VIBRATION CONTROL REPORT CLEANROOM PHYSICS AND NANOTECHNOLOGY BUILDING UNIVERSITY OF MINNESOTA MINNEAPOLIS, MINNESOTA
|
|
- Elvin Joseph
- 5 years ago
- Views:
Transcription
1 VIBRATION CONTROL REPORT CLEANROOM PHYSICS AND NANOTECHNOLOGY BUILDING UNIVERSITY OF MINNESOTA MINNEAPOLIS, MINNESOTA ESI Project 1721 November 15, 2011 (Rev. 2) Prepared for: Ms. Ellen Olson, AIA Architectural Alliance 400 Clifton Avenue South Minneapolis, MN Tel: D Prepared by Barry Whiteaker, P.E. ESI ENGINEERING, INC Glenroy Road, Suite 430 Minneapolis, Minnesota Tel (952) Fax (952) esi-engineering.com
2 VIBRATION CONTROL REPORT PHYSIC AND NANOTECHNOLOGY BUILDING UNIVERSITY OF MINNESOTA MINNEAPOLIS, MINNESOTA ESI Engineering, Inc. 1 INTRODUCTION A new Physics and Nanotechnology Building at the Minneapolis campus of the University of Minnesota, is currently being designed. The new facility has been on the U s wish list for many years and has finally emerged as a project with a high priority. This is due in part to the increased interest in nanotechnology. Research in this area is on the cutting edge of science and promises to be an important part of our future. Figure 1 1. View of the Physics and Nanotechnology building from the southwest. Nanotechnology depends on working at higher and higher resolutions with equipment that deals with ever smaller particles and components. Vibration at even very low levels is an important aspect in the design of this facility. A key component of the new building is a cleanroom that will be used for nanotechnology research. Some of this research is currently being done in the Semiconductor facility in the Electrical Engineering Building located southwest of the new building. The cleanroom is roughly 60 x 90 and is near grade level on the west side of the building. There is no basement under this portion of the building. There is, however a basement under the remainder of the building located east of the cleanroom area. There are many causes of vibration in a building including movement of people and equipment inside the facility, and mechanical HVAC equipment. Outside sources must also be considered. This building has traffic on streets adjacent to the site and from a new Light Rail Transit (LRT) line that is under construction, just one block away, on Washington Avenue. Physics & Nanotechnology Building University of Minnesota 1-1
3 2 VIBRATION DESIGN GOAL The vibration design goal for the cleanroom floor has been discussed many times during the early phases of this project. These discussions have also dealt with the site-related and budgetary constraints of the project. It is our understanding that some but not all of the research planned for this facility is very sensitive to vibrations VC-E, the lowest curve shown in Figure 2-1. This curve in terms of velocity is a straight line at 125 μ-inches/sec from 1 Hz to 80 Hz. The VC-E criterion is recognized as being difficult to achieve, and is at a level that can be easily exceeded by a variety of transient and steady state disturbances, some of which may be impossible to identify and/or control. This is especially true in a highly developed, dense urban environment such as exists on the Minneapolis campus. For comparison the vibration used for hospital OR s is at 4000 μ-inches/sec which is near the limit of human perception for most people. Some of the research in the cleanroom could be done at a vibration level of VC-D which is a straight line at 250 μ-inches/sec shown just above VC-E in the Figure OFFICE (ISO) Velocity, micro-in/sec rms 00 0 RESIDENCES, DAY (ISO) SLEEP AREAS (ISO) ISO BASE CURVE OP ROOMS (ISO), MICROSCOPES TO X (~PERCEPTION LIMIT) VC-A, MICROSCOPES TO 400X VC-B: MICRO-SURGERY, MICROSCOPES > 400X VC-C: Inspection and lithography equipment to 1 detail Velocity, db re micro-in/sec VC-D: Electron microscopes and E-Beam systems VC-E: Difficult to achieve - long path, laser based, small target systems One-Third Octave Band Center Frequency, Hz. Figure 2 1. Vibration criteria curves. Physics & Nanotechnology Building University of Minnesota 2-1
4 3 MEASURED VIBRATION LEVELS Vibration tests for the new facility were conducted on December 20, The purpose of these tests was to determine the current vibration levels at the site. 3.1 Building location The new building will be located one block north of Washington Avenue, north of the Washington Avenue Parking Ramp and West of Harvard Street S E as shown in Figure 3-1. The portion of Union Street SE at the site is being abandoned and Akerman Hall is to the west. Four points were chosen for the accelerometer locations, one at each corner of the building. The results of the tests show that the lowest vibration levels are on the west side of the site, where the cleanroom will be located. The lowest levels measured are on the north end of the cleanroom at Point 3. This data shows the current ground vibration at the site. Changes in traffic have already occurred due to construction of the Central Corridor LRT. Changes will occur in the future as the campus grows and the LRT becomes operational. While the LRT is a concern, the designers of the system are using an isolated floating bed and they predict that the resulting vibrations caused by normal operations of the LRT will be at or below the levels currently caused by buses and trucks on Washington Avenue. Since the new building is one block away, vibration levels will be lower than those adjacent to the LRT. Figure 3 1. Site Plan with test locations. Harvard St. (curved road) was in place at time of tests. Physics & Nanotechnology Building University of Minnesota 3-1
5 3.2 Test Equipment Vibration monitoring equipment uses a transducer to sense motion. For this project the transducer used was a very sensitive piezoelectric accelerometer. When the accelerometer is in motion it produces an electrical voltage proportional to its acceleration. The output of the amplified accelerometer signals is then analyzed using a spectrum analyzer. The following instrumentation was used in this project: 1. Accelerometers -- PCB Peizotronics, Inc., Model 393B12 and 393B31 seismic accelerometers. These accelerometers produce 10 volt/g over a frequency range of 0.1 to 200 Hz. 2. Amplifiers -- PCB signal conditioning amplifiers provide variable voltage amplification for each accelerometer. 3. Spectrum Analyzer -- Oros OR four-channel, Fast Fourier Transform (FFT) spectrum analyzer used to capture and analyze the vibration data. 4. Personal Computer -- The data from the FFT spectrum analyzer is transferred directly to a PC providing data analysis, output, and storage capabilities. 3.3 Equipment Settings The spectrum analyzer was configured for narrow-band Fast Fourier Transforms (FFT s) with 800 lines of resolution over the 0 to Hz. frequency range (delta f = Hz.). The data was analyzed using sum averaging (200 averages typical) with 90% overlap and a Hanning window. The vibration amplitude for the narrow band data is presented as acceleration with units of g rms (micro g rms). 3.4 Measurement Locations The tests occurred over several hours and captured ambient levels as well as transients due to buses, trucks and small equipment. 3.5 Typical Spectrum Plot For each test a separate plot was made showing the filename, time and a brief description of the event. In Figure 3-2, the event was caused by a delivery truck exiting the drive between the Computer Science and Engineering Building and the Mechanical Engineering Building. The upper plots show the acceleration at Points 3 and 4. The middle plots show a peakhold, narrowband velocity spectrum for the full duration of the test and a 1/3 octave spectrum. These plots were used as the basis for calculations shown in later sections of this report. For this test, there is higher vibration at Point 3 than at Point 4 at frequencies below 2 Hz. A peak just below VC-D occurs at 12.5 Hz for both points. The remaining plots show the instantaneous spectra for the window at the end of the test. This plot was not used in subsequent calculations because the event is enveloped by the peakhold plot. Physics & Nanotechnology Building University of Minnesota 3-2
6 Figure 3 2. Typical response spectrum plot. Physics & Nanotechnology Building University of Minnesota 3-3
7 3.6 Summary Plots of the Test Results Summaries of the results of the peaks of the tests are shown in Figures 3-3 and 3-4. Notice that the levels at Points 1 and 2 are significantly higher than those at Points 3 and 4. This is due to the distance from the heavier and faster moving traffic on Harvard. The west side of the site has lower vibration as expected. In Figure 3-4, the levels at Point 4 are approximately twice those measured at Point 3. This higher ground vibration is expected to result in higher floor vibration in the south end of the cleanroom. Summary of Peak Ground Velocity Measurements, 20 Dec 2010 Points 1 & 2, East Side(Peakhold, Third Octave) Velocity (micro-in/s rms) VC-C VC-D VC-E CH 1 (NE) CH 2 (SE) Third Octave Center Freq (Hz) Figure 3 3. Peak vibrations for Points 1 and 2. Summary of Peak Ground Velocity Measurements, 20 Dec 2010 Points 3 & 4, Clean Room(Peakhold, Third Octave) Velocity (micro-in/s rms) VC-C VC-D VC-E CH 3 (Cln Rm N) CH 4 (Cln Rm S) Third Octave Center Freq (Hz) Figure 3 4. Peak vibrations for the cleanroom Points 3 and 4. Physics & Nanotechnology Building University of Minnesota 3-4
8 4 CLEANROOM FLOOR SYSTEM Although the levels in this area are relatively low compared to the east side, the tests indicate that a slab on grade will not be sufficient to provide the necessary isolation from traffic on adjacent streets. Since the building will be supported on drilled piers, a decision was made to use the same means to support the laboratory floor. Figures 4-1 through 4-3 show a schematic of the structure proposed originally by ESI. In order to isolate the slab from the soil below, precast inverted T-beams are placed on top of the drilled piers. The T-beams support the precast planks, which in turn support a cast in place slab until the concrete hardens to form a thick monolithic slab. There is an air space below the slab so there is no direct contact with the soil below. This will significantly reduce the vertical motion in the cleanroom slab. The design has evolved as shown in Figures 4 4 through 4 6. Following extensive discussions with the design team and contractor, the total slab thickness was reduced to 24 inches. The final design consists of 8-inch precast planks plus 16 inches of cast in place concrete. The final design was based upon a 12.5 x 20 array of piers, with some modification to accommodate the main building columns. A small pier spacing (12.5 x 10 ) was used in the southwest corner of the cleanroom to provide enhanced vibration mitigation for the sensitive equipment that will be located there. The main building columns are isolated from the cleanroom slab. It was suggested that cardboard forms could be used rather than the precast elements to reduce cost. While this seems like it might be a reasonable alternative, it is our experience that the cardboard forms do not break down as expected. There is not sufficient moisture in the sandy soil at the University to decompose this material readily so the forms remain in contact and transmit vibration from the soil to the slab. Figure 4 1. Early schematic of the cleanroom structure (elevation). Physics & Nanotechnology Building University of Minnesota 4-1
9 Figure 4 2. Early schematic of the cleanroom structure (plan) Piers for cleanroom slab Piers for shearwall (isolated from cleanroom slab) Piers for building columns (isolated from cleanroom slab) Figure 4 3. Early schematic of foundation plan Physics & Nanotechnology Building University of Minnesota 4-2
10 Figure 4 4. Current (BP 1) foundation plan in cleanroom area. Physics & Nanotechnology Building University of Minnesota 4-3
11 N Figure 4 5. Current (BP 1) foundation/framing plan in cleanroom area. Physics & Nanotechnology Building University of Minnesota 4-4
12 Figure 4 6. Sections through cleanroom slab at interior and outside beam lines. Physics & Nanotechnology Building University of Minnesota 4-5
13 5 MODELING THE SYSTEM Analysis of the floor system for dynamic response went through several iterations. The original calculations were done with Mathcad to determine the natural frequency and stiffness of the proposed system. A single mass oscillator model was used and the goal was to find a system with a thick slab and drilled piers stiff enough to produce a system with a natural frequency that is significantly higher than the fundamental frequency of the soil which is around 12 Hz. This was accomplished with the scheme shown above in Figures 4-2 and 4-3. Computer models confirmed the Mathcad calculation. Cost estimates of the whole building showed that significant cuts needed to be made overall and that any reductions that could be made to the cost of the cleanroom floor should be considered. In order to accomplish this goal, the model was refined to evaluate variations on the initial design. 5.1 Detailed Finite Element Model A detailed Finite Element Analysis (FEA) was used to examine the slab, drilled piers and soil. A parameter study was done by varying the thickness of the slab, spacing of the piers and the diameter of the piers to determine the effects each parameter has on the performance of the structure. The first cases were done without including the soil in the model. After the importance of these parameters was evaluated, the soil was added to the model to further understand the interaction of the whole system. The refined model is shown in Figure 5-1. The model has more than 9400 nodes and 8400 elements. As shown, the model includes only the south half of the cleanroom floor structure (approximately up to Grid 6) and the soil below it. The soil and drilled piers extend down to bedrock. drilled piers SE corner of clean room floor soil N (soil not shown) Figure 5 1. Finite Element Model Physics & Nanotechnology Building University of Minnesota 5-1
14 5.2 Third Octave Ground Motion The data collected from the site monitoring at Points 3 and 4 is shown in Figures 5-2 and 5-3 respectively. The peak of all of the data points at each third octave band was used as the driving function for the FEA model. Summary of Peak Ground Velocity Measurements, 20 Dec 2010 Point 3, Clean Room(Peakhold, Third Octave) Velocity (micro-in/s rms) VC-C VC-D VC-E CH 3 (Cln Rm N) Third Octave Center Freq (Hz) Figure 5 2. Third octave ground data at Point 3 Summary of Peak Ground Velocity Measurements, 20 Dec 2010 Point 4, Clean Room(Peakhold, Third Octave) Velocity (micro-in/s rms) VC-C VC-D VC-E CH 4 (Cln Rm S) Third Octave Center Freq (Hz) Figure 5 3. Third octave ground data at Point 4 Physics & Nanotechnology Building University of Minnesota 5-2
15 5.3 Frequency Response Analysis Methodology A frequency response analysis was performed on the model. A line of harmonic vertical forces is assumed on the soil surface, just south the cleanroom floor, and the ground velocity is computed as a function of frequency. Figure 5-4 shows the applied soil forces. The measured ground motion is then compared to predicted ground motion, and an appropriate scale factor is determined. The predicted response at any point in the soil or on the floor slab is then determined by applying the same scale factor to that point. The plots which follow are the result of that technique. N Forces on soil surface Figure 5 4. Applied forces on the soil surface used for the frequency response analysis. Figure 5-5 shows the nodal points on the cleanroom floor where the velocity response was computed. The velocity was computed along four lines extending from the south edge of the cleanroom floor back into the middle of the floor. In addition, in the southeast corner, the floor response was evaluated at six additional points in the area where the sensitive Vistec-E-Beam equipment will be located. A modal damping value of 5 percent of critical was assumed for all modes. In our opinion, this represents a conservative assumption. Soil damping and structural damping due to equipment and walls located on the cleanroom slab will contribute. Physics & Nanotechnology Building University of Minnesota 5-3
16 N Row 7 Row 6 Row 5 Row 4 SE corner of clean room floor Figure 5 5. Nodal points for frequency response analysis. Labels represent node numbers Results Figures 5-6 through 5-10 show the predicted velocity on the cleanroom floor. As explained in Section 5.2, the predictions are calibrated with the peak ground measured at Points 3 and 4. Each curve represents a point on the floor, with the velocity predicted at each third octave frequency. The highest response is just above 150 μ-inches/sec at 20 Hz, and occurs at node in Row 7, as seen in Figure 5-9. Recall that the VC-E criterion is at 125 μ-inches/sec independent of frequency. It is noted that the all the predicted responses are at or below the VC-E criterion, with the exception of a few points on the south edge of the floor slab. The magnitude of the predicted velocity generally falls below μ-inches/sec for nodal locations north of the first line of drilled piers. Figure 5-10 shows that the predicted velocity in the area of the sensitive Vistec E-Beam equipment located at the southeast corner of the cleanroom floor, is below the VC-E criterion, in spite of being close to the disturbing forces. It appears that the closer spacing of the drilled piers in this area is effective in reducing vibration. Physics & Nanotechnology Building University of Minnesota 5-4
17 Velocity - (micro-in/sec) /3 Octave Velocity vs. Frequency Floor, Row 4 Predicted Response at Predicted Response at 69 Predicted Response at 539 Predicted Response at 544 Predicted Response at 549 Predicted Response at 555 Predicted Response at 560 Predicted Response at 574 Predicted Response at 584 VC-E Frequency (Hz) Figure 5 6. Predicted floor response in Row 4 Velocity - (micro-in/sec) /3 Octave Velocity vs. Frequency Floor, Row 5 Predicted Response at Predicted Response at 81 Predicted Response at 1247 Predicted Response at 1252 Predicted Response at 1257 Predicted Response at 1263 Predicted Response at 1268 Predicted Response at 1282 Predicted Response at 1292 VC-E Frequency (Hz) Figure 5 7. Predicted floor response in Row 5 Physics & Nanotechnology Building University of Minnesota 5-5
18 Velocity - (micro-in/sec) /3 Octave Velocity vs. Frequency Floor, Row 6 Predicted Response at Predicted Response at 95 Predicted Response at 2073 Predicted Response at 2089 Predicted Response at 2108 VC-E Frequency (Hz) Figure 5 8. Predicted floor response in Row 6 Velocity - (in/sec) /3 Octave Velocity vs. Frequency Floor, Row 7 Predicted Response at Predicted Response at 109 Predicted Response at 2899 Predicted Response at 2909 Predicted Response at 1257 VC-E Frequency (Hz) Figure 5 9. Predicted floor response in Row 7 Physics & Nanotechnology Building University of Minnesota 5-6
19 Velocity - (in/sec) /3 Octave Velocity vs. Frequency Floor Response at Vistec-E-Beam Predicted Response at 75 Predicted Response at 893 Predicted Response at 898 Predicted Response at 4 Predicted Response at 126 VC-E Frequency (Hz) Figure Predicted floor response at Vistec E-Beam. Physics & Nanotechnology Building University of Minnesota 5-7
20 6 SUMMARY ESI performed a vibration survey in December 2010, to characterize current vibration at the site. The data indicated that a slab on grade would not be sufficient to provide the necessary isolation from traffic on adjacent streets. Since the building columns will be supported on drilled piers, a decision was made to use the same means to support the laboratory floor. Based upon our preliminary analysis and experience with previous designs, ESI recommended a closely spaced array of piers, drilled to bedrock, supporting a thick monolithic floor slab. Following the vibration survey, ESI collaborated with the other team members to refine the design and minimize cost. The critical element of the current design is a void between the top of the soil and the bottom of the floor slab so that vibration from the soil is not transmitted directly to the floor slab. A total slab thickness of 24 inches was decided upon, after a careful consideration of cost versus performance. The final design consists of 8-inch precast planks plus 16 inches of cast in place concrete. The predicted vibration of the cleanroom floor slab has been analyzed by using a series of increasingly more complex techniques to predict the vibration on the cleanroom floor. The final analysis was done with a FEA model using a frequency response analysis. Using this method, the current measured ground vibration was used as input to predict the expected vibration of the cleanroom floor. This is not an exact analysis but rather it is an approximate method. The accuracy of the model depends on the material properties used, the boundary conditions assumed and details of the model. Additionally, the predictions are based upon the conditions that were encountered during our December 2010 vibration survey, and these conditions may change. The VC-E vibration criterion is difficult to reach even under the best conditions. Our model shows that the predicted vibration of the cleanroom floor should be close to the criteria. The proposed structure is a reasonable solution to a challenging set of requirements and budget constraints, and should serve its intended purpose well. Physics & Nanotechnology Building University of Minnesota 6-1
VALIDATION OF SASSI2010 SOLUTION METHODS THROUGH INDEPENDENT VERIFICATION USING SAP2000 FOR DEEPLY EMBEDDED STRUCTURES WITH LARGE FOOTPRINTS
Transactions, SMiRT-22 VALIDATION OF SASSI2010 SOLUTION METHODS THROUGH INDEPENDENT VERIFICATION USING SAP2000 FOR DEEPLY EMBEDDED STRUCTURES WITH LARGE FOOTPRINTS Lisa M Anderson 1, Tarek Elkhoraibi,
More informationVerification and Validation for Seismic Wave Propagation Problems
Chapter 26 Verification and Validation for Seismic Wave Propagation Problems (1989-2-24-25-28-29-21-211-217-) (In collaboration with Dr. Nima Tafazzoli, Dr. Federico Pisanò, Mr. Kohei Watanabe and Mr.
More informationENHANCED PARKWAY STUDY: PHASE 3 REFINED MLT INTERSECTION ANALYSIS
ENHANCED PARKWAY STUDY: PHASE 3 REFINED MLT INTERSECTION ANALYSIS Final Report Prepared for Maricopa County Department of Transportation Prepared by TABLE OF CONTENTS Page EXECUTIVE SUMMARY ES-1 STUDY
More informationCOSMOS Annual Meeting Example of Current Code Procedure Applied to Ground Motion Scaling at a Northern California Site November 18, 2005 Mark
COSMOS Annual Meeting Example of Current Code Procedure Applied to Ground Motion Scaling at a Northern California Site November 18, 2005 Mark Sinclair, Degenkolb Engineers Outline >Project Summary > Seismic
More informationCHAPTER 5 RANDOM VIBRATION TESTS ON DIP-PCB ASSEMBLY
117 CHAPTER 5 RANDOM VIBRATION TESTS ON DIP-PCB ASSEMBLY 5.1 INTRODUCTION Random vibration tests are usually specified as acceptance, screening and qualification tests by commercial, industrial, and military
More information2008 International ANSYS Conference
2008 International ANSYS Conference AUTODYN Simulation of Blasting at Pointe du Bois Generating Station Nick Rapolti Engineering Analyst SimuTech Group - Toronto Ryan Penner, P.Eng. Project Engineer Manitoba
More information17. SEISMIC ANALYSIS MODELING TO SATISFY BUILDING CODES
17. SEISMIC ANALYSIS MODELING TO SATISFY BUILDING CODES The Current Building Codes Use the Terminology: Principal Direction without a Unique Definition 17.1 INTRODUCTION { XE "Building Codes" }Currently
More informationAbstract. Introduction
A COMPARISON OF SHEAR WAVE VELOCITIES OBTAINED FROM THE CROSSHOLE SEISMIC, SPECTRAL ANALYSIS OF SURFACE WAVES AND MULTIPLE IMPACTS OF SURFACE WAVES METHODS Patrick K. Miller, Olson Engineering, Wheat Ridge,
More informationVibration Transducer Calibration System
0 1 Overview is designed for calibrating sensitivity, frequency response characteristic and amplitude linearity of acceleration transducer. There are three basic operation modes for the calibration system:
More informationModeling Submerged Structures Loaded by Underwater Explosions with ABAQUS/Explicit
Modeling Submerged Structures Loaded by Underwater Explosions with ABAQUS/Explicit David B. Woyak ABAQUS Solutions Northeast, LLC Abstract: Finite element analysis can be used to predict the transient
More information# I-2. Date of Meeting: May 2, 2017 BOARD OF SUPERVISORS BUSINESS MEETING INFORMATION ITEM. Quarterly Metrorail Construction Status Report
BOARD OF SUPERVISORS BUSINESS MEETING INFORMATION ITEM Date of Meeting: May 2, 2017 # I-2 SUBJECT: Quarterly Metrorail Construction Status Report ELECTION DISTRICTS: Ashburn/Broad Run STAFF CONTACTS: Alan
More informationImage representation. 1. Introduction
Image representation Introduction Representation schemes Chain codes Polygonal approximations The skeleton of a region Boundary descriptors Some simple descriptors Shape numbers Fourier descriptors Moments
More informationTutorial. BOSfluids. Water hammer (part 3) Dynamic Analysis using Caesar II
BOSfluids Tutorial Water hammer (part 3) Dynamic Analysis using Caesar II The Water hammer tutorial is a 3 part tutorial describing the phenomena of water hammer in a piping system and how BOSfluids can
More informationAPPENDIX E TRANSPORTATION
APPENDIX E TRANSPORTATION 2011 PATRON SURVEYS VISSIM MODEL CALIBRATION AND VALIDATION Environmental and Planning Consultants 440 Park Avenue South 7th Floor New York, NY 10016 tel: 212 696-0670 fax:
More informationHelp Page for the Java-Powered Simulation for Experimental Structural Dynamics
Help Page for the Java-Powered Simulation for Experimental Structural Dynamics Table of Contents Introduction How to Use the Virtual Laboratory o Control Panel o Animation Panel o Response Plot Panel o
More informationEXPERIMENTAL STUDY ON DETERMINING DAMPING RATIO OF STEEL BRIDGES
EXPERIMENTAL STUDY ON DETERMINING DAMPING RATIO OF STEEL BRIDGES Muharrem AKTAS 1, Serdar KUYUK 2, Cemal YILMAZ 3, Elif AGCAKOCA 4, Erkan ÇELEBİ 5 ABSTRACT Damping property of a light-weight structure
More informationIncreasing Machine Service Life of Large Envelope, High Acceleration AFP Machines
2013-01-2297 Published 09/17/2013 Copyright 2013 SAE International doi:10.4271/2013-01-2297 saeaero.saejournals.org Increasing Machine Service Life of Large Envelope, High Acceleration AFP Machines Justin
More informationA comparison between large-size shaking table test and numerical simulation results of subway station structure
October 127, 28, Beijing, China A comparison between large-size shaking table test and numerical simulation results of subway station structure ABSTRACT : CHEN Guo-xing 1, ZUO Xi 1, ZHUANG Hai-yang 1,
More informationCentral Corridor. - Central Corridor. Management Committee, Light Rail Transit. Rail-Volution - Weaving Transit into Existing Communities
- Central Corridor Rail-Volution - Weaving Transit into Existing Communities Management Committee, October 31, 2009 June Improving 11, 2008 mobility Easing congestion Strengthening our communities Twin
More informationHVAC Project. Comparison of Revit MEP Automatic Duct Sizing and Equal Friction Method Manual Calculations
346P HVAC Project Comparison of Revit MEP Automatic Duct Sizing and Equal Friction Method Manual Calculations ŀare Name: Date: 10 May 2010 Ben Meinke, Jimmy Principe, Richard Sniff Table of Contents Project
More informationS ONIC E CHO/IMPULSE R ESPONSE
SE/IR Methods N D E S ONIC E CHO/IMPULSE R ESPONSE A PPLICATION Sonic Echo/Impulse Response tests are performed to evaluate the integrity and determine the length of deep foundations. SE/IR tests can be
More informationVIBROACOUSTIC MODEL VALIDATION FOR A CURVED HONEYCOMB COMPOSITE PANEL
VIBROACOUSTIC MODEL VALIDATION FOR A CURVED HONEYCOMB COMPOSITE PANEL AIAA-2001-1587 Ralph D. Buehrle and Jay H. Robinson ÿ NASA Langley Research Center, Hampton, Virginia and Ferdinand W. Grosveld Lockheed
More informationDATA REPORT. SASW Measurements at the NEES Garner Valley Test Site, California
13 January 2004 DATA REPORT SASW Measurements at the NEES Garner Valley Test Site, California by Kenneth H. Stokoe, II, Ph.D., P.E., Jennie C. and Milton T. Graves Chair in Engineering Asli Kurtulus, M.S.,
More informationAPPENDIX S HORIZONTAL DIRECTIONAL DRILLING (HDD) ENVIRONMENTAL SOUND LEVEL ASSESSMENT REPORT
ALASKA LNG PROJECT DOCKET NO. CP17- -000 RESOURCE REPORT NO. 9 APPENDIX S HDD ENVIRONMENTAL SOUND LEVEL ASSESSMENT REPORT PUBLIC DOC NO: USAI-PE-SRREG-00-000009-000 DATE: APPENDIX S HORIZONTAL DIRECTIONAL
More informationFEKO Mesh Optimization Study of the EDGES Antenna Panels with Side Lips using a Wire Port and an Infinite Ground Plane
FEKO Mesh Optimization Study of the EDGES Antenna Panels with Side Lips using a Wire Port and an Infinite Ground Plane Tom Mozdzen 12/08/2013 Summary This study evaluated adaptive mesh refinement in the
More informationAdvanced Finite Element Model for AE-MDB Side Impact Barrier
Advanced Finite Element Model for AE-MDB Side Impact Barrier Authors: M. Asadi 1, P. Tattersall 1, B. Walker 2, H. Shirvani 3 1. Cellbond Composites Ltd. 2. ARUP Campus (UK) 3. Anglia Ruskin University
More informationDefining the Global Error of a Multi-Axis Vibration Test: An Application of MIL-STD-810G Method 527 Annex C
Defining the Global Error of a Multi-Axis Vibration Test: An Application of MIL-STD-810G Method 527 Annex C Joel Hoksbergen Team Corporation joel.hoksbergen@teamcorporation.com ESTECH 2014 MIMO Concepts
More informationVR9500. Advantages Ease of Use. Features
Ease of Use system and confi gured a test within minutes of unpacking the box. Additionally, our customer support PC & Windows Integration The integrates seamlessly with your PC and Windows operating system,
More informationVE-53 Sensor Uniaxial / Triaxial Surface and Downhole Velocity Sensor. Operation Manual
VE-53 Sensor Uniaxial / Triaxial Surface and Downhole Velocity Sensor Operation Manual Company: Author: Checked: Approved: Level: Distribution: GeoSIG Ltd Wiesenstrasse 39, 8952 Schlieren, Switzerland,
More informationVIBRATION METERS VX-54WH. Hand-Arm Vibration VX-54WB. Whole-Body Vibration VX-54WS. Habitability on Ships. 3-Axis Vibration Meter VM-54
VIBRATION METERS VX-54WH Hand-Arm Vibration VX-54WB Whole-Body Vibration VX-54WS Habitability on Ships 3-Axis Vibration Meter 3-Axis Vibration Meter VX-54WS Marine Vibration Card Vibration measurement
More informationAero-Vibro Acoustics For Wind Noise Application. David Roche and Ashok Khondge ANSYS, Inc.
Aero-Vibro Acoustics For Wind Noise Application David Roche and Ashok Khondge ANSYS, Inc. Outline 1. Wind Noise 2. Problem Description 3. Simulation Methodology 4. Results 5. Summary Thursday, October
More informationMachineryMate 200 operating guide Handheld vibration meter
MachineryMate 200 operating guide Handheld vibration meter Wilcoxon Sensing Technologies 20511 Seneca Meadows Parkway, Germantown MD 20876, USA Amphenol (Maryland), Inc d/b/a Wilcoxon Sensing Technologies
More informationAC-43 Accelerometer. User Manual
AC-43 Accelerometer Manual Page 1 AC-43 Accelerometer User Manual Company: Author: Checked: Approved: Distribution: GeoSIG Ltd Wiesenstrasse 39, 8952 Schlieren, Switzerland, Tel: +41 44 810 21 50, Fax:
More informationChapter 5. Track Geometry Data Analysis
Chapter Track Geometry Data Analysis This chapter explains how and why the data collected for the track geometry was manipulated. The results of these studies in the time and frequency domain are addressed.
More informationWilcoxon Research P702B/P702BF-1 operating guide Power unit/amplifier for piezoelectric transducers with internal amplifiers
Wilcoxon Research P702B/P702BF-1 operating guide Power unit/amplifier for piezoelectric transducers with internal amplifiers Caution: This manual should be read carefully before installation. Meggitt Sensing
More informationStakeholder Engagement Summary Report
Stakeholder Engagement Summary Report South Shore Corridor Project 1. INTRODUCTION 1.1 Project Overview Port Metro Vancouver s South Shore Trade Area is of critical importance to Canadian trade. One of
More informationWashington Square FPO. 111 Washington Square > Office Space FOR LEASE > OFFICE SPACE 111 WASHINGTON AVENUE, MINNEAPOLIS, MN 55401
FOR LEASE > OFFICE SPACE Washington Square 111 WASHINGTON AVENUE, MINNEAPOLIS, MN 55401 FPO 111 Washington Square > Office Space HENNEPIN AVE PARKING RAMP > Built in 1987, 111 Washington is part of a three
More informationMultiple Choice Questions Circle the letter of the correct answer. 7 points each. is:
This Math 114 final exam was administered in the Fall of 008. This is a sample final exam. The problems are not exhaustive. Be prepared for ALL CONCEPTS for the actual final exam. Multiple Choice Questions
More informationHigh-Resolution Ocean Wave Estimation
DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited. High-Resolution Ocean Wave Estimation David Walker SRI International 2100 Commonwealth Boulevard, Third Floor Ann Arbor,
More information(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)
Section 16306 50/60-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER Index PART 1 GENERAL PART 2 PRODUCTS 1.1 References 2.1 Frequency Converters 1.2 Factory Tests 2.2 Conduit and Fittings 1.3 Submittals 2.3
More informationTechnical Issues. Frequently Asked Questions Frequently Encountered Errors. - Featuring - ADAPT-ABI 2009
Technical Issues Frequently Asked Questions Frequently Encountered Errors - Featuring - ADAPT-ABI 2009 ADAPT Corporation, USA ADAPT International Pvt. Ltd, Kolkata, India Tuesday, November 17, 2009 1 What
More informationDesign Optimization of a Weather Radar Antenna using Finite Element Analysis (FEA) and Computational Fluid Dynamics (CFD)
Design Optimization of a Weather Radar Antenna using Finite Element Analysis (FEA) and Computational Fluid Dynamics (CFD) Fernando Prevedello Regis Ataídes Nícolas Spogis Wagner Ortega Guedes Fabiano Armellini
More informationHelios 3D TM Product Sheet
Introduction HELIOS 3D is one of the most powerful layout tools for utility scale solar plants available on the market. It is successfully production proven worldwide for nearly 3 years. Furthermore several
More informationSMSIM Calibration for the SCEC Validation Project NGA-East Workshop Berkeley 12/11/12
SMSIM Calibration for the SCEC Validation Project NGA-East Workshop Berkeley 12/11/12 SWUS GMC SSHAC Level 3 Carola Di Alessandro GeoPentech with inputs from D.M. Boore OUTLINE Introduce SMSIM (Stochastic
More information1224. Seismic test and numerical verification of the scaled-down reinforced concrete containment vessel
1224. Seismic test and numerical verification of the scaled-down reinforced concrete containment vessel Yu-Chih Chen 1, Wei-Ting Lin 2, Tung-Liang Chu 3, Yuan-Chieh Wu 4 1 National Center for Research
More informationTYPE 529: RADIANT SLAB
TYPE 529: RADIANT SLAB General Description This component is intended to model a radiant floor-heating slab, embedded in soil, and containing a number of fluid filled pipes. The heat transfer within the
More informationPlease Check the Installation Notes Portion of this Manual Before Installing the Software Update
SOFTWARE MANUAL V.1.1.7 This manual is designed for viewing on a computer with ADOBE reader and has hyperlinks throughout to help navigation between topics. To view this manual on a computer, select the
More informationAnalysis of the dynamic response of pump-turbine runners- Part I: Experiment
Analysis of the dynamic response of pump-turbine runners- Part I: Experiment A Presas 1, C Valero 1, X Huang 1, E Egusquiza 1, M Farhat 2 and F Avellan 2 1 Center for Industrial Diagnostics, Technical
More informationThe interpolation of a 3-D data set by a pair of 2-D filters
Stanford Exploration Project, Report 84, May 9, 2001, pages 1 275 The interpolation of a 3-D data set by a pair of 2-D filters Matthias Schwab and Jon F. Claerbout 1 ABSTRACT Seismic 3-D field data is
More informationTitle: Standard Operating Procedure for Measurement of Particulate Matter in Ambient Air by Orthogonal Light Scattering
Procedure No: SOP-014 Revision No: 0 (new document) Page No.: 1 of 10 1. INTRODUCTION AND SCOPE The Grimm particulate monitor is used by Alberta Environment (AENV) in the Mobile Air Monitoring Laboratory
More informationME scope Application Note 04 Using SDM for Sub-Structuring
App Note 04 www.vibetech.com 2-Aug-18 ME scope Application Note 04 Using SDM for Sub-Structuring NOTE: The steps in this Application Note can be duplicated using any Package that includes the VES-5000
More informationThe most popular system in the world
408UL TITRE SEISMIC ACQUISITION All-Terrain Vibrators SYSTEM The most popular system in the world 408UL Recognized for the strength and reliability of its components, the 408UL acquisition system has dominated
More informationFB-MULTIPIER vs ADINA VALIDATION MODELING
FB-MULTIPIER vs ADINA VALIDATION MODELING 1. INTRODUCTION 1.1 Purpose of FB-MultiPier Validation testing Performing validation of structural analysis software delineates the capabilities and limitations
More informationPower Quality of Commercial Buildings - Advanced
Buildings - Advanced Hartford Steam Boiler One State Street P.O. Box 5024 Hartford, CT 06102-5024 Tel: (800) 472-1866 www.munichre.com/hsb May 2017 Background Power quality is a general term used to describe
More informationCFD MODELING FOR PNEUMATIC CONVEYING
CFD MODELING FOR PNEUMATIC CONVEYING Arvind Kumar 1, D.R. Kaushal 2, Navneet Kumar 3 1 Associate Professor YMCAUST, Faridabad 2 Associate Professor, IIT, Delhi 3 Research Scholar IIT, Delhi e-mail: arvindeem@yahoo.co.in
More informationTextbook Assignment #1: DUE Friday 5/9/2014 Read: PP Do Review Questions Pg 388 # 1-20
Page 1 of 38 Page 2 of 38 Unit Packet Contents Unit Objectives Notes 1: Waves Introduction Guided Practice: Waves Introduction (CD pp 89-90) Independent Practice: Speed of Waves Notes 2: Interference and
More informationCalibration. Calibration Overview CHAPTER
CHAPTER 21 Calibration Calibration Overview Sensitivity Determination The primary role of sound level meter calibration is to establish a numerical relationship between the sound level at the diaphragm
More informationD&S Technical Note 09-2 D&S A Proposed Correction to Reflectance Measurements of Profiled Surfaces. Introduction
Devices & Services Company 10290 Monroe Drive, Suite 202 - Dallas, Texas 75229 USA - Tel. 214-902-8337 - Fax 214-902-8303 Web: www.devicesandservices.com Email: sales@devicesandservices.com D&S Technical
More informationProceedings of the SEM IMAC XXX Conference Jan. 30 Feb. 2, 2012, Jacksonville, FL USA 2011 Society for Experimental Mechanics Inc.
A Local Solve Method for Extracting Modal Parameters from Inconsistent Data ABSTRACT Michael L. Mains+, Shashank Chauhan #, Henrik B. Herlufsen # + Brüel and Kjær, North America 4665 Cornell Road, Suite
More informationPE Exam Review - Surveying Demonstration Problem Solutions
PE Exam Review - Surveying Demonstration Problem Solutions I. Demonstration Problem Solutions... 1. Circular Curves Part A.... Circular Curves Part B... 9 3. Vertical Curves Part A... 18 4. Vertical Curves
More informationTHE KINEMATIC AND INERTIAL SOIL-PILE INTERACTIONS: CENTRIFUGE MODELLING
THE KINEMATIC AND INERTIAL SOIL-PILE INTERACTIONS: CENTRIFUGE MODELLING Nawel Chenaf, Jean-Louis Chazelas To cite this version: Nawel Chenaf, Jean-Louis Chazelas. THE KINEMATIC AND INERTIAL SOIL-PILE INTER-
More informationProgram ROAD Manager MAP Certification
Program Certification Manager The Route to ESD Control Roadmap The purpose of the Roadmap is to project the impact of technology scaling in the semiconductor industry. To develop the Roadmap, ESD devices
More informationSILICON DESIGNS, INC Model 1210 ANALOG ACCELEROMETER
SILICON DESIGNS, INC Model 1210 ANALOG ACCELEROMETER SENSOR TYPE: Capacitive Micromachined Nitrogen Damped Hermetically Sealed ±4V Differential Output or 0.5V to 4.5V Single Ended Output Fully Calibrated
More informationImage Transformation Techniques Dr. Rajeev Srivastava Dept. of Computer Engineering, ITBHU, Varanasi
Image Transformation Techniques Dr. Rajeev Srivastava Dept. of Computer Engineering, ITBHU, Varanasi 1. Introduction The choice of a particular transform in a given application depends on the amount of
More informationProShake 2.0. The first step in this tutorial exercise is to start the ProShake 2.0 program. Click on the ProShake 2.0 icon to start the program.
PROSHAKE 2.0 TUTORIAL The easiest way to learn the basics of ProShake s organization and operation is to complete the tutorial exercise detailed in this section. This tutorial will take you through nearly
More informationPTC Newsletter January 14th, 2002
PTC Email Newsletter January 14th, 2002 PTC Product Focus: Pro/MECHANICA (Structure) Tip of the Week: Creating and using Rigid Connections Upcoming Events and Training Class Schedules PTC Product Focus:
More informationAutomatically Balancing Intersection Volumes in A Highway Network
Automatically Balancing Intersection Volumes in A Highway Network Jin Ren and Aziz Rahman HDR Engineering, Inc. 500 108 th Avenue NE, Suite 1200 Bellevue, WA 98004-5549 Jin.ren@hdrinc.com and 425-468-1548
More informationWHITEPAPER WHITEPAPER. GE s eboost Technology Reducing Data Center Power Consumption, Ensuring Power Quality. Silvio Colombi.
GE s eboost Technology Reducing Data Center Power Consumption, Ensuring Power Quality Introduction: Playing the Percentages of Uninterruptible Power Supply Efficiency Paying the power bills for today s
More informationCoustyx Tutorial Indirect Model
Coustyx Tutorial Indirect Model 1 Introduction This tutorial is created to outline the steps required to compute radiated noise from a gearbox housing using Coustyx software. Detailed steps are given on
More informationSmoothness of Pavement in Weighin-Motion
Standard Specification for Smoothness of Pavement in Weighin-Motion (WIM) Systems AASHTO Designation: MP 14-05 American Association of State Highway and Transportation Officials 444 North Capitol Street
More informationProblem description. The FCBI-C element is used in the fluid part of the model.
Problem description This tutorial illustrates the use of ADINA for analyzing the fluid-structure interaction (FSI) behavior of a flexible splitter behind a 2D cylinder and the surrounding fluid in a channel.
More informationRClamp TM 0504M RailClamp Low Capacitance TVS Diode Array PRELIMINARY Features
Description RailClamps are surge rated diode arrays designed to protect high speed data interfaces. The RClamp series has been specifically designed to protect sensitive components which are connected
More information(Based on a paper presented at the 8th International Modal Analysis Conference, Kissimmee, EL 1990.)
Design Optimization of a Vibration Exciter Head Expander Robert S. Ballinger, Anatrol Corporation, Cincinnati, Ohio Edward L. Peterson, MB Dynamics, Inc., Cleveland, Ohio David L Brown, University of Cincinnati,
More informationMethodology for Prediction of Sliding and Rocking of Rigid Bodies Using Fast Non-Linear Analysis (FNA) Formulation
Methodology for Prediction of Sliding and Rocking of Rigid Bodies Using Fast Non-Linear Analysis (FNA) Formulation Sohrab Esfandiari - ENOVA Engineering Services Robert P. Kennedy- RPK Structural Consulting
More informationMagnetics. Introduction to Filtering using the Fourier Transform. Chuck Connor, Laura Connor. Potential Fields. Magnetics.
Introduction to using the Chuck Connor, Laura Connor Potential Fields for this week Nm Sm Schematic Earth dipolar magnetic field. The field lines placed in the page plane are drawn as thick lines, those
More informationA New Way for Multi-piece and Multi-hit Fragment Impact Simulation Using LS-DYNA
9 th International LS-DYNA Users Conference Impact Analysis (1) A New Way for Multi-piece and Multi-hit Fragment Impact Simulation Using LS-DYNA Xudong Xin Karagozian and Case 255 N. Hollywood Way, Suite
More informationA Multiscale Nested Modeling Framework to Simulate the Interaction of Surface Gravity Waves with Nonlinear Internal Gravity Waves
DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited. A Multiscale Nested Modeling Framework to Simulate the Interaction of Surface Gravity Waves with Nonlinear Internal Gravity
More informationSOLIDWORKS SIMULATION
SOLIDWORKS SIMULATION Innovation is about taking chances, not taking risks Scootchi by Curventa Designworks LTD What if? is the question that fuels innovation. SolidWorks Simulation software takes the
More informationDS-3000 Series Data Station Operation manual for Vibration Analysis
DS-3000 Series Data Station Operation manual for Vibration Analysis ONO SOKKI CO., LTD. This instruction manual describes basic operations of the DS-3000 Series Data Station for vibration analysis. As
More informationInk Volume Displacement In An Impulse Printhead With Bilaminar Transducer
Ink Volume Displacement In An Impulse Printhead With Bilaminar Transducer Hue Le and Ron Burr Tektronix, Inc., Wilsonville, Oregon Qiming Zhang and Qichang Xu Pennsylvania State University, University
More informationMLEP Intermediate GPS Workshop Exercise Two Using Maps
During this exercise, you will scale coordinates from a map and enter them into the GPS receiver. This requires a ruler (provided) and all calculations require a paper and pencil. During this exercise,
More informationMunicipal Service Park 3 December Consolidation of City services to one centralized complex
Municipal Service Park 3 December 2010 Consolidation of City services to one centralized complex Overview: Operational Challenges and Opportunities South East Connector impacts Opportunities: The South
More informationv SMS 11.1 Tutorial BOUSS2D Prerequisites Overview Tutorial Time minutes
v. 11.1 SMS 11.1 Tutorial BOUSS2D Objectives This lesson will teach you how to use the interface for BOUSS-2D and run the model for a sample application. As a phase-resolving nonlinear wave model, BOUSS-2D
More informationOffshore Platform Fluid Structure Interaction (FSI) Simulation
Offshore Platform Fluid Structure Interaction (FSI) Simulation Ali Marzaban, CD-adapco Murthy Lakshmiraju, CD-adapco Nigel Richardson, CD-adapco Mike Henneke, CD-adapco Guangyu Wu, Chevron Pedro M. Vargas,
More informationFinite Element Simulation using SPH Particles as Loading on Typical Light Armoured Vehicles
10 th International LS-DYNA Users Conference Penetration / Blast Finite Element Simulation using SPH Particles as Loading on Typical Light Armoured Vehicles Geneviève Toussaint and Robert Durocher Defence
More informationIsolated Process Current Input 7B32 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
Isolated Process Current Input 7B32 FEATURES Interfaces, amplifies and filters a process-current input. Module provides a precision output of either +1 V to +5 V or 0 V to +10 V, linear with temperature.
More informationDevelopment of MADYMO Models of Passenger Vehicles for Simulating Side Impact Crashes
SAE TECHNICAL PAPER SERIES 1999-01-2885 Development of MADYMO Models of Passenger Vehicles for Simulating Side Impact Crashes B. R. Deshpande, T. J. Gunasekar, V. Gupta and S. Jayaraman EASi S. M. Summers
More informationHOBO Pendant G Data Logger (UA ) White Paper
HOBO Pendant G Data Logger (UA-4-64) White Paper This white paper explains the operation of the HOBO Pendant G data logger (UA-4-64). Operating Principles The accelerometer used in the Pendant G logger
More information1.1 OVERVIEW OF THIS BOOK
1 Introduction 1.1 OVERVIEW OF THIS BOOK Today s datacom (data and communications) facility managers and operators understand the importance of protecting their business critical data and information technology
More informationEOSC 454 Lab #3. 3D Magnetics. Date: Feb 3, Due: Feb 10, 2009.
EOSC 454 Lab #3 3D Magnetics Date: Feb 3, 2009. Due: Feb 10, 2009. 1 Introduction In this exercise you will perform both forward models and inversions of magnetic data. You will compare the response of
More informationImpact-Echo Instruments, LLC. Ithaca, New York. Field Instruments for Nondestructive Evaluation of Concrete & Masonry
IEI Impact-Echo Instruments, LLC Ithaca, New York Field Instruments for Nondestructive Evaluation of Concrete & Masonry From the people who wrote the book on impact-echo (p. 7) Impact-Echo Instruments,
More informationModal Analysis of Exhaust System to Optimize Mounting Hanger Location
Modal Analysis of Exhaust System to Optimize Mounting Hanger Location Chetan D. Gaonkar Assistant Professor, Mechanical Engineering Dpt., DBCE, Margao, Goa Abstract An exhaust system with a superior performance
More informationFDM Lightweight Structures DESIGN GUIDE
FDM Lightweight Structures THE 3D PRINTING SOLUTIONS COMPANY FDM Lightweight Structures Many aerospace and automotive applications require parts with a very high stiffness-to-weight ratio. Because of the
More informationAISIBEAM User's Manual (Version 3.0)
AISIBEAM User's Manual (Version 3.0) Shabin Taavoni, Ph.D., PE, title Structural Software Inc. location John C. Huang Ph.D., PE, Principal CHC Engineering, LLC Herndon, VA Scope of Software The software
More informationDIGITAL PIGGING AS A BASIS FOR IMPROVED PIPELINE STRUCTURAL INTEGRITY EVALUATIONS
Proceedings of IPC 2006 International Pipeline Conference September 25-29, 2006 Calgary, Alberta, Canada IPC06-10349 DIGITAL PIGGING AS A BASIS FOR IMPROVED PIPELINE STRUCTURAL INTEGRITY EVALUATIONS James
More informationAdvanced Measurement Laboratory
National Nanotechnology Coordinating Office Nanoscale Science, Engineering and Technology (NSET) Subcommittee Committee on Technology National Science and Technology Council National Institute of Standards
More informationSCA620-EF1V1B SINGLE AXIS ACCELEROMETER WITH ANALOG INTERFACE
Datasheet SCA620-EF1V1B SINGLE AXIS ACCELEROMETER WITH ANALOG INTERFACE The SCA620 accelerometer consists of a silicon bulk micro machined sensing element chip and a signal conditioning ASIC. The chips
More informationChapter 3. Thermal Tutorial
Chapter 3. Thermal Tutorial Tutorials> Chapter 3. Thermal Tutorial Solidification of a Casting Problem Specification Problem Description Prepare for a Thermal Analysis Input Geometry Define Materials Generate
More informationTopics in Linguistic Theory: Laboratory Phonology Spring 2007
MIT OpenCourseWare http://ocw.mit.edu 24.910 Topics in Linguistic Theory: Laboratory Phonology Spring 2007 For information about citing these materials or our Terms of Use, visit: http://ocw.mit.edu/terms.
More informationRun multiple analyses which vary soil spring constants and damping ratio to account for uncertainties of soil data.
Heavier equipment with faster machine speeds coupled with higher costs have made rule-of-thumb approaches and "rigid structure" assumptions either unsafe or too conservative for the design of many structures
More information