MiCOM P721 & P723. High Impedance Differential Protection. P72x/EN TDS/B21. Technical Data Sheet. This document does not replace the Technical Manual

Size: px
Start display at page:

Download "MiCOM P721 & P723. High Impedance Differential Protection. P72x/EN TDS/B21. Technical Data Sheet. This document does not replace the Technical Manual"

Transcription

1 MiCOM P721 & P723 High Impedance Differential Protection P72x/EN TDS/B21 Technical Data Sheet This document does not replace the Technical Manual

2 Note: The technical manual for this device gives instructions for its installation, commissioning, and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate Schneider Electric technical sales office and request the necessary information. Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric including settlements of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the technical manual. This device MUST NOT be modified. If any modification is made without the express permission of Schneider Electric, it will invalidate the warranty, and may render the product unsafe. The Schneider Electric logo and any alternative version thereof are trademarks and service marks of Schneider Electric. MiCOM is a registered trademark of Schneider Electric. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. This manual is provided for informational use only and is subject to change without notice. 2012, Schneider Electric. All rights reserved.

3 Protection Relays 01 MiCOM P721 & P723 Numerical High Impedance Differential Relay The new P72x high impedance differential protection series provides an independent and simple high impedance differential protection solution for generator, reactor, motor and busbar applications where fast clearance of faults is required. Combined with the P79x, a standalone metrosil and resistor unit, it provides simplified scheme engineering for single or three-phase differential applications. Customer Benefits Simple scheme engineering Reliable algorithm Supervision functions included in the same protection box As well as offering the same application benefits as traditional high impedance electromechanical protection schemes, it combines the added benefits of numerical technology to provide advanced communications, event records, fault records, disturbance records and ancillary protection features.

4 Protection Relays MiCOM P72x 02 APPLICATION When circulating current protection schemes are subjected to through faults, the sudden and often asymmetrical growth in the system current can cause the line current transformers to reach saturation. Under these conditions the variation in current transformer magnetising characteristics can cause large ratio errors with a consequent circuit imbalance and maloperation of the protective relays. To ensure stability, it is common practice to employ high impedance relays set to operate at a slightly higher voltage than that developed in the worst theoretical case of this condition for a given through fault current. On a balanced earth fault system for example, this is when one current transformer of a group is saturated whilst the others remain unaffected. The saturated transformer presents a low impedance path in parallel with the relay and limits the voltage applied. For internal faults this limitation does not exist and voltages of twice the setting are easily reached resulting in fast operation of the differential relay. The P72x relay together with the P79x unit, is designed for applications where sensitive settings with stability on heavy through faults are required. It offers a reliable protection for busbars, transformers windings, generators, reactors and motors. FUNCTIONAL OVERVIEW OVERVIEW Two models are available: MiCOM P721 is a single-phase high impedance differential protection. It is suitable for restricted earth fault or balanced earth fault applications. MiCOM P723 can be configured either as high impedance differential three-phase protection (87) or as high impedance differential earth protection (87N). The connection setting determines whether 87 or 87N is being used. Main functions Phase segregated high impedance differential protection (87A, 87B, 87C) The application of P723 numerical relay as differential protection for machines and busbar installations is based on the high impedance differential principle. This principle requires stabilising resistors in each phase and a metrosil is generally required across the relay circuit. These are included in the P79x accessory as shown in Figure 1. Stability for any type of fault occurring outside the protected zone and satisfactory operation for faults within the zone are achieved. Figure 1 shows the typical application diagram where P723 is configured as a phase segregated high impedance differential protection. Protected Plant I diff R ST Metrosil P79x 87P 87N Remote Comm. Port Local Communication Self Monitoring Fault Records Measurements Disturbance Record 95P LEDs 95N 50BF Binary Input / Output P72x P72x and P79x together offer a simple and reliable high impedance differential protection

5 Protection Relays MiCOM P72x 03 PROTECTION FUNCTIONS OVERVIEW ANSI Features P721 P723 87P Phase segregated high impedance current differential protection 95P Phase bus-wire supervision 87N Restricted earth fault protection 95N Earth bus-wire supervision 87CZ Check zone input 50BF Breaker failure detection GENERAL FEATURES Features P721 P723 Number of opto-isolated inputs 2 5 Number of relay output contacts 4 8 Event recording Fault recording Disturbance recording 5 5 Instantaneous records 5 5 Setting groups 2 2 Auxiliary timers 4 4 Communication protocols Modbus RTU (rear port) DNP3 (rear port) IEC (rear port) Modbus RTU (front port) Setting software MiCOM S1 Studio Logic equations AND, OR and NOT gates 8 Boolean equations Measurements Neutral supervision/differential currents (INdiff) Phase supervision/differential currents (IAdiff, IBdiff and ICdiff) Maximum differential currents (ImaxAdiff, ImaxBdiff and ImaxCdiff) Maximum differential neutral currents (ImaxNdiff) Figure 1: P723 configured as phase segregated high impedance differential busbar protection

6 Protection Relays MiCOM P72x 04 High impedance differential earth fault protection (87N) The P721 has a single differential element and may only function as an 87N protection. The P723 can be configured as 87N when only one analogue current input is required. Restricted earth fault protection is included to cover a larger percentage of the transformer windings than might be possible with the main biased differential transformer protection. 87N is commonly referred as restricted earth fault (REF) protection for star windings and balanced earth fault (BEF) protection for delta windings. Figures 2 and 3 show the P72x configured for these applications. GENERAL SCHEME LOGIC The schemes in figures 4 and 5 describe the logic of the three-phase high impedance differential protection and high impedance differential earth fault protection relays. External blocking inputs are available to allow the user to configure an input to enable or disable the differential element. A selectable logic input is also available as a check zone input from another P72x or differential relay. [87] DIFF Blocking Logic 1 / 2 & DT [87CZ] Check Zone & Start [87] DIFF Temporized [87] tdiff [95] SUP DT Start [95] SUP Temporized [95] tsup Figure 4: General scheme of the three-phase high impedance differential protection [87N] DIFF Start [87N] DIFF Blocking Logic 1 / 2 & DT Temporized [87N] tdiff [95N] SUP Start [95N] SUP DT Temporized [95N] tsup Figure 2: BEF protection for the delta winding of a power transformer with supply system earthed Figure 5: General scheme of high impedance differential earth fault protection Control AND INDICATION Control Two blocking logics are available where for example opto inputs can be independently configured to block the differential element or any of the auxiliary timer functions. Logic equations The MiCOM P72X relays integrate complete logic equations to allow customization of the product based on customer application. Up to 8 independent Boolean equations can be used. Each equation offers the possibility to use AND, OR & NOT logical gates. Up to 16 parameters can be used for each equation. Every result of equation can be time delayed and assigned to any output relays, trip, trip latching and/or HMI LEDs. Figure 3: REF protection of a 3 phase, 4 wire system applicable to star connected generators or power transformer windings with neutral earthed at generator/transformer star point

7 Protection Relays MiCOM P72x 05 Optos Protection elements Automatic Control Gate Logic Timers Relay contacts LED's Phase segregated outputs are available from the buswire supervision such that each phase can be stabilised by short circuiting the bus-wires as required. The differential elements are internally blocked due to bus-wire supervision (although this will not negate the requirement for external shorting of bus-wires). LEDs Four programmable LEDs are available. Alarms Protection and control functions generate alarms on the screen and LEDs as configured. Certain alarms can be inhibited or automatically reset by preliminary parameter setting. Alarms can be stored in non-volatile memory. SUPERVISORY FUNCTIONS Open circuit failures of the CTs or bus-wires will cause a spill current to flow through the differential element and operation will occur if this current is greater than the setting. Two methods are used to prevent nuisance tripping due to open circuit conditions: 1. Bus-wire supervision elements are provided to monitor for a continuous low level of spill current. After a time delay, this relay would usually short circuit the AC bus-wires to ensure stability and also give an alarm. The disadvantage of this scheme is that the differential elements must be set higher than the bus-wire supervision elements (and usually above maximum load conditions) if nuisance tripping is to be avoided. This may create sensitivity issues. 2. Duplicate differential elements (main and check zones) fed from separate CTs using segregated (phase by phase) bus-wires. Tripping is only permitted when both differential elements operate. The advantage of this scheme is that the differential settings can remain very sensitive (below full load current values), but this will require a total duplication of the scheme. The selectable logic input from another P72x deployed as a check zone is available for this function. The above two methods are usually used in conjunction with each other, although to reduce costs either scheme could be used independently. Bus-wire Shorting To limit the power dissipated in the resistance, after the differential trip protection [87] or bus-wire supervision [95] are activated, the bus-wires must be short-circuited. This function is latched in the internal logic. The bus-wire shorting signal can be connected as shown in figures 1, 2 and 3. CB Failure function The CB failure output from the P72x is an input to the breaker failure scheme. The general scheme for the breaker failure detection function is shown in figure 6. Trip [87] tdiff Idiff< Pick up timer CB Fail time tbf Figure 6 CBF detection logic & CB Fail Operation AND CONfiguRATION Setting groups External conditions may request the need for different settings. MiCOM P72x provide two independent setting groups. The active setting group can be switched to the other from the local HMI or from external conditions (opto input change of state or DCS control). Multi-language user interface (HMI) All functions, including protection, automation, communication, LEDs, inputs and outputs, can be programmed and modified using the front panel user interface (Human Machine Interface, HMI). The backlit LCD informs the user about settings, measurements & faults thanks to the pull-down structure menu allowing easy and quick access to any data. Moreover, even if the relay is delivered with the language specified at the order, the user can change the language used within the relay from the HMI.

8 Protection Relays MiCOM P72x 06 trip led clear Key Alarm led Device fail. Power supply freely Programmable leds battery is not used anymore Read Key cursor Keys Rs 232 The P721 and P723 measure the neutral supervision/differential currents (I Ndiff ). The P723 measures the maximum differential currents (Imax Adiff, Imax Bdiff and Imax Cdiff ). The P721 and P723 measure the maximum differential neutral currents (Imax Ndiff ). Fault records 25 time-tagged fault records that indicate the faulted phase, protection operation, active setting group, pre-fault and differential fault currents magnitudes are available. Disturbance records A disturbance record is generated for every trip. In addition, the disturbance recorder can be triggered by an opto-isolated input, or a remote control signal. MeasuREMENTS and RECORDING Measurements The following measurements are available for display and remote measurements: The P723 measures Phase supervision/ differential currents (I Adiff, I Bdiff and I Cdiff ). Up to five records of 3 seconds each one can be stored. The disturbance records are 32 samples per cycle. Event records 250 time-tagged event records can be stored. Events include operation and reset of inputs/ outputs, alarms, internal signals, and contacts. All events are time stamped to 1ms, and can be accessed either locally or remotely. Figure 7: Disturbance Record

9 Protection Relays MiCOM P72x 07 COMMUNICATION & SYNCHRONIZATION The MiCOM P72x offers a wide range of communication protocols, allowing its utilisation in most of the network control and data acquisition systems (via Modbus, IEC , and DNP3.0). It has been designed for permanent multi-drop connection through the rear RS485 communication port. The MiCOM P72x incorporates an internal clock used for the time tagging of alarms, events, fault and disturbance record. The relay s internal clock is synchronise to the timing information to an accuracy of 1ms.To avoid any drifting of the time tagging clock, it s necessary to periodically synchronize the relays. To do this P72x offers two solutions: 1. Synchronization from the substation control system via the rear communication port 2. Synchronization from an external GPS clock via a dedicated digital input Stabilising RESISTOR AND VARISTOR ACCESSORY The P79x accessory contains a number of fixed resistors that provide stability during external faults. In addition to the stabilising resistors, a varistor is included for each phase. Two models are available: the P791 used in single phase applications and the P793 used in three phase applications. Stabilising resistor Three options of internal stabilising resistors are offered. In each option is possible to get 4 combinations of serial and parallel connections to give various values of resistance as required by the application. Varistor Varistors are used to limit the peak voltage developed by the current transformers under internal fault conditions to a value below the insulation level of the current transformers, relay and interconnecting wiring, which are typically able to withstand approximately 3000V peak. Two options of varistors are available. The half power option may withstand up to 10kJ of transient energy and the full power up to 20kJ. Figures 8 and 9 show P721/P791 and P723/P793 connection diagram. See P79x brochure for more information. A B C P791 Auxiliary supply _ WD RL1 RL2 RL3 RL Watch dog RL1 to RL4 are programmable outputs P791 L1 to 2 are programmable inputs L1 24 _ L2 _ MiCOM P721 Link terminals 30 and 32 if the relay is connected at the end of the RS485 bus * _ RS485 communication port Figure 8: MiCOM P721/P791 diagram connection Simple and reliable high impedance differential scheme protection

10 Protection Relays MiCOM P72x 08 A B C PROTECTED ZONE Three-Phase High Impedance Differential TC1 CT1 TC2 CT2 TCN CTN Auxiliary supply P793 P793 L1 to 5 are programmable inputs _ L1 _ L2 _ L3 _ L4 _ L5 _ WD RL1 RL2 RL3 RL4 RL5 RL6 RL7 RL8 MiCOM P723 (*) Link terminals 30 and 32 if the relay is connected at the end of the RS485 bus * _ Watch dog RL1 to RL8 are programmable outputs RS485 communication port Figure 9: MiCOM P723/P793 diagram connection Device Track Record - High Impedance Differential Protection MiCOM P12x series relays used in high-impedance applications since 1998 MiCOM P14X series relays used in high-impedance applications since 1999 Schneider Electric 35, rue Joseph Monier CS Rueil-Malmaison Cedex, France Tel: 33 (0) RCS Nanterre Capital social As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Publishing: Schneider Electric Design: Schneider Electric Printing: 2010 Schneider Electric - All rights reserved EnergyAutomation-DS-P72x-2200-EN

11 RATINGS Power Supply Nominal auxiliary voltage Vx Operating range Residual ripple Up to 12% Stored energy time Vdc/ Vac Vdc/ Vac DC: ± 20% of Vx AC: 20%, 10% of Vx 50 ms for interruption of Vx Burden Stand by: <3W DC or <8VA AC Max: <6W DC or <14VA AC Phase and earth current transformers consumption P72x phase CT consumption RMS voltage (V) phase transformer phase transformer Current (A) Frequency P72x earth CT consumption Frequency protection functions Nominal frequency 5Hz Nominal frequency 50/60 Hz RMS voltage (V) earth transformer Current inputs earth transformer Phase current inputs 1 and 5 A by connection Current (A) Earth current inputs 1 and 5 A by connection Operating range Burden Phase Current Burden Earth Current Thermal withstand Selected at order (Cortec) < VA (1 A) < 0.3 VA (5 A) < 0.08 VA (1 A) < 0.42 VA (5 A) x rated current 2 40 x rated current 4 x rated current Logic inputs Logic input type Logic input burden Logic input recognition time (DC inputs) Logic input recognition time (AC inputs) Independent optically insulated < 10 ma per input < 5 ms in a 50 Hz system < 4 ms in a 60 Hz system <7 ms in a 50 Hz system < 6 ms in a 60 Hz system Logic input recognition time (ENA inputs) <15 ms in a 50 Hz system < 12 ms in a 60 Hz system P721 P723 Technical DataSheet 9 P72x/EN TDS/B21

12 Supply Output Relay Characteristic Ordering Code Relay auxiliary power supply Nominal Operating voltage range voltage range Vx Nominal Voltage range A* 24 60Vdc 19,2 76Vdc Vdc F* Vdc Vdc Vac Vac Vac T H V W Z Vdc Vac Special EA Vdc Vac Vdc Vac Vdc Vac Vdc Vac Vdc Vdc Vac Vac Logic Inputs Minimal Maximum polarisation polarisation voltage current Holding current after 2ms 19.2Vdc 19.2Vac 35mA 2.3mA 19.2Vdc 19.2Vac 35mA 2.3mA Maximum continuou s withstand 300Vdc 264Vac 300Vdc 264Vac Vdc Vac 129Vdc 105Vdc Vdc 145Vdc Vdc Vac 110Vdc 77Vdc Vdc 132Vdc Vdc Vac 220Vdc 154Vdc Vdc 262Vdc 19,2 300Vdc Vdc 38,2 264Vac Vac 19.2Vdc 19.2Vac 35mA 2.3mA ( * ) Ordering code (Cortec) options A and F are not available for sale ( ** ) Logic input recognition time for EA approval. Dedicated filtering on 24 samples (15ms at 50Hz). 300Vdc 264Vac Contact rating Contact relay Make current Carry capacity Rated Voltage Breaking characteristic Breaking capacity AC Breaking capacity DC Operation time Durability Loaded contact Unloaded contact Dry contact Ag Ni Max. 30 A and carry for 3s 5 A continuous 250 Vac 1500 VA resistive 1500 VA inductive (P.F. = 0.5) 220 Vac, 5 A (cos = 0.6) 135 Vdc, 0.3 A (L/R = 30 ms) 250 Vdc, 50W resistive or 25 W inductive (L/R=40 ms) <7 ms operation minimum operation minimum TYPICAL OPERATING TIMES The typical operating times for Restricted earth fault and balanced earth fault (REF/BEF) applications are shown in Figure 1. To determine the typical operating times the current levels considered were 1In, 5In, 10In and 20In and the point on wave was varied from 0 to 150 in steps. The tests were performed considering [87N] Threshold I Diff set to 0.5In and 0.1In and [87N] Measurement Filter set to Fourier, Sample and Fast Sample time (s) multiple of setting (xisetting) fourier fast sample Figure 1 Typical operating times REF/BEF applications P721 P723 Technical DataSheet 10 P72x/EN TDS/B21

13 The typical operating times for busbar applications are shown in Figure 2, Figure 3 and Figure 4. To determine the typical operating times the current levels considered were 5In, 10In, 25In and 50In and the point on wave was varied from 0 to 150 in 30 steps. The tests were performed considering [87] Threshold I Diff set to 0.5In and 0.1In and [87] Measurement Filter set to Fourier, Sample and Fast Sample. Single Phase Fault typical operating time (s) multiple of setting (xisetting) Fourier Fast Sample Sample Figure 2 Typical operating times Single phase faults Busbar applications P721 P723 Technical DataSheet 11 P72x/EN TDS/B21

14 Phase to Phase Faults typical operating time (s) multiples of setting (xisetting) Fourier Fast Sample Sample Figure 3 Typical operating times Phase to phase faults Busbar applications Three Phase Faults typical operating time (s) multiples of setting (xisetting) Fourier Fast sample Sample Figure 4 Typical operating times Three phase faults Busbar applications P721 P723 Technical DataSheet 12 P72x/EN TDS/B21

15 INSULATION Dielectric withstand IEC : kv common mode 1 kv differential mode ANSI/IEEE C (reaffirmed 1994) 1.5 kv rms AC for 1 minute, across normally open contacts. Impulse voltage IEC : 2000 Insulation resistance IEC : kv common mode 1 kv differential mode > 1000 M EMC TESTS High Frequency Disturbance IEC : kv common mode, Class III 1 kv differential mode, Class III Electrostatic Discharge EN : 1995 and IEC : kv contact discharge, Class 4 15 kv air discharge, Class 4 Fast Transient IEC :2002, Class A 2 kv 5 khz, terminal block comms. 4 kv 2.5 khz, all circuits excluding comms. EN :1995, Level 4 4 kv 5 khz, power supply 2 kv 5 khz, all circuits excluding power supply Surge EN :1995 and IEC : kv common mode, Level 4 2 kv differential mode, Level 4 Conducted Emissions EN 55022: MHz, 79 dbµv (quasi peak) 66 dbµv (average) MHz, 73 dbµv (quasi peak) 60 dbµv (average). Radiated Emissions EN 55022: MHz, 40 dbµv/m at 10 m measurement distance GHz, 47 dbµv/m at 10 m measurement distance. Conducted Immunity EN :1996 Level 3, 10 V 1 khz 80% am, 150 khz to 80 MHz Radiated Immunity EN :2002 ANSI/IEEE C :2004 Level 3, 10 V/m 80 MHz to 1 1 khz 80% am 35 V/m 80 MHz to 1 1 khz 80% am 35 V/m 80 MHz to 1 100% pulse modulated front face only. Radiated immunity from digital telephones EN :2002 ANSI Surge Withstand Capability IEEE/ANSI C : 2002 Magnetic Field Immunity IEC : 1994 IEC : 1993 IEC : 1993 Level 4, 30 V/m 800 MHz to 960 MHz and 1.4 GHz to 2 1 khz 80% am 4 kv fast transient and 2.5 kv oscillatory applied common mode and differential mode Level 5, 100 A/m applied continuously, 1000 A/m for 3 s. Level 5, 1000 A/m. Level 5, 100 A/m at 100 khz and 1 MHz. ENVIRONMENT Temperature IEC : 1993 Storage 25 C to 70 C IEC : 1993 Operation: 25 C to 55 C 25 C to 70 C (*) (*) The upper limit is permissible for a single 6 hour duration within any 24 hour period. Humidity damp heat IEC : days at 93% RH and 40 C Enclosure protection IEC : 2001 Dust IP50 (whole case), Front IP 52, Back IP 10 Sinusoidal Vibrations IEC :1998 Response and endurance, class 2 Shocks IEC :1998 Response and withstand, class 2 Shock withstand & Bump IEC :1998 Response and withstand, class 1 Seismic IEC :1993 Class 2 Corrosive Environments : Per IEC : 1995, Part 2, Test Ke, Method (class) 3 Industrial corrosive environment/poor environmental control, mixed gas flow test. 21 days at 75% relative humidity and 30 C Exposure to elevated concentrations of H²S, NO², Cl² and SO². P721 P723 Technical DataSheet 13 P72x/EN TDS/B21

16 EU DIRECTIVE EMC compliance 89/336/EEC 93/31/EEC Compliance with European Commission EMC Directive. Generic standards were used to establish conformity: EN : 1994 EN : 1995 Product safety 2006/95/EC (replacing 73/23/EEC from 01/2007) Compliance with European Commission Low Voltage Directive. Compliance is demonstrated by reference to generic safety standards: EN : 1993/A2: 1995 EN60950: 1992/A11: 1997 DEVIATION OF PROTECTION ELEMENTS Element Range Deviation Fault timer Reset timer Earth differential protection I diff (V diff) Phase differential protection I diff (V diff) Earth bus-wire supervision Phase bus-wire supervision I Sup (V Sup) 0.01In to 1In (0.5 to 200 V) 0.02 to 2In (1 to 400 V) 0.01 to 1 In (0.5 to 200 V) 0.02 to 2In (1 to 400 V) 2% 0 s 2 s 0 to 600 s 2% 0 s 2 s 0 to 600 s 2% 0.5 s 3 s 0 to 600 s 2% 0.5 s 3 s 0 to 600 s DEVIATION OF AUTOMATION FUNCTIONS TIMERS CB fail & CB monitoring timers Auxiliary timers taux1, taux2, taux3, taux4 2% 0-10 s 2% s DEVIATION OF MEASUREMENTS Measurement Range Deviation Phase current 0.02In to 10In Typical 0.5% at In Earth current 0.004In to 2In Typical 0.5% at In PROTECTIONS FUNCTIONS Settings [87N] Earth differential protection [87N] Earth differential protection [87N] Threshold I diff [87N] Threshold V diff [87N] Filter timer t Diff [87N] Reset timer treset Measurement Filter [95N] Earth bus-wire supervision [95N] Earth bus-wire supervision [95N] Threshold I sup [95N] Threshold V sup [95N] Filter timer t sup [95N] Reset timer treset Measurement Filter Yes / No 0.01In to 1In 0.5 V to 200 V 0 s to 2 s 0 to 600 s Sample mode Fast sample mode Fourier mode Yes / No 0.01In to 1In 0.5 V to 200 V 0.5 s to 3 s 0 to 600 s Sample mode Fast sample mode Fourier mode [87] Phase differential protection (P723 only) [87] Phase differential protection Yes / No [87] Threshold I diff 0.02In to 2In [87] Threshold V diff 1 V to 400 V [87] Filter timer t Diff 0 s to 2 s [87] Check zone Yes / No [87] Reset timer treset 0 to 600 s Measurement Filter Sample mode Fast sample mode Fourier mode [95] Phase bus-wire supervision (P723 only) [95] Phase bus-wire supervision Yes / No [95] Threshold I sup 0.02In to 2In [95] Threshold V sup 0.5 V to 400 V [95] Filter timer t sup 0.5 s to 3 s [95] Check zone Yes / No [95] Reset timer treset 0 to 600 s Measurement Filter Sample mode Fast sample mode Fourier mode P721 P723 Technical DataSheet 14 P72x/EN TDS/B21

17 Automation and accessory functions Trip command Assignation of the following thresholds to trip output relay: all models: [87N] tdiff, t Aux 1, t Aux 2, Control Trip, tequ.a, tequ.b, tequ.c, tequ.d, tequ.e, tequ.f, tequ.g, tequ.h, P723 additional functions: [87] tdiff, t Aux 3 and t Aux 4 Latch functions Trip output relay programmable with one or many thresholds: all models: [87N] tdiff, t Aux 1, t Aux 2, Control Trip, tequ.a, tequ.b, tequ.c, tequ.d, tequ.e, tequ.f, tequ.g, tequ.h. P723 additional functions: [87] tdiff, t Aux 3, t Aux 4. Blocking logic Possibility to block the following delayed thresholds: all models: [87N] tdiff, t Aux 1, t Aux 2, P723 additional functions: [87] tdiff, t Aux 3 and t Aux 4. Output relays Alarm and trip threshold assignation to a logic output: 3 relays (P721) and 7 relays (P723). Assignable functions: all models: [87N] Diff, [87N] tdiff, [95N] Sup, [95N] tsup, Buswire Short, CB Fail, t Aux 1, t Aux 2, Active group, Control trip, Input1, Input2, tequ. A, tequ. B, tequ. C, tequ D, tequ E, tequ. F, tequ. G, tequ. H. P723 additional functions: [87] Diff, [87] tdiff, [87CZ] ChkZone, [95] Sup, [95] tsup, [9] tsup A, [95B] tsup B, [95C] tsup C, t Aux 3, t Aux 4, Input3, Input4, Input5 Latch of the auxiliary output relays Possibility to latch output relays: P721: Output 2 to 4 P723: Output 2 to 8 Inputs Inputs assignation Single function or multiple automation functions assignable to 4 logic inputs: all models: Unlatch, Aux 1, Aux 2, Blocking Logic 1, Blocking Logic 2, Start Disturb, Change setting, Reset LEDs, Maint. Mode, Local Mode, Synchro P723 additional functions: Aux 3, Aux 4, [87CZ] Chk Zone Auxiliary timers: Aux1 time taux1 0 to 200s Aux2 time taux2 0 to 200s Aux3 time taux3 0 to 200s Aux4 time taux4 0 to 200s Circuit Breaker Failure CB Fail Setting Ranges: CB Fail? Yes / No I Diff < 0.01 In to 1 In V Diff < 0.5 v to 200 V CB Fail Time tbf 0 to 10s Logic Equations The MiCOM P721 and P723 relays integrate complete logic equations to allow customization of the product based on customer application. Up to 8 independent Boolean equations can be used (from A to H). Every result of equation can be time delayed and assigned to any output relays, trip, trip latching and/or HMI LEDs. Up to 16 operands can be used (from 00 to 15). Within operands, there are two parts: (1/2) : logical gates (NOT, OR, AND, NOT AND, NOT OR) (2/2) : signals ([87N] Diff, [95N] tsup, taux, input etc) Timer Setting Ranges EQU. A to H Toperat 0 to 600 s EQU. A to H Treset 0 to 600 s Available logical gates: NOT Logical gates OR (by default) AND AND NOT OR NOT Available signals: Text Signals (2/2) Availability (1/2) A00, B00, C00, D00, E00, F00, G00, H00 A01 to A15, B01 to B15, C01 to C15, D01 to D15, E01 to E15, F01 to F15 G01 to G15, H01 to H15 P721 and P723: Null Condition is Null Not Null Condition is not Null [87N] Diff Earth differential protection threshold [87N] tdiff Time delayed earth differential protection threshold [95N] tsup Time delayed earth high impedance differential threshold (buswire supervision) taux 1 Copy of the status of the Logic Input taux 1 taux 2 Copy of the status of the Logic Input taux 2 Input 1 Instantaneous digital input 1 Input 2 Instantaneous digital input 2 Group 2 Group 2 is active (setting) CB Fail Circuit Breaker does not operate P723 only: [87] Diff Phase differential protection threshold [87] tdiff Time delayed phase differential protection threshold [87CZ] Check zone Check Zone status [95] Sup Phase high impedance differential threshold (buswire supervision) [95N] Sup Earth high impedance differential threshold (buswire supervision) [95] tsup Time delayed phase high impedance differential threshold (buswire supervision) [9] tsupa Time delayed phase A (or L1, or R) high impedance differential threshold (buswire supervision) [95B] tsupb As above for phase B (or L2 or S) [95C] tsupc As above for phase C (or L3 or T) Buswire Short Buswires short-circuited taux 3 Copy of the status of the Logic Input taux 3 taux 4 Copy of the status of the Logic Input taux 4 Input 3 Instantaneous digital input 3 Input 4 Instantaneous digital input 4 Input 5 Instantaneous digital input 5 P721 P723 Technical DataSheet 15 P72x/EN TDS/B21

18 RECORDING FUNCTIONS Fault Record Capacity Time-tag Triggers Data 25 faults 1 millisecond Instantaneous recorder Any selected protection alarm and threshold Fault date, Active setting Group, Faulted phase, Threshold, Fault magnitude, [87] tdiff fault (tripping) [87N] tdiff fault (tripping) taux 1 fault (tripping) taux 2 fault (tripping) taux 3 fault (tripping) taux 4 fault (tripping) tequation A, B, C, D, E, F, G and H fault (tripping) Control trip Disturbance Records Triggers; Data; Setting Ranges Triggers Data Any selected protection alarm and threshold, logic input, remote command AC input channels digital input and output states frequency value Default value Setting range P72x Min Max Step Pre-Time 1.0 s 0.1 s 3 s 0.1 s Post-Time 2.0 s 0.1 s 3 s 0.1 s Disturb rec Trig Trigger ON INST ON TRIP or ON INST. Any selected protection alarm and threshold Logic input Remote command Capacity Time-tag Triggers Data 5 starting items of information (instantaneous) 1 millisecond Any selected protection alarm and threshold date, hour origin (any protection alarm) length (duration of the instantaneous trip yes or no Communications Type Port Relay position Physical Link Connectors Data Rate Protocol RS485 Rear port Screened twister pair RS232 Front port Screened twister pair Screws or snapon Sub D 9 pin female connector 300 to baud (programmable) 300 to baud (programmable) ModBus RTU, Courier, IEC , DNP3.0 ModBus RTU P721 P723 Technical DataSheet 16 P72x/EN TDS/B21

19 DIMENSIONS P721 and P723: External size: Height case 152 mm front panel 177 mm Width case 97 mm front panel 103 mm Depth case 226 mm front panel case 252 mm P0078ENb Figure Dimensional drawings P721 P723 Technical DataSheet 17 P72x/EN TDS/B21

20 WIRING CONNECTIONS Typical application diagram P A C B Phase rotation Auxiliary voltage WD Case earth RL1 RL2 RL3 RL Alternative : Restricted Earth Fault Protection (Delta connection) A B C RSt A B C P791 stabilising resistors Alternative : Restricted Earth Fault Protection ( Star connection) Ctrl shorting relay P791 (-V) Auxiliary voltage (-V) Auxiliary voltage P791 RSt Watch dog (4) Programmable tripping output Programmable output Ctrl shorting relay Module terminal blocks viewed fromp rear (with integral case earth link) (V)Auxiliary voltage Programmable output MiCOM P721 Programmable input Programmable input L1 L2 * ( : Link terminals 30 and 32 if the relay is connected at the end of the RS485 bus ) * Case earth connection Port communication RS 485 Nota : (1) (a) (b) (c) (d) CT shorting links make before (b) and (c) disconnect (2) CT connection are typical only Short terminals break before (c) (3) Earth terminals are typical only Long terminals Pins terminals (pcb type) (4) The MICOM P120/P121 relays are shown with supply off P3955ENa P721 P723 Technical DataSheet 18 P72x/EN TDS/B21

21 Typical application diagram P723 Alternative : Restricted Earth Fault Protection ( Star connection) Alternative : Restricted Earth Fault Protection (Delta connection) Terre boîtier Case earth Nota : (1) (a) Module terminal blocks viewed fromp rear (with integral case earth link) CT shorting links make before (b) and (c) disconnect (b) (c) (d) Short terminals break before (c) Long terminals Pins terminals (pcb type) (2) CT connection are typical only (3) Earth terminals are typical only (4) The MICOM relays are shown with supply off. Auxiliary voltage Programmableinput Programmableinput Programmableinput Programmable input Programmable input Three-Phase High Impedance Differential L1 L2 L3 L4 L5 MiCOM P723 * RL7 RL8 ( : Link terminals 30 and 32 if the relay is connected at the end of the RS485 bus ) * Case earth connection Port communication RS A B C Ctrl shorting relay (-V) Auxiliary voltage P A B C A Auxiliary voltage (-V) C B Phase rotation P793 P791 and P793 stabilising resistors WD 36 RL1 RL2 RL3 RL4 RL5 RL Watch Dog (4) Programmable tripping output Programmable output Ctrl shorting relay (V)Auxiliary voltage Programmable output Programmable output Programmable output Programmable output Programmable output CT1 CT2 CTn RSt. Ctrl shorting relay (-V) Auxiliary voltage P791 RSt. 49 RSt. RSt. RSt. P3954ENa P721 P723 Technical DataSheet 19 P72x/EN TDS/B21

22 ORDERING OPTIONS Information Required with Order Relay Type (differential protection) P Variant Simple phase high impedance differential protection Simple phase or three phase high impedance protection with binary I/O extension Auxiliary and digital input voltage Auxiliary voltage digital input voltage Vdc / Vac Vdc / Vac Vdc / Vac Vdc / Vac Vdc / Vac Rear port communication interface Modbus K-Bus/Courier IEC DNP 3.0 Default HMI language French English / American Spanish German Italian Portuguese Platform Vdc (1) Vdc (ENA UK) 110 Vdc 30% / 20% (1) 220 Vdc 30% / 20% (1) Vdc / 24 / 240 Vdc phase 2 with standard software 2 Software Unless specified the latest version will be delivered Mounting option None (default) (2) Pre-fixed HMI (no withdrawability) Sealed cover (2) Pre-fixed HMI Sealed cover (1) : special application (2) : : not available 1 3 H T V W Z P721 P723 Technical DataSheet 20 P72x/EN TDS/B21

23

24 Schneider Electric 35 rue Joseph Monier Rueil-Malmaison FRANCE Phone: 33 (0) Fax: 33 (0) Publishing: Schneider Electric Publication: P72x/EN TDS/B21 03/ Schneider Electric. All rights reserved.

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits 01 MiCOM P721 & P723 Numerical High Impedance Differential Relay The new P72x high impedance differential protection series provides an independent and simple high impedance differential protection solution

More information

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Type MVTT 14 and MVTT 15: Static Digital Time delay relays Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction

More information

MiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation

MiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation MiCOM P123R Overcurrent Relays Upgrade Documentation MiCOM P123R Page 1/14 CONTENTS MiCOM P123R ADDENDUM: MiCOM P12X UPDATE DOCUMENTATION 3 P12X/EN IT/EB6: INTRODUCTION 4 P12x/EN TD/Eb6: TECHNICAL DATA

More information

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS MiCOM 01 MiCOM Fast Feeder Differential Protection The MiCOM relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

MiCOM P111. Three phase and earth fault overcurrent relays

MiCOM P111. Three phase and earth fault overcurrent relays Three phase and earth fault overcurrent relays The relays are suitable for all the application where overcurrent and/or earth-fault protection are required. Thanks to its favorable price vs technical features

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

VIP 40/45 VIP 400/410

VIP 40/45 VIP 400/410 40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered

More information

7SR23 DAD High Impedance Protection Relay Energy Management

7SR23 DAD High Impedance Protection Relay Energy Management Reyrolle Protection Devices 7SR23 DAD High Impedance Protection Relay Energy Management 2 Siemens Protection Devices Limited 7SR23 DAD High Impedance Relay User Interface 20 character x 4 line backlit

More information

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy Reyrolle Protection Devices 7SG117 Argus 7 Synchronising Relay Answers for energy 7SG117 Argus 7 Synchronising Relay Fig 1. Independent check & system synchronising settings Adjustable slip frequency,

More information

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A AUTOMATION MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A GRID Note: The technical manual for this device gives instructions for its installation, commissioning,

More information

Relion 611 series. 611 series Type Test Certificate

Relion 611 series. 611 series Type Test Certificate Relion 611 series 611 series Document ID: 1MRS757466 Issued: 2016-02-22 Revision: B Product version: 2.0 Copyright 2016 ABB. All rights reserved Table of contents Table of contents Section 1 Section

More information

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays 01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

TM221M16R controller M IO relay

TM221M16R controller M IO relay Product data sheet Characteristics TM221M16R controller M221 16 IO relay Complementary Main Discrete I/O number 16 Number of I/O expansion module Supply voltage limits Inrush current Power consumption

More information

NPW800R RETROFITTING. Power and Volatge Protection Relay

NPW800R RETROFITTING. Power and Volatge Protection Relay RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)

More information

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive

More information

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide Directional or Non-Directional Earth-Fault Product Guide Issued: 17.06.19994 Status: Updated Version: C/16.10.2002 Data subject to change without notice Features Directional or non-directional low-set

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006 PowerLogic power-monitoring units Technical data sheet 2006 Functions and characteristics E90463 The PowerLogic PM500 Power Meter provides all measurement capabilities required to monitor an electrical

More information

GRD130 - FEATURES APPLICATION

GRD130 - FEATURES APPLICATION FEATURES Phase undervoltage protection with IDMTL or DTL. Phase overvoltage protection with IDMTL or DTL. Zero phase sequence overvoltage (neutral voltage displacement) protection with IDMTL/DTL. Negative

More information

MiCOM P111 Numerical three phase and earth fault overcurrent relay description

MiCOM P111 Numerical three phase and earth fault overcurrent relay description Numerical three phase and earth fault overcurrent relay description PC15101b relays provide features for easy adaptation to different applications and operation conditions. IEC 60870-5-103 and Modbus RTU

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

Three phase and earth fault overcurrent relays

Three phase and earth fault overcurrent relays 01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM

More information

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy Reyrolle Protection Devices 7SG118 Argus 8 Voltage & Frequency Relay Answers for energy 7SG118 Argus 8 Voltage and Frequency Relay Data Storage and Communication Serial communications conform to IEC60870-5-103

More information

TM3TM3 module TM3-2 temperature inputs and 1 analog output

TM3TM3 module TM3-2 temperature inputs and 1 analog output Characteristics module TM3-2 temperature inputs and 1 analog output Main Range of product Product or component type Range compatibility Analogue input number 2 Analogue input type Analogue output number

More information

extending the boundaries of technology evolution of proven technology FEATURES

extending the boundaries of technology evolution of proven technology FEATURES extending the boundaries of technology evolution of proven technology FEATURES IEC 61850 compliant Advanced AC capabilities with comprehensive fault detection Integrated protection functions Disturbance

More information

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 TOSHIBA Corporation 2004 All Rights Reserved. ( Ver. 1.6 ) Safety Precautions Before using this product, please read this chapter carefully. This

More information

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs SIPROTEC easy 7SJ4 Numerical Overcurrent Protection Relay Powered by CTs Function overview Fig. /1 Description The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended

More information

Protection Relays PHASE & RESIDUAL OVERCURRENT

Protection Relays PHASE & RESIDUAL OVERCURRENT Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent

More information

TM221CE24R controller M IO relay Ethernet

TM221CE24R controller M IO relay Ethernet Product data sheet Characteristics TM221CE24R controller M221 24 IO relay Ethernet Complementary Main Discrete I/O number 24 Number of I/O expansion module Supply voltage limits Network frequency Inrush

More information

TM3AI4 module TM3-4 analog inputs

TM3AI4 module TM3-4 analog inputs Characteristics module TM3-4 analog inputs Main Range of product Product or component type Range compatibility Analogue input number 4 Analogue input type Complementary Analogue input resolution Permissible

More information

Synchro-check relay. Application

Synchro-check relay. Application Issued: April 1999 Status: Updated Version: B/08.11.2001 Data subject to change without notice Features Two identical operation stages allowing the closing conditions of two separate circuit breakers to

More information

Arc protection relay. Features Three-phase overcurrent function. Application

Arc protection relay. Features Three-phase overcurrent function. Application Arc protection relay REA 10_ Page 1 Issued: May 1999 Status: New Data subject to change without notice Features Three-phase overcurrent function Loop-type or radial sensor fibre for arc detection Two high-speed

More information

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Relion 605 series. Self-powered feeder protection REJ603 Product Guide Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1. Description... 3 2. Relay functions... 3 3. Protection functions... 4

More information

TM3TI4 module TM3-4 inputs temperature

TM3TI4 module TM3-4 inputs temperature Characteristics module TM3-4 inputs temperature Main Range of product Product or component type Range compatibility Analogue input number 4 Analogue input type Complementary Analogue input resolution Permissible

More information

PowerLogic power-monitoring units. PM1000 series power meter. Technical data sheet

PowerLogic power-monitoring units. PM1000 series power meter. Technical data sheet PowerLogic power-monitoring units power meter Technical data sheet 2011 Basic energy meters Functions and characteristics PE86261 PE86260 PowerLogic PM1000 power meter. The PowerLogic power meters are

More information

PowerLogic power-monitoring units. EM1000 series power meter. Technical data sheet

PowerLogic power-monitoring units. EM1000 series power meter. Technical data sheet PowerLogic power-monitoring units power meter Technical data sheet Distributed By: MetersUSA www.metersusa.com Meters@MetersUSA.com 1 224 365 5935 Basic energy meters Functions and characteristics PB105460

More information

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC Characteristics on-delay timing relay - 0.02 s..300 h - 24..240 V AC - 2 OC Complementary Product front plate size Control type Housing material Main Range of product Product or component type Electrical

More information

Flair 21D - 22D - 23D - 23DM Self-powered, adjustment-free fault passage indicators

Flair 21D - 22D - 23D - 23DM Self-powered, adjustment-free fault passage indicators Technical leaflet - MV network management 01 Self-powered, adjustment-free fault passage indicators EMS58355 1 Customer benefits At the cutting edge of technology, they are used on underground MV networks

More information

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/ DC - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type Time

More information

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/DC - solid state output Complementary Control type Voltage range Main Range of product Product or component type Discrete output type Width

More information

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D WPM 770 Data Sheet 679.D.141.02 Digital Multifunctional Power Meter with LCD Display and Application The digital Weigel Power Meters WPM 770 have been designed to display the electrical parameters in low

More information

TM221CE40T controller M IO transistor PNP Ethernet

TM221CE40T controller M IO transistor PNP Ethernet Product data sheet Characteristics TM221CE40T controller M221 40 IO transistor PNP Ethernet Complementary Main Discrete I/O number 40 Number of I/O expansion module Supply voltage limits Inrush current

More information

TM221CE40R controller M IO relay Ethernet

TM221CE40R controller M IO relay Ethernet Characteristics controller M221 40 IO relay Ethernet Main Range of product Product or component type [Us] rated supply voltage Jan 6, 2019 Modicon M221 Logic controller 100...240 V AC Discrete input number

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

PowerLogic power-monitoring units. DM6000 series digital panel meters. Technical data sheet

PowerLogic power-monitoring units. DM6000 series digital panel meters. Technical data sheet PowerLogic power-monitoring units digital panel meters Technical data sheet 2011 Authorized Distributor: WESCHLER INSTRUMENTS phone: 800-903-9870 440-378-6580 fax: 800-903-9590 440-238-0660 www.weschler.com

More information

TM221M16TG controller M IO transistor PNP spring

TM221M16TG controller M IO transistor PNP spring Characteristics controller M221 16 IO transistor PNP spring Main Range of product Product or component type [Us] rated supply voltage Discrete input number Analogue input number Discrete output type Discrete

More information

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O Characteristics star-delta timing relay - 230VAC/440VAC - 1 C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts type

More information

HID. GE Consumer & Industrial Multilin. High Impedance Differential Module Instruction manual GEK Copyright 2005 GE Multilin

HID. GE Consumer & Industrial Multilin. High Impedance Differential Module Instruction manual GEK Copyright 2005 GE Multilin g GE Consumer & Industrial Multilin HID High Impedance Differential Module Instruction manual GEK-113064 Copyright 2005 GE Multilin GE Multilin 215 Anderson Avenue L6E 1B3 Markham, ON -CANADA T (905) 294

More information

TM221ME32TK controller M IO transistor PNP Ethernet

TM221ME32TK controller M IO transistor PNP Ethernet Product data sheet Characteristics TM221ME32TK controller M221 32 IO transistor PNP Ethernet Complementary Main Discrete I/O number 32 Number of I/O expansion module Supply voltage limits Inrush current

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

Transformer Protection Relay

Transformer Protection Relay Transformer Protection Relay T-PRO Product Overview The IEC 61850 station bus embedded T-PRO relay provides complete three-phase multi-winding transformer protection and overload protection, DFR-quality

More information

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box INTRODUCTION The PL-50 MO units are available in the next mechanical version: The PL-50 MO and PM-250 families represent the different solutions that Team Arteche offers for motor protection. Both families

More information

TM3TI8T module TM3-8 inputs temperature

TM3TI8T module TM3-8 inputs temperature Characteristics module TM3-8 inputs temperature Main Range of product Product or component type Range compatibility Analogue input number 8 Analogue input type Complementary Analogue input resolution Input

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

High impedance protection relay

High impedance protection relay High impedance protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features High impedance type differential current earth-fault protection, so called restricted

More information

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

2C138. Sensitive Earth Fault Relay. Features. Application. Operation Technical Bulletin 2C138 Sensitive Earth Fault Relay Features High sensitivity (0.1% of I n ) 2 nd & 3rd harmonic & HF noise suppression - tuned to 50 Hz Optional reset functions Instantaneous (Fast),

More information

TM3TI4 module TM3-4 inputs temperature

TM3TI4 module TM3-4 inputs temperature Characteristics module TM3-4 inputs temperature Complementary Analogue input resolution Permissible continuous overload Input impedance LSB value Conversion time Sampling duration Main Range of product

More information

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output Characteristics off-delay timing relay - control - 1 s..100 h - 24..240 V - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type

More information

GRD110 FEATURES APPLICATION

GRD110 FEATURES APPLICATION FEATURES Overcurrent protection for phase and earth faults with IDMTL or DTL. Three instantaneous elements with DTL. Programmable reset characteristics. Sensitive earth fault protection (SEF). Restricted

More information

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET Measurement input, auto range Up to 1000 V AC L-L Up to 12.5 A (sinusoidal) 16 400 Hz Output Up to four analogue outputs Relay output RS 485 Modbus

More information

MiCOM P12x/y. Three phase and earth fault overcurrent relays

MiCOM P12x/y. Three phase and earth fault overcurrent relays 01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM

More information

TM221M32TK controller M IO transistor PNP

TM221M32TK controller M IO transistor PNP Characteristics controller M221 32 IO transistor PNP Main Range of product Product or component type [Us] rated supply voltage Discrete input number Analogue input number Discrete output type Discrete

More information

RT4B-110V/12A RECTIFIER

RT4B-110V/12A RECTIFIER The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs

More information

Table 1 Relay Model and Function

Table 1 Relay Model and Function FEATURES Numerical autoreclosing function Single-shot, single-phase and/or three-phase autoreclose scheme for one or two circuit breakers Multi-shot (selectable between 2 and 4) threephase autoreclose

More information

TM3DI16 module TM3-16 inputs

TM3DI16 module TM3-16 inputs Characteristics module TM3-16 inputs Main Range of product Product or component type Range compatibility Jun 30, 2018 Modicon TM3 Discrete input module Modicon M241 Modicon M251 Modicon M221 Discrete input

More information

Auxiliary Units for 7SR23 High Impedance Protection Energy Management

Auxiliary Units for 7SR23 High Impedance Protection Energy Management Reyrolle Protection Devices Auxiliary Units for High Impedance Protection Energy Management Siemens Protection Devices Limited 2 Auxiliary Units for High Impedance Protection Description 7XG15 High Impedance

More information

Multifunction Transducer MT440

Multifunction Transducer MT440 Multifunction Transducer MT440 Voltage and current auto range measurements up to 600V, 12.5A Universal wide auxiliary power supply range 24 300 Vdc, 40 276 Vac Power accuracy class 0.5 (EN 60 688), Up

More information

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

High Impedance Protection Relay SPAE010, SPAE011. Product Guide SPAE010, SPAE011 SPAE010, SPAE011 1MRS750383-MBG Issued: April 1999 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features High impedance type differential current earth-fault

More information

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation Location(s) where activities are performed under accreditation Head Office Utrechtseweg 310, Building no. R11 6812 AR Arnhem The Netherlands Location Abbreviation/ location code Utrechtseweg 310, Building

More information

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice Issued: July 1998 Status: Revised Version: C/08.10.2003 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types Millenium 3 General Characteristics Millenium 3 Compact Range Millenium 3 Expandable Range Millenium 3 Communication Options Millenium 3 Range General environment characteristics for CB, CD, XD, XR and

More information

TM3SAC5RG SAFETY MODULE FOR PLC TM2xx, 1 FUNCTION, CAT3, SPRING TERMINALS

TM3SAC5RG SAFETY MODULE FOR PLC TM2xx, 1 FUNCTION, CAT3, SPRING TERMINALS Characteristics SAFETY MODULE FOR PLC TM2xx, 1 FUNCTION, CAT3, SPRING TERMINALS Main Range of product Product or component type Device short name Safety module application Function of module Jun 29, 2018

More information

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O Characteristics star-delta timing relay - 230VAC/440VAC - 1 C/ O Main Range of product Product or component type Discrete output type Device short name Nominal output current Zelio Time Modular timing

More information

Protection and control. Sepam range Sepam 100 RT. Merlin Gerin Square D Telemecanique

Protection and control. Sepam range Sepam 100 RT. Merlin Gerin Square D Telemecanique Protection and control epam range epam T Merlin Gerin quare D Telemecanique presentation contents page presentation connection characteristics installation ordering information epam T. on in in in in in

More information

TM3SAF. Main. Device short name

TM3SAF. Main. Device short name Product datasheet Characteristics TM3SAF5R SAFETY MODULE FOR PLC TM2xx, 1 FUNCTION, CAT4, SCREW TERMINALS Complementary Main Range of product Product or component type Device short name Safety module application

More information

INGEPAC DA-CU. Control Unit. Data Sheet ZY8932IMA01E 31/03/2016

INGEPAC DA-CU. Control Unit. Data Sheet ZY8932IMA01E 31/03/2016 ZY8932IMA01E 31/03/2016 INGEPAC DA-CU Control Unit Data Sheet Total or partial reproduction of this publication by any means or procedure is prohibited without previous express written authorisation by

More information

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Complementary Contacts material Width pitch dimension Control type Voltage range Connections - terminals Housing material Main Range

More information

MINER-S Station Controller. Substation Automation

MINER-S Station Controller. Substation Automation Substation Automation MINER-S Station Controller incorporates traditional RTU functions with new technology in a compact design MINER-S Station Controller combines the functions of a traditional RTU with

More information

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC Characteristics time delay relay for star-delta starter - 0.05..1 s - 24 V AC DC - 2OC Main Range of product Product or component type Contacts type and composition Component name Time delay type Time

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

GRE120. Motor Protection and Control for MV Systems

GRE120. Motor Protection and Control for MV Systems Motor Protection and Control for MV Systems FEATURES Overcurrent protection for phase and earth faults (50/51P, 50/51N). Dependent and independent time characteristics (IDMTL and DTL). Restricted earth

More information

Communication Gateway COM 610. Product Guide

Communication Gateway COM 610. Product Guide Communication Gateway COM 610 Product Guide Issued: September 2004 Status: Updated Version: D/17.10.2006 Data subject to change without notice Features Protocol conversion gateway for substation automation:

More information

ATS Automatic transfer switches Advanced version

ATS Automatic transfer switches Advanced version 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 ATS CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. ELECTRICAL AND MECHANICAL CHARACTERISTICS 2 5. CONFORMITY 4 6. EQUIPMENTS

More information

TM3DI16G module TM3-16 inputs spring

TM3DI16G module TM3-16 inputs spring Characteristics module TM3-16 inputs spring Main Range of product Product or component type Range compatibility Modicon TM3 Discrete input module Modicon M221 Modicon M241 Modicon M251 Discrete input number

More information

Type VRLTC tap changer

Type VRLTC tap changer Report No. 1ZUA938502-AGC 2, Rev 0 Date: 6 November 2012 Type VRLTC tap changer Ruggedized electronics systems specification & type test data Product Style No Rating By Type VRLTC, on-tank, vacuum reactance

More information

TM200C24R controller M IO relay

TM200C24R controller M IO relay Product datasheet Characteristics TM200C24R controller M200 24 IO relay Main Range of product Product or component type [Us] rated supply voltage Discrete I/O number 24 Discrete input number Discrete output

More information

Technical specifications

Technical specifications Technical specifications General information Operating temperature -25 to 60 C Storage temperature -40 to 70 C Enclosure type Panel installation (DIN IEC 61554) Enclosure fixing Screw-type clamping technology

More information

MINER-S Station Controller

MINER-S Station Controller MINER-S Station Controller Substation Automation MINER-S Station Controller The MINER-S Station Controller is a SCADA enabled fixed point remote terminal unit (RTU) with a data concentrator, event reporter,

More information

RE8TA31BU industrial timing relay s - type A - 24 V AC/DC, V AC - 1 C/O

RE8TA31BU industrial timing relay s - type A - 24 V AC/DC, V AC - 1 C/O Characteristics industrial timing relay - 0.3..30 s - type A - 24 V AC/DC, 110..240 V AC - 1 C/O Main Range of product Product or component type Component name Time delay type Time delay range [Us] rated

More information

Binary output and supervision 520CSD01 Data sheet

Binary output and supervision 520CSD01 Data sheet RTU520 product line Binary output and supervision 520CSD01 Data sheet R01 C01 O01 R02 O02 RTU I/O bus ERR Microcontroller RAM Flash IOC Output register DC DC (1 out of n) check Output state monitoring

More information

VAMP 11V. Voltage and Frequency Protection Relays. Protection

VAMP 11V. Voltage and Frequency Protection Relays. Protection 01 Voltage and Frequency Protection Relays is a basic numerical relay that provides reliable and effective voltage or voltage and frequency protection with automation, control and measurement functions.

More information

FL MC 2000E (SM40) LC

FL MC 2000E (SM40) LC IEC 61850 fiber optic converter with LC fiber optic connection (1310 nm) to convert 100Base-Tx to single- or multi-mode fiber glass Data sheet 3205_en_C 1 Description PHOENIX CONTACT 2014-04-04 2 Features

More information

RT4F-120V/20A-WAC RECTIFIER

RT4F-120V/20A-WAC RECTIFIER The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with

More information

RT7-48V/6kW Specification

RT7-48V/6kW Specification The RT7-48V/6kW is a 3 phase, active power factor corrected, switched mode rectifier (SMR) module designed to provide up to 6kW of output power (100A nominal) into a 48V nominal system. This rectifier

More information

TM221CE40R controller M IO relay Ethernet

TM221CE40R controller M IO relay Ethernet Product datasheet Characteristics TM221CE40R controller M221 40 IO relay Ethernet Main Range of product Product or component type [Us] rated supply voltage Discrete input number Analogue input number Discrete

More information