1 _A_EN_1609 INSTALLATION AND OPERATION MANUAL ProtoCessor FPC-ED2 and ProtoCessor FPC-ED4 Nortec LINKS Humidification and Evaporative Cooling

2 For Interfacing Nortec Products: NH-EL, GS, EL, RS To Building Automation Systems: BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks Document Revision: 2.H Web Configurator Template Revision: 60 Technical Support Thank you for purchasing the ProtoCessor for Nortec. Please call Nortec for Technical support of the ProtoCessor product. Sierra Monitor Corporation does not provide direct support. If Nortec needs to escalate the concern, they will contact Sierra Monitor Corporation for assistance. Support Contact Information: U.S.A. Nortec Humidity Inc th Street Sturtevant, WI USA Canada Nortec Humidity Ltd Fenton Rd Ottawa, Ontario K1T 3T7 Nortec Service: NORTEC1 Fax: Website: APPLICABILITY & EFFECTIVITY Explains ProtoCessor FPC-ED2 hardware and how to install it. The instructions are effective for the above as of July 2016.

3 INSTALLATION AND OPERATION MANUAL Nortec LINKS ProtoCessor FPC-ED2 and ProtoCessor FPC-ED _A_EN_1609

4 Thank you for choosing Nortec Installation date (DD/MM/YYYY): Commissioning date (DD/MM/YYYY): Site: Model: Serial number: Manufacturer Nortec Humidity Ltd Fenton Road, Ottawa, ON, Canada K1T 3T7 Tel NORTEC1, Fax Proprietary Notice This document and the information disclosed herein are proprietary data of Nortec Humidity Ltd. Neither this document, nor the information contained herein shall be reproduced, used, or disclosed to others without the written authorization of Nortec Humidity Ltd., except to the extent required for installation, operation or maintenance of the customer's equipment. Liability Notice Nortec Humidity Ltd. does not accept any liability due to incorrect installation, maintenance or operation of the equipment, or due to the use of parts/components/equipment that are not authorized by Nortec Humidity Ltd. Copyright Notice Copyright 2016, Nortec Humidity Ltd, All rights reserved. Technical modification rights reserved.

5 Contents 1 Quick Start Guide Certifications Introduction ProtoCessor Gateway Setup for ProtoCessor Record Identification Data Point Count Capacity and Registers per Device Configuring Device Communications Input COM Settings for Device with an Inserted ProtoCessor Set Modbus RTU Node-ID for the Device Interfacing ProtoCessor to Device ProtoCessor FPC-ED2 and FPC-ED4 Mounted onto Board ProtoCessor FPC-ED2 and FPC-ED4 Showing Connection Ports BACnet MS/TP or Metasys N2: Wiring Field Port to RS-485 Network LonWorks (FPC-ED4): Wiring Field Port to LonWorks Network Use ProtoCessor Web Configurator to Setup the Gateway Connect the PC to ProtoCessor via the Ethernet Port Connecting to ProtoCessor Web Configurator Selecting Profiles for Device Connected to ProtoCessor BACnet/IP Setting IP Address for Field Network Select Field Protocol BACnet MS/TP Configuration BACnet/IP Configuration Metasys N2 Configuration BACnet MS/TP and BACnet/IP: Setting Node_Offset to Assign Specific Device Instances How to Start the Installation Over: Clearing Profiles LonWorks (FPC-ED4): Commissioning ProtoCessor on a lonworks Network Commissioning ProtoCessor FPC-ED4 on a LonWorks Network Instructions to Download XIF File from ProtoCessor FPC-ED4 Using Browser...28 A Troubleshooting... i A.1 Lost or Incorrect IP Address... i A.2 Viewing Diagnostic information... ii A.3 Check Wiring and Settings... ii A.4 LED Diagnostics for Communications Between ProtoCessor and Device... iii A.5 Take Diagnostic Capture With the FieldServer Utilities... iv Nortec LINKS _A_EN I V

6 A.6 Update Firmware... vii A.7 BACnet: Setting Network_Number for more than one ProtoCessor on Subnet... vii A.8 Securing the ProtoCessor with Passwords... viii B Vendor Information - Nortec... viii B.1 NHEL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks... viii B.2 GS Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks... ix B.3 EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks... x B.4 EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks... xi C Reference... xiii C.1 Specifications... xiii C.2 Compliance with UL Regulations... xiii VI _A_EN_1609 Nortec LINKS

7 1 Quick Start Guide 1. Record the information about the unit. (Section 4.1) 2. Set the device s Modbus RTU serial settings (i.e. baud rate, parity, stop bits) and Modbus Node-ID s for the device that will be connected to ProtoCessor FPC-ED2 or FPC-ED4. (Section 4.3) 3. Metasys N2 (FPC-ED2): Set the Node-ID. (Section 4.3.2) 4. BACnet MS/TP or BACnet/IP: Set the BACnet Device Instance. (Section 7) 5. Connect ProtoCessor FPC-ED2 s 3 pin RS-485 port to the Field Protocol cabling, (Section 5.3) or connect ProtoCessor FPC-ED4 s 2 pin LonWorks port to the Field Protocol cabling. (Section 5.4) 6. Use a browser to access the ProtoCessor s embedded tool, which is referred to in this manual as the Web Configurator, to select the device that will be attached to ProtoCessor and set the Modbus Node-ID. Once the device is selected, the ProtoCessor Automatically builds and loads the Configuration. (Section 6) 7. BACnet/IP (FPC-ED2): Use a browser to access the ProtoCessor Web Configurator to change the IP Address. No changes to the configuration are necessary. (Section 6.4) 8. LonWorks (FPC-ED4): The ProtoCessor must be commissioned on the LonWorks Network. This needs to be done by the LonWorks administrator using a LonWorks Commissioning tool. (Section 9) Nortec LINKS _A_EN_1609 I 7

8 2 Certifications BTL MARK BACNET TESTING LABORATORY The BTL Mark on ProtoCessor is a symbol that indicates that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing. The mark is a symbol of a highquality BACnet product. Go to for more information about the BACnet Testing Laboratory. Click here for BACnet PIC Statement. LONMARK CERTIFICATION LonMark International is the recognized authority for certification, education, and promotion of interoperability standards for the benefit of manufacturers, integrators and end users. LonMark International has developed extensive product certification standards and tests to provide the integrator and user with confidence that products from multiple manufacturers utilizing LonMark devices work together. Sierra Monitor has more LonMark Certified gateways than any other gateway manufacturer, including the ProtoCessor, ProtoCarrier and ProtoCessor for OEM applications and the full featured, configurable gateways _A_EN_1609 Nortec LINKS

9 3 Introduction 3.1 ProtoCessor Gateway ProtoCessor is an external, high performance Building Automation multi-protocol gateway that is preconfigured to automatically communicate between Nortec s products (hereafter called device ) connected to the ProtoCessor and automatically configures them for BACnet 1 MS/TP, BACnet/IP, Metasys 2 N2 by JCI or LonWorks 3. It is not necessary to download any configuration files to support the required applications. The ProtoCessor is pre-loaded with tested Profiles/Configurations for the supported devices. 1 BACnet is a registered trademark of ASHRAE 2 Metasys is a registered trademark of Johnson Controls Inc. 3 LonWorks is a registered trademark of Echelon Corporation Nortec LINKS _A_EN_1609 I 9

10 4 Setup for ProtoCessor 4.1 Record Identification Data Each ProtoCessor has a unique part number located on the side or the back of the unit. This number should be recorded, as it may be required for technical support. The numbers are as follows: Table 1: ProtoCessor Part Numbers Model ProtoCessor FPC-ED2 ProtoCessor FPC-ED4 Part Number FPC-ED FPC-ED FPC-ED2 units have the following 2 ports: RS Ethernet FPC-ED4 units have the following 2 ports: LonWorks + Ethernet 4.2 Point Count Capacity and Registers per Device The total number of Registers presented by the device attached to the ProtoCessor cannot exceed: Table 2: Supported Point Count Capacity Part Number Total Registers FPC-ED FPC-ED Table 3: Registers per Device Devices Registers per Device NHEL 35 GS 22 EL 35 RS Configuring Device Communications Input COM Settings for Device with an Inserted ProtoCessor Set the serial device that the ProtoCessor is plugged into to have the same Baud Rate, Data Bits, Stop Bits, and Parity settings as the ProtoCessor. Table 4: COM Settings specifies the device serial port settings required to communicate with the ProtoCessor _A_EN_1609 Nortec LINKS

11 Table 4: COM Settings Serial Port Setting Device Protocol 35 Baud Rate 9600 Parity Even Data Bits 8 Stop Bits Set Modbus RTU Node-ID for the Device Set Modbus Node-ID for the device the ProtoCessor is plugged into. (See Section 6.5 to input Node-ID) The Modbus Node-ID needs to be uniquely assigned between 1 and 255. o The Modbus Node-ID that is assigned for the device needs to be documented The Modbus Node-ID assigned is used for designating the Device Instance for BACnet/IP and BACnet MS/TP The Metasys N2 and Modbus TCP/IP field protocol Node-IDs are automatically set to be the same value as the Node-ID of the Modbus RTU device. Nortec LINKS _A_EN_1609 I 11

12 5 Interfacing ProtoCessor to Device 5.1 ProtoCessor FPC-ED2 and FPC-ED4 Mounted onto Board Figure 1: Mounted ProtoCessor BACnet FPC-ED2 (upper) and ProtoCessor FPC-ED4 (lower) _A_EN_1609 Nortec LINKS

13 5.2 ProtoCessor FPC-ED2 and FPC-ED4 Showing Connection Ports Figure 2: ProtoCessor FPC-ED2 (upper) and ProtoCessor FPC-ED4 (lower) Nortec LINKS _A_EN_1609 I 13

14 + 5.3 BACnet MS/TP or Metasys N2: Wiring Field Port to RS-485 Network Connect the BACnet MS/TP or Metasys N2 RS-485 network wires to the 3-pin RS-485 connector on ProtoCessor ED2 as shown below in Figure 3. o The RS-485 GND (Pin 3) is not typically connected See Section 7 for information on connecting to BACnet/IP network. If the ProtoCessor is the last device on the BACnet MS/TP or Metasys N2 trunk, then the End-Of-Line Termination Switch needs to be enabled (Figure 4). o o The default setting from the factory is OFF (switch position = right side) To enable the EOL Termination, turn the EOL switch ON (switch position = left side) BMS RS-485 Wiring ProtoCessor Pin # Pin Assignment RS Pin 1 RS RS Pin 2 RS Pin 3 RS-485 GND Figure 3: Connection from ProtoCessor to RS-485 Field Network End-of-Line Switch Figure 4: RS-485 BMS Network EOL Switch 5.4 LonWorks (FPC-ED4): Wiring Field Port to LonWorks Network Connect ProtoCessor to the field network with the LonWorks terminal using approved cable per the FT-10 installation guidelines. LonWorks has no polarity. Figure 5: LonWorks Terminal Connector _A_EN_1609 Nortec LINKS

15 6 Use ProtoCessor Web Configurator to Setup the Gateway 6.1 Connect the PC to ProtoCessor via the Ethernet Port Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the local PC and ProtoCessor. The Default IP Address of ProtoCessor is , Subnet Mask is If the PC and ProtoCessor are on different IP Networks, assign a static IP Address to the PC on the xxx network. For Windows XP: Go to > > Right-click on Local Area Connection > Properties Highlight > For Windows 7: Go to > > > > Right-click on Local Area Connection > Properties Highlight > For Windows XP and Windows 7, use the following IP Address: Click twice. Nortec LINKS _A_EN_1609 I 15

16 6.2 Connecting to ProtoCessor Web Configurator After setting a local PC on the same subnet as the ProtoCessor (Section 6.1), open a web browser on the PC and enter the IP Address of the ProtoCessor; the default address is NOTE: If the IP Address of the ProtoCessor has been changed by previous configuration, the assigned IP Address must be gathered from the network administrator. 6.3 Selecting Profiles for Device Connected to ProtoCessor In the Web Configurator, the Active Profiles section is shown on the lower left side of the screen. The Active Profiles section lists the currently active device profiles, including previous Web Configurator additions. This list will be empty for new installations, or after clearing all configurations. ( Figure 6) To add an active profile to support a device, click the ADD button under Active Profiles. This will present a drop-down box underneath the Current Profile column that lists all the available profiles. ( Figure 7) For every device that is added, assign a unique Modbus Node-ID. This specification must match the device s network settings _A_EN_1609 Nortec LINKS

17 Figure 6: Web Configurator Showing no Active Profiles Once the Profile for the device has been selected from the drop-down list, enter the value of the device s Modbus Node-ID which was assigned in Section Nortec LINKS _A_EN_1609 I 17

18 Figure 7: Web Configurator Showing Available Profiles for Selection Then press the Submit button to add the Profile as a device to be configured. Completed additions will be listed under Active Profiles as shown in Figure _A_EN_1609 Nortec LINKS

19 Figure 8: Web Configurator Showing Active Profile Additions 6.4 BACnet/IP Setting IP Address for Field Network After setting a local PC to the same subnet as the ProtoCessor (Section 6.1), open a web browser on the PC and enter the IP Address of the ProtoCessor; the default address is The Web Configurator is displayed as the landing page. (Figure 9) To access the Web GUI, click on the Diagnostics & Debugging button in the bottom right side of the page. Nortec LINKS _A_EN_1609 I 19

20 Figure 9: Web Configurator Screen From the Web GUI landing page, click on Setup to expand the navigation tree and then select Network Settings to access the IP Settings menu. (Figure 10) _A_EN_1609 Nortec LINKS

21 Figure 10: Changing IP Address via Web GUI Modify the IP Address (N1 IP Address field) of the ProtoCessor Ethernet port. If necessary, change the Netmask (N1 Netmask field). Type in a new Subnet Mask. If necessary, change the IP Gateway (Default Gateway field). Type in a new IP Gateway. NOTE: If the ProtoCessor is connected to a router, the IP Gateway of the ProtoCessor should be set to the IP Address of that router. Reset ProtoCessor. Unplug Ethernet cable from PC and connect it to the network hub or router. Record the IP Address assigned to the ProtoCessor for future reference. Nortec LINKS _A_EN_1609 I 21

22 6.5 Select Field Protocol For ED2 Use the Protocol Selector by typing in the corresponding number next to the desired protocol: o BACnet MS/TP 1 o BACnet/IP 2 o Metasys N2 3 Then click System Restart to bring up options to configure the desired protocol. For ED4 There are no device details to be entered for this protocol combination BACnet MS/TP Configuration Enter the appropriate details for BACnet MS/TP ( Figure 11): _A_EN_1609 Nortec LINKS

23 Figure 11: Web Configurator Showing BACnet MS/TP Configuration BACnet/IP Configuration Enter the appropriate details for BACnet/IP (Figure 12): Nortec LINKS _A_EN_1609 I 23

24 Figure 12: Web Configurator Showing BACnet/IP Configuration Metasys N2 Configuration Enter the appropriate details for Metasys N2 (Figure 13): _A_EN_1609 Nortec LINKS

25 Figure 13: Web Configurator Showing Metasys N2 Configuration Nortec LINKS _A_EN_1609 I 25

26 7 BACnet MS/TP and BACnet/IP: Setting Node_Offset to Assign Specific Device Instances After setting a local PC to the same subnet as the ProtoNode (Section 6.1), open a web browser on the PC and enter the IP Address of the ProtoNode; the default address is o The Web Configurator will be displayed as the landing page. ( o o Figure 11 or Figure 12) The Node_Offset field shows the current value (default = 50,000). o The values allowed for a BACnet Device Instance can range from 1 to 4,194,303. To assign a specific Device Instance (or range), change the Node_Offset value accordingly. o Given that: Node_Offset + Modbus Node_ID = Device Instance o Then: Node_Offset (required) = Device Instance (desired) Modbus Node_ID For example, if the desired Device Instance for the device is 1,001: o Device has a Modbus Node-ID of 1 o Node_Offset (required) = 1,001 (Modbus Node_ID) = 1,001 1 = 1,000 NOTE: The Node_Offset value will be applied to the device. o Device Instance will then be = 1,000 + Modbus Node_ID = 1, = 1,001 Click Submit once the desired value is entered. Figure 14: Active Profiles with Node-ID _A_EN_1609 Nortec LINKS

27 8 How to Start the Installation Over: Clearing Profiles After setting a local PC to the same subnet as the ProtoCessor (Section 6.1), open a web browser on the PC and enter the IP Address of the ProtoCessor; the default address is If the IP Address of the ProtoCessor has been changed by previous configuration, the assigned IP Address must be gathered from the network administrator. The Web Configurator is displayed as the landing page. At the bottom-left of the page, click the Clear Profiles and Restart button. Once restart is complete, all past profiles discovered and/or added via Web configurator are deleted. The unit can now be reinstalled. Nortec LINKS _A_EN_1609 I 27

28 9 LonWorks (FPC-ED4): Commissioning ProtoCessor on a lonworks Network Note: Commissioning may only be performed by the LonWorks administrator 9.1 Commissioning ProtoCessor FPC-ED4 on a LonWorks Network The User will be prompted by the LonWorks Administrator to hit the Service Pin on the ProtoCessor FPC-ED4 at the correct step of the Commissioning process which is different for each LonWorks Network Management Tool. If an XIF file is required, see steps in Section to generate XIF. Figure 15: LonWorks Service Pin Location Instructions to Download XIF File from ProtoCessor FPC-ED4 Using Browser Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and ProtoCessor. The Default IP Address of ProtoCessor is , Subnet Mask is If the PC and ProtoCessor are on different IP Networks, assign a static IP Address to the PC on the xxx network. For Windows XP: Go to > > Right-click on Local Area Connection > Properties Highlight > _A_EN_1609 Nortec LINKS

29 For Windows 7 or later: Go to > > > > Right-click on Local Area Connection > Properties Highlight > For Windows XP and Windows 7, use the following IP Address: Click twice. Open a web browser and go to the following address: [IP Address of ProtoCessor]/fserver.xif Example: /fserver.xif If the web browser prompts to save the file, save the file onto the PC. If the web browser displays the xif file as a web page, save the file onto the local PC as fserver.xif. Figure 16: Sample of Fserver.XIF File Generated Nortec LINKS _A_EN_1609 I 29

30 This page intentionally left blank _A_EN_1609 Nortec LINKS

31 A TROUBLESHOOTING A.1 Lost or Incorrect IP Address Ensure that FieldServer Toolbox is loaded onto the local PC. If not, download FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care- Resource Center, Software Downloads: Extract the executable file and complete the installation. Ethernet Port Figure 17: Ethernet Port Location Disable any wireless Ethernet adapters on the PC/Laptop. Disable firewall and virus protection software if possible. Connect a standard CAT5 Ethernet cable between the PC and ProtoCessor. Double click on the FS Toolbox Utility. Check IP Addresses from the Device listings. Nortec LINKS _A_EN_1609 Appendix I i

32 Correct IP Address(es) by right clicking the settings icon Address. and changing the IP A.2 Viewing Diagnostic information Type the IP Address of the ProtoCessor into the web browser or use the FieldServer Toolbox to connect to the ProtoCessor. Click on Diagnostics and Debugging Button, then click on view, and then on connections. If there are any errors showing on the Connection page, please refer to A.3 for the relevant wiring and settings. Figure 18: Error messages screen A.3 Check Wiring and Settings No COMS on Modbus RTU side. If the Tx/Rx LEDs are not flashing rapidly then there is a COM issue. To fix, check the following: o o Visual observations of LEDs on ProtoCessor (A.4) Check baud rate, parity, data bits, stop bits ii Appendix _A_EN_1609 Nortec LINKS

33 o Check device address o Verify wiring Field COM problems: o Visual observations of LEDs on ProtoCessor (A.4) o Check dipswitch settings (using correct baud rate and device instance) o Verify IP Address setting o Verify wiring NOTE: If the problem persists, a Diagnostic Capture needs to be taken and sent to support. (A.5) A.4 LED Diagnostics for Communications Between ProtoCessor and Device Please see the diagram below for ProtoCessor FPC-ED2 (left) and FPC-ED4 (right) LED Locations. Figure 19: Diagnostic LEDs Nortec LINKS _A_EN_1609 Appendix I iii

34 Table 5 :Diagnostic LEDs Tag Run Sys/Config Error Node Offline RX TX PWR Description The Run LED will start flashing 20 seconds after power indicating normal operation. The Heat Beat LED has the same functionality but flashes more rapidly. The Sys/Config Error LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will indicate there is a system error on ProtoCessor. If this occurs, immediately report the related system error shown in the error screen of the GUI interface to Sierra Monitor Corporation for evaluation. The Node Offline LED will turn on and stay solid if there is no communication with the device. The RX LED will flash when a message is received on the field port. The TX LED will flash when a message is sent on the field port. This is the power light and should show steady green at all times when ProtoCessor is powered. A.5 Take Diagnostic Capture With the FieldServer Utilities Once the Diagnostic Capture is complete, it to Nortec@Humidity.com. The Diagnostic Capture will accelerate diagnosis of the problem. Ensure that FieldServer Toolbox is Loaded on the PC that is currently being used, or download FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care: Resource Center, Software Downloads: Extract the executable file and complete the installation. Ethernet Port Figure 20: Ethernet Port Location Disable any wireless Ethernet adapters on the PC/Laptop. Disable firewall and virus protection software if possible. Connect a standard CAT5 Ethernet cable between the PC and ProtoCessor. Double click on the FS Toolbox Utility. iv Appendix _A_EN_1609 Nortec LINKS

35 Step 1: Take a Log o Click on the diagnose icon of the desired device o Select Full Diagnostic" NOTE: If desired, the default capture period can be changed o Click on Start Diagnostic Nortec LINKS _A_EN_1609 Appendix I v

36 o When the capture period is finished, the Diagnostic Test Complete window will appear Step 2: Send Log o Once the diagnostic test is complete, a.zip file will be saved on the PC o o Click Open to launch explorer and have it point directly at the correct folder, then the diagnostic zip file to Nortec@Humidity.com vi Appendix _A_EN_1609 Nortec LINKS

37 A.6 Update Firmware To load a new version of the firmware, follow these instructions: 1. Extract and save the new file onto the local PC. 2. Open a web browser and type the IP Address of the FieldServer in the address bar. NOTE: Default IP Address is NOTE: Use the FS Toolbox utility if you do not know the IP Address (A.1) 3. Click on the Diagnostics & Debugging button. 4. In the Navigation Tree on the left hand side, do the following: a. Click on Setup b. Click on File Transfer c. Click on the Firmware tab 5. In the Firmware tab, click on Choose Files and select the firmware file extracted in step Click on the orange Submit button. 7. When the download is complete, click on the System Restart button. A.7 BACnet: Setting Network_Number for more than one ProtoCessor on Subnet For both BACnet MS/TP and BACnet/IP, if more than one ProtoCessor is connected to the same subnet, they must be assigned unique Network_Number values. On the main Web Configuration screen, update the Network Number with the network_nr field and click submit. The default value is 50. Figure 21: Configuration Parameters Setting Network Number for BACnet Nortec LINKS _A_EN_1609 Appendix I vii

38 A.8 Securing the ProtoCessor with Passwords Access to the ProtoCessor can be restricted by enabling a password. There are 2 access levels defined by 2 account names: Admin and User. The Admin account has unrestricted access to the ProtoCessor. The User account can view any ProtoCessor information, but cannot make any changes or restart the ProtoCessor. The password needs to be a minimum of eight characters and is case sensitive. If the password is lost, click cancel on the password authentication popup window, and the password recovery token to Nortec@Humidity.com to receive a temporary password from the support team. Access the ProtoCessor to set a new password. B VENDOR INFORMATION - NORTEC B.1 NHEL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet Object Type BACnet Object ID 2Data Type N2 Address LonWorks Name LonWorks nvostatus AV 1 AO 1 nvostatus_xxx nvisigsource AV 2 AO 2 nvictrlmode AV 3 AO 3 nvi/nvosigsource_x XX nvi/nvoctrlmode_xx X nvictrlchannel AV 4 AO 4 nvi/nvoctrlch_xxx nvibmstimeout AV 5 AO 5 nvi/nvobmstmeout_ XXX nvohouropt_a AV 6 AO 6 nvohropt_a_xxx nvohourweight_a AV 7 AO 7 nvohrwght_a_xxx SNVT SNVT_lev_per SNVT_lev_per SNVT_lev_per SNVT_lev_per SNVT_time_se c SNVT_time_ho ur SNVT_time_ho ur nvorhdem_a1 AV 8 AO 8 nvorhdem_a1_xxx SNVT_lev_per nvorhdem_a2 AV 9 AO 9 nvorhdem_a2_xxx SNVT_lev_per nvosysdem_a AV 10 AO 10 nvosysdem_a_xxx SNVT_lev_per nvimancapacity_a AV 11 AO 11 nvisetpoint_a1 AV 12 AO 12 nvisetpoint_a2 AV 13 AO 13 nvidrhdem_a1 AV 14 AO 14 nvidrhdem_a2 AV 15 AO 15 nvohouropt_b AV 16 AO 16 nvohropt_b_xxx nvi/nvomancap_a_x XX SNVT_lev_per nvi/nvosetpnt_a1_x SNVT_lev_per XX nvi/nvosetpnt_a2_x SNVT_lev_per XX nvi/nvodrhdem_a1 SNVT_lev_per _XXX nvi/nvodrhdem_a2 SNVT_lev_per _XXX SNVT_time_ho ur viii Appendix _A_EN_1609 Nortec LINKS

39 nvohourweight_b AV 17 AO 17 nvohrwght_b_xxx SNVT_time_ho ur nvorhdem_b1 AV 18 AO 18 nvorhdem_b1_xxx SNVT_lev_per nvorhdem_b2 AV 19 AO 19 nvorhdem_b2_xxx SNVT_lev_per nvosysdem_b AV 20 AO 20 nvosysdem_b_xxx SNVT_lev_per nvimancapacity_b AV 21 AO 21 nvi/nvomancap_b_x SNVT_lev_per XX nvisetpoint_b1 AV 22 AO 22 nvi/nvosetpnt_b1_x SNVT_lev_per XX nvisetpoint_b2 AV 23 AO 23 nvi/nvosetpnt_b2_x SNVT_lev_per XX nvidrhdem_b1 AV 24 AO 24 nvi/nvodrhdem_b1 SNVT_lev_per _XXX nvidrhdem_b2 AV 25 AO 25 nvi/nvodrhdem_b2 SNVT_lev_per _XXX nvoconnection BV 1 DO 1 nvoconnectn_xxx SNVT_switch nvoservice BV 2 DO 2 nvoservice_xxx SNVT_switch nvofault BV 3 DO 3 nvofault_xxx SNVT_switch nvidisable BV 4 DO 4 nvi/nvodisable_xxx SNVT_switch nvosecurity_a BV 5 DO 5 nvosecurty_a_xxx SNVT_switch nvobloweract_a BV 6 DO 6 nvoblwract_a_xxx SNVT_switch nvofanact_a BV 7 DO 7 nvofanact_a_xxx SNVT_switch nvosecurity_b BV 8 DO 8 nvosecurty_b_xxx SNVT_switch nvobloweract_b BV 9 DO 9 nvoblwract_b_xxx SNVT_switch nvofanact_b BV 10 DO 10 nvofanact_b_xxx SNVT_switch B.2 GS Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet Object Type BACnet Object ID N2 Data Type N2 Address LonWorks Name LonWorks nvostatus AV 1 AO 1 nvostatus_xxx nvisigsource AV 2 AO 2 nvictrlmode AV 3 AO 3 nvi/nvosigsource_x XX nvi/nvoctrlmode_xx X nvictrlchannel AV 4 AO 4 nvi/nvoctrlch_xxx nvibmstimeout AV 5 AO 5 nvi/nvobmstmeout_ XXX nvohouropt_a AV 6 AO 6 nvohropt_a_xxx nvohourweight_a AV 7 AO 7 nvohrwght_a_xxx SNVT SNVT_lev_per SNVT_lev_per SNVT_lev_per SNVT_lev_per SNVT_time_se c SNVT_time_ho ur SNVT_time_ho ur nvorhdem_a1 AV 8 AO 8 nvorhdem_a1_xxx SNVT_lev_per nvorhdem_a2 AV 9 AO 9 nvorhdem_a2_xxx SNVT_lev_per nvosysdem_a AV 10 AO 10 nvosysdem_a_xxx SNVT_lev_per nvimancapacity_a AV 11 AO 11 nvi/nvomancap_a_x SNVT_lev_per Nortec LINKS _A_EN_1609 Appendix I ix

40 XX nvisetpoint_a1 AV 12 AO 12 nvi/nvosetpnt_a1_x SNVT_lev_per XX nvisetpoint_a2 AV 13 AO 13 nvi/nvosetpnt_a2_x SNVT_lev_per XX nvidrhdem_a1 AV 14 AO 14 nvi/nvodrhdem_a1 SNVT_lev_per _XXX nvidrhdem_a2 AV 15 AO 15 nvi/nvodrhdem_a2 SNVT_lev_per _XXX nvoservinterval_a AV 16 AO 16 nvosrvintv_a_xxx SNVT_lev_per nvodaysservice_a AV 17 AO 17 nvodaysrvc_a_xxx SNVT_count_f nvoconnection BV 18 DO 18 nvoconnectn_xxx SNVT_switch nvoservice BV 19 DO 19 nvosrvc_xxx SNVT_switch nvofault BV 20 DO 20 nvofault_xxx SNVT_switch nvidisable BV 21 DO 21 nvi/nvodisable_xxx SNVT_switch nvosecurity_a BV 22 DO 22 nvosecurty_a_xxx SNVT_switch B.3 EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet Object Type BACnet Object ID N2 Data Type N2 Address LonWorks Name LonWorks nvostatus AV 1 AO 1 nvostatus_xxx nvisigsource AV 2 AO 2 nvictrlmode AV 3 AO 3 nvi/nvosigsource_x XX nvi/nvoctrlmode_xx X nvictrlchannel AV 4 AO 4 nvi/nvoctrlch_xxx nvibmstimeout AV 5 AO 5 nvi/nvobmstmeout_ XXX nvohouropt_a AV 6 AO 6 nvohropt_a_xxx nvohourweight_a AV 7 AO 7 nvohrwght_a_xxx SNVT SNVT_lev_per SNVT_lev_per SNVT_lev_per SNVT_lev_per SNVT_time_se c SNVT_time_ho ur SNVT_time_ho ur nvorhdem_a1 AV 8 AO 8 nvorhdem_a1_xxx SNVT_lev_per nvorhdem_a2 AV 9 AO 9 nvorhdem_a2_xxx SNVT_lev_per nvosysdem_a AV 10 AO 10 nvosysdem_a_xxx SNVT_lev_per nvimancapacity_a AV 11 AO 11 nvi/nvomancap_a_x SNVT_lev_per XX nvisetpoint_a1 AV 12 AO 12 nvi/nvosetpnt_a1_x SNVT_lev_per XX nvisetpoint_a2 AV 13 AO 13 nvi/nvosetpnt_a2_x SNVT_lev_per XX nvidrhdem_a1 AV 14 AO 14 nvi/nvodrhdem_a1 SNVT_lev_per _XXX nvidrhdem_a2 AV 15 AO 15 nvi/nvodrhdem_a2 SNVT_lev_per _XXX nvohouropt_b AV 16 AO 16 nvohropt_b_xxx SNVT_time_ho ur nvohourweight_b AV 17 AO 17 nvohrwght_b_xxx SNVT_time_ho x Appendix _A_EN_1609 Nortec LINKS

41 ur nvorhdem_b1 AV 18 AO 18 nvorhdem_b1_xxx SNVT_lev_per nvorhdem_b2 AV 19 AO 19 nvorhdem_b2_xxx SNVT_lev_per nvosysdem_b AV 20 AO 20 nvosysdem_b_xxx SNVT_lev_per nvimancapacity_b AV 21 AO 21 nvi/nvomancap_b_x SNVT_lev_per XX nvisetpoint_b1 AV 22 AO 22 nvi/nvosetpnt_b1_x SNVT_lev_per XX nvisetpoint_b2 AV 23 AO 23 nvi/nvosetpnt_b2_x SNVT_lev_per XX nvidrhdem_b1 AV 24 AO 24 nvi/nvodrhdem_b1 SNVT_lev_per _XXX nvidrhdem_b2 AV 25 AO 25 nvi/nvodrhdem_b2 SNVT_lev_per _XXX nvoconnection BV 1 DO 1 nvoconnectn_xxx SNVT_switch nvoservice BV 2 DO 2 nvosrvc_xxx SNVT_switch nvofault BV 3 DO 3 nvofault_xxx SNVT_switch nvidisable BV 4 DO 4 nvi/nvodisable_xxx SNVT_switch nvosecurity_a BV 5 DO 5 nvosecurty_a_xxx SNVT_switch nvobloweract_a BV 6 DO 6 nvoblwract_a_xxx SNVT_switch nvofanact_a BV 7 DO 7 nvofanact_a_xxx SNVT_switch nvosecurity_b BV 8 DO 8 nvosecurty_b_xxx SNVT_switch nvobloweract_b BV 9 DO 9 nvoblwract_b_xxx SNVT_switch nvofanact_b BV 10 DO 10 nvofanact_b_xxx SNVT_switch B.4 EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks Point Name BACnet Object Type BACnet Object ID N2 Data Type N2 Address LonWorks Name LonWorks SNVT MI_UnitStatusA MI 1 ADI 1 nvounitstata_xxx SNVT_count MI_UnitStatusB MI 2 ADI 2 nvounitstatb_xxx SNVT_count MI_ServStatusA MI 3 ADI 3 nvoservstata_xxx SNVT_count MI_ServStatusB MI 4 ADI 4 nvoservstatb_xxx SNVT_count MI_HumType MI 5 ADI 5 nvohumtype_xxx SNVT_count MI_NomVoltage MI 6 ADI 6 nvonomvolt_xxx SNVT_count MI_LevelA MI 7 ADI 7 nvolevela_xxx SNVT_count MI_LevelB MI 8 ADI 8 nvolevelb_xxx SNVT_count AI_ErrorCode AI 1 AI 1 nvoerrorcode_xxx SNVT_count AI_OperatHours AI 2 AI 2 nvooperathr_xxx SNVT_time_ho ur AI_HoursToServA AI 3 AI 3 nvohrtoserva_xxx SNVT_time_ho ur AI_HoursToServB AI 4 AI 4 nvohrtoservb_xxx SNVT_time_ho ur AI_SystemDemandA AI 5 AI 5 nvosysdem_xxx SNVT_count AI_InputA1 AI 6 AI 6 nvoinputa1_xxx SNVT_count AI_InputA2 AI 7 AI 7 nvoinputa2_xxx SNVT_count AI_MaxHumOut AI 8 AI 8 nvomaxhumout_xx X SNVT_count AI_CylMaxCapA AI 9 AI 9 nvocylmxcapa_xxx SNVT_count Nortec LINKS _A_EN_1609 Appendix I xi

42 AI_CylMaxCapB AI 10 AI 10 nvocylmxcapb_xxx SNVT_count AI_ActCapHum AI 11 AI 11 nvoaccaphum_xxx SNVT_count AI_CylActCapA AI 12 AI 12 nvocylaccapa_xxx SNVT_count AI_CylActCapB AI 13 AI 13 nvocylaccapb_xxx SNVT_count AV_SetPointA1 AV 1 ADF 1 nvi/nvosetpnta1_xx X SNVT_count AV_SetPointA2 AV 2 ADF 2 nvi/nvosetpnta2_xx X SNVT_count AV_PropBandA1 AV 3 ADF 3 nvi/nvopropbnda1_x SNVT_count XX AV_PropBandA2 AV 4 ADF 4 nvi/nvopropbnda2_x SNVT_count XX AV_IntTimeA1 AV 5 ADF 5 nvi/nvointtimea1_x XX SNVT_count AV_DampTimeA2 AV 6 ADF 6 nvi/nvodmptimea2_ XXX SNVT_count AV_CapLimitA AV 7 ADF 7 nvi/nvocaplimita_x XX SNVT_count AV_RemoteDrain AV 8 ADF 8 AO_RemRHorDemA1 AO 1 AO 1 nvi/nvormrhrdma1 _XXX SNVT_count AO_RemRHorDemA2 AO 2 AO 2 nvi/nvormrhrdma2 _XXX SNVT_count BI_BlowerPackA BI 1 DI 1 nvoblwrpacka_xxx SNVT_switch BI_BlowerPackB BI 2 DI 2 nvoblwrpackb_xxx SNVT_switch BI_ExtSChStaA BI 3 DI 3 nvoextschsta_xxx SNVT_switch BI_ExtSChStaB BI 4 DI 4 nvoextschstb_xxx SNVT_switch BI_IntSChStaA BI 5 DI 5 nvointschsta_xxx SNVT_switch BI_IntSChStaB BI 6 DI 6 nvointschstb_xxx SNVT_switch BI_HeatVoltageA BI 7 DI 7 nvoheatvolta_xxx SNVT_switch BI_HeatVoltageB BI 8 DI 8 nvoheatvoltb_xxx SNVT_switch BI_LevelSafetyA BI 9 DI 9 nvolvlsaftya_xxx SNVT_switch BI_LevelSafetyB BI 10 DI 10 nvolvlsaftyb_xxx SNVT_switch BI_LeakA BI 11 DI 11 nvopressurea_xxx SNVT_switch BI_LeakB BI 12 DI 12 nvopressureb_xxx SNVT_switch BI_MainContactA BI 13 DI 13 nvomainconta_xxx SNVT_switch BI_MainContactB BI 14 DI 14 nvomaincontb_xxx SNVT_switch BI_PumpA BI 15 DI 15 nvopumpa_xxx SNVT_switch BI_PumpB BI 16 DI 16 nvopumpb_xxx SNVT_switch BI_InletA1 BI 17 DI 17 nvoinleta1_xxx SNVT_switch BI_InletB1 BI 18 DI 18 nvoinletb1_xxx SNVT_switch BI_InletA2 BI 19 DI 19 nvoinleta2_xxx SNVT_switch BI_InletB2 BI 20 DI 20 nvoinletb2_xxx SNVT_switch BI_DrainA1 BI 21 DI 21 nvodraina1_xxx SNVT_switch BI_DrainB1 BI 22 DI 22 nvodrainb1_xxx SNVT_switch BI_DrainA2 BI 23 DI 23 nvodraina2_xxx SNVT_switch BI_DrainB2 BI 24 DI 24 nvodrainb2_xxx SNVT_switch BI_FanA BI 25 DI 25 nvofana_xxx SNVT_switch BI_FanB BI 26 DI 26 nvofanb_xxx SNVT_switch BI_FlushValveA BI 27 DI 27 nvoflushvlva_xxx SNVT_switch BI_FlushValveB BI 28 DI 28 nvoflushvlvb_xxx SNVT_switch xii Appendix _A_EN_1609 Nortec LINKS

43 C REFERENCE C.1 Specifications Electrical Connections Approvals Power Requirements Physical Dimensions Weight Operating Temperature Surge Suppression Humidity ProtoCessor FPC-ED2 ProtoCessor FPC-ED4 One 3-pin Phoenix connector with One 2-pin Phoenix connector with: RS-485 port (+ / - / gnd) One FTT-10 LonWorks port One Ethernet 10/100 BaseT port One Ethernet 10/100 BaseT port CE Certified; TUV approved to UL 916, EN , EN and CSA C22-2 standards; FCC Class A Part 15; DNP3 Conformance Tested; RoHS Compliant; CSA 205 Approved BTL Marked LonMark Certified Multi-mode power adapter: 9-30VDC or 12-24VAC 6.9 x 3.0 x 2.0 cm 2.7 x 1.2 x 0.8 in kg (0.07 lbs) -40 C to 75 C (-40 F to167 F) (Specifications subject to change without notice) Figure 22: Specifications 8.5 x 3.0 x 2.0 cm 3.3 x 1.2 x.08 in. EN ESD EN EMC EN EFT 5-90% RH (non-condensing) C.2 Compliance with UL Regulations For UL compliance, the following instructions must be met when operating ProtoCessor.The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature range.the interconnecting power connector and power cable shall: Comply with local electrical code Be suited to the expected operating temperature range Meet the current and voltage rating for ProtoCessor Furthermore, the interconnecting power cable shall: Be of length not exceeding 3.05m (118.3 ) Be constructed of materials rated VW-1, FT-1 or better If the unit is to be installed in an operating environment with a temperature above 65 C, it should be installed in a Restricted Access Area requiring a key or a special tool to gain access. This device must not be connected to a LAN segment with outdoor wiring. Nortec LINKS _A_EN Appendix I xiii

44 Page intentionally left blank xiv Appendix _A_EN_1609 Nortec LINKS

45 Warranty Nortec Humidity Inc. and/or Nortec Humidity Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer s ship date, whichever date is earlier, that THE COMPANY s manufactured and assembled products, not otherwise expressly warranted, are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations. THE COMPANY s obligations and liabilities under this warranty are limited to furnishing replacement parts to the customer, F.O.B. THE COMPANY s factory, provided that the defective part(s) is returned freight prepaid by the customer. The replacement parts are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer. The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY. THE COMPANY s limited warranty on accessories, not manufactured by the COMPANY, such as controls, humidistats, pumps, etc., is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier. THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase, and by a contractor approved by THE COMPANY to install such equipment. THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment. THE COMPANY makes no warranty and assumes no liability whatsoever for damage to the humidifier, supply lines, drain lines, or steam distribution systems caused by freezing. THE COMPANY reserves the right to change the design, specifications and performance criteria of its products without notice or obligation.

46 Consulting, Sales and Service: U.S.A. 835 Commerce Park Ave Ogdensburg, NY CANADA 2740 Fenton Road Ottawa, ON, K1T 3T7 Tel: NORTEC1 Fax: Website:

Hubbell Building Automation #LXBASM. ProtoNode LER Startup Guide

Hubbell Building Automation #LXBASM. ProtoNode LER Startup Guide Hubbell Building Automation #LXBASM ProtoNode LER Startup Guide For Interfacing Customer Product: Hubbell Automation LX Lighting Control Panels To Building Automation Systems: BACnet MS/TP, BACnet/IP,

More information

LINKS 2. NHTC OPTIONS Installation and Operation Manual

LINKS 2. NHTC OPTIONS Installation and Operation Manual Important: Read and save these instructions. This guide to be left with equipment. LINKS 2 NHTC OPTIONS Installation and Operation Manual Includes installation, operation maintenance and troubleshooting

More information

FieldServer EZ Gateway Modbus to BACnet Start-up Guide FS-EZX-MOD-BAC

FieldServer EZ Gateway Modbus to BACnet Start-up Guide FS-EZX-MOD-BAC FieldServer EZ Gateway Modbus to BACnet Start-up Guide FS-EZX-MOD-BAC APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after July 2017. Document Revision: 8.B Technical Support Please

More information

AERCO ProtoNode FPC-N34 and FPC-N35 User Manual

AERCO ProtoNode FPC-N34 and FPC-N35 User Manual User Manual OMM-0107 GF-150 AERCO ProtoNode FPC-N34 and FPC-N35 User Manual AERCO Serial ProtoNode FPC-N34 Part Number 64129 AERCO LonWorks ProtoNode FPC-N35 Part Number 64130 For interfacing with the

More information

ProtoAir FPA-W34 Start-up Guide For Interfacing the Siemens MAG6000 To Building Automation Systems: BACnet/IP, Modbus TCP/IP and EtherNet/IP

ProtoAir FPA-W34 Start-up Guide For Interfacing the Siemens MAG6000 To Building Automation Systems: BACnet/IP, Modbus TCP/IP and EtherNet/IP ProtoAir FPA-W34 Start-up Guide For Interfacing the Siemens MAG6000 To Building Automation Systems: BACnet/IP, Modbus TCP/IP and EtherNet/IP APPLICABILITY & EFFECTIVITY Explains ProtoAir hardware and installation.

More information

BACnet Router Start-up Guide

BACnet Router Start-up Guide BACnet Router Start-up Guide BAS Router (BACnet Multi-Network Router) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after October 2014 Kernel Version: 6.15 Document Revision: 3 QuickServer

More information

LINKS 2. GSTC / SETC B+ Models Installation and Operation Manual

LINKS 2. GSTC / SETC B+ Models Installation and Operation Manual Important: Read and save these instructions. This guide to be left with equipment. LINKS 2 GSTC / SETC B+ Models Installation and Operation Manual Includes installation, operation maintenance and troubleshooting

More information

APPLICABILITY & EFFECTIVITY

APPLICABILITY & EFFECTIVITY ProtoAir FPA-W34 Start-up Guide For Interfacing Eaton Products: Greengate, ilumin and Fifth Light To Building Automation Systems: BACnet MS/TP, BACnet/IP, Modbus TCP/IP and Modbus RTU APPLICABILITY & EFFECTIVITY

More information

BACnet Router Start-up Guide

BACnet Router Start-up Guide BACnet Router Start-up Guide BAS Router (BACnet Multi-Network Router) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after January 2015 Kernel Version: Application Version: Document

More information

FieldServer X-25 Start-Up Guide

FieldServer X-25 Start-Up Guide Sierra Monitor Company FieldServer X-25 Start-Up Guide APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after April 2013 Kernel Version: 6.10 Document Revision: 0 FieldServer FS-X25 Start-Up

More information

FieldServer EZ Gateway M-Bus to Modbus & BACnet Start-up Guide FS-EZX-MBUS-MOD-BAC

FieldServer EZ Gateway M-Bus to Modbus & BACnet Start-up Guide FS-EZX-MBUS-MOD-BAC FieldServer EZ Gateway M-Bus to Modbus & BACnet Start-up Guide FS-EZX-MBUS-MOD-BAC APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after July 2018. Document Revision: 2.B T18047 Technical

More information

FieldServer BACnet Router Wi-Fi FS-ROUTER-BACW Start-up Guide BAS Router (BACnet Multi-Network Router)

FieldServer BACnet Router Wi-Fi FS-ROUTER-BACW Start-up Guide BAS Router (BACnet Multi-Network Router) FieldServer BACnet Router Wi-Fi FS-ROUTER-BACW Start-up Guide BAS Router (BACnet Multi-Network Router) APPLICABILITY & EFFECTIVITY The instructions are effective for the above as of May 2018. Document

More information

FieldServer BACnet Router FS-ROUTER-BACX Start-up Guide BAS Router (BACnet Multi-Network Router)

FieldServer BACnet Router FS-ROUTER-BACX Start-up Guide BAS Router (BACnet Multi-Network Router) FieldServer BACnet Router FS-ROUTER-BACX Start-up Guide BAS Router (BACnet Multi-Network Router) APPLICABILITY & EFFECTIVITY The instructions are effective for the above as of July 2018. Document Revision:

More information

USER MANUAL Installation, Operation, and Maintenance

USER MANUAL Installation, Operation, and Maintenance GF-29 AERCO/ProtoNode Gateway Installation, Operation, and Maintenance ProtoNode-RER (Serial Ethernet, P/N 64084) ProtoNode-LER (LonWorks, P/N 64085) For Interfacing AERCO Equipment to Building Automation

More information

FieldServer X-20 Start-Up Guide

FieldServer X-20 Start-Up Guide A Sierra Monitor Company FieldServer X-20 Start-Up Guide APPLICABILITY & EFFECTIVITY This manual provides instructions for the FS-B20XX-00 Models. Effective for all systems manufactured after May 2013

More information

FieldServer BACnet Router Wi-Fi FS-ROUTER-BACW Start-up Guide BAS Router (BACnet Multi-Network Router)

FieldServer BACnet Router Wi-Fi FS-ROUTER-BACW Start-up Guide BAS Router (BACnet Multi-Network Router) FieldServer BACnet Router Wi-Fi FS-ROUTER-BACW Start-up Guide BAS Router (BACnet Multi-Network Router) APPLICABILITY & EFFECTIVITY The instructions are effective for the above as of January 2019. Document

More information

BACnet, Supplemental Installation and Operation Manual. Thank you for choosing Condair.

BACnet, Supplemental Installation and Operation Manual. Thank you for choosing Condair. Important: Read and save these instructions. This guide to be left with equipment owner. BACnet, LONWORKS Supplemental Installation and Operation Manual Using BACnet or LonWorks with Condair humidifiers.

More information

LINKS XPS. MH Installation and Operation Manual

LINKS XPS. MH Installation and Operation Manual Important: Read and save these instructions. This guide to be left with equipment. LINKS XPS MH Installation and Operation Manual Includes installation, operation maintenance and troubleshooting information

More information

FieldServer Toolbox and Graphic User Interface (FS-GUI) Manual

FieldServer Toolbox and Graphic User Interface (FS-GUI) Manual FieldServer Toolbox and Graphic User Interface (FS-GUI) Manual This manual provides instructions for the following FieldServer products: ProtoAir FS-B35 Series SlotServer QuickServer Description FieldServer

More information

USB Server User Manual

USB Server User Manual 1 Copyright Notice Copyright Incorporated 2009. All rights reserved. Disclaimer Incorporated shall not be liable for technical or editorial errors or omissions contained herein; nor for incidental or consequential

More information

Plus-X 600. Installation and Operation Manual

Plus-X 600. Installation and Operation Manual Plus-X 600 Installation and Operation Manual Table of Contents Introduction... 1 Compatibility... 1 Unpacking... 1 Front Panel Indicators... 2 Hardware Configuration... 2 Installation... 4 Software Configuration...

More information

BACnet/IP to BACnet MS/TP Router

BACnet/IP to BACnet MS/TP Router BACnet/IP to BACnet MS/TP Router Features Compact Size Routes between BACnet /IP and BACnet MS/TP networks 10/100Mbps Ethernet Auto-MDIX port Optically isolated MS/TP communications port MS/TP baud rates:

More information

BACnet /IP to MS/TP Adapter User Guide

BACnet /IP to MS/TP Adapter User Guide BACnet /IP to MS/TP Adapter User Guide Document Revision History: Version 1.0 - Initial Release February, 2010 BACnet/IP to MS/TP Adapter - User Guide 1.0 05DI-UGBRTPB-10 Copyright Distech Controls Inc.

More information

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng IntesisBox Modbus Server KILSEN KSA-7xx User s Manual 08/2013 r1.2 eng Intesis Software S.L. 2013 All rights reserved. Information in this document is subject to change without notice. The software described

More information

Doc October ProtoNode Reference Manual

Doc October ProtoNode Reference Manual Doc. 66932-001 October 2015 ProtoNode Reference Manual ii ProtoNode Reference Manual 66932-001 Table of Contents 1.0 INTRODUCTION... 1 2.0 PACKAGE COMPONENTS (CHECK-LIST)... 1 3.0 PRODUCT DESCRIPTION...

More information

e-links Building Management Integration INTEGRATION INSTRUCTIONS FOR CONDAIR CP3 PRO EN 1304

e-links Building Management Integration INTEGRATION INSTRUCTIONS FOR CONDAIR CP3 PRO EN 1304 e-links Building Management Integration INTEGRATION INSTRUCTIONS FOR CONDAIR CP3 PRO 2534746 EN 1304 Contents 1 Notes for the planning engineer 4 1.1 Overview 4 1.2 Network diagrams 4 1.2.1 BACnet/IP

More information

EtherSeries. EtherSeries CR-2. CR-2-Opto. User s Guide. Revised October 7, 2013 Firmware Version 1.X

EtherSeries. EtherSeries CR-2. CR-2-Opto. User s Guide. Revised October 7, 2013 Firmware Version 1.X EtherSeries EtherSeries CR-2 & CR-2-Opto User s Guide Revised October 7, 2013 Firmware Version 1.X TABLE OF CONTENTS SECTION 1 - DESCRIPTION... 2 SECTION 2 - SPECIFICATIONS... 4 SECTION 3 - INSTALLATION...

More information

VP Process Inc. Model: VP-EC-RDU Modbus RTU LCD Display

VP Process Inc. Model: VP-EC-RDU Modbus RTU LCD Display VP Process Inc. Model: Modbus RTU LCD Display User Manual Ver: 2.0 Aug. 2017 P a g e 1 Standard Features Low Power (12-24 VDC) 2.1 x 5mm Barrel Plug, RJ45 and Terminal Block Input On-Board Local Temperature

More information

USB 3.0 Spectra

USB 3.0 Spectra USB 3.0 Spectra 3001-15 1-Port USB 3.0 15m Active Extension Cable User Guide Thank you for purchasing the Icron USB 3.0 Spectra 3001-15. Please read this guide thoroughly. This document applies to Part

More information

PG AA JCI Metasys N2 to SNMP Protocol Converter

PG AA JCI Metasys N2 to SNMP Protocol Converter PG-106-104-AA JCI Metasys N2 to SNMP Protocol Converter PG-106-104-AA is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators to effortlessly

More information

IntesisBox Modbus Server Fidelio IP

IntesisBox Modbus Server Fidelio IP IntesisBox Modbus Server Fidelio IP User Manual r1 eng Issue Date: 10/04/2014 Intesis Software S.L. All Rights Reserved. Information in this document is subject to change without notice. The software described

More information

USB Ranger Fiber Optic USB 2.0 Extender. User Guide

USB Ranger Fiber Optic USB 2.0 Extender. User Guide USB Ranger 2224 Fiber Optic USB 2.0 Extender User Guide Thank you for purchasing the USB Ranger 2224. Please read this guide thoroughly. This document applies to Part Numbers: 00-00260, 00-00261, 00-00262,

More information

IntesisBox Modbus Server - BACnet/IP Client

IntesisBox Modbus Server - BACnet/IP Client IntesisBox Modbus Server - BACnet/IP Client Gateway for integration of devices into Modbus (RTU and TCP) systems. Integrate Daikin VRV Air Conditioners into your Modbus system (SCADA, BMS, PLC ). For this,

More information

62532 (EN649) Ethernet Adapter

62532 (EN649) Ethernet Adapter 62532 (EN649) Ethernet Adapter INSTALLATION AND OPERATING INSTRUCTIONS For sales and Service in North America contact: ESD Systems.com www.esdsystems.com sales@esdsystems.com Phone: 508-485-7390 Fax: 508-480-0257

More information

Industrial Ethernet Ethernet to Serial Gateways Ethernet to Serial Converters for Modbus, Red lion and other protocols

Industrial Ethernet Ethernet to Serial Gateways Ethernet to Serial Converters for Modbus, Red lion and other protocols USER MANUAL Industrial Ethernet Ethernet to Serial Gateways Ethernet to Serial Converters for Modbus, Red lion and other protocols Contents at a Glance: Section 1 General Information RM-PS-024-01F 3 Section

More information

PG AA Modbus RTU to SNMP Protocol Converter

PG AA Modbus RTU to SNMP Protocol Converter PG-100-104-AA Modbus RTU to SNMP Protocol Converter PG-100-104-AA is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators to effortlessly

More information

The max number of C910 controllers is 8 per ProtoNode.

The max number of C910 controllers is 8 per ProtoNode. ProtoNode Configuring ProtoNode to Communicate with multiple RAYCHEM C910 controllers Application Design Note The ProtoNode multi-protocol device servers (ProtoNode-RER and ProtoNode- LER) are designed

More information

PG AB Omron FINS to Modbus RTU Protocol Converter

PG AB Omron FINS to Modbus RTU Protocol Converter PG- 135-100-AB Omron FINS to Modbus RTU Protocol Converter PG-135-100-AB is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators to

More information

Zodiac WX QUICK START GUIDE

Zodiac WX QUICK START GUIDE Zodiac WX QUICK START GUIDE Oct 2017 - Page 1 - Important Information Limited warranty: Northbound Networks warrants that the Zodiac WX will be free from defects in material or workmanship for a period

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS BACnet Communication Card RXRX-AY01 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED

More information

Ethernet Interface Module

Ethernet Interface Module Interface Manual 1 Ethernet Interface Module SignalFire Number: ENET-DIN The SignalFire Ethernet Gateway has the following features: - Wide range DC power input. 6 to 36VDC - Power Over Ethernet (POE)

More information

LabelWriter. Print Server. User Guide

LabelWriter. Print Server. User Guide LabelWriter Print Server User Guide Copyright 2011 Sanford, L.P. All rights reserved. 04/11 No part of this document or the software may be reproduced or transmitted in any form or by any means or translated

More information

GV-Card Reader. User s Manual

GV-Card Reader. User s Manual GV-Card Reader User s Manual Before attempting to connect or operate this product, please read these instructions carefully and save this manual for future use. READER-B 2016 GeoVision, Inc. All rights

More information

Smart Equipment Controls (SEC)

Smart Equipment Controls (SEC) Smart Equipment Controls (SEC) Product Bulletin SE-SPU1001-0, SE-SPU1002-0, SE-SPU1011-0, SE-SPU1011-0, SE-SPU1012-0, SE-SPU1004-0, SE-FDD1001-0, SE-ECO1001-0, SE-COM1001-0 Code No. LIT-12011934 Issued

More information

C1002 IP Camera. Quick Installation Guide. Solwise Ltd., 1

C1002 IP Camera. Quick Installation Guide. Solwise Ltd.,   1 C1002 IP Camera Quick Installation Guide Solwise Ltd., www.solwise.co.uk, sales@solwise.co.uk 1 Trademarks and/or registered trademarks are the property of their respective owners The information presented

More information

BAS Router BACnet Multi-Network Router

BAS Router BACnet Multi-Network Router BAS Router BACnet Multi-Network Router The BAS Router provides stand-alone routing between BACnet networks such as BACnet/IP, BACnet Ethernet, and BACnet MS/TP thereby allowing the system integrator to

More information

FA-2448 SIX POSITION Filter Wheel

FA-2448 SIX POSITION Filter Wheel 15 Discovery Way, Acton, MA 01720 Phone: (978)263-3584, Fax: (978)263-5086 Web Site: www.acton-research.com Operating Instructions Acton Research Corporation FA-2448 SIX POSITION Filter Wheel Rev. 3.05.17

More information

BACnet, LonWorks. Supplemental Installation and Operation Manual. For use with RS, EL, DL, and ME humidifiers with Software version 5.7.x.

BACnet, LonWorks. Supplemental Installation and Operation Manual. For use with RS, EL, DL, and ME humidifiers with Software version 5.7.x. 2585293-I EN 1901 BACnet, LonWorks Supplemental Installation and Operation Manual For use with RS, EL, DL, and ME humidifiers with Software version 5.7.x.x Humidification and Evaporative Cooling Thank

More information

Modbus TCP/RTU Gateway

Modbus TCP/RTU Gateway Modbus TCP/RTU Gateway Hardware Installation Guide for models IE-GW-MB-2TX-1RS232/485 IE-GWT-MB-2TX-1RS232/485 Second Edition, June 2014 1516600000/01/06.14 Important note: The detailed user manual, additional

More information

factory field upgrade

factory field upgrade CK721-A Network Controller factory field upgrade version 3.1 build 25 24-10025-75 Revision B October, 2013 Copyright 2013 Johnson Controls, Inc. All Rights Reserved No part of this document may be reproduced

More information

PG AC Modbus TCP to LonWorks Protocol Converter

PG AC Modbus TCP to LonWorks Protocol Converter PG-101-105-AC Modbus TCP to LonWorks Protocol Converter PG-101-105-AC is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators to effortlessly

More information

Installation Manual SM-RS Port RS232 Router with optional TCP/IP control

Installation Manual SM-RS Port RS232 Router with optional TCP/IP control Installation Manual SM-RS232 16-Port RS232 Router with optional TCP/IP control Control up to 16 RS232 compliant devices up to 50 feet away over UTP or from anywhere via TCP/IP (optional) What s in the

More information

1 LIMITED WARRANTY STORCASE TECHNOLOGY, Incorporated ( StorCase ) warrants that its products will be free from defects in material and workmanship, su

1 LIMITED WARRANTY STORCASE TECHNOLOGY, Incorporated ( StorCase ) warrants that its products will be free from defects in material and workmanship, su StorCase Technology Rhino JR FJR110 1-Bay External FireWire 800/USB 2 0-to-IDE Expansion Chassis User's Guide Part No D89-0000-0249 A04 July 2005 StorCase Technology, Inc 17600 Newhope Street Fountain

More information

AT IEEE 802.3af Universal Multi-voltage PoE Splitter. Installation and User Guide. PN Rev A

AT IEEE 802.3af Universal Multi-voltage PoE Splitter. Installation and User Guide. PN Rev A AT-6102 IEEE 802.3af Universal Multi-voltage PoE Splitter Installation and User Guide PN 613-000635 Rev A Electrical Safety and Emissions Standards Standards: This product meets the following standards.

More information

tsh-700 Series User Manual

tsh-700 Series User Manual tsh-700 Series User Manual Tiny Serial Port Sharer Aug. 2017 Ver. 1.6 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery

More information

EMC-1 TM. Ethernet Meterbus Converter. DIMENSIONS [inches (millimeters)] Installation and Operation Manual

EMC-1 TM. Ethernet Meterbus Converter. DIMENSIONS [inches (millimeters)] Installation and Operation Manual EMC-1 TM Ethernet Meterbus Converter Installation and Operation Manual DIMENSIONS [inches (millimeters)] 4.85 ( 123 ) For the most recent manual revisions, see the version at: www.morningstarcorp.com 3.37

More information

SHEET. BAS Portable Router BACnet Multi-Network Router. BAS Portable Router

SHEET. BAS Portable Router BACnet Multi-Network Router. BAS Portable Router BAS Portable Router d a t a SHEET BAS Portable Router BACnet Multi-Network Router The BAS Portable Router provides stand-alone routing between BACnet networks such as BACnet/IP, BACnet Ethernet, and BACnet

More information

LON Module for Variable Speed Drive

LON Module for Variable Speed Drive 5 193. LON Module for Variable Speed Drive SED2 Conforms to and is certified to the LONMARK Interoperability Guidelines enabling information sharing with other LONMARK products. LONMARK-compliant with

More information

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision 1.03.00 Motortronics / Phasetronics 1600 Sunshine Drive Clearwater, Florida 33765 Tel: 727-573-1819 Fax: 727-573-1803

More information

Plus-X 300. Installation and Operation Manual

Plus-X 300. Installation and Operation Manual Plus-X 300 Installation and Operation Manual Table of Contents Introduction... 1 Compatibility... 1 Installation... 1 Configuration... 2 Operation... 5 Getting Help... 6 Warranty... 6 Appendix A: Specifications...

More information

IntesisBox Modbus Server - Honeywell XLS 80

IntesisBox Modbus Server - Honeywell XLS 80 IntesisBox Server - Honeywell XLS 80 Gateway for integration of Honeywell XLS 80 fire panels into (RTU and TCP) enabled control systems. Integrate your Honeywell fire panels into your master device or

More information

IntesisBox Modbus Server Siemens Synova FC330A

IntesisBox Modbus Server Siemens Synova FC330A IntesisBox Modbus Server Siemens Synova FC330A User's Manual V10 r10 eng Intesis Software S.L. 2009. All Rights Reserved. Information in this document is subject to change without notice. The software

More information

LX Series Remote Input/Output (I/O) Controller

LX Series Remote Input/Output (I/O) Controller LX Series Remote Input/Output (I/O) Controller Product Bulletin LX-IO520-1, LX-IO401-1, LX-IO301-1 Code No. LIT-12011491 Issued June 22, 2009 The LX Series Remote Input/Output (I/O) controller extends

More information

2-Port RS-232/422/485 Serial over IP Ethernet Device Server Installation Guide

2-Port RS-232/422/485 Serial over IP Ethernet Device Server Installation Guide 2-Port RS-232/422/485 Serial over IP Ethernet Device Server Installation Guide Introduction The 2-Port RS-232/422/485 Serial over IP Ethernet Device Server is designed to operate serial ports over 10/100

More information

Presented By: Tim McLaughlin, Director of Business Development - Engnuity and Richard Theron, Product Manager FieldServer Agenda: Introduction Who is

Presented By: Tim McLaughlin, Director of Business Development - Engnuity and Richard Theron, Product Manager FieldServer Agenda: Introduction Who is Presented By: Tim McLaughlin, Director of Business Development - Engnuity and Richard Theron, Product Manager FieldServer Agenda: Introduction Who is Engenuity? Who is FieldServer? Identifying protocol

More information

ewon Flexy 2 Serial Ports Ext. Card FLA 3301

ewon Flexy 2 Serial Ports Ext. Card FLA 3301 Installation Guide IG 016 / Rev. 1.2 FLA 3301 This Installation Guide explains how to install the 2 Serial Ports Extension Card FLA 3301. support.ewon.biz Table of Contents 1. Product Summary... 3 2. Safety,

More information

IntesisBox Modbus Server - LON

IntesisBox Modbus Server - LON IntesisBox Server - LON Gateway for integration of LON devices into enabled control systems. Integrate Air Conditioning from the main manufacturers (DAIKIN, Mitsubishi Electric, Mitsubishi Heavy Industries,

More information

PG AB Notifier NFS 3030 to Modbus RTU Protocol Converter

PG AB Notifier NFS 3030 to Modbus RTU Protocol Converter PG-141-100-AB Notifier NFS 3030 to Modbus RTU Protocol Converter PG-141-100-AB is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators

More information

PG AB Fike Cheetah to Modbus TCP Protocol Converter

PG AB Fike Cheetah to Modbus TCP Protocol Converter PG-139-101-AB Fike Cheetah to Modbus TCP Protocol Converter PG-139-101-AB is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators to

More information

Wireless Location Receiver PLK-TR015-10

Wireless Location Receiver PLK-TR015-10 L o c a t e t o S i m p l i f y Wireless Location Receiver PLK-TR015-10 Industry Industrie User Guide 2012 Purelink Technology Incorporated. All rights reserved. Purelink Wireless Location Receiver PLK-TR015-10

More information

EZ Bridge B 100mW Product Guide

EZ Bridge B 100mW Product Guide EZ Bridge 802.11B 100mW Product Guide I. Introduction Section - Product Information Product Name: EZ Bridge Model: 802.11B 100mW Item Number: 11-207 (PCB Kit) and 11-208 (NEMA4 Box) II. Technical Specs

More information

efive 25 Installation Guide

efive 25 Installation Guide ewon Installation Guide IG 012 / Rev 1.3 efive 25 Installation Guide Contents This short guide explains how to install the efive 25 Firewall and to get started with the embedded configuration web site.

More information

1. Introduction... 1 Features... 1 Package Contents... 1 System Requirements... 1 LED Status... 2

1. Introduction... 1 Features... 1 Package Contents... 1 System Requirements... 1 LED Status... 2 - i - Table of Contents 1. Introduction... 1 Features... 1 Package Contents... 1 System Requirements... 1 LED Status... 2 2. Installation... 3 Windows 7/ Vista... 3 Windows XP... 5 Windows 2000... 7 Windows

More information

Plus-X RP-8 Adapter. Installation and Operation Manual

Plus-X RP-8 Adapter. Installation and Operation Manual Plus-X RP-8 Adapter Installation and Operation Manual Table of Contents Introduction... 1 Compatibility... 1 Unpacking... 2 Front Panel Indicators... 3 Hardware Configuration... 3 Installation... 4 Software

More information

SMC Cloud. Start-up Guide. (Instructions for Field Installers, Support and Administrator) APPLICABILITY & EFFECTIVITY

SMC Cloud. Start-up Guide. (Instructions for Field Installers, Support and Administrator) APPLICABILITY & EFFECTIVITY SMC Cloud Start-up Guide (Instructions for Field Installers, Support and Administrator) APPLICABILITY & EFFECTIVITY Explains SMC Cloud registration and use. The instructions are effective for the above

More information

Flex Gateway Card. Installation and Operation Manual. For CPS 50kW/60kW 3-Phase String Inverters

Flex Gateway Card. Installation and Operation Manual. For CPS 50kW/60kW 3-Phase String Inverters Flex Gateway Card Installation and Operation Manual For CPS 50kW/60kW 3-Phase String Inverters CHINT POWER SYSTEMS AMERICA CO. Revision 1.0 - June 2017 1 Chapter 1 Overview 1.1 Product Description This

More information

Using Yaskawa CM049 BACnet Option with Delta Controls DSM-RTR

Using Yaskawa CM049 BACnet Option with Delta Controls DSM-RTR Using Yaskawa CM049 BACnet Option with Delta Controls DSM-RTR 1. INTRODUCTION: The following information describes utilizing the Yaskawa E7U and P7U Variable Frequency Drives with Yaskawa s CM049 BACnet

More information

Installation, Operation, and Maintenance Lifetime Power Wireless Sensor System

Installation, Operation, and Maintenance Lifetime Power Wireless Sensor System Installation, Operation, and Maintenance Lifetime Power Wireless Sensor System Rev A.2 2011/10 Lifetime Power Wireless Sensor System Page 1 Copyright 2011 Powercast Corporation. All rights reserved. This

More information

MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module MS/TP

MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module MS/TP Installation and Maintenance Manual IM 704-4 Group: Controls Part Number: IM 704 Date: August 2007 Supersedes: IM 704-3 MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet

More information

VIP-812A DUAL NETWORKED STATION PORT

VIP-812A DUAL NETWORKED STATION PORT ISSUE 1 VIP-812A DUAL NETWORKED STATION PORT INTRODUCTION The VIP-812A Dual Networked Station Port allows most loop start terminal devices to be connected to a managed IP-based LAN/WAN. SPECIFICATIONS

More information

hyperion ! This device requires a downloaded phone app in Instruction Manual Data Transfer Module

hyperion ! This device requires a downloaded phone app in Instruction Manual Data Transfer Module hyperion Data Transfer Module Instruction Manual! This device requires a downloaded phone app in order to control the growing environment. Search Titan Controls Hyperion on: or www.titancontrols.net Hyperion

More information

Application. Contents of Package. Inspect the CyberSwitch upon receipt. The package should contain the following items:

Application. Contents of Package. Inspect the CyberSwitch upon receipt. The package should contain the following items: Overview CyberPower power manager CyberSwitch is the ultimate power control center to manage multiple network devices via the Internet. After installing the hardware and setting up an IP address, this

More information

ECLYPSE Communication Modules

ECLYPSE Communication Modules Datasheet ECLYPSE Communication Modules Overview Features & Benefits Communication modules enable ECLYPSE Connected Controllers to communicate with a variety of devices. Scalable and Modular An ECY-RS485

More information

TH800DS CONTROLLER MANUAL

TH800DS CONTROLLER MANUAL TH800DS CONTROLLER MANUAL 1 Introduction 3 1.1 Overview 3 1.2 Features 4 1.3 Specifications 4 1.4 Panel 5 1.4.1 Front Panel 5 1.4.2 Rear Panel 6 2 Hardware Installation 7 3 Accessing the Device 8 3.1 Before

More information

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP Installation and Maintenance Manual IM 853 Group: Controls Part Number: IM 853 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet

More information

BASRTP-B. Portable. BACnet Multi-Network Router. Installation Guide. TD II For Firmware Versions 2.7.x

BASRTP-B. Portable. BACnet Multi-Network Router. Installation Guide. TD II For Firmware Versions 2.7.x BASRTP-B Portable BACnet Multi-Network Router Installation Guide For Firmware Versions 2.7.x Trademarks Contemporary Controls, ARC Control, ARC DETECT, EXTEND-A-BUS, RapidRing, and CTRLink are trademarks

More information

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module Installation and Maintenance Manual IM 928-2 Group: Controls Part Number: 669207702 Date: March 2011 Supersedes: IM 928-1 MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module NOTICE

More information

ProtoAir FPA-W44 & FPA-C34 Start-up Guide

ProtoAir FPA-W44 & FPA-C34 Start-up Guide ProtoAir FPA-W44 & FPA-C34 Start-up Guide APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after September 2018. Document Revision: 2.C Technical Support Please call us for any technical

More information

Plus-X Dual IP-8 Adapter. Installation and Operation Manual

Plus-X Dual IP-8 Adapter. Installation and Operation Manual Plus-X Dual IP-8 Adapter Installation and Operation Manual Table of Contents Introduction... 1 Compatibility... 2 Unpacking... 2 Front Panel Indicators... 3 Hardware Configuration... 3 Installation...

More information

UTM Content Security Gateway CS-2001

UTM Content Security Gateway CS-2001 UTM Content Security Gateway CS-2001 Quick Installation Guide Table of Contents 1. Package Contents... 3 2. Setup the UTM Content Security Gateway... 4 3. Hardware Installation... 5 4. Basic System Configuration...

More information

EZ Bridge G Product Guide

EZ Bridge G Product Guide EZ Bridge 802.11G Product Guide I. Introduction Section - Product Information Product Name: EZ Bridge Model: 802.11G Item Number: 11-212 (NEMA-4 Box); 11-130 (PCB Kit) II. Technical Specs Network Standard:

More information

5 Port Industrial Ethernet Switch. IES5100 Instruction Manual

5 Port Industrial Ethernet Switch. IES5100 Instruction Manual 5 Port Industrial Ethernet Switch IES5100 FCC Compliance Statement This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.

More information

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 05/2009 MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES.

More information

USB 2.0 Ranger Port USB m CAT 5e/6/7 Extender System. User Guide

USB 2.0 Ranger Port USB m CAT 5e/6/7 Extender System. User Guide USB 2.0 Ranger 2304 4-Port USB 2.0 100m CAT 5e/6/7 Extender System User Guide Thank you for purchasing the USB 2.0 Ranger 2304. Please read this guide thoroughly. This document applies to Part Numbers:

More information

USB Ranger 110/410 User Guide

USB Ranger 110/410 User Guide USB Ranger 110/410 User Guide Featuring ExtremeUSB Technology USB Ranger 110/410 Thank you for purchasing the USB Ranger. Please read this guide thoroughly before installation. This document applies to

More information

Installation Guide 24-port 10/100 Fast Ethernet Switch with 1 Fiber Connection Model Name: KS-324F

Installation Guide 24-port 10/100 Fast Ethernet Switch with 1 Fiber Connection Model Name: KS-324F Installation Guide 24-port 10/100 Fast Ethernet Switch with 1 Fiber Connection Model Name: KS-324F We make no warranties with respect to this documentation and disclaim any implied warranties of merchantability,

More information

XC300 VDSL Network Extender Owners Manual

XC300 VDSL Network Extender Owners Manual XC300 VDSL Network Extender Owners Manual Warranty GDI Communications LLC warrants to the original consumer purchaser that each of its hardware products, and all components thereof, will be free from defects

More information

1550-N2 Revision 1.7 A-B Drives Protocol Interface September 1999

1550-N2 Revision 1.7 A-B Drives Protocol Interface September 1999 1550-N2 Revision 1.7 A-B Drives Protocol Interface September 1999 ProSoft Technology, Inc 9801 Camino Media Suite 105 Bakersfield, CA 93311 (661) 664-7208 (661) 664-7233 Fax http://www.prosoft-technology.com

More information

GUIDE. EIPR Skorpion IP Router EIPR

GUIDE. EIPR Skorpion IP Router EIPR a p p l i c a t i o n GUIDE EIPR EIPR Skorpion IP Router The EIPR links two Internet Protocol (IPv4) networks together passing appropriate traffic while blocking all other traffic. One of the networks

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION MS1000 2U STANDARD PROCESSOR P/N 901-10320000 Specifications subject to change without notice 901-10327902 Iss. 1.0 KONGSBERG MESOTECH LTD. 1598 Kebet Way, Port Coquitlam B.C. Canada

More information