ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives M/N 915FK2101

Size: px
Start display at page:

Download "ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives M/N 915FK2101"

Transcription

1 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives M/N 915FK2101 Instruction Manual D

2 The information in this manual is subject to change without notice. Throughout this manual, the following notes are used to alert you to safety considerations:! ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Important: Identifies information that is critical for successful application and understanding of the product. The thick black bar shown on the outside margin of this page will be used throughout this instruction manual to signify new or revised text or figures.! ATTENTION: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION: The user is responsible for conforming with all applicable local, national, and international codes. Wiring practices, grounding, disconnects, and overcurrent protection are of particular importance. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION: Do not install modification boards with power applied to the drive. Disconnect and lock out incoming power before attempting such installation. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION: The drive contains ESD- (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing the drive. Erratic machine operation and damage to, or destruction of, equipment can result if this procedure is not followed. Failure to observe this precaution can result in bodily injury. ControlNet is a trademark of ControlNet International, Ltd. FlexPak, WebPak, RSNetWorx, ControlLogix, and Reliance are trademarks of Rockwell Automation Rockwell International Corporation

3 CONTENTS Chapter 1 Chapter 2 Chapter 3 Chapter 4 Chapter 5 Chapter 6 Introduction 1.1 Network Option Board Description Where To Find Additional Information Getting Assistance from Reliance Electric Installation 2.1 Installing the Network Option Board Connecting the Drive to a ControlNet Network Connecting a Programming Device to the Option Board s Network Access Port Drive Configuration 3.1 Setting NETW DROP NUMBER (P.900) Setting CONTROL SOURCE SELECT (P.000) Setting CNI PROG/RUN MODE (P.915) Setting NETW COMM LOSS SELECT (P.901) (FlexPak 3000 Drives Only) Setting NETW OUT REG 1 SELECT (P.902) Setting NETW OUT REG 2 SELECT (P.903) Setting NETW OUT REG 3 SELECT (P.904) NETW COMM STATUS (P.908) NETW TYPE & VERSION (P.909) NETWORK KIT (P.796) NETW IN REG 1 (P.905) NETW IN REG 2 (P.906) NETW IN REG 3 (P.907) Programming the Drive 4.1 About ControlNet Network Communication Configuring Drive Reference and Feedback Data as Scheduled Transfers Configuring Scheduled Data Transfers Programming Scheduled Drive Reference Data Using Scheduled Drive Feedback Data Using Unscheduled Transfers About MSG Instruction Timing About the Files You Can Access Using the Drive Parameters Data (N10:x) Using the Drive Display Data (N11:x) Using the Drive Reference and Feedback Data (N12:x) Using the Write Status (File N20:x) to Troubleshoot a Drive Parameter Configuring ControlLogix Applications Configuring SLC500 Applications 6.1 Required Software and Equipment Network Configuration KFC15 Set Up Contents I

4 6.4 Scheduled Messaging (I/O) Unscheduled Messaging SLC500 Support Chapter 7 Chapter 8 Chapter 9 Register Map for FlexPak 3000 Drives Register Map for WebPak 3000 Drives Communication Error Codes II ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

5 List of Figures Figure 1.1 ControlNet Network Communication Option Board Figure 2.1 Opening the Carrier Figure 2.2 Removing the Carrier Shield Figure 2.3 Removing the Shield Ground Wire Figure 2.4 Installing the Network Communication Option Board Figure 2.5 Connecting a FlexPak 3000 Drive or a WebPak 3000 Drive to the Control- Net Network Figure 4.1 Drive Information Map Figure 5.1 RSLogix 5000: I/O Configuration Selection Figure 5.2 RSLogix 5000: New Module Selection Figure 5.3 Select Module Type: 1756-CNB/B Selection Figure 5.4 Module Properties: Name Selection Figure 5.5 Module Properties: Controller-to-Module Behavior Screen Figure 5.6 Module Properties: Identification/Status Screen Figure 5.7 Module Properties: Informational Screen Figure 5.8 RSLogix 5000: I/O Configuration Folder Figure 5.9 RSLogix 5000: New Module Selection Screen Figure 5.10 Select Drive Type: FlexPak Figure 5.11 Module Properties: Name Selection Figure 5.12 Module Properties: RPI Selections Figure 5.13 Module Properties: Cnet_Bridge Figure 5.14 RSLogix: Configure Additional Nodes Screen Figure 5.15 RSLogix 5000: Module-Defined Screen Figure 5.16 Download to the Controller Dialog Box Figure 5.17 RSLogix: Attention Symbol Figure 5.18 RSNetWorx for ControlNet Screen Figure 6.1 Network Configuration: Connection Properties Figure 6.2 Channel Configuration: Chan 0-System Figure 6.3 Controller Properties: Controller Communications Figure KFC15 Set Up Figure 6.5 Scheduled Messaging Example 1a Figure 6.6 Scheduled Messaging Example 1b Figure 6.7 Unscheduled Messaging Setup Screen Figure 6.8 Unscheduled Messaging Example Contents III

6 IV ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

7 List of Tables Table 4.1 Network Update Time Components Table 4.2 ControlNet Scheduled Traffic Configuration Fields Table 4.3 Data Sent/Received 8 Words (Maximum) Table 4.4 FlexPak 3000 Scheduled Drive Reference Data Table 4.5 WebPak 3000 Scheduled Drive Reference Data Table 4.6 FlexPak 3000 Scheduled Drive Feedback Data Table 4.7 WebPak 3000 Scheduled Drive Feedback Data Table 6.1 Required Software and Equipment Table 7.1 File N10:x (Drive Read/Write Parameters) for FlexPak 3000 Drives Table 7.2 File N11:x (Drive Display Data (Read Only)) for FlexPak 3000 Drives 7-11 Table 7.3 File N12:x (Drive Reference and Feedback Data) for FlexPak 3000 Drives Table 8.1 File N10:x (Drive Read/Write Parameters) for WebPak 3000 Drives Table 8.2 File N11:x (Drive Display Data (Read Only)) for WebPak 3000 Drives8-17 Table 8.3 File N12:x (Drive Reference and Feedback Data) for WebPak 3000 Drives Table 9.1 Error Codes Contents V

8 VI ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

9 CHAPTER 1 Introduction This manual describes the ControlNet Network Communication Option board. (M/N 915FK2101). This kit allows a FlexPak 3000 or a WebPak 3000 DC drive to send and receive data via a control processor over the ControlNet network. WebPak 3000 drives (version 1.1 or later) require version 2.2 or later of the ControlNet Network Option board. FlexPak 3000 drives (version 4.2 or later) are compatible with all versions of the network option board. Unless specified otherwise, the material in this manual applies to both FlexPak 3000 and WebPak 3000 drives. 1.1 Network Option Board Description The ControlNet Network Communication Option board makes the drive a slave node on the ControlNet network. It is a printed circuit board assembly that mounts inside the drive and connects to the drive s Regulator board through a ribbon cable. The network option board is powered from the standard drive power supply. The network option board has an RJ-45 connector that is used as a Network Access Port (NAP) that allows temporary access to the network and/or products connected to the network. A 9-pin D-shell connector is used for RS-232 communication to program the flash memory on the board. Two BNC connectors are used for ControlNet communication. A drop cable is used to link each BNC connector through a passive tap to the network. The network option board contains its own microprocessor. The microprocessor connects to one port of the board s dual-port memory. The other port interfaces with the drive s Regulator board. The ControlNet Network Communication Option board is shown in figure 1.1. Introduction 1-1

10 RS-232 Connector Ribbon Cable Connector RJ-45 Connector (Network Access Port) BNC Connectors Figure 1.1 ControlNet Network Communication Option Board 1-2 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

11 1.2 Where To Find Additional Information You must be familiar with all the instruction manuals that describe your system. This can include, but is not limited to: FlexPak 3000 DC Drive Hardware Reference, D FlexPak 3000 DC Drive Software Reference, D WebPak 3000 DC Drive Hardware Reference, D WebPak 3000 DC Drive Software Reference, D ControlNet Network System Overview, ControlNet Cable System Component List, AG-2.2 ControlNet Cable Planning and Installation Manual, ControlNet Coax Tap Installation Manual, ControlNet Network Access Cable Installation Instructions, ControlNet Repeater Installation Instructions, You can obtain the ControlNet manuals listed above from The Automation Bookstore at Getting Assistance from Reliance Electric If you have any questions or problems with the products described in this instruction manual, contact your local Reliance Electric sales office. For technical assistance, call Before calling, please review the troubleshooting section of this manual and check the standard drives website for additional information. When you call this number, you will be asked for the drive model number and this instruction manual number. Also, please have your product version number ready. Introduction 1-3

12 1-4 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

13 CHAPTER 2 Installation This section describes how to install the network option board in the drive and connect the drive to a ControlNet network. 2.1 Installing the Network Option Board! ATTENTION: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION: The user is responsible for conforming with all applicable local, national, and international codes. Wiring practices, grounding, disconnects, and overcurrent protection are particularly important. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION: Do not install modification boards with power applied to the drive. Disconnect and lock out incoming power before attempting such installation. Failure to observe this precaution could result in severe bodily injury or loss of life. To install the network option board: Step 1. Turn off, lock out, and tag all incoming power to the drive. Step 2. Loosen the two (2) OIM cover retaining screws and remove the cover. Step 3. Loosen the captive screw on the carrier. Swing open the carrier. See figure 2.1. Loosen Captive Screw and Swing Carrier Open Figure 2.1 Opening the Carrier Installation 2-1

14 Step 4. Remove the screws that attach the carrier shield to the carrier. See figure 2.2. Carrier Shield Figure 2.2 Removing the Carrier Shield Step 5. Remove the connector that attaches the shield ground wire to the drive power supply. Set the shield aside. See figure 2.3. Ground Wire Power Supply Figure 2.3 Removing the Shield Ground Wire Step 6. Position the network option board over the standoffs. Refer to figure 2.4. Step 7. Step 8. Secure the network option board using three captive screws on the board. Plug the network option board ribbon cable into the network option board. 2-2 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

15 Attach Network board to carrier s molded standoffs using captive screws (qty. 3) Plug option board ribbon cable into Network board Step 9. Reattach the carrier shield ground wire to the drive power supply. Step 10. Reattach the carrier shield to the carrier. Step 11. Close the carrier and fasten it with the captive screw. Step 12. Reinstall the drive cover. 2.2 Connecting the Drive to a ControlNet Network See figure 2.5 for cabling and termination connections. Refer to the ControlNet Cable Planning and Installation Manual, , for a detailed description of how to add a node to the network. Step 1. Lock out and tag all power to the drive. Step 2. Connect the ControlNet cable tap(s) to the ControlNet media and the network option board. To connect to the network option board, twist the ControlNet cable tap(s) onto the BNC connectors. You will hear the tap(s) click into a locked position. Step 3. Figure 2.4 Installing the Network Communication Option Board Remove the lockout and tag. Apply power to the drive. If a problem is detected during diagnostics, a fault or alarm will occur. Refer to the FlexPak 3000 Software Reference Manual, D2-3405, or the WebPak 3000 Hardware Reference Manual, D2-3443, for information on faults and alarms. Installation 2-3

16 Repeater Programmable Logic Controller (PLC) Drop Cable FlexPak 3000 or WebPak 3000 Drive Note: This diagram shows redundant media being used. Tap Trunk Cable Terminator Figure 2.5 Connecting a FlexPak 3000 Drive or a WebPak 3000 Drive to the ControlNet Network You can run a second trunk cable between your ControlNet nodes for redundant media. With redundant media, nodes send signals on two separate segments. The receiving node automatically compares the quality of the two signals and accepts the better signal. This also provides a backup cable should one cable fail. When using redundant media, you must use two passive taps. If you do not use redundant media, the option board can operate using only channel A or channel B, as long as all other drops on the network are also on the same channel. 2.3 Connecting a Programming Device to the Option Board s Network Access Port You can gain full access to the ControlNet network by connecting a programming device to the option board s Network Access Port, an RJ-45 connector. Important: Be sure to use a network access cable that is approved by a ControlNet vendor. Using an unsuitable cable could result in network failures. 2-4 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

17 CHAPTER 3 Drive Configuration This chapter describes how to configure a drive for use with a ControlNet network. The sections that follow describe all of the FlexPak 3000 and WebPak 3000 drive parameters related to ControlNet operation. 3.1 Setting NETW DROP NUMBER (P.900) Use NETW DROP NUMBER (P.900) to assign a node number to the drive. The node number can be changed (through a local operator interface) only when the drive is stopped. This parameter cannot be written over the ControlNet network. The node number must be changed to a value greater than 1 to begin ControlNet communication. After the network has been configured and after NETW DROP NUMBER is set to a value greater than 1, NETW COMM STATUS (P.908) should indicate ACTIVE. If the node number is changed from any value other than 1, the new value must be saved to non-volatile memory and then the power to the drive must be turned off and back on to have the new value take effect. If NETW DROP NUMBER is not equal to 1 on power up, the drive will attempt to communicate on the ControlNet network immediately after the drive diagnostics are complete. Range: 1-99 Type: Non-volatile, Configuration (Read-only over the ControlNet network) Default: 1 (Drive is not communicating on the network) 3.2 Setting CONTROL SOURCE SELECT (P.000) CONTROL SOURCE SELECT (P.000) determines the source of control information for the drive (start, jog, direction, etc.). Setting CONTROL SOURCE SELECT to NETWORK allows the drive to be controlled, and the reference to be supplied, from the ControlNet network. After CONTROL SOURCE SELECT is set to NETWORK, the LCD status on the OIM keypad should change to show the network is in control of the drive. Note that setting CONTROL SOURCE SELECT to any value but NETWORK does not prevent the drive from communicating on the ControlNet network. In other words, CONTROL SOURCE SELECT does not have to be set to NETWORK to modify or read drive parameters. Range: TERMBLK (1), KEYPAD (2), SERIAL (3), NETWORK (4) Type: Non-volatile, Configuration Default: TERMBLK (1) Drive Configuration 3-1

18 3.3 Setting CNI PROG/RUN MODE (P.915)! ATTENTION: CNI PROG/RUN MODE (P.915) allows you to configure the drive to continue to run when the PLC is put into program mode. You must provide some form of hardwired stop in case of communication loss, since stopping the drive through the network might not be possible. Failure to observe this precaution could result in bodily injury or damage to, or destruction of, equipment. CNI PROG/RUN MODE (P.915) selects how the drive will respond when communicating with a PLC that is put into program mode while CONTROL SOURCE SELECT (P.000) is set to NETWORK. When the PLC is put into program mode, alarm A00006 (CNI PROGRAM MODE), is generated to indicate the change in operation of the drive. An alarm is not generated when the PLC is returned to run mode, since that is considered normal operation. When CNI PROG/RUN MODE = STOP (1), the drive will coast/db stop when the PLC is put into program mode. The drive can be started only when the PLC is in run mode. When CNI PROG/RUN MODE = USE LAST REF (2), the drive will not stop (if running) or start (if stopped) when the PLC is put into program mode. The drive will continue to use the last network reference received as its speed reference. This will continue until the PLC is returned to run mode and a new reference value is received. When CNI PROG/RUN MODE = USE TRMBLK CNTL (3), the drive will not stop (if running) or start (if stopped) when the PLC is put into program mode (or returned to run mode). The drive's terminal block will become the source for all control (run, jog, stop, fault reset, direction and OCL enable) and speed (auto) reference signals. For FlexPak 3000 drives, the Speed Loop PI Reset and Underwind/Overwind bits cannot be changed while operating in this mode. They will remain at the last values received from the network. This will continue until the PLC is returned to run mode when control/reference will come from the network again. Range: STOP (1), USE LAST REF (2), USE TRMBLK CNTL (3) Type: Non-volatile, Configuration Default: STOP (1) 3.4 Setting NETW COMM LOSS SELECT (P.901) (FlexPak 3000 Drives Only)! ATTENTION: NETW COMM LOSS SELECT (P.901) allows you to configure the drive to continue to run if a loss of network communication occurs. You must provide some form of hardwired stop in case of communication loss, since stopping the drive through the network might not be possible. Failure to observe this precaution could result in bodily injury or damage to, or destruction of, equipment. NETW COMM LOSS SELECT (P.901) is not used in WebPak 3000 drives. For WebPak 3000 drives, a fault is generated when network communication is lost if CONTROL SOURCE SELECT (P.000) is set to NETWORK. This causes the drive to coast/db stop. The drive cannot be restarted until the fault is cleared. 3-2 ControNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

19 For FlexPak 3000 drives, NETW COMM LOSS SELECT (P.901) defines how the drive will respond to network communication loss when CONTROL SOURCE SELECT (P.000) is set to NETWORK. Alarms do not cause the drive to stop. Therefore, some form of hardwired stop must be available in case of communication loss, since stopping the drive through the network might not be possible. When NETW COMM LOSS SELECT = FAULT (1), a fault is generated when network communication is lost, causing the drive to coast/db stop. The drive can not be restarted until the fault is cleared. When NETW COMM LOSS SELECT = HOLD LAST REF (2), the drive continues to run if network communication is lost, using the last reference value received over the network. Alarm A00004 (NETWORK COMMUNICATION TIMEOUT) is generated if network communication is lost. The drive will maintain the last reference until network communication is reestablished and a new drive reference value is provided. When NETW COMM LOSS SELECT = USE TRMBLK REF (3), the drive continues to run if network communication is lost, using the selected auto reference value from the regulator board terminal strip (terminals 19 and 20). The drive automatically switches back to the network reference when network communication is re-established. Alarm A00004 (NETWORK COMMUNICATION TIMEOUT) is generated if network communication is lost. The drive can still be stopped through the terminal block and local keypad, but can not be restarted. When NETW COMM LOSS SELECT = USE TRMBLK CNTL (4), the drive continues to run if network communication is lost. The Regulator board terminal strip will become the source for all control (run, jog, stop, fault reset, direction and OCL enable) and speed (auto) reference signals. The Speed Loop PI Reset and Underwind/Overwind bits can not be changed while operating in this mode. They will remain at the last values received from the network. The drive automatically switches back to the network reference and control when network communication is re-established. Alarm A00004 (NETWORK COMMUNICATION TIMEOUT) Is generated if network communication is lost. Range: FAULT (1), HOLD LAST REF (2), USE TRMBLK REF (3), USE TRMBLK CNTL (4) Type: Non-volatile, Tunable Default: FAULT (1) 3.5 Setting NETW OUT REG 1 SELECT (P.902) NETW OUT REG 1 SELECT (P.902) defines a parameter number whose value will be monitored and saved in the network option board s dual-port memory. For example, setting this parameter equal to 588 will cause the value of FIELD DELTA (P.588) to be written to file address N10:47 in the dual-port memory for FlexPak 3000 drives, address N10:87 for WebPak 3000 drives. Range: to Type: Non-volatile, Tunable Default: 0 Drive Configuration 3-3

20 3.6 Setting NETW OUT REG 2 SELECT (P.903) NETW OUT REG 2 SELECT (P.903) defines a parameter number whose value will be monitored and saved in the network option board s dual-port memory. For example, setting this parameter equal to 588 will cause the value of FIELD DELTA (P.588) to be written to file address N10:48 in the dual-port memory for FlexPak 3000 drives, address N10:88 for WebPak 3000 drives. Range: to Type: Non-volatile, Tunable Default: Setting NETW OUT REG 3 SELECT (P.904) NETW OUT REG 3 SELECT (P.904) defines a parameter number whose value will be monitored and saved in the network option board s dual-port memory. For example, setting this parameter equal to 588 will cause the value of FIELD DELTA (P.588) to be written to file address N10:49 in the dual-port memory for FlexPak 3000 drives, address N10:89 for WebPak 3000 drives. Range: to Type: Non-volatile, Tunable Default: NETW COMM STATUS (P.908) NETW COMM STATUS (P.908) indicates the status of network communication. When NETW COMM STATUS = NOT ACTIVE, the network option board is not communicating on the ControlNet network. When NETW COMM STATUS = ACTIVE, the network option board is communicating properly with the ControlNet network. Range: NOT ACTIVE (1), ACTIVE (2) Type: Read-only (output) 3.9 NETW TYPE & VERSION (P.909) NETW TYPE & VERSION indicates the type of network board installed and its software version. The format is of the form TV.VV, where: T = board type: 2 = AutoMax, Profibus, InterBus 4 = DeviceNet (FlexPak 3000 drives only) 5 = ControlNet V.VV = major and minor version numbers (e.g. 1.03) Range: to Type: Read-only (output) 3-4 ControNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

21 3.10 NETWORK KIT (P.796) NETWORK KIT (P.796) indicates whether the network option board is operating correctly in the drive. Range: PRESENT (1), NOT PRESENT (2), FAILED DIAGS (3) Type: Read-only (output) 3.11 NETW IN REG 1 (P.905) NETW IN REG 1 (P.905) indicates the value being written by the network master into file address N11:10 in the network option board s dual-port memory. Range: to 4095 Type: Read-only (output) 3.12 NETW IN REG 2 (P.906) NETW IN REG 2 (P.906) indicates the value being written by the network master into file address N11:11 in the network option board s dual-port memory. Range: to 4095 Type: Read-only (output) 3.13 NETW IN REG 3 (P.907) NETW IN REG 3 (P.907) indicates the value being written by the network master into file address N11:12 in the network option board s dual-port memory. Range: to 4095 Type: Read-only (output) Drive Configuration 3-5

22 3-6 ControNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

23 CHAPTER 4 Programming the Drive This section describes how to program the drive over the ControlNet network. 4.1 About ControlNet Network Communication The ControlNet network transports time-critical control information (for example, drive reference and feedback information) as scheduled data, as well as non-time-critical information (for example, accessing drive parameters) as unscheduled data. The transportation of the non-time-critical information does not interfere with the time critical messages. A node s access to the network is controlled by a time-slice access algorithm, which determines a node s opportunity to transmit in each network update interval. You configure how often the network update interval repeats by selecting a network update time (NUT) in milliseconds. The minimum network update time you can specify is 2ms. The network update time is how often you want to send scheduled traffic. You configure when a node will transmit during the network update time (scheduled vs. unscheduled). See table 4.1 for more information about the components of the network update time. Table 4.1 Network Update Time Components Network Update Time Component scheduled unscheduled Function Information that is time-critical (drive reference and feedback) should be sent during this part of the NUT interval. Information that can be delivered without time constraints should be sent during this part of the NUT interval. The amount of time available for the unscheduled portion is determined by the traffic load of the scheduled portion. During this part of the interval, nodes may have many or no chances to transmit. For optimum throughput, assign addresses to ControlNet nodes in a sequential order. Programming the Drive 4-1

24 4.2 Configuring Drive Reference and Feedback Data as Scheduled Transfers This section describes how to: configure scheduled traffic for the drive control the drive using the drive reference data use scheduled drive feedback data Configuring Scheduled Data Transfers Before the drive can communicate on the ControlNet network, you must configure its scheduled traffic information by using some type of ControlNet configuration software. By configuring scheduled traffic, you define how much data the drive can send, how often the data is sent, and where the data is written to and read from (mapped) in the programmable controller. You must configure each drive on the ControlNet network. Table 4.2 lists the configuration information you must enter if you are using RSNetWorx and a PLC-5. Table 4.2 ControlNet Scheduled Traffic Configuration Fields In this field: Enter this information: Node Enter the drive s node number that you defined in P.900. Slot These fields are not used by the drive. Message Module Enter FlexPak 3000 or WebPak API This field is read-only. RPI Enter how often you want to exchange scheduled data between the programmable controller and the drive. Connection Type Select Exclusive Owner. FlexPak 3000 and WebPak 3000 drives do not support Multicast operation. Input Address Enter the programmable controller s integer file number that will store data received from the drive (drive feedback data). Input Size Enter the number of words of drive feedback data that you want the programmable controller to receive from the drive (1 to 8). See section for information about the type of data that is sent. Output Address Enter the programmable controller s integer file number that will store data sent to the drive (drive reference data). Output Size Enter the number of words of drive reference data that you want the programmable controller to send to the drive (1 to 8). See section for information about the type of data that is sent. Status Address Enter the programmable s integer file number that will store the status of the ControlNet connection to the drive. Config Address These fields are not used by the drive. Config Size 4-2 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

25 4.2.2 Programming Scheduled Drive Reference Data Setting CONTROL SOURCE SELECT to NETWORK allows the scheduled data from the PLC to control the drive. If CONTROL SOURCE SELECT NETWORK, then scheduled drive reference data from the ControlNet network is not used. The scheduled drive reference data can be configured as one to eight words of data. The first word of the scheduled drive reference data is always the drive control word; it is written in element 0 of the Output file. Should you configure less than eight words of output data, you can access the Scheduled Drive Reference Data through file N12 (see section 4.3) as unscheduled data messages. You must create a drive control application program to run in the programmable controller. This application program must write from one to eight words of data to the file you defined during drive configuration as the Output Address. The value you defined as the Output Size determines how many words of data the option board can accept from the programmable controller. During a scheduled data transfer, the programmable controller writes the data contained in the Output Address to the option board. Reference and control information is scanned by the drive at different rates depending on the type of data and the drive operating mode (speed regulator or voltage regulator). If the drive is configured as a speed regulator, all of the reference inputs are evaluated every 5 ms for FlexPak 3000 drives, every 10 ms for WebPak 3000 drives. If the drive is configured as a voltage regulator, all of the reference inputs are scanned every 10 ms. The drive control bits are always evaluated every 20 ms. Table 4.4 describes the function of each word of the FlexPak 3000 scheduled drive reference data. Table 4.5 describes the function of each word of the WebPak 3000 scheduled drive reference data. Table 4.3 Data Sent/Received 8 Words (Maximum) PLC to Drive FlexPak WebPak Word 0 Control Control Word 1 Reference Reference Word 2 Reference Network 1 Word 3 Network 1 Network 2 Word 4 Network 2 Network 3 Word 5 Network 3 Field Reference Word 6 Speed FB. Gain Not Used Word 7 Speed Loop PI Not Used Programming the Drive 4-3

26 Name Word 0 Drive Control Word Bit 00 Run Bit 01 Stop Bit 02 Fault Reset Table 4.4 FlexPak 3000 Scheduled Drive Reference Data Description (PLC to Drive) This word consists of a set of bits written to by the PLC to control the state of the drive (only when CONTROL SOURCE SELECT = NETWORK). Starts the drive in run mode. A 0-to-1 transition causes the drive to start (if ready). Setting this bit to zero (0) does not stop the drive. A value of 0 stops the drive. A value of 1 allows the drive to become ready. Resets (only) the latched fault on a 0-to-1 transition. This bit does not affect the contents of the fault log. Bit 03 Jog/Stop Starts the drive in jog mode. A 0-to-1 transition causes the drive to start (if ready). Setting this bit to zero (0) causes the drive to stop (only after jog time-out or if no run command is asserted). Bit 04 Forward/Reverse Operating direction command: Forward (0) or reverse (1). Bit 05 Overwind/Underwind Selects the direction in winder applications; overwind (0) or underwind (1). Bit 06 Speed Loop PI Reset Selects the operational state of the Speed Loop PI block; normal (0) or reset (1). Bit 07 OCL Enable Disables/holds in reset (0) or enables (1) the Outer Control Loop. Bit 08 Fault Log Clear, Reset Clears the fault log contents on a 0-to-1 transition and resets the latched fault. Bit 09 Alarm Log Clear, Reset Clears the alarm log contents on a 0-to-1 transition and resets the alarm indicator. Bit 10 Alarm Reset Resets (only) the alarm on a 0-to-1 transition. This bit does not affect the alarm log. Bit 11 Memory Save Performs a memory save operation in the drive on a 0-to-1 transition. Bit Reserved Reserved Word 1 Speed/Torque Reference This word is written to by the ControlNet network to command a speed or torque reference. When the drive is configured as a speed regulator, a value of 4095 corresponds to TOP SPEED (P.011). When the drive is configured as a torque/current regulator, a value of 4095 corresponds to MAXIMUM CURRENT (P.007) percent of MOTOR RATED ARM AMPS (P.008). Word 2 Field Reference This word is written to by the ControlNet network to command a field reference value. 1= 1/4095 of MOTOR HOT FLD AMPS (P.510). This value is only used by the drive if a field current regulator kit is installed. Word 3 Network Input 1 A value that is input in various places of the speed loop. Word 4 Network Input 2 A value that is input in various places of the speed loop. Word 5 Network Input 3 A value that is input in various places of the speed loop. Word 6 Speed Feedback Gain Value (1000 = 1.000) multiplied by speed feedback (range 1000 to Used in simple winder applications for roll diameter compensation. Word 7 Speed Loop PI Initial Value Initial value of speed loop PI block when CONTROL SOURCE SELECT (P.000) = NETWORK and Spd Loop PI Reset (bit 06, Drive Control Word) = 1. Range to ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

27 Name Word 0 Drive Control Word Bit 00 Section Run Bit 01 Section Off Bit 02 Fault Reset Table 4.5 WebPak 3000 Scheduled Drive Reference Data Description (PLC to Drive) This word consists of a set of bits written to by the PLC to control the state of the drive (only when CONTROL SOURCE SELECT = NETWORK). Starts the drive in run mode. A 0-to-1 transition causes the drive to start (if ready). Setting this bit to zero (0) does not stop the drive. A value of 0 stops the drive. A value of 1 allows the drive to become ready. Resets (only) the latched fault on a 0-to-1 transition. This bit does not affect the contents of the fault log. Bit 03 Jog Fwd Starts the drive in jog forward mode. A 0-to-1 transition causes the drive to start (if ready). Setting this bit to zero (0) causes the drive to stop (only after jog time-out or if no run command is asserted). Bit 04 Jog Rev Starts the drive in jog reverse mode. A 0-to-1 transition causes the drive to start (if ready). Setting this bit to zero (0) causes the drive to stop (only after jog time-out or if no run command is asserted). Bit 05 Underwind Selects the direction in winder applications: Overwind (0) or underwind (1). Bit 06 Slack Take Up Selects the operational state of the slack take up function: Off (0), or on (1). Bit 07 Tension On Starts the drive in run mode only when OCL SELECT (P.817) is set to any value but NONE. A 0-to-1 transition causes the drive to start (if ready). Setting this bit to zero (0) may also stop the drive. Refer to the drive sequencing description in the WebPak 3000 DC Drive Software Reference Manual (D2-3444). Bit 08 Diameter Reset Resets the diameter calculator output when (1). Bit 09 Current Memory Selects the operational state of the current memory function: Off (0) or on (1). See CURRENT MEMORY ENABLE (P.314). Bit 10 Memory Save Performs a memory save operation in the drive on a 0-to-1 transition. Bit 11 Current/Speed Permits switch-on-the-fly transitions between current and speed regulation: Speed (0), current (1). See the description of CURRENT/SPEED SWITCH (P.811) in the WebPak 3000 DC Drive Software Reference Manual (D2-3444) for more information Bit 12 Diameter Select A Bits 12 and 13 are the network equivalents to the terminal block inputs used to select the diameter calculator reset source: Bit 12 (A) Bit 13 (B) Reset Diameter Value Bit 13 Diameter Select B ON (1) OFF (0) WINDER CORE DIA 1 (P.822) OFF (0) ON (1) WINDER CORE DIA 2 (P.824) ON (1) ON (1) WINDER CORE DIA 3 (P.825) OFF (0) OFF (0) UNWIND DIAMETER IN (P.828) Bits Reserved Programming the Drive 4-5

28 Name Word 1 Speed/Torque Reference Word 2 Network Input 1 Word 3 Network Input 2 Word 4 Network Input 3 Word 5 Field Reference Words 6 and 7 Table 4.5 WebPak 3000 Scheduled Drive Reference Data (Continued) Description (PLC to Drive) This word is written to by the ControlNet network to command a speed or torque reference. When the drive is configured as a speed regulator, a value of 4095 corresponds to TOP LINE SPEED (P.020). When the drive is configured as a torque/current regulator, a value of 4095 corresponds to MAXIMUM CURRENT (P.007) percent of MOTOR RATED ARM AMPS (P.008). A value that is input in various places of the speed loop. A value that is input in various places of the speed loop. A value that is input in various places of the speed loop. This word is written to by the ControlNet network to command a field reference value. 1= 1/4095 of MOTOR HOT FLD AMPS (P.510). This value is only used by the drive if a field current regulator kit is installed. Unused Using Scheduled Drive Feedback Data The scheduled drive feedback data provides status to the programmable controller. This data is sent over the ControlNet network as scheduled data, which is transmitted at the configured update rate. However, the FlexPak 3000 drive sends the feedback data to the option board every 5 ms and the WebPak 3000 drive sends the feedback data to the option board every 10 ms, independent of the value of CONTROL SOURCE SELECT (P.000). Scheduled drive feedback data is composed of one to eight words. You must create a drive control application program to run in the programmable controller to read from one to eight words of data to the file you defined during drive configuration as the Input Address. The value you defined as the Input Size determines how many words of data the programmable controller accepts from the option board. During a scheduled data transfer, the option board writes the data contained in the Input Address to the programmable controller. The first word of the scheduled drive feedback data is always the drive status word; it is written to element 0 in the Input file. Should you configure less than eight words of input data, you can access the drive reference and feedback data through file N12 as an unscheduled data transfer. See section 4.3. Table 4.5 describes the function of each word of the FlexPak 3000 scheduled drive feedback data. Table 4.6 describes the function of each word of the WebPak 3000 scheduled drive feedback data. 4-6 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

29 Table 4.6 FlexPak 3000 Scheduled Drive Feedback Data Name Description (Drive to PLC) Word 0 Drive Status Word 1 Indicates drive status Bit 00 Ready 0 = Not ready, 1 = Ready Bit 01 Running 0 = Stopped, 1 = Running Bit 02 Fault 0 = No Fault, 1 = Fault Bit 03 Jogging 0 = Not jogging, 1 = Jogging Bit 04 Actual direction 0 = Forward, 1 = Reverse Bit 05 Stopping 0 = Not stopping, 1 = Stopping Bit 06 Mode 0 = Manual, 1 = Auto Bit 07 At speed reference 0 = Not at reference, 1 = At reference Bit 08 Alarm 0 = No alarm, 1 = Alarm Bit 09 Current Limit 0 = Not limited, 1 = Current limited Bit 10 Parameter Process Error 0 = No Error, 1 = Error Bit 11 Level Detect 1 Output 0 = Off, 1 = On Bit 12 Level Detect 2 Output 0 = Off, 1 = On Bit 13 Acceleration 0 = Not accelerating, 1 = Accelerating Bit 14 Deceleration 0 = Not decelerating, 1 = Decelerating Bit 15 Reserved Reserved Word 1 Speed Feedback The speed of the motor as measured by the drive. Range is ±4095. The units depend on the value of FEEDBACK SELECT (P.200). 1 = 1/4095 of TOP SPEED (P.011). Word 2 Current Feedback The current being supplied by the drive. Range ±4095. Units are amps. 1 = 1/4095 of product of MAXIMUM CURRENT (P.007) and MOTOR RATED ARM AMPS (P.008). Word 3 Network Output 1 Displays value selected by NETW OUT REG 1 SELECT (P.902). Word 4 Network Output 2 Displays value selected by NETW OUT REG 2 SELECT (P.903). Word 5 Network Output 3 Displays value selected by NETW OUT REG 3 SELECT (P.904). Word 6 Speed Feedback Gain Displays the value of SPEED FEEDBACK GAIN, range 1000 to (1000 = 1.000). Word 7 Speed Loop PI Initial Value Initial value of speed loop PI block when CONTROL SOURCE SELECT (P.000) is NETWORK and Spd Loop PI Reset (bit 06, Drive Control Word) is set to 1. Range to Programming the Drive 4-7

30 Table 4.7 WebPak 3000 Scheduled Drive Feedback Data Name Description (Drive to PLC) Word 0 Drive Status Word 1 Indicates drive status Bit 00 Ready 0 = Not Ready, 1 = Ready Bit 01 Running 0 = Stopped, 1 = Running Bit 02 Fault Active 0 = No fault, 1 = Fault Bit 03 Jogging Fwd 0 = Not jogging fwd, 1 = Jogging fwd Bit 04 Jogging Rev 0 = Not jogging rev, 1 = Jogging rev Bit 05 Underwind Active 0 = Overwind, 1 = Underwind Bit 06 Stopping 0 = Not stopping, 1 = Stopping Bit 07 Tension On Active 0 = Not active, 1 = Active Bit 08 Stall Tension Active 0 = Not active, 1 = Active Bit 09 Current Memory Active 0 = Not active, 1 = Active Bit 10 Current Limit 0 = Not limited, 1 = Current limited Bit 11 Alarm Active 0 = Not active, 1 = Active Bit 12 Current/Speed Active 0 = Not active, 1 = Active Bit 13 Processing Error 0 = No processing error, 1 = Parameter processing error Bit 14 Level Detect 1 Output 0 = Off, 1 = On Bit 15 Level Detect 2 Output 0 = Off, 1 = On Word 1 Reserved Reserved Word 2 Speed Feedback The speed of the motor as measured by the drive. Range is ±4095. The units depend on the value of FEEDBACK SELECT (P.200). 1 = 1/4095 of GEAR IN SPEED (P.011). Word 3 Current Feedback The current being supplied by the drive. Range ±4095. Units are amps. 1 = 1/4095 of product of MAXIMUM CURRENT (P.007) and MOTOR RATED ARM AMPS (P.008). Word 4 Network Output 1 Displays value selected by NETW OUT REG 1 SELECT (P.902). Word 5 Network Output 2 Displays value selected by NETW OUT REG 2 SELECT (P.903). Word 6 Network Output 3 Displays value selected by NETW OUT REG 3 SELECT (P.904). Word 7 Unused Unused. 4.3 Using Unscheduled Transfers Use the unscheduled transfer portion of the Network Update Time (NUT) to: read and write drive parameters that are not time-critical read drive display data read and write drive reference and feedback data that is not time-critical read the status of Typed Write messages. The drive sends and receives Typed Read and Typed Write messages. Refer to the appropriate instruction manual to configure your system to use Typed messages. 4-8 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

31 4.3.1 About MSG Instruction Timing When a Typed Read message is sent to the drive, the response is returned in under 20 ms. When a Typed Write message is sent to the drive, the message is first processed by the drive. Therefore, up to 600 ms may elapse before the response is returned. These times are applicable only when the network update time and unscheduled traffic bandwidth are not limiting factors About the Files You Can Access When you send an unscheduled message to the drive, the data table address you specify for the target device determines what drive information you want to access. The data table address is in the form of: Nff:eee where: N specifies the file type as integer, ff is the file number, and eee is the element number (word). The network option board supports these file numbers: N10 -- Drive parameters (read and write) N11 -- Drive display data (read only) N12 -- Drive reference and feedback data (read and write) N20 -- Status of the most recent write parameter command (read only) Figure 4.2 shows how the drive information maps to the drive information integer files. Unscheduled Traffic File in Drive Option Board N10:0 - N10:273 N11:0 - N11:172 N12:0 - N12:31 N20:0 - N20:273 Drive Information Read/Write Parameters (500 ms update) Drive Display Data (100 ms update) Reference and Feedback Data (FlexPak: 5 or 10 ms update; WebPak: 10 ms update) Write Status (Read Only) Scheduled Traffic Figure 4.1 Drive Information Map Using the Drive Parameters Data (N10:x) Beginning at N10:0, the PLC can read from and write to drive parameters. The drive processes these parameters every 500 ms. From N10:1 - N10:06, there is a one-to-one mapping with P P.006. Programming the Drive 4-9

32 All the parameters may accessed with one message block. Any contiguous subset of the parameters may be changed without sending a new copy of the entire block. Some of the parameters are marked Config (configuration), meaning that they may only be changed while the drive is stopped. Any attempt to change the value of these parameters while the drive is in a running state will result in an error, and the value in the drive will not be changed. For this reason, the configuration parameters are all grouped together after the tunable parameters. (CONTROL SOURCE SELECT (P.000) is located at the start of the Config section, N10:150.) Tunable and configuration parameters are also grouped according to potential frequency of use, from most-used to least-used. Refer to table 5.1 for a listing of the file N10 parameters for FlexPak 3000 drives. Refer to table 6.1 for a listing of the file N10 parameters for WebPak 3000 drives Using the Drive Display Data (N11:x) The drive display data can be accessed beginning at N11:0. Attempting to write to any of these parameters will cause an error. The drive updates these parameters every 100 ms. Selected speed feedback parameters are updated at the speed loop scan period (FlexPak 3000 drives: 5 ms for a speed regulator, 10 ms for a voltage regulator; WebPak 3000 drives: 10 ms for a speed regulator, 10 ms for a voltage regulator). Refer to table 5.2 for a listing of the file N11 parameters for FlexPak 3000 drives. Refer to table 6.2 for a listing of the file N11 parameters for WebPak 3000 drives Using the Drive Reference and Feedback Data (N12:x) When scheduled traffic is reduced to transmit only a subset of the drive reference and feedback data, the information that is not transmitted as scheduled data can be accessed in file N12 as unscheduled data. The drive updates this data at the speed loop scan period (FlexPak 3000 drives: 5 ms for a speed regulator, 10 ms for a voltage regulator; WebPak 3000 drives: 10 ms for a speed regulator, 10 ms for a voltage regulator). A message block can be used to read any or all of the data. The Drive Control word and all of the Drive Feedback data are read only when accessed through file N12. All other words accessible through file N12 are read/write. Refer to table 5.3 for a listing of the file N12 parameters for FlexPak 3000 drives. Refer to table 6.3 for a listing of the file N12 parameters for WebPak 3000 drives Using the Write Status (File N20:x) to Troubleshoot a Drive Parameter You can troubleshoot errors that may occur when you write values to parameters to the drive. When a write command is sent from the PLC to the drive, it is possible that the value may not be accepted because: The parameter is read-only The parameter is a configuration parameter and the drive is in run or jog The value is out of range (less than the minimum or greater than the maximum) 4-10 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

33 When this occurs, the MSG instruction s ER coil is set and an error code (=11 or 0B hex) is written into an element in N20 that corresponds to the parameter that was not accepted. For every element in N10:x there is a corresponding element in N20:x. In response to the error coil, the PLC can read N20:x to find out which parameters were not accepted. When parameters are written to, only the corresponding status words are updated. If a valid value is written, the corresponding element in N20:x is cleared (= 0). See table 7.1 for the error codes that the drive will return to the PLC when a Typed Read or Typed Write message fails. Programming the Drive 4-11

34 4-12 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

35 CHAPTER 5 Configuring ControlLogix Applications Chapter 5 provides information and examples that explain how to use I/O Messaging to control, configure, and monitor scheduled and unscheduled data on a FlexPak 3000 or Webpak 3000 drive using a ControlNet scanner module.! ATTENTION: The examples in this publication are intended solely for purpose of example. There are many variables and requirements with any application. Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use of the examples shown in this publication. Failure to observe this precaution could result in bodily injury or damage to equipment. Configuring a ControlLogix CNB scanner, and the network, is mainly done using RSLogix 5000 software (figure 5.1). RSNetWorx is still required, but only at the end of the configuration process. Start the RSLogix 5000 software to begin the configuration process. Figure 5.1 RSLogix 5000: I/O Configuration Selection Configuring ControlLogix Applications 5-1

36 Step 1. Right-click on the I/O Configuration folder and select New Module (figure 5.2). Figure 5.2 RSLogix 5000: New Module Selection Step 2. Select the ControlNet module used by the controller. In this example (figure 5.3), a 1756-CNB Series B ControlNet Bridge is selected.click OK. Figure 5.3 Select Module Type: 1756-CNB/B Selection 5-2 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

37 Step 3. Enter a Name, Slot number, and Revision number (figure 5.4). Click Next>. Figure 5.4 Module Properties: Name Selection Step 4. This step is used to define controller-to-module behavior (figure 5.5). Inhibit Module inhibits/un-inhibits the connection to the module. The Major Fault check-box selects if a failure on the connection of this module causes a major fault on the controller if the connection for the module fails. Click Next>. Figure 5.5 Module Properties: Controller-to-Module Behavior Screen Configuring ControlLogix Applications 5-3

38 Step 5. This window (figure 5.6) is displayed for informational purposes only. Click Next>. Figure 5.6 Module Properties: Identification/Status Screen Step 6. This window (figure 5.7) is displayed for informational purposes only. Click Finish>>. Figure 5.7 Module Properties: Informational Screen 5-4 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

39 Step 7. The 1756-CNB/B now appears in the I/O Configuration folder (figure 5.8). Figure 5.8 RSLogix 5000: I/O Configuration Folder Step 8. Right-click on the 1756-CNB and select New Module (figure 5.9). Figure 5.9 RSLogix 5000: New Module Selection Screen Configuring ControlLogix Applications 5-5

40 Step 9. To configure a FlexPak3000 drive, select the FlexPak3000 (figure 5.10). Click OK. Figure 5.10 Select Drive Type: FlexPak 3000 Step 10. Enter a Name, Node number, and Revision number (figure 5.11). Click Next>. Important: Electronic Keying should be set to disabled. Figure 5.11 Module Properties: Name Selection Step 11. The Requested Packet Interval (RPI) schedules the connection to move data to or from the module at least this often or the connection will fail with the RPI Not Valid error. Set this value to 5 ms or greater, and click Next> (figure 5.12). 5-6 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

41 Important: The RPI time must be set greater than or equal to the Network Update Time (NUT). Figure 5.12 Module Properties: RPI Selections Step 12. This window (figure 5.13) is for informational purposes only. Click Finish>>. Module Properties Cnet Bridge: 0 (Flexpak ) Figure 5.13 Module Properties: Cnet_Bridge Configuring ControlLogix Applications 5-7

42 Step 13. The configured node ( FlexPak 3000 in this example) now appears under the 1756-CNB module in the I/O Configuration folder. Figure 5.14 RSLogix: Configure Additional Nodes Screen Step 14. Repeat the previous steps for each additional node you need to configure. Step 15. In the Data Types folder, click on the Module-Defined sub-folder. When you create a module, module-defined data types and tags are automatically created. These tags allow you to access the Input and Output Data of the module via the controller s ladder logic. Figure 5.15 RSLogix 5000: Module-Defined Screen 5-8 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

43 Step 16. Select Communications / Download to download the configuration to the controller (figure 5.16). RSLogix automatically enters on-line mode when complete. Cnet_bridge:0 (FlexPak ) Figure 5.16 Download to the Controller Dialog Box Step 17. An Attention symbol is located next to the Node 2 (FP3000) icon in figure 5.17, which indicates the ControlNet scanner needs to be configured. Figure 5.17 RSLogix: Attention Symbol Step 18. Start RSNetWorx and perform the following: a. Click the On-line icon and browse the network. b. Select Edits Enabled and view the messages in the Message View for completion (figure 5.18). The icon should disappear from the nodes in the Graphical View. c. Select File / Save and save the project. d. Close RSNetworx. This schedules the I/O that was configured in the RSLogix Configuring ControlLogix Applications 5-9

44 Figure 5.18 RSNetWorx for ControlNet Screen Step 19. The Attention symbol on the RSLogix 5000 connection tree will disappear if the network has been configured properly. You are now ready to develop your ladder logic program ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

45 CHAPTER 6 Configuring SLC500 Applications Chapter 6 describes how to configure a SLC500 PLC on a ControlNet network with a FlexPak3000 or Webpak3000 drive. Both the 1747-SCNR and 1747-KFC15 modules are required to communicate fully with a drive and both must be configured as drops on the ControlNet network. If the application only calls for access to Drive Reference and Feedback Data (such as Drive Control and Status Words), and does not call for access to any N10, N11, or N12 drive parameters, the 1747-KFC card will not be required. However, Unscheduled Messaging will not be possible and another connection option to the processor will be required for downloading the required ladder logic. The examples in this chapter reference a FlexPak3000 drive. A similar process can be followed if your application uses a Webpak3000 drive with the appropriate ControlNet Options Board. Your rack configuration for the Webpak3000 may be different then the included examples. Adjust the examples to match your Nodes and Slots accordingly. This chapter is intended for use by personnel familiar with the installation and operation of the Reliance Drive and the installation, programming, I/O configuration and operation of the SLC processor using RSLinx, RSLogix 5000 and RSNetWorx for ControlNet software. Personnel should also be familiar with the system configuration documentation. 6.1 Required Software and Equipment Software and equipment required for configuring a SLC500 on a ControlNet network is listed in table 6.1. Table 6.1 Required Software and Equipment Equipment Description RSLinx Software RSNetWorx for ControlNet software RSLogix 500 software SLC 500 Chassis w/appropriately sized Power Supply SLC 5/03 processor (1747-L532) or SLC 5/04 processor ControlNet Scanner Module: 1747-SCNR ControlNet RS-232 Interface: 1747-KFC15 PC with 1784-KXTC15 or 1784-PCIC interface card Flexpak3000/Webpak3000 ControlNet Communications Board (915FK2101) Version Version 2.20 or later Version 2.25 or later Version 3.01 or later OS 301 or higher Any OS Version 2.20 or later Configuring SLC500 Applications 6-1

46 6.2 Network Configuration Configure the ControlNet network using RSLinx and RSNetWorx for ControlNet software. Using the parameters suggested in chapter 4 of this manual, configure scheduled traffic with RSNetWorx, by doing a scanlist configuration of the 1747-SCNR module to the drive. It is recommended that Input and Output files are used instead of M1 and M0 files, as discrete I/O is more appropriate for critical data transfer. Make sure keyswitch is in program position before download of configuration. Input address should be [ I:x:y ] with x = slot of SCNR module and y = 1 or greater. Output address should be [ O:x:y ] with x = slot of SCNR module and y = 1 or greater. Input and Output size for Flexpak3000 and Webpak3000 drives = 8. Important: Any address offset is limited by 31 words maximum minus the drive I/O word size. Figure 6.1 Network Configuration: Connection Properties 6-2 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

47 KFC15 Set Up Unlike PLC5 or ControlLogix controllers, the unscheduled messages between the SLC controller and the drive must pass through the KFC15 module and the serial cable, included with the KFC15 module, that physically connects the module and the processor. Important: ControlNet unscheduled messaging is not fully deterministic and may be further limited by the baud rate selected for Channel 0 (RS232/DF1) communications. The communication parameters between the SLC500 and the KFC15 must be identical. Set the DIP switches on the KFC15 according to the application. In most cases, choose all default settings. However, the value is preferable over the default value (1200) for Serial Port Baud Rate. In RSLogix5000, choose Channel Configuration in the project tree and verify that the General and Chan 0-System parameters are the same as you set on the KFC15 DIP switches. Figure 6.2 Channel Configuration: Chan 0-System Configuring SLC500 Applications 6-3

48 In the project tree, choose Controller Properties and Controller Communications. Set the appropriate Driver, Node and Path for Communications. The Node and Path must be the ControlNet Mode of the 1747-KFC15 module. After applying all settings, download to the processor. Figure 6.3 Controller Properties: Controller Communications Figure KFC15 Set Up 6-4 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

49 6.4 Scheduled Messaging (I/O) To use scheduled messaging, the Ladder Logic must include a line that sets a bit in the SCNR module. The processor must be in run or remote run. Include a line that has a coil that sets word 0, bit 10 in the SCNR module. [O:x:0/10], where x = the slot number where the SCNR module resides. Output word 0 is the SCNR command word. Input word 0 is the SCNR status word. In the example below: O:3.3 had been set up as the output address and I:3.3 had been set up as the input address. There is a four (4) word offset in the discrete I/O Input. The drive appears to the processor as an IO rack with several modules, causing the Input offset. O:3.3 (Output register of the SCNR, word 3) shows the Word 0 - Drive Control Word. It is set to 3, meaning bits 00 and 01 (Run and Stop Not) are asserted and the drive is running. O:3.4 is Word 1 - Speed/Torque Reference. It shows the drive reference at 50% full speed. O:3.5 is Word 2 - Field Reference. If a Flexpak3000 is using a field current regulator kit option, this parameter must be set high enough to prevent a drive Field Loss Fault. I:3.7 is Word 0 - Drive Status Word (shown in decimal). Individual bits could be used for programming information. I:3.8 is Word 1 - Speed Feedback, which closely follows Output Speed Reference. Figure 6.5 Scheduled Messaging Example 1a Configuring SLC500 Applications 6-5

50 6.5 Unscheduled Messaging Figure 6.6 Scheduled Messaging Example 1b Unscheduled communications must use PLC5 Typed Read and Write messages. In the example below, drive (Cnet mode 6) parameters at file address N10:0 through N10:9 are read into the controller registers N10:0 through N10:9. Important: For each message, the element size may not exceed the processor limit of 103 elements. Figure 6.7 Unscheduled Messaging Setup Screen 6-6 ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

51 6.6 SLC500 Support Figure 6.8 Unscheduled Messaging Example For drives technical assistance, call For assistance from Rockwell Software, call To reach the Control and Information Group (SLC Modules), call Section 1.3 of this manual outlines the information that you need before calling for support. Configuring SLC500 Applications 6-7

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000 GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000 Instruction Manual D2-3390-2 The information in this manual is subject to change without notice. Throughout this manual, the

More information

FlexPak 3000 Drive Operator Interface Module (OIM) User s Guide

FlexPak 3000 Drive Operator Interface Module (OIM) User s Guide FlexPak 3000 Drive Operator Interface Module (OIM) User s Guide Instruction Manual D2-3344 The information in this manual is subject to change without notice. Throughout this manual, the following notes

More information

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000 GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000 Instruction Manual D2-3342-2 The information in this manual is subject to change without notice. Throughout this manual, the

More information

LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.4

LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.4 LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.4 Instruction Manual D2-3410-7 The information in this manual is subject to change without

More information

EtherNet/IP Communications Module

EtherNet/IP Communications Module EtherNet/IP Communications Module M/N RECOMM-ENET Firmware Version 2.xxx Firmware Version 3.xxx Instruction Manual D2-3510-1 The information in this manual is subject to change without notice. Throughout

More information

Regulator Board Installation Instructions for WebPak 3000 Version 1.x Drives

Regulator Board Installation Instructions for WebPak 3000 Version 1.x Drives Regulator Board Installation Instructions for WebPak 3000 Version 1.x Drives M/N 920WK0011 Instruction Manual D2-3465! ATTENTION: Only qualified personnel familiar with the construction and operation of

More information

WebPakCS Software Version 1.0

WebPakCS Software Version 1.0 WebPakCS Software Version 1.0 Instruction Manual D2-3447 The information in this manual is subject to change without notice. Throughout this manual, the following notes are used to alert you to safety

More information

AutoMax Network Communication Option Board for use with GV3000/SE AC Drives M/N 2AX3000

AutoMax Network Communication Option Board for use with GV3000/SE AC Drives M/N 2AX3000 AutoMax Network Communication Option Board for use with GV3000/SE AC Drives M/N 2AX3000 Instruction Manual D2-3308-7 The information in this manual is subject to change without notice. Throughout this

More information

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04 GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04 Instruction Manual D2-3387-4 The information in this manual is subject

More information

DeviceNet Network Communication Option Board for use with Reliance Electric FlexPak 3000 DC Drive

DeviceNet Network Communication Option Board for use with Reliance Electric FlexPak 3000 DC Drive User s Manual for the HEC-FP3-DN DeviceNet Network Communication Option Board for use with Reliance Electric FlexPak 3000 DC Drive Fourth Edition February 25, 1998 MAN0086-04 PREFACE 2-25-98 PAGE 2 PREFACE

More information

Allen-Bradley 1397 AC Tachometer Interface Card

Allen-Bradley 1397 AC Tachometer Interface Card Instructions Allen-Bradley 1397 AC Tachometer Interface Card Cat. No. 1397-AC Contents Topic Page What This Option Provides 1 Where This Option Is Used 1 What These Instructions Contain 1 Specifications

More information

460 to 230 Volt Conversion Kit for FlexPak 3000 or WebPak 3000 Drives

460 to 230 Volt Conversion Kit for FlexPak 3000 or WebPak 3000 Drives 460 to 230 Volt for FlexPak 3000 or WebPak 3000 Drives s: 916FK0100 and 916FK0200 Instruction Manual D2-3329-2! ATTENTION: Only qualified personnel familiar with the construction and operation of this

More information

ControlNet Adapter. 20-COMM-C FRN 1.xxx. User Manual

ControlNet Adapter. 20-COMM-C FRN 1.xxx. User Manual ControlNet Adapter 20-COMM-C FRN 1.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

More information

DeviceNet Adapter for use with DPI AC Drives

DeviceNet Adapter for use with DPI AC Drives DeviceNet Adapter for use with DPI AC Drives M/N RECOMM-DNET Instruction Manual D2-3478 The information in this manual is subject to change without notice. Throughout this manual, the following notes are

More information

ControlNet Adapters. User Manual. 20-COMM-C (coax) 20-COMM-Q (fiber) FRN 1.xxx

ControlNet Adapters. User Manual. 20-COMM-C (coax) 20-COMM-Q (fiber) FRN 1.xxx ControlNet Adapters 20-COMM-C (coax) 20-COMM-Q (fiber) FRN 1.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

RS485 DF1 Communications Module

RS485 DF1 Communications Module RS485 DF1 Communications Module M/N RECOMM-485 Instruction Manual D2-3514 The information in this manual is subject to change without notice. Throughout this manual, the following notes are used to alert

More information

DeviceNet Adapter. 20-COMM-D FRN 1.xxx. User Manual

DeviceNet Adapter. 20-COMM-D FRN 1.xxx. User Manual DeviceNet Adapter 20-COMM-D FRN 1.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

More information

GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting VAC Version 6.04

GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting VAC Version 6.04 GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting -20 HP @ 230 VAC Version 6.04 c Instruction Manual D2-3388-4 The information in this manual is subject to change without notice.

More information

CS3000 MMI SW-Version 6.1 Control and Configuration Software for FlexPak3000 V , GV3000 V and Liqui-Flo. Instruction Manual

CS3000 MMI SW-Version 6.1 Control and Configuration Software for FlexPak3000 V , GV3000 V and Liqui-Flo. Instruction Manual CS3000 MMI SW-Version 6.1 Control and Configuration Software for FlexPak3000 V2.0-4.3, GV3000 V2.0-6.0 and Liqui-Flo Instruction Manual Manual P/N: 899.05.84 Firmware P/N: 788.05.30 User Manual: 49 1307e

More information

User Guide SE73-PROFIBUS-DP. Commander SE. Part Number: Issue Number: 4.

User Guide SE73-PROFIBUS-DP. Commander SE. Part Number: Issue Number: 4. EF User Guide SE73-PROFIBUS-DP Commander SE Part Number: 0452-0057-04 Issue Number: 4 www.controltechniques.com Safety Information The option card and its associated drive are intended as components for

More information

L5351 DeviceNet Communications Interface

L5351 DeviceNet Communications Interface L5351 DeviceNet Communications Interface Technical Manual HG353798 Issue 2 Copyright SSD Drives, Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or

More information

ControlNet Adapter Module

ControlNet Adapter Module ControlNet Adapter Module (Catalog Numbers 1747-ACN15, 1747-ACNR15) User Manual Important User Information Because of the variety of uses for the products described in this publication, those responsible

More information

EtherNet/IP Adapter. 20-COMM-E FRN 2.xxx. User Manual. AB Drives

EtherNet/IP Adapter. 20-COMM-E FRN 2.xxx. User Manual. AB Drives AB Drives EtherNet/IP Adapter 20-COMM-E FRN 2.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety

More information

270 MHz Control Modules

270 MHz Control Modules 2400 / 2420 / 2450 Performance Drives A D D E N D U M 270 MHz Control Modules Notices 2000.40(A2) 01 11/08 Copyright 2002-2008 by Unico, Incorporated. All rights reserved. No part of this publication may

More information

Distributed Power System SB3000 Synchronous Rectifier &RQILJXUDWLRQDQG3URJUDPPLQJ

Distributed Power System SB3000 Synchronous Rectifier &RQILJXUDWLRQDQG3URJUDPPLQJ Distributed Power System SB3000 Synchronous Rectifier &RQILJXUDWLRQDQG3URJUDPPLQJ Instruction Manual S-3034 Throughout this manual, the following notes are used to alert you to safety considerations:!

More information

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC Software Start-Up and Reference Manual D2-3416-2 GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, 30-100 HP, 230V AC Version 6.04 Important User Information Solid-state equipment has operational

More information

PowerFlex ControlNet Adapters 20-COMM-C (Coax) Series A FRN 2.xxx, Series B FRN 3.xxx 20-COMM-Q (Fiber) Series A FRN 3.xxx

PowerFlex ControlNet Adapters 20-COMM-C (Coax) Series A FRN 2.xxx, Series B FRN 3.xxx 20-COMM-Q (Fiber) Series A FRN 3.xxx PowerFlex ControlNet Adapters 20-COMM-C (Coax) Series A FRN 2.xxx, Series B FRN 3.xxx 20-COMM-Q (Fiber) Series A FRN 3.xxx User Manual Important User Information Solid state equipment has operational characteristics

More information

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon Allen-Bradley PLC-5 Backup Communication Module User Manual (1785-BCM, 1785-BEM) product icon Important User Information Because of the variety of uses for this product and because of the differences between

More information

Super Remote Meter Interface (RMI) Board For Use With GV3000/SE and VTAC 7 Drives

Super Remote Meter Interface (RMI) Board For Use With GV3000/SE and VTAC 7 Drives Super Remote Meter Interface (RMI) Board For Use With GV3000/SE and VTAC 7 Drives M/N 2SI3000 M/N 2SI3000E Instruction Manual D2-3341-2 The information in this manual is subject to change without notice.

More information

GV3000/SE AC Bookshelf Drive Hardware Reference, Installation, and Troubleshooting Version 6.06

GV3000/SE AC Bookshelf Drive Hardware Reference, Installation, and Troubleshooting Version 6.06 GV3000/SE AC Bookshelf Drive Hardware Reference, Installation, and Troubleshooting Version 6.06 Instruction Manual D2-3427-2 The information in this manual is subject to change without notice. Throughout

More information

GV3000/SE AC Drive 1-20 HP, 230V AC

GV3000/SE AC Drive 1-20 HP, 230V AC Hardware Reference, Installation, and Troubleshooting Manual D2-3388-5 GV3000/SE AC Drive - 20 HP, 230V AC Version 6.04 Important User Information Solid-state equipment has operational characteristics

More information

Allen-Bradley 1397 L11 I/O Expansion Card

Allen-Bradley 1397 L11 I/O Expansion Card Installation Instructions IN Allen-Bradley 1397 L11 Expansion Card Cat. No. 1397-L11 What This Option Provides The Expansion Card is a drive mounted board that provides these additional signals. (5) Digital

More information

Varispeed SERIES OPTION CARD DeviceNet COMMUNICATION INTERFACE CARD USER'S MANUAL Model: SI-N1

Varispeed SERIES OPTION CARD DeviceNet COMMUNICATION INTERFACE CARD USER'S MANUAL Model: SI-N1 YASKAWA Varispeed SERIES OPTION CARD DeviceNet COMMUNICATION INTERFACE CARD USER'S MANUAL Model: SI-N1 YASKAWA MANUAL NO. SIBP C730600 01B Copyright 2004 YASKAWA ELECTRIC CORPORATION All rights reserved.

More information

The easy to use three-phase digital DC drive for regenerative and non-regenerative applications from HP

The easy to use three-phase digital DC drive for regenerative and non-regenerative applications from HP Digital DC Drives The easy to use three-phase digital DC drive for regenerative and non-regenerative applications from 1.5-600 HP The FlexPak 3000 digital DC drive features a unique ergonomic user interface

More information

User Manual. PowerFlex DNET DeviceNet Option Module Firmware Revision Number 1.xxx

User Manual. PowerFlex DNET DeviceNet Option Module Firmware Revision Number 1.xxx User Manual PowerFlex 20-750-DNET DeviceNet Option Module Firmware Revision Number 1.xxx Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical

More information

ControlNet Modules in Logix5000 Control Systems

ControlNet Modules in Logix5000 Control Systems ControlNet Modules in Logix5000 Control Systems 1734-ACNR, 1756-CNB, 1756-CNBR, 1784-PCC, 1784-PCIC, 1784-PCICS, 1788-CNC, 1788-CNCR, 1788-CNF, 1788-CNFR, 1794-ACN15, 1794-ACNR15, 1797-ACNR15 User Manual

More information

GV3000/SE AC Drive HP, 230V AC

GV3000/SE AC Drive HP, 230V AC Hardware Reference, Installation, and Troubleshooting Manual D2-347-2 GV3000/SE AC Drive 30-00 HP, 230V AC Version 6.04 Important User Information Solid-state equipment has operational characteristics

More information

Spare Allen-Bradley Parts

Spare Allen-Bradley Parts ControlNet Scanner Module 1747-SCNR Reference Manual Spare Allen-Bradley Parts Important User Information Because of the variety of uses for the products described in this publication, those responsible

More information

SCS AUTOMATION & CONTROL

SCS AUTOMATION & CONTROL - 1 - SCS AUTOMATION & CONTROL PROJECT XXXX Issue A Winder Customer: XXXXXXX Ltd.. Automation Center 156 Stanley Green Road Poole Dorset England BH15 3AH - 2 - Contents 1. Introduction 2. Safety 3. Specification

More information

Allen-Bradley Motors

Allen-Bradley Motors Installation Instructions Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Purpose Firmware Update Kit Contents Hardware and Software Requirements This

More information

PowerFlex 400 Frame G and H Replacement Procedure for Gate Power Board

PowerFlex 400 Frame G and H Replacement Procedure for Gate Power Board Service Bulletin PowerFlex 400 Frame G and H Replacement Procedure for Gate Power Board Contents This publication provides instructions for replacing the gate power board for PowerFlex 400 Frame G and

More information

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE INSTRUCTIONS MODBUS RTU MODULE for use with WSIQ2/WSE WorldWide Electric Corporation Phone: 1-8-88-2131 Fax: 1-8-711-1616 www.worldwideelectric.net Product Compatibility This communications module is suitable

More information

Profinet Module. User Manual. Contents

Profinet Module. User Manual. Contents User Manual Contents 1 Important User Information... 2 2 Installation... 3 3 Connection... 4 4 Device Configuration... 5 5 Operation... 7 6 Packet Structures... 8 7 Network Design... 16 8 Specifications...

More information

DriveLogix 5730 Controller

DriveLogix 5730 Controller DriveLogix 5730 Controller for PowerFlex 700S Drives with Phase II Control Firmware Version 13.XX User Manual Important User Information Solid state equipment has operational characteristics differing

More information

Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller

Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller Safety Application Example Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller Safety Rating: Category 3, according to EN954-1 Introduction...

More information

PROFIBUS Adapter. 20-COMM-P FRN 1.xxx. User Manual

PROFIBUS Adapter. 20-COMM-P FRN 1.xxx. User Manual PROFIBUS Adapter 20-COMM-P FRN 1.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

More information

PowerFlex 525 DeviceNet Adapter

PowerFlex 525 DeviceNet Adapter User Manual PowerFlex 525 DeviceNet Adapter Catalog Number: 25-COMM-D Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment.

More information

Ethernet/IP Module. User Manual. Contents

Ethernet/IP Module. User Manual. Contents User Manual Contents 1 Important User Information... 2 2 Installation... 3 3 Connection... 4 4 Device Configuration... 5 5 Operation... 8 6 Packet Structures... 9 7 Network Design... 18 8 Specifications...

More information

PowerFlex DC Drive Frame B Pulse Transformer Circuit Board

PowerFlex DC Drive Frame B Pulse Transformer Circuit Board Installation Instructions PowerFlex DC Drive Frame B Pulse Transformer Circuit Board ATTENTION: Only qualified personnel familiar with DC drives and associated machinery should plan or implement the installation,

More information

GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting Version 6.06

GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting Version 6.06 GV3000/SE AC Drive Hardware Reference, Installation, and Troubleshooting Version 6.06 Instruction Manual D2-3360-5 The information in this manual is subject to change without notice. Throughout this manual,

More information

SITRANS F. Flowmeters SysCom Upgrade Kit IP65 (NEMA 4X) Multi-Channel. Introduction 1. Installing/Mounting 2. Hardware Installation Instructions

SITRANS F. Flowmeters SysCom Upgrade Kit IP65 (NEMA 4X) Multi-Channel. Introduction 1. Installing/Mounting 2. Hardware Installation Instructions Introduction 1 Installing/Mounting 2 SITRANS F Flowmeters SysCom Upgrade Kit IP65 (NEMA 4X) Multi-Channel Hardware Installation Instructions 1/2010 A5E02518333A Revision 04 Legal information Warning notice

More information

Throughout this manual we use notes to make you aware of safety considerations:

Throughout this manual we use notes to make you aware of safety considerations: Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have

More information

EtherNet/IP and ControlNet to FOUNDATION Fieldbus Linking Device

EtherNet/IP and ControlNet to FOUNDATION Fieldbus Linking Device User Manual EtherNet/IP and ControlNet to FOUNDATION Fieldbus Linking Device Catalog Numbers 1788-EN2FFR, 1788-CN2FFR Important User Information Solid-state equipment has operational characteristics differing

More information

PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller

PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller Safety Application Example PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller Safety Rating: Category 3 (also see Achieving a Cat. 4 Safety Rating)

More information

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication Remote I/O Scanner Catalog Number 1747-SN Installation Instructions 2 Remote I/O Scanner Important User Information Because of the variety of uses for the products described in this publication, those

More information

Logix5000 Controllers Produced and Consumed Tags

Logix5000 Controllers Produced and Consumed Tags Logix5 Controllers Produced and Consumed Tags Catalog Numbers 1756 ControlLogix, 1756 GuardLogix, 1768 Compact GuardLogix, 1769 CompactLogix, 1789 SoftLogix, PowerFlex with DriveLogix Programming Manual

More information

DeviceNet PCI Card Instructions Manual

DeviceNet PCI Card Instructions Manual Motoman NX100 Controller DeviceNet PCI Card Instructions Manual Part Number: 151799-1CD Revision: 0 Motoman, Incorporated 805 Liberty Lane West Carrollton, OH 45449 TEL: (937) 847-6200 FAX: (937) 847-6277

More information

Distributed Power System SA3100 Drive Configuration and Programming

Distributed Power System SA3100 Drive Configuration and Programming Distributed Power System SA3100 Drive Configuration and Programming Instruction Manual S-3056-1 Throughout this manual, the following notes are used to alert you to safety considerations:! ATTENTION: Identifies

More information

6053/6055 ControlNet Communications Interface

6053/6055 ControlNet Communications Interface EUROTHERM DRIVES 6053/6055 ControlNet Communications Interface Technical Manual HA468029U001 Issue 2 Compatible with Version 1.x Firmware Copyright Eurotherm Drives Limited 2003 All rights strictly reserved.

More information

PCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer

PCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer Installation Instructions PCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer Catalog Number 6189V-2PCI15R Topic Page About This Publication 1 Important User Information 2 Safety

More information

BACnet MS/TP Adapter. 20-COMM-B FRN 1.xxx. User Manual

BACnet MS/TP Adapter. 20-COMM-B FRN 1.xxx. User Manual BACnet MS/TP Adapter 20-COMM-B FRN 1.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

More information

G3 Series DeviceNet TM Technical Manual

G3 Series DeviceNet TM Technical Manual G3 Series DeviceNet TM Technical Manual Table of Contents G3 Series DeviceNet Technical Manual PAGE About DeviceNet... 3 Overview... 3 G3 DeviceNet Features... 3 Cabling and Drop Line Lengths (as defined

More information

Copyright: December 2017 Nidec Issue: E

Copyright: December 2017 Nidec Issue: E General Information The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or incorrect installation or adjustment of the optional parameters of the equipment

More information

PowerFlex DC Stand-Alone Regulator (SAR) Field Circuit Board

PowerFlex DC Stand-Alone Regulator (SAR) Field Circuit Board Installation Instructions PowerFlex DC Stand-Alone Regulator (SAR) Field Circuit Board ATTENTION: Only qualified personnel familiar with DC drives and associated machinery should plan or implement the

More information

GV3000/SE AC Drive Quick Reference Version 6.06

GV3000/SE AC Drive Quick Reference Version 6.06 RMI Terminal Strip 41. Digital Input 1 42. Digital Input 2 43. Digital Input 3 44. Digital Input 4 45. Digital Input +24 Vdc 46. Digital Output External +24 Vdc 47. Digital Output 1 48. Digital Output

More information

BICN ControlNet Interface

BICN ControlNet Interface BICN ControlNet Interface BALOGH 7699 Kensington Court Brighton, MI 48116-8561 (248) 486-7343 Notes are used to call attention to information that is significant to the understanding and operation of equipment.

More information

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE INSTRUCTIONS MODBUS TCP MODULE for use with WSIQ2/WSE WorldWide Electric Corporation Phone: 1-800-808-2131 Fax: 1-800-711-1616 www.worldwideelectric.net Product Compatibility This communications module

More information

PowerFlex DC Stand-Alone Regulator (SAR) Power Interface Circuit Board

PowerFlex DC Stand-Alone Regulator (SAR) Power Interface Circuit Board Installation Instructions PowerFlex DC Stand-Alone Regulator (SAR) Power Interface Circuit Board ATTENTION: Only qualified personnel familiar with DC drives and associated machinery should plan or implement

More information

Bulletin 1395 ControlNet TM Communication Board

Bulletin 1395 ControlNet TM Communication Board Bulletin 1395 ControlNet TM Communication Board Firmware Rev 1.1 Compatible with ControlNet Version 1.5 User Manual Important User Information Solid state equipment has operational characteristics differing

More information

DriveGuard. Safe-Off Option for PowerFlex 70 AC Drives. User Manual.

DriveGuard. Safe-Off Option for PowerFlex 70 AC Drives. User Manual. DriveGuard Safe-Off Option for PowerFlex 70 AC Drives User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Allen-Bradley. User Manual. ControlNet Adapter Module. (Cat. No ACN and -ACNR Series B)

Allen-Bradley. User Manual. ControlNet Adapter Module. (Cat. No ACN and -ACNR Series B) Allen-Bradley ControlNet Adapter Module (Cat. No. 1771-ACN and -ACNR Series B) User Manual Important User Information Because of the variety of uses for the products described in this publication, those

More information

Copyright: December 2017 Nidec Issue: E

Copyright: December 2017 Nidec Issue: E General Information The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or incorrect installation or adjustment of the optional parameters of the equipment

More information

ControlNet Network Configuration

ControlNet Network Configuration User Manual ControlNet Network Configuration 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, Studio 5000 Logix Emulate Important User Information Solid-state

More information

SMVector Additional I/O Module Installation and Operation Manual

SMVector Additional I/O Module Installation and Operation Manual SMVector Additional I/O Module Installation and Operation Manual About These Instructions This documentation applies to the optional Additional I/O module for the SMVector inverter and should be used in

More information

CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter

CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter User Manual CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter Catalog Numbers 2100-ENET Series A FRN 1.XXX Important User Information Solid-state equipment has operational characteristics

More information

YASKAWA AC Drive 1000-Series Option EtherNet/IP. Technical Manual

YASKAWA AC Drive 1000-Series Option EtherNet/IP. Technical Manual YASKAWA AC Drive 1000-Series Option EtherNet/IP Technical Manual Type: SI-EN3 To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure

More information

Memory Expansion for DriveLogix Controller

Memory Expansion for DriveLogix Controller Installation Instructions Memory Expansion for rivelogix ontroller!!! TTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any work

More information

Profibus DP Expansion Board

Profibus DP Expansion Board Profibus DP Expansion Board Catalog No. EXBD04 Installation and Operating Manual 10/02 MN1393 Table of Contents Section 1 General Information................................................... 1 1 Introduction.......................................................

More information

ControlLogix Analog I/O Modules

ControlLogix Analog I/O Modules ControlLogix Analog I/O Modules 1756-IF16,- IF6CIS, -IF6I, -IF8, -IR6I, -IT6I, -IT6I2, -OF4, -OF6CI, -OF6VI, -OF8 User Manual Important User Information Because of the variety of uses for the products

More information

DeviceNet Network Communication Option Board for use with Reliance Electric GV3000 AC Drive

DeviceNet Network Communication Option Board for use with Reliance Electric GV3000 AC Drive User Manual for the HEC-GV3-DN Option Card DeviceNet Network Communication Option Board for use with Reliance Electric GV3000 AC Drive Third Edition 22 September 1998 MAN0096-03 PREFACE 22 SEPTEMBER 1998

More information

ControlLogix Configurable Flowmeter Module

ControlLogix Configurable Flowmeter Module User Manual ControlLogix Configurable Flowmeter Module Catalog Numbers 1756-CFM Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical

More information

Advanced User Guide. SE77-DeviceNet. Commander SE. Part Number: Issue Number: 1.

Advanced User Guide. SE77-DeviceNet. Commander SE. Part Number: Issue Number: 1. EF Advanced User Guide SE77-DeviceNet Commander SE Part Number: 0452-0054 Safety Information The solutions module and its associated drive are intended as components for professional incorporation into

More information

Technical Manual Type SI-N3

Technical Manual Type SI-N3 YASKAWA AC Drive-Option Card DeviceNet Technical Manual Type SI-N3 To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user

More information

H1 Linking Device User Manual

H1 Linking Device User Manual Allen-Bradley ControlNet-to- FOUNDATION Fieldbus (Cat. No. 1788-CN2FF) H1 Linking Device User Manual Important User Information Because of the variety of uses for the products described in this publication,

More information

Operating Guide FC Series Add-On Instruction for VLT EtherNet/IP MCA 121

Operating Guide FC Series Add-On Instruction for VLT EtherNet/IP MCA 121 ENGINEERING TOMORROW Operating Guide FC Series Add-On Instruction for VLT EtherNet/IP MCA 121 VLT HVAC Drive FC 102 VLT AQUA Drive FC 202 VLT AutomationDrive FC 301/302 VLT Decentral Drive FCD 302 vlt-drives.danfoss.com

More information

DeviceNet Communications Module

DeviceNet Communications Module DeviceNet Communications Module Catalog Number 1203-GK5 or 1336-GM5 Firmware 1.xxx-3.xxx TM CONFORMANCE TESTED User Manual Important User Information Solid state equipment has operational characteristics

More information

PanelView Standard Operator Terminals

PanelView Standard Operator Terminals PanelView Standard Operator Terminals PV300 Micro, PV300, PV550, PV600, PV900, PV1000, PV1400 User Manual Important User Information Because of the variety of uses for the products described in this publication,

More information

PS/IO Circuit Board Retrofit

PS/IO Circuit Board Retrofit S&C 6800 Series Automatic Switch Controls PS/IO Circuit Board Retrofit Table of Contents Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this Instruction Sheet....

More information

Master Pulse Reference/ Isolated Pulse Follower Expansion Board

Master Pulse Reference/ Isolated Pulse Follower Expansion Board Master Pulse Reference/ Isolated Pulse Follower Expansion Board Catalog No. EXB005A01 Installation and Operating Manual 2/03 MN1312 Y1 Table of Contents Section 1 General Information.............................

More information

Installation Note. Source Attenuators and Bias Tees Upgrade Kit. For E8362B/C PNA Series Microwave Network Analyzers. Network Analyzer Model Number

Installation Note. Source Attenuators and Bias Tees Upgrade Kit. For E8362B/C PNA Series Microwave Network Analyzers. Network Analyzer Model Number Installation Note Source Attenuators and Bias Tees Upgrade Kit For E8362B/C PNA Series Microwave Network Analyzers Network Analyzer Model Number Upgrade Kit Part Number E8362B/C E8362-60115 Agilent Part

More information

Enhanced DeviceNet Communications Module

Enhanced DeviceNet Communications Module Enhanced DeviceNet Communications Module Catalog Numbers: 1203-GU6 and 1336-GM6 Firmware: 2.xxx User Manual Important User Information Because of the variety of uses for the products described in this

More information

AutoScan to MultiScan Replacement Kit

AutoScan to MultiScan Replacement Kit Instruction Sheet P/N AutoScan to MultiScan Replacement Kit WARNING: Allow only qualified personnel to perform the following tasks. Observe and follow the safety instructions in this document and all other

More information

SmartGuard 600 Controllers

SmartGuard 600 Controllers SmartGuard 600 Controllers Catalog Number 1752-L24BBB Safety Reference Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

LiquiFlo 1.5 AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 1.2

LiquiFlo 1.5 AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 1.2 LiquiFlo 1.5 AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 1.2 Instruction Manual D2-3495 The information in this manual is subject to change without

More information

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice MPCR Series DeviceNet Technical Manual Table of Contents MPCR Series Introduction... 3 Product Overview... 3 About DeviceNet... 4 Overview... 4 MPCR DeviceNet Features... 4 Cabling and Drop Line Lengths

More information

Lightning Stitch Assembly

Lightning Stitch Assembly ABM International, Inc. 1 1.0: Parts List Lightning stitch motor and drive assembly (Qty. 1) Lightning stitch piggy backed controller board assembly (Qty. 1) Touchscreen (Qty. 1) 2 9-pin Serial cable (Qty.

More information

Interbus Adapter. 20-COMM-I FRN 1.xxx. User Manual

Interbus Adapter. 20-COMM-I FRN 1.xxx. User Manual Interbus Adapter 20-COMM-I FRN 1.xxx User Manual Table of Contents Table of Contents Preface Chapter 1 Chapter 2 Chapter 3 Chapter 4 About This Manual Related Documentation.............................

More information

Ethernet/IP Single and Dual-Port

Ethernet/IP Single and Dual-Port YASKAWA Z1000 Bypass Option Ethernet/IP Single and Dual-Port Technical Manual Type: SI-EN3/SI-EN3D Applicable Products : Z1B1- To properly use the product, read this manual thoroughly and retain for easy

More information

Operation manual. HDOM-Profibus-V0. More options please visit;www.veikong-electric.com

Operation manual. HDOM-Profibus-V0. More options please visit;www.veikong-electric.com Operation manual HDOM-Profibus-V0 More options please visit;www.veikong-electric.com Contents 1 Introduction... 1 1.1 Product description... 1 1.2 HDOM-Profibus-V0 label... 1 1.3 Technical specifications...

More information

Installation Guide EtherNet/IP Module

Installation Guide EtherNet/IP Module ENGINEERING TOMORROW Installation Guide EtherNet/IP Module VLT Compact Starter MCD 201/MCD 202 VLT Soft Starter MCD 500 vlt-drives.danfoss.com Contents Installation Guide Contents 1 Introduction 3 1.1

More information