1 Galaxy 7000 Shore Connection 500 kva Operation 04/2016

2 Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this guide are the sole property of Schneider Electric SA and its subsidiaries. They may not be used for any purpose without the owner's permission, given in writing. This guide and its content are protected, within the meaning of the French intellectual property code (Code de la propriété intellectuelle français, referred to hereafter as "the Code"), under the laws of copyright covering texts, drawings and models, as well as by trademark law. You agree not to reproduce, other than for your own personal, noncommercial use as defined in the Code, all or part of this guide on any medium whatsoever without Schneider Electric's permission, given in writing. You also agree not to establish any hypertext links to this guide or its content. Schneider Electric does not grant any right or license for the personal and noncommercial use of the guide or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this publication.

3 Shore Connection 500 kva Table of Contents Important Safety Instructions SAVE THESE INSTRUCTIONS...5 Safety Precautions...6 Overview...7 User Interface...7 Menu Tree...8 Display Symbols...9 Configuration...10 Configure the Display Language...10 Configure the Date and Time Set the Dry Contacts...12 Access the Parameters...12 Available Commands and Status Conditions...12 Set Up a Contact...14 Other Available Settings...14 Personalise the GFC...15 Access the Personalisation Parameters...15 Available Personalisation Commands...15 Operation...16 Operating Modes...16 Normal Mode...16 Standby Mode...16 Operation Procedures...16 Start Up the GFC...16 Isolate an Installation...17 Transfer the GFC Back to Normal AC Power...18 GFC Monitoring...19 Overview...19 PLC Setting...20 Building Management System Setting...20 Remote Monitoring System Setting (Option)...20 Maintenance...21 Life Cycle Monitoring (LCM)...21 Disable the Life Cycle Monitoring (LCM) Function...21 Troubleshooting...22 General Status LEDs...22 Buzzer...22 Mimic Panel

4

5 Important Safety Instructions SAVE THESE INSTRUCTIONS Important Safety Instructions SAVE THESE INSTRUCTIONS Shore Connection 500 kva Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following safety messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of this symbol to a Danger or Warning safety message indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages with this symbol to avoid possible injury or death. DANGER DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. Failure to follow these instructions will result in death or serious injury. WARNING WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. Failure to follow these instructions can result in death, serious injury, or equipment damage. CAUTION CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Failure to follow these instructions can result in injury or equipment damage. NOTICE NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this type of safety message. Failure to follow these instructions can result in equipment damage. Please Note Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

6 Shore Connection 500 kva Important Safety Instructions SAVE THESE INSTRUCTIONS A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved. Safety Precautions DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH All safety instructions in this document must be read, understood and followed. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH After the UPS system has been electrically wired, do not start up the system. Start-up must only be performed by Schneider Electric. Failure to follow these instructions will result in death or serious injury

7 Overview Overview Shore Connection 500 kva User Interface A. Graphical display B. Output ON C. Minor or environmental alarm LED D. Major alarm E. Help/buzzer off button F. Function keys G. Main menu button H. OFF button. I. ON button. J. Voltage on GFC load K. Inverter LED L. PFC LED

8 Shore Connection 500 kva Overview Menu Tree Main Menu Measurements Alarms History Settings Controls Measurements Alarms History Settings Controls Load Inverter Normal AC Time-stamping Statistics since last maintenance Statistics since the commissioning Language Date and time Contrast Buzzer volume Temperature units Screensaver Personalisation 1 Output voltage Dry contacts Password Reset alarm Enable PLC control mode Connect the load LED test Reset statistics Disable LCM signalization Disable OOL signalization Confirm number of available GFC Personalisation Automatic start Rated Output voltage Frequency Rated Output 1. Only available if no PLC is installed

9 Overview Shore Connection 500 kva Display Symbols Vertical selection Delete Other selection Measurements Enter/confirm Increase Next page Decrease Previous page Save Details Alarm History Details on each module Return to previous screen/menu

10 Shore Connection 500 kva Configuration Configuration Configure the Display Language 1. Press the button. 2. Press the button until Settings is highlighted, and press the button. 3. Press the button until Languages is highlighted, and press the button. 4. Press the button until the desired language is highlighted, and press the button. 5. Press the button

11 Configuration Shore Connection 500 kva Configure the Date and Time NOTE: For event time-stamping, the correct date and time must be set. 1. Press the button. 2. Press the button until Settings is highlighted and press the button. 3. Press the button until Date and time is highlighted and press the button. 4. Press the and buttons until the desired date is displayed and press the button. 5. Repeat step 3 to set the month, year, hour, minutes, and seconds. 6. Press the button. 7. Press the button

12 Shore Connection 500 kva Configuration Set the Dry Contacts Access the Parameters NOTE: The default password (factory set) is Press the button. 2. Press the button until Settings is highlighted, and press the button. 3. Press the button until Dry contacts is highlighted, and press the button. 4. Press the and buttons until the first digit of the password is displayed, and press the button. 5. Repeat step 4 to select the second and third digits of the password. NOTE: The default password (factory set) is Press the button. Available Commands and Status Conditions Available Status Conditions Outputs O1 to O6 NOTE: If PLC is used, outputs O1 and O2 are reserved for GFC state. A GFC state is encoded in 2 bits: GFC state Bit value for output O1 Bit value for output O2 Standby (GFC power converter off; electronic only powered) OFF (GFC started, output static switch opened) ON (GFC connected to the load) Major alarm or powered off (maintenance mode) Closed contact. Output relay contact is normally open

13 Configuration Shore Connection 500 kva Charger inoperable Check the GFC Environment alarm EPO activated Fuse blown General alarm Inverter inoperable Load protected Overload PFC inoperable Phase rotation inoperable Maintenance position GFC fan inoperable Available commands Inputs I1 to I4 If PLC is used, inputs I1, I2, and I3 are forced for following commands: Inputs Commands Activation I1 PLC start On rising edge when relay contact closes I2 PLC standby On rising edge when relay contact closes I3 Dry contact output forced in 50 Hz On level when relay contact is closed Input state change is validated when the input state is stable for 200 ms. Customer alarm 1 Customer alarm 2 Customer alarm 3 Customer alarm 4 Limit input power during operation on genset power

14 Shore Connection 500 kva Configuration Set Up a Contact The example shows a setup of an output contact. The procedure is identical for an input contact. It is necessary to first access the parameters (See Access the Parameters, page 12.) 1. Press the button until Output is highlighted and press the button. 2. Press the button until the contact to be set is highlighted and press the button. 3. Press the button until the desired status condition is highlighted and press the button. 4. Press the and buttons until the desired delay is displayed and press the button. 5. Press the button. 6. Press the button until Yes is highlighted and press press the button. 7. Press the button. Other Available Settings Settings Contrast Buzzer volume Possible choices 0 to 100% in 10% steps 0 to 100% in 10% steps Temperature units C or F Screensaver Output voltage Default welcome screen, alarms, normal AC measurements +/-3% in 0.5 V steps Password New password (the default value is 000)

15 Configuration Shore Connection 500 kva Personalise the GFC Access the Personalisation Parameters Only available if PLC is not used. Before starting, the GFC must be in maintenance bypass mode. 1. Press the button. 2. Press the button until Settings is highlighted and press the button. 3. Press the button until Personalisation is highlighted and press the button. 4. Press the and buttons until the first digit of the password is displayed and press the button. 5. Repeat step 4 to set the second and third digits of the password. 6. Press the button. Available Personalisation Commands Before starting the personalisation sequence, the GFC must be stopped. Standard personalisation functions 3 Factory set-up Other possible choices Automatic start Disabled Enabled Rated output voltage 400 V 380 V, 415 V, 440 V Rated output frequency 60 Hz 50 Hz Load level warning 4 100% 40 to 100% in 10% steps 3. Some personalisation functions may not be available depending on your installation. 4. These personalisation settings do not require the GFC to be stopped

16 Shore Connection 500 kva Operation Operation NOTE: Only trained and certified personnel must carry out the following operation procedures. Operating Modes Normal Mode Normal AC source is available, GFC coupled: Load powered LED (A) is ON. The load is powered by the GFC. Standby Mode Normal AC source is available, GFC is stopped: Minor or environmental alarm LED (B) is orange and load LED (C) is orange. The buzzer sounds intermittently. The load is not powered by the GFC. Operation Procedures Start Up the GFC CAUTION HAZARD OF INJURY OR EQUIPMENT DAMAGE Connection of power and control cables must be carried out and checked by qualified personnel. Failure to follow these instructions can result in injury or equipment damage. The doors of the cabinets must be open. Before starting the sequence, the switches must be in off position, as indicated below:

17 Operation Shore Connection 500 kva GFC Cabinets The circuit breakers upstream of the normal AC line must be open. The GFC must be shut down; the load is not powered. 1. Close the upstream circuit breakers on the normal AC lines and external power source ventilation. 2. Perform the following steps on all GFC cabinets: a. Turn the Q1 switch to ON. b. Check that the PFC LED is green 3. Turn the Q5N switches on all GFC cabinets to ON. 4. Check the presence of all GFC units on the display of one of the GFC units. 5. Press the button. 6. Close the doors. 7. Press the ON button on all the GFC units. The load is powered by the GFC system when enough units are ready and all LEDs are green. Isolate an Installation NOTE: The GFC must be ON. At the end of this procedure, the load is no longer powered with AC power

18 Shore Connection 500 kva Operation 1. Perform the following steps on the first GFC cabinet: a. Press the OFF button for 3 seconds. The load is powered by the other GFC unit. If there is no other GFC unit, the load is no longer powered. b. Open the door. 2. Perform the following steps on the first GFC cabinet: a. Turn the Q5N switch to OFF. b. Turn the Q1 switch to OFF. 3. Press the OFF button of the last GFC cabinet for 3 seconds. The load is no longer powered. 4. Perform the following steps on the last GFC cabinet: a. Turn the Q1 switch to OFF. b. Turn the Q5N switch to OFF. 5. Open the upstream circuit breaker for external power source for ventilation. Transfer the GFC Back to Normal AC Power The doors of the cabinets must be open. Before starting the sequence, the switches must be in off position, as indicated below: GFC Cabinets 1. Close the upstream circuit breakers on the normal AC lines and external power source ventilation

19 Operation Shore Connection 500 kva 2. Perform the following steps on all GFC cabinets: a. Turn the Q1 switch to ON. b. Check that the PFC LED is green. 3. Turn the Q5N switches on all GFC cabinets to ON. 4. Check the presence of all GFC units on the display of one of the GFC units. 5. Press the button. 6. Close the doors. 7. Press the ON button on all the GFC units. The load is powered by the GFC system when enough units are ready and all LEDs are green. GFC Monitoring Overview A. Remote Monitoring System (RMS) network via ethernet 5 B. Remote Monitoring System (RMS) network via modem C. PLC network or Building Management System (BMS) network via Modbus D. PLC I/O network E. PLC F. Hub G. RMS center 5. For monitoring via web, please consult the after-sales support or the local office

20 Shore Connection 500 kva Operation PLC Setting PLC setting is done by a Schneider Electric field service engineer during installation. Building Management System Setting For building management system setting, refer to: AP9635 network management card user s guide Modbus register map Remote Monitoring System Setting (Option) Remote monitoring system setting is done by a Schneider Electric field service engineer during installation

21 Maintenance Maintenance Shore Connection 500 kva Life Cycle Monitoring (LCM) The life cycle monitoring function provides GFC maintenance advice. A. Environment alarm LED B. Enter button Press the Enter button to display the LCM ALERT information Alarm details LCM alarm details End of warranty. Check recommended. End of wearing parts service life. Technical check recommended. Description Contact Schneider Electric to extend the optimum operating period of your installation. The parts of the product that are subject to wear should be checked. Contact Schneider Electric. Disable the Life Cycle Monitoring (LCM) Function 1. Follow one of the procedures when LCM messages are displayed: For temporary disabling: Press the ESC button. The message will be repeated twice every 30 days 6. For complete disabling of LCM messages: Select Disable LCM indications in the Controls menu. NOTE: You will no longer be informed of LCM events related to your GFC. 6. Default setting

22 Shore Connection 500 kva Troubleshooting Troubleshooting An alarm is present when: at least one LED is red at least one LED is orange the buzzer beeps If an anomaly occurs, the display instructs the operator on the required action. General Status LEDs The load powered LED (A) is ON and green: The load is powered. The major alarm LED (B) goes ON red: The load is not powered. Follow the displayed instructions. The environment alarm LED (C) is ON and orange: Minor or environment alarm. The load is still powered. Follow the displayed instructions. Buzzer Stop the buzzer by pressing the Stop buzzer button (A). Mimic Panel One of the following LEDs goes ON red: A. PFC is inoperable

23 Troubleshooting Shore Connection 500 kva B. Inverter is inoperable. C. Load is not powered. One of the main GFC functions is unoperable. Follow the displayed instructions

24 Printed in. Schneider Electric Schneider Electric 35 rue Joseph Monier Rueil Malmaison France + 33 (0) As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication Schneider Electric. All rights reserved

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/ Symmetra PX 160 Maintenance Bypass Enclosure Installation 05/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

StruxureWare. Power Monitoring Expert 8.2 Hierarchy Manager Help Topics 7EN /2017

StruxureWare. Power Monitoring Expert 8.2 Hierarchy Manager Help Topics 7EN /2017 StruxureWare Power Monitoring Expert 8.2 Hierarchy Manager Help Topics 7EN52-0413-00 03/2017 Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

Symmetra MW kw 380/400/480 V Operation. UPS System with External Bypass 01/

Symmetra MW kw 380/400/480 V Operation. UPS System with External Bypass 01/ Symmetra MW 800 1600 kw 380/400/480 V Operation UPS System with External Bypass 01/2017 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider

More information

Galaxy VX. UPS System Operation 02/

Galaxy VX. UPS System Operation 02/ Galaxy VX Operation 02/2018 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this guide are the

More information

Galaxy VM. System Bypass Cabinet 640 kva Installation GVMSBC640KHEL 06/2016.

Galaxy VM. System Bypass Cabinet 640 kva Installation GVMSBC640KHEL 06/2016. Galaxy VM System Bypass Cabinet 640 kva Installation GVMSBC640KHEL 06/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric

More information

Galaxy VM kva 480 V, kva 400 V. Operation 05/2014.

Galaxy VM kva 480 V, kva 400 V. Operation 05/2014. Galaxy VM 160 225 kva 480 V, 160 200 kva 400 V Operation 05/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

MultiTech Router Commissioning for Com X 200/210/510

MultiTech Router Commissioning for Com X 200/210/510 Knowledge Base 7EN42-0166 05/2017 MultiTech Router Commissioning for Com X 200/210/510 This document describes installation recommendations and how to commission a MultiTech rcell Series router for use

More information

Smart Mode Measurements

Smart Mode Measurements Smart Mode Measurements Technical Reference for Maintenance PME 7.2.3 V1.0 Safety Information Important Information Read these instructions carefully before trying to install, configure, or operate this

More information

StruxureWare Power Monitoring Expert 8.0 Data Center Edition

StruxureWare Power Monitoring Expert 8.0 Data Center Edition StruxureWare Power Monitoring Expert 8.0 Data Center Edition Breaker Performance Guide 7EN02-0367-01 06/2015 Safety information Important information Read these instructions carefully and look at the

More information

Change Report Colors and Logo

Change Report Colors and Logo How to Change Report Colors and Logo Report Developer Kit V1.0 Safety Information Important Information Read these instructions carefully before trying to install, configure, or operate this software.

More information

TeSys Programmer. Firmware Update Utility for LTMR & LTMCU User Manual. January 2017

TeSys Programmer. Firmware Update Utility for LTMR & LTMCU User Manual. January 2017 TeSys Programmer Firmware Update Utility for LTMR & LTMCU User Manual January 2017 Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

PowerLogic ION7550 RTU option

PowerLogic ION7550 RTU option 70052-0213-02 PRODUCT OPTION 01/2011 PowerLogic ION7550 RTU option The PowerLogic ION7550 Remote Terminal Unit (RTU) option is designed for data acquisition from WAGES (water, air, gas, electricity, steam)

More information

Acti 9 Communication System

Acti 9 Communication System Acti 9 Communication System Diagnostics User Manual 05/2012 DOCA0042EN-00 www.schneider-electric.com This document contains general descriptions and/or general technical specifications of the products

More information

Conext CL-60 Inverter Firmware Upgrade Process

Conext CL-60 Inverter Firmware Upgrade Process Conext CL-60 Inverter Firmware Upgrade Process http://solar.schneider-electric.com 976-0380-01-01/B August 2017 Application Note EXCLUSION FOR DOCUMENTATION UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER

More information

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN Important Safety Information Read the instructions carefully to become familiar with the equipment before trying to install, operate, service

More information

EcoStruxure Power Commission Installation Guide

EcoStruxure Power Commission Installation Guide EcoStruxure Power Commission DOCA0134EN 03/2019 EcoStruxure Power Commission Installation Guide 03/2019 DOCA0134EN-04 www.schneider-electric.com The information provided in this documentation contains

More information

Power Management Module

Power Management Module Power Management Module 30 300 kva Installation and Operation 10/2017 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

StruxureWare Power Monitoring 7.0

StruxureWare Power Monitoring 7.0 StruxureWare Power Monitoring 7.0 OPC Server Assistant 7EN02-0309-00 02/2012 Contents Safety information 5 Introduction 7 Scope 7 Optional OPC Server License 8 OPC Server Type 8 OPC Server Support 9 Creating/Updating

More information

Electrical network protection Sepam series 20 Sepam series 40 Quick start

Electrical network protection Sepam series 20 Sepam series 40 Quick start 03146790FE+01+NP00000000 Electrical network protection Sepam series 20 Sepam series 40 Quick start PE50465 Storage Sepam may be stored in its original packaging in a closed sheltered location: b ambient

More information

MGE Galaxy kva 208V. Operation

MGE Galaxy kva 208V. Operation MGE Galaxy 4000 40 75 kva 208V Operation Table of Contents About This Manual... 1 Companion Manuals... 1 Find Updates to this Manual... 1 Overview... 2 Operator Interface Keys and Indicators... 2 LED

More information

How Can I. Integrate a Third-Party Modbus Device with PowerSCADA Expert? System Technical Note PowerSCADA Expert V1.0

How Can I. Integrate a Third-Party Modbus Device with PowerSCADA Expert? System Technical Note PowerSCADA Expert V1.0 How Can I Integrate a Third-Party Modbus Device with PowerSCADA Expert? System Technical Note PowerSCADA Expert V1.0 Safety Information Important Information Read these instructions carefully before trying

More information

PowerLogic High Density Metering System 1-Meter Enclosure

PowerLogic High Density Metering System 1-Meter Enclosure PowerLogic High Density Metering System 1-Meter Enclosure Installation Guide 63230-508-211A1 Safety information PowerLogic High Density Metering System 1-Meter Enclosure Important information Read these

More information

Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit

Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit Important Safety Messages SAVE THESE INSTRUCTIONS - This section contains important instructions that should be followed during installation

More information

Symmetra PX. 250/500 kw 400/480 V Single and Parallel Operation 10/

Symmetra PX. 250/500 kw 400/480 V Single and Parallel Operation 10/ Symmetra PX 250/500 kw 400/480 V Single and Parallel Operation 10/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

How can I. Implement a cost-effective energy monitoring system for small to medium buildings using Com'X 510?

How can I. Implement a cost-effective energy monitoring system for small to medium buildings using Com'X 510? How can I Implement a cost-effective energy monitoring system for small to medium buildings using Com'X 510? Tested Validated Documented Architecture Develop your project Important Information Notice

More information

Installing Powerlink NF3500G4 Controllers

Installing Powerlink NF3500G4 Controllers Installing Powerlink NF3500G4 Controllers for Use with Powerlink Systems RETAIN FOR FUTURE USE Installing Powerlink NF3500G4 Controllers 63249-420-374A3 Instruction Bulletin 09/2015 2 2015 Schneider Electric.

More information

5521 Potentiometer Analog Input Module

5521 Potentiometer Analog Input Module 55 Potentiometer Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

5504 Thermocouple Analog Input Module

5504 Thermocouple Analog Input Module 550 Thermocouple Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

PowerLogic ION7300 Series

PowerLogic ION7300 Series PowerLogic ION7300 Series Power and Energy Meter Advanced Field Retrofit Instructions August 2006 Danger This symbol indicates the presence of dangerous voltage within and outside the product enclosure

More information

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Clipsal Bus Couplers Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Instruction Bulletin Retain for future use. Clipsal Bus Couplers 63249-420-236A2 Instruction

More information

Conext EasyConfig Tool

Conext EasyConfig Tool Conext EasyConfig Tool Owner s Guide 975-0796-01-01 Revision A 05-2018 http://solar.schneider-electric.com Copyright 2018 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider

More information

Generator Performance Guide 7EN /2015

Generator Performance Guide 7EN /2015 Generator Performance Guide 7EN02-0368-00 05/2015 Safety information Important information Read these instructions carefully and look at the equipment to become familiar with the device before trying

More information

DRAFT. Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters. 1.0 Introduction DANGER. 1.1 Related Documents

DRAFT. Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters. 1.0 Introduction DANGER. 1.1 Related Documents Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters AP-XC-025 Revision B 1.0 Introduction DANGER RISK OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This Application Note is in

More information

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.6 11/2013 A5E32845290B AA

More information

Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters

Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters 976-0312-01-01 Revision A DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION, AND

More information

Schneider Electric. DTN Guardian3 Tank Scan for GuardianControl Configuration Guide. November

Schneider Electric. DTN Guardian3 Tank Scan for GuardianControl Configuration Guide. November Schneider Electric DTN Guardian3 Tank Scan for GuardianControl Configuration Guide November 2015 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks

More information

Installing and Configuring Rialto Analytic Appliances

Installing and Configuring Rialto Analytic Appliances Installing and Configuring Rialto Analytic Appliances Important Safety Information This manual provides installation and operation information and precautions for the use of this camera. Incorrect installation

More information

SCADAPack E Idec PLC Interface Manual

SCADAPack E Idec PLC Interface Manual SCADAPack E Idec PLC Interface Manual 2 SCADAPack E Idec PLC Interface Manual Table of Contents Part I Idec PLC Interface 3 1 Technical... Support 3 2 Safety... Information 4 3 Preface... 6 4 Overview...

More information

Installation Instructions

Installation Instructions Installation Instructions Variable Frequency Drive (VFD) 7 ½ - 25 Ton Units with 2 Wire Control WARNING UNINTENDED EQUIPMENT OPERATION Modifying or changing parame eters whose function is not described

More information

PowerLogic TM Series E4800 Multi-Circuit Meters. Configuration Guide

PowerLogic TM Series E4800 Multi-Circuit Meters. Configuration Guide PowerLogic TM Series E4800 Multi-Circuit Meters Configuration Guide PowerLogic TM E4800 Series 930-112-01 02/2009 Hazard Categories and Special Symbols Read these instructions carefully and look at the

More information

Conext TM ComBox USB Application Note reset_logs.lux, reset_logs_cfgs.lux

Conext TM ComBox USB Application Note reset_logs.lux, reset_logs_cfgs.lux Conext TM ComBox USB Application Note reset_logs.lux, reset_logs_cfgs.lux 976-0682-01-01 Rev A DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH This Application Note is in addition to, and

More information

Business continuity made easy

Business continuity made easy Business continuity made easy Schneider Electric Easy UPS 3 Series Easy UPS 3S: 220/230/240/380/400/415V Easy UPS 3M: 380/400/415V schneider-electric.com/ups Business continuity made easy The Schneider

More information

PowerLogic TM Series EM4800 Multi-Circuit Meters. Configuration Guide

PowerLogic TM Series EM4800 Multi-Circuit Meters. Configuration Guide PowerLogic TM Series EM4800 Multi-Circuit Meters Configuration Guide PowerLogic TM EM4800 Series 930-112-01-B.00 01/2011 Hazard Categories and Special Symbols Read these instructions carefully and look

More information

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216 Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216 Instruction Bulletin 30072-452-48 Retain for future use. 30072-452-48 Altivar 61/71 Heatsink Fan Kits VZ3V1212 and VZ3V1216

More information

Modbus Map: System Control Panel (SCP) Device

Modbus Map: System Control Panel (SCP) Device Modbus Map: System Control Panel (SCP) Device 503-0251-01-01 Revision A.1 UNINTENDED OPERATION WARNING The use of this product with Modbus communications requires expertise in the design, operation, and

More information

SCADAPack E Target 5 DF1 PLC Interface

SCADAPack E Target 5 DF1 PLC Interface SCADAPack E Target 5 DF1 PLC Interface 2 Table of Contents Part I 3 1 Technical... Support 3 2 Safety... Information 4 3 Overview... 7 4 I/O Device... Interface 7 4.1 Input Devices... 9 4.2 Output Devices...

More information

General Information 1. Connection 2. User Interface 3 ATC5300. Menus 4. Automatic Transfer Controller. Remote Control Software Manual A5E

General Information 1. Connection 2. User Interface 3 ATC5300. Menus 4. Automatic Transfer Controller. Remote Control Software Manual A5E s General Information 1 Connection 2 Automatic Transfer Controller User Interface 3 Menus 4 Remote Control Software Manual Edition 01/2010 A5E02469028-01 Legal information Warning notice system This manual

More information

Multi-Loader. User manual 06/ BBV48778

Multi-Loader. User manual 06/ BBV48778 Multi-Loader User manual 06/2009 BBV48778 www.schneider-electric.com Contents Important information 4 Before you begin 5 Documentation structure 6 Setup procedure 7 Introduction 8 Receipt of the Multi-Loader

More information

Square D Clipsal Pascal Automation Controller

Square D Clipsal Pascal Automation Controller Square D Clipsal Pascal Automation Controller SLC5500PACA For Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal Pascal Automation Controller 63249-420-258A2 Instruction

More information

How Can I. Integrate a Third-Party DNP3 Device? System Technical Note PowerSCADA Expert V1.0

How Can I. Integrate a Third-Party DNP3 Device? System Technical Note PowerSCADA Expert V1.0 How Can I Integrate a Third-Party DNP3 Device? System Technical Note PowerSCADA Expert V1.0 Safety Information Important Information Read these instructions carefully before trying to install, configure,

More information

Galaxy VM. Three-phase power protection. Galaxy VM trusted partner for your business continuity

Galaxy VM. Three-phase power protection. Galaxy VM trusted partner for your business continuity Galaxy VM Three-phase power protection Galaxy VM trusted partner for your business continuity Highly efficient, easy-to-deploy, three-phase power protection that seamlessly integrates into the electrical,

More information

Conext TM ComBox USB Application Note - copy_settings

Conext TM ComBox USB Application Note - copy_settings Conext TM ComBox USB Application Note - copy_settings 976-2105-01-01 Rev A DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH This Service Bulletin is in addition to, and incorporates by reference,

More information

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24 Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24 Section Page Introduction 1 Materials Provided 1 I) Safety Instructions 1 A) Inverter Safety Instructions 1 B) Battery Safety

More information

Application Note: Using Modbus With the Conext CL Series. Important Safety Instructions

Application Note: Using Modbus With the Conext CL Series. Important Safety Instructions : Using Modbus With the Conext CL Series 976-0317-01-01 Rev A Important Safety Instructions READ AND SAVE THESE INSTRUCTIONS - DO NOT DISCARD This document contains important safety instructions that must

More information

EIO /2011. Magelis HMISTO501. Zelio/Millenium Driver 07/2011 EIO

EIO /2011. Magelis HMISTO501. Zelio/Millenium Driver 07/2011 EIO EIO0000001026 07/2011 Magelis HMISTO501 Zelio/Millenium Driver 07/2011 EIO0000001026.00 www.schneider-electric.com 2 EIO0000001026 07/2011 Table of Contents Safety Information.............................

More information

Modbus Map: Conext System Control Panel (SCP) Device

Modbus Map: Conext System Control Panel (SCP) Device Modbus Map: Conext System Control Panel (SCP) Device 503-0251-01-01 Revision A.3 UNINTENDED OPERATION WARNING The use of this product with Modbus communications requires expertise in the design, operation,

More information

AC-115 Compact Networked Single-Door Controller Hardware Installation and Programming

AC-115 Compact Networked Single-Door Controller Hardware Installation and Programming AC-115 Compact Networked Single- Controller Hardware Installation and Programming Copyright 2013 by Rosslare. All rights reserved. This manual and the information contained herein are proprietary to REL,

More information

Conext CL-60 EasyConfig Tool

Conext CL-60 EasyConfig Tool Conext CL-60 EasyConfig Tool Owner s Guide 975-0773-01-01 Revision B 08-2017 http://solar.schneider-electric.com Copyright 2017 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider

More information

Power Management Module 2

Power Management Module 2 Power Management Module 2 30 300 kva Technical Specifications 10/2017 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B SURGE PROTECTION PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) USER MANUAL Surge Protection Device B 01 156 9000 This Surge Protection Device is intended for professional use only Read this

More information

QUICK START GUIDE Paralleling and Protection Unit PPU 300

QUICK START GUIDE Paralleling and Protection Unit PPU 300 QUICK START GUIDE Paralleling and Protection Unit PPU 300 DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4189341107C 1. Introduction

More information

Installation. MGE Galaxy 3500 and Smart-UPS VT. Maintenance Bypass, Distribution and Transformer Cabinet

Installation. MGE Galaxy 3500 and Smart-UPS VT. Maintenance Bypass, Distribution and Transformer Cabinet Installation MGE Galaxy 3500 and Smart-UPS VT Maintenance Bypass, Distribution and Transformer Cabinet American Power Conversion Legal Disclaimer The information presented in this manual is not warranted

More information

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC Software Start-Up and Reference Manual D2-3416-2 GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, 30-100 HP, 230V AC Version 6.04 Important User Information Solid-state equipment has operational

More information

Galaxy kva UPS Installation 03/

Galaxy kva UPS Installation 03/ Galaxy 7000 Installation 03/2018 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this guide are

More information

Schneider Electric Easy UPS 3S

Schneider Electric Easy UPS 3S Schneider Electric Easy UPS 3S Business continuity made easy 10 40 kva 380/400/415 V schneider-electric.com/ups Business continuity made easy The Schneider Electric Easy UPS 3S is an easy-to-install, easy-to-use,

More information

Event Notification Module

Event Notification Module Event Notification Module Installation Guide Version 8.2 4/2014 2014 Schneider Electric. All Rights Reserved. SAFETY INFORMATION Read these instructions carefully and look at the equipment to become familiar

More information

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English Configurable Output Distribution 120V / 208V / 240V 60Hz User Manual English TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS.......................... 1 GLOSSARY OF SYMBOLS....................................

More information

Pulsar EXtreme 2000/3000 VA

Pulsar EXtreme 2000/3000 VA www.mgeups.com MGE UPS SYSTEMS Pulsar EXtreme 2000/3000 VA Installation and user manual P O W E R P R O V I D E R L E I B E R R U P T N T N I E U T H 51033211EN/AC - Page 1 Introduction Thank you for selecting

More information

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3 Overview Safety notes 1 SITOP power supply Manual Description, device design, dimension drawing 2 Mounting/removal 3 Mounting position, mounting clearances 4 Installation 5 Technical data 6 Safety, approvals,

More information

Modbus Map: Automatic Generator Start (AGS) Device

Modbus Map: Automatic Generator Start (AGS) Device Modbus Map: Automatic Start (AGS) Device 503-0247-01-01 Revision A.1 UNINTENDED OPERATION WARNING The use of this product with Modbus communications requires expertise in the design, operation, and programming

More information

Schneider Electric Easy UPS 3S

Schneider Electric Easy UPS 3S Schneider Electric Easy UPS 3S Business continuity made easy 10 40 kva 380/400/415 V schneider-electric.com/ups Schneider Electric Easy UPS 3S The Schneider Electric Easy UPS 3S is an easy-to-install,

More information

TSXCUSBMBP USB Modbus Plus Communications Adapter User Manual eng

TSXCUSBMBP USB Modbus Plus Communications Adapter User Manual eng TSXCUSBMBP USB Modbus Plus Communications Adapter User Manual 35011984 eng 2 Table of Contents Safety Information.................................... 5 About the Book.......................................7

More information

Galaxy VM. 160/200 kva Parallel capable up to 800 kva. Three-phase power protection. Galaxy VM trusted partner for your business continuity

Galaxy VM. 160/200 kva Parallel capable up to 800 kva. Three-phase power protection. Galaxy VM trusted partner for your business continuity Galaxy VM 160/200 kva Parallel capable up to 800 kva Three-phase power protection Galaxy VM trusted partner for your business continuity Highly efficient, easy-to-deploy, three-phase power protection that

More information

Galaxy 5500 / Galaxy 5500 Marine

Galaxy 5500 / Galaxy 5500 Marine Galaxy 5500 / Galaxy 5500 Marine 20-120 kva 400 V Installation 05/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

ACCESS 9340/9360 Meter Input/Output Module

ACCESS 9340/9360 Meter Input/Output Module Installation Manual PMIM-IOMOD-0208 ACCESS 9340/9360 Meter Input/Output Module 9340-60-I/O2222 and 9340-60-I/O26 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the

More information

User Manual Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 BN 1100/1350/1500 M2-CA

User Manual Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 BN 1100/1350/1500 M2-CA User Manual Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 BN 1100/1350/1500 M2-CA Safety and General Information Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.

More information

Com'X 510. User Manual DOCA0098EN-02 12/2015

Com'X 510. User Manual DOCA0098EN-02 12/2015 Com'X 510 User Manual DOCA0098EN-02 12/2015 Safety Information Safety Information Important Information Read these instructions carefully and look at the equipment to become familiar with the device before

More information

XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language)

XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language) XPSMCMx Fieldbus Expansion Modules EAV8283001 12/2014 XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language) 12/2014 EAV8283001.00 www.schneider-electric.com The information provided

More information

Packaging User Guide for Temperature Control M221 Project Template

Packaging User Guide for Temperature Control M221 Project Template Packaging EIO0000001762 04/2014 Packaging User Guide for Temperature Control M221 Project Template 04/2014 EIO0000001762.00 www.schneider-electric.com The information provided in this documentation contains

More information

Galaxy kva UPS Installation 08/2017.

Galaxy kva UPS Installation 08/2017. Galaxy 7000 250 500 kva UPS Installation 08/2017 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to

More information

PowerPak Power Distribution Unit

PowerPak Power Distribution Unit WaveStar PowerPak Power Distribution Unit Permissive Signals for Manual Dual Redundant System Ctrl Nr: DOC15029 Revision: 002 PowerPak Manual Dual Redundant PDU Thank you for your recent purchase of a

More information

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING (SAVE THESE INSTRUCTIONS): This manual contains important instructions that should be followed during installation

More information

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

CEM M-RS485 INSTRUCTION MANUAL (M014B A) Communications interface CEM M-RS485 INSTRUCTION MANUAL (M014B01-03-14A) 2 SAFETY PRECAUTIONS Follow the warnings described in this manual with the symbols shown below. DANGER Warns of a risk, which could

More information

StruxureWare Power Monitoring Expert for Healthcare 7.2

StruxureWare Power Monitoring Expert for Healthcare 7.2 StruxureWare Power Monitoring Expert for Healthcare 7.2 Commissioning Guide 7EN42-0070-04 09/2013 Safety Information Read these instructions carefully and look at the equipment to become familiar with

More information

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE IMPORTANT! Please read all the information on this sheet. SAVE THESE INSTRUCTIONS! NOTICE BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL

More information

V E2B Snap-in I/O Module

V E2B Snap-in I/O Module i4 Automation Ltd - 01480 395256 V200-18-E2B Snap-in I/O Module The V200-18-E2B plugs directly into the back of compatible Unitronics OPLCs, creating a selfcontained PLC unit with a local I/O configuration.

More information

TeSys UASILUFC5 - ASILUFC51 AS-i Communication Module

TeSys UASILUFC5 - ASILUFC51 AS-i Communication Module 1639093 03/2009 TeSys UASILUFC5 - ASILUFC51 AS-i Communication Module User Manual 03/2009 1639093 www.schneider-electric.com Schneider Electric assumes no responsibility for any errors that may appear

More information

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example Introduction 1 Application example 2 Industrial Controls Motor management and control devices SIMOCODE pro - Application examples Application Manual Example circuits control functions 3 Further application

More information

Readme SiVArc V14 SP1 Update 6

Readme SiVArc V14 SP1 Update 6 Product version 1 Improvements in Update 6 2 Readme 05/2018 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as

More information

SERVICE BULLETIN DEPARTMENT OF COMPLIANCE VEHICLE SAFETY AND RECALL MANAGEMENT BUILDING N MAIN ST MIDDLEBURY, INDIANA

SERVICE BULLETIN DEPARTMENT OF COMPLIANCE VEHICLE SAFETY AND RECALL MANAGEMENT BUILDING N MAIN ST MIDDLEBURY, INDIANA SERVICE BULLETIN DEPARTMENT OF COMPLIANCE VEHICLE SAFETY AND RECALL MANAGEMENT BUILDING 11 423 N MAIN ST MIDDLEBURY, INDIANA 46540-9218 Technical Service Bulletin: 225-0754 O Integrity O Safety O Quality

More information

Series 8000 RF Signal Switch Solution

Series 8000 RF Signal Switch Solution RF Signal Switch Solution Operation Manual Operation Manual, Part Number 07508000 006, Rev. B, Oct 7, 2014 All technical data and specifications in this publication are subject to change without prior

More information

MUST900 Modular UPS. Datacenter & servers. Internet centers. Local Area Networks (LAN) Telecommunication devices. Emergency application

MUST900 Modular UPS. Datacenter & servers. Internet centers. Local Area Networks (LAN) Telecommunication devices. Emergency application MUST900 Modular UPS 30-300 kva modular UPS - up to 900 Datacenter & servers Internet centers Local Area Networks (LAN) Telecommunication devices Emergency application Smart Energy Solutions HOT SWAP 0.9

More information

Siemens Industrial s

Siemens Industrial s SINAMICS G130 Operating Instructions 05/2010 SINAMICS Siemens Industrial s Sinusoidal filter Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical

More information

B63/ NS MS. EtherNet/IP LINK

B63/ NS MS. EtherNet/IP LINK 3 609 929 B63/ IMenip 2008-09 NS MS EtherNet/IP LINK 3 609 929 B63/2008-09 IMenip Bosch Rexroth AG 15/76 Table of Contents About this document................. 16 General safety instructions............

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

Installation Guide. QBox-V6. Standalone/Spare V6 SDI QBox. Standalone/Spare V6 SDI QBox. Part No. A

Installation Guide. QBox-V6. Standalone/Spare V6 SDI QBox. Standalone/Spare V6 SDI QBox. Part No. A Installation Guide Standalone/Spare V6 SDI QBox QBox-V6 Standalone/Spare V6 SDI QBox Part No. A9009-0004 EN www.autocue.com Copyright 2017 All rights reserved. Original Instructions: English All rights

More information

Altivar - Lexium. Option modules DANGER S1A S1A /8 VW3A3601 / VW3A3608 VW3A3616 / VW3A3627 VW3A3619 VW3A3720 VW3A3721 VW3M3308

Altivar - Lexium. Option modules DANGER S1A S1A /8 VW3A3601 / VW3A3608 VW3A3616 / VW3A3627 VW3A3619 VW3A3720 VW3A3721 VW3M3308 S1A4559106 Option modules Altivar - Lexium 01 / 08 16 / 27 19 09 28 3725 3M3301 07 18 3720 3721 3M3308 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH DANGER Only appropriately trained persons who are

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

Com'X 510. User Manual DOCA0098EN-03 04/2016

Com'X 510. User Manual DOCA0098EN-03 04/2016 Com'X 510 User Manual DOCA0098EN-03 04/2016 Com'X 510 User Manual Safety Information Safety Information Important Information Read these instructions carefully and look at the equipment to become familiar

More information

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp Single phase two wire DIN rail energy meter (One module) 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic

More information