MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module
|
|
- Nickolas Francis
- 5 years ago
- Views:
Transcription
1 Installation and Maintenance Manual IM Group: Controls Part Number: Date: March 2011 Supersedes: IM MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module NOTICE Use this manual to physically connect the BACnet Communication Module to various McQuay MicroTech III Unitary Controllers, and connect the Unitary Controller to your BACnet network. Connections and service to the MicroTech III Controller must be performed only by personnel knowledgeable in the operation of the equipment being controlled. Use the appropriate McQuay Engineering Data (ED), known as the Protocol Information document, to integrate the unit into your network. The Protocol Information document contains addressing details, BACnet protocol information, and a list of the data points available to the network. See the Reference Documents section of this manual for Protocol Information document numbers. MicroTech III control integration literature is available from your local McQuay International sales representative and McQuay International
2 Contents Revision History... 3 Reference Documents... 3 Limited Warranty... 3 Notice... 3 GENERAL INFORMATION... 4 Hazard Identification Messages... 4 APPLICATION... 6 COMPONENT DATA... 6 Light Emitting Diodes (LEDs)... 6 BACnet MS/TP Network Connector (P3)... 6 BACnet Board-Mounted Switches... 6 BACnet Board-Mounted Plugs... 7 Address Switch Pin Header... 7 Jumper J INSTALLATION... 8 Required Equipment... 8 Installing a new BACnet MS/TP Communication Module... 8 Replacing a BACnet MS/TP Communication Module... 8 INTEGRATION CONNECTING UNIT TO THE NETWORK Addressing and Establishing Communications Verifying the Network Address using the Wink Command Configuring the Unit Controller Restoring the BACnet Communication Module to Default Values Factory Configuration Settings for the BACnet Communication Module Field-Installed BACnet Communication Module Important Notes SERVICE INFORMATION TROUBLESHOOTING REPLACEMENT PARTS Figures Figure 1. MicroTech III BACnet Communication Module Figure 2. Building Automation System Figure 3. BACnet MS/TP Communication Module Mounted on the Unit Controller s Main Control Board Figure 4. BACnet MS/TP Connection Schematic Diagram Figure 5. BACnet Communicaiton Module Address Switch (S3) Default Settings to OFF (Open)* Figure 6. BACnet Communicaiton Module Address Switch (S3 )- Example of Common Network Address Setting* IM 928-2
3 Revision History IM 928 February 2009 Initial release IM July 2009 Added PN to front cover, added sensors to Parts list. IM March 2011 Added Wink command to Integraiton section. Removed typo from Instance Number. Added to Baud Rates supported. Removed references to MS/TP Network Number. Added the dip switch information on page and Important Notes on page 13, indicating that APDU length cannot be adjusted through HyperTerminal and bringing up the configuration menu in number 5. Reference Documents Number Company Title Source ANSI/ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers A Data Communication Protocol for Building Automation and Control Networks ED McQuay International Protocol Information for MicroTech III Water Source Heat Pump Unit Controller, LonWorks and BACnet MS/TP ED McQuay International Protocol Implementation and Conformance Statement (PICS) for MicroTech III WSHP Unit controller OM 931 McQuay International MicroTech III Water Source Heat Pump Unit Controller Operation and Maintenance Manual ED McQuay International Protocol Information for MicroTech III Fan Coil Unit Controller, LonWorks and BACnet MS/TP ED McQuay International Protocol Implementation and Conformance Statement (PICS) for MicroTech III FCU Unit controller OM 1095 McQuay International MicroTech III Fan Coil Unit Controller Operation and Maintenance Manual Limited Warranty Consult your local McQuay Representative for warranty details. Refer to Form Y. To find your local McQuay Representative, go to Notice 2011 McQuay International, Minneapolis MN. All rights reserved throughout the world. McQuay International reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this product is appropriate for his or her application. The following are trademarks or registered trademarks of their respective companies. Windows from Microsoft Corporation; BACnet from ASHRAE; from Echelon Corporation; McQuay, MicroTech III, and Applied Terminal Systems from McQuay International. IM
4 General Information This manual contains the information you need to install the MicroTech III BACnet Communication Module to a McQuay MicroTech III Unit Controller and integrate it into the network. Hazard Identification Messages! DANGER Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.! WARNING Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.! CAUTION Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded. Connections and service to the MicroTech III Unit Controller must be performed only by personnel knowledgeable in the operation of the equipment being controlled.! CAUTION Static sensitive components. Can cause equipment damage. Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work. Never unplug cables, circuit board terminal blocks, or power plugs while power is applied to the panel. NOTICE This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his or her own expense. McQuay International disclaims any liability resulting from any interference or for the correction thereof. IM
5 Description The BACnet Communication Module incorporates a MicroTech III Unit Controller into a BACnet Local Area Network (LAN). It supports the BACnet MS/TP (EIA 485) data link layer (physical layer). The BACnet Communication Module mounts in the MicroTech III Unit Controller panel. The BACnet Communication Module is a rectangular printed circuit card with indicators (D1, D2, D3, & D4) on the top (see Figure 1). Each MicroTech III BACnet Communication Module is a printed circuit board that plugs on the top side of the MicroTech III unit controller baseboard. Figure 1 is an outline drawing with dimensions and major components of the MicroTech III BACnet Communication Module. Figure 1. MicroTech III BACnet Communication Module IM
6 Application The BACnet Communication Module connects the MicroTech III Unit Controller to the Building Automation System (BAS) on a BACnet Local Area Network. It is the interface adapter for the exchange of BACnet objects between the network and the unit controller. Figure 2 shows the BACnet Communication Module and MicroTech III Unit Controller integrated into a BAS. Refer to the appropriate MicroTech III Unit Controller Operation and Maintenance manual for details. Figure 2. Building Automation System BACnet MS/TP Communication Module BACnet MS/TP Network MicroTech III Control Board Component Data Figure 1 shows the location of the major components (described in the section below) of the MicroTech III BACnet Communication Module. Light Emitting Diodes (LEDs) The MicroTech III BACnet MS/TP communication module has four LEDs to indicate communication activity and status of the MicroTech III BACnet Communication Module. LED Function Description D1 Program Running Program main loop activity D2 Baseboard Message SPI Activity, LED on during baseboard message D3 MS/TP Transmit Flashes on when transmitting a MS/TP message D4 MS/TP Receive Flashes on when receiving a MS/TP message BACnet MS/TP Network Connector (P3) The P3 connector connects the MicroTech III BACnet MS/TP Communication Module to the BACnet MS/TP network. Pin Designation Function 1 + Non-inverting Input 2 -- Inverting Input 3 GND Reference used where isolated device require a reference 4 Shield Shield (isolated terminal for connection of shields) BACnet Board-Mounted Switches Switch Designation Function S1 Reset Used to reset the BACnet Communication Module S2 Default Used to reset the BACnet Communication Module to default parameters 6 IM 928-2
7 BACnet Board-Mounted Plugs Plugs Function J1 P2 P3 P4 Used in configuring the BACnet Communication Module Used to program the BACnet Communication Module BACnet MS/TP network connection point 8-pin header plug connects to Unit Controller Baseboard Address Switch The Address Switch, S3, must be set to the MAC address of the BACnet MS/TP Communication Module. The valid range is 0 to Pin Header P4 is an 8-pin connection port on the back side of the BACnet MS/TP Communication Module. It matches up to the 8-Pin header on the MicroTech III unit controller baseboard. Jumper J2 Jumper J2 is used only for internal development and testing purposes. IM
8 Installation A BACnet MS/TP Communication Module can be factory or field-installed (see the Replacement Parts section for details). The following section describes how to install a new BACnet MS/TP Communication Module or replace an existing module. It also describes how to connect the BACnet MS/TP Communication Module to a BACnet network. The BACnet MS/TP Communication Module mounts on connector pins and is held in place with four plastic locking standoffs. The BACnet MS/TP network connects to the BACnet MS/TP Communication Module at the network connector plug, P3. Required Equipment Field installation/replacement and network connection requires the following: A BACnet MS/TP Communication Module (included in kit) Stand-offs (included in kit) IM 928 (included in kit) Shielded, twisted pair pigtail wire and plug for network connection Installing a new BACnet MS/TP Communication Module! DANGER The terminals on the Water Source Heat Pump unit controller are high voltage. Disconnect power to avoid electrical shock potential, which will result in death or serious injury. 1. Disconnect power from the MicroTech III unit controller. 2. Remove the network cable plug-in connector terminal block in P3 (see Figure 3.) 3. Locate the four standoffs for the BACnet MS/TP Communication Module. 4. Install the four standoffs on the MicroTech III unit controller circuit board (see Figure 3). 5. Orient the BACnet MS/TP Communication Module printed circuit board so that the side with the components faces out and the connector socket can mate with the 8-Pin header on the MicroTech III unit controller circuit board. 6. Push the BACnet MS/TP Communication Module onto the connector pins and standoffs until you hear the faint click of the locking standoffs securing the communication module in place. Replacing a BACnet MS/TP Communication Module! DANGER The terminals on the Water Source Heat Pump unit controller are high voltage. Disconnect power to avoid electrical shock potential, which will result in death or serious injury. 1. Disconnect power from the MicroTech III unit controller. 2. Record the MAC Address set in Address Switch S3. 3. Remove the network cable plug-in connector terminal block P3 (see Figure 3.) 4. Locate the four standoffs for the BACnet MS/TP Communication Module from the unit controller main circuit board (see Figure 3.) 5. Depress the barb on one standoff and gently pull the corner of the BACnet MS/TP Communication Module over the barb. Do not bend the BACnet MS/TP Communication Module or misalign the connector pins. 6. Proceed to the other three corners, remove the BACnet MS/TP Communication Module from each standoff, and pull the module over the standoffs. 7. Gently lift the BACnet MS/TP Communication Module from the unit controller. 8 IM 928-2
9 8. Locate the empty connector pins and four standoffs for the BACnet MS/TP Communication Module in the unit controller (see Figure 3.) 9. Orient the BACnet MS/TP Communication Module printed circuit board so that the side with the components faces out and the connector socket can mate with the 8-Pin header on the MicroTech III unit controller circuit board. 10. Push the BACnet MS/TP Communication Module onto the connector pins and standoffs until you hear the faint click of the locking standoffs securing the communication module in place. Figure 3. BACnet MS/TP Communication Module Mounted on the Unit Controller s Main Control Board The BACnet module connects to the unit controller via 8- pin header and plug P4 on the back of the BACnet module. Test Jmpr 1 H5 1 1 H7 H6 H4 Config Jumpers JP8 JP7 JP6 JP5 JP4 JP3 JP2 PRG RUN BLUE Header Compressor Relay Omron G8P H3 HP1-2 HP1-1 JTAG PORT Pin 1 TB2 TB R W2 W1 Y2 Y1 G O C A Switched L1 No Connection TB3 U DANGER - HIGH VOLTAGE L1 NEUTRAL H2 L1-1 L1-2 L1-3 N1 N2 N3 N SL1 MTIIIUC-WSHP Base Controller Part # E 1 JP1 H8 BLUE Header Standoff 1 S1 U5 1 D4 D3 D2 D1 J2 H9 YELLOW Header U2 U6 J1 U1 U4 U3 S2 T S3 ON P2 Standoff Shield Signal - Signal + P3 R W2 W1 Y2 Y1 G Test-1 24 C H1 IM
10 Figure 4. BACnet MS/TP Connection Schematic Diagram BACnet MS/TP Communication Module Shield GND - + GND or Reference is only used on three wire isolated systems that require a reference 10 IM 928-2
11 Integration Integrating the BACnet MS/TP Communication Module into a BAS involves three steps: 1. Connecting the unit controller to the network 2. Addressing and establishing communications with the unit controller 3. Configuring the unit controller Required Equipment Laptop with a serial port Serial terminal device application (such as Windows HyperTerminal) Null modem serial cable for setting the device instance number. Refer to the MicroTech III Unit Controller Protocol Information document, ED (available on for details. Connecting Unit to the Network After inserting the BACnet Communication Module to the unit controller, connect the unit controller into the BACnet network following the three steps below: 1. Replace network cable plug in P3 (see Figure 3.) 2. Set the MAC Address in Address Switch S3. Note: A MAC (Media Access Control) address must be assigned to the BACnet MS/TP Communication Module. See your network administrator for assistance, if necessary. 3. Apply power to the unit controller. Note: You must maintain the polarity of the signal throughout the network. Always connect + to + and to. Addressing and Establishing Communications Once the unit controller with attached BACnet Communicaiton Module has been connected to the network, it is ready to be addressed so that communicaiton can be established. The steps below describe this process (see Table 2 for additional BACnet parameters and their default values). 1. Verify that the MAC address of the unit controller is unique on the BACnet network. 2. Change the default BACnet MS/TP Address of the unit controller. The BACnet MS/TP device address (MAC) Address of the unit controller in a BACnet MS/TP network is set in an eight-position dipswitch (i.e. address switch) on the BACnet MS/TP Communication Module. The address is physically set using eight binary switches. Bit 0 of the address corresponds to switch position 1 and bit 7 of the address corresponds to switch position 8. All MicroTech III unit controllers must be masters; therefore, bit 7 (switch 8) is always equal to 0 (open). Table 1summarizes the various ways to describe a dipswitch setting. A closed switch (switch ON) is a 1 and an open switch is a 0. Figure 5 shows the address switch as set from the factory with all switches OFF = open (i.e. in the up position). Table 2 summarizes the address values when the dipswitches are ON. Figure 6 shows an example of the dipswitch settings for a common network address. Note that he MAC address of the device must be unique on the BACnet network. Table 1. Explanation of Dipswitch States (ON or OFF) Address Switch State Description ON Closed = dipswitch in down position = 1 OFF Open = dipswitch in up position = 0 IM
12 Figure 5. BACnet Communicaiton Module Address Switch (S3) Default Settings to OFF (Open)* * Note that the switches on the actual BACnet Communication Module are numbered: 8, 7, 6, 5, 4, 3, 2, 1 from left to right when the module is attached on the unit controller baseboard (as shown in Figures 1 and 3). Table 2. Address Switch Values When Switch is ON (Closed) Switch # Value Value When Switch is ON = Closed 1 2 to the zero power to the 1 st power to the 2 nd power to the 3 rd power to the 4 th power to the 5 th power to the 6 th power 64 8 Must always be in the up (OFF) position N/A Figure 6 shows an example of a typical address setting. The digital switch positions as read from right to left are: This provides an address of 76 as illustrated below. Figure 6. BACnet Communicaiton Module Address Switch (S3 )- Example of Common Network Address Setting* = 76 * Note that the switches on the actual BACnet Communication Module are numbered: 8, 7, 6, 5, 4, 3, 2, 1 from left to right when the module is attached on the unit controller baseboard (as shown in Figures 1 and 3). 3. Cycle power to the unit controller. Note: After you set the address in the switches, you must cycle power (turn the unit controller off and then on again) in order for the new address to take effect. 4. Change the data transmission rate, if necessary. The D4 LED flickers when the module is receiving data from the network, and the D3 LED flickers when the communication module is sending data to the network. See Figure 1 for details. 5. Verify the network address using the Wink Command process as described below (optional). Verifying the Network Address using the Wink Command The BACnet Communication Module implements a unit identification mode command to the unit controller by using the BACnet ReinitializeDevice request with a password of wink (all lower case). The Wink unit identification function allows verification of an individual unit network address without opening the unit access panels. The compressor shuts off during this period and the Minimum Compressor Off Countdown Timer must expire before the compressor is allowed to run again. The Wink command can be used during all operating and non-operating modes (ex. Alarms) except for Brownout Mode. Upon receiving a wink command from a network management node, the unit controller exhibits the following identification sequence (all occur simultaneously): 12 IM 928-2
13 Room Sensor Status LED: Flashes (on 0.5 sec, off 0.5 sec) for 15 seconds. Fan: The fan turns off for 5 seconds, turns on for 5 seconds, then off again for 5 seconds. Compressor: The compressor turns off for a minimum of 15 seconds. Configuring the Unit Controller All unit controllers are loaded with software and configured at the factory for standalone operation. The unit is ready to operate with default setpoint parameters that can be changed via the BAS (building automation system). Refer to the Protocol Document, ED (available on for descriptions of the available BACnet objects. Restoring the BACnet Communication Module to Default Values Setting the BACnet Communicaiton Module back to its default configuration requires the following steps: 1. Press and hold the DEFAULT switch S2. While holding this switch, press and release the RESET switch S1. The LEDs should flash once, turn off and turn on one after another. 2. Release the DEFAULT switch S2 (once all four LEDs are steady) to restore the BACnet Communicaiton Module to default values. Factory Configuration Settings for the BACnet Communication Module If the unit controller is equipped with a factory-installed BACnet MS/TP Communication Module, the unit controller is preconfigured with the values shown in Table 3. Field-Installed BACnet Communication Module A BACnet MS/TP Communication Module can be added to a unit controller in the field for these reasons: The unit did not originally ship with a communication module. The unit originally shipped with a LONWORKS Communication Module but requires replacement with a BACnet Communication Module. Table 3. Default Communication Setup Parameter Settings Parameter Name BACnet MSTP MSTP MAC Address 1 Switch Setting MSTP Baud Rate (9600, 19200, and 76800) Device Instance Number Max APDU Length Device Object Name 4 WSHP = MTIIIUC_WSHP_ FCU = MTIIIUC_FCU_ Important Notes 1. The MAC address is set by switch setting on the BACnet MS/TP Communication Module. 2. The device instance number is factory set at 300. This number must be unique on the network and must be set in the field. 3. The Max APDU Length parameter should not be set higher than 480 for BACnet MS/TP (this value can not be adjusted through the Configuration Menu). 4. The Device Object Name is set to factory default. This must be unique on the network and must be set in the field. 5. You need a computer with a serial port, and serial terminal device application (such as Windows HyperTerminal), and a serial null modem cable for setting the device instance number using the Configuration Menu. Refer to the Protocol Information Document, ED (available on IM
14 Service Information Troubleshooting If you can control the unit from the thermostat, but you are not able to communicate with unit via the network: Verify the network (bus) wiring. Verify that the Transmit LED (D3) is flickering. Verify that the MS/TP MAC address (S3) is set in the range (Master). Check the network communication parameters in the unit controller for proper settings. If the BACnet Communication Module still does not respond, contact the McQuay Controls Customer Support group at 866-4McQuay ( ). Replacement Parts Contact the McQuay Parts group at for replacement parts related to the BACnet MS/TP Communication Module. McQuay does not supply the network connector. Description MicroTech III BACnet MS/TP Communication Module Field Installation Kit Kit includes the following: MicroTech III BACnet MS/TP Communication Module Four stand-offs Discharge air temperature sensor, return air temperature sensor, and leaving water temperature sensor assembly IM 928 Part Number MicroTech III BACnet MS/TP Communication Module Replacement Parts Kit Kit includes the following: MicroTech III BACnet MS/TP Communication Module Four stand-offs IM 928 MicroTech III BACnet MS/TP Communication Module Temperature Sensor Assembly Assembly includes the following: Discharge air temperature sensor Return air temperature sensor Leaving water temperature sensor This document contains the most current product information as of this printing. For the most current product information, please go to IM 928-2
MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module
Installation and Maintenance Manual IM 928- Group: Controls Part Number: 66920770 Date: July 2009 Supersedes: IM 928 MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module NOTICE Use this
More informationMicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module MS/TP
Installation and Maintenance Manual IM 704-4 Group: Controls Part Number: IM 704 Date: August 2007 Supersedes: IM 704-3 MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet
More informationInstallation and Maintenance Manual IM 928-5
Installation and Maintenance Manual IM 928-5 MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module Group: Controls Part Number: IM 928 Date: February 2016 Table of Contents Introduction....
More informationMicroTech II Applied TM Rooftop Unit Controller and Self-Contained Unit Controller BACnet TM MSTP Communication Module
Installation and Maintenance Manual IM 704-3 Group: Controls Part Number: IM 704-3 Date: November 2004 Supersedes: IM 704-2 MicroTech II Applied TM Rooftop Unit Controller and Self-Contained Unit Controller
More informationInstallation and Maintenance Manual IM
Installation and Maintenance Manual IM 1013-1 MicroTech III Fan Coil BACnet MS/TP Communication Module Group: Controls Part Number: IM 1013 Date: February 2016 Table of Contents Introduction.... 3 Revision
More informationMicroTech II BACnet Communication Module Ethernet/IP
Installation & Maintenance Manual IM703-0 Group: McQuay Controls Date: October 2001 MicroTech II BACnet Communication Module Ethernet/IP ASHRAE 135, Annex J 10 BASE-T 1998 McQuay International Contents
More informationMicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module BACnet/IP
Installation and Maintenance Manual IM703-2 Group: McQuay Controls Date: February 2002 MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module BACnet/IP
More informationMicroTech II BACnet Communication Module Ethernet/IP
Installation & Maintenance Manual IM703-1 Group: McQuay Controls Date: November 2001 MicroTech II BACnet Communication Module Ethernet/IP ASHRAE 135, Annex J 10 BASE-T 2001 McQuay International Contents
More informationMicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 967 Group: Controls Part Number: IM 967 Date: October 2009 Supercedes: New MicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP) Pathfinder
More informationMicroTech II TM Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet TM Communication Module BACnet/IP
Installation and Maintenance Manual IM 703-3 Group: Controls Part Number: IM 703-3 Date: November 2004 Supersedes: IM 703-2 MicroTech II TM Applied Rooftop Unit Controller and Self-Contained Unit Controller
More informationMagnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)
Installation and Maintenance Manual IM 963 Group: Controls Part Number: IM 963 Date: April 2010 Supercedes: New Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet) Daikin
More informationMicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 852-2 Group: Controls Part Number: IM 852 Date: January 2008 Supercedes: IM 852-1 MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module
More informationMicroTech III Rooftop and Self Contained Unit Controller BACnet IP Communication Module
Installation and Maintenance Manual IM 916-2 Group: Controls Part Number: IM 916 Date: October 2009 Supercedes: IM 916-1 MicroTech III Rooftop and Self Contained Unit Controller BACnet IP Communication
More informationMicroTech III Chiller Unit Controller BACnet IP Communication Module
Installation and Maintenance Manual IM 966 Group: Controls Part Number: IM 966 Date: October 2009 Supercedes: New MicroTech III Chiller Unit Controller BACnet IP Communication Module Pathfinder Chiller,
More informationMicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP
Installation and Maintenance Manual IM 853 Group: Controls Part Number: IM 853 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet
More informationLONWORKS Plug-In Software
Installation and Maintenance Manual IM 933 Group: McQuay Controls Part Number: IM 933 Date: September 2008 Supercedes: New LONWORKS Plug-In Software For use with the MicroTech III Unitary Controller -
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS BACnet Communication Card RXRX-AY01 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
More informationBACnet VAV Actuator Start-up Guide IM 1040
BACnet VAV Actuator Start-up Guide IM 1040 Group: Controls Part Number: IM 1040 Date: 3/4/2010 Supersedes: New BACnet VAV Actuator--Electronic Output Start-up Procedures 2010 McQuay International Table
More informationBCM. MicroTech II Chiller Unit Controller BACnet Communication Module. Installation and Maintenance Manual IM ASHRAE 135, MCQ Rev.
Installation and Maintenance Manual IM 736-0 Part No: 736015423 Group: McQuay Controls Date: January 2003 MicroTech II Chiller Unit Controller BACnet Communication Module ASHRAE 135, 2001 WSC Water-Cooled
More informationInstallation and Maintenance Manual IM 966-3
Installation and Maintenance Manual IM 966-3 Group: Controls Part Number: IM 966 Date: March 2017 MicroTech III Chiller BACnet IP Communication Module Models AGZ and AMZ Trailblazer Air-Cooled Scroll Chiller
More informationInstallation and Maintenance Manual IM 969-5
Installation and Maintenance Manual IM 969-5 Group: Controls Part Number: IM 969 Date: January 2018 MicroTech III Chiller Unit Controller Modbus Communication Module Models AGZ and AMZ Trailblazer Air-cooled
More informationInstallation and Maintenance Manual IM 963-2
Installation and Maintenance Manual IM 963-2 Group: Controls Part Number: IM 963 Date: March 2017 Daikin Magnitude Chiller BACnet Networks (MS/TP, IP, Ethernet) Communication Module Model WME Magnetic
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS LonWorks Communication Card RXRX-AY02 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
More informationMicroTech II Chiller Unit Controller LonWorks Communication Module
Installation and Maintenance IM 735-1 Group: Controls Part Number: IM 735 Date: May 2005 Supersedes: IM735-0 MicroTech II Chiller Unit Controller LonWorks Communication Module WSC Water-Cooled Centrifugal,
More informationMicroTech Modem Kit. Installation & Maintenance Data IM 682. Group: Controls Part Number: Date: October, 1996.
Installation & Maintenance Data IM 682 Group: Controls Part Number: 629976 Date: October, 1996 MicroTech Modem Kit Telephone Line Modem Controller cns no. a0006 1996 McQuay International Contents Contents...2
More informationInstallation and Maintenance Manual IM
Installation and Maintenance Manual IM 1084-2 Group: WSHP Part Number: 910167578 Date: July 2015 MicroTech III Boilerless System Kit for use with all MicroTech III Controlled Water Source Heat Pumps Description
More informationMicroTech II Chiller Unit Controller BACnet Communication Module
Installation and Maintenance Manual IM 736-2 Group: Controls Part Number: IM 736 Date: November 2005 Supercedes: IM 736-1 MicroTech II Chiller Unit Controller BACnet Communication Module WSC WDC WPV HSC
More informationMicroTech 2000 Water Source Heat Pump Unit Controller
Installation Manual IM 660-4 Group: Controls Part Number: IM 660 Date: June 2012 Supersedes: IM 660-3 MicroTech 2000 Water Source Heat Pump Unit Controller NOTICE Use this manual to physically install
More informationInstallation and Maintenance Manual IM 966-4
Installation and Maintenance Manual IM 966-4 Group: Controls Part Number: IM 966 Date: January 2018 MicroTech III Chiller Unit Controller BACnet IP Communication Module Models AGZ and AMZ Trailblazer Air-cooled
More informationMicroTech II McQuay Chiller Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 906 Group: Controls Part Number: IM 906 Date: February 2008 Supersedes: New MicroTech II McQuay Chiller Unit Controller BACnet Communication Module (MS/TP) WSC WDC
More informationInstallation and Operation Manual IM
Installation and Operation Manual IM 1005-4 MicroTech III Unit Controller Remote User Interface Group: Controls Part Number: IM 1005 Date: January 2018 RoofPak Singlezone Heating and Cooling Units, Models
More informationMicroTech II Daikin Chiller Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 906-2 Group: Controls Part Number: IM 906 Date: December 2010 Supersedes: IM 906-1 MicroTech II Daikin Chiller Unit Controller BACnet Communication Module (MS/TP)
More informationMicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers
Engineering Data ED15080-1 Group: Controls Date: June 2002 MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers Alerton BACtalk Building
More informationMicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers
Engineering Data ED 15080-2 Group: Controls Part Number: ED 15080 Date: April 2006 Supercedes: ED 15080-1 MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained
More informationInstallation and Maintenance Manual IM Replacement Intelligent Equipment Gateway
Installation and Maintenance Manual IM 1229 Group: Controls Replacement Intelligent Equipment Gateway Commercial Rooftop Models: DPS and MPS Applied Rooftop Models: RDS and RPS Part Number: 910159718 Date:
More informationMicroTech II Remote I/O Panel Installation Manual
MicroTech II Remote I/O Panel Installation Manual Installation Manual IM 783-2 Group: Controls Part Number: IM 783 Date: November 2006 Supersedes: IM 783-1 Table of Contents Notice... 3 Reference Documents...
More informationOM Operation and Maintenance Manual. Intelligent Equipment for Daikin Applied Trailblazer Air-cooled Scroll Chiller. Models: AGZ-D and AGZ-E
Operation and Maintenance Manual Intelligent Equipment for Daikin Applied Trailblazer Air-cooled Scroll Chiller OM 1241 Group: Controls Part Number: 910166134 Date: June 2015 Models: AGZ-D and AGZ-E Table
More informationInstallation and Maintenance Manual IM
Installation and Maintenance Manual IM 1229-1 Group: Controls Replacement Intelligent Equipment Gateway Commercial Rooftop Models: DPS and MPS Applied Rooftop Models: RDS and RPS Part Number: 910159718
More informationMicroTech II TM Remote I/O Panel Installation Manual
Installation Manual IM 783-0 MicroTech II TM Remote I/O Panel Installation Manual Group: Controls Part Number: IM 783-0 Date: February 2004 Supersedes: New 2004 McQuay International Page 2 IM-783 Table
More informationInstallation and Maintenance Manual IM 968-4
Installation and Maintenance Manual IM 968-4 Group: Controls Part Number: IM 968 Date: January 2018 MicroTech III Chiller Unit Controller LonWorks Communication Module Models AGZ and AMZ Trailblazer Air-cooled
More informationMicroTech II Chiller Unit Controller BACnet Communication Module, Ethernet or IP
Installation and Maintenance Manual IM 837 Group: Controls Part Number: IM 837 Date: June 2006 Supercedes: New MicroTech II Chiller Unit Controller BACnet Communication Module, Ethernet or IP WSC Water-Cooled
More informationInstallation and Operations Manual IOM
Installation and Operations Manual IOM 1135-2 MicroTech III I/O Manager Group: Controls Part Number: IOM 1135 Date: February 2015 Supercedes: IOM 1135-1 For use with Daikin MicroTech Integrated System
More informationCOMFORT CONTROL CENTER SERVICE INSTRUCTIONS
USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516 574-294-2511 CANADA Dometic Corporation 46 Zatonski, Unit 3 Brantford, ON N3T 5L8 CANADA 519-720-9578 For Service Center
More informationResolver to Digital Expansion Board
Resolver to Digital Expansion Board Catalog No. EXB009A01 Installation and Operating Manual 6/98 MN1313 Table of Contents Section 1 General Information............................. 1-1 Introduction....................................
More informationETM-2050/ETM-2051 Service Manual
Introduction Novar s Electronic Thermostat Modules (ETMs) are intelligent control modules that provide local, direct digital control of unitary, packaged, staged HVAC systems. This document: Describes
More informationObsolete. BR Series USB Tech Kit. B l u e R i d g e. T e c h n o l o g i e s. User Guide. Page 1. Hardware and Software Instructions
Hardware and Software Instructions Page 1 Attention Page 2 This section serves as a notice of the immediate or potential dangers involved when working with the equipment described throughout this manual.
More information3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions
3710 ACM 3750 PDC 3800 RTU ISOCOM Communications Card Retrofit Instructions Danger During normal operation of this device, hazardous voltages are present which can cause severe injury or death. These
More informationInstalling and Configuring Rialto Analytic Appliances
Installing and Configuring Rialto Analytic Appliances Important Safety Information This manual provides installation and operation information and precautions for the use of this camera. Incorrect installation
More informationGROUND FAULT TESTER, A , -02, & -03) (PART OF SEAR II ACCESSORY GROUP)
USER'S GUIDE GROUND FAULT TESTER, A80297-01, -02, & -03) (PART OF SEAR II ACCESSORY GROUP) MARCH 2004 (REVISED JUNE 2014) DOCUMENT NO. SIG-00-03-05-003 VERSION B.3 Siemens Industry, Inc., Rail Automation
More informationINSTRUCTION MANUAL DISTRIBUTION UNIT. Please read this manual thoroughly before use, and keep it handy for future reference.
INSTRUCTION MANUAL DISTRIBUTION UNIT Please read this manual thoroughly before use, and keep it handy for future reference. ISSUE 1 May 2006 LIMITATION OF LIABILITY THE INFORMATION IN THIS PUBLICATION
More informationUser Guide CPSMP VAC Power Supply Module: PointSystem CPSMC Accessory CPSMC Accessory. Contents.
User Guide CPSMP-205 110 240 VAC Power Supply Module: PointSystem CPSMC1800-200 Accessory CPSMC1900-100 Accessory Contents Contents...1 Description...1 Cautions and Warnings...2 Definitions...2 Power supply
More informationAC300/AC400 SERIES DYNAMIC BRAKING and ADDITIONAL FORM C RELAY. INSTALLATION INSTRUCTIONS Document Number:
Minarik Variable Speed AC Motor Drives AC300/AC400 SERIES DYNAMIC BRAKING and ADDITIONAL FORM C RELAY INSTALLATION INSTRUCTIONS Document Number: 250-0297 These instructions apply to models rated: 7.5 25
More informationMicroTech II Vertical Self-contained Systems Unit Controller
Installation and Maintenance IM-710 Group: Applied Systems Part Number: IM710 Date: February 2002 MicroTech II Vertical Self-contained Systems Unit Controller Used with McQuay models: SWP and SWT BACK
More informationAE R6 July 2018 Electronic Unit Controller
July 2018 Electronic Unit Controller TABLE OF CONTENTS Safety... 3 Safety Instructions... 3 Safety Icon Explanation... 3 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons...
More informationOperations Manual OM
Operations Manual OM 1254-1 Daikin System Manager Group: Controls Part Number: OM 1254 Date: February 2017 Use with Daikin Intelligent Systems Table of Contents Introduction.... 3 Revision History...3
More informationFX-2 Control Board ASY-360-XXX Setup and Configuration Guide
FX-2 Control Board ASY-360-XXX Setup and Configuration Guide Micro Air Corporation Phone (609) 259-2636 124 Route 526. WWW.Microair.net Allentown NJ 08501 Fax (609) 259-6601 Table of Contents Introduction...
More informationBluetooth Shielding Instructions
Mac mini 2012 Bluetooth Shielding Instructions 1 INTRODUCTION 1.1 STATIC PRECAUTIONS 1.2 TOOLS REQUIRED 2 DISASSEMBLY 3 SHIELDING 4 FAQ 4.1 FAQ 5 CUSTOMER SERVICE 5.1 Before Contacting Customer Service
More informationPhase Loss Protection Upgrade. Phase Loss Protection Upgrade. In this bulletin:
Phase Loss Protection Upgrade In this bulletin: Introduction... 2 Purpose... 2 General... 2 Applicability... 2 HD3070 Phase Loss Protection Upgrade Kit Parts... 2 Preparation... 4 Install the Phase Loss
More information4170 POS System Installation Guide
4170 POS System 4170 Installation Guide Thank you for selecting UTC RETAIL s innovative Model 4170 Point of Sale solution! This Installation Guide will help you efficiently install the 4170 POS. The document
More informationCOOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN
Voltage Regulators MN225074EN Effective March 2017 Supersedes January 2012 (S225-40-7) RS-485 digital communications accessory board installation and operation instructions COOPER POWER SERIES DISCLAIMER
More informationMaverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE , BACnet
Engineering Data ED 15126 Group: Controls Part Number: ED 15126 Date: April 2010 Supersedes: New Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement
More informationSER8300 Series Line Voltage Room Controller with Optional PIR Sensor Installation Guide
Line Voltage Room Controller with Optional PIR Sensor Commercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 3 Location 3 Installation 3 Terminal, Identification and Function 4 Communication
More informationand Network Interface Modules Installation Instructions
4010-9817 and 4010-9821 Network Interface Modules Installation Instructions Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the
More informationChapter 2. Installing the Chapter 2. Contents
Contents Chapter 2 Installing the 3512 Overview... 2-2 Unpacking... 2-2 Telephone Equipment... 2-3 Customer-Provided Telephone Equipment... 2-3 Telephone Company Procedures and Regulatory Requirements...
More informationEncoder Firmware V User s Manual. Outdoor PTZ Camera Hardware Manual KCM /05/09.
Encoder Firmware V4.06.09 User s Manual Outdoor PTZ Camera Hardware Manual KCM-8211 2013/05/09 1 Table of Contents Precautions... 3 Introduction... 4 List of Models... 4 Package Contents... 5 Safety Instructions...
More informationHES-3109 SERIES 9 PORTS 10/100/1000BASE-T MANAGEMENT ETHERNET SWITCH
HES-3109 SERIES 9 PORTS 10/100/1000BASE-T MANAGEMENT ETHERNET SWITCH 8 PORTS 10/100/1000BASE-T MANAGEMENT ETHERNET SWITCH WITH 1 PORT 1000BASE-X UPLINK OR 1 PORT 100/1000BASE-X UPLINK 8 PORTS 10/100/1000BASE-T
More informationHomePro ZRF113. Z-Wave Radio Frequency (RF) Controlled, 120 VAC, Isolated Contact Fixture Module, Series 200, Release 2.2
RF Home Automation ZRF113 Z-Wave Radio Frequency (RF) Controlled, 120 VAC, Isolated Contact Fixture Module, Series 200, Release 2.2 Note: This module must be Included in the Network only where it will
More informationBACnet MS/TP Interface User s Guide
PoolPak MPK with CommandPak Control System CPCS BACnet MS/TP Interface User s Guide DOCUMENT #: SVW07-BACNET-MSTP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak
More informationFX-2 Control Board ASY-360-XXX Setup and Configuration Guide
FX-2 Control Board ASY-360-XXX Setup and Configuration Guide Micro Air Corporation Phone (609) 259-2636 124 Route 526. WWW.Microair.net Allentown NJ 08501 Fax (609) 259-6601 Table of Contents Introduction...
More informationDTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A
DTS 310 DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter Page 1 1 PRODUCT OVERVIEW... 3 1.1 SUPPLIED ITEMS... 3 1.2 DOCUMENT CONVENTIONS... 4 1.3 PRODUCT SPECIFICATION... 4 1.3.1 Current
More informationUNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN
1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,
More informationInstallation Manual. Model: HILU Ultra HD Interactive Flat Panel Display
Installation Manual Model: HILU750 '' Ultra HD Interactive Flat Panel Display QUICK SETUP GUIDE For further information, see the User Manual. Please contact HITACHI directly if you have questions on the
More informationSER8300 Series Line Voltage Room Controller with Optional PIR Sensor Installation Guide
Line Voltage Room Controller with Optional PIR Sensor Commercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 3 Location 3 Installation 3 Terminal, Identification and Function 4 Communication
More informationKvaser Linx J1587 User's Guide
Kvaser Linx J1587 User's Guide Copyright 2007-2011 Kvaser AB, Mölndal, Sweden http://www.kvaser.com Last updated Thursday, 28 April 2011 We believe that the information contained herein was accurate in
More informationSigma DeviceNet Tool Change Systems USER S GUIDE Rev 05
Sigma DeviceNet Tool Change Systems USER S GUIDE 94018 Rev 05 648 Saratoga Road Glenville, NY 12302 USA Phone: 518 384 1000 Fax 518 384 1200 www.arobotics.com 1. PRECAUTIONS 1 Sigma DNET Module 1 2.0 DNET
More informationrcc.1081 Installation Instructions
rcc.1081 Installation Instructions Table of Contents Introduction...1 Specifications...2 Mounting...3 Wiring...5 Wiring Method...7 BACnet Network Wiring...8 Setting BACnet Address...9 Setting the BACnet
More informationAURA SSD FOR MAC PRO. Installation Guide
AURA SSD FOR MAC PRO Installation Guide CONTENTS Introduction... 1 1.1 System Requirements 1.2 Package Contents 1.3 About This Manual Installation... 2 2.1 Preparing the Mac Pro 2.2 Installing the Aura
More informationPro-Star AVW200 Installation and Operation Manual Protel, Inc. ALL RIGHTS RESERVED AVW200HM01.1
Pro-Star AVW200 Installation and Operation Manual 2005 Protel, Inc. ALL RIGHTS RESERVED AVW200 Installation and Operation Manual Revision History Revision Date Description of Changes AVW200HM01.0 12/05
More informationMicroprocessor Module Replacement Kit for Multi-Zone Leak Monitors Instruction Manual
621 Hunt Valley Circle New Kensington, PA 15068 3015-5547 Tel: 724-334-5000 Revision 4 Fax: 724-334-5001 May 17, 2013 Microprocessor Module Replacement Kit for Multi-Zone Leak Monitors Instruction Manual
More informationMODELS DSH/DSV R-410A AIR SIDE ECONOMIZER KIT
MODELS DSH/DSV R-410A AIR SIDE ECONOMIZER KIT Form 145.11-IOM1 (412) AIR SIDE ECONOMIZER FOR DSH AND DSV R-410A AIR COOLED AIR CONDITIONING UNITS INSTALLATION INSTRUCTIONS B Style IMPORTANT! READ BEFORE
More informationSAS JBOD Installation Reference Guide Revision 1.0
SAS JBOD 16-bay Rackmount Enclosure Installation Reference Guide Revision 1.0 P/N: PW0020000000281 Copyright No part of this publication may be reproduced, stored in a retrieval system, or transmitted
More informationMicroTech II BACnet Communication Module Configuration Tool for McQuay Maverick II Rooftop Unit Controllers
Users Manual UM 855 Group: Controls Part Number: UM 855 Date: June 2007 Supersedes: New MicroTech II BACnet Communication Module Configuration Tool for McQuay Maverick II Rooftop Unit Controllers Commercial
More informationMODELS DSH/DSV R-410A AIR SIDE ECONOMIZER KIT
MODELS DSH/DSV R-410A AIR SIDE ECONOMIZER KIT Form 145.11-IOM1 (412) AIR SIDE ECONOMIZER FOR DSH AND DSV R-410A AIR COOLED AIR CONDITIONING UNITS INSTALLATION INSTRUCTIONS B Style IMPORTANT! READ BEFORE
More informationInstallation- and Operating instructions for CU Ethernet Controller with USB Input. Version: 1.4 Date:
Installation- and Operating instructions for CU8880-0010 Ethernet Controller with USB Input Version: 1.4 Date: 2018-04-12 Table of contents Table of contents 1. 2. 3. 4. 5. General instructions 2 Notes
More informationSPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS
SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS (WITH CAPACITOR CHARGER BOARD A3517-02) The process depends on Generator and System configuration. This document applies to installation of Capacitors
More information3-Phase, Dual-Input 6-Slot Power Supply System STARTUP GUIDE
3-Phase, Dual-Input 6-Slot Power Supply System STARTUP GUIDE -ST-01 Page 1 of 10 November 2016 2016 Copyright Lite-On Technology Corporation ALL RIGHTS RESERVED. Lite-On is a trademark of Lite-On Technology
More informationMANUAL INSTALLATION. Multi-Variable Monitor. MVM Series. Issue Date: 02/07/ Price Industries Limited. All rights reserved.
MANUAL INSTALLATION Multi-Variable Monitor MVM Series Issue Date: 02/07/18 2018 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview General...1 MVM Specifications...1 Included
More informationSidewinder Pumps Inc. AC Timer/Controller
Sidewinder Pumps Inc. AC Timer/Controller Page 1 of 12 Rev 032417 Table of Contents 1. Warnings-------------------------------------------------------------------------------------------------- 3 1.1.
More informationMicroTech Unit Ventilator Controller
Installation & Maintenance Data IM 613-1 MicroTech Unit Ventilator Controller Group: Unit Ventilator Part No.: 106102101 Date: July 1999 Used with AAF-HermanNelson Models AVS, AVV, AVR, AHF, AHV, AHR,
More informationPerle MCR200 Installation Guide
Perle MCR200 Installation Guide P/N 5500322-10 Introduction The Perle MCR200 Chassis is a 2 slot chassis able to accommodate up to 2 Perle Media Converter modules or 1 Media Converter Module and an MCR-MGT
More informationContent. Product Description
EY-modulo 4 EY-RU482F001 Room Operating Unit with Display for Fan Coil applications EY-RU483F001 Room Operating Unit with Display for VAV applications en Guidelines for the electrician Content 1 Product
More informationAM3517 experimenter Kit. QuickStart Guide O
AM3517 :: :: O M QuickStart Guide www.logicpd.comz O QuickStart Guide We fast forward the evolution of new products. Table of Contents 1 Introduction 4 1.1 Scope of Document 4 1.2 Zoom AM3517 Contents
More informationTABLE OF CONTENTS INTRODUCTION...1 DEVICE SETUP...4 SUPPORT RESOURCES...9
TABLE OF CONTENTS INTRODUCTION...1 1.1 Minimum System Requirements 1.2 Package Contents 1.3 About This Manual 1.4 Rear View 1.4.1 Rear Features 1.5 Usage Notes DEVICE SETUP...4 2.1 Quick Start 2.2 Assembly
More informationCSM200 Expansion Tray
CSM200 Expansion Tray Initial Setup Guide for SANtricity users or VTL environments EC1718-1-E3, Third Edition Proprietary Rights Notice This document contains proprietary information of LSI Logic Corporation
More informationUser s Manual. 8-channel MPEG-4 1U Video Encoder ACD Ver
8-channel MPEG-4 1U Video Encoder ACD-2300 User s Manual Ver.080331 0 0 PRECAUTIONS 1. Read these instructions All the safety and operating instructions should be read before the product is operated.
More informationNMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02
1/8 NRK16/A, NRK16-B/A, (NRK16-T /A, NRK14-T /A, NRK16-WEB/A) Control and interlock devices with pre-programmed system-specific application modules The controllers may be used as stand-alone control and
More informationFX14 Field Controller
Product Bulletin FX14 Field Controller Issue Date January 22, 2010 FX14 Field Controller The FX14 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,
More informationEmbedded Navigation Solutions VN 100, VN 200 & VN 300 Development Board User Manual
Embedded Navigation Solutions VN 100, VN 200 & VN 300 Development Board User Manual VectorNav Technologies Contact Info 10501 Markison Road Phone +1 512 772 3615 Dallas, Texas 75238 Email support@vectornav.com
More informationOWC Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE
OWC Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Apple Mac Requirements 1.1.2 PC Requirements 1.1.3 Supported PCIe Cards 1.2
More informationCOOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN
Voltage Regulators MN225067EN Effective November 2016 Supersedes June 2014 (S225-70-13) COOPER POWER Input/Output (I/O) module installation instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF
More information