAL GP:50 New York LTD. 2770 Long Road Grand Island, NY 14072 USA Tel. (716) 773-9300 Fax (716) 773-5019

More information

General Specifications

General Specifications General Specifications Field Wireless Communication Module GENERAL This General Specification (GS) describes the specifications for Field Wireless Communication Module. This product is based on the industrial

More information

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01 ABB Drives User s Manual Modbus Adapter Module RMBA-01 Modbus Adapter Module RMBA-01 User s Manual 3AFE 64498851 REV A EN EFFECTIVE: 1.3.2002 2002 ABB Oy. All Rights Reserved. Safety instructions Overview

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS LonWorks Communication Card RXRX-AY02 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED

More information

MU110-6U. Analog output module 6 channel. User guide

MU110-6U. Analog output module 6 channel. User guide MU110-6U Analog output module 6 channel User guide MU110-6U_2016.12_0221_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Тел.: +49 (0)

More information

Rosemount 3490 Series Universal Control Unit

Rosemount 3490 Series Universal Control Unit Quick Installation Guide Universal Control Unit Start 1. Introduction 2. Installation 3. Getting Started 4. Application Examples 5. Other Features 6. Product Certifications 7. Other Safety Information

More information

ControlWave Micro HART / BTI Interface Module

ControlWave Micro HART / BTI Interface Module CWMICRO:HIM Product Data Sheet D301636X012 February 2012 ControlWave Micro HART / BTI Interface Module The HART (Highway Addressable Remote Transducer) / BTI (Bristol Transmitters) Interface Module is

More information

ELSETA IOMOD 8DI8DO. User manual. Elseta 3/2017 V1.0

ELSETA IOMOD 8DI8DO. User manual. Elseta 3/2017 V1.0 ELSETA User manual Elseta 3/2017 V1.0 COPYRIGHTS AND TRADEMARKS Elseta is UAB Aedilis trademark that identifies UAB Aedilis manufactured products. All of the products copyright belongs to "Aedilis. These

More information

MGate 5105-MB-EIP Quick Installation Guide

MGate 5105-MB-EIP Quick Installation Guide MGate 5105-MB-EIP Quick Installation Guide Edition 2.2, March 2019 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777 Fax: 1-714-528-6778

More information

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F PSD1000 - PSD1000F INSTRUCTION MANUAL Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD1000 - Universal AC Input Switching Power Supply 24 Vdc Output ISM0089-4

More information

Connecting an Emerson Wireless Gateway to the ABB Totalflow XRC 6490

Connecting an Emerson Wireless Gateway to the ABB Totalflow XRC 6490 Connecting an Emerson Wireless Gateway to the ABB Totalflow XRC 6490 Purpose................................................................... page 1 Emerson WirelessHART Gateway............................................

More information

Micro Motion MVD Direct Connect Meters

Micro Motion MVD Direct Connect Meters Instruction Manual P/N 20002273, Rev. A August 2005 Micro Motion MVD Direct Connect Meters Manual Before You Begin Before You Begin This manual provides installation information for Micro Motion MVD Direct

More information

MPI-DN, MPI-D MULTICHANNEL ELECTRONIC RECORDER for HART or RS-485/ MODBUS RTU SENSORS

MPI-DN, MPI-D MULTICHANNEL ELECTRONIC RECORDER for HART or RS-485/ MODBUS RTU SENSORS MPI-DN, MPI-D MULTICHANNEL ELECTRONIC RECORDER for HART or RS-485/ MODBUS RTU SENSORS 18 channels for HART / Modbus RTU sensors 2 digital channels 16 math channels 4 relay outputs for alarm or control

More information

MGate 5111 Quick Installation Guide

MGate 5111 Quick Installation Guide MGate 5111 Quick Installation Guide Edition 1.0, December 2017 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777 Fax: 1-714-528-6778

More information

Installation & Operation Manual

Installation & Operation Manual Via Enrico Fermi, 2 I-25015 Desenzano del Garda (BS) - Italy Phone: +39 030 7870787 Fax: +39 030 7870777 www.solexy.net BAF Intrinsically Safe Ethernet Coupler for signals operating in Hazardous Areas

More information

Quick Start Guide MHM CC-PBF-EN, Rev 1 April Emerson A0701PBU. Emerson 701P SmartPower Module - Blue

Quick Start Guide MHM CC-PBF-EN, Rev 1 April Emerson A0701PBU. Emerson 701P SmartPower Module - Blue Quick Start Guide MHM-97913-CC-PBF-EN, Rev 1 April 2017 Emerson A0701PBU Emerson 701P SmartPower Module - Blue Quick Start Guide April 2017 Copyright 2017 by Emerson. All rights reserved. No part of this

More information

technical datasheet technical datasheet MTL660 Displays Loop-powered indicators for hazardous areas

technical datasheet technical datasheet MTL660 Displays Loop-powered indicators for hazardous areas technical datasheet technical datasheet MTL0 Displays Loop-powered indicators for hazardous areas Loop powered -0mA Field and panel mounting Environmental protection to IP7 Easy to configure Number of

More information

Smart Wireless Gateway

Smart Wireless Gateway Gateway connects wireless self-organizing networks with any host system Easy configuration and management of self-organizing networks Easy integration into control systems and data applications through

More information

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions Specialists in Liquid Level Indication MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions Section: M500 Bulletin: M500.31 Date: 05-17-16 Supersedes: 09-30-11 1. INTRODUCTION

More information

Installation and Maintenance Manual IM 969-5

Installation and Maintenance Manual IM 969-5 Installation and Maintenance Manual IM 969-5 Group: Controls Part Number: IM 969 Date: January 2018 MicroTech III Chiller Unit Controller Modbus Communication Module Models AGZ and AMZ Trailblazer Air-cooled

More information

SMARTLINE RM76 Supplementary instructions

SMARTLINE RM76 Supplementary instructions SMARTLINE RM76 Supplementary instructions 2-wire / Guided Radar (TDR) Level Meter Supplementary Instructions for ATEX applications CONTENTS SMARTLINE RM76 1 General safety information 5 1.1 Scope of the

More information

Serial Communication Converters & Adapters Instruction Manual

Serial Communication Converters & Adapters Instruction Manual Serial Communication Converters & Adapters Instruction Manual RS-232 to RS-422/485 Converter Isolated RS-232 to RS-422/485 Converter USB to RS-232 Converter USB to RS-422/485 Converter Isolated USB to

More information

Model Hydrostatic Interface Unit. Model 3201

Model Hydrostatic Interface Unit. Model 3201 Hydrostatic Interface Unit Microprocessor-based electronics Performs system calculations including transfer variables Software configurable for specific tank applications Digital and 4 20 ma communication

More information

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50 MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287 Installation and Operations Manual 00-02-0651 09-01-09 Section 50 In order to consistently bring you the highest quality, full featured products,

More information

SPiiPlusEC Network Manager Installation Guide November2014 Document Revision: 02

SPiiPlusEC Network Manager Installation Guide November2014 Document Revision: 02 SPiiPlusEC Network Manager Installation Guide November2014 Document Revision: 02 SPiiPlusEC Release Date: November2014 Copyright ACS Motion Control Ltd.2014. All rights reserved. Changes are periodically

More information

Supplement to Instruction Bulletin Micro-DCI 53ML5100A 53ML5100 MANUAL LOADING STATION REV. 1 FIRMWARE. PN24698 Rev. 1

Supplement to Instruction Bulletin Micro-DCI 53ML5100A 53ML5100 MANUAL LOADING STATION REV. 1 FIRMWARE. PN24698 Rev. 1 Supplement to Instruction Bulletin Micro-DCI 53ML5100A 53ML5100 MANUAL LOADING STATION REV. 1 FIRMWARE PN24698 Rev. 1 The Company MicroMod Automation, Inc. MicroMod Automation is dedicated to improving

More information

Smart Wireless Gateway

Smart Wireless Gateway Product Data Sheet Gateway connects wireless self-organizing networks with any host system Easy configuration and management of self-organizing networks Easy integration into control systems and data applications

More information

PD301 - PD306 Head Mount SMART TEMPERATURE TRANSMITTERS

PD301 - PD306 Head Mount SMART TEMPERATURE TRANSMITTERS PD301 - PD306 Head Mount SMART TEMPERATURE TRANSMITTERS HART Non-HART Smart Temperature Transmitters with HART Protocol Universal Input: RTD, TC, Ohm & mv Program with PC or HART Communicator Low-Cost

More information

Webinar Organizers. Ryan Shea. Bruce McDuffee. Joe Ryan. Webinar Moderator. Applications Specialist. Product Manager. Precision Digital Corporation

Webinar Organizers. Ryan Shea. Bruce McDuffee. Joe Ryan. Webinar Moderator. Applications Specialist. Product Manager. Precision Digital Corporation Webinar Organizers Joe Ryan Product Manager Precision Digital Corporation Ryan Shea Applications Specialist Precision Digital Corporation Bruce McDuffee Webinar Moderator Precision Digital Corporation

More information

Do not open when energized or when an explosive atmosphere is present. Electrostatic hazard, clean only with damp cloth.

Do not open when energized or when an explosive atmosphere is present. Electrostatic hazard, clean only with damp cloth. D460/D470 Series - ATEX certified position transmitter nnnn II 2 GD ITS 11 ATEX 17431X Ex d IIC T* Gb Tamb -*ºC to +*ºC Ex tb IIIC T* Db Tamb -*ºC to +*ºC IP6X Ambient variation -60 C to +110 C (T4/T130

More information

TRANSDUCER T4311, T4411

TRANSDUCER T4311, T4411 TRANSDUCER T4311, T4411 Programmable temperature transducer for RTD Pt1000 sensor with serial output RS232 and RS485 Instruction manual Instruction Manual for use of transducer: T4311 (RS232), T4411 (RS485)

More information

Rosemount 0085 Pipe Clamp Sensor

Rosemount 0085 Pipe Clamp Sensor Product Data Sheet Rosemount Pipe Clamp Sensor Rosemount 0085 Pipe Clamp Sensor Non-intrusive design for fast and easy temperature measurement in piping applications Platinum RTD Temperature Sensors with

More information

CAN485. Wall Mounting CAN to RS-485 Interface Converter. Support data conversion between 1 CAN port and 1 RS-485 serial port

CAN485. Wall Mounting CAN to RS-485 Interface Converter. Support data conversion between 1 CAN port and 1 RS-485 serial port CAN485 Wall Mounting CAN to RS-485 Interface Converter Support data conversion between 1 CAN port and 1 RS-485 serial port Support multiple conversion modes like transparent conversion, marked transparent

More information

Flex Series User Guide

Flex Series User Guide User Programmable Current 4..20mA Digital RS485 Dual & Single Axis Up to 360º 2016 Flex Series User Guide Sensor Installation, Wiring, Flexware App Instructions Page 1 of 33 Page 2 of 33 Table of Contents

More information

Expansion module EM-BAC-MOD-01. Installation manual

Expansion module EM-BAC-MOD-01. Installation manual Installation manual GB/en Expansion module EM-BAC-MOD-01 BACnet MS/TP or Modbus RTU interface card for EASYLAB controller TCU3 and adapter module TAM Firmware from 4.0 TROX GmbH Heinrich-Trox-Platz 47504

More information

4 â Active barrier RN221N with optional HART diagnosis. Technical Information

4 â Active barrier RN221N with optional HART diagnosis. Technical Information Technical Information Active barrier with optional HART diagnosis Active barrier with power supply for safe separation of 4 to 20 ma current circuits Application Galvanic isolation of 4 to 20 ma current

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Vision OPLC V130 COM Modules: V100-17-CAN, V100-17-RS4/X, V100-17-ET2 This guide shows you how to install an additional communication module in a V130 controller. Instructions and technical specifications

More information

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

CEM M-RS485 INSTRUCTION MANUAL (M014B A) Communications interface CEM M-RS485 INSTRUCTION MANUAL (M014B01-03-14A) 2 SAFETY PRECAUTIONS Follow the warnings described in this manual with the symbols shown below. DANGER Warns of a risk, which could

More information

DR7100 SERIES Supplementary instructions

DR7100 SERIES Supplementary instructions DR700 SERIES Supplementary instructions Guided Radar (TDR) Level Instrument for 2-wire control systems Supplementary Instructions for ATEX applications AMETEK Drexelbrook - EDO -0-2, DR700-LM ATEX, Issue

More information

Family of Water Cut Analyzers

Family of Water Cut Analyzers Phase Dynamics Technology for Precision Measurements Phase Dynamics, Inc. 1251 Columbia Drive Richardson, TX 75081 USA E-Mail sales@phasedynamics.com Tel: 972-680-1550 Fax: 972-680-3262 Family of Water

More information

ICF-1150 Series Quick Installation Guide

ICF-1150 Series Quick Installation Guide ICF-1150 Series Quick Installation Guide Fifth Edition, July 2015 2015 Moxa Inc. All rights reserved. P/N: 1802011500014 1802011500014 Overview Introduction ICF-1150 series fiber converters have a multi-interface

More information

Rosemount 3051S MultiVariable Transmitter Rosemount 3051SF Series Flowmeter MultiVariable Transmitter. Start

Rosemount 3051S MultiVariable Transmitter Rosemount 3051SF Series Flowmeter MultiVariable Transmitter. Start Quick Installation Guide Rosemount 3051SMV Rosemount 3051S MultiVariable Transmitter Rosemount 3051SF Series Flowmeter MultiVariable Transmitter Start Step 1: Mount the Transmitter Step 2: Consider Housing

More information

Oldham OLCT 200 Revision 1

Oldham OLCT 200 Revision 1 HART Field Device Specification: Oldham OLCT 200 Revision 1 Initial release: 13 April 2011 Current release: 13 April 2011 Part Number: 77036008 Revision: 02.1 HART is a registered trademark of the HART

More information

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice. MCD Modbus Module Instructions Important User Information INSTALLATION INSTRUCTIONS: MCD MODBUS MODULE Order Code: 175G9000 1. Important User Information Observe all necessary safety precautions when controlling

More information

HRM-0800 Instruction Manual

HRM-0800 Instruction Manual HRM-0800 Instruction Manual Table of Contents 1 Highway Addressable Remote Transducer (HART ) 4 2 General Specifications 5 3 Dimensions: 6 4 General Description 7 4.1 Introduction 7 4.2 Purpose 8 4.3 Functions

More information

Smart Wireless Gateway

Smart Wireless Gateway Product Data Sheet Gateway connects wireless self-organizing networks with any host system Easy configuration and management of self-organizing networks Easy integration into control systems and data applications

More information

Installation and Programming Manual

Installation and Programming Manual PMN Manual PMN Installation and Programming Manual This Manual describes the PMN PowerLogic Modbus Plus Network module, its uses and set up. Effective: 12 August, 1999 Niobrara Research & Development Corporation

More information

ADAMCZEWSKI. Ordering data AD-STVEX 710 GVD Option: Factory-software configuration as per customer specifications.

ADAMCZEWSKI. Ordering data AD-STVEX 710 GVD Option: Factory-software configuration as per customer specifications. EN ADAMCZEWSKI Elektronische Messtechnik GmbH Felix-Wankel-Str. 13 / 74374 Zaberfeld Tel. +49 (0)7046-875 Fax +49 (0)7046-7678 vertrieb@ad-messtechnik.de Operating Instructions Supply Isolation Amplifier

More information

MANUAL Surge Protectors

MANUAL Surge Protectors PROCESS AUTOMATION MANUAL Surge Protectors DP-LBF-I1.36.DE and DP-LBF- I1.36.IE With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery

More information

ICF-1150 Series Quick Installation Guide

ICF-1150 Series Quick Installation Guide ICF-1150 Series Quick Installation Guide Second Edition, March 2012 2012 Moxa Inc. All rights reserved. P/N: 1802011500011 Overview Introduction The ICF-1150 series fiber converters are equipped with a

More information

PACSystems* RX3i IC695CMM002 and IC695CMM004

PACSystems* RX3i IC695CMM002 and IC695CMM004 May 2010 PACSystems* RX3i IC695CMM002 and IC695CMM004 Serial Communications Modules PACSystems* RX3i Serial Communications modules expand the serial communications capabilities of the RX3i system. Serial

More information

MODEL: 6DV-B. [2] TERMINAL BLOCK 0: None (Euro terminal block at the rear of indicator module)

MODEL: 6DV-B. [2] TERMINAL BLOCK 0: None (Euro terminal block at the rear of indicator module) Field-mounted Two-wire Signal Conditioners 6-UNIT -DIGIT LOOP POWERED INDICATOR (outdoor enclosure, intrinsically safe/explosion-proof) Functions & Features -digit LED display No external power source

More information

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for Version 1.0 5.02.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE TTDM-128 TraceTek Leak Detection Master Module Installation Instructions TRACETEK APPROVALS AND CERTIFICATIONS TYPE NM General Signaling Equipment 76LJ GENERAL INFORMATION Please read these instructions

More information

T2314, T2414. Instruction Manual

T2314, T2414. Instruction Manual Atmospheric pressure transmitter T2314, T2414 with RS232 / RS485 serial output Instruction Manual Instruction Manual Device type Pressure Output Galvanic isolated output T2314 RS232 - T2414 RS485 Device

More information

RS-FX-N01 wind transmitter user's Guide (485type)

RS-FX-N01 wind transmitter user's Guide (485type) RS-FX-N01 wind transmitter user's Guide (485type) Issue:. V1. 0 1 2 Context 1. Introduction...4 2. Installation instructions... 5 3. Configure the software installation and use...7 4. Communication Protocol...

More information

TEK- LCD 7804B. Explosion-Proof Modbus Scanner. ACCESSORIES. Technology Solutions

TEK- LCD 7804B. Explosion-Proof Modbus Scanner.   ACCESSORIES. Technology Solutions Technology Solutions TEK- LCD 7804B Explosion-Proof Modbus Scanner ACCESSORIES www.tek-trol.com Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys Introduction The Tek-LCD 7804B Explosion-Proof

More information

PACSystems* RX3i IC695CMM002 and IC695CMM004

PACSystems* RX3i IC695CMM002 and IC695CMM004 April 2010 PACSystems* RX3i IC695CMM002 and IC695CMM004 Serial Communications Modules PACSystems * RX3i Serial Communications modules expand the serial communications capabilities of the RX3i system. Serial

More information

Rosemount 3051P Pressure Transmitter

Rosemount 3051P Pressure Transmitter Quick Start Guide 00825-0200-4007, Rev AA Rosemount 3051P Pressure Transmitter with 4-20 ma HART Protocol (Revision 5 and 7) Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount

More information

Rosemount 3493 LOGView

Rosemount 3493 LOGView Manual Supplement Software Version 1.20 www.rosemount.com Manual Supplement 2007 Rosemount Inc. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and

More information

Technical Information Promonitor NRF560

Technical Information Promonitor NRF560 TI00462G/08/EN/03.14 71264171 Products Solutions Services Technical Information For tank side monitor and control of Proservo NMS5 intelligent tank gauge Application is a monitoring unit for use with Proservo

More information

Process display RIA 251. Digital loop powered display for ma current loops. Application areas. Plant and machine construction.

Process display RIA 251. Digital loop powered display for ma current loops. Application areas. Plant and machine construction. Technical information TI 063R/09/en Mat. No. 510 00857 Process display RIA 251 Digital loop powered display for 4...20 ma current loops Application areas Plant and machine construction Control panels Laboratory

More information

INSTRUCTION MANUAL WCS-Interface Module, DeviceNet

INSTRUCTION MANUAL WCS-Interface Module, DeviceNet FACTORY AUTOMATION INSTRUCTION MANUAL WCS-Interface Module, DeviceNet WCS-DG210 Part. No. 202340 / DOCT-1305 / 11. june 2007 1 Working principle............................ 6 2 Installation and commissioning.................

More information

ScanView EX Software Programming Software for PD6730X & PD6830X Modbus Scanners

ScanView EX Software Programming Software for PD6730X & PD6830X Modbus Scanners ScanView EX Software Programming Software for PD6730X & PD6830X Modbus Scanners TM For PD6730X & PD6830X Vantageview PD6730X ProtEX PD6830X FREE Download Easily Configure PD6730X & PD6830X Modbus Scanners

More information

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions 3710 ACM 3750 PDC 3800 RTU ISOCOM Communications Card Retrofit Instructions Danger During normal operation of this device, hazardous voltages are present which can cause severe injury or death. These

More information

ICN Mini Link/External. User s Guide. 1733N Model A Mini Link/EXT (Version 1) 1732N Model A ICN Interface Board (Version 1)

ICN Mini Link/External. User s Guide. 1733N Model A Mini Link/EXT (Version 1) 1732N Model A ICN Interface Board (Version 1) ICN Mini Link/External User s Guide 1733N Model A Mini Link/EXT (Version 1) 1732N Model A ICN Interface Board (Version 1) MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving

More information

Smart Wireless THUM Adapter

Smart Wireless THUM Adapter Product Data Sheet Smart Wireless THUM Adapter An installation-ready solution that provides rich WirelessHART data 2- or 4-wire HART devices Flexibility to meet your most demanding applications Wireless

More information

RAD-DAIO6-IFS. I/O extension module, 1 analog input/output, 2 digital wide-range inputs/outputs. INTERFACE Data sheet.

RAD-DAIO6-IFS. I/O extension module, 1 analog input/output, 2 digital wide-range inputs/outputs. INTERFACE Data sheet. I/O extension module, 1 analog input/output, 2 digital wide-range inputs/outputs INTERFACE Data sheet 104832_en_01 PHOENIX CONTACT 2013-01-21 1 Description The RAD-DAIO6-IFS I/O extension module can be

More information

Modbus. Instructions 42/ EN

Modbus. Instructions 42/ EN 0XOW9VRQ Modbus Instructions 42/15-727 EN Contents 1 Electrical Connection............................. 2 2 Device Mode..................................... 2 3 Important Information For Users....................

More information

Type i2p-100 Electro-Pneumatic Transducer

Type i2p-100 Electro-Pneumatic Transducer Product Bulletin i2p-100 Transducer Type i2p-100 Electro-Pneumatic Transducer The Type i2p-100 electro-pneumatic transducer, shown in figure 1, uses a patented converter module that converts a milliampere

More information

TFR5. Room or outdoor temperature sensor. Operating instructions for temperature sensor. English page 1...5

TFR5. Room or outdoor temperature sensor. Operating instructions for temperature sensor. English page 1...5 EN/2018-03-14 Design and specifications subject to change without notice Operating instructions for temperature sensor English page 1...5 Field of application CombiTemp is a temperature sensor, based on

More information