CONTROL MICROSYSTEMS Thermocouple Analog Input Module. Hardware Manual
|
|
- Harold Henry
- 5 years ago
- Views:
Transcription
1 550 Thermocouple Analog Input Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: Kanata, Ontario Facsimile: KK A9 Technical Support: Canada -CONTROL
2 Control Microsystems Inc. All rights reserved. Printed in Canada. Trademarks TeleSAFE, TelePACE, SmartWIRE, SCADAPack, TeleSAFE Micro6 and TeleBUS are registered trademarks of Control Microsystems Inc. All other product names are copyright and registered trademarks or trade names of their respective owners. Material used in the User and Reference manual section titled SCADAServer OLE Automation Reference is distributed under license from the OPC Foundation.
3 Table of Contents OVERVIEW... 3 IMPORTANT SAFETY INFORMATION... 3 INSTALLATION Environment Considerations Field Wiring Address Selection Thermocouple Range Selection... 7 OPERATION AND MAINTENANCE Data Format Fail-Safe Conditions Cold Junction Compensation Linearization Maintenance Troubleshooting Calibration SPECIFICATIONS... 6 APPROVALS AND CERTIFICATIONS... Index of Figures Figure : Typical 550 Thermocouple Field Wiring... 6 Figure : 550 Thermocouple Input Address Switches... 7 Figure 3: 550 Thermocouple Range Switches...
4 Overview The Model 550 Thermocouple input module adds eight thermocouple inputs to the 5000 Series input/output system. Up to eight model 550 modules may be connected to the I/O bus, for a total of 6 thermocouple inputs per bus. The 550 module can be used with J, K, E and T type thermocouples or 0 to 0 millivolt input signals. The 550 module provides an iso-thermal block for maintaining the thermocouple termination wiring at a know temperature. The temperature of this block is monitored to provide cold junction compensation. The 550 module uses a 0000 count, integrating, analog to digital (A/D) converter. A single chip microcontroller with integral watchdog timer operates the A/D, linearizes and scales the output data and communicates over the I/O bus. All inputs are transient protected and optically isolated from the main logic power. 3
5 Important Safety Information Power, input and output (i/o) wiring must be in accordance with Class I, Division wiring methods Article 50- (b) of the National Electrical Code, NFPA 70 for installations in the U.S., or as specified in Section -J of the Canadian Electrical Code for installations within Canada and in accordance with the authority having jurisdiction. WARNING! EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS, DIVISION. WARNING! EXPLOSION HAZARD WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE REPLACING OR WIRING MODULES. WARNING! EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS.
6 3 Installation The installation of the 550 module requires mounting the module on the 7.5mm by 35mm DIN rail and connecting the module to the system I/O Bus. Refer to the System Configuration Guide, at the beginning of this manual, for complete information on system layout, I/O Bus cable routing and module installation. 3.. Environment Considerations The 550 module cold junction compensation circuitry must not be subjected to rapid temperature changes. These can occur when a cabinet door is opened. Install 550 modules in a manner, which will eliminate, or at least minimize, the possibility of rapid temperature changes. 3. Field Wiring The 550 module provides eight thermocouple inputs. Figure : Typical 550 Thermocouple Field Wiring shows how to wire the inputs. An external volt supply powers the isolated input circuits. A 5000 Series power supply normally sources this voltage. A range of voltages can be tolerated. Refer to section 5-Specifications for details. If an isolated V-power supply is used, such as a 5000 Series 503 power supply, it is necessary to reference this supply to chassis ground. This connection to chassis may be built into another device being powered from the V power supply but is most easily accomplished by connecting the V of one of the 550 modules to the nearest DIN rail chassis ground. If it is necessary to have the thermocouples at a potential other than chassis ground this chassis connection can be made through a high value resistor. Screw termination style connectors are used for termination of field wiring. They accommodate solid or stranded wires from to AWG. The connectors are fixed to the circuit board and are not removable. CAUTION: To remove the connector: Remove power before servicing unit. Pull the connector upward from the board. Apply even pressure to both ends of the connector. To install the connector: Line up the pins on the module with the holes in the connector. Make sure all the pins line up properly. Push the connector onto the pins. Apply even pressure to both ends on the connector. 5
7 Volt Input P P V Supply T/C 0 T/C T/C T/C 3 T/C T/C 5 T/C 6 T/C 7 See Field Wiring section regarding chassis ground connection. Figure : Typical 550 Thermocouple Field Wiring 3.3 Address Selection The 5000 Series I/O bus will support a maximum of forty I/O (input/output) modules Series I/O module types may be combined in any manner to the maximum supported by the controller used. The types of input and output modules available are: Digital Input modules Digital Output modules Analog Input modules Analog Output modules Counter Input modules Each type of I/O module, connected to the I/O bus, must have a unique I/O module address. Different types of I/O modules may have the same module address. The address range supported by the SmartWIRE, SCADAPack or TeleSAFE Micro6 controller module may restrict the I/O module address range. Refer to the controller manual for the maximum address supported. The three address switches labeled,, and set the module address. To set the address: Open all three switches by pressing down the left side of the switch. Close the switches that total to the desired address. Figure : 550 Thermocouple Input Address Switches shows the switch settings for all 6 possible module addresses. 6
8 How to Set Switches Determine the module address. Press the side of the switches shown in gray above. Press this side to ignore switch value Press this side to add switch value Figure : 550 Thermocouple Input Address Switches 3. Thermocouple Range Selection The 550 module scales and linearizes input readings depending on the thermocouple range selected. These ranges are summarized in the table below. Figure 3: 550 Thermocouple Range Switches below shows the switch settings for the 5 possible ranges. Input Type Range Resolution at 0ºC J 00 to 760ºC 0.0ºC 0 K 70 to 370ºC 0.0ºC E 70 to 000ºC 0.07ºC T 70 to 00ºC 0.0ºC 3 Voltage 0 to 0 mv µv Select Range The resolution shown above is typical of the resolution over most of the range for temperatures above 0ºC. Thermocouples are very non-linear, especially at temperatures below 00ºC. 7
9 Range 0 J type Range K type Range E type Range 3 T type Range ±0mV How to Set Range Switches Determine the desired range. Press the side of the switches shown in gray above. Figure 3: 550 Thermocouple Range Switches
10 Operation and Maintenance. Data Format 5000 Series analog input and output modules use 6 bit signed numbers (5 bits plus sign). The 550 module has a 0000 count, bipolar, analog to digital (A/D) converter. All of the thermocouple ranges use a fraction of the A/D range. The readings are scaled and linearized to provide output data in the 6 bit signed format. The table below shows output values for several temperature inputs based on the J type thermocouple range. Temperature Conditio n Output < 00ºC operating 63 00ºC operating 63 0ºC operating 0 0.0ºC operating 3 00ºC operating 3 30ºC operating ºC operating ºC operating 3767 NA open 3767 input NA +V off 0. Fail-Safe Conditions The 550 module output data has two special conditions. If the thermocouple is open the data goes to full scale (3767). If the V power supply is off the data goes to 0..3 Cold Junction Compensation When the thermocouple wiring is terminated on a terminal block a second thermocouple is created. Cold junction compensation is necessary to eliminate the effects of this cold junction thermocouple. The terminal block of the 550 module is connected a large mass (iso-thermal block). The cold junction sensor measures the temperature of this block. The 550 module compensates the thermocouple readings for temperature variations at the terminal block. The cold junction compensation circuit must not be subjected to rapid temperature changes, for the circuit to function properly. These can occur when a cabinet door is opened. Install 550 modules in a manner, which will eliminate, or at least minimize, the possibility of rapid temperature changes.. Linearization The 550 module scales and linearizes the output data for the thermocouple range selected. Linearization is accomplished by dividing the temperature vs. voltage curve into approximately 0 segments and extrapolating to generate an output that is a function of temperature. 9
11 Some thermocouples become extremely non-linear at temperatures below 00ºC. The low temperature limit on the accuracy specification reflects this limitation of the thermocouple. Range Temperature Linearization Errors J 00 to 760ºC +0.03% K 30 to 370ºC +0.03% E 0 to 000ºC +0.03% T 0 to 00ºC +0.03% ±0mV NA NA.5 Maintenance This module requires no routine maintenance. If the module is not functioning correctly, contact Control Microsystems Technical Support for more information and instructions for returning the module for repair..6 Troubleshooting Problem Inputs always read 0. Inputs always read Reading is constant. Action Check +V power. Check the range switches. Check for open input. Check the range switches. Check that the analog input is not forced..7 Calibration The 550 module is calibrated and burned in at the factory. It does not require periodic calibration. Calibration may be necessary if the module has been repaired as a result of damage. There is one potentiometer for calibration of the analog inputs. The GAIN potentiometer (R) adjusts the gain. Calibration requires that you read the converted value from the module using a communication controller, SCADAPack or TeleSAFE Micro6 controller module. Refer to the controller module manual for details. To calibrate the module:. Set the range switches to range (±0mV).. Short any one of the analog inputs. 3. Adjust the ZERO potentiometer until a reading of 0 is obtained.. Apply a stable voltage between 70 and 0 mv on any one of the analog inputs. 5. Calculate the correct reading for the applied voltage using the formula: voltage reading 376 0mV 6. Adjust the GAIN potentiometer until the correct reading is obtained. 0
12 The calibration may be verified by applying other voltages or voltages of the opposite polarity to the other input terminals. Use the formula above to determine the correct reading for each input voltage.
13 5 Specifications Disclaimer: Control Microsystems reserves the right to change product specifications without notice. For more information visit Inputs Thermocouple Types and Ranges Resolution Input Resistance Accuracy over 0 o C to 60 o C operating temperature range thermocouples or millivolt signals Type J 00 to 760ºC Type K 70 to 370ºC Type E 70 to 000ºC Type T 70 to 00ºC mv ±0mV 0.00 mv approximately 0.0 o C refer to section 3.-Thermocouple Range Selection. M Type J ±0.0% of full scale Type K ±0.0% of full scale Type E ±0.5% of full scale Type T ±0.50% of full scale mv ±0.5% of full scale Cold Junction Compensation Converter type Common mode voltage range Isolation Transient Protection Response Time Power Requirements Terminations Dimensions Mounting Packaging All figures include linearization errors, but not cold junction compensation errors. Errors at operating temperatures from 0 o C to 50 o C are typically one-half those stated above. Accuracy decreases at measured temperatures below 00ºC. Refer to section.-linearization for details. ±0.5ºC maximum error from 0 to 60ºC ±ºC maximum error from 0 to 0ºC ±0000 count, integrating ±0V can be applied to the inputs, relative to the V power supply input. 500 VAC from the logic power MOVs on each input 0.5 seconds 5V at 0mA 0 to V at 5mA 0 pole and pole two fixed terminal blocks to AWG 5 amp contacts 5.65 inch ( mm) wide.65 inch ( mm) high.75 inch ( mm) deep 7.5 x 35 DIN rail corrosion resistant zinc plated steel with black enamel paint
14 Environment 5% RH to 95% RH, non-condensing 0 o C to 60 o C 0 o F to 0 o F 3
15 6 Approvals and Certifications Safety Non-Incendive Electrical Equipment for Use in Class I, Division Groups A, B, C and D Hazardous Locations.
CONTROL MICROSYSTEMS Analog Input Module. Hardware Manual
550 Analog Input Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676 Canada -CONTROL
More informationCONTROL MICROSYSTEMS Differential Analog Input Module. Hardware Manual
550 Differential Analog Input Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676
More informationCONTROL MICROSYSTEMS Potentiometer Analog Input Module. Hardware Manual
55 Potentiometer Analog Input Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676
More informationCONTROL MICROSYSTEMS and 5404 Digital Input Module. Hardware Manual
503 and 50 Digital Input Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676
More informationCONTROL MICROSYSTEMS Toggle Switch Digital Input Module. Hardware Manual
5 Toggle Switch Digital Input Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 8 Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support:
More information5504 Thermocouple Analog Input Module
550 Thermocouple Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical
More informationCONTROL MICROSYSTEMS Analog Output Module. Hardware Manual
5304 Analog Output Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:
More informationCONTROL MICROSYSTEMS and 5402 Digital I/O Module. Hardware Manual
50 and 50 Digital I/O Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676
More informationCONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual
506 and 507 Relay Output Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676
More informationCONTROL MICROSYSTEMS High Speed Counter Input Module. Hardware Manual
50 High Speed Counter Input Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance Steacie Drive Telephone: 63-59-93 Kanata, Ontario Facsimile: 63-59-0 KK A9 Technical Support: -6-676
More informationCONTROL MICROSYSTEMS SDI-12 Interface Module. Hardware Manual
5915 SDI-12 Interface Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:
More informationCONTROL MICROSYSTEMS. SCADAPack Micro 16. Quick Start Guide
SCADAPack Micro 16 Quick Start Guide CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:
More information5502 Differential Analog Input Module
550 Differential Analog Input Installation, Operation and Maintenance Setup Manual //07 Copyright 0-07 Schneider Electric Canada Inc. All rights reserved. 550 Differential Analog Input The information
More informationCONTROL MICROSYSTEMS and 5601A Input/Output (I/O) Module. Hardware Manual
5601 and 5601A Input/Output (I/O) Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9
More information5403 and 5404 Digital Input Modules
503 and 50 Digital Input Modules Installation, Operation and Maintenance Setup Manual //07 Copyright 0-07 Schneider Electric Canada Inc. All rights reserved. 503 and 50 Digital Input Modules The information
More information5521 Potentiometer Analog Input Module
55 Potentiometer Analog Input Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical
More information5401 and 5402 Digital I/O Modules
50 and 50 Digital I/O Modules Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical
More informationCONTROL MICROSYSTEMS Input/Output (I/O) Module. Hardware Manual
5604 Input/Output (I/O) Module Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical
More informationCONTROL MICROSYSTEMS. SCADAPack 100 Controller. Hardware Manual
SCADAPack 100 Controller Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:
More informationCONTROL MICROSYSTEMS. TeleSAFE Micro16 Controller. Hardware Manual
TeleSAFE Micro16 Controller Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support:
More informationSCADAPack E 5405 Digital Input Hardware Manual
SCADAPack E 5405 Digital Input Hardware Manual 2 SCADAPack E 5405 Digital Input Hardware Manual Table of Contents Part I 5405 Digital Input Module 3 1 Technical... Support 3 2 Safety... Information 4 3
More informationSCADAPack E 5505 RTD Input Hardware Manual
SCADAPack E 5505 RTD Input Hardware Manual 2 SCADAPack E 5505 RTD Input Hardware Manual Table of Contents Part I 5505 RTD Input Module 3 1 Technical... Support 3 2 Safety... Information 4 3 Overview...
More information5607 Input/Output (I/O) Module
5607 Input/Output (I/O) Module Installation, Operation and Maintenance Setup Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or technical
More informationRSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3704, EP GFK-2960B November 2017
November 2017 Module Status LED Channel Status LEDs Digital Input Connector Ground 24 V DC FE Analog Input Module RSTI-EP Slice I/O Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3704,
More informationPM Series Power Meter
PM Series Power Meter Quick Setup Guide - PMC-1000, PMC- 1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See
More informationVersaMax* Analog Input, 16-Bit Thermocouple Module
VersaMax* Analog Input, 16-Bit Module Product Description The Analog Input Module is an intelligent module that accepts seven independent thermocouple or millivolt inputs. The module receives power from
More informationCONTROL MICROSYSTEMS. SOLARPack 210. Hardware Manual
SOLARPack 210 Hardware Manual CONTROL MICROSYSTEMS SCADA products... for the distance 48 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support: 888-226-6876
More informationINSTALLATION INSTRUCTIONS
www.altroniccontrols.com INSTALLATION INSTRUCTIONS EXACTA 21 MONITORING AND CONTROL SYSTEM CAUTION: The EXACTA 21 CONTROL SYSTEM is CSA CERTIFIED FOR use in Class I, GROUPS C & D, Division 2 hazardous
More informationRSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664, EP-3704, EP GFK-2960F September 2018
September 2018 Module Status LED Channel Status LEDs Digital Input Connector Ground 24 V DC FE Analog Input Module RSTI-EP Slice I/O Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664,
More informationQUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.
PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA
More informationSCADAPack 350E 357E. Smart Remote Terminal Unit
SCADAPack 350E 357E Smart Remote Terminal Unit 1 The SCADAPack 300E Smart RTU is a platform built on a 32-bit processor and fitted with a 12-30 Vdc supply, various communication links and a wide range
More information5910 Ethernet Gateway Module
Hardware Manual 2/24/2017 Copyright 2014-2017 Schneider Electric Canada Inc. All rights reserved. 5910 Ethernet Gateway Module The information provided in this documentation contains general descriptions
More informationSCADAPack 32. Smart RTU
SCADAPack 32 Smart RTU 1 Compared to the SCADAPack 300 platform, the SCADAPack 32 is a higher performance Smart RTU built to meet the demands of larger applications including support for up to 10 gas flow
More informationAnalog Input, 16-Bit Thermocouple Module
Analog Input, 16-Bit Module Product Description The Analog Input Module is an intelligent module that accepts seven independent thermocouple or millivolt inputs. The module receives power from the backplane
More informationRSTI-EP Slice I/O. EtherCAT Network Adapter Module EPXETC001. GFK-2967B Septembery 2016
Septembery 2016 RSTI-EP Slice I/O EtherCAT Network Adapter Module PWR, BF, MT, L/A IN, L/A OUT, RUN, and ERROR LEDs Ethernet Ports Door for Micro USB Port EtherCAT Network Adapter Power Supply LED The
More informationSCADAPack Input/Output Module Hardware Manual. Version: February 2016
SCADAPack Version: Date: February 2016 Table of Contents 1 Legal Information...6 2 Technical Support...7 3 Safety Information...8 4 Documentation...11 Check 5 About this Manual...13 6 About the 5607 I/O
More informationMODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50
MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287 Installation and Operations Manual 00-02-0651 09-01-09 Section 50 In order to consistently bring you the highest quality, full featured products,
More informationSCADAPack E I/O Module Hardware Manual (337E Only) Version: Date: August 2017
SCADAPack E 5606 I/O Module Hardware Manual (337E Only) Version: Date: August 2017 Table of Contents 1 Legal...5 Information 2 Technical...6 Support 3 Safety...7 Information 4 Overview...10 5 Installation...11
More informationSCADAPack E 5607 I/O Hardware Manual
SCADAPack E 5607 I/O Hardware Manual 2 SCADAPack E 5607 I/O Hardware Manual Table of Contents Part I 5607 Input/Output Module 3 1 Technical... Support 3 2 Safety... Information 4 3 Overview... 6 4 Installation...
More informationFLEX Ex Spring Clamp Terminal Base
Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification
More informationSCADAPack Smart RTU
SCADAPack 330 334 Smart RTU 1 Built on the proven SCADAPack 300 platform, the SCADAPack 330 and 334 feature high-performance 32-bit processing, highspeed LAN, serial and USB communications, integrated
More informationRSTI-EP Slice I/O. PROFINET Scanner EPXPNS001. GFK-2965C November 2017
November 2017 Ethernet Ports PWR, SF, BF, MT, LINK 1, ACT 1, LINK 2, and ACT 2 LEDs Door for Micro USB Port PROFINET Scanner Power Supply LED RSTI-EP Slice I/O PROFINET Scanner The PROFINET Scanner is
More informationSCADAPack 312E 313E 314E
Smart Remote Terminal Units The 300E Smart RTU is a platform built on a 32-bit processor and fitted with a 12...30 Vdc supply, various communication links and a wide range of analog and digital I/O that
More informationSCADAPack 530E 535E. remote Programmable Automation Controller
SCADAPack 530E 535E remote Programmable Automation Controller 1 With the SCADAPack 500E range, Schneider Electric introduces the first ever remote Programmable Automation Controller (rpac). This data sheet
More informationEMS467 Monitoring System. Installation and Operations Manual Section 40
EMS467 Monitoring System Installation and Operations Manual 00-02-0672 01-26-10 Section 40 In order to consistently bring you the highest quality, full featured products, we reserve the right to change
More informationOBSOLETE. Isolated, Linearized, Thermocouple Input 3B47 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
FEATURES Interfaces, amplifies, filters, isolates, & linearizes analog input voltages from a J, K, T, E, R, S or B-type thermocouple Thermocouple input signal is internally linearized High accuracy internal
More information5601/5601A Input / Output (I/O) Module
5601/5601A Input / Output (I/O) Module Installation, Operation and Maintenance Setup Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or
More informationMeasurement Systems Datascan Installation and User Guide
Measurement Systems Datascan Installation and User Guide Supplied By Contents Contents 1. INTRODUCTION... 1 1.1 GENERAL... 1 1.2 DATASCAN MODULE RANGE... 1 1.2.1 Measurement Processors... 1 1.2.2 Analog
More informationRhino Buffer Module PSM24-BFM600S. Operating Instructions
Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts
More informationSCADAPack E Input/Output Module Hardware Manual. Version: March 2016
SCADAPack E Version: Date: March 2016 Table of Contents 1 Legal Information...5 2 Technical Support...6 3 Safety Information...7 4 About this Manual...11 5 About the 6601 I/O Expansion Module...12 6 Hardware
More informationSCADAPack. I/O Expansion & Communication Modules
SCADAPack I/O Expansion & Communication Modules 1 Welcome to the SCADAPack family of I/O Expansion and Communication modules, providing flexible I/O and telemetry options. With the addition of I/O Expansion
More informationSCADAPack E Input/Output Module Hardware Manual. Version: Date: August 2017
SCADAPack E Version: Date: August 2017 Table of Contents 1 Legal Information...5 2 Technical Support...6 3 Safety Information...7 4 Documentation Check...10 5 About this Manual...11 6 About the 5610 I/O
More informationDBK48. Multipurpose Isolated Signal-Conditioning Module. Description. Supports up to Sixteen 8B Modules
DBK48 Multipurpose Isolated Signal-Conditioning Module Description 1 Safety Concerns 2 Hardware Setup 2 Installing 8B Modules 4 Installing Plug-in Resistors to Create 4 to 20 ma Loops 5 Making Terminal
More informationComponent identification
IO-ATC8 I/O Expansion Module 8 Analog/Thermocouple Inputs The IO-ATC8 is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 8 inputs that
More informationIsolated, Voltage or Current Input 7B30 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
Isolated, Voltage or Current Input 7B30 FEATURES Interfaces, amplifies and filters unipolar and bipolar millivolt and voltage inputs. Provides a protected precision output of either +1 V to +5 V or 0 V
More informationQUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!
QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationBCM2 Series Branch Circuit Monitors Quick Setup Guide
BCM2 Series Branch Circuit Monitors Quick Setup Guide Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationClipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems
Clipsal Bus Couplers Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Instruction Bulletin Retain for future use. Clipsal Bus Couplers 63249-420-236A2 Instruction
More informationIsolated, Field Configurable Analog Input 6B11 / 6B11HV FEATURES APPLICATIONS PRODUCT OVERVIEW
Isolated, Field Configurable Analog Input 6B11 / 6B11HV FEATURES Single-channel isolated signal-conditioning modules. Accepts outputs from Thermocouple, millivolt, volt and current signals. Complete microcomputer-based
More informationTable of Contents. Introduction... 2 Description...2 Specifications...3 Installation.. 5 Calibration.. 6 General Maintenance...7
User's Manual: Series 330I Model 330I DC-Powered Three-Way Isolator Table of Contents Page Introduction... 2 Description....2 Specifications....3 Installation.. 5 Calibration.. 6 General Maintenance...7
More information5OOO Series. Expansion & Communication Modules. Product Selection Guide. Expansion. Communication CONTROL MICROSYSTEMS
CONTROL MICROSYSTEMS Product Selection Guide 5OOO Series Expansion & Communication Modules Expansion Analog input module: 5 variations Analog output module: 5 variations Digital input/output relay module:
More informationIsolated Process Current Input 7B32 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
Isolated Process Current Input 7B32 FEATURES Interfaces, amplifies and filters a process-current input. Module provides a precision output of either +1 V to +5 V or 0 V to +10 V, linear with temperature.
More informationDT1102 V (PS) Fully Configurable Galvanic Isolator. Operating Instructions
(PS) Fully Configurable Galvanic Isolator Operating Instructions Contents 1. About this document...4 1.1. Function... 4 1.2. Target group... 4 1.3. Symbolism used... 4 2. For your safety...5 2.1. Authorized
More informationIsolated Wideband Voltage Input 3B40 / 3B41 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
Isolated Wideband Voltage Input 3B40 / 3B41 FEATURES Interfaces, amplifies, protects& filters wide-bandwidth (h0 khz) single-channel analog voltage inputs. Module provides simultaneous precision voltage
More informationINSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F
PSD1000 - PSD1000F INSTRUCTION MANUAL Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD1000 - Universal AC Input Switching Power Supply 24 Vdc Output ISM0089-4
More informationGeneral Specifications. P2-08THM Analog Input
General Specifications Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to Logic Side Isolation Heat Dissipation Enclosure Type Agency Approvals Module Keying
More informationPACSystems* RX3i and Series IC693MDL940 / IC694MDL940
May 2015 PACSystems* RX3i and Series 90-30 IC693MDL940 / IC694MDL940 Output Module, Relay, NO, 2 Amp, 16 Point The Series 90*-30 and PACSystems * MDL940 2 Amp Relay Output module provides 16 normally-open
More informationMagnetic Style Safety Interlock Switches
Non-contact safety interlock switches are the best choice for washdown applications; the switch components are sealed and rated NEMA 4X, IEC IP67 Tolerant of dirt buildup, sensing distance, and alignment
More informationThis Datasheet for the IC660BBA103. Block 115Vac/125Vdc Thermocouple Input 6 Channels.
This Datasheet for the IC660BBA103 Block 115Vac/125Vdc Thermocouple Input 6 Channels http://www.qualitrol.com/shop/p-14424-ic660bba103.aspx Provides the wiring diagrams and installation guidelines for
More informationSCM5B. SLX200 Data Acquisition System. isolynx. Data Acquisition Systems. Visit our website Features
Data Acquisition Systems SCM5B SLX200 Data Acquisition System Features Modbus RTU Support on RS-232 and RS-485 Modbus TCP Support (optional) 240VAC Continuous Analog Input Protection Channel-to-Channel
More informationMYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL
MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM MYR QLC MANUAL 013114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING
More informationIsolated Voltage Input 3B30 / 3B31 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
Isolated Voltage Input 3B30 / 3B31 FEATURES Interfaces, amplifies, & filtersanalog input voltages. Narrow-bandwidth (3Hz) single-channel single conditioning. Module provides simultaneous precision voltage
More informationLED55WPG Programmable LED Driver
Dimmable Constant Current Rev 8-9-7 Electrical Specifications Input Voltage Range: Frequency: Power Factor: Inrush Current: Input Current (Max): -77 Vac Nom. (8-35 V Min/Max) 5/6 Hz Nom. (47-63 Hz Min/Max)
More informationF101, F102, F104. Relcom Installation Instructions. Fieldbus Power Supply F101-PS
F101, F102, F104 Fieldbus Power Supply F101-PS Installation Instructions Relcom www.mtl-fieldbus.com CONTENTS PAGE 1 OVERVIEW 2 2 DESCRIPTION 2 3 COMPONENTS AND ACCESSORIES 2 4 MECHANICAL 3 4.1 Mounting
More informationPart Numbers. SNAP-AIARMS-i SNAP-AIARMS-i-FM* SNAP-AIVRMS-i SNAP-AIVRMS-i-FM* SNAP-AIMA-i. SNAP-AIMA-iSRC SNAP-AIMA-iSRC-FM* SNAP-AIMA2-i.
SNAP Isolated Analog Input Modules Features Channel-to-channel isolation Rugged packaging and convenient pluggable wiring. Accepts up to 14 AWG wire. Factory calibrated; no user adjustment necessary Out-of-range
More informationIO-AO6X I/O Expansion Module 6 Isolated Analog Outputs
IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs The IO-AO6X is an I/O Expansion Module that can be used in conjunction with specific Unitronics OPLC controllers. The module offers 6 12-bit isolated
More informationTelePACE Studio Ladder Logic Training Manual
TelePACE Studio Ladder Logic Training Manual SCADA products... for the distance TelePACE Studio Ladder Editor Training Manual 1999-2009 Control Microsystems Inc. All rights reserved. Printed in Canada.
More informationBlack Box Tech Support: FREE! Live. 24/7.
Black Box Tech Support: FREE! Live. 24/7. Tech support the way it should be. Great tech support is just 30 seconds away at 724-746-5500 or blackbox.com. About Black Box Black Box Network Services is your
More informationUltra-Accurate Measurement for Temperature and Voltage
Ultra-Accurate Measurement for Temperature and Voltage MEASURpoint is an ultra-accurate instrument for measuring any combination of thermocouple, RTD, and voltage inputs. MEASURpoint is available as a
More informationIsolated Process Current Input with Loop Power 7B35
Isolated Process Current Input with Loop Power 7B35 FEATURES Single-channel signal conditioning current input module that interfaces with two-wire transmitters. Module provides a precision output of either
More informationEX-RC1 Remote I/O Adapter
EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter
More informationSCADAPack 350E 357E. Smart Remote Terminal Units. Distributed by Relevant Solutions relevantsolutions.com
Smart Remote Terminal Units The SCDPack 300E Smart RTU is a platform built on a 32-bit processor and fitted with a 12...30 Vdc supply, various communication links and a wide range of analog and digital
More informationProduct User Guide. QuadTemp and OctTemp. QuadTemp 4-Channel Thermocouple Based Temperature Data Logger
Product User Guide QuadTemp and OctTemp *Thermocouple Plugs/Probes Sold Separately *Thermocouple Plugs/Probes Sold Separately QuadTemp 4-Channel Thermocouple Based Temperature Data Logger OctTemp 8-Channel
More informationSCADAPack 312E 313E. Smart RTUs for water
SCADAPack 312E 313E Smart RTUs for water 1 SCADAPack 312E and 313E Smart RTUs feature 32-bit processing, serial and US communications, integrated 12-30Vdc power supply, advanced power-management and a
More informationQUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER!
QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationSCADAPack 330E 333E 334E 337E
Smart Remote Terminal Units The 300E Smart RTU is a platform built on a 32-bit processor and fitted with a 12...30 Vdc supply, various communication links and a wide range of analog and digital I/O that
More informationPACSystems* RX3i IC695PSA140
August 2012 PACSystems* RX3i IC695PSA140 120/240VAC or 125VDC, 40 Watts The PACSystems * RX3i IC695PSA140 is a multi-purpose 40-Watt supply that operates from an input voltage source in the range of 85
More informationIsolated Linearized RTD Input 5B34 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
Isolated Linearized RTD Input 5B34 FEATURES Amplifies, Protects, Filters, and Isolates Analog Input. Linearize a wide variety of 2 & 3 wire RTDs. (True 4-wire RTD measurements are provided by the 5B35).
More informationEXPANSION PERIPHERAL CVM-R10 C. (Code ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.
EXPANSION PERIPHERAL CVM-R10 C (Code 7 70 217 ) INSTRUCTION MANUAL ( M 981 170 / 00 A ) (c) CIRCUTOR S.A. ------ CVM-R10 C Peripheral --------------- Pag. 1 CVM-R10C EXPANSION PERIPHERAL 1.- DESCRIPTION
More informationACTIONI/Q Q498. DC Powered DC Input Field Configurable Isolator with Math Functions
ACTIONI/Q Q498 DC Powered DC Input Field Configurable Isolator with Math Functions Q498-0000 Provides 2 Isolated Analog Inputs, 1 Analog Output & 1 Frequency Output, as well as a Discrete Input & Output
More informationPACSystems* RX3i IC695PSA040
August 2012 PACSystems* RX3i IC695PSA040 Power Supply, 120/240VAC or 125VDC, 40 Watts The PACSystems * RX3i power supply IC695PSA040 is a 40-Watt supply that operates from an input voltage source in the
More informationUltra-Accurate Measurement for Temperature and Voltage
Ultra-Accurate Measurement for Temperature and Voltage MEASURpoint is an ultra-accurate instrument for measuring any combination of thermocouple, RTD, and voltage inputs. MEASURpoint is available as a
More informationAS-i Safety Analog Input Module, IP20
2 safe inputs in one module: 4... 20 ma or 0... 10 V or Pt100 or thermocouple (type J / K / N / R / S) Applications up to category 4/PLe/SIL 3 (figure similar) The AS-i Safety Input Module for analog inputs
More informationQUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter
QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices.
More information5604 Input/Output (I/O) Module
5604 Input/Output (I/O) Module Installation, Operation and Maintenance Setup Manual 5/19/2011 Safety Information The information provided in this documentation contains general descriptions and/or technical
More informationICS Regent. Thermocouple Input Assembly. Input Module, Mux, Termination Panel and Cable (T3431-IM, T3431-Mux, T3431-TP and T3431-CA) PD-6024
ICS Regent Thermocouple Input Assembly Input Module, Mux, Termination Panel and Cable (T3431-IM, T3431-Mux, T3431-TP and T3431-CA) Issue 1, March, 06 The thermocouple input assembly consists of a thermocouple
More informationPV Rapid Shutdown device
PV Rapid Shutdown device Installation and Operation Manual Solis-RSD-1G(1:1) Solis-RSD-1G(2:2) Manufacturer: Ginlong (Ningbo) Technologies Co.,Ltd., Ningbo, Zhejiang, P.R.China US Office: 565 Metro Pl.
More informationD7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES
11/17 D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES D7000 FEATURES Complete data acquisition systems. Analog and Digital I/O models available. RJ-45 Ethernet 10/100MB interface. Modbus TCP/IP Ethernet
More informationUltra-Accurate Temperature Measurement Instruments
TEMPpoint Temperature Measurement Instruments Ultra-Accurate Temperature Measurement Instruments TEMPpoint is a series of precision temperature measurement instruments designed for high accuracy and industrial
More informationEX-RC1 Remote I/O Adapter
EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter
More information