ARMORSTART DISTRIBUTED MOTOR CONTROLLER

Size: px
Start display at page:

Download "ARMORSTART DISTRIBUTED MOTOR CONTROLLER"

Transcription

1 QUICK START ARMORSTART DISTRIBUTED MOTOR CONTROLLER Getting Started BULLETIN 283D Introduction This guide provides the basic information required to start up your ArmorStart Distributed Motor Controller. Factory default settings and information regarding installing, programming, and DeviceNet Node Commissioning are described here. For detailed information on specific product features or configurations, refer to the ArmorStart user manual, publication 283-UM001*-EN-P. This guide is intended for qualified service personnel responsible for setting up and servicing these devices. You must have previous experience with and a basic understanding of electrical terminology, configuration procedures, required equipment, and safety precautions. You should understand DeviceNet network operations, including how slave devices operate on a network and communicate with a DeviceNet master. You should also be familiar with RSNetWorx for DeviceNet. You must use RSNetWorx for DeviceNet Revision 3.21 Service Pack 2 or later. This software package is referred to often in this manual. Rockwell Automation product EDS files are available on the internet at:

2 2 Installation Dimensions The ArmorStart Distributed Motor Controller is convection cooled. Operating temperature must be kept between C ( F). Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change. Figure 1 Dimensions for IP67/NEMA Type 4 with Conduit Entrance

3 3 Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change. Figure 2 Dimensions for IP67/NEMA Type 4 with ArmorConnect Connectivity ArmorStart device with a 10 A short circuit protection rating ArmorStart device with a 25 A short circuit protection rating

4 4 Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change. Figure 3 Dimensions for NEMA Type 4X with Conduit Entrance

5 5 Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change. Figure 4 Dimensions for NEMA Type 4X with ArmorConnect Connectivity ArmorStart device with a 10 A short circuit protection rating ArmorStart device with a 25 A short circuit protection rating

6 6 Wiring Power, Control, Safety Monitor Inputs, and Ground Wiring Table 1 provides the power, control, safety monitor inputs, and ground wire capacity and the tightening torque requirements. The power, control, ground, and safety monitor terminals will accept a maximum of two wires per terminal. Table 1 Power, Control, Safety Monitor Inputs, Ground Wire Size and Torque Specifications Terminals Wire Size Torque Wire Strip Length Power and Ground Primary/Secondary Terminal: mm 2 (#18 #10 AWG) Primary Terminal: lb.-in. ( N m) Secondary Terminal: lb.-in ( N m) 0.35 in. (9 mm) Control and Safety Monitor Inputs 0.34mm mm 2 (#22 #10 AWG) lb.-in (0.6 N m) 0.35 in. (9 mm) Terminal Designations for Conduit Entrance As shown in Figure 5, the ArmorStart Distributed Motor Controller contains terminals for power, control, safety monitor inputs, and ground wiring. Access can be gained by removing the terminal access cover plate. Figure 5 ArmorStart Power, Control, and Safety Monitor Terminals Secondaries Primaries

7 7 Table 2 Power, Control, Safety Monitor, and Ground Terminal Designations Terminal Designations No. of Poles Description SM1 ➊ 2 Safety Monitor Input SM2 ➊ 2 Safety Monitor Input A1 (+) 2 Control Power Input A2 (-) 2 Control Power Common PE 2 Ground 1/L1 2 Line Power Phase A 3/L3 2 Line Power Phase B 5/L5 2 Line Power Phase C ➊ Only available with the Safety Monitor option. Operation of NEMA Type 4X Disconnect Handle To Open Disconnect Handle 1. Rotate locking ring 45 until it stops. 2. To open, push the tab on the left-hand side and lift the access cover. Note: The access door can not be closed when 140 (black handle) is in the OFF position. To Close Disconnect Handle for Lockout/Tag out With disconnect handle in the ON position, rotate lockout/tag out ring counterclockwise until the disconnect handle is in the OFF position. Note: The disconnect hanlde is designed to be used with a 1/4 in. lockout/tag out padlock.

8 RESET OFF 8 ArmorConnect Power Media Enclosure Description The ArmorStart Power Media offers both three-phase and control power cable system of cordsets, patchcords, receptacles, tees, reducers and accessories to be utilized with the ArmorStart Distributed Motor Controller. These cable system components allow quick connection of ArmorStart Distributed Motor Controllers and reduce installation time. They provide for repeatable, reliable connection of the three-phase and control power to the ArmorStart Distributed Motor Controller and motor by providing a plug and play environment that also avoids system mis-wiring. When specifying power media for use with the ArmorStart Distributed Motor Controllers (Bulletins 280, 281, 283, and 284) use only the Bulletin 280 ArmorConnect power media. Figure 6 Three-Phase Power System Overview PLC Bulletin 1492FB Branch Circuit Protective Device Bulletin 1606 Power Supply 1606-XLSDNET4 DeviceNet Power Supply Bulletin 280/281 ArmorStart Bulletin 283 ArmorStart Bulletin 284 ArmorStart Bulletin 800F Emergency Stop Pushbutton ➊ Three-Phase Power Trunk- PatchCord cable with integral female or male connector on each end. (Example Part Number: 280-PWR35A-M*) ➋ Three-Phase Drop Cable- PatchCord cable with integral female or male connector on each end (Example Part Number: 280-PWR22A-M*) ➌ Three-Phase Power Tees and Reducer - Tee connects to a single drop line to trunk with quick change connectors Part Number: 280-T35 Reducing Tee connects to a single drop line (Mini) to trunk (Quick change) connector Part Number: 280-RT35 Reducer connects from quick change male connector to mini female connector Part Number: 280-RA35 ➍ Three-Phase Power Receptacles - Female receptacles are a panel mount connector with flying leads Part Number: 280-M35F-M1

9 RESET OFF 9 Enclosure Figure 7 Control Power Media System Overview PLC Bulletin 1492FB Branch Circuit Protective Device Bulletin 1606 Power Supply 1606-XLSDNET4 DeviceNet Power Supply Bulletin 280/281 ArmorStart Bulletin 283 ArmorStart Bulletin 284 ArmorStart Bulletin 800F Emergency Stop Pushbutton ➏ Control Power Media Patchcords - PatchCord cable with integral female or male connector on each end Example Part Number: 889N-F65GFNM-* ➐ Control Power Tees - The E-stop In Tee (Part Number: 898N-653ES-NKF) is used to connect to the Bulletin 800F On-Machine E-Stop station using a control power media patchcord. The E-stop Out tee (Part Number: 898N-653ST-NKF) is used with cordset or patchcord to connect to the ArmorStart Distributed Motor Controller. ➑ Control Power Receptacles - Female receptacles are a panel mount connector with flying leads Part Number: 888N-D65AF1-*

10 10 ArmorStart with ArmorConnect Connectivity ArmorStart devices with 10 A short circuit protection rating ArmorStart devices with 25 A short circuit protection rating Control Power Receptacle Three-Phase Power Receptacle Control Power Receptacle Three-Phase Power Receptacle Installing ArmorConnect Power Media using Cord Grips Cord Grips for ArmorStart Devices with 10 A short circuit protection rating 3/4 in. Lock Nut 1 in. Lock Nut Thomas & Betts Cord Grip Part Number: 2931NM 3/4 in. Stain Relief Cord Connector Cable Range: in. Used with Control Power Media Cordset - Example Part Number: 889N-M65GF-M2 Thomas & Betts Cord Grip Part Number: 2940NM 1 in. Stain Relief Cord Connector Cable Range: in. Used with Three-Phase Power Media Cordset - Example Part Number: 280-PWR22G-M1 Cord Grips for ArmorStart Devices with 25 A short circuit protection rating 3/4 in. Lock Nut 1 in. Lock Nut Thomas & Betts Cord Grip Part Number: 2931NM 3/4 in. Stain Relief Cord Connector Cable Range: in. Used with Control Power Media Cordset - Example Part Number: 889N-M65GF-M2 Thomas & Betts Cord Grip Part Number: 2942NM 1 in. Stain Relief Cord Connector Cable Range: in. Used with Three-Phase Power Media Cordset - Example Part Number: 280-PWR35G-M1

11 11 Terminal Designations Description Color Code A1 (+) Control Power Input Blue A2 (-) Control Power Common Black PE Ground Green/Yellow 1/L1 Line Power - Phase A Black 2/L2 Line Power - Phase B White 3/L3 Line Power - Phase C Red ArmorConnect Cable Ratings The ArmorConnect Power Media cables are rated per UL Type TC 600V 90 C Dry 75 C Wet, Exposed Run (ER) or MTW 600V 90 C or STOOW 105 C 600V - CSA STOOW 600V FT2. For additional information regarding ArmorConnect Power Media see the ArmorStart User Manual. Branch Circuit Protection Requirements for ArmorConnect Three-Phase Power Media When using ArmorConnect Three-Phase Power Media, only fuses can be used for the motor branch circuit protective device, for the group motor installations. The recommended fuse types are the following: Class CC, T, or J type fuses. For additional information, see the ArmorStart User Manual.

12 12 Group Motor Installations for USA and Canada Markets The ArmorStart Distributed Motor controllers are listed for use with each other in group installations per NFPA 79, Electrical Standard for Industrial Machinery. When applied according to the group motor installation requirements, two or more motors, of any rating or controller type, are permitted on a single branch circuit. Group Motor Installation has been successfully used for many years in the USA and Canada. Wiring and Workmanship Guidelines In addition to conduit and seal-tite raceway, it is acceptable to utilize cable that is dual rated Tray Cable, Type TC-ER and Cord, STOOW, for power and control wiring on ArmorStart installations. In the USA and Canada installations, the following guidance is outlined by the NEC and NFPA 79. In industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation, and where the exposed cable is continuously supported and protected against physical damage using mechanical protection, such as struts, angles, or channels, Type TC tray cable that complies with the crush and impact requirements of Type MC (Metal Clad) cable and is identified for such use with the marking Type TC-ER (Exposed Run)* shall be permitted between a cable tray and the utilization equipment or device as open wiring. The cable shall be secured at intervals not exceeding 1.8 m (6 ft) and installed in a good workman-like manner. Equipment grounding for the utilization equipment shall be provided by an equipment grounding conductor within the cable. *Historically cable meeting these crush and impact requirements were designated and marked Open Wiring. Cable so marked is equivalent to the present Type TC-ER and can be used. While the ArmorStart is intended for installation in factory floor environments of industrial establishments, the following must be taken into consideration when locating the ArmorStart in the application: Cables, including those for control voltage including 24V DC and communications, are not to be exposed to an operator or building traffic on a continuous basis. Location of the ArmorStart to minimize exposure to continual traffic is recommended. If location to minimize traffic flow is unavoidable, other barriers to minimize inadvertent exposure to the cabling should be considered. Routing cables should be done in such a manner to minimize inadvertent exposure and/or damage. Additionally, if conduit or other raceways are not used, it is recommended that strain relief fittings be utilized when installing the cables for the control and power wiring through the conduit openings. The working space around the ArmorStart may be minimized as the ArmorStart does not require examination, adjustment, servicing or

13 13 maintenance while energized. In lieu of this service, the ArmorStart is meant to be unplugged and replaced after proper lockout/tag-out procedures have been employed. Since the ArmorStart is available with a factory installed HOA keypad option this may require the ArmorStart to be selected and installed as follows if the application requires frequent use of the hand operated interface by the equipment operator: 1. They are not less than 0.6 m (2 ft) above the servicing level and are within easy reach of the normal working position of the operator. 2. The operator is not placed in a hazardous situation when operating them. 3. The possibility of inadvertent operation is minimized. If the operated interface is used in industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons operate and service the ArmorStart's operator interface, and the installation is located so that inadvertent operation is minimized then other installation locations with acceptable access can be provided. DeviceNet Network Installation The ArmorStart Distributed Motor Controller contains the equivalent of 30 in. (0.76 m) of Device Net drop cable's electrical characteristics and therefore 30 in. of drop cable must be included in the DeviceNet drop cable budget for each ArmorStart in addition to actual drop cable required for the installation. Other DeviceNet System Design Considerations The separation of the control power and DeviceNet power is recommended as a good design practice. This minimizes the load on the DeviceNet supply, and prevents transients which may be present on the control power system from influencing the communication controls.

14 14 LED Status Indication The LED Status Indication provides 4 status LEDs and a Reset button. The LEDs provide status indication for the following: POWER LED The LED is illuminated solid green when control power is present and with the proper polarity RUN LED This LED is illuminated solid green when a start command and control power are present NETWORK LED This bi-color (red/green) LED indicates the status of the communication link FAULT LED Indicates Controller Fault (trip) condition The Reset Button as a local trip reset. Figure 8 LED Status Indication and Reset DeviceNet Node Commissioning Establishing a DeviceNet Node Address The ArmorStart is shipped with a default node address of 63 and Autobaud enabled. Each device on a DeviceNet network must have a unique node address or MAC ID which can be set to a value from Keep in mind that most DeviceNet systems use address 0 for the master device (Scanner) and node address 63 should be left vacant for introduction of new slave devices. The ArmorStart offers two methods for node commissioning as shown in the following pages. Node Commissioning using Software To set the node address of the ArmorStart using software or other handheld tools, leave the hardware rotary switches in their default position (99) or insure that they are set to something greater then (63). With the hardware switches set, use the software or handheld tool to change the address. When using software to node commission a device, it may be necessary to have the EDS file stored on the computer. The EDS file defines how the software such as RSNetWorx for DeviceNet will communicate to the ArmorStart. Rockwell Automation product EDS files are available on the internet at: You must use RSNetWorx for DeviceNet Revision 3.21 Service Pack 2 or later.

15 15 Node Commissioning using Hardware The ArmorStart is shipped with the hardware rotary switches set to a value of (99). If the switches are set to a value of (64) or above, the device will automatically configure itself to the software node address. If the switches are set to a value of (63) or less, the device will be at the node address designated by the switch configuration. To set an address using the hardware rotary switches, simply set the switches to the desired node address. To access the node address rotary switches, three-phase and control power should be turned off. Then remove the starter module from the base unit. The rotary node address switches are located on the back side of the starter module. Change the switches to the desired node address. Re-install the starter module to the base unit. Reapply power and the device will re-start at the new address. Figure 9 Rotary Node Address Configuration See Detail A Detail A MSD LSD System Configuration Information The following information is provided to identify the default method for setting up communication to the ArmorStart. Additional configuration information and advanced settings help can be found in the ArmorStart User Manual, Publication 283-UM001*-EN-P. Using Automap feature with default Input and Output (I/O) assemblies The Automap feature available in all Rockwell Automation scanners will automatically map the information as shown below. If manual mapping is required, the information below can be used to map a device based on the default configuration.

16 16 Table 3 Default I/O Messaging Data Default Message type Consumed data size Produced data size Polled 1 byte (Rx) 2 bytes (Tx) Default Input and Output (I/O) Assembly Formats The I/O assembly formats for the ArmorStart are identified by the value in parameter 11 (Consumed IO Assy.) and parameter 12 (Produced IO Assy.). These values determine the amount and arrangement of the information communicated to the master scanner. The tables below identify the default information produced and consumed by the Bulletin 283 devices. For additional formats and advance configurations please reference the user manual: Defaults for Standard Distributed Motor Controllers Table 4 Instance Default Consumed data for Standard Distributed Motor Controller Output information arrangement (1 byte) Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 User Out B User Out A Not Used Not Used Not Used Fault Reset Run Fwd Table 5 Instance Default Produced data for Standard Distributed Motor Controller Input information arrangement (2 bytes) Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Not Used Not Used Not Used Ready Running Fwd Warning Tripped 1 Not Used Not Used 140M On HOA Status User In 3 User In 2 User In 1 User In 0

17 17 Setting the Motor FLA ATTENTION! Control power must be applied to the Bulletin 283 Distributed Motor Controller, to gain access to the soft starter parameters. The product should now be configured and communicating on the network. The last step is to program the proper motor FLA setting (parameter #106). This can be accomplished by using software such as RSNetWorx for DeviceNet or a handheld DeviceNet tool. Use the software to access the device parameters screen. By default the motor FLA is set to the minimum FLA setting for the device and the overload trip class is set to 10. Set these parameters to the desired values and download to the device. Select FLA setting (parameter #106) and enter a value that corresponds to the FLA of the motor connected to the ArmorStart. Make sure the Single radio button is selected and then select Download to Device. The Overload Trip class for the Bulletin 283 Distributed Motor Controller is class 10. The proper motor protection is now in place. Figure 10 RSNetWorx Parameter Screen

18 18 Quick Reference Troubleshooting There are four LEDs on the front of the ArmorStart that can provide an indication as to the health of the device. The following is a brief explanation of the operation of each LED. Table 6 LED Status Indication LED Power Run Network Fault Definition This LED will be illuminated solid green when control power is present and with the proper polarity. This LED will be illuminated solid green when a start command and control power are present. This bi-color LED is used to indicate the status of the DeviceNet network. See the Network Status LED table below for additional information. This LED is used to indicate the fault status of the ArmorStart. When the unit is faulted, the unit will respond with a specific blink pattern to identify the fault. See the Fault LED table below for additional information. Table 7 Network LED Status Indication Off Network Status LED Definition Possible Causes Flashes green-red-off Solid Green Flashing Green The device has not completed the initialization, is not on an active network, or may not be powered up. While waiting to detect the network baud rate, the LED will flash this pattern about every 3 seconds. The device is operating in a normal condition, and is communicating to another device on the network. The device is operating in a normal condition, is on-line, but with no connection to another device. This is the typical state for new devices. Check to make sure the product is properly wired and configured on the network. If the product stays in this state it means that there is no set baud rate. Insure that at least one device on the network has a set baud rate. No action required. The device may need to be mapped to a master scanner, placed in a scanlist, or have another device communicate to it. Flashing Red Recoverable fault has occurred. Check to make sure the PLC and scanner are operating correctly and that there are no media/cabling issues. Check to see if other networked devices are in a similar state. Solid Red The device has detected a major error that has rendered it incapable of communicating on the network (Duplicate MAC ID, Bus-off, media issue). Troubleshooting should be done to ensure that the network is correct (terminators, lengths, etc.) and there is not a duplicate node problem. If other devices on the network appear to be operating fine and power cycling the device does not work, contact Technical Support. Flashing Red and Green The device is in a communication faulted state. Power cycling the device may resolve the problem; however, if the problem continues, it may be necessary to contact Technical Support.

19 19 Fault LED indications for Bulletin 283D ArmorStart Distributed Motor Controllers Table 8 Controller Fault LED Definitions Blink Pattern Definitions Possible Causes or Remedies Short Circuit Overload trip Phase Loss Shorted SCR Phase Rotation Control Power I/O Fault The motor circuit protector has tripped, or the internal wiring protection algorithm has detected an unsafe current range. Try to reset the protector if tripped. If the condition continues, check the power wiring. This fault cannot be disabled. The load has drawn excessive current and based on the trip class selected, the device has tripped. Verify that the load is operating correctly and the ArmorStart is properly set-up. This fault cannot be disabled. The ArmorStart has detected a missing phase. Verify that three-phase voltage is present at the line side connections. This fault can be disabled and is disabled by default. Prior to every start, the unit will check all SCRs for shorts and unit load connections to the motor. If there is a shorted SCR in the SMC-3 and/or open load, the start will be aborted and a shorted SCR/open load fault will be indicated. This prevents damage from phase imbalance. This fault cannot be disabled. When enabled, 3-phase input power will be verified before starting. If input power phasing is detected to be incorrect, the start will be aborted and a fault indicated. This fault can be disabled and is disabled by default. The ArmorStart has detected a loss of the control power voltage. Check control voltage, wiring, and proper polarity. Also, check and replace the control voltage fuse,if necessary. This fault can be disabled and is disabled by default. This error indicates a shorted sensor, shorted input device, wiring input mistakes, or a blown output fuse. If this fault occurs, the offending problem should be isolated or removed prior to restarting the system. This fault can be disabled and is disabled by default. 8 Over Temperature This fault is generated when the operating temperature has been exceeded. This fault cannot be disabled. 9 Phase Imbalance The ArmorStart has detected a voltage imbalance. Check the power system and correct if necessary. This fault can be disabled and is disabled by default. 10 DNet Power Loss DeviceNet power has been lost or has dropped below the 12V threshold. Check the state of the network power supply and look for DeviceNet media problems. This fault can be disabled and is disabled by default. 11 Internal Communication This fault occurs when communication between the main board and the SMC-3 is lost. This fault cannot be disabled Heatsink Over temperature/jam EEPROM Fault This fault indicates either an over temperature fault or a JAM fault. The heatsink is monitored by thermistors and the SCR temperature is tracked by an algorithm. When a maximum temperature is reached by either, the microcomputer switches off the SMC and indicates a fault code of 12. A fault code of 12 could also indicate a JAM fault.this fault cannot be disabled. This is a major fault, which renders the ArmorStart inoperable. Possible causes of this fault are transients induced during EEprom storage routines. If the fault was, initiated by a transient, power cycling should clear the problem otherwise replacement of the ArmorStart may be required. This fault cannot be disabled. 14 Hardware Fault 16 Miscellaneous Fault This fault cannot be disabled. This fault indicates that a serious hardware problem exists. Check for a base/starter module mismatch. If no mismatch exists, the ArmorStart may need to be replaced. (Hdw Flt is the factory-enabled default setting.) This fault cannot be disabled.

20 20 Bulletin 283 Parameters Table 9 Starter Display and Parameter Settings Parameter Name String Path (hex) Min Max Dflt Type Value SMC Display 101 Phase A Current 002C INT xxx.x Amps 102 Phase B Current 002C INT xxx.x Amps 103 Phase C Current 002C 01 0A INT xxx.x Amps 104 Average Current 002C INT xxx.x Amps 105 % Therm Utilized 002C USINT xxx % SMC Settings 106 FLA Setting 002C See Table 10 below Min I INT xxx.x Amps 107 OL Trip Class 002C BYTE 1 = OL Reset Level BYTE xxx % 109 Start Time 000F - 06D USINT sec 110 Start Mode 000F - 06E BOOL 0 = Current Limit 1 = Soft Start 111 Current Limit 000F UINT xxx % FLA Display multiplier of 10. SMC is looking for values between 15 and Initial Torque 000F USINT % LRT 113 Soft Stop Time 000F USINT sec 114 Kick Start 000F USINT sec 115 SCR Temp Reset Mode 000F BOOL 0 = Manual 1 = Auto Reset 116 Phase Rotation 000F BOOL 0 = Disable 1 = Enable Table 10 FLA Setting Ranges and Default Values (with indicated setting precision) Minimum Value FLA Current Range (A) Maximum Value Default Value

21 21 Figure 11 Bulletin 283 ArmorStart Local Disconnect LED Status Indication 2 Outputs (Micro/M12) 4 Inputs (Micro/M12) Source Brake Connector DeviceNet Connection (Mini/M18) Motor Connection Ground Terminal Figure 12 Bulletin 283 ArmorStart Ground Terminal Ground Terminal Control Power Three-Phase Power Control Power Three-Phase Power

22 22 Table 11 DeviceNet Media ➊ Description Length m (ft) Cat. No. KwikLink pigtail drops are Insulation Displacement Connector (IDC) with integral Class 1 round cables for interfacing devices or power supplies to flat cable Sealed 1 m (3.3) 1485P-P1E4-B1-N5 2 m (6.5) 1485P-P1E4-B2-N5 3 m (9.8) 1485P-P1E4-B3-N5 6 m (19.8) 1485P-P1E4-B6-N5 DeviceNet Mini- T-Port Tap Right Keyway Left Keyway 1485P-P1N5-MN5NF 1485P-P1N5-MN5KM Gray PVC Thin Cable Thick Cable Connector Mini Straight Female Mini Straight Male Mini Straight Female Mini Right Angle Male Mini Right Angle Female Mini Straight Male Mini Right Angle Female Mini Straight Male Mini Straight Female Mini Straight Male Mini Straight Female Mini Right Angle Male Mini Right Angle Female Mini Straight Male Mini Right Angle Female Mini Straight Male Cat. No. 1485G-P ➋ N5-M5 1485G-P ➋ W5-N5 1485G-P ➋ M5-Z5 1485G-P ➋ W5-Z5 1485C-P ➌ N5-M5 1485C-P ➌ W5-N5 1485C-P ➌ M5-Z5 1485C-P ➌ W5-Z5 ➊ See publication M116-CA001A-EN-P for complete cable selection information. ➋ Replace symbol with desired length in meters (Example: 1485G-P1N5-M5 for a 1 m cable). Standard cable lengths: 1 m, 2 m, 3 m, 4 m, 5 m, and 6 m. ➌ Replace symbol with desired length in meters (Example: 1485C-P1N5-M5 for a 1 m cable). Standard cable lengths: 1 m, 2 m, 3 m, 4 m, 5 m, 6 m, 8 m, 10 m, 12 m, 18 m, 24 m, and 30 m. NOTE: Stainless steel versions may be ordered by adding an S to the cat. no. (Example: 1485CS-P1N5-M5)

23 23 Table 12 Sensor Media ➊ Description ArmorStart I/O Connection Pin Count Connector Cat. No. 0 Straight Female Straight Male 889D-F4ACDM- ➋ 0 DC Micro Patchcord Input 5-Pin Straight Female Right Angle Male 889D-F4AACDE- ➋ 0 Straight Female 879D-F4ACDM- ➋ Input 5-pin Right Angle Male 879D-R4ACM- ➋ 0 DC Micro V-Cable 0 Input 5-pin Straight Female Right Angle Male 879D-F4ACTE- ➋ 0 DC Micro Y-Cable Straight Female Straight Male 889R-F3AERM- ➋ AC Micro Patchcord Output 3-pin Straight Female Right Angle Male 899R-F3AERE- ➋ ➊ See publication M116-CA001A-EN-P for complete cable selection information. ➋ Replace symbol with desired length in meters (Example: 889D-F4ACDM-1 for a 1 m cable). Standard cable lengths: 1 m, 2 m, 5 m, and 10 m. NOTE: Stainless steel versions may be ordered by adding an S to the cat. no. (Example: 889DS-F4ACDM-1) Table 13 Sealing Caps ➌ Description Used on I/O Connection Catalog Number Plastic Sealing Cap (M12) Input 1485A-M12 Aluminum Sealing Cap Output 889A-RMCAP ➌ To achieve IP67 rating, sealing caps must be installed on all unused I/O connections.

24 Registered Trademark List ArmorPoint and ArmorStart are registered trademarks of Rockwell Automation, Inc. Trademark List ArmorConnect, RSLogix5000, PLC, RSNetWorx, and SLC are trademarks of Rockwell Automation, Inc. DeviceNet and the DeviceNet logo are trademarks of the Open Device Vendors Association (ODVA). Publication 283D-QS001C-EN-P July (1) Superecedes Publication 283D-QS001B-EN-P September 2005 Copyright 2006 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.

ARMORSTART DISTRIBUTED MOTOR CONTROLLER SAFETY VERSION

ARMORSTART DISTRIBUTED MOTOR CONTROLLER SAFETY VERSION QUICK START ARMORSTART DISTRIBUTED MOTOR CONTROLLER SAFETY VERSION Getting Started BULLETIN 280D/281D Introduction This guide provides the basic information required to start up your ArmorStart Distributed

More information

ARMORSTART DISTRIBUTED MOTOR CONTROLLER SAFETY VERSION

ARMORSTART DISTRIBUTED MOTOR CONTROLLER SAFETY VERSION QUICK START ARMORSTART DISTRIBUTED MOTOR CONTROLLER SAFETY VERSION Getting Started BULLETIN 280G/281G Introduction This guide provides the basic information required to start up your ArmorStart Distributed

More information

Bulletin 280/281 ArmorStart Distributed Motor Controller Overview

Bulletin 280/281 ArmorStart Distributed Motor Controller Overview Overview 1 2 3 5 6 7 8 9 10 11 12 13 The Bulletin 280/281 ArmorStart Distributed Motor Controller is an integrated, pre-engineered, starter for full-voltage and reversing applications. The ArmorStart offers

More information

ArmorConnect Power and Control Media

ArmorConnect Power and Control Media Selection Guide ArmorConnect Power and Control Media Bulletins 280, 888, 889, 898 2 Bulletin 280, 888, 889, 898 Power Media Product Overview Media Description Features Trunk Cable Cordset - Cable with

More information

Bulletin 280E/281E, 284E ArmorStart Distributed Motor Controller Product Overview

Bulletin 280E/281E, 284E ArmorStart Distributed Motor Controller Product Overview , 284E Product Overview Product Line The ArmorStart Distributed Motor Controller is an integrated, preengineered, motor starter solution for On-Machine applications. The ArmorStart offers as standard,

More information

ArmorStart Distributed Motor Controllers

ArmorStart Distributed Motor Controllers ArmorStart Distributed Motor Controllers ArmorStart ST Expands the ArmorStart Portfolio with Safety Features/Benefits Features built-in dual port for EtherNet/IP allowing a DLR to enhance efficiency and

More information

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice MPCR Series DeviceNet Technical Manual Table of Contents MPCR Series Introduction... 3 Product Overview... 3 About DeviceNet... 4 Overview... 4 MPCR DeviceNet Features... 4 Cabling and Drop Line Lengths

More information

DeviceNet Module. User Manual. 1 Important User Information. 2 Installation

DeviceNet Module. User Manual. 1 Important User Information. 2 Installation User Manual 1 Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. It is the installer's

More information

Power Supply and Media

Power Supply and Media Power Supply and Table of Contents Quick Selection Introduction Supply & General Power Supply and General Information Selection Criteria...11-2 Quick Selection Guide...11-4 Three-Phase Power Three-Phase

More information

Solid-State Motor Control Table of Contents

Solid-State Motor Control Table of Contents Solid-State Motor Control Table of Contents ArmorStart Distributed Motor Controller Page - Bulletin 0/... Page - Bulletin... Page - Bulletin... Page - Bulletin 00 DSA I/O for Distributed Starters... Web

More information

DeviceNet Pendant Stations

DeviceNet Pendant Stations DeviceNet Pendant Stations Bulletin 800E/F User Manual Important User Information The illustrations, charts, sample programs, and layout examples shown in this guide are intended solely for purposes of

More information

Bulletin 280/281 ArmorStart Distributed Motor Controller. DeviceNet Media

Bulletin 280/281 ArmorStart Distributed Motor Controller. DeviceNet Media Bulletin 280/281 ArmorStart Distributed Motor Controller DeviceNet Media Length [m (ft)] Sealed KwikLink pigtail drops are Insulation Displacement Connector (IDC) with integral Class 1 round cables for

More information

ARMORSTART POWER MEDIA SYSTEM QUICK REFERENCE GUIDE COLLECTION :

ARMORSTART POWER MEDIA SYSTEM QUICK REFERENCE GUIDE COLLECTION : ARMORSTART POWER MEDIA SYSTEM QUICK REFERENCE GUIDE COLLECTION : Single page documents providing comprehensive system examples of the cable assemblies for ArmorStart, ArmorStart ST, ArmorStart LT, and

More information

Allen-Bradley Automation

Allen-Bradley Automation Product Data 1791D CompactBlock I/O for DeviceNet 1791D CompactBlock I/O modules contain I/O circuits, a built-in power supply, and a built-in DeviceNet I/O adapter. CompactBlock I/O modules are ideal

More information

L5351 DeviceNet Communications Interface

L5351 DeviceNet Communications Interface L5351 DeviceNet Communications Interface Technical Manual HG353798 Issue 2 Copyright SSD Drives, Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or

More information

Install the DeviceNet Module using the following procedure:

Install the DeviceNet Module using the following procedure: Installation INSTALLATION INSTRUCTIONS: MCD DEVICENET MODULE Order Code: 175G9002 1. Installation Install the DeviceNet Module using the following procedure: 1. Remove control power and mains supply from

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. MCD DeviceNet Module Instructions Important User Information INSTALLATION INSTRUCTIONS: MCD DEVICENET MODULE Order Code: 175G9002 1. Important User Information Observe all necessary safety precautions

More information

CATALOG NUMBER 193-EDN

CATALOG NUMBER 193-EDN USER MANUAL BULLETIN 193 E1 Plus DeviceNet Module CATALOG NUMBER 193-EDN Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

MCD 200 Series. MCD 200 DEVICENET Module OPERATING INSTRUCTIONS. MCD 200 DEVICENET Module. Order Code: 175G9002. Adjustment.

MCD 200 Series. MCD 200 DEVICENET Module OPERATING INSTRUCTIONS. MCD 200 DEVICENET Module. Order Code: 175G9002. Adjustment. Installation OPERATING INSTRUCTIONS Order Code: 175G9002 Adjustment 35 mm (1.38 inches) Control power and mains supply must be removed from the MCD 200 before attachment or removal of an accessory module.

More information

1. Installation DEVICENET INTERFACE. Install the DeviceNet Interface using the following procedure:

1. Installation DEVICENET INTERFACE. Install the DeviceNet Interface using the following procedure: PIM-DN-01 DeviceNet Interface 1. Installation Install the DeviceNet Interface using the following procedure: 1. Remove control power and mains supply from the soft starter. 2. Attach the DeviceNet Interface

More information

DeviceNet ArmorBlock Network Powered 16-input Module

DeviceNet ArmorBlock Network Powered 16-input Module Installation Instructions DeviceNet ArmorBlock Network Powered 16-input Module Catalog number 1732D-IBDPM12MND, Series A Table of Contents Topic Page Important User Information 2 Environment and Enclosure

More information

MPCR Series DeviceNet Technical Manual

MPCR Series DeviceNet Technical Manual MPCR Series DeviceNet Technical Manual Table of Contents MPCR Series Introduction...3 Product Overview...3 About DeviceNet...4 Overview...4 MPCR DeviceNet Features...4 Cabling and Drop Line Lengths (as

More information

Ethernet/IP Module. User Manual. Contents

Ethernet/IP Module. User Manual. Contents User Manual Contents 1 Important User Information... 2 2 Installation... 3 3 Connection... 4 4 Device Configuration... 5 5 Operation... 8 6 Packet Structures... 9 7 Network Design... 18 8 Specifications...

More information

ArmorBlock MaXum I/O and ArmorBlock I/O Selection Guide. 1792D and 1732 Series

ArmorBlock MaXum I/O and ArmorBlock I/O Selection Guide. 1792D and 1732 Series ArmorBlock MaXum I/O and ArmorBlock I/O Selection Guide 1792D and 1732 Series 2 ArmorBlock I/O Overview The ArmorBlock family provides industrially hardened blocks of 24V dc digital I/O that can be mounted

More information

- 15G0078B120 - DEVICENET MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

- 15G0078B120 - DEVICENET MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB - 5G0078B0 - DEVICENET MODULE INSTRUCTIONS FOR ASAC-0/ASAC-/ASAB Issued on 5/06/ R. 0 This manual is integrant and essential to the product. Carefully read the instructions contained herein as they provide

More information

PV Rapid Shutdown device

PV Rapid Shutdown device PV Rapid Shutdown device Installation and Operation Manual Solis-RSD-1G(1:1) Solis-RSD-1G(2:2) Manufacturer: Ginlong (Ningbo) Technologies Co.,Ltd., Ningbo, Zhejiang, P.R.China US Office: 565 Metro Pl.

More information

PowerLogic High Density Metering System 1-Meter Enclosure

PowerLogic High Density Metering System 1-Meter Enclosure PowerLogic High Density Metering System 1-Meter Enclosure Installation Guide 63230-508-211A1 Safety information PowerLogic High Density Metering System 1-Meter Enclosure Important information Read these

More information

DeviceNet ArmorBlock Network and Auxiliary Powered I/O Module

DeviceNet ArmorBlock Network and Auxiliary Powered I/O Module Installation Instructions DeviceNet ArmorBlock Network and Auxiliary Powered I/O Module Catalog Number 1732D-8X81212D Topic Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic

More information

DeviceNet ArmorBlock Network Powered 16-input Module, Series A

DeviceNet ArmorBlock Network Powered 16-input Module, Series A Installation Instructions DeviceNet ArmorBlock Network Powered 16-input Module, Series A Catalog Number 1732D-IB161212D Topic Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic

More information

ArmorStart Distributed Motor Controller

ArmorStart Distributed Motor Controller User Manual ArmorStart Distributed Motor Controller Catalog Numbers 280, 281, 284 Important User Information Read this document and the documents listed in the additional resources section about installation,

More information

G3 Series DeviceNet TM Technical Manual

G3 Series DeviceNet TM Technical Manual G3 Series DeviceNet TM Technical Manual Table of Contents G3 Series DeviceNet Technical Manual PAGE About DeviceNet... 3 Overview... 3 G3 DeviceNet Features... 3 Cabling and Drop Line Lengths (as defined

More information

DeviceNet ArmorBlock Network and Auxiliary Powered Module, Series A

DeviceNet ArmorBlock Network and Auxiliary Powered Module, Series A Installation Instructions DeviceNet ArmorBlock Network and Auxiliary Powered Module, Series A Catalog Number 1732D-8X81212HD Topic Page Important User Information 2 Environment and Enclosure 3 Prevent

More information

Copyright: December 2017 Nidec Issue: E

Copyright: December 2017 Nidec Issue: E General Information The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or incorrect installation or adjustment of the optional parameters of the equipment

More information

2002 Series DeviceNet Technical Manual

2002 Series DeviceNet Technical Manual 2002 Series DeviceNet Technical Manual Table of Contents 2002 Series DeviceNet Technical Manual 2002 Introduction...4 Product Overview...4 About DeviceNet...5 Overview...5 2002 DeviceNet Features...5 Cabling

More information

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE INSTRUCTIONS MODBUS TCP MODULE for use with WSIQ2/WSE WorldWide Electric Corporation Phone: 1-800-808-2131 Fax: 1-800-711-1616 www.worldwideelectric.net Product Compatibility This communications module

More information

QCPort Cover Control Trouble Shooting Guide

QCPort Cover Control Trouble Shooting Guide QCPort Cover Control Trouble Shooting Guide Technical Document Feb. 2006 Page 1 of 14 QCPort Cover Control Description Door Defeater Address/Options Bucket Latch Breaker Actuator Hasp Lock Keypad Overlay

More information

Bulletin 290/291, 294 ArmorStart LT Distributed Motor Controllers Description/Features

Bulletin 290/291, 294 ArmorStart LT Distributed Motor Controllers Description/Features Bulletin 290/291, 294 /Features Product Line ArmorStart LT, Bulletin 290/291/294 is an integrated, pre-engineered distributed motor control solution. It provides excellent performance at a great value

More information

DeviceNet Media Media, Sensors and Distributed I/O

DeviceNet Media Media, Sensors and Distributed I/O DeviceNet Media Media, Sensors and Distributed I/O Flat, Thick and Thin Media Photoelectric and Inductive Proximity Sensors Limit Switches Encoders ArmorBlock MaXum, Point I/O, Compact I/O and Flex I/O

More information

Instructions. Modbus RTU Card (WSIQ-COM-MB)

Instructions. Modbus RTU Card (WSIQ-COM-MB) Instructions (WSIQ-COM-MB) Contents 1 Warnings... 2 2 Important User Information... 2 3 Installation... 2 4 Operation... 3 5... 4 6 Specifications... 15 Product Compatibility The is suitable for use with

More information

DNETEXT-C CAN Bus Extender, Version 3 User s Manual. Brad Harrison

DNETEXT-C CAN Bus Extender, Version 3 User s Manual. Brad Harrison DNETEXT-C CAN Bus Extender, Version 3 User s Manual Brad Harrison Although every effort has been made to insure the accuracy of this document, all information is subject to change without notice. Woodhead

More information

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017 APPLICATION CONTROL GUIDELINES IntelliROL Power Supply PN 1176718 Revision Date: March 15, 2017 Table of Contents List of Tables...3 TGW Safety Recommendation...4 Warnings and Safety Instructions...5 Introduction...6

More information

DeviceNet Physical Media

DeviceNet Physical Media DeviceNet Physical Media Round Media Round trunk cable is available in bulk spools or as pre-molded cordsets or patchcords in varying lengths. A wide variety of rugged, durable DeviceNet components is

More information

Section 1.0 Description Section 2.0. Section 3.0. Section 4.0. MCD3000 DeviceNet Gateway. Contents

Section 1.0 Description Section 2.0. Section 3.0. Section 4.0. MCD3000 DeviceNet Gateway. Contents Section 1.0 Description... 2 Section 2.0 Installation 2.1 Soft starter to gateway connection... 3 2.2 Soft starter configuration... 3 2.3 Gateway to DeviceNet connection... 3 2.4 Gateway configuration...

More information

PanelView Plus/VersaView CE Terminals and Display Modules

PanelView Plus/VersaView CE Terminals and Display Modules Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3

More information

Profinet Module. User Manual. Contents

Profinet Module. User Manual. Contents User Manual Contents 1 Important User Information... 2 2 Installation... 3 3 Connection... 4 4 Device Configuration... 5 5 Operation... 7 6 Packet Structures... 8 7 Network Design... 16 8 Specifications...

More information

DeviceNet Communications Module

DeviceNet Communications Module DeviceNet Communications Module Catalog Number 1203-GK5 or 1336-GM5 Firmware 1.xxx-3.xxx TM CONFORMANCE TESTED User Manual Important User Information Solid state equipment has operational characteristics

More information

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) Instruction Bulletin 8222-0513B Retain for future use. SPIKESHIELD Wired-In Branch Panels 8222-0513B 05/2012 Table of Contents Precautions...

More information

Enhanced DeviceNet Communications Module

Enhanced DeviceNet Communications Module Enhanced DeviceNet Communications Module Catalog Numbers: 1203-GU6 and 1336-GM6 Firmware: 2.xxx User Manual Important User Information Because of the variety of uses for the products described in this

More information

FOOD AND BEVERAGE AUTOMATION & ELECTRICAL SOLUTIONS

FOOD AND BEVERAGE AUTOMATION & ELECTRICAL SOLUTIONS FOOD AND BEVERAGE AUTOMATION & ELECTRICAL SOLUTIONS MOLEX PROVIDES SOLUTIONS FOR FOOD AND BEVERAGE AUTOMATION PLANT INFRASTRUCTURES GLOBALLY. Our team of highly-skilled experts is focused on designing

More information

ArmorStart ST Motor Controllers: Safety and Standard Versions

ArmorStart ST Motor Controllers: Safety and Standard Versions Selection Guide ArmorStart ST Motor Controllers: Safety and Standard Versions Bulletins 281E and 284E (With RRG Gland) ArmorStart ST Motor Controllers: Safety and Standard Versions What s Inside Topic

More information

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000 GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000 Instruction Manual D2-3390-2 The information in this manual is subject to change without notice. Throughout this manual, the

More information

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS SECTION 26 29 13.16 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide solid-state reduced voltage motor starters, complete and operable, in accordance with the Contract Documents.

More information

Profibus DP Expansion Board

Profibus DP Expansion Board Profibus DP Expansion Board Catalog No. EXB014A01 Installation and Operating Manual 8/03 MN1323 Table of Contents Section 1 General Information................................... 1-1 Introduction.........................................

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. MCD Profibus Module Instructions Important User Information Installation Instruction: MCD Profibus Module Order Code: 175G9001 1. Important User Information Observe all necessary safety precautions when

More information

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE INSTRUCTIONS MODBUS RTU MODULE for use with WSIQ2/WSE WorldWide Electric Corporation Phone: 1-8-88-2131 Fax: 1-8-711-1616 www.worldwideelectric.net Product Compatibility This communications module is suitable

More information

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice. Important User Information User Manual: MCD Profibus Module Order Code: 175G9001 1. Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert

More information

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data: Instruction Manual M Pump Motor Controller For file reference, please record the following data: Model No: Serial No: Installation Date: Installation Location: When ordering replacement parts for your

More information

ETHERNET/IP & PROFINET MODULE

ETHERNET/IP & PROFINET MODULE 5108 en - 2013.12 / a Ready Stop Run Start Trip Local Reset LCL RMT er w Po n Er 1 2 us k 1 /RX k 2 /RX at Lin TX St Lin TX 2 14702.A r ro 1 give e b s to i l a nu se r a u m d This o the en t ETHERNET/IP

More information

Technical Data DeviceNet Motor Control Centers (MCCs)

Technical Data DeviceNet Motor Control Centers (MCCs) Technical Data DeviceNet Motor Control Centers (MCCs) Overview......................................................................................2 DeviceNet.....................................................................................2

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481200 VGD-100 Vari-Green Drive Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

CompactBlock I/O for DeviceNet

CompactBlock I/O for DeviceNet Technical Data CompactBlock I/O for DeviceNet 1791D The 1791D CompactBlock I/O modules contain I/O circuits, a built-in power supply, and a built-in DeviceNet I/O adapter. CompactBlock I/O modules are

More information

PG Softstarter Installation Manual for 5A, 9A and 16A Controllers

PG Softstarter Installation Manual for 5A, 9A and 16A Controllers PG Softstarter Installation Manual for 5A, 9A and 16A Controllers Important User Information The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many

More information

MCD 200 MCD 500. Remove the Profibus Module using the following procedure: 1. Remove power from the module.

MCD 200 MCD 500. Remove the Profibus Module using the following procedure: 1. Remove power from the module. Installation INSTALLATION INSTRUCTIONS: MCD PROFIBUS MODULE Order Code: 175G9001 1. Installation 1. Remove control power and mains supply from the soft starter. 2. Attach the module to the soft starter

More information

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet General Information ControlKeeper 4 Installation Sheet Model# CK4-120NO- Model# CK4-277NO The ControlKeeper-4 model is shipped in one package and is configured with either a 120V or a 277V transformer.

More information

SMVector Additional I/O Module Installation and Operation Manual

SMVector Additional I/O Module Installation and Operation Manual SMVector Additional I/O Module Installation and Operation Manual About These Instructions This documentation applies to the optional Additional I/O module for the SMVector inverter and should be used in

More information

Redundancy unit CP-A RU

Redundancy unit CP-A RU 2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power

More information

Safety Light Curtains GuardShield Remote Teach

Safety Light Curtains GuardShield Remote Teach Specifications Presence Sensing Safety Devices Description The system provides a remote means of changing a fixed blanking configuration within the GuardShield safety light curtain. This keyswitch box

More information

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions HP UPS R/T3000 G2 Installation Instructions Overview The HP UPS R/T3000 G2 features a 2U rack-mount with convertible tower design and offers power protection for loads up to a maximum of 3300 VA/3000 W

More information

PowerFlex 400 Frame G and H Replacement Procedure for Gate Power Board

PowerFlex 400 Frame G and H Replacement Procedure for Gate Power Board Service Bulletin PowerFlex 400 Frame G and H Replacement Procedure for Gate Power Board Contents This publication provides instructions for replacing the gate power board for PowerFlex 400 Frame G and

More information

Control Box Setup - PRSalpha

Control Box Setup - PRSalpha 888-680-4466 ShopBotTools.com Control Box Setup - PRSalpha Copyright 2016 ShopBot Tools, Inc. page 1 Copyright 2016 ShopBot Tools, Inc. page 2 Parts List: Hooking Up a PRSalpha Gantry Tool Powering the

More information

Installation Instructions for DeviceNet E50 Limit Switches

Installation Instructions for DeviceNet E50 Limit Switches Cutler-Hammer Installation Instructions for DeviceNet E50 Limit Switches DESCRIPTION General Information Network Media - DeviceNet Protocol - DeviceNet Rel 2.0 Type - Group 2 Only Slave Device using Predefined

More information

ASTAT XB/XBm Remote Operator

ASTAT XB/XBm Remote Operator ASTAT XB/XBm Remote Operator User Manual 1 Introduction 1.1 Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery

More information

PM Series Power Meter

PM Series Power Meter PM Series Power Meter Quick Setup Guide - PMC-1000, PMC- 1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See

More information

SECTION WIRING DEVICES

SECTION WIRING DEVICES SECTION 16141 WIRING DEVICES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Copyright: December 2017 Nidec Issue: E

Copyright: December 2017 Nidec Issue: E General Information The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or incorrect installation or adjustment of the optional parameters of the equipment

More information

C-POWER AC AUTOMATIC CONTROL

C-POWER AC AUTOMATIC CONTROL Issue 1 Print 1 C-POWER AC AUTOMATIC CONTROL INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model: 93 ACMC100I A Charles Industries, Ltd. All rights reserved. Printed in the United States of America. Issue

More information

1395 Node Adapter Board Troubleshooting

1395 Node Adapter Board Troubleshooting 1395 Node Adapter Board Troubleshooting Specifications Electrical: Board power provided by Drive (+5V) Discrete Input 24V DC or 115V AC, jumper selectable Environmental: Ambient Operating Temperature Storage

More information

Pile Driver Weld Immune Sensors

Pile Driver Weld Immune Sensors DC... 190 8, 12, 18, and 30 mm Diameter... 190 3- and 4-Wire DC... 192 8, 12, 18, and 30 mm Diameter... 192 AC/DC... 194 12, 18, and 30 mm Diameter... 194 Pile Driver Sensors P+F s weld immune Pile Driver

More information

WINSTA. Full Line Catalog 2008/2009

WINSTA. Full Line Catalog 2008/2009 WINSTA Full Line Catalog 2008/2009 5 Contents FULL LINE CATALOG W4, Volume 1 Rail-Mounted Terminal Block Systems FULL LINE CATALOG W4 Rail-Mounted Terminal Blocks Volume 1 X-COM -SYSTEM Terminal Strips

More information

INSTRUCTION MANUAL IM253 R0. AquaStart COMBINATION SOFT STARTERS START-UP MANUAL

INSTRUCTION MANUAL IM253 R0. AquaStart COMBINATION SOFT STARTERS START-UP MANUAL INSTRUCTION MANUAL IM253 R0 AquaStart COMBINATION SOFT STARTERS START-UP MANUAL INDEX Power Connections...3 Basic Wiring...4 Start-Up By Voltage Ramp...5 Local / Remote Modes...6 Control and Signal Connections...6

More information

General-Purpose Photoelectric Sensor

General-Purpose Photoelectric Sensor General-Purpose Photoelectric Sensor Compact Limit Switch Style with Universal Supply FET output allows for solid state switching of AC or DC Universal AC/DC power supply Choose cable or connector types

More information

PowerFlex 755 Transition Section and Splicing Kit for Floormount Drives and CENTERLINE 2100 Motor Control Centers

PowerFlex 755 Transition Section and Splicing Kit for Floormount Drives and CENTERLINE 2100 Motor Control Centers Installation Instructions PowerFlex 755 Transition Section and Splicing Kit for Floormount Drives and CENTERLINE 2100 Motor Control Centers Topic Page Introduction, Compatibility 1 Additional Resources

More information

Elco BradControl DEVICENET ACTIVE 60mm Input/Output Interface Block May, 2008

Elco BradControl DEVICENET ACTIVE 60mm Input/Output Interface Block May, 2008 Elco BradControl DEVICENET ACTIVE 60mm Input/ Interface Block May, 2008 1. INTRODUCTION The following product numbers are covered by the information presented in this booklet: PART NUMBER BCDN-1600P-M12

More information

AC Micro Style Cordsets and Receptacles

AC Micro Style Cordsets and Receptacles AC Micro Style Cordsets and Receptacles Description Rockwell Automation/Allen-Bradley offers a wide variety of connection products for interfacing field devices to I/O, junction boxes, PLCs, etc. Connection

More information

mbc082 Bus Converter

mbc082 Bus Converter BUS CONVERTER RS485 TO 1-WIRE BUS mbc082 mbc082 Bus Converter Document. 10910, Revision - February 2007 2007 CMC Industrial Electronics Ltd. This page intentionally left blank. mbc082 Bus Converter Technical

More information

BCM2 Series Branch Circuit Monitors Quick Setup Guide

BCM2 Series Branch Circuit Monitors Quick Setup Guide BCM2 Series Branch Circuit Monitors Quick Setup Guide Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable

More information

ArmorStart LT Distributed Motor Controller

ArmorStart LT Distributed Motor Controller User Manual ArmorStart LT Distributed Motor Controller Catalog Numbers 290D, 291D, 294D Important User Information Because of the variety of uses for the products described in this publication, those responsible

More information

Emery County Senior Center Green River 06/07

Emery County Senior Center Green River 06/07 SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2. Section 1.0 Introduction 1.1 Important user information... 2 1.2 General... 2 1.3 Manual description...2 Contents Section 2.0 Specification 2.1 General technical data...3 2.2 Dimensions...3 Section 3.0

More information

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Clipsal Bus Couplers Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Instruction Bulletin Retain for future use. Clipsal Bus Couplers 63249-420-236A2 Instruction

More information

Resolver to Digital Expansion Board

Resolver to Digital Expansion Board Resolver to Digital Expansion Board Catalog No. EXB009A01 Installation and Operating Manual 6/98 MN1313 Table of Contents Section 1 General Information............................. 1-1 Introduction....................................

More information

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service. PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA

More information

Differential Liquid/Gas Pressure Transmitter

Differential Liquid/Gas Pressure Transmitter Installation Instruction Differential Liquid/Gas Pressure Transmitter Catalog Number(s) 1414-CPZ10FWFAA, 1414-IPZ10FWFAA Explosion Hazard WARNING Do not use in an explosive or hazardous environment, with

More information

Complete UL/CSA Disconnect Switch Kits

Complete UL/CSA Disconnect Switch Kits Product Selection Complete UL/CSA Disconnect Switch Kits Includes disconnect switch, operating handle with defeater mechanism and operating shaft, NFPA handle, auxiliary contacts, and padlock attachment.

More information

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier. I P MAC AD D RE S S Getting Started This is a brief document designed to quickly get you started setting up your valve manifold with an integrated Numatics G2-2 Series EtherNet/IP communication node. 1)

More information

SMC FLEX QUICK START BULLETIN 150

SMC FLEX QUICK START BULLETIN 150 QUICK START SMC FLEX BULLETIN 0 This guide provides you with the basic information required to start up your SMC Flex controller. When reading this document, look for this symbol Step x to guide you through

More information

SMVector Additional I/O Module Installation and Operation Manual

SMVector Additional I/O Module Installation and Operation Manual SMVector Additional I/O Module Installation and Operation Manual About These Instructions This documentation applies to the optional Additional I/O module for the SMVector inverter and should be used in

More information

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE IMPORTANT! Please read all the information on this sheet. SAVE THESE INSTRUCTIONS! NOTICE BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL

More information