Masterpact NW Restricted Earth Fault Protection
|
|
- Vernon Smith
- 6 years ago
- Views:
Transcription
1 Masterpact NW Restricted Earth Fault Protection Date: November 2011 Page 1 of 12
2 Contents Introduction 3 Principle of Operation 4 Equipment Required 5 Installation of the Neutral CT 5 Connection of the Neutral CT 6 24V DC power supply 6 Programming the M2C Contact with the Micrologic 6.0E 7 & 8 Programming the M2C/M6C Contact with the Micrologic 6.0P/6.0H 9 Resetting the ACB after a Fault 10 Resetting the M2C/M6C after a Fault 10 Test Procedure 11 & 12 For further information please consult our technical support department on Date: November 2011 Page 2 of 12
3 Introduction Restricted earth fault protection provides earth fault protection for the secondary side of the transformer and the cables/busbars up to the incoming terminals of the LV incoming circuit breaker. This type of fault occurs upstream of the incoming circuit breaker and therefore can only be disconnected by the MV circuit breaker on the primary side of the transformer. The Masterpact NW 3 or 4 pole ACB can be used to detect restricted earth faults. The ACB uses its internal CT s on phases L1, L2, L3, external neutral CT and an appropriate Micrologic trip unit to monitor the system. The neutral CT should be fitted as close to the ACB as possible. The neutral to earth link is connected upstream of the neutral CT as shown in Fig 1. Fig 1: Restricted Zone Unrestricted Zone L3 L2 L1 N Ext CT ACB N/E Link Date: November 2011 Page 3 of 12
4 Principle of Operation In the event of an earth fault upstream of the Masterpact ACB, the fault current will flow from the source of the fault, to earth. The earth fault current will then return back to star point of the transformer via the neutral earth link, external neutral CT and neutral cable/busbar. Earth fault currents upstream of the ACB are not detected by the ACB s internal CT s on L1, L2 or L3. However, the earth fault current returns to the star point of the transformer via the neutral earth link and external neutral CT. The Micrologic trip unit carries out a summation calculation of the currents in all of the CT s (L1, L2, L3 & external neutral CT). If the resultant summated current is greater than the earth fault setting on the Micrologic trip unit, the ACB will trip. When the ACB trips on an earth fault, the Micrologic trip unit will signal the programmable M2C or M6C contact to operate. This contact is used to trip the MV circuit breaker via a tripping coil on the primary side of the transformer. When the earth fault has been rectified, the M2C or M6C contact is reset via the Micrologic trip unit, along with the red reset button on the front of the ACB. It will then be possible to re-close the MV circuit breaker if it s safe to do so. Figure 2 shows the LV side of the transformer and an example of an earth fault upstream of the ACB. Fig 2: Date: November 2011 Page 4 of 12
5 Equipment Required Restricted earth fault protection can be achieved using either a 3 or 4 pole Masterpact NW ACB which must be equipped with the following parts. Micrologic 6.0E*, 6.0P** or 6.0H** trip unit Programmable M2C or M6C contacts External Neutral CT for 3 & 4 pole devices 24V DC Power supply module Battery module*** * The Micrologic 6.0E only supports the M2C contacts, which can only be programmed for non-latching control when used with the Micrologic 6.0E. ** The Micrologic 6.0P or 6.0H support either the M2C or M6C contacts, which can be programmed for either latching or non-latching control. *** The battery module is required if the M2C or M6C contacts are programmed for latched output. It s used to provide a back up to the 24V DC feed to the trip unit in the event of the power supply losing its input supply. If the 24V DC power supply is independently fed from a secure supply the battery module may not be required. Note: If a 4 pole Masterpact NW is used, please state at the time of ordering that it s going to be used on a restricted earth fault application. Installation of the Neutral CT The external neutral CT must be installed upstream of the neutral earth link for the restricted earth fault system to operate correctly. The length of the secondary wiring must not be greater than 4 metres. The polarity of the CT is vital. The orientation of the CT (H1 & H2) is always the same with respect to the ACB, irrespective of the direction of the power flow. This is because the orientation of the CT s inside the ACB are fixed, i.e. H1 connected to the bottom terminal and H2 connected to the top terminal. See figure 3. Fig 3: Date: November 2011 Page 5 of 12
6 Connection of the Neutral CT The secondary connections between the external CT and the Micrologic 6.0 trip unit are shown in figure 4. Fig 4: Notes: The maximum length of the secondary winding between the CT and the Micrologic trip unit is 4 metres. The dotted VN connection on the diagram is required to be connected when using a 3 pole ACB. The link & capacitor shown between terminals T1, T3 & T4 on the CT are supplied with the CT. 24V DC Power Supply A 24V DC power supply must be connected to terminals F1 & F2 on the Micrologic trip unit when the M2C or M6C contacts are used. Terminals F1 & F2 will automatically power the M2C contacts if fitted. If the M6C contacts are used the same power supply can be used to feed the Micrologic and the M6C contacts. The recommended 24V DC power supply can be found in the ACB catalogue. Date: November 2011 Page 6 of 12
7 Programming of the M2C contact with the Micrologic 6.0E The following Instructions show how to set up the M2C contact with the Micrologic 6.0E. The Isd setting shown in the example below should be replaced with the earth fault trip indication when used in a restricted earth fault application. Note: The text below refers to page 32 this information is on the next page of this document. Date: November 2011 Page 7 of 12
8 Information regarding page32 referred to on the previous page. Date: November 2011 Page 8 of 12
9 Programming of the M2C or M6C contact with the Micrologic 6.0P or 6.0H Note: Before programming the contacts the cover over the trip unit dials needs to be opened. The alarm type is selected from the alarm menu, which is accessed by pressing the spanner button on the trip unit as shown below. Any contact can be chosen and the alarm type is set to earth fault. When the alarm type has been confirmed, press the spanner button and select yes and then press the spanner button again to return to the previous menu. The contact is then set up to either latching or non-latching mode. When the alarm mode has been confirmed, press the spanner button and select yes and then press the spanner button again to return to the previous menu. If latching is selected the 24V DC power supply must be maintained to the Micrologic trip unit & M6C (if fitted). If the 24V DC supply is not maintained the alarm contact cannot be reset after tripping on an earth fault. Date: November 2011 Page 9 of 12
10 Resetting the Masterpact ACB & M2C or M6C contact after an earth fault trip When the reason for the ACB tripping after an earth fault has been identified and resolved, the ACB can be reset. If the M2C or M6C contact has been set to non-latching mode the red reset and LED reset buttons on the front of the ACB have to be reset as shown in step 1 below. If the M2C or M6C contact has been set to latching mode, the additional operation of resting the contact will also have to be carried out as shown in step 2 below. 1. Resetting the ACB Resetting the fault Indication LED 2. Resetting the M2C or M6C latching contact Date: November 2011 Page 10 of 12
11 Test Procedure When the Masterpact has been installed into the switchboard, it s necessary to carry out primary current injection tests to prove that the earth fault protection operates correctly. The tests detailed below will prove the following: The ACB trips at the required earth fault value set on the Micrologic trip unit. The external neutral CT has been fitted and wired correctly. The M2C or M6C contacts have been programmed correctly to operate when the ACB trips on an earth fault. Test Procedure (Quick Test) It s safe to assume that the CT s inside the circuit breaker are fitted & connected correctly. Therefore, the Quick Test can be used to prove that the connection and polarity of the Neutral CT is correct compared to the circuit breaker. 1. The Micrologic trip unit & M6C contact if fitted need to be supplied with 24V DC. 2. Set the earth fault element Ig on the trip unit to a suitable current, with the time delay Ih set to zero seconds. 3. Inject any one of the phases of the circuit breaker with current, slowly increasing it until the circuit breaker trips. The tripping current will be the E/F setting current +/- the published tolerance, as shown in diagram 1. The M2C Contact should operate each time the circuit breaker trips. 4. Inject the same phase, connected in series with the Neutral CT as shown in diagram 2. The test current should be about 20% higher than the previous tripping current and should be maintained for several seconds. The circuit breaker should not trip on earth fault if the Neutral CT has been fitted and wired correctly. Test Procedure (Full Test) It should only be necessary to carry out this test if there is a problem regarding the correct operation of the earth fault element on the circuit breaker. This test procedure will compare the polarity of any CT in the circuit breaker to any other CT in the circuit breaker. 1. The Micrologic trip unit & M6C contact if fitted need to be supplied with 24V DC. 2. Set the earth fault element Ig on the trip unit to a suitable current, with the time delay Ih set to zero seconds. 3. Inject any one of the phases of the circuit breaker with current, slowly increasing it until the circuit breaker trips. The tripping current will be the E/F setting current +/- the published tolerance, as shown in diagram 1. Repeat the test on the other two phases. The M2C Contact should operate each time the circuit breaker trips. 4. Inject a phase connected in series with the Neutral CT as shown in diagram 2. The test current should be about 20% higher than the previous tripping current and should be maintained for several seconds. The circuit breaker should not trip on earth fault if the Neutral CT has been fitted and wired correctly. Repeat for the other two phases. 5. Inject a phase connected in series with another phase i.e. L1 to L2 as shown in diagram 3. The test current should be about 20% higher than the previous tripping current and should be maintained for several seconds. The circuit breaker should not trip. Repeat for the other combinations i.e. L1 to L3 and L2 to L3. Date: November 2011 Page 11 of 12
12 Diagrams showing Primary Current Injection set (AC) connected to the power connections on the rear of the ACB/Chassis. Diagram 1: Diagram 2: Diagram 3: Notes: If the circuit breaker trips during the test shown in diagram No.2. Check the polarity of the CT, the secondary wiring and that the correct CT has been used. If the circuit breaker is equipped with an ammeter it will indicate the injected currents (check Micrologic instruction manual for minimum operating threshold). Date: November 2011 Page 12 of 12
NW08 to NW63 fixed circuit breakers Circuit breakers
fixed circuit breakers Circuit breakers DB404362.eps DB404363.eps A Masterpact fixed circuit breaker is described by 4 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b
More informationCompact NSX communication
Functions and characteristics Compact NSX communication Communications modules All Compact NSX devices can be equipped with the communication function via a prewired connection system and a Modbus network
More informationCompact NSX communication
Functions and characteristics Compact NSX communication Communications modules All Compact NSX devices can be equipped with the communication function via a prewired connection system and a network interface.
More informationADDENDUM FOR 20, 27, & 28 OPTIONS
ADDENDUM FOR 20, OPTIONS GENERAL The 20, 27, and 28 option provides for an alarm contact OR an AC transfer switch on EXELTECH XP Series inverters. The alarm relay monitors the inverter s AC output and
More informationMemshield Overcurrent Protection Relay (AOR1B)
(AOB) Multi-function Protection Device Local and remote trip indication AO-B type OCs are available with trip indications. Two types of trip indication function are available: single contact type and individual
More informationPOWER GRID AUTOMATION. Pág.. n. RMU Automation
POWER GRID AUTOMATION RMU Automation Distribution Network Non-Controlled Secondary Distribution Systems Distribution Network RMU Automation - Levels RMU Automation - RTU / FRTU SMART CONTROLLER Monitoring
More informationOvercurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin
Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection
More informationAir Circuit Breaker (ACB)
MPACT Air Circuit Breaker (ACB) Rated from 0 to 000A the MPACT circuit breaker has been designed to meet the most stringent demands in fault detection and safe interruption thereof. Available in frame
More informationMiCOM P111. Three phase and earth fault overcurrent relays
Three phase and earth fault overcurrent relays The relays are suitable for all the application where overcurrent and/or earth-fault protection are required. Thanks to its favorable price vs technical features
More informationCommon Departures Interconnecting Facilities Requirements
Welcome to our e-rew Express. In our last issue, we discussed the common departures on metering installation requirements. This time, we would like to discuss the common departures on the customer low
More information3- and 4-pole switching in UPS installation
Smart tricks to improve power supply reliability White paper series Power Distribution & UPS 3- and 4-pole switching in UPS installation Janne Paananen Technology Manager, Critical Power Solutions, Eaton
More informationNPIH800 NPIH800R. First Handling Guide Earth overcurrent relay
Earth overcurrent relay FOREWORD The aim of this handbook is to provide to the User information useful for the commissioning and the tests of NPIH800 and NPIH800R relays, multifunction digital protections
More informationUL 489 Listed Masterpact NT and NW
LV power circuit breakers and automatic switches UL 489 Listed Masterpact NT and NW Catalogue 2006 The original Masterpact has set a new standard for power circuit breakers around the world. PB101942-50
More informationPGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR
Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Revision 0-C-041918 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document
More informationREYROLLE 2RMLG. Operating Recommendations
2RMLG Operating Recommendations SAFETY The commissioning and maintenance of protection equipment should only be carried out by skilled personnel trained in protective relay operation and capable of observing
More informationBCM ULP Breaker Communication Module
DOCA0152EN-00 BCM ULP Breaker Communication Module Firmware Version 4.1.9 Release Note 05/2018 The information provided in this documentation contains general descriptions and/or technical characteristics
More informationMasterpact MTZ Micrologic X Control Unit
Masterpact MTZ Micrologic X Control Unit Firmware Version 002.000.003 Release Note 05/2018 DOCA0144EN-01 The information provided in this documentation contains general descriptions and/or technical characteristics
More informationPGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY
Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com/pgr-4700 PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY REVISION 2-B-032218 Copyright 2018 by Littelfuse, Inc. All rights reserved.
More informationLV power circuit breaker and switch-disconnectors. Masterpact NW Direct current 1000 to 4000 A. Catalogue
LV power circuit breaker and switch-disconnectors Masterpact NW Direct current 1000 to 4000 A Catalogue 2002 Get more with the world s Power & Control specialist Masterpact NW General contents Presentation
More informationTitle System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)
Discipline Engineering Standard - NSW Category Electrical Title s Reference Number PCP 07 - (RIC Standard: EP 99 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards
More informationADDENDUM TO IB17555D INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE OF THE CUTLER-HAMMER DIGITRIP 3000 SERIES OF PROTECTIVE RELAYS
ADDENDUM TO IB17555D INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE OF THE CUTLER-HAMMER DIGITRIP 3000 SERIES OF PROTECTIVE RELAYS INSTRUCTION LEAFLET IB17555D_ADDENDUM Effective Date: 11/02
More informationNPI800 NPI800R. First Handling Guide. Phase and earth overcurrent relay
Phase and earth overcurrent relay FOREWORD The aim of this handbook is to provide to the User information useful for the commissioning and the tests of NPI800 and NPI800R relays, multifunction digital
More informationPGR-6100 MANUAL GROUND-FAULT & INSULATION MONITOR
Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com/pgr-6100 PGR-6100 MANUAL GROUND-FAULT & INSULATION MONITOR Revision 2-C-050818 Copyright 2018 Littelfuse All rights reserved. Document
More informationMMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A
AUTOMATION MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A GRID Note: The technical manual for this device gives instructions for its installation, commissioning,
More informationCommunication COM option in Masterpact
CT CCM modbus CD CE Functions and characteristics Communication COM option in 056431 056401 The COM option is required for integration of the circuit breaker or switch-disconnector in a supervision system.
More informationSession Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers
Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power 1. Abstract Dinesh Mithanthaya Design Manager, Horizon Power Higher capacity substation power transformers ( 5MVA),are
More informationVIP 40/45 VIP 400/410
40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered
More informationICTD-100CP / ICTD-101CP ICTD-102CP / ICTD-103CP
PATENT PENDING ICTD-100CP / ICTD-101CP ICTD-102CP / ICTD-103CP Capacitor Trip Devices with Contact Protect Technology TM Operation Manual and Data sheet 2015 Intermountain Electronics, Inc. Important Notice
More informationEnhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades
Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades May 2012 / 1910DB1202 by Hal Theobald, Product Manager, Schneider Electric Services and Reza Tajali, P.E.,
More informationSACE Emax 2 Specification guide
SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or
More informationNEUTRAL GROUNDING RESISTOR WITH, N.G.R. MONITORING & PROTECTION RELAY
EUTAL GOUDIG ESISTO WITH,.G.. MOITOIG & POTECTIO ELA MODEL: AC/33/EL&M/10k, AC/66/EL&M/20k PAT O.: 1503300091, 1506600092 APPLICATIO There are power distribution networks which feed certain earth-fault
More informationReinforced discrimination
Reinforced discrimination Compact NSX Additional characteristics Contents Presentation Functions and characteristics A- Installation recommendations B- Dimensions and connection C- Wiring diagrams D- Compact
More information7XG225-3RMLG Test Block System Answers for infrastructure & cities.
Reyrolle Protection Devices 7XG5-3RMLG Test Block System Answers for infrastructure & cities. Siemens Protection Devices Limited 7XG5-3RMLG Test Block System Application Test blocks enable test technicians
More informationGENIEEVO Range. Protection and Control Module P4. Unit Protection Cable Feeder. Functional Description. Issue A1
GENIEEVO Range Protection and Control Module Unit Protection Cable Feeder Functional Description Issue A1 B Abbreviations and Glossary of Terms Revisions Issue A0 24.02.00 Draft Issue A1 16.05.03 Changed
More informationControl Panel Technical Guide. How to choose the circuit breaker and transfer switch for a generator set
Control Panel Technical Guide How to choose the circuit breaker and transfer switch for a generator set Standby power supply by generator set Everything has been planned so that this will not happen If
More informationHarmonicGuard Series Bus-Applied Active Harmonic Filter Quick Start Unit Software Setup
HarmonicGuard Series Bus-Applied Active Harmonic Filter Quick Start Unit Software Setup TCI, LLC W132 N10611 Grant Drive Germantown, Wisconsin 53022 Phone: 414-357-4480 Fax: 414-357-4484 Helpline: 800-TCI-8282
More informationST: TP14D/2 TEST SHEET COMBINED LV CT & METER CABINET INSTALLATIONS OFF-LOAD TESTING
COMBINED LV CT & METER CABINET INSTALLATIONS Summary This Test Sheet shall be employed during the off-load testing of Combined LV CT & Meter Cabinet Installations in accordance with Standard Technique
More informationModbus Communication for Circuit Breakers
Modbus Communication for Circuit Breakers Modbus Communication for Circuit Breakers Compact NSX, Compact NS and Masterpact NT/NW Circuit Breakers Quick Start Guide 03/2011 COM-LVP38EN www.schneider-electric.com
More informationVoltage surge suppressor
Sheet 1 PRODUCT DESCRIPTION AC/DC converter are used to rectify the line supply voltage for the DC link, normally are used uncontrolled or controlled rectifier without or with regenerative feedback unit.
More informationOCR alarm (AL) (standard) When it happen to trip by over current, ground fault ( GFR ) and Earth leakage ( ER ), it issue a warning alarm.
A Power supply module This module provides control source for DISPLAY module,trip indicator and several indicators (LEDs). (Even when the control power source is off, the function of over current protection
More informationElectrical Demand Specification (Reference SOP: )
Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3
More informationCommission Testing Methods for Protection Systems
Commission Testing Methods for Protection Systems Tom Ernst GE Grid Solutions Ken Sletten Minnesota Power Abstract Commission testing should be designed to assure that the protection system is set and
More informationBranch Procedure. Document No. Issue No. : : 29/06/ /06/2021 (Supersedes CEOP8012, Generation Connection: Protection Guidelines, Issue 4.
Branch Procedure Document No. Issue No. : : CEOP8012 5 Approved By : Specialist Engineering NETWORK : Manager Approval Date Review Date : : 29/06/2018 29/06/2021 (Supersedes CEOP8012, Generation Connection:
More informationPower-Style QED-2, Series 2 Low Voltage Switchboards
Power-Style QED-2, Series 2 Low Voltage Switchboards Catalog 2742CT1001 (Addendum to 2742CT9501R12/09) 2010 Class 2742 CONTENTS Description............................................. Page Features...................................................
More informationSEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay
Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.
More informationMESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset
More informationLow Voltage Catalogue Compact NS. Circuit breakers and switch-disconnectors from 630b to 3200 A
Low Voltage Catalogue 2013 Compact NS Circuit breakers and switch-disconnectors from 630b to 3200 A Compact NS Setting the standard, once again... The launch of Schneider Electric Compact NS in 1994 revolutionised
More informationTSC Schneider-PDI Agenda
TSC Schneider-PDI Agenda General Electrical Power Layouts and Equipment Single Phase UPS s Three Phase UPS s Trends In Data Center Power Distribution Data Center Cooling Trends and Products Jim Tubbesing
More informationPUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System
PUBLIC SERVICE OF NEW HAMPSHIRE Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System September 2013 1.0 Purpose of this document Public Service of New Hampshire
More informationAUGUST 2001 APPLICATION AND COMMISSIONING MANUAL MIT161 RELAY EASUN REYROLLE LIMITED
AUGUST 2001 APPLICATION AND COMMISSIONING MANUAL MIT161 RELAY EASUN REYROLLE LIMITED 1 Issue No : 2nd Issue Date of Issue : 30.08.2001 Department : TP-CTS 2 SENSITIVE CURRENT PROTECTION PROTECTION HEALTHY
More informationPhase Comparison Testing Of REL350 Relays Using One Test Device Or Two Test Devices Not Synchronized
ABB Application Note AN-87L-01 Substation Automation and Protection Division Phase Comparison Testing Of Relays Using One Test Device Or Two Test Devices Not Synchronized Introduction Satellite synchronized
More informationPhase Comparison Testing Of REL350 Relays Using One Test Device Or Two Test Devices Not Synchronized
ABB Application Note Substation Automation and Protection Division AN-87L-01 Phase Comparison Testing Of Relays Using One Test Device Or Two Test Devices Not Synchronized Introduction Satellite synchronized
More informationIntegrated Safety Relay ISR
Integrated Safety Relay ISR Option X/ X- (dual channel) DO0.00 V0. Regatron AG Feldmühlestrasse 0 CH-00 Rorschach Tel + 8 Fax + 8 www.regatron.com topcon@regatron.com Distributor-Aufkleber Option X Integrated
More informationekor.stp Programmable transfer unit General instructions IG-164-EN, version 04, 06/04/2017 LIB
Programmable transfer unit General instructions IG-164-EN, version 04, 06/04/2017 LIB CAUTION! When medium-voltage equipment is operating, certain components are live, other parts may be in movement and
More information5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...
.1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....
More informationMiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits
01 MiCOM P721 & P723 Numerical High Impedance Differential Relay The new P72x high impedance differential protection series provides an independent and simple high impedance differential protection solution
More informationPGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY
Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY REVISION 3-B-041318 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document
More informationBusbar protection REB 670
Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features
More informationSIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics
SIA-C Overcurrent and Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered Main characteristics The SIA-C is a overcurrent protection relay with self powered and dual powered (self
More information1. Project Description
Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal
More informationPROCEDURE FOR TESTING P122 THREE PHASE OVERCURRENT & EARTH FAULT PROTECTION RELAY S.E.P TRAINING CENTRE
PROCEDURE FOR TESTING P122 THREE PHASE OVERCURRENT & EARTH FAULT PROTECTION RELAY INDEX CHAPTER 1: 1. INTERFACING PC WITH RELAY 2. EXTRACTING SETTINGS FROM THE RELAY CHAPTER 2: 1. SETTING VALUES AS PER
More informationPower Entry. Version 1.0 June 2, 2017
Power Entry Version 1.0 June 2, 2017 1 Overview The Power Entry board is used for distributing AC power and 4 different DC voltages, generally 5v, 12v, 15v, and high voltage (typically 48v or 70v). A 12v
More informationMRT1 Test Unit. Manual MRT1 (Revision A)
MRT1 Test Unit Manual MRT1 (Revision A) Woodward Manual MRT1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor
More informationINSTALLATION & COMMISIONING GUIDE
SIA C Self Power O/C & E/F Protection Relay INSTALLATION & COMMISIONING GUIDE www.fanox.com SIAC11500032AG_Rev. 12 1 / 32 1. RECEPTION & INSTALLATION... 3 1.1. Relay unpacking... 3 1.2. Relay verification...
More informationTroubleshooting guide for the S100 Energy meter and EPS
Troubleshooting guide for the S100 Energy meter and EPS The S100 Energy Meter is the brains of the Sungrow hybrid system. It tells the inverter when to charge or discharge the battery, when to go into
More informationVAMP 221. Table of Contents
2 V221/EN M/E019 VAMP 221 Table of Contents Table of Contents 1. General... 7 1.1. VAMP 221 arc protection system components... 7 1.1.1. Central unit VAMP 221... 9 1.1.2. I/O units VAM 12L / VAM 12 LD,
More informationLV power circuit breakers and switch-disconnectors. Masterpact NT and NW Merlin Gerin. << Back. Catalogue. Building a New Electric World
More information
i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection
i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection 1 Process PG&E Order No. 754 Analysis Receive Bus List from Planning that Meet the Criteria in Table A Protection Computes Actual Clearing
More informationHigh-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay
High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay IE ON RESET.5 X1 t IE X1.6%.2.4.8 1.6 X1.1s.2.4.8 1.6 X2 OFF ON S1 S2 IRI1-ES IRI1-ES C&S Electric Limited (Protection & Control Division) Contents
More informationFunction permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%
Operating range: 0.10 to 30 xin (step 0.01) 50P(2) Activation level 100% Deactivation level 95% Timer accuracy: 30 ms Operating range: 0.10 to 30 xin (step 0.01) 50N/G(2) Activation level 100% Deactivation
More informationSMARTSTART MOTOR STARTERS
SMARTSTART MOTOR STARTERS MCG WWW.MCG-USA.COM 1 AT A GLANCE Covers all line voltages from 200-600V AC, single or three phase Transformer supplies a 24V AC coil voltage, no matter the line voltage 12V AC/DC
More informationQUICK REFERENCE PRICE GUIDE JUNE 2016
QUICK REFERENCE PRICE GUIDE JUNE 2016 OUR CUSTOMER CARE COMMITMENTS Quality is Guaranteed All products supplied from this Quick Price Guide carry a guarantee against defects in materials and workmanship
More informationRelion 650 series. Accessories, 650 series IEDs versions 1.0 to 1.3, ANSI Product Guide
Relion 650 series Accessories, 650 series IEDs versions 1.0 to 1.3, ANSI Product Guide Contents 1. Available accessories...3 2. Mounting kit for 3U... 3 3. Mounting kits for 6U...4 4. RHGS cases...6 5.
More informationWhite paper - Preliminary. Emax 2, all-in-one innovation Interface Protection System and Interface Device
White paper - Preliminary Emax 2, all-in-one innovation Interface Protection System and Interface Device Emax 2 Interface Protection System and Interface Device Index General introduction... 2 Emax 2
More informationDescription. Installation. Power supply
Air circuit breakers Special versions Series MEGT07 0V/500V/DC 50 up to 5000 A The air circuit breakers MEGT07 are suitable for use as disconnecting switch in DC distributions up to a rated voltage of
More informationEnerlin'X IFE Switchboard Server IFE/EIFE Ethernet Interface
DOCA0147EN-01 Enerlin'X IFE Switchboard Server IFE/EIFE Ethernet Interface Firmware Version 003.007.024 Release Note 05/2018 The information provided in this documentation contains general descriptions
More information1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection
Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output
More informationMini Recessed PIR. Model: PDFM360MINI. Installation & Operating Instructions
Mini Recessed PIR Model: PDFM360MINI Installation & Operating Instructions 1 1. General Information These instructions should be read carefully and retained for further reference and maintenance. 2. Safety
More informationGCI-5K INSTALLATION AND OPERATOR S MANUAL
GCI-5K INSTALLATION AND OPERATOR S MANUAL Grid-tied inverter for wind Ningbo Ginlong Technologies 1 INTRODUCTION 2 SAFETY GUIDELINES AND WARNINGS 3 INSTALLATION 3.1 Selecting a location for the inverter
More informationCisco CRS 16-Slot Chassis Power Systems
This chapter includes the following sections: Power specifications are provided in Technical Specifications Power Systems Overview, on page 1 Power Component Information Common to the Two Types of Power
More informationPOWER FACTOR REGULATOR
POWER FACTOR REGULATOR Computer Smart 6/Computer Smart 12 Instruction Manual (M98235701-03-12A) - 1 - Table of Contents 1 INTRODUCTION AND SAFETY TIPS...3 1.1 CHECKS TO BE CARRIED OUT WHEN THE REGULATOR
More informationBS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0
BS 287 DUAL CHANNEL POWER SUPPLY User Manual January 2017 V1.0 Table of contents 1.0 SAFETY INSTRUCTIONS... 3 2.0 GENERAL DESCRIPTION PS 289... 4 3.0 MECHANICAL INSTALLATION... 5 4.0 MAINS POWER & SAFETY
More informationBest Practices Guide. EMC VMAX3 Family. Best Practices Guide for AC Power Connections REVISION 2.0. August, 2015
Best Practices Guide EMC VMAX3 Family Best Practices Guide for AC Power Connections REVISION 2.0 August, 2015 Best practices overview for AC power connections... 3 Selecting the proper AC power connection
More informationEHS INC. Electric Heating Systems, Inc. 109 North Gold Drive Robbinsville, NJ Phone: (609) Fax: (609)
EHS INC. Electric Heating Systems, Inc. 109 North Gold Drive Robbinsville, NJ 08691 Phone: (609) 259-4116 Fax: (609) 259-4119 6-Way RAMP Mobile Console Standard Features Are: 50/73/90 KVA Air Natural Transformer
More informationUSE AND MOUNTING INSTRUCTIONS
Doc. N MO-0216-ING POLE MOUNTED RECLOSER ENEL SPECIFIC DY 1539 USE AND MOUNTING INSTRUCTIONS Copyright 2010 - Microener Pag 1 of 11 INDICE 1 Installation and connection 3 1.1 Recloser 3 1.2 Voltage Transformers
More informationQuick Start Guide TS A
Quick Start Guide TS 930 125-630A DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer
More informationModbus Register Map: Galaxy 5000 & Galaxy 5500
Modbus Map: Galaxy 5000 & Galaxy 5500 Notes: 1. 16-bit registers are transmitted MSB first (i.e. big-endian). 2. INT32 UINT16 and and UINT32 are are most-significant word in in n+0, least significant word
More informationAuxiliary Units for 7SR23 High Impedance Protection Energy Management
Reyrolle Protection Devices Auxiliary Units for High Impedance Protection Energy Management Siemens Protection Devices Limited 2 Auxiliary Units for High Impedance Protection Description 7XG15 High Impedance
More informationINSTRUCTION MANUAL FOR BREAKER FAILURE RELAY BE1-50BF. BE1-50BF BREAKER FAILURE RELAY Style No. XXX XXX XXXXX Serial No. HXXXXXXX
INSTRUCTION MANUAL FOR BREAKER FAILURE RELAY BE1-50BF BE1-50BF BREAKER FAILURE RELAY Style No. XXX XXX XXXXX Serial No. HXXXXXXX P0048-40 Publication: 9190600990 Revision: G 01/10 *9190600990* INTRODUCTION
More informationLow Voltage Catalogue Masterpact NT and NW. LV power circuit breakers and switch-disconnectors
Low Voltage Catalogue 2013 Masterpact NT and NW LV power circuit breakers and switch-disconnectors Masterpact NT and NW The standard for power circuit breakers around the world. Over the years, other
More informationECOFIT. Masterpact M to Masterpact NW upgrade solutions. Make the most of your energy
Low oltage Electrical Distribution - Switchboard modernisation Catalog I 2014 ECOFIT Masterpact M to Masterpact NW upgrade solutions Make the most of your energy Masterpact M ECOFIT Contents Masterpact
More informationIRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)
IRI1-ES Sensitive Earth Fault Current Relay Manual IRI1-ES (Revision A) Woodward Manual IRI1-ES GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
More informationUser Guide Automatic Transfer Switch (ATS)
User Guide Automatic Transfer Switch (ATS) V.1.0 Table of Contents 1. Introduction... 2 2. Product Overview... 2 3. Important Safety Warnings... 3 4. Operation Indicators & Status... 3 5. Installation...
More informationInstallation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE
IMPORTANT! Please read all the information on this sheet. SAVE THESE INSTRUCTIONS! NOTICE BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL
More informationPLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet
Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical
More informationIO Input/Output Interface Module for LV Circuit Breakers
IO Input/Output Interface Module for LV Circuit Breakers DOCA0055EN-02 06/2015 IO Input/Output Interface Module for LV Circuit Breakers User Guide 07/2015 DOCA0055EN-02 www.schneider-electric.com The information
More informationetc-12 / etd Wiring, Set Up, Operation, and Test Instructions for: C O R P O R A T I O N Section II Instruction Manual
etc-12 / etd Section II Instruction Manual Instructions for: Wiring, Set Up, Operation, and Test satinamerican Shelton, Ct 1-800-272-7711 C O R P O R A T I O N www.satinamerican.com etc-12 / etd Section
More informationUPS READY POWER DISTRIBUTION ASSEMBLY
UPS READY POWER DISTRIBUTION ASSEMBLY FOR TRAFFIC CABINETS with LED Signals INSTALLATION & OPERATOR S MANUAL VERSION 1.2 1 Note The instructions contained in this manual are not intended to cover all of
More informationIndoor Unit Controller (IUC) Quick Reference and Fault Diagnosis
Indoor Unit Controller (IUC) Quick Reference and Fault Diagnosis Date: 1 November 2015 Issue: 1 IUC software version: 1.5 Index 1. Introduction... 2 2. List of units with IUC... 2 3. Features and functions...
More informationLandsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network.
Landsnet-Icegrid Requirements for protection and control systems. Principles for the Icelandic power transmission network. Introduction.... 4 System requirements... 6 Validity:... 6 Requirements for protection:...
More information