7SG14 Duobias-M Transformer Protection

Size: px
Start display at page:

Download "7SG14 Duobias-M Transformer Protection"

Transcription

1 7SG4 Duobias-M Transformer Protection Document Release History This document is issue 200/02. The list of revisions up to and including this issue is: Pre release 200/02 Document reformat due to rebrand 25/09/2006 Reformatted to match other manual sections R2 20/0/2004 Article Number added R2 7/06/2004 First Version based upon Duobias-M-20-2W R Software Revision History The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. 200 Siemens Protection Devices Limited

2 Contents INTRODUCTION DUOBIAS-M-22-2W RELAY SETTING LIST SYSTEM CONFIG MENU CT/VT CONFIG MENU BIASED DIFFERENTIAL MENU WINDING MENU WINDING 2 MENU STATUS INPUT MENU REYLOGIC CONTROL MENU REYLOGIC ELEMENT MENU OUTPUT RELAY MENU LED MENU DATA STORAGE MENU COMMUNICATIONS MENU INSTRUMENTS IEC COMMUNICATIONS INFORMATION IEC Semantics in monitor direction IEC Semantics in control direction REYLOGIC DIAGRAMS LABEL INSERTS Figures Figure - Duobias-M-22-2W [DU3-209] Siemens Protection Devices Limited Chapter 3 Page 2 of 27

3 Introduction This relay settings section covers the following Duobias-M models:- Model No Cat No Configuration No Duobias-M-22-2W-STD-50Hz DU3-209-** H80055R2 W 74TC W2 74TC W W2 W 50 W REF 87REF W 5 W2 5 W 50N W2 50N W 5N W2 5N 87HS W 46 W Figure - Duobias-M-22-2W [DU3-209] 200 Siemens Protection Devices Limited Chapter 3 Page 3 of 27

4 2 DUOBIAS-M-22-2W Relay Setting List 2. System Config Menu Active Group,2 8 Selects which settings group is currently activated View/Edit Group,2 8 Selects which settings group is currently being displayed Default Screens Timer OFF,,2,5,0,5,30,60 min 60 min Selects the time delay after which, if no key presses have been detected, the relay will begin to poll through any screens which have been selected as default instruments screens Backlight timer OFF,,2,5,0,5,30,60 min 5 Min Controls when the LCD backlight turns off Date Date //980 Time Time 00:00:00 Clock Sync. From Status, Seconds, Minutes Minutes Real time clock may be synchronised using a status input (See Clock Sync. in Status Input Menu) Operating Mode To allow access to change configuration files using Reylogic Toolbox the relay must be placed Out Of Service. Local, Remote, Local Or Remote, Out Of Service Local Or Remote Change Password Allows a 4 character alphanumeric code to be entered as the password. Note that the display shows a password dependant encrypted code on the second line of the display Relay Identifier An alphanumeric string shown on the LCD normally used to identifier the circuit the relay is attached to or the relays purpose 2.2 CT/VT Config Menu AAAA ZZZZ Up to 6 characters displayed as NOT ACTIVE DUOBIAS-M-22-2W W Input,5 A A Selects whether or 5 Amp terminals are being used for winding W CT Ratio 5: :7 2000: Winding CT ratio to scale primary current instruments W REF Input,5 A A Selects whether or 5 Amp terminals are being used for winding REF W2 Input,5 A A Selects whether or 5 Amp terminals are being used for winding 2 W2 CT Ratio 5: :7 2000: Winding 2 CT ratio to scale primary current instruments W2 REF Input Selects whether or 5 Amp terminals are being used for winding 2 REF,5 A A 200 Siemens Protection Devices Limited Chapter 3 Page 4 of 27

5 2.3 Biased Differential Menu W Interposing CT Multiplier 0.25, x.00 x Winding scaling factor W Interposing CT Connection Yy0, Yd, Yy2, Yd3, Yy4, Yy0, 0 Winding transformer vector group compensation and/or zero sequence filtering Yd5, Yy6, Yd7, Yy8, Yd9, Yy0, Yd, Ydy0 W2 Interposing CT Multiplier Winding 2 scaling factor 0.25, x.00 x W2 Interposing CT Connection Winding 2 transformer vector group compensation and/or zero sequence filtering 87 Inrush Inhibit Selects whether the biased differential characteristic is inhibited from operating when magnetising inrush is detected 87 Inrush Bias Selects the bias method used for magnetising inrush Phase Segregated, each phase blocks itself. Cross Blocked, each phase can block the operation of other phases (Modular method). Sum - Of Squares, each phase blocks itself using the square root of the sum of squares of the even harmonics.(improves SOTF performance when REF not applied). 87 Inrush Setting The magnetising inrush detector operates when the even harmonics in the differential operate current exceed a set percentage of the differential operate current 87 Biased Differential Selects whether the transformer differential protection element is enabled 87 Initial Setting The initial unbiased pickup level 87 Bias Slope The bias slope varies the pickup level to compensates for CT measuring errors and tap changer not mid tap errors as the through current (bias) increases 87 Bias Slope Limit At this point in the characteristics the bias slope increases tot provide increased security when additional measuring errors are introduced due to CT saturation effects. 87 Delay The operation of the differential may be delayed to cater for special system conditions e.g. for use on cable circuits a delay of 5ms is recommended 87HS Differential Highset Selects whether the differential Highset element is enabled. Note this element is never blocked by magnetising inrush Yy0, Yd, Yy2, Yd3, Yy4, Yd5, Yy6, Yd7, Yy8, Yd9, Yy0, Yd, Ydy0 Phase, Cross, Sum 0., xid 0., xin 0, x,2 20 xin 0.005,0.00 s Yy0, 0 Enabled Cross 0.20 xid 0.20 xin 0.20 x 4 xin s 87HS Setting,2 30 xin 4 xin the differential setting pickup setting 87HS Delay 0.005,0.00 s s 200 Siemens Protection Devices Limited Chapter 3 Page 5 of 27

6 the operation of the differential may be delayed to cater for special system conditions e.g. for use on cable circuits a delay of 5ms is recommended 2.4 Winding Menu Gn W 5 Element Selects whether the winding IDMTL Overcurrent element is enabled Gn W 5 Setting 0.0, xin.5 xin Gn W 5 Char IEC-NI, IEC-VI, IEC-EI, IEC- IEC-NI Selects characteristic curve or DTL operation LTI, ANSI-MI, ANSI-VI, ANSI-EI, DTL Gn W 5 Time Mult (IEC/ANSI) 0.025, Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn W 5 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) 0, s 5 s Gn W 5 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn W 50 Element Selects whether the winding DTL Overcurrent element is enabled Gn W 50 Setting Gn W 50 Delay Pickup delay Gn W 5N Element Selects whether the winding IDMTL derived Earth Fault element is enabled Gn W 5N Setting Gn W 5N Char Selects characteristic curve or DTL operation Gn W 5N Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn W 5N Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn W 5N Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn W 50N Element Selects whether the winding DTL derived Earth fault element is enabled Gn W 50N Setting Gn W 50N Delay Pickup delay Gn W 46IT Element Selects whether winding 46IT IDMTL/DTL negative phase sequence current element is enabled Gn W 46IT Setting Gn W 46IT Char Selects characteristic curve to be IEC or (ANSI) Decaying, INST,,2, 60 s INST 0.0, xin 20 xin 0, s , xin.0 xin IEC-NI, IEC-VI, IEC-EI, IEC- IEC-NI LTI, ANSI-MI, ANSI-VI, ANSI-EI, DTL 0.025, , s 5 s (ANSI) Decaying, INST,,2 60 s INST 0.25, xin 0.5 xin 0, s , xin IEC-NI, IEC-VI, IEC-EI, IEC- LTI, ANSI-MI, ANSI-VI,.0 xin IEC-NI 200 Siemens Protection Devices Limited Chapter 3 Page 6 of 27

7 ANSI IDMTL or DTL ANSI-EI, DTL Gn W 46IT Time Mult (IEC/ANSI) 0.025, Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn W 46IT Delay (DTL) 0, s 5 s Delay (applicable only when DTL is selected for characteristic) Gn W 46IT Reset (ANSI) Decaying, INST, INST Selects between an ANSI decaying reset characteristic or a definite time reset,2 60 s Gn W 46DT Element Selects whether winding 46DT INST/DTL negative sequence current element is enabled Gn W 46DT Setting 0.02, xin 0.25 xin Gn W 46DT Delay 0, s 0.02 Pickup delay Gn W 87REF Element High impedance restricted earth fault current element Gn W 87REF Setting 0.020, xin xin Gn W 87REF Delay Pickup delay 0, s Winding 2 Menu Gn W2 5 Element Selects whether the winding 2 IDMTL Overcurrent element is enabled Gn W2 5 Setting 0.0, xin.5 xin Gn W2 5 Char IEC-NI, IEC-VI, IEC-EI, IEC- IEC-NI Selects characteristic curve or DTL operation LTI, ANSI-MI, ANSI-VI, ANSI-EI, DTL Gn W2 5 Time Mult (IEC/ANSI) 0.025, Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn W2 5 Delay (DTL) Delay (applicable only when DTL is selected for characteristic) 0, s 5 s Gn W2 5 Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn W2 50 Element Selects whether the winding 2 DTL Overcurrent element is enabled (ANSI) Decaying, INST,,2 60 s INST Gn W2 50 Setting 0.0, xin 20 xin Gn W2 50 Delay 0, s 0.0 Pickup delay Gn W2 5N Element Selects whether the winding 2 IDMTL derived Earth Fault element is enabled Gn W2 5N Setting 0.25, xin.0 xin Gn W2 5N Char IEC-NI, IEC-VI, IEC-EI, IEC- IEC-NI Selects characteristic curve or DTL operation LTI, ANSI-MI, ANSI-VI, ANSI-EI, DTL Gn W2 5N Time Mult (IEC/ANSI) 0.025, Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn W2 5N Delay (DTL) 0, s 5 s 200 Siemens Protection Devices Limited Chapter 3 Page 7 of 27

8 Delay (applicable only when DTL is selected for characteristic) Gn W2 5N Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn W2 50N Element Selects whether the winding 2 DTL derived Earth fault element is enabled Gn W2 50N Setting Gn W2 50N Delay Pickup delay Gn W2 46IT Setting Gn W2 46IT Char Selects characteristic curve to be IEC or ANSI IDMTL or DTL Gn W2 46IT Time Mult (IEC/ANSI) Time multiplier (applicable to IEC and ANSI curves but not DTL selection) Gn W2 46IT Delay (DTL) Delay (applicable only when DTL is selected for characteristic) Gn W2 46IT Reset Selects between an ANSI decaying reset characteristic or a definite time reset Gn W2 46DT Element Selects whether winding 46DT INST/DTL negative sequence current element is enabled Gn W2 46DT Setting Gn W2 46DT Delay Pickup delay Gn W2 87REF Element High impedance restricted earth fault current element Gn W2 87REF Setting Gn W2 87REF Delay Pickup delay 2.6 Status Input Menu (ANSI) Decaying, INST,,2 60 s INST 0.25, xin 0.5 xin 0, s , xin.0 xin IEC-NI, IEC-VI, IEC-EI, IEC- IEC-NI LTI, ANSI-MI, ANSI-VI, ANSI-EI, DTL 0.025, , s 5 s (ANSI) Decaying, INST,,2 60 s INST 0.02, xin 0.25 xin 0, s , xin xin 0, s Aux I/P Pickup Delay 0.000, s 0 s Delay on pickup of DC Status input Aux I/P 2 Pickup Delay 0.000, s 0 s Aux I/P 3 Pickup Delay 0.000, s 0 s Aux I/P 4 Pickup Delay 0.000, s 0 s Aux I/P 5 Pickup Delay 0.000, s 0 s Aux I/P 6 Pickup Delay 0.000, s 0 s Aux I/P 7 Pickup Delay 0.000, s 0 s Aux I/P 8 Pickup Delay 0.000, s 0 s Aux I/P 9 Pickup Delay 0.000, s 0 s Aux I/P 0 Pickup Delay 0.000, s 0 s Aux I/P Pickup Delay 0.000, s 0 s Aux I/P 2 Pickup Delay 0.000, s 0 s Aux I/P 3 Pickup Delay 0.000, s 0 s Aux I/P 4 Pickup Delay 0.000, s 0 s Aux I/P 5 Pickup Delay 0.000, s 0 s Aux I/P 6 Pickup Delay 0.000, s 0 s Aux I/P 7 Pickup Delay 0.000, s 0 s Aux I/P 8 Pickup Delay 0.000, s 0 s 200 Siemens Protection Devices Limited Chapter 3 Page 8 of 27

9 Aux I/P 9 Pickup Delay 0.000, s 0 s Aux I/P 20 Pickup Delay 0.000, s 0 s Aux I/P 2 Pickup Delay 0.000, s 0 s Aux I/P 22 Pickup Delay 0.000, s 0 s Aux I/P 23 Pickup Delay 0.000, s 0 s Aux I/P 24 Pickup Delay 0.000, s 0 s Aux I/P 25 Pickup Delay 0.000, s 0 s Aux I/P 26 Pickup Delay 0.000, s 0 s Aux I/P 27 Pickup Delay 0.000, s 0 s Inhibit W 5 Selects which inputs inhibit the W 5 element Inhibit W 50 Selects which inputs inhibit the W 50 element Inhibit W 5N Selects which inputs inhibit the W 5N element Inhibit W 50N Selects which inputs inhibit the W 50N element Inhibit W 46IT Selects which inputs inhibit the W 24IT element Inhibit W 46DT Selects which inputs inhibit the W 46DT element Inhibit W 87REF Selects which inputs inhibit the W 87REF element Inhibit W2 5 Selects which inputs inhibit the W2 5 element Inhibit W2 50 Selects which inputs inhibit the W2 50 element Inhibit W2 5N Selects which inputs inhibit the W2 5N element Inhibit W2 50N Selects which inputs inhibit the W2 50N element Inhibit W2 46IT Selects which inputs inhibit the W2 24IT element Inhibit W2 46DT Selects which inputs inhibit the W2 46DT element Inhibit W2 87REF Selects which inputs inhibit the W2 87REF element Trip Circuit Fail Selects which inputs are monitoring trip circuits, inputs should normally also be selected as Inverted Inputs (see below) Trigger Storage Selects which inputs can trigger a waveform record Clock Sync. Selects which input is used to synchronise the real time clock Inverted Inputs Selects which inputs pickup when voltage is removed, often used when 200 Siemens Protection Devices Limited Chapter 3 Page 9 of 27

10 monitoring trip circuits. ) Only when fitted. 2) 27 status inputs represents maximum configuration. 2.7 Reylogic Control Menu General Logic Selects whether the logic diagram is enabled, if disabled then no outputs will be driven. Enable, Disable Enable 2.8 Reylogic Element Menu Trip Cct Pickup Delay 0, ms 400 ms 2.9 Output Relay Menu 87, 29 4,5 Biased Differential 87HS, 29 4,5 Differential Highset W 5, 29 4,5 Winding IDMTL Overcurrent W 50, 29 4,5 Winding DTL Overcurrent W 5N, 29 4,5 Winding IDMTL derived Earth Fault W 50N, 29 4,5 Winding DTL derived Earth Fault W 46IT, 29 4,5 Winding IDMTL/DTL NPS Overcurrent W 46DT, 29 4,5 Winding INST/DTL NPS Overcurrent W 87REF, 29 4,5 Winging High Impedance Restricted Earth Fault W2 5, 29 4,5 Winding 2 IDMTL Overcurrent W2 50, 29 4,5 Winding 2 DTL Overcurrent W2 5N, 29 4,5 Winding 2 IDMTL derived Earth Fault W2 50N, 29 4,5 Winding 2 DTL derived Earth Fault W2 46IT, 29 4,5 Winding 2 IDMTL/DTL NPS Overcurrent W2 46DT, 29 4,5 Winding 2 INST/DTL NPS Overcurrent W2 87REF, 29 4,5 Winging 2 High Impedance Restricted Earth Fault W3 5 3, 29 4,5 Winding 3 IDMTL Overcurrent W3 50 3, 29 4,5 200 Siemens Protection Devices Limited Chapter 3 Page 0 of 27

11 Winding 3 DTL Overcurrent W3 5N 3, 29 4,5 Winding 3 IDMTL derived Earth Fault W3 50N 3, 29 4,5 Winding 3 DTL derived Earth Fault W3 87REF 3, 29 4,5 Winging 3 High Impedance Restricted Earth Fault Phase A, 29 A phase A element Phase B, 29 A phase B element Phase C, 29 A phase C element General Starter, 29 A starter element is picked up General Trip, 29 An element has. Useful when testing individual functions! Trip Circuit Fail, 29 A trip circuit has failed, look at status input Leds to find out which one New Data Stored, 29 The waveform recorder has stored new information Note: this is a pulsed output Aux I/P Operated, 29 DC Status has Aux I/P 2 Operated, 29 Aux I/P 3 Operated, 29 Aux I/P 4 Operated, 29 Aux I/P 5 Operated, 29 Aux I/P 6 Operated, 29 Aux I/P 7 Operated, 29 Aux I/P 8 Operated, 29 Aux I/P 9 Operated, 29 Aux I/P 0 Operated, 29 Aux I/P Operated, 29 Aux I/P 2 Operated, 29 Aux I/P 3 Operated, 29 Aux I/P 4 Operated, 29 Aux I/P 5 Operated, 29 Aux I/P 6 Operated, 29 Aux I/P 7 Operated, 29 Aux I/P 8 Operated, 29 Aux I/P 9 Operated, 29 Aux I/P 20 Operated, 29 Aux I/P 2 Operated, 29 Aux I/P 22 Operated, 29 Aux I/P 23 Operated, 29 Aux I/P 24 Operated, 29 Aux I/P 25 Operated, 29 Aux I/P 26 Operated, 29 Aux I/P 27 Operated, 29 Hand Reset Outputs, 29 Relays selected, as Hand Reset will remain latched until manually reset from front panel or via communications link or by removing DC Supply. By default relays are Self Resetting and will reset when the driving signal is removed. Protection Healthy, Siemens Protection Devices Limited Chapter 3 Page of 27

12 Relays selected are energised whilst relay self-monitoring does NOT detect any hardware or software errors and DC Supply is healthy. A changeover contact or normally closed contact may be used to generate Protection Defective from this output ) 29 output relays represents maximum configuration. 2) Only when fitted. 2.0 LED Menu 87, 32 7 Biased Differential 87HS, 32 8 Differential Highset W 5, 32 5,22 Winding IDMTL Overcurrent W 50, 32 5,20 Winding DTL Overcurrent W 5N, 32 5,23 Winding IDMTL derived Earth Fault W 50N, 32 5,2 Winding DTL derived Earth Fault W 46IT, 32 Winding 46 IDMTL/DTL NPS overcurrent W 46DT, 32 Winding 46 INST/DTL NPS overcurrent W 87REF, 32 5,9 Winging High Impedance Restricted Earth Fault W2 5, 32 6,22 Winding 2 IDMTL Overcurrent W2 50, 32 6,20 Winding 2 DTL Overcurrent W2 5N, 32 6,23 Winding 2 IDMTL derived Earth Fault W2 50N, 32 6,2 Winding 2 DTL derived Earth Fault W2 46IT, 32 Winding 2 46 IDMTL/DTL NPS overcurrent W2 46DT, 32 Winding 2 46 INST/DTL NPS overcurrent W2 87REF, 32 6,9 Winging 2 High Impedance Restricted Earth Fault Phase A, 32 2 A phase A element Phase B, 32 3 A phase B element Phase C, 32 4 A phase C element General Starter A starter element is picked up. Useful when testing individual functions!, Siemens Protection Devices Limited Chapter 3 Page 2 of 27

13 General Trip, 32 An element has. Useful when testing individual functions! Trip Circuit Fail, A trip circuit has failed, look at status inputs Leds to find out which one New Data Stored, 32 The waveform recorder has stored new information Aux I/P Operated, 32 9 DC Status has Aux I/P 2 Operated, 32 0 Aux I/P 3 Operated, 32 Aux I/P 4 Operated, 32 2 Aux I/P 5 Operated, 32 3 Aux I/P 6 Operated, 32 4 Aux I/P 7 Operated, 32 5 Aux I/P 8 Operated, 32 6 Aux I/P 9 Operated, Aux I/P 0 Operated, Aux I/P Operated, Aux I/P 2 Operated, 32 Aux I/P 3 Operated, 32 Aux I/P 4 Operated, 32 Aux I/P 5 Operated, 32 Aux I/P 6 Operated, 32 Aux I/P 7 Operated, 32 Aux I/P 8 Operated, 32 Aux I/P 9 Operated, 32 Aux I/P 20 Operated, 32 Aux I/P 2 Operated, 32 Aux I/P 22 Operated, 32 Aux I/P 23 Operated, 32 Aux I/P 24 Operated, 32 Aux I/P 25 Operated, 32 Aux I/P 26 Operated, 32 Aux I/P 27 Operated, 32 Self Reset LEDs LEDs selected, as Self Reset will automatically reset when the driving signal is removed. By default all LEDs are Hand Reset and must be manually reset either locally via the front fascia or remotely via communications., 32 ) Only when fitted. 2) 3W Only 2. Data Storage Menu Clear Faults NO, YES NO Clear Events NO, YES NO Pre-Trigger Storage 0 90 % 20 % Data Record Duration 5 Recs x Seconds, 5 Recs x Second 2 Recs x 2 Seconds, Recs x 5 Seconds Trigger Waveform NO, YES NO Clear Waveforms NO, YES NO ) Number of records and duration available is dependent upon relay model 200 Siemens Protection Devices Limited Chapter 3 Page 3 of 27

14 2.2 Communications Menu Station Address IEC Station Address IEC870 On Port None, Com, Com2, Auto Com Selects which port to use for IEC communications Line Switch Time When IEC870 On Port is selected to Auto the communications ports are scanned for valid IEC communications frames. Once valid frames are detected the com port will remain selected. Subsequently if there are no valid frames received for the Line Switch Time period then the driver will assume the communications circuit has failed and will resume scanning the com ports.,2, 60 s 30 s Only visible when set to Auto. Com Baud Rate Sets the communications baud rate for com port (Rear upper Fibre optic port) Com Parity Selects whether parity information is used Com Line Idle Selects the communications line idle sense Com Data Echo Enables echoing of data from RX port to TX port when operating relays in a Fibre Optic ring configuration Com2 Baud Rate Sets the communications baud rate for com port 2 (Rear lower Fibre optic port AND Front Fascia RS232 port) Com2 Parity Selects whether parity information is used Com2 Line Idle Selects the communications line idle sense Com2 Data Echo Enables echoing of data from RX port to TX port when operating relays in a Fibre Optic ring configuration Com2 Direction Selects how Com2 is shared between the front fascia port and the rear fibre optic port. This allows interlocking to prevent remote access whilst an engineer is attached locally on site if IEC870 is on Com2 and Auto-detect is enabled 75, 0, 300, 600, 200, 2400, 4800, 9600, 9200, 38400, 57600, 5200 Even, Odd, None Light Off, Light On Off, On 75, 0, 300, 600, 200, 2400, 4800, 9600, 9200, 38400, 57600, 5200 Even, Odd, None Light Off, Light On Off, On AUTO-DETECT, FRONT PORT, REAR PORT 9200 Even Light Off Off Even Light Off Off AUTO-DETECT 200 Siemens Protection Devices Limited Chapter 3 Page 4 of 27

15 3 Instruments INSTRUMENT [ WINDING METERS ] --> press down <-- W Primary Currents ka W Sec y Currents A W Nom Currents xin W Res Nom Current 0.00 xin W 5/5N Status % W Izps Ipps Inps xin W 46IT Status 0 % W REF Sec Current 0.00 A W REF Nom Current 0.00 xin [ WINDING 2 METERS ] --> press down <-- W2 Primary Currents ka W2 Sec y Currents A W2 Nom Currents xin W2 Res Nom Current 0.00 xin W2 5/5N Status % W2 Izps Ipps Inps xin W2 46IT Status 0 % W2 REF Sec Current 0.00 A W2 REF Nom Current 0.00 xin [ BIAS DIFF METERS ] --> press down <-- W Line Currents xin W2 Line Currents xin W Relay Currents xin W2 Relay Currents xin Operate Currents xin Restrain Currents xin Mag Inrush Currents xin [ MISC METERS ] --> press down <-- Status Inputs Status Inputs DESCRIPTION Start of Winding meters Winding primary currents Winding secondary currents Winding nominal currents Winding residual nominal current Operation progress meters for Winding (5/5N) IDMTL elements, phases A, B, C and E/F Winding Nominal sequence currents Operation progress meters for Winding (46IT) IDMTL element Winding secondary restricted earth fault current Winding nominal restricted earth fault current Start of Winding 2 meters Winding 2 primary currents Winding 2 secondary currents Winding 2 nominal currents Winding 2 residual nominal current Operation progress meters for Winding 2 (5/5N) IDMTL elements, phases A, B, C and E/F Winding 2 Nominal sequence currents Operation progress meters for Winding 2 (46IT) IDMTL element Winding 2 secondary restricted earth fault current Winding 2 nominal restricted earth fault current Start of (87) Biased Differential meters Winding measured currents Winding 2 measured currents Winding currents after Interposing CT correction factors applied Winding 2 currents after Interposing CT correction factors applied Differential operate currents Differential restrain currents Differential magnetising inrush currents (even harmonic content of operate currents but mainly 2nd harmonic content) Start of miscellaneous meters Displays the state of DC status inputs to 6 Displays the state of DC status inputs 7 to Siemens Protection Devices Limited Chapter 3 Page 5 of 27

16 INSTRUMENT Output Relays Output Relays Time & Date 3/08/2002 0:6: ) Display is different when fewer status inputs are fitted 2) Display is different when fewer output relays are fitted DESCRIPTION Displays the state of output relays to 62 Displays the state of output relays 7 to 22 Time and Date 200 Siemens Protection Devices Limited Chapter 3 Page 6 of 27

17 4 IEC Communications Information 4. IEC Semantics in monitor direction FUN INF Description GI TYP COT 60 IEC870 Active Com x, IEC870 Active Com2 x, Front Port OverRide x, GI End Time Synchronisation Reset FCB Reset CU Start/Restart Settings changed Setting G selected x, Setting G2 selected x, Setting G3 selected x, Setting G4 selected x, Status Input x, Status Input 2 x, Status Input 3 x, Status Input 4 x, Trip Circuit Fail x, Start/Pick-up L x 2, Start/Pick-up L2 x 2, Start/Pick-up L3 x 2, Start/Pick-up N x 2, General Trip Trip L Trip L Trip L General Start/Pick-up x 2, Biased Differential Differential Highset W Restricted Earth Fault W2 Restricted Earth Fault W2 Phase Fault W Phase Fault W Residual Earth Fault W2 Residual Earth Fault W NPS Overcurrent W2 NPS Overcurrent Cold Start Warm Start Re-Start Trigger Storage Status Input 5 x, Status Input 6 x, Status Input 7 x,9 200 Siemens Protection Devices Limited Chapter 3 Page 7 of 27

18 FUN INF Description GI TYP COT Status Input 8 x, Status Input 9 x, Status Input 0 x, Status Input x, Status Input 2 x, Status Input 3 x, Status Input 4 x, Status Input 5 x, Status Input 6 x, Status Input 7 x, Status Input 8 x, Status Input 9 x, Status Input 20 x, Status Input 2 x, Status Input 22 x, Status Input 23 x, Status Input 24 x, Status Input 25 x, Status Input 26 x, Status Input 27 x, Plant Control Relay x, Plant Control Relay 2 x, Plant Control Relay 3 x, Plant Control Relay 4 x, Plant Control Relay 5 x, Plant Control Relay 6 x, Plant Control Relay 7 x, Plant Control Relay 8 x, Plant Control Relay 9 x, Plant Control Relay 0 x, Plant Control Relay x, Plant Control Relay 2 x, Plant Control Relay 3 x, Plant Control Relay 4 x, Plant Control Relay 5 x, Plant Control Relay 6 x, Plant Control Relay 7 x, Plant Control Relay 8 x, Plant Control Relay 9 x, Plant Control Relay 20 x, Plant Control Relay 2 x, Plant Control Relay 22 x, Plant Control Relay 23 x, Plant Control Relay 24 x, Plant Control Relay 25 x, Plant Control Relay 26 x, Plant Control Relay 27 x, Plant Control Relay 28 x,9 200 Siemens Protection Devices Limited Chapter 3 Page 8 of 27

19 FUN INF Description GI TYP COT Plant Control Relay 29 x,9 200 Siemens Protection Devices Limited Chapter 3 Page 9 of 27

20 4.2 IEC Semantics in control direction FUN INF Description COM TYP COT 76 0 GI Initiation Time Synchronisation LED reset ON Settings Group Select ON Settings Group 2 Select ON Settings Group 3 Select ON Settings Group 4 Select ON Settings Group 5 Select ON Settings Group 6 Select ON Settings Group 7 Select ON Settings Group 8 Select ON Siemens Protection Devices Limited Chapter 3 Page 20 of 27

21 5 Reylogic Diagrams 87/87HS BIASED DIFFERENTIAL LOGIC A87_Output IEC Event Code 78-7 A87_Output2 A87_Output3 A87_Trip 87 A87HS_Output IEC Event Code 78-8 A87HS_Output2 A87HS_Trip 87HS A87HS_Output3 W 5 IDMTL OVERCURRENT W_5_Operated W_5_Operated2 W_5_Operated3 W_5_Trip W 5 Inhibit W 5 W_5_Inhibit_Input W_5_Inhibit W 50 DTL OVERCURRENT W_50_Operated W_50_Operated2 W_50_Operated3 W_50_Trip W 50 Inhibit W 50 W_50_Inhibit_Input W_50_Inhibit W 5N IDMTL EARTH FAULT W_5N_Operated W_5N_Trip W 5N Inhibit W 5N W_5N_Inhibit_Input W_5N_Inhibit W 5N IDMTL EARTH FAULT W_50N_Operated W_50N_Trip W 50N Inhibit W 50N W_50N_Inhibit_Input W_50N_Inhibit W_5_Trip W_50_Trip W_5N_Trip W_50N_Trip W_50_5_Trip W_50N_5N_Trip W 46IT NPS IDMTL./DTL OVERCURRENT W_46IT_Operated IEC Event Code W_50_5_Trip IEC Event Code W_50N_5N_Trip W_50550N5N_Trip W_46IT_Trip W 46IT Inhibit W 46IT W_46IT_Inhibit_Input W_46IT_Inhibit W 46DT NPS INST/DTL OVERCURRENT W_46DT_Operated W_46DT_Trip W 46DT Inhibit W 46DT W_46DT_Inhibit_Input W_46DT_Inhibit W_46IT_Trip W_46DT_Trip W 87 RESTRICTED EARTH FAULT LOGIC W_87REF_Operated IEC Event Code W_46IT_46DT_Trip IEC Event Code 78-9 W_87REF_Trip W 87REF Inhibit W 87REF W_87REF_Inhibit_Input W_87REF_Inhibit 200 Siemens Protection Devices Limited Chapter 3 Page 2 of 27

22 W2 5 IDMTL OVERCURRENT W2_5_Operated W2_5_Operated2 W2_5_Operated3 W2_5_Trip W2 5 Inhibit W2 5 W2_5_Inhibit_Input W2_5_Inhibit W2 50 DTL OVERCURRENT W2_50_Operated W2_50_Operated2 W2_50_Operated3 W2_50_Trip W2 50 Inhibit W2 50 W2_50_Inhibit_Input W2_50_Inhibit W2 5N IDMTL EARTH FAULT W2_5N_Operated W2_5N_Trip W2 5N Inhibit W2 5N W2_5N_Inhibit_Input W2_5N_Inhibit W2 5N IDMTL EARTH FAULT W2_50N_Operated W2_50N_Trip W2 50N Inhibit W2 50N W2_50N_Inhibit_Input W2_50N_Inhibit W2_5_Trip W2_50_Trip W2_5N_Trip W2_50N_Trip IEC Event Code 78-6 W2_50_5_Trip IEC Event Code W2_50N_5N_Trip W2_50_5_Trip W2_50N_5N_Trip W2 46IT NPS IDMTL./DTL OVERCURRENT W2_46IT_Operated W2_50550N5N_Trip W2_46IT_Trip W2 46IT Inhibit W2 46IT W2_46IT_Inhibit_Input W2_46IT_Inhibit W2 46DT NPS INST/DTL OVERCURRENT W2_46DT_Operated W2_46DT_Trip W2 46DT Inhibit W2 46DT W2_46DT_Inhibit_Input W2_46DT_Inhibit W2_46IT_Trip W2_46DT_Trip W2 87 RESTRICTED EARTH FAULT LOGIC W2_87REF_Operated IEC Event Code W2_46IT_46DT_Trip IEC Event Code 78-0 W2_87REF_Trip W2 87REF Inhibit W2 87REF W2_87REF_Inhibit_Input W2_87REF_Inhibit 200 Siemens Protection Devices Limited Chapter 3 Page 22 of 27

23 OVERALL PHASE SELECTION LOGIC A87_Output A87HS_Output W_5_Starter W_50_Starter W2_5_Starter W2_50_Starter A87_Output2 A87HS_Output2 W_5_Starter2 W_50_Starter2 W2_5_Starter2 W2_50_Starter2 A87_Output3 A87HS_Output3 W_5_Starter3 W_50_Starter3 W2_5_Starter3 W2_50_Starter3 W_5N_Starter W_50N_Starter W2_5N_Starter W2_50N_Starter W_87REF_Starter W2_87REF_Starter IEC Event Code PhaseA_Starter IEC Event Code PhaseB_Starter IEC Event Code PhaseC_Starter IEC Event Code PhaseN_Starter A87_Output A87HS_Output W_5_Operated W_50_Operated IEC Event Code PhaseA_Trip Phase A W2_5_Operated W2_50_Operated A87_Output2 A87HS_Output2 W_5_Operated2 W_50_Operated2 IEC Event Code PhaseB_Trip Phase B W2_5_Operated2 W2_50_Operated2 A87_Output3 A87HS_Output3 W_5_Operated3 W_50_Operated3 IEC Event Code 76-7 PhaseC_Trip Phase C W2_5_Operated3 W2_50_Operated3 200 Siemens Protection Devices Limited Chapter 3 Page 23 of 27

24 GENERAL STARTER LOGIC PhaseA_Starter PhaseB_Starter PhaseC_Starter PhaseN_Starter W_46IT_Starter W_46DT_Starter W2_46IT_Starter W2_46DT_Starter IEC Event Code General_Starter General Starter GENERAL TRIP LOGIC PhaseA_Trip PhaseB_Trip PhaseC_Trip W_5N_Operated W_50N_Operated W2_5N_Operated W2_50N_Operated W_46IT_Operated W_46DT_Operated W_87REF_Operated W2_46IT_Operated W2_46DT_Operated W2_87REF_Operated TRIP CIRCUIT FAILURE LOGIC Trip Circuit Fail TCSAlarmInput TripCctTimer 400 / 0 Trip Cct Pickup Delay = 400ms Trip Cct Dropoff Delay = 0ms IEC Event Code General_Trip General Trip IEC Event Code TCSAlarmOutput Trip Circuit Fail FAULT AND WAVEFORM RECORDER LOGIC Trigger Storage General_Trip StatusTrigger TRIGD & TRIGD TRIGGERSTORAGE New Data Stored General_Trip TriggerHold 0 / 0 & TRIGFLTREC TriggerHold PU = 0ms TriggerHold DO = 0ms TriggerReset 2000 / Siemens Protection Devices Limited Chapter 3 Page 24 of 27

25 6 LABEL INSERTS DUOBIAS-M-22-2W-R2 3i5o in E8 Case DU3-209-*A 09/02/200 09:08:00 GENERAL STARTER 2 PHASE A 3 PHASE B 4 PHASE C 5 WDG 6 WDG2 7 (87) BIAS. DIFFERENTIAL 8 (87HS) DIFF. HIGHSET 9 (87REF) RESTRICTED E/F 0 (50/5) O/C (50N/5N) DERIVED E/F 2 (74TC) TRIP CIRCUIT FAIL 3 (46IT/46DT) NPS O/C 4 AUX I/P OPERATED 5 AUX 2 I/P OPERATED 6 AUX 3 I/P OPERATED 200 Siemens Protection Devices Limited Chapter 3 Page 25 of 27

26 DUOBIAS-M-22-2W-R2 DU3-209-** DUOBIAS-M-22-2W-R2 DU3-209-** Left Right 09/02/200 09:08:00 09/02/200 09:08:00 GENERAL STARTER (87) BIAS. DIFFERENTIAL 7 2 PHASE A (87HS) DIFF. HIGHSET 8 3 PHASE B (87REF) RESTRICTED E/F 9 4 PHASE C (50) O/C 20 5 WDG (50N) DERIVED E/F 2 6 WDG2 (5) O/C 22 7 (5N) DERIVED E/F 23 8 (46IT/46DT) NPS O/C (74TC) TRIP CIRCUIT FAIL 24 9 AUX I/P OPERATED AUX 9 I/P OPERATED 25 0 AUX 2 I/P OPERATED AUX 0 I/P OPERATED 26 AUX 3 I/P OPERATED AUX I/P OPERATED 27 2 AUX 4 I/P OPERATED 28 3 AUX 5 I/P OPERATED 29 4 AUX 6 I/P OPERATED 30 5 AUX 7 I/P OPERATED 3 6 AUX 8 I/P OPERATED Siemens Protection Devices Limited Chapter 3 Page 26 of 27

27 DUOBIAS-M-22-3W-R2 DU3-309-** DUOBIAS-M-22-3W-R2 DU3-309-** Left Right 09/02/200 09:08:00 09/02/200 09:08:00 GENERAL STARTER (87) BIAS. DIFFERENTIAL 7 2 PHASE A (87HS) DIFF. HIGHSET 8 3 PHASE B (87REF) RESTRICTED E/F 9 4 PHASE C (50) O/C 20 5 WDG (50N) DERIVED E/F 2 6 WDG2 (5) O/C 22 7 WDG3 (5N) DERIVED E/F 23 8 (46IT/46DT) NPS O/C (74TC) TRIP CIRCUIT FAIL 24 9 AUX I/P OPERATED AUX 9 I/P OPERATED 25 0 AUX 2 I/P OPERATED AUX 0 I/P OPERATED 26 AUX 3 I/P OPERATED AUX I/P OPERATED 27 2 AUX 4 I/P OPERATED 28 3 AUX 5 I/P OPERATED 29 4 AUX 6 I/P OPERATED 30 5 AUX 7 I/P OPERATED 3 6 AUX 8 I/P OPERATED Siemens Protection Devices Limited Chapter 3 Page 27 of 27

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay 7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms module

More information

7SR242 Duobias Transformer Protection Relay Answers for energy.

7SR242 Duobias Transformer Protection Relay Answers for energy. Reyrolle Protection Devices 7SR242 Duobias Transformer Protection Relay Answers for energy. 2 Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration & Instruments 3.

More information

Reyrolle Protection Devices. 7SR10 Argus User Manual Overcurrent and Earth Fault Relay

Reyrolle Protection Devices. 7SR10 Argus User Manual Overcurrent and Earth Fault Relay Reyrolle Protection Devices 7SR10 Argus User Manual Overcurrent and Earth Fault Relay Siemens Protection Devices Limited 2 7SR10 Argus Contents Contents Technical Manual Chapters 1. Description of Operation

More information

7SR11 and 7SR12 Settings and Instruments

7SR11 and 7SR12 Settings and Instruments 7SR11 and 7SR12 Settings and Instruments Document Release History This document is issue 2012/01. The list of revisions up to and including this issue is: 2012/01 Software Maintenance 2011/06 Software

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms modules

More information

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK SDR recloser A PH Fault B PH Fault C PH Fault Ground Fault SGF Lockout Aux Power OK Recloser OK Open Close Reclose ON Hot Line Tag ON All Protn OFF Inst Protn OFF Ground Fault Protn OFF SGF Protn OFF Trip

More information

7SR11 & 7SR12 Argus Overcurrent Relay Energy Management

7SR11 & 7SR12 Argus Overcurrent Relay Energy Management Reyrolle Protection Devices 7SR11 & 7SR12 Argus Overcurrent Relay Energy Management 7SR11 & 7SR12 Argus Contents Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration

More information

7SR11 and 7SR12 Description of Operation

7SR11 and 7SR12 Description of Operation 7SR11 and 7SR12 Description of Operation Document Release History This document is issue 2012/02. The list of revisions up to and including this issue is: 2012/02 AC auxiliary power supply added 2012/01

More information

7SG22 Iota Programmable Logic Module Answers for energy

7SG22 Iota Programmable Logic Module Answers for energy Reyrolle Protection Devices 7SG22 Iota Programmable Logic Module Answers for energy 7SG22 Iota Contents Contents Technical Manual Chapters 1 Description of Operation 2 Performance Specification 3 Relay

More information

Reyrolle Protection Devices. 7SR45 Argus Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault Relay

Reyrolle Protection Devices. 7SR45 Argus Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault Relay Reyrolle Protection Devices 7SR45 Argus Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault Relay 2018 Siemens Protection Devices Limited 2 7SR45 Argus Contents Contents Technical Manual

More information

(1) Description of Operation 7SR224 Recloser Controller

(1) Description of Operation 7SR224 Recloser Controller (1) Description of Operation 7SR224 Recloser Controller DOCUMENTATION SET This document is part of a set. The full list of documents in the set, and the publication numbers under which they can be ordered,

More information

7SR105 Rho User Manual Motor Protection Relay Energy Management

7SR105 Rho User Manual Motor Protection Relay Energy Management Reyrolle Protection Devices 7SR105 Rho User Manual Motor Protection Relay Energy Management 2016 Siemens Limited 2 7SR105 Rho Contents Contents Technical Manual Chapters 1. Description of Operation 2.

More information

Protection Products. Catalogue

Protection Products. Catalogue Protection Products Numerical Multi-Function Relays Catalogue Selection Guide Product Range Feeder Protection Model Argus 1 Argus 2 Argus 7 Argus 8 Delta Delta Lite Motor Protection Model Rho 3 Description

More information

7SR191 Capa Capacitor Protection Relay Energy Management

7SR191 Capa Capacitor Protection Relay Energy Management Reyrolle Protection Devices 7SR191 Capa Capacitor Protection Relay Energy Management 7SR191 Contents Contents Technical Manual Chapters 1. Description of Operation 2. Settings & Instruments 3. Performance

More information

Reyrolle Protection Devices. 7SG13 Delta Protection and Control Relays. Answers for energy

Reyrolle Protection Devices. 7SG13 Delta Protection and Control Relays. Answers for energy Reyrolle Protection Devices 7SG13 Delta Protection and Control Relays Answers for energy 7SG13 Delta Protection and Control Relays User Interface 20 character x 2 line backlit LCD Menu navigation keys

More information

7SR11 & 7SR12 Argus Overcurrent Relay Energy Management

7SR11 & 7SR12 Argus Overcurrent Relay Energy Management Reyrolle Protection Devices 7SR11 & 7SR12 Argus Overcurrent Relay Energy Management 7SR11 & 7SR12 Argus Contents Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration

More information

7SG11 Argus 7 Check and System Synchronising Relays

7SG11 Argus 7 Check and System Synchronising Relays 7SG11 Argus 7 Check and System Synchronising Relays Document Release History This document is issue 2010/02. The list of revisions up to and including this issue is: Pre release 2010/02 Document reformat

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

SOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection

SOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection SOLKO-N (7S18) Feeder Differential Protection CLASSIFICATION OF UNIT TYPE POTECTION Summation Transformer, Circulating Current Protection B B 3 1 1 O O 3 1 1 SUMMATION TANSFOME SUMMATION TANSFOME O - Operating

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

GRD110 FEATURES APPLICATION

GRD110 FEATURES APPLICATION FEATURES Overcurrent protection for phase and earth faults with IDMTL or DTL. Three instantaneous elements with DTL. Programmable reset characteristics. Sensitive earth fault protection (SEF). Restricted

More information

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy Reyrolle Protection Devices 7SR11 and 7SR12 Argus Overcurrent Relays Answers for energy 7SR11 and 7SR12 Argus Overcurrent Relays Control 79 Auto Reclose 86 Lockout CB Control Features Cold Load Settings

More information

Reyrolle Protection Devices. 7SR242 Duobias Transformer Protection Relay. Energy Management. Unrestricted

Reyrolle Protection Devices. 7SR242 Duobias Transformer Protection Relay. Energy Management. Unrestricted Reyrolle Protection Devices 7SR4 Duobias Transformer Protection Relay Energy Management Unrestricted Unrestricted Siemens Protection Devices Limited 7SR4 Duobias Transformer Protection Relay User Interface

More information

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS MiCOM 01 MiCOM Fast Feeder Differential Protection The MiCOM relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring

More information

7SR11 and 7SR12 Argus Overcurrent Relays Answers for infrastructure & cities.

7SR11 and 7SR12 Argus Overcurrent Relays Answers for infrastructure & cities. Reyrolle Protection Devices 7SR11 and 7SR12 Argus Overcurrent Relays Answers for infrastructure & cities. 7SR11 and 7SR12 Argus Overcurrent Relays Supervision 60CTS CT Supervision 74T/CCS Trip & Close

More information

Reyrolle Catalogue Answers for Energy

Reyrolle Catalogue Answers for Energy Reyrolle Protection Devices Reyrolle Catalogue Answers for Energy Index Compact Overcurrent Argus C 7SR11 & 7SR12 1 Multifunction Overcurrent Argus M 7SR21 & 7SR22 2 Multifunction Reclose Controller Recloser

More information

7SR21 & 7SR22 Argus Overcurrent Relay Energy Management

7SR21 & 7SR22 Argus Overcurrent Relay Energy Management Reyrolle Protection Devices 7SR21 & 7SR22 Argus Overcurrent Relay Energy Management Contents Technical Manual Sections 1. 7SR210 and 7SR220 Description of Operation 2. 7SR210 and 7SR220 Configuration

More information

7SR23 DAD High Impedance Protection Relay Answers for energy.

7SR23 DAD High Impedance Protection Relay Answers for energy. Reyrolle Protection Devices 7SR23 DAD High Impedance Protection Relay Answers for energy. Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration & Instruments 3. Performance

More information

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy Reyrolle Protection Devices 7SR11 and 7SR12 Argus Overcurrent Relays Answers for energy 7SR11 and 7SR12 Argus Overcurrent Relays 74T/CCS Trip & Close Circuit Supervision 60VTS VT Supervision Control 79

More information

APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL OVER CURRENT & EARTH FAULT PROTECTION RELAY TYPE MJT 315

APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL OVER CURRENT & EARTH FAULT PROTECTION RELAY TYPE MJT 315 JUNE 2009 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL OVER CURRENT & EARTH FAULT PROTECTION RELAY TYPE MJT 315 EASUN REYROLLE LIMITED 1 ISSUE NO : Ist Issue DATE OF ISSUE : 17-06 - 2009 DEPARTMENT

More information

7SG18 Solkor N Numeric Differential Protection

7SG18 Solkor N Numeric Differential Protection 7SG18 Solkor N Numeric Differential Protection Document Release History This document is issue 2010/02. The list of revisions up to and including this issue is: Pre release 2010/02 Document reformat due

More information

7SR17 Rho Motor Protection Relay Answers for energy.

7SR17 Rho Motor Protection Relay Answers for energy. Reyrolle Protection Devices 7SR17 Rho Motor Protection Relay Answers for energy. Page 2 of 6 2016 Siemens Protection Devices Limited Contents Technical Manual Chapters 1. Description of Operation 2. Settings,

More information

GRD130 - FEATURES APPLICATION

GRD130 - FEATURES APPLICATION FEATURES Phase undervoltage protection with IDMTL or DTL. Phase overvoltage protection with IDMTL or DTL. Zero phase sequence overvoltage (neutral voltage displacement) protection with IDMTL/DTL. Negative

More information

7SR18 Solkor Line Differential Protection Energy Management

7SR18 Solkor Line Differential Protection Energy Management Reyrolle Protection Devices 7SR18 Solkor Line Differential Protection Energy Management 7SR18 Solkor five or eight user-programmable binary output contacts and three or six user programmable status inputs

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

Reyrolle Protection Devices. 7SR210 & 7SR220 Argus Overcurrent Protection Relay. Answers for energy

Reyrolle Protection Devices. 7SR210 & 7SR220 Argus Overcurrent Protection Relay. Answers for energy Reyrolle Protection Devices 7SR10 & 7SR0 Argus Overcurrent Protection Relay Answers for energy 7SR10 7SR0 Argus Overcurrent Protection Relay Additional Functionality 7SR0n Directional Relay 7/59 Under/Over

More information

Reyrolle Protection Devices. 7PG2113/4/5/6 Solkor Pilot Wire Current Differential Protection with integrated Overcurrent Guard. Answers for energy

Reyrolle Protection Devices. 7PG2113/4/5/6 Solkor Pilot Wire Current Differential Protection with integrated Overcurrent Guard. Answers for energy Reyrolle Protection Devices 7PG2113/4/5/6 Solkor Pilot Wire Current Differential Protection with integrated Overcurrent Guard Answers for energy 7PG2113/4/5/6 Solkor Pilot Wire Current Differential Protection

More information

(1) Description of Operation. Autoreclose. 7SR224 Recloser Controller. (1) Description of Operation 7SR224 Appendix 2) Single/Triple Autoreclose

(1) Description of Operation. Autoreclose. 7SR224 Recloser Controller. (1) Description of Operation 7SR224 Appendix 2) Single/Triple Autoreclose (1) Description of Operation 7SR224 Appendix 2) Single/Triple Autoreclose (1) Description of Operation Appendix 2): 7SR224 Recloser Controller Single/Triple Autoreclose The copyright and other intellectual

More information

7SG1641 Ohmega Protection Relays Answers for energy

7SG1641 Ohmega Protection Relays Answers for energy Reyrolle Protection Devices 7SG1641 Ohmega 402-50 Protection Relays Answers for energy 7SG1641 Ohmega 402 50 Contents Contents 1 Description of Operation 2 Impedance Functions 3 Protection Schemes 4 Relay

More information

Reyrolle Protection Devices. 7SR10 Argus Overcurrent and Earth Fault Relay

Reyrolle Protection Devices. 7SR10 Argus Overcurrent and Earth Fault Relay Reyrolle Protection Devices 7SR10 Argus Overcurrent and Earth Fault Relay 7SR10 Argus Overcurrent and Earth Fault Relay Control 79 Auto Reclose 86 Lockout CB Control CB Trip/Close Features Cold Load Settings

More information

GRE120. Motor Protection and Control for MV Systems

GRE120. Motor Protection and Control for MV Systems Motor Protection and Control for MV Systems FEATURES Overcurrent protection for phase and earth faults (50/51P, 50/51N). Dependent and independent time characteristics (IDMTL and DTL). Restricted earth

More information

PRON NA60-CBA. IEC Communication Protocol User Guide PRON NA60-CBA. Version Page: 1 of 13 PRON NA60-CBA IEC

PRON NA60-CBA. IEC Communication Protocol User Guide PRON NA60-CBA. Version Page: 1 of 13 PRON NA60-CBA IEC IEC 870-5-103 Communication Protocol User Guide PRON NA60-CBA Page: 1 of 13 PRON NA60-CBA IEC 870-5-103 Contents Contents...2 1 IEC 870-5-103 Protocol...3 8.1 Physical Layer...3 8.1.1 Electrical Interface...3

More information

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy Reyrolle Protection Devices 7SG117 Argus 7 Synchronising Relay Answers for energy 7SG117 Argus 7 Synchronising Relay Fig 1. Independent check & system synchronising settings Adjustable slip frequency,

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

7SR45 Argus 7SR45 Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault Relay

7SR45 Argus 7SR45 Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault Relay 7SR5 Argus 7SR5 Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault Relay Energy Management 7SR5 Argus 7SR5 Argus Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault

More information

7SR23 DAD High Impedance Protection Relay Energy Management

7SR23 DAD High Impedance Protection Relay Energy Management Reyrolle Protection Devices 7SR23 DAD High Impedance Protection Relay Energy Management 2 Siemens Protection Devices Limited 7SR23 DAD High Impedance Relay User Interface 20 character x 4 line backlit

More information

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy Reyrolle Protection Devices 7SG118 Argus 8 Voltage & Frequency Relay Answers for energy 7SG118 Argus 8 Voltage and Frequency Relay Data Storage and Communication Serial communications conform to IEC60870-5-103

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics SIA-B Overcurrent & Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered / Standard CTs Main characteristics The SIA-B is an protection relay with self powered and dual powered (Self-powering

More information

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100% Operating range: 0.10 to 30 xin (step 0.01) 50P(2) Activation level 100% Deactivation level 95% Timer accuracy: 30 ms Operating range: 0.10 to 30 xin (step 0.01) 50N/G(2) Activation level 100% Deactivation

More information

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement

More information

7SR11 and 7SR12 Argus Overcurrent Relays Energy Management

7SR11 and 7SR12 Argus Overcurrent Relays Energy Management Reyrolle Protection Devices 7SR11 and 7SR12 Argus Overcurrent Relays Energy Management 7SR11 and 7SR12 Argus Overcurrent Relays Supervision 60CTS CT Supervision 74T/CCS Trip & Close Circuit Supervision

More information

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits 01 MiCOM P721 & P723 Numerical High Impedance Differential Relay The new P72x high impedance differential protection series provides an independent and simple high impedance differential protection solution

More information

7SR158 Argus Voltage and Frequency Relay Energy Management.

7SR158 Argus Voltage and Frequency Relay Energy Management. Reyrolle Protection Devices 7SR158 Argus Voltage and Frequency Relay Energy Management. Siemens Protection Devices Limited 2 7SR158 Argus Voltage & Frequency Relay User Interface 20 Character x 4 Line

More information

Reyrolle 7SR45 Self/Dual Powered Overcurrent Protection. Catalogue Reyrolle 7SR45 Edition 1. siemens.com/reyrolle

Reyrolle 7SR45 Self/Dual Powered Overcurrent Protection. Catalogue Reyrolle 7SR45 Edition 1. siemens.com/reyrolle Reyrolle 7SR45 Self/Dual Powered Overcurrent Protection Catalogue Reyrolle 7SR45 Edition 1 siemens.com/reyrolle 2 Digital Grid 7SR45 Self Powered/Dual Powered Non-Directional Overcurrent and Earth Fault

More information

GRE130. Protection and Control for MV Systems

GRE130. Protection and Control for MV Systems Protection and Control for MV Systems FEATURES Phase undervoltage protection with IDMTL or DTL(27). Phase overvoltage protection with IDMTL or DTL(59). Zero phase sequence overvoltage (neutral voltage

More information

EDR-3000 Eaton Distribution Relay

EDR-3000 Eaton Distribution Relay EDR-3000 Eaton Distribution Relay Technical Data New Information Description Page 1. General Description.......................... 2 2. Applications............................... 2 3. Drilling Pattern.............................

More information

GRE160. Transformer Protection

GRE160. Transformer Protection Transformer Protection FEATURES Fully numerical transformer protection Current differential protection for two-winding transformers with inrush restraint (87T) High-set differential overcurrent protection

More information

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Relion 605 series. Self-powered feeder protection REJ603 Product Guide Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1. Description... 3 2. Relay functions... 3 3. Protection functions... 4

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc Redundant Bus Protection Using High-Impedance Differential Relays Josh LaBlanc Purpose Discuss the configuration of the bus under study, and touch on the needs for redundant protection on the bus. Briefly

More information

VIP 40/45 VIP 400/410

VIP 40/45 VIP 400/410 40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

Transformer Protection IED

Transformer Protection IED Transformer Protection IED GR-00 series - The GR-00 Series is Toshiba s next generation of protection and control IED s, designed for transmission/distribution networks and providing a platform for distributed

More information

7SR210 & 7SR220 Argus Overcurrent Protection Relay Energy Management

7SR210 & 7SR220 Argus Overcurrent Protection Relay Energy Management Reyrolle Protection Devices 7SR0 & 7SR220 rgus Overcurrent Protection Relay Energy Management 7SR0 7SR220 rgus Overcurrent Protection Relay Description The 7SR0 and 7SR220 are a new generation of nondirectional

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

TWO-WINDING TRANSFORMER DIFFERENTIAL

TWO-WINDING TRANSFORMER DIFFERENTIAL E3-TR PROTECTION WITH AUTOMATIC VOLTAGE Because of the control, measuring and monitoring functions implemented, the IED can also be used as a bay control unit. The EuroCAP configuration tool, which is

More information

MiCOM P111 Numerical three phase and earth fault overcurrent relay description

MiCOM P111 Numerical three phase and earth fault overcurrent relay description Numerical three phase and earth fault overcurrent relay description PC15101b relays provide features for easy adaptation to different applications and operation conditions. IEC 60870-5-103 and Modbus RTU

More information

Current Matters. The Device issue. Siemens Protection Devices Ltd. In-depth looks at some of our best and most versatile products to date

Current Matters. The Device issue. Siemens Protection Devices Ltd. In-depth looks at some of our best and most versatile products to date Offshore Spotlight ENERGY Issue 02 Oct 2013 www.siemens.com/reyrolle Current Matters Siemens Protection Devices Ltd Protecting your electrical assets... today and tomorrow The Device issue In-depth looks

More information

Sepam IEC communication

Sepam IEC communication Electrical network protection Sepam IEC 60870-5-03 For Sepam series 20/40/60/80 User s manual 03/20 Safety instructions 0 Safety symbols and messages Read these instructions carefully and look at the equipment

More information

GRE110. Protection and Control for MV Systems

GRE110. Protection and Control for MV Systems Protection and Control for MV Systems FEATURES Overcurrent protection for phase and earth faults (50/5P, 50/5N). Dependent and independent time characteristics (IDMTL and DTL). Four independent current

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

7SR210 & 7SR220 Argus Overcurrent Protection Relay Energy Management.

7SR210 & 7SR220 Argus Overcurrent Protection Relay Energy Management. Reyrolle Protection Devices 7SR10 & 7SR0 rgus Overcurrent Protection Relay Energy Management. 7SR10 7SR0 rgus Overcurrent Protection Relay Standard Functionality - 7SR0 Directional Relay 1FL Fault Locator

More information

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 Content FPC 200 USER MANUAL Mar 2017 Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 1 USER MANUAL FPC 200-3/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

General Guidance, Secondary Injection

General Guidance, Secondary Injection General Guidance, Secondary Injection The following details the procedure for basic secondary injection to determine and verify the correct operation of the Motorvision2, the procedure therefore is applicable

More information

AUGUST 2001 APPLICATION AND COMMISSIONING MANUAL MIT161 RELAY EASUN REYROLLE LIMITED

AUGUST 2001 APPLICATION AND COMMISSIONING MANUAL MIT161 RELAY EASUN REYROLLE LIMITED AUGUST 2001 APPLICATION AND COMMISSIONING MANUAL MIT161 RELAY EASUN REYROLLE LIMITED 1 Issue No : 2nd Issue Date of Issue : 30.08.2001 Department : TP-CTS 2 SENSITIVE CURRENT PROTECTION PROTECTION HEALTHY

More information

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, 2 x RJ-45 Main Range of product Product or component type Relay application Configuration type (Cortec) [Us] rated supply voltage

More information

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, RS-485 Main Range of product Product or component type Relay application Device short name [Us] rated supply voltage Type of

More information

GRT100 FEATURES APPLICATION

GRT100 FEATURES APPLICATION FEATURES Fully numerical transformer protection Current differential protection for two-winding or three-winding transformers High-set differential overcurrent protection No interposing CTs required CT

More information

Using the Bitronics 70 Series to Improve Local Monitoring and Control

Using the Bitronics 70 Series to Improve Local Monitoring and Control Automate a Substation and Preserve the Electromechanical Relay Investment Part Two of Four Using the Bitronics 70 Series to Improve Local Monitoring and Control Paul Grabowski - Bitronics Senior Application

More information

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

Recloser Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast

More information

Configuration and Interoperability Guide for IEC for the SEL-751 Feeder Protection Relay. July 10, 2015

Configuration and Interoperability Guide for IEC for the SEL-751 Feeder Protection Relay. July 10, 2015 Configuration and Interoperability Guide for IEC 60870-5-103 for the SEL-751 Feeder Protection Relay July 10, 2015 Contents 1 Interoperability... 3 1.1 Physical Layer... 3 Electrical Interface... 3 Optical

More information

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and

More information

IED (Intelligent Electronic Device)

IED (Intelligent Electronic Device) IED (Intelligent Electronic Device) Neopis IED (Intelligent Electronic Device) Intelligent Electronic Device Dynamic Characteristics PROMET 4300-F PROMET 4300-M Relay Type Setting Setting Range Setting

More information

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements Introduction to Bus Protection By Matt Horvath, P.E. November 6, 2018 Electrical Buses Physical and Electrical Junction A bus is a critical element of a power system, as it is the point of convergence

More information

Type: P9680 Combined Overcurrent and Earth Fault Relay

Type: P9680 Combined Overcurrent and Earth Fault Relay Type: P9680 Combined Overcurrent and Earth Fault Relay True R.M.S. measurements Low Set and High Set tripping thresholds for both Overcurrent and Earth Fault detection 6 selectable IDMT (Inverse Definite

More information

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4 Content FPC 400 USER MANUAL Apr 2017 Feeder F3 Motor M4 Busbar B3 Transformer T4 1 USER MANUAL FPC 400-4/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia 2016. All rights reserved.

More information

SIL-A. Overcurrent and Earth Fault Relay for Primary and Secondary Distribution. Main characteristics

SIL-A. Overcurrent and Earth Fault Relay for Primary and Secondary Distribution. Main characteristics SIL-A Overcurrent and Earth Fault Relay for Primary and Secondary Distribution Main characteristics The SIL-A is an overcurrent and earth fault protection relay for primary and secondary distribution with

More information

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays 01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety

More information

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead solutions Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead switching products Brochure Your outdoor overhead distribution

More information

GRE140. Protection and Control for MV Systems

GRE140. Protection and Control for MV Systems Protection and Control for MV Systems FEATURES Four stage non-directional and directional overcurrent protection for phase and earth faults with IDMTL or DTL. Polarizing voltage memory. Directional earth

More information

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays... .1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....

More information

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay Protective Relays Electrical Apparatus ixp-420 Transformer Protection Relay 165-420 Figure 1: Edison Idea Relay The ixp-420 is a member of Cooper Power Systems Edison Idea line of protective relays. The

More information

VISIONr TECHNICAL MANUAL Issue 3. VISIONr. Technical Manual

VISIONr TECHNICAL MANUAL Issue 3. VISIONr. Technical Manual VISIONr Technical Manual Contents 1 INTRODUCTION....7 1.1 Protection Functions...7 1.2 Real Time Metering Data....7 2 TECHNICAL SPECIFICATION...8 2.1 Power Supply...8 2.2 Measurement...8 2.3 Protection

More information

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation

More information