M-6200A DIGITAL VOLTAGE REGULATOR CONTROL SUGGESTED SPECIFICATIONS
|
|
- Lesley Dawson
- 5 years ago
- Views:
Transcription
1 M-6200A DIGITAL VOLTAGE REGULATOR CONTROL SUGGESTED SPECIFICATIONS Pole-Top/Pad Mount Digital Voltage Regulator Control, for metering, monitoring, and operational control for step-voltage Regulators shall be provided by a microprocessor-based package. The microprocessor-based package shall be suitable for Pole Top Mounted or Pad Mounted single-phase voltage regulators, as well as Substation single-phase voltage regulators. The control shall have the following minimum functional and behavioral attributes: CONTROL FUNCTIONS The control shall include the following features and can be used for pole-mounted or padmounted single-phase voltage regulators as well as substation installations where SCADA communications are desired. Automatic/Manual Control: The Control shall have user-selectable control on the front panel for Automatic or Manual operation. In addition, it shall have an option for SCADA command to change the Auto/Manual control state remotely. Automatic/Manual Switch Status: The control shall provide indication of the Automatic/Manual Switch status via the communication ports. Voltage Limits, Tap Position Limits, and Runback: The control shall have Overvoltage and Undervoltage limits that are independently adjustable from 95 V to 135 V in 0.1 V increments. It shall have user-settable Upper and Lower tap position limits, with tap position knowledge active. There shall be an option for an adjustable deadband (above the overvoltage limit) of 1 V to 4 V to set the runback limit. Position Tracking: The control shall have a means of accurately tracking tap position information that can be integrated into an Integrated Volt VAr Management (IVVM) system. Operations Counter: The control shall have a pre-settable counter that records the number of raise and lower operations and increments based on the counter configuration, as set by the user. The counter shall be able to store up to operation counts without being affected by a loss of power supply. Resettable Operations Counter: The control shall have a second user-resettable software counter similar to the Operations Counter. Neutral Counter: The control shall have a pre-settable neutral counter that records the number of times the Neutral Input is energized. The counter shall be able to store up to operation counts without being affected by a loss of power supply. Bandcenter and Bandwidth: The control shall have an adjustable bandcenter range from 100 V to135 V in 0.1 V increments. The bandwidth shall have an adjustable bandwidth range from 1 V to 10 V in 0.1 V increments. Line Drop Compensation: The control shall have R and X compensation adjustable from 24 V to +24 V in 1 V increments. There shall also be an option for Z compensation with the voltage raise adjustment range from 0 V to +24 V, in increments of 1 V. Time-Delay: The control shall have a Definite Time-Delay function adjustable from 1 second to 360 seconds, in 1-second increments and Inverse Time-Delay adjustable from 1 second to 360 seconds, in 1-second increments. Inter-Tap Time-Delay: The control shall have an Inter-Tap Time-Delay to introduce time-delay between tap operations when control is in sequential mode. The time-delay range shall be adjustable from 0 to 60 seconds in 1 second increments and require input from an operation Page 1 of 9
2 counter or seal-in circuit validating the tap change operation actually occurred before allowing tap change operation to the next step. Selectable Outputs: The control shall provide user-selectable continuous or pulsed outputs. When the output selection is in continuous mode, an output (raise or lower) signal runs the tapchanger until the voltage moves within the band setting. When pulsed output is selected and initiated, the pulse will continue until it reaches the programmed pulse time-out or a counter contact or motor hold input operates. The pulse length is programmable from 0.2 to 12 seconds, in increments of 0.1 second. Reverse Power Operation: The control shall be able to detect a power flow reversal automatically and determine the direction of power flow, the LTC tap position, and the magnitude of the reverse power voltage to the regulator. The operational choices shall include Ignore (does not use power direction to make control decisions), Block (remain in present tap position and stop operating as a controller), Regulate-in-Reverse (use power reversal as the new source side voltage and change LTC tap position accordingly), and Run-to-Neutral (change LTC taps to the neutral position). CT to VT Phasing Correction: The control shall provide CT to VT phasing correction adjustable from 0 to +330 in 30 increments. VT Ratio Correction: The control shall provide a means of VT correction from 15 V to +15 V in 0.1 V increments Normalizing Voltage: The control shall offer an option for a Normalizing Voltage Multiplier with a range of 0.80 to 1.20 to be applied to Meter-Out Voltage. This shall be displayed in real-time as Normalizing Voltage to allow the user to overcome differences in the ratio of the PT that the Load Voltage input is using versus the PT the end user or other metering methods are using. Voltage Reduction: The control shall have three independent steps of voltage reduction, each adjustable from 0% to 10% in 0.1% increments of the bandcenter set point. The Voltage Reduction function shall be capable of operating from the front panel or through contact inputs and disabled locally or remotely. SCADA REMOTE MANUAL CONTROL MODE: SCADA Remote Manual Mode: The SCADA Remote Manual Mode shall allow the integrated volt-var control (IVVC) algorithm residing at the Master Control Center of the SCADA computer or other Host computer to operate from SCADA signals received through wired or wireless communications media to command Regulator RAISE or LOWER operations. The voltage regulator control shall maintain an Overvoltage and Undervoltage Limit supervision to protect the never to exceed voltages set as standard by the local Public Utilities Commission and SCADA shall be allowed to make RAISE and LOWER commands as necessary when operating within those safety limits. The voltage regulator control shall provide a means to switch from Remote Mode to Automatic Mode if communications fail and continue to operate autonomously until communications are restored. The control shall provide contingency responses upon extended loss of communications. SCADA Remote Manual Mode - SCADA Heartbeat: A SCADA Heartbeat Remote Mode shall be provided as a means for the SCADA system to place the unit in Remote Operation and perform RAISE and LOWER operations as directed by a central control source. This mode shall have a timer, and as long as the Remote Timer setting in the control is refreshed by the SCADA system writing a timer value to a DNP Analog Output point, the control shall remain in Remote Manual Operation. If the timer reaches zero, the control shall revert to Local Automatic Operation. The Local Automatic Operation shall switch back to Remote Manual Operation when SCADA writes a valid timer value to the DNP Analog Output point. Page 2 of 9
3 SCADA REMOTE MANAGEMENT OF LOCAL AUTOMATIC CONTROL MODE: SCADA Remote Management of Local Automatic Control Mode: The voltage regulator control shall have the capability to allow Remote SCADA Management of Local Automatic voltage regulator control. In this way, the Centralized Control can monitor voltage regulator controls allowing them to operate autonomously and only controlling them directly when emergency situations arise. Management via SCADA or other Host computer capable of operating through wired or wireless communications media allows SCADA to effect control by either changing the local automatic control settings via analog signal or, by sending binary commands for direct RAISE and LOWER operations. Sending analog settings to the control and letting it operate based on its new marching orders instead of directing each RAISE and LOWER command conserves bandwidth considerably and thereby minimizes the communications burden and total cost of operation. This mode shall employ a SCADA heartbeat feature as described in SCADA Remote Manual Mode to return the unit to operation using its programmed settings instead of those the SCADA system was controlling by. COMMUNICATIONS The communication ports shall provide access to all features, including metering, software updates, and programming of all functions. This shall be accomplished using a modem or direct serial connection from any PC-compatible personal computer running the control s Communications Software package or via SCADA communications software. Communications Ports: Communication ports shall be optionally available in the following forms: Ethernet 10/100 Mbps through a copper RJ-45 connection (100 Base-T) Ethernet 100Mbps Fiber Optic with ST connectors (100 Base-FX) Serial Ports with RS-485, ST or V-Pin Fiber Optics, or RS-232 Protocols: The control shall support the following standard protocols: DNP3.0 and MODBUS. The USB port shall utilize MODBUS for local interface communications. The Ethernet port supports DNP 3.0 and MODBUS. ADVANCED SCADA COMMUNICATIONS True Ethernet The control shall provide an integrated, true 10/100 Mbps Ethernet, auto negotiable, capable of supporting up to eight concurrent sessions and simultaneous multiple protocols with up to eight sockets (concurrent sessions) open at a time. The eight sockets shall be capable of supporting Modbus and DNP over TCP/IP and UDP with up to five of the eight sockets capable of supporting DNP 3.0. This requirement allows users simultaneous remote access to the control via the same physical Ethernet port to view/change settings or retrieve data, without affecting the SCADA communications. Full DNP Implementation The control shall provide full DNP implementation to support both report-by-exception and unsolicited reporting within DNP 3.0 to aid in the reduction of bandwidth requirements. The control shall also provide DNP File Transfer to permit the recovery of data logs and triggered events, oscillography, and device discovery to facilitate setting up the integrated system. The control shall support DNP security as defined in the DNP 3.0 standard. The control shall have DNP addressing capability that allows networking of multiple controls. The DNP implementation shall support the pre-defined global addresses within DNP 3.0 and allow the user to define two additional global addresses. Each control shall be able to be assigned a Device Address, Feeder Address, and Substation Address ranging from 1 to The control shall support broadcast commands from the master to all controls on the network in order to allow some or all controls to act on one command at the same time. This capability reduces bandwidth Page 3 of 9
4 and is critical for rapid response to changing system requirements with settings changes in multiple controls in selected zones. The control shall provide a configuration program that allows any point to be mapped into any DNP location and allows dummy filler points to be added to facilitate interoperability by replicating legacy vendor point-maps to SCADA. This program shall also allow for individual point dead-banding and individual point assignments into Class 1, 2, or 3. Cyber Security Within DNP, the control shall permit multiple master source-address authentications, sourceaddress validation, and multilevel access codes logged with date and time. It shall support Secure DNP authentication using FIPS Secure Hash Standard (SHA-1). The control shall be fully compliant and offer all settings and configuration as defined by the DNP3 user group and IEC The control shall have a 6-15 character password and an audit log that shows when someone is logged on the control and which password was used to gain access to the control, in compliance with NERC CIP standards. The control shall allow for storage of 30 unique passwords within each control and have an SD card slot to allow the use of a password-keyed SD card that the control automatically reads to allow user login. The control s design shall include the ability to disable ports and services not required for normal or emergency operations. In cases where disabling is not possible, the port or service shall be password and access level protected through a communication access security and timeout feature in the communication software. Bluetooth The control shall have an option for Bluetooth capability to enable wireless access to the control that allows the user to configure the control, read status and metering values, as well as change set points. A generic serial service shall be provided by the control s Bluetooth capability to facilitate establishing initial communications should the Bluetooth not automatically recognize listed services. The Bluetooth feature shall include a secure mode with the Bluetooth module undiscoverable without a user knowing the Bluetooth hardware address in the unit to meet NERC requirements for Bluetooth communications. MONITORING/METERING Harmonic Analysis: The control shall measure, log, and display individual harmonics including THD (total harmonics distortion) and the harmonic content of the load voltage and load current up to the 31 st harmonic. Oscillograph Recorder: The control shall have an oscillograph recording function that provides comprehensive data recording (voltage, current, and status input/output signals) for all monitored waveforms (at 16, 32 or 64 samples per cycle). The control shall have a means of downloading oscillograph data via the communications ports to any PC compatible personal computer running the included communications software program. The downloaded data shall be in a format that can be examined and printed. The waveform data shall also be available in COMTRADE file format. Tap Position Record: The control shall provide means of maintaining tap position information and a record of the number of times the moving contacts pass through each tap position. The tap position record is user resettable AUTO/OFF/MANUAL Switch Status: The control shall provide indication of the AUTO/OFF/MANUAL switch status through the communication ports. A or B Regulator Type: The control shall allow the user to select the type of regulator being used to provide a more accurate source voltage calculation. Page 4 of 9
5 User-Programmable Alarm/Self-Test Contact: The control shall have alarm capability to alert operator personnel to one or more of the following system conditions: Communications Block Invoked Block Lower Voltage Limit Exceeded Reverse Power Flow Condition Detected Tap Block Raise in Effect Self-test (Deadman) Abnormal Tap Position Block Raise Voltage Limit Exceeded Voltage Reduction (any step) Invoked Load Current Limit Exceeded Tap Block Lower in Effect LDC/LDZ Motor Seal-in Failure Real-Time Metering: The control shall meter the following measured and calculated values in real-time: Average Load Voltage Primary Voltage Tap Position Average Source Voltage Primary Current Drag Hands Control Load, kva or MVA Primary Watts Raise/Lower Timer Power Factor Load, Lead/Lag Primary Vars Intertap Timer Normalizing Voltage Primary VA Operation Control Average Load Current Frequency Resettable Counter Average Compensated Voltage Present Demand: The control shall provide a Present Demand feature that captures the maximum values during the specified time interval. The user-selectable time interval shall be 15, 30, or 60 minutes. Demand Load Voltage Primary Watts Primary VA Demand Primary Current Primary VArs Demand History (Drag Hands Operation): The control shall have the following drag-hand values stored with date and time stamping, averaged over 32 seconds: Min Local Voltage Max Local Voltage The control shall have capability to store the following drag-hand values with date and time stamping and calculated over the demand of the user-selectable time intervals of 15, 30, or 60 minutes: Max Primary Current (Amps) Max Primary Watts (kw or MW) Max Primary VA (kva or MVA) Max Primary VArs (kvar or MVAr) Power Max VA Energy Metering: The control shall be capable of retaining the following measured values in nonvolatile memory and have a real-time clock to record the date/time stamp for each quantity indicating when the measurement period was initiated. Watt Hours Forward (kwh) Watt Hours Reverse (kwh) VAr Hours Forward (kvarh) VAr Hours Reverse (kvarh) Data Logging: Data logging shall be provided that allows the user to record data internally into nonvolatile memory. The Data Log shall be saved in COMTRADE format and shall be capable of being downloaded using either MODBUS or DNP protocols. Sequence Of Events (SOE): The control shall contain a Sequence of Events recorder for comprehensive time tagged data recording of control parameters that include Voltage, Frequency, Tap Position, Current, Counters, and Harmonics. The Sequence of Events Recorder is triggered by user-selectable programmable parameter logic or manually by the user and shall be capable of recording up to 129 events. Computer Business Equipment and Manufacturers Association (CBEMA) Sag & Swell Recorder: The control shall provide CBEMA monitoring to detect sags and swells and trigger data collection and alarming functions. Page 5 of 9
6 INPUTS The control shall have the following inputs: Load Voltage Input: Nominal 120 VAC, 60 Hz (50 Hz optional); operates properly from 90 VAC to 140 VAC. If set at 60 Hz, the operating system frequency shall be from 55 to 65 Hz; if set at 50 Hz, the operating system frequency shall be from 45 to 55 Hz. The burden imposed on the input shall be 8 VA or less. A voltage transformer connected at the controlled voltage bus shall provide power to the unit. The unit shall be able to withstand twice the voltage input for one second and four times the voltage input for one cycle. Motor Power Input: The motor power input to the control shall be a nominal 120 VAC or 240 VAC, at up to 6 A as required by the load, with no wiring changes required. Motor Seal-In Input: The control shall receive an input from the regulator motor seal-in circuit. Load Current Input: The control shall have line drop compensation provided by a current transformer input with a 0.2 A full-scale rating. The burden imposed on the current source shall be 0.03 VA or less at 200 ma. The control s load current input shall withstand 400 ma for two hours and 4 A for 1 second. Control Power Backup Input: The control shall have a DC Control Power Backup Input feature to sustain operation of the control in the event of a loss of AC input power to the control and shall be able to respond to Raise and Lower commands as long as the control s motor power remains energized. Counter Input: The control shall have a Counter Input to detect tap position changes; the input shall update two counters, one pre-settable and one resettable. Neutral Tap Position Detect Input: The control shall have a Neutral Position Detect Input to detect the neutral tap position, which assists the tap position function. Source Voltage Input: Nominal 120 VAC, 60 Hz (50 Hz optional); operates properly from 90 VAC to 140 VAC. If set at 60 Hz, the operating system frequency shall be from 55 to 65 Hz; if set at 50 Hz, the operating system frequency shall be from 45 to 55 Hz. The burden imposed on the input shall be 8 VA or less. A voltage transformer connected at the controlled voltage bus shall provide power to the unit. The unit shall withstand twice the voltage input for one second and four times the voltage input for one cycle. The control shall use this input with the Reverse Power Measured feature when reverse power operation is desired and a Source Side PT input is available. Binary Inputs Voltage Reduction 1 and 2 Inputs: The control shall have Voltage Reduction 1 and 2 inputs to provide three levels of programmable voltage reduction that can be manually invoked. The control shall allow the Voltage Reduction Level 2 input to be used as an auxiliary input that is monitored remotely via SCADA by setting its input to AUX. Non-Sequential/ Auto Tapchanger Inhibit Input: The control shall have non-sequential/auto tapchanger inhibit input to provide the means to perform non-sequential operations. Page 6 of 9
7 OUTPUTS The control shall have the following outputs: Raise Output: Capable of switching 6 A at 120 VAC to 240 VAC motor power. Lower Output: Capable of switching 6 A at 120 VAC to 240 VAC motor power. User Programmable Alarm Output: One Form C contact capable of switching 6 A at 125 VAC or 0.2 A at 125 Vdc. FRONT PANEL CONTROLS The control shall provide the following features: The control shall provide menu-driven access to all functions by way of seven pushbuttons and a two-line alphanumeric display. There shall be two programmable Access Codes available to provide various levels of access to the control functions. The control shall have a 2-line by 20-character backlit LCD display for enhanced viewing in direct sunlight and also have a low-level LED backlight for reading in darker environments. The front panel HMI screen shall be available in either English or Spanish. RAISE/LOWER switch allows local manual raise and lower commands to be initiated. AUTO/OFF/MANUAL switch allows auto operation of the control or manual operation from the panel by using the Raise/Lower toggle switch. When this switch is in Off or Manual, the Control shall be physically unable to operate the Regulator, acting as a hard copper disconnect. VOLTAGE SOURCE switch disconnects processing power from the unit when selected to the OFF position. The EXT position allows the control to be powered from the front panel test jacks. SCADA CUTOUT (LOCAL/REMOTE) switch allows the local blocking of write commands from COM1, COM2, or Ethernet. DRAG HANDS RESET switch resets the tapchanger position indicator drag hands. EXTERNAL POWER/COM binding posts allows application of a 120 VAC rms nominal voltage to the unit for test procedures. METER OUT/COM binding posts allows measurement of the input voltage with a voltmeter. Smart Flash SD Card Slot: The control shall have an SD Card slot that allows the user to perform the following functions without the need for a laptop: Load Set Points Save Set Points Save Data Log Load DNP Configuration Clone Save Clone Load Save DNP Configuration Firmware Update Save Metering Data Save Wake Screen Data Save Oscillographic Records Physical Security Key Quick Capture LED Indicators: The control shall have the following LED Indicators on the front panel: Out-of- Band RAISE, Out-of-Band LOWER, REVERSE POWER flow detected, CPU OK, ALARM, VOLTAGE REDUCTION in effect, MANUAL, LOCAL, NEUTRAL, and TX/RX transmit and receive. Page 7 of 9
8 TESTS AND STANDARDS The control shall comply with the following type tests and standards: ELECTRICAL ENVIRONMENT Voltage Measurement Accuracy The control shall have a voltage measuring accuracy of ± 0.3 % when tested in accordance with ANSI/IEEE C standard over a temperature range of 40 C to + 85 C. Dielectric Withstand IEC : Impulse Voltage IEC : Insulation Resistance IEC Surge Immunity 2,000 VAC for 1 minute applied to each independent circuit to earth 2,000 VAC for 1 minute applied between each independent circuit. 5,000 V pk, +/- polarity applied to each independent circuit to earth 5,000 V pk, +/- polarity applied between each independent circuit 1.2 s by 50 s, 500Ω impedance, three 1 every 5 seconds IEC > 100 MΩ. IEC : 2,000 V pk, ± polarity applied, 1.2 s by 50 s, 2Ω/12Ω impedance, five 1 every 5 seconds Voltage Interruptions Immunity IEC TRANSIENT PROTECTION High Voltage All input and output terminals shall withstand 2,000 VAC rms to chassis or instrument ground for one minute with a leakage current not to exceed 25 ma for all terminals to ground. Input and output circuits are electrically isolated from each other, from other circuits, and from ground. Surge Withstand Capacity IEEE C IEEE C ,500 V pk Oscillatory 4,000 V pk Fast Transient Burst 2,500 V pk Oscillatory 5,000 V pk Fast Transient NOTE: Disturbance is applied to digital data circuit (RS-485) ports through capacitive coupling clamp. Radiated Immunity IEC V/M Fast Transient Burst Immunity IEC Class A (4 kv, 2.5 khz) NOTE: Disturbance is applied to digital data circuit (RS-485) ports through capacitive coupling clamp. Page 8 of 9
9 ATMOSPHERIC ENVIRONMENT Temperature: Control shall operate from 40 C to +85 C; the LCD display s visible temperature range shall be 20 C to +70 C IEC : Cold, 40 C IEC : Dry Heat, + 80 C IEC : Damp Heat, % RH IEC : Damp Heat Condensing Cycle: 25 C, % RH MECHANICAL ENVIRONMENT The control shall meet the following mechanical environmental specifications: IEC Vibration response Class 1: 0.5 g Vibration endurance Class 1: 1.0 g IEC Shock Response Class 1: 5g Shock Response Class 1: 15g Bump Endurance Class 1: 10g STORAGE PARAMETERS The control s design shall allow for storage under the following conditions: Temperature Range: +5 C to +40 C Humidity: Maximum relative humidity of 80% for temperatures up to 31 C, decreasing from 31 C linearly to 50% relative 40 C Page 9 of 9 File: M-6200A-Sugg-Spec.doc
M-2001D DIGITAL TAPCHANGER CONTROL SUGGESTED SPECIFICATIONS
M-2001D DIGITAL TAPCHANGER CONTROL SUGGESTED SPECIFICATIONS Pole-Top/Pad Mount Digital Tapchanger Control, for metering, monitoring, and operational control of step-voltage load tapchangers shall be provided
More informationCONTROLS. Digital Regulator. Digital Regulator Control for General Electric, Siemens, Cooper and Howard Regulators
CONTROLS Digital Regulator Control ol M-6200 Digital Regulator Control for General Electric, Siemens, Cooper and Howard Regulators Features Adjustable Bandcenter Adjustable Bandwidth Line Drop Compensation,
More informationDigital Voltage Regulator Control M-6200A
CONTROLS Digital Voltage Regulator Control M-6200A Digital Regulator Control for General Electric, Siemens, Cooper and Howard Regulators Maximum Communication Options For Wired or Wireless Networks Standard
More informationDigital Tapchanger Control M-2001C
CONTROLS Digital Tapchanger Control M-2001C Digital Tapchanger Control for Transformers and Regulators LTC transformer, substation regulator, and line regulator control provides reliable operation with
More informationDigital Tapchanger Control M 2001D
CONTROLS Digital Tapchanger Control M 2001D Digital Tapchanger Control for Transformers and Regulators LTC transformer, substation regulator, and line regulator control provides reliable operation with
More informationDigital Tapchanger Control M-2001B
CONTROLS igital Tapchanger Control M-2001B igital Tapchanger Control for Transformers and Regulators Microcontroller-based LTC transformer and regulator control provides reliable operation and expanded
More informationInstruction Book. M 2001C (Comprehensive) Tapchanger Control
Instruction Book M 2001C (Comprehensive) Tapchanger Control CONTROLS Digital Tapchanger Control M-2001C Digital Tapchanger Control for Transformers and Regulators Comprehensive Model Shown LTC transformer,
More informationBus Bar Protection Relay B-PRO 4000
Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation
More informationAutodaptive Capacitor Control M 2501B
CONTROLS Autodaptive Capacitor Control M 2501B Capacitor Control for Pole-Top Capacitor Banks Increases effectiveness of installed capacitors for voltage control to reduce system losses Adapts reference
More informationEM132 EM132. Main Features. Multi-functional 3-Phase Transducer. Energy Meter
EM132 MULTI-FUNCTION TRANSDUCER SATEC EM132 is a Smart DIN Rail Multi-Function Transducer with a local display. It is based on SATEC s best seller PM130 PLUS with an off-the-shelf LCD display (similar
More informationg Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications
Multilin Voltage Regulator DGCV KEy BENEFITS Increases grid efficiency by optimizing voltage regulation Through deployment of the Volt/VAR system, the Multilin DGCV: - Enables up to a 6% reduction in energy
More informationUW Purchase Specification Section
Page 1 of 9 PART 2 GENERAL 2.01 DESCRIPTION A. Purpose 1. This section covers electrical service meters and sub-meters for use in the Owner's power distribution systems. 2.02 QUALIFICATIONS A. Approved
More informationBFM-II BFM-II BRANCH FEEDER MONITOR. Highlights
BRANCH FEEDER MONITOR SATEC s is the second generation of Branch Feeder Monitor, providing energy management for multi-point power solutions. Ideal for both new and retrofit projects, the automatically
More informationDigital Multifunction Meters. Digital Multifunction Meters
Digital Multifunction Meters Digital Multifunction Meters DIGITAL MULTIFUNCTIOL METERS SECTION INDEX 1. MFM 3410 3420 3430 3440 6100 & 2000 - Multifunctional Instrument Series 2. EM 3490, 3490SS, 3490DS
More informationwww. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES
Protective Relays Electrical Apparatus Capacitor Bank Protection Relay 165-440-900 Figure 1: Edison Idea Relay The capacitor bank protection relay is a member of Cooper Power Systems Edison Idea TM line
More informationPMC 530 Series Advanced Multifunction Meter
IEC 62053 22 Class 0.5S WF Capture @ 128 samples/cycle WF and Data Recording Harmonics & Transient Monitoring I residual Monitoring Setpoint Alarms, SOE Log RS 485 and I/O Capabilities Large, Bright, Backlit
More informationUSER MANUAL 2012 V1.1
SMART MINI POWER SDM630 USER MANUAL 2012 V1.1-1 - Installation and Operation Instructions Important Safety Information is contained in the Maintenance section. Familiarise yourself with this information
More informationProviding the missing piece in your Condition Based Monitoring platform
QUALITROL Transformer Monitoring System Providing the missing piece in your Condition Based Monitoring platform Modular design; full customization of monitoring parameters to meet specification Reduce
More informationPM174 PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER. Features
PM174 IEEE1159 ADVANCED POWER QUALITY ANALYZER The PM174 is a compact, multi-function, three-phase AC powermeter and power quality analyzer specially designed to meet the requirements of users ranging
More informationSEL-734B Data Sheet. Advanced Monitoring and Control System. Major Features and Benefits
Advanced Monitoring and Control System Compact Enclosure Full-Size Enclosure Major Features and Benefits The SEL-734B combines volt/var based capacitor bank control with power quality monitoring and advanced
More informationCommunication Gateway COM 610. Product Guide
Communication Gateway COM 610 Product Guide Issued: September 2004 Status: Updated Version: D/17.10.2006 Data subject to change without notice Features Protocol conversion gateway for substation automation:
More informationElectronic Submeter with Advanced WiFi Ethernet Capability
SH RK 100S Electronic Submeter with Advanced WiFi Ethernet Capability AGGRESSIVE TECHNOLOGY W NEIndustry Leading Technology High Performance Metering Technology 0.2% Accuracy Class Revenue Certifiable
More informationMehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording
Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording Two independent, simultaneously operating recorders in one package Triggering on input quantities and calculated values, such as
More informationEPM g Energy. Multilin BUILDING AUTOMATION POWER METER. BACnet /IP Communications and Energy Measurement KEY BENEFITS APPLICATIONS FEATURES
Multilin EPM 6010 BUILDING AUTOMATION POWER METER BACnet /IP Communications and Energy Measurement KEY BENEFITS Rapid integration into BACnet management systems High accuracy multifunction power meter,
More informationDGC-2000 DIGITAL GENSET CONTROLLER
DGC-2000 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-2000) offers an integrated alternative for genset control and monitoring. Control includes engine starting and shutdown
More informationMultilin EPM Energy and Demand Submeter with Wi-Fi. Monitoring & Metering. Communications. Key Benefits. Applications
Multilin EPM 6100 Energy and Demand Submeter with Wi-Fi The EPM 6100 is a powerful tool that allows customers to monitor and manage their energy usage within factories, businesses and across campuses.
More informationMultifunction Transducer MT440
Multifunction Transducer MT440 Voltage and current auto range measurements up to 600V, 12.5A Universal wide auxiliary power supply range 24 300 Vdc, 40 276 Vac Power accuracy class 0.5 (EN 60 688), Up
More informationQUALITROL QTMS Transformer Monitoring System
QUALITROL QTMS Transformer System Providing the Missing Piece in Your Condition Based Platform Modular design; full customization of monitoring parameters to meet specification Reduce installation and
More informationEM133 EM133 TOU SMART ENERGY METER. Main Features. Multifunctional 3-Phase Smart Meter. Billing/TOU Energy Meter
TOU SMART ENERGY METER SATEC is a Smart DIN Rail TOU Energy Meter. It is based on SATEC s best seller PM130 PLUS with an off-theshelf LCD display (similar to the BFM136 display). The provides the full
More informationMIC-2 Multi-instrument DATA SHEET
Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional) Profibus DP (optional) I/O modules
More informationRT4F-110V/25A RECTIFIER
The RT4F-110V/25A is a hot-pluggable switched mode rectifier (SMR) module designed to provide up to 25A of output current into a 110V nominal system. Examples of such systems are 60 cells lead acid (136V
More informationSwitching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers
Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers Switching Control Sentinel (SCS) for circuit breakers Voltage and current transients generated during switching
More informationAPU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET
APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET Measurement input, auto range Up to 1000 V AC L-L Up to 12.5 A (sinusoidal) 16 400 Hz Output Up to four analogue outputs Relay output RS 485 Modbus
More informationextending the boundaries of technology evolution of proven technology FEATURES
extending the boundaries of technology evolution of proven technology FEATURES IEC 61850 compliant Advanced AC capabilities with comprehensive fault detection Integrated protection functions Disturbance
More informationSDM630M CT USER MANUAL 2016 V4.7. DIN Rail Energy Meter for Single and Three Phase Electrical Systems
SDM630M CT DIN Rail Energy Meter for Single and Three Phase Electrical Systems Measures kwh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, THD,etc. Bi-directional measurement IMP & EXP Two pulse outputs
More informationMIC-2 MKII, Multi-instrument DATA SHEET
MIC-2 MKII, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 26 2713 ELECTRICITY METERING PART 1 - GENERAL 1.1 SUMMARY A. Section includes equipment for metering of the electrical power system. B. Related Sections: 1. Section 26 2300 for metering installed
More informationMIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET
& DIN, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)
More informationProtection Relays PHASE & RESIDUAL OVERCURRENT
Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent
More informationVoltage Transducer UMT516 / MT516
Voltage Transducer UMT516 / MT516 True RMS AC voltage measurements Voltage auto range measurements up to 600V # Wide frequency measurement range 16 400 Hz High accuracy class 0.2 (IEC-688), 0.1 on communication
More informationRT4F-48V/50A-WAC RECTIFIER
The RT4F-48V/50A-WAC is a switched mode rectifier (SMR) module designed to provide up to 58A of output current into a 48V nominal system, over a wide range of AC input voltage. This rectifier has been
More informationRT4F-120V/20A-WAC RECTIFIER
The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with
More informationMW/MVAR Transducer Specifications
GUARANTEED TECHNICAL PARTICULARS (To be submitted by bidder with the tender) MW/MVAR Transducer Specifications Sr.No. Descriptions Details Offered by supplier 1 2 3 4 Transducer suitable for Input Output
More informationTransformer Protection Relay
Transformer Protection Relay T-PRO Product Overview The IEC 61850 station bus embedded T-PRO relay provides complete three-phase multi-winding transformer protection and overload protection, DFR-quality
More informationEM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters
Power and Energy Meters Code No. LIT-1900845 Issued December 4, 2013 EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters EM-1000 Series Meter Description The EM-1000 Series monitor is
More informationPMC-630 Series Advanced Multifunction Meter
IEC 62053-22 Class 0.5S Compliant 2MB Log Memory Power Quality Monitoring Waveform Recording SOE Log Setpoint Alarms RS-485 and I/O Capabilities I residual Monitoring Large, Bright, Backlit LCD Display
More informationIndustry Leading Performance From Simple to Sophisticated The Leader in Power Monitoring and Control
www.electroind.com Shark 200T Transducer Only Shark 200 Meter/Transducer From Simple to Sophisticated Simple Multifunction Meter: VSwitch Key 1 Historical Datalogging: VSwitch Key 2 Advanced Power Quality
More informationIndustry Leading Performance From Simple to Sophisticated The Leader in Power Monitoring and Control
www.electroind.com Shark 200T Transducer Only Shark 200 Meter/Transducer From Simple to Sophisticated Simple Multifunction Meter: VSwitch Key 1 Historical Datalogging: VSwitch Key 2 Advanced Power Quality
More informationType MVTT 14 and MVTT 15: Static Digital Time delay relays
Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction
More informationU niversal Measuring Device UMG 96 S. Little Fieldbus Giant. Modbus / Profibus. Harmonics. Memory. Analogue outputs. Digital I/O
U niversal Measuring Device Little Fieldbus Giant Modbus / Profibus Harmonics Memory Analogue outputs Digital I/O Modem Recorder Profibus Modbus PC I/O Universal Measuring Device Application Application
More informationComprehensive Modular Genset Controller
Inteligen Learn More Comprehensive Modular Genset Controller Brief Description The Inteligen is a comprehensive controller for single and multiple generating sets operating in standby or parallel to the
More informationB+G E-Tech User Manual for SDM630 SDM630. Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 2013 V1.
SDM630 Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 203 V. Important Safety Information is contained in the Maintenance section. Familiarize yourself with this
More informationRT4B-110V/12A RECTIFIER
The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs
More informationIPD163C. Single-Phase Multifunction Meter User Manual Version: V1. August 20, 2017
163C Single-Phase Multifunction Meter User Manual Version: V1 August 20, 2017 This manual may not be reproduced in whole or in part by any means without the express written permission from IPD. The information
More informationMID PRELIMINARY DATA SHEET. RI-D Series. Single Phase Multifunction Energy Meter (MID Certified) MID
PRELIMINARY DATA SHEET RI-D35-100 Series Single Phase Multifunction Energy Meter (MID Certified) MID direct connected Two pulse outputs LED pulse indication High definition LCD display with white backlight
More informationMONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES
MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity
More informationPower Meter PowerMonitor 500
ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION PowerMonitor 500 NOTICE: The specification guidelines in this document are intended to aid in the specification of products. Specific
More informationPM800 series. Applications
Functions and characteristics PE86134 The PowerLogic meters offers many high-performance capabilities needed to meter and monitor an electrical installation in a compact 96 x 96 mm unit. All models include
More informationMetering Devices IQ 300
Effective: May 2001 Page 1 New Information Contents Description Page General Description......... 2 Specifications.............. 3 Field Wiring Connections.... 4 Page 2 Effective: May 2001 Applications
More informationEPM Multilin ADVANCED POWER QUALITY METER. High Performance Power Quality and Transient Recorder Meter KEY BENEFITS APPLICATIONS FEATURES
Multilin EPM 9900 ADVANCED POWER QUALITY METER High Performance Power Quality and Transient Recorder Meter KEY BENEFITS Auto-calibrating metrology means the meter maintains its accuracy over temperature
More informationBulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications
Power Circuit Control Circuit (External Source) Control Circuit (Internal Source) Short Circuit Current Rating (SCCR) Application Electrical Ratings Three-phase Number of Poles 3 Input Power Terminals
More informationDesigned For Reliability Manufactured To Last
512/1024 samples/cycle IEC 62053-22 Class 0.2S Compliant IEC 61000-4-30 Class A Sag/Swell, Transient and Flicker Comprehensive Data Recording PQDIF & COMTRADE Compatible 5.7 Color LCD Display @ 640x480
More informationekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB
MO-067-EN Operation Manual MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB Transformer Substations Secondary Distribution Switchgear Primary Distribution Switchgear Protection
More informationOHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L
AC PROGRAMMABLE TRANSDUCERS MODBUS OR LONWORKS DESCRIPTION The DMT-1000 is a programmable transducer with an RS-485 bus interface (MODBUS ). It supervises several variables of a poly-phase electrical power
More informationwww. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay
Protective Relays Electrical Apparatus ixp-420 Transformer Protection Relay 165-420 Figure 1: Edison Idea Relay The ixp-420 is a member of Cooper Power Systems Edison Idea line of protective relays. The
More informationGRD130 - FEATURES APPLICATION
FEATURES Phase undervoltage protection with IDMTL or DTL. Phase overvoltage protection with IDMTL or DTL. Zero phase sequence overvoltage (neutral voltage displacement) protection with IDMTL/DTL. Negative
More informationINTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box
INTRODUCTION The PL-50 MO units are available in the next mechanical version: The PL-50 MO and PM-250 families represent the different solutions that Team Arteche offers for motor protection. Both families
More informationMultilin EPM 6010 YEAR. GE Grid Solutions. Building Automation Power Meter with BacNET /IP Communications. Monitoring & Metering
GE Grid Solutions Multilin EPM 6010 Building Automation Power Meter with BacNET /IP Communications The Multilin EPM 6010 is an industry leading revenue grade power meter with native BACnet/ IP communications.
More informationDigital On-Load Tap Changer Voltage Controller TAPCON 250 Operating Instructions (short version) BA 289
www.reinhausen.com Digital On-Load Tap Changer Voltage Controller Operating Instructions (short version) BA 289 Defined movement of the drive shaft REGULATING TRANSFORMER Changing the Transformer Ratio
More informationPower System Monitoring Recorder TESLA 3000
Power System Monitoring Recorder TESLA 3000 Product Overview TESLA 3000 is an easy-to-use and cost-effective, stateof-the-art, multi-time frame (simultaneous) power system recording monitor. The optional
More informationRelion 611 series. 611 series Type Test Certificate
Relion 611 series 611 series Document ID: 1MRS757466 Issued: 2016-02-22 Revision: B Product version: 2.0 Copyright 2016 ABB. All rights reserved Table of contents Table of contents Section 1 Section
More informationApplication Guide. M-2270B Adapter Panel
Application Guide M-70B Adapter Panel CONTROLS Adapter Panel M-70B Adapts M-00 Series Digital Tapchanger Control as a General Replacement for Transformer and Regulator Controls Provides mounting adaptable
More informationType VRLTC tap changer
Report No. 1ZUA938502-AGC 2, Rev 0 Date: 6 November 2012 Type VRLTC tap changer Ruggedized electronics systems specification & type test data Product Style No Rating By Type VRLTC, on-tank, vacuum reactance
More informationPROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL
MICROPROCESSOR PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL MICROELETTRICA SCIENTIFICA MANUFACTURES A COMPLETE RANGE OF
More informationSDM530CT-Modbus USER MANUAL 2015 V1.6. Three Phase Multi-function DIN rail meter. Eastron SDM530CT-Modbus User Manual
SDM530CT-Modbus Three Phase Multi-function DIN rail meter Measures kwh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, etc. Bi-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting
More informationU niversal Measuring Device NEW! UMG 96 S. Little Fieldbus Giant. Modbus / Profibus. Harmonics. Memory. Analogue outputs.
U niversal Measuring Device NEW! Little Fieldbus Giant Modbus / Profibus Harmonics Memory Analogue outputs Digital I/O Modem Recorder Profibus Modbus PC I/O Universal Measuring Device Application Application
More informationData Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D
WPM 770 Data Sheet 679.D.141.02 Digital Multifunctional Power Meter with LCD Display and Application The digital Weigel Power Meters WPM 770 have been designed to display the electrical parameters in low
More informationMultiCube Single Phase Multi-Function Electricity Meter. Installation and Operation
MultiCube Single Phase Multi-Function Electricity Meter Installation and Operation PREFACE MultiCube Single Phase Meter Operating Guide Revision 5.01 August 2002 This manual represents your meter as manufactured
More information5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...
.1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....
More informationUMG 96RM. UMG 96RM Universal measurement instrument. Areas of application
UMG 96RM UMG 96RM Universal measurement instrument The UMG 96RM is a very compact and powerful universal measurement device designed for use in low and medium voltage distribution systems. In addition
More informationCurrent Fault Signatures and Analysis Auto-calibrating metrology means the meter maintains its accuracy over temperature and time
Multilin EPM 9900 High Performance Power Quality and Transient Recorder Meter The EPM 9900 is one of the most advanced monitoring products on the market today, providing you with the total picture of energy
More informationSmart Energy & Power Quality Solutions. UMG 96S Universal flush-mounting measuring instrument
Smart Energy & Power Quality Solutions UMG 96S Universal flush-mounting measuring instrument UMG 96S UMG 96S Universal flushmounting measuring instrument Universal flush-mounting measuring instruments
More informationUMG 20CM. 20 Channel Branch Circuit Monitoring Device with RCM
20 Channel Branch Circuit Monitoring Device with RCM RCM Harmonics via analysis channel Alarm management GridVis Analysis software 20 current channels Interfaces / communication RS485 RTU Accuracy of measurement
More informationFor Transmission, Distribution and Machinery protection.
Founded in 1953, Microelettrica Scientifica has developed a wide range of products, divided into three main lines: For Transmission, Distribution and Machinery protection. A-Line Electronic analogic. M-Line
More informationDKM-405 NETWORK ANALYSER WITH TOTAL HARMONIC DISTORTION DISPLAY
datakom@datakom.com.tr http://www.datakom.com.tr Tel: +9-216 466 84 6 Fax: +9-216 364 65 65 DKM-45 NETWORK ANALYSER WITH TOTAL HARMONIC DISTORTION DISPLAY INTRODUCTION The DKM-45 is a low cost precision
More informationVCL-TP, Teleprotection Equipment With Trip Counter Display Panel
VCL-TP, Teleprotection Equipment With Trip Counter Display Panel Data Sheet Copyright: Valiant Communications Limited. 2008-2014 1 Product Overview VCL-TP, Teleprotection Equipment is an extremely reliable
More informationPart No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version
Ordering Data DATA SHEET TU520 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 214 400 R0001 1SAP 414 400 R0001 TU520-ETH, PROFINET I/O terminal unit, 24 VDC, spring
More informationPowerLogic power-monitoring units. PM1000 series power meter. Technical data sheet
PowerLogic power-monitoring units power meter Technical data sheet 2011 Basic energy meters Functions and characteristics PE86261 PE86260 PowerLogic PM1000 power meter. The PowerLogic power meters are
More informationINSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:
DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated
More informationPQM - Power Quality Monitoring
UMG 96S PQM - Power Quality Monitoring The little field bus giant Universal flush-mounting measuring instruments of the UMG 96S product family are mainly designed for use in low and medium voltage distribution
More informationDEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S
Multi-instrument 4921210107G Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Intelligent Suitable for all 3-phase network topologies Replaces transducers Accuracy U,
More informationTF501, TF521 Terminal Bases
Ordering Data DATA SHEET TF501, TF521 Terminal Bases 1 Ordering Data Part No. Scope of delivery Product life cycle status 1SAP 117 000 R0271 1SAP 317 000 R0271 1SAP 117 200 R0271 1SAP 317 200 R0271 TF501-CMS,
More informationNewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators
NewCode Comprehensive Motor Protection and Control Relay Relay Field Input and Output LEDs LED Fault Indicators Configurable Memory Module on a T-Bus IrDA and USB Connectors Profibus Address Indicator
More informationRemote Terminal Unit ER1000 APPLICATION FEATURES
Remote Terminal Unit ER1000 ERL with more than three decades of expertise in Power System Protection have developed state of the art Automation Solutions. The whole family of ERL s Remote Terminal Unit
More informationFL MC 2000E (SM40) LC
IEC 61850 fiber optic converter with LC fiber optic connection (1310 nm) to convert 100Base-Tx to single- or multi-mode fiber glass Data sheet 3205_en_C 1 Description PHOENIX CONTACT 2014-04-04 2 Features
More informationSmart Energy & Power Quality Solutions. UMG 505 Power analysis, LON and I/O-Vielfalt
Smart Energy & Power Quality Solutions UMG 505 Power analysis, LON and I/O-Vielfalt UMG 505 UMG 505 Power analysis, LON and I/O-Vielfalt Power analysers of the UMG505 product family are mainly designed
More informationTM221M16TG controller M IO transistor PNP spring
Characteristics controller M221 16 IO transistor PNP spring Main Range of product Product or component type [Us] rated supply voltage Discrete input number Analogue input number Discrete output type Discrete
More information4 Is this model available for special primary current and special primary voltage?
Category: Sales 1 Is it possible to exchange the backlights? The backlights are LED, no need to exchange. Fukuyama Works, Mitsubishi Electric Corporation March, 2018 2 Which standards does this model support?
More informationTU531, TU532 Terminal Unit
Ordering Data DATA SHEET TU531, TU532 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 217 200 R0001 1SAP 217 000 R0001 1SAP 417 000 R0001 TU531, terminal unit, 230 VAC,
More informationRT12-240V/2.4kW Rectifier Specification
The RT12-240V/2.4kW is a switched mode rectifier (SMR) module that delivers up to 2.4kW of output power (and up to 11A output current) into a 240V nominal DC system. The RT12 suits AC supply voltages between
More information