CSC-121 Breaker Protection IED Technical Application Manual

Size: px
Start display at page:

Download "CSC-121 Breaker Protection IED Technical Application Manual"

Transcription

1 CSC-121 Breaker Protection IED Technical Application Manual

2 Version:V1.01 Doc. Code: 0SF (E) Issued Date: Copyright owner: Beijing Sifang Automation Co., Ltd Note: the company keeps the right to perfect the instruction. If equipments do not agree with the instruction at anywhere, please contact our company in time. We will provide you with corresponding service. is registered trademark of Beijing Sifang Automation Co., Ltd. We reserve all rights to this document, even in the event that a patent is issued and a different commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is not permitted. This document has been carefully checked. If the user nevertheless detects any errors, he is asked to notify us as soon as possible. The data contained in this manual is intended solely for the IED description and is not to be deemed to be a statement of guaranteed properties. In the interests of our customers, we constantly seek to ensure that our products are developed to the latest technological standards as a result it is possible that there may be some differences between the hardware/software product and this information product. Manufacturer: Beijing Sifang Automation Co., Ltd. Tel: , ext Fax: sf_sales@sf-auto.com Website: Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C

3 Preface Purpose of this manual This manual describes the functions, operation, installation, and placing into service of IED CSC-121. In particular, one will find: Information on how to configure the IED scope and a description of the IED functions and setting options; Instructions for mounting and commissioning; Compilation of the technical specifications; A compilation of the most significant data for experienced users in the Appendix. Target Audience Protection engineers, commissioning engineers, personnel concerned with adjustment, checking, and service of selective protective equipment, automatic and control facilities, and personnel of electrical facilities and power plants. Applicability of this Manual This manual is valid for SIFANG Breaker Protection IED CSC-121; firmware version V1.00 and higher Indication of Conformity Additional Support In case of further questions concerning IED CSC-121 system, please contact SIFANG representative. Safety information Strictly follow the company and international safety regulations. Working in a high voltage environment requires serious approch to aviod human injuries and damage to equipment

4 Do not touch any circuitry during operation. Potentially lethal voltages and currents are present Avoid to touching the circuitry when covers are removed. The IED contains electirc circuits which can be damaged if exposed to static electricity. Lethal high voltage circuits are also exposed when covers are removed Using the isolated test pins when measuring signals in open circuitry. Potentially lethal voltages and currents are present Never connect or disconnect wire and/or connector to or from IED during normal operation. Dangerous voltages and currents are present. Operation may be interrupted and IED and measuring circuitry may be damaged Always connect the IED to protective earth regardless of the operating conditions. Operating the IED without proper earthing may damage both IED and measuring circuitry and may cause injuries in case of an accident. Do not disconnect the secondary connection of current transformer without short-circuiting the transformer s secondary winding. Operating a current transformer with the secondary winding open will cause a high voltage that may damage the transformer and may cause injuries to humans. Do not remove the screw from a powered IED or from an IED connected to power circuitry. Potentially lethal voltages and currents are present Using the certified conductive bags to transport PCBs (modules). Handling modules with a conductive wrist strap connected to protective earth and on an antistatic surface. Electrostatic discharge may cause damage to the module due to electronic circuits are sensitive to this phenomenon 4

5 Do not connect live wires to the IED, internal circuitry may be damaged When replacing modules using a conductive wrist strap connected to protective earth. Electrostatic discharge may damage the modules and IED circuitry When installing and commissioning, take care to avoid electrical shock if accessing wiring and connection IEDs Changing the setting value group will inevitably change the IEDs operation. Be careful and check regulations before making the change

6 Contents Chapter 1 Introduction Overview Features Functions Protection functions Monitoring functions Station communication IED software tools... 6 Chapter 2 General IED application Display information LCD screen display function Analog display function Report display function Menu dispaly function Report record Disturbance recorder Introduction Setting Self supervision function Introduction Self supervision principle Self supervision report Time synchronization Introduction Synchronization principle Synchronization from IRIG Synchronization via PPS or PPM Synchronization via SNTP Setting Introduction Operation principle Authorization Introduction Chapter 3 Overcurrent protection Overcurrent protection Introduction Protection principle Time characteristic Inrush restraint feature Direciton determination feature Logic diagram Input and output signals

7 1.4 Setting parameters Setting list Reports Technical data Chapter 4 Earth fault protection Earth fault protection Introduction Protection principle Time characteristic Inrush restraint feature Direction determination feature Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 5 Neutral earth fault protection Neutral earth fault protection Introduction Protection principle Time characteristic Inrush restraint feature Direction determination Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 6 Sensitive earth fault protection Sensitive earth fault protection Introduction Protection principle Time characteristic Direction determination feature Logic diagram Input and output signals Setting parameters Setting list IED report Technical data Chapter 7 Negative sequence overcurrent protection Negative sequence overcurrent protection... 68

8 1.1 Introduction Protection principle Protection function description Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 8 Thermal overload protection Thermal overload protection Introduction Function principle Function description Input and output signals Setting parameters Setting lists Reports Technical data Chapter 9 Overload protection Overload protection Protection principle Function description Logic diagram Input and output signals Setting parameters Setting lists Reports Chapter 10 Overvoltage protection Overvoltage protection Introduction Protection principle Phase to phase overvoltage protection Phase to earth overvlotage protection Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 11 Undervoltage protection Undervoltage protection Introduction Protection principle

9 1.2.1 Phase to phase underovltage protection Phase to earth undervoltage protection Depending on the VT location Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 12 Displacement voltage protection Displacement voltage protection Introduction Protection principle Function description Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 13 Circuit breaker failure protection Circuit breaker failure protection Introduction Function Description Current criterion evaluation Circuit breaker auxiliary contact evaluation Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 14 Dead zone protection Dead zone protection Introduction Protection principle Function description Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 15 STUB protection

10 1 STUB protection Introduction Protection principle Function description Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 16 Poles discordance protection Poles discordance protection Introdcution Protection principle Function description Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 17 Synchro-check and energizing check function Synchro-check and energizing check function Introduction Function principle Synchro-check mode Energizing check mode Override mode Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 18 Auto-reclosing function Auto- reclosing Introduction Function principle Single-shot reclosing Multi-shot reclosing AR coordination between tie CB and side CB Auto-reclosing operation mode Auto-reclosing initiation Cooperating with external protection IED

11 1.2.7 Auto-reclosing logic AR blocked conditions Logic diagram Input and output signals Setting parameters Setting lists Reports Technical data Chapter 19 Secondary system supervision Current circuit supervision Function description Input and output signals Setting parameters Setting lists Reports Fuse failure supervision Introduction Function principle Three phases (symmetrical) VT Fail Single/two phases (asymmetrical) VT Fail Logic diagram Input and output signals Setting parameters Setting list Reports Technical data Chapter 20 Monitoring Synchro-check reference voltage supervision Check auxiliary contact of circuit breaker Chapter 21 Station communication Overview Protocol IEC communication protocol IEC communication protocol Communication port Front communication port RS485 communication ports Ethernet communication ports Technical data Typical substation communication scheme Typical time synchronizing scheme Chapter 22 Hardware Introduction IED structure

12 1.2 IED module arrangement Local human-machine interface Introduction Liquid crystal display (LCD) LED Keyboard IED menu Menu construction Operation status Reports search Set time Contrast Settings IED setting Test binary output Testing operation Analog input module Introduction Terminals of analog input module Technical data Communication module Introduction Terminals of Communication module Substaion communication port RS232 communication ports RS485 communication ports Ethernet communication ports Time synchronization port Technical data Binary input module Introduction Terminals of Binary Input Module Technical data Binary output module Introduction Terminals of Binary Output Module Technical data Power supply module Introduction Terminals of Power Supply Module Technical data Techinical data Type tests Product safety-related tests

13 8.1.2 Electromagnetic immunity tests DC voltage interruption test Electromagnetic emission test Mechanical tests Climatic tests CE Certificate IED design Chapter 23 Appendix General setting list Function setting list Binary setting list General report list Typical connection Time inverse characteristic kinds of IEC and ANSI inverse time characteristic curves User defined characteristic Typical inverse curves CT requirement Overview Current transformer classification Abbreviations (according to IEC , -6, as defined) General current transformer requirements Protective checking current CT class Accuracy class Ratio of CT Rated secondary current Secondary burden Rated equivalent secondary e.m.f requirements Line differential protection Transformer differential protection Busbar differential protection Distance protection Definite time overcurrent protection and earth fault protection Inverse time overcurrent protection and earth fault protection

14

15 Chapter 1 Introduction Chapter 1 Introduction About this chapter This chapter gives an overview of SIFANG Breaker Protection IED CSC

16 Chapter 1 Introduction 1 Overview The CSC-121 is selective, reliable and high speed breaker management and backup protection IED (Intelligent Electronic Device), which is used as backup protection cooperating with main protection in different applications such as overhead line, cable, transformer, reactor and busbar protection. It can also work as a dedicated breaker management relay for circuit breaker. The IED has powerful capabilities to cover following applications: Used in a wide range of voltage levels, up to 1000kV Applied to overhead lines and cables, as backup protection IED Applicable in subtransmission network and distribution network Applied to transformer as backup protection IED Breaker management protection for any substation arrangement such as one and half breakers arrangement, double bus arrangement, etc. Work as a dedicated breaker protection for single circuit breaker Suitable for single pole/three poles tripping and closing conditions Communication with station automation system The IED provides a completely protection functions library, including current protection, voltage protection, auto-reclosing, breaker failure protection, thermal overload protection, etc., to cover most of the requirements of different applications. 2

17 Chapter 1 Introduction 2 Features Protection and monitoring IED with extensive functional library, user configuration possibility and expandable hardware design to meet with user s special requirements A complete protection functions library, include: Overcurrent protection (50, 51, 67) Earth fault protection (50N, 51N, 67N) Neutral earth fault protection (50G, 51G, 67G) Sensitive earth fault protection (50Ns, 51Ns, 67Ns) Negative-sequence overcurrent protection (46) Thermal overload protection (49) Overload protection (50OL) Overvoltage protection (59) Undervoltage protection (27) Displacement voltage protection (64) Circuit breaker failure protection (50BF) Poles discordance protection (50PD) Dead zone protection (50SH-Z) STUB protection (50STUB) Synchro-check and energizing check (25) Auto-recloser function for single- and/or three-phase reclosing (79) Voltage transformer secondary circuit supervision (97FF) Current transformer secondary circuit supervision Self-supervision to all modules in the IED Complete information recording: tripping reports, alarm reports, startup reports and general operation records. Any kind of reports can be stored up to 2000 and be memorized in case of power disconnection Up to three electric/optical Ethernet ports can be selected to communicate with substation automation system by IEC61850 or IEC protocols Up to two electric RS-485 ports can be selected to communicate with 3

18 Chapter 1 Introduction substation automation system by IEC protocol Time synchronization via network(sntp), pulse and IRIG-B mode Configurable LEDs (Light Emitting Diodes) and output relays satisfied users requirement Versatile human-machine interface Multifunctional software tool CSmart for setting, monitoring, fault recording analysis, configuration, etc. 4

19 Chapter 1 Introduction 3 Functions 3.1 Protection functions Description ANSI Code IEC Logical Node Name IEC graphical symbol Current protection Overcurrent protection 50,51,67 PTOC Earth fault protection 50N, 51N, 67N PEFM 3I INV > 3I >> 3I >>> I 0INV > I 0 >> I 0 >>> Neutral earth fault protection Sensitive earth fault protection Negative-sequence overcurrent protection 50G, 51G, 67G 50Ns, 51Ns, 67Ns 46 3I NE > 3I NE >> Thermal overload protection 49 PTTR Ith Overload protection 50OL PTOC 3I >OL Voltage protection Overvoltage protection 59 PTOV Undervoltage protection 27 PTUV 3U> 3U>> 3U< 3U<< Displacement voltage protection 64 V E > Breaker control function Breaker failure protection 50BF RBRF 3I> BF I 0 >BF I 2 >BF Dead zone protection 50SH-Z STUB protection 50STUB PTOC 3I>STUB Poles discordance protection 50PD RPLD 3I< PD I 0 >PD I 2 >PD Synchro-check and energizing check 25 RSYN Auto-recloser 79 RREC O I 5

20 Chapter 1 Introduction Description ANSI Code IEC Logical Node Name Single- and/or three-pole tripping 94-1/3 PTRC IEC graphical symbol CT secondary circuit supervision Secondary system supervision VT secondary circuit supervision 97FF 3.2 Monitoring functions Description Synchro-check reference voltage supervision Auxiliary contacts of circuit breaker supervision Self-supervision Fault recorder 3.3 Station communication Description Front communication port Isolated RS232 port Rear communication port 0-2 isolated electrical RS485 communication ports 0-3 Ethernet electrical/optical communication ports Time synchronization port Communication protocols IEC protocol IEC protocol 3.4 IED software tools Functions 6

21 Chapter 1 Introduction Functions Reading measuring value Reading IED report Setting IED testing Disturbance recording analysis IED configuration Printing 7

22 Chapter 1 Introduction 8

23 Chapter 2 General IED application Chapter 2 General IED application About this chapter This chapter describes the use of the included software functions in the IED. The chapter discusses general application possibilities. 9

24 Chapter 2 General IED application 1 Display information 1.1 LCD screen display function The LCD screen displays measured analog, report ouputs and menu. 1.2 Analog display function The analog display includes measured Ia, Ib, Ic, 3I0, I5, Ua, Ub, Uc, U4 1.3 Report display function The report display includes tripping, alarm and operation recording. 1.4 Menu dispaly function The menu dispaly includes main menu and debugging menu, see chapter Chapter 22 for detail. 10

25 2 Report record Chapter 2 General IED application The report record includes tripping, alarm and operation reports. See Chapter 23 General report list for detail. 11

26 Chapter 2 General IED application 3 Disturbance recorder 3.1 Introduction To get fast, complete and reliable information about fault current, voltage, binary signal and other disturbances in the power system is very important. This is accomplished by the disturbance recorder function and facilitates a better understanding of the behavior of the power system and related primary and secondary equipment during and after a disturbance. An analysis of the recorded data provides valuable information that can be used to explain a disturbance, basis for change of IED setting plan, improvement of existing equipment etc. The disturbance recorder, always included in the IED, acquires sampled data from measured analogue quantities, calculated analogue quantity, binary input and output signals. The function is characterized by great flexibility and is not dependent on the operation of protection functions. It can even record disturbances not tripped by protection functions. The disturbance recorder information is saved for each of the recorded disturbances in the IED and the user may use the local human machine interface or dedicated tool to get some general information about the recordings. The disturbance recording information is included in the disturbance recorder files. The information is also available on a station bus according to IEC and IEC Fault wave recorder with great capacity, can record full process of any fault, and can save the corresponding records. Optional data format or wave format is provided, and can be exported through serial port or Ethernet port by COMTRADE format. 3.2 Setting Abbr. Explanation Default Unit Min. Max. T_Pre Fault Time setting for recording time before fault occurred 0.05 s T_Post Fault Time setting for recording time after fault occurred 1 s DR_Sample Rate Sample rate for fault recording

27 Chapter 2 General IED application Abbr. Explanation Default Unit Min. Max. (0: 600 sample/cycle, 1:1200 sample/cycle) 13

28 Chapter 2 General IED application 4 Self supervision function 4.1 Introduction The IED may test all hardware components itself, including loop out of the relay coil. Watch can find whether or not the IED is in fault through warning LED and warning characters which show in liquid crystal display and display reports to tell fault type. The method of fault elimination is replacing fault board or eliminating external fault. 4.2 Self supervision principle Measuring the resistance between analog circuits and ground Measuring the output voltage in every class Checking the zero drift and scale Verifying alarm circuit Verifying binary input Checking actual live tripping including circuit breaker Checking the setting values and parameters 4.3 Self supervision report Table 1 Self supervision report Abbr.(LCD Display) Sample Err Soft Version Err EquipPara Err ROM Verify Err Setting Err Set Group Err BO No Response Description AI sampling data error Soft Version error Equipment parameter error CRC verification for ROM error Setting value error Pointer of setting group error Binary output (BO) no response 14

29 Chapter 2 General IED application Abbr.(LCD Display) BO Breakdown SRAM Check Err FLASH Check Err BI Config Err BO Config Err BI Comm Fail BO Comm Fail Test BO Un_reset BI Breakdown DI Input Err NO/NC Discord BI Check Err BI EEPROM Err BO EEPROM Err Sys Config Err Battery Off Meas Freq Alarm Not Used Trip Fail PhA CB Open Err PhB CB Open Err PhC CB Open Err 3Ph Seq Err AI Channel Err 3I0 Reverse 3I0 Imbalance Description Binary output (BO) breakdown SRAM check error FLASH check error BI configuration error BO configuration error BI communication error BO communication error Test BO unreset BI breakdown BI input error NO/NC discordance BI check error BI EEPROM error BO EEPROM error System Configuration Error Battery Off Measurement Frequency Alarm Not used Trip fail PhaseA CB position BI error PhaseB CB position BI error PhaseC CB position BI error Three phase sequence error AI channel error 3I0 reverse 3I0 imbalance 15

30 Chapter 2 General IED application 5 Time synchronization 5.1 Introduction Use the time synchronization source selector to select a common source of absolute time for the IED when it is a part of a protection system. This makes comparison of events and disturbance data between all IEDs in a SA system possible. 5.2 Synchronization principle Time definitions The error of a clock is the difference between the actual time of the clock, and the time the clock is intended to have. The rate accuracy of a clock is normally called the clock accuracy and means how much the error increases, i.e. how much the clock gains or loses time. A disciplined clock is a clock that knows its own faults and tries to compensate for them, i.e. a trained clock. Synchronization principle From a general point of view synchronization can be seen as a hierarchical structure. A module is synchronized from a higher level and provides synchronization to lower levels. A module is said to be synchronized when it periodically receives synchronization messages from a higher level. As the level decreases, the accuracy of the synchronization decreases as well. A module can have 16

31 Chapter 2 General IED application several potential sources of synchronization, with different maximum errors, which gives the module the possibility to choose the source with the best quality, and to adjust its internal clock from this source. The maximum error of a clock can be defined as a function of: The maximum error of the last used synchronization message The time since the last used synchronization message The rate accuracy of the internal clock in the module Synchronization from IRIG The built in GPS clock module receives and decodes time information from the global positioning system. The module is located on the Communication Module (MASTER). The GPS interfaces to the IED supply two possible synchronization methods, IRIGB and PPS (or PPM) Synchronization via PPS or PPM The IED accepts PPS or PPM to the GPS interfaces on the Communication Module. These pulses can be generated from e.g. station master clock. If the station master clock is not synchronized from a world wide source, time will be a relative time valid for the substation. Both positive and negative edges on the signal can be accepted. This signal is also considered as a fine signal Synchronization via SNTP SNTP provides a Ping-Pong method of synchronization. A message is sent from an IED to an SNTP-server, and the SNTP-server returns the message after filling in a reception time and a transmission time. SNTP operates via the normal Ethernet network that connects IEDs together in an IEC61850 network. For SNTP to operate properly, there must be a SNTP-server present, preferably in the same station. The SNTP synchronization provides an accuracy that will give 1ms accuracy for binary inputs. The IED itself can be set as a SNTP-time server. 17

32 Chapter 2 General IED application 6 Setting 6.1 Introduction Settings are divided into separate lists according to different functions. The printed setting sheet consists of two parts -setting list and communication parameters. 6.2 Operation principle The setting procedure can be ended at the time by the key SET or QUIT. If the key SET is pressed, the display shows the question choose setting zone. The range of setting zone is from 1 to 16. After confirming with the setting zone-key SET, those new settings will be valid. If key QUIT is pressed instead, all modification which have been changed will be ignored. 18

33 7 Authorization 7.1 Introduction Chapter 2 General IED application To safeguard the interests of our customers, both the IED and the tools that are accessing the IED are protected, subject of authorization handling. The concept of authorization, as it is implemented in the IED and the associated tools is based on the following facts: There are two types of points of access to the IED: local, through the local HMI remote, through the communication ports There are different levels (or types) of guest, super user and protection engineer that can access or operate different areas of the IED and tools functionality. 19

34 Chapter 2 General IED application 20

35 Chapter 3 Overcurrent protection Chapter 3 Overcurrent protection About this chapter This chapter describes the protection principle, input and output signals, parameter, IED report and technical data used for overcurrent protection. 21

36 Chapter 3 Overcurrent protection 1 Overcurrent protection 1.1 Introduction The directional/non-directional overcurrent protection function can be applied as backup protection functions in various applications for transmission lines. The directional overcurrent protection can be used based on both the magnitude of the fault current and the direction of power flow to the fault location such as parallel lines. Main features of the overcurrent protection are as follows: Two definite time stages One inverse time stage 11 kinds of IEC and ANSI inverse time characteristic curves as well as optional user defined characteristic Selectable directional element characteristic angle to satisfy the different network conditions and applications Each stage can be set individually as directional/non-directional, Directional element can be set to be forward toward the protected object or reverse toward system for all stages Each stage can be set individually for inrush restraint Cross blocking function for inrush detection Settable maximum inrush current VT secondary circuit supervision for directional protection. Once VT failure happens, the directional stage can be set to be blocked or to be non-directional stage 1.2 Protection principle Time characteristic The IED is designed with three overcurrent protection stages of which two 22

37 Chapter 3 Overcurrent protection stages operate as definite overcurrent stages and the other one operates with inverse time-current characteristic. 11 kinds of inverse time characteristics are available. It is also possible to create a user defined time characteristic. Each stage can operate in conjunction with the integrated inrush restraint, directional functions and operate based on measured phase current. Furthermore, each stage is independent from each other and can be combined as desired. Pickup value for the definite stage can be set in setting value. Each phase current is compared with the corresponding setting value with delay time. If currents exceed the associated pickup value, after expiry of the time delay, the trip command is issued. The pickup value for inverse time stage can be set in setting value. The measured phase currents are compared with corresponding setting value and if any phase exceeds that setting, the protection will issue a trip command with corresponding delay time. The time delay of inverse time characteristic is calculated based on the type of the set characteristic, the magnitude of the current and a time multiplier. For the inverse time characteristic, both ANSI and IEC based standard curves are available, and any user-defined characteristic can be defined using the following equation: t = i I_OC A_OC p _OC 1 + B_OC K_OC Equation 1 where: A_OC: Time factor for inverse time stage B_OC: Delay time for inverse time stage P_OC: index for inverse time stage K_OC: Time multiplier Inrush restraint feature The IED may detect large magnetizing inrush currents during transformer energizing. Inrush current comprises large second harmonic current which 23

38 Chapter 3 Overcurrent protection does not appear in short circuit current. Therefore, inrush current may affect the protection functions which will operate based on the fundamental component of the measured current. Accordingly, inrush restraint logic is provided to prevent overcurrent protection from maloperation. The inrush restraint feature operates based on evaluation of the 2 nd harmonic content which is present in measured current. The inrush condition is recognized when the ratio of second harmonic current to fundamental component exceeds the corresponding setting value for each phase. The setting value is applicable for both definite time stage and inverse time stage. The inrush restraint feature will be performed as soon as the ration exceeds the set threshold. Furthermore, by recognition of the inrush current in one phase, it is possible to set the protection in a way that not only the phase with the considerable inrush current, but also the other phases are blocked for a certain time. This is achieved by cross-blocking feature integrated in the IED. The inrush restraint function has a maximum inrush current setting. Once the measuring current exceeds the setting, the overcurrent protection will not be blocked any longer Direciton determination feature The direction detection is performed by determining the position of current vector in directional characteristic. In other word, it is done by comparing phase angle between the fault current and the reference voltage. Figure 1 illustrates the direction detection characteristic for phase A element. Two operation areas are provided for direction determination, the forward area toward the protected object and the reverse area toward the system, which are shown in Figure 1. Forward 90 I A ΦPh_Char 0 U BC_Ref I A Reverse 24

39 Chapter 3 Overcurrent protection Figure 1 Direction detection characteristic of overcurrent protection directional element where: Ф Ph _Char: The settable characteristic angle The assignment of the applied measuring values used in direction determination shows in Table 2 for different types of faults. Table 2 Assignment of current and reference voltage for directional element Phase Current Voltage A B C I a Ib I c U bc U ca U ab For three-phase short-circuit fault, without any healthy phase, memory voltage values are used to determine direction clearly if the measured voltage values are not sufficient. The detected direction is based on the memory voltage of previous power cycles. If VT fail happen (a short circuit or broken wire in the voltage transformer's secondary circuit or voltage transformer fuse), the protection can be set to be blocked or to be applied as non-directional overcurrent protection Logic diagram The following logic diagram is applicable for phase A. Phase B and phase C logic diagrams are similar with the phase A logic. 25

40 Chapter 3 Overcurrent protection Ia>I_OC1 OC Dir To Sys VT fail AND 1 OC1 Direction Off OC1 Direction On AND OC Dir To Equip VT fail AND OR 0 OC1 Inrush Block Off <Imax_2H_UnBlk Ia2/Ia1> AND OC1 Inrush Block On T_OC1 0 OC_Inrush Block Off AND Func_OC1 Trip Cross blocking OC_Inrush Block On Ia2/Ia1 > Ib2/Ib1 > OR Ic2/Ic1 > AND Cross blocking T2h_Cross_Blk< Figure 2 Logic diagram for phase A of overcurrent protection 1.3 Input and output signals 26

41 Chapter 3 Overcurrent protection IP1 IP2 IP3 UP1 UP2 UP3 Relay Startup OC1_Trip OC2_Trip OC Inv Trip Table 3 Analog input list Signal Description IP1 Signal for current input 1 IP2 Signal for current input 2 IP3 Signal for current input 3 UP1 Signal for voltage input 1 UP2 Signal for voltage input 2 UP3 Signal for voltage input 3 Table 4 Binary output list Signal Relay Startup Trip 3Ph OC1_Trip OC2_Trip OC Inv Trip Description Relay startup Trip three phases Overcurrent protection stage 1 trip Overcurrent protection stage 2 trip Overcurrent protection inverse time stage trip 1.4 Setting parameters Setting list Table 5 Overcurrent protection function setting list Parameter Description Default Unit Min. Max. I_OC1 Current setting for stage 1 2In A T_OC1 Time setting for stage s I_OC2 Current setting for stage 2 1.2In A T_OC2 Time setting for stage s Curve_OC Inv Inverse time curve I_OC Inv Current setting for inverse time 1.2In A

42 Chapter 3 Overcurrent protection Parameter Description Default Unit Min. Max. stage K_OC Inv Time multiplier for inverse time stage A_OC Inv Time factor for inverse time stage 0.14 s B_OC Inv Delay time for inverse time stage 0 s P_OC Inv Index for inverse time stage Angle_OC Direction characteristic angle 60 Degree Imax_2H_UnBlk Maximum inrush current setting 5In A Ratio_I2/I1 Ratio for second harmonic current to fundamental component T2h_Cross_Blk Time for cross blocking 1 s Table 6 Overcurrent protection binary setting list Name Description Default Unit Min. Max. Func_OC1 OC1 Direction OC1 Dir To Sys OC1 Inrush Block Func_OC2 OC2 Direction OC2 Dir To Sys OC2 Inrush Block Func_OC Inv OC Inv Direction OC Inv Dir To Sys OC Inv Inrush Block Overcurrent stage 1 enabled or disabled Direction of overcurrent stage 1 enabled or disabled Direction toward system (0) or toward equipment (1) for stage Inrush restraint for overcurrent stage 1 enabled or disabled Overcurrent stage 2 enabled or disabled Direction of overcurrent stage 2 enabled or disabled Direction toward system (0) or toward equipment (1) for stage Inrush restraint for overcurrent stage 2 enabled or disabled Inverse time stage for overcurrent enabled or disabled Direction of inverse time stage enabled or disabled Direction toward system (0) or toward equipment (1) for inverse time stage Inrush restraint for inverse time stage enabled or disabled Blk OC at VT VT failure block overcurrent protection

43 Chapter 3 Overcurrent protection Name Description Default Unit Min. Max. Fail enabled or disabled OC Init CBF Overcurrent protection initiate CBF protection enabled or disabled Reports Table 7 Event report list Information OC1 Trip OC2 Trip OC Inv Trip Description Overcurrent stage 1 trip Overcurrent stage 2 trip Inverse time stage of overcurrent protection trip 1.6 Technical data NOTE: Ir: CT rated secondary current, 1A or 5A; In: nominal current of the reference side of transformer; Table 8 Overcurrent protection technical data Item Rang or Value Tolerance Definite time characteristics Current 0.08 Ir to Ir ±3% setting or ±0.02Ir Time delay 0.00 to 60.00s, step 0.01s Reset time approx. 40ms Reset ratio Approx at I/In 0.5 Inverse time characteristics ±1% setting or +40ms, at 200% operating setting Current 0.08 Ir to Ir ±3% setting or ±0.02Ir IEC standard ANSI Normal inverse; Very inverse; Extremely inverse; Long inverse Inverse; Short inverse; Long inverse; Moderately inverse; Very inverse; Extremely inverse; ±5% setting + 40ms, at 2 <I/I SETTING < 20, in accordance with IEC ±5% setting + 40ms, at 2 <I/ISETTING < 20, in accordance with ANSI/IEEE C37.112, 29

44 Chapter 3 Overcurrent protection Definite inverse user-defined characteristic T= A + B k ±5% setting + 40ms, at 2 i ( I_SET )P 1 <I/I SETTING < 20, in accordance with IEC Time factor of inverse time, to 200.0s, step 0.001s A Delay of inverse time, B to 60.00s, step 0.01s Index of inverse time, P to 10.00, step set time Multiplier for step n: 0.05 to 999.0, step 0.01 k Minimum operating time Maximum operating time Reset mode Reset time 20ms 100s instantaneous approx. 40ms, Directional element Operating area range 170 ±3, at phase to phase Characteristic angle 0 to 90, step 1 voltage >1V Table 9 Inrush restraint function Item Range or value Tolerance Upper function limit Max current for inrush 0.25 Ir to Ir ±3% setting value or ±0.02Ir restraint Ratio of 2 nd harmonic current 0.10 to 0.45, step 0.01 to fundamental component current Cross-block (IL1, IL2, IL3) 0.00s to s, step 0.01s ±1% setting or +40ms (settable time) 30

45 Chapter 4 Earth fault protection Chapter 4 Earth fault protection About this chapter This chapter describes the protection principle, input and output signals, parameter, IED report and technical data used for earth fault protection. 31

46 Chapter 4 Earth fault protection 1 Earth fault protection 1.1 Introduction The earth fault protection can be used to clear phase to earth faults as system back-up protection. The earth fault protection is can also be applied for coordination based on both magnitude of earth fault current and the direction of power flow to the fault location. The protection provides the following features: Two definite time stages One inverse time stage 11 kinds of the IEC and ANSI inverse time characteristic curves as well as optional user defined characteristic Zero sequence directional element Negative sequence directional element can be applied as a supplement to zero sequence directional element. It can be enabled/disabled by setting Each stage can be set individually as directional/non-directional Directional element can be set to be forward toward the protected object or reverse toward system for all stages Settable directional element characteristic angle to satisfy the different network conditions and applications Each stage can be set individually for inrush restraint Settable maximum inrush current VT secondary circuit supervision for directional protection function. Once VT failure happens, the directional stage can be set to be blocked or to be non-directional Zero-sequence current is calculated using summation of 3 phase currents or measured from 4 th phase CT (selectable) 32

47 Chapter 4 Earth fault protection Zero-sequence voltage calculated by summation of 3 phase voltage or measured from earth phase VT selectable 1.2 Protection principle Time characteristic The IED is designed with three earth fault protection stages of which two stages operate as definite earth fault stages and the other one operates with inverse time-current characteristic. All stages can operate in conjunction with the integrated inrush restraint and directional functions. This protection function can operate based on the zero-sequence current which is calculated by summation of three phase currents or measured from earth phase CT Furthermore, the stages are independent from each other and can be combined as desired. They can be enabled or disabled by dedicated binary setting. Individual pickup value for each definite stage can be defined in setting value. By applying the settings, the measured zero sequence current is compared separately with the setting value for each stage. If zero-sequence current exceed the associated pickup value, after expiry of the time delay, the trip command is issued. The time delay of inverse time characteristic is calculated based on the type of the set characteristic, the magnitude of the current and a time multiplier. For the inverse time characteristic, both ANSI and IEC based standard curves are available, and any user-defined characteristic can be defined using the following equation: t = i I_EF A_EF p _EF 1 + B_EF K_EF Equation 2 where: A_EF: Time factor for inverse time stage B_EF: Delay time for inverse time stage P_EF: index for inverse time stage 33

48 Chapter 4 Earth fault protection K_EF: Time multiplier The time is set to count up for a user-defined time delay. The time delay can be set for each definite stage individually through corresponding settings. After the user-defined time delays elapsed, a trip command is issued Inrush restraint feature The IED may detect large magnetizing inrush currents during transformer energizing. Inrush current comprises large second harmonic current which does not appear in short circuit current. Therefore, inrush current may affect the protection functions which will operate based on the fundamental component of the measured current. Accordingly, inrush restraint logic is provided to prevent earth fault protection from maloperation. The inrush restraint feature operates based on evaluation of the 2 nd harmonic content which is present in measured current. The inrush condition is recognized when the ratio of second harmonic current to fundamental component exceeds the corresponding setting value for each phase. The condition for phase current inrush or zero sequence current inrush can be selected by binary setting. The setting value is applicable for both definite time stage and inverse time stage. The inrush restraint feature will be performed as soon as the ratio exceeds the set threshold. The inrush restraint function has a maximum inrush current setting. Once the measuring current exceeds the setting, the earth fault protection will not be blocked any longer Direction determination feature The integrated directional function can be applied to each stage of earth fault element via binary setting. There are two direction elements for direction determination of earth faults. The first is based on zero sequence components and the second is based on negative sequence components. During direction determination by directional function (using zero or negative sequence components), a VT fail condition may result in false or undesired tripping by directional earth fault element. Therefore, under the VT failure situation, it can be set to block directional earth fault protection or to apply non-directional earth fault protection. The following subsections go on to demonstrate basic principle of these two direction element. 34

49 Chapter 4 Earth fault protection Zero sequence directional element In this method, the direction determination is performed by comparing the zero sequence quantities. In current path, the zero sequence current is calculated from the sum of the three phase currents or measured from earth CT. In the voltage path, the zero sequence voltage (3U 0 ) is used as reference voltage if it is connected. Otherwise, the zero sequence voltage, is calculated from the sum of the three phase voltages. In order to satisfy different network conditions and applications, the reference voltage can be rotated by adjustable angle between 0 and 90 in clockwise direction (negative sign). It should be noted that the settings affect all the directional stages of earth fault element. In this way, the vector of rotated reference voltage can be closely adjusted to the vector of fault current -3I0 which lags the fault voltage 3V 0 by the fault angle Φ 0 _Char. This would provide the best possible result for the direction determination. The rotated reference voltage defines the forward and reverse area. Figure 3 shows an example of direction determination. Bisector -3I0 90 Reverse 0 3U0_Ref Φ0_Char Forward -3I 0 Bisector Figure 3 Direction detection characteristic of earth fault protection directional element Negative sequence directional element This method is particularly suitable in case of too low zero sequence voltage due to some fault condition e.g. when a considerable zero sequence mutual coupling exists between parallel lines or there is an unfavorable zero sequence impedance. In such cases it may be desirable to determine direction of fault current by using negative sequence components. To do so, it is required to enable the negative sequence directional element in setting 35

50 Chapter 4 Earth fault protection value. By applying this setting, the default direction determination of earth fault current is performed by the zero sequence element. However, when the magnitude of zero sequence voltage falls below permissible threshold of 1V and negative sequence voltage is larger than 2V, the negative sequence element is in service for direction determination. On the contrary, if the negative sequence directional element is disabled, the direction of earth fault current is only determined by using the zero sequence element. In this regard, if the zero sequence voltage has a magnitude larger than 1V, proper determination of fault direction is performed. However, for the condition that zero sequence voltages below 1V, no direction determination would be possible. Thus, the fault is assumed to be in reverse direction. Accordingly, for the negative sequence element, the direction determination is performed by comparing the negative sequence system quantities. To do so, three times of the calculated negative sequence current 3I 2 (3I 2 =I A +a 2 I B +ai C ) is compared with three times of the calculated negative sequence voltage 3V 2 (3V 2 =V A +a 2 V B +av C ) as reference voltage, where a is equal to e j120. The fault current -3I 2 is opposite to the fault current 3I 2 and lags from the voltage 3V 2 by the fault angle, which is a setting value defined in setting value. In order to satisfy different applications, the reference voltage can be rotated by adjustable angle between 0 and 90 in clockwise direction (negative sign) to be closely adjusted to the vector of fault current -3I 2. This would provide the best possible result for the direction determination. The rotated reference voltage defines the forward and reverse area. Figure 4 shows an example of direction determination. Bisector -3I 2 90 Reverse 0 3U 2_ Ref Φ2_Char Forward -3I 2 Bisector Figure 4 Direction detection characteristic of negative sequence directional element Logic diagram 36

CSC-150 Busbar Protection IED Technical Application Manual

CSC-150 Busbar Protection IED Technical Application Manual CSC-150 Busbar Protection IED Technical Application Manual CSC-150 Busbar Protection IED Technical Application Manual Compiled: Jin Rui Checked: Hou Changsong Standardized: Li Lianchang Inspected: Cui

More information

CSC-150 Busbar Protection IED Technical Application Manual

CSC-150 Busbar Protection IED Technical Application Manual CSC-150 Busbar Protection IED Technical Application Manual CSC-150 母线保护装置 技术应用说明书 编制 : 校核 : 标准化审查 : 审定 : 版本号 :V1.02 文件代号 : 出版日期 :2015.9 Version:V1.02 Doc. Code: 0SF.450.087(E) Issued Date:2015.9 Copyright

More information

CSC-121 Breaker Protection IED Product Guide

CSC-121 Breaker Protection IED Product Guide CSC-121 Breaker Protection IED Product Guide Version V1.10 Doc. Code: 0SF.492.053(E) Issued Date 2012.8 Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect

More information

CSC-211 Multifunction Protection IED Product Guide

CSC-211 Multifunction Protection IED Product Guide CSC-211 Multifunction Protection IED Product Guide Version V1.0 Doc. Code: 0SF.492.057(E) Issued Date 201. Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect

More information

CSC-161 Line Protection IED Product Guide

CSC-161 Line Protection IED Product Guide CSC-161 Line Protection IED Product Guide Version V1.10 Doc. Code: 0SF.492.052(E) Issued Date 2012.8 Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect the

More information

CSC-211 Multifunction Protection IED Product Guide

CSC-211 Multifunction Protection IED Product Guide CSC-211 Multifunction Protection IED Product Guide Version:V1.20 Doc. Code: 0SF.492.057(E) Issued Date:2013.12 Copyright owner: Beijing Sifang Automation Co., Ltd Note: The company keeps the right r to

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms modules

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

CSC-326 Transformer Protection IED Engineering and Operation Manual

CSC-326 Transformer Protection IED Engineering and Operation Manual CSC-326 Transformer Protection IED Engineering and Operation Manual CSC-326 Transformer Protection IED Engineering and Operation Manual Compiled: Jin Rui Checked: Hou Changsong Standardized: Li Lianchang

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

Siprotec 7ST61 / 7ST63

Siprotec 7ST61 / 7ST63 Siprotec / Numerical overhead contact line protection for AC traction power supply siemens.de/rail-electrification The numerical overhead contact line protection relay Siprotec / is a selective and quick

More information

CSC-150 Busbar Protection IED Product Guide

CSC-150 Busbar Protection IED Product Guide CSC-150 Busbar Protection IED Product Guide Version V1.0 Doc. Code: 0SF.492.056(E) Issued Date 201. Copyright owner: Beijing Sifang Automation Co., Ltd. Note: The company keeps the right to perfect the

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

TWO-WINDING TRANSFORMER DIFFERENTIAL

TWO-WINDING TRANSFORMER DIFFERENTIAL E3-TR PROTECTION WITH AUTOMATIC VOLTAGE Because of the control, measuring and monitoring functions implemented, the IED can also be used as a bay control unit. The EuroCAP configuration tool, which is

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

(1) Description of Operation 7SR224 Recloser Controller

(1) Description of Operation 7SR224 Recloser Controller (1) Description of Operation 7SR224 Recloser Controller DOCUMENTATION SET This document is part of a set. The full list of documents in the set, and the publication numbers under which they can be ordered,

More information

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL Circuit Breaker Failure Relay Operating Principle Revision: 2 from 2005-02-25 Edition: 2005-02-25 _CBF-description_eng.doc Page 1 /14 Table of Contents: 1 GENERAL DESCRIPTION 4 2 FUNCTIONAL DESCRIPTION

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 Content FPC 200 USER MANUAL Mar 2017 Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 1 USER MANUAL FPC 200-3/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

Recloser Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

Protection relays.

Protection relays. Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement

More information

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays 01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety

More information

InteliPro. Protection Relay for Parallel Applications. Technical Specification

InteliPro. Protection Relay for Parallel Applications. Technical Specification InteliPro Protection Relay for Parallel Applications Product description InteliPro is a highly flexible interconnection/mains decoupling protective relay with extensive protective functions. It meets the

More information

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits 01 MiCOM P721 & P723 Numerical High Impedance Differential Relay The new P72x high impedance differential protection series provides an independent and simple high impedance differential protection solution

More information

7SR11 and 7SR12 Description of Operation

7SR11 and 7SR12 Description of Operation 7SR11 and 7SR12 Description of Operation Document Release History This document is issue 2012/02. The list of revisions up to and including this issue is: 2012/02 AC auxiliary power supply added 2012/01

More information

GRD130 - FEATURES APPLICATION

GRD130 - FEATURES APPLICATION FEATURES Phase undervoltage protection with IDMTL or DTL. Phase overvoltage protection with IDMTL or DTL. Zero phase sequence overvoltage (neutral voltage displacement) protection with IDMTL/DTL. Negative

More information

Feeder/ Motor Protection Relay VAMP 40

Feeder/ Motor Protection Relay VAMP 40 Feeder/ Motor Protection Relay Feeder/motor protection relay Main characteristics Complete protection Comprehensive selection of protection functions for distribution network overhead line feeders, cable

More information

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4 Content FPC 400 USER MANUAL Apr 2017 Feeder F3 Motor M4 Busbar B3 Transformer T4 1 USER MANUAL FPC 400-4/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia 2016. All rights reserved.

More information

SIPROTEC. Numerical Overhead Contact Line Protection for AC Traction Power Supply 7ST6. Preface. Introduction 1. Functions 2

SIPROTEC. Numerical Overhead Contact Line Protection for AC Traction Power Supply 7ST6. Preface. Introduction 1. Functions 2 SIPROTEC Numerical Overhead Contact Line Protection for AC Traction Power Supply 7ST6 V4.2 Manual Preface Introduction 1 Functions 2 Mounting and Commissioning 3 Technical Data 4 Appendix Literature Glossary

More information

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

CSC-326 Transformer Protection IED Product Guide

CSC-326 Transformer Protection IED Product Guide CSC-326 Transformer Protection IED Product Guide Version:V1.11 Doc. Code: 0SF.492.054(E) Issued Date: 2013.12 Copyright owner: Beijing Sifang Automation Co., Ltd Note: The company keeps the t right to

More information

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection

More information

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 PC83 and PC830 series devices are designed to perform the relay protection functions and 6-154 kv networks automation, have different functionality

More information

Feeder protection relay

Feeder protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay modules and a flexible

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

DRS-LIGHT. Device Description DRS-LP824. Digital Unit Decoupling Relay Type DRS-LP824. Device Description DIL

DRS-LIGHT. Device Description DRS-LP824. Digital Unit Decoupling Relay Type DRS-LP824. Device Description DIL DRS-LIGHT Digital Unit Decoupling Relay Type DRS-LP824 Device Description Edition:09.05.2008 SLLR_LP824_e.doc Page 1 /10 CAUTION Installing, commissioning and operating of this product may be performed

More information

DRTS 33. The new generation of advanced three phase relay test set

DRTS 33. The new generation of advanced three phase relay test set The new generation of advanced three phase relay test set Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Local control with color display Simultaneously available:

More information

Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Numerical motor protection in medium voltage networks Motor Protection and Control REM620 Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,

More information

NPI800 NPI800R. First Handling Guide. Phase and earth overcurrent relay

NPI800 NPI800R. First Handling Guide. Phase and earth overcurrent relay Phase and earth overcurrent relay FOREWORD The aim of this handbook is to provide to the User information useful for the commissioning and the tests of NPI800 and NPI800R relays, multifunction digital

More information

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES Introduction The supply of electrical energy occupies an important position in the life of modern society. Operation of commerce, industry, transport,

More information

750/760 Feeder Management Relay Instruction Manual

750/760 Feeder Management Relay Instruction Manual GE Digital Energy 750/760 Feeder Management Relay Instruction Manual Software Revision: 7.4x Manual P/N: 1601-0120-AK Manual Order Code: GEK-106471T GE Digital Energy 650 Markland Street Markham, Ontario

More information

MiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation

MiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation MiCOM P123R Overcurrent Relays Upgrade Documentation MiCOM P123R Page 1/14 CONTENTS MiCOM P123R ADDENDUM: MiCOM P12X UPDATE DOCUMENTATION 3 P12X/EN IT/EB6: INTRODUCTION 4 P12x/EN TD/Eb6: TECHNICAL DATA

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay 7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional

More information

GE Multilin 350 Feeder Protection Relay Specifications

GE Multilin 350 Feeder Protection Relay Specifications GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following

More information

PROTECTION, AUTOMATION & CONTROL

PROTECTION, AUTOMATION & CONTROL PROTECTION, AUTOMATION & CONTROL 1. DTIVA The members of the DTIVA product line are configured to protect and control the elements of not solidly grounded radial networks. Here the application of Petersen

More information

2 nd Edition INTRODUCTION

2 nd Edition INTRODUCTION 2 nd Edition INTRODUCTION TPU S220 compact protection and control relay, part of Efacec CLP-500 platform, is a cost-effective and secure solution for line/feeder protection. They can also be used for backup

More information

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay SPAA 341 C. Product Guide Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay

More information

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 TOSHIBA Corporation 2004 All Rights Reserved. ( Ver. 1.6 ) Safety Precautions Before using this product, please read this chapter carefully. This

More information

Transformer Protection Relay

Transformer Protection Relay Transformer Protection Relay T-PRO Product Overview The IEC 61850 station bus embedded T-PRO relay provides complete three-phase multi-winding transformer protection and overload protection, DFR-quality

More information

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead solutions Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead switching products Brochure Your outdoor overhead distribution

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

7SR11 and 7SR12 Settings and Instruments

7SR11 and 7SR12 Settings and Instruments 7SR11 and 7SR12 Settings and Instruments Document Release History This document is issue 2012/01. The list of revisions up to and including this issue is: 2012/01 Software Maintenance 2011/06 Software

More information

NPW800R RETROFITTING. Power and Volatge Protection Relay

NPW800R RETROFITTING. Power and Volatge Protection Relay RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)

More information

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs SIPROTEC easy 7SJ4 Numerical Overcurrent Protection Relay Powered by CTs Function overview Fig. /1 Description The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended

More information

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager ABB Oy Distribution Automation Prashant Ganoo Regional Product Marketing Manager Feeder Protection REF615 Ver. 1.1 Technical Presentation 9/26/2008-1 - 1MRS756407 C Self Introduction Prashant Ganoo B.E.(ELECT),

More information

TM221M16R controller M IO relay

TM221M16R controller M IO relay Product data sheet Characteristics TM221M16R controller M221 16 IO relay Complementary Main Discrete I/O number 16 Number of I/O expansion module Supply voltage limits Inrush current Power consumption

More information

MiCOM Agile P746. Grid Solutions. Key Benefits. Numerical Busbar Protection. A Combination of Speed, Security and Selectivity. About MiCOM P40 Agile

MiCOM Agile P746. Grid Solutions. Key Benefits. Numerical Busbar Protection. A Combination of Speed, Security and Selectivity. About MiCOM P40 Agile GE Grid Solutions MiCOM Agile P746 Numerical Busbar Protection The MiCOM Agile P746 centralized numerical busbar protection provides complete protection for all voltage levels up to extra voltage busbar

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

DRTS 66. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 66. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

TM221CE40T controller M IO transistor PNP Ethernet

TM221CE40T controller M IO transistor PNP Ethernet Product data sheet Characteristics TM221CE40T controller M221 40 IO transistor PNP Ethernet Complementary Main Discrete I/O number 40 Number of I/O expansion module Supply voltage limits Inrush current

More information

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4.

Branch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4. Branch Procedure Document No. Issue No. : : CEOP8012 5 Approved By : Specialist Engineering NETWORK : Manager Approval Date Review Date : : 29/06/2018 29/06/2021 (Supersedes CEOP8012, Generation Connection:

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

A low-cost, economical solution for distribution feeder protection

A low-cost, economical solution for distribution feeder protection SEL-351A Protection System A low-cost, economical solution for distribution feeder protection Achieve sensitive and secure fault detection using comprehensive protection functions. Track breaker status

More information

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS MiCOM 01 MiCOM Fast Feeder Differential Protection The MiCOM relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring

More information

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9 PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6

More information

GRD110 FEATURES APPLICATION

GRD110 FEATURES APPLICATION FEATURES Overcurrent protection for phase and earth faults with IDMTL or DTL. Three instantaneous elements with DTL. Programmable reset characteristics. Sensitive earth fault protection (SEF). Restricted

More information

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology HGM9580 Bus Tie Bus Parallel Unit USER MANUAL Smartgen Technology This manual is suitable for HGM9580 bus tie bus parallel unit only. Clarification of notation used within this publication. SIGN INSTRUCTION

More information

DRTS 66 can test all the following relays

DRTS 66 can test all the following relays Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual control with color display Simultaneously available: 6 Current and 6 Voltage plus 1 battery simulator outputs

More information

TM221CE24R controller M IO relay Ethernet

TM221CE24R controller M IO relay Ethernet Product data sheet Characteristics TM221CE24R controller M221 24 IO relay Ethernet Complementary Main Discrete I/O number 24 Number of I/O expansion module Supply voltage limits Network frequency Inrush

More information

TM221M16TG controller M IO transistor PNP spring

TM221M16TG controller M IO transistor PNP spring Characteristics controller M221 16 IO transistor PNP spring Main Range of product Product or component type [Us] rated supply voltage Discrete input number Analogue input number Discrete output type Discrete

More information

TM221ME32TK controller M IO transistor PNP Ethernet

TM221ME32TK controller M IO transistor PNP Ethernet Product data sheet Characteristics TM221ME32TK controller M221 32 IO transistor PNP Ethernet Complementary Main Discrete I/O number 32 Number of I/O expansion module Supply voltage limits Inrush current

More information

7SR242 Duobias Transformer Protection Relay Answers for energy.

7SR242 Duobias Transformer Protection Relay Answers for energy. Reyrolle Protection Devices 7SR242 Duobias Transformer Protection Relay Answers for energy. 2 Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration & Instruments 3.

More information

Application Notes on Generator Protection Schemes

Application Notes on Generator Protection Schemes Application Notes on Generator Protection Schemes Single Line Diagram Examples 1. Introduction The application notes provide selected single line diagrams for the SIPROTEC 4 generator protection device

More information

F6150. Power System Simulator For Testing Protection Relays and Schemes.

F6150. Power System Simulator For Testing Protection Relays and Schemes. F6TesT Visual protection testing software for f6000 power system simulators The ultimate software for the automated testing of individual relays and complete protection schemes F6TesT software offers the

More information

7SR11 & 7SR12 Argus Overcurrent Relay Energy Management

7SR11 & 7SR12 Argus Overcurrent Relay Energy Management Reyrolle Protection Devices 7SR11 & 7SR12 Argus Overcurrent Relay Energy Management 7SR11 & 7SR12 Argus Contents Contents Technical Manual Chapters 1. Description of Operation 2. Settings, Configuration

More information

Protection Relays PHASE & RESIDUAL OVERCURRENT

Protection Relays PHASE & RESIDUAL OVERCURRENT Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent

More information

Bus Protection Application Challenges

Bus Protection Application Challenges Bus Protection Application Challenges KN Dinesh Babu - Megger JC Theron, Lubomir Sevov GE Grid Solutions 2017 Texas A&M Protective Relay Conference Content Introduction Application Challenges Increase

More information

EDR-3000 Eaton Distribution Relay

EDR-3000 Eaton Distribution Relay EDR-3000 Eaton Distribution Relay Technical Data New Information Description Page 1. General Description.......................... 2 2. Applications............................... 2 3. Drilling Pattern.............................

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation 111 Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation Z. Gajić (ABB, Sweden) JP Wang / PW Gong / YS Xu (ABB China) ZX Zhou (CERPI, China) Summary Power utilities

More information

TM221M32TK controller M IO transistor PNP

TM221M32TK controller M IO transistor PNP Characteristics controller M221 32 IO transistor PNP Main Range of product Product or component type [Us] rated supply voltage Discrete input number Analogue input number Discrete output type Discrete

More information

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

CEM M-RS485 INSTRUCTION MANUAL (M014B A) Communications interface CEM M-RS485 INSTRUCTION MANUAL (M014B01-03-14A) 2 SAFETY PRECAUTIONS Follow the warnings described in this manual with the symbols shown below. DANGER Warns of a risk, which could

More information