Application of Green Technology For Data Centre
|
|
- Adelia Russell
- 5 years ago
- Views:
Transcription
1 Application of Green Technology For Data Centre Steven So Vice President Data Centre Business Cloud Business Division NTT Com Asia Limited 25 Sep 2013
2 Today s Agenda Why? How? What?
3
4
5
6 Business Drivers for Green DC Bottom Line Less energy cost Less equipment & maintenance cost Top Line More inventory Regulatory CSR Compliance to standard Perception Customer expectation
7 Effectiveness Efficiency Energy Saving Approach BETTER USE OF RESOURCE Supply Demand Energy cycle REDUCE energy input to Facility For SAME power input to IT equipment Facility IT REDUCE power input to IT Equipment For SAME computing output Effectiveness
8 You will see sunlight for data centre energy saving after moving to cloud 8
9 Demand Side Management - Virtualization Effective use of computing resources including server, storage, network Traditional Architecture Virtual Architecture
10 Facility Utilization Virtualizing Facility System Server 1+1 BMS 1+1 CCTV 1+1 Access 3:1 1 Duty (3VM) 1 Standby (3VM) X 6 X 2 20% CPU Utilization 35% Facility Utilization 1.68kW 60% CPU utilization 50% facility utilization 0.8kW 52% electricity Saving CPU Utilization
11 NTT Com Enterprise Cloud Footprint 11 locations in 9 countries more to come UK US(West coast) US(East coast) Thailand HK Japan Singapore Malaysia Australia
12 Supply Side Management
13 Effectiveness Supply Side Management Operation Loss Reduction Energy Efficient Equipment Alternative Energy
14 NTT Data Centre Footprint 142 Locations in 78 Cities (As of August 2013) 3 locations Europe (13 locations/ 8 cities) China/ Hong Kong (10 locations/ 4 cities) Japan (93 locations/ 49 cities) APAC (19 locations/ 11 cities) Americas (7 locations/ 6 cities) 7 locations 1 location (Scheduled for June 2014) 4 locations
15 Cold Aisle Containment Loss Reduction
16 Cold Aisle Containment Loss Reduction ROI 3 years Benefit 10% overall cooling efficiency Reduce fan power Reduce pump power Increase cooling capacity Consideration Leakage Fire services compliance Thermal ride through Human comfort
17 Dynamic Air Control Loss Reduction Conventional Airflow Management Cold aisle temperature co-work Raised floor pressure co-work Dynamic Airflow Management Self learning artificial intelligence to map CRAH to sensors Cold aisle temperature individual control
18 Dynamic Air Control Loss Reduction ROI 3 years Benefit 15% overall cooling efficiency Reduce fan power Reduce pump power More stable supply air temperature Increase cooling capacity Consideration Load profile
19 Eco-mode UPS Efficient Facility ROI Immediate Onlinemode Ecomode 4ms Onlinemode 0ms Eco-mode Consideration Coordination along the entire power supply chain Quality of utility power Benefit 6% overall power efficiency 99% vs 93% No investment needed
20 Fuel Cell Energy Station Alternative Energy Inputs Outputs Solid Oxide Fuel Cell
21 Fuel Cell Energy Server Alternative Energy 30-50% Efficiency Large CO 2 footprint for coal-fired plant 60-90% Efficiency Centralized Power Generation Distributed Power Generation 60% Efficiency
22 Fuel Cell Energy Server Alternative Energy ROI 3 years Consideration Electricity $ vs fuel $ Utility power stability Government incentive Fuel storage Local support Benefit Lower carbon footprint than coal/gas-fired power plant More efficient than centralized power plant Simple, fast & scalable
23 Free Cooling Alternative Energy ROI 2 years Benefit 60% overall cooling efficiency 120 free cooling days in a year Operating Ambient Condition 25⁰C DB 60% RH Consideration Ambient condition Air quality Space factor
24 What Happens Beyond Data Center = 322 kwh per year 361 kwh per year 1.58G Data per month 361kWh Transmission 3.5kWh Charging 361 TWh per year World Electricity Consumption 19,000 TWh per year ICT Electricity Consumption 1,900 TWh per year Data Center 380 TWh Non Data Center 1520TWh
25 Thank You Contact Us 25
26 Rotary UPS Efficient Facility ROI 7 years Benefit 3% overall power efficiency 96% vs 93% for static UPS No battery Lower running cost Consideration 10 to 15 second mechanical battery Form factor Noise & vibration Local support
How High-Density Colocation and Enhanced Visibility Improve Business Performance
How High-Density Colocation and Enhanced Visibility Improve Business Performance Steven So Vice President Data Center Business Cloud Business Division NTT Com Asia Limited 11 Sep 2015 NTT Communications
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationEP s approach to Power & Energy efficiency in DCs & paradigms
DG for Innovation and Technological Support EP s approach to Power & Energy efficiency in DCs & paradigms Presentation Presentation subtitle subtitle or lead-in or lead-in that says that what says what
More informationMaking the impossible data center a reality.
United Nations ITU WSIS 2016 WINNER E-Environment Malaysia s First Win 2015 ASIA PACIFIC WINNER 2015 Best of Sustainability and Environmental Technology WINNER 2015 Best of Sustainability and Environmental
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationGreen Data Centers A Guideline
Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging
More informationCase study on Green Data Center. Reliance Jio Infocomm Limited
Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center
More informationINSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE
INSIDE THE PROTOTYPE BODENTYPE DATA CENTER: OPENSOURCE MONITORING OF OPENSOURCE HARDWARE Dr Jon Summers Scientific Leader in Data Centers, RISE Adjunct Professor of Fluid Mechanics, Lulea University of
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationCase Study Leicester City Council
Data Centre Solutions...energy efficient by design Case Study Leicester City Council Leicester City Council Deploys New Sub 1.1 PUE3 Data Centre Infrastructure. Designed & Installed by Workspace Technology
More informationLiebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets
Liebert DM High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Emerson Network Power, a business of Emerson (NYSE: EMR), is a worldwide leader in infrastructure solutions across
More informationData Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology
Data Centre Energy Efficiency Duncan Clubb EMEA Data Centre Practice Director CS Technology Key Messages No more silos energy efficiency only comes from a holistic approach to DC design and operation If
More informationLiebert APM The Compact Row-Based UPS With Flexpower Technology TM 30kW - 300kW. AC Power For Business-Critical Continuity
Liebert APM The Compact Row-Based UPS With Flexpower Technology TM 30kW - 300kW AC Power For Business-Critical Continuity Emerson Network Power, a division of Emerson, is a global company that combines
More informationRockwell Automation ODVA Annual Meeting
Rockwell Automation ODVA Annual Meeting Copyright 2011 Rockwell Automation, Inc. All rights reserved. Topics Industrial Energy Management: Industrial GreenPrint Business Drivers Enabling Solutions Copyright
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationWe are Ready to Enable
Face to Face We are Ready to Enable Akram Tuffaha Huawei Middle East Region Account Service Department Director In recent industry transformations of measuring the network quality, you have mentioned the
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationRF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink
INDUSTRIAL INTERNET IN ACTION CASE STUDY RF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink CLIENT PROFILE CenturyLink Technology Solutions is the second largest telecommunications
More informationData Center. Tai Po Data Center
Data Center Tai Po Data Center TAI PO DATA CENTER Nexcenter The Global Data Center Vision NTT Communications offers data center services at hundreds of locations worldwide under the brand name Nexcenter.
More informationScalable, Secure. Jason Rylands
Energy Efficient, Modular, Scalable, Secure Jason Rylands The planning, construction and operation of IT infrastructure for mission critical applications in reliable Datacentres represents a real challenge.
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationMicrosoft s Cloud. Delivering operational excellence in the cloud Infrastructure. Erik Jan van Vuuren Azure Lead Microsoft Netherlands
Microsoft s Cloud Delivering operational excellence in the cloud Infrastructure Erik Jan van Vuuren Azure Lead Microsoft Netherlands 4 Megatrends are driving a revolution 44% of users (350M people) access
More informationData Center Optimized Controls
Data Center Optimized Controls Controls Agenda 30 min. Emerson Control Products icom (Dynamic Thermal Optimization) 20 min. Station Rotation Station 1: Controller Challenge Station 2: Wireless Demo 5 min.
More informationContinuity Insights Chicago: Evolving Data Center Trends & Design Standards. 19 June Jose Hernandez, 30+ years of design/build experience
Continuity Insights Chicago: Evolving Data Center Trends & Design Standards Technology Management, Inc. 1911 Rohlwing Rd., Suite E Rolling Meadows, IL 60008 847 394 8900 19 June 2013 www.tmiamerica.com
More informationData Center. Nexcenter Providing world-class quality and full-support Global x Non-stop data center service
Data Center Nexcenter Providing world-class quality and full-support Global x Non-stop data center service Consistent contracting worldwide with the ability to distribute workloads globally. Quality Supporting
More informationDC Energy, Efficiency Challenges
DC Energy, Efficiency Challenges Choosing a density strategy Implementing a high density environment Maximizing the efficiency benefit Anticipating the dynamic data center Key points on energy usage in
More information1.0 Executive Summary. 2.0 Available Features & Benefits
Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions
More informationGlobal Leased Line Service
SERVICE BROCHURE Global Leased Line Service from NTT Communications Predictable, low latency global networking with the highest quality A global managed bandwidth solution from NTT Communications (NTT
More informationWorld Class. Globally Certified. High Availability.
Intellicentre 2 World Class. Globally Certified. High Availability. Intellicentre 2 Macquarie Park, Sydney 2 Intellicentre 2 A new generation of data centre solutions. Australia s first showcase Tier III
More informationIndustry leading low energy evaporative fresh air cooling.
Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationDatacentre Reading East 2 Data sheet
Datacentre Reading East 2 Data sheet Data sheet Datacentre Reading East 2 Find us With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our datacentre locations, Pulsant has the
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationAMS6, Amstel Business Park Campus. Highly connected, Energy efficient data centre. Duivendrechtse kade 80A 1096 AH Amsterdam Netherlands
AMS6, Amstel Business Park Campus Highly connected, Energy efficient data centre. Duivendrechtse kade 80A 1096 AH Amsterdam Netherlands Tel: +31 (0) 20 592 9263 Nl.info@telecity.com www.telecitygroup.nl
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationHIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.
HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market
More informationEcotel Free Cool 5-15kW
Precision Air Conditioning Free-cooling Ecotel Free Cool 5-15kW + + Self-contained compact outdoor cabin cooler + + 100% free-cooling + + -48V DC supply option + + Easy serviceability (front component
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationBENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS
BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid
More informationData Center Design and. Management. Steve Knipple. August 1, CTO / VP Engineering & Operations
Data Center Design and Energy Management Steve Knipple CTO / VP Engineering & Operations August 1, 2013 Agenda Introduction to EasyStreet Speaker Bio EasyStreet Sustainability Data Center 1 (Retrofit completed
More informationData Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationIT Level Power Provisioning Business Continuity and Efficiency at NTT
IT Level Power Provisioning Business Continuity and Efficiency at NTT Henry M.L. Wong Intel Eco-Technology Program Office Environment Global CO 2 Emissions ICT 2% 98% Source: The Climate Group Economic
More informationNexcenter Providing world-class quality and full support Global x Non-stop data center service
Data Center Nexcenter Providing world-class quality and full support Global x Non-stop data center service NTT Communications Corporation Website http://www.ntt.com http://www.ntt.com/nexcenter About NTT
More informationUBS Data Center Efficiency Strategy
UBS Group Technology Public UBS Data Center Efficiency Strategy Steps in Efficiency, Automation leading to enabling the Cloud October 18, 2011 UBS one of the leading financial firms UBS draws on its 150-year
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationMunters third quarter 2018 Sales and earnings growth
Munters third quarter 2018 Sales and earnings growth Sales and earnings growth Order intake increased by 14% driven by growth in Data Centers and AgHort Net sales increased by 13% with strong growth in
More informationNTT Com Press Conference March 1, 2016 #enterprisecloud
NTT Com Press Conference March 1, 2016 #enterprisecloud 1 Significant Enhancement of Enterprise Cloud - Realizing Digital Transformation - NTT Communications March 1, 2016 2 NTT Communications Initiatives
More informationCloud environment. dr inż. Piotr Boryło , Kraków
Cloud environment dr inż. Piotr Boryło 7.03.2018, Kraków Agenda Cloud fundamentals Greening the cloud Intercloud Fog/Edge Computing Network Function Virtualization SDN for clouds Testing the cloud vs cloud
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationTim Dillon. The Data Centre and Hosting Services. Supporting the Drive to New Normal. Associate Vice President Research, IDC Australia
Tim Dillon Associate Vice President Research, IDC Australia The Data Centre and Hosting Services Supporting the Drive to New Normal Brought to you by: The Data Centre and Hosting Services Supporting the
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationData Center. Data Centers in Hong Kong
Data Center Data Centers in Hong Kong DATA CENTERS IN HONG KONG Nexcenter The Global Data Center Vision NTT Communications offers data center services at hundreds of locations worldwide under the brand
More informationWHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net
Digi-RTU WHAT IS THE DIGI-RTU The Digi-RTU is a Heating, Ventilation, and Air Conditioning (HVAC) rooftop unit control kit that is both a demand management and energy usage device. It is designed to improve
More informationSchneider Electric. November, 2014
Schneider Electric November, 2014 1 Three trends set to double energy demand by 2050 Urbanization Industrialization Digitization Challenges: > Increasing energy cost > Peaks in demand > Pollution > City
More informationCITIC 1616 Holdings Limited 中信 1616 集團有限公司
Holdings Limited 中信 1616 集團有限公司 (Stock Code: 1883) (Stock Code: 1883) Interim Results Announcement for the six months ended 3 June 21 11 August 21 1 Highlights for the Six Months Ended 3 June 21 Profit
More informationUPS PRO MODERNÍ DATOVÁ CENTRA. Rastislav Smatana AC Power Sales Manager CZ&SK
UPS PRO MODERNÍ DATOVÁ CENTRA Rastislav Smatana AC Power Sales Manager CZ&SK VERTIV BY THE NUMBERS SALES $4.4B EMPLOYEES ~20,000 CUSTOMERS INCLUDE America Movil, AT&T, China Mobile, Ericsson, Facebook,
More informationLiebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets
Liebert DM High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Emerson Network Power, a business of Emerson (NYSE: EMR), is a worldwide leader in infrastructure solutions across
More informationKeeping. Businesses Secure, Connected & Profitable
Keeping Businesses Secure, Connected & Profitable A HISTORY of DEDICATED SERVICE Founded in world-renowned data center One Wilshere, Los Angeles, PLTPRO has always offered first class products and services.
More informationGreen Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
More informationOvercoming the Challenges of Server Virtualisation
Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement
More informationData Center Optimization Services. Maximize Your Data Center
Data Center Optimization Services Maximize Your Data Center Energy savings was definitely the key driver in my decision to use the SmartAire dampers and DirectAire panels. - Larry Hood Senior Construction
More informationFt Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work
Ft Worth Data Center Power Metering for Real Time PUE Calculation Scope of Work Prepared for the General Services Administration By Lawrence Berkeley National Laboratory Rod Mahdavi December 13, 2010 Executive
More informationInternational 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase
International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations
More informationIBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling
IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and
More informationCyrusOne Case Study About CyrusOne
CyrusOne Case Study About CyrusOne CyrusOne is a world-renowned enterprise data center provider that offers 31 data centers across the U.S., Europe and Asia with a three million-plus square feet of total
More informationHow Huawei s Solutions Address the Challenges of Powering ICT Network
How Huawei s Solutions Address the Challenges of Powering ICT Network www.huawei.com Environmental Protection Digital Divide Supply Chain Employee Community Support Reducing environmental impact throughout
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationOptimizing Cooling Performance Of a Data Center
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationPartner Introduction
P R E S E N T S Partner Introduction September 16, 2013 Today s Agenda The Market Opportunity The Cooling Capacity Factor (CCF) New service Benefits to Upsite Partners How to Sell Launch Plan & Support
More informationThe End of Redundancy. Alan Wood Sun Microsystems May 8, 2009
The End of Redundancy Alan Wood Sun Microsystems May 8, 2009 Growing Demand, Shrinking Resources By 2008, 50% of current data centers will have insufficient power and cooling capacity to meet the demands
More informationAirflow Management s Role in Data Center Cooling Capacity
Airflow Management s Role in Data Center Cooling Capacity By Larry Mainers, CEO Subzero Engineering 2014 Subzero Engineering SUMMARY Airflow management (AFM) is changing the way data centers cool the IT
More information84 kw, Tier 3, Direct Expansion, 937 ft 2
[Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density
More informationCost Model Energy Benefits DirectAire & SmartAire Overview & Explanation
Cost Model Energy Benefits DirectAire & SmartAire Overview & Explanation A cost model (See figure 1) has been created to provide the user a simplified method for directly comparing the energy cost of a
More informationIs Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP
Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect
More informationbrightsolid Data Hall 1 Keysource Technical Specifications
brightsolid Data Hall 1 Keysource Technical Specifications Page 1 Introduction A Data Centre is a highly controlled environment that provides IT to external organisations seeking to outsource their requirements
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationDigital Transformation by Global ICT Infrastructure
Digital Transformation by Global ICT Infrastructure Hajime MIYAZAKI Vice President & COO, Country Director (Cambodia, Laos, Myanmar) NTT Communications Thailand 1 NTT Group Regional Communication ICT solutions
More informationIndustrial Energy Efficiency
ABB Global Consulting, APW 2011, Orlando Industrial Energy Efficiency Metals Industry Case Study April 19, 2011 Slide 1 Introduction ABB Global Consulting Products Capability Industrial Energy Efficiency
More informationDATA CENTER MEETING ALL POWER REQUIREMENTS IN THE DATA CENTER
DATA CENTER MEETING ALL POWER REQUIREMENTS IN THE DATA CENTER DO YOU HAVE THE POWER TO GROW YOUR DATA CENTER BUSINESS? Data center operation is a no compromise business. Customers are buying peace-of-mind
More informationServer Room & Data Centre Energy Efficiency. Technology Paper 003
Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:
More informationin ICT Prof. Dr.-Ing. Wolfgang Nebel OFFIS Institute for Information Technology
Energy Efficiency i in ICT Page 1 Energy Consumption, Climate Protection, Costs Power Consumption of ICT (End Devices and Infrastructure) in Germany (Source: Cremer et al. 2003) 2001: 38 TWh (8% of power
More informationEnergy Efficiency Guidelines
NTT Group Energy Efficiency Guidelines Version 6 April 2015 revision Revision History Version Enacted/revised Date Changes Version 1.0 Initial version Apr. 2010 Version 1.1 Revised Dec. 2010 Changes to
More informationYour data center s hidden source of revenue
WHITEPAPER Your data center s hidden source of revenue Harvesting heat from data centers with Low Speed Ventilation server coolers February 2016 Contents 1. Introduction...2 2. Challenges...3 3. Heat harvesting
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationPower Monitoring in the Data Centre
Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags
More informationWHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net
WHAT IS THE DIGI-RTU The Digi-RTU is a Heating, Ventilation, and Air Conditioning (HVAC) rooftop unit control kit that is both a demand management and energy usage device. It is designed to improve the
More informationPEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers
TM PEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds, and services mission critical technologies that
More informationAT&T Enterprise Hosting Services
AT&T Enterprise Hosting Services Irvine, CA Internet Data Center Last Update: 09.25.2008 2008 AT&T Intellectual Property. All rights reserved. AT&T and the AT&T logo are trademarks of AT&T Intellectual
More informationBSRIA Air Conditioning Worldwide Market Intelligence
2013 BSRIA Air Conditioning Worldwide Market Intelligence Over 25 years experience researching key markets worldwide market intelligence in 94 Countries integrated technical and market expertise management
More informationThe ETNO CORE Energy Task Force
ETSI Workshop on Environmental Impact Assessment and Energy Efficiency Athens, October 7 th 8 th 2013 The ETNO CORE Energy Task Force Goals and main activities Gianluca Griffa ETNO CORE ETF Chairman gianluca.griffa@telecomitalia.it
More informationDATA CENTER COLOCATION BUILD VS. BUY
DATA CENTER COLOCATION BUILD VS. BUY Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for
More informationWIRELESS ENVIRONMENTAL MONITORS
Packet Powers compact wireless Environmental Monitors makes it easy and affordable to monitor all environmental conditions in your facility. From installation to monitoring in minutes 1 Place wireless
More informationCisco Lab Setpoint Increase. Energy Efficient Data Center Demonstration Project
Cisco Lab Setpoint Increase Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify key technology, policy and
More informationECOBAY: Closed loop water cooled server cabinet for data centers
ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical
More information