SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM (SCADA)

Similar documents
Master Hub Ethernet Switch (MHES)

TECHNICAL SPECIAL PROVISION FOR. ITS Automatic Vehicle Identification System (AVI): Financial Project ID:

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

SECTION SURGE PROTECTIVE DEVICES

1510 MOTOR CONTROLLERS

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD)

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM

E1 Plus Electronic Overload Relay

4300 WINDFERN RD #100 - HOUSTON TX VOICE (713) FAX (713) web: IMPORTANT!!!

ITS DEVICE INTEGRATION AND TESTING

4300 WINDFERN RD #100 HOUSTON TX VOICE (713) FAX (713) web: IMPORTANT!!!

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR MICROWAVE VEHICLE DETECTION SYSTEM

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

SPECIAL SPECIFICATION 8939 Retrofit Existing Fiber Optic Dynamic Message Sign System to LED

SPECIAL SPECIFICATION 6230 Fiber Optic RS-232 Data Modem

E2EY. A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Aluminum-detecting Proximity Sensor

SPECIAL SPECIFICATION 8143 Wireless Ethernet Radio System

SECTION ELECTRIC METERING

SPECIAL SPECIFICATION 6518 IP Video Codec

ITS DEVICE INTEGRATION AND TESTING

SECTION ( ) LIGHTING CONTROL PANELBOARD

TECHNICAL SPECIAL PROVISION FOR. Network Devices: Financial Project ID: ORANGE COUNTY & SEMINOLE COUNTY

PIMA COUNTY REGIONAL WASTEWATER RECLAMATION DEPARTMENT SCADA STANDARDIZATION PROJECT TABLE OF CONTENTS

X-12s Users Manual. X-12s User Manual Revisions Revision Description Initial release. Xytronix Research & Design, Inc.

PDI Modular Compact Remote Power Panel

Connecting a Cisco Output Module

STATUS Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

*REQUIRED* 169 Main Street 700 Plaza Middlesex Middletown, CT T: F:

Total Protection Solutions Surge Protective Devices SurgeTrack Series: 080, 120, 160, 240, 300 and 400

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4.

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

SECTION MODEL 2577 INDOOR SCOREBOARD. A. Single-face electronic scoreboard and control console for indoor use.

SVP110 SURGE VOLTAGE PROTECTOR INSTRUCTION MANUAL

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION PROGRAMMABLE LOGIC CONTROLLER (PLC)

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

SPECIAL SPECIFICATION 6322 Digital Video Encoder/Decoder (Ethernet) System

Power Meter PowerMonitor 500

IF-80x Outdoor Terminal

E2KQ-X. Fluororesin-coated Capacitive Sensor with Sensitivity Adjuster. Chemical-resistant Proximity Sensor. Ordering Information

Global Water Instrumentation, Inc.

SECTION MODEL INDOOR SCOREBOARD. A. Four-face electronic scoreboard and control console for indoor use.

Sensing method Appearance Connection method Sensing distance Model. Pre-wired (2 m) Power supply Application Appearance Function Model

RE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

G3B/G3BD. Model Number Structure. Ordering Information. Solid State Relays Model Number Legend. List of Models

SECTION VARIABLE FREQUENCY DRIVES

Ordering Information. I/O Relay G7T. Model Number Legend Slim-styled I/O Relay Saves Space in Panel

The Next-generation Sensor Networking Units That Revolutionize the Workplace from Introduction and Startup though Operation. Fiber Units.

Power Supply (48Vdc, 2.5A)

LCI User Manual mantracourt.com

SPECIAL SPECIFICATION 8885 Wireless Ethernet Radio (Backhaul) Link

Installation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment

SECTION FARE COLLECTION SYSTEM

MAXIMA + Series ROTARY LEVEL CONTROL

G3FM. Model Number Structure. Ordering Information. Solid State Relays. Model Number Legend. List of Models

PowerFlex 400 AC Drive Guide Specification

LINCOLN AUTHORIZED SERVICE FACILITY (LASF) SERVICE CODE TERMS & CONDITIONS

AirTest Model CN9000 Series Sensor Controller

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M

Connecting a Cisco Input Module

X-11s Users Manual. X-11s User Manual Revisions Revision Description Initial release. Xytronix Research & Design, Inc.

Basketball Shot Clock Set LX2180 Manual

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console

MAXIMA + Series ROTARY LEVEL CONTROL

OZONE SWITCH Model OS-6. OS-6 Features

SPECIAL SPECIFICATION 6146 Fiber Optic RS-232 Data Modem

LCI Load Cell Junction Box with Fault Monitor

SPECIAL SPECIFICATION 7443 Radar Vehicle Sensing Device (RVSD) System Maintenance

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual

G3NE. Model Number Structure. Solid State Relays. Model Number Legend. Compact, Low-cost, SSR Switching 5 to 20 A

S82S (3/7.5-W Models)

SAVE THESE INSTRUCTIONS

TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT

Model Number Structure

High Voltage DC Meter

Aluminum Excellent Performance, with Aluminum Chip Immunity! The indicator is visible from any direction.

Name No. of I/O points Model Safety inputs: 12, test outputs: 4

SPECIAL SPECIFICATION 1303 Lifelink

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Installation, Operation and Maintenance Manual

212iL Rev. 1.1

I/O Expansion Box Installation & Operator s Instruction Manual

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

E3Z-G. Photoelectric Sensor with Grooved Design and Easy Settings. Grooved-type Photoelectric Sensor with Built-in Amplifier. Ordering Information

Solid State Relays with Failure Detection Function

SPECIAL SPECIFICATION 6838 Wireless Ethernet Microwave Radio

Sync Control for Eaton 9395P and 93PM User s and Installation Guide

FBT-10. Fieldbus Commissioning Box. User Manual FBT-10 User Manual Rev A.0

E2EC. Subminiature Sensors with Long-distance Detection. Cable Amplifier Proximity Sensor. Ordering Information

SECTION MICROPROCESSORS

CK3W-PD048 CSM_CK3W-PD048_DS_E_DITA_1_2

X-18s Users Manual. X-18s User Manual Revisions Revision Description Initial release. Xytronix Research & Design, Inc.

HIGH-VOLTAGE DC METER

MAXIMA+ Series Rotary Level Indicator

Transcription:

TECHNICAL SPECIAL PROVISION FOR SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM (SCADA) FINANCIAL PROJECT NO.: 428213-2-52-02 MARION COUNTY The official record of this Technical Special Provision is the electronic file signed and sealed under rule 61G 15-23.003, F.A.C. PREPARED BY: Robert Mastascusa, P.E Fla. License No. 66600 Certificate of Authorization No. 2294 Metric Engineering 615 Crescent Executive Court Suite 524 Lake Mary, Florida 32746 Date: 03/31/2015 Page 1 of 7

T0000500 SUPERVISORY CONTROL AND DATA ACQUISITION (SCADA) SYSTEM T0000500-1 Description. Furnish and install Supervisory Control and Data Acquisition (SCADA) in accordance with the Contract Documents. The SCADA Control Panel will use IEEE 802.3u, 100 Mbps, Fast Ethernet protocol to communicate with the Department s Ethernet network. Voltage/Current Analog sensors, monitors, and position indicating contacts will be installed to provide inputs to the SCADA system. The remote sensors, monitors and components will be connected to the SCADA system with power and communication cables labeled and stored neatly in raceways to form a complete system. Some equipment, such as cabinet door switches, will send information indirectly to the SCADA system. A technician from the Department will load the final programming at the primary SCADA control panel necessary for final acceptance and commissioning tests. T0000500-2 Materials. Furnish all labor and materials necessary to provide, install, and test a Supervisory Control and Data Acquisition (SCADA) System in each local hub cabinet and master hub building. Refer to the Supervisory Control and Data Acquisition Details in the ITS Plans. A SCADA system to monitor various parameters and conditions associated with the ITS equipment and electrical distribution system to be installed at each location will include at a minimum but not be limited to the following components listed in Table 1: Table 1 QUANTITY PART NUMBER DESCRIPTION 1 OTB1E0DM9LP TCP/IP Network Interface Module 1 TM2AMM6HT Analog Expansion (Analog 4 In, 2 Out) 2 H921 Veris Current Sensor (4-20mA output) 2 RMCV60BD Voltage/Current Analog Converter 6 RXZE2S108M Relay Socket (Spares to be provided to Department) 6 RXM2AB2BD 24 VDC Relay rated for 12 A / 250 VAC All ancillary items required for a fully operational SCADA system including but not limited to connectors, wires (colored per plans), wireway (cable management ducts), VDC terminal block, Grounding terminal block, fuse block, fuse(s) as required. Page 2 of 7

Provide a SCADA power supply Module (Sola SDN 10-24-100C or Equivalent). The SCADA power supply module shall include a 24 VDC power supply module to power SCADA system components as well as other DC powered ITS devices per plans, and shall have the following specifications: Input voltage range of 115 230 VAC, Output voltage of 24 VDC (23.5 VDC Min. to 28.5 VDC Max.), Operating Temperature range of -25 Celsius to +60 Celsius, Weight of 1.1 pounds or less, Din Rail mountable (Din Rail included), Internally fused, and a 5-Year limited Warranty. T0000500-3 Component Input/Output Parameters. T0000500-3.1 Analog Inputs. The SCADA system shall be capable of receiving up to four Analog Inputs At all local hub cabinet installations, the incoming utility power voltage and current will be monitored between the primary surge protection device and the UPS, by a RMCV60BD Voltage/Current Analog Converter and a H921 Veris Current Sensor (4-20mA output). At all local hub cabinet installations, the UPS output power voltage and current will be monitored between after the UPS, by a RMCV60BD Voltage/Current Analog Converter and a H921 Veris Current Sensor (4-20mA output). T0000500-3.2 Digital Inputs. The SCADA system shall be capable of receiving up to twelve Digital Inputs. The door positions on the local hub cabinet doors (front and back) will be monitored by door position dry contact tamper switches. The door tamper switches contacts will be open when the door(s) are open and closed when the door(s) are closed. The position of the UPS external maintenance bypass switch will be monitored using factory installed dry contacts to indicate the switch position. The alarm contact on the surge suppression devices at each local hub cabinet shall be monitored by the SCADA system. T0000500-3.3 Digital Outputs. The SCADA system shall be capable of sending up to eight Digital Outputs. Digital Outputs shall be wired to the Relay Sockets to be installed for the CCTV Power, Device Server power, MVDS power, and Media Converter power. T0000500-3.4 Power Input/Outputs. The SCADA system will utilize the 120 VAC power circuit powering the local hub cabinet and all of its components. This 120 VAC circuit will feed the 24 VDC power converter which will feed the SCADA devices as required. T0000500-4 Environmental Specifications. T0000500-4.1 Ambient Temperature. The SCADA system shall have a minimum operating temperature range of 0 C to +60 C and a storage temperature of 0 C to +60 C. Page 3 of 7

T0000500-4.2 Relative Humidity. The SCADA system shall have a minimum operating relative humidity range of 10 to 95% non-condensing, and a storage temperature of 10 to 95% noncondensing. T0000500-5 Shop Drawings. Shop drawings shall be submitted for the SCADA system. The SCADA system shop drawings shall include hardware product information including, but not be limited to catalog cut sheets, data sheets, performance surveys, test reports, equipment lists, material list, diagrams, pictures, and descriptive material. The product information shall cover all items including mechanical devices, mounting components, wiring, terminal strips, connectors, accessories, and spare parts. The submittal information shall show the standard and optional product features, as well as all performance data and specifications. Prior to commencement of manufacture (or shipment for stock items), the SCADA System Provider shall submit for review product information for all equipment and material specified in this Section. Include specification sheets on each remote sensor, power meter, or interface card that will communicate or provide status to the SCADA system. T0000500-6 Quality Assurance. The SCADA Control Panel Integrator minimum qualifications include a minimum of ten years of experience in the design, manufacture, testing, or installation of solidstate PLC systems. Before shipment, the manufacturer fully and completely tests the system to assure compliance with the specifications. T0000500-7 Product and Product Fabrication. Products submitted other than listed part numbers are the responsibility of the contractor for system integration and revised PLC programming to make any substitute product integrate into the SCADA system. All materials and components making up the SCADA system will be new, of current design, and not in prior service except as required during factory testing. The SCADA system will be constructed of replaceable subassemblies. Products submitted other than listed part numbers are the responsibility of the contractor for system integration and revised PLC programming to make any substitute product integrate into the SCADA system. T0000500-8 Wiring. Wiring practices, materials, and coding will be in accordance with the requirements of the National Electrical Code (NFPA 70) and the National Electrical Page 4 of 7

Manufacturer Association. Cables with shields and/or drain wires will have the shield and/or drain wire grounded at the SCADA control panel end only. Each cable or conductor installed for the SCADA system will be field labeled at both ends of the cable or conductor. Labels will be installed within 6 inches of the ends of each cable or conductor. Ensure the labels are self-laminating and the label material is vinyl with white matte finish and black 12 point text that is heat and solvent resistant. Contact the TSM&O Engineering Department for wire naming conventions and label syntax. Wiring inside the SCADA control cabinet will be routed through proposed cable management ducts. The white wiring ducts will have removable covers. The wiring duct will be equal to Panduit, Type G wide finger wiring duct. T0000500-9 Location. The SCADA system shall be installed with the local hub or master hub as detailed in the ITS plans. T0000500-10 Network Connection. The SCADA system shall be connected to the Local Hub Ethernet Switch or the Master Hub Ethernet Switch. The Ethernet switches are to be paid for separately. T0000500-11 Contractor Field Services and Department Provided Services. T0000500-11.1 Contractor Provided Field Services. The contractor shall install, inspect, and test the SCADA installation before notifying the Department that the SCADA system is ready to be programmed. All inspections and test procedures shall be performed by trained field service personnel during the SCADA system start-up and commissioning. Visually inspect the installation to ensure the equipment shows no signs of shipping or installation damage. Visually verify the completed installation has been installed per the plans and detail drawings. Visually inspect the installation to ensure that all I/O modules are correctly fitted, all power supply modules are correctly fitted, and all terminal screws, nuts, and/or spade lugs for tightness. Mechanical Inspections shall include the verification that all I/O modules are correctly fitted, all power supply modules are correctly fitted, and all terminal screws, nuts, and/or spade lugs for tightness. Electrical Inspections shall include the verification that SCADA system control panel is energized at each local hub, and that the input and output voltages for all SCADA system related components are within tolerance. Confirm the Remote I/O is connected to the local area network. Confirm each remote sensor, meter, and interface card is functioning correctly. Page 5 of 7

T0000500-11.2 Department Provided Services. The Department will provide and install the back end SCADA hardware to be installed at the Traffic Management Center and the software program for the SCADA system PLC. Upon Contractor completion of all Contractor required field services in this section, notify the Department 4 weeks prior to proposed testing date, which includes 14 days for the Department to install and test the PLC program. T0000500-12 Replacement Part Stocking and Availability. Replacement parts shall be available through a local distributor within 100 miles of the job site. All SCADA parts and materials will be available 24 hours a day, 7 days a week, 365 days a year from a local distributor. Include the local distributors name on the shop drawings. T0000500-13 Test and Performance Verification. The completed SCADA system will be operationally tested in accordance with the following requirements. Verify capability to remotely power off all ITS devices connected to Relay each Socket. Verify capability to remotely power on all ITS devices connected to Relay Sockets. Verify receipt of accurate current readings from both Analog Current Sensors. Verify receipt of accurate voltage readings from both Analog Voltage Sensors. Verify digital inputs trigger alarms when Front Door Opens, Rear Door Opens, UPS set to bypass, and Surge Protection Device (SPD) trips. T0000500-14 Warranty. The manufacturer will warranty all components against defects in materials and workmanship for five years from the date of final acceptance by the Engineer. The warranty will cover all parts and onsite labor required for troubleshooting and repair. Contractor hereby assigns to the Department any and all manufacturers' or other sellers' warranties that come with any products, material or supplies which are incorporated into or are consumed in the project in any way. To the extent that any such warranties do not extend to subsequent purchasers or owners or such warranties contain a limitation on assignment, Contractor agrees that Contractor purchased the products, materials and supplies on behalf of the Department with the intent that the Department be the intended recipient of any warranties. All documents associated with or describing any such warranties shall be delivered to the Department along with the other project final acceptance documents and shall be deemed to be a part of the required final acceptance documentation. Contractor shall not take any action or fail to act in any way which voids any such warranties. All subcontracts shall contain a similar provision which requires subcontractors to assign any such warranties to the Department. Page 6 of 7

T0000500-15 Method of Measurement. The Contract unit price for each SCADA system furnished and installed, will include furnishing, placement, and testing of all equipment and materials, and for all tools, labor, hardware, supplies, support, personnel training, shop drawings, documentation, and incidentals necessary to complete the work. T0000500-16 Basis of Payment. Price and payment will be full compensation for all work specified in this Technical Special Provision. Payment will be made under: Item No. 0000500-1 SCADA System-assembly. Page 7 of 7