1 Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden
2 What is the greatest DC challenge you face?
3 Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell 1855 Blade Centers T1 CFM kw T2 100% of the power supplied to IT gears is transferred into heat
4 Air Flow to Heat Load Relation At sea level, heat is transferred to air according to; CFM = 3160 * kw / ΔT Server Inlet Fans Chips LOAD Outlet Where CFM = Cubic Feet per Minutes kw = Kilos Watts ΔT = T 2 - T 1 (ºF) T1 CFM kw T2 For ΔT = 36º F (ref. Dell) and 1kW load CFM = 3160 (1kW) / 36º F = 88 CFM
5 Servers OEM challenge Reducing energy consumption Older (3Y) Server, ΔT = 26 ºF consume 120CFM per kw of load Typical (Today) Server, ΔT = 32 ºF consume 100CFM per kw of load Energy Stars Server, ΔT = 39 ºF consume 80CFM per kw of load Smart > consumption = f(computing state)
6 Environmental guidelines ASHRAE Environmental guidelines for datacom equipment TC T 1 = ºC (68-77 ºF) % Relative Humidity 2009 T 1 = ºC ( ºF) % Relative Humidity
7 CRAC Data Center 101 Hot/Cold Aisles Concept CRAC = Computer Room Air Conditioning unit Raised floor tiles are typically 24 x 24 Solid tiles in hot aisles, graded/perforated tiles in cold aisles Rack = Cabinet = Enclosures 24 W x 42 D x 84 H (44RU) typical Average installed power density = 1.5>2kW/cabinet
8 Traditional Cold / Hot Aisle Supply air/cold side Return air/hot side deployment Substantial mixing of hot & cold air leads to hot spots Mixed air leads to low CRAC/CRAH return temperatures, decreasing cooling efficiency Floor tile gymnastics are required to attempt to handle or eliminate hot spots Environment must be micromanaged as adds, moves and changes move heat loads
9 Data Centers are environmentally unstable The enemies > Bypass air, Air flow Recirculation Uptime Institute Study (1) 19 data centers, 204,000 sq-ft of floor, 15,000 measurements On average 2.6 times more cooling is being delivered than is required by the IT equipment load 60% of the cool air that is generated by computer room air conditioning units is not getting to the intakes of the IT equipment but rather is short cycling back to the cooling unit 10% of the racks where still experiencing hot spots (intake temperature above 77 ºF) Hot spots at the IT Equipment intakes cause premature failure, active OEM warranty issues Cool air is exiting through perforated floor tiles and floor cable cut-outs and is returning to the cooling unit unused > Bypass Air Hot air is cycling back to the IT equipment intake > Air Flow Recirculation (1) White Paper Reducing bypass airflow is essential for eliminating computer room hot spots
10 Data Centers Challenges Power consumption density is increasing Peak Electrical Demand of 16 Houses 1 X 42RU Blade Server Rack = 84 x 24 x 42 Dell 1855 Blade Cente
11 Instability = Complexity IT equipment intake temperatures are compromised by high heat loads and recirculation of the exhaust heat Excessive cooling oversupply is the most common method to reduce IT equipment intake temperatures Delivering more air and at lower Hot Hot Cold Cold temperatures Aisle Aisle Aisle is inefficient and does Aisle not produce predictable CRAC results CFD modeling CRAC
12 Warnings from IT Equipment OEMs Dell on server thermal issues from hot air recirculation due to downstream pressure on server fans Reference: 7x24 Exchange Conference Boca Raton 2008, David Moss
13 Short Term Fix
14 Cooling Options 42u Cooling Fans 42u Cooling Mini Air Conditioner
15 Air flow management cold aisle containment
16 Cold Aisle Containment - Under floor air pressure balance is critical to achieve balanced cooling in all aisles - Oversupply of air to maintain under floor pressures leads to wasted fan energy - Not suitable for slab environments - Majority of white space is hot aisle leading to undesirable working conditions - Doors and ceiling of containment can lead to challenges in lighting and fire suppression
17 Let s build a Dc, hot aisle containment
18 Hot Aisle Containment - High containment aisle pressures lead to wrap around heating - Doors and ceiling of containment can lead to challenges in lighting and fire suppression - High containment aisle pressure force server fans to speed up, increasing fan speed energy and decreasing cooling efficiency
19 Cabinet Level Containment Passive and Active Cabinet (24 W x 84 H 44RU x 42 D), 12 KW per cabinet current. Capability to increase to 20KW. Solid rear door, rail seal kit, use of blanking panel on open RU. Side panels and separator panels between cabinets.
20 Cabinet Level Containment Support of high density applications Consistent server inlet temperatures Higher return temps=greater CRAC/H efficiency Reduced energy costs Unlock stranded cooling capacities
21 Facebook to Sweden
22 Adaptive Enclosure Heat Containment Physical separation of the hot and cold air, lower cooling cost by 30-50% Separation predictable airflow paths, Controlled/Stable environment Eliminates Bypass Air and Air Recirculation/Mixing Reduce or eliminate cool air oversupply (2.5 to <1.2) Elimination of hot spots, increase IT equipment availability Allows for high density deploy (up to 30KW/rack) without precision cooling Increase supply air temperature (8-10 degree) Increase return air temperature to CRAC (increase CRAC efficiency) Allow deploy of high density computing anywhere in the data center (increased flexibility) Build in environmental, air flow monitoring/alarming AC Rack Rack Rack Rack
23 Deploy discussion High Density clusters deploy
24 Deploy discussion Sharing containment between 2 or 3 cabinets Low-Medium Density on Racks without Divider Panels
25 AEHC Fully Managed, Intelligent system
26 Air Flow management containment no raised floor scenario hot air return duct ducted air supply no drop ceiling Create separation between cold and hot side Define path of return to CRAC units
27 Retrofit to existing
28 Heat Containment Forcing separation between cold and hot side 105 ºF 75 ºF
29 AEHC System Components AEHC Chimney, allows connection to drop ceiling Custom height project specific AEHC Fan Cartridge 2 per Chassis AEHC Chassis H x W x D inches Chassis Adaptor plate Belden AEHC can be retrofitted to third party enclosure Custom adaptor plate required AEHC Pressure sensor Enclosure rear AEHC Host/Controller Enclosure requirement Perforated front door Solid side panels or separator panels Solid rear door Unused Rack Unit must be blocked using blanking panels Rails sealing kit to be used Optimal for XUSD 42 deep or 48 enclosure
30 AEHC Host / Controller
31 Passive cabinet level containment 3-5Kw
32 Passive cabinet level containment 10 Kw
33 Active Containment Constant speed fans
34 AEHC ROI combine with Green
35 Questions???
Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationReclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data
White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationData Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center
Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationHigh Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach
High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationEffectiveness and Implementation of Modular Containment in Existing Data Centers
WHITE PAPER Effectiveness and Implementation of Modular Containment in Existing Data Centers By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. 505.798.0200 upsite.com
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationRittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy
Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Executive Summary Increasing power requirements for new servers have created the need to support
More informationVariable Density, Closed-Loop, Water-Cooled Data Center Solution
Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationGreat Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch
Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches Table of Contents
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.
More informationCabinet Level Containment. IsoFlo Cabinet. Isolated Airfl ow Cabinet for Raised Floor Data Centers
Cabinet Level Containment IsoFlo Cabinet Isolated Airfl ow Cabinet for Raised Floor Data Centers IsoFlo Cabinet Cabinet Level Containment Tate s IsoFlo cabinet completely isolates the IT cooling from the
More informationFundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationData Center Airflow Management Basics: Comparing Containment Systems
WHITE PAPER Data Center Airflow Management Basics: Comparing Containment Systems Edited by David Knapp Product Marketing Manager Published: February 2017 US & Canada +1-800-834-4969 Toronto, Ontario, Canada
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationA LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER
A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER By David Moss Dell Data Center Infrastructure dell.com/hiddendatacenter Many people see an IT rack as a glorified shelving system.
More informationSurvey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered
Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace
More informationAir Containment Design Choices and Considerations
Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationHIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE
HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation DC ASSESSMENT SERVICES AISLE CONTAINMENT AIRFLOW MANAGEMENT Achieving true 24/7/365 operation
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More information1.866.TRY.GLCC WeRackYourWorld.com
cool it. 1.866.TRY.GLCC WeRackYourWorld.com In order to maximize space in the data center and accommodate for increased data, rack-mount enclosures are becoming populated with high-density servers and
More informationAvoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms
Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationThe Energy. David L. Moss Dell Data Center Infrastructure
The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square
More informationImproving Rack Cooling Performance Using Blanking Panels
Improving Rack Cooling Performance Using Blanking By Neil Rasmussen White Paper #44 Revision 1 Executive Summary Unused vertical space in open frame racks and rack enclosures creates an unrestricted recycling
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationA) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.
DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationOptimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering
Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data
More informationTo Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels
To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels The use of a hot aisle/cold aisle configuration in the data center has long been considered a best practice
More informationAirflow Management s Role in Data Center Cooling Capacity
Airflow Management s Role in Data Center Cooling Capacity By Larry Mainers, CEO Subzero Engineering 2014 Subzero Engineering SUMMARY Airflow management (AFM) is changing the way data centers cool the IT
More informationENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD
R I T T A L T H E R M A L S E R I E S ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD FRIEDHELM L O H GROUP I. INTRODUCTION As a leading manufacturer of enclosure solutions, Rittal is frequently
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More informationReverse Flow Cabinet. ContraFlo Cabinet. Reverse Flow Cabinet for Raised Floor Data Centers
Reverse Flow Cabinet ContraFlo Cabinet Reverse Flow Cabinet for Raised Floor Data Centers ContraFlo TM Cabinet Reverse Flow Cabinet The ContraFlo cabinet turns airflow upside down to offer an alternative
More informationAPC APPLICATION NOTE #146
#146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating
More informationNew Techniques for Energy-Efficient Data Center Cooling
New Techniques for Energy-Efficient Data Center Cooling Applications for Large and Small Data Centers By Wally Phelps Director of Engineering AdaptivCOOL www.adaptivcool.com Copyright Degree Controls,
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationTen Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42
Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing
More informationGreen Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex
Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,
More informationCooling Case Studies
Cooling Case Studies About Geist Geist designs and manufactures industry leading technology and software for powering, monitoring, cooling and managing critical data center infrastructure. We produce affordable,
More informationsurvey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1.
:: In a recent Uptime Institute survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1. 2 Maintain Assess Control ROI Monitor Optimize The Need for a Better Approach
More informationHIGH DENSITY RACK COOLING CHOICES
WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationHow to Increase Data Center Efficiency
How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between
More informationFREEING HPC FROM THE DATACENTRE
FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented
More informationViable Options for Data Center Solutions. By Ning Liu Offering Group Panduit APJ
Viable Options for Data Center Solutions By Ning Liu Offering Group Panduit APJ Agenda Market Overview Data Center Challengers Business Drivers Data Center Standards Data Center Technologies Panduit Solutions
More informationTen Cooling Solutions to Support High- Density Server Deployment
Ten Cooling Solutions to Support High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 2 Executive Summary High-density servers offer a significant performance per watt benefit. However,
More informationData Centre Products. Airflow Management Solutions
Data Centre Products Airflow Management Solutions Computational Fluid Dynamics (CFD) model of an optimised data centre illustrating cold-aisle isolation and Eaton s Heat Containment System (HCS). See CFD
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationDesign and Installation Challenges: Aisle Containment Systems
Design and Installation Challenges: Aisle Containment Systems 1 We all know the Benefits of Containment 1. Reduces Total Cost of Data Center Ownership 2. Eliminates hot spots 3. Supports higher heat and
More informationRethinking Datacenter Cooling
Rethinking Datacenter Cooling www.sempertec.com SemperTec White Paper Rethinking Datacenter Cooling Contents Executive Summary Introduction Air Distribution: Three Cooling Design Considerations Cold Aisle
More informationOptimizing Cooling Performance Of a Data Center
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More informationEnabling Business Critical Continuity for Unified Communications. Andy Liu Product Manager, Asia Pacific
Enabling Business Critical Continuity for Unified Communications Andy Liu Product Manager, Asia Pacific Emerson Creating Technology and Solutions for a World in Action #1 AC & DC Power System #1 OEM Embedded
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationThe Four 4R s. of Data Center Airflow Management. About Upsite Technologies
About Upsite Technologies Upsite Technologies, Inc., a pioneer, and industry thought leader specializing in data center airflow management, provides a full suite of products and services designed to enable
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationLiebert DCW CATALOGUE
Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers
More informationRunning Your Data Center Under Ideal Temperature Conditions
TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient
More informationGoogle s Green Data Centers: Network POP Case Study
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationCertified 1. AMCO Enclosures Containment Brochure. Hot/Cold Aisle Containment Solutions ACB3.0. Designed and Manufactured in the USA
ACB3.0 Designed and Manufactured in the USA Hot/Cold Aisle Containment Solutions AMCO Enclosures Containment Brochure IMS Engineered Products is Certified 1 Aisle Containment Solutions AMCO Enclosures
More informationHP Modular Cooling System: water cooling technology for high-density server installations
HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased
More informationTemperature monitoring and CFD Analysis of Data Centre
Available online at www.sciencedirect.com Procedia Engineering 56 (2013 ) 551 559 5 th BSME International Conference on Thermal Engineering Temperature monitoring and CFD Analysis of Data Centre N.M.S.
More informationCOOLING SOLUTIONS. SmartRack Close-Coupled Cooling for IT Environments
COOLING SOLUTIONS SmartRack Close-Coupled Cooling for IT Environments Efficient, flexible, manageable cooling reduces costs and simplifies installation. Efficient, flexible, manageable cooling for IT environments
More informationEvolution of Facebook s data center design. Veerendra Mulay, PhD Strategic Engineering and Development
Evolution of Facebook s data center design Veerendra Mulay, PhD Strategic Engineering and Development Agenda 1 Introduction 2 Electrical design 3 Mechanical design 4 Design evolution 5 RDDC Introduction
More informationTMS-08. Thermal. Management Solutions
TMS-08 Thermal Management Solutions Contents Section Page Introduction 1 Flexibility on Demand 2 The Cabinet 3 Configuring a Cabinet for Thermal Loads 4 19 Blanking Panels 8 Front to Rear Blanking Panels
More informationDATACOM CABINETS SOLUTION GUIDE
DATACOM CABINETS SOLUTION GUIDE designed to be better. LEGRAND S CABINET OFFERING Legrand cabinets are designed with cable management, airflow management and effortless installation to meet all network
More informationMECHANICAL AND THERMAL CONSIDERATIONS FOR RACK DEPLOYMENT OF THE DELL POWEREDGE M-SERIES. One Dell Way Round Rock, Texas
One Dell Way Round Rock, Texas 78682 www.dell.com DELL ENTERPRISE WHITEPAPER MECHANICAL AND THERMAL CONSIDERATIONS FOR RACK DEPLOYMENT OF THE DELL POWEREDGE M-SERIES Dominick Lovicott Enterprise Thermal
More information» BEST PRACTICES FOR AIRFLOW MANAGEMENT AND COOLING OPTIMISATION IN THE DATA CENTRE
» BEST PRACTICES FOR AIRFLOW MANAGEMENT AND COOLING OPTIMISATION IN THE DATA CENTRE CoolControl Cold Aisle Containment Blanking Panels Hot Aisle Containment Network Switch Cooling Data Centre Optimisation
More informationPower & Cooling Considerations for Virtualized Environments
Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationData center solutions for successful companies Cooling solutions
Data center solutions for successful companies Cooling solutions WeRackYourWorld.com great lakes cooling solutions Power and cooling are of prime importance to anyone working in a data center. As information
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationApplication of TileFlow to Improve Cooling in a Data Center
Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More informationPERFORMANCE DATA SCD. SCD 12 in. x 12 in. Face Size. SCD 20 in. x 20 in. Face Size. Square Cone Diffuser
12 in. x 12 in. Face 4 Neck Velocity (fpm) 400 00 00 00 00 900 00 1200 1400 0 Velocity Pressure (in. w.g.)..01.022.031.040.00.02.090.122..013.021.030.041.04.0.04.121.1.21 Flow Rate (cfm) 3 44 2 1 0 4 122
More informationTotal Modular Data Centre Solutions
Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system
More informationOptimizing data centers for high-density computing
Optimizing data centers for high-density computing technology brief, 2nd edition Abstract... 2 Introduction... 2 Power consumption and heat load... 2 Power consumption... 2 Heat load... 5 The Need for
More informationPower Monitoring in the Data Centre
Power Monitoring in the Data Centre Fixed or Wireless Steve Strange RCDD ANIXTER INTERNATIONAL Agenda Energy Consumption Case Study Reasons to Monitor Power Monitoring Environmental Monitoring Asset Tags
More informationNREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions
NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center
More information