1 Environmental Noise Study of Findlay Creek Public School 3010 Findlay Creek Drive, Ottawa, Ontario. R1 Prepared for: N45 Architecture Inc. Prepared by: Eric Sladic February 5 th, 2015

2 Contents 1.0 Introduction Facility Description Noise Sources Points of Reception Methodology Used in Noise Impact Calculation Acoustic Assessment Summary Conclusion... 13

3 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 1 of Introduction State of the Art Acoustik Inc. has been commissioned by N45 Architecture to complete an environmental noise study for the Findlay Creek Public School development to be located at 3010 Findlay Creek Drive, Ottawa, Ontario. Due to the school s proximity to local residences, this report s environmental noise assessment and design recommendations will ensure adherence to the City of Ottawa s noise by-law and the Environmental Noise Control Guidelines. This requires that the noise pressure level from all mechanical equipment must be below 50 dba SPL during the day and below 45dBA SPL during the night (or the existing background noise level, whichever is higher) at noise sensitive points of reception. This assessment assumes the mechanical equipment operates at all times. The significant noise sources which are being considered for this assessment are: o Twelve Roof Top Air Handling Units (RTUs): The acoustical data for the Aaon RTUs have been provided by McKee Engineering and have been confirmed to represent the full radiated noise power levels from the casing of the RTUs to the environment. This data has been summarized in Tables and o Two Washroom Exhaust Fans: As provided by McKee Engineering, these fans are 1300 c.f.m. and of the rooftop mounted domex style. The exact model is yet unknown. This report will use representative data from a similar 1300 c.f.m. Carnes Fan VEBK10P1 rooftop fan that is of the domex style. This data has been summarized in Tables and Facility Description The school building being reviewed will be located at 3010 Findlay Creek Drive at the intersection of Kelly Farm Drive in Ottawa, Ontario. It will be a 2 storey building which is approximately 8 meters tall and be located in a neighbourhood which contains residential buildings. 2.1 Operation hours for the Facility The twelve roof top air handling units (RTUs) and two exhaust fans are all assumed to run 24 hours a day, seven days a week. 2.2 Site Plan and Scaled Area Location Plan On the following page is a copy of the site plan (Figure 2.2.1) for the Findlay Creek School from N45 Architects and on the following page is a zoning plan (Figure 2.2.2) from the City of Ottawa GeoOttawa map service:

4 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 2 of 13 NORTH Figure Findlay Creek South Public School, Orleans, Ontario Site Plan

5 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 3 of 13 Kelly Farm Drive Zoning Info: I1E - Minor Institutional Zone (Sec ) NORTH Location of Findlay Creek School 100m 500ft Findlay Creek Drive Figure Location of Findlay Creek School Source City of Ottawa emaps 2.3 Noise By-Law and Noise Control Guidelines The City of Ottawa noise by-law no states: No person shall use or operate or cause to be used or operated any exhaust fan, exhaust system, intake fan, generators, dryer in a commercial car wash or similar device which includes combustion exhaust of a high efficiency furnace, the noise from which has a level greater than 50 dba when measured at the point of reception. The City of Ottawa Environmental Noise Control Guidelines (May 10, 2006) states that the highest permissible Noise Sound Pressure Level at the plane of window at a noise sensitive location in a Class 1 area at night is 45 dba SPL. Where the: "point of reception" means any point on the premises of a person where sound or vibration originating from other than those premises is received; For our analysis, the points of reception are chosen based on the principle of "predictable worst case scenario" for noise impact. This will allow us to calculate the largest noise impact and mitigate it accordingly.

6 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 4 of Noise Sources The following sections describe the characteristics of the noise source(s). 3.1 Significant Noise Sources Tables and summarize the sound power levels for the twelve Roof Top Air Handling Units (RTUs) and two exhaust fans. These RTU noise sources are located on the roof of the school and have been placed in the model based on information received from McKee Engineering. The locations of the RTUs can be found in Figures and on the next page. The RTU noise level data in the tables below (from Aaon data sheet in Appendix) are the total radiated sound power levels as provided by the equipment manufacturer, Aaon. Noise SWL Level Used in Manufacturer Model Quantity Sources Report (dba) RTUs Aaon RQ 2-3 Ton 1 78 RTUs Aaon RN 6-11 Ton 8 88 RTUs Aaon RN Ton 2 91 RTUs Aaon RN Ton 1 91 *Washroom Exhaust Fans Carnes VEBK10P1 2 72* Table Summary of Noise Power Levels Used in this Analysis (*see paragraph below) Noise Source 63Hz 125Hz 250Hz 500Hz 1KHz 2KHz 4KHz 8KHz Total dba RTU Aaon RQ 2-3 ton RTU Aaon RN 6-11Ton RTU Aaon RN Ton RTU Aaon RN Ton *Exhaust Fan, Carnes VEBK10P * Table Total Radiated Octave Band Sound Power Levels of Noise Sources in db as Provided by Aaon *Since the washroom exhaust fans have not been selected yet. This is representative data from known 1300 c.f.m. Carnes domex type washroom exhaust fans. However, since the total noise from both these fans combined (75dBA) is more than 10dBA lower the total noise from the other 12 RTUs, the noise from these fan can safely be omitted from this study. From this point on, we will not include the fans in this report.

7 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 5 of 13 Figure Location of 12 x RTUs on the Roof of the School as provide by McKee Eng. Locations of 12 RTUs as seen, looking to the N-E towards the intersection of Findlay Creek Dr. and Kelly Farm Dr. Figure D Illustration of RTU locations as seen in Acoustic Model NORTH

8 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 6 of Noise Source Summary Table Source ID Source Description 1 x RTU: Aaon RQ 2-3 ton 8 x RTU: Aaon RN 6-11 ton 2 x RTU: Aaon RN ton Source Location 1 Sound Characteristics 2 Noise Control Measures 3 Sound Power Level (dba) O S U 78* O S U 88* O S U 91* 1 x RTU: 4 O S U 91* Aaon RN ton Table 3.2 Acoustical Information for each significant source included in this study. 1. Source Location: O - located/installed outside the building, including on the roof I - located/installed inside the building 2. Sound Characteristics: S: Steady Q: Quasi Steady Impulsive I: Impulsive B: Buzzing T: Tonal C: Cyclic 3. Noise Control Measures S: silencer, acoustic louver, muffler A: acoustic lining, plenum B: barrier, berm, screening L: lagging E: acoustic enclosure O: other U: uncontrolled * This data may be found in the Appendix.

9 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 7 of Points of Reception Points of reception have been selected by using worst case situations for the following types of development: permanent or seasonal residences, hotels/motels, nursing/retirement homes, rental residences, hospitals, camp grounds, and noise sensitive buildings such as schools and places of worship. We have chosen three Points of Reception (POR) for the noise level analysis. POR1 is at ground level (1.5 meters high) at a residence located across the street on Kelly Farm Drive (approximately 65 meters to the North). POR2 is also at ground level (1.5 meters high) at a residence at the intersection of Kelly Farm Drive and Findlay Creek Drive which is approximately 70 meters to the North-East. POR3 is located at ground level (1.5 meters) at a residence which is located across the street on Findlay Creek Drive which is approximately 85 meters to the East. All the distances are measured from the closest wall of the school to the point of reception. These points are illustrated below. POR2 1.5m above 70 m POR1 1.5m above 65 m 85 m POR3 1.5m above NORTH Figure 3.3 Illustration of Points of Receptions and Significant Noise Sources (colours will display properly when this document is printed in colour or viewed on a computer) The minimum distances from the source building to the points of reception are stated below: POR1 Residence, 65 meters to the North (1.5 meters above ground) POR2 Residence, 70 meters to the North-East (1.5 meters above ground) POR3 Residence, 85 meters to the South-East (1.5 meters above ground)

10 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 8 of Methodology Used in Noise Impact Calculation The following sections describe the methodology and software used to model the sound pressure levels at the points of reception due to the noise sources while taking into account parameters such as source levels, distance, topography, barriers and building geometry. 5.1 Procedure Used to Assess Noise Impact at Each Point of Reception This environmental noise analysis was done using an environmental noise modeling software called Cadna/A which references ISO Cadna/A predicts environmental noise through calculations based on a 3D model which uses geometrical, landscape and topography data, combined with details of the proposed construction and the noise source power levels. We created a 3D rendering of the neighbourhood around the school and placed the noise sources in the model (represented by the blue 1 crosses) with the sound power levels described in this report. The colours 1 on the ground and building represent the sound pressure level in that area. Sound power levels per octave band were entered into the Cadna/A at the source s location and the resulting sound pressure levels were calculated at the points of reception. Other Parameters/Assumptions Used in Calculations The following chart describes the parameters used in the Cadna/A model: Parameter Value/Condition Temperature ( C) 10 Relative Humidity (%) 70 *All Buildings, Roads and Land Fully Reflective Absorption Coefficient Alpha = 0 Maximum Order of Reflection 2 *No sub. Of neg. Ground Att. ON *No neg. path difference ON Table 5.1 Parameters used in Cadna/A modeling. *These parameters set to simulate the worst case scenario for sound reflection

11 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 9 of Acoustic Assessment Summary This section summarizes the Cadna/A noise pressure mapping results. Section 6.1 below illustrates the steady state sound pressure levels generated by all the RTUs. Section 6.2 assesses the noise impact of quieter RTUs. 6.1 Acoustic Assessment Summary for All Equipment with Current RTUs The next two figures illustrate the predicted sound pressures due to the noise sources at the PORs. The first figure is in 2D with the colour map at a height of 1.5m (6.1.1) and the second is in 3D with the colour height of 1.5m (6.1.2). The figures are similar to a temperature map showing hot zones and cool zones. The red coloured zones are areas with levels at or above 50 dba (which is above the City of Ottawa noise by-law limit of 50dBA); green coloured zones are levels less than 50 dba. The legend attached to the image explains the different colour levels. POR1 52 dba SPL at 1.5m height POR2 48 dba SPL at 1.5m height POR3 51 dba SPL at 1.5m height Figure Model Results 1 : Sound Pressure Levels (SPL) due to Noise Sources 1 colours will display properly when this document is printed in colour or viewed on a computer

12 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 10 of 13 POR2 48 dba SPL at 1.5m height POR1 52 dba SPL at 1.5m height POR3 51 dba SPL at 1.5m height Figure Model Results 1 : Sound Pressure Levels (SPL) due to Noise Sources 1 colours will display properly when this document is printed in colour or viewed on a computer It can be seen in the figures above that the noise exceed 50dBA during the day and exceed 45dBA during the night. The Sound Pressure Levels are summarized below in Table Equipment POR1 (dba) POR2 (dba) POR3 (dba) 12 RTUs Table Sound Pressure Levels (dba) at PORs Under the worst case scenario (all 12 RTUs running), we predict that the RTUs produce sound pressure levels that are above the City of Ottawa noise by-law and guidelines during both the day and the night. Ideally, it would be recommended to have the noise levels at the most noise sensitive points of reception to be 3dBA below 45dBA (42 dba). This extra 3dBA safety margin would ensure compliance to the City of Ottawa noise by-law and guidelines. To reduce the noise the points of reception we propose that quieter RTUs be used. The next section investigates this.

13 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 11 of Acoustic Assessment Summary with Recommended Quieter RTUs In order to bring down the noise at the most sensitive points of reception (PORs) we recommend quieter RTUs. If quieter units cannot be found, other noise mitigation measures may have to be investigated such as a concrete barrier around all the units on the roof or relocation of the RTUs. Currently, the noise levels as seen in Table show that noise levels are as much as 7dBA above 45dBA SPL and 10dBA above our desired target of 42dBA SPL. In order to reduce the predicted noise levels we have reduced the overall sound powers of the RTUs in Table as show below in Table Noise Source 63Hz 125Hz 250Hz 500Hz 1KHz 2KHz 4KHz 8KHz Recommended Total SWL (dba) Current SWL RTU Aaon RQ 2-3 ton (unchanged) RTU Aaon RN 6-11Ton (reduced 7 dba total) RTU Aaon RN Ton (reduced 8 dba total) RTU Aaon RN Ton (reduced 8 dba total) Table Octave Band Sound Power Levels of RTUs with reduced Noise Levels Based on the above recommended quieter RTUs (11units reduced by 8dBA SWL and the smallest unit unchanged) the acoustic model predicts the following noise pattern and levels (Table below). These levels are below or very close to the target of 42dBA SPL. (dba)

14 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 12 of 13 POR2 41 dba SPL at 1.5m height POR1 43 dba SPL at 1.5m height POR3 41 dba SPL at 1.5m height Figure Model Results 1 : Sound Pressure Levels (SPL) due to Quieter RTUs 1 colours will display properly when this document is printed in colour or viewed on a computer

15 REP N45 FINDLAY CREEK PUBLIC SCHOOL - ENVIRONMENTAL NOISE ANALYSIS - R1 Page 13 of Conclusion We have found that the currently selected roof top units (with radiated sound power levels as provided by the manufacturer) will create noise levels at the most noise sensitive points of reception near the school which are up to 7dBA higher than is acceptable by the City of Ottawa. We recommend that the RTUs selected for this school to have radiated sound power levels at the casing which are not louder than as shown in Table This amounts to a 8dBA reduction in noise power levels for the 11 loudest RTUs which were presented to us. If RTUs with this reduction in radiated sound power levels can be selected, the worst case noise level at a sensitive point of reception will be 43dBA SPL (POR1 in Figure 6.2.1). This will be well below the City of Ottawa Noise by-law and Environmental Noise Control Guidelines for both the day and night with a 2dBA safety factor. Should you have any questions regarding this report, please do not hesitate to contact us. Prepared by: Reviewed by: Eric Sladic B.Sc., B.Eng. Acoustical Consultant Claude Fortier, Ph.D. Principal

16 APPENDIX

17 AAON Condenser Radiated Sound Levels Sound Power Level Fans Dia RPM LwA Inlet HB 2-3 Ton Outlet Total Inlet HB 4-5 Ton Outlet Total Inlet RQ 2-3 Ton Outlet Total Inlet RQ 4-5 Ton Outlet Total Inlet RN 6-11 Ton Outlet RN Ton RN Ton Total Inlet Outlet Total Inlet Outlet Total Inlet RN Ton Outlet Total Inlet RN Ton Outlet Total Inlet RN Ton Outlet Total Inlet RN Ton Outlet Total Inlet RN 90 Ton Outlet Total Inlet RN Ton Outlet Total Inlet RN Ton MC Outlet Total Inlet RN Ton MC Outlet Total This is the total radiated sound data for the rooftop units. The only models used will be the RN and RQ units. The sizes for the rooftop units are as follows: RTU-1 = 16 tons RTU-2 = 10 tons RTU-3 = 8 tons RTU-4 = 8 tons RTU-5 = 9 tons RTU-6 = 8 tons RTU-7 = 7 tons RTU-8 = 2 tons RTU-9 = 14 tons RTU-10 = 12 tons RTU-11 = 9 tons RTU-12 = 7 tons

18

REP N BANK ST. ENVIRONMENTAL NOISE STUDY Page 1 of 14

REP N BANK ST. ENVIRONMENTAL NOISE STUDY Page 1 of 14 REP N45 852 BANK ST. ENVIRONMENTAL NOISE STUDY Page 1 of 14 2014-06-02 Robert Matthews, B.ARCH., O.A.A., A.A.N.B., R.A.I.C. N45 ARCHITECTURE INC. 2nd floor, 43 Eccles Street Ottawa, Ontario Canada K1R

More information

Stationary Noise Feasibility Assessment. 10 Cope Drive. Ottawa, Ontario

Stationary Noise Feasibility Assessment. 10 Cope Drive. Ottawa, Ontario Stationary Noise Feasibility Assessment 10 Cope Drive Ottawa, Ontario REPORT: GWE17-196 - Stationary Noise Prepared For: Alex Turner Taggart Realty Management 225 Metcalfe Street, Suite 708 Ottawa, ON

More information

APPENDIX S HORIZONTAL DIRECTIONAL DRILLING (HDD) ENVIRONMENTAL SOUND LEVEL ASSESSMENT REPORT

APPENDIX S HORIZONTAL DIRECTIONAL DRILLING (HDD) ENVIRONMENTAL SOUND LEVEL ASSESSMENT REPORT ALASKA LNG PROJECT DOCKET NO. CP17- -000 RESOURCE REPORT NO. 9 APPENDIX S HDD ENVIRONMENTAL SOUND LEVEL ASSESSMENT REPORT PUBLIC DOC NO: USAI-PE-SRREG-00-000009-000 DATE: APPENDIX S HORIZONTAL DIRECTIONAL

More information

The noise of cloud computing

The noise of cloud computing The noise of cloud computing Radek Kochanowski (1) (1) Acoustic Engineer, Aurecon, Sydney, Australia ABSTRACT With Cloud computing and Cloud data storage being sold as the way of the future for storing

More information

Calculation of sound propagation and prediction of noise levels inside

Calculation of sound propagation and prediction of noise levels inside Ottawa, Canada INTER-NOISE 2009 2009 August 23-26 Calculation of sound propagation and prediction of noise levels inside Wolfgang Probst, Heinrich A. Metzen DataKustik GmbH Gewerbering 5 86926 Greifenberg

More information

CONTROLLING ROOFTOP UNIT (RTU) NOISE

CONTROLLING ROOFTOP UNIT (RTU) NOISE HUSHCORE Acoustical Products & Systems Technical Discussion General Information Terminology & Definitions Product Types Treatment Strategies Applications/Uses Industrial Architectural HVAC OEM Environmental

More information

EBR Application for Review Request to Review Environmental Compliance Approval Cruickshank Construction Limited Elginburg Quarry, Kingston

EBR Application for Review Request to Review Environmental Compliance Approval Cruickshank Construction Limited Elginburg Quarry, Kingston EBR Application for Review Request to Review Environmental Compliance Approval Cruickshank Construction Limited Elginburg Quarry, Kingston Decision Summary EBRO File No.: 16EBR001.R Issue: The Ministry

More information

Rooftop Unit System Solution. for noise, vibration, and seismic/wind effects

Rooftop Unit System Solution. for noise, vibration, and seismic/wind effects Rooftop Unit System Solution for noise, vibration, and seismic/wind effects Rooftop Units Noise Problems RTUs are currently the most common cause of noise in HVAC, and thus a major reason for tenant complaints.

More information

CORSAIR HD120 RGB LED High Performance RGB LED 120mm PWM Fan

CORSAIR HD120 RGB LED High Performance RGB LED 120mm PWM Fan Embargo Date 9/02/16 First Customer Ship Date N/A Product Full Name CORSAIR HD120 RGB LED Etail Product Title CORSAIR HD Series, HD120 RGB LED, 120mm High Performance Individually Addressable RGB LED PWM

More information

ROOFTOP UNIT NOISE CONTROL SOLUTIONS

ROOFTOP UNIT NOISE CONTROL SOLUTIONS ROOFTOP UNIT NOISE CONTROL SOLUTIONS NOISE PROBLEMS RTUs are one of the most common causes of HVAC noise problems and a major reason for tenant complaints. ROOFTOP UNITS The most commonly used heating,

More information

Projects with. Successful symbiosis of acoustics and software

Projects with. Successful symbiosis of acoustics and software Cadna A for Windows is a softwareprogram for prediction and assessment of noise levels in the vicinity of: industrial facilities, sport- and leisure facilities, roads and railways, airports and any other

More information

TECHNICAL DATA SHEET DS 16S/DS 16SE. FreeSpace. Loudspeakers. Product Overview. Key Features. Product Information. Applications

TECHNICAL DATA SHEET DS 16S/DS 16SE. FreeSpace. Loudspeakers. Product Overview. Key Features. Product Information. Applications Product Overview Bose FreeSpace DS 16S and FreeSpace DS 16SE loudspeakers are high-performance, surfacemount loudspeakers designed for background music and speech reproduction in a wide range of commercial

More information

KINETICS Vibration Isolation Manual

KINETICS Vibration Isolation Manual The Pitfalls of Combining Internal & External Equipment Isolation Introduction: Almost all Make-up Air Units (MAU), Air Handling Units (AHU), and Rooftop Units (RTU) have internal spring-type isolation

More information

TECHNICAL DATA SHEET. FreeSpace DS 100SE. Loudspeaker. Product Overview. Key Features. Product Information. Applications

TECHNICAL DATA SHEET. FreeSpace DS 100SE. Loudspeaker. Product Overview. Key Features. Product Information. Applications Product Overview The Bose FreeSpace DS 100SE loudspeaker is a high-performance, surface-mount loudspeaker designed for foreground music and speech reproduction in a wide range of commercial applications,

More information

ANP Data Verification and Validation

ANP Data Verification and Validation ANP Data Verification and Validation JRC Workshop 19-20 January Brussels Laurent Cavadini The European Organisation for the Safety of Air Navigation ANP Data - Contents and Formats Aircraft table Jet engine

More information

PCIe Electromechanical Updates Yun Ling Intel Corporation

PCIe Electromechanical Updates Yun Ling Intel Corporation PCIe Electromechanical Updates Yun Ling Intel Corporation * Third party marks and brands are the property of their respective owners. Agenda 225/300 Watt High Power CEM Spec Overview System Volumetric

More information

Changes and innovations delivered with SoundPLAN version 7.0

Changes and innovations delivered with SoundPLAN version 7.0 Changes and innovations delivered with SoundPLAN version 7.0 Highlights New layout and more information in the SoundPLAN Manager New Dynamic Search calculation core with Multi-threading, higher accuracy

More information

Alternative Site Analysis

Alternative Site Analysis Attachment 4F Grand & 13 th Alternative Site Analysis The location of a wireless telecommunications facility to fulfill the above referenced service objective is dependent upon many different factors,

More information

Acoustic Nozzle Design for Fire Protection Application

Acoustic Nozzle Design for Fire Protection Application Acoustic Nozzle Design for Fire Protection Application Melissa A. Loureiro, Alan Elder, Arash Ahmadzadegan Johnson Controls, Cranston, RI, USA Abstract Data centers are relied upon to store and distribute

More information

Content Copy Of Original

Content Copy Of Original Content Copy Of Original Ministry of the Environment and Climate Change Ministère de l Environnement et de l Action en matière de changement climatique Hydro One Networks Inc. 483 Bay St 14th Floor, South

More information

Duct Pulsation Problem Captured and Solved Using STAR-CCM+

Duct Pulsation Problem Captured and Solved Using STAR-CCM+ Duct Pulsation Problem Captured and Solved Using STAR-CCM+ Eric Duplain, Eng., M.Eng. (BMA) François McKenty, Eng., Ph.D. (BMA) Normand Brais, Eng., Ph.D. (BMA) John Viskup, President (Victory Energy)

More information

Gardner Denver / Tamrotor Enduro 12 Rotary Screw Compressor, with Adaptable Compressor Speed, designed to produce more gas flow per bhp.

Gardner Denver / Tamrotor Enduro 12 Rotary Screw Compressor, with Adaptable Compressor Speed, designed to produce more gas flow per bhp. Technical Specifications Compressor Gardner Denver / Tamrotor Enduro 12 Rotary, with Adaptable Compressor Speed, designed to produce more gas flow per bhp. Engine Cummins G5.9, 6 cylinder natural gas engine.

More information

Product Library and ISO 16757

Product Library and ISO 16757 Product Library and ISO 16757 Wolfgang Wilkes Bjørn Stangeland Manfred Pikart 1 Building information modelling and catalogues Building Owner s Data : Requirements, Restrictions... Manufacturer s Data:

More information

Gardner Denver / Tamrotor Enduro 25 Rotary Screw Compressor, with Adaptable Compressor Speed, designed to produce more gas flow per bhp.

Gardner Denver / Tamrotor Enduro 25 Rotary Screw Compressor, with Adaptable Compressor Speed, designed to produce more gas flow per bhp. Technical Specifications Compressor Gardner Denver / Tamrotor Enduro 25 Rotary, with Adaptable Compressor Speed, designed to produce more gas flow per bhp. Engine Cummins G8.3, 6 cylinder natural gas engine.

More information

SoundPLAN Designing a Sound Environment

SoundPLAN Designing a Sound Environment SoundPLAN Designing a Sound Environment A&WMA Ontario Section Air Quality and Environmental Acoustic Modeling Conference October 22, 2013 Presented by Hans Forschner Navcon Engineering Network Trends North-America

More information

Rectangular straight silencer

Rectangular straight silencer silencer DLD Dimensions b a l Description DLD has a conventional design with dimensions that not exceed the corresponding connection dimensions. The silencer can be manufactured in all standard duct sizes.

More information

Calibration. Calibration Overview CHAPTER

Calibration. Calibration Overview CHAPTER CHAPTER 21 Calibration Calibration Overview Sensitivity Determination The primary role of sound level meter calibration is to establish a numerical relationship between the sound level at the diaphragm

More information

SoundPLAN Special 4/2012

SoundPLAN Special 4/2012 If you are not a SoundPLAN user and want to experiment with the capabilities of the Facade Noise Map to see how easy it is to get EU noise statistics, please feel free to download the demo version from

More information

Product Overview. Cisco ME 6524 Ethernet Switch (ME-C6524GS-8S) CHAPTER

Product Overview. Cisco ME 6524 Ethernet Switch (ME-C6524GS-8S) CHAPTER 2 7 CHAPTER This chapter describes the Cisco ME 00 series Ethernet switches and contains these sections: Cisco ME 2 Ethernet Switch (ME-C2GS-8S), page - Cisco ME 2 Ethernet Switch (ME-C2GT-8S), page -7

More information

ARLINGTON COUNTY, VIRGINIA

ARLINGTON COUNTY, VIRGINIA ARLINGTON COUNTY, VIRGINIA County Board Agenda Item Meeting of December 12, 2015 DATE: December 1, 2015 SUBJECT: SP-84-U-15-1 USE PERMIT ASSOCIATED WITH A SITE PLAN for a telecommunications facility; located

More information

Perforated diffuser PAKA, PBKA, PCKA, PDKA, PEKA

Perforated diffuser PAKA, PBKA, PCKA, PDKA, PEKA Perforated diffuser PAKA, PBKA, PCKA, PDKA, PEKA TECHNICAL DATA - 0 page Perforated diffuser PAKA, PBKA, PCKA, PDKA, PEKA Diffusers with perforated panels type PAKA, PBKA, PCKA, PDKA, PEKA can be used

More information

NEOSTAR AXIAL FAN CONDENSER COMMERCIAL AND INDUSTRIAL RANGE HFC. 18 > 1240 kw. NEOSTAR POWER The choice of performance and low space requirement.

NEOSTAR AXIAL FAN CONDENSER COMMERCIAL AND INDUSTRIAL RANGE HFC. 18 > 1240 kw. NEOSTAR POWER The choice of performance and low space requirement. AXIAL FAN CONDENSER COMMERCIAL AND INDUSTRIAL RANGE Hard Discount - Supermarkets - Hypermarkets Refrigerated storage and transit stocking - Dispatch centres Food processing - Canteen kitchens HFC 18 >

More information

Application of Modular, Rapidly Deployable CBR Filtration and Environmental Conditioning Systems for Building Collective Protection

Application of Modular, Rapidly Deployable CBR Filtration and Environmental Conditioning Systems for Building Collective Protection Application of Modular, Rapidly Deployable CBR Filtration and Environmental Conditioning Systems for Building Collective Protection Carl S. Pates III, Ph.d, P.E., New World Associates John Milligan, P.E.,

More information

Scale model measurements of the acoustic performance of vented and absorptive road covers

Scale model measurements of the acoustic performance of vented and absorptive road covers Scale model measurements of the acoustic performance of vented and absorptive road covers Isabelle Schmich, Jerôme Defrance, Gabriel Kirie, Pierre Bruder Centre Scientifique et Technique du Bâtiment (CSTB),

More information

Digital "Mini" SiSonic TM Microphone Specification - Halogen Free. Knowles Acoustics 1151 Maplewood Drive Itasca, IL 60143

Digital Mini SiSonic TM Microphone Specification - Halogen Free. Knowles Acoustics 1151 Maplewood Drive Itasca, IL 60143 Digital "Mini" SiSonic TM Microphone Specification - Halogen Free Knowles Acoustics 1151 Maplewood Drive Itasca, IL 60143 Sheet 1 of 11 1. DESCRIPTION AND APPLICATION 1.1 DESCRIPTION Digital "Mini" Surface

More information

NSRT_mk2. Data Sheet. June Bruno Paillard

NSRT_mk2. Data Sheet. June Bruno Paillard NSRT_mk2 Data Sheet June 8 2018 Bruno Paillard 1 PRODUCT DESCRIPTION 2 2 APPLICATIONS 2 3 SPECIFICATIONS 3 3.1 Frequency Response 4 4 NS_RT_MANAGER APPLICATION SPECIFICATIONS 4 5 OTHER APPLICATIONS 5 NSRT_mk2

More information

DUCTED SPLIT SYSTEMS With Scroll compressors

DUCTED SPLIT SYSTEMS With Scroll compressors DUCTED SPLIT SYSTEMS With Scroll compressors 2 Benefits TOTAL COMFORT ON WIDE AREAS The Ducted Blower Split Systems for light commercial applications of DXDXT-M/K series are the ideal solution for keeping

More information

Disk. Zone 7 (Inner) Data tracks per surface: Data sectors per track: Data bytes per track: Zone 3. Zone 4

Disk. Zone 7 (Inner) Data tracks per surface: Data sectors per track: Data bytes per track: Zone 3. Zone 4 return to original page HP SureStore Disks C2244, C2245, C2246, and C2247 - Technical Specifications In this document: HP SureStore Disks C2244, C2245, C2246, and C2247 technical specifications Table of

More information

Transition Flow and Aeroacoustic Analysis of NACA0018 Satish Kumar B, Fred Mendonç a, Ghuiyeon Kim, Hogeon Kim

Transition Flow and Aeroacoustic Analysis of NACA0018 Satish Kumar B, Fred Mendonç a, Ghuiyeon Kim, Hogeon Kim Transition Flow and Aeroacoustic Analysis of NACA0018 Satish Kumar B, Fred Mendonç a, Ghuiyeon Kim, Hogeon Kim Transition Flow and Aeroacoustic Analysis of NACA0018 Satish Kumar B, Fred Mendonç a, Ghuiyeon

More information

NSRT_mk2. Data Sheet. June Bruno Paillard

NSRT_mk2. Data Sheet. June Bruno Paillard NSRT_mk2 Data Sheet June 23 2017 Bruno Paillard 1 PRODUCT DESCRIPTION 2 2 APPLICATIONS 2 3 SPECIFICATIONS 2 3.1 Frequency Response 4 4 NS_RT_MANAGER APPLICATION SPECIFICATIONS 4 5 OTHER APPLICATIONS 5

More information

Data Sheet FUJITSU Server PRIMERGY CX420 S1 Out-of-the-box Dual Node Cluster Server

Data Sheet FUJITSU Server PRIMERGY CX420 S1 Out-of-the-box Dual Node Cluster Server Data Sheet FUJITSU Server PRIMERGY CX420 S1 Out-of-the-box Dual Node Cluster Server Data Sheet FUJITSU Server PRIMERGY CX420 S1 Out-of-the-box Dual Node Cluster Server High availability for lower expertise

More information

Z-Wave Ceiling-mount Smoke Detector HZS-200E/HZS-200A

Z-Wave Ceiling-mount Smoke Detector HZS-200E/HZS-200A Z-Wave Ceiling-mount Smoke Detector Copyright Z-Wave Ceiling-mount Smoke Detector Copyright 2015 by PLANET Technology Corp. All rights reserved. No part of this publication may be reproduced, transmitted,

More information

Johnson Controls York Acoustics

Johnson Controls York Acoustics Johnson Controls York Acoustics If you can read this Click on the icon to choose a picture or Reset the slide. To Reset: Right click on the slide thumbnail and select reset slide or choose the Reset button

More information

Data Sheet FUJITSU Server PRIMERGY CX400 M1 Scale out Server

Data Sheet FUJITSU Server PRIMERGY CX400 M1 Scale out Server Data Sheet FUJITSU Server Scale out Server Data Sheet FUJITSU Server Scale out Server Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing FUJITSU Server PRIMERGY will give you the servers you

More information

MONTE VILLA FARMS MONTE VILLA PARKWAY BOTHELL, WASHINGTON

MONTE VILLA FARMS MONTE VILLA PARKWAY BOTHELL, WASHINGTON 70,000 94,000 RSF AVAILABLE» High visibility landmark office, assembly and life sciences campus» Convenient freeway access to I-405» Abundant surface parking» High-end Russell s restaurant including catering

More information

HV-STYLVENT Series WALL OR WINDOW EXTRACT FANS. Wall or window extract fans HV-STYLVENT. Elegant design harmonising with any environment

HV-STYLVENT Series WALL OR WINDOW EXTRACT FANS. Wall or window extract fans HV-STYLVENT. Elegant design harmonising with any environment WALL OR WINDOW EXTRACT FANS HV-STYLVENT Series 688 679 Shutter Reversible Natural ventilation position Complete range of axial flow fans for wall or window mounting applications. All the fans are supplied

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Floormaster DVQA, quarter-cylindrical terminals

Floormaster DVQA, quarter-cylindrical terminals Floormaster DVQA are quarter-cylindrical supply air terminals for positioning on the floor in a corner. The terminals are designed for displacement air handling in accordance with the Floormaster system

More information

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net Digi-RTU WHAT IS THE DIGI-RTU The Digi-RTU is a Heating, Ventilation, and Air Conditioning (HVAC) rooftop unit control kit that is both a demand management and energy usage device. It is designed to improve

More information

VIREO Ceiling with ALX

VIREO Ceiling with ALX Square ceiling air diffuser with nozzles for supply air, with plenum box QUICK FACTS Flush design Suitable for VAV-applications Fast and easy installation Sealing ring, standard for spigot Energy efficient

More information

Atrium Design Strategies for Daylighting and Natural Ventilation

Atrium Design Strategies for Daylighting and Natural Ventilation GreenBuild: International Conference & Expo Atrium Design Strategies for Daylighting and Natural Ventilation S. Faruq Ahmed, PE ahmed@burthill.com Pittsburgh, Pennsylvania November 12 14, 2003 P. Richard

More information

Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure

Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure Scale-Out Smart for HPC and Cloud Computing with enhanced

More information

IBIS. Duct diffuser with discs for supply air QUICK FACTS

IBIS. Duct diffuser with discs for supply air QUICK FACTS Duct diffuser with discs for supply air QUICK FACTS 0 flexible distribution pattern Suspended installation Easy installation Modular length: 00 mm Standard colour White RAL 900 -- alternative standard

More information

Bremner Transformer Station and Cable Tunnel PROGRESS OF THE CLASS ENVIRONMENTAL ASSESSMENT STUDY

Bremner Transformer Station and Cable Tunnel PROGRESS OF THE CLASS ENVIRONMENTAL ASSESSMENT STUDY May 19, 2011 Community Meeting Metro Toronto Convention Centre North Building, Room 203B May 19 th, 2011, 4:30 p.m. to 7:30 p.m. Please sign in and complete a comment sheet Project team members are available

More information

HPA4202 1/5. 2-Channel High Power Multi-Impedance Amplifier. General Description. Features. Applications. AtlasIED.com. HPA4202 Front.

HPA4202 1/5. 2-Channel High Power Multi-Impedance Amplifier. General Description. Features. Applications. AtlasIED.com. HPA4202 Front. 1/5 HPA4202 2-Channel High Power Multi-Impedance Amplifier Features 70.7V/100V and 2Ω, 4Ω, and 8Ω Output 100V 70.7V 8Ω 2 x 1200W 4Ω 2Ω 2 x 2500W 8Ω BRIDGED 1 x 3800W 4Ω BRIDGED 1 x 4800W Balanced Inputs

More information

PRESSURE DROP AND FLOW UNIFORMITY ANALYSIS OF COMPLETE EXHAUST SYSTEMS FOR DIESEL ENGINES

PRESSURE DROP AND FLOW UNIFORMITY ANALYSIS OF COMPLETE EXHAUST SYSTEMS FOR DIESEL ENGINES PRESSURE DROP AND FLOW UNIFORMITY ANALYSIS OF COMPLETE EXHAUST SYSTEMS FOR DIESEL ENGINES André Bergel 1 Edson L. Duque 2 General Motors Global Propulsion Systems South America 12 E-mail: andrebergel84@yahoo.com.br

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Data Sheet FUJITSU JX60 S2 DAS Subsystem

Data Sheet FUJITSU JX60 S2 DAS Subsystem Data Sheet FUJITSU JX60 S2 DAS Subsystem Data Sheet FUJITSU JX60 S2 DAS Subsystem High-capacity Direct Attached Storage (DAS) subsystem FUJITSU JX DAS Subsystem Data centers today are evolving, adopting

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -H Performance High Plume April 07 Laboratory Exhaust Systems Model Vektor -H Table of Contents Vektor-H Specification Chart.... Plume Height Calculation... Quick Select

More information

Data Sheet Fujitsu Server PRIMERGY CX400 M1 Compact and Easy

Data Sheet Fujitsu Server PRIMERGY CX400 M1 Compact and Easy Data Sheet Fujitsu Server Compact and Easy Data Sheet Fujitsu Server Compact and Easy Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing The Fujitsu Server helps to meet the immense challenges

More information

Acoustical investigation of open-plan offices in green building: Simulation experiment

Acoustical investigation of open-plan offices in green building: Simulation experiment Acoustical investigation of open-plan offices in green building: Simulation experiment Nazli CHE DIN 1 ; Nurul Amira Abd JALIL; Nila Inangda KEUMALA; Asrul Sani RAZAK Department of Architecture, Faculty

More information

Data Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server

Data Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server Data Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server Workload-specific power in a modular form factor FUJITSU Server PRIMERGY will give you the servers you need to power any workload and changing

More information

Licensees Name: New Gullen Range Wind Farm Pty Ltd. Address of licenced premise: Gullen Range Wind Farm 250 Storriers Lane Banniester NSW 2580

Licensees Name: New Gullen Range Wind Farm Pty Ltd. Address of licenced premise: Gullen Range Wind Farm 250 Storriers Lane Banniester NSW 2580 New Gullen Range Wind Farm Pty Ltd ACN 167 4 211 Correspondence Address: Level 21, 1 York Street Sydney, NSW 2000 info@gullenrangewindfarm.com Toll Free: 1800 9711 Description: The following report was

More information

Efficiency of application the liquid cooling system in a personal hybrid computing system based on graphics processors

Efficiency of application the liquid cooling system in a personal hybrid computing system based on graphics processors Efficiency of application the liquid cooling system in a personal hybrid computing system based on graphics processors D. Akhmedov, S. Yelubayev, F. Abdoldina, T. Bopeyev, D. Muratov Institute of space

More information

2 Telecommunications Data Center Facility Requirements

2 Telecommunications Data Center Facility Requirements Generic Requirements for Telecommunications Data Center Equipment and Spaces GR-3160-CORE Table of Contents Table of Contents Generic Requirements Notice of Disclaimer..................... iii Preface...........................................

More information

Application of TileFlow to Improve Cooling in a Data Center

Application of TileFlow to Improve Cooling in a Data Center Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance

More information

APPENDIX. Larson Davis CAL200. Technical Reference Manual. I200.1 Rev F

APPENDIX. Larson Davis CAL200. Technical Reference Manual. I200.1 Rev F APPENDIX Larson Davis CAL200 Technical Reference Manual I200.1 Rev F Copyright Copyright 2006, 2007, 2008, 2009, 2010 by PCB Piezotronics, Inc. This manual is copyrighted, with all rights reserved. The

More information

MONITOR MR5S/MR5SW. Compact Two-Way Speaker. Safety First! Quick-Start Guide

MONITOR MR5S/MR5SW. Compact Two-Way Speaker. Safety First! Quick-Start Guide The MR5S (Black) and MR5SW (White) are a compact two-way speaker system designed for constant-impedance systems. The 5" carbon fiber woofer, in combination with a 0.75" soft dome tweeter mounted on a 105

More information

Wireless Telecommunication Facility

Wireless Telecommunication Facility Wireless Telecommunication Facility PROJECT DESCRIPTION SITE: CN4973 Solano & Curtis APN# 067-2847-015-04 Address: 1495 Solano Avenue Albany, CA 94706 REPRESENTATIVE: Valerie Tallerico 7901 Stoneridge

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

Personal Sound Level Meter

Personal Sound Level Meter User's Guide Personal Sound Level Meter Model SL10 Introduction Congratulations on your purchase of the Extech SL10 Personal Sound Level Meter. The SL10 measures and displays sound pressure levels in db

More information

General-Purpose 8-Slot Chassis for PXI

General-Purpose 8-Slot Chassis for PXI NI Series 0 to 55 C extended temperature range () 43 dba acoustic emissions (Q) Accept both 3U PXI and CompactPCI modules Comply with all PXI and CompactPCI Specifications Low-jitter internal 10 MHz reference

More information

NSRTW_mk2. Data Sheet. Nov Bruno Paillard

NSRTW_mk2. Data Sheet. Nov Bruno Paillard NSRTW_mk2 Data Sheet Nov 15 2017 Bruno Paillard 1 PRODUCT DESCRIPTION 2 2 APPLICATIONS 2 3 SPECIFICATIONS 3 3.1 Frequency Response 4 4 NS_RT_MANAGER APPLICATION SPECIFICATIONS 4 5 OTHER APPLICATIONS 5

More information

AIR COOLED CONDENSERS

AIR COOLED CONDENSERS AIR COOLED CONDENSERS NQAC Quiet Line HNSQAC NQAC Quiet Line kw () Highly efficient external rotor fan motors give optimum performance with low noise levels Multiple fans (on all except smallest models)

More information

IBISTM. Duct diffuser with discs for supply air

IBISTM. Duct diffuser with discs for supply air TM Duct diffuser with discs for supply air Quick facts 0 flexible distribution pattern High induction capacity Suspended installation Easy installation Modular length: 00 mm Available in alternative colours

More information

OPERATING MANUAL. Measurement Microphones

OPERATING MANUAL. Measurement Microphones OPERATING MANUAL Measurement Microphones Contact NTi Audio at Headquarters +423 239 6060 info@nti-audio.com Americas +1 503 684 7050 americas@nti-audio.com China +86 512 6802 0075 china@nti-audio.com Czech

More information

REDUCING NOISE AND OPTIMIZING SOUND WITHIN WORKING SPACES

REDUCING NOISE AND OPTIMIZING SOUND WITHIN WORKING SPACES The 21 st International Congress on Sound and Vibration 13-17 July, 2014, Beijing/China REDUCING NOISE AND OPTIMIZING SOUND WITHIN WORKING SPACES Fabian Probst DataKustik GmbH, Gewerbering 5, 86926 Greifenberg,

More information

Thermal Design Tool for Outdoor Space Based on a Numerical Simulation System Using 3D-CAD

Thermal Design Tool for Outdoor Space Based on a Numerical Simulation System Using 3D-CAD September 2004 Page 1 of 6 Thermal Design Tool for Outdoor Space Based on a Numerical Simulation System Using 3D-CAD Takashi Asawa 1, Akira Hoyano 1 and Kazuaki Nakaohkubo 1 1 Tokyo Institute of Technology,

More information

COMPRESSED AIR SAVINGS CALCULATOR USER GUIDE. Contents SMART $AVER CUSTOM INCENTIVES CUSTOM-TO-GO

COMPRESSED AIR SAVINGS CALCULATOR USER GUIDE. Contents SMART $AVER CUSTOM INCENTIVES CUSTOM-TO-GO COMPRESSED AIR SAVINGS CALCULATOR USER GUIDE SMART $AVER CUSTOM INCENTIVES CUSTOM-TO-GO Contents 1. GETTING STARTED... 2 2. MEASURE TOOL DESCRIPTION... 2 2.1. Appropriate Use of the Tool... 3 2.2. Applicable

More information

PERFORMANCE DATA SCD. SCD 12 in. x 12 in. Face Size. SCD 20 in. x 20 in. Face Size. Square Cone Diffuser

PERFORMANCE DATA SCD. SCD 12 in. x 12 in. Face Size. SCD 20 in. x 20 in. Face Size. Square Cone Diffuser 12 in. x 12 in. Face 4 Neck Velocity (fpm) 400 00 00 00 00 900 00 1200 1400 0 Velocity Pressure (in. w.g.)..01.022.031.040.00.02.090.122..013.021.030.041.04.0.04.121.1.21 Flow Rate (cfm) 3 44 2 1 0 4 122

More information

Knowles Acoustics 1151 Maplewood Drive Itasca, IL 60143

Knowles Acoustics 1151 Maplewood Drive Itasca, IL 60143 Zero Height SiSonic Microphone Specification Knowles Acoustics 1151 Maplewood Drive Itasca, IL 60143 1of 10 1. DESCRIPTION AND APPLICATION 1.1 Description Zero Height Surface Mount Silicon Microphone 1.2

More information

HV-STYLVENT Series WALL OR WINDOW EXTRACT FANS HV-STYLVENT. Wall or window extract fans. Elegant design harmonising with any environment

HV-STYLVENT Series WALL OR WINDOW EXTRACT FANS HV-STYLVENT. Wall or window extract fans. Elegant design harmonising with any environment WALL OR WINDOW EXTRACT FANS Series Complete range of axial flow fans for wall or window mounting applications. All the fans are supplied with tough ABS plastic grilles, shutter and single phase V- 5Hz

More information

PowerLINE 1000, 1010 and 1200 Adapters

PowerLINE 1000, 1010 and 1200 Adapters 1000, 1010 and 1200 Adapters User Manual Models PL1000, PL1000v2 PL1010, PL1010v2 PLP1000 PLW1000, PLW1000v2 PLW1010, PLW1010v2 PL1200 PLP1200 January 2017 202-11566-03 350 E. Plumeria Drive San Jose,

More information

Three Hundred. User s Manual Manuel de l utilisateur Anwenderhandbuch Manuale per l operatore Manual del usuario

Three Hundred. User s Manual Manuel de l utilisateur Anwenderhandbuch Manuale per l operatore Manual del usuario Three Hundred User s Manual Manuel de l utilisateur Anwenderhandbuch Manuale per l operatore Manual del usuario At Antec, we continually refine and improve our products to ensure the highest quality. As

More information

The 5.8mm diameter ROM-2235L-HD-R is designed for extreme fidelity in a compact housing with true 20 Hz to 20 khz performance.

The 5.8mm diameter ROM-2235L-HD-R is designed for extreme fidelity in a compact housing with true 20 Hz to 20 khz performance. Data Sheet ROM-2235L-HD-R PUI Audio s all-new HD Series microphones use premium-grade FETs and diaphragms for high sensitivity and superior signal-to-noise ratio. Each microphone features GSM buzz-blocking

More information

diffusers F24 PERFORMANCE DATA PERFORMANCE DATA ML-37 / ½" SLOT SPACING WIDTH / SUPPLY WITH CONTINUOUS PLENUM Throw correction multiplier for length

diffusers F24 PERFORMANCE DATA PERFORMANCE DATA ML-37 / ½ SLOT SPACING WIDTH / SUPPLY WITH CONTINUOUS PLENUM Throw correction multiplier for length ML-37 / ½" SLOT SPACING WIDTH / SUPPLY WITH CONTINUOUS PLENUM 5-Slot 6-Slot 7-Slot 8-Slot Airflow, cfm/ft. 5 10 16 21 26 31 36 42 47 NC (Noise Criteria) - - 20 27 32 37 40 44 46 Horizontal 1-1-6 3-6-12

More information

Noise-Sentry-RT- Wireless Network

Noise-Sentry-RT- Wireless Network Noise-Sentry-RT- Wireless Network Data Sheet Sept 2nd 2014 Bruno Paillard 1 PRODUCT DESCRIPTION 2 2 APPLICATIONS 2 3 SPECIFICATIONS 2 3.1 Frequency Response 4 4 NS_RT_MANAGER APPLICATION SPECIFICATIONS

More information

A ROOM ACOUSTICAL COMPUTER MODEL FOR INDUSTRIAL ENVIRONMENTS - THE MODEL AND ITS VERIFICATION

A ROOM ACOUSTICAL COMPUTER MODEL FOR INDUSTRIAL ENVIRONMENTS - THE MODEL AND ITS VERIFICATION page number:1 A ROOM ACOUSTICAL COMPUTER MODEL FOR INDUSTRIAL ENVIRONMENTS - THE MODEL AND ITS VERIFICATION Claus Lynge Christensen Department of Acoustic Technology, Technical University of Denmark 2800

More information

Pro II. Sound Level Meter V-9992

Pro II. Sound Level Meter V-9992 Pro II Sound Level Meter V-9992 Title Page I. Safety Information...1 II. General Description...1-2 III. Specifications...2-3 IV. Name and Functions...4-5 V. Calibration Procedures...6-7 VI. Measurement

More information

Knowles Acoustics 1151 Maplewood Drive Itasca, IL 60143

Knowles Acoustics 1151 Maplewood Drive Itasca, IL 60143 Enhanced RF Protected Amplified Mini SiSonic Microphone Specification Knowles Acoustics 1151 Maplewood Drive Itasca, IL 60143 1 of 10 1. DESCRIPTION AND APPLICATION 1.1 Description Mini Surface Mount Silicon

More information

Omnidirectional Microphone with Bottom Port and Analog Output ADMP401

Omnidirectional Microphone with Bottom Port and Analog Output ADMP401 FEATURES 4.72 mm 3.76 mm 1.0 mm surface-mount package High SNR of 62 dba Sensitivity of 42 dbv Flat frequency response from 100 Hz to 15 khz Low current consumption of

More information

Applicant Type (Conditional Use Permit, Variance, Tract Map, etc.): Applicant: Address: Phone(s): Fax:

Applicant Type (Conditional Use Permit, Variance, Tract Map, etc.): Applicant: Address: Phone(s): Fax: ENVIRONMENTAL QUESTIONNAIRE City of Twentynine Palms Community Development Department 6136 Adobe Road Twentynine Palms, CA 92277 (760) 367-6799 Fax (760) 367-5400 29palms.org : Please complete each statement

More information

PREFABRICATED SUBSTATIONS AND E-HOUSES. tgood.com. Energy, Fast!

PREFABRICATED SUBSTATIONS AND E-HOUSES. tgood.com. Energy, Fast! PREFABRICATED SUBSTATIONS AND E-HOUSES tgood.com Energy, Fast! Global leader in prefabricated substations and E-House systems PRODUCT OVERVIEW Fully integrated prefabricated substations and E-House systems.

More information

Validation and Uncertainty Characterization for Energy Simulation

Validation and Uncertainty Characterization for Energy Simulation Validation and Uncertainty Characterization for Energy Simulation Multi-Zone HVAC System using ORNL s Flexible Research Platform (FRP) For: ASHRAE SSPC140 June 26, 2016 PM: Joshua New PIs Piljae Im and

More information

Data Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server

Data Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server Data Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server Data Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server Workload-specific power in a modular form factor FUJITSU Server PRIMERGY will give

More information

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 3.1 FACTORS AFFECTING

More information

Low-Noise Bottom Port Piezoelectric MEMS Microphone

Low-Noise Bottom Port Piezoelectric MEMS Microphone Low-Noise Bottom Port Piezoelectric MEMS Microphone Data Sheet PMM-3738-VM1000-R PUI Audio, featuring Vesper s exclusive technology, presents the world s first and only piezoelectric MEMS microphone. The

More information

Achieving Good Natural Ventilation through the Use of High Performance Computer Simulations Singapore Case Studies

Achieving Good Natural Ventilation through the Use of High Performance Computer Simulations Singapore Case Studies Achieving Good Natural Ventilation through the Use of High Performance Computer Simulations Singapore Case Studies Po Woei Ken (powk@bsd.com.sg) Building System & Diagnostics Pte Ltd Outlines 1. Importance

More information

Adjustable swirl diffuser PDZA TECHNICAL DATA

Adjustable swirl diffuser PDZA TECHNICAL DATA Adjustable swirl diffuser PDZA TECHNICAL DATA Adjustable swirl diffuser PDZA Adjustable ceiling swirl diffuser PDZA is intended for commercial and industrial buildings with a large room volume and high

More information

ROL and ROL-S. climecon.fi

ROL and ROL-S. climecon.fi ROL and ROL-S The stylish and silent nozzle duct ROL is designed for rooms requiring large air volumes distributed evenly and without draught. The functional entity is completed by the ROL-S Adjustment

More information