MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module MS/TP

Size: px
Start display at page:

Download "MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module MS/TP"

Transcription

1 Installation and Maintenance Manual IM Group: Controls Part Number: IM 704 Date: August 2007 Supersedes: IM MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module MS/TP NOTICE Use this manual to physically install the McQuay MicroTech II Communication Module into the rooftop unit controller and connect the rooftop unit controller to your network. Use the appropriate McQuay Engineering Data (ED), known as the Protocol Information document, to integrate the unit into your network. The Protocol Information document contains addressing details, BACnet protocol information, and a list of the data points available to the network. See the Reference Documents section of this manual for Protocol Information document numbers. MicroTech II control integration literature is available from your local McQuay International sales representative and McQuay International

2 Contents Figures... 2 Revision History... 3 Reference Documents... 3 Limited Warranty... 3 INTRODUCTION... 4 Recognize Safety Symbols, Words and Labels... 4 GENERAL INFORMATION... 5 DESCRIPTION... 5 APPLICATION... 6 COMPONENT DATA... 6 Light Emitting Diodes (LEDs)... 7 BACnet MS/TP Network Connector (P1)... 7 Address Switch Pin Header... 7 INSTALLATION AND NETWORK CONNECTION... 8 General... 8 Required Equipment... 8 Installing a new BACnet MS/TP Communication Module... 8 Connecting the BACnet/IP Communication Module to the Network: Applied Rooftop Units... 8 Connecting the BACnet/IP Communication Module to the Network: Self-Contained Units... 9 Replacing a BACnet MS/TP Communication Module... 9 Connecting a BACnet MS/TP Communication Module to the Network... 9 INTEGRATION NETWORK CONNECTION BACnet MS/TP Network Addressing CONFIGURING THE UNIT CONTROLLER Factory-Installed BACnet MS/TP Communication Modules Field-Installed BACnet MS/TP Communication Modules Important Notes SERVICE INFORMATION TROUBLESHOOTING REPLACEMENT PARTS Figures Figure 1. BACnet MS/TP Communication Module... 5 Figure 2. Building Automation System... 6 Figure 3. BACnet MS/TP Communication Module Major Components... 6 Figure 4. BACnet MS/TP Communication Module Mounted on the Unit Controller s Main Control Board Figure 5. Mount BACnet MS/TP Communication Module Figure 6. BACnet MS/TP Connection Schematic Diagram Figure 7. BACnet MS/TP Network Cable Routing, Applied Rooftop Units Figure 8. BACnet MS/TP Network Cable Routing, Self-Contained Units IM704-4

3 Revision History IM 704 IM IM IM November 2004 Initial release IM August 2007 Updated IP router address on Table 1. Minor formatting. Reference Documents Number Title Company Source IM696 MicroTech II Applied Rooftop Unit Controller Installation Manual McQuay International OM137 MicroTech II Applied Rooftop Discharge Air Controller Operation Manual McQuay International OM138 MicroTech II Applied Rooftop Space Comfort Controller Operation Manual McQuay International IM710 MicroTech II Vertical Self-Contained Unit Controller Installation Manual McQuay International OM711 MicroTech II Vertical Self-Contained Discharge Air Controller Operation Manual McQuay International OM712 MicroTech II Vertical Self-Contained Space Comfort Controller Operation Manual McQuay International ED15060 MicroTech II Protocol Information Data for McQuay International Applied Rooftop Units McQuay International ED15061 MicroTech II Protocol Information Data for McQuay International Self-Contained Units McQuay International E LonMark Layers 1-6 Interoperability Guidelines, Version 3.0 LonMark Interoperability Assoc E LonMark Application Layer Interoperability Guidelines, Version 3.2 LonMark Interoperability Assoc _10 LonMark Functional Profile: Space Comfort Controller, Version 1.0 LonMark Interoperability Assoc _10 LonMark Functional Profile: Discharge Air LonMark Interoperability G Controller, Version LONWORKS FTT-10A Free Topology Transceiver Users Guide Assoc. Echelon Corporation Limited Warranty Consult your local McQuay Representative for warranty details. Refer to Form Y. To find your local McQuay Representative, go to Notice Copyright 2007 McQuay International, Minneapolis MN. All rights reserved throughout the world. McQuay International reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this software is appropriate for his or her application. The following are tradenames or registered trademarks of their respective companies. BACnet from the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.; LONWORKS and LONMARK from Echelon, Inc.; Windows from Microsoft Corporation; McQuay and MicroTech II from McQuay International. IM

4 Introduction Recognize Safety Symbols, Words and Labels The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the owner and installer s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of property damage and/or product damage, serious personal injury or death. Improper installation, operation and maintenance can void the warranty.! CAUTION Hazards or unsafe practice CAN result in property damage, product damage, severe personal injury and or death. NOTICE Hazards or unsafe practices, which CAN result in property, damage, product damage, and or personal injury. IM

5 General Information This manual contains the information you need to install the MicroTech II Communication Module for BACnet MS/TP and connect it to a BACnet network.! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded. Connections and service to the MicroTech II control panel must be performed only by personnel who are knowledgeable in the operation of the equipment being controlled.! CAUTION Static sensitive components. Can cause equipment damage. Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work. Never unplug cables, circuit board terminal blocks, or power plugs while power is applied to the panel. NOTICE This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his or her own expense. McQuay International disclaims any liability resulting from any interference or for the correction thereof. Description A MicroTech II BACnet MS/TP Communication Module incorporates a MicroTech II rooftop or self-contained unit controller into a BACnet MS/TP Local Area Network (LAN). It supports the BACnet MS/TP (EIA 485) data link layer (physical layer.) It is the interface to the Building Automation Network using BACnet objects. The BACnet MS/TP Communication Module is a printed circuit board that plugs onto the MicroTech II unit controller s main control board. Figure 1 shows an outline drawing of the BACnet MS/TP Communication Module. Figure 1. BACnet MS/TP Communication Module IM

6 Application The MicroTech II BACnet MS/TP Communication Module connects the MicroTech II applied rooftop or self-contained unit controller to the building automation system (BAS) via BACnet MS/TP LAN. It is the interface adapter for the exchange of BACnet objects between the network and the unit controller. Figure 2 shows the BACnet MS/TP Communication Module and unit controller integrated into a BAS. Figure 2. Building Automation System BACnet MSTP Network MicroTech II Main Control Board BACnet MSTP Communications Module MicroTech II Keypad Component Data Figure 3 shows the location of the major components of the BACnet MS/TP Communication Module. Figure 3. BACnet MS/TP Communication Module Major Components Network Connector Plug + _ P1 SG Transmit LED DS2 Receive LED DS1 Address Switch SW1 12 Pin Header 6 IM704-4

7 Light Emitting Diodes (LEDs) The MicroTech II BACnet MS/TP Communication Module has two LEDs to indicate communication activity and status of the communication module. LED DS1 DS2 Function Lights when the BACnet MS/TP Communication Module is receiving data Lights when the BACnet MS/TP Communication Module is transmitting data BACnet MS/TP Network Connector (P1) The P1 connector connects the MicroTech II BACnet MS/TP Communication Module to the BACnet MSTP network. Pin Designation Connection Function 1 REF TB2-130 Reference 2 N2- TB2-129 Inverting Input 3 N2+ TB2-128 Non-inverting Input Address Switch The Address Switch, SW1, must be set to the MAC address of the BACnet MS/TP Communication Module. The valid range is 0 to Pin Header The 12-pin header, J1, connects the unit controller to the BACnet MS/TP Communication Module through the bottom of the BACnet MS/TP Communication Module. IM

8 Installation and Network Connection General A BACnet MS/TP Communication Module can be factory or field-installed and can be purchased by itself or as a kit. The BACnet MS/TP Communication Module, cable harness, and this installation manual are available as a kit (see the Replacement Parts section for details). The following section describes how to install a new BACnet MS/TP Communication Module or replace an existing module. It also describes how to connect the BACnet MS/TP Communication Module it to a BACnet network. The BACnet MS/TP Communication Module mounts on connector pins and is held in place with four plastic locking standoffs. The BACnet MS/TP network connects to the BACnet MS/TP Communication Module at the network connector plug, P1. The BACnet MS/TP network cable connects TB2 in the unit cabinet. Required Equipment Field installation/replacement and network connection requires the following: A BACnet MS/TP Communication Module (included in kit) Cable harness (included in kit) Shielded, twisted pair pigtail wire and plug for network connection Small, straight-blade screwdriver Installing a new BACnet MS/TP Communication Module Note: A MAC (Media Access Control) address must be assigned to the BACnet MS/TP Communication Module. See your network administrator. 1. Remove power from the unit controller. 2. Remove the network cable plug-in connector terminal block in P1 (see Figure 3.) 3. Locate the empty connector and four standoffs for the BACnet MS/TP Communication Module on the unit controller s main control board (see Figure 4.) 4. Orient the BACnet MS/TP Communication Module printed circuit board so that the side with the components faces out and connector pins can penetrate the 12-Pin Header on the BACnet MS/TP Communication Module. 5. Push the BACnet MS/TP Communication Module onto the connector pins and standoffs until you hear the faint click of the locking standoffs securing the board in place. Connecting the BACnet/IP Communication Module to the Network: Applied Rooftop Units 1. Connect the MS/TP BACnet MS/TP Communication Module to the network with wire harness (see Figure 6). 2. Connect the cable harness clear wire (No. 522) to the N2+ terminal of the P1 connector plug and connect the black wire (No. 523) to the N2 terminal of the P1 connector plug. Note: You must maintain the polarity of the signal throughout the network. Always connect + to + and to. 3. Connect the cable harness drain wire (No. 524) to one of DRN terminals on TB6. 4. Route the cable harness down to the shelf below the unit controller and to the left along the shelf to the edge. 5. Route the cable through a hole down the cable raceway to Terminal Block TB2 (see Figure 7.) 6. Connect the cable harness clear wire (No. 522) to terminal 128 of TB2 and connect the black wire (No. 523) to terminal 129 of TB2. Note: You must maintain the polarity of the signal throughout the network. Always connect + to + and to. 8 IM704-4

9 Connecting the BACnet/IP Communication Module to the Network: Self-Contained Units 1. Connect the BACnet MS/TP Communication Module to the network with cable harness (see Figure 6). 2. Connect the cable harness clear wire (No. 522) to the N2+ terminal of the P1 connector plug and connect the black wire (No. 523) to the N2 terminal of the P1 connector plug. 3. Connect the cable harness drain wire (No. 524) to one of the DRN terminals on TB7. Note: You must maintain the polarity of the signal throughout the network. Always connect + to + and to. 4. Route the cable harness down and over to your right along the main control board and up to Terminal Block TB2 (see Figure 8.) 5. Connect the cable harness clear wire (No. 522) to terminal 128 of TB2 and connect the black wire (No. 523) to terminal 129 of TB2. Note: You must maintain the polarity of the signal throughout the network. Always connect + to + and to. 6. Connect the BACnet MS/TP network cable to TB 2 terminals 128, 129, and Set the MAC Address in Address Switch SW1 (assigned by the network administrator.) The valid range is 0 to Apply power to the unit controller. Note: Terminal 130 of TB 2 is provided as a common connection point for the shield of the network cable. The shield must be continuous throughout the entire network cable and must be connected to earth ground at one and only one point. The BACnet MS/TP network must be terminated at each end with a 120 ohm resistor between the + and - terminals Replacing a BACnet MS/TP Communication Module 1. Remove power from the unit controller. 2. Record the MAC Address set in Address Switch SW1. 3. Remove the network cable plug-in connector terminal block P1 (see Figure 3.) 4. Locate the four standoffs for the BACnet MS/TP Communication Module in the unit controller s main control board (see Figure 4.) 5. Use a pliers or screwdriver to depress the barb on one standoff and gently pull the corner of the BACnet MS/TP Communication Module over the barb. Do not bend the BACnet MS/TP Communication Module or misalign the connector pins. 6. Proceed to the other three corners, remove the BACnet MS/TP Communication Module from each standoff, and pull the module over the standoffs. 7. Gently lift the BACnet MS/TP Communication Module from the unit controller. 8. Locate the empty connector pins and four standoffs for the BACnet MS/TP Communication Module in the unit controller (see Figure 4.) 9. Orient the BACnet MS/TP Communication Module so that the component side faces out and the connector pins can penetrate the 12-Pin Header on the BACnet MS/TP Communication Module (see Figure 5.) 10. Push the BACnet MS/TP Communication Module onto the connector pins and standoffs until you hear the faint click of the locking standoffs securing the module in place. Connecting a BACnet MS/TP Communication Module to the Network 1. Replace network cable plug in P1 (see Figure 3.) 2. Reconnect the network to TB 2 terminals 128, 129, and 130 if it is necessary. 3. Set the MAC Address in Address Switch SW1 (see Step 2.) 4. Apply power to the unit controller. IM

10 Figure 4. BACnet MS/TP Communication Module Mounted on the Unit Controller s Main Control Board Main Control Board Network Connector Plug 12-Pin Header Location of Standoff (4 places) 10 IM704-4

11 Figure 5. Mount BACnet MS/TP Communication Module 12-Pin Header BACnet MSTP Communications Module Address Switch, SW1 Network Connector Plug LED Indicators Locking Stnadoff Standoff (4 Places) Figure 6. BACnet MS/TP Connection Schematic Diagram Unit Terminal Block TB2 BACnet MSTP Communication Module N2+ N2- REF TB6 (Applied Rooftop) TB7 (Self-Contained) DRN IM

12 REF Figure 7. BACnet MS/TP Network Cable Routing, Applied Rooftop Units TB6 Controller BACnet MSTP Communications Comunications Module Cable Shelf N2+ N2- BACnet MSTP Comm Card Network Cable Cable Raceway Terminal Block TB2 12 IM704-4

13 Figure 8. BACnet MS/TP Network Cable Routing, Self-Contained Units Controller BACnet MSTP Communications Coomunications Module Terminal Block TB2 Network Cable Harness TB7 IM

14 Integration Integrating the BACnet MS/TP Communication Module into a BAS involves three steps: Connecting the rooftop or self-contained unit controller to the network Addressing and establishing communications with the unit controller Configuring the unit controller Network Connection After inserting the BACnet/IP Communication Module to the MicroTech II unit controller, connect the MicroTech II unit controller into the BACnet network. You will need a straight-through ethernet cable connected to a hub (see the Installation and Network Connection section for details. BACnet MS/TP Network Addressing Follow these procedures to properly address and establish communications with the unit controller (see Table 1for details.) Verify that the MAC address of the unit controller is unique on the BACnet network Cycle power to the unit controller Change the data transmission rate, if necessary Change the default BACnet MS/TP Address The BACnet MS/TP device address (MAC) Address of the MicroTech II controller in a BACnet Master Slave/Token Passing (MSTP) Local Area Network (LAN) is set in an eight-position dipswitch on the BACnet MS/TP Communication Module (see Figure 3. BACnet MS/TP Communication Module Major Components.) The address is physically set in eight binary switches. Bit 0 of the address corresponds to switch position 1 and bit 7 of the address corresponds to switch position 8. All MicroTech II controllers must be master controllers; therefore, bit 7 is always equal to 0 (open). An open switch (switch up) is a 0, and a closed switch (switch down) is a 1. This address must be unique and is determined during installation. After you set the address in the switches, you must cycle power (turn the unit controller off and then on again) in order for the new address to take effect. The Receive LED flickers when the module is receiving data from the network, and the Transmit LED flickers when the module is sending data to the network. The default data transmission rate is set to 19,200 bps (baud). You can change the data transmission rate to 9600 or 38,400 bps. Refer to the MicroTech II Protocol Data Information Packet (See Reference Documents). The default BACnet MS/TP network address of the MicroTech II Unit Controller is You can change this address but it must be the same as all other BACnet devices on the network for devices to communicate with each other. Refer to the MicroTech II Protocol Data Information Packet (See Reference Documents section). Configuring the Unit Controller All Rooftop and Self-contained unit controllers are loaded with software and configured at the factory for stand-alone operation. The unit is ready to operate with default set point parameters that can be changed with the unit s keypad/display or via a network signal. Refer to the appropriate operation manual for the default values and keypad/display operating instructions. Refer to the appropriate MicroTech II Protocol Information documents for descriptions of the available network variables (see Reference Documents section). There are 12 communication parameters involved in setting up the unit controller for proper communication with the various communication module options (BACnet IP, BACnet MS/TP or LONWORKS ). These parameters are set differently by the factory depending on which communication module is ordered and shipped with the unit. Table 1 below lists the four possible sets of default parameter settings. Not all the parameters apply to all the communication module options. The entries in the table that are shown in bold font apply to a particular communication module option. Factory-Installed BACnet MS/TP Communication Modules If the rooftop or self-contained unit controller is equipped with a factory-installed BACnet MS/TP Communication Module, the controller is pre-configured with the values shown in Table 1. These parameters do not require field modification. 14 IM704-4

15 Field-Installed BACnet MS/TP Communication Modules A BACnet MS/TP Communication Module can be added to a rooftop or self-contained unit controller in the field for these reasons: The unit did not originally ship with a communication module. The unit originally shipped with a LONWORKS Communication Module but requires replacement with a BACnet Communication Module. Refer to Table 1 to determine whether or not changes are required to communication setup parameters. Note: McQuay MicroTech II ServiceTools software is required to modify these parameters. Call the McQuay Controls Customer Support group at 866-4MCQUAY for more information. Table 1. Factory Communication Setup Parameter Settings Parameter Name BACnet IP BACnet MSTP LON (DAC or SCC) No Communication Module lp Address IP Subnet Mask UDP Port Number IP Router Address IP Network Address MSTP Network Address MSTP MAC Address MSTP Baud Rate Communication Option None MSTP MSTP MSTP Device Instance Number 2 XXXXXX XXXXXX XXXXXX XXXXXX Max APDU Length Device Object Name 4 MTll RTUC XXXXXXXXX or MTII SCUC XXXXXXXXX MTll RTUC XXXXXXXXX or MTII SCUC XXXXXXXXX MTll RTUC XXXXXXXXX or MTII SCUC XXXXXXXXX MTll RTUC XXXXXXXXX or MTII SCUC XXXXXXXXX Important Notes 1. The BACnet MS/TP MAC Address is not adjustable from the MicroTech II ServiceTools; it is set via the dipswitch block on the MSTP communication module. 2. The Device Instance Number is factory set equal to the last six significant digits of the 18 digit number on the barcode label on the unit controller s main control board. For example, if the last six digits are , then the Device Instance Number is set to Whether or not this parameter is use by the systems integrator, it must be set to a unique value from all other controllers in the network. 3. The Max APDU Length parameter should not be set higher than 501 for BACnet MS/TP. 4. The Xs in Device Object Name are factory set equal to the last nine digits of the 18 digit number on the bar-code label on the unit controller s main control board. For example, if the last nine digits are , then the Device Object Name is set to MTII RTUC for an applied rooftop unit or MTII SCUC for a self-contained unit. Whether or not this parameter is use by the systems integrator, it must be set to a unique value from all other controllers in the network. IM

16 Service Information Troubleshooting If you can control the unit from the unit s keypad, but you are not able to communicate with unit via the network: Verify the network (bus) wiring. Verify the cable harness to the network terminals. Verify that the Transmit LED (DS2) is flickering. Verify that the MS/TP MAC address (SW1) is set in the range (Master). Check the network communication parameters in the unit controller for proper settings. Refer Configuring the Unit Controller section of this document for details. If the BACnet MS/TP Communication Module still does not respond, contact the McQuay Controls Customer Support group at 866-4McQuay ( ). Replacement Parts Contact the McQuay Parts group at for replacement parts related to the BACnet MS/TP Communication Module. McQuay does not supply the network connection plug. The three-contact network connection plug has custom graphics, but can be replaced with a standard network connector. The table below provides two manufacturers with the generic version of the network connection plug. Description Part Number Source BACnet MS/TP Communication Module installation kit (kit includes communication module, cable harness, and IM 704) McQuay Parts Cable harness McQuay Parts Connector plug (standard) Phoenix Contact Connector plug (standard) Altech Corp This document contains the most current product information as of this printing. For the most current product information, please go to All McQuay equipment is sold pursuant to McQuay's Standard Terms and Conditions of Sale and Limited Product Warranty McQuay International IM704-4

MicroTech II Applied TM Rooftop Unit Controller and Self-Contained Unit Controller BACnet TM MSTP Communication Module

MicroTech II Applied TM Rooftop Unit Controller and Self-Contained Unit Controller BACnet TM MSTP Communication Module Installation and Maintenance Manual IM 704-3 Group: Controls Part Number: IM 704-3 Date: November 2004 Supersedes: IM 704-2 MicroTech II Applied TM Rooftop Unit Controller and Self-Contained Unit Controller

More information

MicroTech II TM Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet TM Communication Module BACnet/IP

MicroTech II TM Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet TM Communication Module BACnet/IP Installation and Maintenance Manual IM 703-3 Group: Controls Part Number: IM 703-3 Date: November 2004 Supersedes: IM 703-2 MicroTech II TM Applied Rooftop Unit Controller and Self-Contained Unit Controller

More information

MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module BACnet/IP

MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module BACnet/IP Installation and Maintenance Manual IM703-2 Group: McQuay Controls Date: February 2002 MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module BACnet/IP

More information

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module Installation and Maintenance Manual IM 928- Group: Controls Part Number: 66920770 Date: July 2009 Supersedes: IM 928 MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module NOTICE Use this

More information

MicroTech II BACnet Communication Module Ethernet/IP

MicroTech II BACnet Communication Module Ethernet/IP Installation & Maintenance Manual IM703-0 Group: McQuay Controls Date: October 2001 MicroTech II BACnet Communication Module Ethernet/IP ASHRAE 135, Annex J 10 BASE-T 1998 McQuay International Contents

More information

MicroTech II BACnet Communication Module Ethernet/IP

MicroTech II BACnet Communication Module Ethernet/IP Installation & Maintenance Manual IM703-1 Group: McQuay Controls Date: November 2001 MicroTech II BACnet Communication Module Ethernet/IP ASHRAE 135, Annex J 10 BASE-T 2001 McQuay International Contents

More information

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module Installation and Maintenance Manual IM 928-2 Group: Controls Part Number: 669207702 Date: March 2011 Supersedes: IM 928-1 MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module NOTICE

More information

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP Installation and Maintenance Manual IM 853 Group: Controls Part Number: IM 853 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet

More information

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP) Installation and Maintenance Manual IM 852-2 Group: Controls Part Number: IM 852 Date: January 2008 Supercedes: IM 852-1 MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module

More information

MicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP)

MicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP) Installation and Maintenance Manual IM 967 Group: Controls Part Number: IM 967 Date: October 2009 Supercedes: New MicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP) Pathfinder

More information

Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)

Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet) Installation and Maintenance Manual IM 963 Group: Controls Part Number: IM 963 Date: April 2010 Supercedes: New Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet) Daikin

More information

MicroTech III Rooftop and Self Contained Unit Controller BACnet IP Communication Module

MicroTech III Rooftop and Self Contained Unit Controller BACnet IP Communication Module Installation and Maintenance Manual IM 916-2 Group: Controls Part Number: IM 916 Date: October 2009 Supercedes: IM 916-1 MicroTech III Rooftop and Self Contained Unit Controller BACnet IP Communication

More information

MicroTech III Chiller Unit Controller BACnet IP Communication Module

MicroTech III Chiller Unit Controller BACnet IP Communication Module Installation and Maintenance Manual IM 966 Group: Controls Part Number: IM 966 Date: October 2009 Supercedes: New MicroTech III Chiller Unit Controller BACnet IP Communication Module Pathfinder Chiller,

More information

LONWORKS Plug-In Software

LONWORKS Plug-In Software Installation and Maintenance Manual IM 933 Group: McQuay Controls Part Number: IM 933 Date: September 2008 Supercedes: New LONWORKS Plug-In Software For use with the MicroTech III Unitary Controller -

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS BACnet Communication Card RXRX-AY01 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS LonWorks Communication Card RXRX-AY02 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED

More information

MicroTech II Chiller Unit Controller LonWorks Communication Module

MicroTech II Chiller Unit Controller LonWorks Communication Module Installation and Maintenance IM 735-1 Group: Controls Part Number: IM 735 Date: May 2005 Supersedes: IM735-0 MicroTech II Chiller Unit Controller LonWorks Communication Module WSC Water-Cooled Centrifugal,

More information

Installation and Maintenance Manual IM 928-5

Installation and Maintenance Manual IM 928-5 Installation and Maintenance Manual IM 928-5 MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module Group: Controls Part Number: IM 928 Date: February 2016 Table of Contents Introduction....

More information

Installation and Maintenance Manual IM

Installation and Maintenance Manual IM Installation and Maintenance Manual IM 1013-1 MicroTech III Fan Coil BACnet MS/TP Communication Module Group: Controls Part Number: IM 1013 Date: February 2016 Table of Contents Introduction.... 3 Revision

More information

BCM. MicroTech II Chiller Unit Controller BACnet Communication Module. Installation and Maintenance Manual IM ASHRAE 135, MCQ Rev.

BCM. MicroTech II Chiller Unit Controller BACnet Communication Module. Installation and Maintenance Manual IM ASHRAE 135, MCQ Rev. Installation and Maintenance Manual IM 736-0 Part No: 736015423 Group: McQuay Controls Date: January 2003 MicroTech II Chiller Unit Controller BACnet Communication Module ASHRAE 135, 2001 WSC Water-Cooled

More information

Installation and Maintenance Manual IM 969-5

Installation and Maintenance Manual IM 969-5 Installation and Maintenance Manual IM 969-5 Group: Controls Part Number: IM 969 Date: January 2018 MicroTech III Chiller Unit Controller Modbus Communication Module Models AGZ and AMZ Trailblazer Air-cooled

More information

Installation and Maintenance Manual IM 966-3

Installation and Maintenance Manual IM 966-3 Installation and Maintenance Manual IM 966-3 Group: Controls Part Number: IM 966 Date: March 2017 MicroTech III Chiller BACnet IP Communication Module Models AGZ and AMZ Trailblazer Air-Cooled Scroll Chiller

More information

MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers

MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers Engineering Data ED15080-1 Group: Controls Date: June 2002 MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers Alerton BACtalk Building

More information

Installation and Maintenance Manual IM 963-2

Installation and Maintenance Manual IM 963-2 Installation and Maintenance Manual IM 963-2 Group: Controls Part Number: IM 963 Date: March 2017 Daikin Magnitude Chiller BACnet Networks (MS/TP, IP, Ethernet) Communication Module Model WME Magnetic

More information

MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers

MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained Unit Controllers Engineering Data ED 15080-2 Group: Controls Part Number: ED 15080 Date: April 2006 Supercedes: ED 15080-1 MicroTech II Alerton BACtalk Integration Information for MicroTech II Applied Rooftop and Self-Contained

More information

Installation and Operation Manual IM

Installation and Operation Manual IM Installation and Operation Manual IM 1005-4 MicroTech III Unit Controller Remote User Interface Group: Controls Part Number: IM 1005 Date: January 2018 RoofPak Singlezone Heating and Cooling Units, Models

More information

MicroTech II Chiller Unit Controller BACnet Communication Module

MicroTech II Chiller Unit Controller BACnet Communication Module Installation and Maintenance Manual IM 736-2 Group: Controls Part Number: IM 736 Date: November 2005 Supercedes: IM 736-1 MicroTech II Chiller Unit Controller BACnet Communication Module WSC WDC WPV HSC

More information

Installation and Maintenance Manual IM 966-4

Installation and Maintenance Manual IM 966-4 Installation and Maintenance Manual IM 966-4 Group: Controls Part Number: IM 966 Date: January 2018 MicroTech III Chiller Unit Controller BACnet IP Communication Module Models AGZ and AMZ Trailblazer Air-cooled

More information

Installation and Maintenance Manual IM Replacement Intelligent Equipment Gateway

Installation and Maintenance Manual IM Replacement Intelligent Equipment Gateway Installation and Maintenance Manual IM 1229 Group: Controls Replacement Intelligent Equipment Gateway Commercial Rooftop Models: DPS and MPS Applied Rooftop Models: RDS and RPS Part Number: 910159718 Date:

More information

BACnet VAV Actuator Start-up Guide IM 1040

BACnet VAV Actuator Start-up Guide IM 1040 BACnet VAV Actuator Start-up Guide IM 1040 Group: Controls Part Number: IM 1040 Date: 3/4/2010 Supersedes: New BACnet VAV Actuator--Electronic Output Start-up Procedures 2010 McQuay International Table

More information

MicroTech Modem Kit. Installation & Maintenance Data IM 682. Group: Controls Part Number: Date: October, 1996.

MicroTech Modem Kit. Installation & Maintenance Data IM 682. Group: Controls Part Number: Date: October, 1996. Installation & Maintenance Data IM 682 Group: Controls Part Number: 629976 Date: October, 1996 MicroTech Modem Kit Telephone Line Modem Controller cns no. a0006 1996 McQuay International Contents Contents...2

More information

Installation and Maintenance Manual IM

Installation and Maintenance Manual IM Installation and Maintenance Manual IM 1229-1 Group: Controls Replacement Intelligent Equipment Gateway Commercial Rooftop Models: DPS and MPS Applied Rooftop Models: RDS and RPS Part Number: 910159718

More information

Installation and Maintenance Manual IM 968-4

Installation and Maintenance Manual IM 968-4 Installation and Maintenance Manual IM 968-4 Group: Controls Part Number: IM 968 Date: January 2018 MicroTech III Chiller Unit Controller LonWorks Communication Module Models AGZ and AMZ Trailblazer Air-cooled

More information

MicroTech II McQuay Chiller Unit Controller BACnet Communication Module (MS/TP)

MicroTech II McQuay Chiller Unit Controller BACnet Communication Module (MS/TP) Installation and Maintenance Manual IM 906 Group: Controls Part Number: IM 906 Date: February 2008 Supersedes: New MicroTech II McQuay Chiller Unit Controller BACnet Communication Module (MS/TP) WSC WDC

More information

Installing and Configuring Rialto Analytic Appliances

Installing and Configuring Rialto Analytic Appliances Installing and Configuring Rialto Analytic Appliances Important Safety Information This manual provides installation and operation information and precautions for the use of this camera. Incorrect installation

More information

MicroTech II Daikin Chiller Unit Controller BACnet Communication Module (MS/TP)

MicroTech II Daikin Chiller Unit Controller BACnet Communication Module (MS/TP) Installation and Maintenance Manual IM 906-2 Group: Controls Part Number: IM 906 Date: December 2010 Supersedes: IM 906-1 MicroTech II Daikin Chiller Unit Controller BACnet Communication Module (MS/TP)

More information

BACnet Router Start-up Guide

BACnet Router Start-up Guide BACnet Router Start-up Guide BAS Router (BACnet Multi-Network Router) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after October 2014 Kernel Version: 6.15 Document Revision: 3 QuickServer

More information

MicroTech II Remote I/O Panel Installation Manual

MicroTech II Remote I/O Panel Installation Manual MicroTech II Remote I/O Panel Installation Manual Installation Manual IM 783-2 Group: Controls Part Number: IM 783 Date: November 2006 Supersedes: IM 783-1 Table of Contents Notice... 3 Reference Documents...

More information

MicroTech II Chiller Unit Controller BACnet Communication Module, Ethernet or IP

MicroTech II Chiller Unit Controller BACnet Communication Module, Ethernet or IP Installation and Maintenance Manual IM 837 Group: Controls Part Number: IM 837 Date: June 2006 Supercedes: New MicroTech II Chiller Unit Controller BACnet Communication Module, Ethernet or IP WSC Water-Cooled

More information

OM Operation and Maintenance Manual. Intelligent Equipment for Daikin Applied Trailblazer Air-cooled Scroll Chiller. Models: AGZ-D and AGZ-E

OM Operation and Maintenance Manual. Intelligent Equipment for Daikin Applied Trailblazer Air-cooled Scroll Chiller. Models: AGZ-D and AGZ-E Operation and Maintenance Manual Intelligent Equipment for Daikin Applied Trailblazer Air-cooled Scroll Chiller OM 1241 Group: Controls Part Number: 910166134 Date: June 2015 Models: AGZ-D and AGZ-E Table

More information

and Network Interface Modules Installation Instructions

and Network Interface Modules Installation Instructions 4010-9817 and 4010-9821 Network Interface Modules Installation Instructions Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the

More information

MicroTech II BACnet Communication Module Configuration Tool for McQuay Maverick II Rooftop Unit Controllers

MicroTech II BACnet Communication Module Configuration Tool for McQuay Maverick II Rooftop Unit Controllers Users Manual UM 855 Group: Controls Part Number: UM 855 Date: June 2007 Supersedes: New MicroTech II BACnet Communication Module Configuration Tool for McQuay Maverick II Rooftop Unit Controllers Commercial

More information

Bluetooth Shielding Instructions

Bluetooth Shielding Instructions Mac mini 2012 Bluetooth Shielding Instructions 1 INTRODUCTION 1.1 STATIC PRECAUTIONS 1.2 TOOLS REQUIRED 2 DISASSEMBLY 3 SHIELDING 4 FAQ 4.1 FAQ 5 CUSTOMER SERVICE 5.1 Before Contacting Customer Service

More information

MicroTech 2000 Water Source Heat Pump Unit Controller

MicroTech 2000 Water Source Heat Pump Unit Controller Installation Manual IM 660-4 Group: Controls Part Number: IM 660 Date: June 2012 Supersedes: IM 660-3 MicroTech 2000 Water Source Heat Pump Unit Controller NOTICE Use this manual to physically install

More information

BACnet Router Start-up Guide

BACnet Router Start-up Guide BACnet Router Start-up Guide BAS Router (BACnet Multi-Network Router) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after January 2015 Kernel Version: Application Version: Document

More information

AURA SSD FOR MAC PRO. Installation Guide

AURA SSD FOR MAC PRO. Installation Guide AURA SSD FOR MAC PRO Installation Guide CONTENTS Introduction... 1 1.1 System Requirements 1.2 Package Contents 1.3 About This Manual Installation... 2 2.1 Preparing the Mac Pro 2.2 Installing the Aura

More information

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN Voltage Regulators MN225074EN Effective March 2017 Supersedes January 2012 (S225-40-7) RS-485 digital communications accessory board installation and operation instructions COOPER POWER SERIES DISCLAIMER

More information

MicroTech II TM Remote I/O Panel Installation Manual

MicroTech II TM Remote I/O Panel Installation Manual Installation Manual IM 783-0 MicroTech II TM Remote I/O Panel Installation Manual Group: Controls Part Number: IM 783-0 Date: February 2004 Supersedes: New 2004 McQuay International Page 2 IM-783 Table

More information

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN Voltage Regulators MN225067EN Effective November 2016 Supersedes June 2014 (S225-70-13) COOPER POWER Input/Output (I/O) module installation instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF

More information

Analog Monitor Installation Manual

Analog Monitor Installation Manual Analog Monitor Installation Manual Part Number: 144-23919 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems and equipment.

More information

Analog Input Installation Manual

Analog Input Installation Manual Analog Input Installation Manual August 2011 Part Number: 144-23917 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems

More information

CubePro. Main PCB Replacement Guide. Prosumer 3D Printer. Original Instructions

CubePro. Main PCB Replacement Guide. Prosumer 3D Printer. Original Instructions CubePro Prosumer 3D Printer Main PCB Replacement Guide Original Instructions 1 INTRODUCTION COPYRIGHT 2014 by All rights reserved. This document is subject to change without notice. This document is copyrighted

More information

Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE , BACnet

Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE , BACnet Engineering Data ED 15126 Group: Controls Part Number: ED 15126 Date: April 2010 Supersedes: New Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement

More information

Installing the Cisco SFS 3504 Server Switch

Installing the Cisco SFS 3504 Server Switch CHAPTER 3 This chapter describes how to mount your Cisco SFS 3504 Server Switch on a rack, boot the Cisco SFS 3504 Server Switch, and configure basic services. For advanced configuration information, see

More information

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions 3710 ACM 3750 PDC 3800 RTU ISOCOM Communications Card Retrofit Instructions Danger During normal operation of this device, hazardous voltages are present which can cause severe injury or death. These

More information

BACnet /IP to MS/TP Adapter User Guide

BACnet /IP to MS/TP Adapter User Guide BACnet /IP to MS/TP Adapter User Guide Document Revision History: Version 1.0 - Initial Release February, 2010 BACnet/IP to MS/TP Adapter - User Guide 1.0 05DI-UGBRTPB-10 Copyright Distech Controls Inc.

More information

PS/IO Circuit Board Retrofit

PS/IO Circuit Board Retrofit S&C 6800 Series Automatic Switch Controls PS/IO Circuit Board Retrofit Table of Contents Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this Instruction Sheet....

More information

DATA DOUBLER. Apple Mac mini (2009)

DATA DOUBLER. Apple Mac mini (2009) DATA DOUBLER Apple Mac mini (2009) TABLE OF CONTENTS Introduction... 1 1.1 Hardware Compatibility 1.1.1 Host Computer Compatibility 1.1.2 Drive Compatibility 1.2 Package Contents 1.3 About This Manual

More information

Resolver to Digital Expansion Board

Resolver to Digital Expansion Board Resolver to Digital Expansion Board Catalog No. EXB009A01 Installation and Operating Manual 6/98 MN1313 Table of Contents Section 1 General Information............................. 1-1 Introduction....................................

More information

AC300/AC400 SERIES DYNAMIC BRAKING and ADDITIONAL FORM C RELAY. INSTALLATION INSTRUCTIONS Document Number:

AC300/AC400 SERIES DYNAMIC BRAKING and ADDITIONAL FORM C RELAY. INSTALLATION INSTRUCTIONS Document Number: Minarik Variable Speed AC Motor Drives AC300/AC400 SERIES DYNAMIC BRAKING and ADDITIONAL FORM C RELAY INSTALLATION INSTRUCTIONS Document Number: 250-0297 These instructions apply to models rated: 7.5 25

More information

4100/ VDC Converter Installation Instructions

4100/ VDC Converter Installation Instructions 4100/4120-0156 8 VDC Converter Installation Instructions Introduction This publication describes the installation procedure for the 8 VDC Converter. Related Documentation Field Wiring Diagram for 4100

More information

EDG Port Industrial 10/100 Mbps Ethernet Switch. User Manual

EDG Port Industrial 10/100 Mbps Ethernet Switch. User Manual EDG-6528 8-Port Industrial 10/100 Mbps Ethernet Switch User Manual Copyright The documentation and the software included with this product are copyrighted 2005 by Advantech Co., Ltd. All rights are reserved.

More information

MicroTech II Vertical Self-contained Systems Unit Controller

MicroTech II Vertical Self-contained Systems Unit Controller Installation and Maintenance IM-710 Group: Applied Systems Part Number: IM710 Date: February 2002 MicroTech II Vertical Self-contained Systems Unit Controller Used with McQuay models: SWP and SWT BACK

More information

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxMB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541 PoE Model: KSD-541-P. Installation Guide

Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541 PoE Model: KSD-541-P. Installation Guide Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports Basic Model: KSD-541 PoE Model: KSD-541-P Installation Guide DOC.080104-1- (C) 2008 KTI Networks Inc. All rights reserved.

More information

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A DTS 310 DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter Page 1 1 PRODUCT OVERVIEW... 3 1.1 SUPPLIED ITEMS... 3 1.2 DOCUMENT CONVENTIONS... 4 1.3 PRODUCT SPECIFICATION... 4 1.3.1 Current

More information

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516 574-294-2511 CANADA Dometic Corporation 46 Zatonski, Unit 3 Brantford, ON N3T 5L8 CANADA 519-720-9578 For Service Center

More information

GPIB-232CT-A IBCL EPROM Installation Guide

GPIB-232CT-A IBCL EPROM Installation Guide NATIONAL INSTRUMENTS The Software is the Instrument Installation Guide GPIB-232CT-A IBCL EPROM Installation Guide This guide describes how to replace the factory-installed EPROM that comes with your GPIB-232CT-A.

More information

Hubbell Building Automation #LXBASM. ProtoNode LER Startup Guide

Hubbell Building Automation #LXBASM. ProtoNode LER Startup Guide Hubbell Building Automation #LXBASM ProtoNode LER Startup Guide For Interfacing Customer Product: Hubbell Automation LX Lighting Control Panels To Building Automation Systems: BACnet MS/TP, BACnet/IP,

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Vision OPLC V130 COM Modules: V100-17-CAN, V100-17-RS4/X, V100-17-ET2 This guide shows you how to install an additional communication module in a V130 controller. Instructions and technical specifications

More information

Sigma DeviceNet Tool Change Systems USER S GUIDE Rev 05

Sigma DeviceNet Tool Change Systems USER S GUIDE Rev 05 Sigma DeviceNet Tool Change Systems USER S GUIDE 94018 Rev 05 648 Saratoga Road Glenville, NY 12302 USA Phone: 518 384 1000 Fax 518 384 1200 www.arobotics.com 1. PRECAUTIONS 1 Sigma DNET Module 1 2.0 DNET

More information

OWC Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE

OWC Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE OWC Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Apple Mac Requirements 1.1.2 PC Requirements 1.1.3 Supported PCIe Cards 1.2

More information

Phase Loss Protection Upgrade. Phase Loss Protection Upgrade. In this bulletin:

Phase Loss Protection Upgrade. Phase Loss Protection Upgrade. In this bulletin: Phase Loss Protection Upgrade In this bulletin: Introduction... 2 Purpose... 2 General... 2 Applicability... 2 HD3070 Phase Loss Protection Upgrade Kit Parts... 2 Preparation... 4 Install the Phase Loss

More information

CSM200 Expansion Tray

CSM200 Expansion Tray CSM200 Expansion Tray Initial Setup Guide for SANtricity users or VTL environments EC1718-1-E3, Third Edition Proprietary Rights Notice This document contains proprietary information of LSI Logic Corporation

More information

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B. Vision OPLC Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V290-19-C30B and V290-19-T40B. General Description Vision OPLCs are programmable

More information

INCOM communications adapter module

INCOM communications adapter module Instruction Leaflet IL0131124EN Supersedes July 2016 INCOM communications adapter module Power Defense ICCB Instructions apply to: UL489 : PD-NF UL489 : PD-RF IEC : PD-NF, IZMX16 IEC : PD-RF, IZMX40 WARNING

More information

MicroTech Communications Gateway

MicroTech Communications Gateway Installation & Maintenance Data IM 661-1 Group: Controls Part Number: 594881Y-01 Date: June 1998 MicroTech Communications Gateway MicroTech 2000 LonWorks -Based Controllers MicroTech Communications Gateway

More information

To connect the AC adapter:

To connect the AC adapter: Replacing the AC Adapter Replacing the AC Adapter 3 Plug the power cord into a wall outlet. The power indicator turns on. To connect the AC adapter: Connect the power cord to the AC adapter. Power indicator

More information

Installation and Operations Manual IOM

Installation and Operations Manual IOM Installation and Operations Manual IOM 1135-2 MicroTech III I/O Manager Group: Controls Part Number: IOM 1135 Date: February 2015 Supercedes: IOM 1135-1 For use with Daikin MicroTech Integrated System

More information

Installation Instructions for UL Rev A

Installation Instructions for UL Rev A NetController II Installation Instructions for UL 864 30-3001-1008 Rev A Mounting Screw Andover Continuum Power Supply Connector Third-Party Power Supply Connector I/O Bus Connector Cover Mounting Screw

More information

TABLE OF CONTENTS INTRODUCTION...1 DEVICE SETUP...4 SUPPORT RESOURCES...9

TABLE OF CONTENTS INTRODUCTION...1 DEVICE SETUP...4 SUPPORT RESOURCES...9 TABLE OF CONTENTS INTRODUCTION...1 1.1 Minimum System Requirements 1.2 Package Contents 1.3 About This Manual 1.4 Rear View 1.4.1 Rear Features 1.5 Usage Notes DEVICE SETUP...4 2.1 Quick Start 2.2 Assembly

More information

Microphone Mux Module Installation Instructions

Microphone Mux Module Installation Instructions 4100-1274 Microphone Mux Module Installation Instructions Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation manual. These instructions must be followed

More information

Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

Preface Digital Electronics Corporation. All rights reserved. Digital Electronics Corporation December LT Type-D User Manual Supplement 1

Preface Digital Electronics Corporation. All rights reserved. Digital Electronics Corporation December LT Type-D User Manual Supplement 1 Preface Thank you for purchasing the Pro-face LogiTouch Type-D DeviceNet master unit. The LogiTouch Type-D (also referred to as the LT Type-D ) allows connection to the DeviceNet Fieldbus to access many

More information

MicroTech Series-100 Application Specific Controller

MicroTech Series-100 Application Specific Controller Installation & Maintenance Data IM 657-1 Group: Controls Part Number: 594861Y Date: March 1998 MicroTech Series-100 Application Specific Controller a0196 1998 McQuay International Contents Contents...2

More information

COOPER POWER SERIES. 600 A U-OP visible break connector system operation instructions. Deadbreak Apparatus Connectors MN650022EN

COOPER POWER SERIES. 600 A U-OP visible break connector system operation instructions. Deadbreak Apparatus Connectors MN650022EN Deadbreak Apparatus Connectors MN650022EN COOPER POWER Effective March 2016 Supersedes S600-14-1 June 2010 SERIES 600 A U-OP visible break connector system operation instructions DISCLAIMER OF WARRANTIES

More information

CrystalView DVI Multi INSTALLATION AND OPERATIONS MANUAL Stancliff Road Phone: (281)

CrystalView DVI Multi INSTALLATION AND OPERATIONS MANUAL Stancliff Road Phone: (281) CrystalView DVI Multi INSTALLATION AND OPERATIONS MANUAL 10707 Stancliff Road Phone: (281) 933-7673 Houston, Texas 77099 WWW.ROSE.COM LIMITED WARRANTY Rose Electronics warrants the CrystalView Multi to

More information

Model 2380 Rack-Mount Kit

Model 2380 Rack-Mount Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley Model 2380 Rack-Mount Kit Installation Instructions Introduction The Model 2380 Fixed Rack-Mount

More information

Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

MONTANa. User s Guide

MONTANa. User s Guide MONTANa User s Guide Dakota, Montana, Sierra, SoDA, Tango24, and Zulu are trademarks of Frontier Design Group, LLC. All other trademarks and registered trademarks are the property of their respective holders.

More information

DYNAMIC ENGINEERING. 150 DuBois St. #3, Santa Cruz Ca Fax Est

DYNAMIC ENGINEERING. 150 DuBois St. #3, Santa Cruz Ca Fax Est DYNAMIC ENGINEERING 150 DuBois St. #3, Santa Cruz Ca. 95060 831-457-8891 Fax 831-457-4793 sales@dyneng.com www.dyneng.com Est. 1988 User Manual PC104p2PMC Alternate Name: PCI1042PMC Adapt a 32 bit PMC

More information

User Guide CPSMP VAC Power Supply Module: PointSystem CPSMC Accessory CPSMC Accessory. Contents.

User Guide CPSMP VAC Power Supply Module: PointSystem CPSMC Accessory CPSMC Accessory. Contents. User Guide CPSMP-205 110 240 VAC Power Supply Module: PointSystem CPSMC1800-200 Accessory CPSMC1900-100 Accessory Contents Contents...1 Description...1 Cautions and Warnings...2 Definitions...2 Power supply

More information

INSTRUCTION MANUAL DISTRIBUTION UNIT. Please read this manual thoroughly before use, and keep it handy for future reference.

INSTRUCTION MANUAL DISTRIBUTION UNIT. Please read this manual thoroughly before use, and keep it handy for future reference. INSTRUCTION MANUAL DISTRIBUTION UNIT Please read this manual thoroughly before use, and keep it handy for future reference. ISSUE 1 May 2006 LIMITATION OF LIABILITY THE INFORMATION IN THIS PUBLICATION

More information

Installation Guide. Wyse Rx0L Thin Client Flash and RAM Upgrade Option Kit. Issue: PN: L Rev. A

Installation Guide. Wyse Rx0L Thin Client Flash and RAM Upgrade Option Kit. Issue: PN: L Rev. A Installation Guide Wyse Rx0L Thin Client Flash and RAM Upgrade Option Kit Issue: 052209 PN: 883884-11L Rev. A ii Copyright Notice 2009, Wyse Technology Inc. All rights reserved. This manual and the software

More information

Model 2380 Rack-Mount Kit

Model 2380 Rack-Mount Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley Model 2380 Rack-Mount Kit Installation Instructions Introduction The Model 2380 Fixed Rack-Mount

More information

Expansion module EM-BAC-MOD-01. Installation manual

Expansion module EM-BAC-MOD-01. Installation manual Installation manual GB/en Expansion module EM-BAC-MOD-01 BACnet MS/TP or Modbus RTU interface card for EASYLAB controller TCU3 and adapter module TAM Firmware from 4.0 TROX GmbH Heinrich-Trox-Platz 47504

More information

Chapter 2. Installing the Chapter 2. Contents

Chapter 2. Installing the Chapter 2. Contents Contents Chapter 2 Installing the 3512 Overview... 2-2 Unpacking... 2-2 Telephone Equipment... 2-3 Customer-Provided Telephone Equipment... 2-3 Telephone Company Procedures and Regulatory Requirements...

More information

Mercury Elite Pro mini ASSEMBLY MANUAL & USER GUIDE

Mercury Elite Pro mini ASSEMBLY MANUAL & USER GUIDE Mercury Elite Pro mini ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS 1. INTRODUCTION... 1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Mac Requirements 1.1.2 PC Requirements 1.2 PACKAGE CONTENTS 1.3 ABOUT THIS

More information

Demo Kit Quick Start Guide

Demo Kit Quick Start Guide Near Field Imaging (NFI) Projected Capacitive Touch Screen Systems Read and understand all safety information contained in this document before using this product. Introduction This is intended to help

More information

5 B&W Rear View System Camera

5 B&W Rear View System Camera 5 B&W Rear View System Camera Instruction Manual MODEL: CA453 www.lorexcctv.com Copyright 2007 LOREX Technology Inc. Thank you for purchasing the Lorex 5 Black & White Rear View System Camera. This system

More information