MV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA)

Size: px
Start display at page:

Download "MV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA)"

Transcription

1 MV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA) Runjic Darijo Koncar Power Plant and Electric Traction Engineering Inc. - Croatia darijo.runjic@koncar-ket.hr Sporec Marko, Strmecki Goran HEP distribution - "Elektra" Zagreb - Croatia marko.sporec@hep.hr, goren.strmecki@hep.hr INTRODUCTION This paper describes the basic characteristics of MV network in the distribution area (DA) "Elektra" Zagreb and gives criteria for the selection of network points that are, due to their exceptional importance, required to have remote control capability. It also gives a description of procedure for remote control of switching devices built in medium voltage fields in MV/LV cable substations. Every element in the remote control system is described with all important tehnical data. 1. DA "ELEKTRA" ZAGREB POWER NETWORK Power network of DA "Elektra" Zagreb (that is a part of the state-owned Power Distribution Company that provides electric energy supply to the town of Zagreb and its neighbourhood) is a complex system of 0.4kV, 10kV, 20kV, 30kV and 110kV switchyards. Due to a relatively big surface of the distribution area, which has a variety of urbanisation degrees, as well as specific qualities of individual zones, during the process of planning and construction of power network, a range of parameters have to be taken into consideration. Since the construction of the first thermal power plant in Zagreb in 1907, the town power network has been widened from the centre outwards and together with a parallel development of neighbouring places have led to situation that today we practically do not have boundaries between the town and its suburbs. Circumstances under which the town was developing during the last century an absence of high quality and long term urbanisation plans that would be followed by long term plans for power system development, has resulted in insufficient capacities of existing supply points as well as distribution circulation the middle voltage power network in the centre of the town. Under today's conditions of the high degree urbanisation in the centre of the town, with existing complex public utilities network the great problem we are facing is resolving of property-rights relations bound to building sites for new substations, whether for new supply points subsations 110/10(20) kv, whether for new MV/LV cable substations and corridors for passing of new cables Supply points Supply points in power network of DA "Elektra" Zagreb are substations 110/10(20) kv and 30/10(20) kv. During a long period of time, building of new supply points in DA "Elektra" Zagreb has not followed a big increase in electric energy consumption, and the power load in some supply points has reached critical levels. A special problem represents switching off of some supply points due to ordinary maintenance during which supply of electric energy to consumers has to be accomplished through neighbouring supply points what causes their high power loading. In 2001 the DA "Elektra" Zagreb have maximum demand of 632,386MW. In 2002 preparations for construction of three new important supply points (substations 110/10(20)kV) in Zagreb have started. Making of investment and technical documentation for substations, as well as distribution of medium voltage cables from those stations, have entered into the final phase, while finishing of the construction and putting into operation is expected to be in a few years. By putting those supply points into operation, not only the reliability of DA "Elektra" Zagreb power system will be increased, but also preconditions for urbanisation and business development of some parts of the narrower and the wider centre of the town of Zagreb, that today are at a standstill due to overloading of some existing supply points, will be created. In development plans of DA "Elektra" Zagreb a tendency is to phase out supply points from the voltage 30kV, and to introduce middle voltage level 20kV. In accordance, transformations 110/30kV and 30/10kV are going to be abandoned, and the final aim is establishment of distribution power system with transformations 110/20kV and 20/0,4kV. For those reasons DA "Elektra" Zagreb has started the project of MV distribution network automation through installation of remotely monitored and controlled switching devices in the MV/LV cable substations. KON_Runjic_A1 Session 3 Paper No

2 During selection of MV/LV cable substations in which the equipment that enable remote control is being built-in, the following criteria have been taken into consideration: Substation supplies a consumer with a need of an increased reliability in power supply (consumer of an especial state or business importance); Substation on a long distance or on a difficult terrain a significant time is necessary for an operative team to access the substation, or the entrance into it is difficult; Substation in the area where a possibility of faults on middle voltage cables is high (pursuant existing statistics); Substation that represents a supporting point of a part of the middle voltage network; Substation in the middle of connective MV line (in connective network) and in the middle of a ring (in ring network) from the cable loading point of view; Substation in the place of important transversal connections between individual connection cables; 1.2. Middle voltage (MV) network development MV network configurations In DA "Elektra" Zagreb, three types of MV power network configurations are comprised: Radial network Ring network Connective network Radial network model in which a range of cable substations 10(20)/0,4kV is radially supplied from a central supply point is present on margin parts of DA "Elektra" Zagreb, where a smaller number of consumers are placed on relatively big geographical surfaces. The terrain is often very difficult and the costs of establishing of a feedback connection that ensures higher reliability of electric energy supply are very high. Ring network model in which a cable output from one supply point supplies a certain number of MV/LV cable substations and it comes back to the starting supply point, exists in margin areas of the centre of the town of Zagreb where a relative high density of consumers exists, but it is significantly lower in comparison with the one in the centre of the town. Increasing of reliability of power supply in these areas is reached by transforming of ring network into connective network. point is present in the centre of the town of Zagreb, where the density of consumers is the highest, and where the need for increased reliability of power supply is expressed because a majority of state and social institutions, as well as important business subjects are placed there. Due to the limited possibility of building a new supply points, the connective network model with a support point is used, in which a direct cable from a neighbouring feeder point is led to the centre of the ring (in ring network) or to the centre of the connecting cable (in connective network), and in such a way transmitting capacity of cable outputs from supply points is significantly increased MV/LV cable substations remote control A continuous growth of industrial production, other economy branches and living standard results in the constant increase of power consumption in Croatia, especially in its capital, the town of Zagreb. On the other hand, the existing complex economic situation requires business rationalisation of all the subjects in the production chain, from generation to distribution of electric energy and exploitation of all existing capacities up to the highest level. Regardless of such conditions the distribution company task is to increase the reliability and quality of delivered electric energy (with minimal costs), in order to be, as much as possible, prepared for forthcoming process of energy market opening. 2. REMOTE CONTROL SYSTEM IN MV/LV CABLE SUBSTATIONS In the area of the town of Zagreb, in 2000 the total number of cable substations 10(20)/0.4kV was 1898, but neither station did have a possibility of remote monitor and control. At the beginning of 2001, starting form the defined criteria (pointed out in item ) the first 20 cable substations were selected in which MV switchgears with a possibility of remote control were built-in by the end of Low voltage switchgears do not have a possibility of remote control, but they are necessary for functioning of remote control system due to supply of some elements with 230V AC. A power transformer is seen as a source of 230V AC and as an element that has to be protected from faults. Besides MV switchgear with a possibility of remote control, other equipment necessary for realisation of all the foreseen remote monitor and control functions was built-in in each cable susbstation. Under term "other equipment" we consider devices placed in appropriate cubicles or independently, as shown in Fig.1, and described together with MV switchgear in items below. Connective network model in which each cable output from the individual supply point supplies a certain number of MV/LV cable substations and ends in some other supply KON_Runjic_A1 Session 3 Paper No

3 Fig.1: Elements of remote control system in MV/LV cable substation 2.1. Middle voltage switchgear manually also, as a reserve to the remote control. A middle voltage switchgear consists of one or more switching blocks that are equipped with supplementary components in comparison with blocks of classical manufacture for manual operation Motor drive The basic function of the motor is winding up of the spring (that is a part of driving mechanism) for manipulation of switching devices. During the process of manipulation of switching device a discharge of accumulated energy in the spring occurs. After that, the motor automatically receives the signal for switching on and winds the spring up. The process of winding up of a spring lasts 5-6 seconds and after that the driving mechanism of the switching block is ready to perform the following operation. A motor has demand of 350W and it is supplied by 48V DC Signalling switches Their main purpose is to determine switch position of switching devices Electromagnetic solenoids for switching on/off As a difference to switching blocks for manual operation where the command for opening/closing of a switching device is directed exclusively in mechanical way with the help of managing handles, switching devices in a remotely controlled switching block must have solenoids for switch-on/off that receive control signal from the remote terminal unit (RTU) and forward them to the driving mechanism. Each circuit breaker has a solenoid for switching on and switching off, while switch disconnector have one solenoid for grounding out and switching on, and the other solenoid for switching off and grounding (switch disconnectors are threeposition switches). The only device in switching block without a solenoid for switching on/off is a ground connector in transformer field that can be operated manually, only. Circuit breakers and switch disconnectors can be operated Indication of voltage presence on the MV cables In order that the operator in the control centre is sure in performance of manipulation with switch disconnectors in MV cable fields, besides the information on switch position received via RTU, the operator has to know whether the MV cable is powered or not, That is enabled by a voltage indicator that forwards the signal of voltage presence to the RTU/control centre DC switchgear DC switchgear of the rated voltage 48VDC ensures uninterruptible power supply for all substation components. It consists of a battery produced in "dry fit" technology gel (dry battery), composed of four 12V blocks, of rated capacity 25Ah. The battery is charged over a rectifier produced in switching mode with input voltage 230V AC and output voltage 48V DC Power transformer protection Rated powers of power transformers in MV/LV substations are placed within the range from 400kVA to 1000kVA. With regard to power and importance in power system, these power transformers are protected from a short circuit (which is provided by digital relay), internal faults in the transformer (provided by Buchholz relay) while detection of transformer overheating is provided by contact thermometer. Buchholz relay and the contact thermometer have two levels of protection: the first level warns that it is necessary to perform certain measures for prevention of possible forthcoming fault, while the second level switches the circuit bracker off. In the case of activation of any protection, signal generated by auxiliary protection elements placed in a separate cubicle is forwarded to the RTU /control centre, and switched off the transformer circuit breaker in the following way: KON_Runjic_A1 Session 3 Paper No

4 Activation of the first level of the contact thermometer or the first level of Buchholz relay activates the following occurrence: The signal of activation of the protection is forwarded to the control centre. Activation of the second level of the contact thermometer or the second level of Buchholz relay or digital relay (short circuit protection) activates the following occurrence: Local signal - flashing lamp; The signal of activation of protection is forwarded to the RTU/control centre; Circuit breaker in the MV transformer field is switched off; As long as the signal of activation of the second level of protection or short circuit protection is present, the transformer circuit breaker control is blocked until the intervention team repairs the fault, and resets the protection activation signal Fault indication on the MV cables For realisation of the fault indication on the MV cables, a fault indicator is needed, placed in a separate cubicle and connected with signalling cables with three current sensors built on the end of the MV cable on the point where the cable enters the MV switchgear. Types of faults registered by the fault indicator are phase to phase and phase to earth faults, with a remark that the indicator does not distinguishes the type of the fault. After the fault detection, local fault signalization takes place and also, fault indicator forward signal to the RTU/control centre. The function of the fault indicator is to accelerate the procedure of MV network fault location and isolation. In the case that the remotely controlled cable substation 10(20)/0,4kV X is placed in a range of N stations counting from the supply point towards the end of the middle voltage cable, and a fault occurs "behind" the controlled cable substation X when we look at it from the feeding side, the fault current will flow through the controlled cable substation X towards the supply point where the appropriate protection will switch off circuit breaker. When the fault current flows through the controlled cable substation X the fault indicator will react and forward the signal towards the RTU/control centre and towards the local signalling blinking lamp. Based on the information on cable protection activation in the supply point and information on fault indicator activation in the substation X it can easily be concluded that the fault has happened "behind" the substation X and, in such a way, determine more precisely the location of the fault (Fig.2.). If the fault occurs "before" the substation X only the feeder protection in the supply point will be activated, while fault indicator in the substation X will not be activated what represents a sufficient number of information for making the decision that the fault has happened "before" the substation X (Fig.3.). 10(20)kV cable L FAULT Supply point substation 110/10kV x n-1 n 1,2,3...x...n-1,n - MV/LV substations Fig. 2: Fault on the MV cable "behind" monitored MV/LV substation in respect with the supply point (L local flashing lamp is on). 10(20)kV cable FAULT L Supply point substation 110/10kV x n-1 n 1,2,3...x...n-1,n - MV/LV substations Fig. 3: Fault on the MV cable "before" monitored MV/LV substation in respect with the supply point (L local flashing lamp is off) 2.5. Remote terminal unit DSSN 200 The main requirements regarding of MV/LV cable substations KON_Runjic_A1 Session 3 Paper No

5 remote control is to apply the control unit of acceptable price and appropriate capacity. In that sense the remote terminal unit (RTU) DSSN 200, shown in Fig.4, has been developed. It represents a central unit of the secondary system in the MV/LV cable substation and allows remote monitoring and control. Switching commands: opening and closing of switching devices in MV switchgear Measuring: DC supply voltage, load current of low voltage switchgear Indications: Double: open/close positions of switching devices in MV switchgear Single: activation of short circuit protection of the transformer activation of thermal protection of the transformer activation of Buchholz protection of the transformer. fault current (for each MV cable) charger fault battery fault operating mode local or remote the position on entrance door of the substation voltage presence (for each MV cable) Fig. 4. Remote terminal unit DSSN 200 RTU DSSN 200 includes 64 digital optically insulated inputs, 8 analogous inputs and 16 double digital outputs. Coloured LED's display the flow of communication with control centre and communication errors, while sets of LED's besides digital inputs, also have the function of a local indication of the states of switching devices and the other equipment in the MV/LV cable substation. The remote terminal unit comprises the integrated modem RM 1200 as well. RTU communication interface consists of 4 communication ports. The communication port COM, beside the local programming of the RTU processor, also enables working with an external modem. TEST port is used for local configuration of the modem that is performed, the same as programming of the processor, by portable PC. LINE port is used for connecting of the RTU to the communication line towards the control centre, while EXP port enables extending of the RTU. Remote programming of processor is possible from the control centre through the regular communication line. RTU DSSN 200 incorporates within a single unit all the functions necessary for remote MV/LV cable substation monitor and control, namely: collecting and processing of signals generated by equipment in substation, collecting and processing of analogous measuring, communication with control centre, executing of switch devices opening and closing commands from the control centre. Data exchanged between RTU DSSN 200 and control centre may be, in respect to their character, divided into: 3. CONTROL CENTRE Software and hardware for remote monitor and control of the MV/LV cable substations are placed in the control centre of DA "Elektra" Zagreb. The computer that consists of an industrial PC with a monitor performs the function of realtime remote control. SCADA software system PROZA R/F based on operation system UNIX and Windows environment has been implemented. The software system WINARH enables searching of SCADA archive based on different criteria and export of data to Windows platform, with no influences on SCADA system performance and operation function. Remote searching of SCADA archive via Web (Internet) is also possible. 4. COMMUNICATION SYSTEM During selection of a communication system that is used for communication between SCADA system and remote terminal units in MV/LV cable substations, the following facts have been considered: The plan is to control remotely about 100 substations Geographically speaking the substations are very dispersed Communication should be reliable, safe and highly available Communication with RTU's should be permanent Considering fundamental advantages and disadvantages of possible communication systems, the following have been selected: Utility owned telecommunication cable network and Radio communication system with a simplex channel (441,975MHz). KON_Runjic_A1 Session 3 Paper No

6 Utility owned telecommunication network has been used in the centre of the town, where it was built for needs of connection of primary substations (transformer stations 110/30kV, 110/10(20) kv, 30/10kV) and business buildings of DA "Elektra" Zagreb. All the locations that are not covered by the cable system, and that are in the first line locations on the periphery, are connected by radio connection with the control centre. It is important to mention that remote terminal units DSSN 200 are able to perform the function store and forward which make them to be digipitors for substations that are optically invisible from the control centre. Communication protocol is made in accordance with IEC standard CONCLUSION With realisation of the first phase of MV network automation precious knowledge and experience have been obtained and good bases for a wider application of distribution automation have been built. A more detailed financial analyses and optimisation algorithm will determine in which scope it would be necessary to realise MV network automation in the end. KON_Runjic_A1 Session 3 Paper No

MV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA)

MV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA) MV NETWORK AUTOMATION IN THE TOWN OF MILLION - ZAGREB (CROATIA) Runjic Darijo Koncar Power Plant and Electric Traction Engineering Inc. - Croatia darijo.runjic@koncar-ket.hr Sporec Marko, Strmecki Goran

More information

////// SUBSTATIONS. Control command and local Scada

////// SUBSTATIONS. Control command and local Scada ////// SUBSTATIONS Control command and local GENERAL INFORMATION The solution provided by Sécheron for local control and monitoring of traction substations is a significant step in supporting operations

More information

AUTOMATIC NETWORK RECONFIGURATION IN SPLIT AIRPORT pilot project of complete MV grid automation

AUTOMATIC NETWORK RECONFIGURATION IN SPLIT AIRPORT pilot project of complete MV grid automation AUTOMATIC NETWORK RECONFIGURATION IN SPLIT AIRPORT pilot project of complete MV grid automation KONČAR Power Plant and Electric Traction Engineering Inc. Zagreb Boris Brestovec, B.Sc.El. EXISTING AIRPORT

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

EARTH-FAULT AND SHORT-CIRCUIT INDICATOR TYPE EKL8001 / EKL8002 surface mounted

EARTH-FAULT AND SHORT-CIRCUIT INDICATOR TYPE EKL8001 / EKL8002 surface mounted EARTH-FAULT AND SHORT-CIRCUIT INDICATOR TYPE EKL8001 / EKL8002 surface mounted General description The earth-fault and short-circuit indicators type EKL8001 and type EKL8002 can be used in radial networks

More information

Grid Automation packaged solutions Optimal automation of medium voltage grids

Grid Automation packaged solutions Optimal automation of medium voltage grids Grid Automation packaged solutions Optimal automation of medium voltage grids Application principles of the Zone concept Grid Automation (GA) packaged solutions The zone concept offers a method to analyze

More information

MV Network Switchgear, Protection and Control

MV Network Switchgear, Protection and Control MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control

More information

IDS SAS. Station Automation System for Complex Applications

IDS SAS. Station Automation System for Complex Applications IDS SAS Station Automation System for Complex Applications IDS SAS The IDS SAS automation system for switchgear significantly reduces costs and efforts for the installation of secondary equipment and enables

More information

DC Substations / Supply Program

DC Substations / Supply Program DC Substations / Supply Program Sécheron offers an extensive range of products for DC electrification of public transport This document is intended to give a brief idea of our services, cubicles and systems

More information

AUTOMATION OF POWER DISTRIBUTION USING SCADA

AUTOMATION OF POWER DISTRIBUTION USING SCADA 1 2 ABSTRACT In every substation certain measurements, supervision, control, operation and protection functions are necessary. Traditionally these functions were performed manually by system operator from

More information

Development Of EMCS In Power Plants

Development Of EMCS In Power Plants Development Of EMCS In Power Plants Eng. H.S.Mohamed, Dr. S.A.Nagy,Dr. S.K.EL-Sayed Dept. of Electrical Engineering Al-Azhar University Cairo, Egypt h_alazhary@yahoo.com Abstract Recently improvement of

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

MEDIUM VOLTAGE RING MAIN UNIT

MEDIUM VOLTAGE RING MAIN UNIT MEDIUM VOLTAGE RING MAIN UNIT SFA-RM up to www.alfanar.com Contents 1 - Introduction 4 Introduction to SFA-RM 4 a - SFA - RM Solution 4 b - Quality Management 4 c - Quality Checks and Tests 4 d - Environmental

More information

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power 1. Abstract Dinesh Mithanthaya Design Manager, Horizon Power Higher capacity substation power transformers ( 5MVA),are

More information

INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS

INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS Konstantine Kolevatov, AS Tavrida Electric Export It has become a major task to provide uninterrupted electricity supply to customers and minimize the outage

More information

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB MO-067-EN Operation Manual MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB Transformer Substations Secondary Distribution Switchgear Primary Distribution Switchgear Protection

More information

PROTECTION RELAYS: INNOVATIONS FOR THE BENEFIT OF THE USER

PROTECTION RELAYS: INNOVATIONS FOR THE BENEFIT OF THE USER PROTECTION RELAYS: INNOVATIONS FOR THE BENEFIT OF THE USER C. Petit Schneider Electric, France Innovation in the field of medium voltage protection devices is accelerating to meet the ever growing demands

More information

NU-LEC. Loop Automation. Reclosers & Sectionalizers

NU-LEC. Loop Automation. Reclosers & Sectionalizers NU-LEC Loop Automation Reclosers & Sectionalizers 1 NU-LEC LLC NU-LEC LLC is a wholly unit of NU-LEC Industries, Pty, Ltd. Sales and service center for United States, Canada, and the Caribbean. Warehouse

More information

Monitoring Relays. SIRIUS 3UG Monitoring Relays for Stand-Alone Installation. Line monitoring. 8/62 Siemens IC Overview

Monitoring Relays. SIRIUS 3UG Monitoring Relays for Stand-Alone Installation. Line monitoring. 8/62 Siemens IC Overview Siemens AG 2010 Overview Benefits Can be used without auxiliary voltage in any network from 160 to 600 V AC worldwide thanks to wide voltage range Variably adjustable to overvoltage, undervoltage or range

More information

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title s Reference Number PCP 07 - (RIC Standard: EP 99 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

Small Generator Interconnection System Impact Study Report. Completed For Q0047

Small Generator Interconnection System Impact Study Report. Completed For Q0047 Small Generator Interconnection Completed For Q0047 Proposed Interconnection PacifiCorp s Existing Goshen Rigby 69 kv Line March 7, 2005 1.0 Description of the Generation Facility Q0047 ( Interconnection

More information

iswitch imotor Compact QR

iswitch imotor Compact QR PRODUCT DATA SHEET iswitch imotor Compact QR Features: Compact design Fit for purpose Suitable for 2 feeder switches Quick Release for manual operation High operation torque Operation monitoring (max.

More information

ekor.stp Programmable transfer unit General instructions IG-164-EN, version 04, 06/04/2017 LIB

ekor.stp Programmable transfer unit General instructions IG-164-EN, version 04, 06/04/2017 LIB Programmable transfer unit General instructions IG-164-EN, version 04, 06/04/2017 LIB CAUTION! When medium-voltage equipment is operating, certain components are live, other parts may be in movement and

More information

Protection relay for secondary distribution

Protection relay for secondary distribution Protection relay for secondary distribution Dual and Self powered Signalling with flag indicators High electromagnetic compatibility Events recorder and specific test menu Protection relay for secondary

More information

3M Sensored Cable Accessories for Underground Medium Voltage Distribution System

3M Sensored Cable Accessories for Underground Medium Voltage Distribution System 3M Sensored Cable Accessories for Underground Medium Voltage Distribution System 3M Electronics & Energy Business 1 Introduction The focus on enhancing reliability and efficiency of the power grid has

More information

VIP 40/45 VIP 400/410

VIP 40/45 VIP 400/410 40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered

More information

SCADA Training - T&D Automation

SCADA Training - T&D Automation SCADA Training - T&D Automation Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq This course covers all the

More information

MV overhead feeder automation

MV overhead feeder automation MV overhead feeder automation by John Cossey, Nu-Lec Industries Electricity providers are under immense pressure to improve the reliability of supply to their customers. Providers have a number of options

More information

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet S&C IntelliNode Interface Module Product Description Table of Contents Section Page Section Page Introduction Qualified Persons.......................... 2 Read this Instruction Sheet..................

More information

MV Circuit Breaker Control with PLC and SCADA

MV Circuit Breaker Control with PLC and SCADA 2017 Published in 5th International Symposium on Innovative Technologies in Engineering and Science 29-30 September 2017 (ISITES2017 Baku - Azerbaijan) MV Circuit Breaker Control with PLC and SCADA * 1

More information

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards)

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards) ////// SUBSTATIONS DC Switchgear Range Type MBS (IEEE/ANSI standards) GENERAL INFORMATION With a complete range of equipment and a leading expertise in DC traction power substations, Sécheron SA is a world

More information

Digital substations. Introduction, benefits, offerings

Digital substations. Introduction, benefits, offerings Digital substations Introduction, benefits, offerings Outline What is a digital substation? Benefits of digital substations ABB offering for digital substations Substation evolution June 26, 2017 Slide

More information

Distribution Management System Open++ Opera v.3.3. User Manual

Distribution Management System Open++ Opera v.3.3. User Manual Distribution Management System Open++ Opera v.3.3 User Manual 1MRS 751464-MUM Issued: 31.12.1999 Version: D/29.8.2003 Program Revision: 3.3D We reserve the right to change data without prior notice. User

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

GENERAL INFORMATION. The time it takes to find the fault The time it takes to repair the fault.

GENERAL INFORMATION. The time it takes to find the fault The time it takes to repair the fault. GENERAL INFORMATION Improve customer satisfaction Customer satisfaction is often difficult to measure. One of the key figures used to indicate the performance of a distribution network is SAIDI. SAIDI

More information

MODERN-PLANNING TOOLS CONNECTED WITH GEOGRAPHIC INFORMATION SYSTEM IN UTILITY COMPANY

MODERN-PLANNING TOOLS CONNECTED WITH GEOGRAPHIC INFORMATION SYSTEM IN UTILITY COMPANY MODERN-PLANNING TOOLS CONNECTED WITH GEOGRAPHIC INFORMATION SYSTEM IN UTILITY COMPANY Vybiralik Frantisek STE - Stredoceska Energetika a.s. - Czech Republic fvybiralik@ste.cz Josef Tlusty Technical University

More information

Arc protection relay. Features Three-phase overcurrent function. Application

Arc protection relay. Features Three-phase overcurrent function. Application Arc protection relay REA 10_ Page 1 Issued: May 1999 Status: New Data subject to change without notice Features Three-phase overcurrent function Loop-type or radial sensor fibre for arc detection Two high-speed

More information

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Small Generator Interconnection Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Proposed Interconnection PacifiCorp s 34.5-kV West Cedar Substation December 29, 2010 TABLE OF CONTENTS

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

Substation monitoring and control

Substation monitoring and control Substation monitoring and control Part 3. Substation Automation Author Peter Johansen, www.jomitek.dk In the preceding 2 articles the topics of measurement techniques for voltage and current has been covered.

More information

DISCERN SGAM Visio Template User Guide

DISCERN SGAM Visio Template User Guide Distributed Intelligence for Cost-Effective and Reliable Distribution Network Operation DISCERN SGAM Visio Template User Guide Author: OFFIS Date: 22.04.2016 www.discern.eu The research leading to these

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

Flexible Connections for DG Customers

Flexible Connections for DG Customers Flexible Connections for DG s Session 1b: Connections Paul Pretlove UK Power Networks Ruth Kemsley Wind Prospect In partnership with: Deployment Key outputs REQUIREMENTS Interface specification guidance

More information

ATS Automatic transfer switches Advanced version

ATS Automatic transfer switches Advanced version 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 ATS CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. ELECTRICAL AND MECHANICAL CHARACTERISTICS 2 5. CONFORMITY 4 6. EQUIPMENTS

More information

Integrated monitoring system for power transformers and hydro generators as an asset management and "smart grid" component. Miroslav Poljak, Ph.

Integrated monitoring system for power transformers and hydro generators as an asset management and smart grid component. Miroslav Poljak, Ph. Integrated monitoring system for power transformers and hydro generators as an asset management and "smart grid" component Miroslav Poljak, Ph.D Monitoring - Definition On-line monitoring system (MS) is

More information

UMG 20CM. 20 Channel Branch Circuit Monitoring Device with RCM

UMG 20CM. 20 Channel Branch Circuit Monitoring Device with RCM 20 Channel Branch Circuit Monitoring Device with RCM RCM Harmonics via analysis channel Alarm management GridVis Analysis software 20 current channels Interfaces / communication RS485 RTU Accuracy of measurement

More information

SICAM Products and Solutions for Energy Automation

SICAM Products and Solutions for Energy Automation SICAM Products and Solutions for Energy Automation Manfred Haslinger, Product Lifecycle Manager SICAM RTUs Josef Müllner, Product Lifecycle Manager SICAM TOOLBOX II siemens.at/future-of-energy SICAM Products

More information

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

Traction Power Systems / Program

Traction Power Systems / Program Traction Power Systems / Supply Program Sécheron offers an extensive range of products for DC electrification of public transport This document is intended to give a brief idea of our services, cubicles

More information

DNP Points List and Implementation

DNP Points List and Implementation S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) DNP Points List and Implementation Table of Contents Section Page Section Page Introduction...1 Status Points...2

More information

Installation. Symmetra MW II kw 400 V. UPS Summary Normal Normal

Installation. Symmetra MW II kw 400 V. UPS Summary Normal Normal UPS Summary ~ ~ Normal Normal Installation Symmetra MW II 600 kw 400 V Contents Safety... IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS.......................... Symbols used in this guide.........................

More information

CONTENTS... 2 COMTROLL SAS. SURVEILLANCE AND AUTOMATION SYSTEM...

CONTENTS... 2 COMTROLL SAS. SURVEILLANCE AND AUTOMATION SYSTEM... GENERAL INFORMATION Contents CONTENTS... 2 COMTROLL SAS. SURVEILLANCE AND AUTOMATION SYSTEM... 3 COMMUNICATION... 4 BUILDING-BLOCKS... 5 NETTROLL AND NETDRAW... 5 NETALERT... 6 NETGRAPH... 7 COMTROLL OUTSTATIONS...

More information

Loop Automation. Technical Manual for the ADVC Controller Range

Loop Automation. Technical Manual for the ADVC Controller Range Loop Automation Technical Manual for the ADVC Controller Range Contents List of Figures 5 List of Tables 7 Acronyms 7 Symbols 7 Introduction 8 About this Manual 8 ADVC Controller Firmware Version 9 WSOS

More information

KUUMIC OY DATA TRANSFER FALLBACK SWITCH KU113. Technical Reference

KUUMIC OY DATA TRANSFER FALLBACK SWITCH KU113. Technical Reference FALLBACK SWITCH Technical Reference CONTENTS 1. GENERAL...1 1.1. INTRODUCTION...1 1.1.1. Basic functions...1 1.2. TECHNICAL SPECIFICATIONS...3 1.2.1. CONNECTORS...3 1.2.2. LED INDICATORS...5 1.2.3. JUMPERS

More information

How smart can the grid really be?

How smart can the grid really be? How smart can the grid really be? by Dale Pudney, HVT Power Systems and Luo Wei, NR Electric With the improvement of electronic communications and computing technology, it becomes possible to integrate

More information

IntelliTeam II Automatic Restoration System

IntelliTeam II Automatic Restoration System No system is too complex to automate with... IntelliTeam II Automatic Restoration System Introduced in 1997, the IntelliTeam Automatic Restoration System was the first product of its kind. Using peer-to-peer

More information

ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS

ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS Presentation by: RANA NASIR ALI General Manager, Power Plants Projects, at PITCO November 02, 2017 ELECTRICAL PLANT CONCEPT The electrical equipment, depending

More information

Microprocessor protection and automation devices

Microprocessor protection and automation devices Microprocessor protection and automation devices THE ТЭМП 2501 MICROPROCESSOR PROTECTION TERMINALS It is well known that microprocessor protection devices have indisputable advantages over electromechanical

More information

Research on Technologies in Smart Substation

Research on Technologies in Smart Substation Available online at www.sciencedirect.com Energy Procedia 12 (2011) 113 119 ICSGCE 2011: 27 30 September 2011, Chengdu, China Research on Technologies in Smart Substation Hongwei Li *, Lixin Wang Technology

More information

TSC Schneider-PDI Agenda

TSC Schneider-PDI Agenda TSC Schneider-PDI Agenda General Electrical Power Layouts and Equipment Single Phase UPS s Three Phase UPS s Trends In Data Center Power Distribution Data Center Cooling Trends and Products Jim Tubbesing

More information

SP Energy Networks Business Plan

SP Energy Networks Business Plan SP Energy Networks 2015 2023 Business Plan Updated March 2014 Annex 132kV Substation Plant Strategy SP Energy Networks 29 March 2014 March 2014 Issue Date Issue No. Document Owner Amendment Details 17th

More information

Zartek. CDP-808 Two Button Wireless Intercom Installers Manual

Zartek. CDP-808 Two Button Wireless Intercom Installers Manual Zartek CDP-808 Two Button Wireless Intercom Installers Manual ZA-614 Two Button Gate station including power supply, relay board and external antenna ZA-613 Handsets with charger ZA-613-E Handsets with

More information

Integral solution for photovoltaic plants supervision

Integral solution for photovoltaic plants supervision Integral solution for photovoltaic plants supervision Energy efficiency technology Efficiency combined with energy control System supplies Project development Start-up Remote maintenance 2 Solar photovoltaic

More information

EFASOLAR PVStation Solutions

EFASOLAR PVStation Solutions www.efacec.com EFASOLAR PVStation Solutions EFASOLAR PVStation EFASOLAR PVStation Solutions 0,5 MW 1 x EFASOLAR 50 0,50 MW 1 x EFASOLAR 500M 1 MW 1,46 MW Efacec is a century-long experienced company in

More information

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with

More information

Synchronous switching of distribution sub networks

Synchronous switching of distribution sub networks Synchronous switching of distribution sub networks Paul Stergiou ConEdison USA Manuel P Pimenta, - ConEdison USA Sergio A Rodriguez ConEdison USA Thomas Horan ConEdison USA Andre Smit- Siemens Industry

More information

Automation System Solutions

Automation System Solutions Automation System Solutions Automation Systems for Power Grid, Power Plant and Industries NR Electric Corporation Automation for Power Grid Substation Automation System Conventional Substation Automation

More information

ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER

ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER smallhydro PRIME ENGINEERING LIMITED IS AN ELECTRICAL ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, IMPLEMENTATION AND MAINTENANCE. OUR TEAM OF PROFESSIONALS

More information

Lecture 6 Substation Automation Systems

Lecture 6 Substation Automation Systems Lecture 6 Substation Automation Systems 1 Course map 2 Contents of the Lecture Part 1 Substation Automation Components & Architectures Substation Automation Functions Communication within the Substation

More information

MINER-S Station Controller

MINER-S Station Controller MINER-S Station Controller Substation Automation MINER-S Station Controller The MINER-S Station Controller is a SCADA enabled fixed point remote terminal unit (RTU) with a data concentrator, event reporter,

More information

IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7

IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7 IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7 LINETROLL 110Eµ 8 LINETROLL 111K 9 LINETROLL L400D 10

More information

ES Energy Saver Product Ranges 90Amp 6000Amp

ES Energy Saver Product Ranges 90Amp 6000Amp Product Ranges 90Amp 6000Amp Energy Saving from Voltage Reduction The Digit@l ES Energy Saver is a specially designed voltage stabilizer that allows for the voltage received by the distribution system

More information

S&C 6801M Automatic Switch Operator

S&C 6801M Automatic Switch Operator S&C 6801M Automatic Switch Operator for Overhead Distribution Switches and Disconnects Simple, Economical Switch Automation S&C s 6801M Automatic Switch Operators make it easy to automate new or existing

More information

UMG 20CM. UMG 20CM 20 Channel Branch Circuit Monitoring Device with RCM. Harmonics via analysis channel RCM. Alarm management.

UMG 20CM. UMG 20CM 20 Channel Branch Circuit Monitoring Device with RCM. Harmonics via analysis channel RCM. Alarm management. RCM Harmonics via analysis channel Alarm management GridVis Analysis software 20 current channels 20 Channel Branch Circuit Monitoring Device with RCM Interfaces / communication RS485 RTU Accuracy of measurement

More information

Power Transmission Division Link between power generation and distribution

Power Transmission Division Link between power generation and distribution Power Transmission Division Link between power generation and distribution Seite 4 High Voltage Substations Schemes, Devices and Types of AIS Installation Content Link between power generation and distribution

More information

AUTOMATION OF DISTRIBUTION KIOSKS TECHNICAL AND FINANCIAL EVALUATION - "TYPICAL CASE STUDY"

AUTOMATION OF DISTRIBUTION KIOSKS TECHNICAL AND FINANCIAL EVALUATION - TYPICAL CASE STUDY AUTOMATION OF DISTRIBUTION KIOSKS TECHNICAL AND FINANCIAL EVALUATION - "TYPICAL CASE STUDY" Mohamed Khaled El-Sayed Alexandria Electricity Distribution Company - AEDC Egypt khaled_mks@hotmail.com 1-INTRODUCTION

More information

Substation SCADA Monitoring

Substation SCADA Monitoring Substation SCADA Monitoring Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Substations are a critical component

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

Ground Breaking MV Switchgear

Ground Breaking MV Switchgear ISO 9001:2008 and ISO 14001:2004 certification ETALON Ground Breaking MV Switchgear Etalon is vacuum switchgear that fits most of the switchgear applications available and meets the most strict safety

More information

DNP Points List and Implementation for Universal Controls

DNP Points List and Implementation for Universal Controls S&C 6800 Series Automatic Switch Control DNP Points List and Implementation for Universal Controls Table of Contents Section Page Section Page DNP Points List for 6801 Universal Controls...1 6801 Status

More information

COMPANY PROFILE. Kontrolmatik has accomplished local and international projects with great success. Some of fields that KONTROLMATIK serves,

COMPANY PROFILE. Kontrolmatik has accomplished local and international projects with great success. Some of fields that KONTROLMATIK serves, MOBILE SUBSTATIONS COMPANY PROFILE Kontrolmatik has accomplished local and international projects with great success. As one of the leading engineering companies in Turkey, Kontrolmatik has successfully

More information

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A AUTOMATION MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A GRID Note: The technical manual for this device gives instructions for its installation, commissioning,

More information

MV Network Managment Fault tracking, monitoring and control. Easergy Range Merlin Gerin

MV Network Managment Fault tracking, monitoring and control. Easergy Range Merlin Gerin MV Network Managment Fault tracking, monitoring and control Easergy Range Merlin Gerin References Schneider Electric Industries SAS Postal address MV department F-38050 Grenoble Cedex 9 Tél. : +33 (0)4

More information

Blueprint Data Center

Blueprint Data Center Systems and Applications for Data Center Siemens Industy 1. Overview / Purpose In EM EA the datacenter market is seen as one of the fastest growing of the energy businesses. This blueprint is designed

More information

SICAM A8000 Series. Operation, telecontrol, and automation in the smallest spaces. siemens.com/sicam-a8000

SICAM A8000 Series. Operation, telecontrol, and automation in the smallest spaces. siemens.com/sicam-a8000 SICAM A8000 Series Operation, telecontrol, and automation in the smallest spaces siemens.com/sicam-a8000 4 Applications 5 Scalability in the application 6 Highlights at a glance 8 The entire product family

More information

POWER GRID AUTOMATION. Pág.. n. RMU Automation

POWER GRID AUTOMATION. Pág.. n. RMU Automation POWER GRID AUTOMATION RMU Automation Distribution Network Non-Controlled Secondary Distribution Systems Distribution Network RMU Automation - Levels RMU Automation - RTU / FRTU SMART CONTROLLER Monitoring

More information

Specification Voltage Limiting Device

Specification Voltage Limiting Device Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering,

More information

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note www.siemens.com/protection SIPROTEC 5 Application Note SIP5-APN-001: Properties and Functional Structure Answers for infrastructure and cities SIPROTEC 5 Properties SIPROTEC 5 - Application: SIP5-APN-001

More information

CABLETROLL 3 CABLETROLL CABLETROLL CABLETROLL CABLETROLL LED-2 5 CABLETROLL CABLETROLL REMOTE INDICATION 7

CABLETROLL 3 CABLETROLL CABLETROLL CABLETROLL CABLETROLL LED-2 5 CABLETROLL CABLETROLL REMOTE INDICATION 7 CABLETROLL 3 CABLETROLL 2310 4 CABLETROLL 2320 4 CABLETROLL 2330 5 CABLETROLL 2350 5 LED-2 5 CABLETROLL 2410 6 CABLETROLL 2440 6 REMOTE INDICATION 7 The CableTroll indicators are fault current detectors

More information

DNP Points List and Implementation

DNP Points List and Implementation S&C 6800 Series Automatic Switch Control DNP Points List and Implementation Table of Contents Section Page Section Page DNP Points List for 6801 Controls...1 6801 Status Points...2 6801 Double-bit Status

More information

coal mining Solutions

coal mining Solutions coal mining Solutions Ampcontrol connects you to coal mining solutions For nearly 50 years Ampcontrol has designed, manufactured and delivered integrated electrical solutions that improve safety, maintain

More information

REYROLLE 2RMLG. Operating Recommendations

REYROLLE 2RMLG. Operating Recommendations 2RMLG Operating Recommendations SAFETY The commissioning and maintenance of protection equipment should only be carried out by skilled personnel trained in protective relay operation and capable of observing

More information

Presented by: Oscar Araujo Photovoltaic Solutions Manager. 4 th Canadian German Solar PV Conference March 2 nd 2011

Presented by: Oscar Araujo Photovoltaic Solutions Manager. 4 th Canadian German Solar PV Conference March 2 nd 2011 Photovoltaic Solutions Make the most of your solar PV project Presented by: Oscar Araujo Photovoltaic Solutions Manager 4 th Canadian German Solar PV Conference March 2 nd 2011 Agenda Solutions for Renewable

More information

DISTRIBUTION CONTROL CENTER OF DISTRIBUTION UTILITY "ELEKTROSTRUMICA", STRUMICA (THE REPUBLIC OF MACEDONIA)

DISTRIBUTION CONTROL CENTER OF DISTRIBUTION UTILITY ELEKTROSTRUMICA, STRUMICA (THE REPUBLIC OF MACEDONIA) DISTRIBUTION CONTROL CENTER OF DISTRIBUTION UTILITY "ELEKTROSTRUMICA", STRUMICA (THE REPUBLIC OF MACEDONIA) Konar-Inženjering za energetiku i transport d.d., Fallerovo šetalište 22, Zagreb, Hrvatska E.

More information

MNS Platform, low voltage systems Rear Access Power Motor Control Center. Alberto Carini, Global Product Manager

MNS Platform, low voltage systems Rear Access Power Motor Control Center. Alberto Carini, Global Product Manager MNS Platform, low voltage systems Rear Access Power Motor Control Center Alberto Carini, Global Product Manager MNS Platform, low voltage systems Add Value to our customers Sales After sales Maximum safety;

More information

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and

More information

Products for increased power system availability

Products for increased power system availability Products for increased power system availability P R O D U C T G U I D E Fault detectors and protective relays Protrol s products are designed for reliable and cost-effective performance monitoring and

More information

Small hydro power plant automation. Oswaldo Kaschny Schneider Electric Brazil CDI Power

Small hydro power plant automation. Oswaldo Kaschny Schneider Electric Brazil CDI Power Small hydro power plant automation Oswaldo Kaschny Schneider Electric Brazil CDI Power Small Hydroelectric: Power and Control solution Operation Centre Turbine Measurement board Power meters And quality

More information

RT4F-120V/20A-WAC RECTIFIER

RT4F-120V/20A-WAC RECTIFIER The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with

More information