1 Installation Instructions Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Purpose Firmware Update Kit Contents Hardware and Software Requirements This document describes how to update firmware on your Ethernet, Enhanced, or ControlNet PLC-5 programmable controller. Depending on your requirements, the firmware update kit may contain: ControlFLASH software with the firmware update these installation instructions applicable firmware release notes a firmware revision label firmware EPROMS, if applicable Your computer must meet the following requirements to perform the firmware update: at least a 486 processor Windows 95, Windows 98, or Windows NT, or later, operating system at least 16 Mbytes of available memory To perform Ethernet Series C, or later, firmware updates, you will need a Network Interface Card and a switch, Ethernet hub or crossover cable. To perform other updates, you need a shielded serial cable, either 1784-CP10 or 1784-CP11. ATTENTION You must save the controller s processor memory to your hard disk or to an EEPROM. If you do not, the controller s user memory will be lost because the firmware update procedure erases memory. Locate Your Controller s Update Procedure in this Document To update the firmware on this controller: Go to this page: Ethernet PLC-5, Series C and D 4 Ethernet PLC-5, Series E or Later 13 Enhanced PLC-5, Series A thru D 21 Enhanced PLC-5, Series E or Later 25 ControlNet PLC-5, All Series 33 Allen-Bradley Motors 1

2 2 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual, when necessary we use notes to make you aware of safety considerations. WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. IMPORTANT Identifies information that is critical for successful application and understanding of the product. ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you: identify a hazard avoid a hazard recognize the consequence SHOCK HAZARD Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present. BURN HAZARD Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be dangerous temperatures.

3 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 3 ATTENTION Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: Touch a grounded object to discharge potential static. Wear an approved grounding wrist strap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. If available, use a static-safe workstation. When not in use, store the equipment in appropriate static-safe packaging. ATTENTION This version of ControlFLASH is only suitable for this firmware update. Do not use this version of ControlFLASH to update firmware on any other PLC-5 programmable controller. Allen-Bradley Motors

4 4 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Important Considerations for CL I, Div. 2 Installations WARNING When you connect or disconnect the battery, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. For safety information on the handling of lithium batteries, including handling and disposal of leaking batteries, refer to Guidelines for Handling Lithium Batteries, publication AG-5.4 Store batteries in a cool, dry environment. We recommend 25 C with 40% or 60% relative humidity. You may store batteries up to 30 days between C, such as during transportation. To avoid possible leakage, do not store batteries above 60 C for more than 30 days. WARNING When you install or remove the module with power applied, or you connect or disconnect the serial cable with power applied to this programmable controller or the device on the other end of the cable, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Ethernet PLC-5 Programmable Controllers L20E L40E L80E Series C and D To update these series of Ethernet PLC-5 firmware, you must first use ControlFLASH through the Ethernet channel, and then replace the applicable EPROMS. To start this firmware update, follow these steps: Step 1 - Prepare the PLC-5 Programmable Controller ATTENTION You must save the controller s processor memory to your hard disk or to an EEPROM. If you do not, the controller s user memory will be lost because the firmware update procedure erases memory. 1. Save the controller s processor memory to your hard disk or to an EEPROM. 2. Remove power from the controller. 3. Remove the controller battery cover and disconnect the battery. 4. Remove the controller from the chassis.

5 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 5 5. Locate and document the controller s hardware Ethernet address. The address is on the circuit board label toward the back of the controller. 6. If applicable, disconnect the coprocessor or Ethernet Interface sidecar module. 7. Reinstall the controller into the chassis. 8. Apply power to the controller. 9. Through the Ethernet port, use either a switch, hub or crossover cable to connect the computer to the controller. Make sure the TCP/IP is configured and running on the personal computer. 10. Assign the controller s IP address by going online with the controller via DH+ or serially. Use the channel configuration screen to configure the IP address for Channel 2 (uncheck the BOOTP enabled box). 11. Turn the controller keyswitch to PROGRAM mode. Allen-Bradley Motors

6 6 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 2 - Install the ControlFLASH Software 1. Insert the ControlFLASH disk into the floppy drive of your computer. 2. Browse the A: drive and select the setup.exe program. 3. If you have an earlier version of ControlFLASH installed, we recommend to install this version into the same directory. 4. Follow the Setup Wizard as it guides you through the installation process. Step 3 - Perform the ControlFLASH Update ATTENTION Failure to follow these procedures exactly or to cause an interruption during them may result in an inoperable controller. 1. If you have not already done so, connect the computer to the controller through the Ethernet channel: use either a switch, hub or crossover cable to connect the computer to the controller 2. Close all applications including RSLinx.

7 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 7 3. Start ControlFLASH: 3A - Start the ControlFLASH software. Click Next. 3B - Select the appropriate PLC-5 Programmable Controller catalog number. Use the cursor to highlight the PLC-5 type Click Next. Allen-Bradley Motors

8 8 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 3C - Enter the Ethernet IP address of the PLC-5 you are updating. Click Get Info to verify the programmable controller you are updating. Click OK. 3D - Select the firmware revision. Select the correct update revision. Click Next. 3E - Verify the update. Click Finish.

9 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 9 3F - Start the firmware update. Click Yes. The progress indicator shows how much of the update has been performed. Important: This update can take up to two minutes to complete. 3G - Check the STAT LED on the PLC-5. If it is flashing green, the ControlFLASH update was successful - continue to step 3H. If the STAT LED is not flashing green, the update was not successful - call Rockwell Automation Technical Support at H - Follow the power cycle instructions during and after the update process. When the update is complete, the software will prompt you to cycle power. Important: Do not click OK until you complete the next three steps: - Install the New Firmware EPROMS - Apply the Firmware Revision Label - Complete the Firmware Update These procedures are detailed on the following pages. 4. Remove power from the controller. 5. Remove the controller from the chassis. Allen-Bradley Motors

10 10 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 4 - Install the New Firmware EPROMS On the Ethernet PLC-5, Series C and D: 1785-L20E programmable controller Replace the U61 and U70 EPROMS* If applicable, replace the U18 EPROM* U18* (if applicable) U61* U70* Do this: 1. Remove the four screws that hold the right side plastic cover. 2. Remove the cover. 3. Remove the two large screws and washers located in the center of the exposed circuit board. 4. Carefully separate the two processor boards by pulling the exposed circuit board at the backplane edge connector away from the metal cover as you would open a book. 5. Remove and replace the firmware EPROMS one at a time, taking note of the location number and the orientation of the notch in each of the EPROMS. 6. See the figure to the left for the numbers and locations of the EPROMS. 7. Reassemble the controller by reversing steps 1 thru L40E and -L80E programmable controllers 1. On the front of the controller, remove the 2 hex nuts on Channel Remove the screw on the communication card and gently pull the card out of the Replace the U5 and U31 EPROMS on the circuit board* If applicable, replace the U7 or U12 EPROM on the communication card* U5* U31* U7 or U12* (if applicable) Remove communication card controller. 3. Remove the four screws that hold the right side plastic cover and remove the cover. 4. Remove the two large screws and washers located in the center of the exposed circuit board. 5. Carefully separate the two processor boards by pulling the exposed circuit board at the backplane edge connector away from the metal cover as you would open a book. 6. Remove and replace the firmware EPROMS one at a time, taking note of the location number and the orientation of the notch in each of the EPROMS. 7. See the figure to the left for the numbers and locations of the EPROMS. 8. Reassemble the controller by reversing steps 1 thru 5. * EPROM numbers may vary and their locations shown in these illustrations are approximate. Your series and revision of controller and firmware may be different. Make certain the EPROM numbers from your firmware update match the numbers on their respective circuit boards and communication cards. Note: Do not reinstall the controller until you complete the next step.

11 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 11 Step 5 - Apply the Firmware Revision Label IMPORTANT It is important to apply this label to your programmable controller to ensure you receive the correct version back if you send it in for repair. 1. Apply the new firmware revision label on or below the existing product identification label (depending on the series and revision of controller). Make certain to place the label so that the current series and revision information is clearly visible. CAT. NO. REV L40E C D ETHERNET PLC-5/40 PROCESSOR MADE IN USA PART NO A01 BACKPLANE CURRENT REQUIREMENTS 3.3A AT 5VDC F/W REV Q.2 SERIES C FIRMWARE UPGRADE CAT. NO L40E SERIES REV. D G.2 Place new label over previous label or below entire product label. Step 6 - Complete the Firmware Update 1. Install the controller into the chassis. 2. Apply power to the controller. 3. After powerup, check the status of the controller: If: PROC LED is solid red and CH1A DH+ LED is flashing green PROC LED is solid red but the CH1A DH+ LED is not flashing green PROC LED is flashing red and green Then: Update is complete. Proceed to the next step. Make certain that all new EPROMS are properly installed (notches on circuit board and EPROMS match, there are no bent pins, EPROMS are installed in the correct location). Repeat the ControlFLASH procedure Allen-Bradley Motors

12 12 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 4. Since you removed the controller from the chassis, you must reenter the computer s Ethernet IP address and subnet mask (for example, for Class C).The controller should have an IP address with the same first three octets as the computer s Ethernet network interface address. If it doesn t, then you can assign the IP either by going online with the controller over DH+ or serially, and configuring the IP address for Channel 2 via the channel configuration screen (uncheck the BOOTP enabled box). Or, by setting up a BOOTP server with this module s assigned IP address. 5. In ControlFLASH: At the Cycle Power prompt, click OK The update process is now complete. The Status windows displays the result of the update. If an error occurs, it is displayed in this window. If an error occurs, click View Log to see specific error information. Click OK. 6. When the update is successful: restore all connections to the controller download the program back into memory and make certain that it runs properly Your firmware update is complete. If you have any questions, call Rockwell Automation Technical Support at

13 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 13 Ethernet PLC-5 Programmable Controllers L20E L40E L80E Series E or Later To update these series of Ethernet PLC-5 programmable controller firmware, you must first use ControlFLASH and then if applicable, replace EPROMS. To start this firmware update, follow these steps: Step 1 - Prepare the PLC-5 Programmable Controller ATTENTION You must save the controller s processor memory to your hard disk or to an EEPROM. If you do not, the controller s user memory will be lost because the firmware update procedure erases memory. 1. Save the controller s processor memory to your hard disk or to an EEPROM. 2. Disconnect all cables (serial, DH+, ControlNet, Ethernet, etc.) from the controller. 3. Remove power from the controller and remove it from the chassis. 4. Remove the controller battery cover and disconnect the battery. This resets the serial port to its default configuration so that the controller and ControlFLASH can communicate. 5. If applicable, disconnect the coprocessor or Ethernet Interface sidecar module. 6. Verify that the serial port DIP switches are set for RS Reinstall the controller and apply power. 8. Turn the controller keyswitch to PROGRAM mode. Allen-Bradley Motors

14 14 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 2 - Install the ControlFLASH Software 1. Insert the ControlFLASH disk into the floppy drive of your computer. 2. Browse the A: drive and select the setup.exe program. 3. If you have an earlier version of ControlFLASH installed, we recommend to install this version into the same directory. 4. Follow the Setup Wizard as it guides you through the installation process. Step 3 - Perform the ControlFLASH Update ATTENTION Failure to follow these procedures exactly or to cause an interruption during them may result in an inoperable controller. 1. Connect the computer to the controller using a 1784-CP10 or -CP11 cable between the computer and Channel 0 of the controller 2. Close all applications including RSLinx.

15 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Start ControlFLASH: 3A - Start the ControlFLASH software. Click Next. 3B - Select the appropriate PLC-5 Programmable Controller catalog number. Use the cursor to highlight the PLC-5 type Click Next. Allen-Bradley Motors

16 16 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 3C - Select the serial port of the computer to which you connected the 1784-CP10 or -CP11 cable. Select COM1 or COM2. Click Get Info to verify the programmable controller you are updating. Click Next. 3D - Select the firmware revision. Select the correct update revision. Click Next. 3E - Verify the update. Click Finish.

17 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 17 3F - Start the firmware update. Click Yes. The progress indicator shows how much of the update has been performed. Important: This update will take approximately 13 minutes to complete. 3G - Follow the power cycle instructions during and after the update process. When the update is complete, the software will prompt you to cycle power. Important: If you are updating the firmware EPROM on the communication card, you must first complete the next three steps: - Install the New Firmware EPROMS - Apply the Firmware Revision Label - Complete the Firmware Update If you are not updating the firmware EPROM on the communication card, skip to step 5 Apply the Firmware Revision Label. These procedures are detailed on the following pages. 4. Remove power from the controller. 5. Remove the controller from the chassis. Allen-Bradley Motors

18 18 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 4 - Install the New Firmware EPROM (if applicable) On the Ethernet PLC-5 Programmable Controller, Series E or Later: Do this: E, -L40E and -L80E programmable controllers 1. On the front of the controller, remove the 2 hex nuts on Channel Remove the screw on the communication card. 3. Remove the four screws that hold the right side plastic cover and remove the cover. If applicable, replace the U7 or U12 EPROM on the communication card* U7 or U12 (if applicable)* Remove communication card 4. Remove the two large screws and washers located in the center of the exposed circuit board. 5. Carefully separate the two processor boards by pulling the exposed circuit board at the backplane edge connector away from the metal cover as you would open a book. 6. Gently pull the communication card off of the circuit board. 7. Remove and replace the U7 or U12 firmware EPROM, taking note of the location number and the orientation of the notch on the EPROM. 8. See the figure to the left for the number and location of the EPROM. 9. Reassemble the controller by reversing steps 1 thru 6. * EPROM numbers may vary and their locations shown in these illustrations are approximate. Your series and revision of controller and firmware may be different. Make certain the EPROM numbers from your firmware update match the numbers on their respective circuit boards and communication cards. Note: Do not reinstall the controller until you complete the next step.

19 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 19 Step 5 - Apply the Firmware Revision Label IMPORTANT It is important to apply this label to your programmable controller to ensure you receive the correct version back if you send it in for repair. 1. Apply the new firmware revision label on or below the existing product identification label (depending on the series and revision of controller). Make certain to place the label so that the current series and revision information is clearly visible. CAT. NO. REV L40E C D ETHERNET PLC-5/40 PROCESSOR MADE IN USA PART NO A01 BACKPLANE CURRENT REQUIREMENTS 3.3A AT 5VDC F/W REV Q.2 SERIES C FIRMWARE UPGRADE CAT. NO L40E SERIES REV. D G.2 Place new label over previous label or below entire product label. Step 6 - Complete the Firmware Update 1. Install the controller into the chassis. 2. Apply power to the controller. Allen-Bradley Motors

20 20 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 3. In ControlFLASH: At the Cycle Power prompt, click OK The update process is now complete. If an error occurs, click View Log to see specific error information (see the table below). The Status windows displays the result of the update. If an error occurs, it is displayed in this window. Click OK. 4. After powerup, check the status of the controller: If: PROC LED is solid red and CH1A DH+ LED is flashing green PROC LED is flashing red. CH1A is not flashing green PROC LED is flashing red and green Then: Update is complete. Proceed to Step 5 below. Call Rockwell Automation Technical Support at Send controller in for repair. Repeat the ControlFLASH procedure 5. When the update is successful: restore all connections to the controller download the program back into memory and make certain that it runs properly Your firmware update is complete. If you have any questions, call Rockwell Automation Technical Support at

21 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 21 Enhanced PLC-5 Programmable Controllers - Series A thru D To update these series of Enhanced PLC-5 firmware, you must replace the applicable EEPROMS. To start this firmware update, follow these steps: Step 1 - Prepare the PLC-5 Programmable Controller ATTENTION You must save the controller s processor memory to your hard disk or to an EEPROM. If you do not, the controller s user memory will be lost because the firmware update procedure erases memory. 1. Save the controller s processor memory to your hard disk or to an EEPROM. 2. Disconnect all cables (serial, DH+, ControlNet, Ethernet, etc.) from the controller. 3. Remove power from the controller and remove it from the chassis. 4. Remove the controller battery cover and disconnect the battery. 5. If applicable, disconnect the coprocessor or Ethernet Interface sidecar module. Allen-Bradley Motors

22 22 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 2 - Install the New Firmware EPROMS 1. Disassemble the controller to begin the EPROM replacement: On the Enhanced PLC-5 Programmable Controllers, Series A thru D: L11B, -L20B and -L26B programmable controllers Replace the U61 and U70 EPROMS* If applicable, replace the U18 EPROM* U18* (if applicable) U61* U70* Do this: 1. Remove the four screws that hold the right side plastic cover. 2. Remove the cover. 3. Remove the two large screws and washers located in the center of the exposed circuit board. 4. Carefully separate the two processor boards by pulling the exposed circuit board at the backplane edge connector away from the metal cover as you would open a book. 5. Remove and replace the firmware EPROMS one at a time, taking note of the location number and the orientation of the notch in each of the EPROMS. 6. See the figure to the left for the numbers and locations of the EPROMS. 7. Reassemble the controller by reversing steps 1 thru 4. On the Enhanced PLC-5 Programmable Controllers, Series A thru D: Do this: 1785-L30B programmable controller 1. On the front of the controller, remove the 2 hex nuts on Channel Remove the screw on the communication card and remove the card. Replace the U5 and U31 EPROMS on the circuit board* If applicable, replace the U7 or U12 EPROM on the communication card* U5* U31* U7 or U12 (if applicable) Remove communication card 3. Remove the four screws that hold the right side plastic cover and remove the cover. 4. Remove the two large screws and washers located in the center of the exposed circuit board. 5. Carefully separate the two processor boards by pulling the exposed circuit board at the backplane edge connector away from the metal cover as you would open a book. 6. Gently pull the communication card off of the circuit board. 7. Remove and replace the firmware EPROMS one at a time, taking note of the location number and the orientation of the notch in each of the EPROMS. 8. See the figure to the left for the numbers and locations of the EPROMS. 9. Reassemble the controller by reversing steps 1 thru 6. * EPROM numbers may vary and their locations shown in these illustrations are approximate. Your series and revision of controller and firmware may be different. Make certain the EPROM numbers from your firmware update match the numbers on their respective circuit boards and communication cards.

23 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 23 On the Enhanced PLC-5 Programmable Controllers, Series A thru D: 1785-L40B, -L46B, -L60B, -L80B and -L86B programmable controllers Replace the U5 and U31 EPROMS on the circuit board* Replace the U7 or U12 EPROM on the chassis communication card (if applicable)* U5* U31* U12* U7* Replace the firmware EPROM on the chassis circuit board (if applicable)* Replace the U12 EPROM on the circuit board communication card* PLC-5 Chassis Do this: 1. Remove the four screws that hold the right side plastic cover. 2. Remove the cover and remove the communication cards. 3. Remove the two large screws and washers located in the middle of the exposed circuit board. 4. Separate the two processor boards by pulling the exposed circuit board at the backplane edge connector away from the metal cover as you would open a book. 5. Notice the direction in which the battery cable is wrapped around the nearby standoff. 6. Disconnect the wires leading from the battery to the stake pins on the exposed circuit board. 7. Disconnect the wires leading from the keyswitch to the stake pins on the exposed circuit board. 8. Remove both communication cards. 9. Remove and replace the firmware EPROMS one at a time, taking note of the location number and the orientation of the notch in each of the EPROMS. 10. See the figure to the left for the numbers and locations of the EPROMS. 11. Reassemble the controller by reversing steps 1 thru 8. * EPROM numbers may vary and their locations shown in these illustrations are approximate. Your series and revision of controller and firmware may be different. Make certain the EPROM numbers from your firmware update match the numbers on their respective circuit boards and communication cards. Allen-Bradley Motors

24 24 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 4 - Apply the Firmware Revision Label IMPORTANT It is important to apply this label to your programmable controller to ensure you receive the correct version back if you send it in for repair. 1. Apply the new firmware revision label on or below the existing product identification label (depending on the series and revision of controller). Make certain to place the label so that the current series and revision information is clearly visible. CAT. NO. REV L40E C D ETHERNET PLC-5/40 PROCESSOR MADE IN USA PART NO A01 BACKPLANE CURRENT REQUIREMENTS 3.3A AT 5VDC F/W REV Q.2 SERIES C FIRMWARE UPGRADE CAT. NO L40E SERIES REV. D G.2 Place new label over previous label or below entire product label. Step 5 - Complete the Firmware Update 1. Install the controller into the chassis. 2. Reconnect any cables. 3. Apply power to the controller. 4. After powerup, check the status of the controller: If: PROC LED is solid red and CH1A DH+ LED is blinking green PROC LED is solid red but the CH1A DH+ LED is not blinking green Then: Update is complete. Proceed to Step 5 below. Make certain that all new EPROMS are properly installed (notches on circuit board and EPROMS match, there are no bent pins, EPROMS are installed in the correct location).

25 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers When the update is successful: restore all connections to the controller download the program back into memory and make certain that it runs properly Your firmware update is complete. If you have any questions, call Rockwell Automation Technical Support at Enhanced PLC-5 Programmable Controllers - Series E or Later To update these series of Enhanced PLC-5 firmware, you must first use ControlFLASH and then if applicable, replace EPROMS. To start this firmware update, follow these steps: Step 1 - Prepare the PLC-5 Programmable Controller ATTENTION You must save the controller s processor memory to your hard disk or to an EEPROM. If you do not, the controller s user memory will be lost because the firmware update procedure erases memory. 1. Save the controller s processor memory to your hard disk or to an EEPROM. 2. Disconnect all cables (serial, DH+, ControlNet, Ethernet, etc.) from the controller. 3. Remove power from the controller and remove it from the chassis. 4. Remove the controller battery cover and disconnect the battery. This resets the serial port to its default configuration so that the controller and ControlFLASH can communicate. 5. If applicable, disconnect the coprocessor or Ethernet Interface sidecar module. 6. Verify that the serial port DIP switches are set for RS Reinstall the controller and apply power. 8. Turn the controller keyswitch to PROGRAM mode. Allen-Bradley Motors

26 26 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 2 - Install the ControlFLASH Software 1. Insert the ControlFLASH disk into the floppy drive of your computer. 2. Browse the A: drive and select the setup.exe program. 3. If you have an earlier version of ControlFLASH installed, we recommend to install this version into the same directory. 4. Follow the Setup Wizard as it guides you through the installation process. Step 3 - Perform the ControlFLASH Update ATTENTION Failure to follow these procedures exactly or to cause an interruption during them may result in an inoperable controller. 1. Connect the computer to the controller using a 1784-CP10 or -CP11 cable between the computer and Channel 0 of the controller 2. Close all applications including RSLinx.

27 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Start ControlFLASH: 3A - Start the ControlFLASH software. Click Next. 3B - Select the appropriate PLC-5 Programmable Controller catalog number. Use the cursor to highlight the PLC-5 type Click Next. Allen-Bradley Motors

28 28 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 3C - Select the serial port of the computer to which you connected the 1784-CP10 or -CP11 cable. Select COM1 or COM2. Click Get Info to verify the programmable controller you are updating. Click Next. 3D - Select the firmware revision. Select the correct update revision. Click Next. 3E - Verify the update. Click Finish.

29 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 29 3F - Start the firmware update. Click Yes. The progress indicator shows how much of the update has been performed. Important: This update will take approximately 8 or 9 minutes to complete. 3G - Follow the power cycle instructions during and after the update process. When the update is complete, the software will prompt you to cycle power. Important: If you are updating the firmware EPROM on the communication card, you must first complete the next three steps: - Install the New Firmware EPROMS - Apply the Firmware Revision Label - Complete the Firmware Update If you are not updating the firmware EPROM on the communication card, skip to step 5 Apply the Firmware Revision Label. These procedures are detailed on the following pages. 4. Remove power from the controller. 5. Remove the controller from the chassis. Allen-Bradley Motors

30 30 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 4 - Install the New Firmware EPROMS (if applicable) 1. Disassemble the controller to begin the EPROM replacement: On the Enhanced PLC-5 Programmable Controllers, Series E or later: If applicable, replace the U18 EPROM* U18* (if applicable) Do this: 1. Remove the four screws that hold the right side plastic cover. 2. Remove the cover. 3. Remove the two large screws and washers located in the center of the exposed circuit board. 4. Carefully separate the two processor boards by pulling the exposed circuit board at the backplane edge connector away from the metal cover as you would open a book. 5. Remove and replace the firmware EPROMS one at a time, taking note of the location number and the orientation of the notch in each of the EPROMS. 6. See the figure to the left for the numbers and locations of the EPROMS. 7. Reassemble the controller by reversing steps 1 thru L30B, -L40B, -L46B, -L60B, -L80B and -L86B programmable controllers Replace the U7 or U12 EPROM on the chassis communication card (if applicable)* U12* U7* PLC-5 Chassis Replace the U12 EPROM on the circuit board communication card* 1. Remove the four screws that hold the right side plastic cover. 2. Remove the cover. 3. Remove the two large screws and washers located in the middle of the exposed circuit board. 4. Separate the two processor boards by pulling the exposed circuit board at the backplane edge connector away from the metal cover as you would open a book. 5. Notice the direction in which the battery cable is wrapped around the nearby standoff. 6. Disconnect the wires leading from the battery to the stake pins on the exposed circuit board. 7. Disconnect the wires leading from the keyswitch to the stake pins on the exposed circuit board. 8. Remove both communication cards. 9. Remove and replace the firmware EPROMS one at a time, taking note of the location number and the orientation of the notch in each of the EPROMS. 10. See the figure to the left for the numbers and locations of the EPROMS. 11. Reassemble the controller by reversing steps 1 thru 8. * EPROM numbers may vary and their locations shown in these illustrations are approximate. Your series and revision of controller and firmware may be different. Make certain the EPROM numbers from your firmware update match the numbers on their respective circuit boards and communication cards.

31 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 31 Step 5 - Apply the Firmware Revision Label IMPORTANT It is important to apply this label to your programmable controller to ensure you receive the correct version back if you send it in for repair. 1. Apply the new firmware revision label on or below the existing product identification label (depending on the series and revision of controller). Make certain to place the label so that the current series and revision information is clearly visible. CAT. NO. REV L40E C D ETHERNET PLC-5/40 PROCESSOR MADE IN USA PART NO A01 BACKPLANE CURRENT REQUIREMENTS 3.3A AT 5VDC F/W REV Q.2 SERIES C FIRMWARE UPGRADE CAT. NO L40E SERIES REV. D G.2 Place new label over previous label or below entire product label. Allen-Bradley Motors

32 32 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 6 - Complete the Firmware Update 1. Install the controller into the chassis. 2. Apply power to the controller 3. In ControlFLASH: At the Cycle Power prompt, click OK The update process is now complete. If an error occurs, click View Log to see specific error information (see the table below). The Status windows displays the result of the update. If an error occurs, it is displayed in this window. Click OK. 4. After powerup, check the status of the controller: If: PROC LED is solid red and CH1A DH+ LED is flashing green PROC LED is solid red but the CH1A DH+ LED is not flashing green PROC LED is flashing red. CH1A is not flashing green Then: Update is complete. Proceed to Step 5 below. Make certain that all new EPROMS are properly installed (notches on circuit board and EPROMS match, there are no bent pins, EPROMS are installed in the correct location). Call Rockwell Automation Technical Support at Send controller in for repair. 5. When the update is successful: restore all connections to the controller download the program back into memory and make certain that it runs properly Your firmware update is complete. If you have any questions, call Rockwell Automation Technical Support at

33 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 33 ControlNet PLC-5 Programmable Controllers - All Series To update these series of ControlNet PLC-5 firmware, you must first use ControlFLASH and then if applicable, replace EPROMS. To start this firmware update, follow these steps: Step 1 - Prepare the PLC-5 Programmable Controller ATTENTION You must save the controller s processor memory to your hard disk or to an EEPROM. If you do not, the controller s user memory will be lost because the firmware update procedure erases memory. 1. Save the controller s processor memory to your hard disk or to an EEPROM. 2. Disconnect all cables (serial, DH+, ControlNet, Ethernet, etc.) from the controller. 3. Remove power from the controller and remove it from the chassis. 4. Remove the controller battery cover and disconnect the battery. This resets the serial port to its default configuration so that the controller and ControlFLASH can communicate. 5. If applicable, disconnect the coprocessor or Ethernet Interface sidecar module. 6. Verify that the serial port DIP switches are set for RS Reinstall the controller and apply power. 8. Turn the controller keyswitch to PROGRAM mode. Allen-Bradley Motors

34 34 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 2 - Install the ControlFLASH Software 1. Insert the ControlFLASH disk into the floppy drive of your computer. 2. Browse the A: drive and select the setup.exe program. 3. If you have an earlier version of ControlFLASH installed, we recommend to install this version into the same directory. 4. Follow the Setup Wizard as it guides you through the installation process. Step 3 - Perform the ControlFLASH Update ATTENTION Failure to follow these procedures exactly or to cause an interruption during them may result in an inoperable controller. 1. Connect the computer to the controller using a 1784-CP10 or -CP11 cable between the computer and Channel 0 of the controller 2. Close all applications including RSLinx.

35 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Start ControlFLASH: 3A - Start the ControlFLASH software. Click Next. 3B - Select the appropriate PLC-5 Programmable Controller catalog number. Use the cursor to highlight the PLC-5 type Click Next. Allen-Bradley Motors

36 36 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 3C - Select the serial port of the computer to which you connected the 1784-CP10 or -CP11 cable. Select COM1 or COM2. Click Get Info to verify the programmable controller you are updating. Click Next. 3D - Select the firmware revision. Select the correct update revision. Click Next. 3E - Verify the update. Click Finish.

37 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 37 3F - Start the firmware update. Click Yes. The progress indicator shows how much of the update has been performed. Important: This update will take approximately 13 minutes to complete. 3G - Follow the power cycle instructions during and after the update process. When the update is complete, the software will prompt you to cycle power. Important: If you are updating the firmware EPROM on the communication card, you must first complete the next three steps: - Install the New Firmware EPROMS - Apply the Firmware Revision Label - Complete the Firmware Update If you are not updating the firmware EPROM on the communication card, skip to step 5 Apply the Firmware Revision Label. These procedures are detailed on the following pages. 4. Remove power from the controller. 5. Remove the controller from the chassis. Allen-Bradley Motors

38 38 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Step 4 - Install the New Firmware EPROMS (if applicable) On the ControlNet PLC-5 Programmable Controllers, Series C and D: 1785-L20C, -L40C, -L60C, -L80C, -L20C15, -L40C15, -L60C15, and L80C15 programmable controllers Do this: 1. On the front of the controller, remove the screw on the communication card. 2. Gently pull the communication card out of the controller chassis. 3. Remove and replace the U7 or U12 EPROM, taking note of the location number and the orientation of the notch in the EPROM. 4. See the figure to the left for the location of the EPROM. 9. Reassemble the controller by reversing steps 1 thru 3. U7 or U12* Remove communication card On the ControlNet PLC-5 Programmable Controllers, Series E and F: Do this: 1785-L20C, -L40C, -L80C, -L20C15, -L40C15 and L80C15 programmable controllers 1. On the front of the controller, remove the 2 hex nuts on Channel Remove the screw on the communication card. 3. Remove the four screws that hold the right side plastic cover and remove the cover. 4. Remove the two large screws and washers located in the center of the exposed circuit board. 5. Carefully separate the two processor boards by pulling the exposed circuit board at U7 or U12 the backplane edge connector away from the (if applicable)* metal cover as you would open a book. 6. Gently pull the communication card off of the circuit board. 7. Remove and replace the U7 or U12 EPROM, taking note of the location number and the orientation of the notch in the EPROM. 8. See the figure to the left for the location of Remove communication card the EPROM. 9. Reassemble the controller by reversing steps 1 thru 6. * EPROM numbers may vary and their locations shown in these illustrations are approximate. Your series and revision of controller and firmware may be different. Make certain the EPROM numbers from your firmware update match the numbers on their respective circuit boards and communication cards. Note: Do not reinstall the controller until you complete the next step.

39 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers 39 Step 5 - Apply the Firmware Revision Label IMPORTANT It is important to apply this label to your programmable controller to ensure you receive the correct version back if you send it in for repair. 1. Apply the new firmware revision label on or below the existing product identification label (depending on the series and revision of controller). Make certain to place the label so that the current series and revision information is clearly visible. CAT. NO. REV L40E C D ETHERNET PLC-5/40 PROCESSOR MADE IN USA PART NO A01 BACKPLANE CURRENT REQUIREMENTS 3.3A AT 5VDC F/W REV Q.2 SERIES C FIRMWARE UPGRADE CAT. NO L40E SERIES REV. D G.2 Place new label over previous label or below entire product label. Step 6 - Complete the Firmware Update 1. Install the controller into the chassis. 2. Apply power to the controller. 3. In ControlFLASH: At the Cycle Power prompt, click OK The update process is now complete. The Status windows displays the result of the update. If an error occurs, it is displayed in this window. If an error occurs, click View Log to see specific error information (see the table on the next page). Click OK. Allen-Bradley Motors

40 4. After powerup, check the status of the controller: If: PROC LED is solid red and CH1A DH+ LED is blinking green PROC LED is flashing red. CH1A is not flashing green PROC LED is flashing red and green You get a PLC Mismatch error: Incorrect Selection of PLC Device You get an Error Reading Serial Number: Invalid Serial Number Then: Update is complete. Proceed to Step 5 below. Call Rockwell Automation Technical Support at Send controller in for repair. Repeat the ControlFLASH procedure The controller you selected and the controller you are trying to update are different. Repeat the procedure and select the correct controller. The PLC-5 programmable controller was previously updated incorrectly. Send it in for repair. 5. When the update is successful: restore all connections to the controller download the program back into memory and make certain that it runs properly Your firmware update is complete. If you have any questions, call Rockwell Automation Technical Support at PLC-5, ControlNet, Allen-Bradley, DH+, PLC-5/20, -5/20C, -5/30, -5/40, -5/40C, -5/60, -5/80, -5/80C, -5/20E, -5/40E, -5/80E, and RSLinx are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. 40 PN Supersedes Publication 1785-IN022B-EN-P - November 2002 Copyright 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

InView Firmware Update

InView Firmware Update Installation Instructions InView Firmware Update Topic Page Hazardous Voltage 3 Change EPROM on 2706-P72, 2706-P74 Display 3 Change EPROM on 2706-P42, 2706-P44 Displays 5 Firmware Upgrade Kit 7 2 InView

More information

PCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer

PCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer Installation Instructions PCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer Catalog Number 6189V-2PCI15R Topic Page About This Publication 1 Important User Information 2 Safety

More information

PowerMonitor 5000 Unit Catalog Number Upgrade

PowerMonitor 5000 Unit Catalog Number Upgrade Installation Instructions PowerMonitor 5000 Unit Catalog Number Upgrade Catalog Numbers 1426-MxE-xxx Topic Page Upgrade the Device Catalog Number with the ControlFLASH Utility 3 Determine Communication

More information

ProcessLogix R510.0 Server Installation Instructions

ProcessLogix R510.0 Server Installation Instructions ProcessLogix R510.0 Server Installation Instructions Installation Instructions Before you begin... This publication guides you through the remaining processes required to initialize a ProcessLogix Server.

More information

PowerMonitor 1000 Unit Catalog Number Upgrade

PowerMonitor 1000 Unit Catalog Number Upgrade Installation Instructions PowerMonitor 1000 Unit Catalog Number Upgrade Catalog Numbers 1408-UPT1-E3, 1408-UPT2-E3, 1408-UPE1-E3, 1408-UPE2-E3, 1408-UP485-ENT, 1408-UPT3-E3 Topic Important User Information

More information

Installation Instructions

Installation Instructions Installation Instructions (Cat. No. 1771-OBN Series B) Use this document as a guide when installing the catalog number 1771-OBN series B output module. Because of the variety of uses for the products described

More information

Digital ac/dc (24V) Input Module

Digital ac/dc (24V) Input Module Installation Instructions Digital ac/dc (24V) Input Module Catalog Number 1771-IND, Series C Topic Page Important User Information 2 Before You Begin 3 Power Requirements 3 Prevent Electrostatic Discharge

More information

Adapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout

Adapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout Installation Instructions Adapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout Catalog Numbers 2711-NR5T, 2711P-RAT12E2 Topic Page About This Publication 1 Important User Information 2 About

More information

Installation Instructions

Installation Instructions Installation Instructions Cat. No. 1771 P3, P4, P5 and P5E Use this document as a guide when installing the catalog number 1771-P3, -P4, -P5 or -P5E power supplies. Because of the variety of uses for the

More information

Catalog Numbers 9308-RSFB64ENE, 9308-RSFB256ENE, 9308-RSFB1024ENE

Catalog Numbers 9308-RSFB64ENE, 9308-RSFB256ENE, 9308-RSFB1024ENE Release Notes RSFieldbus Software Catalog Numbers 9308-RSFB64ENE, 9308-RSFB256ENE, 9308-RSFB1024ENE Topic Page Important User Information 2 Before You Begin 3 Software Requirements 4 Install the Software

More information

Kinetix 300 Memory Module Programmer

Kinetix 300 Memory Module Programmer Kinetix 300 Memory Module Programmer Catalog Number 2097-PGMR Topic About the Memory Module Programmer 1 Parts List 3 Batteries Operation 4 Using Memory Module Programmer 6 Switch On/Off Memory Module

More information

ControlLogix Redundancy Update and Module Replacement Guidelines

ControlLogix Redundancy Update and Module Replacement Guidelines Reference Manual Original Instructions ControlLogix Redundancy Update and Module Replacement Guidelines Product Family ControlLogix 5570 Controllers Important User Information Read this document and the

More information

Kinetix 6000 Axis Module and Shunt Module

Kinetix 6000 Axis Module and Shunt Module Installation Instructions Kinetix 6000 and Shunt Module Catalog Numbers 2094-AMxx, 2094-BMxx 2094-AMxx-S, 2094-BMxx-S 2094-BSP2 Topic Page About This Publication 1 Important User Information 2 Before You

More information

Throughout this manual we use notes to make you aware of safety considerations:

Throughout this manual we use notes to make you aware of safety considerations: Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have

More information

PanelViewt 1200 Transfer Utility User Manual

PanelViewt 1200 Transfer Utility User Manual User Manual Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State

More information

Using GuardShield Light Curtains (Safe 4, Micro 400, or 440L), with ArmorBlock Guard I/O and SmartGuard Controller

Using GuardShield Light Curtains (Safe 4, Micro 400, or 440L), with ArmorBlock Guard I/O and SmartGuard Controller Safety Application Example Using GuardShield Light Curtains (Safe 4, Micro 400, or 440L), with ArmorBlock Guard I/O and SmartGuard Controller Light Curtain with On-machine Components Safety Rating: Category

More information

Installation Instructions

Installation Instructions Installation Instructions (Catalog Number 1771-OD) This document provides information on: Because of the variety of uses for the products described in this publication, those responsible for the application

More information

Simple Package Measurement Connected Components Building Block. Quick Start

Simple Package Measurement Connected Components Building Block. Quick Start Simple Package Measurement Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

Color-Sensing Connected Components Building Block. Quick Start

Color-Sensing Connected Components Building Block. Quick Start Color-Sensing Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety

More information

GuardLogix: Safety Gate Application with SensaGuard Switch

GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example GuardLogix: Safety Gate Application with SensaGuard Switch Safety Rating: PLe, Cat. 4 to EN ISO 13849.1 2008 Introduction...2 Important User Information...2 General Safety Information...3

More information

ControlLogix SIL2 System Configuration

ControlLogix SIL2 System Configuration ControlLogix SIL2 System Configuration Using RSLogix 5000 Subroutines Application Technique (Catalog Numbers 1756 and 1492) Important User Information 8 / 2011 Solid state equipment has operational characteristics

More information

Differential Liquid/Gas Pressure Transmitter

Differential Liquid/Gas Pressure Transmitter Installation Instruction Differential Liquid/Gas Pressure Transmitter Catalog Number(s) 1414-CPZ10FWFAA, 1414-IPZ10FWFAA Explosion Hazard WARNING Do not use in an explosive or hazardous environment, with

More information

Teaching Color-Sensing Connected Components Building Block. Quick Start

Teaching Color-Sensing Connected Components Building Block. Quick Start Teaching Color-Sensing Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

Installation Instructions

Installation Instructions Installation Instructions (Cat. No. 71-A1B, -A2B, -A3B, -A3B1, -A4B Series B) Because of the variety of uses for the products described in this publication, those responsible for the application and use

More information

GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch

GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch Safety Application Example GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch Safety Rating: PLd, Cat. 3 to EN ISO 13849.1 2008 Introduction... 2 Important User Information...

More information

GuardLogix Controller to Kinetix 6000 Drive with Safe-Off using EtherNet/IP CompactBlock Guard I/O Module

GuardLogix Controller to Kinetix 6000 Drive with Safe-Off using EtherNet/IP CompactBlock Guard I/O Module Safety Application Example GuardLogix Controller to Kinetix 6000 Drive with Safe-Off using EtherNet/IP CompactBlock Guard I/O Module Safety Rating: SIL3/Category 3 (also see SIL3/CAT4 section), according

More information

Throughout this manual we use notes to make you aware of safety considerations:

Throughout this manual we use notes to make you aware of safety considerations: Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have

More information

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon Allen-Bradley PLC-5 Backup Communication Module User Manual (1785-BCM, 1785-BEM) product icon Important User Information Because of the variety of uses for this product and because of the differences between

More information

Installation Instructions

Installation Instructions Installation Instructions Use these instructions to help you: determine the equipment needed for installing the A-B station module install the A-B station module Before installing the A-B station module,

More information

InView Communication Modules

InView Communication Modules Installation Instructions InView Communication Modules Catalog Numbers 2706-PxM, 2706-PxK, 2706-PxP Topic Page About This Publication 1 Important User Information 2 Power Supply Requirements 3 Mount the

More information

DeviceNet Network Configuration

DeviceNet Network Configuration User Manual DeviceNet Network Configuration 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, Studio 5000 Logix Emulate Important User Information Solid-state

More information

Logix5000 Controllers Nonvolatile Memory Card

Logix5000 Controllers Nonvolatile Memory Card Programming Manual Logix5000 Controllers Nonvolatile Memory Card 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, 5069 CompactLogix, Studio 5000 Logix Emulate

More information

Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller

Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller Safety Application Example Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller Guardlocking with On-machine Components Safety Rating: Category 3, according to EN954-1

More information

GuardLogix: TLS Guardlocking Application

GuardLogix: TLS Guardlocking Application Safety Application Example GuardLogix: TLS Guardlocking Application Safety Rating: PLd, Cat. 3 to EN ISO 13849.1 2008 Introduction... 2 Important User Information... 2 General Safety Information... 3 Description...

More information

Studio 5000 Architect Getting Results Guide

Studio 5000 Architect Getting Results Guide Getting Results Studio 5000 Architect Getting Results Guide Rockwell Automation Publication ARCH-GR001I-EN-E Supersedes Publication ARCH-GR001H-EN-E Important user information Read this document and the

More information

ArmorPoint I/O Field Potential Distributor, Series A

ArmorPoint I/O Field Potential Distributor, Series A Installation Instructions ArmorPoint I/O Field Potential Distributor, Series A (Cat. No. 1738-FPD) The field potential distributor (Cat. no. 1738-FPD) lets you change the field power distribution source

More information

Micro800 Controllers Starter Pack Quick Start

Micro800 Controllers Starter Pack Quick Start Quick Start Micro800 Controllers Starter Pack Quick Start Catalog Numbers Bulletin 2080-LC20, 2080-LC30, 2080-LC50 Important User Information Read this document and the documents listed in the additional

More information

PanelView 600 Terminals

PanelView 600 Terminals Installation Instructions PanelView 600 Terminals Catalog Numbers 2711-K6Cxx, 2711-B6Cxx Topic Page Hazardous Location Considerations 3 European Union Directive Compliance 4 Wiring and Safety Guidelines

More information

DriveGuard. Safe-Off Option for PowerFlex 70 AC Drives. User Manual.

DriveGuard. Safe-Off Option for PowerFlex 70 AC Drives. User Manual. DriveGuard Safe-Off Option for PowerFlex 70 AC Drives User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Installation Instructions

Installation Instructions Installation Instructions Cat. No. 1771-IQ16 Series C This document provides information on: The dc isolated input module is shipped in static-shielded packaging to guard against electrostatic discharge

More information

CompactLogix Power Supplies Specifications

CompactLogix Power Supplies Specifications Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,

More information

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication Remote I/O Scanner Catalog Number 1747-SN Installation Instructions 2 Remote I/O Scanner Important User Information Because of the variety of uses for the products described in this publication, those

More information

CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter

CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter User Manual CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter Catalog Numbers 2100-ENET Series A FRN 1.XXX Important User Information Solid-state equipment has operational characteristics

More information

256 Kbytes (1771-DRS) 1 Mbyte (1771-DRS1) 4 Mbytes (1771-DRS4) Installation Data

256 Kbytes (1771-DRS) 1 Mbyte (1771-DRS1) 4 Mbytes (1771-DRS4) Installation Data Installation Data You can add static RAM memory to your control coprocessor main module to expand user memory. The RAM single inline memory module (SIMM) is available in the following sizes: 256 Kbytes

More information

DeviceNet Communications

DeviceNet Communications DeviceNet Communications For PanelView Plus and PanelPlus CE Terminals 2711P User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

PanelView 800 HMI Terminals

PanelView 800 HMI Terminals User Manual PanelView 800 HMI Terminals Catalog Numbers 2711R-T4T, 2711R-T7T, 2711R-T10T Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

EtherNet/IP Adapter. 20-COMM-E FRN 2.xxx. User Manual. AB Drives

EtherNet/IP Adapter. 20-COMM-E FRN 2.xxx. User Manual. AB Drives AB Drives EtherNet/IP Adapter 20-COMM-E FRN 2.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety

More information

PanelView 800 HMI Terminals

PanelView 800 HMI Terminals User Manual PanelView 800 HMI Terminals Catalog Numbers 2711R-T4T, 2711R-T7T, 2711R-T10T Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Logix5000 Control Systems: Connect a PanelView Plus Terminal over an EtherNet/IP Network

Logix5000 Control Systems: Connect a PanelView Plus Terminal over an EtherNet/IP Network Quick Start Logix5000 Control Systems: Connect a PanelView Plus Terminal over an EtherNet/IP Network Catalog Numbers Logix5000 Controllers, 2711P PanelView Plus Terminals Important User Information Solid-state

More information

PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller

PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller Safety Application Example PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller Safety Rating: Category 3 (also see Achieving a Cat. 4 Safety Rating)

More information

Import/Export Project Components. Programming Manual

Import/Export Project Components. Programming Manual Import/Export Project Components Programming Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

More information

Micro800 Programmable Controllers: Getting Started with Motion Control Using a Simulated Axis

Micro800 Programmable Controllers: Getting Started with Motion Control Using a Simulated Axis Quick Start Micro800 Programmable Controllers: Getting Started with Motion Control Using a Simulated Axis Catalog Numbers Bulletin 2080-LC30, 2080-LC50 Important User Information Solid-state equipment

More information

Installation Instructions

Installation Instructions Installation Instructions (Catalog Number 1771-IR Series D) Use this document as a guide when installing the 1771-IR/D input module. The RTD input module is sensitive to electrostatic discharge. ATTENTION:

More information

Field Upgrading Bulletin 1404 Power Monitor Version 4.2x base and 4.1x Ethernet Communications Firmware

Field Upgrading Bulletin 1404 Power Monitor Version 4.2x base and 4.1x Ethernet Communications Firmware Field Upgrading Bulletin 1404 Power Monitor Version 4.2x base and 4.1x Ethernet Communications Firmware Introduction Please read this document before upgrading a Powermonitor 3000 to version 4.2x firmware

More information

Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller

Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller Safety Application Example Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller Safety Rating: Category 3, according to EN954-1 Introduction...

More information

Simple Motion Control Connected Components Building Block. Quick Start

Simple Motion Control Connected Components Building Block. Quick Start Simple Motion Control Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

Application Technique. Safety Function: Safety Camera with E-stop

Application Technique. Safety Function: Safety Camera with E-stop Application Technique Safety Function: Safety Camera with E-stop Products: Guardmaster Dual-input Safety Relay, Guardmaster SC300 Safety Camera Safety Rating: PLd, Cat. 3 to EN ISO 13849-1: 2008 2 Safety

More information

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000 GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000 Instruction Manual D2-3390-2 The information in this manual is subject to change without notice. Throughout this manual, the

More information

Installation Instructions

Installation Instructions Installation Instructions This document provides information on: important pre-installation considerations power supply requirements initial handling procedures installing the module using the indicators

More information

Installation Instructions

Installation Instructions Installation Instructions (1771-ODD Series B) Use this document as a guide when installing the catalog number 1771-ODD series B output module. The ac isolated output module is shipped in static-shielded

More information

Version 1.2. January Publication ERSC-1300

Version 1.2. January Publication ERSC-1300 Version 1.2 January 2016 Publication ERSC-1300 ConveyLinx module firmware and functionality is protected by U.S. and international patents. For complete patent information visit www.pulseroller.com/patents

More information

PowerFlex 700S Phase II Drives DriveLogix Option Card Battery Extension Cable

PowerFlex 700S Phase II Drives DriveLogix Option Card Battery Extension Cable Installation Instructions PowerFlex 700S Phase II Drives DriveLogix Option Card Battery Extension Cable!!!!! ATTENTION: To avoid an electric shock hazard, ensure that all power to the drive has been removed

More information

PCI 2 Axis Servo Card

PCI 2 Axis Servo Card Installation Instructions PCI 2 Axis Servo Card (Catalog Number 1784-PM02AE) This manual provides the instructions for installing the PCI 2 Axis Servo card (1784-PM02AE) in a PC computer using the NT operating

More information

DataSite Electronic Flow Meter and Remote Terminal Unit

DataSite Electronic Flow Meter and Remote Terminal Unit DataSite Electronic Flow Meter and Remote Terminal Unit Catalog Numbers 1758-FLO301, 1758-FLO302, 1758- RTU201, 1758-RTU202 Software User Manual FRN 1.30 Important User Information Solid state equipment

More information

Logix5000 Controllers Produced and Consumed Tags

Logix5000 Controllers Produced and Consumed Tags Logix5 Controllers Produced and Consumed Tags Catalog Numbers 1756 ControlLogix, 1756 GuardLogix, 1768 Compact GuardLogix, 1769 CompactLogix, 1789 SoftLogix, PowerFlex with DriveLogix Programming Manual

More information

Embedded I/O Expansion Board with 10 Outputs

Embedded I/O Expansion Board with 10 Outputs Installation Instructions Embedded I/O Expansion Board with 10 Outputs Catalog Number 1799-OQ10X Topic Page Important User Information 2 Environment and Enclosure 3 About the Board 4 Install the Board

More information

ArmorPoint 24V dc Input Modules, Series A

ArmorPoint 24V dc Input Modules, Series A Installation Instructions ArmorPoint V dc Input Modules, Series A Cat. Nos. 8-IBM, -IBM8, -IBM, -IB8M8, -IB8M, -IB8M, -IVM, -IV8M8, -IV8M, -IV8M The ArmorPoint I/O family consists of modular I/O modules.

More information

Micro800 Programmable Controllers: Getting Started with CIP Client Messaging

Micro800 Programmable Controllers: Getting Started with CIP Client Messaging Quick Start Micro800 Programmable Controllers: Getting Started with CIP Client Messaging Catalog Numbers Bulletin 2080-LC20, 2080-LC30, 2080-LC50 Important User Information Solid-state equipment has operational

More information

Installation Instructions

Installation Instructions Installation Instructions Cat. No. 1771-OND Series B This document provides information on: important pre-installation considerations power supply requirements installing the module setting the fault mode

More information

DriveLogix 5730 Controller

DriveLogix 5730 Controller DriveLogix 5730 Controller for PowerFlex 700S Drives with Phase II Control Firmware Version 13.XX User Manual Important User Information Solid state equipment has operational characteristics differing

More information

SequenceManager Controls

SequenceManager Controls Reference Manual SequenceManager Controls 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, Studio 5000 Logix Emulate Important user information Read this

More information

PanelView 800 HMI Terminals

PanelView 800 HMI Terminals User Manual PanelView 800 HMI Terminals Catalog Numbers 2711R-T4T, 2711R-T7T, 2711R-T10T Industrial automation Elincom Group European Union: www.elinco.eu Russia: www.elinc.ru Important User Information

More information

A TCP/IP network CAT 5 cable If the network is faster than 10baseT a switching hub will be needed Static IP address

A TCP/IP network CAT 5 cable If the network is faster than 10baseT a switching hub will be needed Static IP address Requirements A TCP/IP network CAT 5 cable If the network is faster than 10baseT a switching hub will be needed Static IP address Power Up A Reader with an Ethernet adaptor installed and the network cable

More information

ControlNet Adapters. User Manual. 20-COMM-C (coax) 20-COMM-Q (fiber) FRN 1.xxx

ControlNet Adapters. User Manual. 20-COMM-C (coax) 20-COMM-Q (fiber) FRN 1.xxx ControlNet Adapters 20-COMM-C (coax) 20-COMM-Q (fiber) FRN 1.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

NHP SAFETY REFERENCE GUIDE

NHP SAFETY REFERENCE GUIDE NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Cable Pull Switch - Products: GuardLogix Series Connection of Cable Pull Switches Safety Rating: PLd, Cat. 3 to EN ISO 13849-1: 2008 Table

More information

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC Software Start-Up and Reference Manual D2-3416-2 GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, 30-100 HP, 230V AC Version 6.04 Important User Information Solid-state equipment has operational

More information

Product Compatibility and Download Center

Product Compatibility and Download Center Product Compatibility and Download Center Important User Information This documentation, whether, illustrative, printed, online or electronic (hereinafter Documentation ) is intended for use only as a

More information

Replacement Keyswitch Assembly

Replacement Keyswitch Assembly Installation Instructions Replacement Keyswitch Assembly (Catalog No. 2711E-NKSW1) Applicable Terminals Use this replacement keyswitch with PanelView Terminals 2711-KA1, -KC1, -TA1, -TC1, -TA4, -TC4 and

More information

ControlLogix Configurable Flowmeter Module

ControlLogix Configurable Flowmeter Module User Manual ControlLogix Configurable Flowmeter Module Catalog Numbers 1756-CFM Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical

More information

ControlNet Adapter. 20-COMM-C FRN 1.xxx. User Manual

ControlNet Adapter. 20-COMM-C FRN 1.xxx. User Manual ControlNet Adapter 20-COMM-C FRN 1.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

More information

Application Guide. Considerations for 32 Bit Integer Parameters in 16 Bit Processors. PowerFlex 700VC, PowerFlex 700S. Introduction.

Application Guide. Considerations for 32 Bit Integer Parameters in 16 Bit Processors. PowerFlex 700VC, PowerFlex 700S. Introduction. Topic: Drive Product: Introduction User Information Considerations for 32 Bit Integer Parameters in 16 Bit Processors PowerFlex 700VC, PowerFlex 700S An Application Guide provides generic information on

More information

RGU Main Control Board Replacement Firmware Version 3.01

RGU Main Control Board Replacement Firmware Version 3.01 Replacement Kit Instructions RGU Main Control Board Replacement Firmware Version 3.0 Contents This document shows how to remove and replace the main control board in a Regenerative DC Bus Supply Unit (RGU).

More information

FLEX I/O Dual Port EtherNet/IP Adapter Modules

FLEX I/O Dual Port EtherNet/IP Adapter Modules User Manual FLEX I/O Dual Port EtherNet/IP Adapter Modules Catalog Numbers 1794-AENTR, 1794-AENTRXT Important User Information Solid-state equipment has operational characteristics differing from those

More information

Getting Results Guide. RSLinx Enterprise

Getting Results Guide. RSLinx Enterprise Getting Results Guide RSLinx Enterprise Important user information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this

More information

USB-to-DeviceNet Cable

USB-to-DeviceNet Cable Installation Instructions USB-to-DeviceNet Cable Catalog Number 1784-U2DN Topic Page Important User Information 2 Environment and Enclosure 3 About the Cable 4 Install the Cable 5 Status Indicators 10

More information

PowerFlex DC Drive - Frame A Switching Power Supply Circuit Board

PowerFlex DC Drive - Frame A Switching Power Supply Circuit Board Installation Instructions PowerFlex DC Drive - Frame A Switching Power Supply Circuit Board ATTENTION: Only qualified personnel familiar with DC drives and associated machinery should plan or implement

More information

Getting Started Guide

Getting Started Guide Getting Started Guide DESKTOP Welcome to LumenX Programming Engine Desktop Model The LumenX Desktop is Data I/O s desktop version programming engine. Designed for programming first-article builds to validate

More information

Bidirectional (4-sensor, T-type) Muting With MSR42 Relay Connected Components Building Block

Bidirectional (4-sensor, T-type) Muting With MSR42 Relay Connected Components Building Block Bidirectional (4-sensor, T-type) Muting With MSR42 Relay Connected Components Building Block Catalog Numbers MSR42, MicroLogix 1100, GuardShield Micro 400 Light Curtains Quick Start Important User Information

More information

Logix5000 Controllers Function Block Diagram

Logix5000 Controllers Function Block Diagram Logix5000 Controllers Function Block Diagram Catalog Numbers 1756 ControlLogix, 1769 CompactLogix, 1789 SoftLogix, 1794 FlexLogix, PowerFlex 700S with DriveLogix Programming Manual Important User Information

More information

MC-12 Software Installation Instructions

MC-12 Software Installation Instructions MC-12 DOCUMENTATION CONVENTIONS This document contains software installation instructions for the MC-12/MC-12 Balanced. Refer to the MC-12 User Guide for general safety, installation, and operating instructions.

More information

Logix5000 Control Systems: Connect POINT I/O Modules over a DeviceNet Network

Logix5000 Control Systems: Connect POINT I/O Modules over a DeviceNet Network Quick Start Logix5000 Control Systems: Connect POINT I/O Modules over a DeviceNet Network Catalog Numbers Logix5000 Controllers, 1734 POINT I/O Modules Important User Information Solid-state equipment

More information

Installation Data. The 1771 OB module can control the following output devices: dc motor starters indicators solenoids

Installation Data. The 1771 OB module can control the following output devices: dc motor starters indicators solenoids Installation Data This document provides information on: important pre installation considerations power supply requirements initial handling procedures installing the module using the indicators for troubleshooting

More information

Revision History E F G H J K Revision Description: K > Allegion Rebranding.

Revision History E F G H J K Revision Description: K > Allegion Rebranding. Notes: Enter any notes here. These notes must include: how many sides of the paper are printed ink color (usually black, may also be one or two specific colors, such as a Pantone value, or 17.000 8.500

More information

*E * E E0606

*E * E E0606 75000 SERIES B Instrument BASIC Installation Note Copyright Agilent Technologies, Inc., 1990-2006 *E1300-90020* E1300-90020 E0606 Manual Part Number: E1300-90020 Printed: June 2006 Edition 1 Rev 2 Microfiche

More information

Installation of Firmware Updates on H-2221 GOES Transmitters

Installation of Firmware Updates on H-2221 GOES Transmitters Technical Note H-5221 Firmware Update D117 November 2, 2018 Installation of Firmware Updates on H-2221 GOES Transmitters INTRODUCTION The intent of this document is to provide WaterLOG H-2221 GOES transmitter

More information

Bulletin 1395 ControlNet TM Communication Board

Bulletin 1395 ControlNet TM Communication Board Bulletin 1395 ControlNet TM Communication Board Firmware Rev 1.1 Compatible with ControlNet Version 1.5 User Manual Important User Information Solid state equipment has operational characteristics differing

More information

PCI 2 Axis Servo Card

PCI 2 Axis Servo Card Installation Instructions PCI 2 Axis Servo Card (Catalog Number 1784-PM02AE) This manual provides the instructions for installing the PCI 2 Axis Servo card (1784-PM02AE) in a PC computer using the NT operating

More information

Rockwell Automation Library of Steam Table Instructions

Rockwell Automation Library of Steam Table Instructions Reference Manual Original Instructions Rockwell Automation Library of Steam Table Instructions Version 4.0 Important User Information Read this document and the documents listed in the additional resources

More information

ControlNet Modules in Logix5000 Control Systems

ControlNet Modules in Logix5000 Control Systems ControlNet Modules in Logix5000 Control Systems 1734-ACNR, 1756-CNB, 1756-CNBR, 1784-PCC, 1784-PCIC, 1784-PCICS, 1788-CNC, 1788-CNCR, 1788-CNF, 1788-CNFR, 1794-ACN15, 1794-ACNR15, 1797-ACNR15 User Manual

More information