CB-7000 DIO User s Manual

Size: px
Start display at page:

Download "CB-7000 DIO User s Manual"

Transcription

1 CB-7000 DIO User s Manual CB-7041/7041D CB-7042/7042D CB-7043/7043D CB-7044/7044D CB-7050/7050D CB-7052/7052D CB-7053/7053D CB-7060/7060D CB-7063/7063D/A/AD/B/BD CB-7065/7065D/A/AD/B/BD CB-7066/7066D CB-7067/7067D Measurement Computing Corp. Copyright September, All rights are reserved. CB-7000 DIO Manual 1

2 Table of Contents 1. Introduction More Information Pin Assignments Specifications Block Diagrams Wire Connection Quick Start Default Settings Jumper Settings Configuration Tables Command %AANNTTCCFF #** #AABBDD #AAN $AA $AA $AA $AA $AAF $AAM $AAC $AACN CB-7000 DIO Manual

3 2.13 $AALS ~AAO(Data) ~** ~AA ~AA ~AA ~AA3EVV ~AA4V ~AA5V Application Note INIT* pin Operation Module Status Dual Watchdog Operation Reset Status Digital Output Latch Digital Input DN Module DN-SSR DN-PR RM-104, RM-108, RM RM-204, RM-208, RM Application...64 CB COM Digital.p65 CB-7000 DIO Manual 3

4 1. Introduction CB-7000 is a family of network data acquisition and control modules. They provide analog-to-digital, digital-to-analog, digital input/output, timer/counters and other functions. These modules can be remotely controlled by a set of commands. The DIO modules support TTL signals, photo-isolated digital inputs, relay contact outputs, solid-state relay outputs, PhotoMOS outputs, and open-collector outputs. Refer to Sec. 1.3 for detailed information. 4 CB-7000 DIO Manual

5 1.1 Pin Assignments CB-7000 DIO Manual 5

6 6 CB-7000 DIO Manual

7 CB-7000 DIO Manual 7

8 8 CB-7000 DIO Manual

9 1.2 Specifications Digital Input Modules I-7041/41D I-7052/52D I-7053/53D Input Channels Isolation Isolation Voltage Digital Digital Input Power Level 0 Level 1 Impedance Input Power Consumption Isolation with Common Source 6 differential and 2 common ground Non-Isolated 3750 Vrms 5000 Vrms Non-Isolate d + 1V max + 1V max +2V max + 4 to +30 V + 4 to +30 V +4 to +30 V 3K ohms 3K ohms 820 ohms 0.2W(I-7041) 0.9W(I-7041D) +10 to +30 VDC 0.2W(I-7052) 0.6W(I-7052D) 0.7W(I-7053) 0.9W(I-7053D) PhotoMOS Output Module I-7066/66D Output Channels 7 Load Load Current Voltage Isolation Voltage TurnOn Time TurnOff Power Time Input Power Consumption A 350V max 5000VA C 0.7mS 0.05mS to +30 typ typ VDC 0.5W(I-7066) 0.8W(I-7066D) CB-7000 DIO Manual 9

10 Open Collector Output Modules I-7042 I-7042D I-7043 I-7043D I-7044 I-7044D I-7050 I-7050D Output Channels Isolation Isolation Voltage Load Max Load Voltage Current Input Channels Isolation Isolation Voltage Digital Digital Input Power Level 0 Level 1 Impedance Input Power Consumption Isolation with Common Power Isolation with Common Power 3750 Vrms 3750 Vrms 1.0W (I-7042) 1.7W (I-7042D) Max +30V 100mA 375mA 30mA No-Inputs +10 to 0.4W (I-7043) 1.1W (I-7043D) Isolation with Common Source 3750 Vrms Non-Isolation Non-Isolation Non-Isolation 1V max 1V max 4 to 30V 3.5 to 30V 3K ohms VDC 1.0W (I-7044) 1.7W (I-7044D) 0.4W (I-7050) 1.1W (I-7050D) 10 CB-7000 DIO Manual

11 Relay Output Modules I-7060 I-7060D I-7063 I-7063D I-7065 I-7065D I-7067 I-7067D Output Channels Relay Type Contact Rating Surge Operate Release Strength Time Time RL1, RL2 : Form A RL3, RL4 : Form C Form A Form 5A@250VAC 5A@30VDC A Form A 500V 4000V 1500V 3 ms 6 ms Max. 5mS Max. 2 ms 3 ms Max. 2mS Max. 5 Min. Life 5*10 ops ops ops. Input Channels Isolation Isolation Voltage Digital Digital Input Power Level 0 Level 1 Impedance Input Power Consumption Isolation with Common Source 1.3W (I-7060) 1.9W (I-7060D) 3750Vrms +4 +1V max to +30 3K ohms +10 to V 1.0W (I-7063) 1.5W (I-7063D) +30 VDC 1.3W (I-7065) 2.2W (I-7065D) No input 1.5W (I-7067) 2.2W (I-7067D) CB-7000 DIO Manual 11

12 Solid-State Relay Output Modules I-7063A I-7063AD I-7065A I-7065AD I-7063B I-7063BD I-7065B I-7065BD Output Channels SSR Type Load Voltage Range Leakage Max Load Min. Min. Operate Release Dielectric Current Current Time Time Strength AC-SSR, Normal Open DC-SSR, Normal Open 24 to 265 Vrms 3 to 30 VDC 1.5 marm s 0.1 ma 1.0 Arms 1.0 A 1mS 1/2 cycle + 1mS 1mS 2500 Vrms Input Channels Isolation Isolation Voltage Digital Digital Input Power Level 0 Level 1 Impedance Input Power Consumption 0.7W (I-7063A) 1.5W (I-7063AD) Isolation with Common Source 3750Vrms V max to +30 3K ohms to 0.8W (I-7065A) 1.6W (I-7065AD) +30 V VDC 0.6W (I-7063B) 1.4W (I-7063BD) 0.7W (I-7065B) 1.5W (I-7065BD) Note: Model numbers I-nnnn and model numbers CB-nnnn are identical. 12 CB-7000 DIO Manual

13 1.3 Block Diagrams CB-7000 DIO Manual 13

14 14 CB-7000 DIO Manual

15 CB-7000 DIO Manual 15

16 16 CB-7000 DIO Manual

17 CB-7000 DIO Manual 17

18 18 CB-7000 DIO Manual

19 CB-7000 DIO Manual 19

20 20 CB-7000 DIO Manual

21 1.4 Connections Dry Contact signal input CB-7052/52D TTL/CMOS signal input CB-7052/52D CB-7050/50D/53/53D CB-7050/50D/53/53D CB-7041/41D/44/44D/60/60D/ 63/63D/63A/63AD/63B/63BD/ 65/65D/65A/65AD/65B/65BD CB-7041/41D/44/44D/60/60D/ 63/63D/63A/63AD/63B/63BD/ 65/65D/65A/65AD/65B/65BD CB-7000 DIO Manual 21

22 Open Collector signal input CB-7052/52D CB-7041/41D/44/44D/60/60D/ 63/63D/63A/63AD/63B/63BD/ 65/65D/65A/65AD/65B/65BD CB-7050/50D/53/53D 22 CB-7000 DIO Manual

23 Open Collector output CB-7050/50D Note: When connecting inductive loads (for example, a relay), install a diode to prevent counter EMF kickback. CB-7043/43D CB-7042/42D/44/44D CB-7000 DIO Manual 23

24 1.5 Quick Start Refer to CBCOM Series Network Setup and Quick Start Manual and Getting Started for details. 1.6 Default Setting Default setting for CB-7000 DIO modules: l Address: 01 l l l l l Baud rate: 9600 bps Type: Type 40 for DIO mode Checksum Disable CB-7043/43D jumper setting at INIT* CB-7053/53D jumper setting at INIT* 1.7 Jumper Setting CB-7043/43D: Jumper J3 for select the pin INIT*/DO15 Select DO15 Select INIT* (default) CB-7053/53D: Jumper J1 for select the pin INIT*/DI15 Select DI15 Select INIT* 1.8 Configuration Tables (default) Configuration Table of CB-7000 DIO modules Baud rate Setting (CC) Code A Baudrate CB-7000 DIO Manual

25 Type Setting (TT) Type = 40 for DIO mode Data Format Setting (FF) * 1 * * 3 *1: Counter Update Direction: 0=Falling Edge, 1=Rising Edge *2: Checksum Bit: 0=Disable, 1=Enable *3: 7050 = 0 (Bit[2.1.0] = 000), 7060 = 1 (Bit[2.1.0] = 001) 7052 = 2 (Bit[2.1.0] = 010), 7053 = 3 (Bit[2.1.0] = 011) Read Digital Input/Output Data Format Data of $AA6,$AA4,$AALS: (First Data)(Second Data)00 Data (First Data)(Second Data) First I -7041/41D DI(8-13) I -7042/42D DO(8-12) I -7043/43D DO(8-15) I -7044/44D DO(1-8) I -7050/50D DO(0-7) I -7052/52D DI(0-7) I -7053/53D DI(8-15) I -7060/60D DO(1-4) 1 I-7063s 2 I-7065s * O(1-3) Data 00 to 3F DI(0-7) 00 to 1F DO(0-7) 00 to FF DO(0-7) 00 to FF DI(1-4) 00 to FF DI(0-6) CB-7000 DIO Manual Second Data 00 to FF 00 to FF 00 to FF 00 to 0F 00 to 7F 00 to FF to FF DI(0-7) 00 to 0F DI(1-4) D 00 to 07 DI(1-8) * DO(1-5 ) I -7066/66D DO(1-7) I -7067/67D DO(1-7) 00 to 1F DI(1-4) * 1 I-7063s include : I-7063/63D/63A/63AD/63B/63B D * 2 I-7065s include : I-7065/65D/65A/65AD/65B/65B D 00 to FF 00 to 0F 00 to FF 00 to 0F 00 to 7F to 7F

26 2. Commands Command Format: (Leading)(Address)(Command)[CHK](cr) Response Format: (Leading)(Address)(Data)[CHK](cr) [CHK] 2-character checksum (cr) end-of-command character, character return(0x0d) Calculate Checksum: 1. Calculate ASCII sum of all characters of command (or response) string except the carriage return (cr). 2. Mask the sum of string with 0ffh. Example: Command string: $012(cr) Sum of string = $ = 24h+30h+31h+32h = B7h The checksum is B7h, and [CHK] = B7 Command string with checksum: $012B7(cr) Response string:! (cr) Sum of string:! = 21h+30h+31h+34h+30h+30h+36h+30h+30h = 1ACh The checksum is ACh, and [CHK] = AC Response string with checksum:! ac(cr) 26 CB-7000 DIO Manual

27 Command Command Host Watchdog Respons e ~ ** No Response Command Sets CB-7000 DIO Manual Descriptio n Section Host OK Sec.2.17 ~ AA0! AASS Read Module Status Sec.2.18 ~ AA1! AA Reset Module Status Sec.2.19 ~ AA2!AAV V ~ AA3EVV!AA General Command Sets Respons e Descriptio n Read Host Watchdog Timeout Value Set Host Watchdog Timeout Value Section % AANNTTCCFF! AA Set Module Configuratio n Sec.2. 1 #** No Response Synchronized Samplin g Sec.2. 2 # AABBDD > Digital Ouput Sec.2. 3 # AAN! AA(Data ) Read Digital Input Counte r Sec.2. 4 $ AA2! AATTCCF F Read Configuratio n Sec.2. 5 $ AA4! S(Data) Read Synchronized Data Sec.2. 6 $ AA5! AAS Read Reset Status Sec.2. 7 $ AA6!(Data) Read Digital I/O Status Sec.2. 8 $ AAF! AA(Data ) Read Firmware Versio n Sec.2. 9 $ AAM! AA(Data ) Read Module Name Sec.2.10 $ AAC! AA Clear Latched Digital Input Sec.2.11 $ AACN! AA Clear Ditial Input Count Sec.2.12 $ AALS!(Data) Read Latched Digital Input AA > (Data) Read Digital Input AA(Data) > Set Digital Output Sec.2.15 ~ AAO(Data)! AA Set Module Name Sec.2.16 Sec.2.20 Sec.2.21 ~ AA4V! AA(Data ) Read PowerOn/Safe Valu e Sec.2.22 ~ AA5V! AA Set PowerOn/Safe Valu e Sec

28 2.1 %AANNTTCCFF Description: Set module Configuration Syntax: %AANNTTCCFF[CHK](cr) % Delimiter character AA Address of setting module (00 to FF) NN New Address for setting module (00 to FF) TT Type 40 for DIO module CC New baud rate for setting module (Ref. Sec. 1.9). Short INIT* to ground when changing baud rate. (Ref Sec. 3.1) FF New data format for setting module (Ref. Sec. 1.9). Short the INIT* to ground to change checksum setting. (Ref. Sec. 3.1) Response: Valid Command:!AA[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) Example: Command: % Receive:!02 Set module Address 01 to 02; return successful. Related Command: Sec. 2.5 $AA2 Related Topics: Sec. 1.9 Configuration Tables, Sec. 3.1 INIT* pin Operation 28 CB-7000 DIO Manual

29 2.2 #** Description: Synchronized Sampling Syntax: #**[CHK](cr) # Delimiter character ** Synchronized sampling Command Response: No response Example: Command: #** No response Send synchronized sampling Command to all modules. Command: $014 Receive:!10F0000 Read synchronized data from Address 01, return S=1, first read and data. Command: $014 Receive:!00F0000 Read synchronized data from Address 02, return S=0, have read data. Related Command: Sec. 2.6 $AA4 CB-7000 DIO Manual 29

30 2.3 #AABBDD Description: Digital Output Command: #AABBDD[CHK](cr) # Delimiter character AA Address of reading module(00 to FF) BBDD Output command and parameter For multichannel outputs, set BB = 00, 0A, or 0B. It selects the output group. DD is the output value. Parameter for Multi-Channel Output Output Channels DD for command #AABBDD BB=00/0A I-7042/42D to FF DO(0-7) I-7043/43D to FF DO(0-7) I-7044/44D 8 00 to FF DO(1-8) I-7050/50D 8 00 to FF DO(0-7) I-7060/60D 4 00 to 0F RL(1-4) 1 I-7063s * 3 00 to 0 7 RL(1-3) 2 I-7065s * 5 00 to 1 F RL(1-5) I-7066/66D 7 00 to 7F RL(1-7) I-7067/67D 7 00 to 7F RL(1-7) BB=0B 00 to 1F DO(8-12) 00 to FF DO(8-15) NA NA NA NA NA NA NA * 1 I-7063s include : I-7063/63D/63A/63AD/63B/63B D * 2 I-7065s include : I-7065/65D/65A/65AD/65B/65B D NA NA NA NA NA NA NA To output a single-channel, set BB = 1c, Ac, or Bc where c is the selected channel. Set DD to 00 to clear output and 01 to set the output. 30 CB-7000 DIO Manual

31 Parameter for Single-Channel Output Response: Valid Command: >[CHK](cr) Invalid Command: Single channel output command #AABBDD c for BB=1c/Ac Ignored Command: Command: # Receive: > CB-7000 DIO Manual c for BB=Bc I-7042/42D 0 to 7 DO(0-7) 0 to 4 DO(8-12) I-7043/43D 0 to 7 DO(0-7) 0 to 7 DO(8-15) I-7044/44D 0 to 7 DO(1-8) I-7050/50D 0 to 7 DO(0-7) I-7060/60D 0 to 3 RL(1-4) 1 I-7063s 2 I-7065s * to 2 0 RL(1-3) * to 4 0 RL(1-5) I-7066/66D 0 to 6 RL(1-7) I-7067/67D 0 to 6 RL(1-7)?[CHK](cr)![CHK](cr) Syntax or communication error may get no response. > Delimiter for valid Command? Delimiter for invalid Command! Delimiter for ignoring the Command. The module s host watchdog timeout status is set, and the output is set to Safe Value. Example: Command: #0100FF Receive: > Assume module is CB-7044, set Address 01 output value FF; return is successful. NA NA NA NA NA NA NA * 1 I-7063s include : I-7063/63D/63A/63AD/63B/63B D * 2 I-7065s include : I-7065/65D/65A/65AD/65B/65B D NA NA NA NA NA NA NA 31

32 Assume module is CB-7067, set Address 02 channel 0 on, return is successful. Command: # Receive:? Set Address 02 channel 7 on, return the channel is invalid for CB-7067; it only has seven outputs (0 to 6). Command: #0300FF Receive:! Set Address 03 output value FF, return ignore. The module s host watchdog timeout status is set, and the output is set to Safe Value. Related Command: Sec. Sec ~AA0, Sec ~AA1 Related Topics: Sec. 1.9 Configuration Tables, Sec. 3.2 Module Status, Sec. 3.3 Dual Watchdog Operation Note: The Command is not for CB-7041/41D/52/52D/53/53D. 32 CB-7000 DIO Manual

33 2.4 #AAN Description: Read Digital Input Counter from channel N Command: #AAN[CHK](cr) # Delimiter character AA Address of reading module (00 to FF) N channel to read Response: Valid Command:!AA(Data)[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) (Data) Digital input counter value in decimal, from to Example: Command: #032 Receive:! Read Address 03 digital input counter value of channel 2, return value 103. Command: #025 Receive:?02 Read Address 02 digital input counter value of channel 5, return the channel is not available. Related Command: Sec $AACN Note: The Command is not for CB-7042/42D/43/43D/66/66D/67/67D. CB-7000 DIO Manual 33

34 2.5 $AA2 Description: Read Configuration Command: $AA2[CHK](cr) $ Delimiter character AA Address of reading module (00 to FF) 2 Command for read configuration Response: Valid Command:!AATTCCFF[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) TT Type code of module; it must be 40 CC Baud rate code of module (Ref. Sec. 1.9) FF Data format of module (Ref. Sec. 1.9) Example: Command: $012 Receive:! Read Address 01 status, return DIO mode, baud 9600, no checksum. Related Command: Sec. 2.1, %AANNTTCCFF Related Topics: Sec. 1.9, Configuration Tables; Sec. 3.1, INIT* pin Operation 34 CB-7000 DIO Manual

35 2.6 $AA4 Description: Read Synchronized Data Command: $AA4[CHK](cr) $ Delimiter character AA Address of reading module (00 to FF) 4 Command for read synchronized data Response: Valid Command:!S(Data)[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) S Status of synchronized data, 1 = first read, 0 = been read (Data) synchronized DIO value (Ref. Sec. 1.9) Example: Command: $014 Receive:?01 Read Address 01 synchronized data, return no data available. Command: #** Receive: no response Send synchronized sampling to all modules. Command: $014 Receive:!1000F00 Read Address 01 synchronized data, return S=1, first read, and synchronized data 0F00 Related Command: Sec. 2.2, #** Related Topics: Sec. 1.9, Configuration Tables CB-7000 DIO Manual 35

36 2.7 $AA5 Description: Read Reset Status Command: $AA5[CHK](cr) $ Delimiter character AA Address of reading module (00 to FF) 5 Command for read reset status Response: Valid Command:!AAS[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) S Reset status, 1 = the module has been reset, 0 = the module has not been reset. Example: Command: $015 Receive:!011 Read Address 01 reset status, return first read. Command: $015 Receive:!010 Read Address 01 reset status, return no reset occurred. Related Topics: Sec3.4, Reset Status 36 CB-7000 DIO Manual

37 2.8 $AA6 Description: Read Digital I/O Status Command: $AA6[CHK](cr) $ Delimiter character AA Address of reading module (00 to FF) 6 Command for read digital input/output status Response: Valid Command:!(Data)[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) (Data) Digital input/output value (Ref. Sec. 1.9) Example: Command: $016 Receive:!0F0000 Assume module is CB Read Address 01 DIO status, return 0F00; digital input IN1 to IN4 are open, digital output RL1 to RL4 are off. Related Command: Sec. Related Topics: Sec. 1.9, Configuration Tables CB-7000 DIO Manual 37

38 2.9 $AAF Description: Read Firmware Version Command: $AAF[CHK](cr) $ Delimiter character AA Address of reading module (00 to FF) F Command for read firmware version Response: Valid Command:!AA(Data)[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) (Data) Firmware version of module Example: Command: $01F Receive:!01A2.0 Read Address 01 firmware version, return version A2.0. Command: $02F Receive:!01B1.1 Read Address 01 firmware version, return version B CB-7000 DIO Manual

39 2.10 $AAM Description: Read Module Name Command: $AAM[CHK](cr) $ Delimiter character AA Address of reading module (00 to FF) M Command for read module name Response: Valid Command:!AA(Data)[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) (Data) Name of module Example: Command: $01M Receive:! Read Address 01 module name, return name Command: $03M Receive:!037060D Read Address 03 module name, return name 7060D. Related Command: Sec. 2.16, ~AAO(Data) CB-7000 DIO Manual 39

40 2.11 $AAC Description: Clear Latched Digital Input Command: $AAC[CHK](cr) $ Delimiter character AA Address of setting module (00 to FF) C Command for clear latched digital input Response: Valid Command:!AA[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) Example: Command: $01L0 Receive:!01FFFF00 Read Address 01 latch-low data, return FFFF. Command: $01C Receive:!01 Clear Address 01 latched data, return successful. Command: $01L0 Receive:! Read Address 01 latch-low data, return Related Command: Sec. 2.13, $AALS Note: The Command is not for CB-7042/42D/43/43D/66/66D/67/67D. 40 CB-7000 DIO Manual

41 2.12 $AACN Description: Clear Digital Input Counter Command: $AACN[CHK](cr) $ Delimiter character AA Address of setting module (00 to FF) C Command for clear digital input counter N Digital counter channel N to clear Response: Valid Command:!AA[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) Example: Command: #010 Receive:! Read Address 01 input channel 0 counter value, return 123. Command: $01C0 Receive:!01 Clear Address 01 input channel 0 counter value, return successful. Command: #010 Receive:! Read Address 01 input channel 0 counter value, return 0. Related Command: Sec. 2.4, #AAN Note: The Command is not for CB-7042/42D/43/43D/66/66D/67/67D. CB-7000 DIO Manual 41

42 2.13 $AALS Description: Read Latched Digital Input Command: $AALS[CHK](cr) $ Delimiter character AA Address of reading module (00 to FF) L Command for reading latched digital input S 1 = select latched high status, 0 = select latched low Response: Valid Command:!(Data)[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) (Data) read status (Ref. Sec. 1.9) 1= the input channel is latched, 0=the input channel is not latched. Example: Command: $01L1 Receive:! Read Address 01 latch-high data, return Command: $01C Receive:!01 Clear Address 01 latched data, return successful. Command: $01L1 Receive:! Read Address 01 latch-high data, return 0. Related Command: Sec. 2.11, $AAC Note: The Command is not for CB-7042/42D/43/43D/66/66D/67/67D. 42 CB-7000 DIO Manual

43 Description: Read Digital Input/Output Delimiter character AA Address of reading module (00 to FF) Response: Valid Command: >(Data)[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response. > Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) (Data) Read DIO status (Ref. Sec. 1.9) Example: Receive: >0F00 Read Address 01 DIO status, return 0F00. Related Command: Sec. 2.8, $AA6 Related Topics: Sec. 1.9, Configuration Tables CB-7000 DIO Manual 43

44 Description: Set Digital Delimiter character AA Address of setting module (00 to FF) (Data) output value, the data format is following: (Data) is one character for output channel less than 4 For CB-7060/60D, from 0 to F For CB-7063/63D/63A/63AD/63B/63BD, from 0 to 7 (Data) is two characters for output channel less than 8 For CB-7044/44D/50/50D, from 00 to FF For CB-7065/65D/65A/65AD/65B/65BD, from 00 to 1F For CB-7066/66D/67/67D, from 00 to 7F (Data) is four characters for output channel less than 16 For CB-7042/42D, from 0000 to 1FFF For CB-7043/43D, from 0000 to FFFF Response: Valid Command: >[CHK](cr) Invalid Command:?[CHK](cr) Ignore Command:![CHK](cr) Syntax or communication error may get no response. > Delimiter for valid Command.? Delimiter for invalid Command.! Delimiter for ignore Command. The module is in Host Watchdog Timeout Mode, and the output is set to SafeValue. Example: Receive: > 44 CB-7000 DIO Manual

45 Output Address 02 value 7, return successful.(the example is suitable for CB-7060/60D/63/63D/63A/63AD/63B/63BD) Receive: > Output Address 01 value 00, return successful.(the example is suitable for CB-7044/44D/50/50D/65/65D/65A/65AD/65B/ 65BD/66/66D/67/67D) Receive:! Output Address 03 value 0012, return the module is in host watchdog timeout mode, the output Command is ignored. (The example is suitable for CB-7042/42D/43/43D) Related Command: Sec. 2.3, #AABBDD; Sec. 2.18, ~AA0; Sec. 2.19, ~AA1 Relate;d Topics: Sec. 1.9, Configuration Tables; Set.3.2, Module Status; Sec. 3.3 Dual Watchdog Operation; Sec. 3.5, Digital Output Note: The Command is not for CB-7041/41D/52/52D/53/53D. CB-7000 DIO Manual 45

46 2.16 ~AAO(Data) Description: Set Module Name Command: ~AAO(Data)[CHK](cr) ~ Delimiter character AA Address of setting module (00 to FF) O Command for set module name (Data) New name for module, max 6 characters Response: Valid Command:!AA[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) Example: Command: ~01O7050 Receive:!01 Set Address 01 module name 7050, return successful. Command: $01M Receive:! Read Address 01 module name, return name Related Command: Sec. 2.10, $AAM 46 CB-7000 DIO Manual

47 2.17 ~** Description: Host OK. Host send this Command to all modules for send the information Host OK. Command: ~**[CHK](cr) ~ Delimiter character ** Command for all modules Response: No response. Example: Command: ~** No response Related Command: Sec. 2.18, ~AA0; Sec. 2.19, ~AA1; Sec. 2.20, ~AA2; Sec. 2.21, ~AA3EVV; Sec. 2.22, ~AA4V; Sec. 2.23, ~AA5V Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation CB-7000 DIO Manual 47

48 2.18 ~AA0 Description: Read Module Status Command: ~AA0[CHK](cr) ~ Delimiter character AA Address of reading module (00 to FF) 0 Command for read module status Response: Valid Command:!AASS[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) SS Module status, 00=host watchdog timeout status is clear, 04=host watchdog timeout status is set. The status will store into EEPROM and only may reset by the Command ~AA1. Example: Refer to Sec. 2.21, ~AA3EVV example. Related Command: Sec. 2.17, ~**; Sec. 2.19, ~AA1; Sec. 2.20, ~AA2; Sec. 2.21, ~AA3EVV; Sec. 2.22, ~AA4V; Sec. 2.23, ~AA5V Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation 48 CB-7000 DIO Manual

49 2.19 ~AA1 Description: Reset Module Status Command: ~AA1[CHK](cr) ~ Delimiter character AA Address of setting module (00 to FF) 1 Command for reset module status Response: Valid Command:!AA[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module (00 to FF) Example: Refer to Sec. 2.21, ~AA3EVV example. Related Command: Sec. 2.17, ~**; Sec. 2.18, ~AA0; Sec. 2.20, ~AA2; Sec. 2.21, ~AA3EVV; Sec. 2.22, ~AA4V; Sec. 2.23, ~AA5V Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation CB-7000 DIO Manual 49

50 2.20 ~AA2 Description: Read Host Watchdog Timeout Value Command: ~AA2[CHK](cr) ~ Delimiter character AA Address of reading module (00 to FF) 2 Command for read host watchdog timeout value Response: Valid Command:!AAEVV[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) E Host watchdog enable status, 1 = Enable, 0 = Disable VV Timeout value in HEX format, each count is 0.1 second, 01h = 0.1 second and FFh = 25.5 seconds Example: Refer to Sec. 2.21, ~AA3EVV example. Related Command: Sec. 2.17, ~**; Sec. 2.18, ~AA0; Sec. 2.19, ~AA1; Sec. 2.21, ~AA3EVV; Sec. 2.22, ~AA4V; Sec. 2.23, ~AA5V Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation 50 CB-7000 DIO Manual

51 2.21 ~AA3EVV Description: Set Host Watchdog Timeout Value Command: ~AA3EVV[CHK](cr) ~ Delimiter character AA Address of setting module (00 to FF) 3 Command for set host watchdog timeout value E 1 = Enable, 0 = Disable host watchdog VV Timeout value, from 01 to FF, each for 0.1 second Response: Valid Command:!AA[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module (00 to FF) Example: Command: ~010 Receive:!0100 Read Address 01 module status, return host watchdog timeout status is clear. Command: ~ Receive:!01 Set Address 01 host watchdog timeout value 10.0 seconds and enable host watchdog, return successful. Command: ~012 Receive:!01164 Read Address 01 host watchdog timeout value; return that host watchdog is enabled, and time interval is 10.0 seconds. Command: ~** No response CB-7000 DIO Manual 51

52 Reset the host watchdog timer. Wait for about 10 seconds and don t send command ~**, the LED of module will flash. The flashing LED indicates the host watchdog timeout status is set. Command: ~010 Receive:!0104 Read Address 01 modul status, return host watchdog timeout status is set. Command: ~012 Receive:!01064 Read Address 01 host watchdog timeout value, return that host watchdog is disabled, and time interval is 10.0 seconds. Command: ~011 Receive:!01 Reset Address 01 host watchdog timeout status, return successful. And the LED of this module stop flash. Command: ~010 Receive:!0100 Read Address 01 module status, return host watchdog timeout status is clear. Related Command: Sec. 2.17, ~**; Sec. 2.18, ~AA0; Sec. 2.19, ~AA1; Sec. 2.20, AA2; Sec. 2.22, ~AA4V; Sec. 2.23, ~AA5V Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation 52 CB-7000 DIO Manual

53 2.22 ~AA4V Description: Read PowerOn/Safe Value. Command: ~AA4V[CHK](cr) ~ Delimiter character AA Address of reading module (00 to FF) 4 Command for read PowerOn/Safe Value V P = read PowerOn value, S = read Safe Value Response: Valid Command:!AA(Data)[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) (Data) PowerOn Value or Safe Value For CB-7042/42D/43/43D (Data) is VVVV, where VVVV is the PowerOn Value (or Safe Value). For other modules, (Data) is VV00, where VV is the PowerOn Value(or Safe Value). Example: Receive: > Output Address 01 value 0000, return successful. Command: ~015S Receive:!01 Set Address 01 Safe Value, return successful. Receive: > Output Address 01 value FFFF, return successful. Command: ~015P Receive:!01 CB-7000 DIO Manual 53

54 Set Address 01 PowerOn Value, return successful. Command: ~014S Receive:! Read Address 01 Safe Value, return Command: ~014P Receive:!01FFFF Read Address 01 PowerOn Value, return FFFF. Related Command: Sec. 2.17, ~**; Sec. 2.18, ~AA0; Sec. 2.19, ~AA1; Sec. 2.20, ~AA2; Sec. 2.21, ~AA3EVV; Sec. 2.23, ~AA5V Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation Note: The Command is not for CB-7041/41D/52/52D/53/53D. 54 CB-7000 DIO Manual

55 2.23 ~AA5V Description: Set PowerOn/Safe Value. Command: ~AA5V[CHK](cr) ~ Delimiter character AA Address of setting module (00 to FF) 5 Command for set PowerOn/Safe Value V P = set current output as PowerOn Value, S = set current output as Safe Value Response: Valid Command:!AA[CHK](cr) Invalid Command:?AA[CHK](cr) Syntax or communication error may get no response.! Delimiter for valid Command? Delimiter for invalid Command AA Address of response module(00 to FF) Example: Receive: > Output Address 01 value AA, return successful. Command: ~015P Receive:!01 Set Address 01 PowerOn Value, return successful. Receive: > Output Address 01 value 55, return successful. Command: ~015S Receive:!01 Set Address 01 Safe Value, return successful. Command: ~014P Receive:!01AA00 Read Address 01 PowerOn Value, return PowerOn Value AA. Command: ~014S Receive:! CB-7000 DIO Manual 55

56 Read Address 01 Safe Value, return Safe Value 55. Related Command: Sec. 2.17, ~**; Sec. 2.18, ~AA0; Sec. 2.19, ~AA1; Sec. 2.20, ~AA2; Sec. 2.21, ~AA3EVV; Sec. 2.22, ~AA4V Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation Note: The Command is not for CB-7041/41D/52/52D/53/53D. 56 CB-7000 DIO Manual

57 3. Application Notes 3.1 INIT* pin Operation Each CB-7000 module has a build-in EEPROM to store configuration information such as address, type, baud rate and other information. Sometimes, a user may forget the configuration of the module. Therefore, the CB-7000 have a special mode named INIT mode, to help user to resolve the problem. The INIT mode is setting as Address=00, baud rate=9600bps, no checksum To enable INIT mode, please follow these steps: Step 1. Power-down the module. Step 2. Connect the INIT* pin to the GND pin. Step 3. Power-up the module. Step 4. Send Command $002(cr) in 9600 bps to read the configuration stored in the module s EEPROM. Refer to 7000 Bus Converter User Manual Sec. 5.1 and Getting Started for more information. 3.2 Module Status PowerOn Reset or Module Watchdog Reset will set all outputs to the PowerOn Value. The module can accept the host s Command to change the output value. Host Watchdog Timeout will set all output to the Safe Value.The module s status (read by Command ~AA0) will be 04, and the output Command will be ignored. CB-7000 DIO Manual 57

58 3.3 Dual Watchdog Operation Dual Watchdog = Module Watchdog + Host Watchdog The Module Watchdog is a hardware reset circuit that monitors the module s operating status. When working in harsh or noisy environment, the module may go down by a noise signal. The Module Watchdog times out and sets output to PowerOn value. The Host Watchdog is a software function to monitor the host s operating status. Its purpose is to detect a network communication problem or a halted host. When the timeout interval expired, the module will put all outputs to the predefined Safe Value. This places the controlled element in a known-safe condition. The CB-7000 module with Dual Watchdog makes the control system more reliable and stable. 3.4 Reset Status The Reset Status is set while the module power on or reset by Module Watchdog, and is cleared when the Command read Reset Status ($AA5) is applied. This is useful for user to check the module s working status. When the Reset Status is set means the module is reset and the output may be changed to the PowerOn Value. When the Reset Status is clear means the module is not reset, and the output cannot be changed. 3.5 Digital Output A module s output can have one of three values: 1. Safe Value. If the host watchdog timeout status is set, the output is set to Safe Value.If the module receives an output 58 CB-7000 DIO Manual

59 Command, such or #AABBDD, the module ignores the command and returns!, and will not change the output to the output command value. The host watchdog timeout status is set and stored in EEPROM when the host watchdog timeout interval expired, and only can be cleared by Command ~AA1. If user wants to change the output, he first needs to clear the host watchdog timeout status, then send an output command to change the output to a desired value. 2. PowerOn Value. When the Module Watchdog Timer is set, and the host watchdog timeout status is clear, the module s output is set to the predefined PowerOn Value. 3. Output Command value. If the host watchdog timeout status is clear, the user issues a digital output command such or #AABBDD to the module for changing the output value. The module will respond successful (receive >). 3.6 Latched Digital Inputs If, for example, the user connects a PB switch to a a digital I/O module input channel and wants to read the switch stoke. The input is a pulse digial input, and user will lose the data. When read by Command $AA6 in A or B position, the response is that no input occurred and he will lose the pulse information. However, the read latch-low digital input Command $AAL0 will solve this problem. When $AAL0 Command in A and B position is issued, the response indicates that there was a low pulse between A and B position for a switch closure. CB-7000 DIO Manual 59

60 4 DN Module 4.1 DN-SSR4 Output Channel: Four Solid State Relay Contacts Output Specification: Type: Zero-Cross AC Solid-State Relay Output Rated Load Voltage: 200 to 240 VAC Rated Load Current: 4 Amps Surge Current: 50 A, Max. Off-State Leakage Current: 5.0 ma Operate Time: 1/2 cycle of voltage sine wave + 1ms Input Impedance: 1.5K Ohms DIN-Rail mounted Power Input: +24VDC 60 CB-7000 DIO Manual

61 4.2 DN-PR4 Output Channel: Four Mechanical Relay Contacts Output Specification: Type: 1 form-c Relay Contact Nominal Load: 5A@250VAC, 5A@30VDC Max. Switching Power: 1250VAC Max. Switching Voltage: 250VAC, 150VDC Max. Switching Current: 5 A. Mechanical/Electrical Life: Min. 10x10 6 /10x10 4 operations. Operate/Release Time: Max. 10 ms/5 ms Dielectric Strength: 2000VAC 1 minute Nominal Coil Power: 360 mw DIN-Rail mounted Power Input: 24VDC CB-7000 DIO Manual 61

62 4.3 RM-104, RM-108, RM-116 Output Channel: 4/8/16 Relay Contacts Output Specification: Type: 1 Form-C Relay Contact Rated Load: 16 A.@250VAC Max. Switching Voltage: 400VAC Max. Peak Current: 30 A. Standard Contact Material: AgCd0 Min. Life: 100,000 operations. Din-Rail mounted Dimension: RM-104: 78 x 77mm RM-108: 135 x 77mm RM-116: 270 x 77mm Power Input: 24VDC 62 CB-7000 DIO Manual

63 4.4 RM-204, RM-208, RM-216 Output Channel: 4/8/16 Relay Contacts Relay Specification: Type: 2 Form-C Rated Load: 5 A.@250VAC Max. Switching Voltage: 400VAC Max. Peak Current: 10 A. Standard Contact Material: Ag Nt Min. Life: 100,000 operations. Din-Rail mounted Dimension: RM-204: 78 x 77mm RM-208: 135 x 77mm RM-216: 270 x 77mm Power Input: 24VDC CB-7000 DIO Manual 63

64 4.5 Application The DN Modules are the IO extension of CB-7000 modules. These modules can drive more power and heavy loads. User may use CB-7000 modules, like CB-7043 or others, to control the DN modules to drive loads. 64 CB-7000 DIO Manual

65 For your notes. CB-7000 DIO Manual 65

66 For your notes. 66 CB-7000 DIO Manual

67 EC Declaration of Conformity We, Measurement Computing Corp., declare under sole responsibility that the product: CB-7041/42/43/44/50/52/ 53/60/63/65/66/67 Part Number Digital I/O Modules Description to which this declaration relates, meets the essential requirements, is in conformity with, and CE marking has been applied according to the relevant EC Directives listed below using the relevant section of the following EC standards and other normative documents: EU EMC Directive 89/336/EEC: Essential requirements relating to electromagnetic compatibility. EU Class B: Limits and methods of measurements of radio interference characteristics of information technology equipment. EN : EC generic immunity requirements. IEC 801-2: Electrostatic discharge requirements for industrial process measurement and control equipment. IEC 801-3: Radiated electromagnetic field requirements for industrial process measurements and control equipment. IEC 801-4: Electrically fast transients for industrial process measurement and control equipment. Carl Haapaoja, Director of Quality Assurance CB-7000 DIO Manual 67

68 Measurement Computing Corporation 10 Commerce Way Suite 1008 Norton, Massachusetts (508) Fax: (508)

I-7000 DIO Manual Warranty Warning Copyright Trademark

I-7000 DIO Manual Warranty Warning Copyright Trademark I-7000 DIO Manual Warranty All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery to the original purchaser. Warning ICP DAS assume

More information

8000 DIO Manual Warranty Warning Copyright Trademark

8000 DIO Manual Warranty Warning Copyright Trademark 8000 DIO Manual Warranty All products manufactured by SuperLogics are warranted against defective materials for a period of one year from the date of delivery to the original purchaser. Warning SuperLogics

More information

8013,8013D, 8033 User Manual

8013,8013D, 8033 User Manual 8013,8013D, 8033 User Manual Warranty All products manufactured by SuperLogics are warranted against defective materials for a period of one year from the date of delivery to the original purchaser. Warning

More information

1. Introduction. Note: For EX9050HD the (INIT*) switch located on the rear side of the module.

1. Introduction. Note: For EX9050HD the (INIT*) switch located on the rear side of the module. 1. Introduction EX-9050HD/HD-M/ provides 8 non-isolated digital output(sink) channels and 8 non-isolated digital input(source)channels All input/output channels are single-ended with common ground (See

More information

I-7000 and M-7000 DIO User Manual

I-7000 and M-7000 DIO User Manual I-7000 and M-7000 DIO User Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery to the original purchaser.

More information

I-7000 and M-7000 DIO User Manual

I-7000 and M-7000 DIO User Manual I-7000 and M-7000 DIO User Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery to the original purchaser.

More information

EX9017H-M is a analog input module with 8 input channels. Eight channels are differential type and individual channel configuration support.

EX9017H-M is a analog input module with 8 input channels. Eight channels are differential type and individual channel configuration support. 1.1 Introduction EX9017H-M is a analog input module with 8 input channels. Eight channels are differential type and individual channel configuration support. Specifications: Interface: RS-485, 2 wires

More information

I-7021, I-7022, I-7024, M-7022, M-7024 and M-7028 Series User Manual

I-7021, I-7022, I-7024, M-7022, M-7024 and M-7028 Series User Manual I-7021, I-7022, I-7024, M-7022, M-7024 and M-7028 Series User Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date

More information

SuperLogics 8000 Series Analog Input Modules

SuperLogics 8000 Series Analog Input Modules SuperLogics 8000 Series Analog Input Modules SuperLogics 8000 Series of compact remote data acquisition modules provides intelligent signal conditioning, analog I/O, and digital I/O. Through a cost-effective

More information

I-7083/7083D/7083B/7083BD

I-7083/7083D/7083B/7083BD I-7083/7083D/7083B/7083BD User s Manual I-7000 New Features 1. Self Tuner Inside 2. Multiple Baud Rate 3. Multiple Data Format 4. Dual WatchDog Inside 5. True Distributed Control 6. High Speed & High Density

More information

CIO-DO48H, CIO-DO96H and CIO-DO192H. User s Guide

CIO-DO48H, CIO-DO96H and CIO-DO192H. User s Guide CIO-DO48H, CIO-DO96H and CIO-DO192H User s Guide Revision 4A April, 2001 Trademark and Copyright Information Measurement Computing Corporation, InstaCal, Universal Library, and the Measurement Computing

More information

ZB-2024 Series User Manual

ZB-2024 Series User Manual ZB-2024 Series User Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery to the original purchaser. Warning

More information

TRP-C28. 4-channel isolated digital input and 4-channel power relay output RS485 module, Support ASCII and Modbus Protocol.

TRP-C28. 4-channel isolated digital input and 4-channel power relay output RS485 module, Support ASCII and Modbus Protocol. TRP-C28 4-channel isolated digital input and 4-channel power relay output RS485 module, Support ASCII and Modbus Protocol. User s Manual Printed NOV. 2007 Rev 1.0 Trycom Technology Co.,Ltd 1F, No.2-11,Sihu

More information

GPS-721 User Manual v2.0

GPS-721 User Manual v2.0 GPS-721 User Manual v2.0 High-quality Industrial Data Acquisition and Control Products 1/98 V2.0, Oct. 2010 Warranty All products manufactured by ICP DAS are warranted against defective materials for a

More information

TRP-C28 User s Manual

TRP-C28 User s Manual Introductions Features TRP-C28 provides 4 optical isolated digital input channels that allow you to input the logic signal from to 3V DC and 4 power relays output. All channel features screw terminals

More information

I-7080, I-7080B. User Manual

I-7080, I-7080B. User Manual I-7080, I-7080B User Manual I-7000 New Features 1. Self Tuner Inside 2. Multiple Baud Rate 3. Multiple Data Format 4. Dual WatchDog Inside 5. True Distributed Control 6. High Speed & High Density I/O Your

More information

TRP-C channel Digital Input Isolated RS485 Module, Support ASCII and Modbus Protocol. User s Manual. Printed APR Rev 1.

TRP-C channel Digital Input Isolated RS485 Module, Support ASCII and Modbus Protocol. User s Manual. Printed APR Rev 1. TRP-C26 16-channel Digital Input Isolated RS485 Module, Support ASCII and Modbus Protocol. User s Manual Printed APR. 2007 Rev 1.0 Trycom Technology Co.,Ltd 1F, No.2-11,Sihu street,yingge Township, Taipei,

More information

8017, 8018, 8019, 8017, M-8018, M-8019 Series User's Manual

8017, 8018, 8019, 8017, M-8018, M-8019 Series User's Manual 8017, 8018, 8019, 8017, M-8018, M-8019 Series User's Manual Warranty All products manufactured by SuperLogics are under warranty regarding defective materials for a period of one year from the date of

More information

4.6 Digital I/O and Relay Output Module Command

4.6 Digital I/O and Relay Output Module Command 4050, 4052, 4053, 4060 Chapter 4 4.6 Digital I/O and Relay Output Module Command Command Syntax Command % AANNTTCCFF C onfiguration Sets the address, input range, baud rate, and/or checksum status, to

More information

I-7017, I-7018, I-7019, M-7017, M-7018 and M-7019 Series User Manual

I-7017, I-7018, I-7019, M-7017, M-7018 and M-7019 Series User Manual I-7017, I-7018, I-7019, M-7017, M-7018 and M-7019 Series User Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date

More information

I-7520: RS-232 to RS-485. Input: RS-232 protocol Output:RS-485/RS-422 Speed: Self Tuner 'inside, auto switching baud rate, 300~ BPS

I-7520: RS-232 to RS-485. Input: RS-232 protocol Output:RS-485/RS-422 Speed: Self Tuner 'inside, auto switching baud rate, 300~ BPS I-7520 RS-232 to RS-485 Converter I-7510 RS-485 Repeater RS-232 RS-485 I-7000 SERIES Common Specifications Isolation voltage: 3000VDC Speed: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115000 Dual watchdog

More information

USB-PDISO8/40. USB-based Isolated Input and Relay Output. User's Guide. September Rev 6 Measurement Computing Corporation

USB-PDISO8/40. USB-based Isolated Input and Relay Output. User's Guide. September Rev 6 Measurement Computing Corporation USB-PDISO8/40 USB-based Isolated Input and Relay Output User's Guide September 2017. Rev 6 Measurement Computing Corporation Trademark and Copyright Information Measurement Computing Corporation, InstaCal,

More information

JSD81 series products are based on SCM's intelligent monitoring and control system, users set the calibration value,

JSD81 series products are based on SCM's intelligent monitoring and control system, users set the calibration value, 8-Channel Analog Signals to RS485/232 Converter(A/D Converter JSD81 series) Features: 8-CH analog signal acquisition/isolation,rs-485/232 output 24-bit AD converter, testing accuracy>0.05% Can Program

More information

PCI-PDISO8. Isolated Input and Relay Output. User's Guide

PCI-PDISO8. Isolated Input and Relay Output. User's Guide PCI-PDISO8 Isolated Input and Relay Output User's Guide Document Revision 10A April 2012 Copyright 2012 Trademark and Copyright Information Measurement Computing Corporation, InstaCal, Universal Library,

More information

TRP-C29. 8-channel isolated digital input and 8-channel isolated digital output(o.c) RS485 module, Support ASCII and Modbus Protocol.

TRP-C29. 8-channel isolated digital input and 8-channel isolated digital output(o.c) RS485 module, Support ASCII and Modbus Protocol. TRP-C29 8-channel isolated digital input and 8-channel isolated digital output(o.c) RS485 module, Support ASCII and Modbus Protocol. User s Manual Printed Sep. 2013 Rev 1.3 Trycom Technology Co.,Ltd No.35,

More information

TRP-C68. 8-Channel Analog Input to Digital Output Isolated Module Support ASCII and Modbus RTU protocol USER S MANUAL. June Rev 1.

TRP-C68. 8-Channel Analog Input to Digital Output Isolated Module Support ASCII and Modbus RTU protocol USER S MANUAL. June Rev 1. TRP-C68 8-Channel Analog Input to Digital Output Isolated Module Support ASCII and Modbus RTU protocol USER S MANUAL June. 2007 Rev 1.0 Trycom Technology Co.,Ltd 1F, No.2-11,Sihu street,yingge Township,

More information

NuDAM-6050 NuDAM-6052 NuDAM-6053 NuDAM-6054 NuDAM-6056 NuDAM-6058 NuDAM-6060 NuDAM Digital I/O Modules

NuDAM-6050 NuDAM-6052 NuDAM-6053 NuDAM-6054 NuDAM-6056 NuDAM-6058 NuDAM-6060 NuDAM Digital I/O Modules NuDAM-6050 NuDAM-6052 NuDAM-6053 NuDAM-6054 NuDAM-6056 NuDAM-6058 NuDAM-6060 NuDAM-6063 Digital I/O Modules Copyright 1995~2001 ADLINK Technology Inc. All Rights Reserved. Manual Rev. 3.51: March 27, 2001

More information

CIO-DO24DD & CIO-DO48DD. User s Manual

CIO-DO24DD & CIO-DO48DD. User s Manual CIO-DO24DD & CIO-DO48DD User s Manual Revision 5A November, 2000 Trademark and Copyright Information Measurement Computing Corporation, InstaCal, Universal Library, and the Measurement Computing logo are

More information

i-7005 and M-7005 User s Manual

i-7005 and M-7005 User s Manual i-7005 and M-7005 User s Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery to the original purchaser.

More information

User's Guide. CIO-PDISO8

User's Guide.    CIO-PDISO8 User's Guide http://www.omega.com e-mail: info@omega.com CIO-PDISO8 INTRODUCTION... DESCRIPTION... ACCESSORIES... 2 INSTALLATION... 3 SOFTWARE... 3 BASE ADDRESS... 3 WAIT STATE... 4 AC INPUT FILTER...

More information

PCM-DAC02. PCMCIA Dual Analog Outputs. User s Manual

PCM-DAC02. PCMCIA Dual Analog Outputs. User s Manual PCM-DAC02 PCMCIA Dual Analog Outputs User s Manual Revision 3 August, 2001 MEGA-FIFO, the CIO prefix to data acquisition board model numbers, the PCM prefix to data acquisition board model numbers, PCM-DAS08,

More information

Ethernet I/O Module by ICP DAS Co., Ltd. All Rights Reserved. Comparison Item tpet PETL-7000 PET-7000 CPU 32-bit ARM Ethernet

Ethernet I/O Module by ICP DAS Co., Ltd. All Rights Reserved. Comparison Item tpet PETL-7000 PET-7000 CPU 32-bit ARM Ethernet Providing networking ability and various digital I/O functions, the PETL-7000 and tet/tpet series are IP-based Ethernet I/O monitoring and control modules. The module can be remotely controlled through

More information

TRP-C24 User's Manual

TRP-C24 User's Manual Introductions Features The TRP-C24, an RS-485 isolated open collector output module, provides 16 digital outputs channels. Each channel features screw terminals for the convenience connection of field

More information

TRP-C68. 8-Channel Analog Input to Digital Output Isolated Module Support ASCII and Modbus RTU protocol USER S MANUAL. Dec Rev 1.

TRP-C68. 8-Channel Analog Input to Digital Output Isolated Module Support ASCII and Modbus RTU protocol USER S MANUAL. Dec Rev 1. TRP-C68 8-Channel Analog Input to Digital Output Isolated Module Support ASCII and Modbus RTU protocol USER S MANUAL Dec. 2010. Rev 1.2 Trycom Technology Co.,Ltd 1F, No.2-11,Sihu street,yingge Township,

More information

Signal Isolators & Conditioners

Signal Isolators & Conditioners 8-ch DI Switch Signal to RS485/232 Converters (WJ62 Series) Features: >> Eight channels switch signal acquisition,isolated RS-485/232 output >> Each input channel adopts optical isolation >> Can read level

More information

Analog signal to RS485 or RS232 Converter, A/D Converter

Analog signal to RS485 or RS232 Converter, A/D Converter Analog signal to RS485 or RS232 Converter, A/D Converter Features: Analog signal acquisition, isolated RS-485/232 output 12-bit AD converter, testing accuracy>0.1% Can be remotely reconfigured for modules

More information

Produkt-Datenblatt. Technische Daten, Spezifikationen. MEsstechnik fängt mit ME an. Kontakt

Produkt-Datenblatt. Technische Daten, Spezifikationen. MEsstechnik fängt mit ME an.   Kontakt Produkt-Datenblatt Technische Daten, Spezifikationen Kontakt Technischer und kaufmännischer Vertrieb, Preisauskünfte, Angebote, Test-Geräte, Beratung vor Ort: Tel: (0 81 41) 52 71-0 FAX: (0 81 41) 52 71-129

More information

OMR-6011/D OMR-6014D OMR-6012/D OMR-6017 OMR-6013 OMR Analog Input Modules

OMR-6011/D OMR-6014D OMR-6012/D OMR-6017 OMR-6013 OMR Analog Input Modules OMR-6011/D OMR-6014D OMR-6012/D OMR-6017 OMR-6013 OMR-6018 Analog Input Modules Contents 1 Introduction... 1-1 1. 1. ABOUT THE OMR ANALOG INPUT MODULES...1-1 1. 2. OVERVIEW OF OMR-6011/D...1-1 1. 3. OVERVIEW

More information

USB-ERB24. USB-based 24-Channel Electromechanical Relay Interface Device. User's Guide. May Rev 8A Measurement Computing Corporation.

USB-ERB24. USB-based 24-Channel Electromechanical Relay Interface Device. User's Guide. May Rev 8A Measurement Computing Corporation. USB-ERB24 USB-based 24-Channel Electromechanical Relay Interface Device User's Guide May 2016. Rev 8A Measurement Computing Corporation. Trademark and Copyright Information Measurement Computing Corporation,

More information

Relays & Sockets. RSC Series. RSC Series Solid State Relays. Part Number Selection Specifications

Relays & Sockets. RSC Series. RSC Series Solid State Relays. Part Number Selection Specifications RSC Series RSC Series Solid State Relays Key features of the RSC series include: Slim design allows for DIN rail or panel mounting Built-in heat sink maximizes current output capability Epoxy-free design

More information

PC104-CTR10HD. User s Manual

PC104-CTR10HD. User s Manual PC104-CTR10HD User s Manual Revision 2 October, 2000 MEGA-FIFO, the CIO prefix to data acquisition board model numbers, the PCM prefix to data acquisition board model numbers, PCM-DAS08, PCM-D24C3, PCM-DAC02,

More information

PCI-DIO24H Digital I/O User's Guide

PCI-DIO24H Digital I/O User's Guide PCI-DIO24H Digital I/O User's Guide Document Revision 3A, May, 2009 Copyright 2009, Measurement Computing Corporation Trademark and Copyright Information Measurement Computing Corporation, InstaCal, Universal

More information

Amazing Electronic (HK) Limited Serial RS232/RS485 to analog signal converter

Amazing Electronic (HK) Limited Serial RS232/RS485 to analog signal converter DAM-DA D/A converter Datasheet Overview: DAM module is a new generation data acquisition and control system based on modular embedded systems. Adopting standard DIN35 rail mounting package is simple, flexible

More information

Signal Isolators & Conditioners

Signal Isolators & Conditioners RS485/232 to Analog Signal Converter Signal Isolators & Conditioners (D/A Converter,WJ31 series) Features: >> RS-485/232 interface, isolation convert standard analog signal output >> Analog signal output

More information

RTD Temperature acquisition converter WJ25

RTD Temperature acquisition converter WJ25 8-CH Thermocouple Signal to RS485/232 Acquisition Converter (WJ27 series 24Bits A/D Converter, data acquisition) Features: >> Eight channels thermocouple signal acquisition, isolated converter RS-485/232

More information

Model Number Structure

Model Number Structure Solid State Relays with Failure Detection Function G3PC Detects failures in SSR used for heater temperature control and simultaneously outputs alarm signal. This SSR supports the safe design of heater

More information

Signal Isolators & Conditioners

Signal Isolators & Conditioners WJ21 series Analog Signal to RS485/232 Converter (A/D Converter) Features: >> Analog signal acquisition, isolated RS-485/232 output >> 12-bit AD converter, testing accuracy>0.1% >> Can Program and calibrate

More information

CompactBlock Guard I/O EtherNet/IP Safety Modules

CompactBlock Guard I/O EtherNet/IP Safety Modules Installation Instructions CompactBlock Guard I/O EtherNet/IP Safety Modules Catalog Numbers 1791ES-IB8XOBV4, 1791ES-IB16 Topic Page Important User Information 2 North American Hazardous Location Approval

More information

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend Solid State Relays with Failure Detection Function G3PC Refer to Warranty and Application Considerations (page 1), Safety Precautions (page 4), and Technical and Safety Information (page 6). Detects failures

More information

The I-7530A RS-232/485/422 to CAN Converter

The I-7530A RS-232/485/422 to CAN Converter The I-7530A RS-232/485/422 to CAN Converter User s Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery

More information

8520/8520R. User Manual

8520/8520R. User Manual /R User Manual Warranty All products manufactured by SuperLogics are warranted against defective materials for a period of one year from the date of delivery to the original purchaser. Disclaimer SuperLogics

More information

Signal Isolators & Conditioners

Signal Isolators & Conditioners Analog Signal to RS485/232 Converter Signal Isolators & Conditioners (WJ21 series A/D Converter) Features: >> Analog signal acquisition, isolated RS-485/232 output >> 12-bit AD converter, testing accuracy>0.1%

More information

Produkt-Datenblatt. Technische Daten, Spezifikationen. MEsstechnik fängt mit ME an. Kontakt

Produkt-Datenblatt. Technische Daten, Spezifikationen. MEsstechnik fängt mit ME an.   Kontakt Produkt-Datenblatt Technische Daten, Spezifikationen Kontakt Technischer und kaufmännischer Vertrieb, Preisauskünfte, Angebote, Test-Geräte, Beratung vor Ort: Tel: (0 81 41) 52 71-0 FAX: (0 81 41) 52 71-129

More information

The I-7530A-MR Modbus RTU to CAN Converter

The I-7530A-MR Modbus RTU to CAN Converter The I-7530A-MR Modbus RTU to CAN Converter User s Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery

More information

USB-SSR08. USB-based Solid-State 8 I/O Module Interface Device. User's Guide. January Rev 6A Measurement Computing Corporation

USB-SSR08. USB-based Solid-State 8 I/O Module Interface Device. User's Guide. January Rev 6A Measurement Computing Corporation USB-SSR08 USB-based Solid-State 8 I/O Module Interface Device User's Guide January 2017. Rev 6A Measurement Computing Corporation Trademark and Copyright Information Measurement Computing Corporation,

More information

Programmable Relay ZEN V2 Units

Programmable Relay ZEN V2 Units Programmable Relay ZEN V2 Units Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to Warranty

More information

CIO-DIO48 Digital Input/Output Board User s Guide

CIO-DIO48 Digital Input/Output Board User s Guide CIO-DIO48 Digital Input/Output Board User s Guide Document Revision 1A, December, 2006 Copyright 2006, Measurement Computing Corporation Trademark and Copyright Information Measurement Computing Corporation,

More information

Brainboxes Ethernet to Digital IO

Brainboxes Ethernet to Digital IO Print Date: 06.05.2015 Brainboxes Ethernet to Digital IO Brainboxes Limited, 18 Hurricane Drive, Liverpool International Business Park, Speke, Liverpool, Merseyside, L24 8RL Tel: +44 (0)151 220 2500 Fax:

More information

NuDAM-6050 NuDAM-6052 NuDAM-6053 NuDAM-6054 NuDAM-6056 NuDAM-6058 NuDAM-6060 NuDAM-6063 Digital I/O Modules

NuDAM-6050 NuDAM-6052 NuDAM-6053 NuDAM-6054 NuDAM-6056 NuDAM-6058 NuDAM-6060 NuDAM-6063 Digital I/O Modules NuDAM-6050 NuDAM-6052 NuDAM-6053 NuDAM-6054 NuDAM-6056 NuDAM-6058 NuDAM-6060 NuDAM-6063 Digital I/O Modules Recycled Paper Copyright 1995~2001 ADLINK Technology Inc. All Rights Reserved. Manual Rev. 3.51:

More information

OMR-6021 Analog Output OMR Channel Analog Output

OMR-6021 Analog Output OMR Channel Analog Output OMR-6021 Analog Output OMR-6024 4-Channel Analog Output Contents 1. INTRODUCTION...1-1 1. 1. ABOUT THE OMR ANALOG OUTPUT MODULES 1-1 1. 2. OVERVIEW OF OMR-6021 1-1 1. 3. OVERVIEW OF OMR-6024 1-4 2. INITIALIZATION

More information

USB-201. Analog and Digital I/O. User's Guide. January Rev 7 Measurement Computing Corporation

USB-201. Analog and Digital I/O. User's Guide. January Rev 7 Measurement Computing Corporation USB-201 Analog and Digital I/O User's Guide January 2019. Rev 7 Measurement Computing Corporation Trademark and Copyright Information Measurement Computing Corporation, InstaCal, Universal Library, and

More information

Features and Benefits. Certifications

Features and Benefits. Certifications iologik R1200 Series RS-485 remote I/O Features and Benefits Dual RS-485 remote I/O with built-in repeater Supports the installation of multidrop communications parameters Install communications parameters

More information

PCD3.C90. Date Modification Asked by: Version E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1

PCD3.C90. Date Modification Asked by: Version E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1 Manual PCD3.C90 Revision History Date Modification Asked by: Version 14.09.09 E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1 22.09.09 Added E/A Bus Connector PCD3.K116 Müller.R 1.2 06.01.10

More information

User's Guide. PCI-DAS08

User's Guide.    PCI-DAS08 User's Guide http://www.omega.com e-mail: info@omega.com PCI-DAS8 TABLE OF CONTENTS. INTRODUCTION.... INSTALLATION.... HARDWARE INSTALLATION.... SOFTWARE INSTALLATION, WINDOWS 9, 98 & NT..... INTRODUCTION.....

More information

93 SERIES. Timed socket for 34 series 93.68/93.69

93 SERIES. Timed socket for 34 series 93.68/93.69 93 93 Slim timed sockets for 34 series, 6.2 mm wide Timer adjustment via top mounted rotary knob accessible after assembly Control signal terminal DIP-switch for selection of 4 time scales and 8 functions

More information

02/11/2015

02/11/2015 DIN Rail Mount 22.5 mm TU2R1 Part number 88865305 Product with 1 relays (88 865 100/103/105/115/125/135/145/155/185/503) : Replaced by the 17,5 mm range For instance : previous part number 88 865 XXX /

More information

Brainboxes Ethernet to Digital IO

Brainboxes Ethernet to Digital IO Print Date: 09.03.18 Brainboxes Ethernet to Digital IO Brainboxes Limited, 18 Hurricane Drive, Liverpool International Business Park, Speke, Liverpool, Merseyside, L24 8RL Tel: +44 (0)151 220 2500 Fax:

More information

USB-2001-TC. USB-based Thermocouple Input. User's Guide

USB-2001-TC. USB-based Thermocouple Input. User's Guide USB-2001-TC USB-based Thermocouple Input User's Guide Document Revision 6A November 2014 Copyright 2014 Trademark and Copyright Information Measurement Computing Corporation, InstaCal, Universal Library,

More information

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O Characteristics star-delta timing relay - 230VAC/440VAC - 1 C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts type

More information

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide Warnings and legal information Installation and terminals Communication I/O options Alarming Utility software More information Specifications

More information

PC-CARD-DAC08. User s Manual

PC-CARD-DAC08. User s Manual PC-CARD-DAC8 Analog Outputs & Digital I/O User s Manual Revision March, 2 (C) Copyright 2, Measurement Computing Corporation MEGA-FIFO, the CIO prefix to data acquisition board model numbers, the PCM prefix

More information

Manual 601: : USB/RS232. Specifications. Contents. Options

Manual 601: : USB/RS232. Specifications. Contents. Options Page 1 ATE-601 601: : USB/RS232 I/O Controller - 8 Inputs, 4/8 Relays The ATE-500/600 series is a range of modular I/O controllers. It uses small standardized boards which allows you to configure the system

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules 39 SERIES Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention

More information

WLS-TC Specifications

WLS-TC Specifications Specifications Document Revision 1.0, February, 2010 Copyright 2010, Measurement Computing Corporation Typical for 25 C unless otherwise specified. Specifications in italic text are guaranteed by design.

More information

Model Number Structure

Model Number Structure Solid State Relays with Failure Detection Function G3PC CSM_G3PC_DS_E_1_1 Refer to Safety Precautions for All Solid State Relays. Detects failures in SSR used for heater temperature control and simultaneously

More information

GFK-2415A March Type of sensor connection

GFK-2415A March Type of sensor connection VersaMax IP Expansion Module has four analog differential inputs that can be configured as current or voltage inputs. It connects to a local bus that is interfaced to a Profibus-DP / PROFINET network by

More information

Safety Standards. Model Number:

Safety Standards. Model Number: 090AAS15 F/B Highlights & Features Meet Efficiency Level VI Safety Approvals to IEC 60601-1 3.1rd ed. & IEC 60950-1 Compliant with IEC 60601-1-2 4th Ed. Requirements Low touch current (

More information

NuDAM-6011/ NuDAM-6014D NuDAM-6012/D NuDAM-6017 NuDAM-6013/ NuDAM-6018 Analog Input Modules User s Guide

NuDAM-6011/ NuDAM-6014D NuDAM-6012/D NuDAM-6017 NuDAM-6013/ NuDAM-6018 Analog Input Modules User s Guide NuDAM-6011/ NuDAM-6014D NuDAM-6012/D NuDAM-6017 NuDAM-6013/ NuDAM-6018 Analog Input Modules User s Guide Copyright 1996~2001 ADLINK Technology Inc. All Rights Reserved. Manual Rev. 5.15: October 2, 2001

More information

Warranty. Warning. Copyright. Contact Us

Warranty. Warning. Copyright. Contact Us M-6026U-32 16-channel Universal Input and 16-channel Universal Output Version: 1.0.0 Date: Dec. 2017 Edited by Horse Chien M-6026U-32 User Manual Version 1.0.0 Dec. 2017-1 - Warranty All products manufactured

More information

08/07/2015

08/07/2015 DIN Rail Mount 22.5 mm TUR1 Part number 88865105 Product with 1 relays (88 865 100/103/105/115/125/135/145/155/185/503) : Replaced by the 17,5 mm range For instance : previous part number 88 865 XXX /

More information

ICP DAS. ICP DAS 2015 M2M WLAN Wireless Solutions

ICP DAS. ICP DAS 2015 M2M WLAN Wireless Solutions ICP DAS 2015 M2M WLAN Wireless Solutions Industrial Computer Industrial Product Data Computer Acquisition Product System Data Acquisition System PAC WLAN Wireless Solutions Wi-Fi Products WLAN Converter

More information

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide Warnings and legal information Installation and terminals Communication I/O options Alarming Utility software More information Specifications

More information

USB-PDISO8 Specifications

USB-PDISO8 Specifications USB-PDISO8 Specifications Document Revision 1.2, February, 2010 Copyright 2010, Measurement Computing Corporation Typical for 25 C unless otherwise specified. Specifications in italic text are guaranteed

More information

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

RM35JA32MR Current control relay 0.15A 15A, 2 C/O Characteristics Current control relay 0.15A 15A, 2 C/O Main Range of product Product or component type Relay type Relay name Relay monitored parameters Time delay type Switching capacity in VA Measurement

More information

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current. Encoder supply. Output current Data sheet *** SPARE PART*** SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 50 KB General

More information

iologik R1200 Series User s Manual

iologik R1200 Series User s Manual User s Manual First Edition, April 2013 www.moxa.com/product 2013 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used

More information

BARIX IO12. I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL. Version: 2.

BARIX IO12. I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL. Version: 2. BARIX IO12 I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL Version: 2.01 Date: 06/03/2014 For Firmware Version 10 Table of Contents

More information

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current Datasheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 75 KB General information Engineering

More information

iothinx 4500 Series (45MR) Modules

iothinx 4500 Series (45MR) Modules iothinx 4500 Series (45MR) Modules Modules for iothinx 4500 Series Feature and Benefits Easy tool-free installation and removal Built-in LED indicators for IO channels Wide operating temperature range:

More information

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory Datasheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 75 KB Display with display Supply

More information

Energy Management Modular Energy meters Type EM2-96

Energy Management Modular Energy meters Type EM2-96 Energy Management Modular Energy meters Type EM2-96 Product Description µp-based modular energy meter with a built-in configuration key-pad. The energies are both partial and total counted. The housing

More information

USB-1024LS. 24-bit Digital I/O Low-speed USB 2.0 device. User s Guide

USB-1024LS. 24-bit Digital I/O Low-speed USB 2.0 device. User s Guide USB-1024LS 24-bit Digital I/O Low-speed USB 2.0 device User s Guide USB-1024LS USB-based Digital I/O Module User's Guide Document Revision 2A, May, 2006 Copyright 2006, Measurement Computing Corporation

More information

8430/8830/8KE4/8KE8 Ethernet I/O Unit User s Manual

8430/8830/8KE4/8KE8 Ethernet I/O Unit User s Manual 8430/8830/8KE4/8KE8 Ethernet I/O Unit User s Manual Version 1.0, January 2005 I-8430 I-8830 I-8KE4-G I-8KE8-G ICP DAS, Co., LTD www.icpdas.com 8430/8830/8KE4/8KE8 User s manual, Jan 2005, Version 1.0,

More information

General information. Display. Supply voltage. Input current

General information. Display. Supply voltage. Input current Datasheet SIMATIC S7-1200, CPU 1212C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 8 DI 24V DC; 6 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 50 KB General information Engineering

More information

XT-9100 Technical Bulletin

XT-9100 Technical Bulletin System 9100 Technical Manual 636.4 Technical Bulletins Section Technical Bulletin Issue Date 0896 XT-9100 Technical Bulletin XT-9100 Extension Module/XP-910x Expansion Modules Page 3 Introduction 3 SX

More information

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current. Encoder supply. Output current Data sheet SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC 20.4-28.8 V DC, PROGRAM/DATA MEMORY: 75 KB General information Engineering

More information

AI-EXP32. Analog Input Expansion Device for USB-2416 Series Devices. User's Guide

AI-EXP32. Analog Input Expansion Device for USB-2416 Series Devices. User's Guide AI-EXP32 Analog Input Expansion Device for USB-2416 Series Devices User's Guide Document Revision 4A September 2013 Copyright 2013 Trademark and Copyright Information Measurement Computing Corporation,

More information

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points) Remote I/O R1M Series THERMOCOUPLE & DC INPUT MODULE (16 points) MODEL MODEL & SUFFIX CODE SELECTION R1MGH2T MODEL Modbus protocol I/O TYPE GH2 : Thermocouple or DC input, 16 points FIELD TERMINAL TYPE

More information

Signal Isolators & Conditioners

Signal Isolators & Conditioners 4-ch DI 4-ch Relay Output, RS485/232 Remote Acquisition I/O (WJ70 Series) Features: >> Four switch input, four relay output >> Can read input level status via the RS-485/232 interface >> Can set output

More information

Safety Standards. Model Number:

Safety Standards. Model Number: 150AAS12 F/B Highlights & Features Meet DOE Level VI and ErP Lot 7 Safety Approvals to IEC 60601-1 3.1rd ed. & IEC 60950-1 Compliant with IEC 60601-1-2 4th Ed. Requirements Low touch current (

More information