Relion 670 series. Generator protection REG670 ANSI Operator's manual

Size: px
Start display at page:

Download "Relion 670 series. Generator protection REG670 ANSI Operator's manual"

Transcription

1 Relion 670 series Generator protection REG670 ANSI

2

3 Document ID: 1MRK UUS Issued: February 2015 Revision: B Product version: 1.2 Copyright 2012 ABB. All rights reserved

4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license. Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. Warranty Please inquire about the terms of warranty from your nearest ABB representative. ABB Inc Main Campus Drive Raleigh, NC 27606, USA Toll Free: HELP-365, menu option #8 ABB Inc Harvester Road Burlington, ON L7N 3W5, Canada Toll Free: HELP-365, menu option #8 ABB Mexico S.A. de C.V. Paseo de las Americas No. 31 Lomas Verdes 3a secc , Naucalpan, Estado De Mexico, MEXICO Phone: (+1) , menu option #8

5 Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

6 Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN and EN for the EMC directive, and with the product standards EN and EN for the low voltage directive. The product is designed in accordance with the international standards of the IEC series and ANSI C37.90.

7 Table of contents Table of contents Section 1 Section 2 Section 3 Section 4 Section 5 Introduction...11 Introduction to the operator s manual...11 About the complete set of manuals for an IED...11 About the operator s manual...12 Intended audience...13 Related documents...13 Revision notes...14 Safety information...15 Warnings...15 Overview...17 Operator overview...17 Identify the IED...17 Understand the IED local human-machine interface...21 Overview...21 Keypad...21 Key activated screens...23 The Help screen...23 The Reset screen...23 LCD...24 Medium...24 LED...24 Introduction...24 Status indication LEDs...24 Indication LEDs...25 Local HMI setup...25 How to navigate...26 Read...26 Change...26 Control...26 Understand the injection unit local human-machine interface...29 Injection unit REX REX060 start up sequence

8 Table of contents REX060 Front panel controls...30 Display...31 How to set frequency and voltage and current gain factors...33 Setting system frequency...33 Setting stator and rotor injection frequency...33 Selecting rotor gain...33 Selecting stator gain...34 Resetting overvoltage...34 Section 6 Section 7 Section 8 Section 9 Understand the HMI tree...37 Overview...37 Menu-tree for REG Read measured values...39 Overview...39 View analog primary values...40 Overview...40 View analog secondary values...40 Overview...40 View analog mean values...41 Overview...41 ma input module MIM...41 Signal matrix for ma inputs SMMI...41 View monitoring values...42 Service values CVMMXN...42 Current phasors CMMXU...42 Voltage phasors VMMXU/VNMMXU...42 Current sequence component CMSQI...42 Voltage sequence component VMSQI...42 View metering values...43 Pulse counter logic PCGGIO...43 Function for energy calculation and demand handling ETPMMTR...43 Event list...45 View events...45 Overview...45 Handle disturbances...47 Identify a disturbance...47 View disturbance record details

9 Table of contents View general information...47 View disturbance indications...47 View event recordings...48 View trip values...48 Trigger a disturbance report manually...48 Section 10 Read and change settings...49 System time and synchronization...49 System time...49 Time synchronization...49 Overview...49 TimeSynch...50 TIMESYNCHBIN...50 DSTBEGIN...50 DSTEND...50 SYNCHIRIG-B...50 SYNCHSNTP...50 TIMEZONE...51 General settings...51 Power system...51 Overview...51 Identifiers...51 Primary values...51 Communication...52 Overview...52 Remote communication...52 SPA, LON and IEC settings...52 Station communication...53 Ethernet configuration...55 Analog and I/O modules...55 Overview...55 Analog modules...56 I/O modules...57 HMI...57 Overview...57 LEDs...57 Screen...57 Functions...57 Change lock...58 Differential protection

10 Table of contents Overview...58 Generator differential protection GENPDIF (87G)...58 Transformer differential protection, two winding T2WPDIF (87T)...58 Transformer differential protection, three winding T3WPDIF (87T)...58 Impedance protection...59 Sensitive rotor earth fault protection, injection based ROTIPHIZ (64R) % stator earth fault protection STTIPHIZ (64S)...59 Control...59 Apparatus control...59 Control commands...60 Synchronism-check and energizing check SESRSYN (25)...61 Monitoring...61 Overview...61 Service values CVMMXN...61 Current phasors CMMXU...62 Voltage phasors VMMXU/VNMMXU...62 Current sequence components CMSQI...62 Voltage sequence components VMSQI...62 Disturbance report DRPRDRE...63 Generic measured value MVGGIO...63 Event function...63 Logical signal status report BINSTATREP...64 IEC Metering...64 Overview...64 Pulse counter logic PCGGIO...64 Function for energy calculation and demand handling ETPMMTR...65 Setting group N...65 Overview...65 Differential protection...65 Overview...65 Generator differential protection GENPDIF (87G)...65 Transformer differential protection, two winding T2WPDIF (87T)...65 Transformer differential protection, three winding T3WPDIF (87T)...66 Restricted ground fault protection REFPDIF (87N)

11 Table of contents High impedance differential protection HZPDIF (87X)...66 Impedance protection...66 Overview...66 Full-scheme distance protection, mho characteristic ZMHPDIS (21)...67 Directional impedance element for mho characteristics ZDMRDIR (21D)...67 Pole slip protection PSPPPAM (78)...67 Sensitive rotor earth fault protection, injection based ROTIPHIZ (64R) % stator earth fault protection STTIPHIZ (64S)...67 Loss of excitation (40)...67 Current protection...68 Overview...68 Accidental energizing protection for synchronous generator AEGGAPC (50AE)...68 Breaker failure protection CCRBRF (50BF)...68 Directional over-power protection GOPPDOP (32)...68 Directional under-power protection GUPPDUP (37)...68 Instantaneous phase overcurrent protection PHPIOC (50)...69 Instantaneous residual overcurrent protection EFPIOC (50N)...69 Negativ sequence time overcurrent protection for machines NS2PTOC (46I2)...69 Four step directional negative phase sequence overcurrent protection NS4PTOC (46I2)...69 Four step phase overcurrent protection OC4PTOC (51_67)...69 Pole discrepancy protection CCRPLD (52PD)...70 Four step residual overcurrent protection EF4PTOC (51N67N)...70 Sensitive directional residual over current and power protection SDEPSDE (67N)...70 Thermal overload protection, two time constants TRPTTR (49)...70 Voltage protection...70 Overview...70 Overexcitation protection OEXPVPH (24)...71 Two step overvoltage protection OV2PTOV (59)...71 Two step residual overvoltage protection ROV2PTOV (59N)

12 Table of contents 100% stator earth fault protection, 3rd harmonic based STEFPHIZ (59THD)...71 Two step undervoltage protection UV2PTUV (27)...71 Voltage differential protection VDCPTOV (60)...72 Frequency protection...72 Overview...72 Overfrequency protection SAPTOF (81)...72 Rate-of-change frequency protection SAPFRC (81)...72 Underfrequency protection SAPTUF (81)...72 Multipurpose protection...73 Overview...73 General current and voltage protection CVGAPC...73 Secondary system supervision...73 Overview...73 Current circuit supervision CCSRDIF (87)...73 Fuse failure supervision SDDRFUF...73 Control...74 Overview...74 synchronism-check and energizing check SESRSYN (25)...74 Monitoring...74 Overview...74 Event counter CNTGGIO...74 Logic...74 Overview...74 Tripping logic SMPPTRC (94)...75 Trip matrix logic TMAGGIO...75 LogicGate...75 LogicRSMemory...75 LogicSRMemory...75 LogicTimerSet...75 Activate setting group...75 Language...76 Section 11 Diagnose IED status...77 Read internal events...77 Find available functions...77 Section 12 Test the IED...79 Overview...79 IED test mode...80 View binary input values

13 Table of contents Overview...80 Binary Input Module BIM...81 View binary output values...81 Overview...81 Binary Output Module BOM...81 Function test modes...81 Overview...81 Differential protection...81 Impedance protection...81 Current protection...82 Voltage protection...82 Frequency protection...82 Multipurpose protection...82 Secondary system protection...82 Control...82 Monitoring...82 Logic...83 Function status...83 Overview...83 Differential protection...83 Generator differential protection GENPDIF (87G)...83 Transformer differential protection, two winding T2WPDIF (87T)...83 Transformer differential protection, three winding T3WPDIF (87T)...83 Restricted ground fault protection, low impedance REFPDIF (87N)...84 High impedance differential protection HZPDIF (87)...84 Impedance protection...84 Full-scheme distance protection, mho characteristic ZMHPDIS (21)...84 Directional impedance element for mho characteristic ZDMRDIR (21D)...84 Pole slip protection PSPPPAM (78)...85 Sensitive rotor earth fault protection, injection based ROTIPHIZ (64R) % stator earth fault protection STTIPHIZ (64S)...85 Loss of excitation LEXPDIS (40)...85 Current protection...85 Accidental energizing protection for synchronous generator AEGGAPC (50AE)

14 Table of contents Breaker failure protection CCRBRF (50BF)...85 Directional over-power protection GOPPDOP (32)...86 Directional under-power protection GUPPDUP (37)...86 Instantaneous phase overcurrent protection PHPIOC (50)...86 Instantaneous residual overcurrent protection EFPIOC (50N)...86 Negative sequence time overcurrent protection for machines NS2PTOC (46I2)...86 Four step directional negative phase sequence overcurrent protection NS4PTOC (46I2)...87 Four step phase overcurrent protection OC4PTOC(51_67)...87 Pole discordance protection CCRPLD (52PD)...87 Four step residual overcurrent protection EF4PTOC (51N_67N)...87 Sensitive directional residual over current and power protection SDEPSDE (67N)...87 Thermal overload protection, two time constants TRPTTR (49)...87 Voltage protection...88 Overexcitation protection OEXPVPH (24)...88 Two step overvoltage protection OV2PTOV (59)...88 Two step residual overvoltage protection ROV2PTOV (59N) % Stator earth fault protection, 3rd harmonic based STEFPHIZ (59THD)...88 Two step undervoltage protection UV2PTUV (27)...89 Voltage differential protection VDCPTOV (60)...89 Frequency protection...89 Overfrequency protection SAPTOF (81)...89 Rate-of-change frequency protection SAPFRC (81)...89 Underfrequency protection SAPTUF (81)...89 Multipurpose protection...90 General current and voltage protection CVGAPC...90 Secondary system supervision...90 Current circuit supervision CCSRDIF...90 Fuse failure supervision SDDRFUF...90 Control...91 Apparatus control...91 Commands...95 IEC61850 generic communication I/O functions DPGGIO...96 Synchronism check and energizing check SESRSYN (25)

15 Table of contents Monitoring...96 Logical signal status report BINSTATREP...96 Disturbance report DRPRDRE...96 Event counter CNTGGIO...97 Generic measured value MVGGIO...97 Global positioning system...97 IEC61850 generic communication I/O functions 16 inputs SP16GGIO...97 LEDs...97 Measured value expander block RANGE_XP...98 IEC61850 generic communication I/O functions SPGGIO...98 Logic...98 Boolean 16 to Integer conversion B16IFCVI, B16I...98 Integer to Boolean 16 conversion IB16FCVB, IB Tripping logic SMPPTRC (94)...98 Trip matrix logic TMAGGIO...99 Logic gate...99 Logic SR/RS memory...99 Logic timer set...99 Communication...99 Remote communication...99 Station communication Setting groups Test Authorization LED Test Line differential test Section 13 Control and supervise the bay Overview Read measured values and check apparatus status Locating and using the single line diagram Control screen messages Section 14 Reset Reset guide for IED Reset counters Circuit breaker SXCBR Circuit switch SXSWI Reset event counter CNTGGIO Reset pulse counter PCGGIO

16 Table of contents LDCM clear counters Function for energy calculation and demand handling ETPMMTR Reset disturbances and event list DRPRDRE Reset LEDs Start and trip LEDs All indication LEDs Reset lockout SMPPTRC (94) Reset process eventlist Reset temperature functions Reset guide for REX Resetting overvoltage Section 15 Authorization Overview Principle of operation LogOn or logoff Authorization handling in the IED Internet Protocol ports security guideline Section 16 Glossary

17 Planning & purchase Engineering Installing Commissioning Operation Maintenance Decommissioning deinstalling & disposal 1MRK UUS B Section 1 Introduction Section 1 Introduction About this chapter This chapter is an introduction to the operator s manual, its purpose and usage. 1.1 Introduction to the operator s manual About the complete set of manuals for an IED The user s manual (UM) is a complete set of five different manuals: Engineeringmanual Installation and Commissioning manual Operator s manual Application manual Technical reference manual IEC V1 EN IEC en.vsd The Application Manual (AM) contains application descriptions, setting guidelines and setting parameters sorted per function. The application manual should be used to find out when and for what purpose a typical protection function could be used. The manual should also be used when calculating settings. 11

18 Section 1 Introduction 1MRK UUS B The Technical Reference Manual (TRM) contains application and functionality descriptions and it lists function blocks, logic diagrams, input and output signals, setting parameters and technical data sorted per function. The technical reference manual should be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. The Installation and Commissioning Manual (ICM) contains instructions on how to install and commission the protection IED. The manual can also be used as a reference during periodic testing. The manual covers procedures for mechanical and electrical installation, energizing and checking of external circuitry, setting and configuration as well as verifying settings and performing directional tests. The chapters are organized in the chronological order (indicated by chapter/section numbers) in which the protection IED should be installed and commissioned. The Operator s Manual (OM) contains instructions on how to operate the protection IED during normal service once it has been commissioned. The operator s manual can be used to find out how to handle disturbances or how to view calculated and measured network data in order to determine the cause of a fault. The Engineering Manual (EM) contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also recommends a sequence for engineering of protection and control functions, LHMI functions as well as communication engineering for IEC and DNP About the operator s manual Use the operator s manual for instruction on how to perform common tasks during normal service. The operator s manual contains the following chapters: The chapter Safety information presents warnings and notices, which the user should pay attention to. The chapter Overview describes operations an operator may perform on a daily basis or when the need arises. The chapter Understand the local human-machine interface describes how to use the human-machine interface. The chapter Understand the HMI tree describes the different menu trees. The chapter Read measured values describes how to locate and identify available measurement data. The chapter Event list describes the location and nature of recorded events. The chapter Handle disturbances describes how to retrieve disturbance information and reset alarms. The chapter Read and change settings describes how to locate, and change settings and parameters. 12

19 1MRK UUS B Section 1 Introduction The chapter Diagnose IED status describes the location and use of available diagnostic tools. The chapter Test the IED describes the tests applicable to the IED. The chapter Control and supervise the bay describes how to use the Single Line Diagram to open and close primary apparatuses. The chapter Reset describes resetting procedures. The chapter Authorization describes user categories and password procedures. The chapter Glossary describes words and acronyms used in the literature describing the IED. This manual does not contain any instructions for commissioning or testing Intended audience General The operator s manual addresses the operator, who operates the IED on a daily basis. Requirement The operator must be trained in and have a basic knowledge of how to operate protection equipment. The manual contains terms and expressions commonly used to describe this kind of equipment Related documents Documents related to REG670 Operator s manual Installation and commissioning manual Technical reference manual Application manual Product guide customized Identity number 1MRK UUS 1MRK UUS 1MRK UUS 1MRK UUS 1MRK BUS Connection and Installation components 1MRK BEN Test system, COMBITEST 1MRK BEN Accessories for 670 series IEDs 1MRK BEN 670 series SPA and signal list 1MRK WUS IEC Data objects list for 670 series 1MRK WUS Engineering manual 670 series 1MRK UUS Buyer s guide REG 216 1MRB BEN Communication set-up for Relion 670 series 1MRK UEN 13

20 Section 1 Introduction 1MRK UUS B More information can be found on Revision notes Revision Description - First issue for 670 series version 1.2 A Maintenance updates, PR corrections B Maintenance updates, PR corrections 14

21 1MRK UUS B Section 2 Safety information Section 2 Safety information About this chapter This chapter lists warnings and cautions that must be followed when handling the IED. 2.1 Warnings Do not touch circuitry during operation. Potentially lethal voltages and currents are present. Always connect the IED to protective ground, regardless of the operating conditions. This also applies to special occasions such as bench testing, demonstrations and off-site configuration. Operating the IED without proper grounding may damage both IED and measuring circuitry and may cause injuries in the event of an accident. Never remove any screw from a powered IED or from a IED connected to powered circuitry. Potentially lethal voltages and currents are present. Always avoid touching the circuitry when the cover is removed. The product contains electronic circuitries which can be damaged if exposed to static electricity (ESD). The electronic circuitries also contain high voltage which is lethal to humans. 15

22 16

23 1MRK UUS B Section 3 Overview Section 3 Overview About this chapter This chapter presents a general overview of the. 3.1 Operator overview The Local human-machine interface (LHMI) on the IED provides an ideal mechanism for the day to day operation and even advanced use of the IED. The keypad, LCD and LEDs on the front of the IED are what constitute the LHMI. Troubleshooting, apparatus control, monitoring, setting and configuring are all possible via this interface. Through the screens and menu elements available, as well as the keypad, the user is able to navigate throughout the menu structure and move from screen to screen. This document is, to a great extent, arranged in the same way as the IED software is structured and describes all aspects of operation via the LHMI. The operator can document disturbances so that their causes can be analyzed and evaluated for future reference. For example, the fault currents and voltages at the time of the fault can be documented. The operator can also retrieve data about protected objects, providing further information for fault analysis. This implies viewing the mean value of current, voltage, power and frequency or primary and secondary measured phasors. The operator can check the IED status at any time. In some cases the operator may need to change the way the IED operates. This might include changing the active setting group or a parameter value. This must always be done strictly according to applicable regulations because un-authorized changes may lead to severe damage of the protected object especially if a fault is not properly disconnected. 3.2 Identify the IED To identify the IED, open the diagnostics menu. The identity of the IED along with other data is found under: Main menu/diagnostics/ied status/product Identifiers When the Product identifiers submenu is opened, the user sees the following screen: 17

24 Section 3 Overview 1MRK UUS B IEC en.vsd IED V1 EN Figure 1: Typical example of product identifier screen on local HMI IEDProdType ProductDef is the Relion 670 series product type (REB, REC, RED, REG, REL, RET and so on) specifies the version of the product, in the following order: major version. minor version. major revision. minor revision ( for example) Both IEDProdType and ProductDef are visible in the PCM600 tool, under Properties: 18

25 1MRK UUS B Section 3 Overview IEC V1 EN IEC en.vsd Figure 2: Typical example of IED product type and version properties in PCM600 FirmwareVer IEDMainFunType Specifies the version of the product firmware Specifies the main IED functionality, in accordance to IEC numbering: REL - 128, compatible range REC - 242, private range RED - 192, compatible range RET - 176, compatible range REB - 207, private range REG - 150, private range REQ 245, private range SerialNo OrderingNo ProductionDate Are production identifiers 19

26 20

27 1MRK UUS B Section 4 Understand the IED local human-machine interface Section 4 Understand the IED local human-machine interface About this chapter This chapter describes the display, its keys (buttons) and LEDs that make up the local HMI on the IED. How the keys are used to navigate the HMI, how to interpret the graphic information on the LCD and, what the LEDs indicate is explained in the sections that follow. 4.1 Overview The human machine interface is used to monitor and to some extent control the way the IED operates. The configuration designer can add functions that alert to events requiring the attention of the operator. ANSI V1 EN Figure 3: 1/1 x 19 case with medium LCD 4.2 Keypad The keypad is used to monitor and operate the IED. The keypad has the same look and feel in all IEDs. LCD screens and other details may differ but the way the keys function is identical. 21

28 Section 4 Understand the IED local human-machine interface 1MRK UUS B IEC V1 EN Figure 4: The HMI keypad. Table 1 describes the HMI keys that are used to operate the IED. Table 1: Key Function HMI keys on the front of the IED Press to close or energize a breaker or disconnector. IEC V1 EN Press to open a breaker or disconnector. IEC V1 EN Press to open two sub menus: Key operation and IED information. IEC V1 EN Press to clear entries, cancel commands or edit. IEC V1 EN Press to open the main menu and to move to the default screen. IEC V1 EN Press to set the IED in local or remote control mode. IEC V1 EN Press to open the reset screen. IEC V1 EN Press to start the editing mode and confirm setting changes, when in editing mode. IEC V1 EN Table continues on next page 22

29 1MRK UUS B Section 4 Understand the IED local human-machine interface Key Function Press to navigate forward between screens and move right in editing mode. IEC V1 EN Press to navigate backwards between screens and move left in editing mode. IEC V1 EN Press to move up in the single line diagram and in the menu tree. IEC V1 EN Press to move down in the single line diagram and in the menu tree. IEC V1 EN 4.3 Key activated screens The Help screen The help screen is activated by pressing the Help key on the front panel of the IED. It includes the submenu listed below: General operation The Reset screen The General Operation submenu provides information about the IED keypad. The Open and Close keys are used to open (OFF) and close (ON) breakers and disconnectors when using the Single Line Diagram (SLD) in direct control situations. The reset screen is activated by the Reset key on the front panel of the IED or via the main menu. The reset screen includes the submenus listed below: Reset LEDs Reset lockout Reset counters Reset temperature functions The Reset LEDs submenu consists of two lower level menus which are the Start and trip LEDs and All indication LEDs submenus. To reset a counter, the actual counter must first be selected. The submenus and their structures are discussed in the Reset chapter of this document. 23

30 Section 4 Understand the IED local human-machine interface 1MRK UUS B 4.4 LCD Medium The following case sizes can be equipped with the medium size LCD: 1/2 x 19 3/4 x 19 1/1 x 19 This is a fully graphical monochrome LCD which measures 4.7 x 3.5 inches. It has 28 lines with up to 40 characters per line. To display the single line diagram, this LCD is required. 4.5 LED Introduction The LED module is a unidirectional means of communicating. This means that events may occur that activate a LED in order to draw the operators attention to something that has occurred and needs some sort of action Status indication LEDs The three LEDs above the LCD provide information as shown in the table below. LED Indication Green: Steady Flashing Dark Yellow: Steady Flashing Red: Steady Information In service Internal failure No power supply Dist. rep. triggered Terminal in test mode Trip command issued 24

31 1MRK UUS B Section 4 Understand the IED local human-machine interface Indication LEDs The LED indication module comprising 15 LEDs is standard in 670 series. Its main purpose is to present an immediate visual information for protection indications or alarm signals. Alarm indication LEDs and hardware associated LEDs are located on the right hand side of the front panel. Alarm LEDs are located on the right of the LCD screen and show steady or flashing light. Steady light indicates normal operation. Flashing light indicates alarm. Alarm LEDs can be configured in PCM600 and depend on the binary logic. Therefore they can not be configured on the local HMI. Typical examples of alarm LEDs Bay controller failure CB close blocked Interlocking bypassed Differential protection trip SF6 Gas refill Position error CB spring charge alarm Oil temperature alarm Thermal overload trip Pressure relief/bucholtz The RJ45 port has a yellow LED indicating that communication has been established between the IED and a computer. The Local/Remote key on the front panel has two LEDs indicating whether local or remote control of the IED is active. 4.6 Local HMI setup The contrast and other settings of the LCD can be adjusted from the local HMI menu tree. The contrast and other factory settings for the local HMI can be adjusted as follows: Settings/General settings/hmi/screen 25

32 Section 4 Understand the IED local human-machine interface 1MRK UUS B 4.7 How to navigate Read To read values and access information about the objects being monitored the operator must navigate the menu tree using the arrow keys. The active submenu or value is highlighted. Navigation is as follows: Press the right arrow key to move to the main menu. Press the down arrow key to move from the Single line diagram to the desired submenu. Use the right arrow key to move downwards in the HMI tree until the desired parameter is displayed. Press C and the down arrow key simultaneously to see the next page in the parameter screen. Press C and the up arrow key simultaneously to return to the previous parameter screen. Use the left arrow key to navigate back up the menu tree Change To change a parameter setting the following steps should be followed: 1. Navigate to the desired parameter or quantity using the arrow keys. 2. Press the E key when the parameter to be changed is highlighted. 3. Move between digits or letters using the left and right arrow keys. 4. Use the up and down arrow keys to change the digit or letter concerned. 5. Press the E key once the desired changes have been made. 6. Press the left arrow key to move up a level in the HMI tree. 7. You will be prompted to confirm the changes, use the left and right arrow keys to toggle between yes and no in the pop up window and press the E key to confirm your choice. 8. Press the left arrow key to move up to the next level in the HMI tree Control The HMI offers the operator the opportunity to exercise direct local control over breakers and other apparatuses in the bay using the graphic display and designated keys on the front panel of the IED. 26

33 1MRK UUS B Section 4 Understand the IED local human-machine interface By pressing the L/R key until the uppermost of the two LEDs next to the key lights up, local operator control can be exercised from the HMI. An apparatus is selected using the up and down arrow keys. The active apparatus is highlighted in the display. The Open or Close commands are issued by pressing the Open or Close keys; The user is requested to confirm the command in a pop-up window. E confirms a command; C cancels it. Interlocking or synchronism-check conditions may cause other query windows to popup. 27

34 28

35 1MRK UUS B Section 5 Understand the injection unit local human-machine interface Section 5 Understand the injection unit local humanmachine interface 5.1 Injection unit REX060 The injection unit REX060 is used to inject voltage and current signals to the generator or motor stator and rotor circuits. REX060 generates two square wave signals with different frequencies for injection into the stator and rotor circuits respectively. The response from the injected voltage and currents are then measured by the REX060 unit and amplified to a level suitable for the analog voltage inputs of IED. For local operation, the REX060 unit is provided with a control panel on the front. Local operation shall only be performed according to the operation regulations set up by the relevant operation authority of the plant. 5.2 REX060 start up sequence When the injection unit REX060 is energized, the ABB logotype is shown followed by current REX060 revision status. When the start up sequence is completed, the main menu (normal display content) is shown. The duration of the start up sequence is a few seconds. 29

36 Section 5 Understand the injection unit local human-machine interface 1MRK UUS B 5.3 REX060 Front panel controls IEC en.vsd IEC V1 EN Figure 5: REX060 front panel 30

37 1MRK UUS B Section 5 Understand the injection unit local human-machine interface Table 2: Key HMI keys on the front of the injection unit REX060 Function The Injection switch enables injection at rotor and stator 2 s after switching on. A LED indicates that the injection switch is set to enable injection. The injection switch can be padlocked in off position in order to cut-off both injection signals. The Key-lock button enables/disables the keypad. Hold the Key-lock button for a period of 1.2 s to 4 s to lock or unlock the keys. A key-lock LED indicates when the keypad is unlocked. Moves the cursor in the direction of the arrows With the cursor is in value change state, pressing the up button increases the value and pressing the down button decreases the value. Pressing the clear button cancels changes that have not been stored. Pressing the enter button stores the changed value. If the value is outside range, the limit value is stored. 5.4 Display On the front of the enclosure there is a backlit LCD. 6 x 12 pixel characters Graphical LCD 128 x 64 pixels In figure 6 the content of the display is shown for a REX060 with one SIM and one RIM module. Row 1 contains mains frequency information. Row 2-3 contains stator information and row 4-5 rotor information. Column 1 (empty) gives status, column 2 and 3 are informative and column 4 contains variables, settable by the keypad. 31

38 Section 5 Understand the injection unit local human-machine interface 1MRK UUS B Row Column System STATOR UmaxEF ROTOR Gain f [Hz] : 50 f [Hz] : [V] : f [Hz] : IEC en.vsd IEC V1 EN Figure 6: Display content in normal operation Column 1 (status column) symbols Table 3: Status symbols and their description Status symbol Description of the status Priority IEC V1 EN IEC V1 EN Ø IEC V1 EN Over voltage occurred, injection is blocked. This can occur on both X61/62 and X81/82 (Stator & Rotor) simultaneously or on either of them. The symbol is displayed in the status column (column 1) in row 2 for X61/62 and in row 4 for X81/82. The injection is blocked until a manual reset of the blocking occurs. Injection blocked by the injection switch. The symbol is displayed in the status column (column 1) and is always shown in both row 2 and 4. Injection blocked by binary input. Blocked injection will be shown in the status column (column 1) depending on binary in status. This can occur on both X61/62 then shown in row 2 and X81/82 then shown in row 4 (Stator & Rotor) simultaneously or on ether of them. Analog output saturation. This status is set when the analog signal, current and or voltage, to REG670 IED is too high and may thereby be incorrect due to saturation in amplifier stage. Saturation status will be shown in the status column (column 1) in row 3 or 5 depending on the saturation occurrence 1 2 Over voltage blocked status overrides displaying of this status 3 Injection switch and over voltage blocked overrides displaying of this status Not applicable Backlight is on for 30 seconds after pressing any button. Backlight activation by pressing any button does not cause any other action than turning on the backlight. 32

39 1MRK UUS B Section 5 Understand the injection unit local human-machine interface 5.5 How to set frequency and voltage and current gain factors Frequency, current and voltage gain for the stator and/or rotor can be set and stored from the injection unit HMI. If a value is out of range, the limit value is stored. The display shows the latest stored settings. The settings are stored in non-volatile memory, which means that they remain stored in case IED is powered off Setting system frequency Frequency can be set to either 50 or 60 Hz. 1. Use the Up and Down button to select frequency. 2. Store the new frequency by pressing the Enter button, or clear the last stored frequency by pressing the Clear button Setting stator and rotor injection frequency Frequency can be set as integer in range 50 to 250 Hz for a stator and 75 to 250 Hz for a rotor. 1. Use the keypad to navigate to stator or rotor frequency (row 2 or 4) 2. Press E to enter value change state 3. Use the Up and Down button to select frequency 4. Store the new frequency by pressing the E (Enter) button, or clear the chosen frequency by pressing the C (Clear) button Selecting rotor gain Default (gain factor 3) is the recommended level, where a defined effect of worst case single fault at exciter circuit is allowed. A higher gain factor (4) may cause saturation in case of single fault in exciter circuit. A lower gain factor may be needed if the degree of disturbance is high. Change from default value only if requested by ICT tool during calibration procedure. Select rotor gain factor according to the table below. 33

40 Section 5 Understand the injection unit local human-machine interface 1MRK UUS B Table 4: Rotor gain Gain factor Note 1 Extreme 2 Enhanced 3 Default 4 Reduced Selecting stator gain Stator gain factor for both voltage and current depends on the highest voltage that may occur at the injection point of VT or DT. That voltage depends on the VT/DT ratio and the stator rated primary voltage. Select gain factor in accordance with highest voltage that may occur at the injection point. See Technical reference manual for exact formulas depending on particular injection arrangement. Table 5: Stator gain VmaxEF [V] Default value up to 120 Note Resetting overvoltage Stator and rotor injection output is protected against voltages exceeding maximum operating range (10% of rated VT/DT) by a relay blocking the injection circuit. This blocking is controlled by measuring the stator and/or rotor voltage, and remains blocked until manually reset. The blocking remains in the non-volatile memory when the IED is powered off. Overvoltage blocking is indicated by a symbol shown in Table 3. Resetting procedure: 34

41 1MRK UUS B Section 5 Understand the injection unit local human-machine interface 1. Power off the REX Press and hold the C and Key-lock buttons. 3. Power on the REX060 and wait until the status indication Over-voltage (symbol) disappears from the display. 4. Release the C and Key-lock buttons. REX060 stator and rotor overvoltage protection of injection circuit Both rotor and stator have two levels of protection, injection circuit interruption controlled by the voltage sense input and a fuse for over-current protection. The voltage controlled interruption, overvoltage, will normally occur prior to interruption by fuse and the reset sequence is described above. A blown fuse requires module disassembling to replace the fuse (F 4 A 250 V for stator and F 160 ma 250 V for rotor). However, if this occurs it is recommended to identify the reason for the overcurrent and take necessary actions to reduce the current before restarting the unit. The problem must be outside the injection unit since this unit cannot provide enough energy to blow the fuse. REX062 input protection REX062 limits overvoltage by a varistor at the injection output to stator. Normally, REX060 will interrupt the injection circuit in case of excessive over-current in the injection chain. Fuse within REX062 is an additional protection in case of failure within REX062 during over-voltage condition. A blown REX062 fuse requires a module disassembling to replace the fuse (F 6.3 A 250 V). However, if this occurs it is recommended to identify the reason for the overcurrent and do needed actions to reduce the current. 35

42 36

43 1MRK UUS B Section 6 Understand the HMI tree Section 6 Understand the HMI tree About this chapter This chapter describes the structure of the HMI. The main menu includes submenus such as Measurements, Events, Disturbance Report, Settings, Diagnostics, Test and Reset. These branch out into a typical tree structure. 6.1 Overview The local HMI has the following main menu: Control Measurements Events Disturbance records Settings Diagnostics Test Reset Authorization Language Each main menu item can have several other submenus Menu-tree for REG670 Main menu Sub menu Sub-sub menu Control Measurements Events Single line diagram Commands Disturbance records Manual trig Settings Time Table continues on next page Analog primary values Analog secondary values Analog mean values Monitoring Metering 37

44 Section 6 Understand the HMI tree 1MRK UUS B Main menu Sub menu Sub-sub menu Diagnostics Test Reset Authorization Language General settings Setting group N Activate setting group Internal events IED status IED test mode Binary input values Binary output values Function test modes Function status LED test Line differential test Reset counters Reset internal eventlist Reset LEDs Reset lockout Reset temperature Power system Communication Analog modules I/O modules HMI Differential protection Impedance protection Current protection Voltage protection Control Monitoring Metering Differential protection Impedance protection Current protection Voltage protection Frequency protection Multipurpose protection Scheme communication Secondary system supervision Control Monitoring Logic 38

45 1MRK UUS B Section 7 Read measured values Section 7 Read measured values About this chapter This chapter describes measurement categories and how to locate them using the HMI. Each measurement category has a section of its own that includes a general description of the type of quantity being measured and the path in the local HMI to the measurement. 7.1 Overview The measurement menu contains primarily analog measurement data. External signals can also be viewed as they are or as they appear in the Signal Matrix Tool (SMT). These signals are a virtual representation of the hard wired signals on the various inputs and outputs. SMT is only accessible via PCM600 and is intended to simplify the configuration of the IED. It allows hardware changes to be made without having to reconfigure the internal logic. Signals that can be used in SMT are indicated with the Suffix SMT. The functions available under measurements are outlined below. 1. Analog primary values are the quantities measured on the primary side of the current and voltage transformers (CTs and VTs). 2. Analog secondary values are the quantities measured on the secondary side of the current and voltage transformers. These are the quantities measured on the Transformer module (TRM) inputs. 3. Analog mean values are the quantities measured at the inputs of the milliampere module (MIM). 4. Under Monitoring a number of submenus are available. These include Service values, Current phasors, Voltage phasors, Current sequence components and Voltage sequence components. 5. Metering displays the pulse counter and energy calculation and demand handling functions. The measurements available for pulse counter show pulse counter status data. All measurement descriptions in this document reflect the maximum number of hardware units possible in any application. In reality the hardware in the IED will be chosen according to a particular application. For example, it is possible to equip a 1/1 x 19 case IED with 14 I/O modules. In reality fewer I/O modules may be installed. In 39

46 Section 7 Read measured values 1MRK UUS B the measurements menu the operator will only see data from the hardware and software installed. Measurement for voltage channels used for injection protection (i.e. connected to REX060) will not display correct values because injection frequency differs from the rated power system frequency. To monitor these values use service values under respective protection function. 7.2 View analog primary values Overview The analog primary values are analog quantities measured on the primary side of the TRM and reflect the actual current or voltage on the primary side of the VTs and CTs. The ratio is adjusted under settings and also depends on the rating of the TRM. 24 primary values and phase angles are displayed in this view. The analog primary values are values on the input (primary equipment side) of the merging unit (MU) when IEC LE process bus communication is used. These values are scaled according to a fixed "universal" scaling of 1 ma per LSB and 10 mv per LSB and transmitted to the IED via IEC LE protocol. Main menu/measurements/analog primary values Displays the quantities measured by the transformer module (TRM) or received via IEC LE process bus. For each channel used the amplitude of the voltage or current and its phase angle is shown. If the amplitude is to low for calculation, the angle will be indicated with "- - -". The status of the module is always shown and channels not in use are indicated with "- - ". Data from TRMs and LDCMs as well as Merging Units can be viewed. All currents and voltages are given in RMS values. 7.3 View analog secondary values Overview 40

47 1MRK UUS B Section 7 Read measured values Analog secondary values shows secondary CT currents and VT voltages. These are the actual current and voltage values at the TRM inputs. For analog values received from Merging Units, no analog secondary values are shown. Main menu/measurements/analog secondary values Displays up to 24 channels with secondary CT and VT data. RMS values are shown. 7.4 View analog mean values Overview Measurements from the Milliampere Input Module (MIM) are found in this part of the measurements menu. Data from either the hard wired ma module or Signal Matrix Tool ma modules are shown here ma input module MIM Main menu/measurements/analog mean values/ma modules/mim:x Displays input data from the milli-ampere module which has six inputs. Each input has a range of +/- 20 ma. The value displayed on the screen is however dependant on the settings for the Milli-ampere Module. In the menu for settings, the range and a transformation factor can be adjusted to suit the application. This means that an input 3 ma may be displayed as temperature of 45 degrees. The output values shown are without units Signal matrix for ma inputs SMMI Main menu/measurements/analog mean values/smt ma modules/instance:x Displays the input signals coming into the Milli-ampere Module. Each module has six physical inputs with an input tolerance of +/- 20mA. The value displayed depends on the settings applied to this board which may for example cause an input of 3mA to show a value 30. The SMT ma modules are the virtual representation of MIMs in Signal Matrix Tool. 41

48 Section 7 Read measured values 1MRK UUS B 7.5 View monitoring values Service values CVMMXN Main menu/measurement/monitoring/servicevalues(mmxn)/cvmmxn:x Displays up to three instances of CVMMXN with measured values for S, P, Q, PF, U, I, ILead, ILag and F Current phasors CMMXU Main menu/measurement/monitoring/currentphasors(mmxu)/cmmxu:x All three phase currents and their phase angles are displayed here Voltage phasors VMMXU/VNMMXU Main menu/measurements/monitoring/voltagephasors(mmxu)/phase - Phase/ VMMXU:x Phase to phase voltages and phase angles are displayed here. Main menu/measurement/monitoring/voltagephasors(mmxu)/phase - Earth/ VNMMXU:x Phase to ground voltages and phase angles are displayed here Current sequence component CMSQI Main menu/measurements/monitoring/currentsequencecomponents(msqi)/ CMSQI:x The current sequence component under monitoring displays the positive (I1), negative (I2) and zero sequence (I0) current values for a three phase line, both magnitude and phase angle for each component are displayed. These indicate how well balanced a system is. In an ideal balanced system the zero sequence current should be zero, the positive sequence current should be equal to the current of each phase with the same phase angle (relative to GPS) as the A phase signal and the negative sequence current should be zero Voltage sequence component VMSQI Main menu/measurements/monitoring/voltagesequencecomponents(msqi)/ VMSQI:x 42

49 1MRK UUS B Section 7 Read measured values The Voltage sequence component displays the positive (V1), negative (V2) and zero (V0) sequence components in the system, and includes the magnitude and phase angle of each component. 7.6 View metering values Pulse counter logic PCGGIO Main menu/measurements/metering/pulsecounter(pcggio)/pcggio:x The output data generated from the pulse counter function include data about the status of the counter and counter values Function for energy calculation and demand handling ETPMMTR Main menu/measurements/metering/threephenergmeas(mmtr)/etpmmtr:x The output data generated from the energy measuring function includes active forward/ reverse energy and reactive forward/reverse energy. 43

50 44

51 1MRK UUS B Section 8 Event list Section 8 Event list About this chapter This chapter describes how to find and read the event list. 8.1 View events Overview Events displays recorded events such as trips and breaker opened or closed. Main menu/events Displays a list of events in chronological order and where each event has a time stamp. The latest event is at the top of the list. 45

Relion 670 series. Generator protection REG670 ANSI Operator's manual

Relion 670 series. Generator protection REG670 ANSI Operator's manual Relion 670 series Generator protection REG670 ANSI Document ID: 1MRK 502 014-UUS Issued: June 2010 Revision: B Product version: 1.1 Copyright 2010 ABB. All rights reserved Copyright This document and

More information

Relion 670 series. Phasor measurement unit RES670 ANSI Operator's manual

Relion 670 series. Phasor measurement unit RES670 ANSI Operator's manual Relion 670 series Phasor measurement unit RES670 ANSI Document ID: 1MRK511251-UUS Issued: February 2015 Revision: B Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document

More information

Relion 670 series. Busbar protection REB670 Operator's manual

Relion 670 series. Busbar protection REB670 Operator's manual Relion 670 series Busbar protection REB670 Document ID: 1MRK505209-UEN Issued: February 2015 Revision: E Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document and parts

More information

Relion 670 series. Line differential protection RED670 Operator's manual

Relion 670 series. Line differential protection RED670 Operator's manual Relion 670 series Line differential protection RED670 Document ID: 1MRK505223-UEN Issued: February 2015 Revision: E Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document

More information

Relion 670 series. Line distance protection REL670 Operator's manual

Relion 670 series. Line distance protection REL670 Operator's manual Relion 670 series Line distance protection REL670 Document ID: 1MRK506313-UEN Issued: February 2015 Revision: E Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document and

More information

Relion 670 series. Busbar protection REB670 Operator's manual

Relion 670 series. Busbar protection REB670 Operator's manual Relion 670 series Busbar protection REB670 Document ID: 1MRK 505 179-UEN Issued: June 2010 Revision: C Product version: 1.1 Copyright 2010 ABB. All rights reserved Copyright This document and parts thereof

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

Relion 670 series. Busbar protection REB670 ANSI Installation and commissioning manual

Relion 670 series. Busbar protection REB670 ANSI Installation and commissioning manual Relion 670 series Busbar protection REB670 ANSI Document ID: 1MRK505210-UUS Issued: February 2015 Revision: D Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document and parts

More information

Relion 670 series. Bay control REC670 Customized Product Guide

Relion 670 series. Bay control REC670 Customized Product Guide Relion 670 series Bay control REC670 Product Guide Contents 1. Application...3 2. Functionality...3 3. Hardware description...17 4. Connection diagrams...20 5. Technical data...30 6. Ordering...74 Disclaimer

More information

Relion 670 series. Line differential protection RED LE Customized Product Guide

Relion 670 series. Line differential protection RED LE Customized Product Guide Relion 670 series Line differential protection RED670 9-2 LE Product Guide Contents 1. Application...3 2. Available functions...6 3. Differential protection...9 4. Current protection...12 5. Voltage protection...12

More information

Relion 670 series. Phasor measurement unit RES670 ANSI Customized Product Guide

Relion 670 series. Phasor measurement unit RES670 ANSI Customized Product Guide Relion 670 series Phasor measurement unit RES670 ANSI Product Guide Contents 1. Application...4 2. Available functions...5 3. Wide area measurement system...8 4. Current protection...9 5. Voltage protection...10

More information

Relion 670 series. Busbar protection REB670 Customized Product Guide

Relion 670 series. Busbar protection REB670 Customized Product Guide Relion 670 series Busbar protection REB670 Product Guide Contents 1. Application...3 2. Available functions...9 3. Differential protection...13 4. Zone selection...14 5. Current protection...17 6. Voltage

More information

Relion 670 series. Line distance protection REL670 ANSI Pre-configured Product Guide

Relion 670 series. Line distance protection REL670 ANSI Pre-configured Product Guide Relion 670 series Line distance protection REL670 ANSI Product Guide Contents 1. Application...3 2. Available functions...6 3. Impedance protection...11 4. Current protection...12 5. Voltage protection...14

More information

Relion 670 series. Line differential protection RED670 ANSI Customized Product Guide

Relion 670 series. Line differential protection RED670 ANSI Customized Product Guide Relion 670 series Line differential protection RED670 ANSI Product Guide Contents 1. Application...3 2. Available functions...4 3. Differential protection...9 4. Impedance protection...15 5. Current protection...19

More information

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement

More information

Relion 670 series. Busbar protection REB670 ANSI Customized Product Guide

Relion 670 series. Busbar protection REB670 ANSI Customized Product Guide Relion 670 series Busbar protection REB670 ANSI Product Guide Contents 1. Application...3 2. Available functions...10 3. Differential protection...14 4. Zone selection...15 5. Current protection...18 6.

More information

Relion 670 series. Line differential protection RED670 Customized Product Guide

Relion 670 series. Line differential protection RED670 Customized Product Guide Relion 670 series Line differential protection RED670 Product Guide Contents 1. Application...3 2. Available functions...4 3. Differential protection...8 4. Impedance protection...11 5. Current protection...15

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

Relion Protection and Control. 670 series 2.1 IEC Operation manual

Relion Protection and Control. 670 series 2.1 IEC Operation manual Relion Protection and Control 670 series 2.1 IEC Document ID: 1MRK 500 123-UEN Issued: December 2015 Revision: - Product version: 2.1 Copyright 2015 ABB. All rights reserved Copyright This document and

More information

Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Numerical motor protection in medium voltage networks Motor Protection and Control REM620 Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,

More information

Relion 670 series. Busbar protection REB670 Installation and commissioning manual

Relion 670 series. Busbar protection REB670 Installation and commissioning manual Relion 670 series Busbar protection REB670 Document ID: 1MRK 505 180-UEN Issued: June 2010 Revision: C Product version: 1.1 Copyright 2010 ABB. All rights reserved Copyright This document and parts thereof

More information

Relion 650 series. Generator protection REG650 ANSI Product Guide

Relion 650 series. Generator protection REG650 ANSI Product Guide Relion 650 series Generator protection REG650 ANSI Product Guide Contents 1. 650 series overview...3 2. Application...3 3. Available functions...5 4. Differential protection...15 5. Impedance protection...17

More information

Relion Protection and Control. 650 series DNP3 Point List Manual

Relion Protection and Control. 650 series DNP3 Point List Manual Relion Protection and Control 650 series DNP3 Document ID: 1MRK 511 244-UEN Issued: February 2011 Revision: - Product version: 1.1 Copyright 2011 ABB. All rights reserved Copyright This document and parts

More information

Connectivity Packages. User's Guide - ANSI Version

Connectivity Packages. User's Guide - ANSI Version Connectivity Packages 1MRS756194 Issued: 30.11.2006 Version: A/30.11.2006 Connectivity Packages Contents Copyrights... 5 1. Introduction...... 7 1.1. Intended audience...... 7 1.2. Related documents.........

More information

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied:

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied: 1) IED Protection and Control Manager PCM 600 Tool (SEP-601) PCM 600 Introduction and Overview Application Configuration Tool (CAP 531) Signal Matrix Tool, SMT Graphical Display Editor, GDE Parameter Setting

More information

GE Multilin 350 Feeder Protection Relay Specifications

GE Multilin 350 Feeder Protection Relay Specifications GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

The power of one What s new in Relion 670 and 650 series version 2.2?

The power of one What s new in Relion 670 and 650 series version 2.2? 2017-06-28 The power of one What s new in Relion 670 and 650 series version 2.2? The power of one solution for protection and control Presenters Joseph Menezes Global Product Manager, Relion 670 series

More information

Relion 605 series. Self-powered feeder protection REJ603 Application Manual

Relion 605 series. Self-powered feeder protection REJ603 Application Manual Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection REJ603 Document ID: 1MDU07221-YN Issued: 2017-10-30 Revision: D Product version: 3.0 Copyright 2017 ABB. All rights

More information

DRS-LIGHT. Device Description DRS-LP824. Digital Unit Decoupling Relay Type DRS-LP824. Device Description DIL

DRS-LIGHT. Device Description DRS-LP824. Digital Unit Decoupling Relay Type DRS-LP824. Device Description DIL DRS-LIGHT Digital Unit Decoupling Relay Type DRS-LP824 Device Description Edition:09.05.2008 SLLR_LP824_e.doc Page 1 /10 CAUTION Installing, commissioning and operating of this product may be performed

More information

Relion Protection and Control. 650 series ANSI DNP3 Point list manual

Relion Protection and Control. 650 series ANSI DNP3 Point list manual Relion Protection and Control 650 series ANSI DNP3 Document ID: 1MRK 511 283-UUS Issued: October 2016 Revision: A Product version: 1.3 Copyright 2014 ABB. All rights reserved Copyright This document and

More information

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual Overcurrent and Earth-Fault Relay MRS75094-MUM Issued: 4.09.998 Version: D/4..2005 Overcurrent and Earth-Fault Relay Contents. About this manual...5.. Copyrights...5.2. Trademarks...5.3. Guarantee...5.4.

More information

750/760 Feeder Management Relay Instruction Manual

750/760 Feeder Management Relay Instruction Manual GE Digital Energy 750/760 Feeder Management Relay Instruction Manual Software Revision: 7.4x Manual P/N: 1601-0120-AK Manual Order Code: GEK-106471T GE Digital Energy 650 Markland Street Markham, Ontario

More information

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation

More information

Relion Protection and Control. 650 series DNP3 Point List Manual

Relion Protection and Control. 650 series DNP3 Point List Manual Relion Protection and Control 650 series DNP3 Document ID: 1MRK 511 260-UEN Issued: June 2012 Revision: - Product version: 1.2 Copyright 2012 ABB. All rights reserved Copyright This document and parts

More information

Relion 650 series. Breaker protection REQ650 Application Manual

Relion 650 series. Breaker protection REQ650 Application Manual Relion 650 series Breaker protection REQ650 Document ID: 1MRK 505 266-UEN Issued: February 2011 Revision: Product version: 1.1 Copyright 2011 ABB. All rights reserved Copyright This document and parts

More information

ABB Substation Automation Products Relion 670 series Ver. 2.0, IEC & ANSI What s new?

ABB Substation Automation Products Relion 670 series Ver. 2.0, IEC & ANSI What s new? ABB Substation Automation Products Relion 670 series Ver. 2.0, IEC & ANSI What s new? Relion 670 series Ver. 2.0 Relion Product Family 605 610 615 620 630 650 670 Relion 670 series Ver. 2.0 Relion Product

More information

Distributed busbar protection REB500 Operation Manual

Distributed busbar protection REB500 Operation Manual REB500 Substation Automation Products Operation Manual Document ID: 1MRK 500 121-UEN Issued: May 2015 Revision: - Product version: 8.10 Copyright 2015 ABB. All rights reserved Copyright This document

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

Relion Protection and Control. 650 series ANSI DNP3 Point List Manual

Relion Protection and Control. 650 series ANSI DNP3 Point List Manual Relion Protection and Control 650 series ANSI DNP3 Document ID: 1MRK 511 244-UUS Issued: April 2011 Revision: Product version: 1.1 Copyright 2011 ABB. All rights reserved Copyright This document and parts

More information

Relion 650 series. Accessories, 650 series IEDs versions 1.0 to 1.3, ANSI Product Guide

Relion 650 series. Accessories, 650 series IEDs versions 1.0 to 1.3, ANSI Product Guide Relion 650 series Accessories, 650 series IEDs versions 1.0 to 1.3, ANSI Product Guide Contents 1. Available accessories...3 2. Mounting kit for 3U... 3 3. Mounting kits for 6U...4 4. RHGS cases...6 5.

More information

Relion 650 series. 650 series 2.1 IEC LON Communication protocol manual

Relion 650 series. 650 series 2.1 IEC LON Communication protocol manual Relion 650 series 650 series 2.1 IEC LON Document ID: 1MRK 511 378-UEN Issued: January 2016 Revision: - Product version: 2.1 Copyright 2016 ABB. All rights reserved Copyright This document and parts thereof

More information

MCCB-250 MOLDED-CASE CIRCUIT BREAKER TESTER

MCCB-250 MOLDED-CASE CIRCUIT BREAKER TESTER MCCB-250 MOLDED-CASE CIRCUIT BREAKER TESTER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 January 2015 Revision

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs The IO-AO6X is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 6 12-bit isolated

More information

Relion 670 series. Busbar protection REB670 ANSI Pre-configured Product Guide

Relion 670 series. Busbar protection REB670 ANSI Pre-configured Product Guide Relion 670 series Busbar protection REB670 ANSI Product Guide Contents 1. Application...3 2. Available functions...10 3. Differential protection...13 4. Zone selection...14 5. Current protection...17 6.

More information

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators. SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

Operation Manual Feeder Protection Relay REF615

Operation Manual Feeder Protection Relay REF615 Feeder Protection Relay REF615 Document ID: 1MRS756376 Issued: 02.07.2008 Revision: C Product version: 1.1 Copyright 2008 - ABB. All rights reserved Copyright This document and parts thereof must not

More information

Relion 650 series. Transformer protection RET650 Product Guide

Relion 650 series. Transformer protection RET650 Product Guide Relion 650 series Transformer protection RET650 Product Guide Contents 1. 650 series overview...3 2. Application...3 3. Available functions...7 4. Differential protection...17 5. Current protection...18

More information

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL Circuit Breaker Failure Relay Operating Principle Revision: 2 from 2005-02-25 Edition: 2005-02-25 _CBF-description_eng.doc Page 1 /14 Table of Contents: 1 GENERAL DESCRIPTION 4 2 FUNCTIONAL DESCRIPTION

More information

Relion 650 series. Transformer protection RET650 ANSI Application Manual

Relion 650 series. Transformer protection RET650 ANSI Application Manual Relion 650 series Transformer protection RET650 ANSI Document ID: 1MRK 504 124-UUS Issued: April 2011 Revision: - Product version: 1.1 Copyright 2011 ABB. All rights reserved Copyright This document and

More information

Protection relays.

Protection relays. Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation

More information

Electrical Integration with Smart Communication

Electrical Integration with Smart Communication Electrical Integration with Smart Communication New possibilities with Industrial Ethernet ABB Group September 24, 2009 Slide 1 Unified Integration Approach MES and Business Systems Knowledge Portals as

More information

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, RS-485 Main Range of product Product or component type Relay application Device short name [Us] rated supply voltage Type of

More information

Relion 670 series. Busbar protection REB670 Pre-configured Product Guide

Relion 670 series. Busbar protection REB670 Pre-configured Product Guide Relion 670 series Busbar protection REB670 Product Guide Contents. Application...3 2. Available functions...9 3. Differential protection...6 4. Zone selection...7 5. Current protection...2 6. Control...22

More information

Bay protection functions REB500 Application Manual

Bay protection functions REB500 Application Manual png Substation Automation Products Application Manual Document ID: 1MRK 505 353-UEN Issued: March 2016 Revision: A Product version: 8.2 Copyright 2016 ABB. All rights reserved Copyright This document

More information

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

TWO-WINDING TRANSFORMER DIFFERENTIAL

TWO-WINDING TRANSFORMER DIFFERENTIAL E3-TR PROTECTION WITH AUTOMATIC VOLTAGE Because of the control, measuring and monitoring functions implemented, the IED can also be used as a bay control unit. The EuroCAP configuration tool, which is

More information

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay 7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional

More information

Relion 670 series. Busbar protection REB670 Pre-configured Product Guide

Relion 670 series. Busbar protection REB670 Pre-configured Product Guide Relion 670 series Busbar protection REB670 Product Guide Contents 1. Application...3 2. Available functions...9 4. Functionality...11 5. Hardware description...23 6. Connection diagrams...25 7. Technical

More information

VAMP 221. Table of Contents

VAMP 221. Table of Contents 2 V221/EN M/E019 VAMP 221 Table of Contents Table of Contents 1. General... 7 1.1. VAMP 221 arc protection system components... 7 1.1.1. Central unit VAMP 221... 9 1.1.2. I/O units VAM 12L / VAM 12 LD,

More information

Relion Protection and Control. 650 series Engineering manual

Relion Protection and Control. 650 series Engineering manual Relion Protection and Control 650 series Document ID: 1MRK 511 284-UEN Issued: October 2016 Revision: A Product version: 1.3 Copyright 2013 ABB. All rights reserved Copyright This document and parts thereof

More information

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 Content FPC 200 USER MANUAL Mar 2017 Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 1 USER MANUAL FPC 200-3/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia

More information

Grid Automation Products. SAM600 Process Bus I/O System Operation Manual

Grid Automation Products. SAM600 Process Bus I/O System Operation Manual b Grid Automation Products SAM600 Process Bus I/O System Document ID: 1MRK 511 434-UEN Issued: June 2017 Revision: A Product version: 1.2 Copyright 2016-2017 ABB. All rights reserved Copyright This document

More information

Application. The control is performed from remote (SCADA/Station) through the communication bus

Application. The control is performed from remote (SCADA/Station) through the communication bus Revision: H Issued: February 2007 Data subject to change without notice Page 1 Features Three configuration alternatives for single- or multi-breaker arrangements available ready to connect For all types

More information

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE INSTRUCTIONS MODBUS TCP MODULE for use with WSIQ2/WSE WorldWide Electric Corporation Phone: 1-800-808-2131 Fax: 1-800-711-1616 www.worldwideelectric.net Product Compatibility This communications module

More information

Protection System Simulator SIM600. Installation Manual

Protection System Simulator SIM600. Installation Manual Protection System Simulator SIM600 1MRS756102 Issued: 08.12.2008 Version: B Protection System Simulator SIM600 Contents: 1. About this manual... 5 1.1. Copyrights... 5 1.2. Trademarks... 5 1.3. Guarantee...

More information

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 January 2015 Revision

More information

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, 2 x RJ-45 Main Range of product Product or component type Relay application Configuration type (Cortec) [Us] rated supply voltage

More information

ACCESS 9340/9360 Meter Input/Output Module

ACCESS 9340/9360 Meter Input/Output Module Installation Manual PMIM-IOMOD-0208 ACCESS 9340/9360 Meter Input/Output Module 9340-60-I/O2222 and 9340-60-I/O26 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the

More information

ACOPOSinverter P74. User's Manual. Version: 2.20 (August 2016) Model no.: Original instruction

ACOPOSinverter P74. User's Manual. Version: 2.20 (August 2016) Model no.: Original instruction ACOPOSinverter P74 User's Manual Version: 2.20 (August 2016) Model no.: MAACPIP74-ENG Original instruction All information contained in this manual is current as of its creation/publication. We reserve

More information

Relion 650 series. Generator protection REG650 ANSI Product Guide

Relion 650 series. Generator protection REG650 ANSI Product Guide Relion 650 series Generator protection REG650 ANSI Product Guide Contents 1. 650 series overview...3 2. Application...3 3. Available functions...6 4. Differential protection...14 5. Impedance protection...15

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

Relion 650 series. Busbar protection REB650 Product Guide

Relion 650 series. Busbar protection REB650 Product Guide Relion 650 series Busbar protection REB650 Product Guide Contents 1. 650 series overview...3 2. Application...3 3. Available functions...4 4. Differential protection...11 5. Current protection...11 6.

More information

User Guide. Cloning interface small option module for Unidrive and Commander GP. Part Number: Issue Number: 3

User Guide. Cloning interface small option module for Unidrive and Commander GP. Part Number: Issue Number: 3 User Guide UD55 Cloning interface small option module for Unidrive and Commander GP Part Number: 0460-0095 Issue Number: 3 General Information The manufacturer accepts no liability for any consequences

More information

Relion 615 series. Motor Protection and Control REM615 Modbus Point List Manual

Relion 615 series. Motor Protection and Control REM615 Modbus Point List Manual Relion 615 series Motor Protection and Control REM615 Modbus Document ID: 1MRS756877 Issued: 03.07.2009 Revision: A Product version: 2.0 Copyright 2009 ABB. All rights reserved Copyright This document

More information

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

Relion 650 series. Breaker protection REQ650 Commissioning manual

Relion 650 series. Breaker protection REQ650 Commissioning manual Relion 650 series Breaker protection REQ650 Document ID: 1MRK 505 293-UEN Issued: October 2016 Revision: A Product version: 1.3 Copyright 2013 ABB. All rights reserved Copyright This document and parts

More information

FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP750-51(B) FTA750 Full Voltage Starting Limited Service Electric Fire Pump Controllers Product Description Description Firetrol

More information

Relion Protection and Control. 650 series Engineering Manual

Relion Protection and Control. 650 series Engineering Manual Relion Protection and Control 650 series Document ID: 1MRK 511 245-UEN Issued: February 2011 Revision: - Product version: 1.1 Copyright 2011 ABB. All rights reserved Copyright This document and parts

More information

MicroSCADA Pro SYS

MicroSCADA Pro SYS MicroSCADA Pro SYS 600 9.2 1MRS756170 Issued: 02.03.2007 Version: B/28.03.2008 MicroSCADA Pro SYS 600 9.2 Contents Copyrights...15 1. Introduction...17 1.1. This Manual...17 1.2. Use of symbols...17 1.3.

More information

Application Notes on Generator Protection Schemes

Application Notes on Generator Protection Schemes Application Notes on Generator Protection Schemes Single Line Diagram Examples 1. Introduction The application notes provide selected single line diagrams for the SIPROTEC 4 generator protection device

More information

PROTECTION, AUTOMATION & CONTROL

PROTECTION, AUTOMATION & CONTROL PROTECTION, AUTOMATION & CONTROL 1. DTIVA The members of the DTIVA product line are configured to protect and control the elements of not solidly grounded radial networks. Here the application of Petersen

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms module

More information

Protection Relays PHASE & RESIDUAL OVERCURRENT

Protection Relays PHASE & RESIDUAL OVERCURRENT Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent

More information

Protective Relays & SCADA Systems

Protective Relays & SCADA Systems 14 SWITCHGEAR Protective Relays & SCADA Systems SCADA Substation Automation SICAM PAS & PQ Analyzer SICAM PAS (Power Automation System) is a complete substation automation control and protection system

More information

Relion 650 series. Busbar protection REB650 ANSI Product Guide

Relion 650 series. Busbar protection REB650 ANSI Product Guide Relion 650 series Busbar protection REB650 ANSI Product Guide Contents 1. 650 series overview...3 2. Application...3 3. Available functions...4 4. Differential protection...12 5. Current protection...12

More information

Relion Protection and Control. 615 series IEC Communication Protocol Manual

Relion Protection and Control. 615 series IEC Communication Protocol Manual Relion Protection and Control 615 series IEC 60870-5-103 Communication Protocol Manual Document ID: 1MRS756710 Issued: 2016-05-20 Revision: G Product version: 5.0 FP1 Copyright 2016 ABB. All rights reserved

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

RELION SAM600. Switchgear control unit SAM600-IO Version 2.2 IEC Engineering manual

RELION SAM600. Switchgear control unit SAM600-IO Version 2.2 IEC Engineering manual RELION SAM600 Switchgear control unit SAM600-IO Version 2.2 IEC Document ID: 1MRK 511 442-UEN Issued: November 2017 Revision: A Product version: 2.2 Copyright 2017 ABB. All rights reserved Copyright This

More information

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus Non-conventional instrument transformers Advanced GIS substations with IEC 61850-9-2LE process bus Content Towards the digital GIS substations Optimized substation design NCIT for gas-insulated switchgears

More information

Relion Protection and Control. 615/620 series ANSI Modbus Communication Protocol Manual

Relion Protection and Control. 615/620 series ANSI Modbus Communication Protocol Manual Relion Protection and Control 615/620 series ANSI Modbus 615 series Product version 2.0 620 series Product version 1.0 Document ID: 1MAC052634-MB Issued: 11/23/2010 Revision: D Copyright 2010 ABB. All

More information