REGARD mA output module. Installation, operation and maintenance
|
|
- Shauna McKinney
- 5 years ago
- Views:
Transcription
1 REGARD mA output module Installation, operation and maintenance Issue 1 November 2006
2 FOR YOUR SAFETY Follow the instructions Read this manual before installing the module. Maintenance The equipment must be inspected and serviced regularly by trained personnel. Keep a record of inspections and servicing. Repairs of this equipment should only be carried out by competent personnel. We recommend that either a training course or service contract is obtained from Draeger and that all repairs are carried out by them. If the system is being used to monitor flammable gases/vapours and/or oxygen, refer to EN and/or local regulations. Not for use in areas where explosion hazards are possible This equipment is not approved or certified for installation in potentially explosive atmospheres. Liability for proper function or damage Liability for proper function of the equipment is irrevocably transferred to the owner or operator to the extent that the equipment is serviced or repaired by personnel not employed or authorised by Draeger, or if the equipment is used in a manner not conforming to its intended use. Draeger Safety UK Limited can not be held responsible for any damage caused by non-compliance with the above recommendations. The warranty and liability provisions of the terms and conditions of sale and delivery of Draeger Safety UK Limited are likewise not modified by the recommendations given above. 2 Issue 1 November 2006
3 INTENDED USE For remote indication or recording of gas levels. Not for control of counter-measures against risk of explosion. The 4-20mA output module is not included in the scope of the Regard 3900 ATEX EC-type examination. The module must be mounted within the Regard 3900 control unit enclosure. Up to four modules can be installed if there is space in the enclosure. Do not mount the module outside the 3900 enclosure. Do not extend the 3900 ribbon cable or use a longer ribbon cable, in order to install output modules remote from the input module(s). The module can be used in Regard 3910 systems. Do not exceed 2m ribbon cable length. The Regard mA output module will not work with Regard DESCRIPTION The module has eight outputs, electrically isolated from the Regard 3900 system. Each output is a current source and will only work when connected to a passive load. Each output has two terminals: + output module 0V The module s 0V is isolated from the Regard 3900 system 0V. Each output supplies a 4..20mA signal proportional to the gas level for its corresponding input channel. The module s outputs correspond to channels 1-8 or channels 9-16 of the Regard 3900 system, depending on the position of the Channels link on the 4-20mA output module. The output of inactive channels is 0mA. Issue 1 November
4 Zero clamp Because the system s gas level reading is clamped to zero when the gas level is within 2% of zero, the output of the 4-20mA will also will also jump between 4.0 to 4.3 ma when the gas level varies around zero. Example for input channel with measuring range 0 100: Gas sensor input (ma) Regard 3900 display reading 4-20mA module output (ma) Inhibit When the Regard 3900 inhibit switch is set to position 1 all 4-20mA outputs freeze at the output level at that time the Inhibit switch is operated. When the inhibit switch is returned position 0 all outputs return to normal. Module fault If the 4-20mA output module has a fault all outputs on the module will jump to a steady 1mA (±0.3mA) LEDs Green LED: DC power on; lit when DC supply to the module is on. Red LEDs: diagnostics; flicker or dimly lit during normal operation. 4 Issue 1 November 2006
5 INSTALLATION & CONFIGURATION 1. Fit the output module in an unused position, or on top of any existing modules, in the 3900 enclosure using the spacers and fittings provided. 2. Connect the Regard 3900 ribbon cable to the module(s). 3. Set the Channels link on the module. Link on position 1-8: Link on position 9-16: Issue 1 November
6 Two or more modules can be set to the same channels (1-8 or 9-16) 4. Connect the signal outputs. Unused outputs can be left unconnected. MAINTENANCE Check the module for correct operation at regular intervals. Fault finding Fault Cause Remedy No signal from all outputs; green LED not lit. No signal from all or some outputs; green LED is lit. Output constant approx. 1mA Output constant but gas level display changing Output current too low or will not reach 20mA Red LEDs unlit or permanently lit No DC supply to module Faulty module No signal from input modules Wrong channels selected on 4-20mA module No signal from input module(s) Fault on output module. Connect system ribbon cable to module Replace module Check input modules Check position of Channels link Press Acknowledge Check connection to input module(s) If fault persists then replace module. System in inhibit Return Inhibit switch to position 0 Load resistance too high Fault on output module or input or relay modules Reduce load resistance Check all modules 6 Issue 1 November 2006
7 SPECIFICATIONS Output range ma Isolation 50 V Cable cross-section 0.5 to 2.5 mm 2 Resolution 0.1mA Accuracy ± 1% Maximum load 500 ohms Operating temperature range 0 to 55 C Storage temperature range -25 to +70 C DC input voltage 18 to 30V DC Power / current consumption Approx. 7W / 300mA at 24V Part numbers Description Part number 4-20mA output module mA output module manual (English) mA output module manual (German) The Regard mA output module will not work with Regard Issue 1 November
8 Draeger Safety UK Ltd Riverside Business Park Blyth, Northumberland NE24 4RG United Kingdom Tel Fax Manual part number Issue 1 November 2006
Operating Instructions. Intrinsically Safe Isolation Relay for Switches Model: REL manual_rel-6_0505
Operating Instructions Intrinsically Safe Isolation Relay for Switches Model: REL-6003 manual_rel-6_0505 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...3 5. Operating
More informationADAMCZEWSKI. Ordering data AD-STVEX 710 GVD Option: Factory-software configuration as per customer specifications.
EN ADAMCZEWSKI Elektronische Messtechnik GmbH Felix-Wankel-Str. 13 / 74374 Zaberfeld Tel. +49 (0)7046-875 Fax +49 (0)7046-7678 vertrieb@ad-messtechnik.de Operating Instructions Supply Isolation Amplifier
More informationPolymer Electric. Operating Instructions. Control Unit SG-RST 153. Version 0.3
Operating Instructions Control Unit SGRST 153 Version 0.3 1004931 SGRST 153 Original instructions GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY Tel.: +49 731 20610 Fax: +49 731 2061222 EMail: info.ulm@mayser.com
More informationOperating Instructions. Isolation Relay for Switches Model: RL manual_rl-6100_1116
Operating Instructions Isolation Relay for Switches Model: RL-6100 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...3 5. Operating Principle...4 6. Mechanical Connection...4
More informationOperating instructions. Switching amplifier DN0210 DN / / 2015
Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5
More informationOperating Instructions. Power Supply & Isolation Relay for Switches Model: RL manual_rl-5900_0215
Operating Instructions Power Supply & Isolation Relay for Switches Model: RL-5900 manual_rl-5900_0215 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...3 5. Operating
More informationEnglish. Operating manual. Universal transmitter UT125. Save for later reference. Companies / brands of GHM
English Operating manual Universal transmitter UT125 Companies / brands of GHM www.ghm-messtechnik.de Save for later reference. Table of contents page 1. Intended use (areas of application)... 3 1.1 Safety
More informationGEMS SENSORS & CONTROLS SERIES 35XX
GEMS SENSORS & CONTROLS OPERATING & INSTALLATION INSTRUCTIONS SERIES 35XX PLEASE READ CAREFULLY BEFORE INSTALLING Part Number: 560550-0128 Issue: B INTRODUCTION Series 35XX high output pressure transducers
More informationVDI Pro Voltage & Dry Contact Interface Installation and programming Guide MODEL VDI MK2
VDI Pro Voltage & Dry Contact Interface Installation and programming Guide MODEL VDI MK2 1 of 18 PREFACE Important Installation Information It is the purchasers responsibility to determine the suitability
More informationOperating instructions AS-i SmartLine module AC3200 AC /00 06/2016
Operating instructions AS-i SmartLine module AC3200 AC3201 80237876/00 06/2016 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Warnings used...3 2 Safety instructions...3 2.1 General...3 2.2 Target
More informationOperating instructions. Speed monitor D / / 2014
Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5
More informationMSR Level Control Relay Module Operating Instructions for Level Control Relay Module Model: MSR
Operating Instructions for Level Control Relay Module Model: MSR MSR Operation Instructions Rev. Apr 07 Page 1/8 1. Note Please read and take note of these operating instructions before unpacking and commissioning.
More informationSUPPLEMENTARY TYPE EXAMINATION CERTIFICATE
1. SUPPLEMENTARY TYPE EXAMINATION CERTIFICATE 2. Equipment or Protective System Intended for use in Potentially Explosive Atmospheres Directive 94/9/EC 3. Type Examination Certificate Number: ITS13ATEX47876X/1
More informationOperating Instructions
Innovative by tradition. Operating Instructions Control Unit SG-RSV 239 Version 1 1003986 SG-RSV 239/24 24 V= 1005372 SG-RSV 239/36 36 V= 1003271 SG-RSV 239 50-150 V= Mayser GmbH & Co. KG Örlinger Straße
More informationControl unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~
Innovative by tradition. Control unit SG-EFS 104/2W EN Operating instructions Version 0.9 1005196 SG-EFS 104/2W 24 V=/~ Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY
More informationPolymer Electric. Operating Instructions. Control Unit SG-TRS 3X8. Version 1
Operating Instructions Control Unit SGTRS 3X8 Version 1 100597 SGTRS 318 110 V= 100596 SGTRS 38 4 V= Original instructions GmbH & Co KG Örlinger Straße 1 3 89073 Ulm GERMANY Tel: +49 731 0610 Fax: +49
More informationExplosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter
Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2
More informationMSI-RM2 Safety Relays
MSI-RM2 Safety Relays EN 2010/11-603021 We reserve the right to make technical changes SAFE IMPLEMENTATION AND OPERATION Original operating instructions Relay module for Optoelectronic Protective Devices
More informationOperating instructions. Standstill monitor A / / 2011
Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II
More informationOperating Instructions. Power Supply & Latching Relay For Switches Model: RL manual_rl-6000_1016
Operating Instructions Power Supply & Latching Relay For Switches Model: RL-6000 manual_rl-6000_1016 1. Contents 1. Contents...2 2. Note...3 3. Instrument Inspection...3 4. Regulation Use...3 5. Operating
More informationType 9160 / Transmitter supply unit / Isolating repeater. Safety manual
Type 9160 / 9163 Transmitter supply unit / Isolating repeater Safety manual Safety manual English Content 1 General information... 3 1.1 Manufacturer... 3 1.2 Information regarding the Safety Manual...
More informationInductive sensor Dual sensors with extended temperature range NI4-DSU35TC-2Y1X2/S97
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex-zone 20 for temperatures up to -25 C SIL2 acc. to IEC 61508 Rectangular, housing DSU35 Plastic, PP-GF30-VO Two outputs for monitoring the position
More informationCU port USB 2.0 hub. Version: 1.1 Date:
CU8004-0000 4 port USB 2.0 hub Version: 1.1 Date: 2006-08-11 Table of Contents Table of Contents 1 Foreword 1 1.1 Notes on the documentation 1 1.1.1 Liability Conditions 1 1.1.2 Conditions of delivery
More informationThis installation guide provides instructions for installing the SPARTAN HP Highbay/ Floodlight series of explosion protected floodlights.
SPX/SPZ SPARTAN HIGH POWER LUMINAIRE RANGE Installation Guide Zone 1 Variant - CML17ATEX1148 & IEC Ex CML17.0074 Zone 2 Variant - CML17ATEX4149 & IEC Ex CML17.0074 This installation guide provides instructions
More informationLEDsmart+ Slave Relay Device
Installation Guide MMSR Provides general purpose ON/OFF control via 2-wire trailing edge devices Compatible with Diginet MEDM Dimmer Diginet LEDsmart+ Dimmers (Rotary and Push Button versions) Diginet
More informationHST -TZ1 Guard-locking mechanism (Translation of Original Manual)
Installation and Operating Manual for Components HST -TZ1 Guard-locking mechanism (Translation of Original Manual) HST-TZ1 Ident.-No.: 10234 HST-TZ1 Ident.-No.: 10236 HST-TZ1 Ident.-No.: 10235 HST-TZ1
More informationDo not open when energized or when an explosive atmosphere is present. Electrostatic hazard, clean only with damp cloth.
D460/D470 Series - ATEX certified position transmitter nnnn II 2 GD ITS 11 ATEX 17431X Ex d IIC T* Gb Tamb -*ºC to +*ºC Ex tb IIIC T* Db Tamb -*ºC to +*ºC IP6X Ambient variation -60 C to +110 C (T4/T130
More informationPolymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3
Operating Instructions Control Unit SG-EFS 1X4 ZK2/1 8k2 Version 3 1003100 SG-EFS 104 ZK2/1 8k2 24 V=/~ 7500354 SG-EFS 134 ZK2/1 8k2 230 V~ Original instructions GmbH & Co. KG Polymer Electric Örlinger
More informationMAINS DISTRIBUTION UNIT MDU14-CO
MAINS DISTRIBUTION UNIT MDU14-CO Dual Input Auto Changeover 14 Output Mains Distribution Unit. Handbook Television Systems Limited. Vanwall Road, Maidenhead, Berkshire, SL6 4UB Telephone +44 (0)1628 676200,
More informationEnglish. Operating manual. Limit switch GS125. Keep for future reference. Ventures / brands of GHM
English Operating manual Limit switch GS125 Ventures / brands of GHM www.ghm-messtechnik.de Keep for future reference. Table of contents Page 1. Intended use (areas of application)... 3 1.1 Safety signs
More informationPerformance Level PL d. Safety Category Type 3. Automatic reset / Manual reset. Very short reaction times. Connection of several signal transmitters
E L E K T R O N I K Data sheet Safety Relais STM STK 41-322 RLU for Safety-contact-mat STM PL d ISO 13849 Typ 3 EN 61496 Kat. 3 ISO 13849 SIL 2 EN 61508 Performance Level PL d Safety Category Type 3 Automatic
More informationOperating Instructions
Operating Instructions t i SPAN NOT USED - - 4...20mA DISPLAY t i SPAN END POINT DISPLAY Ð - 4...20mA p Safety information, Note Ex area Safety information Please read this manual carefully, and also take
More informationOperating instructions Evaluation system for flow sensors VS / / 2013
Operating instructions Evaluation system for flow sensors VS3000 7097 / 0 07 / 203 Contents Preliminary note...2 2 Safety instructions...3 3 Function and features... Mounting.... Mounting of the sensors...
More informationOperating Manual. English. Digital-Analog Converter DACON8-UMB.
English Digital-Analog Converter www.lufft.de G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany. We reserve the right to amend technical specifications at any time. Contents 1 Please Read Before
More informationOperating Manual / IEC. Explosion-Proofed Junction Boxes, Polyester. Wallücker Bahndamm 7 DE Kirchlengern
Operating Manual / IEC Explosion-Proofed Junction Boxes, Polyester Wallücker Bahndamm 7 DE- 32278 Kirchlengern Tel.: +49 5223 49107-0 Fax: +49 5223 49107-28 info@multi-box.com www.multi-box.com Contents
More informationInductive dual sensor For rotary actuators NI4-DSU35TC-2Y1X2/S933
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Rectangular, housing DSU35 Plastic, PP-GF30-VO Two outputs for monitoring the position of rotary actuators Mounting
More informationSIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5A ST (6ES7132-4BD02-0AA0) Preface. Properties 2. Diagnostics 3.
Preface 1 Properties 2 SIMATIC Diagnostics 3 ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5A ST (6ES7132-4BD02- Manual 01/2008 A5E01254028-01 Safety Guidelines This manual contains notices
More informationIsolating repeater IRU 420
Isolating repeater IRU 420 Universal intrinsically safe isolating repeater of current signals 0/4 20 ma with option voltage output 0 10 V For supply sensors with output 0/4 20 ma in Galvanic separation
More informationACS-30-EU-MONI-RMM2-E
Multi-application heat tracing Control & Monitoring in commercial and residential buildings Technical Information Description Approvals CE marked Ambient operating Temperature range 25 C to +6 C Mounting
More informationDANGER indicates that death or severe personal injury will result if proper precautions are not taken.
Preface SIMATIC ET 200S distributed I/O Digital electronic module 2RO NO/NC DC24..48V/5A AC24..230V/5A (6ES7132-4HB50-0AB0) SIMATIC ET 200S distributed I/O Digital electronic module 2RO NO/NC DC24..48V/5A
More informationAssembly MAU. MUX 4 Channels 8 Channels Zone 1
Multi-Input/Output Device for Cabinet Installation Features Assembly For discrete inputs and outputs Installation in Zone 1/Div. 1, intrinsically safe Sensors in Zone 0/Div. 1 Connection to fieldbus acc.
More informationOperating Instructions (Translation) 3. Safety Information. 1. Description. 2. Explosion Protection. Supply module Type 17-21BB-170x
1. Description The supply module was developed specially for direct mounting in hazardous areas in Zone 1 and 21 and is ATEX-certified. The supply module is a permanently installed piece of electrical
More informationSIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A ST (6ES7132-4BD01-0AA0) Preface. Properties 1. Diagnostics 2.
SIMATIC ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A ST (6ES7132-4BD01- SIMATIC Preface Properties 1 Diagnostics 2 ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A
More informationInductive sensor For rotary actuators NI4-DSU35TC-2Y1X2
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationControl unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V
Innovative by tradition. Control unit SG-EFS 104/4L EN Operating instructions Version 2 1004128 SG-EFS 104/4L AC/DC 24 V Original instructions Mayser GmbH & Co. KG Örlinger Straße 1 3 89073 Ulm GERMANY
More informationVISY-Output 8. Technical Documentation. 8-Channel relay output module. Version: 3 Edition: Art. no.:
Technical Documentation VISY-Output 8 8-Channel relay output module Version: 3 Edition: 2016-09 Art. no.: 350072 FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg Germany Tel.: +49 / 40 / 39 82 07 0 Fax:
More informationINSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F
PSD1000 - PSD1000F INSTRUCTION MANUAL Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD1000 - Universal AC Input Switching Power Supply 24 Vdc Output ISM0089-4
More informationInstallation- and Operating instructions for CU Ethernet Controller with USB Input. Version: 1.4 Date:
Installation- and Operating instructions for CU8880-0010 Ethernet Controller with USB Input Version: 1.4 Date: 2018-04-12 Table of contents Table of contents 1. 2. 3. 4. 5. General instructions 2 Notes
More informationInductive sensor For rotary actuators NI4-DSU35TC-2Y1X2/S933
ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 (Low Demand Mode) acc. to IEC 61508, PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508, PL e acc. to ISO 13849-1
More informationOperating Instructions for Level Switch for Liquids. Model: RFS
Operating Instructions for Level Switch for Liquids Model: RFS 1. Contents 1. Contents... 2 2. Note... 3 3. Instrument Inspection... 3 4. Regulation Use... 3 5. Operating Principle... 4 6. Use in Hazardous
More informationInstallation instructions Inclination sensor EC2019 EC / / 2013
Installation instructions Inclination sensor UK EC219 EC245 739215 / 3 1 / 213 Inhalt 1 Safety instructions 3 2 Mounting 4 3 Electrical connection 4 4 Dimensions 4 5 Technical Data 5 6 Characteristics
More informationAssembly. Front view. LED yellow: Relay output. LED red: LB/SC Power Rail
Switch Amplifier Features Assembly -channel isolated barrier 4 V DC supply (Power Rail) Dry contact or NAMUR inputs Relay contact output Line fault detection (LFD) Reversible mode of operation Up to SIL
More informationPTB 01 ATEX Example / Beispiel / Exemple. Type Operating Instructions
Device with II 2G EX i approval Geräte mit II 2G EX i Zulassung Appareils avec mode de protection II 2G EX i Example / Beispiel / Exemple Type 6106 Operating Instructions Bedienungsanleitung Manuel d utilisation
More informationOriginal instructions JSHD4 AS-i Enabling device with safe AS-i input slave
Original instructions JSHD4 AS-i Enabling device with safe AS-i input slave Jokab Safety AB Varlabergsvägen 11, S-434 39, Sweden Table of Contents 1 Introduction... 3 Scope... 3 Audience... 3 Prerequisites...
More informationNMEA Multiplexer Owner s Handbook. Document Number: Date: February 2005
NMEA Multiplexer Owner s Handbook Document Number: 81250-1 Date: February 2005 Copyright Raymarine (UK) Ltd 2005 i Preface Congratulations on having bought a Raymarine NMEA Multiplexer. This enables you
More informationAssembly MAU. MUX 4 Channels 8 Channels Zone 1
Multi-Input/Output Device for Cabinet Installation Features Assembly For discrete inputs and outputs Installation in Zone 1/Div. 1, intrinsically safe Sensors in Zone 0/Div. 1 Connection to fieldbus acc.
More informationConductive Level Controller
Conductive Level Controller 61F-D21T-V1 Ideal for level control for industrial facilities and equipment. Outputs can be set to self-hold at ON or OFF using self-holding circuits. Sensitivity adjustment
More informationYT-870 / 875 Series. Rotork YTC Limited VERSION 1.06
PRODUCT MANUAL Rotork YTC Limited VERSION 1.06 Contents 1 Introduction... 3 1.1 General Information for the users... 3 1.2 Manufacturer Warranty... 3 1.3 Explosion Proof Warning... 4 2 Product Description...
More informationInstallation Manual Series PQ-L. Electronic Module. Bulletin /UK
Bulletin 5715-571 /UK Installation Manual Electronic Module Gutenbergstr. 38 41564 Kaarst, Germany Tel.: (+) 2131-513-0 Fax: (+) 2131-513-230 www.parker.com Copyright Ó 2000, Note This document and other
More informationOverview. Applications. Benefits. Ordering Information. Sensors OHD Thermal Guard
Sensors OHD Thermal Guard Overview The OHD Thermal Guard is developed for thermal problem countermeasures and safety standard conformity, which are becoming increasingly important for electronic devices
More informationOriginal operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016
Original operating instructions Safety relay with relay outputs with and without delay UK G50S 803638 / 00 0 / 06 Contents Preliminary note...4. Symbols used...4 Safety instructions...5 3 Items supplied...6
More informationFunctional safety manual RB223
SD00011R/09/EN/13.13 71238251 Products Solutions Services Functional safety manual RB223 Passive barrier Application Galvanic isolation of active 0/4 to 20 ma signals from transmitters, valves and adjusters,
More informationPROCESS AUTOMATION MANUAL. Temperature Trip Amplifier. KFD2-GU-(Ex)1 ISO9001
PROCESS AUTOMATION MANUAL Temperature Trip Amplifier KFD2-GU-(Ex)1 ISO9001 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery
More informationOperating Instructions Differential Pressure Transducer PS27
Operating Instructions Differential Pressure Transducer PS27 halstrup-walcher GmbH Stegener Straße 10 79199 Kirchzarten/Germany Phone: +49 (0) 76 61/39 63 0 Fax: +49 (0) 76 61/39 63 99 E-mail: info@halstrup-walcher.com
More informationIntrinsically safe batch controller Batching Master 110i
Intrinsically safe batch controller Batching Master 110i Installation Guide BVS 04 AT E 172 Revision 12.2 IBS BatchControl GmbH Im Sträßchen 2-4 Tel.: ++49 2441 9199 801 53925 Kall Fax.: ++49 2441 9199
More informationConveyor Belt Alignment Switches from IDEM
Conveyor Belt Alignment Switches from IDEM Data Sheet Die-Cast Models Python Line Series Stainless Steel Models Using Conveyor Belt Alignment Switches Application: Conveyor Belt Alignment switches are
More informationVigil 3 Amplifiers. Installation Instructions
Manual name: Vigil 3 Amplifier Installation Manual Issue: 1 ECR: N/A Date of issue: Dec 2016 Dec 2016 Baldwin Boxall Communications Limited Wealden Industrial Estate Farningham Road, Jarvis Brook Crowborough
More informationInstallation Instruction. HART Add-On Module
- Translation Typs 17-A1Z0-0005, B7-A2Z0-0033 and G7-A0Z0-0007 Version for: Non hazardous areas ATEX/IECEx Zone 1 and Zone 2 UL Class I Division 1 and Division 2 Document No.: B1-A2Z0-7N0001 / 400570 Revision
More informationDocumentation. CU20xx, CU22xx. Ethernet Switch. Version: Date:
Documentation CU20xx, CU22xx Ethernet Switch Version: Date: 2.1 2017-12-18 CU20xx, CU22xx - Product overview 1 CU20xx, CU22xx - Product overview CU2005 [} 8] - 5 RJ-45-Ethernet-Ports CU2008 [} 8] - 8
More informationSIWAREX JB Aluminum Housing. Instruction Manual Edition 03/2006
s SIWAREX JB Aluminum Housing Instruction Manual Edition 03/2006 Table of Contents Table of Contents... 2 Warning and Safety Terms... 3 General... 4 1 Technical Description... 5 1.1 Area of Application...
More informationET 200S distributed I/O Digital electronic module 2DO AC V (6ES7132-4FB01-0AB0)
SIMATIC ET 200S distributed I/O SIMATIC Preface ET 200S distributed I/O Digital electronic module 2DO AC24..230V (6ES7132-4FB01-0AB0) Properties 1 Parameters 2 Diagnostics 3 Manual 04/2007 A5E01077264-01
More informationInductive sensor with analog output BI15-M30-LI-EXI
ATEX category II 1 G, Ex-zone 0 ATEX category II 2 D, Ex-zone 21 Threaded barrel, M30 x 1.5 Chrome-plated brass Analog+ Extended operating range 2-wire, 14 30 VDC Analog output 4 20 ma Cable connection
More informationOperating and installation instructions Differential pressure monitor
Operating and installation instructions Differential pressure monitor RM-DPC Micro SensorLine Table of contents 1 Safety instructions...3 2 Equipment specification...3 3 Assembly...4 4 Step-by-step installation...4
More informationPI-EX-ME-2NAM/COC-120VAC
PI-EX-ME-NAM/COC-0VAC Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Relay Output, PDT, Two-Channel, 0 V AC Supply INTERFACE Data Sheet 0944_00_en PHOENIX CONTACT - 0/008 Description
More informationFLEX Ex Spring Clamp Terminal Base
Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification
More informationPI-EX-ME-2NAM/COC-24VDC
Ex-i NAMUR Isolation Amplifier, With Intrinsically Safe Input and Relay Output, PDT, Two-Channel, 4 V DC Supply INTERFACE Data Sheet 0033_0_en PHOENIX CONTACT - /007 Description The PI-EX-ME-NAM/COC-4VDC
More informationD5090S INSTRUCTION MANUAL. D A SIL 3 Relay Output Module for NE Load. DIN-Rail and Termination Board, Model D5090S
D5090S INSTRUCTI MANUAL 4 A Relay Output Module for NE, DIN-Rail and Termination Board, Model D5090S D5090-4 A Relay Output Module for NE G.M. International ISM09-3 Characteristics General Description:
More informationInstruction Manual. T3110 T3110L T3110Ex
www.cometsystem.cz Instruction Manual T3110 T3110L T3110Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with 4-20 ma outputs Copyright: COMET System,
More informationSCD96 DMX Output Interface. Installation guide
SCD96 DMX Output Interface Installation guide Contents Introduction 2 Welcome 2 Dimensions 2 Specification 2 Safety 3 Please read this first 3 Mounting 4 Location and spacing 4 Ambient atmosphere requirements
More informationD1093S INSTRUCTION MANUAL. D SIL 3 Relay Output Module with Line and Load diagnostics. DIN-Rail Model D1093S
D109S INSTRUCTION MANUAL SIL Relay Output Module with Line and diagnostics DINRail Model D109S D109 SIL Relay Output Module with Line and diagnostics ISM0096 SIL Applications For Safety Related System
More informationPOCKET GUIDE ROUTINE MAINTENANCE, SAFETY, INSTALLATION & TROUBLESHOOTING
The 350 REFERENCE SERIES MULTI-PRICE TOTALISER POCKET GUIDE ROUTINE MAINTENANCE, SAFETY, INSTALLATION & TROUBLESHOOTING CashFlow CashFlow CashFlow C ashflow CashFlow CashFlow Cas hflow CashFlow CashFlow
More informationInstallation instructions Diagnostic electronics for vibration sensors VSE / / 2007
Installation instructions Diagnostic electronics for vibration sensors UK VSE00 70406 / 00 07 / 2007 Contents Safety instructions 3 Function and features 4 Mounting 4 Mounting of the sensors 5 Electrical
More informationPROCESS AUTOMATION MANUAL. Universal Temperature Converter KCD2-UT2-(Ex)1 ISO9001
PROCESS AUTOMATION MANUAL Universal Temperature Converter KCD2-UT2-(Ex)1 ISO9001 With regard to the supply of products, the current issue of the following document is applicable: The general terms of delivery
More informationWG 20. The WG 20 achieves an extraordinarily. accuracy for hazardous-area. applications.
Modular Housings for Hazardous Areas For transmission of 0(4)... 20-mA signals from hazardous areas or supply of intrinsically safe 2-wire transmitters. The Task The power supply/isolator is used to supply
More informationOperating Instructions VEGAMET 381
Operating Instructions VEGAMET 381 in out Contents Contents 1 About this document... 4 1.1 Function... 4 1.2 Target group... 4 1.3 Symbolism used... 4 2 For your safety... 6 2.1 Authorised personnel...
More informationInstallation and Operations Manual INVOLAR MAC250 Microinverter
Installation and Operations Manual INVOLAR MAC250 Microinverter Contact Information INVOLAR Corporation, Ltd. 887 Zuchongzhi Road, Build 84, Room 408, Shanghai, China 201203 Tel: 86-21-50272208 Fax: 86-21-50277705
More informationDeltaV Bulk Power Supplies
DeltaV Distributed Control System Product Data Sheet DeltaV Bulk Power Supplies DeltaV 5 A, 10A, 20 A, 40 A Bulk Power Supplies. DeltaV 20 A, 40 A and 80 A Bulk Power Supply Redundancy Modules. Easy to
More informationInstallation Guide MODELS 522 / 526. Pressure Transducers TOLL FREE FAX Web Site.
Installation Guide MODELS 522 / 526 Pressure Transducers 1-800-257-3872 TOLL FREE 1-978-264-0292 FAX www.setra.com Web Site 560550-0087 Rev A Setra offers a complete line of products for these industries:
More informationOperating instructions (Safety-related part ATEX and IECEx) Inductive NAMUR sensors NN504A NN505A NN506A NN507A /00 08/2015
Operating instructions (Safety-related part ATEX and IECEx) Inductive NAMUR sensors NN504A NN505A NN506A NN507A 80013497/00 08/015 Remarks for safe use in hazardous areas Functions and features Use in
More informationF101, F102, F104. Relcom Installation Instructions. Fieldbus Power Supply F101-PS
F101, F102, F104 Fieldbus Power Supply F101-PS Installation Instructions Relcom www.mtl-fieldbus.com CONTENTS PAGE 1 OVERVIEW 2 2 DESCRIPTION 2 3 COMPONENTS AND ACCESSORIES 2 4 MECHANICAL 3 4.1 Mounting
More informationPAT-Cal 2 TECHNICAL MANUAL
Portable Appliance Tester Calibrator PAT-Cal 2 TECHNICAL MANUAL 1 Time Electronics Limited Botany Industrial Estate, Tonbridge, Kent, TN9 1RH. Tel: +44(0)1732 355993 Fax: +44(0)1732 770312 Email: info@timeelectronics.co.uk
More informationInstruction Manual, Alfa Laval Rotacheck Sensor and Relay
Instruction Manual Alfa Laval Rotacheck Sensor and Relay Covering Standard Instruments Instruments delivered with ATEX Certification in accordance with Directive 94/9/EC IM-TE91A663-EN9 ESE01763EN Date
More informationLoop-powered Transmitter for Thermocouple Type K (NiCr-Ni)
Data sheet 302040_en MTP300i-SIL-K Loop-powered Transmitter for Thermocouple Type K (NiCr-Ni) Properties 2-wire temperature transmitter for DIN rails Galvanic isolated TC-input with cold-junction compensation
More informationVMS Co., Ltd. VMS Reliability Systems - Korea
VMS Co., Ltd VMS Reliability Systems - Korea Room 1106, QB Centum Bldg, 90, Centum Jungang-ro, Haeundae-gu, Busan, Korea TEL +82 51 782 2323 FAX +82 51 782 0808 E-MAIIL admin@vmsco.co.kr www.vmsco.co.kr
More informationDocumentation ZB8610. Fan cartridge for EtherCAT and Bus Terminals. Version: Date:
Documentation Fan cartridge for EtherCAT and Bus Terminals Version: Date: 1.5 2017-08-07 Table of contents Table of contents 1 Foreword... 5 1.1 Notes on the documentation... 5 1.2 Safety instructions...
More informationShown with terminal block Supports diagnostic point fault contacts in the logic program
GFK-2482F PACSystems* RX3i Isolated Analog Input Modules, IC695ALG106-EA, IC695ALG112-EA Product Description Isolated Analog Voltage/Current Input module IC695ALG106 provides 6 isolated input channels.
More informationABB Drives. User s Manual. Digital I/O Extension Module RDIO-01
ABB Drives User s Manual Digital I/O Extension Module RDIO-01 Digital I/O Extension Module RDIO-01 User s Manual 3AFE 64485733 REV B EN EFFECTIVE: 10.2.2003 2003 ABB Oy. All Rights Reserved. Safety Instructions
More informationPRO-75 SERIES. User manual
PRO-75 SERIES DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
More informationOperating instructions Optical distance sensor. OID20x / / 2014
Operating instructions Optical distance sensor OID0x 800005 / 00 08 / 01 Contents 1 Preliminary note... 1.1 Symbols used... 1. Warning signs used... Safety instructions... Functions and features...5.1
More informationIO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs
IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs The IO-DI8-TO8 and IO-DI8-TO8-L are I/O expansion modules that can be used in conjunction with specific Unitronics OPLC controllers. The
More information