The Importance of Contamination Control at Floor Level. Carlos Mourelle EMEA Director Nov 2018
|
|
- Myron Bryant
- 5 years ago
- Views:
Transcription
1 The Importance of Contamination Control at Floor Level Carlos Mourelle EMEA Director Nov 2018
2 Contamination is a Reality According to the major IT equipment manufacturers, the number of data centres with contamination-related failures is on the rise American Society of Heating, Refrigerating and Air Conditioning Engineers Inc. (Ashrae) 2011 Gaseous and Particulate Contamination Guidelines for Data Centers
3 Green can be Green Dust and Dirt are enemies of the Data Center. Dust has a way to clogging equipment, air inlets, and clinging to the inside of active equipment. All of this dust requires more airflow and more cooling dollars in the Data Center Creating the Green Data Center Simple measures to reduce energy consumption ADC
4 The Facts Dust and dirt are two of the biggest enemies in a data centre They force greater energy use They clog fans They get into computers They collect and are a major fire hazard They are created by Equipment They are introduced through People They come from the environment 1 hour of downtime can cost from 50,000 to 500,000 (IBM Today)
5 Who Generates these Particles? In short, everything generates particles 97% of these particles are not visible to us All particles represent a threat/danger to the integrity and quality of the Data Centre 80% generated by personnel 15% generated by equipment 5% generated by environment
6 How and Where does Contamination Enter?
7 The Problem Dust contamination is known as the Undetected Disaster IT industry research has concluded that up to 70% of computer-related breakdowns are caused by dust and other debris. This often takes the form of construction dust or Organic Particulate It can build up over time, often unnoticed, until it causes a catastrophic failure in the Data Centre, e.g. Fan burn out leading to a discharge of expensive fire suppressing gas. It creates the slowing down of mission critical systems It can cause unexplained disk errors It can be responsible for the overheating of servers or other boxes It can explain the reason why servers and/or other IT Equipment shuts down unexpectedly
8 ASHRAE 2009 Data Centres must be kept clean to at least Class 8 of ISO Incumbent on Data Centre Managers to do their part in maintaining hardware reliability by monitoring and controlling the dust and gaseous contaminations in their Data Centres Sources of Dust inside Data Centres should be reduced. Every effort should be made to filter out dust that has deliquescent humidity less than the maximum allowable relative humidity in the Data Centre Objective of this White Paper is the need to control airborne contaminants both particulate and Gaseous in Data Centres
9 Why the need to Control? Components are getting smaller Increased heat load burning more energy Higher packing density exposes electronics to these factors Decreased spacing increases possibility of short circuiting Expanding corrosion approaches the size of the components Focus on Green
10 The Damage: Hardware Dust can cause irreversible harm to computer systems by clogging heat-sinks and cooling systems This could lead to overheating and induce a fire hazard. As well as reducing the lifespan of any of your systems Higher cost for replacing filters, or using more expensive filters
11 The Damage: Loss of Data Malfunctions in hardware Leads to problems with operation of servers, and software used on systems Loss of data Possible large cost replicating lost data Customers not satisfied with service if data is lost Damage to company reputation
12 The Damage: Energy Dust clogging filters and heat sinks Leads to excess heat and more energy used by the severs and all the cooling units Added cost for all the excess energy usage Lowered efficiency of data centre More emphasis on running Green technology in data centres
13 Dust will Affect Power Consumption Total reliance on power presents a concentrated area of significant risk to modern data centres The needs of Facilities Management (FM) and Data Centre Infrastructure Management (DCIM) is protection from: - External power supply restrictions - Rising energy prices - Total power failures caused by local overloads Global energy consumption is set to treble by 2050, which will further impact the energy shortfalls already being experienced in some of the world s technology hotspots (Jimmy Chang ATEN)
14 Filters Preventative Measures Specialist Cleaning (Sun Micro Best Practise 2000) Personnel Habits Introduction of foreign materials (Cardboard, Packaging etc) Contamination Control Flooring/Mats
15 Prevention of Contamination 70% to 80% of all contamination entering a room is carried in on wheels or feet (Department of the Environment) Contamination on unprotected floors will rise to shoulder level and above on air particle movement created by vortices Installation of a contamination control system at floor level is the most cost effective solution to the removal of the majority of contamination By removing 80% for small cost compared with the expense of trying to cope with the 20% (air handling systems, gowns, hats, gloves, Server Room costs!!)
16 Benefits of contamination prevention Less chance of System failure costing millions of pounds/dollars and even threatening the viability of the business - reduced downtime and costs. The equipment may last longer and cost less to run Staff and other stakeholders see you are serious about the importance of the equipment Reduced Life Cycle cost Increased confidence Less time and money spent on people fault finding and repairing breakdowns
17 So how do we prevent... This sort of contamination from dust and dirt?
18 Solutions: Tacky Mats Multiple Layers of Polyethylene film coated with an acrylic adhesive Adhesive strength alone collects contamination Performance deteriorates after several footsteps/overstrikes Appropriate for confined spaces, with low personnel traffic volumes Low efficiency in particulate removal for smaller particle sizes of less than 10µmicrons When peeled, tens of thousands of viable and non-viable particulates are released into the environment Cannot be recycled High costs when analysed on an annual basis
19 Solutions: Polymeric flooring Polymeric Composition Optically smooth, flexible surface enabling maximum contact between shoe and wheels High surface energy (Van de Vaals forces) allows maximum collection and retention of all particulate sizes Ability to collect/retain contamination over a wide range of particle sizes, with effective removal in the 2 to 10 µmicron range Simple and regular cleaning regime guarantees effective contamination control over several years Picks up contamination over a full floor coverage Particulates removed are contained within the controlled medium thereby preventing their release into the environment Flooring can be recycled at the end of its life
20
21 Summary Contamination can cause any number of equipment problems, including intermittent or permanent failures, overheating and loss of energy efficiency This damage is caused by the chemical, electrical and mechanical properties of the contamination The amount of contamination will depend upon a number of factors particularly the amount of traffic (feet and wheels), the location and the design and construction of the Data Centre
22 Conclusion IT Industry research has concluded that up to 70% of computer-related breakdowns are caused by particles of dust and dirt The Environment is the source of this contamination 80% of all dirt and dust is brought into areas on the soles of feet and/or wheels at floor level Unless controlled and trap this dust can cause untold damage and affect performance/energy consumption/hardware For a relatively small investment this dust/dirt can be controlled, trapped and removed preventing it from continuing to be
23 The End Any Questions?
The modular application of the cleanroom solutions for manufacturing facilities
White Paper The modular application of the cleanroom solutions for manufacturing facilities Cleanroom facilities in the U.S. have grown fourfold since 1998, reaching an estimated 180 million square feet.
More informationA) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.
DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic
More informationWHITEPAPER CLEAN ROOM DESIGN AND THE ROLE OF FLOORING. An overview of cleanroom design and flooring considerations to ensure regulatory compliance.
CLEAN ROOM DESIGN AND THE ROLE OF FLOORING An overview of cleanroom design and flooring considerations to ensure regulatory compliance. Contact the Flooring Specialist +61 7 3205 7115 (Brisbane) +61 2
More informationROOM INTEGRITY TESTING
Fire suppressing agents are designed to protect rooms in addition to using traditional sprinkler methods. 59% of Clean Agent systems FAILED to keep out fire and smoke.* Agents MUST remain in room for a
More informationRF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink
INDUSTRIAL INTERNET IN ACTION CASE STUDY RF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink CLIENT PROFILE CenturyLink Technology Solutions is the second largest telecommunications
More informationAPRIL 2010 VOL. 13 NO. 4. Modular Cleanrooms for Business Startups and New Product Development
APRIL 2010 VOL. 13 NO. 4 Modular Cleanrooms for Business Startups and New Product Development Modular Cleanrooms for Business Startups and New Product Development www.cemag.us Modular Cleanrooms for Business
More informationThinking Outside The Box Kieron Smith Kingspan Cleanroom Systems
Thinking Outside The Box Kieron Smith Kingspan Cleanroom Systems Thinking outside the box When designing a cleanroom, it is natural to focus on aspects such as hygiene, air cleanliness, thermal performance
More informationCONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 3
CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 3 Thomas B. Jones 1 Introduction Operators and managers consider outages, operational faults and interruptions
More informationData Center Trends and Challenges
Data Center Trends and Challenges, IBM Fellow Chief Engineer - Data Center Energy Efficiency Customers challenges are driven by the following Increasing IT demand Continued cost pressure Responsive to
More informationHOW TO SELECT A CLEANROOM: MODULAR CLEANROOMS FOR NEW BUSINESSES, NEW PRODUCT DEVELOPMENT
HOW TO SELECT A CLEANROOM: MODULAR CLEANROOMS FOR NEW BUSINESSES, NEW PRODUCT DEVELOPMENT By Kevin Weist, president Clean Air Products A well-designed, aesthetically pleasing modular hardwall cleanroom
More informationBuilding Cleanrooms. - Regulations, Air-Handling, Design & Construction -
Building Cleanrooms - Regulations, Air-Handling, Design & Construction - Created by Michael Starke, Solutions and Handling GmbH, Germany Tel.: +49-2152-553800, Fax: +49-2152-553805, mail: info@solutions-handling.com
More informationBUSINESS CONTINUITY: THE PROFIT SCENARIO
WHITE PAPER BUSINESS CONTINUITY: THE PROFIT SCENARIO THE BENEFITS OF A COMPREHENSIVE BUSINESS CONTINUITY STRATEGY FOR INCREASED OPPORTUNITY Organizational data is the DNA of a business it makes your operation
More informationPreventing Outages by Monitoring, Managing, and Controlling the Data Center Environment
Preventing Outages by Monitoring, Managing, and Controlling the Data Center Environment APC BY SCHNEIDER ELECTRIC: NETBOTZ EGUIDE Data centers are under greater threat than ever. According to the Ponemon
More informationAir Quality Analysis
CHOICE SOLUTIONS LIMITED REFERENCE BOOKLET Air Quality Analysis Inside This Case Study Air Quality 1 Air Quality Measurement 1 Reactivity Monitoring Coupons 1 Environmental Condition Monitor 2 Air Sampling
More informationObtaining the Weld Quality You Need. What to Look for in a Cleanroom Welding Contractor
Obtaining the Weld Quality You Need What to Look for in a Cleanroom Welding Contractor What is Cleanroom Welding? Welding within a cleanroom ensures that there is a low level of contaminants such as dust,
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationScalable, Secure. Jason Rylands
Energy Efficient, Modular, Scalable, Secure Jason Rylands The planning, construction and operation of IT infrastructure for mission critical applications in reliable Datacentres represents a real challenge.
More informationIntroduction. Service and Support
We Do It Better. Contents Introduction... 3 Service and Support... 3 Data Center Details... 4 Security... 4 Location... 4 Power... 4 Humidification... 5 AC... 5 Cooling... 6 Datacenter Features... 6 SAS
More informationCleanroom manufacture and online supplies
Cleanroom manufacture and online supplies cleanroomshop.com Introduction 1 Welcome to CONNECT 2 CLEANROOMS Connect 2 Cleanrooms Ltd design, manufacture, install and validate cleanrooms, specialising in
More informationEC Series. Safety Guide
EC Series Safety Guide R5906018/02 01/07/2017 Barco Inc, Image Processing 3078 Prospect Park Drive, Rancho Cordova, CA, 95670, USA Phone: +1 916 859-2500 Fax: +1 916 859-2515 Support: www.barco.com/en/support
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationRunning Your Data Center Under Ideal Temperature Conditions
TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient
More informationCOPYRIGHTED MATERIAL. Introduction. 1.1 What is a Cleanroom?
1 Introduction 1.1 What is a Cleanroom? It is clear that a cleanroom is a room that is clean. However, a cleanroom has a special meaning and it is defined in the International Organization for Standarization
More informationSurvey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered
Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationDCIM Solutions to improve planning and reduce operational cost across IT & Facilities
DCIM Solutions to improve planning and reduce operational cost across IT & Facilities Presented by: Chi Sen, Director, Data Centre Software Solutions, APJ & EMEA Schneider Electric Data Center Solutions
More informationLawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title Airflow design for cleanrooms and its economic implications Permalink https://escholarship.org/uc/item/2zv466b4 Author
More informationServer Technology, Inc.
Server Technology, Inc. Smart Load Shedding ensures Uptime White Paper STI-100-004 Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 +1 (775) 284-2000 sales@servertech.com www.servertech.com Smart
More informationLine Interactive 1000VA/1400VA/2000VA Uninterruptible Power System
USER MANUAL Line Interactive 1000VA/1400VA/2000VA Uninterruptible Power System 614-06762-00 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for Line Interactive
More informationNext Generation Backup: Better ways to deal with rapid data growth and aging tape infrastructures
Next Generation Backup: Better ways to deal with rapid data growth and aging tape infrastructures Next 1 What we see happening today. The amount of data businesses must cope with on a daily basis is getting
More informationFinding Reliability and Availability in the Cloud
Client: Henry Schein Project: Finding Reliability and Availability in the Cloud White Paper 1 st draft: October 1 st, 2013 Finding Reliability and Availability in the Cloud When you consider the possibility
More information15 Ways Belden Helps Reduce Human Error to Improve Uptime
15 Ways Belden Helps Reduce Human Error to Improve Uptime Up to 75% of data center downtime is caused by human error. While no data center is capable of being completely immune to mistakes, implementing
More informationCooling Contingency Planning. Planni ng for the U nexpected. Is Your Health Care Facility Prepared?
Cooling Contingency Planning Planni ng for the U nexpected Is Your Health Care Facility Prepared? R isk Management Unexpected events, such as natural disasters, can expose organizations to risks. Even
More informationData Center Lifecycle and Energy Efficiency
Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014
More informationdescribe how ESD is created list the causes of ESD describe and use ESD protection methods
ESD All rights reserved. Welcome to the ESD training module. If you need help navigating this module, please click the button in the top right corner. To view the presenter notes as text, please click
More informationIT CONTINUITY, BACKUP AND RECOVERY POLICY
IT CONTINUITY, BACKUP AND RECOVERY POLICY IT CONTINUITY, BACKUP AND RECOVERY POLICY Effective Date May 20, 2016 Cross- Reference 1. Emergency Response and Policy Holder Director, Information Business Resumption
More informationPrecision Cooling. Precision Cooling Advantages
Precision Cooling Today s computing technologies compound conventional cooling problems. Blade servers, communications switches and other electronics are being packed into tighter and tighter spaces. Computing
More informationPowering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM
Powering Change in the Data Center A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity are driving change in the power and
More informationIT S TIME FOR DATA CENTRE SUPPORT
IT S TIME FOR DATA CENTRE SUPPORT Knowing that your Data Centre is functioning effectively is critical to IT availability. Design, maintenance, operations and speedy fault resolution are key requirements
More informationCommon Power Problems & Power Protection Solutions
W H I T E P A P E R Common Power Problems & Power Protection Solutions Executive Summary All systems, from home theaters and office desktops to enterprise IT equipment in data centers, are prone to downtime,
More informationPHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL
PHASETRONICS Specialists EP1 Series Power Control Single Phase SCR 10-50 Amps OPERATION & SERVICE MANUAL Phasetronics, Inc. P.O. Box 5988 1600 Sunshine Drive Clearwater, FL 33765 (727)573-1900 FAX(727)573-1803
More informationSwitchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability
Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability 1910DB1207 By Hal Theobald, Product Marketing Manager, Schneider Electric Services Summary 1.0 Abstract...3 2.0 Introduction...3
More informationGoogle s Green Data Centers: Network POP Case Study
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationEquipment Strategy For High Voltage Circuit Breakers
Current version: 23/05/2018 EXTERNAL USE Page 1 of 7 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References... 3 1.4 Defined terms... 3 1.5 Monitoring and compliance... 3
More informationPower Monitoring in the Data Centre: Is the Right Time Now? Jacarta Ltd
Power Monitoring in the Data Centre: Is the Right Time Now? Jacarta Ltd www.jacarta.com Power Monitoring in the Data Centre: Is the Right Time Now? Introduction Data centre power monitoring has been much
More informationRegulations Determining Computer Room Cooling Selection
PRECISION COOLING FOR MISSION CRITICAL APPLICATIONS Regulations Determining Computer Room Cooling Selection Precision vs Comfort Cooling White Paper STULZ USA All rights reserved New Regulatory Standards
More informationCLEAN ROOM PROTOCOL AND WAFER HANDLING
CLEAN ROOM PROTOCOL AND WAFER HANDLING Prof. Madya Dr. Uda Hashim 1 Outline Cleanroom Cleanroom protocol Wafer handling procedure 2 CLEANROOM Definition Cleanroom - The cleanliness of the air inside the
More informationMLI INTRODUCTION GUIDE. copyright reserved 2012 MLI
MLI INTRODUCTION GUIDE Table of Contents MLI, the Company Introduction of MLI Why MLI MLI Test Equipments Pellicle Introduction Pellicle Film Transmission Pellicle Mounting Tool MLI Quality System 3 4
More informationASSURING BUSINESS CONTINUITY THROUGH CONTROLLED DATA CENTER
ASSURING BUSINESS CONTINUITY THROUGH CONTROLLED DATA CENTER IT Audit, Information Security & Risk Insight Africa 2014 Johnson Falana CISA,MIT,CEH,Cobit5 proverb814@yahoo.com Overview Information technology
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationData Centre In A Box
Data Centre In A Box Data Centre In A Box Rittal s Data Centre In A Box replicates all of the key data centre capabilities but on a smaller scale. The Data Centre In A Box mitigates risk and provides compelling
More informationX-3 LED. Owner s Manual ROBOHEAD
X-3 LED Owner s Manual ROBOHEAD Thanks a lot for purchasing our LED robohead. Please read this user manual carefully and follow the instructions to avoid danger or damage to the unit due to mishandling.
More informationWHAT NEW TECHNOLOGIES AND DATA CAN DO FOR THE WATER INDUSTRY
WHAT NEW TECHNOLOGIES AND DATA CAN DO FOR THE WATER INDUSTRY Increase Quality and Safety of Products, and Improve Performance with New Technologies and Continuous Availability simplify and modernize automation
More informationHelpline No. UK/Northern Ireland Rep. Ireland Web Support Model Number 82069
Introduction 1 Congratulations on choosing to buy a Tevion product. By doing so you now have the assurance and peace of mind that comes with purchasing a product made by one of Europe s leading manufacturers.
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationAchieving Rapid Data Recovery for IBM AIX Environments An Executive Overview of EchoStream for AIX
Achieving Rapid Data Recovery for IBM AIX Environments An Executive Overview of EchoStream for AIX Introduction Planning for recovery is a requirement in businesses of all sizes. In implementing an operational
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationAre all CFD s created equal? Prepared by: Associate Director: Sam Wicks
Are all CFD s created equal? Prepared by: Associate Director: Sam Wicks samwicks@sudlows.com Keeping cool under pressure Imagine waking up at 04:00 to an escalated BMS alert that your Dubai data hub has
More informationTHERMAL MANAGEMENT THE PROMISE THE PROOF HEATEX AIR-TO-AIR HEAT EXCHANGERS
TM THERMAL MANAGEMENT THE PROMISE THE PROOF HEATEX AIR-TO-AIR HEAT EXCHANGERS DYNAMIC AND EVOLVING MARKET FORCES REQUIRE INNOVATIVE SOLUTIONS The pace and growth of modern technology places numerous challenges
More informationWhitepaper. 10 Reasons to Move to the Cloud
Whitepaper 10 Reasons to Move to the Cloud 2 10 Reasons to Move to the Cloud 10 Reasons to Move to the Cloud and Why It Will Be the Best Business Decision You Will Ever Make Convergia s CloudOffice is
More informationThin clients JC500X - 1 Reference guide
Thin clients JC500X - 1 Reference guide 1. Product introduction 1-1 product overview Using Intel N2840 BayTrail dual-core embedded processor ( or Intel J2900), low power consumption new fashionable appearance,
More informationData Centre. Design and Build. Everything you need to know about designing, installing and maintaining a. Data Centre
Data Centre Design and Build Everything you need to know about designing, installing and maintaining a Data Centre UPS Generators Maintenance Data Centre Design and Build Introduction You are looking to
More informationNo. of. Voltage. Power
Value Flex Eco VFEG1 Data Sheet Benefits Energy saving low-power LED flexible strip for decorative, shelf and hospitality lighting. Self-adhesive tape on the back for easy and fast installation. Consistent
More informationASHRAE. Shaping Tomorrows Built Environment Today. Erich Binder - Director At Large
ASHRAE Shaping Tomorrows Built Environment Today Erich Binder - Director At Large http://ashare.org/ ASHRAE is the Answer People spend about 90 % of their lives indoors. Buildings are the places where
More information1395 Node Adapter Board Troubleshooting
1395 Node Adapter Board Troubleshooting Specifications Electrical: Board power provided by Drive (+5V) Discrete Input 24V DC or 115V AC, jumper selectable Environmental: Ambient Operating Temperature Storage
More informationSite Preparation for ClearCube Installation. Rev. F
Site Preparation for ClearCube Installation Rev. F EXECUTIVE SUMMARY Because of the centralized nature of the ClearCube architecture, installation of the system requires a certain degree of site preparation.
More informationPredictive Maintenance in a Mission Critical Environment
CSI 2130 Predictive Maintenance in a Mission Critical Environment This paper discusses the need to proactively protect mechanical and electrical support systems in data processing centers and data storage
More informationData Center Infrastructure Management ( DCiM )
Page 1 Data Center Infrastructure Management ( DCiM ) DCiM is defined by technology researchers and analysts as the integration of information technology (IT) and facility management disciplines to centralize
More informationARE YOU DRESSED FOR SUCCESS?
ARE YOU DRESSED FOR SUCCESS? COMPLEXITY IS SIMPLE AGAIN. Contamination Control is complex. But it doesn t have to be. With today s standards and regulations, it s challenging to determine where the breach
More informationData Centers & Technology:
Data Centers & Technology: Risk in the digital landscape Presented by; Ralph de Mesquita Principal Risk Analyst, Risk Engineering UK Agenda Rise of cloud providers Four scenarios: where are the insurable
More informationInformation Services IT Security Policies L. Network Management
Information Services IT Security Policies L. Network Management Version 1.1 Last updated: 11th August 2010 Approved by Directorate: 2nd July 2009 Review date: 1st August 2011 Primary owner of security
More informationCleanroom Air Showers. Esco Cleanroom Air Shower, Model EAS-2C_.
Cleanroom Air Showers Esco Cleanroom Air Shower, Model EAS-C_. Esco Cleanroom Air Shower, Model EAS-C_. Standards Compliance Filtration EN- (H), Europe IEST-RP-CC00., USA IEST-RP-CC007, USA IEST-RP-CC0.,
More informationPower & Cooling Considerations for Virtualized Environments
Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted
More informationDENSITY SOLUTIONS BASED ON PULLED FIBRE TECHNOLOGY
Pub Club Meeting DATA CENTRE Fibre Connectivity Review HIGH DENSITY SOLUTIONS BASED ON PULLED FIBRE TECHNOLOGY Andrew Black Agenda Company and Technology Overview System Features Conventional LAN solutions
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationTable of Contents UK/ N. IRELAND HELPLINE REP. IRELAND HELPLINE
Table of Contents Table of Contents... 1 Safety and Maintenance... 3 Safety Instructions...3 Operational Safety...3 Point of Use...3 Electro-Magnetic Compatibility...4 Information of Conformity...4 Battery
More informationRevo 120. User Manual
Revo 120 User Manual GENERAL INFORMATION Congratulations, you have just purchased one of the most innovative and reliable lighting fixtures on the market today! The Revo 120 has been designed to perform
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationRoutine Care. Document Part Number: October 2005
Routine Care Document Part Number: 383058-002 October 2005 Contents 1 Hardware maintenance Battery pack..................................... 3 TouchPad and keyboard............................ 4 Display.........................................
More informationIt's hosting, safe and secure.
It's hosting, safe and secure. Optus EXPAN NEXTDC provides colocated hosting services for your IT equipment in secure Tier 3 data centre facilities in most capital cities around Australia.. It's world-class
More informationInformation Technology in Green Buildings.
Information Technology in Green Buildings. How can a commercial building claim to be Green when one of the most fundamental elements of the infrastructure, communication and information technology systems,
More informationAddressing Deferred Maintenance with Advanced Facility Condition Assessments at the University of Arizona
Addressing Deferred Maintenance with Advanced Facility Condition Assessments at the University of Arizona Christopher M. Kopach, AVP, The University of Arizona; APPA President Phillip Saieg, Regional Technical
More informationOperating instructions
ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone: +49(0)7938/81-0 Fax: +49(0)7938/81-110 info1@de.ebmpapst.com www.ebmpapst.com CONTENTS 1. SAFETY REGULATIONS AND NOTES Please read these
More informationWhere have all the landlines gone? A white paper from Sensaphone, Inc.
Telephone reliability for alarm notification: Where have all the landlines gone? A white paper from Sensaphone, Inc. Technology advancements continue to open communication without tethering users to a
More informationLiebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets
Liebert DM High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Emerson Network Power, a business of Emerson (NYSE: EMR), is a worldwide leader in infrastructure solutions across
More informationWhite Paper. Archival Media for the Masses. Written by: Arthur G. Blanck. January 2005 WP , REV 1.1
White Paper Written by: Arthur G. Blanck January 2005 WP-120804-001, REV 1.1 Since the beginning of recorded history, humankind s attempts to keep records of social importance have been under the relentless
More information3M Data Center Solutions. Innovation. is the. Solution
3M Data Center Solutions Innovation is the Solution Biometric Physical Security Multi-factor biometric access control reader for data center physical security needs. Air Filtration Filters help provide
More informationViable Options for Data Center Solutions. By Ning Liu Offering Group Panduit APJ
Viable Options for Data Center Solutions By Ning Liu Offering Group Panduit APJ Agenda Market Overview Data Center Challengers Business Drivers Data Center Standards Data Center Technologies Panduit Solutions
More information10 COMMON TRAPS IN DESIGNING A CLEANROOM
10 COMMON TRAPS IN DESIGNING A CLEANROOM Executive summary Cleanrooms provide a controlled environment with a low level of pollutants. They are typically used for manufacturing or scientific research activities
More informationEquipment Strategy for Voltage Transformers Strategy
Equipment Strategy for Voltage Transformers Strategy Current version: 19/06/2018 EXTERNAL USE Page 1 of 6 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References... 3 1.4
More informationWhitepaper. 10 Reasons to Move to the Cloud
Whitepaper 10 Reasons to Move to the Cloud 2 10 Reasons to Move to the Cloud 10 Reasons to Move to the Cloud and Why It Will Be the Best Business Decision You Will Ever Make RapidScale s CloudOffice is
More informationPowerMust Office Uninterruptible Power System
USER MANUAL E PowerMust Office Uninterruptible Power System 614-05737-05 28-2PRO000001 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for Models PowerMust
More informationHigh Efficient Data Center Cooling
Nordborg High Efficient Data Center Cooling Copenhagen Center on Energy Efficiency webinar 12. July 2017 Jörg Saar, Danfoss Cooling 1 Danfoss Cooling Contents 1. Short intro to Danfoss Cooling 2. Introduction
More informationCLEANROOM TECHNOLOGY CERTIFICATION -EXAMINATION
Cleanroom Testing and Certification Board Irish Cleanroom Society CLEANROOM TECHNOLOGY CERTIFICATION -EXAMINATION 1 April 2009 1730-1930 Candidates should read the following instructions: 1) Candidates
More informationJunos WebApp Secure 5.0 Hardware Guide
Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide This document contains a specification for the MWS1000 hardware appliance, as well as instructions for installation into a
More informationRaMP Data Center Manager. Data Center Infrastructure Management (DCIM) software
RaMP Data Center Manager Data Center Infrastructure Management (DCIM) software One solution for both IT and facilities managers As data centers become more complex, it becomes increasingly important to
More informationSamuel Tepp Engineering Seminar Topics
Samuel Tepp Associates 11 Leonard Street Metuchen, New Jersey 08840 Contact: Keith Miller, Cell: 201-638-6591, kmiller@samtepp.net Samuel Tepp Engineering Seminar Topics All topics are approved for New
More informationDATA CENTRE. JT Five Oaks. Facility Product Description. Data Centre Services
JT Five Oaks DATA CENTRE Facility Product Description JT s Data Centre Hosting Service provides a secure computer room environment with protected and backup power, security and bandwidth. Data Centre specification
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More information