diffusers F24 PERFORMANCE DATA PERFORMANCE DATA ML-37 / ½" SLOT SPACING WIDTH / SUPPLY WITH CONTINUOUS PLENUM Throw correction multiplier for length
|
|
- Oswald Pierce
- 6 years ago
- Views:
Transcription
1 ML-37 / ½" SLOT SPACING WIDTH / SUPPLY WITH CONTINUOUS PLENUM 5-Slot 6-Slot 7-Slot 8-Slot Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical NC corrections for various diffuser lengths Length Supply Return Throw correction multiplier for length Length Throw Correction Performance notes appear at end of performance data
2 ML-38, -TZ / ¾" SLOT SPACING WIDTH / SUPPLY WITH CONTINUOUS PLENUM 5-Slot 6-Slot 7-Slot 8-Slot Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical NC corrections for various diffuser lengths Length Supply Return Throw correction multiplier for length Length Throw Correction Performance notes appear at end of performance data 25
3 26 ML-39 / 1" SLOT SPACING WIDTH / SUPPLY WITH CONTINUOUS PLENUM Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft Slot NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft Slot NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft Slot NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft Slot NC (Noise Criteria) Horizontal Vertical NC corrections for various diffuser lengths Throw correction multiplier for length Length Supply Return Data obtained from tests conducted in accordance with ANSI/ ASHRAE Standard Actual performance, with flexible duct inlet, may vary in the field. See the engineering section of this catalog for additional information. Horizontal throw values given are for terminal velocities of 150, 100 and 50 fpm Throw values given are for isothermal conditions, and are based on 4-foot active section. or other lengths, see the Throw Correction Table. Pressure is given in inches of WG for ML only Vertical throw values are given for terminal velocities of 50 fpm or divided throw, use the cfm-per-foot value for the number of slots in each direction. or sound, use the NC values for cfm-perfoot for the total number of slots. Length Throw Correction Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10 db, re watts or vertical throw, deduct 11 NC Dash (-) in space denotes an NC value of less than 10 NC is based on 4-foot lengths; for other lengths use the NC correction table Throws listed are for the 1-way pattern. or divided airflow, select the airflow in each direction according to the number of slots aimed in that direction, with the total airflow apportioned between slots. or an explanation of catalog throw data, see the Engineering Guidelines section of the catalog. Data obtained using plenums with duct velocities less than 800 fpm. See model MP (pages 34-45) for data with Titus plenums. or continuous lengths it is recommended that maximum active lengths are no longer than 10 feet
4 ML-40 / 1½" SLOT SPACING WIDTH / SUPPLY WITH CONTINUOUS PLENUM Number of Total Pressure Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Airflow, cfm/ft NC (Noise Criteria) Horizontal Vertical Throw correction table for lengths ML-40 length (ft) Correction factor NC correction table for lengths ML-40 length (ft) Correction factor Data obtained from tests conducted in accordance with ANSI/ ASHRAE Standard Actual performance, with flexible duct inlet, may vary in the field. Refer to the engineering section of the catalog for additional information. Throw values given are for isothermal conditions, and are based on 6-foot active section. or other lengths, see the Throw Correction Table. Horizontal throw values given are for terminal velocities of 150, 100 and 50 fpm Vertical throw values given are for terminal velocity of 50 fpm Throws listed are for the 1-way pattern or divided throw, use the cfm-per-foot value for the number of slots in each direction. or sound, use the NC values for cfm-perfoot for the total number of slots. Pressure is given in inches of water gauge (WG) Each NC value represents the noise criteria curve which will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th, with a room absorption of 10 db, re watts or vertical throw, deduct 11 NC Dash (-) in space denotes an NC value of less than 10 NC is based on 6-foot lengths. or other lengths use the NC correction table above. Data was obtained using plenums with duct velocities less than 800 fpm. See model MP (pages 34-45) for data with Titus plenums. or continuous lengths, a one foot blankoff should be used in between every 6 foot active section. A two foot blankoff should be used in between 10 foot active sections. Active sections should not exceed 10 feet without a blankoff. or continuous lengths it is recommended that maximum active lengths are no longer than 10 feet 27
5 RETURN OR PLENUM APPLICATIONS All pressures are in inches of water NC values are based on a room absorption of 10 db, re watts, with a 10-foot active diffuser section (see the table below) Dash ( ) in space denotes NC value less than 10 Data obtained from tests conducted in accordance with ANSI/ASHRAE Standard or continuous lengths it is recommended that maximum active lengths are no longer than 10 feet MLR-37 No. of Negative SP cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC NC Correction for Various MLR Lengths Length (ft.) MLR MLR-38, -TZ No. of Negative SP cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC MLR-39 No. of Negative SP cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC cfm per ft NC
6 MLR-40 Number of Negative Static Pressure Airflow, cfm/ft NC (Noise Criteria) Airflow, cfm/ft NC (Noise Criteria) Airflow, cfm/ft NC (Noise Criteria) Airflow, cfm/ft NC (Noise Criteria) NC correction table for lengths ML-40 length (ft) Correction factor Data obtained from tests conducted in accordance with ANSI/ ASHRAE Standard Pressure is given in inches of water gauge (WG) NC values are based on a room absorption of 10 db, re watts, with a 10-foot active diffuser section. or other lengths, refer to the NC correction table above. Dash (-) in space denotes an NC value of less than 10 or continuous lengths it is recommended that maximum active lengths are no longer than 10 feet 29
PERFORMANCE DATA SCD. SCD 12 in. x 12 in. Face Size. SCD 20 in. x 20 in. Face Size. Square Cone Diffuser
12 in. x 12 in. Face 4 Neck Velocity (fpm) 400 00 00 00 00 900 00 1200 1400 0 Velocity Pressure (in. w.g.)..01.022.031.040.00.02.090.122..013.021.030.041.04.0.04.121.1.21 Flow Rate (cfm) 3 44 2 1 0 4 122
More informationFALCON High Flow. Circular ceiling air diffuser for supply air QUICK FACTS
Circular ceiling air diffuser for supply air QUICK FACTS Ceiling air diffuser for supply air in rooms with high ceiling Manual operated change of spread direction as standard Motor operated change of spread
More informationPerforated diffuser PAKA, PBKA, PCKA, PDKA, PEKA
Perforated diffuser PAKA, PBKA, PCKA, PDKA, PEKA TECHNICAL DATA - 0 page Perforated diffuser PAKA, PBKA, PCKA, PDKA, PEKA Diffusers with perforated panels type PAKA, PBKA, PCKA, PDKA, PEKA can be used
More informationLaboratory Exhaust Systems
Laboratory Exhaust Systems Vektor -H Performance High Plume April 07 Laboratory Exhaust Systems Model Vektor -H Table of Contents Vektor-H Specification Chart.... Plume Height Calculation... Quick Select
More informationVIREO Ceiling with ALX
Square ceiling air diffuser with nozzles for supply air, with plenum box QUICK FACTS Flush design Suitable for VAV-applications Fast and easy installation Sealing ring, standard for spigot Energy efficient
More informationDRI. VARIZON Displacement unit with adjustable spread pattern
VARIZON Displacement unit with adjustable spread pattern Quick facts Adjustable spread pattern and affected area Suitable for all types of rooms Cleanable Air volume measuring point Very simple to install
More informationSlot diffusers, Round duct diffusers IMP Klima 04 Slot diffusers Round duct diffusers 176
B 0 LD- F 9. φ D H H a 8.5 5 5 A E 7 LD- F 8 8.5 9. 5 5 A 7 E LD-/ LD-/ LD- O/ LD- O/ LD- O/ LD- O/.5.5.5.5 LD-/ LD-/ LD-/ LD-/ LD-/ LD-/ 7.5 7.5 07 LD- O/ LD- O/ LD- O/ LD- O/ 5.5 5.5 5.5 5.5 9.5 87.5
More informationNozzle diffuser DYVZ / Supply air unit DYVB TECHNICAL DATA
Nozzle diffuser DYVZ / Supply air unit DYVB TECHNICAL DATA Nozzle diffuser DYVZ / Supply air unit DYVB (DYVZ+ATVA) DYVZ DYVB (DYVZ + ATVA) The DYVB is a quiet wall mounted supply air unit that consists
More informationIBISTM. Duct diffuser with discs for supply air
TM Duct diffuser with discs for supply air Quick facts 0 flexible distribution pattern High induction capacity Suspended installation Easy installation Modular length: 00 mm Available in alternative colours
More informationIBIS. Duct diffuser with discs for supply air QUICK FACTS
Duct diffuser with discs for supply air QUICK FACTS 0 flexible distribution pattern Suspended installation Easy installation Modular length: 00 mm Standard colour White RAL 900 -- alternative standard
More informationDKC. VARIZON Displacement unit with adjustable spread pattern
VARIZON Displacement unit with adjustable spread pattern Quick facts Adjustable spread pattern and affected area Suitable for all types of room which require large airflows Simple installation Cleanable
More informationSLOT DIFFUSERS ALS SERIES SLOT DIFFUSER ALS37. The Airvector exclusive UNIFLEX pattern and volume controller Deflector-damper
SLO DIFFUSERS ALS SERIES SLO DIFFUSER For, and Installation Series ALS Architectural Linear Slot Diffusers are designed for installation in the ceiling, sidewall or sill and are recommended for supplying
More informationSquare swirl diffuser PZK(A,B), PWK(A,B)
Square swirl diffuser PZK(A,B), PWK(A,B) TECHNICAL DATA - 01 page 4 Square swirl diffuser PZK(A,B), PWK(A,B) PZK(A,B) and PWK(A,B) diffusers assort to swirl devices group. Diffuser s gaps are equipped
More informationGTH. Rectangular double deflection grille QUICK FACTS
Rectangular double deflection grille QUICK FACTS For supply air Adjustable air deflectors Cleanable Installed using mounting frames FHB / FHA or commissioning box TRG Standard colour White RAL 900 -- alternative
More informationGrille. Min. - max. dimensions
Min. - max. dimensions 1 / 0 00 0 500 2 / 0 00 0 Description is a supply grille made from aluminum with curved adjustable blades, oriented 1-way or 2-way horizontal or vertical both for wall and ceiling
More informationFloormaster DVQA, quarter-cylindrical terminals
Floormaster DVQA are quarter-cylindrical supply air terminals for positioning on the floor in a corner. The terminals are designed for displacement air handling in accordance with the Floormaster system
More informationBYPASS TERMINAL UNITS 3400 SERIES
400 SRIS 400 SRIS "DUMP BOX" UNIQU "FLO DIVRTR" VALV Models: 400 Cooling 4R Cooling with ot ater Reheat 4R Cooling with lectric Reheat Model 400 The 400 Series Bypass Terminal Unit is a single duct pressure
More informationSamuel Tepp Engineering Seminar Topics
Samuel Tepp Associates 11 Leonard Street Metuchen, New Jersey 08840 Contact: Keith Miller, Cell: 201-638-6591, kmiller@samtepp.net Samuel Tepp Engineering Seminar Topics All topics are approved for New
More informationHVAC Project. Comparison of Revit MEP Automatic Duct Sizing and Equal Friction Method Manual Calculations
346P HVAC Project Comparison of Revit MEP Automatic Duct Sizing and Equal Friction Method Manual Calculations ŀare Name: Date: 10 May 2010 Ben Meinke, Jimmy Principe, Richard Sniff Table of Contents Project
More informationCONTROLLING ROOFTOP UNIT (RTU) NOISE
HUSHCORE Acoustical Products & Systems Technical Discussion General Information Terminology & Definitions Product Types Treatment Strategies Applications/Uses Industrial Architectural HVAC OEM Environmental
More informationState University of Nuevo Leon, Mexico Mechanical & Electrical Engineering School
State University of Nuevo Leon, Mexico Mechanical & Electrical Engineering School ACOUSTICS LABORATORY SIMULATION OF THE ACOUSTIC WAVE BEHAVIOR OF DUCTS AND PLENUMS USING ANSYS JOSE DE JESUS VILLALOBOS
More information1450 First Ave. Page 1 of 7 Chippewa Falls, WI (800) or (715) Fax: (715)
1450 First Ave. Page 1 of 7 Model DA30 User Manual 1450 First Ave. Page 2 of 7 Warranty This product is fully warranted against defective materials and/or workmanship for a period of one year after purchase,
More informationFundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational
More informationPCI-SIG ENGINEERING CHANGE NOTICE
PCI-SIG ENGINEERING CHANGE NOTICE TITLE: PCIe CEM Thermal Reporting DATE: May 18, 2017 AFFECTED DOCUMENT: PCI Local Bus Specification Revision 3.0 PCI Express Card Electromechanical Specification 3.0 SPONSOR:
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationAdjustable swirl diffuser PDZA TECHNICAL DATA
Adjustable swirl diffuser PDZA TECHNICAL DATA Adjustable swirl diffuser PDZA Adjustable ceiling swirl diffuser PDZA is intended for commercial and industrial buildings with a large room volume and high
More informationIRIS Damper Application Guide
IRIS Damper Application Guide IRIS & IRIS-S S INTRODUCTION The IRIS damper is a brilliantly simple solution for fast and exact measurement, balance and control of airflow. It is ideal for supply and exhaust
More informationLDK Slot Diffusers. Description. Throw directions. 2
Slot Diffusers LDK LDK Slot Diffusers Description LDK linear slot diffusers are designed to meet high comfort requirements and modern slot diffuser application standards. LDK slot diffusers, providing
More informationAir Moving Solutions. axipal adjustable pitch airfoil fans
Air Moving Solutions. axipal adjustable pitch airfoil fans ATAD ATAB CATALOG AX210 December 2012 AdjustablePitch Models ATAD ATAB Model ATAD Arrangement 4 - Direct Drive The ATAD Adjustable Pitch Airfoil
More information1450 First Ave. Page 1 of 9 Chippewa Falls, WI (800) or (715) Fax: (715)
1450 First Ave. Page 1 of 9 Model DA40V User Manual 1450 First Ave. Page 2 of 9 Warranty This product is fully warranted against defective materials and/or workmanship for a period of one year after purchase,
More informationVRF. Technical Data Book. Slim duct for America (R410A, 60Hz, HP) Model : AM***FNLDCH***
VRF Technical Data Book Slim duct for America (R41A, 6Hz, HP) Model : AM***FNLDCH*** History Version Modification Date Remark Ver.1. Release Slim duct for America (R41A, 6Hz, HP) 1.11.4 - Ver.1.1 1.12.28
More informationNORDgrille Internal grilles
NORDgrille Internal grilles NORDgrille Contents RSP/RSV General grille RPS/RPV General grille RPSL/RPVL Floor grille RSO Transfer air grille RSL Transfer air grille RSM Transfer air grille RSI Exhaust
More informationEQUIPMENT ENGINEERING & SPACE PLANNING DATA SYSTEM LEVEL
ESP-001 Form EQUIPMENT ENGINEERING & SPACE PLANNING DATA SYSTEM LEVEL Acoustic Noise Engineering Data Physical Data Equipment System Manufacturer: Date: Product Name: Equip. Functional Description and
More informationRectangular straight silencer
silencer DLD Dimensions b a l Description DLD has a conventional design with dimensions that not exceed the corresponding connection dimensions. The silencer can be manufactured in all standard duct sizes.
More informationYour Clean Air Source!
In-Line Centrifugal Fans Your Clean Air Source! CENTRIFAN IN-LINE CENTRIFUGAL FAN HIGH QUALITY... HIGH EFFICIENCY... VERSATILITY CENTRIFAN IN-LINE CENTRIFUGAL FANS INDEX Centrifan Brochure Index..................
More informationGrilles Type AR. AE for return air 1 / 1.3 / B / 1
Grilles Type for return air 1 / 1 / B / 1 Contents Description Construction Cover Page 1 Contents 2 Description 2 Construction 2 Materials Standard Sizes Technical Data Technical Data Type Nomenclature
More informationAPPENDIX S HORIZONTAL DIRECTIONAL DRILLING (HDD) ENVIRONMENTAL SOUND LEVEL ASSESSMENT REPORT
ALASKA LNG PROJECT DOCKET NO. CP17- -000 RESOURCE REPORT NO. 9 APPENDIX S HDD ENVIRONMENTAL SOUND LEVEL ASSESSMENT REPORT PUBLIC DOC NO: USAI-PE-SRREG-00-000009-000 DATE: APPENDIX S HORIZONTAL DIRECTIONAL
More informationINSTALLATION INSTRUCTIONS
INSTALLATION FORM# 597A-0711 (Replaces 597A- 1004) UNIT FILTER PLENUM CONTROL MOTOR ECONOMIZER FRESH AIR EXHAUST AIR ROOF CURB FLEXIBLE DUCT CON CEN TRIC DIFFUSER BOX INSTALLATION FLUSH MOUNT SYSTEMS Flush
More informationUniversal Valve Module (UVM) Installation Manual Version: Triatek Universal Valve Module
Installation Manual Version: 05.19.16 Triatek Universal Valve Module SUBHEAD TABLE OF CONTENTS Setup Overview...3 Introduction.......4 Overview of Operation.........4 Basic Functionality of the UVM...5
More informationHardwall & Softwall Cleanrooms
Hardwall & Softwall Cleanrooms 1467 Pinewood St * Rahway, NJ 07065 * 732 381-8200 * www.lmairtech.com *Email-- Sales@LMAIRTECH.com Hardwall & Softwall Cleanrooms MDR Series Modular Hardwall Cleanrooms
More informationFan-Powered VAV Terminal Units
This article was published in ASHRAE Journal, November 2017. Copyright 2017 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationVentilation grille. Dimensions
Ventilation grille B0 Dimensions B+/A+ B-/A- Description B0 is a rectangular aluminium grille with fixed horizontal bars. B0 is used for both supply and exhaust air, and is supplied as standard with springs
More informationOPEN FACE Industrial East Grand Ave., Pomona, CA Fax:
OPEN FACE Industrial Dry Booths Environmentally Safe Each Industrial Dry Booth is designed to meet or exceed safety and code requirements: NFPA- and IFC, to protect those that work in any industrial spray
More informationApplication of TileFlow to Improve Cooling in a Data Center
Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance
More informationStandard Construction. Options and Accessories
SP, SP-L, SP 22 ath and Inline ans SP SP UL/cUL 507-599 - eiling xhaust ans SP-90 and smaller and SP- are UL/cUL Listed for above bathtub/shower with I branch protected circuit. SP- is UL/cUL Listed UL/cUL
More informationFAN POWERED TERMINAL UNITS
GENERAL PRODUT OVERVIEW Leading The Industry Providing products that incorporate the desires and requirements of the industry we serve has traditionally been a primary focus at Nailor. We listened in-depth
More informationSwirl diffusers, Variable swirl diffusers Swirl diffusers
Swirl diffuser OD-7 Fixed blades Different installation possibilities Three possible diffuser shapes St R 90 CD OD-7/R OD-7/K OD-7/RC OD-7/K/PM F 9 x9 φd1 C C F x F C φ D2 φ D 1 9 x 9 Size ФD1 ФD2 ФD F
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationClean Room Certification Reports Interpreting and Acting on the Good, the Bad and the Ugly!
Clean Room Certification Reports Interpreting and Acting on the Good, the Bad and the Ugly! Marc Stranz, PharmD, Vice President of Clinical Operations BioScrip, East Greenville, PA Jim Wagner, President
More informationSpecification and Design Catalog. Waterside Economizer
Specification and Design Catalog Waterside Economizer Table of Contents Waterside Economizer Applications.................................................... 4 Application Notes..................................................................
More informationAccuDuct ACCA Manual-D Duct Design
AccuDuct ACCA Manual-D Duct Design Software Inside This Manual How to Input Data for Duct Design Calculations. View Design Summaries and Print Reports. Using AccuDuct on a Tablet PC. Import AccuLoad Room
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationCeiling diffusers - visible
Ceiling diffusers - visible About Lindab Comfort and Design Product overview / symbols Theory Ceiling diffusers Ceiling diffusers - visible Plenum boxes Wall diffusers Nozzles Ventiduct Grilles Displacement
More informationCreating an Energy-Efficient, Automated Monitoring System for Temperature and Humidity at a World-Class Data Center
About CyrusOne CyrusOne is a world-renowned enterprise data center provider that offers 40 data centers across the U.S., Europe and Asia with a three million-plus square feet of total net rentable space.
More informationBuilding Loads and Dedicated Outdoor Air Systems
AMCA International Building Loads and Dedicated Outdoor Air Systems Dan Int-Hout Chief Engineer, Krueger, Richardson, Tx. Dint-Hout@Krueger-hvac.com KRUEGER EXCELLENCE IN AIR DISTRIBUTION Air System Engineering
More informationHIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Min. Circuit Ampacity
ENVIRONMENTALLY SOUND REFRIGERANT C4H(5, 7) Product Specifications HIGH EFFICIENCY 15 and 17 TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 2, 3, 4, and 5 TONS SPLIT SYSTEM 208 / 230 Volt,
More informationFilter Fan Unit LIGHT
Filter Fan Unit LIGHT Type LIGHT EC Technical Concept Technical Concept Filter Fan Unit LIGHT Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide clean air to individual
More informationHigh Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach
High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationDuctworkPro. User Guide
DuctworkPro for AutoCAD User Guide Version 2.0, March. 2004 Copyright 2004, Randall C. Wilkinson By Randall C. Wilkinson Freeware Version Users: This document describes the Professional Version of Ductwork.
More informationOptimizing Cooling Performance Of a Data Center
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationitool Installation and User s Manual
itool Installation and User s Manual Introduction In this Publication This manual contains instructions on how to install and operate the Tyco Safety Products itool. The itool is a software program designed
More informationDIRECT DRIVE VANEAXIAL FIXED PITCH FANS
DIRECT DRIVE VANEAXIAL FIXED PITCH FANS BULLETIN 6 DECEMBER 201 Capacities to 100,000 Static pressures to WG Temperatures to 10 F. THE NEW YORK BLOWER COMPANY 660 Quincy Street Willowbrook, IL 602-0 Visit
More informationHeavy Duty Hot Wire CFM Thermo-Anemometer
User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extecch 407119 Product Page Heavy Duty Hot Wire CFM Thermo-Anemometer
More informationAPC APPLICATION NOTE #114
APPLICATION NOT #4 Using the Rack Air Containment System with the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC00 and ACSC0) is a self-contained air conditioner for server
More informationCyrusOne Case Study About CyrusOne
CyrusOne Case Study About CyrusOne CyrusOne is a world-renowned enterprise data center provider that offers 31 data centers across the U.S., Europe and Asia with a three million-plus square feet of total
More informationHARBEC Inc Ontario, NY
HARBEC Inc Ontario, NY Cleanroom Certification Report PREPARED FOR 369 Route 104 Ontario, NY 14519-8999 Paul Scheible Engineering Manager Main Cleanroom Gown Room Room Design Classification ISO Class 8
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationChapter 3 Practice Test
1. Complete parts a c for each quadratic function. a. Find the y-intercept, the equation of the axis of symmetry, and the x-coordinate of the vertex. b. Make a table of values that includes the vertex.
More informationResidential air leakage measurement system comparison: Retrotec Blower Door & Minneapolis Blower Door
Residential air leakage measurement system comparison: Retrotec Blower Door & Minneapolis Blower Door Use this guide to compare features of the two top US manufacturers. Retrotec Model 1000 Blower Door
More informationEnvironmental Noise Study of. Findlay Creek Public School Findlay Creek Drive, Ottawa, Ontario. R1. Prepared for: N45 Architecture Inc.
Environmental Noise Study of Findlay Creek Public School 3010 Findlay Creek Drive, Ottawa, Ontario. R1 Prepared for: N45 Architecture Inc. Prepared by: Eric Sladic February 5 th, 2015 Contents 1.0 Introduction...1
More informationModel 6812 VOLUME FLOW ANEMOMETER. User Manual. Kanomax USA, Inc. 219 Route 206 PO Box 372. Andover, NJ USA. (800) Fax: (973)
Kanomax USA, Inc. 219 Route 206 PO Box 372 Andover, New Jersey 07821 USA (800) 247-8887 Fax: (973) 786-7586 Model 6812 VOLUME FLOW ANEMOMETER User Manual www.kanomax-usa.com Copyright 2008, Kanomax USA,
More informationMCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH
MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal
More informationModel 6812 VOLUME FLOW ANEMOMETER. User Manual. 219 Route 206 Phone: PO Box 372 Fax: (973)
Model 6812 VOLUME FLOW ANEMOMETER User Manual Copyright 2008, Kanomax USA, Inc. Page 1 of 29 INTRODUCTION Congratulations on your purchase of a 6812 Digital Anemometer with Volume Calculation! You now
More informationTemperature monitoring and CFD Analysis of Data Centre
Available online at www.sciencedirect.com Procedia Engineering 56 (2013 ) 551 559 5 th BSME International Conference on Thermal Engineering Temperature monitoring and CFD Analysis of Data Centre N.M.S.
More informationMCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH
MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH 1 Chilled and Hot Water Fan Coil Low Static 4-Pipe Nominal Size:
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationApproval Block. Prepared by: Signature Date Evan Parnell 08 NOV Reviewed by: Signature Date. Approved by: Signature Date
ATS-ATP-3440 Page: 1 of 6 Approval Block Prepared by: Signature Date Evan Parnell 08 NOV 2013 Reviewed by: Signature Date Brian Flynn 08 NOV 2013 Approved by: Signature Date Kristal Jewell 08 NOV 2013
More informationPP-8516 & PP Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions
PP-8516 & PP-8616 Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions Part Number PP-8516 Static Pressure Controller/Transmitter PP-8616 Static Pressure
More informationMCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH
MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal
More informationGX7300 SERIES CHASSIS AND CONTROLLERS 20 SLOT, 3U PXI CHASSIS DESCRIPTION FEATURES CONFIGURATION
20 SLOT, 3U PXI CHASSIS 20 slots supporting a 3U (embedded or remote) PXI controller and 19 3U PXI or ccpi instruments Built-in peripherals (hard disk drive, and a DVD-RW drive) for embedded controller
More informationNetShelter CX Technical Guide
NetShelter CX Technical Guide A soundproofed Server Room in a Box which allows for IT deployment wherever and whenever it is needed, saving space, cost and deployment time. Model AR4038 & AR4038I >Physical
More informationMinneapolis Blower Door Building Air tightness Testing Systems
DIAGNOSTIC TOOLS TO MEASURE BUILDING PERFORMANCE ENERGY CONSERVATORY The Blower Door Minneapolis Blower Door Building Air tightness Testing Systems Minneapolis Blower Door Blower Door tests are used to
More informationSlim duct (AMTTTFNLDEH ) Indoor units
Slim duct (AMTTTFNLDEH ) Slim duct. Specifications 1) Technical specifications Model AM22FNLDEH AM28FNLDEH AMFNLDEH AM4FNLDEH AMFNLDEH Power Supply Ø, #, V, Hz 1,2,22-24, 1,2,22-24, 1,2,22-24, 1,2,22-24,
More information1.5 to 5 Tons INDOOR COILS CH35. Horizontal PRODUCT SPECIFICATIONS CH A - 2 F MODEL NUMBER IDENTIFICATION FEATURES
INDOOR COILS PRODUCT SPECIFICATIONS Horizontal Bulletin No. 20667 November 206 Supersedes August 206.5 to 5 Tons MODEL NUMBER IDENTIFICATION CH 35-8 A - 2 F Unit Type CH = Indoor - Horizontal Series Nominal
More informationMin. Circuit Ampacity. Max. Fuse or Breaker. Ship / Operating Weight lbs. (kg) C4H524GKD 2 24,
ENVIRONMENTALLY SOUND REFRIGERANT C4H(5, 7) SXT+ Product Specifications HIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 2, 3, 4, and 5 TONS SPLIT SYSTEM 208
More informationDWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.
Series AVUL Air Velocity Transmitter Specifications - Installation and Operating Instructions Bulletin P-AVUL 3-49/64 [95.71] 2-43/64 [67.92] 1/2 NPS 3-3/16 [80.81] 1-19/32 [40.59] 31/32 24.58 3-33/64
More informationMeasure Sounds Reliably
Measure Sounds Reliably Sound Level Meter Class1 NL-52 Sound Level Meter Class2 NL-42 Extremely User Friendly Rion s NL-52 and NL-42 sound level meters provide full support for the process. The NL-52 and
More informationANSYS AIM Tutorial Fluid Flow Through a Transition Duct
ANSYS AIM Tutorial Fluid Flow Through a Transition Duct Author(s): Sebastian Vecchi, ANSYS Created using ANSYS AIM 18.1 Problem Specification Start Up Geometry Import Geometry Extracting Volume Suppress
More informationNetShelter CX Performance Guide
NetShelter CX Performance Guide The Netshelter CX is a soundproofedd Room in a Box which allows for IT deployment wherever and whenever it is needed, saving space, cost and deployment time. Here is one
More informationLOCAL EXTRACTORS. The ideal extractor for industrial environments. Pure advantage
The ideal extractor for industrial environments. New technology in combination with new materials and a focus on design gives Movex PR many new and important advantages: - Unique ease of maneuverability.
More informationSurface Area and Volume
15 CHAPTER Surface Area and Volume Worksheet 1 Building Solids Using Unit Cubes How many unit cubes are used to build each solid? This is a unit cube. 1. 2. unit cubes 3. 4. unit cubes unit cubes unit
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationInstallation and Operation Instructions
33ZC ComfortID Test and Balance Tool Software Installation and Operation Instructions Part Number 33ZCBAL-SA INSTALLATION The ComfortID Test and Balance Tool software requires no special installation.
More informationAcoustic Nozzle Design for Fire Protection Application
Acoustic Nozzle Design for Fire Protection Application Melissa A. Loureiro, Alan Elder, Arash Ahmadzadegan Johnson Controls, Cranston, RI, USA Abstract Data centers are relied upon to store and distribute
More informationModel 6813 THERMO-ANEMOMETER. User Manual. Kanomax USA, Inc. 219 Route 206 PO Box 372. Andover, NJ USA. (800) Fax: (973)
Kanomax USA, Inc. 219 Route 206 PO Box 372 Andover, New Jersey 07821 USA (800) 247-8887 Fax: (973) 786-7586 Model 6813 THERMO-ANEMOMETER User Manual www.kanomax-usa.com Copyright 2008, Kanomax USA, Inc
More informationVRF Technical Data Book
VRF Technical Data Book Wind-Free 4Way Cassette for North America (R4A, HP) Model : AM***NN4DCH/** History Version Modification Date Remark Ver.1. Released VRF Wind-Free 4Way Cassette for north America
More informationoom Pressurization Con
Technical Specification Sheet Rev. 3, December, 1998 Room Pressurization Controllers equipment. This approach to room control includes the following features. Features gure 1. Roo oom Pressurization Con
More informationSlim Ducted type. Contents MMD-AP 4SPH2UL MMD-AP0094SPH2UL MMD-AP0124SPH2UL MMD-AP0154SPH2UL MMD-AP0184SPH2UL
E5-3I D-AP 4SP2U Slim Ducted type D-AP0074SP2U D-AP0094SP2U D-AP024SP2U D-AP054SP2U D-AP084SP2U Contents. Specifications 2. Dimensions 3. Center of gravity 4. Piping diagram 5. Wiring diagram 6. Electrical
More informationBACnet Terminal Box (VAV) Controller
Technical Specification Sheet May 30, 2012 BACnet Terminal Box (VAV) Controller Figure 1. BACnet Terminal Box Controller. The BACnet Terminal Box Controller (Figure 1) provides high performance Direct
More information