Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Size: px
Start display at page:

Download "Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden"

Transcription

1 Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden

2 What is the greatest DC challenge you face?

3 Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell 1855 Blade Centers T1 CFM kw T2 100% of the power supplied to IT gears is transferred into heat

4 Air Flow to Heat Load Relation At sea level, heat is transferred to air according to; CFM = 3160 * kw / ΔT Server Inlet Fans Chips LOAD Outlet Where CFM = Cubic Feet per Minutes kw = Kilos Watts ΔT = T 2 - T 1 (ºF) T1 CFM kw T2 For ΔT = 36º F (ref. Dell) and 1kW load CFM = 3160 (1kW) / 36º F = 88 CFM

5 Servers OEM challenge Reducing energy consumption Older (3Y) Server, ΔT = 26 ºF consume 120CFM per kw of load Typical (Today) Server, ΔT = 32 ºF consume 100CFM per kw of load Energy Stars Server, ΔT = 39 ºF consume 80CFM per kw of load Smart > consumption = f(computing state)

6 Environmental guidelines ASHRAE Environmental guidelines for datacom equipment TC T 1 = ºC (68-77 ºF) % Relative Humidity 2009 T 1 = ºC ( ºF) % Relative Humidity

7 CRAC Data Center 101 Hot/Cold Aisles Concept CRAC = Computer Room Air Conditioning unit Raised floor tiles are typically 24 x 24 Solid tiles in hot aisles, graded/perforated tiles in cold aisles Rack = Cabinet = Enclosures 24 W x 42 D x 84 H (44RU) typical Average installed power density = 1.5>2kW/cabinet

8 Traditional Cold / Hot Aisle Supply air/cold side Return air/hot side deployment Substantial mixing of hot & cold air leads to hot spots Mixed air leads to low CRAC/CRAH return temperatures, decreasing cooling efficiency Floor tile gymnastics are required to attempt to handle or eliminate hot spots Environment must be micromanaged as adds, moves and changes move heat loads

9 Data Centers are environmentally unstable The enemies > Bypass air, Air flow Recirculation Uptime Institute Study (1) 19 data centers, 204,000 sq-ft of floor, 15,000 measurements On average 2.6 times more cooling is being delivered than is required by the IT equipment load 60% of the cool air that is generated by computer room air conditioning units is not getting to the intakes of the IT equipment but rather is short cycling back to the cooling unit 10% of the racks where still experiencing hot spots (intake temperature above 77 ºF) Hot spots at the IT Equipment intakes cause premature failure, active OEM warranty issues Cool air is exiting through perforated floor tiles and floor cable cut-outs and is returning to the cooling unit unused > Bypass Air Hot air is cycling back to the IT equipment intake > Air Flow Recirculation (1) White Paper Reducing bypass airflow is essential for eliminating computer room hot spots

10 Data Centers Challenges Power consumption density is increasing Peak Electrical Demand of 16 Houses 1 X 42RU Blade Server Rack = 84 x 24 x 42 Dell 1855 Blade Cente

11 Instability = Complexity IT equipment intake temperatures are compromised by high heat loads and recirculation of the exhaust heat Excessive cooling oversupply is the most common method to reduce IT equipment intake temperatures Delivering more air and at lower Hot Hot Cold Cold temperatures Aisle Aisle Aisle is inefficient and does Aisle not produce predictable CRAC results CFD modeling CRAC

12 Warnings from IT Equipment OEMs Dell on server thermal issues from hot air recirculation due to downstream pressure on server fans Reference: 7x24 Exchange Conference Boca Raton 2008, David Moss

13 Short Term Fix

14 Cooling Options 42u Cooling Fans 42u Cooling Mini Air Conditioner

15 Air flow management cold aisle containment

16 Cold Aisle Containment - Under floor air pressure balance is critical to achieve balanced cooling in all aisles - Oversupply of air to maintain under floor pressures leads to wasted fan energy - Not suitable for slab environments - Majority of white space is hot aisle leading to undesirable working conditions - Doors and ceiling of containment can lead to challenges in lighting and fire suppression

17 Let s build a Dc, hot aisle containment

18 Hot Aisle Containment - High containment aisle pressures lead to wrap around heating - Doors and ceiling of containment can lead to challenges in lighting and fire suppression - High containment aisle pressure force server fans to speed up, increasing fan speed energy and decreasing cooling efficiency

19 Cabinet Level Containment Passive and Active Cabinet (24 W x 84 H 44RU x 42 D), 12 KW per cabinet current. Capability to increase to 20KW. Solid rear door, rail seal kit, use of blanking panel on open RU. Side panels and separator panels between cabinets.

20 Cabinet Level Containment Support of high density applications Consistent server inlet temperatures Higher return temps=greater CRAC/H efficiency Reduced energy costs Unlock stranded cooling capacities

21 Facebook to Sweden

22 Adaptive Enclosure Heat Containment Physical separation of the hot and cold air, lower cooling cost by 30-50% Separation predictable airflow paths, Controlled/Stable environment Eliminates Bypass Air and Air Recirculation/Mixing Reduce or eliminate cool air oversupply (2.5 to <1.2) Elimination of hot spots, increase IT equipment availability Allows for high density deploy (up to 30KW/rack) without precision cooling Increase supply air temperature (8-10 degree) Increase return air temperature to CRAC (increase CRAC efficiency) Allow deploy of high density computing anywhere in the data center (increased flexibility) Build in environmental, air flow monitoring/alarming AC Rack Rack Rack Rack

23 Deploy discussion High Density clusters deploy

24 Deploy discussion Sharing containment between 2 or 3 cabinets Low-Medium Density on Racks without Divider Panels

25 AEHC Fully Managed, Intelligent system

26 Air Flow management containment no raised floor scenario hot air return duct ducted air supply no drop ceiling Create separation between cold and hot side Define path of return to CRAC units

27 Retrofit to existing

28 Heat Containment Forcing separation between cold and hot side 105 ºF 75 ºF

29 AEHC System Components AEHC Chimney, allows connection to drop ceiling Custom height project specific AEHC Fan Cartridge 2 per Chassis AEHC Chassis H x W x D inches Chassis Adaptor plate Belden AEHC can be retrofitted to third party enclosure Custom adaptor plate required AEHC Pressure sensor Enclosure rear AEHC Host/Controller Enclosure requirement Perforated front door Solid side panels or separator panels Solid rear door Unused Rack Unit must be blocked using blanking panels Rails sealing kit to be used Optimal for XUSD 42 deep or 48 enclosure

30 AEHC Host / Controller

31 Passive cabinet level containment 3-5Kw

32 Passive cabinet level containment 10 Kw

33 Active Containment Constant speed fans

34 AEHC ROI combine with Green

35 Questions???

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing

More information

A Green Approach. Thermal

A Green Approach. Thermal A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout

More information

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

Effectiveness and Implementation of Modular Containment in Existing Data Centers

Effectiveness and Implementation of Modular Containment in Existing Data Centers WHITE PAPER Effectiveness and Implementation of Modular Containment in Existing Data Centers By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. 505.798.0200 upsite.com

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy

Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Executive Summary Increasing power requirements for new servers have created the need to support

More information

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Variable Density, Closed-Loop, Water-Cooled Data Center Solution Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of

More information

Impact of Air Containment Systems

Impact of Air Containment Systems White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch

Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches Table of Contents

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.

More information

Cabinet Level Containment. IsoFlo Cabinet. Isolated Airfl ow Cabinet for Raised Floor Data Centers

Cabinet Level Containment. IsoFlo Cabinet. Isolated Airfl ow Cabinet for Raised Floor Data Centers Cabinet Level Containment IsoFlo Cabinet Isolated Airfl ow Cabinet for Raised Floor Data Centers IsoFlo Cabinet Cabinet Level Containment Tate s IsoFlo cabinet completely isolates the IT cooling from the

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

Data Center Airflow Management Basics: Comparing Containment Systems

Data Center Airflow Management Basics: Comparing Containment Systems WHITE PAPER Data Center Airflow Management Basics: Comparing Containment Systems Edited by David Knapp Product Marketing Manager Published: February 2017 US & Canada +1-800-834-4969 Toronto, Ontario, Canada

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER

A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER By David Moss Dell Data Center Infrastructure dell.com/hiddendatacenter Many people see an IT rack as a glorified shelving system.

More information

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace

More information

Air Containment Design Choices and Considerations

Air Containment Design Choices and Considerations Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

APC APPLICATION NOTE #74

APC APPLICATION NOTE #74 #74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.

More information

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation DC ASSESSMENT SERVICES AISLE CONTAINMENT AIRFLOW MANAGEMENT Achieving true 24/7/365 operation

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

1.866.TRY.GLCC WeRackYourWorld.com

1.866.TRY.GLCC WeRackYourWorld.com cool it. 1.866.TRY.GLCC WeRackYourWorld.com In order to maximize space in the data center and accommodate for increased data, rack-mount enclosures are becoming populated with high-density servers and

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase

More information

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

Close Coupled Cooling for Datacentres

Close Coupled Cooling for Datacentres Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

The Energy. David L. Moss Dell Data Center Infrastructure

The Energy. David L. Moss Dell Data Center Infrastructure The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square

More information

Improving Rack Cooling Performance Using Blanking Panels

Improving Rack Cooling Performance Using Blanking Panels Improving Rack Cooling Performance Using Blanking By Neil Rasmussen White Paper #44 Revision 1 Executive Summary Unused vertical space in open frame racks and rack enclosures creates an unrestricted recycling

More information

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic

More information

Green IT and Green DC

Green IT and Green DC Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental

More information

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data

More information

To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels

To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels The use of a hot aisle/cold aisle configuration in the data center has long been considered a best practice

More information

Airflow Management s Role in Data Center Cooling Capacity

Airflow Management s Role in Data Center Cooling Capacity Airflow Management s Role in Data Center Cooling Capacity By Larry Mainers, CEO Subzero Engineering 2014 Subzero Engineering SUMMARY Airflow management (AFM) is changing the way data centers cool the IT

More information

ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD

ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD R I T T A L T H E R M A L S E R I E S ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD FRIEDHELM L O H GROUP I. INTRODUCTION As a leading manufacturer of enclosure solutions, Rittal is frequently

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it

More information

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total

More information

Reverse Flow Cabinet. ContraFlo Cabinet. Reverse Flow Cabinet for Raised Floor Data Centers

Reverse Flow Cabinet. ContraFlo Cabinet. Reverse Flow Cabinet for Raised Floor Data Centers Reverse Flow Cabinet ContraFlo Cabinet Reverse Flow Cabinet for Raised Floor Data Centers ContraFlo TM Cabinet Reverse Flow Cabinet The ContraFlo cabinet turns airflow upside down to offer an alternative

More information

APC APPLICATION NOTE #146

APC APPLICATION NOTE #146 #146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating

More information

New Techniques for Energy-Efficient Data Center Cooling

New Techniques for Energy-Efficient Data Center Cooling New Techniques for Energy-Efficient Data Center Cooling Applications for Large and Small Data Centers By Wally Phelps Director of Engineering AdaptivCOOL www.adaptivcool.com Copyright Degree Controls,

More information

Energy Efficient Data Centers

Energy Efficient Data Centers IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an

More information

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42 Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing

More information

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,

More information

Cooling Case Studies

Cooling Case Studies Cooling Case Studies About Geist Geist designs and manufactures industry leading technology and software for powering, monitoring, cooling and managing critical data center infrastructure. We produce affordable,

More information

survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1.

survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1. :: In a recent Uptime Institute survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1. 2 Maintain Assess Control ROI Monitor Optimize The Need for a Better Approach

More information

HIGH DENSITY RACK COOLING CHOICES

HIGH DENSITY RACK COOLING CHOICES WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

How to Increase Data Center Efficiency

How to Increase Data Center Efficiency How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between

More information

FREEING HPC FROM THE DATACENTRE

FREEING HPC FROM THE DATACENTRE FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented

More information

Viable Options for Data Center Solutions. By Ning Liu Offering Group Panduit APJ

Viable Options for Data Center Solutions. By Ning Liu Offering Group Panduit APJ Viable Options for Data Center Solutions By Ning Liu Offering Group Panduit APJ Agenda Market Overview Data Center Challengers Business Drivers Data Center Standards Data Center Technologies Panduit Solutions

More information

Ten Cooling Solutions to Support High- Density Server Deployment

Ten Cooling Solutions to Support High- Density Server Deployment Ten Cooling Solutions to Support High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 2 Executive Summary High-density servers offer a significant performance per watt benefit. However,

More information

Data Centre Products. Airflow Management Solutions

Data Centre Products. Airflow Management Solutions Data Centre Products Airflow Management Solutions Computational Fluid Dynamics (CFD) model of an optimised data centre illustrating cold-aisle isolation and Eaton s Heat Containment System (HCS). See CFD

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

Design and Installation Challenges: Aisle Containment Systems

Design and Installation Challenges: Aisle Containment Systems Design and Installation Challenges: Aisle Containment Systems 1 We all know the Benefits of Containment 1. Reduces Total Cost of Data Center Ownership 2. Eliminates hot spots 3. Supports higher heat and

More information

Rethinking Datacenter Cooling

Rethinking Datacenter Cooling Rethinking Datacenter Cooling www.sempertec.com SemperTec White Paper Rethinking Datacenter Cooling Contents Executive Summary Introduction Air Distribution: Three Cooling Design Considerations Cold Aisle

More information

Optimizing Cooling Performance Of a Data Center

Optimizing Cooling Performance Of a Data Center ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Enabling Business Critical Continuity for Unified Communications. Andy Liu Product Manager, Asia Pacific

Enabling Business Critical Continuity for Unified Communications. Andy Liu Product Manager, Asia Pacific Enabling Business Critical Continuity for Unified Communications Andy Liu Product Manager, Asia Pacific Emerson Creating Technology and Solutions for a World in Action #1 AC & DC Power System #1 OEM Embedded

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies About Upsite Technologies Upsite Technologies, Inc., a pioneer, and industry thought leader specializing in data center airflow management, provides a full suite of products and services designed to enable

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

Running Your Data Center Under Ideal Temperature Conditions

Running Your Data Center Under Ideal Temperature Conditions TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient

More information

Google s Green Data Centers: Network POP Case Study

Google s Green Data Centers: Network POP Case Study Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Certified 1. AMCO Enclosures Containment Brochure. Hot/Cold Aisle Containment Solutions ACB3.0. Designed and Manufactured in the USA

Certified 1. AMCO Enclosures Containment Brochure. Hot/Cold Aisle Containment Solutions ACB3.0. Designed and Manufactured in the USA ACB3.0 Designed and Manufactured in the USA Hot/Cold Aisle Containment Solutions AMCO Enclosures Containment Brochure IMS Engineered Products is Certified 1 Aisle Containment Solutions AMCO Enclosures

More information

HP Modular Cooling System: water cooling technology for high-density server installations

HP Modular Cooling System: water cooling technology for high-density server installations HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased

More information

Temperature monitoring and CFD Analysis of Data Centre

Temperature monitoring and CFD Analysis of Data Centre Available online at www.sciencedirect.com Procedia Engineering 56 (2013 ) 551 559 5 th BSME International Conference on Thermal Engineering Temperature monitoring and CFD Analysis of Data Centre N.M.S.

More information

COOLING SOLUTIONS. SmartRack Close-Coupled Cooling for IT Environments

COOLING SOLUTIONS. SmartRack Close-Coupled Cooling for IT Environments COOLING SOLUTIONS SmartRack Close-Coupled Cooling for IT Environments Efficient, flexible, manageable cooling reduces costs and simplifies installation. Efficient, flexible, manageable cooling for IT environments

More information

Evolution of Facebook s data center design. Veerendra Mulay, PhD Strategic Engineering and Development

Evolution of Facebook s data center design. Veerendra Mulay, PhD Strategic Engineering and Development Evolution of Facebook s data center design Veerendra Mulay, PhD Strategic Engineering and Development Agenda 1 Introduction 2 Electrical design 3 Mechanical design 4 Design evolution 5 RDDC Introduction

More information

TMS-08. Thermal. Management Solutions

TMS-08. Thermal. Management Solutions TMS-08 Thermal Management Solutions Contents Section Page Introduction 1 Flexibility on Demand 2 The Cabinet 3 Configuring a Cabinet for Thermal Loads 4 19 Blanking Panels 8 Front to Rear Blanking Panels

More information

DATACOM CABINETS SOLUTION GUIDE

DATACOM CABINETS SOLUTION GUIDE DATACOM CABINETS SOLUTION GUIDE designed to be better. LEGRAND S CABINET OFFERING Legrand cabinets are designed with cable management, airflow management and effortless installation to meet all network

More information

MECHANICAL AND THERMAL CONSIDERATIONS FOR RACK DEPLOYMENT OF THE DELL POWEREDGE M-SERIES. One Dell Way Round Rock, Texas

MECHANICAL AND THERMAL CONSIDERATIONS FOR RACK DEPLOYMENT OF THE DELL POWEREDGE M-SERIES. One Dell Way Round Rock, Texas One Dell Way Round Rock, Texas 78682 www.dell.com DELL ENTERPRISE WHITEPAPER MECHANICAL AND THERMAL CONSIDERATIONS FOR RACK DEPLOYMENT OF THE DELL POWEREDGE M-SERIES Dominick Lovicott Enterprise Thermal

More information

» BEST PRACTICES FOR AIRFLOW MANAGEMENT AND COOLING OPTIMISATION IN THE DATA CENTRE

» BEST PRACTICES FOR AIRFLOW MANAGEMENT AND COOLING OPTIMISATION IN THE DATA CENTRE » BEST PRACTICES FOR AIRFLOW MANAGEMENT AND COOLING OPTIMISATION IN THE DATA CENTRE CoolControl Cold Aisle Containment Blanking Panels Hot Aisle Containment Network Switch Cooling Data Centre Optimisation

More information

Power & Cooling Considerations for Virtualized Environments

Power & Cooling Considerations for Virtualized Environments Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted

More information

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Data center solutions for successful companies Cooling solutions

Data center solutions for successful companies Cooling solutions Data center solutions for successful companies Cooling solutions WeRackYourWorld.com great lakes cooling solutions Power and cooling are of prime importance to anyone working in a data center. As information

More information

Switch to Perfection

Switch to Perfection Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of

More information

Application of TileFlow to Improve Cooling in a Data Center

Application of TileFlow to Improve Cooling in a Data Center Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

PERFORMANCE DATA SCD. SCD 12 in. x 12 in. Face Size. SCD 20 in. x 20 in. Face Size. Square Cone Diffuser

PERFORMANCE DATA SCD. SCD 12 in. x 12 in. Face Size. SCD 20 in. x 20 in. Face Size. Square Cone Diffuser 12 in. x 12 in. Face 4 Neck Velocity (fpm) 400 00 00 00 00 900 00 1200 1400 0 Velocity Pressure (in. w.g.)..01.022.031.040.00.02.090.122..013.021.030.041.04.0.04.121.1.21 Flow Rate (cfm) 3 44 2 1 0 4 122

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

Optimizing data centers for high-density computing

Optimizing data centers for high-density computing Optimizing data centers for high-density computing technology brief, 2nd edition Abstract... 2 Introduction... 2 Power consumption and heat load... 2 Power consumption... 2 Heat load... 5 The Need for

More information

Power Monitoring in the Data Centre

Power Monitoring in the Data Centre Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags

More information

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center

More information