1SDH001103R0001. Settings conversion from ATS010 to ATS022. User Manual. Technical guide ABB. Power and productivity for a better world TM

Similar documents
SACE PR010/T test unit annex RH SACE PR010/T ABB SACE 1/20 L0876

White Paper. Emax 2, all-in-one innovation Embedded ATS system

White paper - Preliminary. Emax 2, all-in-one innovation Interface Protection System and Interface Device

Iso DIN. User Manual. 1 channel Earth Fault Monitoring

Control instruments GUARDIAN 2 - GUARDIAN 3

Please comply with all warnings and operating. instructions in this manual strictly. Save this. manual properly and read carefully the following

HAT160 ATS CONTROLLER USER MANUAL

NPW800R RETROFITTING. Power and Volatge Protection Relay

Installation & Operation and Maintenance

Spec Sheet: Zenith ZXS (ZTX) Transfer switch

SIGMA. Advanced Generator Protection and Control. Short Form Catalogue

SIL-A. Overcurrent and Earth Fault Relay for Primary and Secondary Distribution. Main characteristics

Specification Voltage Limiting Device

M2500 Engine Controller Configuration Manual

Quick Start Guide TS A

User s Manual E-Clipse Bypass Configurations (BCR, BDR, VCR, or VDR) for ACH550 Drives (1 400 HP)

Technology Security Low consumption

TSC 80 TRANSFER SWITCH CONTROLLER INSTALLATION, OPERATING & SERVICE MANUAL

02/11/2015

ABB LVP&S Training AC500 to EMAX Modbus RTU ABB Automation Technologies

AN004 Using the PMDX-126 s Error Input and Restart Output with Geckodrive Servo Drivers and Mach3 CNC Software

Other standard features include current and voltage monitoring, overvoltage, overtemperature as well as short circuit protection.

MRI1-IU - Voltage controlled time overcurrent relay

User Guide Automatic Transfer Switch (ATS)

SD-Pocket User Manual

HAT162 ATS CONTROLLER USER MANUAL

Emax X1-Tmax T7-Tmax T8

251 Nuthatch Court Three Bridges, New Jersey Office: Fax: USER S MANUAL

DCN0114 ATS Remote Annunciator Operation Manual. Automatic Transfer Switch Annunciator. Operation Manual. DCN0114 Rev 1

SmartVFD Frame 8 Wiring Diagrams and Dimensional Drawings

Innovation on Medium Voltage Switchgear

Remote communication options include IEC Ethernet communications or Modbus (RS485).

Chloride CROSS Rack 16 A, 32 A and 63 A

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics

Air & Moulded Case Circuit Breaker Service & Maintenance

Obsolete. BR Series USB Tech Kit. B l u e R i d g e. T e c h n o l o g i e s. User Guide. Page 1. Hardware and Software Instructions

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

ADXL Series SIMPLE, EFFICIENT AND SAFE MOTOR CONTROL

Model: KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

SACE Emax 2 Specification guide

ATS Automatic transfer switches Advanced version

ES3 OP - EUROSTEP3 for ac power supply input

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Bus communication with ABB circuit-breakers

ATS CONTROLLER [ ACD-III ], [ ACD-III-C ] User s Manual. O-Sung Electric Machinery Co., Ltd.

General introduction Part 2, chapter 11

Protection System Simulator SIM600. Installation Manual

Alberto Carini, LPLS Italy, June 2013 MNS is The Intelligent MCC. ABB Group June 21, 2013 Slide 1

Manual. Water Vend Controller Model ESDI WARNING! ELECTRICAL SHOCK HAZARD! AUTHORIZED PERSONNEL ONLY. EXPOSED 120 VAC ON CIRCUIT BOARD

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

Automatic Transfer Switch OTM_C_20D. Installation and Operation Instructions

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

User manual. TRIOU(Temperature Remote I/O Unit) Before using the product, be sure to read Safety Cautions, and use exactly as described.

General characteristics of C-type relay modules

M-5072 Retrofit Kit For M-4272 Digital Motor Bus Transfer System

Quick Start Guide TS 870 ATS

Wiring Instructions for Replacement of 2301A Load Sharing and Speed Controls with 2301D Load Sharing and Speed Controls

ADDENDUM TO IB17555D INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE OF THE CUTLER-HAMMER DIGITRIP 3000 SERIES OF PROTECTIVE RELAYS

Busbar protection REB 670

CDW7. Standard: IEC Application. Standard and certification. International standard: IEC Approved certification: CB, CE, KEMA

HAT560NC SERIES (HAT560NC /HAT560NBC) ATS CONTROLLER USER MANUAL

[ ACD-NA ] User s Manual. O-Sung Electric Machinery Co., Ltd. 136, Hataemal-gil, Wollong-Myeon Paju-si, Gyeonggi-do, Korea

Power Factor Controller

1 Extended and Advanced Cascade Controller Option 3

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

User Manual SolarTracker

PACSystems RX3i and Series IC694MDL916 and IC693MDL916 Output Module, Isolated Relay, N.O., 4 Amp, 16 Point

DOCUMENTATION CONTENTS

32MP Gateway. Overview and Configuration Manual

Welcome to the safety functions configuration training module for ACS880 Cabinet-built industrial drives.

Configuration and Interoperability Guide for IEC for the SEL-751 Feeder Protection Relay. July 10, 2015

ABB Data Center Forum 2017

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

APC Next Generation Rack ATS

SIGMA D++ / SIGMA D+ / SIGMA D Directional Fault Indicator

GE Zenith ZDEC Modular Paralleling Switchgear

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

ac wave 2 supply ( analog device )

Product Discontinuation Notices. Discontinuation Notice of open-circuit time delay relay RD2P-30

ES 4000 STANDARD. 1 General information Document Overview General description Introduction... 4

Applications & Tools. Safe switching of the motor starters 3RM10 and 3RM12. SIRIUS Safety. FAQ February Answers for industry.

Keor HPE UPS THREE-PHASE UPS. from 60 to 200 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

FLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS FOR PLUG FANS. POWER RANGE IS FROM 0,8 KW TO 15 KW.

OVERCURRENT / GROUND FAULT PROTECTION RELAY MPRB GF. (Code ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

ATS CONTROLLER OPERATING MANUAL

EP010. Modbus/FBP Interface

MNS Platform, low voltage systems Rear Access Power Motor Control Center. Alberto Carini, Global Product Manager

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

Redline. Extensions. Display contacts. Function S. Display contact CA. Function. Add-on Devices T3.2

Distribution Management System Open++ Opera v.3.3. User Manual

Instruction manual 1/52 LB-DTEA L9249. Author Autore. Title. ENG Titolo PR223DS Modbus System Interface Doc. No N. Doc. 1SDH000658R0001 Tot. Pag.

Operator's manual 4000 Instrumentation en-gb Issue 1.0

Protection relays.

Switching module for AC V and up to three load stages, with manual switching

Automatic transfer switches. TruONE ATS, OX_ _. 34OX_ rev. A / 1SCC303011M0201. Automatic transfer switches

FP5000. Refer to for the latest information on this constantly evolving product

100% electricity. Automatic transfer switch controllers ATL series

1/ 58 LB-PA L0440. Lang. Lingua Title Titolo PR112/PD-M Modbus System Interface. Author Autore. Doc. Type Tipo Doc. Approv. Approv.

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

Transcription:

Settings conversion from ATS010 to ATS022 User Manual Settings conversion from ATS010 to ATS022 Settings conversion from ATS010 to ATS022 Technical guide Power and productivity for a better world TM ABB

INDEX 1 Preliminary Operations... 3 1.1 ATS010 features not available with ATS022... 3 2 Settings configuration during retrofitting from ATS010 to ATS022... 5 2.1 Selection mode... 5 2.2 Voltage... 6 2.3 Frequency... 6 2.4 Other Settings... 7 2.5 Times Delay... 7 2.5.1 Switching procedure comparison between ATS010 and ATS022... 8 2.6 Operating mode selection... 9 3 ANNEX A... 10 2/10

1 Preliminary Operations Retrofitting activity allows the substitution of an obsolete device, without altering in any manner the data of original project of the existing switchgear. It is customer's responsibility to verify correspondence of functions supplied by the new ATS022 and to check if these functions are sufficient to comply with the original certification of the switchgear. 1.1 ATS010 features not available with ATS022 a) Switch Logic Strategy 1 is no more available. ATS022 behaves according only to strategy 2. b) Digital Inputs ATS010 had capabilities to be connected simultaneously up to 3 different digital inputs: SW ABLE (pin 5), G AUTO (pin 6), RESET (pin 48). ATS022 have only a single DI, which function could be programmed by the customer: DI10 (pin X32:2); The mentioned functions are in alternative, and defined as described below: SW ABLE G AUTO RESET Hardware connection existing as default. pin 5 of ATS010 to X32:2 of ATS022 (DI10) Please enable this function via sw by using main menu. Please contact ABB in case needed. This function is in alternative to sw enable. Hardware connection must be changed: please remove cable from pin 5 of ATS010 and connect it to pin 48 of ATS010. No changes over ATS022 pin X32:2. Please enable this function via sw by using main menu. The meaning of this function is partially different from ATS010 and ATS022: With ATS010, while switching this contact were generated two effects, reset of active alarms and operating logic change AUTO/MAN; With ATS022, this input only affects the reset of active alarms but there is no effect over operating logic. c) Digital outputs ALARM Hardware connection existing as default. pins 49 50 of ATS010 and pins X29:7 X29:1 of ATS022 (DO6). Activation of this contact keep the same logical behavior of ATS010, even if the hardware configuration of ATS022 contact is NO. NPL LOADS The meaning of this function is partially different from ATS010 and ATS022: With ATS022 it is mandatory to connect the CB status of CB3 (open/close) to DI11 pin X32:1 and common to pin X32:9. CB3 is dedicated to control not priority loads. Please enable this function via sw by using main menu: 3CBsNPL. If there is need to control CB3 only at opening, please select 3CBsNPL opening. If there is need to control CB3 at opening and closing, please select 3CBsNPL opening & closing, and it is necessary to use external relays according to following table. In case of need, please contact ABB. 3/10

REMINDER: Please take note of the existing settings of the ATS010 following table at ANNEX A before to uninstall the device. Refer to the instructions manual 1SDH001059R0001 in order to be able to uninstall ATS010 and to install mechanically and electrically new ATS022. Please follow ATS022 standard instruction manual, in order to configure properly the unit settings and protection functions. Figure 1. Functional mode, thresholds and parameters selection of ATS010 4/10

2 Settings configuration during retrofitting from ATS010 to ATS022 REMINDER: ATS010 controls two power supply lines: the first supplies normal power from the net, the second from a gen set. These two power supply lines are connected to the same busbar system through two CBs controlled by the ATS010. The ATS010 only monitors one phase of the three phases of the emergency line. WARNING: While configuring settings and parameters of ATS022, please put the device in manual mode and follow the instructions written in the ATS022 user manual 1SDH001059R0001 (paragraph 5.5.2 ). Make sure the device is powered by an auxiliary voltage or by a voltage present on at least one of the two main lines (normal or emergency). 2.1 Selection mode REMINDER: With ATS022, to access to main menu: Press Enter to access the main Menu. Insert a 4-digit password which must be entered using the UP DOWN and TER keys [default password: 0001]. To confirm all settings (whenever user wants to come out menu): 1. Press ESC key until will appear a window with request to confirm modification saving. 2. Confirm with TER. WARNING: Please contact ABB SACE experts if ATS010 was installed in a customized solution, that differs from the one described in the table below. PARAMETER Selection Mode 1. On menu, select: System Configuration set Protection devices : 2CBs set Utilization of Generator : Generator in use set Line priority : Line LN1 set Switching : with inverse procedure 2. Select setting with UP DOWN key, and confirm with TER. 5/10

2.2 Voltage WARNING: Max rated voltage of ATS022 is 480Vac; for higher values must be used an external voltage transformers. For details see user manual 1SDH001059R0001 PARAMETER Voltage Threshold 1. Select: Configuration Voltage thresholds Min voltage threshold 2. Select setting with UP DOWN key, and confirm with TER. PARAMETER Rated Voltage 1. Press Enter to access the main Menu. 2. Insert a 4 digit password which must be entered using the UP DOWN and TER keys 3. Select: System Configuration Rated voltage 4. Select setting with UP DOWN key, and confirm with TER. 5. Press ESC key until will appear confirm request window. 2.3 Frequency PARAMETER Frequency threshold +/ 10% as default 1. Press Enter to access the main Menu. 2. Insert a 4 digit password which must be entered using the UP DOWN and TER keys 3. Select: Configuration Frequency thresholds Min Frequency threshold 4. Select setting with UP DOWN key, and confirm with TER. 5. Press ESC key until will appear confirm request window. PARAMETER Rated Frequency 1. Press Enter to access the main Menu. 2. Insert a 4 digit password which must be entered using the UP DOWN and TER keys 3. Select: System Configuration Rated frequency 4. Select setting with UP DOWN key, and confirm with TER. 5. Press ESC key until will appear confirm request window. 6/10

2.4 Other Settings PARAMETER Plant configuration PARAMETER Strategy 1. Press Enter to access the main Menu. 2. Insert a 4 digit password which must be entered using the UP DOWN and TER keys 3. Select: System Configuration Number of phases LN1 and Number of phases LN2 4. Select setting with UP DOWN key, and confirm with TER. 5. Press ESC key until will appear confirm request window. ATS022 always operates according to strategy 2 mode regardless where the breakers motors are powered from 2.5 Times Delay PARAMETER Delay settings 1. Select: Configuration Delay Times Delay Ts 2. Select setting with UP DOWN key, and confirm with TER. T1: delay between fault detection and opening of CB over the standard line Ts (ATS022 configured without generator): opening delay of standard CB, after fault detection in standard line. 1. Select: Configuration Delay Times Delay Ts 2. Select setting with UP DOWN key, and confirm with TER. T2: delay between fault detection and gen set startup T3: delay between opening of circuit breaker over the emergency line and gen set stop T4: delay between standard line voltage is back and inverse switching sequence is activated Ts (ATS022 configured with generator): Generator start delay, after fault detection in standard line. 1. Select: Configuration Delay Times Delay TG off 2. Select setting with UP DOWN key, and confirm with TER. TG Off: generator switching off delay after closure of standard line CB 1. Select: Configuration Delay Times Delay Tbs 2. Select setting with UP DOWN key, and confirm with TER. 3. Select: Configuration Delay Times Delay Tcn 4. Select setting with UP DOWN key, and confirm with TER. Tbs: opening delay of emergency line CB, after detection of stabilized voltage on standard line. Tcn: closing delay of standard line CB after opening of emergency line CB 1. Select: Configuration Delay Times Delay TCE 2. Select setting with UP DOWN key, and confirm with TER. T5: Delay for Emergency voltage stabilization after gen set started Tce: closing delay of emergency line CB, after detection of stabilized voltage on emergency line 7/10

2.5.1 Switching procedure comparison between ATS010 and ATS022 WARNING: Management of the switching procedure of ATS022 can be identified as Strategy 2 operating mode of ATS010; before to control the breakers, ATS022 waits availability of voltage on the emergency line regardless of the feeding mode of motors and electrical auxiliaries inside the breakers. Following graphs compare the switching procedure of ATS010 and ATS022 ATS010 ATS022 8/10

2.6 Operating mode selection PARAMETER Functioning selection TEST AUTOMATIC 1. Check if Generator is set in use from the menu on the display 2. Set the ATS022 in manual mode Follow indication of 1SDH001059R0001, par. 5.7 Test Modes 3. Keep the TEST key pressed for at least 3 seconds 4. On releasing the TEST key, all the LEDs, except Tx/Rx, flash simultaneously four times and then the Auto LED flashes at 0.5Hz; the graphic display shows the GT icon. 5. Press TEST; generator starts 6. Press TEST; generator stops Follow indication of 1SDH001059R0001, par. 5.4.2 Automatic mode 1. Make sure the Power LED is On, see Figure 5.3/1 2. Press RESET once, see Figure 5.3/2. If the Auto LED is ON, the automatic transfer switch ATS022 is in Automatic mode, see Figure 5.3/3. 3. If the Auto LED is OFF, press RESET again, see Figure 5.3/3; the Auto LED switches to ON and the device is in Automatic mode/ Figure 5.3/4 NORMAL 1. Set the ATS022 in manual mode 2. Open CB2 pressing the CB2 key 3. Close CB1 pressing the CB1 key 4. Switch off the generator. Keeping RESET pressed, press CB2 NORMAL & EMERGCY OFF 1. Set the ATS022 in manual mode 2. Open CB2 pressing the CB2 key 3. Open CB1 pressing the CB1 key 4. Switch off the generator. Keeping RESET pressed, press CB2 G SET START 1. Set the ATS022 in manual mode 2. Open CB2 pressing the CB2 key 3. Open CB1 pressing the CB1 key 4. Switch on the generator. Keeping RESET pressed, press CB1 5. Close CB2 pressing the CB2 key EMERGCY ON 9/10

3 ANNEX A ATS010 existing settings Operating mode selection Description To record Actual value TEST It allows gen set startup in order to verify effective start with switching logic Active AUTOMATIC Switching logic Active NORMAL ON NORMAL & EMERGCY OFF Gen Set START EMERGCY ON Emergency line circuit breaker is opened and it is forced closing of the Normal line; generator is stopped and logic disabled Both Standard and Emergengy line circuit breakers are forced open. Useful for plant maintenance purpose Both the Normal and Emergency line circuit breakers are forced to open and the gen set start up command is disabled After Gen set start selection is done, both circuit breakers are kept open and the gen set is started up whether the line is powered or not Voltage level trimmers Description To record Atcual value Un max Maximum voltage limit trim Un min Minimum voltage limit trim Time delay switching settings Description To record Atcual value T1 Time delay between fault detection and opening of circuit breaker over the standard line T2 Time delay between fault detection and gen set startup T3 T4 Time delay between opening of circuit breaker over the emergency line and gen set stop Time delay between standard line voltage is back and inverse switching sequence is activated T5 Delay for Emergency voltage stabilization after gen set started Dip switch selection Description To record Atcual value DIP 1 4 Nominal voltages definition DIP 5 Not used DIP 6 Distribution system definition DIP 7 Nominal Frequency definition DIP 8 Switching strategy definition 10/10