1 IEC Power Control Devices Training Manual XT Training Module New Information March 08 Contents Description Page Overview Contactors Overload Relays (Bimetal) Starters Electronic Overload Relays Reversing Contactors Contactor Accessories Contactor Coils Manual Motor Protectors Combination Style Starters Overview This training module focuses on Eaton s newest line of IEC Power Control, called XT. The XT line consists of the following components: Contactors Overload Relays (Bimetal and Electronic) Starters Coils and Accessories Manual Motor Protectors Combination Style Controllers Power Control products consist of devices that are used to start, stop and protect motors. There are several types of power control devices that are used for various applications, see Table. Table. IEC Power Control Devices Description Cost Electrical Operations Reduced Voltage NEMA IEC Definite Purpose (DP) Soft starters or drives that gradually start and stop motors. Contactors and overload relays with a complete line of accessories and ratings. Large in size. Contactors, overload relays, and MMPs with a complete line of accessories and ratings. Small in size. Contactors and overload relays with a limited line of accessories and ratings. Small size. IEC Power Control devices are a very common choice because they provide a good balance of features, ratings, and performance, all at an economical price. IEC contactors are designed according to a global standard called International Electrotechnical Commission (IEC). This global standard enables power control and other devices to share a common base High to million Moderate to million Common Approvals UL, CSA UL, CSA Low. million UL, CE, CSA, KEMA, CCC, etc. Low 0 to 00 thousand UL, HACR Common Applications High inertia motors or fragile applications Motor control centers OEM machine control applications Heating, AC, and Refrigeration for design, ratings, and classification. Although IEC is a global system, each country has its own set of governing standards. For example, Underwriter s Laboratories (UL) is an organization that writes safety standards for electrical products in the U.S. In order for IEC contactors to be used in the U.S., they must also be tested and approved by UL. TR0000E

2 Training Manual Page Effective: March 08 IEC Power Control Devices Contactors Contactors are devices used to start and stop motors. They include a set of contacts that open and close when the coil is energized. When contacts close, power can flow to the motor enabling the motor to operate. Unlike a manual switch, contactors can be operated remotely. This means an operator can Table. Catalog Numbering System Contactors start a motor without opening the control panel by using pushbutton controls, or a PLC can operate the contactor. Table shows the catalog numbering system for XT contactors, and Table lists the IEC and UL ratings that are used when selecting the XT contactor. X T C E B 0 A As you can see, the B-frame and C-frame contactors include either a NO or a NC auxiliary contact. Auxiliary contacts will be discussed in a later section. XT Contactor B-Frame Series XT = XT Series CE = Contactor Size 000 = IEC AC- Amp Rating Frame B = B-Frame C = C-Frame D = D-Frame Coil Voltage A = V AC B = 0V AC C = 80V AC E = 8V AC T = V AC TD = V DC Aux. Contacts 00 = 0NO 0NC 0 = 0NO NC = NO 0NC Table. Contactor Selection, Frames B D IEC Ratings UL Ratings Aux. I e (A) I e = I th Maximum kw Maximum -Phase Motor Rating, UL/CSA Contacts (A) Ratings AC- AC- Frame B Frame C 8 8 Frame D AC- (60 C) Phase Motors 0 60 Hz -Phase hp Ratings -Phase hp Ratings / V 80/ 00V V 660/ 690V V 0V V 0V V 60V V / / / / / / -/ -/ -/ -/ -/ -/ -/ -/ -/ -/ / -/ NO NC NO NC NO NC NO NC NO NC NO NC NO NC Catalog Number Screw Terminals XTCE00B_ XTCE00B0_ XTCE009B_ XTCE009B0_ XTCE0B_ XTCE0B0_ XTCE0B_ XTCE0B0_ XTCE08C_ XTCE08C0_ XTCE0C_ XTCE0C0_ XTCE0C_ XTCE0C0_ XTCE00D00_ XTCE00D00_ XTCE06D00_ TR0000E

3 IEC Power Control Devices Training Manual Effective: March 08 Page Select an XT contactor for a hp, 60V motor with a NO auxiliary and a V AC Coil: What is the frame size for this contactor? The AB part number 0-C6D is rated for HP at 60V (UL) and 6 amps per AC- (IEC) and has a V AC coil and a NO aux. Cross reference this part number according to UL and then to IEC: UL: IEC: Overload Relays (Bimetal) Overload relays are devices that monitor the current going to the motor. If too much current is flowing to the motor, there could be a problem with the motor or the load it s pulling. Continued operation in this condition could damage the motor. Overload relays are designed to take a contactor offline in the event of an overcurrent situation. Overload relays are selected based on the desired ampere protection level for the motor. When selecting overload relays, it is important to be sure to match the overload frame size with the contactor frame size, so that the overload will mount correctly to the contactor. Overload relays have a current range that is set to the appropriate protection level by adjusting the dial on the face of the overload relay. It is best to select an overload that has a range where the desired full load current setting is in the middle to lower portion of the range if possible, especially if the exact full load current is unknown. This way, the end user will be able to adjust the overload relay per regulation. Overloads are selected based on the full load amp (FLA or FLC) and the service rating of the motor. If the service factor is less than., then the target amp setting is 0.9 times the FLA. If the service factor is. or greater, then the target amp setting is the FLA. Service factors of. are very common. For example, if a motor has an.6 FLA and a. service factor, the target amp setting would be.. Assuming the contactor used for this application is an XT B-frame, the overload selection would be part number XTOB0BC, which has an overload setting range of 9 amps. Tables and show the overload numbering system and the selection table. Table. Catalog Numbering System Overload Relay X T O B 0 B C Series XT = XT Series Coil Voltage C = Class A XT Overload Relay B-Frame OB = Bimetallic Overload Size 000 = Amp Size Frame B = B-Frame C = C-Frame D = D-Frame There are two types of overload relays, bimetallic and electronic. Bimetallic overloads have heaters that bend during an overcurrent situation to trigger a mechanism that changes the state of the auxiliary contacts. The contactor is wired in such a manner that it is taken offline if the overload trips. TR0000E

4 Training Manual Page Effective: March 08 IEC Power Control Devices Table. Overload Relay Selection, Frames B D Overload Releases, I r Frame B Direct Mount Frame C Direct Mount Frame D Direct Mount Contact Sequence A/ / Contact Configuration For Use with Contactor Amp Range A A A A A A A A A A 9 A A 8 A 8 A 8 A 8 A 8 A 8 A 8 A 8 A 8 A 8 A 8 A 8 A A 0 6A 0 6A 0 6A 0 6A 0 6A 6A Short-Circuit Protection (A) Fuse Maximum Circuit Coordinationnation, Coordi- Breaker gg/gl gg/gl CEC/NEC Fuse Catalog Number XTOBP6BC XTOBPBC XTOBP0BC XTOBP60BC XTOB00BC XTOBP6BC XTOBPBC XTOB00BC XTOB006BC XTOB0BC XTOB0BC XTOB06BC XTOBP6CC XTOBPCC XTOBP0CC XTOBP60CC XTOB00CC XTOBP6CC XTOBPCC XTOB00CC XTOB006CC XTOB0CC XTOB06CC XTOB0CC XTOB0CC XTOB0DC XTOB06DC XTOB0DC XTOB00DC XTOB0DC XTOB06DC Select a C-frame XT contactor for a hp, 60V motor with a NO auxiliary and a V AC Coil: Select an overload relay for the contactor selected previously for a desired amp setting of amps: TR0000E

5 IEC Power Control Devices Training Manual Effective: March 08 Page Starters A starter consists of a contactor assembled with an overload relay. Starters can be ordered as components and assembled in the Table 6. Catalog Numbering System Starters field or as a fully assembled device. Selecting a starter uses the same selection rules as for contactors and overload relays, but combined into a single part number. X T A E B 0 A 0 0 Table 6 shows the catalog number system for XT starters. Series XT = XT Series Overload Size 000 = Max. Amp Setting XT Starter AE = Contactor & Overload Size 000 = IEC AC- Amp Rating Frame B = B-Frame C = C-Frame D = D-Frame Coil Voltage A = V AC B = 0V AC C = 80V AC E = 8V AC T = V AC TD = V DC Aux. Contacts 00 = 0NO 0NC 0 = 0NO NC = NO 0NC Select an XT starter for a hp, 60V motor (Full Load Current = 0A) with a NO auxiliary and a V AC Coil: What is the frame size for this starter? Break down catalog part number XTAE009BA0 into its component part numbers: Contactor: Overload Relay: Pull these components from your inventory and assemble them together to make the starter. TR0000E

6 Training Manual Page 6 Effective: March 08 IEC Power Control Devices Table. Full Voltage Non-reversing -Pole Starters with Bimetallic Overload I e (A) Maximum kw Ratings AC- Maximum -Phase Motor Rating Auxiliary AC- AC- -Phase Motors 0 60 Hz -Phase hp Ratings -Phase hp Ratings Contacts Frame B Frame C / V / 00V V 660/ 690V V V V 0V V 60V V / / / / -/ -/ -/ -/ -/ -/ -/ -/ -/ -/ NO NC NO NC NO NC NO NC NO NC NO NC NO NC Catalog Number XTAE00B XTAE00B0 XTAE009B XTAE009B0 XTAE0B XTAE0B0 XTAE0B XTAE0B0 XTAE08C XTAE08C0 XTAE0C XTAE0C0 XTAE0C XTAE0C0 Table 8. XTOB and XTOT Overload Relay Suffix Motor Full Load Amperes Frame B Frame C Suffix Code P6 P P0 P60 00 P6 P P6 P P0 P60 00 P6 P For Use with Contactor Amp Range A A A A A A A A A A 9 A A 8 A 8 A 8 A 8 A 8 A 8 A 8 A 8 A 8 A 8 A 8 A 8 A A Overload Relay Catalog Number XTOBP6BC XTOBPBC XTOBP0BC XTOBP60BC XTOB00BC XTOBP6BC XTOBPBC XTOB00BC XTOB006BC XTOB0BC XTOB0BC XTOB06BC XTOBP6CC XTOBPCC XTOBP0CC XTOBP60CC XTOB00CC XTOBP6CC XTOBPCC XTOB00CC XTOB006CC XTOB0CC XTOB06CC XTOB0CC XTOB0CC TR0000E

7 IEC Power Control Devices Training Manual Effective: March 08 Page Electronic Overload Relays The XT line of IEC power control also has an electronic overload relay called the C96. Electronic overload relays serve the same purpose as bimetallic overload relays, but they use a circuit board to monitor current instead of a bimetal element. Electronic overloads have larger amp setting ranges than bimetals, generate less heat, and they also have excellent phase loss and phase imbalance protection. Tables 9 show the part numbering structure for the electronic overload relay, the electronic overload starter, the selection table for the direct mount electronic overload (XT Frames B D) and the selection table for stand-alone electronic overloads. As is true for the bimetal overloads, the overload is selected based on the desired amp setting and matching contactor frame size. Table 9. Catalog Numbering System Overload Relay (Electronic) C 9 6 A A P 0 S E L A X Device C96 = C96 Electronic Overload Relay Frame Size A = mm B = 6 mm C = mm Feature Set Reset = Standard A = Auto C96 Electronic Overload Relay Max. Amperes Current Rating Frame A ( mm) P0 = = = 008 = = 6. 0 = 9 Frame B (6 mm) 0 = = Frame C ( mm) 0 = 0 0 Stand-Alone Overload Relay Suffix AX = All Frame Sizes XT IEC Adapter Suffix Frame B XB = 0. 0.A 0..0A A.6 8A 6. A Frame C XC = 0. 0.A 0..0A A.6 8A 6. A Class SEL = Selectable Frame D XD = 6. A 9 A A Frame F G XF = A TR0000E

8 Training Manual Page 8 Effective: March 08 IEC Power Control Devices Table. Catalog Numbering System Starter (with Electronic Overload) X T A E B 0 A E 0 0 Series XT = XT Series Overload Size 000 = Max. Amp Setting AE = Contactor & Overload Size 000 = IEC AC- Amp Rating Frame B = B-Frame C = C-Frame D = D-Frame Coil Voltage A = V AC B = 0V AC C = 80V AC E = 8V AC T = V AC TD = V DC Aux. Contacts 00 = 0NO 0NC 0 = 0NO NC = NO 0NC Table. Electronic Overload Relay Selection (for XT Frames B C) FLA Suffix XT IEC Contactor Catalog Range Frame Size / Width Number (Amps) Standard Class Standard Class ///0 ///0 mm Overload Frame Size EP0 B / mm C96AAP0SELXB 0..0 E00 B / mm C96AA00SELXB E00 B / mm C96AA00SELXB.6 8 E008 B / mm C96AA008SELXB 6. E0 B / mm C96AA0SELXB EP0 E00 E00 E008 E0 C / mm C / mm C / mm C / mm C / mm C96AAP0SELXC C96AA00SELXC C96AA00SELXC C96AA008SELXC C96AA0SELXC Table. Electronic Overload Relay Selection (Stand-Alone) FLA Range (Amps) Standard Class ///0 Catalog Number mm Overload Frame Size C96AAP0SELAX 0..0 C96AA00SELAX C96AA00SELAX.6 8 C96AA008SELAX 6. C96AA0SELAX 9 C96AA0SELAX 6 mm Overload Frame Size C96BA0SELAX C96BASELAX Select an electronic overload for a stand-alone application for a motor with a full load current of amps: Select an XT starter (with an electronic overload) for a hp (60V) motor with a full load current of amps: List the components of the starter from the previous question: Contactor: Overload Relay: TR0000E

9 IEC Power Control Devices Training Manual Effective: March 08 Page 9 Reversing Contactors Reversing contactors enable motors to operate in a forward and reverse operation. They consist of two contactors that are interlocked together such that both contactors cannot be operated at the same time. Reversing contactors can be interlocked both mechanically (by using the mechanical interlock) and electrically (by using NC auxiliary contacts wired with the opposing coil from the opposing contactor). Table lists the mechanical interlocks by frame size. Table. Mechanical Interlock Selection for XT Frame B G For Use with XTCE00B XTCE0B, XTCF0B Pkg. Qty. Catalog Number XTCEXMLB XTCE08C XTCE0C XTCEXMLC XTCE00D XTCE06D XTCEXMLD XTAE080F XTCE0G XTCEXMLG The XT line also has wiring link kits that make wiring a reversing contactor much faster to install. The following table lists the reversing link kits for the XT. IMPORTANT NOTE: The reversing link kit for the B-frame contactors includes an electrical interlock wiring link for contactors that have a NC aux contact built in to the contactor. If the contactors you have chosen have a NO aux contact instead of a NC, do not use the electrical interlock wiring link, as this will cause both contactors to attempt to pull in and will result in chattering. Table shows the reversing link kits for XT. Table. Mechanical Interlock Selection for XT Frame B G For Use with Pkg. Qty. Catalog Number XTCE00B XTCE0B XTCEXRLB XTCE08C XTCE0C XTCEXRLC XTCE00D XTCE06D XTCEXRLD XTCE080F XTCE0G XTCEXRLG Select the mechanical interlock for the B-frame contactor: Select the reversing link kit for the B-frame contactor: Pull () B-frame contactors and the B-frame mechanical interlock from your inventory and use the instruction pub to assemble a reversing contactor. Using the reversing contactor built in the previous practice section, install the reversing B-frame reversing link kit using the instruction pub to finish assembly of the reversing contactor. TR0000E

10 Training Manual Page Effective: March 08 IEC Power Control Devices Contactor Accessories The XT line has a variety of accessories from auxiliary contacts to timers to plug-in surge suppressors. The most commonly used accessory is the auxiliary contact. An auxiliary contact is a device that assembles to the contactor either on the front (face) or the side of the contactor, and contains contacts that change state in concert with the power pole contacts inside the contactor. Auxiliary contacts can be used to turn on a pilot light, signal a PLC that the contactor is closed, or can be used for a variety of other types of control activities. The most common use for an auxiliary contact is to enable continued operation of a contactor without having an operator to continually push a start button. Auxiliary contacts come in a variety of combinations of normally open (NO) and normally closed (NC) contacts. This means that the contact in a NO aux contact is open when the contactor is not in operation. When the contact in the contactor closes, the NO auxiliary contact also closes. A NC auxiliary would remain closed unless the contacts in the contactor close. As is true with overload relays, accessories should be selected to match the contactor frame size. In some cases, there are other specifications, such as coil voltage, that must match the corresponding specification of the contactor. These accessory attributes can be found in the selection tables for the contactor accessories in the catalog. Table shows the general numbering scheme for just a few of the contactor accessories, but all accessories generally follow this same system. Table. Catalog Numbering System Contactor Accessories X T C E X M L B Series XT = XT Series CE = Contactor X = Accessory Frame B = B-Frame C = C-Frame D = D-Frame, etc. Accessory ML = Mechanical InterLock RL = Reversing Link VS = Varistor Surge Suppressor CLK = Common Link Kit ( contactors) SDB = Star-Delta Bridge PB = Paralleling Bridge etc. TR0000E

11 IEC Power Control Devices Training Manual Effective: March 08 Page Contactor Coils Contactor Coils The XT line of contactors includes coils with a variety of voltages for replacement or exchange purposes. Many distributors stock contactors with one common coil voltage and a variety of contactor coils with other coil voltages. This way, they can easily switch out coils if they get a request for a contactor of a different coil voltage. This helps minimize the total cost of inventory. Contactor coils are selected based on the frame size and the desired coil voltage. Table 6 lists the numbering scheme for the XT contactor coils. Coils are only available for C-frame contactors and larger. Table 6. Catalog Numbering System Contactor Coils X T C E R E N C O I L C T D Series XT = XT Series CE = Contactor REN = Renewal Part REN = Renewal Part Frame C = C-Frame D = D-Frame etc. Coil Voltage A = V AC B = 0V AC C = 80V AC D = 600V AC E = 8V AC T = V AC TD = V DC etc. All contactor frames can have replaceable coils except the B-frame. For about the same price as the coil, the entire B-frame contactor can be replaced. Select a replacement coil for a C-frame contactor that is rated for 80V AC: Pull the coil part selected in the previous question and a C-frame contactor from your inventory and practice switching out the coils. Use the instructions to assist you with the coil exchange. TR0000E

12 Training Manual Page Effective: March 08 IEC Power Control Devices Manual Motor Protectors MMP B-Frame Like contactors, Manual Motor Protectors (MMPs) are devices used to start and stop motors. They differ from contactors in that they can only be operated manually, not remotely like contactors. MMPs have overload protection (similar to the overload relay). They also have short circuit protection, similar to breakers. This means they are designed to interrupt high current in the event of a short circuit. In some countries, MMPs can be used in the same applications as breakers. The XT line of MMPs have two operator types: pushbutton style and rotary style. Tables and 8 show the numbering structure of the XT MMP. Table. Catalog Numbering System Overload Relay (Bimetal) X T P R 0 B C Series XT = XT Series Coil Voltage C = Class A PB = Pushbutton Style PR = Rotary Style Frame B = B-Frame D = D-Frame Size 000 = Amp Size MMPs are selected similarly to overload relays in that the FLA is multiplied by 0.9 for service factors less than. to determine the target amp setting and the FLA is the target amp setting for service factors equal to or larger than.. Even though MMPs have HP ratings, these ratings should only be used as a guide. The MMP cannot adequately protect a motor if the amp range is too large or too small for the motor. The following table lists the selection table for the B-frame XT rotary style MMPs: Table 8. Rotary MMP Selection for XT Frames B G (Bimetal) Rated Uninterrupted Current I u = I e (Amps) Frame B FLA Adjustment Range / Overload Release I r (Amps) Short Circuit Release I rm (Amps) Maximum Motor Ratings Maximum kw Rating AC- P (kw) -Phase 0V V V 00V V Maximum hp Rating P (hp) UL 08/CSA C. No. -Phase 0V 0V 80V 600V / -/ -/ / -/ -/ / / -/ -/ / -/ 0 Screw Terminals Catalog Number XTPRP6BC XTPRPBC XTPRP0BC XTPRP6BC XTPR00BC XTPRP6BC XTPRPBC XTPR00BC XTPR6PBC XTPR0BC XTPR0BC XTPR06BC XTPR0BC XTPR0BC XTPR0BC Select a manual motor protector for a -/ hp motor with a FLA of A and a service factor of.: TR0000E

13 IEC Power Control Devices Training Manual Effective: March 08 Page Combination Style Starters Combination style starters consist of a manual motor protector assembled with a contactor. This relatively new type of starter is growing in popularity because it can be used in place of a breaker/fuse block, contactor and overload relay. Combination style starters install more quickly and require less space that the traditional scheme. There are two types of combinations style controllers: one with a line side adapter and one without a line side adapter. The line side adapter increases the voltage creepage clearance on the line side of the combination style starters. The line side adapter is required for UL08 F combinations. Combination style starters are selected using the same rules as manual motor protectors. Tables 9 and show the numbering scheme and a portion of the selection table for the combination style controllers. Table 9. Catalog Numbering System Combination Style X T S C 0 0 B B A Series XT = XT Series SC = Combined Style FC = UL08 F Combination Motor Controllers Size 000 = Amp Size Coil Voltage A = V AC B = 0V AC C = 80V AC E = 8V AC T = V AC TD = V DC Contactor Frame B = B-Frame C = C-Frame D = D-Frame XT Combination Starter MMP Frame B = B-Frame C = C-Frame Table. Factory Assembled Motor Protective Device with Thermal and Magnetic Trip + Contactor FLA Adjustment Range / Overload Release I r (Amps) Select Manual Motor Protectors by full load amperes. Maximum Motor Ratings (kw, hp) are for reference only. For additional voltages not listed, see Table - on Page -8 of the Control Catalog. Short-Circuit Release I rm (Amps) Frame B MMP + Frame B Contactor Maximum Motor Ratings P Maximum Motor kw Rating AC- P (kw) Maximum hp Rating P (hp) Assembled Manual Motor Controller Three-Phase Three-Phase Non-reversing 0V V V V V 0V 80V 600V Catalog Number / / Using the above table, select a combination style controller for a hp motor (80V) with a. service factor, a FLA of 9 amps and a coil voltage of V AC: -/ -/ / / / / / / -/ -/ / / / / / -/ XTSCP6BB_ XTSCPBB_ XTSCP0BB_ XTSCP6BB_ XTSC00BB_ XTSCP6BB_ XTSCPBB_ XTSC00BB_ XTSC6PBB_ XTSC0BB_ XTSC0BB_ XTSC06BB_ TR0000E

14 Training Manual Page Effective: March 08 IEC Power Control Devices Combination style controllers can be either purchased as an assembled device, or can be built from stocked components. Table lists the components used in the assembly of the combination style starters for the B-frame. Table. Factory Assembled Motor Protective Device with Thermal and Magnetic Trip + Contactor Assembled Manual Motor Controller Non-reversing XTSC Frame B MMP + Frame B Contactor XTSCP6BB_ XTSCPBB_ XTSCP0BB_ XTSCP6BB_ XTSC00BB_ XTSCP6BB_ XTSCPBB_ XTSC00BB_ XTSC6PBB_ XTSC0BB_ XTSC0BB_ XTSC06BB_ FLA Adjustment Range / Overload Release I r (Amps) Component Catalog Numbers Manual Motor Protector XTPRP6BC XTPRPBC XTPRP0BC XTPRP6BC XTPR00BC XTPRP6BC XTPRPBC XTPR00BC XTPR6PBC XTPR0BC XTPR0BC XTPR06BC Combination Connection Kit Contactor XTCE00B_ XTCE00B_ XTCE00B_ XTCE00B_ XTCE00B_ XTCE00B_ XTCE00B_ XTCE00B_ XTCE00B_ XTCE009B_ XTCE0B_ XTCE0B_ Manual Motor Protector Auxiliary Contact XTPAXFA XTPAXFA XTPAXFA XTPAXFA XTPAXFA XTPAXFA XTPAXFA XTPAXFA XTPAXFA XTPAXFA XTPAXFA XTPAXFA Using the above table, list the components of the starter selected in the previous section: Pull these components from stock and use the instructions to build the assembled starter. TR0000E

15 IEC Power Control Devices Training Manual Effective: March 08 Page TR0000E

16 Eaton Corporation Electrical Group 00 Cherrington Parkway Moon Township, PA 8 United States 8-ETN CARE (8-86-) Eaton.com 08 Eaton Corporation All Rights Reserved Printed in USA Publication No. TR0000E/CPG March 08

XT IEC Power Control Contactors, Starters and Overload Relays

XT IEC Power Control Contactors, Starters and Overload Relays May 00 Product Family Overview 9 Contents Features and Benefits Description Page Contactors and Starters Catalog Number Selection................. Non-reversing Contactors.... Reversing Contactors........

More information

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control . Contents Description Relays and Timers......................... Miniature Controls......................... Contactors and Starters.................... Thermal Overload Relays.................... C440/XT

More information

IMS Control & EPR, We keep your motors running ABB s new control & protection devices up to 18.5 kw / 20 hp

IMS Control & EPR, We keep your motors running ABB s new control & protection devices up to 18.5 kw / 20 hp IMS Control & EPR, 2010 01 29 We keep your motors running ABB s new control & protection devices up to 18.5 kw / 20 hp October 27, 2010 1SBC101089D0201 ABB s new control and protection devices Up to 18.5

More information

Large Frame IEC Contactors

Large Frame IEC Contactors Large Frame IEC Contactors Bulletin 100-E PUBLIC Copyright 2017 Rockwell Automation, Inc. All Rights Reserved. 1 Changing Applications for Contactors There are fewer and fewer traditional large motor starting

More information

Allen-Bradley Bulletin 100 Contactors

Allen-Bradley Bulletin 100 Contactors Allen-Bradley Bulletin 100 Contactors An integrated portfolio of IEC Contactors that save panel-space and energy Features and Benefits: Direct-on-line and reversing contactors Built-in surge suppression

More information

IEC Contactors & Starters XT IEC Power Control

IEC Contactors & Starters XT IEC Power Control -49 Accessories Auxiliary Contacts Front mounted snap-on auxiliary contacts for XT contactors are available with screw or spring cage terminals in a variety of contact configurations. Notes: The 7 32A

More information

Controls Enclosed Non-Combination Starters - PESW Series

Controls Enclosed Non-Combination Starters - PESW Series NEMA 4/4X Non Metallic Enclosure Product Features WEG offers non-reversing and non-combination NEMA-4X magnetic starter up to 75HP at 460V. Featuring components that meet IEC design standards and UL horsepower

More information

Mini Contactors & Overloads

Mini Contactors & Overloads 108 Mini s & Overloads GMC-12M Surface or DIN rail mountable UL508 compliant 1/ to 7-1/ 50/60Hz AC and DC versions available Direct-mounting overloads RoHS compliant Auxiliary contacts standard (1 N.0.)

More information

CS7 Industrial Control Relays

CS7 Industrial Control Relays CS7 Industrial Control Relays Reliable, general purpose relays for heavy duty applications The base four pole CS7 relay can be expanded up to twelve poles with the addition of front and side mount auxiliaries

More information

3RA13, 3RA14 Contactor Assemblies

3RA13, 3RA14 Contactor Assemblies RA1, RA Contactor Assemblies RA1 complete units,... kw Overview The RA1 reversing contactor assemblies can be ordered as follows: Sizes S00 to S Fully wired and tested, with mechanical and electrical interlock

More information

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series POWER & ACTUATION OVERLOAD RELAYS series Need reliable, accurate overload and phase-loss protection for your motors? c3controls Series Bimetallic Overload Relays provide unmatched protection and can be

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Product Application AP01102005E WMZT WMZS Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers two types of miniature circuit breakers for use in North

More information

29 $ Manual Motor Starters FREESHIPPING. MOTOR CONTROLS 25. Features: MMS-32H Frame. MMS-63H Frame.

29 $ Manual Motor Starters FREESHIPPING.  MOTOR CONTROLS 25. Features: MMS-32H Frame. MMS-63H Frame. www.factorymation.com/motorcontrols MOTOR CONTROLS 25 Manual Motor Starters High interrupt capacity Din rail and surface mounting Lockable handle (OFF position) IP20 finger safe terminals Class 10 thermal

More information

IEC Contactors. Auxiliary Contact Blocks GENERAL

IEC Contactors. Auxiliary Contact Blocks GENERAL IEC Contactors Auxiliary Contact Blocks GENERAL Description 3RH19 Auxiliary contact blocks The 3RH19 auxiliary contact blocks are available in 1, 2, 3 and 4-pole front mount versions and 2-pole side mount

More information

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Thermal Overload Relays. XT IEC Power Control

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Thermal Overload Relays. XT IEC Power Control . IEC ors and Starters XTOB, XTOT Overload Relays Contents Description Relays and Timers......................... Miniature Controls......................... ors and Starters.................... Thermal

More information

Series CA7 Contactors

Series CA7 Contactors Series Rugged, space saving and modular Sprecher + Schuh s newest contactor for applications up to 6HP Over years of design experience has produced Sprecher + Schuh s seventh generation contactor line.

More information

UL 508A Industrial Control Panels Eaton. All Rights Reserved.

UL 508A Industrial Control Panels Eaton. All Rights Reserved. UL 508A Industrial Control Panels Objectives Who is UL? UL508A Origin Current emphasis on UL508A What is the UL 508A Standard? Implementation of the Standard Component Selection Short Circuit Current Ratings

More information

Cert.Record No _C_000, Class No , DQD No 548 Rev

Cert.Record No _C_000, Class No , DQD No 548 Rev Page 1 of 7 CERTIFICATION RECORD The company named below has been authorized by CSA International to represent the products listed in this record as CSA Certified and to affix the CSA Mark to these products

More information

Miniature Circuit Breakers and Supplementary Protectors. Contents

Miniature Circuit Breakers and Supplementary Protectors. Contents . Optimum and Efficient Protection for Every Application Product Overview Features Optimum product quality, tested reliability and safety stand for best protection of personnel, installations and plant.

More information

Power Control. Drives & Soft Starters Soft starters Variable Speed Drives

Power Control. Drives & Soft Starters Soft starters Variable Speed Drives Motor Control... 223-267 XT/Xstart EC Motor Control... 224 XT/Xstart EC Mini Contactors... 226 XT/Xstart EC Contactors... 228 Overload Relays... 234 EC Manual Motor Protectors... 243 Electronic Motor-protective

More information

Protection Equipment

Protection Equipment Protection Equipment Price groups 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J, 143, 401 /2 Introduction Motor starter protectors/ circuit breakers SIRIUS 3RV2 motor starter protectors up to 40 A / General data

More information

Enclosed Non-Reversing Combination Controller, AC Operation - Type 1/12K/IP66 ➏➐. Non-Metallic Type 1/12K/IP66 Enclosure (KS7-C0C4R)

Enclosed Non-Reversing Combination Controller, AC Operation - Type 1/12K/IP66 ➏➐. Non-Metallic Type 1/12K/IP66 Enclosure (KS7-C0C4R) KWIKstarter/CX7 CX7 Non-Reversing Combination Controller, AC Enclosed Non-Reversing Combination Controller, AC Operation - Type 1/12K/IP66 ➏➐ Catalog Number ➍➏➑➒ ~ ~ ~ ~ 0.10 0.16 2.1 1 CX7-9-10- -AS0.16A-A10-PG

More information

K-Line Mini - Contactors, Overload Relays and Accessories

K-Line Mini - Contactors, Overload Relays and Accessories K-Line Mini - Contactors, Overload Relays and Accessories Class 8502 CONTENTS Description...................................................... Page General Information...............................................

More information

TeSys IEC Contactors and Overload Relays

TeSys IEC Contactors and Overload Relays TeSys IEC Contactors and Overload Relays Making High-Fault Short-Circuit Current Ratings Simple Schneider Electric is an industry leader in IEC contactors and overload relays, and is recognized as the

More information

Intelligent Technologies (IT.) Starter Network Adapter Products (SNAP) Product Focus D77B-DSNAP D77B-QSNAP

Intelligent Technologies (IT.) Starter Network Adapter Products (SNAP) Product Focus D77B-DSNAP D77B-QSNAP Intelligent Technologies (IT.) Starter Network Adapter Products (SNAP) Product Focus D77B-DSNAP D77B-QSNAP Extending the Communication Capabilities of Electromechanical Starters and Soft Starters 0 1 2

More information

UL 489 DIN rail branch circuit breakers

UL 489 DIN rail branch circuit breakers UL 9 DI rail branch circuit breakers FAZ-A circuit breakers Product Overview UL 9 DI rail branch circuit breakers FAZ-A circuit breakers PRODUCT OVERVIEW Optimum and efficient protection Optimum product

More information

WMS SUPPLEMENTARY PROTECTORS

WMS SUPPLEMENTARY PROTECTORS WMS Supplementary Protectors Overview WMS SUPPLEMENTARY PROTECTORS Product Specification The WMS Supplementary Protector is a dual-rated product for both AC and DC supplies, in accordance with UL 1077

More information

low voltage GLOBAL CATALOGUE RANGE Motor Control Contactors - Thermal Overload Relay s - Manual Motor Starters

low voltage GLOBAL CATALOGUE RANGE Motor Control Contactors - Thermal Overload Relay s - Manual Motor Starters CTLOGUE GLOBL RNGE 2. Motor Control Contactors - Thermal Overload Relay s - Manual Motor Starters 2. 2. Product Overview. 2.2 Overload Relay Setting Range 2. - 2.8 Product Specifications 2.9-2. Contactor

More information

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD United States MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD Product Information Features and Specifications For Use With: OEM Panels Approvals: UL

More information

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview Supplementary Protectors / Miniature Circuit Breakers Page System overview 10/003 10/001 Supplementary protectors

More information

Table of Specifications

Table of Specifications Table of Specifications Midi-Contactors 3-Pole Magnetic Contactors Terminal type CC9 CC12 CC18 CC22 CC32 CC40 Screw Only Screw Only GUA1, GUA2, GUA4 GUA-1 GUA-2, GUA-4 GUA-1 GUA-2, GUA-4 GT Type Thermal

More information

CS7 Industrial Control Relays

CS7 Industrial Control Relays CS7 Industrial Control Relays Reliable, general purpose relays for heavy duty applications The base four pole CS7 relay can be expanded up to twelve poles with the addition of front and side mount auxiliaries

More information

Enclosed Non-Reversing Combination Controller, AC Operation - Type 1/12K/IP66 ➏➐ (KS7-C0C4R) Discount Schedule F-1

Enclosed Non-Reversing Combination Controller, AC Operation - Type 1/12K/IP66 ➏➐ (KS7-C0C4R) Discount Schedule F-1 KWIKstarter/CX7 CX7 Non-Reversing Combination Controller, AC Enclosed Non-Reversing Combination Controller, AC Operation - Type 1/12K/IP66 ➏➐ ~ ~ ~ ~ 0.10 0.16 2.1 1 CX7-9-10- -AS0.16A-A10-PG 551 Q4 ~

More information

60103 Circuit Breaker

60103 Circuit Breaker 6003 Circuit Breaker United States MINIATURE CIRCUIT BREAKER, 20/240VAC, 2A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Circuit Breaker Type: Standard

More information

Motor protection relays

Motor protection relays Thermal overload relays for currents between 0.09 and 420A Electronic thermal overload relays for currents between 0.4 and A Electronic thermal overload relays with selectable tripping class: 5--20-30

More information

CS8 Industrial Control Relays

CS8 Industrial Control Relays CS8 Industrial Control Relays Despite increasing complexity, control systems and installations must become increasingly compact. And the CS8 Miniature Relay System packs maximum performance into minimum

More information

Selection Guide. Control Circuit and Load Protection. Allen-Bradley 1489-M2C020

Selection Guide. Control Circuit and Load Protection. Allen-Bradley 1489-M2C020 Selection Guide Control Circuit and Load Protection Circuit Protection Portfolio 1489-M Circuit Breakers Approved for branch circuit protection in the United States and Canada, and certified as Miniature

More information

1 Installation of accessories in molded case switches requires dummy trip; see page. Breaker/Switch Type TQD/TJD

1 Installation of accessories in molded case switches requires dummy trip; see page. Breaker/Switch Type TQD/TJD Molded Case Circuit Section Tri-Break Line Integrally Fused Thermal Magnetic Circuit Integrally Fused Magnetic Circuit Integrally Fused Molded Case Switches These breakers are available in three types.

More information

78 Series Electromechanical Relay Selection Guide

78 Series Electromechanical Relay Selection Guide 78 Series Electromechanical Relay Selection Guide Specification 781 Series 782 Series 783 Series 784 Series Coil Voltages Configuration SPDT DPDT 3PDT 4PDT Contact Rating 15A 15A 15A 15A Base Socket 5

More information

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA Delivery program Contactor relay, 3N/O+1N/C, DC current Part no. DILA-31(24VDC) Catalog No. 276379 Eaton Catalog No. XTRE10B31TD EL-Nummer 4130206 (Norway) Product range DILA relays Application Contactor

More information

BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS

BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS Safety Controller Suitable for use with Coded-Magnet Sensor Part Numbers below BNS250... BNS33... BNS303...

More information

Contactors and Contactor Assemblies

Contactors and Contactor Assemblies SIRIUS Contactors and Contactor Assemblies Application WYE-delta starting can only be used either if the motor normally operates in a d (delta) connection or starts softly or if the load torque during

More information

3RT, 3TB, 3TF Contactors for Switching Motors

3RT, 3TB, 3TF Contactors for Switching Motors RT, TB, TF Contactors for Switching Motors Overview RT contactors and coupling relays Size S00 with mountable accessories The SIRIUS generation of controls is a complete, modular system family, logically

More information

Applying branch circuit breakers and supplementary protectors in North America

Applying branch circuit breakers and supplementary protectors in North America Supersedes June 2017 FAZ-NA-L FAZ-NA FAZ Applying branch circuit breakers and supplementary protectors in North America Introduction Eaton offers three types of miniature circuit breakers for use in North

More information

onlinecomponents.com

onlinecomponents.com ccessories Field Installable Top (Front) Mount uxiliary Contact Blocks ➊ Contact Block NO NC Top mount auxiliary contact blocks snap-on to the top (front) of any contactor 4-pole auxiliary 2-pole auxiliary

More information

Revolutionizing control wiring

Revolutionizing control wiring SmartWire-DT Panel Wiring Solutions Revolutionizing control wiring 797-6925 Fax: (215) 221-1201 www.royalelectric.com SmartWire-DT Changing the way panels are wired. Reduce cost throughout the value chain.

More information

Sentron 3VT circuit breakers Simply Smart: First choice for power distribution

Sentron 3VT circuit breakers Simply Smart: First choice for power distribution s Sentron 3VT circuit breakers Simply Smart: First choice for power distribution www.siemens.com/industry Sentron 3VT Molded Case Circuit-Breakers - 10-1600Amperes With the standard line of 3VT molded-case

More information

MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors

MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors B Curve NC100H Supplementary Protectors Rating 1P 2P 3P 4P 80 MG27164 MG27175 MG27186 MG27197 MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors C Curve NC100H Supplementary Protectors

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable options

More information

Jockey Pump Controllers

Jockey Pump Controllers BR081001EN Microprocessor Based with Color Touchscreen Product Description ACROSS THE LINE Controllers operate across-the-line. Full voltage is applied to the motor for starting by the use of a single

More information

C E R T I F I C A T E O F C O M P L I A N C E

C E R T I F I C A T E O F C O M P L I A N C E Issued to: This is to certify that representative samples of SIEMENS AG DF CP R&D VC 2 WERNER-VON-SIEMENS-STRASSE 48 92224 AMBERG, GERMANY MOTOR CONTROLLERS, MANUAL (See following page for additional information.)

More information

UL 489 DIN Rail Miniature Circuit Breakers

UL 489 DIN Rail Miniature Circuit Breakers UL 9 DIN Rail Miniature Circuit Breakers Product Overview................................................ Product Selection................................................ Accessories.....................................................

More information

Jockey Pump Controllers

Jockey Pump Controllers BR081001EN Microprocessor Based with Color Touchscreen Product Description ACROSS THE LINE Controllers operate across-the-line. Full voltage is applied to the motor for starting by the use of a single

More information

Contactors and Contactor Assemblies

Contactors and Contactor Assemblies Contactor Industrial Controls Product Catalog 07 Section c o n t e n t s Section Overview / - /5 Product Overview /6 - /7 Contactors 3RT0, 3-pole to 95 /8 3RT0, 3-pole to 500 /9 3RT, 3-pole Vacuum to 500

More information

Contactors and Contactor Assemblies

Contactors and Contactor Assemblies RT contactors, size S00 The product range at a glance The new generation is a complete, modular system family, logically designed right down to the last detail, from the basic units to the accessories.

More information

1 Installation of accessories in molded case switches requires dummy trip; see page. Breaker/Switch Type TQD/TJD

1 Installation of accessories in molded case switches requires dummy trip; see page. Breaker/Switch Type TQD/TJD Molded Case Circuit Section Tri-Break Line Integrally Fused Thermal Magnetic Circuit Integrally Fused Magnetic Circuit Integrally Fused Molded Case Switches These breakers are available in three types.

More information

3 Pole Contactors with AC operating coils

3 Pole Contactors with AC operating coils 1 3 Pole Contactors with AC operating coils Characteristics General Characteristics Switching Current 9A ~ Rated insulation voltage (Ui) (Conforming to IEC 158-1) V 750 IEC 60947-4 V 1000 Conforming to

More information

Intelligent Technologies

Intelligent Technologies Intelligent Technologies QCPort Starter Network Adapter Product (QSNAP) Installation and User Manual Publication No. MN05001001E New Important Notice Please Read The product discussed in this literature

More information

Control Transformers Control transformers

Control Transformers Control transformers Control Transformers It is often desirable to operate the control circuit at a lower voltage than the power circuit. Control transformers are used to step a voltage down to a lower level. Siemens Class

More information

UL 489 DIN Rail Miniature Circuit Breakers

UL 489 DIN Rail Miniature Circuit Breakers UL 489 DIN Rail Miniature Circuit Breakers Product Overview................................................ 2 Product Selection................................................ 4 Accessories.....................................................

More information

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. MOTOR SYMBOLS. 2010, The McGraw-Hill Companies, Inc.

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. MOTOR SYMBOLS. 2010, The McGraw-Hill Companies, Inc. Chapter 2 MOTOR SYMBOLS 1 Symbols are used to represent the different components of a motor control system. Symbols sometimes look nothing like the real thing, so we have to learn what the symbols mean.

More information

Series CA7 Contactors

Series CA7 Contactors C7 Series C7 Rugged, space saving and modular Sprecher + Schuh s newest contactor for applications up to 6HP Over years of design experience has produced Sprecher + Schuh s seventh generation contactor

More information

NF44E-.. / NFZ44E-.. Contactor Relays AC / DC Operated - with Screw Terminals

NF44E-.. / NFZ44E-.. Contactor Relays AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC1010D0201 28/03/11 NFE-.. / NFZE-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits. NF(Z)

More information

194E FA 32 E P11 P11 6

194E FA 32 E P11 P11 6 Bulletin E IEC Load Switches, A Product Selection/Catalog Number Explanation Bulletin E Enclosed Disconnect Load Switches with R Handles (with Defeater, suitable for padlocks) E-FA Painted Steel Enclosure

More information

sirius Switching. Protecting. Starting. SIRIUS Product Overview

sirius Switching. Protecting. Starting. SIRIUS Product Overview sirius Switching. Protecting. Starting. SIRIUS Product Overview S00 Design Direct-on-line starting Reversing duty Assembly kit for busbar mounting 0 mm: RA9 -C 0 mm: RA9 -D Consisting of: wiring kit busbar

More information

Allen-Bradley Drives

Allen-Bradley Drives Overview/Product Selection Bulletin IEC Industrial Safety Relay Positively Guided/Mechanically Linked as Per IEC 947-5-1 Annex L Third Party Certification By SUVA Red Cover and Mechanically Linked Contact

More information

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated

More information

Solid-State Switching Devices

Solid-State Switching Devices Overview 3RF21 3RF20 3RF22 3RF23 SIRIUS 3RF2 solid-state switching devices Solid-state switching devices for resistive loads Solid-state relays Solid-state contactors Function modules Solid-state switching

More information

Click 'n' Go: SIRIUS Modular System SIRIUS. Highly flexible system-based switching, protecting and starting. Answers for industry.

Click 'n' Go: SIRIUS Modular System SIRIUS. Highly flexible system-based switching, protecting and starting. Answers for industry. Click 'n' Go: SIRIUS Modular System SIRIUS Highly flexible system-based switching, protecting and starting. Answers for industry. s Everything for the electrical cabinet: SIRIUS Modular System. Contents

More information

Control, Timing + Ice Cube Relays

Control, Timing + Ice Cube Relays ... 2 Technical Information... 14 CS8... 18 Technical Information... 21 RZ7-FS Electronic... 24 Technical Information... 34 RZ7-FE Electronic... 36 Technical Information... 42 Relpol Ice Cube Relays R2/R4

More information

Starters. Power. Manual Motor Low Voltage Starters 600, 609, 609U, 609TU. 600 Manual Starting Switches 609 Manual Starting Switches

Starters. Power. Manual Motor Low Voltage Starters 600, 609, 609U, 609TU. 600 Manual Starting Switches 609 Manual Starting Switches Starters Manual Motor Low Voltage Starters 600, 609, 609U, 609TU Compact design Undervoltage protection Manual operation with overload protection Ideal for low HP applications, up to 10 HP three phase

More information

Cutler-Hammer. January 2001

Cutler-Hammer. January 2001 Cutler-Hammer January 0 Vol.,Ref. 2-2 Product Line Overview January 0 Vol., Ref. No. [068] 2 Product Line Description Cutler-Hammer Molded Case Circuit s are designed to provide circuit protection for

More information

Mini contactors. K 3-pole contactors for motor control, 6 and 9 A Utilisation category AC-3 Control circuit : a.c. a.c. control contactors (1)

Mini contactors. K 3-pole contactors for motor control, 6 and 9 A Utilisation category AC-3 Control circuit : a.c. a.c. control contactors (1) K 3-pole contactors for motor control, 6 and 9 A Utilisation category AC-3 Control circuit : a.c. c LC-K060ii a.c. control contactors () Standard power ratings Rated Type of Instantaneous Basic reference.

More information

Cert.Record No _0_000, Class No , DQD No 557 Rev SUPPLEMENTARY PROTECTORS COMPONENT ACCEPTANCE PROGRAM

Cert.Record No _0_000, Class No , DQD No 557 Rev SUPPLEMENTARY PROTECTORS COMPONENT ACCEPTANCE PROGRAM Seite 1 von 6 ACCEPTANCE RECORD File No: Class No: 016186_0_000 321530 SUPPLEMENTARY PROTECTORS COMPONENT ACCEPTANCE PROGRAM SUBMITTOR 4544043 E-T-A Circuit Breakers Limited 100 Leek Cr, Unit 11 Richmond

More information

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog Issued February 2011 DATA SHEET 5SX2 MCB Based on Siemens Industrial Control Catalog General Data Trip characteristics Tripping characteristics acc. to EN 60 898 Tripping characteristic A, -5 Type A characteristic

More information

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays... .1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....

More information

Industrial Controls. Protection Devices. Gerätehandbuch. Answers for industry. Edition 09/2014

Industrial Controls. Protection Devices. Gerätehandbuch. Answers for industry. Edition 09/2014 Industrial Controls Protection Devices SIRIUS Innovations - Thermal Overload Relays SIRIUS 3RU2 / Solid-State Overload Relays SIRIUS 3RB3 Gerätehandbuch Manual Edition 09/2014 Answers for industry. SIRIUS

More information

Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A DATASHEET - PKZM4-25 Delivery program Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection Part no. PKZM4-25 Catalog No. 222352 Eaton Catalog No. XTPR025DC1NL EL-Nummer 0004355158 (Norway)

More information

3RM1 Hybrid Starters 6SIRIUS. contents. Industrial Controls Product Catalog 2017

3RM1 Hybrid Starters 6SIRIUS. contents. Industrial Controls Product Catalog 2017 3RM1 Hybrid Starters Industrial Controls Product Catalog 2017 Section contents 3RM1 Compact - Hybrid Starters Overview /2 General Data /3 Selection and ordering data /4 Accessories /5 - /9 Technical Data

More information

IEC Power Control Contactors and Contactor Assemblies

IEC Power Control Contactors and Contactor Assemblies IEC Power Control Contactors and Contactor ssemblies Contents Pages Contents Pages Section Overview......................... / - /5 Product Overview......................... /6 - /7 Contactors 3RT0 / 3RT0,

More information

Siemens AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE AMBERG, GERMANY

Siemens AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE AMBERG, GERMANY Issued to: Siemens AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE 48 92220 AMBERG, GERMANY This is to certify that Auxiliary Devices representative samples of 3UF70 followed by 0 or 1 followed by 0

More information

ELR W1/ 6-24DC. Extract from the online catalog. Order No.:

ELR W1/ 6-24DC. Extract from the online catalog. Order No.: Extract from the online catalog ELR W1/ 6-24DC Order No.: 2982090 Illustration shows item ELR W1/ 6-24DC Electronic reversing load relay, for driving DC motors, with light indicator and protection circuit,

More information

CurrentWatch Current Sensors. EGF Series Ground Fault Sensors. Ground Fault Sensors with Solid-State or Mechanical Relay Outputs.

CurrentWatch Current Sensors. EGF Series Ground Fault Sensors. Ground Fault Sensors with Solid-State or Mechanical Relay Outputs. CurrentWatch Current Sensors Ground Fault Sensors with Solid-State or Mechanical Relay s 1 Contents Overview.................... 1 Model Selection, Switches...... 2 Model Selection, Accessories... 3 Wiring

More information

TABLE OF CONTENTS Bulletin 700-HA General Purpose Relays and Timing Relays. Description Page Description Page. Description

TABLE OF CONTENTS Bulletin 700-HA General Purpose Relays and Timing Relays. Description Page Description Page. Description 9 Bulletin 700-HA Bulletin 700-HA 10 A Rating DPDT 3PDT Pin Style Terminals Standard ON/OFF Flag Indicator Finger Grips for Easy Installation and Removal Optional Manual Operator Optional Pilot Light Optional

More information

Contacts Contact Arrangement. 8-Pole Relay. 12-Pole Relay

Contacts Contact Arrangement. 8-Pole Relay. 12-Pole Relay Bulletin -P Heavy-Duty Industrial s Product Selection DC-Operated s Rail Mount DIN Rail Mount Cat. No. Cat. No. -Pole DC-P DC-PD DC-P DC-PD -Pole DC-P DC-PD DC-P DC-PD -Pole DC-P DC-PD DC-P DC-PD DC Coil

More information

SSW06. Soft Starters. Applications. Standard Features. Pumps Fans Blowers Compressors Crushers Saws Grinders Mixers.

SSW06. Soft Starters. Applications. Standard Features. Pumps Fans Blowers Compressors Crushers Saws Grinders Mixers. General Information CFW10 CFW100 CFW08 CFW500 CFW700 CFW701 CFW11 EDP11 CFW11M SSW05 SSW07 GPH2 TPH2 The is WEG s third generation Soft Starter line. The keypad, with dual display, has red LED digits which

More information

CI-tronic Soft start motor controller

CI-tronic Soft start motor controller MAKING MODERN LIVING POSSIBLE CI-tronic Soft start motor controller MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 40-3D and MCI 50-3 I-O Technical brochure Contents Page Soft start motor controller, MCI 3, MCI

More information

Product Description. Table of Contents

Product Description. Table of Contents Product Providing users with easy installation in mechanical fan and pump systems, the Allen-Bradley PowerFlex 400 AC drive offers a wide range of built-in features allowing for seamless building system

More information

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A POWER DISTRIBUTION JK Series Solid State Starters Medium Voltage 200-400-600-720A SOLID STATE STARTER JKSSS4+ Series The JKSSS Series of motor starter is the result of extensive research and development.

More information

Crane Control Contactors and Relays

Crane Control Contactors and Relays October 8 DC Relays Type KC Heavy-Duty Mill 75 Contact Conversion The fully visible contacts have NEMA ICS--5 heavy-duty interrupting ratings and are easily converted in the field using just a screwdriver

More information

Overload Relays. 3RB2 Solid-State Overload Relays. 3RB20, 3RB21 for standard applications. 5/48 Siemens LV Overview

Overload Relays. 3RB2 Solid-State Overload Relays. 3RB20, 3RB21 for standard applications. 5/48 Siemens LV Overview Overload Relays Siemens AG 2009 Overview 1 2 2 (1)Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors and soft starters, these connecting

More information

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5

More information

Learning Module 9: Miniature Circuit Breakers and Supplementary Protectors. 101 Basic Series

Learning Module 9: Miniature Circuit Breakers and Supplementary Protectors. 101 Basic Series Learning Module 9: Miniature Circuit Breakers and Supplementary Protectors 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Miniature Circuit Breakers

More information

UL 489 Cable-In / Cable-Out Branch Circuit Breaker

UL 489 Cable-In / Cable-Out Branch Circuit Breaker Product Overview UL 9 Cable-In / Cable-Out Branch Circuit Breaker PRODUCT OVERVIEW Optimum and Efficient Protection Features Complete range of UL 9 listed DIN rail mounted miniature circuit breakers up

More information

SSW06. Soft Starters.

SSW06. Soft Starters. The is WEG s third generation Soft Starter line. The keypad, with dual display, has red LED digits which provide visibility and make programming easier. Integral bypass contacts eliminate heat dissipation

More information

Product Guide. UL 489 DIN rail miniature circuit breakers

Product Guide. UL 489 DIN rail miniature circuit breakers Product Guide UL 489 DIN rail miniature circuit breakers UL 489 DIN rail miniature circuit breakers Product Overview................................................ 2 Product Selection WMZT 10 kaic at

More information

Motor Control Products Selection Guide

Motor Control Products Selection Guide MKING MODERN LIVING POSSIBLE Motor Control Products Selection Guide Contactors, Relays, and Circuit Breakers www.danfoss.com/ia c o n t e n t s Minicontactors CI 5 Thermal Overload Relays TI 9C for Minicontactors

More information

Switching, protecting, starting and monitoring with the highly flexible modular system usa.siemens.com/controls

Switching, protecting, starting and monitoring with the highly flexible modular system usa.siemens.com/controls SIRIUS Modular System. The perfect combination Switching, protecting, starting and monitoring with the highly flexible modular system usa.siemens.com/controls Everything for the control cabinet: the SIRIUS

More information

Micro Contactor MA Series

Micro Contactor MA Series Relay-sized contactor, making it the world s smallest >3mm contact clearance acc. to IEC 60335-1 for Safety Applications Reversing contactor with mechanical interlock 3 Pole and 1 Aux. Contact NO or NC

More information

SIRIUS modular system

SIRIUS modular system SIRIUS modular system Switching, protecting, starting and monitoring with the highly flexible modular system siemens.com/sirius Everything for the control cabinet: the SIRIUS modular system. Press shop

More information