1 Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note establishes standards and procedures for the design and installation of network cable (both fiber and copper) and the related network infrastructure (e.g., punch down blocks, cross-connect panels, conduit, enclosures, power outlets, fire stopping, and uninterruptible power supplies). Network cables and their infrastructure provide access to information technology (IT) systems, the data network, telephones and Automated Information Systems (AIS). NOTE: Smithsonian buildings that are not capable of meeting the standard requirements, such as trailers or sheds, will be handled on a case-by-case basis. 2. Scope and Applicability This technical note applies to all Smithsonian Institution employees, interns, volunteers, contractors, and consultants who install and maintain network cables and their related infrastructure anywhere across the Institution. This technical note applies to both new construction and renovations of existing Smithsonian buildings. It provides broad guidance to be used across the Institution and must be used with common sense when applied to buildings that range from new construction to those that predate the telephone. 3. Responsibilities A. Network Management Division (NMD). Manages and maintains all the fiber optic cable throughout the institution, the voice and data cabling infrastructure for many Institutional systems and the Institutional network. NMD also reviews and approves the implementation of voice and data network designs, plans, and installation across the Institution. B. Office of Facilities Engineering and Operations (OFEO). Manages the contractor implementing voice and data network plans, designs, installations for new construction and major renovations (i.e., requires 410 Review ) under the oversight of OCIO. Page 1 of 12
2 Cabling Standards 4. Procedure A. Renovations (Minor). The NMD and its contractors will plan, design, and install network cables and the related infrastructure for existing Smithsonian buildings. The exception is major renovation projects that require a SD 410, Facility Construction and Improvement Projects, review. B. New Installations & Major Renovations. OFEO and its contractors will plan, design, and install network cables and their related infrastructure in new Smithsonian buildings and major renovations (those requiring a SD 410 Review). OCIO will actively participate in these installations by reviewing and approving them. C. Cable Installation. The type of cable to be installed is dependent on its usage. Once the cable type is determined using the following table, it will be installed in accordance with the cable specifications in Appendix A, and color coded appropriately. Usage Backbone & Riser Cabling Laboratory Areas Requirements Fiber Optic cabling will be used. The choice of single mode vs. multimode can be based on the distances and technical considerations. It is recommended for all new Fiber installation that the newer 50/125 micron fiber be used instead of the 62.5 micron currently recommended. In some sites with short lengths between floors use of Cat 6e may be allowed. It is advised that a mix of single and multimode fiber be installed at the rate of three times the quantity that is required for the installation. Whenever possible, aggregate and run the cabling in Underwriters Laboratory/Electronic Industries Alliance (UL/EIA)-approved duct work such as open trays, conduit, latch duct or, in the case of fiber optic cable, in inner-duct. Recommendation is to have two 4-Pair copper installed every 6 feet of running lab bench. Instances needing fiber to lab benches will require OCIO review. Normal Desktops A minimum of (2) 4-pair of copper cable be installed, with 3 desirable Page 2 of 12
3 Cabling Standards Reception, Meeting Rooms & Public Gathering Areas (2) 4-pair of copper cable for every 30 linear feet of wall space. Note: All fiber and copper cabling must be tested in accordance with the ANSI/EIA/TIA-568 Standard, with hard and soft copies of the test results to be provided to the NMD Manager. Under no circumstances is a "FAIL" result acceptable. D. Color Code. Patch cables come in many colors and should be color coded based on their usage as described in the table below. Usage Cross-Over Cables VoIP and Network Cables (crossconnect & wire closet cables) Analog Voice Color Red (required) Yellow (preferred) Pink (preferred) E. Wire Closets & Enclosures. Wire closets and their enclosures must meet the minimum requirements described in Wire Closet Specifications in Appendix B. Within each wire closet, there may be one or more enclosures (e.g., cabinets, racks, boxes, patch panels). In addition, all cross connect cables for the wire closets will be sized to the shortest pre-manufactured length needed to make the connection that satisfies the requirements set forth in the table below 5. Grounding and Bonding (ANSI/TIA/EIA-607) Commercial Building Grounding and Bonding Requirements for Telecommunications. This standard specifies uniform telecommunications grounding and bonding infrastructure that shall be followed within commercial buildings. A. Purpose of ANSI/TIA/EIA 607 Grounding by attachment to the nearest piece of iron pipe is no longer satisfactory to provide ground-reference for sophisticated active electronics systems. Telecommunications equipment, frames, cabinets and voltage protectors must be grounded to busbars, as described in Section B, Design Considerations, below. B. Design Considerations Solid copper grounding busbars are installed with insulated standoffs in entrance facilities (1/4 thick X 4 high X variable length) and the equipment room, as well as each telecom closet (2 high is sufficient here). Each busbar is drilled with rows of holes according to NEMA standards, for attachment of bolted compression fittings. Telecommunications equipment, racks, frames, cabinets and voltage Page 3 of 12
4 Cabling Standards protectors must be grounded to these busbars. Busbars are connected by a backbone of insulated, solid copper cable between all closets and rooms (minimum B AWG, 3/0 AWG recommended). This backbone is connected to a main grounding busbar in the telecommunications entrance facility, to an earth ground in the electrical entrance facility, and to structural steel on each floor. Bonding conductor cabling shall be colored green or labeled appropriately. C. Terms Telecommunications Main Grounding Telecom Bonding Backbone (TBB) Telecom Grounding Busbar (TGB) Telecom Bonding Backbone Interconnecting Bondin Conductor (TBBIBC) D. Schematic of Grounding/Bonding Network The following schematic shows the grounding/bonding network. Schematic of Grounding/Bonding Network Copy of 50D A86256CB0005E0847?OpenDocument, with some modifications TGB Detail To Upper Floors Variable 2" { ¼ Telecom Equipment Panel TBB 6 AWG Minimum TGB Structural Steel Electrical Entrance Grounding??? System Telecommunications Entrance Telecom Equipment 2'-1 1/8" Equipment Room Telecom Equipment Panel Panel IMGB IGB Page 4 of 12
5 Cabling Standards 6. Technical Note Change Log Date of Revision Description of Changes 2/8/2012 Combined the responsibilities of the Network Operations Branch and general OCIO and placed all under the Network Management Division (NMD). In Appendix A, corrected recommended type of fiber connectors. In Appendix B, added several requirements for wire closets. Added Appendix C: Standard Rack Guidelines Diagram 4/21/2009 Revised color coding. Specified use of racks. In Appendix A, noted that use of lockable front panels in cabinets, if deemed necessary by OCIO and revised specifications for special purpose cabling. In Appendix B, revised specifications of wire closets. 5/20/2008 Minor revisions 3/22/2007 Added color coding info for Cat6 and jacks at work site. Made minor revisions to Appendices A and B. 5/25/2006 Extensive update of grounding information 7/28/2004 Initial release. Page 5 of 12
6 Appendix A: Cable Specifications Cable Specification Copper Project Type Specification for Copper Cable Connectors & Conduit New Construction and Renovation (Major & Minor) ANSI/EIA/TIA-568 standard for testing, length, plenum rating, bend radius Cat 6 IEEE 802.3ab standard Connectors for Cat6 cable will be EIA approved RJ-45 connectors. No inline RJ-45 extenders will be used. In the wire closet, all worksite cable running from the workstation to the closet will be terminated on IEEE Cat6 approved patch panels equipped with a lockable front panel, if deemed necessary by OCIO. All non-plenum rated cable will be placed in conduit, or installed to local code and OFEO design specifications. Page 6 of 12
7 Cable Specification Fiber Mode Applicable Specification for Fiber Cable New Construction Renovation Connectors & Conduit Multimode ANSI/EIA/TIA-568-B standard for testing, length, plenum rating, bend radius 50/125 micron ANSI/EIA/TIA-568-B standard for testing, length, plenum rating, bend radius 50/125 micron unless extenuating circumstances require 62.5/125 micron Unless otherwise specified it is recommended that SC type connecters be used for terminations and fiber distribution boxes and panels. All new fiber installation between distribution and access switches should be 50/125 micron. Single mode ANSI/EIA/TIA 568-B standard for testing, length, plenum rating, bend radius ANSI/EIA/TIA 568-B standard for testing, length, plenum rating, bend radius All termination and cross connect panels will be EIA approved. All panels will be secured and lockable. 8.2/125 micron Single mode 8.2/125 micron fiber All fiber cable will be installed in metal conduit, and all elbows and boxes will meet the EIA/TIA/569 standards for bend radius for the particular cable that is being installed. All non-plenum rated cable will be placed in conduit, or installed to local code and OFEO design specifications. Page 7 of 12
8 Cable Specification Special Purpose Cable Type New Construction Specification Renovation Connectors & Conduit New multi purpose antenna systems for wireless Cable specifications are determined by the design. Cable specifications are determined by the design. Cable specifications are determined by the design. Armored cable (outdoor or hazardous installations) Wireless Access Points - ISO/IEC TR Information Technology Customer Premises Cabling Shielded CAT 5e or CAT 6 Shielded CAT 5e or CAT 6 Shielded CAT 5e or CAT 6 Standard CAT 5e or CAT 6 Standard CAT 5e or CAT 6 Standard CAT 5e or CAT 6 Page 8 of 12
9 Appendix B: Wire Closet Specifications Closet Physical Backer Board Environmental Requirements Minimum floor space of 10 feet by 8 feet. Room/closet must be secured with either badge reader access (preferred) or key access. The door to room/closet should swing out to maximize usable space. Must have wall mounted fire-rated plywood backer board. Two walls should have 21mm (0.75 in.) A-C plywood 2.4m (8 ft.) high. Positive ventilation and air conditioning is required to remove the heat load generated by the equipment. HVAC requirements to maintain temperature the same as adjacent office area. A positive pressure shall be maintained with a minimum of one air change per hour or per code. Overhead HVAC units are not to be used in the IT closets. The preferred method is that these spaces have their own thermostat and be served by external HVAC units. Lighting shall be a minimum of 500 lx (50 foot candles) and mounted 2.6m (8.5 ft.) above floor. Standard work place lighting is required. At least one proper code approved ground bus bar for each closet is required. Page 9 of 12
10 Closet Electrical Requirements Technical Note: IT-960-TN14 Dedicated grounded electrical feeds. Minimum of two dedicated 20 Amp, non-switched, duplex electrical outlet receptacles (or equivalent); each on separate branch circuits. Additional convenience duplex outlets placed at 1.8m (6 ft.) intervals around perimeter, 150mm (6 in.) above floor. The manufacturer s installation site requirements guide for each device should be used to determine the NEMA outlet specification, and the voltage and current requirements. When equipment has redundant power supplies, the electrical outlets/supplies for each power supply in the device should be on a separate dedicated electrical line. Unless otherwise specified, electrical receptacles should not be installed on or above the IT racks. The receptacles for IT equipment should be tied to emergency backup power systems whenever possible. Closet Uninterruptible Power Supply (UPS) Requirements The UPS should be sized to support each piece of equipment located in the wire closet. One UPS is used per electrical supply line. When equipment has redundant power supplies, one power supply is connected directly to a dedicated electrical outlet and the other is connected to a UPS on a different dedicated electrical outlet. All equipment must be properly grounded according to code. Page 10 of 12
11 Closet Enclosures (e.g., box, cabinet, two-rail rack) Requirements Technical Note: IT-960-TN14 The upper part of any wall mounted equipment, racks or cabinets shall not exceed 6 in height from the floor so that they can be safely managed without the use of ladders or other means necessary for elevated access. All enclosures for cable terminations will comply with the applicable EIA standard for the type of cable being installed. All enclosures for communication equipment will meet EIA standards, as well as the device site requirements specified by the equipment manufacturer. Enclosures will be attached to a ground bus bar in the closet. If deemed necessary by OCIO, all communication fiber optic patch panels will be lockable and use the recommended Master Lock product # 1520D combination lock. The combination of the lock will be managed, changed, and maintained by OCIO. Unless otherwise specified, 7 ft high 2-post open frame 19 inch racks are the standard for mounting patch panels, fiber enclosures and equipment. Rack elevations should follow the guidelines below: o Fiber enclosures should be situated at the top of the rack (2U to 4U depending on fiber quantities). o 2U RJ45 48-port patch panels should be installed below the fiber enclosure(s), beginning from the upper part of the rack and working down. o A single 1U RJ45 24-port patch panel should be installed immediately above the first 2U RJ45 panel for the termination of a 25 pair cable for analog lines. o 2U horizontal cable managers should be installed below the fiber enclosure, between each RJ45 panel, and one below the last panel. o Each side rail should be equipped with vertical cable managers (4 wide minimum). Adjacent racks can share a single vertical manager. See Appendix C, Standard Rack Guideline Diagram, for more information. Labeling of copper ports & fiber links All copper pairs will be labeled with the wireclosetroom#-room#- [a-z]. All fiber links will be labeled with wireclosetroom#-[01-99]- wireclosetroom#-[01-99] Page 11 of 12
12 Appendix C: Standard Rack Guidelines Diagram Units Fiber Termination Box (2RU or 4RU) U Cable Management 1U 24 Port RJ45 Patch Panel 48 Port CAT6 Patch Panel U Cable Management " C a b l e 48 Port CAT6 Patch Panel 2U Cable Management 48 Port CAT6 Patch Panel 2U Cable Management 4" C a b l e Port CAT6 Patch Panel 7' M a n a g e m e n t 2U Cable Management 48 Port CAT6 Patch Panel 2U Cable Management M a n a g e m e n t OCIO Network Equipment " Page 12 of 12
Tarleton State University. Specifications
Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication
More informationCommunications. UNM IT/Telecommunications Guide Specification Communications
The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary
More informationThe six major components of a structured wiring system are:
OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.
More informationComputer Network Design Guide Existing Systems 1 / 6
COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should
More informationLos Angeles Community College District Design Standards
LACCD Facilities Design Standards - Structural Cabling and Telecommunications Room Facilities Ver Approved: DTC February 0, 0 LACCD has developed the following Districtwide standard for IT infrastructure
More informationCOMPUTER NETWORK WIRING SYSTEMS FOR PLCs
SECTION 13744 COMPUTER NETWORK WIRING SYSTEMS FOR PLCs NOTE TO SPECIFIER: This section applies to primary learning centers only. PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete computer network
More informationNetwork Construction Guide Specification Telecommunications Infrastructure Standards V 2.6
Network Construction Guide Specification Telecommunications Infrastructure Standards 11-16-2018 V 2.6 Springfield Public Schools R12 Prepared by: Approved by: Released by: Springfield Public Schools R12
More informationINTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES
INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES University of California, Riverside Computing and Communications April XX, 2001 R1V6 TABLE OF CONTENTS Introduction and Background...3 Outside
More informationf) Telecommunications Equipment Rooms
SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification
More informationTarget Interface / Construction Compliance Inspection Checklist
TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data
More informationv2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.
Changes in v2.6: v2.5 was updated May 10, 2016. v2.6 is an updated copy from March 1, 2017. Modifications to 4. Horizontal Pathways section with feedback incorporated from UofA Facilities and Operations
More informationInstallation Notes TII Model 341 Protector
Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow
More informationLACCD IT Design Standards
LACCD IT Design Standards March 1 2009 This document establishes a uniform standard for the design of IT Structured Cabling for LACCD. It ensures a secure, consistent, robust system with physical and low-voltage
More informationSPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120
DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified
More informationANSI/TIA/EIA-568-B Cabling Standard NOTE
95 ANSI/TIA/EIA-569-A Though the ANSI/TIA/EIA-568-B Standard describes the subsystems of a structured cabling system, the TIA has published a more thorough document called ANSI/TIA/EIA-569-A Commercial
More informationNewark, Delaware Architectural Engineering Senior Thesis Portfolio
Telecommunications System Design The represents the advancement of solar design in our world today. The building itself is an example of this. A Headquarters this dedicated to moving into the future should
More informationData Cabling / Low Voltage Technology Specifications
P19-02- Forsyth County Schools Data Cabling / Low Voltage Technology Specifications 1. General requirements 1.1 On premise connectivity All building closets (IDF) aside from the main closet (MDF) shall
More informationBonding and grounding NETCONNECT copper cabling systems
White paper Bonding and grounding NETCONNECT copper cabling systems A complete review of bonding and grounding for copper twisted-pair cabling systems www.commscope.com 1 Taking the guesswork out of grounding
More informationANSI/TIA/EIA-568-B Cabling Standard
83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on
More informationDESIGN GUIDELINES. Building Circulation
DESIGN GUIDELINES Building Circulation Conceptual Plan FUNCTIONAL AREA DESCRIPTION Building circulation includes all the elements which enable people (including those with disability restrictions) to circulate
More informationGovernment of Prince Edward Island Structured Cabling Standards August 24, 2009
Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a
More informationThe Riser as a Contract Document. Peter Sharp, RCDD
The Riser as a Contract Document Peter Sharp, RCDD IBI Group 1 1 Who am I? Presenter Credentials Electrical Engineer Specialties in communications, electronics and computer sciences, In practice for 40
More informationClassroom WiFi Network Infrastructure Plan
Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to
More informationTIA/EIA 568A Sub-system HORIZONTAL CABLING
TIA/EIA 568A Sub-system HORIZONTAL CABLING Horizontal Cabling WA 100(120)Ω CAT 3 TP TP 100(120)Ω CAT 5 150Ω STP-A 62.5(50)/125µ FIBER HC/FD WA Horizontal Media Considerations UTP/FTP Consider bandwidth,
More informationSECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations
SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT ITS Telecommunications Standards - Specifications Manual for Construction and Renovations Page 1 of 67 TABLE OF CONTENTS UNC Charlotte Information Technology
More informationPeter Sharp RCDD IBI Group
Peter Sharp RCDD IBI Group Who am I? Presenter Credentials Electrical Engineering Consultant Specialties in communications, electronics and computer sciences, In practice for more than 40 years Member
More informationE. Numbering and Labeling Pathway components. In general, pathway components are not labeled.
27 05 53 Identification (Labeling) for Communications Systems (Revision date: 3/6/13) 1.0 Purpose A. These guidelines provide requirements for designers to incorporate into bid documents. They are part
More informationDesign Guidelines for Facilities Construction:
Western Michigan University Office of Information Technology & Campus Planning, Design & Construction Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG17-12 System Terminology, Definitions,
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationOptimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit
Optimization and Speed: Two Critical Standards Enabling Next Generation Networks Stephanie Montgomery, TIA Brett Lane, Panduit Structure of TIA Standards 2 A family of Standards ANSI/TIA-942-A Telecommunications
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationA. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
UDIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
More informationUMass Lowell. October 1, Network and Voice Infrastructure Specifications Prepared by Network Engineering and Network Project Management
UMass Lowell October 1, 2011 Network and Voice Infrastructure Specifications Version 5.1 Prepared by Network Engineering and Network Project Management TABLE OF CONTENTS NETWORK AND VOICE INFRASTRUCTURE
More informationTelecommunications Structured Cabling Systems
Section 18 Telecommunications Structured Cabling Systems 18.1.0 Introduction 18.1.1 Important Codes and Standards 18.1.2 Comparison of ANSI/TIA/EIA, ISO/IEC, and CENELEC Cabling Standards 18.2.0 Major
More informationThe University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS
SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels
More informationCabling a Data Center to TIA-942 Standard
Cabling a Data Center to TIA-942 Standard BICSI 2006 Winter Conference Wednesday, January 25 th 2006 at 9:15 am Gary J. Bernstein, RCDD HellermannTyton Corporation Agenda Overview of TIA-942 Data Center
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC 5-, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC 5-,
More informationAT&T Virtual Private Network Service (VPN) and AT&T VPN Express
AT&T Virtual Private Network Service (VPN) and AT&T VPN Express Site preparation guide This guide is designed to assist local on-site contacts to understand what you will need to accomplish in preparation
More informationSECTION TELEPHONE AND COMPUTER CABLING
SECTION 16700 TELEPHONE AND COMPUTER CABLING PART 1 - GENERAL Verify the computer and telephone cabling standards with MINES CCIT and Telecommunications departments. Telephone and computer lines shall
More informationCabinet Location Plan FIG.01. Cabinet Symbol Key. Air Handler. Air Handler SAN disk storage. SAN disk storage. option B. Not To Scale.
Cabinet front face - 09 Data Center Storage / Fit-Up Square Feet Square Meters Up Cabinet Symbol Key A Network Row A Network Substation B Server Cabinet A A A A4 A A6 A7 A8 A9 FIG.0 Data Center Square
More informationSPECIFICATION STANDARD
PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing unless otherwise specified, and
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Date: Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of stations meets DD 9, applicable
More informationAT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)
AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide This guide is designed to assist local on-site contacts to understand what you will need to
More informationSECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING
SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete
More informationA/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS
A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS May 1, 2016 Reviewers should - Be aware that these checklists are not allinclusive but only provide important review items. Reviewers should - Use Checklists
More informationCopper Riser And Intrabuilding Cabling
Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable
More informationPoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS
PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS Version 14 November 19, 2014 Digital Realty Table of Contents INTRODUCTION... 3 ACCESS TO THE POP ROOMS, ISP & OSP... 3 PoP- MoP Forms... 3 Who must
More informationData Center Design and the ANSI/TIA-942 Standard
Data Center Design and the BICSI Regional Meeting Ellicott, MD Rick Foster RCDD,TLT Communications Infrastructure Group July 27, 2006 What is ANSI/TIA-942? Published by TIA in April 2005 Telecommunications
More informationAT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)
AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide 2015 AT&T Intellectual Property. All rights reserved. AT&T, the AT&T logo and all other AT&T
More informationSPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING
PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the
More informationANSI/TIA/EIA-568-B Cabling Standard
73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before
More informationNZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling
Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation
More informationAMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo
AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! 2 Standards ISO CENELEC AS/NZS ANSI IEC CSA TIA EIA EN50173 AS/NZS
More information1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM
1993 SPECIFICATIONS CSJ 1685-05-068, ETC. & 1685-02-042 1.0 DESCRIPTION SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM THIS ITEM DESCRIBES THE OPERATION AND INSTALLATION OF AN ARTERIAL
More informationCommunication
27 00 00 Communication 1.01 Scope of Standard A. These guidelines identify and define Texas State University requirements and policies for designing and installing telecommunications infrastructure and
More informationAnticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards
Anticipating Cat 8 Agenda Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards What is Cat 8? Next Generation Copper Cabling 25G and 40G data rates over twisted pair copper
More informationYork Region Information Technology Services. Standards and Guidelines. Cabling and Wiring for Voice and Data Communications
York Region Information Technology Services Standards and Guidelines Cabling and Wiring for Voice and Data Communications Current Published Version May 9, 2018 Table of Contents Document History... 4 Revision
More informationAT&T Virtual Private Network Service (VPN) and AT&T VPN Express
AT&T Virtual Private Network Service (VPN) and AT&T VPN Express Site Preparation Guide 2017 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered
More informationSYSTIMAX GigaSPEED Xpress Solution Design Guidelines
Design Guidelines Issue 2 August 2010 Contents 1.0 Overview 3 2.0 Power Separation 4 3.0 Bonding and Grounding 4 4.0 Administration and Labeling 5 5.0 General Cable Guidelines 5 6.0 Bundling and Alien
More informationBROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS
BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS All noted standards apply to the current revisions applicable at the time of construction or intended construction. NO SUBSTITUTIONS
More informationUniversity of Arkansas at Little Rock
University of Arkansas at Little Rock Policy Name: Infrastructure Cabling and Wiring Standards Policy Number: 702.1 Effective Date: September 24, 2008 Policy: University of Arkansas at Little Rock (UALR)
More informationTechnology Standards
June 6, 211 Communications Infrastructure Cabling Services ITB Addenda #1 APPENDIX D, Revision 3.3, dated May 19, 26, is replaced in its entirety, with APPENDIX D, Revision 9, dated April 211, per the
More informationSite Preparation CHAPTER
CHAPTER 3 Site Preparation This chapter describes the steps to take and the considerations you should keep in mind prior to installing the modules in an open rack. It also contains information that applies
More informationCurrent Control Houses
Current Control Houses Building Shielding db Type Example 0 Transparent Wood 5 Poor Masonry 10 Moderate Concrete 20 Good Metal Siding 30 Metal All-Metal Current Control Houses Points of Entry Electrical
More informationSECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS
SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS CONTENTS PAGE 1. GENERAL... 5-1 1.1. Introduction... 5-1 1.2. Equipment Layout Requirements... 5-1 2. EQUIPMENT FRAMES... 5-2 2.1. Introduction...
More informationBACKBONE CABLING. Structured Cabling Systems. Entrance Closet. Telco Closet. Intermediate Cross Connect. Telco Closet. Main Cross Connect.
Structured Cabling Systems BACKBONE CABLING Bldg 3 Entrance Closet Telco Closet Bldg 2 Telco Closet Intermediate Cross Connect Main Cross Connect Backbone Cabling ER HC/FD UTP STP-A Optical Fiber HC/FD
More informationAT&T Switched Ethernet Service SM
Site Preparation Guide AT&T Switched Ethernet Service SM December 2016 2016 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered trademarks
More informationCommunications Updated April
27 00 00 Communication 27 05 00 Common Work Results for Communications 1. Purpose a. Coastal Carolina University facilities requiring cabling installation. This document provides the minimum performance
More informationSTATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SAFETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625
September 2011 STATE OF NEW JERSEY BUREAUS OF ITS ENGINEERING AND SAFETY & DATA DEVELOPMENT DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 MATERIAL SPECIFICATIONS FOR WEIGH-IN-MOTION SYSTEM The
More informationNZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers
Page 1 of 5 Title Demonstrate knowledge for telecommunications premises network cablers Level 2 Credits 2 Purpose This unit standard is for people installing and maintaining telecommunications cables on
More informationGeneral. Exterior Cameras. Camera Towers
CAMERAS General This section explains the requirements for interior and exterior cameras. Two basic types of training ranges have cameras: Urban Ranges and Instrumented Training Ranges. Refer to the standard
More informationSECTION COMMON WORK RESULTS FOR COMMUNICATIONS
PART 1 - GENERAL SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the
More informationFIBER OPTIC HARDWARE STEVE PAULOV
C H A P T E R 7 FIBER OPTIC HARDWARE STEVE PAULOV The main purpose for hardware is to protect and organize splice and termination points. Hardware can be divided into two categories; indoor and outdoor.
More informationCOMMON WORK RESULTS FOR COMMUNICATIONS
SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the
More informationElement Z General Design Requirements Owner Standards and Other Requirements
Element Z General Design Owner and Other IS Network Services & PART 1 - General Information...2 1.01 Background...2 1.02 Scope...2 1.03 Additions, changes, testing, and acceptance...2 1.04 Special cases
More informationDivision 27 Master Specification for
Division 27 Master Specification for Information Transport Systems and Spaces December 1, 2018 1 Table of Contents 1 Section 27 10 01 Structured Cabling General Requirements 1.1 Scope 1.2 Approved Contractor
More informationCCNA 1: Networking Basics v3.0 Cisco Networking Academy Program
F.A.R.B Case Study F.A.R.B Software Development, LTD.: Network Design and Implementation CCNA 1: Networking Basics v3.0 Cisco Networking Academy Program Overview Students completing this case study should
More informationFall Test 21 due 12/11/2012
Fall Test 21 due 12/11/2012 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Emergency system transfer equipment, including automatic transfer switches,
More informationSection COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cable Management and Ladder Rack
PART 1 GENERAL 1.1 WORK INCLUDED Section 27 11 00 COMMUNICATION EQUIPMENT ROOM FITTINGS Section 27 11 23 Communications Cable Management and Ladder Rack A. Provide all labor, materials, and equipment for
More information2 Telecommunications Data Center Facility Requirements
Generic Requirements for Telecommunications Data Center Equipment and Spaces GR-3160-CORE Table of Contents Table of Contents Generic Requirements Notice of Disclaimer..................... iii Preface...........................................
More informationElectrical Demand Specification (Reference SOP: )
Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3
More informationTechnical Planning for Moving Into a Colocation Data Center
Technical Planning for Moving Into a Colocation Data Center Jonathan Jew - J&M Consultants, Inc. Co-chair BICSI Data Center Subcommittee Secretary TIA TR-4 Telecommunications Cabling Systems Chair TIA
More informationWire Communications Design jfm 07. An Inside Look at Outside Plant
An Inside Look at Outside Plant BICSI Region Meeting 2007 Agenda What is CO-OSP? A close look at the 758-A standard Available Resources What is CO-OSP? Customer Owned Outside Plant Telecommunications infrastructure
More informationSiemon PON Fiber Cabling Solutions
Siemon PON Fiber Cabling Solutions WWW.SIEMON.COM 8 Siemon Enterprise PON Fiber Cabling Solution Siemon Enterprise Passive Optical Network (PON) Fiber Cabling Solution improves the modularity, flexibility
More informationStructured Cabling Guidelines
Informatics Planning and Services Structured Cabling Guidelines Version 1.7 August 2015 Informatics Planning and Services 1 Version 1.7 TABLE OF CONTENTS SECTION 1 STATEMENT OF PURPOSE... 1 SECTION 2 APPLICABLE
More informationICS Entrance Management Sign Installation Guide. Version 1.0
ICS Entrance Management Sign Installation Guide Version 1.0 Thank you for purchasing your new ICS Entrance Management System (EMS) from Innovative Control Systems, Inc. Installation Overview This document
More informationEXHIBIT 6. Number: A1201-S-02 Revision: 4 DRAFT Category: Information Technology Telecommunications Issued: November, 2011
Maricopa County Standard Number: A1201-S-02 Category: Information Technology Telecommunications Issued: November, 2011 Initiated by: Office of Enterprise Technology Reviewed by: OET Revised: Al Brown,
More informationBICSI Northeast Regional Meeting June 17, Storrs CT. Considerations in Data Center Design. Thomas McNamara, RCDD
BICSI Northeast Regional Meeting June 17, Storrs CT Considerations in Data Center Design Thomas McNamara, RCDD AGENDA Purpose is to allow the ITS professional to be aware of the issues and therefore pose
More informationMeter Enclosure and Equipment Standards
Meter Enclosure and Equipment Standards (a) (b) General Requirements: CITY OF OCALA UTILITY SERVICES METER ENCLOSURE AND EQUIPMENT STANDARDS: (1) To avoid the costs associated with having to replace unacceptable
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO/IEC 18010 First edition 2002-05 Information technology Pathways and spaces for customer premises cabling ISO/IEC 2002 All rights reserved. Unless otherwise specified, no part
More informationMICHIGAN DEPARTMENT OF TRANSPORTATION
MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13
More informationor
Infinite possibilities for your data center The F-Series TeraFrame T M Cabinet System The F-Series TeraFrame Cabinet System from Chatsworth Products, Inc. (CPI) provides configurable thermal management
More informationSECTION COMMUNICATIONS BACKBONE CABLING
(NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 GENERAL 1.1 RELATED
More informationTCM-1 Beamtracking Ceiling Microphone TCM-1A Beamtracking Ceiling Microphone with Amplifier TCM-1EX Beamtracking Expansion Ceiling Microphone
TCM-1 Beamtracking Ceiling Microphone TCM-1A Beamtracking Ceiling Microphone with Amplifier TCM-1EX Beamtracking Expansion Ceiling Microphone OPERATION MANUAL APRIL 2018 TCM-1, TCM-1A & TCM-1EX PRODUCT
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationTarget Interface / Construction Compliance Inspection Checklist
A. Targets Quantities meet DD9, applicable TC -, and CEHNC Design Guide 0-- Oriented to face firing line or firing positions/points B. Roads-Service, Lanes Number of lanes meets DD 9, applicable TC -,
More informationNZQA unit standard version 2 Page 1 of 5
Page 1 of 5 Title Demonstrate knowledge of installation practices and procedures for telecommunications network equipment Level 3 Credits 10 Purpose This unit standard covers the installation of basic
More informationQualified Partner Programme QPP. Installation Practice Felice Guarna Wetzikon, July 2001
Qualified Partner Programme QPP Installation Practice Felice Guarna Wetzikon, Why installation quality Product performance must be preserved by an accurate installation Long term warranty requires design
More informationWith the publication. Make the right connection: Bonding a shielded system. installation
Make the right connection: Bonding a shielded system installation With the publication of the IEEE 802.3an 10GBase-T standard in 2006, Augmented Category 6 (i.e., Category 6A) cabling systems are being
More informationInnovative POWER Solutions
Innovative POWER Solutions ISO 9001 : 2008 REGISTERED QUALITY MANAGEMENT SYSTEM PANTROL, INC. INVITES YOU TO REVIEW A SAMPLING OF OUR STANDARD PRODUCTS LINE. FOR SPECIAL APPLICATIONS OR CONFIGURATIONS
More information