F-3100 FLOW METER NETWORK INTERFACE Installation and Operation Guide

Size: px
Start display at page:

Download "F-3100 FLOW METER NETWORK INTERFACE Installation and Operation Guide"

Transcription

1 MODBUS FLOW AND ENERGY MEASUREMENT F-3100 FLOW METER NETWORK INTERFACE Installation and Operation Guide Belcher Road South, Largo, FL USA Tel +1 (727) Fax +1 (727)

2 F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 2

3 TABLE OF CONTENTS 1.0 INTRODUCTION PURPOSE OF THIS GUIDE TYPICAL F-3100 INSTALLATION SPECIFICATIONS DISPLAY AND USER INTERFACE NETWORK SIGNAL CONNECTIONS RS485 BAUD RATE, BIASING AND TERMINATION Baud rate and parity Entering the Program Mode Biasing and Termination MODBUS MEMORY MAP MODBUS REGISTER FORMAT AND NETWORKING INFORMATION NETWORK TROUBLESHOOTING TIPS TROUBLESHOOTING...12 F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 3

4 F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 4

5 SECTION 1: INTRODUCTION 1.1 PURPOSE OF THIS GUIDE The purpose of this guide is to provide installation and basic operating and servicing instructions for the ONICON F-3100 Flow Meter MODBUS RTU serial interface. 1.2 TYPICAL F-3100 INSTALLATION The F-3100 is an inline electromagnetic flow meter that measures liquid flow, provides a local indication of the flow rate and total, and provides this data via a MODBUS RTU RS485 serial interface to the utility or building control network. INSTALLATION IN STEEL (CONDUCTIVE) PIPE Flow Direction 1.3 SPECIFICATIONS MODBUS RTU NETWORK INTERFACE RS485 Transceiver: 2-wire, half-duplex Data format: 8 bit with 1 stop bit Parity: Even, none or odd (default: even) MAC address (device address) range: (Default: 017) Baud rate: 4800, 9600, or (Default: 9600) Termination: None Biasing: None F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 5

6 1.4 DISPLAY AND USER INTERFACE The F-3100 transmitter is equipped with a 2-line by 16-character LCD with 0.2 high characters. Three pushbutton switches located inside the transmitter enclosure are used to change the data that is displayed and to program the meter functions. To access the pushbuttons, loosen the 4 cover screws and open the cover as shown below. Momentarily press the UP (top) button to view alarm messages. Momentarily press the RIGHT (middle) button to advance to the next menu page. The ENTER (bottom) button is used in programming. In the program mode the function of each pushbutton switch changes depending on how long the switch is pressed. Briefly pressing the switch causes one action while pressing the same switch for a longer duration causes the reverse of that action. Each program mode switch function is detailed below. Up Arrow: When in the main menu, a brief press selects the previous option, and a long press selects the next option. In all other program levels, a brief press increments the number or selects the next option, and a long press decrements the number or selects the previous option. Right Arrow: When in the main menu, a brief press selects the next option, and a long press selects the previous option. In all other program levels, a brief press moves the cursor to the right or selects the previous option, and a long press moves the cursor to the left or selects the next option. Enter: When in the main menu, a brief press enters the selected sub-menu, and a long press exits the program mode. Within the sub-menus, a brief press enters or leaves the selected function. It also cancels the selected function in progress. A long press enables the EXECUTE prompt in certain functions such as reset total. A long press also accepts the change and exits the function. F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 6

7 1.5 NETWORK SIGNAL CONNECTIONS MODBUS RS485, 2-wire (half-duplex) serial output connections are made at terminals 7 and 8 as shown below. Incoming and outgoing RS485 cable shield wires should be connected together, but must not be connected to the meter. Shields Outgoing cable Incoming cable Black Red 1.6 RS485 BAUD RATE, BIASING AND TERMINATION Baud Rate and Parity Every ONICON F-3100 is individually programmed at the factory with application specific data provided by the customer during the process of ordering the meter. This normally includes the Baud rate, parity and network address settings. If the information was provided, the meter will be configured to the appropriate settings. If this information was not provided, the meter default settings are: Baud rate: 9600 Parity: Even Network Address: 017 The available Baud rate settings are 4800, 9600, and The available parity settings are odd, even or none. The network address can be from The Baud rate, parity and address settings can be changed via the user interface/display on the front of the meter. The information below details the process of entering the program mode and changing the address, baud rate and parity settings. i Entering The Program Mode: IMPORTANT NOTE The meter will automatically exit the program after 60 seconds of no activity. Briefly press enter. The display will change to keycode L2:00000 with the cursor flashing under the leftmost digit. Using the up arrow key to increment the digits and the right arrow key to move the cursor, enter a code of Briefly press enter. The MAIN MENU page will appear with sub-menu 1 Sensor shown as the selected option. F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 7

8 Changing Address, Baud Rate & Parity STEP ACTION COMMENT 0 Obtain the baud rate, parity and device address settings from the network administrator. 1 The MAIN MENU page shows sub-menu 1-Sensor. Briefly press the right arrow 6 times to advance to sub-menu 7-Communication. 2 Briefly press the enter key to enter the 7-Communication sub-menu. 3 Briefly press the right arrow once to advance to the address function. 4 Briefly press the enter key once to enter the address function. 5 Use the up arrow key to change the value of the leftmost digit. Once the correct value is indicated, use the right arrow to move the cursor to the right. Repeat the process as necessary until the correct address is entered. 6 Briefly press enter once to exit the address function. To exit the program mode at this point, long press enter twice. 7 Briefly press the right arrow once to advance to the Baud rate function. 8 Briefly press enter once to enter the Baud rate function. 9 Use the up arrow to change the Baud rate to the correct setting. 10 Briefly press enter once to exit the Baud rate function. To exit the program mode at this point, long press enter twice. 11 Briefly press the right arrow 3 times to advance to the Parity funciton. 12 Briefly press enter once to enter the parity function. 13 Use the up arrow to change the parity to the correct setting. 14 Briefly press enter once to exit the parity function. 15 Long press enter once to return to the MAIN MENU. 16 Long press enter once to exit the program mode. The display function shown will be IF2 prot=. The displayed function shown will be Address=. The flashing cursor will move from the A in adress to the leftmost digit of the address number. The valid range for the address is from The flashing cursor will move from its current position to immediately below the A in address. The displayed function shown will be RS485 bps: The flashing cursor will move from the R in RS485 to the position right of the colon. The flashing cursor will move from the position right of the colon to immediately below the R in RS485. The displayed function shown will be Parity=. The flashing cursor will move from the P in Parity to the position right of the colon. The flashing cursor will move from the position right of the colon to immediately below the P in Parity. Sub-menu 7-Communication will be selected. F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 8

9 1.6.2 Biasing and Termination The ONICON F-3100 does not provide biasing voltage to the RS485 network. An external 120Ω resistor (not provided) should be connected across the terminals as shown below when the meter is installed at the end of the line Ohm Incoming cable Leave shield unterminated Black Red F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 9

10 SECTION 2.0: MODBUS MEMORY MAP ONICON F-3100 Inline Electromagnetic Flow Meters provide flow rate data, totalized flow data, and operating status data via the MODBUS RTU RS485 serial communications interface. MODBUS data is available in the same engineering units shown on the meter s display. 2.1 MODBUS REGISTER FORMAT AND NETWORKING INFORMATION All registers are 16 bit MODBUS Holding Registers. Only one MODBUS function code is supported. It is function code 3, reading holding registers. Floating point data conforms to IEEE754 format. Long integer (32-bit) data is formatted with the high order word (MSW) on the even addrss and the low order word (LSW) on the odd address. Register Address Description Register Type Comment 001 Flow rate as a % of full scale Floating Point (1 of 2) 002 Flow rate as a % of full scale Floating Point (2 of 2) 003 Current flow rate Floating Point (1 of 2) 004 Current flow rate Floating Point (2 of 2) 005 Positive flow total Scaled Long Integer (1 of 2) Register values must be 006 Positive flow total Scaled Long Integer (2 of 2) scaled according to the number of decimal points 007 Partial positive flow total Scaled Long Integer (1 of 2) shown on the flow meter 008 Partial positive flow total Scaled Long Integer (2 of 2) display. 009 Negative flow total Scaled Long Integer (1 of 2) Example: Displayed value Negative flow total Scaled Long Integer (2 of 2) Register value Partial negative flow total Scaled Long Integer (1 of 2) Scale multiplier Partial negative flow total Scaled Long Integer (2 of 2) 013 Run time clock in seconds Long Integer (1 of 2) 014 Run time clock in seconds Long Integer (2 of 2) F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 10

11 Flow Meter Operating Status Register (Address 35) Bit# Description Comment 000 Coil pulse rate too fast for coil diameter Check for programming error for coil diamter and/or sample rate. 001 Maximum flow alarm is active 002 Minimum flow alarm is active 003 Flow rate exceeds full scale value Change full scale setting 004 Not used 005 Noisy or open elctrode signal Check wiring 006 Empty pipe 007 Coil open or disconnected Check wiring 008 Alternate flow range active 009 Flow rate below low flow cut-off Check low flow cut-off setting 010 Flow in the negative direction 011 Not used 012 Not used 013 Not used 014 Calibration cycle in progress 015 Flow simulation mode active F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 11

12 3.1 TROUBLESHOOTING SECTION 3: NETWORK TROUBLESHOOTING TIPS REPORTED PROBLEM Device will not communicate with the network controller. POSSIBLE SOLUTIONS A unique address is required for each device on the network. Duplicate addresses will cause some or all of the devices on the network to quit working. (See section of this manual for details.) The RS485 network cable connections are polarity sensitive and must be connected the same way on every device (i.e. + to + and - to -). (See section 1.5 of this manual for details.) The Baud rate setting must match the network Baud rate. (See section of this manual for details.) Shield drain connections should be daisy chained in the same manner as the signal cables for RS485. The shield drain wire should be left unterminated at the end of the cable and connected to earth only at the network master controller. Shield wires must not be connected to the the F The maximum number of devices allowed on a RS485 network segment without a repeater is 32. Adding more than 32 devices to a single segment may reduce the transceiver output voltage to a level that is too low to be distinguished from background noise on the cable. RS485 cable impedance should be matched to a termination resistor at the end of the cable. This resistor should only be used if the meter is the last device on the network cable. (See section of this manual for details.) Network communications are disrupted when the device is connected. The RS485 network cable connections are polarity sensitive and must be connected the same way on every device (i.e. + to + and - to -). (See section 1.5 of this manual for details.) A unique address is required for each device on the network. Duplicate addresses will cause some or all of the devices on the network to quit working. (See section of this manual for details.) Shield drain connections should be daisy chained in the same manner as the signal cables for RS485. The shield drain wire should be left unterminated at the end of the cable and connected to earth only at the network master controller. Shield wires must not be connected to the F F-3100-MOD Flow Meter Network Interface Installation Guide 09/ Page 12

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide MODBUS D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 www.onicon.com sales@onicon.com 03-18 0657-9

More information

System-10 BTU Meter MODBUS RTU Network Interface Installation Guide

System-10 BTU Meter MODBUS RTU Network Interface Installation Guide MODBUS ONICON Flow and Energy Measurement System-10 BTU Meter MODBUS RTU Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 0653-13

More information

System-10 BTU Meter BACnet Network Interface Installation Guide

System-10 BTU Meter BACnet Network Interface Installation Guide BACnet ONICON Flow and Energy Measurement System-10 BTU Meter BACnet Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 0652-12

More information

System-10 BTU Meter BACnet Network Interface Installation Guide

System-10 BTU Meter BACnet Network Interface Installation Guide BACnet System-10 BTU Meter BACnet Network Interface Installation Guide 0652-3 1500 North Belcher Road, Clearwater, FL 33765 Tel (727) 447-6140 Fax (727) 442-5699 www.onicon.com sales@onicon.com 04-12 System-10-BAC

More information

Johnson Controls Metasys N2

Johnson Controls Metasys N2 Johnson Controls Metasys N2 FLOW AND ENERGY MEASUREMENT System-10 BTU Meter Johnson Controls Metasys N2 Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140

More information

D-100 FLOW DISPLAY BACnet Network Interface Installation Guide

D-100 FLOW DISPLAY BACnet Network Interface Installation Guide BACnet D-100 FLOW DISPLAY BACnet Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 0635-11 / 18341 www.onicon.com sales@onicon.com

More information

D-100 FLOW DISPLAY Siemens P1-FLN Network Interface Installation Guide

D-100 FLOW DISPLAY Siemens P1-FLN Network Interface Installation Guide Siemens P1-FLN D-100 FLOW DISPLAY Siemens P1-FLN Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 0660-5 / 18343 www.onicon.com

More information

D-100 Flow Display Dual Network Interface Installation Guide. (BACnet & MODBUS)

D-100 Flow Display Dual Network Interface Installation Guide. (BACnet & MODBUS) D-100 Flow Display Dual Network Interface Installation Guide (BACnet & MODBUS) 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 1015-2 / 35094 www.onicon.com sales@onicon.com

More information

Enercept H8035/H8036 Modbus Energy Meter Networked kw/kwh Transducers

Enercept H8035/H8036 Modbus Energy Meter Networked kw/kwh Transducers POWER MONITORING INSTALLATION GUIDE Enercept H8035/H8036 Modbus Energy Meter Networked kw/kwh Transducers US Patent No. 6,373,238 Installer's Specifications Input Voltage 208 to 480 VAC Number of Phases

More information

High Voltage DC Meter

High Voltage DC Meter High Voltage DC Meter Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,

More information

HIGH-VOLTAGE DC METER

HIGH-VOLTAGE DC METER HIGH-VOLTAGE DC METER Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL INTRINSICALLY SAFE DUPLEXER INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision:

More information

installation Operation ADDRESS product diagram H8030/8031 INSTALLATION GUIDE

installation Operation ADDRESS product diagram H8030/8031 INSTALLATION GUIDE POWER MONITORING INSTALLATION GUIDE H8030/8031 H8030/8031 Modbus Energy Meter Networked kw/kwh Transducer Product Identification Model Max Amps CT Size Enhanced Data Stream Meters H8030-0100- 100 H8030-0300-

More information

SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703

SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703 SC1000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Operating Program Revision: 8 Revision Date: 5-16-11 STATION

More information

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2. Section 1.0 Introduction 1.1 Important user information... 2 1.2 General... 2 1.3 Manual description...2 Contents Section 2.0 Specification 2.1 General technical data...3 2.2 Dimensions...3 Section 3.0

More information

IFC 100 Supplementary instructions

IFC 100 Supplementary instructions IFC 100 Supplementary instructions Signal converter for electromagnetic flowmeters Description of Modbus interface Electronic Revision: ER 3.0.xx Modbus version: 1.0.xx KROHNE CONTENTS IFC 100 1 Important

More information

MSOC Communication Commonality with DPU/TPU/GPU 2000R Protective Relays

MSOC Communication Commonality with DPU/TPU/GPU 2000R Protective Relays ABB Application Note MSOC AN-64A-00 Substation Automation and Protection Division MSOC Communication Commonality with DPU/TPU/GPU 2000R Protective Relays Introduction There seems to be some confusion with

More information

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications LAUREL ELECTRONICS, INC. Laureate RTD Temperature Panel Meter / Controller Features Factory calibrated for 100Ω platinum, 10Ω copper & 120Ω nickel RTDs 2, 3 or 4-wire connection with lead resistance compensation

More information

Wireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

Wireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website: Wireless Transducer INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 2 Revision

More information

Flow Measurement Applications

Flow Measurement Applications Flow Measurement Applications ONICON has been a leading provider of the flow and energy measurement solutions required by the HVAC industry for the past 30 years. As the need for accurate and reliable

More information

MODBUS MESSAGE PROTOCOL FOR MODEL FT2 THERMAL MASS FLOWMETER & TEMPERATURE TRANSMITTER

MODBUS MESSAGE PROTOCOL FOR MODEL FT2 THERMAL MASS FLOWMETER & TEMPERATURE TRANSMITTER MODBUS MESSAGE PROTOCOL FOR MODEL FT2 THERMAL MASS FLOWMETER & TEMPERATURE TRANSMITTER Fox Thermal Instruments, Inc 399 Reservation Road Marina, CA 93933 (831) 384-4300 Fax: (831) 384-4312 101479 Revision

More information

H704-42(H)(E), H704-42/1(H)(E)

H704-42(H)(E), H704-42/1(H)(E) POWER MONITORING INSTALLATION GUIDE H704-42(H)(E), H704-42/1(H)(E) Branch Current Monitor DANGER NOTICE Installer's Specifications General: Operating Temp. Range 0 to 60 C (32 to 140 F) (

More information

Carbon Monoxide Sensor - ModBus

Carbon Monoxide Sensor - ModBus Introduction The CO Sensor uses an electrochemical sensor to monitor CO level in a range of 0 to 500 ppm and communicates via an RS-485 network configured for ModBus protocol. Before Installation Read

More information

1. Introduction. 2. Installation MODBUS INTERFACE

1. Introduction. 2. Installation MODBUS INTERFACE 5551.C 8473.C MODBUS INTERFACE PIM-MB-1 Modbus Interface 1. Introduction AuCom soft starters can be controlled and monitored across an RS485 serial communication network using the Modbus RTU and AP ASCII

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

F-4600 FLOW METER With Optional LCD Display Installation and Operation Guide

F-4600 FLOW METER With Optional LCD Display Installation and Operation Guide FLOW AND ENERGY MEASUREMENT F-4600 FLOW METER With Optional LCD Display Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 2020-1

More information

GFC111-MB. Flow Computer With RS485 MODBUS FEATURES 1. DESCRIPTION APPLICATIONS

GFC111-MB. Flow Computer With RS485 MODBUS FEATURES 1. DESCRIPTION APPLICATIONS Flow Computer With RS485 MODBUS FEATURES l RS485 MODBUS RTU, 1/8 LOAD l PROGRAMMABLE ADDRESS, BAUD RATE, PARITY AND STOP BITS l UNIVERSAL INPUT, 5 khz, CAN POWER THE SENSOR l NO NEED OF AMPLIFIERS OR LINEARIZERS

More information

TC Type Range Conformity Error. J -210 C to +760 C (-347 F to F) ±0.09 C (±0.16 F) K -244 C to C (-408 F to F) ±0.1 C (±0.

TC Type Range Conformity Error. J -210 C to +760 C (-347 F to F) ±0.09 C (±0.16 F) K -244 C to C (-408 F to F) ±0.1 C (±0. LAUREL ELECTRONICS, INC. Laureate Thermocouple Panel Meter / Controller Features Factory calibrated for thermocouple types J, K, T, E, N, R, S Entire range of each thermocouple in one scale Highly accurate

More information

Master-Touch and ValuMass. Modbus Communications. INSTRUCTION MANUAL (Rev. 3.1)

Master-Touch and ValuMass. Modbus Communications. INSTRUCTION MANUAL (Rev. 3.1) Master-Touch and ValuMass Modbus Communications Master-Touch and ValuMass flowmeters are shipped with the RS232 communications protocol as the factory default. Prior to connecting a flowmeter to a RS485

More information

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website: SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 12 Revision Date: 8-27-14

More information

Serial Communication Converters & Adapters Instruction Manual

Serial Communication Converters & Adapters Instruction Manual Serial Communication Converters & Adapters Instruction Manual RS-232 to RS-422/485 Converter Isolated RS-232 to RS-422/485 Converter USB to RS-232 Converter USB to RS-422/485 Converter Isolated USB to

More information

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016 Interface Definition RISH EM 2340/1320/30/40 1 2-60-006-00-00494_Rev. D - 8/2016 2 Section DIGITAL MULTIFUNCTION INSTRUMENT Contents 1. Introduction Programmable Multi-function Energy Meter Installation

More information

Trident and Trident X2 Digital Process and Temperature Panel Meter

Trident and Trident X2 Digital Process and Temperature Panel Meter Sign In New User ISO 9001:2008 Certified Quality System Home Products Online Tools Videos Downloads About Us Store Contact Policies Trident and Trident X2 Digital Process and Temperature Panel Meter Products

More information

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature

More information

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description LAUREL ELECTRONICS, INC. Laureate Digital Panel Meter for Process and Ratiometric Signals Features Reads process signals from ±200 mv to ±600V or ±2 ma to ±5A full scale Ratiometric mode for bridges and

More information

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703 SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Operating Program Revision: 10 Revision Date: 1-9-12 STATION

More information

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions Specialists in Liquid Level Indication MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions Section: M500 Bulletin: M500.31 Date: 05-17-16 Supersedes: 09-30-11 1. INTRODUCTION

More information

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points) Remote I/O R1M Series THERMOCOUPLE & DC INPUT MODULE (16 points) MODEL MODEL & SUFFIX CODE SELECTION R1MGH2T MODEL Modbus protocol I/O TYPE GH2 : Thermocouple or DC input, 16 points FIELD TERMINAL TYPE

More information

Instruction Manual February smartlinx interface module MODBUS RTU

Instruction Manual February smartlinx interface module MODBUS RTU Instruction Manual February 2004 smartlinx interface module MODBUS RTU Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product

More information

MODBUS MANUAL For the AccUView UV Transmission Monitor

MODBUS MANUAL For the AccUView UV Transmission Monitor MODBUS MANUAL For the AccUView UV Transmission Monitor HF scientific, inc. 3170 Metro Parkway Ft. Myers, FL 33916 Phone: 239-337-2116 Fax: 239-332-7643 E-Mail: info@hfscientific.com Website: www.hfscientific.com

More information

Integral Electronics with Local Menu System

Integral Electronics with Local Menu System Integral Electronics with Local Menu System THERMAL INSTRUMENT COMPANY Trevose, PA 215-355-8400 New Menu Features & Benefits Available with either Hart Communication or Modbus output Visibility to current

More information

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE INSTRUCTIONS MODBUS RTU MODULE for use with WSIQ2/WSE WorldWide Electric Corporation Phone: 1-8-88-2131 Fax: 1-8-711-1616 www.worldwideelectric.net Product Compatibility This communications module is suitable

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

Getting started with your DGH module:

Getting started with your DGH module: Getting started with your DGH module: This document contains step-by-step instructions to quickly connect and communicate with your new DGH modules. For most applications, new modules require a one-time

More information

PS-IN202 Weighing Indicator User Manual

PS-IN202 Weighing Indicator User Manual PS-IN202 Weighing Indicator User Manual Version 2015.05 Contents FRONT AND REAR VIEW OF THE INDICATOR CHAPTER 1 CONNECTIONS 1.1 WHAT'S IN THE BOX 1.2 CONNECTING TO THE WEIGH PLATFORM 1.3 CONNECTION TO

More information

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS POWER MONITORING ENERCEPT Networked Power Transducer (Modbus RTU) DANGER US Patent No. 6,373,238 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in

More information

205 CPU NETWORK ADAPTER F2-UNICON

205 CPU NETWORK ADAPTER F2-UNICON 205 CPU NEWORK ADAPER F2-UNICON Network Adapter he F2-UNICON Network Adapter is used to place Automationdirect.com DL205 CPUs (except D2-230 and D2-250) on a RS-422 or RS-485 multi-drop network. he Network

More information

MincoSoft CT224 Software

MincoSoft CT224 Software MincoSoft CT224 Software Tel: 763.571.3121 Fax: 763.571.0927 www.minco.com This page left blank intentionally. Minco Tel: 763.571.3121 Fax: 763.571.0927 www.minco.com 2 Table Of Contents 1. System Requirements

More information

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50 MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287 Installation and Operations Manual 00-02-0651 09-01-09 Section 50 In order to consistently bring you the highest quality, full featured products,

More information

MANUAL INSTALLATION. Multi-Variable Monitor. MVM Series. Issue Date: 02/07/ Price Industries Limited. All rights reserved.

MANUAL INSTALLATION. Multi-Variable Monitor. MVM Series. Issue Date: 02/07/ Price Industries Limited. All rights reserved. MANUAL INSTALLATION Multi-Variable Monitor MVM Series Issue Date: 02/07/18 2018 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview General...1 MVM Specifications...1 Included

More information

ASTAT XB/XBm Remote Operator

ASTAT XB/XBm Remote Operator ASTAT XB/XBm Remote Operator User Manual 1 Introduction 1.1 Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery

More information

WARNING. TTDJ Series Fully-Configurable Fault Annunciator Installation and Operations Manual

WARNING. TTDJ Series Fully-Configurable Fault Annunciator Installation and Operations Manual TTDJ Series Fully-Configurable Fault Annunciator Installation and Operations Manual TTDJ-99062N Revised 04-04 Section 50 (00-02-0412) Please read the following information before installing. This installation

More information

MODBUS Message Protocol MODEL FT3

MODBUS Message Protocol MODEL FT3 MODBUS Message Protocol FOR MODEL FT3 THERMAL MASS FLOWMETER & TEMPERATURE TRANSMITTER Fox Thermal Instruments, Inc. 399 Reservation Road Marina, CA 93933 (831) 384-4300 Fax: (831) 337-5786 104985, Revision

More information

DKM-407 DIN RAIL TYPE NETWORK ANALYZER

DKM-407 DIN RAIL TYPE NETWORK ANALYZER DKM-407 User Manual DKM-407 DIN RAIL TYPE NETWORK ANALYZER DESCRIPTION The DKM-407 is a DIN rail mounted precision and low cost unit allowing measurement and remote monitoring of AC parameters of a distribution

More information

Installation and Programming Manual

Installation and Programming Manual PMN Manual PMN Installation and Programming Manual This Manual describes the PMN PowerLogic Modbus Plus Network module, its uses and set up. Effective: 12 August, 1999 Niobrara Research & Development Corporation

More information

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

MOD-IO9 Modbus Input / Output Modules, Wall Mounted Product sheet MOD3.9 Type MOD-IO9 MOD-IO9 Modbus Input / Output Modules, Wall Mounted MOD-IO9 and MOD-IO9-AI have been designed to be a compact wall mounted Modbus RTU input and output module. The module

More information

FASTMARK 4600 PLUS CONTROL PANEL OPERATION. Front Panel

FASTMARK 4600 PLUS CONTROL PANEL OPERATION. Front Panel FASTMARK 4600 PLUS CONTROL PANEL OPERATION Front Panel The front panel includes - LCD display - 3 LED status indicators (READY, MEDIA and RIBBON) - 3 control buttons (FEED, PAUSE and CANCEL) LCD display

More information

MOD-RI Room Interface Modules with Modbus

MOD-RI Room Interface Modules with Modbus Product sheet MOD3.00 Type MOD-RI MOD-RI Room Interface Modules with Modbus The MOD-RI are room interface modules designed to provide room control interface for the building management systems. The MOD-RI

More information

1.Eastron SDM230Modbus Smart Meter Modbus Protocol Implementation V1.2

1.Eastron SDM230Modbus Smart Meter Modbus Protocol Implementation V1.2 1.Eastron SDM230Modbus Smart Meter Modbus Protocol Implementation V1.2 1.1 Modbus Protocol Overview This section provides basic information for interfacing the Eastron Smart meter to a Modbus Protocol

More information

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 4-20 ma & Relay Output Features 4-20 ma, ± 10 V, TC & RTD Inputs 12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 24 VDC @ 200 ma Transmitter Power Supply Options Type

More information

CDD ModBus Carbon Dioxide Detector

CDD ModBus Carbon Dioxide Detector Mounting The room type sensor installs directly on a standard electrical box and should be mounted five feet from the floor of the area to be controlled. Do not mount the sensor near doors, opening windows,

More information

805HP. Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website:

805HP. Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website: 805HP Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website: www.anyload.com Email: info@anyload.com TABLE OF CONTENTS 1. Introduction and Product Features 3 2.

More information

COUNTIS Ci Notice d utilisation GB Operating instructions Bedienungsanleitung NL Gebruiksaanwijzing

COUNTIS Ci Notice d utilisation GB Operating instructions Bedienungsanleitung NL Gebruiksaanwijzing COUNTIS Ci I F Notice d utilisation GB Operating instructions D Bedienungsanleitung NL Gebruiksaanwijzing Istruzioni per l uso SP Instrucciones de servicio P Manual de instruções PRELIMINARY OPERATIONS

More information

Ocean Controls KTA-224 Modbus IO Module

Ocean Controls KTA-224 Modbus IO Module Ocean Controls Ocean Controls 8 Relay outputs (5A, 250VAC contacts) 4 Opto-Isolated Inputs with counters 3 Analog Inputs (10 bit) jumperselectable for 0-5V or 0-20mA 4 Input Counters RS485 or USB (virtual

More information

INSTALLATION INSTRUCTIONS Protocol Energy Meter EM-RS485 and Current/Voltage Transducers DANGER WARNING WARRANTY DISCLAIMER

INSTALLATION INSTRUCTIONS Protocol Energy Meter EM-RS485 and Current/Voltage Transducers DANGER WARNING WARRANTY DISCLAIMER NEED HEL? Call 1-866-660-8864 INSTALLATION INSTRUCTIONS rotocol Energy Meter and Current/Voltage Transducers The is a three channel meter, capable of monitoring single-phase, two-phase and three-phase

More information

RS-FX-N01 wind transmitter user's Guide (485type)

RS-FX-N01 wind transmitter user's Guide (485type) RS-FX-N01 wind transmitter user's Guide (485type) Issue:. V1. 0 1 2 Context 1. Introduction...4 2. Installation instructions... 5 3. Configure the software installation and use...7 4. Communication Protocol...

More information

805HP. Handheld Digital Weight Indicator User s Manual (v1703) Anyload Transducer Co. Ltd Website:

805HP. Handheld Digital Weight Indicator User s Manual (v1703) Anyload Transducer Co. Ltd Website: 805HP Handheld Digital Weight Indicator User s Manual (v1703) Anyload Transducer Co. Ltd Website: www.anyload.com Email: info@anyload.com TABLE OF CONTENTS 1. Introductions and Features 2 2. Safety Recommendations

More information

DECK All-In-One Enclosure. Quick Installation Guide for Field Installers

DECK All-In-One Enclosure. Quick Installation Guide for Field Installers DECK All-In-One Enclosure Quick Installation Guide for Field Installers 1 Contents Legal Statement... 2 Preliminary Considerations... 2 Required Installation Tools and Materials... 2 Networking Information...

More information

KTA-250 Anemometer Alarm Card

KTA-250 Anemometer Alarm Card Connects to Davis Instruments DS7911 Anemometer Monitor both the wind speed and direction Interface to PLCs using the Modbus protocol Communicate via RS232 or 2-wire RS485 Interface to PLCs/Instruments

More information

IPM650 Intelligent Panel-Mount Display

IPM650 Intelligent Panel-Mount Display Quick Start Guide IPM650 Intelligent Panel-Mount Display Sensor Solutions Source Load Torque Pressure Multi Component Calibration Instruments Software www.futek.com Getting Help TECHNICAL SUPPORT For more

More information

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00 g MX200 SERIES Modbus Card 50P-1105 GE Zenith Controls 50R-2200B 12/00 Operation and Maintenance Manual Table of Contents Overview...01 Page LED Indicator...02 Installation...03 Installing the Network

More information

805HP. Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website:

805HP. Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website: 805HP Handheld Digital Weight Indicator Operations Manual (V1612) Anyload Transducer Co. Ltd Website: www.anyload.com Email: info@anyload.com TABLE OF CONTENTS 1. Introduction and Product Features 3 2.

More information

USER GUIDE PEL 8K / PEL 8K-M

USER GUIDE PEL 8K / PEL 8K-M V2.0.0 (24.10.2014) 1 (7) COMMISSIONING Mounting - The transmitter should be installed above the measuring point to avoid condensation problems. - The duct overpressure is detected by connecting the measuring

More information

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat Features Modern Appearance Stylish rotary dial and buttons Large LCD with backlight Support Modbus RTU protocol Support standalone operation

More information

SYSTEM-40 BTU MEASUREMENT SYSTEM Installation and Operation Guide

SYSTEM-40 BTU MEASUREMENT SYSTEM Installation and Operation Guide SYSTEM-40 BTU MEASUREMENT SYSTEM Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 2018-3 / 35870 www.onicon.com sales@onicon.com

More information

PD765 TRIDENT. Trident Series Process & Temperature Meters.

PD765 TRIDENT. Trident Series Process & Temperature Meters. PD765 Trident Series Process & Temperature Meters TRIDENT PROCESS & Temp 4-20 ma, ± 10 V, TC & RTD Inputs 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) Type 4X, NEMA 4X, IP65 Front 1/8 DIN Shallow

More information

Javelin D Model PD644 Instruction Manual

Javelin D Model PD644 Instruction Manual Javelin D Model PD644 Measures DC Voltage up to 300 VDC 4 Digit Display, 0.56" (14 mm) High, Red LEDs Maximum/Minimum Display NEMA 4X, IP65 Front 4-20 ma Transmitter Universal Power Supply 85-265 VAC 12-36

More information

Transmitters RHT-WM-485-LCD, RHT-DM-485-LCD and RHT-P LCD

Transmitters RHT-WM-485-LCD, RHT-DM-485-LCD and RHT-P LCD Transmitters RHT-WM-485-LCD, RHT-DM-485-LCD and RHT-P10-485-LCD TEMPERATURE AND HUMIDITY TRANSMITTER INSTRUCTIONS MANUAL V1.0x D 1 INTRODUCTION The RHT-WM-485-LCD, RHT-DM-485-LCD and RHT-P10-485-LCD transmitters

More information

SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic

SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic MAN0842-02 DIM610 PAGE 1 of 6 SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic 1 SPECIFICATIONS Number of Channels Input Ranges DIM610 12 PLC Update Rate 12/24 VDC Terminal Type DIM610

More information

RS485 MODBUS Module 6RO

RS485 MODBUS Module 6RO Version 2.0 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

PD765 TRIDENT. Trident Series Process & Temperature Meters.

PD765 TRIDENT. Trident Series Process & Temperature Meters. PD765 Trident Series Process & Temperature Meters TRIDENT PROCESS & Temp 4-20 ma, ± 10 V, TC & RTD Inputs 4-Digit Display, 0.56" (14.2 mm) or 1.20" (30.5 mm) Linear or Square Root with Low-Flow Cutoff

More information

P3-SCM. General Specifications

P3-SCM. General Specifications General Specifications Module Type Modules per Base Modules per Group I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to

More information

Control Techniques Variable-Speed Drive (VSD) Interface to E2 v and Above

Control Techniques Variable-Speed Drive (VSD) Interface to E2 v and Above TECHNICAL BULLETIN Part #: 026-4122 Revision 0 Date: 2/5/2007 Control Techniques Variable-Speed Drive (VSD) Interface to E2 v. 2.40 and Overview Beginning with version 2.40, the E2 RX, BX, and CX series

More information

USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX

USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX DOCUMENT NO: TDC 0550 MANUAL - 2 1.0) INTRODUCTION. PAGE 2 1.1) ABOUT THIS MANUAL. PAGE 2 1.2) INTRODUCTION. PAGE

More information

RS-FS-N01 Wind speed transmitter user's Guide (485type)

RS-FS-N01 Wind speed transmitter user's Guide (485type) RS-FS-N01 Wind speed transmitter user's Guide (485type) Issue: V1.0 1 2 Context 1. Introduction... 4 2. Installation instructions...5 3. Configure the software installation and use... 6 4. Communication

More information

T2314, T2414. Instruction Manual

T2314, T2414. Instruction Manual Atmospheric pressure transmitter T2314, T2414 with RS232 / RS485 serial output Instruction Manual Instruction Manual Device type Pressure Output Galvanic isolated output T2314 RS232 - T2414 RS485 Device

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate RTD Temperature Panel Meter / Controller Features Factory calibrated for 100Ω platinum, 10Ω copper & 120Ω nickel RTDs 2, 3 or 4-wire connection with lead resistance compensation

More information

Modbus communication module for TCX2: AEX-MOD

Modbus communication module for TCX2: AEX-MOD Modbus communication module for TCX2: Communication Specification Features S485 2-wire MODBUS standard in accordance with EIA/TIA 485. Slave type of communication Supports up to 127 nodes on one network

More information

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for Version 1.0 5.02.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

EGW1-IA3-MB User s Manual

EGW1-IA3-MB User s Manual www.exemys.com Rev. 0 1 Products are in constant evolution to satisfy our customer needs. For that reason, the specifications and capabilities are subject to change without prior notice. Updated information

More information

GFC114. Low Power Flow Computer FEATURES

GFC114. Low Power Flow Computer FEATURES Low Power Flow Computer FEATURES l UNIVERSAL INPUT, 5 khz, CAN POWER THE l SIMPLIFIED MENUS AND PROGRAMMING l NO NEED OF AMPLIFIERS OR LINEARIZERS l SEVEN DIGIT RATE WITH PROGRAMMABLE DECIMAL PLACES l

More information

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER SERIES CMT CARBON MONOXIDE GAS TRANSMITTER INSTALLATION OPERATION AND MAINTENANCE MANUAL DWYER INTRUMENTS, INC. PO BOX 373, MICHIGAN CITY, IN. 46360 USA PHONE: 800-872-9141 FAX: 219-872-9057 Web: www.dwyer-inst.com

More information

DUCM Hardware. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA

DUCM Hardware. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA DUCM Hardware Manual DUCM Hardware Installation Manual This manual covers the DUCM hardware features and installation procedures. Effective: May 29, 2015 Niobrara Research & Development Corporation P.O.

More information

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES Load Cell and Weighing Indicators A Precision Measurement Instrument with Outstanding Features TRACKER 240 SERIES INDICATORS Ratiometric Measurement Tare and Auto Transducer Excitation

More information

INSTALLATION INSTRUCTIONS Protocol Energy Meter EM-RS485 and Current/Voltage Transducers DANGER WARNING

INSTALLATION INSTRUCTIONS Protocol Energy Meter EM-RS485 and Current/Voltage Transducers DANGER WARNING NEED HEL? Call 1-866-660-8864 INSTALLATION INSTRUCTIONS rotocol Energy Meter and Current/Voltage Transducers The is a three channel meter, capable of monitoring single-phase, two-phase and three-phase

More information

RS485 MODBUS Module 8AO

RS485 MODBUS Module 8AO Version 1.3 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice. MCD Modbus Module Instructions Important User Information INSTALLATION INSTRUCTIONS: MCD MODBUS MODULE Order Code: 175G9000 1. Important User Information Observe all necessary safety precautions when controlling

More information

Iso DIN. User Manual. 1 channel Earth Fault Monitoring

Iso DIN. User Manual. 1 channel Earth Fault Monitoring Page 1 of 5 2017 03 20 User Manual Iso DIN Iso DIN User Manual 1 channel Earth Fault Monitoring Megacon AB Ranhammarsvägen 20 S 168 67 Bromma Sweden Tel: 08 402 42 50 sales@megacon.se www.megacon.se eee

More information

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions. Series AVUL Air Velocity Transmitter Specifications - Installation and Operating Instructions Bulletin P-AVUL 3-49/64 [95.71] 2-43/64 [67.92] 1/2 NPS 3-3/16 [80.81] 1-19/32 [40.59] 31/32 24.58 3-33/64

More information