FLORIDA STATE UNIVERSITY PURCHASING DEPARTMENT A1400 UNIVERSITY CENTER TALLAHASSEE FL ADDENDUM ACKNOWLEDGMENT FORM. DATE: February 15, 2006
|
|
- Prosper Gardner
- 5 years ago
- Views:
Transcription
1 FLORIDA STATE UNIVERSITY PURCHASING DEPARTMENT A1400 UNIVERSITY CENTER TALLAHASSEE FL ADDENDUM ACKNOWLEDGMENT FORM DATE: February 15, 2006 ADDENDUM NO. 2 our Competitive Solicitation Number K 5003-A TITLE: Disaster Recovery & Remote Backup Site Housing INSTRUCTIONS TO RESPONDERS: Attached is additional information pertaining to the Competitive Solicitation. Please read this information carefully and incorporate it into the terms, conditions and specifications submitted with the original solicitation and any prior addendum s. This cover sheet must be signed by the individual signing the solicitation and returned with this Competitive Solicitation.. CERTIFICATION: This is to certify that I did receive the referenced addendum and have incorporated the terms, conditions, and specifications listed therein into the attached Competitive Solicitation. SIGNED TITLE OF ABOVE NAME OF FIRM
2 HOSTED SITE SERVICES 1. What is your ideal dimension for your 200 SF and 600 SF suite (when it expands)? 10 ft. X 20 ft., initially; expandable in 10 ft. X 5 ft. increments. 2. Does FSU prefer hard wall or cage wall suite? No preference. 3. Does FSU prefer key locks or card reader at suite door? No preference. 4. Is FSU supplying the seven cabinets? Yes, but five cabinets initially. 5. Ideally, does FSU prefer that all these cabinets to be in a single row layout? Or does FSU prefer multiple rows? Single row with a gap between tape library and racks. 6. What are the dimensions (width, height, and depth) and weight of a single cabinet? See equipment specifications below. 7. Does FSU require overhead infrastructure (ladder racking) for power cable/circuits, copper data cables (cross-connects), and fiber optic cross connects? Overhead infrastructure is not required. Equipment of the type we plan to use is usually deployed in raised flooring environments. 8. Can the cabinet support overhead infrastructure? Yes. 9. How much power does each of the seven cabinets require? Please provide an itemized list that specifies the following requirements: a. Voltage (120V AC, 240V AC, or -48V DC) b. UPS or non-ups c. Amperage d. Number of power circuits at each cabinets e. AC power redundant (If multiple power circuits per cabinets) by identify primary and secondary power circuits. f. AC power diversity (If multiple power circuits per cabinets) g. Power Receptacle Type and Location h. Fuse Panel requirements See equipment specifications below.
3 10. Can FSU provide the equipment specification (type, function, dimensions, BTUs, etc.)? See equipment specifications below. 11. Does FSU require the need for remote hand services to service the FSU equipment within the suite? Remote hands service is not absolutely required. However, it's an option we'd like to consider EQUIPMENT SPECIFICATIONS: Cabinet #1: IBM 3584-L52 Automated Tape Library 28.5w, 59.8d, 70.9h, inches Min. weight, lbs; Max. weight, lbs Two (2) 208V/15A, single phase circuits with NEMA L6-15R receptacles. These circuits will need to be on UPS and diversely provisioned. KVA: 0.78 KBTUs: 2.57 Phone Line: 1 One (1) 120V/15A single phase circuit with a NEMA 5-15R receptacle. This circuit will need to be on UPS. (Remote Support) Cabinet #2: IBM 3584-D52 Tape Library Expansion Frame 28.5w, 59.8d, 70.9h, inches Min. weight, 784 lbs; Max. weight, lb None KVA: 0.00 KBTUs: 0.00 Phone Line: None Rack #1: IBM 7014-T42 Equipment Rack 24.5w, 43.3d, 79.3h, inches
4 Min. weight, 575 lbs; Max. weight, 2045 lbs Four (4) 208V/30A single-phase circuits with need to be on UPS and diversely provisioned such that two of the four circuits are on separate power sources from the other two. (Rack PDUs) One (1) 120V/15A circuit on UPS with NEMA 5-15R receptacle. (Misc. equipment) KVA: 2.34 KBTUs: 9.00 Phone Line: None Rack #2: IBM 7014-T42 Equipment Rack 24.5w, 43.3d, 79.3h, inches Min. weight, 575 lbs; Max. weight, 2045 lbs Two (2) 208V/30A, single-phase, circuits with need to be on UPS and diversely provisioned. (Rack PDUs) Two (2) 208V/30A, single-phase, circuits with NEMA L6-30R receptacles. These circuits will need to be on UPS and diversely provisioned. (IBM BladeCenter) Two (2) 208V/30A, single-phase, circuits with need to be on UPS and diversely provisioned. (Dell Blade Server) Three (3) 120V/15A circuits with NEMA 5-15R receptacles. These circuits will need to be on UPS and diversely provisioned. (Sun Servers) KVA: 7.77 KBTUs: Phone Line: 1 (dial-in) Rack #3: IBM 7014-T42 Equipment Rack
5 24.5w, 43.3d, 79.3h, inches Min. weight, 575 lbs; Max. weight, 2045 lbs Four (4) 208V/30A, single-phase, circuits with need to be on UPS and diversely provisioned such that two of the four circuits are on separate power sources from the other two. (Rack PDUs) One (1) 120V/15A circuit on UPS with NEMA 5-15R receptacle. (Misc. equipment) KVA: 4.05 KBTUs: Phone Line: 1 HOST SITE CONNECTIVITY 1. For the TCP/IP connectivity to FLR and NLR network, does FSU prefer an IP-VPN on a Private MPLS network or will FSU prefer FSU virtual tunnels on the public Internet? A VPN or tunnel that constrains throughput in any way is undesirable. A private MPLS network that restricts frame size to less that 9K MTUs is also undesirable. We prefer dark fiber or a VLAN capable of supporting frame sizes of 9K MTUs. 2. Does FSU require connecting to FLR and NLR separately GigE/10GigE connections? No. One connection to either FLR or NLR. 3. If separate connections are required, do the connections have to be diversely routed? Only one connection. 4. What location does FSU prefer to connect to the FLR network and the NLR network (Address, City, State, Zip)? No preference as to location. 5. What is the expected monthly usage on each of the two GigE (scaleable to 10GigE) ports?
6 We expect a full 2Gb to be available to us at all times. For the initial deployment, this can be achieved by providing two (2) GigE ports channelized to provide a single 2Gb connection. However, a 10Gb connection rate-limited to 2Gb would also be acceptable and would easily facilitate future growth in bandwidth requirements. 6. Do FLR and NLR have 1Gig LAN PHY and/or 10Gig LAN PHY connectivity at their location? Yes. Both.
ECS APPLIANCES. Specification Sheet
Specification Sheet ECS APPLIANCES This 3rd Generation object storage solution from Dell EMC, ECS is built for accelerating digital transformation by bridging both traditional and next generation applications.
More informationELASTIC CLOUD STORAGE (ECS) APPLIANCE
Specification Sheet ELASTIC CLOUD STORAGE (ECS) APPLIANCE Dell EMC Elastic Cloud Storage (ECS ) Appliance is a multi-purpose, software-defined cloud-storage platform. This 3rd Generation object-based solution
More informationDELL EMC VPLEX FAMILY
Specification Sheet DELL EMC VPLEX FAMILY Introduction Dell EMC VPLEX enables IT organizations to create a storage architecture that enables a data center to be: Always available even in the face of disasters
More informationROUND ROCK INDEPENDENT SCHOOL DISTRICT Data Center Co-Location Request for Proposal (RFP) Number PE15-116
CONTRACT REQUIREMENTS For establishing the terms and conditions for the contract, the awarded Proposer shall hereby be known as Contractor. 1. DESCRIPTION. This contract shall be for the purchase of Data
More informationRack 111 Catalog. Designed and Built to Exceed Your Needs.
Designed and Built to Exceed Your Needs. The Open Frame Server Rack is designed to provide users with a customizable solution engineered to meet a diverse set of rack mounting needs. This EIA server rack
More informationDELL EMC DATA DOMAIN DEDUPLICATION STORAGE SYSTEMS
SPEC SHEET DELL EMC DATA DOMAIN DEDUPLICATION STORAGE SYSTEMS Data Domain Systems Dell EMC Data Domain deduplication storage systems continue to revolutionize disk backup, archiving, and disaster recovery
More informationSPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120
DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified
More informationDELL EMC DATA DOMAIN DEDUPLICATION STORAGE SYSTEMS
Data Domain Systems Table 1. DELL EMC DATA DOMAIN DEDUPLICATION STORAGE SYSTEMS Dell EMC Data Domain deduplication storage systems continue to revolutionize disk backup, archiving, and disaster recovery
More informationIncreasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Revision 1 Executive Summary A new approach to power distribution for high density
More informationDELL EMC DATA DOMAIN DEDUPLICATION STORAGE SYSTEMS
DELL EMC DATA DOMAIN DEDUPLICATION STORAGE SYSTEMS Dell EMC Data Domain deduplication storage systems continue to revolutionize disk backup, archiving, and disaster recovery with high-speed, inline deduplication.
More informationAVR Series 120V 700VA 350W Ultra-Compact Line-Interactive UPS with USB port
AVR Series 120V 700VA 350W Ultra-Compact Line-Interactive UPS with USB port MODEL NUMBER: AVR700U Highlights 700VA ultra-compact 120V line interactive UPS Corrects brownouts and overvoltages from 83V to
More informationOmniSmart 120V 1400VA 940W Line-Interactive UPS, Tower, USB port
OmniSmart 120V 1400VA 940W Line-Interactive UPS, Tower, USB port MODEL NUMBER: OMNISMART1400 Highlights 1400VA / 1.4kVA tower 120V line interactive UPS Corrects brownouts and overvoltages from 75V to 147V
More informationRFQ No C014 Datacenter Colocation and Associated Support Services. December 4, 2017
RFQ No. 1-18-C014 Datacenter Colocation and Associated Support Services December 4, 2017 Questions and Answers Notice: Questions may have been edited for clarity and relevance. 1. Question: Do you have
More informationUltraRack. Advanced Data Centre Enclosures SR SERIES
UltraRack Advanced Data Centre Enclosures SR SERIES Designed for scaleable growth The SR Series UltraRack SR Series - Universal rack enclosure solutions for advanced storage, cooling, power distribution,
More informationPHASE ONE Series 700: Uninterruptible Power Supply (UPS) Systems
PHASE ONE Series 700: Uninterruptible Power Supply (UPS) Systems Features General Universal Application Data Processing Telecommunications Medical/Health Care Manufacturing/ Process Control Quality Design
More informationGreat Falls Public School Districts 1 & A th Street South Great Falls, MT February 16, 2018
Great Falls Public School Districts 1 & A 1100 4th Street South Great Falls, MT 59405 February 16, 2018 Request for Quote for E-rate Category 2 Equipment SLD Entity Number: 134909 Applicant Form 470 Identifier:
More information<Insert Picture Here> Exadata Hardware Configurations and Environmental Information
Exadata Hardware Configurations and Environmental Information Revised July 1, 2011 Agenda Exadata Hardware Overview Environmental Information Power InfiniBand Network Ethernet Network
More informationAVR Series 120V 750VA 450W Ultra-Compact Line-Interactive UPS with USB port
AVR Series 120V 750VA 450W Ultra-Compact Line-Interactive UPS with USB port MODEL NUMBER: AVR750U Highlights 750VA ultra-compact 120V line interactive UPS Corrects brownouts and overvoltages from 83V to
More informationData Center Network Infrastructure
Data Center Network Infrastructure COPPER CAT 6 А, 7, 7 А, 8 Pre-Terminated Copper SOLUTIONS FIBER OPTIC Cables Category 6 A, 7, 7 A, 8.2 Cable Assemblies MTP/MPO Systems Copper Connectors Category 6 A,
More informationSymantec NetBackup 5200
Symantec NetBackup 5200 is a single-vendor enterprise backup appliance that installs in minutes, with 32 TB of disk storage Data Sheet: Data Protection Overview is a single-vendor enterprise backup appliance
More informationNewark, Delaware Architectural Engineering Senior Thesis Portfolio
Telecommunications System Design The represents the advancement of solar design in our world today. The building itself is an example of this. A Headquarters this dedicated to moving into the future should
More informationTECHNICAL SPECIFICATIONS + TECHNICAL OFFER
ANNEX II + III : TECHNICAL SPECIFICATIONS + TECHNICAL OFFER Contract title : Supply of Information & Communication Technology Hardware Publication reference: 2017/386304 10/1/1.1/1.2.2a p 1 / Columns 1-2
More informationE-Series Site Preparation Guide
E-Series Site Preparation Guide September 2017 215-11797_A0 doccomments@netapp.com Table of Contents 3 Contents Deciding whether to use this guide... 10 Specifications of the model 3040 40U cabinet...
More informationDELL EMC DATA DOMAIN DEDUPLICATION STORAGE SYSTEMS
SPEC SHEET DELL EMC DATA DOMAIN DEDUPLICATION STORAGE SYSTEMS Data Domain Systems Dell EMC Data Domain deduplication storage systems continue to revolutionize disk backup, archiving, and disaster recovery
More informationPOWERMAX FAMILY. Appliance-based packaging. PowerMax 2000 and Specifications. Specification Sheet. PowerMax Arrays
Specification Sheet POWERMAX FAMILY PowerMax Arrays PowerMax 2000 and 8000 The new family of Dell EMC NVMe (Non-Volatile Memory Express) arrays resets the bar for enterprise storage with new levels of
More informationINSTRUCTIONS TO RESPONDENTS
Florida State University Competitive Solicitation Addendum Acknowledgement Form Procurement Services Florida State University 282 Champions Way, UCA 1400 Tallahassee, FL 32306-2370 Phone (850) 644-6850
More informationIBM TotalStorage FAStT900 Storage Server New Offering Expands IBM SAN Storage Solutions
Hardware Announcement February 17, 2003 IBM TotalStorage FAStT900 Storage Server New Offering Expands IBM SAN Storage Solutions Overview The IBM TotalStorage FAStT900 Storage Server expands the family
More informationBC Pro 120V 1400VA 940W Standby UPS, Tower, USB port, 6 Outlets
BC Pro 120V 1400VA 940W Standby UPS, Tower, USB port, 6 Outlets MODEL NUMBER: BCPRO1400 Highlights 1400VA / 1.4kVA tower 120V standby UPS Maintains AC output during power failures USB port, Front panel
More informationTAA-Compliant SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial
TAA-Compliant SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMART500RT1UTAA Highlights Federal Trade Agreements Act / TAA compliant for GSA
More informationAVR Series 120V 550VA 300W Ultra-Compact Line-Interactive UPS with USB port
AVR Series 120V 550VA 300W Ultra-Compact Line-Interactive UPS with USB port MODEL NUMBER: AVR550U Highlights 550VA ultra-compact 120V line interactive UPS Corrects brownouts and overvoltages from 83V to
More informationBC Personal 120V 450VA 280W Standby UPS, Tower, USB port, 3 Outlets
BC Personal 120V 450VA 280W Standby UPS, Tower, USB port, 3 Outlets MODEL NUMBER: BCPERS450 Highlights 450VA tower 120V standby UPS Maintains AC output during power failures USB port, Status LEDs NEMA
More informationThis cover sheet must be signed by the individual signing the Proposal and returned with the Proposal.
Florida State University Competitive Solicitation Addendum Acknowledgement Form Procurement Services Florida State University 282 Champions Way, UCA 1400 Tallahassee, FL 32306-2370 Phone (850) 644-6850
More informationv2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.
Changes in v2.6: v2.5 was updated May 10, 2016. v2.6 is an updated copy from March 1, 2017. Modifications to 4. Horizontal Pathways section with feedback incorporated from UofA Facilities and Operations
More informationSavant Host: HST-4501
Savant Host: HST-50 The Savant Host (HST-50) within a Savant System provides numerous functions including high-level automation and control functions, user interface interpretations, system administration,
More informationSECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS
SECTION 5 -- EQUIPMENT LAYOUT & EQUIPMENT ENVIRONMENTS CONTENTS PAGE 1. GENERAL... 5-1 1.1. Introduction... 5-1 1.2. Equipment Layout Requirements... 5-1 2. EQUIPMENT FRAMES... 5-2 2.1. Introduction...
More informationBuilding Backup-to-Disk and Disaster Recovery Solutions with the ReadyDATA 5200
Building Backup-to-Disk and Disaster Recovery Solutions with the ReadyDATA 5200 WHITE PAPER Explosive data growth is a challenging reality for IT and data center managers. IDC reports that digital content
More informationAVR Series 230V 550VA 300W Ultra-Compact Line-Interactive UPS with USB port, C13 Outlets
AVR Series 230V 550VA 300W Ultra-Compact Line-Interactive UPS with USB port, C13 Outlets MODEL NUMBER: AVRX550U Highlights 550VA ultra-compact 230V line interactive UPS Corrects brownouts and overvoltages
More informationDCIM Data Center Infrastructure Management
DCIM Data Center Infrastructure Management Part 3 Operational Management Moves Adds and Changes & Electrical Infrastructure November 5, 2013 Presented by Julius Neudorfer Sponsored by Today s Topics Operational
More informationIBM TotalStorage SAN Switch M12
High availability director supports highly scalable fabrics for large enterprise SANs IBM TotalStorage SAN Switch M12 High port density packaging saves space Highlights Enterprise-level scalability and
More informationPOS Series 120V 50/60Hz 500VA 300W Standby UPS, Tower, USB port, 6 Outlets, TEL/DSL Protection
POS Series 120V 50/60Hz 500VA 300W Standby UPS, Tower, USB port, 6 Outlets, TEL/DSL Protection MODEL NUMBER: POS500 Highlights 500VA low-profile tower 120V standby UPS Maintains AC output during power
More informationASCO 920 Remote Control (RC) Switches
Maximum reliability and excellent value ASCO 920 Remote Control (RC) Switches ASCO 920 Remote Control Switch in Type Enclosure The ASCO 920 is designed as a feeder disconnect switch for load capacities
More informationController Cardax FT Controller The CardaxFT Controller 5000 is the intelligent field controller in the CardaxFT security system.
The features described in this data sheet are being progressively added to the CardaxFT Controller (5000 Series) during 2002/2003. Please contact Cardax for further information. Cardax FT Controller 5000
More informationRetired. Full Rack Vertical PDU Model (Ideal for 36U to 47U racks)
Overview The HP Monitored PDUs allow administrators and facility personnel to monitor current draw directly at the rack and per PDU. HP Monitored PDUs are available in both 1 phase and 3 phase and in single
More informationCutting Cabling Costs By Mike Martin
Data Center Solutions White 01 Cutting Cabling Costs By Mike Martin 603.474.2626 info@martinenclosures.com www.martinenclosures.com Are your cabling costs soaring out of control? Important cable management
More informationCOMCAST ENTERPRISE SERVICES PRODUCT-SPECIFIC ATTACHMENT SOFTWARE-DEFINED WIDE AREA NETWORKING (SD-WAN)
ATTACHMENT IDENTIFIER: SD-WAN, Ver. 1.0 COMCAST ENTERPRISE SERVICES PRODUCT-SPECIFIC ATTACHMENT SOFTWARE-DEFINED WIDE AREA NETWORKING (SD-WAN) The following additional terms and conditions are applicable
More informationSECURE 6. Secure64 Appliances Purpose-built DNS appliances for the most demanding environments DNS APPLIANCES DATA SHEET. Appliance Descriptions
SECURE 6 Secure64 Appliances Purpose-built DNS appliances for the most demanding environments DNS APPLIANCES KEY FEATURES Choice of blade or rack mount form factors Redundant disks, power supplies and
More informationIntroduction to iscsi
Introduction to iscsi As Ethernet begins to enter into the Storage world a new protocol has been getting a lot of attention. The Internet Small Computer Systems Interface or iscsi, is an end-to-end protocol
More informationIBM eserver System x and BladeCenter IBM DPI PDU+ Power Distribution Units. 10/9/ IBM Corporation
IBM eserver System x and BladeCenter IBM DPI PDU+ Power Distribution Units 10/9/2007 Agenda System x Options Program and PDU market overview What is a PDU? Why do you need an IBM DPI PDU? IBM DPI PDU offering
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationftserver 3300 Service Bulletin
ftserver 3300 Service Bulletin Last Updated 2/12/04 1. Overview The ftserver 3300 is based on the 2.4-GHz or 3.06-GHz Intel IA32 architecture using Intel s Xeon processors and one-way or two-way (one or
More informationIBM TotalStorage Enterprise Tape Library 3494
Modular tape automation for multiple computing environments IBM TotalStorage Enterprise Tape Library 3494 A 16-frame IBM TotalStorage Enterprise Tape Library 3494 high availability configuration with two
More informationCenturyLink Service Guide. Colocation Services. CenturyLink Service Guide. North American Colocation Services
CenturyLink Service Guide Colocation Services July 7, 2015 CenturyLink Service Guide This CenturyLink Colocation Service Guide ( SG ) sets forth a description of CenturyLink Colocation Service ( Service
More informationArtico NAS Storage Appliance Site Planning Guide
Artico NAS Storage Appliance Contents Artico NAS Storage Appliance Site Planning Guide Site Requirements... 2 Shipping Information... 2 System Components... 3 Specifications... 8 Selecting an Installation
More informationIBM 42U and 47U 1200mm Deep Static and 42U 1200mm Deep Dynamic Racks for System x
Announcement ZG10-0303, dated September 7, 2010 IBM 42U and 47U 1200mm Deep Static and 42U 1200mm Deep Dynamic Racks for System x Table of contents 1 Overview 4 Product number 2 Key prerequisites 4 Publications
More information550VA Audio/Video Backup Power Block - Exclusive UPS Protection for Structured Wiring Enclosure
550VA Audio/Video Backup Power Block - Exclusive UPS Protection for Structured Wiring Enclosure MODEL NUMBER: AV550SC Highlights 4 AC outlets (including 1 delayon outlet for router) Automatic recycle/reset
More information30 th September Always Right Size Modular Data Centres. Cannon Technologies Ltd (2015)
30 th September 2015 Glenn Conlon Always Right Size Modular Data Centres Traditional DC Build: Image courtesy of ENP Traditional DC: IRO 20 million + @ T2/3 Image courtesy of ENP DC Halls x 2, 500 Cabinets
More informationNetfinity White Paper Netfinity Technology Center
Netfinity White Paper Netfinity Technology Center Rack Storage Expansion Enclosure Planning Guide Abstract This paper is designed for use by Pre-Sales technical marketing representatives. This includes
More informationTAA-Compliant POS Series 120V 500VA 300W Standby UPS, Tower, USB port, 6 Outlets, TEL/DSL Protection
TAA-Compliant POS Series 120V 500VA 300W Standby UPS, Tower, USB port, 6 Outlets, TEL/DSL Protection MODEL NUMBER: POS500TAA Highlights Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases
More informationBroadCom 10 Gb 2-Port and 4-Port Ethernet Expansion Cards (CFFh) for IBM BladeCenter offer multiple interfaces with BladeCenter blades
, dated October 21, 2008 BroadCom 10 Gb 2-Port and 4-Port Ethernet Expansion Cards offer multiple interfaces with BladeCenter blades Table of contents 2 Key prerequisites 7 Product specific information
More informationQuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview
Overview You cannot control what you cannot monitor. The new brings state of the art management and control to rack mounted power distribution units (PDU) to prevent over provisioning of power from restricting
More informationSmartPro 1kVA 800W Line Interactive Sine Wave UPS, SNMPWEBCARD option, 1U Rackmount, USB, RS232, EPO, 120V
SmartPro 1kVA 800W Line Interactive Sine Wave UPS, SNMPWEBCARD option, 1U Rackmount, USB, RS232, EPO, 120V MODEL NUMBER: SMART1000RM1U Description Tripp Lite SMART1000RM1U 1000VA / 1kVA / 800 watt line
More informationSite Preparation CHAPTER
CHAPTER 3 Site Preparation This chapter describes the steps to take and the considerations you should keep in mind prior to installing the modules in an open rack. It also contains information that applies
More informationFLORIDA STATE UNIVERSITY PURCHASING DEPARTMENT A1400 UNIVERSITY CENTER TALLAHASSEE FL ADDENDUM ACKNOWLEDGMENT FORM. DATE: October 28, 2013
FLORIDA STATE UNIVERSITY PURCHASING DEPARTMENT A1400 UNIVERSITY CENTER TALLAHASSEE FL 32306-2370 ADDENDUM ACKNOWLEDGMENT FORM DATE: October 28, 2013 ADDENDUM NO: 3 Competitive Solicitation Number ITB 5665-0
More information24-Port Gigabit Ethernet Switch w/ 12 Outlet PDU, 2 SFP and 8 PoE+ Ports, 120W
Cat6A cables, such as Tripp Lite's N261-Series, are recommended for optimal performance 24-Port Gigabit Ethernet Switch w/ 12 Outlet PDU, 2 SFP and 8 PoE+ Ports, 120W MODEL NUMBER: NSU-G24C2P08 Description
More informationManaged Internet Service (MIS) gives you these features:
Product Description Managed Internet Service (MIS) is an Internet access service that combines a symmetrical, dedicated connection with consolidated application management. MIS includes proactive, 24x7
More informationSolutions Guide for Cisco UCS B and C Series Servers
Solutions Guide for Cisco UCS B and C Series Servers The Cisco Unified Computing System is a next-generation data center platform that unites compute, network, storage access, and virtualization into a
More informationGigaVUE-2404 // Data Sheet
Mgmt Console M/S Rdy 10/100/1000 PORTS (SFP) G1 G2 G3 G4 G1 G2 G3 G4 1 1 2 2 3 3 4 5 4 5 6 6 7 7 8 8 SLOT 2 PORTS 9 16 SLOT 1 PORTS G1-G4 PORTS 1-8 SLOT 3 PORTS 17 24 PS ALARM CUTOFF UP WHEN INSTALLED
More informationTechnical Specifications
Technical s This appendix lists the technical specifications for the Cisco UCS 5108 server chassis and includes the following sections: KVM Cable, page 1 Chassis s, page 2 Environmental s, page 3 s for
More informationVendor must indicate at what level its proposed solution will meet the College s requirements as delineated in the referenced sections of the RFP:
Vendor must indicate at what level its proposed solution will the College s requirements as delineated in the referenced sections of the RFP: 2.3 Solution Vision Requirement 2.3 Solution Vision CCAC will
More informationEMC VNXe SERIES UNIFIED STORAGE SYSTEMS
EMC VNXe SERIES UNIFIED STORAGE SYSTEMS EMC VNXe series unified storage systems deliver exceptional flexibility for the smallto-medium-business, combining a unique, application-driven management environment
More informationIBM BladeCenter HT ac and dc model chassis accommodates BladeCenter blade servers for telecommunications environments and new options
IBM Europe Announcement ZG07-0187, dated February 13, 2007 IBM BladeCenter HT ac and dc model chassis accommodates BladeCenter blade servers for telecommunications environments and new options Key prerequisites...2
More informationSmartPro 230V 1.5kVA 900W Line-Interactive UPS, 2U Rack/Tower, LCD, USB, DB9, 8 Outlets
SmartPro 230V 1.5kVA 900W Line-Interactive UPS, 2U Rack/Tower, LCD, USB, DB9, 8 Outlets MODEL NUMBER: SMX1500LCD Highlights Corrects under- and overvoltages from 144V to 282V 8 C13 outlets Interactive
More informationRFP # ISD Modular/Container Based Recovery Data Center Questions and Answers
RFP # ISD 1806 Modular/Container Based Recovery Data Center Questions and Answers Q. In-rack power outlet requirements (# of C13/C19 etc) A. In-rack power should be flexible per TIA-942 5.11.7.7 and able
More informationRECENTLY RENOVATED OFFICE / DATA CENTER
RECENTLY RENOVATED OFFICE / DATA CENTER AVAILABLE OFFICE SPACE ±46,772 SF 2441 WEST LA PALMA AVENUE: (BUILDING 5) SIZE (SF) ASKING RATE ±46,772 $2.10 MG DESCRIPTION Single Floor. Office/Creative possible.
More informationSmartRow Solution Intelligent, Integrated Infrastructure for the Data Center
SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center Deploy a Fully Configured Data Center in Just Weeks Availability, Capacity, Efficiency. You need them and now you can have them
More informationOracle Communications Diameter Signaling Router
Oracle Communications Diameter Signaling Router Release 6.0 Planning Guide O R A C L E W H I T E P A P E R S E P T E M B E R 2 0 1 4 Table of Contents Acronyms 1 Terminology 1 References 2 Introduction
More informationDelegation of the European Union to Bosnia and Herzegovina
EUROPEAN UNION Delegation of the European Union to Bosnia and Herzegovina Sarajevo, 11.10.2018 CLARIFICATION No. 2 to the Tender Dossier "Supply of IT equipment for four tax administrations in BiH" Publication
More informationRFP Questions Guideline For Data Center Buyers
RFP Questions Guideline For Data Center Buyers Rev: 00W0052015 1 P a g e This guideline document is a supporting download for our webinar titled 5 RFP Questions Data Center Buyers Must Ask a Provider and
More informationOmni LCD 650VA Tower Line-Interactive 120V UPS with LCD display and USB port
Omni LCD 650VA Tower Line-Interactive 120V UPS with LCD display and USB port MODEL NUMBER: OMNI650LCD Highlights 650VA tower 120V line interactive UPS with LCD display Corrects brownouts as low as 89V
More informationAVR Series 120V 700VA 350W Ultra-Compact Line-Interactive UPS with USB port
AVR Series 120V 700VA 350W Ultra-Compact Line-Interactive UPS with USB port MODEL NUMBER: AVR700U Highlights 700VA ultra-compact 120V line interactive UPS Corrects brownouts and overvoltages from 83V to
More informationCharles Nolan. Do more with less with your data centre A customer s perspective. Director IT Infrastructure, UNSW. Brought to you by:
Charles Nolan Director IT Infrastructure, UNSW Do more with less with your data centre A customer s perspective Brought to you by: Today s Enterprise Data Centre Doing more with less High Density Data
More informationSmartPro 120V 1.05kVA 705W Line-Interactive UPS, Tower, 120V, USB port
SmartPro 120V 1.05kVA 705W Line-Interactive UPS, Tower, 120V, USB port MODEL NUMBER: SMART1050 Highlights 1.05kVA / 1050VA line interactive tower UPS system 120V output, Corrects brownouts and overvoltages
More informationQLogic InfiniBand Cluster Planning Guide
QLogic InfiniBand Guide D000051-001 Preliminary QLogic Guide Information furnished in this manual is believed to be accurate and reliable. However, QLogic Corporation assumes no responsibility for its
More informationHP BladeSystem c-class enclosures
Family data sheet HP BladeSystem c-class enclosures Tackle your infrastructure s cost, time, and energy issues HP BladeSystem c3000 Platinum Enclosure (rack version) HP BladeSystem c7000 Platinum Enclosure
More informationModel #: BCPRO1050. BC Pro UPS System - Standby UPS System. Highlights. Description. Features
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 Email: saleshelp@tripplite.com Model #: BCPRO1050 BC Pro UPS System Standby UPS System Highlights 1050VA / 1.05kVA standby
More informationWHITE PAPER. Solutions OnDemand Hosting Overview
WHITE PAPER SAS Title Solutions OnDemand Hosting Overview ii Contents Overview... 1 Cary 1 (US) Facility Specifications...2 Cary 2 (US) Facility Specifications (SAS New Cloud Computing Center)...3 Charlotte
More informationASCENT DATA CENTER. 30 MW Data Center Enterprise Grade Facility LEED Gold ATLANTA, GA ABOUT ASCENT CO LO CAT I O N SUI T E S AVAI LAB LE NO W!
ASCENT DATA CENTER CO LO CAT I O N SUI T E S AVAI LAB LE NO W! ATLANTA, GA 30 MW Data Center Enterprise Grade Facility LEED Gold ABOUT ASCENT Ascent Data Center is located in the greater Atlanta, Georgia
More informationNetworks - Technical specifications of the current networks features used vs. those available in new networks.
APPENDIX V TECHNICAL EVALUATION GUIDELINES Where applicable, the following guidelines will be applied in evaluating the system proposed by a service provider: TABLE 1: HIGH LEVEL COMPONENTS Description
More informationLenovo ThinkAgile CP Planning and Setup Guide
Lenovo ThinkAgile CP Planning and Setup Guide Models: CP 4000, CP 6000 Note Before using this information and the product it supports, be sure to read and understand the safety information and the safety
More informationAVR Series 230V 750VA 450W Ultra-Compact Line-Interactive UPS with USB port, French/Belgian Outlets
AVR Series 230V 750VA 450W Ultra-Compact Line-Interactive UPS with USB port, French/Belgian Outlets MODEL NUMBER: AVRX750UF Highlights 750VA ultra-compact 230V line interactive UPS Corrects brownouts and
More informationRack Power Distribution. Rack power distribution offerings for entry-level networking equipment and high-density server and blade environments
Rack Power Distribution Rack power distribution offerings for entry-level networking equipment and high-density server and blade environments Wiring Closet/Server Rooms IP Telephony High Density Small/Medium
More informationTAA SmartPro 120V 1.5kVA 1.35kW Line- Interactive Sine Wave UPS, 2U, Extended Run, Network Card Options, LCD, USB, DB9
TAA SmartPro 120V 1.5kVA 1.35kW Line- Interactive Sine Wave UPS, 2U, Extended Run, Network Card Options, LCD, USB, DB9 MODEL NUMBER: SM1500RMXL2UTAA Highlights Corrects under- and overvoltages from 83V
More informationASA5525-FPWR-K9 Datasheet. Overview. Check its price: Click Here. Quick Specs
ASA5525-FPWR-K9 Datasheet Check its price: Click Here Overview Cisco ASA with FirePOWER Services brings distinctive threat-focused next-generation security services to the Cisco ASA 5500-X Series Next-
More informationNetwork Services. Product Catalog
Network Services Product Catalog Massive increases in data traffic, mobile devices and cloud-based applications are constantly changing the way your customers do business. AT&T Internet Access Fast, affordable
More informationSmartPro LCD 120V 1200VA 700W Line- Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, DB9 Serial, 8 Outlets
SmartPro LCD 120V 1200VA 700W Line- Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, DB9 Serial, 8 Outlets MODEL NUMBER: SMART1200LCD Highlights Supports a half-load (350W) up to 14.3 min. during power outage
More informationSmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, 2U Rack/Tower, WEBCARDLX Network Interface, LCD, USB, 8 Outlets
SmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, 2U Rack/Tower, WEBCARDLX Network Interface, LCD, USB, 8 Outlets MODEL NUMBER: SMART1500RM2UN Highlights Corrects under- and overvoltages from
More informationSmartOnline 120V 2.2kVA 1.6kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Network Card Slot, USB, DB9 Serial
SmartOnline 120V 2.2kVA 1.6kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Network Card Slot, USB, DB9 Serial MODEL NUMBER: SU2200RTXL2UA Highlights 2200VA / 2.2kVA / 1600 watt on-line double-conversion
More informationSmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, Pre-installed WEBCARDLX Network Interface, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, Pre-installed WEBCARDLX Network Interface, USB, DB9 Serial MODEL NUMBER: SMART750RM1UN Highlights.75kVA / 750VA / 600W line interactive
More informationISILON HD-SERIES. Isilon HD400 ARCHITECTURE SPECIFICATION SHEET Dell Inc. or its subsidiaries.
SPECIFICATION SHEET ISILON HD-SERIES Isilon HD400 The rapid growth of unstructured data combined with increasingly stringent compliance requirements is resulting in a growing need for efficient data archiving
More information4-Post and Universal Telco Frame (UTF) Rack Mount Kit Installation Instructions
4-Post and Universal Telco Frame (UTF) Rack Mount Kit Installation Instructions Review the documentation that comes with your rack cabinet for safety and cabling information. Before installing your server
More information