NUMERICAL MODELLING METHOD FOR THE DESIGN OF DATA CENTRE COOLING

Size: px
Start display at page:

Download "NUMERICAL MODELLING METHOD FOR THE DESIGN OF DATA CENTRE COOLING"

Transcription

1 NUMERICAL MODELLING METHOD FOR THE DESIGN OF DATA CENTRE COOLING AMIN AZARMI Mechanical Engineer Aurecon MOSTAFA MAHDAVI Research Fellow Department of Mechanical and Aeronautical Engineering University of Pretoria AHMAD ERFANI MOGHADAM Research Assistant Institute for Frontier Materials Deakin University ABOUT THE AUTHORS Amin is Mechanical Engineer with 14 years of experience in Designing and Modelling of Building Services of major buildings & infrastructure in Middle East and Australia. He is specialist in HVAC system design, Computational Fluid Dynamic (CFD) modelling of the HVAC systems, Energy and Thermal modelling and analysis. Amin is Green Star Accredited Professional and NABERS Accredited Assessor. He is passionate about innovative HVAC system design & digital engineering to develop sustainable construction. Mostafa is a research fellow in the Department of Mechanical and Aeronautical Engineering at the University of Pretoria. He received his master's degree in Energy Conversion from Shiraz University in Iran. His research interests include heat and mass transfer, natural and force convection, turbulence, Nano fluids, particle migration and multiphase flow modelling. Ahmad is a research assistant in the Institute of Frontier Materials (IFM) at the Deakin University. He received his master's degree in Applied Mechanic of system design from Ferdowsi University of Mashhad in Iran. His research interests include Thermal & Fluid system design, Finite Element Analysis (FEA) and Computational Fluid Dynamic (CFD) modelling of the systems, and system optimisation. ABSTRACT Theoretical modelling analysis can couple with design decisions prior to the detailed design and construction of the ventilation systems for data centre construction. Computational fluid dynamic (CFD) tools effectively solve the governing flow equations for the data centre based on arrangements of equipment, the room and air conditioning standards. The flow was considered highly turbulent and two equation models were utilised for simulations due to high velocity and mixing. Due to many geometrical parameters involved in data centres, the main focus of this paper was concerned to less 1

2 studied areas such as failure of units and partitioning the aisles. Indeed, parameters such as supply to return heat index and return temperature index were introduced to understand functional performance of the cooling system within the simulation modelling. The application of the CFD in the data centre analysis would also be applied to study several failure scenarios of the CRAC and CRAH units enabling designers to optimise the control system for efficiency, as well as the least risk of equipment damage. In addition, temperature distribution was analysed to avoid maximum temperature in the case of failure. Keywords: Data Centre, CFD, CRAC/CRAH, Failure Scenario, Simulation Modelling INTRODUCTION The main centre of each information technology facility, such as computer servers and data storage systems, is undoubtedly a data centre (DC) housing a large number of electrical equipment. However, the efficiency of the servers highly depends on the environment temperature and humidity, and any damage or interruption in computer servers would cause huge costs for the company [1,6]. Hence, air conditioning and cooling the servers are a critical task in a DC. It is worth mentioning that some practical methods were suggested to improve the cooling system and optimise the energy demand in DC [7 9]. Computational fluid dynamic (CFD) is one of the strongest tools for predicting the efficiency and applicability of cooling systems in a DC. A large number of experimental and numerical studies on DC were performed in recent year [10,11]. Since simulation of the entire DC is somewhat expensive, a number of simply numerical and analytical approaches were proposed by researchers [12 14]. Schmidt et al. [13] applied a twodimensional depth-averaged model by only considering the raised floor and the resistance in upstream. Their obtained results were in good agreement with experiment considering the fact that the two-dimensional model can be recommended for 0.26m as the raised floor height. Karki et al. [14] modelled the same DC as Schmidt et al. [13], but in a three dimensional arrangement. They employed an empirical correlation for the resistance coefficient in tiles based on opening area. It should be mentioned that the research on thermal performance of DCs is still at the beginning stages in terms of numerical methods, and particularly three-dimensional models. Additionally, plenty number of geometrical and boundary parameters are involved, and further studies are required. In this paper, the results of the CFD simulations are initially compared with experimental measurements conducted by Schmidt et al. [13]. 1. GOVERNING EQUATIONS AND BOUNDARY CONDITIONS 1.1 Fluid flow equations Airflow is assumed to be turbulent in the entire DC; however, the flow patterns can considerably vary from the raised floor to the inner regions of aisles. The other assumptions are incompressible and single-phase flow being solved under the steady state condition. The flow is governed by three fundamental equations as conservation of mass, momentum and energy as follows [3-5]: u x i i 0 (1) 2

3 u u P u u u g S i i j i j i m x j xi x j x j T 1 T u k c T u q x j cp x j x j j L P j s where i and j are Einstein notation varying from 1 to 3 in 3D dimensions. For instance, ui represents u1 (velocity in x direction), u2 (velocity in y direction) and u3 (velocity in z direction). k L, Sm and q s are laminar thermal conductivity, source terms for momentum and energy equations, respectively. Due to transient nature of turbulent fluid, Reynolds-Average Navier stokes method is utilised to solve turbulent flow at steady state. Therefore, velocity and temperature are broken down into two parts, the time-averaged value ( u,t ) and the fluctuating part ( u,t ). One of the common approaches which can be applied to give an account for fluctuating velocity and temperature is to define turbulent viscosity and thermal conductivity. At this stage, turbulent k model is used to provide the ui general form for Reynolds stresses as uu i j t, known as Boussinesq hypothesis [4]. Two x additional transport equations for the turbulent kinetic energy (k), dissipation rate (ɛ) are solved to obtain the features of turbulence and turbulent viscosity. The transport equations and turbulent viscosity are as follows [5]: j (2) (3) k ( ku ) G G Y S x x x t i k b M k i i k i 2 t u C G C G C S x x x k k i 1 k 3 b 2 i i i (4) (5) 2 k (6) t C tc p k t Pr t (7) Where Pr t is Turbulent Prandtl number with fixed value of 0.9. Since the airflow is weak on top of the racks, the effects of buoyancy force need to be observed in equations. The coupling between momentum and energy equations is conducted by replacing the air density with Boussinesq s approximation as follows: (T T ) (8) ref ref Finite volume method along with staggered grid were utilised to iteratively solve the flow and transport equations. The SIMPLE algorithm developed by Patankar [3] was employed to couple momentum and energy equations based on accuracy of continuity equation in each iteration. 3

4 Flow rate (L/s) Flow rate (L/s) Flow rate (L/s) Flow rate (L/s) a) b) Figure 1. Two sets of experiments are considered for validation purposes. In each set, one of the CRAC units will be shut down. 100 Row Row Experiment Numeric -50 Experiment Numeric Tile number Tile number a) b) Row 3 Row Experiment Numeric -50 Experiment Numeric Tile number c) d) Figure 2. Volume flow rate through each tile when CRAC A is off. Experiment by Schmidt et al. [13] 1.2 Turbulent wall treatment and boundary conditions Tile number The boundary conditions for CRAC units consist of volume flow rate, the capacity of the unit and desirable cold temperature. However, Patankar [16] pointed out the desirable temperature could be less than this value and even could be close to 13 C. Two different servers are assumed in each rack,

5 one with volume flow rate of 0.14m 3 /s and heat generation of 1700W, and the other one with 0.1m 3 /s and heat generation of 1200W. 2. PHYSICAL MODEL FOR VALIDATION The first step in any CFD calculation is to ensure the capabilities of the method in modelling of this specific case. The experimental findings by Schmidt et al. [13] are borrowed to compare with the numerical results. Two CRAC units are considered in front of each other with four rows of perforated tiles and 15 tiles in each row. The height of the raised floor and the size of the tiles are 284mm and 600mm 600mm, respectively. The configuration of the DC is observed in Figure 1, including CRAC units, perforated tiles, the tube next to CRAC-A as an obstacle and stanchions at the corners of the tiles. The results of the simulations are compared with experimental measurements by Schmidt et al. [13] in Figure 2. There is good agreement between results with average deviation of 20% which could be accurate for this type of simulations with many geometrical parameters as well as further simulations with heat transfer presented in the next sections. 3. GEOMETRY PRESENTATION FOR MODELLING AND BOUNDARY CONDITIONS The entire size of the data centre for modelling is considered 15300mm 4770mm with 3500mm height. Fifty-two (52) racks are located in the domain, each twenty-six (26) racks in an isolated room enclosed by glass. Each rack cabinet contains two servers. Two of the CRAH units are always on duty and the other two starts running in the case of failure. The height of the raised floor and ceiling void is approximately 1100mm. The dimensions of the data centre are presented in Table 1, with schematic and geometry of the physical model in Figure 3. Base holders with diameter of 100mm are used at each corner of perforated tiles and also beneath the racks. 4. SIMULATION RESULTS AND DISCUSSION In the current study, several grid sizes were tested to ensure the independency of the simulation on number of cells. The resultant flow rates for two rows of tile in one cold aisle are shown in Figure 6 in terms of air flow (L/s). Finally, the grid size of 2.2 million cells were chosen due to the predictable slight change of accuracy in comparison to smaller grid. One of the most important tasks is to ensure that temperature at the server intake remains in the range of desirable values. Hence, Rack Cooling Index (RCI) [15] is introduced to compare the observed temperatures with those recommended in guidelines such as ASHRAE [2]. The recommended and allowable values are summarised in Table 2. RCI is calculated as follows: RCI 1 Total over temperature Max allowabletemperature (9) Supply air diffuser size Cold-aisle width Hot-aisle width 600mm 600mm 1200mm 600mm 5

6 CRAH unit power 142kW Server power density 2.33kW Number of servers 104 Supply temperature 24.5 o C Ceiling exhaust grilles size 600mm 1200mm Table 1. Details of the data centre sizes. (a) (b) Figure 3. (a) Schematic illustration of racks, raised floor and ceiling void. (b) Top view of the entire data centre. (c) Computational domain of the numerical model Total over temperature is the intake temperature of those servers above maximum recommended. The summation is calculated for the use of RCI. The other terms on the bottom is the multiplication of rack number and the difference between maximum allowable and recommended temperature. The graphical presentation of RCI is illustrated in Figure 4. The rectangle area between max allowable and recommended temperature presents the max allowable amount in RCI. The other important parameter is Return Temperature index (RTI). RTI is the measure of recirculation of hot air in hot aisle to cold aisle and also by-passing of cold air in cold aisle to the CRAH unit without passing through the servers. It is defined as the difference between supply and extract air temperature in air handler over the induced temperature difference in servers. RTI can be also regarded as the proportion of airflow in servers and air handlers. Textract Tsup ply Flowin servers RTI or RTI (10) T FlowinCRAH units server Both RTI and RCI are utilised to evaluate the capability and efficiency of the cooling system in the DC in various circumstances, especially by the drop of over of CRAH units. (c) 6

7 Min and max Min and max allowable recommended 18 o C 27 o C 15 o C 32 o C Table 2. Temperature values from guidelines (ASHRAE) 4.1 Failure scenarios Figure 4. Parameters for definition of RCI Two cases of failure scenarios are shown in Figure 5, CASE B and CASE C. The results of the failure situations are compared with the no failure CASE A in Figure 6. At this range of RCI values (60% to 70%), the inlet temperature of the servers are still below max allowable temperature. It guarantees uninterrupted working of the DC by avoiding overheating. Nonetheless, the intake temperature remains above max recommended values, meaning of poor rate of thermal performance. As can be seen, the trend in both RCI and RTI shows that the failure situation is properly handled by the CRAH standby units in the opposite side. Figure 5. Cases of failure scenarios in this study 7

8 RCI (%) RTI (%) Rows numbers CASE A CASE B CASE C CASE A CASE B CASE C Rack rows number (a) (13 rack cabinets in each row) Figure 6. Variation of RCI and RTI for each rack in the case of failure (the rows number has been annotated by the box). % opening area RCI RTI Table 3. Effects of diffusers opening area on RCI and RTI for the entire DC 4.2 Tile opening area and aisles partitioning Rack rows number One of the important geometrical parameters is the percentage of the opening area for raised perforated tile (diffusers), from 10% to 60%. The impact of diffuser opening area is presented in Table 3, and it illustrates the RTI values is slightly affected by changes in opening area. On the other hand, the thermal efficiency or RCI would enhance by 7.1% with an increase in opening area from 10% to 60%. The other method of improvement in thermal efficiency is to add partition to the DC room. Hence, the cold aisles will be isolated from the rest of the room and cold air should completely pass the rack. In this study, three cases are considered, first the entire DC room isolated from the CRAH units, second the entire DC room and cold aisles isolated, third only cold aisles isolated from the rest of the domain. The results for RCI and RTI values are presented in Figure 7. The ideal value for RCI is 100%, meaning the server intake temperature is similar to recommended one. This happens when cold aisle partition is employed in the design of the DC. Moreover, the absence of glass walls around the racks have no impacts on the thermal performance of the system. On the other hand, adding partition to the cold aisles does not significantly change the RTI, not related to the isolated room. The reason can be understood from Figure 8. Due to leakage in each server, the cold airflow partially passes the gap between servers in the rack and remains untouched from the generated heat. Then, it is mixed with the air in the hot aisle and reduces the return temperature to the CRAH unit. (b) 8

9 (a) (b) (13 rack cabinets in each row) Figure 7. RTI and RCI values for the case with and without cold aisle partition. Figure 8. Leakage of airflow through the gap between servers and mixing with hot air CONCLUSIONS Thermal performance and efficiency of a data centre with four rows of rack were numerically studied. Firstly, the robustness of the model was confirmed with the experimental measurements of the literature and subsequently, a new geometrical model was thermally analysed. The main criteria were considered the intake and outlet temperature from the racks and CRAH units as non-dimensional indexes RCI and RTI. Two failure scenarios were investigated by running the standby CRAH units in the opposite side of the main CRAH units. The results showed that the standby CRAH units could properly manage the thermal distribution in the DC in the case of the main CRAH interruption, without any relationship with the arrangement of the air handler units. However, the thermal performance of this arrangement has not met the expectations. In another situation, it was suggested 9

10 that thermal performance represented by RCI increased only by 7.1% due to expanding the opening area up to 60%. While, installing partition on cold aisle section could improve the thermal performance up to 100%, with no need for isolating the entire room with racks. In other words, it is recommended to only isolate the cold aisle instead of isolating the entire DC. This will prevent extra costs regarding partitioning the entire area. As a future study, different arrangement of CRAH units with respect to racks is analysed and changes are made in the racks to ensure passing maximum cold air going through the servers with optimum RCI and RTI. Furthermore, the energy analysis of the DC will be investigated. 10

11 (a) Books and handbooks REFERENCES 1. J. Dai, M.M. Ohadi, D. Das, M.G. Pecht, Optimum cooling of data centers, Springer, Ashrae, Thermal guidelines for data processing environments, ASHRAE, S. Patankar, Numerical heat transfer and fluid flow, CRC press, J.O. Hinze, Turbulence McGraw-Hill, New York. 218 (1975). 5. B.E. Launder, D.B. Spalding, Lectures in mathematical models of turbulence, Academic press,london, England, (b) Journal articles and papers 6. Y. Joshi, P. Kumar, Energy efficient thermal management of data centers, Springer Science & Business Media, H. Zhang, Z. Shi, K. Liu, S. Shao, T. Jin, C. Tian, Experimental and numerical investigation on a CO 2 loop thermosyphon for free cooling of data centers, Appl. Therm. Eng. 111 (2017) Z. Wang, X. Zhang, Z. Li, M. Luo, Analysis on energy efficiency of an integrated heat pipe system in data centers, Appl. Therm. Eng. 90 (2015) Y. Ma, G. Ma, S. Zhang, F. Zhou, Cooling performance of a pump-driven two-phase cooling system for free cooling in data centers, Appl. Therm. Eng. 95 (2016) J. Ni, X. Bai, A review of air conditioning energy performance in data centers, Renew. Sustain. Energy Rev. 67 (2017) S. Alkharabsheh, J. Fernandes, B. Gebrehiwot, D. Agonafer, K. Ghose, A. Ortega, Y. Joshi, B. Sammakia, A Brief Overview of Recent Developments in Thermal Management in Data Centers, J. Electron. Packag. 137 (2015) H. Fernando, J. Siriwardana, S. Halgamuge, Can a data center heat-flow model be scaled down?, ICIAFS Proc IEEE 6th Int. Conf. Inf. Autom. Sustain. (2012) R.R. Schmidt, K.C. Karki, K.M. Kelkar, A. Radmehr, S. V. Patankar, Measurements and predictions of the flow distribution through perforated tiles in raised-floor data centers, in: Proc. IPACK 01 Pacific Rim/ASME Int. Electron. Packag. Tech. Conf. Exhib., Kauai, Hawaii, USA, 2001: pp K.C. Karki, A. Radmehr, S. V Patankar, K.C. Karki, Use of computational fluid dynamics for calculating flow rates through perforated tiles in raised-floor data centers, HVAC&R Res. 9 (2003) M. Herrlin, R.G. Kluge, Thermal management in telecommunications central offices: The next steps, in: Telecommun. Energy Conf. (INTELEC), 32nd Int., 2010: pp S. V. Patankar, Airflow and Cooling in a Data Center, J. Heat Transfer. 132 (2010)

Optimizing Cooling Performance Of a Data Center

Optimizing Cooling Performance Of a Data Center ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

Numerical Investigation of Cooling of Electronic Servers Racks at Different Locations and Spacing from the Data Center Cooling Unit

Numerical Investigation of Cooling of Electronic Servers Racks at Different Locations and Spacing from the Data Center Cooling Unit International Journal of Current Engineering and echnology E-ISSN 2277 416, P-ISSN 2347 5161 15 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Numerical

More information

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data

More information

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models The MIT Faculty has made this article openly available. Please share how this access benefits

More information

USING CFD SIMULATIONS TO IMPROVE THE MODELING OF WINDOW DISCHARGE COEFFICIENTS

USING CFD SIMULATIONS TO IMPROVE THE MODELING OF WINDOW DISCHARGE COEFFICIENTS USING CFD SIMULATIONS TO IMPROVE THE MODELING OF WINDOW DISCHARGE COEFFICIENTS Erin L. Hult 1, Gianluca Iaccarino 2, and Martin Fischer 2 1 Lawrence Berkeley National Laboratory, Berkeley, CA 2 Stanford

More information

CFD Modeling of an Existing Raised-Floor Data Center

CFD Modeling of an Existing Raised-Floor Data Center CFD Modeling of an Existing Raised-Floor Data Center Amir Radmehr 1, Brendan Noll 2, John Fitzpatrick 2, Kailash Karki 1 1. Innovative Research, Inc. 3025 Harbor Lane N, Suite 300, Plymouth, MN 2. University

More information

Temperature monitoring and CFD Analysis of Data Centre

Temperature monitoring and CFD Analysis of Data Centre Available online at www.sciencedirect.com Procedia Engineering 56 (2013 ) 551 559 5 th BSME International Conference on Thermal Engineering Temperature monitoring and CFD Analysis of Data Centre N.M.S.

More information

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering Energy Efficient Data Center Design Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering 1 Bio Can Ozcan received his Master of Science in Mechanical Engineering from Bogazici University of Turkey in

More information

Numerical Study of Turbulent Flow over Backward-Facing Step with Different Turbulence Models

Numerical Study of Turbulent Flow over Backward-Facing Step with Different Turbulence Models Numerical Study of Turbulent Flow over Backward-Facing Step with Different Turbulence Models D. G. Jehad *,a, G. A. Hashim b, A. K. Zarzoor c and C. S. Nor Azwadi d Department of Thermo-Fluids, Faculty

More information

Modelling of a Wall Inlet in Numerical Simulation of Airflow in Livestock Buildings

Modelling of a Wall Inlet in Numerical Simulation of Airflow in Livestock Buildings 1 Modelling of a Wall Inlet in Numerical Simulation of Airflow in Livestock Buildings B. Bjerg 1, K. Svidt 2, S Morsing 3, G. Zhang 3 and J. O. Johnsen 3 1 The Royal Veterinary and Agricultural University,

More information

Available online at ScienceDirect. Procedia Engineering 146 (2016 )

Available online at   ScienceDirect. Procedia Engineering 146 (2016 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 146 (2016 ) 350 358 8th International Cold Climate HVAC 2015 Conference, CCHVAC 2015 Influence of air-conditioning outdoor unit

More information

Impact of Air Containment Systems

Impact of Air Containment Systems White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase

More information

Simulation of Turbulent Axisymmetric Waterjet Using Computational Fluid Dynamics (CFD)

Simulation of Turbulent Axisymmetric Waterjet Using Computational Fluid Dynamics (CFD) Simulation of Turbulent Axisymmetric Waterjet Using Computational Fluid Dynamics (CFD) PhD. Eng. Nicolae MEDAN 1 1 Technical University Cluj-Napoca, North University Center Baia Mare, Nicolae.Medan@cunbm.utcluj.ro

More information

COMPUTATIONAL FLUID DYNAMICS ANALYSIS OF ORIFICE PLATE METERING SITUATIONS UNDER ABNORMAL CONFIGURATIONS

COMPUTATIONAL FLUID DYNAMICS ANALYSIS OF ORIFICE PLATE METERING SITUATIONS UNDER ABNORMAL CONFIGURATIONS COMPUTATIONAL FLUID DYNAMICS ANALYSIS OF ORIFICE PLATE METERING SITUATIONS UNDER ABNORMAL CONFIGURATIONS Dr W. Malalasekera Version 3.0 August 2013 1 COMPUTATIONAL FLUID DYNAMICS ANALYSIS OF ORIFICE PLATE

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.

More information

Data Center Energy and Cost Saving Evaluation

Data Center Energy and Cost Saving Evaluation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

CFD design tool for industrial applications

CFD design tool for industrial applications Sixth LACCEI International Latin American and Caribbean Conference for Engineering and Technology (LACCEI 2008) Partnering to Success: Engineering, Education, Research and Development June 4 June 6 2008,

More information

Experimental Study of Airflow Designs for Data Centers

Experimental Study of Airflow Designs for Data Centers Experimental Study of Airflow Designs for Data Centers Takashi Tsuchiya*, Yoshihide Suwa 2 and Ryozo Ooka 3 Technical Research Institute, Obayashi Corporation, M. Eng., Japan 2 Technical Research Institute,

More information

INVESTIGATION OF HYDRAULIC PERFORMANCE OF A FLAP TYPE CHECK VALVE USING CFD AND EXPERIMENTAL TECHNIQUE

INVESTIGATION OF HYDRAULIC PERFORMANCE OF A FLAP TYPE CHECK VALVE USING CFD AND EXPERIMENTAL TECHNIQUE International Journal of Mechanical Engineering and Technology (IJMET) Volume 10, Issue 1, January 2019, pp. 409 413, Article ID: IJMET_10_01_042 Available online at http://www.ia aeme.com/ijmet/issues.asp?jtype=ijmet&vtype=

More information

NUMERICAL ANALYSIS OF WIND EFFECT ON HIGH-DENSITY BUILDING AERAS

NUMERICAL ANALYSIS OF WIND EFFECT ON HIGH-DENSITY BUILDING AERAS NUMERICAL ANALYSIS OF WIND EFFECT ON HIGH-DENSITY BUILDING AERAS Bin ZHAO, Ying LI, Xianting LI and Qisen YAN Department of Thermal Engineering, Tsinghua University Beijing, 100084, P.R. China ABSTRACT

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

STAR-CCM+: Ventilation SPRING Notes on the software 2. Assigned exercise (submission via Blackboard; deadline: Thursday Week 9, 11 pm)

STAR-CCM+: Ventilation SPRING Notes on the software 2. Assigned exercise (submission via Blackboard; deadline: Thursday Week 9, 11 pm) STAR-CCM+: Ventilation SPRING 208. Notes on the software 2. Assigned exercise (submission via Blackboard; deadline: Thursday Week 9, pm). Features of the Exercise Natural ventilation driven by localised

More information

c Fluent Inc. May 16,

c Fluent Inc. May 16, Tutorial 1. Office Ventilation Introduction: This tutorial demonstrates how to model an office shared by two people working at computers, using Airpak. In this tutorial, you will learn how to: Open a new

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Effectiveness and Implementation of Modular Containment in Existing Data Centers

Effectiveness and Implementation of Modular Containment in Existing Data Centers WHITE PAPER Effectiveness and Implementation of Modular Containment in Existing Data Centers By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. 505.798.0200 upsite.com

More information

Temperature Analysis of Intel Server by using CFD and Experimentation

Temperature Analysis of Intel Server by using CFD and Experimentation Temperature Analysis of Intel Server by using CFD and Experimentation Chetan A Gawande 1, Prof. S.M. Nakate 2, Prasad Chavan 3 ¹Dept. of Mechanical engineering, MIT Pune, Pune University, pune India ²Dept.

More information

Rack Cooling Effectiveness in Data Centers and Telecom Central Offices: The Rack Cooling Index (RCI)

Rack Cooling Effectiveness in Data Centers and Telecom Central Offices: The Rack Cooling Index (RCI) 2005. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted by permission from ASHRAE Transactions, Vol. 111, Part 2. This material may not be copied nor distributed

More information

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

Computational Simulation of the Wind-force on Metal Meshes

Computational Simulation of the Wind-force on Metal Meshes 16 th Australasian Fluid Mechanics Conference Crown Plaza, Gold Coast, Australia 2-7 December 2007 Computational Simulation of the Wind-force on Metal Meshes Ahmad Sharifian & David R. Buttsworth Faculty

More information

ISSN(PRINT): ,(ONLINE): ,VOLUME-1,ISSUE-1,

ISSN(PRINT): ,(ONLINE): ,VOLUME-1,ISSUE-1, NUMERICAL ANALYSIS OF THE TUBE BANK PRESSURE DROP OF A SHELL AND TUBE HEAT EXCHANGER Kartik Ajugia, Kunal Bhavsar Lecturer, Mechanical Department, SJCET Mumbai University, Maharashtra Assistant Professor,

More information

STUDY OF FLOW PERFORMANCE OF A GLOBE VALVE AND DESIGN OPTIMISATION

STUDY OF FLOW PERFORMANCE OF A GLOBE VALVE AND DESIGN OPTIMISATION Journal of Engineering Science and Technology Vol. 12, No. 9 (2017) 2403-2409 School of Engineering, Taylor s University STUDY OF FLOW PERFORMANCE OF A GLOBE VALVE AND DESIGN OPTIMISATION SREEKALA S. K.

More information

Driven Cavity Example

Driven Cavity Example BMAppendixI.qxd 11/14/12 6:55 PM Page I-1 I CFD Driven Cavity Example I.1 Problem One of the classic benchmarks in CFD is the driven cavity problem. Consider steady, incompressible, viscous flow in a square

More information

Ashwin Shridhar et al. Int. Journal of Engineering Research and Applications ISSN : , Vol. 5, Issue 6, ( Part - 5) June 2015, pp.

Ashwin Shridhar et al. Int. Journal of Engineering Research and Applications ISSN : , Vol. 5, Issue 6, ( Part - 5) June 2015, pp. RESEARCH ARTICLE OPEN ACCESS Conjugate Heat transfer Analysis of helical fins with airfoil crosssection and its comparison with existing circular fin design for air cooled engines employing constant rectangular

More information

Study Of Overloading Effects, In A Refrigerated Display Case

Study Of Overloading Effects, In A Refrigerated Display Case Study Of Overloading Effects, In A Refrigerated Display Case Sandeep Palaksha Senior CAE Engineer HUSSMANN Basavanagudi Bangalore 04, India p.sandeep@hussmann.com Narasimhamurthy CAE Engineer HUSSMANN

More information

To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels

To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels The use of a hot aisle/cold aisle configuration in the data center has long been considered a best practice

More information

1.0 Executive Summary. 2.0 Available Features & Benefits

1.0 Executive Summary. 2.0 Available Features & Benefits Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions

More information

Experimental parametric study of servers cooling management in data centers buildings

Experimental parametric study of servers cooling management in data centers buildings See discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/318107721 Experimental parametric study of servers cooling management in data centers buildings

More information

CFD Analysis of a Fully Developed Turbulent Flow in a Pipe with a Constriction and an Obstacle

CFD Analysis of a Fully Developed Turbulent Flow in a Pipe with a Constriction and an Obstacle CFD Analysis of a Fully Developed Turbulent Flow in a Pipe with a Constriction and an Obstacle C, Diyoke Mechanical Engineering Department Enugu State University of Science & Tech. Enugu, Nigeria U, Ngwaka

More information

Introduction to C omputational F luid Dynamics. D. Murrin

Introduction to C omputational F luid Dynamics. D. Murrin Introduction to C omputational F luid Dynamics D. Murrin Computational fluid dynamics (CFD) is the science of predicting fluid flow, heat transfer, mass transfer, chemical reactions, and related phenomena

More information

Alfonso Ortega Villanova University Site Director Associate Vice President Research and Graduate Programs James R. Birle Professor of Energy Technology Villanova University www.villanova.edu/es2 Villanova

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

TYPE 529: RADIANT SLAB

TYPE 529: RADIANT SLAB TYPE 529: RADIANT SLAB General Description This component is intended to model a radiant floor-heating slab, embedded in soil, and containing a number of fluid filled pipes. The heat transfer within the

More information

Review on Performance Metrics for Energy Efficiency in Data Center: The Role of Thermal Management

Review on Performance Metrics for Energy Efficiency in Data Center: The Role of Thermal Management Review on Performance Metrics for Energy Efficiency in Data Center: The Role of Thermal Management Alfonso Capozzoli 1, Marta Chinnici 2,, Marco Perino 1, Gianluca Serale 1 1 Politecnico di Torino, Corso

More information

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOR INTO THE INLET GUIDE VANE SYSTEM (IGV)

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOR INTO THE INLET GUIDE VANE SYSTEM (IGV) University of West Bohemia» Department of Power System Engineering NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOR INTO THE INLET GUIDE VANE SYSTEM (IGV) Publication was supported by project: Budování excelentního

More information

NUMERICAL MODELING STUDY FOR FLOW PATTERN CHANGES INDUCED BY SINGLE GROYNE

NUMERICAL MODELING STUDY FOR FLOW PATTERN CHANGES INDUCED BY SINGLE GROYNE NUMERICAL MODELING STUDY FOR FLOW PATTERN CHANGES INDUCED BY SINGLE GROYNE Jungseok Ho 1, Hong Koo Yeo 2, Julie Coonrod 3, and Won-Sik Ahn 4 1 Research Assistant Professor, Dept. of Civil Engineering,

More information

Introduction to Computational Fluid Dynamics Mech 122 D. Fabris, K. Lynch, D. Rich

Introduction to Computational Fluid Dynamics Mech 122 D. Fabris, K. Lynch, D. Rich Introduction to Computational Fluid Dynamics Mech 122 D. Fabris, K. Lynch, D. Rich 1 Computational Fluid dynamics Computational fluid dynamics (CFD) is the analysis of systems involving fluid flow, heat

More information

Flow and Heat Transfer in a Mixing Elbow

Flow and Heat Transfer in a Mixing Elbow Flow and Heat Transfer in a Mixing Elbow Objectives The main objectives of the project are to learn (i) how to set up and perform flow simulations with heat transfer and mixing, (ii) post-processing and

More information

New Techniques for Energy-Efficient Data Center Cooling

New Techniques for Energy-Efficient Data Center Cooling New Techniques for Energy-Efficient Data Center Cooling Applications for Large and Small Data Centers By Wally Phelps Director of Engineering AdaptivCOOL www.adaptivcool.com Copyright Degree Controls,

More information

CFD MODELING FOR PNEUMATIC CONVEYING

CFD MODELING FOR PNEUMATIC CONVEYING CFD MODELING FOR PNEUMATIC CONVEYING Arvind Kumar 1, D.R. Kaushal 2, Navneet Kumar 3 1 Associate Professor YMCAUST, Faridabad 2 Associate Professor, IIT, Delhi 3 Research Scholar IIT, Delhi e-mail: arvindeem@yahoo.co.in

More information

OPTIMISATION OF PIN FIN HEAT SINK USING TAGUCHI METHOD

OPTIMISATION OF PIN FIN HEAT SINK USING TAGUCHI METHOD CHAPTER - 5 OPTIMISATION OF PIN FIN HEAT SINK USING TAGUCHI METHOD The ever-increasing demand to lower the production costs due to increased competition has prompted engineers to look for rigorous methods

More information

Speed and Accuracy of CFD: Achieving Both Successfully ANSYS UK S.A.Silvester

Speed and Accuracy of CFD: Achieving Both Successfully ANSYS UK S.A.Silvester Speed and Accuracy of CFD: Achieving Both Successfully ANSYS UK S.A.Silvester 2010 ANSYS, Inc. All rights reserved. 1 ANSYS, Inc. Proprietary Content ANSYS CFD Introduction ANSYS, the company Simulation

More information

A Green Approach. Thermal

A Green Approach. Thermal A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout

More information

Dispersion Modelling for Explosion Risk Analysis

Dispersion Modelling for Explosion Risk Analysis Dispersion Modelling for Explosion Risk Analysis Tim Jones, Principal Consultant, MMI Engineering, The Brew House, Wilderspool Park, Greenall s Avenue, Warrington, WA4 6HL The understanding of the explosion

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

Effect of suction pipe leaning angle and water level on the internal flow of pump sump

Effect of suction pipe leaning angle and water level on the internal flow of pump sump IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Effect of suction pipe leaning angle and water level on the internal flow of pump sump To cite this article: Z-M Chen et al 216

More information

Running Your Data Center Under Ideal Temperature Conditions

Running Your Data Center Under Ideal Temperature Conditions TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient

More information

Tutorial 1. Introduction to Using FLUENT: Fluid Flow and Heat Transfer in a Mixing Elbow

Tutorial 1. Introduction to Using FLUENT: Fluid Flow and Heat Transfer in a Mixing Elbow Tutorial 1. Introduction to Using FLUENT: Fluid Flow and Heat Transfer in a Mixing Elbow Introduction This tutorial illustrates the setup and solution of the two-dimensional turbulent fluid flow and heat

More information

Large Eddy Simulation of Flow over a Backward Facing Step using Fire Dynamics Simulator (FDS)

Large Eddy Simulation of Flow over a Backward Facing Step using Fire Dynamics Simulator (FDS) The 14 th Asian Congress of Fluid Mechanics - 14ACFM October 15-19, 2013; Hanoi and Halong, Vietnam Large Eddy Simulation of Flow over a Backward Facing Step using Fire Dynamics Simulator (FDS) Md. Mahfuz

More information

Axial Channel Water Jacket Cooling

Axial Channel Water Jacket Cooling 28 November 2017 Motor-CAD Software Tutorial: Axial Channel Water Jacket Cooling Contents 1. Description... 1 2. Setting up the housing and axial channels... 2 3. Setting the water jacket fluid and flow

More information

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment

More information

CHAPTER 5 STUDY OF THERMAL COMFORT IN A ROOM WITH INSECT PROOF SCREEN

CHAPTER 5 STUDY OF THERMAL COMFORT IN A ROOM WITH INSECT PROOF SCREEN 146 CHAPTER 5 STUDY OF THERMAL COMFORT IN A ROOM WITH INSECT PROOF SCREEN 5.1 INTRODUCTION In recent days, most of the buildings are equipped with insect proof screens to keep the insect not to enter inside

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

CFD-1. Introduction: What is CFD? T. J. Craft. Msc CFD-1. CFD: Computational Fluid Dynamics

CFD-1. Introduction: What is CFD? T. J. Craft. Msc CFD-1. CFD: Computational Fluid Dynamics School of Mechanical Aerospace and Civil Engineering CFD-1 T. J. Craft George Begg Building, C41 Msc CFD-1 Reading: J. Ferziger, M. Peric, Computational Methods for Fluid Dynamics H.K. Versteeg, W. Malalasekara,

More information

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6)

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6) INT 492 : Selected Topic in IT II (Data Center Design) 3(3-0-6) การออกแบบระบบศ นย สารสนเทศ Overview The American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Technical Committee

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

Simulation of Flow Development in a Pipe

Simulation of Flow Development in a Pipe Tutorial 4. Simulation of Flow Development in a Pipe Introduction The purpose of this tutorial is to illustrate the setup and solution of a 3D turbulent fluid flow in a pipe. The pipe networks are common

More information

EFFECT OF CRAC LOCATION ON A FIXED RACK LAYOUT OF A DATA CENTER VISHWAS BEDEKAR. Presented to the Faculty of the Graduate School of

EFFECT OF CRAC LOCATION ON A FIXED RACK LAYOUT OF A DATA CENTER VISHWAS BEDEKAR. Presented to the Faculty of the Graduate School of EFFECT OF CRAC LOCATION ON A FIXED RACK LAYOUT OF A DATA CENTER by VISHWAS BEDEKAR Presented to the Faculty of the Graduate School of The University of Texas at Arlington in Partial Fulfillment of the

More information

Optimizing Bio-Inspired Flow Channel Design on Bipolar Plates of PEM Fuel Cells

Optimizing Bio-Inspired Flow Channel Design on Bipolar Plates of PEM Fuel Cells Excerpt from the Proceedings of the COMSOL Conference 2010 Boston Optimizing Bio-Inspired Flow Channel Design on Bipolar Plates of PEM Fuel Cells James A. Peitzmeier *1, Steven Kapturowski 2 and Xia Wang

More information

On the numerical accuracy of particle dispersion simulation in operating theatres

On the numerical accuracy of particle dispersion simulation in operating theatres On the numerical accuracy of particle dispersion simulation in operating theatres Wiebe Zoon 1,*, Marcel Loomans 1 and Jan Hensen 1 1 Eindhoven University of Technology, Eindhoven, the Netherlands * Corresponding

More information

Numerical Simulation of Heat Transfer by Natural Convection in Horizontal Finned Channels

Numerical Simulation of Heat Transfer by Natural Convection in Horizontal Finned Channels Numerical Simulation of Heat Transfer by Natural Convection in Horizontal Finned Channels Gabriel Gonçalves da Silva Ferreira, Luiz Fernando Lopes Rodrigues Silva Escola de Química, UFRJ Paulo L. C. Lage

More information

PERFORMANCE OF TEMPERATURE CONTROLLED PERIMETER AND ROW-BASED COOLING SYSTEMS IN OPEN AND CONTAINMENT ENVIRONMENT

PERFORMANCE OF TEMPERATURE CONTROLLED PERIMETER AND ROW-BASED COOLING SYSTEMS IN OPEN AND CONTAINMENT ENVIRONMENT Proceedings of the ASME 2015 International Mechanical Engineering Congress and Exposition IMECE2015 November 13-19, 2015, Houston, Texas, USA IMECE2015-52667 PERFORMANCE OF TEMPERATURE CONTROLLED PERIMETER

More information

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace

More information

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation DC ASSESSMENT SERVICES AISLE CONTAINMENT AIRFLOW MANAGEMENT Achieving true 24/7/365 operation

More information

Airflow Management s Role in Data Center Cooling Capacity

Airflow Management s Role in Data Center Cooling Capacity Airflow Management s Role in Data Center Cooling Capacity By Larry Mainers, CEO Subzero Engineering 2014 Subzero Engineering SUMMARY Airflow management (AFM) is changing the way data centers cool the IT

More information

Calculate a solution using the pressure-based coupled solver.

Calculate a solution using the pressure-based coupled solver. Tutorial 19. Modeling Cavitation Introduction This tutorial examines the pressure-driven cavitating flow of water through a sharpedged orifice. This is a typical configuration in fuel injectors, and brings

More information

CFD validation of the thermal comfort in a room using draft rates

CFD validation of the thermal comfort in a room using draft rates CFD validation of the thermal comfort in a room using draft rates Authors: Mika Ruponen 1 and John A. Tinker 1 1 School of Civil Engineering, University of Leeds, UK Corresponding email: mika.ruponen@halton.com

More information

Numerical Wave Tank Modeling of Hydrodynamics of Permeable Barriers

Numerical Wave Tank Modeling of Hydrodynamics of Permeable Barriers ICHE 2014, Hamburg - Lehfeldt & Kopmann (eds) - 2014 Bundesanstalt für Wasserbau ISBN 978-3-939230-32-8 Numerical Wave Tank Modeling of Hydrodynamics of Permeable Barriers K. Rajendra & R. Balaji Indian

More information

Keywords: flows past a cylinder; detached-eddy-simulations; Spalart-Allmaras model; flow visualizations

Keywords: flows past a cylinder; detached-eddy-simulations; Spalart-Allmaras model; flow visualizations A TURBOLENT FLOW PAST A CYLINDER *Vít HONZEJK, **Karel FRAŇA *Technical University of Liberec Studentská 2, 461 17, Liberec, Czech Republic Phone:+ 420 485 353434 Email: vit.honzejk@seznam.cz **Technical

More information

LCP Hybrid Efficient performance with heat pipe technology

LCP Hybrid Efficient performance with heat pipe technology LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative

More information

Verification and Validation in CFD and Heat Transfer: ANSYS Practice and the New ASME Standard

Verification and Validation in CFD and Heat Transfer: ANSYS Practice and the New ASME Standard Verification and Validation in CFD and Heat Transfer: ANSYS Practice and the New ASME Standard Dimitri P. Tselepidakis & Lewis Collins ASME 2012 Verification and Validation Symposium May 3 rd, 2012 1 Outline

More information

Estimation of Flow Field & Drag for Aerofoil Wing

Estimation of Flow Field & Drag for Aerofoil Wing Estimation of Flow Field & Drag for Aerofoil Wing Mahantesh. HM 1, Prof. Anand. SN 2 P.G. Student, Dept. of Mechanical Engineering, East Point College of Engineering, Bangalore, Karnataka, India 1 Associate

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42 Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing

More information

CIBSE Application Manual AM11 Building Performance Modelling Chapter 6: Ventilation Modelling

CIBSE Application Manual AM11 Building Performance Modelling Chapter 6: Ventilation Modelling Contents Background Ventilation modelling tool categories Simple tools and estimation techniques Analytical methods Zonal network methods Computational Fluid Dynamics (CFD) Semi-external spaces Summary

More information

Lab 9: FLUENT: Transient Natural Convection Between Concentric Cylinders

Lab 9: FLUENT: Transient Natural Convection Between Concentric Cylinders Lab 9: FLUENT: Transient Natural Convection Between Concentric Cylinders Objective: The objective of this laboratory is to introduce how to use FLUENT to solve both transient and natural convection problems.

More information

MOMENTUM AND HEAT TRANSPORT INSIDE AND AROUND

MOMENTUM AND HEAT TRANSPORT INSIDE AND AROUND MOMENTUM AND HEAT TRANSPORT INSIDE AND AROUND A CYLINDRICAL CAVITY IN CROSS FLOW G. LYDON 1 & H. STAPOUNTZIS 2 1 Informatics Research Unit for Sustainable Engrg., Dept. of Civil Engrg., Univ. College Cork,

More information

BURN-IN OVEN MODELING USING COMPUTATIONAL FLUID DYNAMICS (CFD)

BURN-IN OVEN MODELING USING COMPUTATIONAL FLUID DYNAMICS (CFD) BURN-IN OVEN MODELING USING COMPUTATIONAL FLUID DYNAMICS (CFD) Jefferson S. Talledo ATD-P Technology Business Group Intel Technology Philippines, Inc., Gateway Business Park, Gen. Trias, Cavite jefferson.s.talledo@intel.com

More information

Turbulencja w mikrokanale i jej wpływ na proces emulsyfikacji

Turbulencja w mikrokanale i jej wpływ na proces emulsyfikacji Polish Academy of Sciences Institute of Fundamental Technological Research Turbulencja w mikrokanale i jej wpływ na proces emulsyfikacji S. Błoński, P.Korczyk, T.A. Kowalewski PRESENTATION OUTLINE 0 Introduction

More information

EXPERIMENTAL ANALYSIS & SIMULATION OF DOUBLE PIPE HEAT EXCHANGER

EXPERIMENTAL ANALYSIS & SIMULATION OF DOUBLE PIPE HEAT EXCHANGER EXPERIMENTAL ANALYSIS & SIMULATION OF DOUBLE PIPE HEAT EXCHANGER Kale Shivam B 1, Kadam Prashant P 2, Pardeshi Rohansingh G 3, Karwande Swapnil C 4 1 Student, Mechanical Engineering, GHRCOEM, Ahmednagar,

More information

Design Modification and Analysis of Two Wheeler Engine Cooling Fins by CFD

Design Modification and Analysis of Two Wheeler Engine Cooling Fins by CFD Design Modification and Analysis of Two Wheeler Engine Cooling Fins by CFD Mohsin A. Ali and Prof. (Dr.) S.M Kherde Abstract An air-cooled motorcycle engine releases heat to the atmosphere through the

More information

Application of TileFlow to Improve Cooling in a Data Center

Application of TileFlow to Improve Cooling in a Data Center Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance

More information