Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering

Size: px
Start display at page:

Download "Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering"

Transcription

1 Energy Efficient Data Center Design Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering 1

2 Bio Can Ozcan received his Master of Science in Mechanical Engineering from Bogazici University of Turkey in 2005, which involved fracture mechanics of thin films using Ansys Mechanical software. Mr. Ozcan has been involved in CAE consulting and technical support using Ansys software for 6 years with Ozen Engineering in Silicon Valley; specifically working on Applied Mechanics problems. Mr. Ozcan has presented at international conferences in Europe and America and has published articles on various simulation related topics. Emre Turkoz is studying Mechanical Engineering at Bogazici University, Istanbul, Turkey. He is working part-time in the CFD/FMS Lab at the university, dealing mainly with modelling complicated flow problems using particle tracking methods. He s also participating in active research about Domain Decomposition and High Performance Computing algorithm development. 2

3 Ozen Engineering Inc We are the local ANSYS channel partner With over 25 years of experience in Finite Elements Simulations and Engineering Consulting, we collaborate with customers to provide the best in class expertise and solutions to their problems, enabling them to succeed. 3

4 Main Guides Build the Best Data Facility for Your Business, by Dougles Alger The Dell Smart Solution Advisor for data centers 4

5 Air Handler Placement Options Having airflow between the corridors is desired for efficient cooling (Air Handler C) 5

6 Typical Data Center Layouts Larger and smaller data center layouts Area= 2270 ft 2 = m 2 # cabinets = 78 Area per cabinet = 2.7 m 2 Grid edge length ~= 0.6 m Area= 1301 ft 2 = m 2 # cabinets = 36 Area per cabinet = 3.4 m 2 Grid edge length ~= 0.6 m 6

7 Detailed Data Center HVAC Analysis Each unit can be examined in more details by dividing into sub-divisions 7

8 Data Center Cooling Process Overhead or Underfloor? Air handlers circulate air within the Data Center, drawing in warm air from the space between the floor and ceiling and discharging cold air into the room's plenum. (This occurs typically below the raised floor if a Data Center has one, and above the false ceiling if it doesn't.) Air is cooled within the handler by passing over coils containing chilled liquid think of wind blowing across a block of ice and then expelled into the Data Center. The coils are generally maintained at about 43 or 44 Fahrenheit (6.1 or 6.7 Celsius). 8

9 Overhead or Underfloor? Underfloor is harder to install, might need a ramp at the entrance, more expensive Overhead is easier and much cheaper to install. But, It is significantly more difficult to cool a server environment by pushing cold air downward So, if our concern is the energy-efficiency, we should simulate an underfloor simulation. 9

10 Underfloor Cooling Underfloor is preferred for energy efficient cooling 10

11 Cooling Quantities 1 ton of cooling = BTUs 1 Watt = 3.41 BTUs -> 1 ton of cooling ~= 3.5 kw Watts per square foot/meter => a measure of how much energy is used in the data center. 11

12 Simulation Setup For the design, we choose underfloor configuration, i.e. air vent openings will be distributed on the floor Air Handler units will be assigned as outlets Every cabinet/rack will generate 10 kw heat with 0,85 m 3 /s flow rate. [5] Server environment should be kept between 18 and 23 degrees Celcius. AC unit inlet temperature is between 10 and 17 degrees Celcius. AC unit volumetric flow rate ~8 m 3 /s. 12

13 Solver Settings Values taken from the previous analysis: Heat flux from Walls: adiabatic Fluid Material: Air at 25 degrees Celcius Buoyancy Model: Buoyant Turbulence Model: Shear Stress Transport Radiation: Off Inlet turbulence fraction intensity: 0.30 Inlet eddy length scale: 0.1 m 13

14 Geometry for CFD Domain Geometry Details room dimensions (width)x(length)x(height) : 4800mm x 9000mm x 3800mm rack dimensions (width)x(length)x(height) : 1200mm x 600mm x 2100mm air handler dimensions (width)x(length)x(height): 3000mm x 1200mm x 1600mm # of rows of cabinets: 2 # of Cabinets: 8 per each row (10kW each) Floor vent tile openings are modeled as a porous domain with directional loss coefficients plenum 14

15 Problem Setup Boundary Conditions applied on the problem Air Handling Unit (Outlet) Service Racks (8 cabinets, 10kW each) 15 [image textured]

16 Problem Setup Boundary Conditions applied on the problem Air Handling Unit (Outlet 0 pressure) 8.0 m 3 /s flow rate Underfloor Cooling Vent Tile Openings (Porous Domain) 16 [image textured]

17 Problem Setup Boundary Conditions applied on the problem Air Handling Unit (Outlet 0 pressure) 8.0 m 3 /s flow rate Underfloor Air Handling Unit 17C 17 [image textured]

18 Problem Setup Vent tile openings are modeled as porous domain with directional losses [4] Server Room (Lower Pressure wrt. Plenum, pressure drop due to air grill structure) Air Grill (Porous with Loss Coefficient) Plenum (Higher Pressure at Air Inlet Side) 18

19 Optimization for Energy Efficiency We would like to have efficient cooling by finding the right grill sizing and putting correct air deflectors in the room (of course other/more parameters can be used depending on the need ) Input Parameters Grill Free Area Ratio Deflector Length Deflector Height Deflector Position 19

20 Optimization for Energy Efficiency We would like to have efficient cooling by finding the right grill sizing and putting correct air deflectors in the room (of course other/more parameters can be used depending on the need ) Output Parameters Rack Temperature Temperature Uniformity 20

21 Response Surfaces Optimization Design Explorer is employed for performing response surface based optimization Initial DOE generated by Optimal Space Filling algorithm which is suitable for nonlinear response Non-parametric regression algorithm is employed for response surface MOGA (Multi Objective Genetic Algorithm) is used for performing optimization Optimal design candidates are verified for accuracy 21

22 Effect Of Vent Tile Free Area Ratio Air vent tile free area ratio has around minimum 22

23 Effect Of Air Deflector Position Deflector position is found out to be optimum between 3 mto 4m 23

24 Effect Of Air Deflector Length & Height Deflector length should be small Deflector height should be large 24

25 Optimization - TradeOff Pareto frontier surface is useful to determine for multi-objective optimization We would like to minimize both Rack Average Temperatures and Standard Deviation for uniform cooling 25

26 Design Improvements As a result of the parametric optimization study, we were able to improve cooling conditions as outlined below 26 Initial Design Optimized Design

27 Design Improvements As a result of the parametric optimization study, we were able to improve cooling conditions as outlined below 27 Initial Design Optimized Design

28 Design Improvements As a result of the parametric optimization study, we were able to improve cooling conditions as outlined below 28 Initial Design Optimized Design

29 Velocity Vectors Velocity vectors are plotted to see how flow distributes over the grills and around the server room 29 [image textured]

30 Ansys CFX can be used to model thermal-flow conditions of data centers Ansys Design Explorer has robust tools to make parametric design space exploration and optimization based on multiple models Data centers can be designed as energy efficient and kept as energy efficient using simulation technology as needs change Conclusions 30

31 References *1+ U. Singh et.al. CFD-Based Operational Thermal Efficiency Improvement of a Production Data Center [2] S.V. Patankar Computational Modeling of Airflow in Raised-Floor Data Centers *3+ C.D. Patel et. al. Thermal Consideration in Cooling Large Scale High Compute Density Data Centers, EICTT Conference 2002 CA USA [4] Handbook of Hydraulic Resistance 3rd Edition I. E. Idelchik, CRC Begell House 1994 [5] ype=pdf 31

32 QUESTIONS? Thank you for your attention Please join us for Happy Hour following the conference. Ozen Engineering Inc: 1210 E. Arques Ave #207 Sunnyvale, CA (408) Directions: Right on Tasman Left on Lawrence Left on Arques Ave. Second Right into OEI parking lot. 32

Topology Optimization in Fluid Dynamics

Topology Optimization in Fluid Dynamics A Methodology for Topology Optimization in Fluid Dynamics 1 Chris Cowan Ozen Engineering, Inc. 1210 E. Arques Ave, Suite 207 Sunnyvale, CA 94085 info@ozeninc.com Ozen Engineering Inc. We are your local

More information

Optimizing Cooling Performance Of a Data Center

Optimizing Cooling Performance Of a Data Center ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

Study Of Overloading Effects, In A Refrigerated Display Case

Study Of Overloading Effects, In A Refrigerated Display Case Study Of Overloading Effects, In A Refrigerated Display Case Sandeep Palaksha Senior CAE Engineer HUSSMANN Basavanagudi Bangalore 04, India p.sandeep@hussmann.com Narasimhamurthy CAE Engineer HUSSMANN

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

BGA Simulation in Workbench: Challenges and Successes Presented by Kaan Divringi Ozen Engineering Inc

BGA Simulation in Workbench: Challenges and Successes Presented by Kaan Divringi Ozen Engineering Inc BGA Simulation in Workbench: Challenges and Successes Presented by Kaan Divringi Ozen Engineering Inc 1 Ozen Engineering Inc We are the local ANSYS channel partner With over 25 years of experience in Finite

More information

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it

More information

Temperature monitoring and CFD Analysis of Data Centre

Temperature monitoring and CFD Analysis of Data Centre Available online at www.sciencedirect.com Procedia Engineering 56 (2013 ) 551 559 5 th BSME International Conference on Thermal Engineering Temperature monitoring and CFD Analysis of Data Centre N.M.S.

More information

Application of TileFlow to Improve Cooling in a Data Center

Application of TileFlow to Improve Cooling in a Data Center Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance

More information

Effect of suction pipe leaning angle and water level on the internal flow of pump sump

Effect of suction pipe leaning angle and water level on the internal flow of pump sump IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Effect of suction pipe leaning angle and water level on the internal flow of pump sump To cite this article: Z-M Chen et al 216

More information

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models The MIT Faculty has made this article openly available. Please share how this access benefits

More information

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace

More information

Impact of Air Containment Systems

Impact of Air Containment Systems White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

Pramod Mandagere Prof. David Du Sandeep Uttamchandani (IBM Almaden)

Pramod Mandagere Prof. David Du Sandeep Uttamchandani (IBM Almaden) Pramod Mandagere Prof. David Du Sandeep Uttamchandani (IBM Almaden) Motivation Background Our Research Agenda Modeling Thermal Behavior Static Workload Provisioning Dynamic Workload Provisioning Improving

More information

Speed and Accuracy of CFD: Achieving Both Successfully ANSYS UK S.A.Silvester

Speed and Accuracy of CFD: Achieving Both Successfully ANSYS UK S.A.Silvester Speed and Accuracy of CFD: Achieving Both Successfully ANSYS UK S.A.Silvester 2010 ANSYS, Inc. All rights reserved. 1 ANSYS, Inc. Proprietary Content ANSYS CFD Introduction ANSYS, the company Simulation

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Close Coupled Cooling for Datacentres

Close Coupled Cooling for Datacentres Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close

More information

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment

More information

Estimating Data Center Thermal Correlation Indices from Historical Data

Estimating Data Center Thermal Correlation Indices from Historical Data Estimating Data Center Thermal Correlation Indices from Historical Data Manish Marwah, Cullen Bash, Rongliang Zhou, Carlos Felix, Rocky Shih, Tom Christian HP Labs Palo Alto, CA 94304 Email: firstname.lastname@hp.com

More information

Piero Marcolongo, M.S. Alberto Bassanese Design Optimization Applied to the Solar Industry

Piero Marcolongo, M.S. Alberto Bassanese Design Optimization Applied to the Solar Industry Piero Marcolongo, M.S. piero@ozeninc.com Alberto Bassanese alberto.bassanese@ozeninc.com Design Optimization Applied to the Solar Industry Process Integration and Desing Optimization The P.I.D.O. (Process

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

CFD Modeling of an Existing Raised-Floor Data Center

CFD Modeling of an Existing Raised-Floor Data Center CFD Modeling of an Existing Raised-Floor Data Center Amir Radmehr 1, Brendan Noll 2, John Fitzpatrick 2, Kailash Karki 1 1. Innovative Research, Inc. 3025 Harbor Lane N, Suite 300, Plymouth, MN 2. University

More information

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Variable Density, Closed-Loop, Water-Cooled Data Center Solution Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of

More information

Ten Cooling Solutions to Support High- Density Server Deployment

Ten Cooling Solutions to Support High- Density Server Deployment Ten Cooling Solutions to Support High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 2 Executive Summary High-density servers offer a significant performance per watt benefit. However,

More information

APC APPLICATION NOTE #74

APC APPLICATION NOTE #74 #74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for: REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009

More information

Swapnil Nimse Project 1 Challenge #2

Swapnil Nimse Project 1 Challenge #2 Swapnil Nimse Project 1 Challenge #2 Project Overview: Using Ansys-Fluent, analyze dependency of the steady-state temperature at different parts of the system on the flow velocity at the inlet and buoyancy-driven

More information

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Running Your Data Center Under Ideal Temperature Conditions

Running Your Data Center Under Ideal Temperature Conditions TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient

More information

Rethinking Datacenter Cooling

Rethinking Datacenter Cooling Rethinking Datacenter Cooling www.sempertec.com SemperTec White Paper Rethinking Datacenter Cooling Contents Executive Summary Introduction Air Distribution: Three Cooling Design Considerations Cold Aisle

More information

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,

More information

Alfonso Ortega Villanova University Site Director Associate Vice President Research and Graduate Programs James R. Birle Professor of Energy Technology Villanova University www.villanova.edu/es2 Villanova

More information

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOR INTO THE INLET GUIDE VANE SYSTEM (IGV)

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOR INTO THE INLET GUIDE VANE SYSTEM (IGV) University of West Bohemia» Department of Power System Engineering NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOR INTO THE INLET GUIDE VANE SYSTEM (IGV) Publication was supported by project: Budování excelentního

More information

Simulation and Optimization in the wind energy industry

Simulation and Optimization in the wind energy industry Simulation and Optimization in the wind energy industry Numerical Simulation & Optimization www.ozeninc.com/optimization optimization@ozeninc.com Summary Why to use numerical simulations and optimization?

More information

STAR-CCM+: Ventilation SPRING Notes on the software 2. Assigned exercise (submission via Blackboard; deadline: Thursday Week 9, 11 pm)

STAR-CCM+: Ventilation SPRING Notes on the software 2. Assigned exercise (submission via Blackboard; deadline: Thursday Week 9, 11 pm) STAR-CCM+: Ventilation SPRING 208. Notes on the software 2. Assigned exercise (submission via Blackboard; deadline: Thursday Week 9, pm). Features of the Exercise Natural ventilation driven by localised

More information

CIBSE Application Manual AM11 Building Performance Modelling Chapter 6: Ventilation Modelling

CIBSE Application Manual AM11 Building Performance Modelling Chapter 6: Ventilation Modelling Contents Background Ventilation modelling tool categories Simple tools and estimation techniques Analytical methods Zonal network methods Computational Fluid Dynamics (CFD) Semi-external spaces Summary

More information

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic

More information

Explicit Drop Test and Submodeling with ANSYS LS-DYNA

Explicit Drop Test and Submodeling with ANSYS LS-DYNA Explicit Drop Test and Submodeling with ANSYS LS-DYNA 1 Chris Cowan Ozen Engineering, Inc. 1210 E. Arques Ave, Suite 207 Sunnyvale, CA 94085 info@ozeninc.com Ozen Engineering Inc. We are your local ANSYS

More information

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU

More information

c Fluent Inc. May 16,

c Fluent Inc. May 16, Tutorial 1. Office Ventilation Introduction: This tutorial demonstrates how to model an office shared by two people working at computers, using Airpak. In this tutorial, you will learn how to: Open a new

More information

Energy Efficient Data Centers

Energy Efficient Data Centers IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an

More information

A Green Approach. Thermal

A Green Approach. Thermal A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout

More information

Google s Green Data Centers: Network POP Case Study

Google s Green Data Centers: Network POP Case Study Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.

More information

Optimizing data centers for high-density computing

Optimizing data centers for high-density computing Optimizing data centers for high-density computing technology brief, 2nd edition Abstract... 2 Introduction... 2 Power consumption and heat load... 2 Power consumption... 2 Heat load... 5 The Need for

More information

OPTIMISATION OF PIN FIN HEAT SINK USING TAGUCHI METHOD

OPTIMISATION OF PIN FIN HEAT SINK USING TAGUCHI METHOD CHAPTER - 5 OPTIMISATION OF PIN FIN HEAT SINK USING TAGUCHI METHOD The ever-increasing demand to lower the production costs due to increased competition has prompted engineers to look for rigorous methods

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER

A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER By David Moss Dell Data Center Infrastructure dell.com/hiddendatacenter Many people see an IT rack as a glorified shelving system.

More information

HP Modular Cooling System: water cooling technology for high-density server installations

HP Modular Cooling System: water cooling technology for high-density server installations HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased

More information

HIGH DENSITY RACK COOLING CHOICES

HIGH DENSITY RACK COOLING CHOICES WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase

More information

Computational Fluid Dynamics modeling of a Water Flow Over an Ogee Profile

Computational Fluid Dynamics modeling of a Water Flow Over an Ogee Profile FINITE ELEMENT METHOD TECHNICAL REPORT Computational Fluid Dynamics modeling of a Water Flow Over an Ogee Profile ANSYS CFX 12 ENME 547 Dr. Sudak Matias Sessarego Written Report Due Date: Friday December

More information

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell

More information

Intelligent / Sustainable Buildings utilizing Under-Floor HVAC Systems Advantages over the Life Cycle of a Commercial Building

Intelligent / Sustainable Buildings utilizing Under-Floor HVAC Systems Advantages over the Life Cycle of a Commercial Building Intelligent / Sustainable Buildings utilizing Under-Floor HVAC Systems Advantages over the Life Cycle of a Commercial Building We shape our buildings and then our buildings shape us Winston Churchill,

More information

Use of numerical flow simulations (CFD) for optimising heat exchangers

Use of numerical flow simulations (CFD) for optimising heat exchangers www.guentner.eu Technical article from 03.04.2017 Author Dr. Andreas Zürner Research Güntner GmbH & Co. KG Use of numerical flow simulations (CFD) for optimising heat exchangers Numerical flow simulations

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Coupled Analysis of FSI

Coupled Analysis of FSI Coupled Analysis of FSI Qin Yin Fan Oct. 11, 2008 Important Key Words Fluid Structure Interface = FSI Computational Fluid Dynamics = CFD Pressure Displacement Analysis = PDA Thermal Stress Analysis = TSA

More information

midas NFX 2017R1 Release Note

midas NFX 2017R1 Release Note Total Solution for True Analysis-driven Design midas NFX 2017R1 Release Note 1 midas NFX R E L E A S E N O T E 2 0 1 7 R 1 Major Improvements Midas NFX is an integrated finite element analysis program

More information

Modeling Evaporating Liquid Spray

Modeling Evaporating Liquid Spray Tutorial 17. Modeling Evaporating Liquid Spray Introduction In this tutorial, the air-blast atomizer model in ANSYS FLUENT is used to predict the behavior of an evaporating methanol spray. Initially, the

More information

ANSYS AIM Tutorial Fluid Flow Through a Transition Duct

ANSYS AIM Tutorial Fluid Flow Through a Transition Duct ANSYS AIM Tutorial Fluid Flow Through a Transition Duct Author(s): Sebastian Vecchi, ANSYS Created using ANSYS AIM 18.1 Problem Specification Start Up Geometry Import Geometry Extracting Volume Suppress

More information

CHAPTER 5 STUDY OF THERMAL COMFORT IN A ROOM WITH INSECT PROOF SCREEN

CHAPTER 5 STUDY OF THERMAL COMFORT IN A ROOM WITH INSECT PROOF SCREEN 146 CHAPTER 5 STUDY OF THERMAL COMFORT IN A ROOM WITH INSECT PROOF SCREEN 5.1 INTRODUCTION In recent days, most of the buildings are equipped with insect proof screens to keep the insect not to enter inside

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

New Techniques for Energy-Efficient Data Center Cooling

New Techniques for Energy-Efficient Data Center Cooling New Techniques for Energy-Efficient Data Center Cooling Applications for Large and Small Data Centers By Wally Phelps Director of Engineering AdaptivCOOL www.adaptivcool.com Copyright Degree Controls,

More information

Modeling Evaporating Liquid Spray

Modeling Evaporating Liquid Spray Tutorial 16. Modeling Evaporating Liquid Spray Introduction In this tutorial, FLUENT s air-blast atomizer model is used to predict the behavior of an evaporating methanol spray. Initially, the air flow

More information

CFD Simulation of a dry Scroll Vacuum Pump including Leakage Flows

CFD Simulation of a dry Scroll Vacuum Pump including Leakage Flows CFD Simulation of a dry Scroll Vacuum Pump including Leakage Flows Jan Hesse, Rainer Andres CFX Berlin Software GmbH, Berlin, Germany 1 Introduction Numerical simulation results of a dry scroll vacuum

More information

CRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS

CRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS CRITICAL FACILITIES ROUNDTABLE HEAT REMOVAL IN DATA CENTERS ENGINEERED SOLUTIONS Peter Klock, P.E., President ESC Engineering Services Company peter@escengineering.com Bill Henry, P.E., Consulting Mechanical

More information

USING CFD SIMULATIONS TO IMPROVE THE MODELING OF WINDOW DISCHARGE COEFFICIENTS

USING CFD SIMULATIONS TO IMPROVE THE MODELING OF WINDOW DISCHARGE COEFFICIENTS USING CFD SIMULATIONS TO IMPROVE THE MODELING OF WINDOW DISCHARGE COEFFICIENTS Erin L. Hult 1, Gianluca Iaccarino 2, and Martin Fischer 2 1 Lawrence Berkeley National Laboratory, Berkeley, CA 2 Stanford

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD

ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD R I T T A L T H E R M A L S E R I E S ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD FRIEDHELM L O H GROUP I. INTRODUCTION As a leading manufacturer of enclosure solutions, Rittal is frequently

More information

Introduction to ANSYS CFX

Introduction to ANSYS CFX Workshop 03 Fluid flow around the NACA0012 Airfoil 16.0 Release Introduction to ANSYS CFX 2015 ANSYS, Inc. March 13, 2015 1 Release 16.0 Workshop Description: The flow simulated is an external aerodynamics

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

The Role of CFD in Real Life Designs

The Role of CFD in Real Life Designs white paper The Role of CFD in Real Life Designs insight SUMMARY This paper relates two heat sinks, a medical suction device, a household oven, and an industrial control valve as examples that illustrate

More information

Effectiveness and Implementation of Modular Containment in Existing Data Centers

Effectiveness and Implementation of Modular Containment in Existing Data Centers WHITE PAPER Effectiveness and Implementation of Modular Containment in Existing Data Centers By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. 505.798.0200 upsite.com

More information

equivalent stress to the yield stess.

equivalent stress to the yield stess. Example 10.2-1 [Ansys Workbench/Thermal Stress and User Defined Result] A 50m long deck sitting on superstructures that sit on top of substructures is modeled by a box shape of size 20 x 5 x 50 m 3. It

More information

Available online at ScienceDirect. Procedia Engineering 146 (2016 )

Available online at   ScienceDirect. Procedia Engineering 146 (2016 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 146 (2016 ) 350 358 8th International Cold Climate HVAC 2015 Conference, CCHVAC 2015 Influence of air-conditioning outdoor unit

More information

Air Containment Design Choices and Considerations

Air Containment Design Choices and Considerations Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors

More information

Liquid Cooling Package LCP Cooling Systems

Liquid Cooling Package LCP Cooling Systems Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure,

More information

Femap Thermal & Flow V11

Femap Thermal & Flow V11 Femap Thermal & Flow V11 by Carl J. Poplawsky presented to Femap Symposium Ann Arbor, MI. date June 4th, 2015 MAYA Company Overview OEM Foundation Siemens PLM Partner 30+ years Software Developer Femap

More information

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing

More information

Case Study on Cold Air Distribution of a Data Centre

Case Study on Cold Air Distribution of a Data Centre Case Study on Cold Air Distribution of a Data Centre 1 A.S. Chandel, 2 Prabhash Jain 3 Dr. Anil Kumar 1 M.Tech Scholar, Product Design, Department of Mechanical Engineering, BUIT, Bhopal, INDIA 2 Head,

More information

McNair Scholars Research Journal

McNair Scholars Research Journal McNair Scholars Research Journal Volume 2 Article 1 2015 Benchmarking of Computational Models against Experimental Data for Velocity Profile Effects on CFD Analysis of Adiabatic Film-Cooling Effectiveness

More information

NUMERICAL MODELLING METHOD FOR THE DESIGN OF DATA CENTRE COOLING

NUMERICAL MODELLING METHOD FOR THE DESIGN OF DATA CENTRE COOLING NUMERICAL MODELLING METHOD FOR THE DESIGN OF DATA CENTRE COOLING AMIN AZARMI Mechanical Engineer Aurecon amin.azarmi@aurecongroup.com MOSTAFA MAHDAVI Research Fellow Department of Mechanical and Aeronautical

More information

Applications of ICFD solver by LS-DYNA in Automotive Fields to Solve Fluid-Solid-Interaction (FSI) Problems

Applications of ICFD solver by LS-DYNA in Automotive Fields to Solve Fluid-Solid-Interaction (FSI) Problems Applications of ICFD solver by LS-DYNA in Automotive Fields to Solve Fluid-Solid-Interaction (FSI) Problems George Wang(1 ), Facundo del Pin(2), Inaki Caldichoury (2), Prince Rodriguez(3), Jason Tippie

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

First Steps - Conjugate Heat Transfer

First Steps - Conjugate Heat Transfer COSMOSFloWorks 2004 Tutorial 2 First Steps - Conjugate Heat Transfer This First Steps - Conjugate Heat Transfer tutorial covers the basic steps to set up a flow analysis problem including conduction heat

More information

CFD modelling of thickened tailings Final project report

CFD modelling of thickened tailings Final project report 26.11.2018 RESEM Remote sensing supporting surveillance and operation of mines CFD modelling of thickened tailings Final project report Lic.Sc.(Tech.) Reeta Tolonen and Docent Esa Muurinen University of

More information

Preliminary Spray Cooling Simulations Using a Full-Cone Water Spray

Preliminary Spray Cooling Simulations Using a Full-Cone Water Spray 39th Dayton-Cincinnati Aerospace Sciences Symposium Preliminary Spray Cooling Simulations Using a Full-Cone Water Spray Murat Dinc Prof. Donald D. Gray (advisor), Prof. John M. Kuhlman, Nicholas L. Hillen,

More information

Experimental Study of Airflow Designs for Data Centers

Experimental Study of Airflow Designs for Data Centers Experimental Study of Airflow Designs for Data Centers Takashi Tsuchiya*, Yoshihide Suwa 2 and Ryozo Ooka 3 Technical Research Institute, Obayashi Corporation, M. Eng., Japan 2 Technical Research Institute,

More information

Open source software tools for powertrain optimisation

Open source software tools for powertrain optimisation Open source software tools for powertrain optimisation Paolo Geremia Eugene de Villiers TWO-DAY MEETING ON INTERNAL COMBUSTION ENGINE SIMULATIONS USING OPENFOAM TECHNOLOGY 11-12 July, 2011 info@engys.eu

More information

Server Room & Data Centre Energy Efficiency. Technology Paper 003

Server Room & Data Centre Energy Efficiency. Technology Paper 003 Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:

More information

Precision Cooling Mission Critical Air Handling Units

Precision Cooling Mission Critical Air Handling Units M I S S I O N C R I T I CA L C O O L I N G Precision Cooling Mission Critical Air Handling Units Global Expertise for Precision Cooling Solutions STULZ is a privately owned, global manufacturer of highly

More information

Simulation of Turbulent Flow over the Ahmed Body

Simulation of Turbulent Flow over the Ahmed Body Simulation of Turbulent Flow over the Ahmed Body 58:160 Intermediate Mechanics of Fluids CFD LAB 4 By Timur K. Dogan, Michael Conger, Maysam Mousaviraad, and Fred Stern IIHR-Hydroscience & Engineering

More information